Data Sheet DB EN IB IL 24 DO 16

image

Contents

1. General Data Housing dimensions width x height x depth Weight Operating mode Connection method for actuators Ambient temperature operation Ambient temperature storage transport Permissible humidity operation storage transport Permissible air pressure operation storage transport Degree of protection Protection class 5559_en_04 Type Order No IB IL SCN 12 2726340 IB IL SCN 12 OCP 2727624 IB IL DI DO 16 PLSET 2860976 IB IL DO 16 PLSET OCP 2860992 Type Order No IL SYS INST UM E 2698737 IB IL SYS PRO UME 2743048 48 8 mm x 120 mm x 71 5 mm 130 g without conncetor 152 g with connector Process data mode with 1 word 2 and 3 wire technology 25 C to 55 C 25 C to 85 C 10 to 95 according to DIN EN 61131 2 70 kPa to 106 kPa up to 3000 m above sea level IP20 according to IEC 60529 Class according to VDE 0106 IEC 60539 Pcs Pkt 10 10 Pcs Pck 1 1 PHOENIX CONTACT 2 General Data Continued Connection data for Inline connector Connection method Conductor cross section Interface Local bus Transmission Speed IB IL 24 DO 16 IB IL 24 DO 16 PAC IB IL 24 DO 16 PAC SN IB IL 24 DO 16 2MBD IB IL 24 DO 16 2MBD PAC IB IL 24 DO 16 2MBD PAC SN Power Consumption Communications power Current consumption at UL Power consumption at UL Segment supply voltage Us Nominal current consumption at Us IB IL 24 DO 16 Spring cage terminals 0 2 mm to 1 5 mm solid or stranded
2. H Electrically isolated area Other symbols used are explained in the IB IL SYS PRO UM E user manual or the system manual for your bus system 5559 en 04 PHOENIX CONTACT 7 IB IL 24 DO 16 Connection Example Programming Data Configuration Data Local Bus INTERBUS When connecting the actuators observe the BDhex 1894 assignment of the terminal points to the L process data see page 9 i E Uo Process data channel 16 bits Input address area 0 bytes Output address area 2 bytes Parameter channel PCP 0 bytes Register length bus 2 bytes Other Bus Systems For the programming data configuration data of other bus systems please refer to the corresponding electronic device data sheet e g GSD EDS Figure 4 Typical actuator connection A 3 wire termination B 2 wire termination The numbers above the module illustration indicate the connector slots 5559 en 04 PHOENIX CONTACT 8 IB IL 24 DO 16 Process Data Assignment of the Terminal Points to the OUT Process Data Please refer to the data sheet DB GB IBS SYS ADDRESS Order No 9000990 for the assignment of the shown byte bit view to your INTERBUS control or computer system For th
3. 24 16 AWG Through data routing 500 kbps 2 Mbps 500 kbps 2 Mbps 7 5 V DC 7 5 V DC 90 mA maximum 105 mA maximum 0 675 W maximum 24 V DC nominal value 8 A 16 x 0 5 A maximum 0 79 W maximum 24 V DC nominal value 8 A 16 x 0 5 A maximum Supply of the Module Electronics and I O Through Bus Coupler Power Terminal Connection method Digital Outputs Number Nominal output voltage Ugyt Differential voltage for lhom Nominal current lhom per channel Tolerance of the nominal current Total current Protection Through potential routing 16 24 V DC 1V 0 5A 10 8A Short circuit overload 35 Channels are thermally coupled in groups of four i e an error in one channel can affect the other channels Nominal load Ohmic Lamp Inductive Signal delay upon power up of Nominal ohmic load Nominal lamp load Nominal inductive load Signal delay upon power down of Nominal ohmic load Nominal lamp load Nominal inductive load Switching frequency with Nominal ohmic load 48 0 12 W 12W 12 VA 1 2 H 50 500 us typical 100 ms typical with switching frequencies up to 8 Hz above this frequency the lamp load responds like an ohmic load 100 ms 1 2 H 50 Q typical 1 ms typical 1 ms typical 50 ms 1 2 H 50 Q typical 300 Hz maximum 35 This switching frequency is limited by the selected data rate the number of bus devices the bus structure the software and the contr
4. 45 8 V Ugemag demagnetization voltage 400 mJ maximum Integrated 45 V Zener diode in the output chip 0 7 A minimum 300 uA maximum 2 V maximum 25 mA maximum 100 mW at 1 kQ load resistance typical 1 5 A for 20 ms maximum Output Characteristic Curve When Switched On Typical 500 kbps and 2 Mbps Output Current A 0 0 1 0 2 0 3 0 4 0 5 Power Dissipation 500 kbps Output Voltage Difference V 0 0 04 0 08 0 12 0 16 0 20 2 Mbps Formula to Calculate the Power Dissipation of the Electronics Par 2 0 19 W E 0 10 W 1 2x 0 4 Q i 1 Where Prot Total power dissipation in the terminal i index n Number of set outputs n 1 to 16 lj Load current of output i Pror 0 40 W E 0 10 W I x 0 4 Q i 1 Power Dissipation of the Housing Pyoy 500 kbps and 2 Mbps 2 7 W maximum within the permissible operating temperature 5559_en_04 PHOENIX CONTACT 4 Limitation of Simultaneity Derating 500 kbps and 2 Mbps Ambient Temperature TA Simultaneity Simultaneity 25 C lt TA lt 40 C 0 50 0 50 40 C lt TA lt 45 C 0 45 0 50 45 C lt TA lt 50 C 0 40 0 50 50 C lt TA lt 55 C 0 35 0 50 Maximum Load Current at 100 Maximum Load Current at 75 Safety Equipment Overload short circuit in the segment circuit Electronic with four 4 channel drivers Surge voltage Protective elements of the power terminal Protection up to 33 V DC Polarity reversal of the sup
5. CONTACT GmbH amp Co KG 32823 Blomberg Germany 9 mna Phone 49 0 5235 3 00 Fax 49 0 5235 3 4 12 00 www phoenixcontact com
6. the diagnostic LED D flashes on the ter Falling below or exceeding the operating voltage No Approvals For the latest approvals please visit www download phoenixcontact com 5559_en_04 PHOENIX CONTACT IB IL 24 DO 16 5 IB IL 24 DO 16 Local Diagnostic and Status Indicators Local Diagnostic and Status Indicators and Terminal Point Assignment Color Bes Color Meaning D Green Diagnostics 1 2 2 Status indicators of the outputs 3 4 Function Identification Pink 2 Mbps White stripe in the vicinity of the D LED Terminal Point Assignment for Each Connector xA Signal output OUT Ground contact GND for 2 and 3 wire termination FE connection Figure 1 Diagnostic and status indicators for 3 wire termination X4 Signal output OUT Ground contact GND for 2 and 3 wire termination FE connection for 3 wire termination 5559C002 1 1 2 2 3 3 4 4 ONS Gir LS 5 ka 6 6 5559B007 Figure 2 Terminal point numbering when using individual connectors A and when using a connector set B A Using the IB IL 24 DO 16 PAC SN and IB IL 24 DO 16 2MBD PAC S
7. 0 kbps Inline Terminal with 16 digital outputs complete with accessories connectors with individual numbering and labeling fields transmission speed of 500 kbps Inline Terminal with 16 digital outputs without accessories transmission speed of 2 Mbps Inline Terminal with 16 digital outputs complete with accessories connectors and labeling fields transmission speed of 2 Mbps Inline Terminal with 16 digital outputs complete with accessories connectors with individual numbering and labeling fields transmission speed of 2 Mbps Type Order No IB IL 24 DO 16 2726272 IB IL 24 DO 16 PAC 2861292 IB IL 24 DO 16 PAC SN 2862961 IB IL 24 DO 16 2MBD 2855318 IB IL 24 DO 16 2MBD PAC 2862013 IB IL 24 DO 16 2MBD PAC SN 2878324 IB IL 24 DO 16 Pcs Pck 1 Four of the listed connectors or one connector set are needed for complete fitting of the IB IL 24 DO 16 and the IB IL 24 DO 16 2MBD terminals Accessories Description Connector without colored identification for digital 4 or 16 channel Inline terminals Connector colored identification for digital 4 or 16 channel Inline terminals Connector set with 48 spring cage connections green w o color print Connector set with 48 spring cage connections green with color print Documentation Description Automation Terminals of the Inline Product Range user manual Configuring and Installing the INTERBUS Inline Product Range user manual Technical Data
8. IB IL 24 DO 16 Inline Terminal With 16 Digital Outputs AUTOMATIONWORX Data Sheet 5559 en 04 PHOENIX CONTACT 01 2007 Description The terminal is designed for use within an Inline station It is used to output digital signals Features Connections for 16 digital actuators Connection of actuators in 2 and 3 wire technology Nominal current per output 0 5 A Total current of the terminal 8 A Short circuit and overload protected outputs A Diagnostic and status indicators KA S 5559B006 This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system manual for your bus system 35 Please note that the numbering of the terminal points differs with regard to the different connector versions see Figure 2 on page 6 35 Make sure you always use the latest documentation It can be downloaded at www download phoenixcontact com A conversion table is available on the Internet at www download phoenixcontact com general 7000 en OO pdf 35 This data sheet is valid for all products listed on the following page 50050005095005 0 0 C JcoNc INSPIRING INNOVATIONS Ordering Data Products Description Inline Terminal with 16 digital outputs without accessories transmission speed of 500 kbps Inline Terminal with 16 digital outputs complete with accessories connectors and labeling fields transmission speed of 50
9. N with the provided connectors Using individual connectors IB IL SCN 12 or IB IL SCN 12 OCP B Using the IB IL 24 DO 16 PAC and IB IL 24 DO 16 2MBD PAC with the original connector set Using the IB IL DO 16 PLSET OCP or IB IL DI DO 16 PLSET connector sets 5559 en 04 PHOENIX CONTACT 6 IB IL 24 DO 16 Internal Circuit Diagram Local bus ee SE r31 r4 L1 y Y y 2 y y y V y y y V gt gt P gt P P P P P H H bi H H n bi H H bi H Ae C OE IA SES IC lt Be SERE eee ae NE MER amp Y y y y Y y y y y Y Y m e e e z z z c 24V Uy ah I et 9 G Le et Le Ay ts DERM Ma S 3 S e 3 5559B003 Figure 3 Internal wiring of the terminal points Key lt Protocol chip bus logic including voltage conditioning LED Optocoupler Transistor A ep Digital output
10. e assignment of the illustrated byte bit view to control systems of other bus systems please refer to the AH IB IL 24 DI DO 16 ADDRESS document Order No 9014124 35 The following table applies to the IB IL 24 DO 16 PAC and the IB IL 24 DO 16 2MBD PAC terminals with the original connector set and when using the IB IL DI DO 16 PLSET and IB IL DO 16 PLSET OCP connector sets see also Figure 2 on page 6 detail B Byebi vew Byte Byte B rzjejsj4j3 2 1 0 7 6 5 4 3 2 t O Assignment fst o 2 J 4 J 83 Terminal point 4 4 3 4 4 1 3 1 2 4 1 4 2 1 1 1 8 4 7 4 8 1 7 1 6 4 5 4 6 1 5 1 signal Terminal point 4 5 3 5 4 2 3 2 2 5 1 5 2 2 1 2 8 5 7 5 8 2 7 2 6 5 5 5 6 2 5 2 GND Terminal point FE 46 3 6 4 3 3 3 26 1 6 23 1 3 8 6 76 8 3 7 3 6 6 5 6 6 3 5 3 Toa E a LL LRL Status indicator Slot The following table applies to the IB IL 24 DO 16 PAC SN terminal with the original connector set and when using the IB IL SCN 12 or IB IL SCN 12 OCP connectors see also Figure 2 on page 6 detail A Byte bit view Byte 1 Assignment Slt Terminal point aug 1 4 2 1 1 1 uu 1 4 2 1 1 1 ug 1 4 2 1 1 1 nuu 1 4 2 1 1 1 signal Terminal point 2 5 1 5 2 2 1 2 2 5 1 5 2 2 1 2 2 5 1 5 2 2 1 2 2 5 1 5 2 2 1 2 GND 9_ 2 fs Status indicator Slot PHOENIX CONTACT 01 2007 5559 en 04 PHOENIX
11. ol or computer system used Nominal lamp load 5559 en 04 8 Hz maximum PHOENIX CONTACT 3 Digital Outputs Continued IB IL 24 DO 16 This switching frequency is limited by the selected data rate the number of bus devices the bus structure the software and the control or computer system used Nominal inductive load Overload response Response time with ohmic overload 12 Q Restart frequency with ohmic overload Restart frequency with lamp overload Response with inductive overload Response time in the event of a short circuit Reverse voltage protection against short pulses Resistance to permanently applied reverse voltages Validity of output data after connecting the 24 V supply voltage power up Response upon power down Limitation of the voltage induced on circuit interruption Single maximum energy in free running Protective circuit type Overcurrent circuit Output current when switched off Output voltage when switched off Output current with ground connection interrupt Switching power with ground connection interrupt Inrush current with lamp load 0 5 Hz 1 2 H 50 Q maximum Auto restart 3 s approximately 400 Hz approximately 400 Hz approximately Output may be damaged 3 s approximately Protected against reverse voltages Protected against reverse voltages permissible current 2 A maximum 5 ms typical The output follows the supply voltage without delay 15 V Udemag lt
12. ply voltage Protective elements of the power terminal The supply voltage must be protected The power supply unit should be able to supply four times 400 the nominal current of the fuse Reverse voltage Integrated protection against reverse voltages Electrical Isolation Isolation of the Voltage Areas To provide electrical isolation between the logic level and the I O area it is necessary to supply the station bus coupler and the digital output terminal described here via the bus coupler or a power terminal from separate power supply units Interconnection of the power supply units in the 24 V area is not permitted See also application description Common Potentials The 24 V main voltage 24 V segment voltage and GND have the same potential FE is a separate potential area Separate Potentials in the System Consisting of Bus Coupler Power Terminal and I O Terminal Test Distance Test Voltage 5 V supply incoming remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min 5 V supply outgoing remote bus 7 5 V supply bus logic 7 5 V supply bus logic 24 V supply I O 24 V supply I O functional earth ground Error Messages to the Higher Level Control or Computer System Short circuit overload of an output Yes minal at 2 Hz medium under these conditions 35 An error message is generated when an output is short circuited and switched on In addition

Download Pdf Manuals

image

Related Search

Related Contents

Manuale utente Cruiser 250 cc  Descargar Catálogo General de Supresores de Picos Citel Archivo  miniMAXX - Documentação técnica  Akton Psychrometric Chart Tutorial and Examples  ATTA CHEMENT RAMASSEUR  www.ttfone.com  Certificado Zoosanitario para Importación  Intel ESM-2740 Personal Computer User Manual  