Home

Extinguishing Control Panel User Manual

image

Contents

1. NO Call point EOL resistor 6K8 Resistor 2K2 EOL resistor Input line Input line not used Connection example Relative value 0 17 5 28 40 80 100 Measured resistance 0 3700 3900 1K8 1K9 3K2 3K3 6K8 23K gt 24K Resistive EOL inputs threshold for state identification approximate values HLSI MN 103 1 v 05 http www honeywelllifesafety es User Manual 23 RP1r Supra 3 5 Output circuits connexion This section describes the criteria and requirements for the connection of the external circuits and devices which are monitored by the control panel 3 5 1 Extinguishing release circuits Terminal blocks 1 and 2 EOL diode Solenoid 1N4007 The outputs of the terminal blocks 1 and 2 will produce the signal to activate the extinguishing release devices solenoids s5 E te 5 O D Q 2 Ww 8 O EOL diode Connection in case of resistive EOL 1N4007 Solenoid Maximum current supplied by each circuit is 1 A provided that the total sum of intensities supplied by all the control panel outputs do not exceed the power supply limit of 2 4A Extintion circuit 1 Extintion circuit 2 EOL diode Solenoid 6 1N4007 The connection of solenoids depends on the solenoid type and the monitoring method used see figures on the right To ensure the monitoring functi
2. If enabled and flow press signal remains not active after release release signal will be repeated up to 3 times In case of 3 repetitions the flow press signal remains disabled control panel will show a fault on extinguishing circuit Disabled default value Hold device priority Defines if hold device HOLD input is prioritized over release device Release device priority default value Hold device priority Extinguishing notification Defines the extinguishing released status indication by means of the LED on the front panel Active LED after E delay default value 01 Active LED just when LOW PRESS input active HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 5 RP1r Supra 5 3 2 Zone options Zone coincidence condition Mode for Zone 3 Zone verification HLSI MN 103 1 v 05 http www honeywelllifesafety es Defines the alarm combination to make the control panel change into ACTIVE status and start extinguishing seguence P00 Alarm on Z1 amp Z2 or Z3 default value Alarm on any zone Z1 or Z2 or Z3 with extinguishing to one zone Any of the following combinations with extinguishing to two zones Z1 amp Z2 or Z1 amp Z3 or Z2 amp Z3 Alarm on ALL zones Z1 amp Z2 amp Z3 Defines operating mode for zone 3 Z3 asa call point default value Z3 as a detector The system provides a period of time for zone alarm confirmation in order to verify if
3. The control panel provides two different ways to implement the monitoring circuit by means of an EOL element with a capacitor default or with a resistor Refer to Section 5 Control panel configuration for more information 3 4 7 1 Monitoring with an EOL capacitor In order to increase the robustness and stability of the monitoring procedure and in compliance with UNE EN54 13 the control panel uses by default an End Of Line capacitor to monitor the input circuits Call point NO Call point NC o l EOL EOL To do so it is necessary to install at the end of each line a 47pF 2 35V He capacitor capacitor capacitor 4TUF 47uF Moreover this monitoring procedure reduces the system power consumption Monitoring topology for NO circuit Monitoring topology for NC circuit and consequently the batteries useful life is extended without increasing capacitive monitoring mode capacitive monitoring mode the battery capacity NO Call point EOL capacitor Resistor 47UF 2K2 EOL Capacitor 47uF Input line In case of using a capacitive end of line mode the capacitor used as an end of line element in zones will be 47pF 2 35V Input line not used The EOL capacitors supplied with the control panel are bipolar type elements so the polarity of the connection makes no difference Using other than the supplied electrolytic capacitors you must take into account the type of capacit
4. HLSI MN 103 1 v 05 http www honeywelllifesafety es Specifications Compact control panel with modular construction and composed of a metal mounting plate an enclosure which supports the electronic elements and a plastic front cover 353 x 381 x 123mm 4 Kg 9 3 Kg 3 in metal mounting plate to fix it to the wall 4 in enclosure 20mm apertures 15 top and 8 back All field wiring terminations are made using plug in screw terminals capable of accepting conductor sizes between 0 5mm and 2 5mm Class A 5 C to 40 C indoor Max 95 RH non condensing IP30 a 7 segment LED Display 2 digits for configuration and countdown timer b Indicator with the word GAS screen printed for indication of extinguishing release start 38 LEDs are provided for the following indications Alarm faults status of monitored inputs and outputs operating modes external signals release sequence status silence sounders mute buzzer 6 zone LED indicators 2 leds per zone 3 zones 10 push buttons are provided for the following functions Disable test zones test LEDs disable enable sounders mute buzzer manual evacuation sounders delay reset operating mode selection Key to get access level 2 keypad unlock and internal jumper to get access level 3 programming Internal sounder with SPL 60dBA at 1m User Manual 69 RP1r Supra System capacity Detection zones Sounder circuits Release circuits Auxiliary
5. J Automatic Cct Open door Manual Release S s i Pre Activated Activated D 6646 Monitored A J Cct Abor bb d Release 2 Manual z Onl User Manual 33 RP1r Supra 4 2 2 Function keys Panel operation at access Levels 1 and 2 is controlled by the various function keys located on the front fascia Function control keys are single function activation keys and apart from the MUTE BUZZER reguire the panel to be at user access Level 2 before they can be selected Z1 key to disable test Zone 1 access level 2 Z2 key to disable test Zone 2 access level 2 Z3 key to disable test Zone 3 access level 2 Introduction of programming seguences and led test access level 2 Disable Activate sounders access level 2 Manual Activation of Evacuate signal access level 2 Activate Disable the delay before sounders activation access level 2 Mute Buzzer access level 1 always available Control panel Reset access level 2 Operating Mode selection access level 2 Key to disable enable access to keypad access level 2 OO COOCOO The Led Test function of the key 4 is also accessible from level 1 The button for selecting the mode of operation 10 is only enabled from level 2 if the access to this level is gained through the user key 11 For security reasons it is not possible to modify the operating mode if the alternative method for level 2 acc
6. Honeywell RPir Supra VSN RP1r ESS RP1r Supra Extinguishing Control Panel User Manual HLSI MN 103I v 05 March 2015 RP1r Supra Nota This manual is valid for the following control panel models e RP1r Supra e VSN RP1r4 no touch screen e ESS RP1r Supra To make comprehension easier when these control panels are mentioned only the RP1r Supra model name is used however the information is valid for any of the models indicated above HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 2 RP1r Supra Contents 1 Introduction 1 1 CE Marking 1 2 System Design and Planning 1 3 Personnel 1 4 General Installation Guide 21 Introduction 2 2 Pre installation Check List 2 3 Transient Protection 24 Installation Procedure 2 4 1 Mounting Plate Installation 2 4 2 Panel Enclosure Installation 2 4 3 Installing the Batteries 2 44 Enclosure cover Installation 31 Cabling Instructions 3 1 1 Cable Terminations 3 1 2 Cable Quality and Installation 3 2 EMC Considerations 3 2 1 Screen Termination 3 2 2 Ferrite Sleeves Optional 3 3 Base PCB Wiring Connections 3 4 Input circuits connection 3 41 Gas release Terminal Blocks A and B 3 4 2 Hold device Terminal Block C 3 4 3 Emergency abort device Terminal block D 3 4 4 Zone connection Terminal blocks E F and G 3 4 4 1 Call points in zone circuits 3 4 4 2 Gas release call point in zone 3 3 4 5 Technical alarm inputs terminal blocks H and J 3 4 5
7. See Section 5 Control Panel Configuration for more details Resistor 2K2 Refer to Section 3 4 7 Input monitoring for more information NO Call point EOL capacitor 47uF Resistor 2K2 Aux call point Call point 2 NO Call point EOL capacitor Resistor 47uF 2K2 EOL capacitor 47uF AUX MANUAL MAN REL REL 2 Call point 2 not used Manual gas release 4 Aux call point AUX MANUAL MAN REL REL 2 AUX MANUAL HOLD ABORT SND1 SND2 MAN REL REL 2 MAN REL SWITCH Z1 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 15 RP1r Supra 3 4 2 Hold device Terminal Block C The extinguishing control panel has an input for Hold device to comply with the reguirements of UNE EN 12094 1 2004 section 4 20b Emergency detection devices The optional connection of a Hold device to Terminal block C allows you to manually stop the automatic extinguishing sequence While the push button input is active the countdown timer remains held up and awaiting The HOLD input is self resettable By releasing the push button the input is no longer active and the countdown restarts To ensure the monitoring it is necessary to install a serial 2K2 resistor with the call point and a 47yF 2 35V capacitor as an End Of Line element EOL Alternatively and for compatibility reasons with previous installations it is possible to replace the capacitor by an EOL resistor 6K8
8. See Section 5 Control Panel Configuration for more details Refer to Section 3 4 7 Input monitoring for more information Q 3 NO Call point d EOL capacitor S Resistor 47uF D 2K2 O I HOLD EOL MAN REL capacitor 47uF Hold call point not used Hold manual release AUX MANUAI HOLD ABORT SND1 SND2 MAN REL REL 2 MAN REL SWITCH Z1 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 16 RP1r Supra 3 4 3 Emergency abort device Terminal block D The extinguishing control panel has an Abort input to comply with the requirements of UNE EN 12094 1 2004 section 4 27 Devices for emergency abort The optional connection of an Abort device to Terminal block D allows you to manually stop the automatic extinguishing sequence The Abort input is latched so once activated it will require a manual reset of the control panel to enable again the extinguishing process To ensure the monitoring it is necessary to install a serial 2K2 resistor with the call point and a 47yF 2 35V capacitor as an End Of Line element EOL Alternatively and for compatibility reasons with previous installations it is possible to replace the capacitor by an EOL resistor 6K8 See Section 5 Control Panel Configuration for more details Refer to Section 3 4 7 Input monitoring for more information NO switch EOL E capacitor n Resistor 47uF 2K2 Ke lt ABORT EOL SWI
9. Call points can be included optionally in zones 1 and 2 When it is necessary to distinguish between the indication of a detector Zener diode Zener diode AV 51V EOL capacitor 47yF NO Call point NO Call point 1 Detector alarm and a call point alarm in the same zone a 5 1V Zener must be i installed in series connection with each of the call points Alternatively it is possible to use a resistor 80 gt R gt 1500 in series connection with call points l Resistor EOL The detector alarm will be indicated by the zone led in flashing mode and Haa Prada the call point alarm will be indicated by the zone led in steady mode NO Call point Ka 3 4 4 2 Gas release call point in zone 3 iii eia for call poi If Zone 3 is set as Manual Release zone it is not necessary to install a 5 1V Zener to indicate call point alarms Refer to Section 5 Control panel configuration for more information __ Resistor E min 800 max 1500 capacitor Release 47yF call point Connection example Manual release call point onZone 3 Voltage 0 14 27 5 87 94 100 Status Measured resistance 0 601 800 1500 200005 mn masa eea Ee seasons 2K8 3K2 6K9 gt 7K8 Zone status thresholds approximate values HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 19 RP1r Supra 3 4 5 Technical alarm inputs terminal blocks H and J Using the monitored
10. e Locate the batteries in their right position inside the enclosure 2 4 4 Enclosure cover The control panel has a cover door to close the enclosure at the end of the installation Use 4 screws to fix the cover on the enclosure HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 10 RP1r Supra 3 Installation 3 1 Cabling Instructions All wiring should comply with current wiring regulations or the applicable local wiring regulations Note also the requirements of EN54 14 UNE 23007 14 for cabling and interconnection of a fire detection and alarm system For information on wiring inputs and outputs and wiring instructions to identify terminals refer to Section 3 3 External Wiring Use the following rules when installing cables 1 Cables should be brought into the enclosure using the 20mm cable entry points provided on the top face and back of the enclosure Ensure that all openings in the enclosure are closed before connecting power to the panel to prevent inadvertent access to hazardous voltages and protect against foreign bodies which may cause short circuits 2 Tails should be of sufficient length to connect to the appropriate termination points at the commissioning stage Cable conductor size should be a minimum of 0 5mm Terminals accept one 0 5 to 2 5mm stranded or solid conductor 4 Cables should be screened or metal coated and the screens terminated into the earthing points provided within the enclosur
11. fault led steady una ae Active option Manual release 2 MANUAL REL 2 l benda Lan HEEN 4 M Manual release fault led flashing mate oe Active option Hold device HOLD MAN REL Monitored A Monitored Cct led fault in hold mode flashing Automatic reset _ Hold 4 Hold led steady option eng OR Ka 2 SG Pa A Monitored Cct led fault in abort mode flashing eb ari C Abort Abort led steady piae bu required Zone 1 Z1 KY Zone 1 fault led flashing Automatic ieee amp option Zone 2 Z2 Automatic reset Zone 3 G Z3 Automatic reset call point 1 2 9 A C F HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 52 RP1r Supra Low Pressure LOW PRESS Pressure Automatic reset SWITCH Low pressure fault led flashing option Flow Signal FLOW PRESS pressure Ak Artonalcrasei Open door DOOR OPEN Monitored A Automatic reset kost SWITCH Monitored Cct open door led flashing option By default all faults are latched and require the control panel to be reset in order to be restored Except for the abort circuit fault for the rest of the circuits it is possible to modify this operation and perform an automatic restore when the fault condition disappears see Section 5 4 Special functions for more information 4 9 3 Sounders Fault Disabled indicator led There are two possible reasons for the Sounders fault disabled led to be lit e
12. part of the housing Use insulation sleeving on the tails between the cable entry position and the earth post Run the tails close to the rear part of the back box 3 2 2 Ferrite Sleeves Optional In difficult EMC environments or where non preferred cables are used optional ferrite sleeves should be fitted to all the wiring entries The ferrite sleeves A are to be fitted over the conductor s of each cable and as close as possible to the entry point of the cable The sleeve should be held in place using a cable tie not supplied If more ferrite sleeves are required please contact your supplier Fuse L T 4AL 250V OHO ali HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 13 RP1r Supra 3 3 Base PCB Wiring Connections Status relay Preactivation Status relay Extinguishing release in progress Status relay Extinguishing release cancelled Status relay Manual mode 3 Status relay Automatic mode The base PCB of the extinguishing control panel provides the external cable wiring connectors for the following functions OOOO To recognize the function of connectors easily the input connections have been identified with alphabetical characters and the output connexions with numbers OOOO VOOD OOOO Inputs po pa pa pa ma ma ns A Monitored input for gas release optional manual call point on front panel Monitored input for gas release circuit 2 an A A a y W y v y v g
13. 1 Low pressure signal LOW PRESS Terminal block H 3 4 5 2 Flow signal FLOW PRESS Terminal block 3 4 5 3 Door open signal Terminal block J HLSI MN 103 1 v 05 http www honeywelllifesafety es amp ONNN N OOO oO Ol 3 4 6 Digital input Terminal block K 3 4 7 Input Monitoring 3 4 7 1 Monitoring with an EOL capacitor 3 4 7 2 Monitoring with EOL resistor 3 5 Output circuits connexion 3 5 1 Extinguishing release circuits Terminal blocks 1 and 2 3 5 2 Auxiliary 24Vdc Output Circuit Terminal blocks 3and4 25 3 5 3 Sounder circuits Terminal blocks 5 and 6 3 5 4 Status relays Terminal blocks 7 8 9 10 11 12 and 13 27 3 5 4 1 3 5 4 2 Status contacts Terminal blocks 8 9 and 10 General fault contact GEN FAULT Terminal block 7 27 3 5 4 3 Operating mode contacts Terminal blocks 11 12 and 13 28 3 5 5 Output monitoring 3 5 5 1 End of line diode monitoring 3 5 5 2 End of line resistor monitoring 4 Use and operation 4 1 Introduction 4 2 User Interface 4 2 1 LED Status Indicators 4 2 1 1 Front panel detection process 4 2 1 2 Front panel Release process 4 2 2 Function keys 4 3 Access levels 4 4 Operating modes 4 5 Control Panel Status 4 5 1 Normal Status 4 5 2 Preactivated status single zone fire condition 4 5 3 Activated status Double zone alarm condition 4 5 4 Extinguishing release status 4 5 5 End of extinguishing release 4 6 Auxiliary call points 4 6 1 GAS release manual
14. 4 8 1 Disable zones Press the reguired zone key to disable the supervision of one of the 3 detection zones This action is only available in Access Level 2 When a zone is disabled the following indications are present Disabled zone indicator lights yellow Disablement led lights Under these circumstances the alarms and faults of the disabled zone s are not supervised and in consequence they will not be indicated at the control panel HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 48 RP1r Supra 4 8 2 Disable the extinguishing process To disable the extinguishing process the control panel has to be set in Disabled operating mode by pressing repeatedly the mode selector until the required operating mode led is lit see Section 4 4 Operating modes In this operating mode the extinguishing process cannot be started manually or automatically This function is only available in Access Level 2 The following indications are present System Disabled 4 ye Disabled led lights Manual Only DISABLED relay ON 4 8 3 Disable the sounders According to UNE EN 12094 1 2004 section 4 15 Disabling of the transmission path to the alarm devices of a flooding zone shall be possible ONLY with the disabling of the transmission path to the actuators of that flooding zone When the control panel returns to Manual or Automatic operating mode the sou
15. If the EOL element has not been installed in any of the 2 sounder circuits according to Section 3 5 3 Sounder circuits a fault condition will be generated in the monitored circuit In this case the Sounders fault disabled led will be lit in quick flashing mode 2 Hz Additionally the General fault led and contact will be also activated e According to UNE EN54 standard when there is a delay configured for sounders activation this must be indicated by activating the Disabled condition The disablement led lights and the Sounders fault disabled led is also lit but in this case in slow flashing mode 1 Hz When sounders are not still activated because there is a delay on through parameter 5 the led of the Delay ON OFF e key will light HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 53 RP1r Supra 4 10 Other functions 4 10 1 Control panel reset To perform a reset action enter a valid user access level 2 passcode and then press the RESET key Man Refer to Section 4 3 Access levels for more information This action is used to clear all event indications on the control panel and return it to its normal operation On the other hand according to UNE EN 12094 1 2004 Section 4 12 2 itis possible to inhibit the reset function temporarily once the control is ACTIVATED Use the parameter to configure the inhibition period of time from the control panel programming mode See
16. It allows choosing operating mode for contact connected to FLOW PRESS input Normally open circuit NO default value Normally closed circuit NC HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 61 RP1r Supra Input mode for OPEN DOOR signal It allows choosing operating mode for contact connected to OPEN DOOR input Normally open circuit NO default value Normally closed circuit NC Input mode for DIGITAL IN signal It allows choosing operating mode for external contact connected to DIGITAL IN input Normally closed circuit NC Input is activated when the contact opens Nan Normally open circuit NO default value Input is activated when the contact closes HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 62 RP1r Supra 5 3 5 Additional options Sounders delay Reset disabled after release Earth fault level Monitoring mode for outputs HLSI MN 103 1 v 05 http www honeywelllifesafety es Period of time in minutes that elapses between the control panel goes into PREACTIVE status and the sounders are activated If a single zone alarm is activated this period of time can be used to check the alarm and reset the control panel before the sounders activation Time delay until sounders activation default value 00 min Selectable value from 00 to 10 minutes According to UNE EN 12094 1 2004 section 4 12 2 there must be a configurable time gap from 0 to 30 min
17. NO C NO C NO 4 5 1 Normal Status When the panel is at user access Level 1 and also in the quiescent status i e the panel status is normal the following indications are present 2 POWER LED green This is lit continuously when the panel is powered The internal Buzzers silent GENERAL FAULT relay GEN FAULT energized standby continuity between C and NO HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 36 RP1r Supra 4 5 2 Preactivated status single zone fire condition If there is an alarm in one of the zones the control panel goes into preactivated release mode and the following indications are present POWER LED green This is lit continuously when the panel is powered The internal buzzer operates pulsing tone 1 Hz GENERAL FAULT relay GEN FAULT energized standby continuity between C and NO The ALARM led red flashes Zone status leds indicate Alarm in the corresponding zone Flashing in case of a detector alarm Steady in case of a call point alarm Activated OFF Status contacts PREACT ON ACTIV OFF RELEASED OFF ACTIU PREACT RELEASED C NO CNO CNO 7 Silence When the delay configured in parameter 5 is finished sounders can be silent by pressing Silence Resound key Ifa specific delay has been configured sounders will be silent until the delay is finished The delay can be cancelled at SND1 SND2 any time by pressing the
18. Section 3 4 5 2 Flow signal Flow Press to see the connection of this external signal When this input is active the control panel will treat this condition as an alarm and the following indications will be shown The internal buzzer operates steady tone Pre Activated Status leds Preactivated ON Activated ON Activated Status contacts PREACT ON ACTIV ON RELEASED ON ACTIV PREACT RELEASEDI C NO C NO CNO Sounder outputs SND1 and SND2 operate in steady mode SND1 SND2 Pressure Flow led lights in steady mode Flow Released led lights in steady mode The activation of this condition implies a control panel manual reset 4 7 3 Door open signal This monitored input provides the status indication of the door of the building where the extinguishing system is installed Refer to Section 3 4 5 3 Door open signal to see the connection of this external signal This indication is just to provide information however the control panel can be configured so that the automatic release is blocked when the door is open parameter fjd Refer to Section 5 Control panel configuration for more details HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 45 RP1r Supra e To provide information default Monitored A 1 M Cct Door open led lights in steady mode Open door e To block the extinguishing release process while the door is open In this situation
19. call point 4 6 2 Hold device 4 6 3 Emergency Abort device 4 7 External signals 471 LOW PRESSURE signal 44 44 User Manual 3 RP1r Supra 4 7 2 Flow signal FLOW PRESS 45 Appendix A General Wiring Diagram 68 4 7 3 Door open signal 45 _ 4 7 4 Digital input 47 Appendix B Specifications 69 4 8 Disablements 48 Appendix C Accessories 72 4 8 1 Disable zones 48 4 8 2 Disable the extinguishing process 49 4 8 3 Disable the sounders 49 4 8 4 Silence sounders 49 4 8 5 Mute Buzzer 50 4 8 6 Disable external device only for Belgium 50 4 9 Faults 51 4 9 1 Auxiliary power supply fault 51 4 9 2 Monitored circuits faults 51 4 9 3 Sounders Fault Disabled indicator led 53 4 10 Other functions 54 4 10 1 Control panel reset 54 4 10 2 Evacuation 54 4 10 3 Leds test 54 5 Configuration 55 5 1 Overview 55 5 2 Configuration mode navigation 55 5 3 Available options 56 5 3 1 Extinguishing options 56 5 3 3 Sounders options 60 5 3 4 Line options 61 5 3 5 Additional options 63 5 4 Special features UNE EN54 non compliant 64 5 4 1 Overview 64 5 4 2 Special functions configuration 64 5 5 Restore default values 65 5 6 Monitoring functions 66 5 6 1 Overview 66 5 6 2 Access to monitoring functions 66 5 6 3 Monitored parameters 67 The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be correct However the manufacturer assumes no responsibility for inaccuracies and reserves the right to mod
20. condition only while the ABORT input is activated The countdown will be restored automatically once ABORT activated condition dissapears Note The modification of this option contravenes the UNE EN 12094 1 2004 standard 4 7 External signals Following the description of Section 3 4 5 Technical alarm inputs the control panel provides a number of monitored input circuits for external signals to detect and signal events from external devices 4 71 LOW PRESSURE signal The LOW PRESSURE input LOW PRESS allows the control panel to signal the status of loss of extinguishing agent in the bottles sent by the sensors installed in the extinguishing agent bottles Refer to Section 3 4 5 1 Low Pressure Signal to see the connection of this external signal When the control panel receives a low pressure signal this is considered as a fault This input is self resettable The internal buzzer operates pulsing tone GENERAL FAULT relay GEN FAULT non energized fault continuity between C and NC o Toska The ALARM led red lights in flashing mode P F Ta Low Pressure led lights in steady mode HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 44 RP1r Supra 4 7 2 Flow signal FLOW PRESS According to UNE EN 12094 1 2004 section 4 18 Signal flow of extinguishing agent the control panel provides an input which allows the connection of the corresponding flow sensor in order to monitor its status Refer to
21. honeywelllifesafety es NO contact l EOL capacitor 47uF Resistor 2K2 Alam signal EOL capacitor 47uF Alarm signal input not used User Manual 20 RP1r Supra 3 4 6 Digital input Terminal block K The extinguishing control panel has a programmable digital input to connect an external contact in order to control the extinguishing control panel from a higher level and external system Depending on the control panel configuration the external contact can be NO Normally Open or NC Normally Closed Both are voltage free contacts There are different functions which can be associated with the activation of this contact depending on the control panel configuration see Section 5 Control panel configuration for more information e Reset e Evacuate e Mute sounders and buzzer e Delay on off To avoid irreparable damage to the control panel do not use contacts or cables with voltage in the digital input Digital input HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 21 RP1r Supra 3 4 7 Input Monitoring By default all monitored inputs are NO Normally Open contacts and they become activated when the circuit is closed with a serial 2K2 resistor Monitored outputs may also be used with NC Normally Closed contacts which will be activated when the circuit is open In normal status standby the NC contact must be connected in series with a 2K2 resistor
22. in the EOL resistor 6k8 In the absence of this resistor there will be no current flow and the control panel will indicate a fault If there is a short circuit the connected elements are not polarized correctly or the resistor value is not the appropriate the control panel will also indicate a fault e When an output is active the injected signal has direct polarity In this case the correct polarity of the connected elements makes the current flow through these elements not through the EOL resistor Otherwise the control panel will indicate a fault HLSI MN 103 1 v 05 http www honeywelllifesafety es Diode 7 EOL resistor 6K8 Current flow Sounder e be Output state standby reverse polarity EOL Sounder resistor 6K8 urrent flow Output state active direct polarity EOL resistor 6K8 Sounder E7 EOL resistor 6K8 Output 2 not used Connection example User Manual 30 RP1r Supra 4 Use and operation Pre Activated Activated Manual A Release Active Pressure Flow Pressure Low 4 1 Introduction Power This section explains how to use the RP1r Supra panel s built in control functions to access various menu functions and or carry out regular TT releses ese A 1 ceree mandatory procedures reguired by the local regulations Helpful descriptions A and tips are also provided to assist the user in understanding the status Disabled Hold A raul
23. led Delay On Off led Mute Buzzer led OO QDOO QQOOOCOOOOO HLSI MN 103 I v 05 http www honeywelllifesafety es Normal Alarm F ault Release Alarm A disablement Power General Fault Keypad Access TORE 12 Lamp test 3 sec Silence ec 13 Resound Evacuate 3 sec Delay lt Ff On Off 15 Mute Buzzer Earth Fault Sounder AA Fault Disabled Power A sete Fault Auxiliary A Power Supply F fe System Fault User Manual 32 RP1r Supra 4 2 1 2 Front panel Release process The group of leds located on the left side of the front panel are the indicators and keys used for the control panel release process POOC QOOOWOOOOO Released led release has started Countdown timer for release activation display for control panel configuration Released led Release is finished Operating Mode leds Reserved leds for future use Pre activated Activated led Release status indicator Manual Release led Pressure Flow led Extinguishing agent flow indicator Pressure Low led Indicator of low pressure due to loss of extinguishing agent Monitored Circuit Abort and Hold leds Monitored Circuit Open Door led Release Fault led Release Circuit Fault led Manual Release Only led HLSI MN 103 I v 05 http www honeywelllifesafety es System Monitored A Disabled Ct Hold A Monitored A J
24. only result in damage to the equipment but may also cause problems when commissioning the equipment or adversely affect its performance Before selecting a location for the control panel and devices DO make sure that e The operating room temperature is in the recommended range 5 C to 40 C e The relative humidity is between 5 and 95 e The panel is wall mounted in a position which allows clear visibility of displays and easy access to operating controls The height above floor level should be chosen such that the LCD is just above normal eye level approximately 1 5 metres e DO NOT locate the panel where it is exposed to high levels of moisture e DO NOT locate the panel where there are high levels of vibration or shock e DO NOT site the panel where there would be restricted access to the internal equipment and cabling wiring connections 2 3 Transient Protection This eguipment contains transient protection devices Although no system is completely immune from lightning transients and interference forthese devices to function correctly and to reduce susceptibility this equipment must be earthed correctly As with all solid state devices this system may operate erratically or can be damaged if subjected to lightning induced transients The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es
25. open circuit and Output 2 not used indicates a fault If there is a short circuit in the output line or the connected elements are not polarized correctly or even if the wiring resistor was altered and the circuit could not meet its function the control panel will also indicate a fault see Section 5 6 Monitoring functions for more information EOL diode Sounder reverse pol Current flow Connection example e When an output is active the injected signal has direct polarity In this Output state active case the reverse polarity of the diode make the current flow through Sa the connected elements not through the diode if they are polarized correctly Otherwise the control panel will indicate a fault HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 29 RP1r Supra 3 5 5 2 End of line resistor monitoring Alternatively it is possible to use a 6K8 resistor as an End Of Line element for output circuits so that the system is backward compatible with existing installations which use the traditional monitoring EOL resistor This monitoring mode is enabled from the control panel configuration Refer to Section 5 Control panel configuration for more details The criteria for output monitoring by means of an EOL resistor 6K8 is as follows e In standby operation quiescent status the control panel injects into the outputs a reverse polarised signal and monitors the voltage drop caused by the current flow
26. section 5 Control panel configuration for more details 4 10 2 Evacuation To generate an evacuation signal the control panel must be in quiescent status From Access level 2 press and keep pressed the Silence Resound key ons aed for 3 Seconds to activate sounders without activating the release circuits and generate an evacuation signal The following indications are present Alarm led lights in steady mode Sounders outputs SND1 and SND2 pulsing signal SND1 SND2 4 10 3 Leds test To perform a led test in order to check that all of them work properly keep pressed the Keypad access key Jis See Section 4 3 Access levels for more information fy for 3 seconds from any Access level The control panel s LEDs are then lit individually and the internal buzzer sounds HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 54 RP1r Supra 5 Configuration 5 1 Overview This panel has different options that allow the modification of its functionalities in order to fit different needs and reguirements for each particular application These configuration options are only available from access level 3 see section 4 3 Access level for additional information 5 2 Configuration mode navigation Different parameters and options are displayed on the front user panel 7 segment LCD Once access level 3 has been enabled some of the user keys change their normal fun
27. standard profile by default Keypad acc LampTest 3 sec Silence Mute Reserved O Communication faults are indicated for communication channel monitoring with graphic software TG RP1r ot Communication faults are not indicated default Low battery sensitivity Threshold for monitoring the battery inner resistor The threshold selection is done by modifying the position of the user key to gain access to the keypad Only one pve Si change at a time Selection by means of user key Off High battery sensitivity default User Manual 64 RP1r Supra 5 5 Restore default values In order to restore the default values for configuration parameters the following procedure must be followed e Change control panel into level 3 by closing jumper PROG see section 4 3 Access level for additional information e Press and hold Keypad access key ls e While keeping pressed Keypad access key following sequence of keys Z1 Z2 Z2 Z1 HLSI MN 103 I v 05 http www honeywelllifesafety es Key combination to restore configuration default values This option is only available at access level 3 This action only restores the default values corresponding to the configurable options Special functions accessible from level 3 see Section 5 4 Special Functions do not recover the factory defined configuration and if necessary they must be restored manually using the corr
28. 1 RP1r Supra 24 Installation Procedure Installation of the RP1r Supra control panel in line with Easy ix concept is comprised of two stages mounting plate installation and panel enclosure installation Details of each stage are provided in the following sections 2 4 1 Mounting Plate Installation To prevent distortion the RP1r Supra mounting bracket MUST be installed on the wall as flat as possible i e with a maximum flatness deviation between any two points of 3mm Where the wall is out of tolerance use appropriate packing pieces to meet these requirements Step 1 e Hold the mounting plate in the required position on the wall and mark the position of the 3 fixing holes Use a level to ensure these are level e Remove the mounting plate from the wall and drill the 3 holes e Use rawlplugs or equivalent O 6mm to the 3 holes Step 2 e Screw the mounting plate to the wall using the top fixing hole only at this stage and appropriately sized screws Step 3 e Line the 2 holes in the lower area of the mounting plate with the two holes in the wall drilled earlier Use suitably sized screws to secure the mounting plate to the wall Step 4 e Remove all blanks from the 20mm cable entry apertures required for all cable access HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 8 RP1r Supra 2 4 2 Panel Enclosure Installation The control panel enclosure is very simple to install providing the mo
29. 1 2 5 and 6 work based on the detection of a 6k8 resistive load as end of line element By configuring the control panel the monitored outputs can also operate with a polarized diode see Section 3 4 5 2 as an end of line element Refer to Section 5 Control panel configuration for more details 3 5 5 1 End of line diode monitoring In order to increase the robustness and stability of the monitoring procedure and in compliance with UNE EN54 13 the control panel uses by default an End Of Line capacitor to monitor the output circuits A reverse polarity diode 1N4007 or similar is reguired see figure This monitoring procedure reduces the system power consumption and conseguently the batteries useful life is extended without increasing the battery capacity In addition diode allows to monitor wiring determining if this has resistive minimum conditions to guarantee their function In this case and with the outputs in standby status the control panel injects into the outputs a pulsing signal with inverse polarity and monitors the Diode voltage variation in the output terminals In activation status the voltage owen Sauce een Sounder y EOL diode injection has direct polarity tee e In normal operation quiescent status the voltage in the output Output state standby sae terminals must be limited by the EOL diode 0 7V approx In the reverse polarity irevaree vali absence of this diode the control panel detects an
30. 110 230 Vac 1576 50 60 Hz 65 W 125 mA User Manual 70 RP1r Supra Mains fuse rating T4AL 250V 4 A Backup batteries Emergency power supply by means of internal batteries 2 x 12V 7Ah Max Output voltage 28Vdc 100 mV Max Battery power 2 4 A 65 W Battery load current 300 mA Battery resistor test EN54 700 mQ Battery fuse rating F4AL 250V 4 A Battery charger output voltage Max 1 A 30 Vdc Approvals In accordance with UNE EN 12094 1 2004 UNE EN 54 2 and UNE EN 54 4 A2 2006 CPD certification 1134 CPD 045 Battery Disposal R R l As a minimum replace the batteries every four years G The battery units should always be disposed of in accordance with the battery manufacturer s recommendations and local regulations Batteries should be disposed of separately from household waste Always dispose of batteries as per your local regulations Again do not dispose of batteries with normal household waste If you have any questions please contact the local authorities responsible for waste disposal Batteries should not be taken apart thrown in the fire or short circuited If a battery has leaked do not touch the battery fluid Avoid skin contact e g put on protective gloves and clean the battery compartment with a dry cloth e Always replace all batteries at the same time and use batteries of the same type Extreme care must be taken to avoid damage from electricity Use appropriate tools with insul
31. Delay ON OFF key S and the sounders will operate immediately HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 37 RP1r Supra 4 5 3 Activated status Double zone alarm condition By default the control panel starts the release process when there is an alarm coincidence in zone 1 and zone 2 or when the gas release call point has been activated only automatic or manual operating modes In these circumstances the following indications are present POWER LED green This is lit continuously when the panel is powered The internal buzzer operates pulsing tone 1 Hz GENERAL FAULT relay GEN FAULT energized standby continuity between C and NO The ALARM led red flashes Zone status leds indicate Alarm in the corresponding zone Flashing in case of a detector alarm Steady in case of a call point alarm Pre Activated Status leds Preactivated ON Activated ON Activated Status contacts PREACT ON ACTIV ON RELEASED OFF ACTIU PREACT RELEASEDS C NO CNO CNO Sounder outputs SND1 and SND2 will operate with quick pulsing tone 2 Hz SND1 SND2 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 38 RP1r Supra Additionally the release seguence starts According to Section 4 17 of UNE EN 12094 1 2004 it is possible to specify a delay known as a pre discharge warning time which shall be adjustable from 00 and 60 seconds The configurati
32. Of Line element EOL to ensure the monitoring function of the wiring lines See Section 3 Installation for more details If there is a short circuit or the control panel does not detect the EOL resistor a fault will be generated and the indicator led on the front panel will be lit in flashing mode Additionally the General Fault led and contact will also be activated By using the default monitoring mode capacitive EOL in inputs and diodes in outputs the control panel also monitors the wiring determining if it has the resistive minimum conditions to guarantee its function Otherwise a fault will be indicated This additional feature is not present if you are using the monitoring mode by means of a resistive EOL The internal buzzer operates pulsing tone GENERAL FAULT relay GEN FAULT non energized fault continuity between C and NC aceno The General Fault led lights in flashing mode This led ON indicates the presence of any kind of failure in the system HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 51 RP1r Supra Depending on the type of fault the indications are as follows Monitored circuit Term Description Indicator led Block Release circuit 1 CCT EXT 1 TF Automaticresei 3 CCT EXT 2 Circuit AEX Release circuit fault led flashing option SND 1 Automatic reset SND 2 s Sounders fault disabled led flashing option Manual release AUX MAN REL lee ees Pala A ad Manual release
33. R information provided by the RP1r Supra panel s LCD and LED indicators T T ia e Open door Disabled Manual Release Power Delay Only Faut 4 A Supply Ionor e Release Auxiliary Mute Circuit ower Su Fault A Arzu at Manual Release B aor Reset Only Fault Ep qa D Aro Ed 4 2 User Interface AI wn 2 lt The RP1r Supra control panel is provided with all required indicators to allow the user to review the system status and with appropriate user access perform approved system maintenance functions in accordance with the Petahana reguirements of the local regulations cas H Alarm Manual A Release _ Active Power Pressure A System status LEDs are also provided and these divided into two groups 88 Pressure Low Monitored A ct Released c A General Keypad Access Abort Fault Lamp test B sec Silence s Sounder Evacuate ult 3 sec Disabled e Indicators for the extinguishing release process gt gt gt Se m A 2 w oO a a a S z 3 2 System Monitored A h Disabled C Hold Fault e Indicators for the monitoring and events or alarms detection e gt Automatic Cct Open door See Section 4 2 1 Status leds for more information Kawal peers 4 ol o a se 2 SERA n e Manual System Release Bp J Ai Only Function Keys The user interacts with the informat
34. Resistive value of Extinguishing circuit 1 CCT EXT 1 Extinguishing circuit 2 Resistive value of Extinguishing circuit 2 CCT EXT 2 Battery resistor The displays shows the monitored value of the battery inner resistor Depending on the value to be displayed the 7 segment display may be insufficient and for this reason the position of the dot is used for the calculation of the total value 15 1 50 19 100 1150 IS 200 21 50 In the case of the parameter corresponding to the battery inner resistor this value should be interpreted by applying a reduction factor of 10 1 l e IG o150 1G 1 150 Note The values shown in the monitoring mode are only useful if the control panel uses diodes and capacitors for monitorin mode HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 67 RP1r Supra Appendix A Battery connection Power supply connector Inhibition monitoring earth jumper USB port Lithium battery location Access level 3 jumper RS 232 communication port lC auxiliary communication port HLSI MN 103 I v 05 http www honeywelllifesafety es General Wiring Diagram Extinction Aux External circuits power supply Sounders Call points EOL EOL EOL EOL EOL EOL EOL EOL a 3 TI TOW os 2 oH HoH BOs Zones EOL EOL EOL me pt Vv Viiv glass AUX MANUAL HOLD ABORT _ MAN REL REL 2 MAN REL SWITCH OG Pr
35. TCH Capacitor 47 UF Abort switch not used Emergency abort ABORT SWITCH SND1 SND2 MAN REL REL 2 MAN RE SWITCH Z1 VLG ZAE AUX MANUAL HOLD Srey 5 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 17 RP1r Supra 3 44 Zone connection Terminal blocks E F and G The connection terminals for detection zones provide 24Vdc nominal voltage which is used to supply power to conventional detectors and call points When using Notifier series 800 or Morley ECO1000 detectors up to 32 detectors per zone can be installed Detection zone circuits must be wired as a single circuit with no spurs or T junctions to enable the monitoring circuit to work correctly Moreover a 47yF 2 35V capacitor is required as an End Of Line element Alternatively and for compatibility reasons with previous installations it is possible to replace the capacitor by an EOL resistor 6K8 See Section 5 Control Panel Configuration for more details Refer to Section 3 4 7 Input monitoring for more information Detector Detector Detector Detector Detector Detector EOL capacitor ATUF EOL capacitor 47uF Detector Detector Detector Detection zones EA capacitor Zone 3 not used Po Pp AUX MANUAL HOLD ABORT SND1 SND2 IMAN REL REL 2 MAN REL SWITCH Z1 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 18 RP1r Supra 3 4 4 1 Call points in zone circuits
36. ated handles HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 1 RP1r Supra Appendix C Accessories RP1r Supra VSN 232 TG IP 1 VSN 4REL ITAC TG RPir OPC RP itr UCIP HLSI MN 103 1 v 05 http www honeywelllifesafety es Extinguishing control panel RS 232 communication module IP communication module VSN 232 reguired 4 relay module Interface module for RP1r Supra integration into an ID system Graphic management software for RP1r Supra control panel Software based on OPC server standard which meets the Data Access 1 0 and 2 0 protocol The OPC RP1r software is designed for the integration of Notifier Extinguishing control panels RP1r series in any managing system or SCADA with OPC requirements IP GPRS communication module VSN 232 is required User Manual 12 Honeywell Life Safety Iberia C Pau Vila 15 19 08911 Badalona Barcelona apap ya KA aman Honeywell www honeywelllifesafety es
37. ault The control panel carries regular readings of internal battery resistance to check the resistive value If this value exceeds 700 mQ the control panel will show a power supply fault indicating that the battery status is not correct The control panel has 3 input zones for direct connection of 2 wire conventional detectors or external release call points 2 release monitored circuits and 2 sounder outputs with different frequencies in order to identify each release state The control panel also includes different auxiliary inputs and outputs to manage and signal the operating status and different series communication interfaces for optional integration with remote monitoring systems e g TG or Fire IMT According to Section 4 17 of UNE EN 12094 1 2004 it is possible to specify a delay known as a pre discharge warning time which shall be adjustable from 00 and 60 seconds in 5 second intervals The front panel provides an informative 2 digit display which indicates the time remaining to start the extinguishing release HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 6 RP1r Supra 2 Installation Guide 21 Introduction This section is intended to provide you with simple guidelines on how to install the extinguishing control panel quickly and safely 2 2 Pre installation Check List Before installing the extinguishing control panel you must first ensure that the following criteria have been met Failure to do this may not
38. ction and allow navigation through different configuration options Enabled keys for this purpose are highlighted to be identified Press this key to select the next parameter Press this key to select the previous parameter Use this key to increase a value Use this key to decrease a value Press this key to confirm the selection or modified value 3 Automatic SEL OK Note When moving from one parameter to another the latest change is saved without pressing SEL OK HLSI MN 103 1 v 05 http www honeywelllifesafety es Released System Disabled Automatic Manual Only Pre Activated Activated Manual A Release Active Pressure Flow Pressure Low Monitored A t CE Abort Monitored A C Hold Monitored A ct Open door Release Fault A Release Circuit Fault Manual Release Only ATest Power re 5 D kog D 2 General Fault gt Earth Fault gt Sounder Fault Disabled Z1 Z2 0013 E Keypad p KZ Lamp test 3 sec Silence wg Resound gt TNS Evacuate 3 sec EB Delay On Off WH We gt Mute Buzzer WZ KU LN MN al Reset User Manual 55 RP1r Supra 5 3 Available options 5 3 1 Extinguishing options digits is used in case of a parameter Extinguishing release delay Soak time for extinguishing circuit 1 On value introduction mode dot position
39. cuited e Observe correct polarity e Before connecting any external circuit to the control panel check their maximum consumption To comply with the standards batteries must be able to keep the system in standby and alarm status for the required periods of time Ensure that the control panel power supply and batteries provide sufficient capacity Otherwise auxiliary devices must not be supplied by the control panel but by suitable external power supplies Auxiliary modules with optional connection to the control panel such as UCIP VSN 232 VSN 4REL etc get their power from non resettable auxiliary output block 4 therefore the availability of current I a in this output will be reduced proportionally according to the number and specific consumption of the connected devices www 24Vdc outputs 24 Vdc max 250 MA resettable E 2 24Vdc Seay na 250 mA 24Vdc supply output AUX MANUAL HOLD ABORT _ 24V SND1 SND2 IMAN REL REL 2 MAN REL SWITCH Z1 l2 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 25 RP1r Supra 3 5 3 Sounder circuits Terminal blocks 5 and 6 The control panel provides two monitored output circuits for sounder activation The maximum current that each of these circuits can provide is 250 mA If one of the circuits is not used for Sounders a 68k resistor must be connected between terminals to avoid a fault condition Alternatively it i
40. de adequate mains supply input signal cable segregation 3 1 2 Cable Quality and Installation It is vitally important that good quality cable is used and that correct installation techniques are followed In general the following cable installation requirements must be met 1 All cable sections must be circular to allow effective cable clamping using the cable glands 2 The cable must be screened sheathed to provide protection against Radio Frequency Interference RFI and the screen must be connected to earth at the control panel The screen must be continuous throughout the loop 4 Cable recommended for use is MICC with a LSF PVC overcovering a fire resilient cable to BS7629 or PVC SWA PVC to BS6387 HLSI MN 103 I v 05 http www honeywelllifesafety es Zones Leave blank Main power supply Recommended Cables User Manual 12 RP1r Supra 3 2 EMC Considerations Following the above instructions and by using suitable cables EMC problems will be avoided In particularly difficult EMC environments or where non preferred cabling is used it is possible to fit additional ferrite suppressors sleeves to cables entering the control panel 3 2 1 Screen Termination Cables should be screened or metal coated and the screens must be earthed within the enclosure Multiple earthing of cable screens must be avoided Six earthing points are provided for this purpose next to the cable entry points at the rear
41. e Activated Activated Y SIA A Release MA Disablement Active Pressure A AA Test Flow Pressure Power Low Monitored Released Cet A a Seneral Keypad Access Abort Fault Lamp test 3 sec System Nan A a Earth Silence Disabled Co Hold Fault Resound Monitored A Sounder Automatic Cct A Fault Evacuate Open door Disabled fm 8286 Manual Release Power Delay Only Faut 4 A Supply Bt onion Release Auxiliary Mute A Power Supply Fault Buzzer OFF Circuit A Fault ON Manual Release System Only 3 gp 6 oo oo ff oooo mad Z A lol z RS X2 RSZ232 AUX MO BAT BATTERY FUSE PSINEARTH PROG Zi 911910 000 VvVV VV Vv AA AA ON ON 9J 3 NJ3 ONJ ON LAY TIBNNEW ON 3 3NAVSIGASYI NIA L9IPIAd NILIY LINYA N39 0 um EOL mj EOL Lg External signals Digital input Fault relay State relays Preactive Active Released Mode relays Disabled Manual Automatic User Manual 68 RP1r Supra Appendix B Mechanical Construction Dimensions H x W x D Weight no batteries with batteries Mounting holes Cable entry points Terminals Environmental Climatic Classification Operating Temperature Humidity Panel sealing Controls amp Indications Display Status indicators Zone indicators Controls Access control Buzzer
42. e to meet EMC requirements defined by European Directives and to preserve the integrity of the screen connection 5 Use insulation sleeving on the tails between the cable entry position and the earth post Run the tails close to the rear wall of the back box 6 The supply to the panel must be provided with a suitable and readily accessible double pole mains disconnect device The mains supply must be suitably fused and rated according to the specifications 7 The cable entry points on the extreme left hand side of the enclosure should be used for mains cable entry DO NOT route mains cables using any other cable entry points and ensure that the mains wiring is always separated from the low voltage wiring 8 All low voltage cables should have a minimum 300Vac rating HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 11 RP1r Supra 3 1 1 Cable Terminations This section provides guidance on where to bring cables into the enclosure for ease of termination Ensure the following reguirements are met 1 The mains supply should be brought into the control panel such that the cable path to the PSU is kept as short as possible 2 All loop and ancillary cable terminations should be brought into the panel enclosure using cable entry points close to their termination points to ensure tails are kept as short as possible 3 Some cable entry points e g the nearest to mains entry should be left unused where possible to provi
43. esponding procedure User Manual 65 RP1r Supra 5 6 Monitoring functions 5 6 1 Overview The monitoring technigue using a diode or capacitor as an end of line EOL element as opposed to the traditional method of supervision through resistive EOL allows the control panel to monitor the wiring by determining if this has resistive minimum conditions to guarantee its function That is if one of the wiring lines e g extinguishing circuit has an excessive resistance along the length or quality of the cable e g 4 Q with 1A of current this would mean a voltage drop of 4V which could result in that the solenoid valve associated to that circuit could not be activated Classic monitoring method using EOL resistive element only determines the status of a line in relation to short circuits or open circuits so the previous case had not been detected With the technique used in RP1r Supra using diodes and capacitors as end of line elements it is possible to determine the resistance of the line and to be aware of hypothetical faults in the wiring Values which emerge from the supervision of the different circuits can be monitored and visualized at the control panel These monitoring functions are only accessible from access level 3 see Section 4 3 Access Levels for more information 5 6 2 Access to monitoring functions The following procedure must be followed in order to access to monitoring functions e Gain Access Level 3 by c
44. ess without key as described in section 4 3 was used HLSI MN 103 I v 05 http www honeywelllifesafety es x ee ES mip GEA User Manual 34 RP1r Supra 4 3 Access levels The control panel will enable or disable access to system functions depending on the operating access level Level 1 Always available with the control panel ON This level do not require activation The user is only allowed to mute the internal buzzer and the led test If any other push button is pressed the control panel will briefly activate the An eee oe internal buzzer and its led Je DE aa A Level 2 Available by turning the key clockwise in order to unlock the keypad 3 ae i Most of the functions are available function and zone keys O G Ge Keypad access led ON indicates that level 2 is available RAS AA 1 p Access level 2 with restrictions is also gained by means of the following ain ie a BE sequence of keys lt E BLZ o e Press and keep pressed the bz ES Te z rr e While keeping pressed the Ey key press the following keys in this order Z1 Z2 Z2 Z1 Es e ro Ed Level 3 Available by closing the PROG jumper located inside the control panel pais ane Get This access level is used to programme and change the control panel AM Lada Nad0 SSIud wood MOi Mi NI Y11910 i NJ ON3 OND ONJ ON3 ON3 ONNI OLNY TONNYW 0378yS1003S43734 LIPI NILIY LMNYA N39 configuration 4 4 Opera
45. extinguishing release process e Activated terminal block 8 ACTIV e Preactivated terminal block 9 PREACT e Release in progress terminal block 10 RELEASED In standby mode de energized the 3 relays have an open circuit between their terminals C and NO as shown in the illustration O Common O NO O Common oO NO To indicate the control panel status or phase the corresponding relay is activated In that situation the affected relay s will show continuity between the terminals C and NO al loro DISABLED MANUAL C NO C NO 3 5 4 3 Operating mode contacts Terminal blocks 11 12 and 13 The control panel provides 3 output contacts which indicate the control panel status e Disabled terminal block 11 ON IN 9 3 Z e e Manual terminal block 11 e Automatic mode AUTO terminal block 13 Relays for release process indication ON 3 ON 3 In standby mode de energized the 3 relays have an open circuit between their terminals C and NO as shown in the illustration 3 ON To indicate the control panel status the corresponding relay is activated In that situation the affected relay will show a closed contact between the terminals C and NO 3 Relays for operating status indication ON ON 3 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 28 RP1r Supra 3 5 5 Output monitoring By default the control panel s monitored output terminal blocks
46. f UNE EN 12094 1 2004 it is possible to specify a delay known as a pre discharge warning time which shall be adjustable from 00 and 60 seconds The configuration of this delay time is restricted to the access level 3 during the control panel configuration process and by means of the parameter E see Section 5 Control panel configuration for more details The value of this parameter will establish the delay time between the gas release manual call point and the beginning of the release process By default in case of manual call point release the control panel starts the extinction process immediately regardless of the value stored in parameter Ek If the delay is needed this option must be activated through the modification of the parameter Pd refer to section 5 Control panel configuration for more details When the control panel is in Disabled mode the call point activation will only cause the sounder circuit activation Preactivated status To enable the use of a second auxiliary manual call point connected to the MANUAL REL 2 input block B see section 3 4 1 for more details it is necessary to previously activate this feature using the parameter Ec by accessing control panel configuration mode In this case the activation of this second manual call point does not make the control panel enter in Activate status and it only activates extinction circuit 2 block 2 see section 3 5 1 for more details The text EZ is displayed The contr
47. ify and revise this document without notice HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 4 RP1r Supra 1 Introduction The purpose of this manual is to provide the user with all recommended procedure descriptions and full technical details for the successful installation and commissioning of the extinguishing control panel which is referred to Procedures described in this manual include appropriate warnings and cautions to guide the user towards adopting safe and methodical work practices during the installation and commissioning phases 1 1 CE Marking C This panel is CE Marked to show that it conforms to the requirements of the following European Community Directives e Electromagnetic Compatibility Directive 89 336 EEC and the amendment of the Directives 92 31 EEC 93 68 EEC e Low Voltage Directive 73 23 EEC and the amendment of the Directive 93 68 EEC e The Constructive Products Directive by the application of the following standards e UNE EN 54 2 Fire detection and fire alarm systems Control and indicating equipment e UNE EN 54 4 A2 2006 Fire detection and fire alarm systems Power supply equipment e UNE EN 12094 1 2004 Fixed firefighting systems Components for gas extinguishing systems Part 1 1 2 System Design and Planning It is assumed that the system of which the Extinguishing control equipment is a part has been designed by a competent fire alarm system designer in accordance with
48. ing oe Faut e Press the key s associated to special features to be modified see table The LED will change its status showing the modification on the associated function UNE EN 12094 1 2004 non compliant Special setup only for configurations where EN 12094 1 2014 is not applicable If this setup is selected the CE labeling related to this standard has to be removed from the equipment This kind of configurations are not compliant with UNE EN54 4 A2 2006 and UNE EN 54 2 regulations They are only available for special cases and must be used in agreement with the appropriate authority If this setup is selected the CE labeling related to this standard has to be removed from the equipment HLSI MN 103 1 v 05 http www honeywelllifesafety es Latched faults Faults need to be RESET by the control panel default Off Resettable faults Faults are self resettables once the fault cause has disappeared on Main power supply faults are indicated default Main power supply faults are not indicated on Battery faults are indicated default Battery faults are not indicated Sounders will re activate after a new alarm default Sounder will not re activate after a new alarm En VSN4 REL module installed off No VSN4 REL module installed default A number of special configuration profiles can be selected with special functions non standard The selected profile is identified on the 7 segment display
49. inputs for external signals available in the control panel it is possible to detect and signal events from external devices To ensure the monitoring it is necessary to install a serial 2K2 resistor with the corresponding sensor output contact and a 47yF 2 35V capacitor is required as an End Of Line element or alternatively an EOL resistor 6K8 See Section 5 Control Panel Configuration for more details Refer to Section 3 4 7 Input monitoring for more information 3 4 5 1 Low pressure signal LOW PRESS Terminal block H The low pressure input allows the control panel to signal the status of loss of extinguishing agent in the bottles sent by the sensors installed in the bottles 3 4 5 2 Flow signal FLOW PRESS Terminal block The control panel has an input that allows the connection of the corresponding flow sensor which will be monitored to comply with the requirements of UNE EN 12094 1 2004 section 4 18 Signal flow of extinguishing agent This is a self resettable input 3 4 5 3 Door open signal Terminal block J This monitored input indicates the status of the door of the building where the extinguishing system is installed The indication is purely informative however if the control panel is configured properly it is possible to condition the automatic extinguishing process by blocking it when the door is open see Section 5 Control panel configuration for more details HLSI MN 103 I v 05 http www
50. ion displayed on the panel s LCD using the various function keys These keys are located on the right side of the front panel Entering a valid access Level 2 passcode or using the keyswitch optional will make these keys functional See Section 4 2 2 Function keys for more information HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 31 RP1r Supra Internal Buzzer This audible device activates to alert the user to take immediate action whenever the system detects any condition such as a fire or fault event Depending on the type of event the buzzer activates sounds using a different tone pattern Mute nd The MUTE BUZZER control key is used to silence mute the internal buzzer in the event of these conditions occurring 4 2 1 LED Status Indicators The front panel leds are used to know the system status All the information according to the standard requirements is clearly visualized by means of these leds 4 2 1 1 Front panel detection process The group of leds located on the right side of the front panel are the indicators and keys used for the control panel detection process Zone status leds System alarm led Disablement led disabled zone Test led zone test Power led General Fault led Earth Fault led Sounders Fault Disabled led Power Supply Fault led Auxiliary Power Supply Fault led System Fault led Keypad Access led Access Level 2 Silence Resound led Evacuate
51. is used to calculate total time 19 15 sec 100 115 sec 19 200 215 sec Time delay in case of manual release HLSI MN 103 I v 05 http www honeywelllifesafety es In order to differentiate if digits displayed on LCD stand for a parameter or a value Access level 3 a flashing dot between both UNE EN 12094 1 2004 regulation section 4 17 describes a delay time before flooding or extinguishing procedure activation called pre alert or pre soak time This time can be modified from 00 to 60 sec with 5 sec steps Delay t for extinguishing default value 60 sec Selectable value from 00 to 60 sec According to UNE EN 12094 1 2004 regulation section 4 21 there s a soak or flooding time definition for low pressure extinguishing systems Selectable value from Time while extinguishing circuit remains 05 to 295 sec active soak time With 5 sec steps Circuit remains active until control panel is reset default option In case extinguishing is released by manual call point it s possible to set the delay time before extinguishing P00 Immediate release default value 01 Same delay than activated by detection defined by EE parameter User Manual 56 RP1r Supra Release for extinguishing circuit 2 Enable disable release for extinguishing circuit 2 Disabled default value Extinguishing repetition Enable disable supervision for FLOW PRESS input to decide if release signal should be repeated
52. it s real Enabling this parameter and in case there is an alarm on any of the three zones control panel automatically resets the affected zone and waits up to 10 minutes to confirm this alarm If alarm is repeated on the same zone this will be notified immediately Otherwise the timer will be reset after 10 minutes Without alarm confirmation default value With alarm confirmation User Manual 58 RP1r Supra Resettable ABORT input AN UNE EN 12094 1 2004 non compliant Open door behaviour Operating mode for digital input HLSI MN 103 1 v 05 http www honeywelllifesafety es According to UNE EN 12094 1 2004 regulation section 4 27 in case that an emergency abort signal is activated from an external device connected to ABORT input the extinguishing signal will be inhibited and a manual reset will be reguired to enable it again 00 ABORT input not resettable default value ABORT input self resettable Defines how control panel reacts in case its door is opened P00 Just notify Open door default value 01 Extinguishing procedure locked until door is closed Associates a function to DIGITAL IN input Remote reset default value ot Evacuate 01 02 Mute sounders 03 4 Delay ON OFF User Manual 59 RP1r Supra 5 3 3 Sounders options Sounders activation mode Defines when sounders are activated Sounders are activated when PREACTIVE status default value Sounders are acti
53. lays have a short circuit between its terminals C and NO except the general fault relay 7 which has 3 terminals C NO NC and allows two status open circuit C NO closed circuit C NC HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 14 COOEOE RP1r Supra 3 4 Input circuits connection This section describes the criteria and reguirements for the connection of different circuits and devices whose signals will be used as inputs of the control panel 3 4 1 Gas release Terminal Blocks A and B If an auxiliary call point optional is connected to terminal block A the manual gas release can be activated when the control panel is in Automatic or Manual mode When the control panel is in System Disabled mode the manual call point activation will only activate the sounders circuit Preactivated condition Asecond auxiliary call point can be connected to terminal block B in order to activate the release in circuit 2 For this this function must have been previously activated at the control panel configuration See Section 5 Control Panel Configuration for more details To ensure the monitoring it is necessary to install a serial 2K2 resistor with the call point and a 47pF 2 35V capacitor as an End Of Line element EOL NO Call point i EOL capacitor 47uF Alternatively and for compatibility reasons with previous installations it is possible to replace the capacitor by an EOL resistor 6K8
54. losing jumper PROG see Section 4 3 Access Levels for more information e Press Evacuation key to enter Monitoring mode e Evacuation led flashes and the corresponding keys light up to be identified e Parameters and associated values are displayed on the front panel e Press the Evacuation key again to leave the Monitoring mode HLSI MN 103 1 v 05 http www honeywelllifesafety es Released System Disabled Automatic Manual Only Pre Activated Activated Manual A Release Active Pressure Flow Pressure Low Monitored t AN Abort Monitored A Cct Hold Monitored A CL Open door Release Fault A Wy Alarm MA Disablement S Z1 E 22 Z3 oe Keypad Access J Fault Lamp te8t 3 sec EEN in Silence J Fault Resoun MN Sounder wy Evacuate S td A raul ed 3 sec a i gt Power Delay A cer onor e User Manual 66 RP1r Supra 5 6 3 Monitored Parameters The following parameters are monitored by the control panel and accessible through Monitoring mode Earth leakage level The display shows the monitored value of Earth leakage level Leakage to negative will reduce level while leakage to positive will increase it Typical value 99 100 Sounders circuit 1 Resistive value of sounders circuit 1 SND1 Sounders circuit 2 Resistive value of sounders circuit 2 SND2 Extinguishing circuit 1
55. m Monitored input for hold device NO 2 SND1 SND2 MAN REL REL 2 MAN REL SWITCH 21 ZR 25 D Monitored input for extinguishing abort device NO i H E Monitored input for detectors call points connexion Zone 1 er W Alarm 1 F Monitored input for detectors call points connexion Zone 2 Manual A ei 5 Monitored input for detectors call points connexion Zone 3 or manual call o Q point for gas release e A Test E PNE 9 Monitored input for low pressure signal NO ressue AL NAN power 1 Monitored input for flow detection NO mada 5 3 47 J Monitored input for open door detection NO Released opted A d O e z 2 K Digital input for programmable external contact voltage free System oo A gt gt 8 Dus ore ae Ae AG gt mo A Monitored output max 1A for release devices solenoid activation circuit 1 oa n e amp gt 10 2 Monitored output max 1A for release devices solenoid activation circuit 2 a g gt 41 24Vdc output 250mA For release devices supply Resettable an a S 24Vdc output 250mA For auxiliary devices supply Fix dleas E g gt 12 Monitored output max 250mA for sounders activation circuit 1 Oz gt 13 Monitored output max 250mA for sounders activation circuit 2 Status relay General Fault Status relay Extinguishing release activated In standby mode de energized relays or without power supply all the status re
56. nders circuits are automatically restored 4 8 4 Silence sounders Unlike the section above 4 8 3 Disable sounders the active sounders can be silent not disabled temporarily by pressing Silence Resound key rui Mam always from Access Level 2 77 Silence By pressing the Silence Resound Jason K key twice the sounders sound again HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 49 RP1r Supra 4 8 5 Mute Buzzer key 4 8 6 Disable external device only for Belgium pecial Functions for more information the external device key for 3 seconds If the option described in UNE EN 12094 1 2004 section 4 26 is enabled see Section 5 4 S linked to the control panel will be disabled or enabled by pressing the Delay On Off e HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 50 RP1r Supra 4 9 Faults 4 9 1 Auxiliary power supply fault According to UNE EN 54 4 A2 2006 compulsory from August 2009 it is necessary to monitor the batteries internal resistance in order to ensure a correct and safe operation in case of a mains failure The control panel makes periodic measurements of the battery internal resistance to check the resistive value If this value is higher than 700 mQ an Auxiliary power supply fault will be generated to indicate that the state of batteries is not correct 4 9 2 Monitored circuits faults All monitored inputs and outputs require an End
57. ol panel automatically leaves this status when the condition of manual call point 2 activated disappears 4 6 2 Hold device Following the instructions of Section 3 4 2 Hold device and according to the requirements of UNE EN 12094 1 2004 Section 4 20b Emergency detection devices the control panel supports optional the connection of a hold device which will stop manually the automatic release sequence If the hold device is activated when the control panel has already started the countdown Activated mode the control panel sounders will change from rapid frequency mode to low frequency mode the countdown stops and the output contact corresponding to Disabled mode will activate If the Activation has been started from a manual call point the countdown will only be cancelled if the delay option is activated This option which is disabled by default can be enabled by modifying the parameter Pg in the configuration mode see Section 5 Configuration for more details The sequence of actions that are implemented by the control panel once the HOLD call point has been activated is the following HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 42 RP1r Supra While the push button input is active the countdown timer remains held up and awaiting Contact DISABLED ON Sounder outputs SND1 and SND2 operate in slow pulsing mode 1 Hz SND1 SND2 The HOLD input is self resettable By releasing the
58. on an EOL diode is required or alternatively an EOL resistor 6K8 Refer to Section 3 5 5 Output monitoring for more details Circuit 2 not used Extintion circuit 1 To avoid irreparable damage to the control panel always use the diode diagram on the right in connections which involve the use of coils holders relays dampers etc Extinguishing release circuit AUX MANUAL HOLD ABORT SND1 SND2 MAN REL REL 2 MAN REL SWITCH Z1 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 24 RP1r Supra 3 5 2 Auxiliary 24Vdc Output Circuit Terminal blocks 3 and 4 The Base PCB provides two 24Vdc outputs supplied by the control panel power supply which can be used to drive ancillary equipment indicators Maximum current supplied by each output is 250mA Both outputs have an over current protection fuse Aux 24V output terminal block 4 provides constant 24Vdc with 250 mA max current to supply ancillary devices X On the contrary 24V RES output terminal block 3 which is also 24 Vdc and 250 mA provides resettable supply Thus when the control panel is reset the output voltage goes down to OV for 5 seconds approximately This type of output is used to drive external ancillary devices which require a momentarily power cut off in order to be reset Before connecting auxiliary devices to the control panel please consider the following e Ensure that the external wiring is not short cir
59. on of this delay time is restricted to the access level 3 see Section 5 Control panel configuration for more details The GAS sign flashes The countdown begins By default the timer shows 60 seconds When release has been caused by the action of the manual call point the sequence of extinction begins immediately without applying the delay set in the parameter During the delay time the sounders cannot be silent It is possible to change this behaviour by default through the modification of the parameter Pd refer to section 5 Control Panel Configuration for more details HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 39 RP1r Supra 4 5 4 Extinguishing release status When the delay time is over the control panel activates the extinguishing release and the following indications are present POWER LED green This is lit continuously when the panel is powered The internal buzzer operates steady tone GENERAL FAULT relay GEN FAULT energized standby continuity between C and NO The ALARM led red lights in steady mode Zone status leds indicate Alarm in the corresponding zone Flashing in case of a detector alarm Steady in case of a call point alarm Pre Activated Activated i Status leds Preactivated ON Activated ON Status contacts PREACT ON ACTIV ON RELEASED ON ACTIU PREACT RELEASED C NO CNO CNO Sounder outputs SND1 and SND2
60. or used and if necessary respect the polarity of the connection Connection example HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 22 RP1r Supra 3 4 7 2 Monitoring with EOL resistor Alternatively itis possible to use a 6K8 resistor as an End Of Line element for input circuits so that the system is backward compatible with existing installations which use the traditional monitoring EOL resistor This monitoring mode is enabled from the control panel configuration Refer to Section 5 Control panel configuration for more details The criteria for monitoring and discrimination of the different states by using an EOL resistor 6K8 is as follows e For call points with NO contacts default when the R 2K2 line is closed the input becomes ACTIVE regardless of whether the EOL resistor 6K8 is present or not In the latter case ACTIVE input without EOL resistor the control panel will also indicate a fault e For call points with NC contacts when the R 2K2 line is open the input becomes ACTIVE regardless of whether the EOL resistor 6K8 is present or not In the latter case ACTIVE input without EOL resistor the control panel will also indicate a fault Call point NO Call point NC EOL resistor 6K8 EOL resistor 6K8 Resistor 2K2 Resistor 2K2 Monitoring topology for NC circuit resistive monitoring mode Monitoring topology for NO circuit resistive monitoring mode
61. oring of the status of components Low pressure Section 4 19 Emergency hold device Sequence b Section 4 20 Control of flooding time Section 4 21 Manual only mode Section 4 23 Triggering of equipment outside the system Section 4 26 Emergency abort device Section 4 27 Activation of alarm devices with different signals Section 4 30 The RP1r Supra design is based on a modular build concept which offers the user completely flexible system solutions Each control panel is comprised of a number of separate build modules to simplify the installation process The electronic components are contained in an easy to fit enclosure specifically designed to simplify panel installation To this end the electronics need not be installed until system commissioning is to be undertaken thereby reducing the incidence of damage or contamination resulting from other trade activities EQS WFIX concept RP1r Supra is a compact control panel which includes a 65W switched power supply with battery charger circuit and it has space provision for two sealed lead acid batteries has 2 x 7 Ah for backup in case of mains loss In accordance with UNE EN 54 4 A2 2006 compulsory standard from August 2009 it is necessary to supervise the internal battery resistance to guarantee the battery correct operation in the event of a power supply f
62. push button the input is no longer active and the countdown restarts According to UNE EN 12094 1 2004 section 4 20 4 if there is a fault in the hold device monitoring circuit the control panel must indicate the fault condition and avoid the activation of the release circuit It is possible to configure if the Gas release push button input auxiliary or Zone 3 call point or has priority over the Hold device by changing the parameter ha during the control panel configuration refer to Section 5 Control panel configuration for more details 4 6 3 Emergency Abort device Following the instructions of Section 3 4 3 Emergency Abort device and according to the requirements of UNE EN 12094 1 2004 Section 4 27 Devices for emergency abort the control panel supports the connection optional of an emergency ABORT device to manually stop the automatic release sequence DISABLED Contact ON Sounder outputs SND1 and SND2 disabled silent SND1 SND2 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 43 RP1r Supra The Abort input is latched so once activated it will reguire a manual reset of the control panel to enable the extinguishing process again As an alternative and by modifying the parameter Gr see Section 5 Configuration for more details it is possible to change the default operation of the control panel in front of the activation of the ABORT input allowing the control panel to keep the abort
63. relay outputs Auxiliary input contacts Digital input Auxiliary 24Vdc supply Internal clock Event log Communication Electrical supply Classification Mains supply Max Power Standby power consumption HLSI MN 103 1 v 05 http www honeywelllifesafety es 3 independent zones e 2 zones for conventional detectors e 1 configurable zone for detector or manual call point 2 monitored output circuits for sounders 2 x 250 mA 2 monitored output circuits for extinguishing release devices activation 2 x 1 A 7 output contacts for the following functions e 1 general fault relay e 3 release status relays Activated Preactivated In progress e 3 operating mode relays Disabled Manual Automatic 7 monitored input circuits for the following functions e 2 for Manual Release call points connection e 1 for Hold device connection e 1 for Abort emergency device connection e 3 for technical alarm contacts Low pressure Flow and door open 1 digital input which can be configured as NO NC Two 24Vdc outputs resettable and non resettable to supply external devices la 2 x 250 mA Internal clock RTC for event log with lithium battery CR2016 CR2025 or CR2032 Capacity 1000 events Accessible through software 4 internal ports e 2 serial ports RS 232 TTL with Rx Tx and Gnd no hardware flow control e 1 serial port I C e 1 USB port type B connector Installation Class 1 the control panel must be earth
64. s possible to replace this resistor by a reversed polarity diode see diagram below Sounder circuits must be wired as a single circuit with no spurs or T junctions to ensure the correct operation of the monitoring function See figures below Moreover an EOL diode 1N4007 or similar with reversed polarity see figure must be installed after the last sounder EOL diode 1N4007 reverse pol Alternatively and for backward compatibility reasons it is possible to replace the diode by an EOL resistor 6K8 See Section 5 Control panel configuration for more details EOL diode 1N4007 reverse pol Sounders 1 Sounders 2 Refer to Section 3 5 5 Output monitoring for more information The sounders should be polarized otherwise a 1N4007 or similar diode must be connected to sounder positive terminals to avoid fault conditions EOL diode 1N4007 ea reverse pol SND1 SND2 Sounders 1 1 1 I 1 git ty oo I 1 Ea I m 7 IA oe Tya a La Diodes needed ONLY in case of non polarized sounders Sounder circuits E SND1 SND2 AUX MANUAL HOLD ABORT 24V SNDI SND2 MAN REL REL 2 MAN REL SWITCH Zl AA ZAS a HLSI MN 103 1 v 05 User Manual http www honeywelllifesafety es 26 RP1r Supra 3 5 4 Status relays Terminal blocks 7 8 9 10 11 12 and 13 The control panel status and operating mode is indicated by means of output relays In de energized mode all the sta
65. the following indications are present If the countdown is activated release in process and the door is open the release process goes into Hold mode When the door is closed the countdown starts again from the beginning The internal buzzer operates pulsing tone GENERAL FAULT relay GEN FAULT non energized fault continuity between C and NC The ALARM led red lights in flashing mode Monitored A CC pan door o Door open led lights in steady mode Monitored A P npr Cet Hotd MP Hold lights in steady mode If the option 4 26 from EN12094 1 2003 is enabled see Section 5 4 Special Functions for more information then the Open Door led will be used to indicate if the fan output is disabled led ON or enabled led OFF HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 46 RP1r Supra 4 7 4 Digital input Following the description of Section 3 4 6 Digital input the control panel provides a programmable digital input for a free voltage external contact in order to control the panel from any other external system Refer to Section 3 4 6 for more details There are a number of operations which can be carried out when this contact is activated These operations are determined by the indications of parameter IL Refer to Section 5 Control panel configuration for more details User Manual HLSI MN 103 I v 05 47 http www honeywelllifesafety es RP1r Supra 4 8 Disablements
66. the requirements of EN54 Part 14 UNE 23007 14 and other applicable local standards The design drawings should clearly show the positions of all the control panel and field devices Extinguishing control panels are manufactured in compliance with national and local standards and meet the requirements of UNE EN 12094 1 2004 UNE EN 54 2 and UNE EN 54 4 A2 2006 However some installation and configuration practices may not meet the standards Contact the proper authorities to confirm the requirements 1 3 Personnel Installation of this product must be carried out only by suitably qualified electrical engineers Read carefully the commissioning and configuration procedures of this manual It is recommended by the manufacturer to check the wiring lines before making any connection to the panel or equipment Do not carry out any configuration functions without fully understanding of their operation HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 5 RP1r Supra 1 4 General This release control panel RP1r Supra has been designed to manage correctly and according to UNE EN12094 1 2004 UNE EN 54 2 and UNE EN 54 4 A2 2006 the automatic release sequence of most of the extinguishing systems Moreover RP1r Supra meets the following EN12094 1 Options with requirements Delay of extinguishing signal Section 4 17 Signal representing the flow of extinguishing agent Section 4 18 Monit
67. ting modes The control panel has three operating modes which can be selected with the mode selector The corresponding led is ON when a mode is selected The selection of the operating mode can only be carried out from level 2 and only by gaining access by means of the user key e The control panel manages any alarm from zones or from the gas release call point on the front panel and carries out the release process automatically following the conditions and delays already configured Manual only The control panel manages any alarm from zones activating the corresponding conditions and sounders However the release can only be activated from the GAS release call point Automate System Disabled located on the front panel or from the Zone 3 if it is configured as Manual Release System e The same as the above condition but it does NOT allow the release outputs to be activated Disabled even manually Manual Only HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 35 RP1r Supra 4 5 Control Panel Status System Disabled For a description of the different status the control panel is operating in Automatic mode In this situation the led on the front panel is Pa a tomatic lit in amber and the corresponding output contact AUTO keeps activated For any other operating modes the leds and activated Kenalan contacts will be those corresponding to the selected mode DISABLED MANUAL AUTO cC
68. tus relays have a short circuit between its terminals C and NO except the general fault relay 7 which has 3 terminals C NO NC and allows two status open circuit C NO closed circuit C NC 3 5 4 1 General fault contact GEN FAULT Terminal block 7 The general fault relay indicates the existence of a fault condition in the control panel In the panel s quiescent status the relay is energised and when the panel is in a fault condition the relay is non energized Depending on the control panel configuration the fault signals can be resettables or latched refer to Section 5 Control panel configuration for more information Faults are latched by default and the control panel has to be reset for the relay to return to its normal condition energized On the contrary the resettable faults make the relay return to its normal condition automatically when the fault is cleared c O O NC NO VI BA Note the figure on the right shows the fault condition The relay is non energized In the panel s quiescent status the relay is energised e Quiescent status Continuity between C and NO contacts e Fault or without power supply Continuity between C and NC contacts GEN FAULT C NC NO HLSI MN 103 1 v 05 User Manual http www honeywelllifesafety es 2 RP1r Supra 3 5 4 2 Status contacts Terminal blocks 8 9 and 10 The control panel provides 3 output relays to indicate the status of the
69. unting plate has been installed correctly as described in Section 2 4 1 Mounting Plate Installation This procedure assumes that all field cables have been secured on the mounting bracket with fire industry approved cable glands using the appropriate cable apertures knockouts and appropriately labelled by function in readiness for termination within the panel Step 1 e With the mounting plate installed on the wall in the desired location offer the two rebates located at the top of the panel enclosure to engage the enclosure to the mounting plate e While performing this procedure you will need to guide each of the field cables through the aperture located at the back of the enclosure until they are within the enclosure Step 2 e Once the enclosure is aligned correctly with the mounting base use the 4 suitably sized screws to fix it HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 9 RP1r Supra CAUTION ENERGY HAZARD NEVER short the battery terminals CAUTION RISK OF EXPLOSION If battery is replaced with an incorrect type 2 4 3 Installing the Batteries The batteries must be located in the dedicated space in the lower part of the RP1r Supra enclosure which has space provision for two 7Ah 12V sealed lead batteries e Orientate the batteries so that the wiring connection terminals of each unit are adjacent to each other as shown opposite then offer each in turn to the enclosure
70. utes since ACTIVE status is notified and reset is allowed Reset remains disabled until released is finished or until the time configured in parameter A ends A 0 seg Allowed reset at any time default value De 01 a 30 Reset remains disabled during configured time minutes Defines the threshold level to detect an earth fault High Sensitivity It allows choosing End Of Line EOL device used for outputs monitoring EOL is a diode default value User Manual 63 RP1r Supra 5 4 Special features UNE EN54 non compliant 5 4 1 Overview This control panel allows special configurations for resettable faults single 24V operation for naval sites or powered from UPS or single 220Vac operation as a dependant subsystem These configurations do not meet UNE EN 54 4 A2 2006 or UNE EN 54 2 reguirements and are only used for special operations 5 4 2 Special functions configuration In order to modify any of the special features the following procedure should be followed e Switch off the control panel main supply and batteries e Change control panel into level 3 by closing jumper PROG see section 4 3 Access level for additional information e Switch on the panel again e After a few seconds almost all LEDs will turn off and only LEDs associated to special functions will remain turned on showing the current status for special configuration see table The System fault System LED will be flash
71. vated when ACTIVE status Operating mode for sounders 2 Sounders circuit 2 operates by default like sounders circuit 1 flashing mode and its freguency depends on panel status Sounders 2 flashing mode like Sounders 1 default value Sounders 2 always activated on steady mode Disabled sounders notification Defines Disabled sounders LED status during sounders delay According to UNE EN 54 2 regulation section 9 4 2c the sounders delay should be indicated as a disconnection LED ON during sounders delay default value LED OFF during sounders delay HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 60 RP1r Supra 5 3 4 Line options Short circuit mode Defines how a short circuit condition for zones should be indicated Short circuit notified as a fault A default value UNE EN 154 2 non compliant pO Short circuit notified as an alarm Monitoring mode for inputs It allows choosing End Of Line EOL device used for inputs monitoring O A EOL is a capacitor default value Input mode for HOLD and ABORT It allows choosing operating mode for external devices connected to HOLD signals and ABORT inputs Normally open circuit NO default value Normally closed circuit NC Input mode for LOW PRESS signal It allows choosing operating mode for contact connected to LOW PRESS input Normally open circuit NO default value Normally closed circuit NC Input mode for FLOW PRESS signal
72. will operate in steady tone SND1 SND2 HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 40 RP1r Supra wa The GAS sign lights in steady mode The timer keeps the value 00 seconds in flashing mode The Released led flashes GOS Release Circuits the output relays for solenoid activation of release devices are activated during the period of time already aa configured parameter A 295 sec default value CCT EXT 1 2 4 5 5 End of extinguishing release When the release period of time indicated in parameter A is over the following indications are present E i The timer keeps the value 00 seconds in steady mode The Released led lights in steady mode Bove Release Circuits the output relays for solenoid activation of release devices are disabled HLSI MN 103 I v 05 User Manual http www honeywelllifesafety es 41 RP1r Supra 4 6 Auxiliary call points As described in Section 3 4 Input Circuits Connection it is possible to connect a number of auxiliary call points to the control panel to make the remote control easier 4 6 1 GAS release manual call point Following the instructions of Section 3 4 1 Gas release it is possible to connect an auxiliary call point optional for manual release only in Automatic or Manual operating modes The call point activation in this condition will make the control panel go into ACTIVATED status According to Section 4 17 o

Download Pdf Manuals

image

Related Search

Related Contents

KB–7245 - Billiger.de  Page 1 Page 2 ご~あいさっ この度は、 VESTAX PMC  Philips In-Ear Headphones SHE2630  CyberPower CS24U12V uninterruptible power supply (UPS)  Kidde 466425 Data Sheet  Manuel mairie BE1D  Waste King 9910 Use and Care Manual  Garantie des produits du groupe des solutions de télédiffusion et de  Brother 885-U24 Sewing Machine User Manual  Samsung CS-29K10ZQQ Инструкция по использованию  

Copyright © All rights reserved.
Failed to retrieve file