P90L 6kVA & 10kVA Online UPS
Contents
1. Backup Time 990 Minute Batt Test Tvpe Short Time 10 Second ECO 2 6 Status Open HighLoss V 232V LowLoss V 184V HighLoss F 60Hz LowLoss F 60Hz UPS Info 5 6 UPS Model 10KL DSP Ver 99 00 MCU Ver 97 00 Unit Name P90L Manufacturer X PCC Output 3 6 Volt 208V Freq Auto CVCE Disable Others Hot Standby Disable Bypass Mute Disable Batt Mute Disable Fault Mute Disable These pages display the information of parameters setting value or status Press UP or DOWN to navigate the Xtreme Power Conversion Corporation Page 21 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Setting Menu Setting Bvpass ECO Output Batterv Calibration Others This menu is used to adjust the parameters or do the calibrations Note Not all settings are available in every mode If the setting is not available in present mode the LCD will show prompt message with Item cannot be set in this mode Press any button or just wait for several seconds then this message will disappear 1 Bypass setting 1 Status only available in bypass line mode Open Forbid Open Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting Forbid Bypass not allowed When selected it s not allowed to run in Bypass Bypass mode under any situations Enable Disable Status Open This option appears only vvhen Open Forbid is
2. Power Conversion Corporation Page 33 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply product Only those devices registered in that manner will be covered 2 All Connected Equipment must be UL or CSA approved 3 The Product must be plugged into a properly wired and grounded outlet Use of input surge devices ex tension cords adapters ground wires or electrical connections not manufactured by XPC voids the XPC Load Protection Policy No other surge protection device may be connected to the output sockets of the Product The installation must comply with all applicable electrical and safety codes set forth pursuant to the NEC 4 The Product must have undeniable physical evidence of a Power Disturbance that directly and proximately caused the damage 5 The Connected Equipment must have been damaged by a Power Disturbance on a properly installed grounded and National Electric Code NEC code compliant 120 208 240 Volt AC power line in the United States or Canada by a Power Disturbance on standard telephone land line or PBX telephone equip ment line that is properly installed and connected to an RJ11 port on the Product or by a Power Distur bance on a standard Local Area Network connection that is properly installed and connected to an RJ45 port on the Product and d is directly plugged into and properly connected to the Product in its original condition which was properly operated when a Power Disturbance passed t
3. Relay dry contact Modbus Software CD horizontal brackets tower pedestals 5 year extended warranty power distribution XPDU 4 post rail kit 2 post shelf kit isolation transformer with maintenance bypass P90L capacity derates 10 at 200VAC output voltage Frequency converter derates capacity 4096 Xtreme Power Conversion Corporation Page 30 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Obtaining Service If the UPS requires Service 1 Use the TROUBLESHOOTING section in this manual to eliminate obvious causes 2 Verify there are no circuit breakers tripped 3 Callyourdealerforassistance Ifyoucannotreach yourdealer oriftheycannotresolvethe problem call Xtreme Power Conversion Corp Technical Support at 800 582 4524 Technical support inquiries can also be made at support xpcc com Please have the following information available BEFORE calling the Technical Support Department e Your name and address e The serial number of the unit e Where and when the unit was purchased e All of the model information about your UPS e Any information on the failure including LED s that may or may not be illuminated e Adescription of the protected equipment including model numbers if possible e Atechnician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial
4. be void e Non authorized technician is not allowed to install the unit in the following areas a Medical equipment directly related to human life b Elevator Metro Subway system or any other equipment related to human safety c Public System or critical computer Systems e Anyinstallation related to human safety public system or emergency device shall be consulted with deal er first otherwise your warranty will be void e f any liquid is split onto the unit or foreign objects dropped into the unit the warranty will be null and void e Do not install the unit in an environment with sparks smoke or gas e Make sure the unit is installed within a proper environment as specified a Keep itin the place of 0 40 C and 30 90 non condensing humidity b Keep away from direct sunlight c Keep away from the objects that give off excessive heat and areas that are excessively wet d Keep away from the environment that generates ARCs e Keep away from dusty corrosive and salty environments f Install the unit indoors as it is not designed for installation outdoors e To eliminate any overheating of the unit keep all ventilation openings free from obstruction and do not store items on the top of the unit Keep the unit 30 cm away from the wall e The unit is recommended to install in an environment with 5M3 airflow per hour e Make sure the unit is completely turned off when moving the unit from one place to the other It might cause electrical sh
5. control menu to turn on the UPS b On line mode or converter mode or ECO mode or battery mode it will display Turn Off in control menu If it is selected and confirmed the UPS will transfer to bypass mode or shut down Bypass Mode Turn Off IP 208 OV 60 OHz Batt Test OP 208 0V 60 OHz Mute Yes Batt 273 0V 993 Para Unlock gt No Load o Note You could turn off the UPS by pressing OFF ESC button at the home page It is not necessary to enter into this control menu to turn off the UPS 2 Battery Test Battery test is used to ensure that the UPS could work well in battery mode and to test the battery performance This item could be shown in all modes but will not work in Battery Fault Eco mode Related data will be shown at the same time Xtreme Power Conversion Corporation Page 19 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Control Batt Test Mode Batt Test Turn On IP 208 0V 60 OHz Batt Test 0P 208 0V 60 OHz Mute Batt 245 0V 50 Para Unlock Load 0 3 Mute This item is used to mute the buzzer in battery bypass fault mode In any other mode this item also could be seen but does not function and related data will also be shown After confirmation it will go to the home page and you can see the change of the mute icon Control Battery Mode x Turn On IP 0 0V 0 0Hz Batt Test 0P 208 0V 60 OHz gt Mute Batt 245 0V 50 Para Unlock Load 100 4
6. set to Open Enable Enable Bypass enabled When selected Bypass mode is available HighLoss V 264V This means that the UPS can go to Bypass mode automatically or LowLoss V 110V manually HighLoss F 60Hz Disable Bypass disabled When selected automatic bypass is ac 60Hz ceptable but manual bypass is not available Manual bypass means users manually operate UPS to Bypass mode for example in Line mode turning off the UPS to Bypass mode Then the UPS will go to bypass mode but without output if it is turned off in line mode Bvpass NOTE The follovving items are only available in bypass mode 2 HighLoss V Set the acceptable high voltage for bypass Setting range gt Status Forbid is from Rated Output Volt 11V to 276V and the default value is 264V HighLoss V 264V LowLoss V Set the acceptable low voltage for bypass Setting range LowLoss V 110V is from 110V to Rated Output Volt 11V and the default value is HighLoss F 60Hz 110V LowLoss 60Hz HighLoss F Set the acceptable high frequency for bypass 50 Hz Setting range is from 51Hz to 54 Hz 60 Hz Setting range is from 61Hz to 64Hz The default value is 54 0Hz 64 0Hz LowLoss F Set the acceptable high frequency for bypass 50 Hz system Setting range is from 46 0Hz to 49 0Hz 60 Hz system Setting range is from 56 0Hz to 59 0Hz The default value is 46Hz 56Hz LowLoss Xtreme Power Conversion Corporation Page 22 POOL 6kVA amp 10kVA User s Manual Uni
7. 0V 50 OHz Batt 273 0V 994 Load 100 After pressing the UP or DOWN button at the home page the screen will display the main menu of the operation menu In the main menu there are 5 items Control Measurement Information Setting Alarm to select Press UP or DOWN button to select item Press ON ENTER button to confirm the selection Press OFF ESC button to go back to the home page This operation is the same or similar in other menus or pages Please refer to the section of Button Opera tion section Xtreme Power Conversion Corporation Page 18 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Control Items Batt Test Mute Para Unlock Note Turn On will be displayed if UPS is not turned on Turn Off will be displayed if UPS is turned on In general situations these items will not be displayed at the same time or in all operation modes 1 Turn On Turn Off This item is for turning on off the UPS a In Bypass mode it will display Turn On if it is selected and confirmed the UPS will transfer to line mode converter mode ECO mode or battery mode according to the settings and input status Line Mode Turn On IP 208 0V 60 OHz Batt Test OP 208 0V 60 OHz Mute Yes Batt 273 OV 99 Para Unlock gt No Load 100 Note You could turn on the UPS by pressing ON ENTER button at the home page It s not necessary to enter into this
8. Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available as the Technical Sup port Technician about obtaining a replacement set of packaging material It is important to pack the UPS properly in order to avoid damage in transit Never use Styrofoam beads for a packing material 2 Include a letter with your name address daytime phone number RMA number a copy of your original sales receipt and a brief description of the problem 3 Mark the RMA number on the outside of all packages Xtreme Power cannot accept any package without the RMA number marked on the outside of the boxes 4 Return the UPS by insured prepaid carrier to the address provided by the Technician 5 Refer to the Warranty statements in this manual for additional details on what is covered Xtreme Power Conversion Corporation Page 31 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Xtreme Power Conversion Limited Warranty Xtreme Power Conversion XPC Corporation warrants Xtreme Power Conversion equipment when properly ap plied and operated within specified conditions against faulty materials or workmanship for a period of three years for P9OL Series products from the date of purchase XPC Corporation warrants P9OL Series battery packs for a period of three years from the date of purchase For equipmen
9. Bypass Detection FOr UNIEN E IIO RJ 45 connector Bypass Switch WxDxH 17 3 x 28 7 x 3 5 in P90L ISO6MB 17 3 x 28 7 x 5 2 in P90L ISO10MB Unit w Maintenance 92 6 Ibs 116 8 lbs Bypass Switch Unit Ks di Maintenance nribs 1146 Ibs Ks di Switch Current Leakage 100 load Marks CE cUL UL am a ee 184 280Vac 10 Xtreme Povver Conversion Corporation Page 49
10. E E Tm 14 UPS OPONI el ea Tm emm 14 RSbr le cue T NT 17 Main Interface Home Sereen oeste no Verhidavlibe a veenis Enna ERRORES REF AV RN VENULHK SUPROAUUU UN NUU R 18 Sierra lU T 18 TI Mt 19 ICS LC EN EP AD CS uote NE PERO RCP ONERE E ARUM EE RHDER IE RS UR DZPI SN DU RI LEN DEVO eU E CU EPI M DRE MRO 21 IOC CON Pado usted AEE E E E iu mM DIM ccu MIN Me UM L UE 21 SIE PY E Emm 22 PAIS Pale TAE EEEE I EEE E E nes orient iano EUM MM MM MM ME 25 IroubleshoO Dn ase cacac ican sv ecesnccanesccneseeuccceocendecasenscanenvasenuseeustecssereccssexsusvacs O Pasa seitdem m m 26 Fr QUIN OC E E A E A E E 26 Xtreme Power Conversion Corporation Page 3 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Trouble Shooting TaDl mem 26 SOVI ariaren T E EE 29 5 OECIEICA CIONS ossi EEE TE EE ANE AEE 30 Obtaining SELVICEcnensiaemmn tsssimmsssstmmsdsensssestsesismessmsmibneme 31 Xtreme Power Conversion Limited Warranty ssessesescesseceecesceceeceececsecee 32 Xtreme Power Conversion Load Protection Policy 33 Appendix A P9OL BP240 User Guide eee e eee eene ee nennen neus 36 Jngiorerquz nier T 8 AL RTL RTT 36 IS EURO dnd SO prasad eostaramtmmmssedimmnaitumecmcmtettgemimetbseienostmtzemetaca tb 36 Storage amp MAINteNnance c
11. Hz OP 242 8U 68 GHz Batt 2735 90 99 Load 3 LCD Panel Buttons AU OISJSAUO NT E Yo LED indicators AU3 LLV8 4 M M ee D ER EM Linva Xtreme Power Conversion Corporation Page 13 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply There are 4 buttons on front panel e Press this button to turn on the UPS ON ENTER e Or press it to confirm the selection in the menu e P hi ff the UPS OFF ESC ress t is button to turn off the UPS e Or press it to return to last menu Press this button to select the previous item in the menu UP Or press this button to jump to previous page in the screen Or press this button to increase the number in the setting Press this button to select the next item in the menu DOWN Or press this button to jump to next page in the screen Or press this button to decrease the number in the setting If pressing UP and DOWN button together the LCD display will rotate 90 automatically This operation is used when configuring the UPS to Rack or Tower display LED Indicators There are 4 LEDs on front panel to show the UPS working status UPS power on Bypass mode Line mode Converter mode Battery mode Fault mode Battery test mode ECO mode Note e means LED is lit o means LED is off means LED is flashing Audible Alarm Bypass mode Battery Battery test mode normal battery voltage Battery Battery test mode low battery voltage Fau
12. POOL 6kVA amp 10kVA Online UPS 6kVA 10kVA Models User amp Installation Manual www xpcc com 2014 Xtreme Power Conversion Corporation All rights reserved Rev 10 09 14 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Please comply with all warnings and operating instructions in this manual Save this manual and read the following instructions carefully before install ing the unit Do not operate this unit before reading all safety information and operating instructions carefully Xtreme Power Conversion Corporation Page 2 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Table of Contents Safety Warnings and EMC Instructions 4 eee eee eee eene eene eee sooo se e D JI oca s dalla e E E E E m 5 EEES CCD ES etat TT TOTO 5 ECO EE TTD t TEE 5 SX S IR To OS o E m ius vategeitatmen 6 LSTA ATION eT PPM A UPS Unpacking and RS D CC CO DM RO P NE WNW 7 System onele Line DIGBI OTT esteses sastetdausanaiauavacnsenecd EN AN EEREN 10 Rack Tower sta la Conieacmiimmadnmimmmsnmynammsmnsamcabamenmmmnttmai ideals 10 LP SE IG COL IS CON GE ON TE OO DOO 11 OE IONS TP E EEA TTE TRECE Operating Mode Status DescertpriOflussesndagentbbvE RR Rh ex CRISI Por RIR SUD SREREEE IUE SEE RUM E aab IER TU IA 13 DUI O DEL DO PPP RE ETT OO DDR TOURS 13 LEDINO CORS RETE UO E NEUR 14 AQUI AA PI REI O
13. Para Unlock Future Use This selection is for parallel protection unlock to allow for parallel unit operation It only appears when the LCD shows the warning 3F Para Protect that means the parallel system is in protection and cannot startup if you need to startup the parallel UPS this instruction must be executed Note Before executing this instruction you must check that the system s parallel cables and connections are cor rect Please read the related content in the trouble shooting section of this manual Control Is single or Bypass Mode parallel cable OK Parallel Master Turn On IP 208 0V 60 OHz Batt Test OP 208 0V 60 OHz Mute Batt 273 0V 99 gt Para Unlock Load 096 Xtreme Power Conversion Corporation Page 20 POOL 6kVA amp 10kVA User s Manual Measurement Pages Input Volt 208 0V Freq 60 OHz 2 6 208 OV 43 3A 60 OHz 208 0V Apparent Power 10000VA Active Power 9000W Load 100 1 5 Charger 208 OV Volt 60 OHz Status Uninterruptible Power Supply Battery Volt 273 0V Cap 10055 Dischg Time 00 00 00 These pages display the measurement value of the parameters such as voltage current frequency power capacity time etc Press UP or DOWN to navigate the pages Information Pages Bvpass 1 6 Status Open Enable HighLoss V 264V LowLoss V 110V HighLoss F 60Hz LowLoss F 60Hz Batterv DisChg Protect Enable
14. al Block P90L ISO10MB Output Terminal Block pajapaja nil III m w eju m u The drawing shown above is the default configuration Jumpers are pre installed for this configuration internally for 6kVA only 10kVA jumpers are to be made in the field shown below G L1 N L2 E E 0090363 T sin ut than eee ia A _ A E TESCO S TEE e terns WA LYONS ay Oi liebe BAM he da he gt P9OL ISO6MB Internal Jumper 0 P90L IS 10MB Internal Jumper Connect Maintenance Bypass Switch communication cable C1 from RJ45 port on P9OL ISO6MB or P9OL ISO10MB to green molex connector on UPS This prevents UPS damage should it not be in bypass prior to activating Mainte nance Bypass Switch on P9OL ISO6MB or P90L ISO10MB Xtreme Power Conversion Corporation Page 48 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Troubleshooting If the unit cannot be operated normally please check if all the cables are properly connected and the Utility is under normal condition If the problem cannot be solved please consult with your dealer immediately Specifications ME E Specifications Description Condition P9OL ISO6MB P90 ISO10MB AC Input Terminal Unit w o Bypass Switch 160 280Vac 10 Voltage Unit w Bypass 160 280Vac 10 Switch BYPASS 184 280Vac 10 30A max 50A max SOH2 60H2 SHz Output Terminal 30A max 50A max SOHz GOHz 3Hz Maintenance Bypass Switch 0 100 Load Communication
15. als on P9OL ISO10MB terminal block Hardwired output cord with ring terminals connets to UPS output terminals on P9OL ISO10MB terminal block Hardwired output to load RJ45 on transformer to Molex connector on UPS for static bypass interlock Battery connection Anderson to Anderson il a da Xtreme Povver Conversion Corporation Page 46 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation as a Rack Unit ee f 1 TR i AT Ir EJ Th B1 B2 S4 B1 B3 S4 P90L ISOGMB Terminal Block Explanations for Input Output Terminal Block Explanation TR OUTPUT UPS OUTPUT UTILITY INPUT ces Tz uo we v er o2 Tw Tu 6 o T LASTS Clio NO Lit UTILITY INPUT a1 EARTH 10K TROUTPUT TO UPS OUTPUT UTILITY INPUT T TB2 151 UPS Input shares i G2 N2 L2 G1 N1 L1 Utility Input terminal L1 N1 Utility Input UPS Input use same terminals as Utility Input G1 Input Ground L2 N2 Connect to UPS Output Terminal G2 Connect to UPS Output Ground Terminal L11 L12 N11 L22 N22 the Output Terminals of the Unit G3 The Output Ground Terminals of the Unit Output Wiring Explanation e The maximum output current for each terminal is 30A 6K or 50A 10K e fthe input of L2 N2 from UPS OUTPUT block is 208Vac the output voltage shall be 240Vac 120Vac Xtreme Power Conversion Corporation Page 47 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply P90L ISOGMB Output Termin
16. boots d Do not lay tools or metal parts on top of batteries e Disconnect charging source prior to connecting or disconnecting battery terminals e Do not dispose of the batteries in a fire Do not open the batteries The batteries must be disposed of in accordance with local regulations e Do not short or bridge the battery terminals with any object e Unplug and turn off the UPS before performing battery replacement e Battery replacement should be performed only by authorized service personnel using the same number and type of batteries Sealed Lead Acid Use tools with insulated handles The batteries are recyclable e Do not open or mutilate the batteries Released electrolyte is harmful to the skin and eyes and may be toxic e Do not connect or disconnect battery module s while the UPS is operating from the battery supply Standards Category C3 Category C3 Xtreme Power Conversion Corporation Page 6 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation UPS Unpacking and Inspection Open the package and check the contents The shipping package contains e One UPS e One user manual e One 3ft L6 30R output cord P9OL 6K only e One 6ft L6 30P input cord P90L 6X only e One monitoring software CD e One USB cable e Two sets of tower stands including feet and extensions e Two Rack mounting ears Note Before installation please inspect the unit Be sure that nothing inside the package has been damag
17. cccsccsecssecseccscccnccncesecesecsuceneeeecesecseceseseusesceseeeseeeeeeueeeeseueteeeeeeeeesensenes 38 Appendix B P9OL RAIL Installation Guide eere 39 Package CO COMICS RETRO 39 PASS SIMMONS EA E A PAE EN E E E A E A EN T N 39 Appendix C P9OL ISO6MB amp P90L ISO10MB User Guide 42 important Safety NS ECO NETTE 42 Rear Panel Brio CO aO m 43 Installation And OB GO RN eeseurtecicuaritenmiedbutideiess di PRU rupi UI EDAM UNES NPPIIMePPIa Ee UA PNE UNS 44 Terminal Block Explanations for Input Output esee 47 Jide slo NOONE corren da nsqestquesteassacioesavareneenateseapandseessoanbonsessseiapdelecatencenanesdsanstentussteeamiasacstee 49 BIOS IME ATOMS TETTE TT aan Ea A E AE E a TK 49 Xtreme Power Conversion Corporation Page 4 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Safety Warnings and EMC Instructions This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference A UPS Warnings e nstall your UPS indoors away from excess moisture or heat direct sunlight dust and conductive contami nants e nstall your UPS in a structurally sound area Your UPS is extremely heavy take care when m
18. ction Policy THIS POLICY IS NOT A WARRANTY REFER TO THE XPC CORPORATION INC LIMITED WARRANTY FOR INFORMATION CONCERNING THE WARRANTY FOR YOUR XPC PRODUCT THE LIMITATIONS AND CONDITIONS CONTAINED IN THIS POLICY DO NOT AFFECT THE TERMS OF THE XPC LIMITED WARRANTY Definitions 1 Product means a Standard 120 208 or 240 Volt power protection device that is used in the United States and Canada This policy does not include custom manufactured products 2 Power Disturbance means an AC power line transient telephone line or Local Area Network if appli cable spike or surge 3 Connected Equipment properly connected electronic equipment 4 Fair Market Value of damaged Connected Equipment as determined by XPC shall be the lower of a the average price the same or similar items are being sold for on eBay b the price list of Orion Blue Book or if such price list is no longer published a published or announced price list reasonably selected by XPC c the lowest price the same or similar items can be purchased for in the United States or d the total amount of all payment s you have or are entitled to receive from insurance other warranties extended warranties a legal liability claim or from other sources or persons for the damaged Connected Equipment 5 Purchaser means the person or entity that originally purchased the Product from an authorized reseller or distributor of XPC Products The Purchaser of this Product is protected f
19. ect the battery and check 07 Over not matching Warning l the charger output voltage con Charge Charger voltage is too high the l tact the dealer for repair charger failed i lt disch gla dc Recharge the battery VVarning 08 Batt Low 5 Correct the battery number Battery number is not correct Bablace ehe ister Battery is at the end of life p n R f P 09 Over load The load is too heavy excess loads trom UPS e Unblock the fan e Fan is blocked e Contact the dealer for replacin Warning OA Fan Error e Fan is in the end of life ihe far i Fan detection circuit failed e Contact the dealer for repair I e EPO plug jumper is removed or e Connect the EPO plug jumper or DES EPU ENERE the external EPO switch is off switch on the external EPO switch Xtreme Power Conversion Corporation Page 26 P90L 6kVA amp 10kVA Users Manual A4Uhinterruptible Power Supply The internal temperature is too high and has reached the warning Make sure the ambient tempera level ture is not over 40 C Environment is too hot Make sure the fan is OK Warning DUIS ONCE TEND Fan is blocked or failed Make sure the ventilation points UPS ventilation points are blocked are clear by the wall or other goods Reduce the load Load is too heavy Warning OE Charger Fail Charger failed Contact the dealer for repair Warming 10 IP Fuse Input fuse on the power board is Checkond replacethe input tice Open open Remove e
20. ed dur ing transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or missing parts Please keep the original packing material in a safe place for future use Rear Panel View lE ul F P90L 10K Rear Panel P90L 6K ships with default cord kit P90L 6K and 10K Input Output Terminal Xtreme Power Conversion Corporation Page 7 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply o Connection between P90 BP240 and P90L UPS Xtreme Power Conversion Corporation Page 8 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply RS 232 communication port USB communication port EPO Emergency Power Off connector Share current port parallel systems only Parallel port for future use Intelligent slot EMBS External Maintain Bypass Switch port Cooling fan External battery connector Input circuit breaker Input output terminal P9OL 6K ships with default cord kit Input terminal Ground Output terminal Battery pack output circuit breaker pe de ou am up H DHL Bnpmpmpmn U1 0 FKNDPDO Note EPO connector is normally closed NC for normal operation To activate EPO function remove the NC signal Normally Closed EPO WARNING The EPO RS 232 and USB circuits are IEC 60950 safety extra low voltage SELV circuits This circuit must be separated from any hazardous voltage circuits by reinforced insulatio
21. ed the DC bus voltage to be too high The internal converter failed The internal converter failed so Fault 03 Bus Under Contact the dealer for repair the DC bus voltage is too low e Shutdown and restart the system to see if the fault clears Contact the dealer for repair Fault 02 Bus Over Xtreme Power Conversion Corporation Page 27 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply e Theload is abnormal so the inter 04 Bus Unbal nal positive and negative DC bus Fault p B e Contact the dealer ance voltages are unbalanced e The internal converter failed e The internal inverter failed so the Fault 11 Inv Start Fail inverter voltage could not start up le Contact the dealer for repair correctly 12 Inv Volt e The internal inverter failed so the Fault e Contact the dealer for repair High inverter voltage is too high e The internal inverter failed so the Fault 13 Inv Volt Low i e Contact the dealer for repair inverter voltage is too low 14 Output e Short circuit occured on the UPS MM Fault P e Remove the short circuit Short output e UPS output power is negative It means there is energy feedback Fault 1A NegPower LE ES om NU day e Contact the dealer be caused by regenerative load or caused by the current control failure in the parallel system Short shorted e The internal inverter relay is stuck o estere RN contact the dealer for repair shorted fon 35 Para Com
22. ff Power is still applied via bypass mode You could also enter the control menu to select the instruction Turn Off to turn off the UPS Please refer to the section of LCD operation Note Here Turn Off means that UPS is not working on line converter ECO battery battery test mode So even though the UPS is turned off if input or bypass voltage is normal the internal power sup ply will still be working and if bypass status has been set to enable the output voltage of the UPS will still exist If you need to fully cut off the output switch off the external input breaker A few seconds later there is no display shown on the panel and UPS is completely off Turn off the UPS without utility power supply in Battery mode 1 When LCD is on home page press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press ON ENTER the UPS will beep once and turn off Power is still applied via bypass mode You could also enter the control menu to select the instruction Turn Off to turn off the UPS Please refer to the section of LCD operation If there is no bypass input voltage the UPS will cut off all power supply and there is no display shown on the panel Xtreme Power Conversion Corporation Page 16 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply LCD Operation The entire LCD structure is demons
23. he UPS is turned on the inverter is running the UPS will backup power from battery When input voltage is within acceptable range and bypass is enabled and the UPS Bypass Mode inverter is not turned on or the inverter can t support the load the UPS will switch to battery When the input voltage is within voltage regulation range and ECO mode is enabled ECO Mode the UPS will bypass voltage to output for energy saving If the input voltage is out of the regulation range but it is still within acceptable range of Line mode the UPS will transfer to inverter supplying the power to load similar to Line mode When input frequency is within 46 to 64Hz the UPS can be set with a constant output frequency 50 Hz or 60 Hz through the inverter The UPS will still charge the battery in this mode Bypass is disabled in this mode Frequency Converter Mode When the UPS is in Line mode or Converter mode and the battery test command is Battery Test Mode enabled through LCD or monitoring software the UPS will start Battery Test This op eration is used to check the battery status Macias cate If some errors occur in the UPS but it is still running normally buzzer will alarm and B warning code will appear in the LCD for trouble shooting When fatal error occurs in the UPS it will beep continuously and go to fault mode It Fault Mode oe l will display fault codes in LCD Button Operation 083 440 SSVdA8g Line Made IP zZ12 6U 6H 8
24. hrough the Product and i exhausts the protection capacity of the Product or ii damages the Product 6 The Load Protection Policy does not apply if the Product has been operated in a failure mode or not in compliance with XPC operating instructions in the Product user s manual or if the Connected Equipment has not been operated in compliance with the instructions and manuals of its manufacturer vendor 7 This policy is null and void if XPC determines in its sole discretion that the Product has been tampered with or altered in any way What is Not Covered Under the Load Protection Policy The following damage is not covered by this Policy 1 Restoration of lost data and reinstallation of software 2 Damage from a cause other than AC power line transients except for damage due to telephone line Local Area Network or CATV transients which is covered only if the Product offers such protection 3 DAMAGE CAUSED BY FAILURE TO PROVIDE A SUITABLE INSTALLATION ENVIRONMENT FOR THE PRODUCT INCLUDING BUT NOT LIMITED TO LACK OF A PROPER SAFETY GROUND Damage caused by the use of the Product for purposes other than those for which it was designed Damage caused by accidents or natural disasters including but not limited to fire flood and wind Damage caused by abuse misuse alteration modification or negligence Any labor costs or travel room and board expenses associated with the repair and or restoration of lost or damaged hardware s
25. it onto the mounting rail kits Attach the UPS module to the rack with the screws nuts and washers user provided through its mounting ears and into the rack rails 3 See Appendix B P9OL RAIL Installation Guide for further details Step 1 UPS Electrical Installation Installation and wiring must be performed in accordance with local and national code regulations 1 Make sure the mains wire and breakers in the building are rated for the correct capacity of UPS 2 Switch off the main feed before installation 3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Wiring Spec AWG Model P90L 6K 08 8 J 1 9S8 r P90L 10K o 6 6 J 8 Note 1 P9OL 6K input and output cords must be removed prior to proceeding with hardwire installation if required Note 2 The wiring for P9OL 6K should be able to withstand over 40A current It is recommended to use 8AWG Note 3 The wiring for P9OL 10K should be able to withstand over 63A current It is recommended to use 6AWG or Xtreme Power Conversion Corporation Page 11 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply thicker wire for safety and efficiency Note 4 The selections for color of wires should be followed by the local electrical laws and regulations Note 5 External battery wires must use reinforced insulation or double insulated wire AN Warning e For standard P90 BP240 battery module there i
26. le Power Supply must be completed and filed with XPC within 30 days Mark the Load Protection Policy RMA number on the Product the Purchaser is returning Pack the Product in its original packaging or similar packing materials if the original packaging has been discarded Enclose the completed Load Protection Policy claim form and a copy of the Purchas er s original sales receipt for the Product in the box Mark the RMA number clearly on the outside of the box Ship the Product one way shipping charges paid by the Purchaser to XPC Corporation 230 Yuma Street Denver CO 80223 Attn LPP RMA 3 XPC will evaluate the Product to determine its level of functionality and will examine the Product for evidence of damage from a Power Disturbance If XPCs evaluation provides no evidence of damage from a Power Disturbance XPC will send to the Purchaser i a report summarizing the tests performed and ii a rejection of claim notice If the Product shows evidence of damage from a Power Disturbance XPC will request that all Con nected Equipment for which a Load Protection Policy claim has been submitted be sent for evaluation to either XPC or an authorized service center If it is determined that the Connected Equipment has been damaged by a Power Disturbance XPC will in its sole discretion issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment u
27. lider Left rail slider Assembly Steps Step 1 Use 4 screws to mount right and left rail sliders in front See chart below m LOO DONE M MN ual alte ul CO De De De De ED DS De OC Ce DE 2 g g g g an 3 g g g g E g Screw driver Xtreme Power Conversion Corporation Page 39 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Step 2 Use 4 screws to mount rail sliders in back See chart below De Da De De EIS EIS DD DS DS DOS DS DD DIDI Xtreme Power Conversion Corporation Page 40 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Step 5 Fix the UPS in position with screws Tee Dre EE FEES FT AOC Or 7 5 L A H g A d D D C d Cie e CO CI Ee 2e S C9 C2 Step 6 Assembly complete CEI CES CE CL CLIC ES CE CL CL CE CL 3 El i B g IE BE B E I 5 Xtreme Povver Conversion Corporation Page 41 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Appendix C P9OL ISO6MB amp P90L ISO10MB User Guide Important Safety Instructions An Important Notice e Thereis a tiny leakage current from the Transformer Module so make sure to it is correctly grounded be fore connecting to the UPS Utility or Output Device e Do not open the case as there are no serviceable parts inside or your warranty will be void e Donottry to repair the unit yourself contact your local supplier or your warranty will
28. lt Warnings except overload Overload Other UPS Operation Turn on the UPS with utility power supply to Line mode 1 Make sure mains input and battery are connected and the battery pack breaker is in the ON position Set the external mains input breaker to ON position then the fan will be run Xtreme Power Conversion Corporation Page 14 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply ning and the UPS supplies power to the loads via bypass The UPS is operating in Bypass mode Note When UPS is in Bypass mode the output voltage comes directly from utility so the load is not pro tected by the UPS To protect the load the UPS should be turned on to Line mode When LCD is on home screen press the ON ENTER button LCD will show a prompt page of Turn On Move the arrow to Yes by up or down button then press ON ENTER the UPS will beep once and start UPS You could also enter the control menu to select the instruction Turn On to startup the UPS Please refer to the section of LCD operation A few seconds later the UPS will enter into Line mode Line mode will be displayed on LCD In line mode if the utility power is abnormal the UPS will transfer to Battery mode without interruption Turn on the UPS without utility power supply to Battery mode 1 2 Make sure the battery is connected and the battery pack breaker is in the ON position Press the ON ENTER button to start u
29. m e Parallel cable for communication Fault Fail is not connected in the parallel Connect the parallel cable system e The output current is extremely e ter remenat Contact the dealer for repair parallel system The internal temperature is too high h hed the fault level shut l ane SIS ACE NETA AAN Make sure the ambient tempera down 3 e The environment is hot HS NOCO TAE Fault 41 Over Temp Than blacked or failed Make sure the fan is OK RE Make sure the ventilation is clean e The ventilation is blocked by the Remove some loads wall or other goods e Loadis too heavy 42 CPU Comm Internal communication between Fault the CPUs failed Contact the dealer for repair e Overload time is out of the speci e R f P Fault 43 Over load fication and the UPS shut down xdi as Lira output and restart it automatically Xtreme Power Conversion Corporation Page 28 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Storage Before storing charge the UPS batteries for at least 7 hours Store the UPS covered and upright in a cool dry loca tion During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months Xtreme Power Conversion Corporation Page 29 POOL 6kVA amp 10kVA User s Manual Specifications MODEL NUMBER Uninterruptible Power S
30. manually bypassed Note that potentially lethal voltages exist within this unit as long as the battery supply is connected e Your UPS power module and battery module s do not require routine maintenance Do not open them for any reason There are no user serviceable parts inside e Even after the unit is disconnected from the mains components inside the UPS system are still connected to the battery packs which are potentially dangerous e Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists on PCB components e Fuses should be replaced only by factory authorized personnel Blown fuses should be replaced only with fuses of the same rating and type e Verify that no voltage between the battery terminals and the ground is present before maintenance or repair In this product the battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground A Battery VVarnings e Do not operate your UPS without connecting it to an external battery module e Batteries can present a risk of electrical shock and burn from high short circuit current Observe proper Xtreme Power Conversion Corporation Page 5 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply precautions a Remove watches rings and other metal objects b Use tools with insulated handles c Wear rubber gloves and
31. material in a safe place for future use Rear Panel View Xtreme Power Conversion Corporation Page 36 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply im 2 3 DC connector connects to either UPS or 2nd battery box DC breaker Battery over current protection breaker External battery numbers detection port detects the numbers of connected batteries Installation and Setup with UPS Unpacking amp Inspection 1 Remove the battery box from the packing Note The battery box is very heavy be cautious when unpacking and lifting the unit to avoid injury Check the inside package e Battery box unit I 1 TET e Quick guide z i Feal e Battery connection cable x 1 Battery connection cable e Detection cable x 1 e Earx2 amp screwx8 e Extended stand Extended stand Selecting Installation Position 1 o It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery box and extend the life of the batteries Please follovv the instructions belovv Keep at least 20cm 8 inches clearance from the rear panel of the unit from the wall or other obstructions Do not block the air flow to the ventilation openings of the unit Please ensure the installation site environmental conditions are in accordance with the unit s working specifications to avoid overheat and excessive moisture Do not place the unit in a dusty or corrosive environ
32. ment or near any flammable objects This unit is not designed for outdoor use Xtreme Power Conversion Corporation Page 37 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply This unit can either be mounted horizontally in a rack or placed vertically on the floor Rack Installation Connecting with UPS and Other Battery Box Follow below installation diagram to connect with UPS and other battery box with included cable 2nd battery pack Storage amp Maintenance The unit contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer V Q Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the unit 4 hours Store the unit covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months Xtreme Power Conversion Corporation Page 38 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Appendix B P9OL RAIL Installation Guide Package Contents e Right rail slider x 1 e Left rail slider x 1 e Nut M6x6 e Screw M6 x 14 65 65 ay 5656 09009 m Right rail s
33. n Xtreme Power Conversion Corporation Page 9 POOL 6kVA amp 10kVA User s Manual System Single Line Diagram System single line diagram is shown below Emergency line stati bypass Rack Tower Installation Tower Installation Uninterruptible Power Supply BPS STS The UPS system is shipped with four plastic feet and 6 plastic extensions 2 short extensions plus 4 long exten sions These are to be used to install the P9OL UPS or UPS and BP240 battery module in tower configuration 1 ForUPSonly assemble two feet and one short extension together as front support Assemble rear support in the same manner 2 For UPS and Battery Module assemble two feet and two long extensions together as front support As semble rear support in the same manner 3 Align the two supports in your installation area appropriately 14 inches apart 4 Then simply put the UPS module and battery module in the stands as shown in step 3 Be sure that the UPS LCD display is on the upper half part of front panel Step 1 Step 2 Step 3 r Short extension ad m Foot UPS only Xtreme Power Conversion Corporation Page 10 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Step 1 Step 2 UPS and Battery Module Rack Installation 1 Attach mounting ears to the side mounting holes of UPS using the screws provided with the ears facing forward 2 Lift the UPS module and slide
34. n to protect battery after backup time arrives when the Dischg Protect is enabled If Dischg protect is disabled then this setting is not relevant The default value for this setting is 990mins Batt Test Type Short Time Battery test will last for 10 seconds Long Time Battery test time can be adjusted within 01 99 minutes Till Batt Low Battery test will continue until battery voltage is low Page 24 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply 5 Calibration The Batt Inv and Chg calibrations can be adjusted to ensure the front panel display value matches the actual voltages measured in the UPS with a multimeter 1 Batt Calibrate the battery voltage measurement the calibration range is from OV to 5 7V the default value is OV It is available on all operation modes Calibration bBatt 273 0 0 0 Inv 209 0 0 0 Inv Adjust the inverter output voltage the adjustable range is from Chg 23 0 410 0 OV to 6 4V the default value is OV It is only available in line battery converter mode Chg Adjust the Charger output voltage the adjustable value is from OV to 6 9V the default value is OV It is only available in bypass line ECO converter mode Note Before making charger output voltage adjustment be sure to disconnect all batteries first to get the accurate charger voltage Be careful that the adjustment should be suitable to battery specifica tions or the ba
35. nterruptible Power Supply 2 ECO setting only available or effective on bypass mode Status Enable Enable ECO Function Disable Disable ECO Function If ECO function is disabled voltage range and frequency range for ECO ECO mode can still be set but it is meaningless unless the ECO func tion is enabled Status Disable HighLoss V High voltage point in ECO mode The setting range is HighLoss V 232V from 5 to 10 of the nominal voltage LowLoss V 184V LowLoss V Low voltage point in ECO mode The setting range is from HighLoss F 60Hz 3 to 10 of the nominal voltage HighLoss F Set low frequency point for ECO mode LowLoss F 60Hz 50 Hz system Setting range is from 46Hz to 48Hz 60 Hz system Setting range is from 56Hz to 58Hz The default value is 48Hz 58Hz LowLoss F Set high frequency point for ECO mode 50 Hz Setting range is from 52 0Hz to 54 0 Hz 60 Hz Setting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz 3 Output setting only available or effective on bypass mode 1 Volt 208 The voltage is set for 208VAC 220 The voltage is set for 220VAC 230 The voltage is set for 230VAC 240 The voltage is set for 240VAC Freq 50Hz The output frequency is manual set for 50Hz uos 208V 60Hz The output frequency is manual set for 60Hz Freq 60Hz ATO If selected output frequency will be decided according to the CVCF Enable latest normal utility freq uency If it is f
36. ock if the input or output is not turned off completely e Improper grounding might cause unexpected leakage current so please make sure that the utility ground is properly connected e Thisunit includes an optional Maintenance Bypass Switch Please make sure you may follow the operation procedure e When use a damp cloth to clean the unit please make sure the unit is turned off to avoid any hazardous risk e Do not touch any terminals of the unit if it is connected to the Utility Xtreme Power Conversion Corporation Page 42 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Rear Panel Explanation 6kVA 10kVA D F A G B 12 EET ds a i es mac j aos A RJ 45 Communication port B Input amp Output Terminal Block C For UPS Input 6kVA only D Maintenance Bypass Switch E Air Ventilation Openings 6kVA only F Thermal breaker for the protection of Load in abnormal condition CB3 10kVA only G Cooling Fan 10kVA only Xtreme Power Conversion Corporation Page 43 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation And Operation UPS Unpacking e Remove the unit from PE foam e Check Accessories o one set of user s manual one set of accessory kit RJ45 molex cable 2 12 NEMA L6 30P cables 6kVA only 1 12 NEMA L6 30R cable 6kVA only 2 O O O O x Selecting Installation Position e t is necessary to select a proper environment to install the uni
37. ode After the overload is removed it will return to Line mode If the overload time exceeds du ration listed in spec at Battery mode the UPS will enter fault status At this time if bypass is enabled the UPS will power the load via bypass If bypass function is disabled or the input power is not within bypass acceptable range it will cut off the output immediately Charge the batteries 1 2 3 After the UPS is connected to the utility povver the charger vvill charge the batteries automatically except in Battery mode or during battery test Suggest charging batteries at least 4 hours before use Otherwise the backup time may be shorter than expected Make sure the battery numbers setting on the control board Please refer to the section of changing bat tery quantity is consistent with actual connection Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to the battery capacity Normally the buzzer will beep once every 4 seconds in battery mode but when the battery voltage drops to the alarm level the buzzer will beep once per second and the UPS will shut down automatically when the battery reaches cutoff level Users could switch off some non critical loads to delay the shutdown alarm and pro long the backup time If there is no more load to be taken off at that time you must shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of da
38. oftware or data EUR IM EXCEPT AS EXPRESSLY PROVIDED IN THIS POLICY XPC SHALL NOT BE LIABLE FOR ANY DAMAGES WHATSOEVER INCLUDING BUT NOT LIMITED TO DIRECT INDIRECT SPECIAL INCIDENTAL CONSEQUENTIAL OR MULTIPLE DAMAGES ARISING OUT OF THE USE OF THE PRODUCT OR DAMAGE TO THE CONNECTED EQUIPMENT REGARD LESS OF THE LEGAL THEORY ON WHICH SUCH CLAIM IS BASED EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE SUCH DAMAGES INCLUDE BUT ARE NOT LIMITED TO LOSS OF PROFITS LOSS OF SAVINGS OR REV ENUE LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR ANY ASSOCIATED EQUIPMENT LOSS OF SOFTWARE COST OF CAPITAL COST OF ANY SUBSTITUTE EQUIPMENT FACILITIES OR SERVICES DOWNTIME THE CLAIMS OF THIRD PARTIES INCLUDING CUSTOMERS AND INJURY TO PROPERTY Submitting a Load Protection Policy Claim 1 Anyclaim under the Load Protection Policy must be made within 10 days of the date of alleged damage to the Connected Equipment 2 Call the XPC technical support department at 1 800 582 4524 and obtain a Load Protection Policy Returned Material Authorization RMA number Have information on all applicable insurance or other resources of re covery payment that is available to the Purchaser and the name of the power utility supplier for the location of the Connected Equipment XPC will forward to the Purchaser a Load Protection Policy claims form which Xtreme Power Conversion Corporation Page 34 POOL 6kVA amp 10kVA User s Manual Uninterruptib
39. on Page 35 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Appendix A P9OL BP240 User Guide Important Safety Warnings Please comply with all warnings and operating instructions in this manual Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully e Do not try to repair the unit yourself contact your local supplier or your warranty will be void e To eliminate any overheating of the battery box keep all ventilation openings free from obstruction and do not place any foreign objects on top of the battery bank Keep the battery box 8 inches away from the wall e Make sure the battery box is installed within the proper environment as specified 0 40 C and 30 90 non condensing humidity Do not install the battery box under direct sunlight Your warranty will be void if the batteries fail due to overheating e This battery box is not designed for use in dusty corrosive and salty environment e The warranty for this battery bank will be void if water or other liquid is spilled or poured directly onto the battery box Similarly we do not warrant any damage to the battery box if foreign objects are deliberately or accidentally inserted into the battery box enclosure e The battery will discharge naturally if the system is unused for a period of time It should be recharged eve
40. or the term of the XPC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to certain terms and conditions provided below This policy applies only to the original purchaser of the Product If the Product is transferred or sold to another person or entity this policy is void Load Protection Policy Dollar and Period Limits For purchasers that meet the qualifications and conditions set forth in this policy XPC will provide reimbursement cost of repair or fair market value as determined by XPC during the period limits and up to the dollar limits stated as follows S ERE B8 rey This Load Protection Policy is not deemed first dollar coverage XPC s obligation is reduced by any amounts that the Purchaser is entitled to recover from other sources regarding the Connected Equipment including but not limited to insurance other warranty extended warranty or legal liability regardless of whether or not the Pur chaser makes a claim for recovery Eligibility for Coverage Under the Load Protection Policy 1 The Product must be registered on the XPC website www xpcc com within 10 days of purchase All re quired information must be provided and Purchaser should retain a copy for Purchaser s records When registering on the website Purchaser must list all connected equipment that is directly connected to the Xtreme
41. oving and lift ing the unit e Only operate your UPS at indoor temperatures between 32 F and 104 F between O C and 40 C e leave adequate space around all sides of the UPS for proper ventilation e Do not install the UPS near magnetic storage media as this may result in data corruption e Donot mount unit with its front or rear panel facing down at any angle Mounting in this manner will se riously inhibit the unit s internal cooling eventually causing product damage not covered under warranty e This UPS should be connected with a grounded system NEC and local electrical codes apply e The power supply for this unit must be single phase rated in accordance with the equipment nameplate It also must be suitably grounded e Use of this equipment in life support applications where failure of this equipment can reasonably be ex pected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or nitrous oxide e Connect your UPS power module s grounding terminal to a grounding electrode conductor e The UPS is connected to a DC energy source battery The output terminals may be live when the UPS is not connected to an AC supply A Maintenance Warnings e Service and repair should be done only by trained personnel During any service work to the UPS it should be turned off or
42. p the internal power the UPS will enter into bypass mode without output When LCD is on home page press the ON ENTER button LCD will show a prompt page of Turn On Move the arrow to Yes by up or down button then press ON ENTER the UPS will beep once and start up You could also enter the control menu to select the instruction Turn On to startup the UPS Please refer to the section of LCD operation A few seconds later the UPS will enter into Battery mode Battery mode will be displayed on LCD In Battery mode it will shutdown automatically when battery is depleted If the utility power is restored it will auto restart to Line mode Connect devices to UPS After the UPS is turned on you can add load to the UPS li 4 Turn on the UPS first and then switch on the load devices one by one the LCD panel will display total load level If inductive loads such as a printer are connected the in rush current should be calculated carefully to see if the capacity of the UPS is sufficient due to the huge starting power consumption of this kind of load If the UPS is overloaded the buzzer will beep twice every second When the UPS is overloaded please remove some loads immediately It is recommended to have the total load connected to the UPS be less than 8096 of its nominal power capacity for system safety If the overload time exceeds duration listed in the spec at Line mode the UPS will automatically transfer to bypass m
43. p to the dollar limits stated above XPC reserves the right to require the Purchaser to transfer title and deliver the Connected Equipment to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum liability shall be reduced to reflect all such other payments or sources of recovery whether applied for or not 4 If XPC issues payment to the Purchaser to have the Connected Equipment repaired the repair must be per formed at a service center that is authorized by the manufacturer of the Connected Equipment XPC reserves the right to contact the authorized service center directly to discuss repair costs and damage to the Connected Equipment to determine if it was caused by a Power Disturbance and the right to request that the service center forward the Connected Equipment or components of the Connected Equipment to XPC for inspection 5 Unless modified in writing signed by an officer of XPC and the Purchaser the terms of this policy are the com plete and exclusive agreement between the parties superseding all prior agreements oral or written and all other communications between the parties relating to the subject matter of this agreement No employee of XPC or any other party is authorized to make any representations beyond those made in this agreement con cerning the Load Protection Policy XPC Corporation 230 Yuma Street Denver CO 80223 1 800 582 4524 Xtreme Power Conversion Corporati
44. rom 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output fre quency will be 60 0Hz ATO is default setting CVCF Used to enable or disable frequency converter mode Enable The output frequency will be fixed at 50Hz or 60Hz accord ing to setting of Freq The input frequency could be from 46Hz to 64Hz Disable The output frequency will synchronize with the input fre quency within 46754 Hz for 50Hz system or within 56764 Hz for 60Hz system Note CVCF means Constant Voltage and Constant Frequency it rep resents frequnecy converter mode Output Xtreme Power Conversion Corporation Page 23 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply 4 Battery setting available on all operation modes Battery DisChg Protect Enable 090 Minute Batt Test Type Short Time Battery DisChg Protect Enable 990 Minute Batt Test Type Short Time 10 Minute Battery DisChg Protect Enable 990 Minute Batt Test Type Short Time 10 Second Xtreme Power Conversion Corporation 1 Dischg Protect Enable Battery discharge protection function is enabled When UPS has been continuously working in battery battery test mode the UPS will automatically shut down when the running time set by op tion below is met Disable Battery discharge protection function is disabled 000 999 The maximum discharge time ranging from O to 999mins UPS will shut dow
45. ry 2 3 months if unused If this is not done then the warranty will be null and void During normal operation the batteries will be automatically remained in charged condition e Servicing of batteries should be performed or supervised by trained personnel with knowledge of batter ies and the required precautions e When replacing batteries it is necessary to replace ALL batteries with the same quantity type amp capacity e CAUTION Do not dispose of battery or batteries in a fire The battery may explode e CAUTION Do not open or mutilate the batteries The electrolyte from the batteries is toxic and harmful to the skin and eyes e CAUTION Risk of Electric Shock Hazardous voltage may exist between battery terminals and ground Test before touching with bare hands e CAUTION A battery can present a risk of electrical shock and high short circuit current The following precaution should be observed when working on batteries 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Wear rubber gloves and boots 4 Donotlay tools or metal parts on top of batteries 5 Disconnect charging source prior to connecting or disconnecting battery terminals e Do not plug or unplug the battery connector if UPS is in battery discharging mode Installation and Setup Note Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original packing
46. s one DC breaker to disconnect the battery bank and the UPS For nonstandard external battery options make sure a DC breaker or other protection device be tween UPS and external battery module is installed Note Set the battery module breaker in OFF position and then install the battery module e Pay attention to the polarity marking on external battery connector and make sure the battery polarity is correct Wrong connection may cause permanent damage of the UPS e Make sure the protective earth ground wiring is correct The wire current spec color position connection and conductance reliability should be checked carefully e Make sure the utility input amp output wiring is correct The wire current spec color position connection and conductance reliability should be checked carefully Make sure the N or L2 site is correct Xtreme Power Conversion Corporation Page 12 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Operations Operating Mode Status Description Mode Status When UPS is powered on it will enter into this mode for a few seconds for initializing UPS power on the CPU and system When the input voltage is within acceptable range and the UPS is turned on the in Line Mode verter is running the UPS will provide pure and stable sine wave AC voltage The UPS will also charge the battery in Line mode BagsrasSE When the input voltage is out of the acceptable range or a power failure occurs and y t
47. t in order to minimize the possibility of damage to the unit and extend the life of the unit Please follow the advice below e Keepatleast 30 cm 12 inches clearance from the rear panel of the unit to the wall Do not block the air flow to the ventilation openings of the unit Also check the installation site to avoid over heat and exces sive moisture e Do not place the unit in an environment near dust corrosive or salty material or flammable objects e Do not expose the unit to outdoors Xtreme Power Conversion Corporation Page 44 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Installation 6kVA Connection Diagram EE IL 3 d 3 y n aUo P90L ISOGMB mM D P9OL EBP240 Hardvvired input from Utility Input L6 30P cord from UPS input connectes to L6 30R on P90L ISO6MB UPS Input L6 30R cord from UPS connects with L6 30P on P90L ISO6MB UPS Output Hardwired TR Output to load RJ45 on P9OL ISO6MB to Molex connector on P9OL 6K for static bypass interlock Battery connection Anderson to Anderson Er TIN Ww e pops Xtreme Power Conversion Corporation Page 45 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply 10kVA Connection Diagram GI TN ui La Hi AS Es ESSI L EI ae P90L ISO10MB Nugu P9OL EBP240 Hardvvired input from utility Hardwired input cord with ring terminals connects to utility input termin
48. t sites within the United States and Canada this warranty covers repair or replacement at the sole discretion of XPC Corporation The customer is responsible for the costs of shipping the defective product to XPC Corporation XPC Corporation will pay for ground shipment of the repaired or replacement product This warranty applies only to the original purchaser If equipment provided by XPC Corporation is found to be Dead on Arrival DOA XPC Corporation will be respon sible for the costs of shipping product to and returning equipment from the customer in a timely manner as agreed to with the customer once the customer has requested and received a Return Material Authorization RMA number DOA equipment is defined as equipment that does not properly function according to user documenta tion when initially received and connected in conjunction with proper procedures as shown in the user documen tation or via support provided by XPC Corporation personnel or authorized agents This warranty shall be void if a the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written ins
49. ta loss or load failure Xtreme Power Conversion Corporation Page 15 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply 2 gt In Battery mode you can mute the alarm by entering Control gt Mute on LCD to silence it Please refer to the section of LCD operation The backup time depends on the external battery capacity The backup time may change under different environment temperature and load type The maximum backup time is limited by default to 16 5 hours After discharging 16 5 hours UPS will shut down automatically to protect the battery The time could be modified through LCD panel or communica tion port Test the batteries 1 If you need to check the battery status or performance when the UPS is running in Line Converter ECO mode you could enter Control gt Batt Test to instruct the UPS to perform a battery test Please refer to the section of LCD Operation Users also can set battery test through monitoring software If the UPS is in battery testing Battery test mode will be displayed on LCD the buzzer indication will be the same as Battery mode but both line LED and battery LED will be lit Turn off the UPS with utility power supply in Line mode 1 When LCD is on home page press the OFF ESC button LCD will show a prompt page of Turn Off Move the arrow to Yes by up or down button then press ON ENTER the UPS will beep once and turn o
50. trated in diagram below Tura On Batt Test Page 1 Input Page M Battery E LE Prax Paii a Page 4 By pans age 5 C hanger Main Interface Page 4 Hattery Page amp UPS lafo i i Calibration Praa x i thin Eriet i is L 7 I ress Palion Fw Warning Info Xtreme Power Conversion Corporation Page 17 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Main Interface Home Screen ae I Bvpass Mode Bvpass Mode IP 208 0V 50 OHz OP 208 0V 50 OHz Batt 273 0V 99 IP 208 0V 50 OHz OP 208 0V 50 OHz Batt 273 0V 99 Load 0 Load 0 Warning 01 In the first line it will display the current mode the UPS is in When an alarm occurs the warning or fault information will display below the load line When the front panel is not operated for quite a long time the page will default back to this home page Press the UP or DOWN button to enter the main operation menu When LCD is on this home page if UPS is in bypass you could press the ON ENTER button to turn on the UPS to line converter ECO battery mode according to the setting and input status in reverse you could press the OFF ESC button to turn off the UPS to bypass mode or shutdown As previously mentioned in UPS Operation section of this manual Operation Menu Main menu a Mc Md Line Mode IP 208 0V 50 OHz OP 208
51. tructions Any technical advice furnished by XPC Corporation or a XPC Corpora tion authorized representative before or after delivery with regard to the use or application of Xtreme Power Con version equipment is furnished on the basis that it represents XPC Corporations best judgment under the situation and circumstances but it is used at the recipient s sole risk EXCEPT AS STATED ABOVE XPC Corporation DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE EXCEPT AS STATED ABOVE IN NO EVENT WILL XPC Corporation BE LIABLE FOR DIRECT INDIRECT SPECIAL INCI DENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF Xtreme Power Conversion EQUIPMENT including but not limited to any costs lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data cost of substitutes or claims by third parties Purchaser s sole and exclusive remedy for breach of any warranty expressed or implied concerning Xtreme Power Conversion equipment and the only obligation of XPC Corporation under this warranty shall be the repair or replacement of defective equipment components or parts or at XPC Corporations sole discretion refund of the purchase price or substitution of an equivalent replacement product Xtreme Power Conversion Corporation Page 32 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Xtreme Power Conversion Load Prote
52. ttery may be destroyed Alarm Page Alarm Info Fault 14 Output Short Warning Ol Bat Open This page records and displays the faults or warnings event history Xtreme Power Conversion Corporation Page 25 POOL 6kVA amp 10kVA User s Manual Uninterruptible Power Supply Troubleshooting Warning Status When Fault LED flashes and the buzzer beeps once every second it means that the UPS has experienced a warning condition Users can see the warning code on the LCD panel and refer to the trouble shooting table to check the warning condition Fault Mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error with the UPS Users can get the fault code from LCD panel Please refer to the trouble shooting table to check the fault condition 2 Don ttry to turn on the UPS again until the fault is cleared If the fault can t be fixed please contact the manufacturer immediately 3 n case of an emergency please cut off the connection from utility external battery and output immedi ately to avoid more risk or danger Trouble Shooting Table If the UPS system does not operate correctly please solve the problem by referring to the table below Alarm type LCD display The battery connection is loose Tighten the battery connection Warning 01 Batt Open The battery protection device is Replace or restore the protection open device B ane meis a gt Senne Disconn
53. upply P9OL 6K P9OL 10K CAPACITY 6kVA 5 4kW 10kVA 9kW INPUT Voltage 110 300VAC Frequency 50 60Hz OUTPUT Voltage 200 208 220 230 240VAC 240 120VAC with optional isolation transformer with maintenance bypass Frequency 50 60Hz 4Hz THD full load lt 2 Overload capacity 110 10 min 130 1 min gt 130 1 sec Crest factor 3 1 BATTERY Charger amps 4A CHARGER Nominal float voltage 240 270VDC PHYSICAL UPS dimensions W x D x H 17 2 x 26 3 x 5 3 in 17 2 x 29 5 x 5 3 in UPS weight 55 lbs 60 Ibs Input connection Terminal block with 6 ft L6 30P Terminal block Output connection ENVIRONMENT Efficiency Terminal block with 3 ft LO 30R Terminal block Up to 9896 ECO mode and 9296 online mode Operating temperature 32 104 F 0 40 C Audible noise 58dBA 60dBA Altitude OPTIONAL Model number 11 500 ft above sea level P9OL BP240 BATTERY PACKS Dimensions W x D x H 17 3 x 25 1 x 5 3 in Weight 165 Ibs Battery quantity type 20 12V9AH 240V 17 3 x 28 7 x 3 5 in 17 3 x 31 8 x 5 2 OPTIONAL Dimensions W x D x H TRANSFORMER Weight 99 Ibs 122 Ibs APPROVALS UL cUL RoHS WARRANTY COMMUNICATIONS INTERFACE INCLUDED IN BOX AVAILABLE OPTIONS Depending on load level 3 years electronics and battery 2 years outside of USA RS 232 USB EPO intelligent slot for optional cards Web SNMP
54. xcess loads from UPS output first then shut down the UPS and restart it 33 Overload 3 Locked in bypass after overload 3 Warnin l l 5 Times times in 30 minutes External Maintenance Bypass Switch EMBS port is open or the maintain switch sensor connected to EMBS port is triggered The UPS is transferred to bypass 3A Maintain Open If the EMBS port is short circuited Wenning the warning will disappear If the system still needs to be oper ated in parallel mode please con nect the parallel cable and choose Para Unlock in control menu to remove the warning then the UPS can start up Parallel cable is still not connected If the UPS in the system are sepa when restart after the parallel rated to single UPS please discon system is faulty because of parallel nect the output to other UPS and communication failure When this choose Para Unlock in control warning appears the UPS can not menu to remove the warning then start up it is protection for parallel the UPS can start up system 3F Para Protect AAE Future Use Note Be careful to check the UPS operation mode parallel or single and the connections If the paral lel cable is not connected in the parallel mode the UPS may be damaged The internal converter failed so the DC bus voltage could not be e Contact the dealer for repair boosted correctly 01 Bus Start Faul a Fail The mains input or load transient current caus