Test report
Contents
1. k AgroTech DANETV LevelTec Online monitoring of slurry storage tanks Test report Document information Project ETV Test Center and Test Organisation 2 1 2 Date 05 12 2012 Status Approved for publication DANETV mk AgroTech TABLE OF CONTENTS TABLE OF CONTENTS kk tk kk LER ER ES REE RELSE ERE SEES ERE ERE E REE E RENE REESE E REE REE REESE RER anrea ns 1 NO TO ete en MD eee nent eee cee eee ee een ee 2 1 1 Name and contact of proposer ccccesccceecceececeeecceeeceuceceeceucecsueesseessuseseeeseeessusensess 2 1 2 Name of test body and test responsible 4 2 1 3 Reference to test plan and specific verification protocol 2 1 4 Deviations 10 leS Dial METTE T R Tm 2 2 TEST DE SION c eee 2 2 1 TESAHOlG AV CES CHOC aera Eee 3 2 2 SSE SIS SR A ican 3 2 3 PEES E S E c M 4 2 3 1 Performance test methods is 4 2 3 2 Environmental testmethode eis cuota nieto duca etapas iuto o ia center eat Du copain eo c cete ent 5 2 4 MST SOMES E 6 3 BES I RS ME 6 3 1 WSR CES NA asscsstomsbunume E E 6 3 1 1 Perormance Test oo NITET 6 3 1 2 Environmental test results 10 3 1 3 Additional test parameters sise 11 3 2 Test performance observation 13 9d Test quality assurance summary including audit results
2. No malfunction was observed during the exposure and the function of the test objects was OK after the exposure Performance criterion A Conducted radio frequency The purpose of the test is to verify the immunity of the test object to low frequency fields generated by intentional transmitters AM radio TV cell etc Applicable to AC input and I O cabling greater than 3 m in length Product application standard EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Reference standard DANAK 19 12336 DELTA T202349 Page 17 of 45 IEC 61000 4 6 2007 Testing and measurement techniques Immunity to conducted disturbances induced by radio frequency fields SUO Iko 4 11 SUO Iko DANAK 19 12336 DELTA T202349 Page 18 of 45 Severity control unit and level sensor including all cables greater than 3 m Frequency range 150 kHz 80 MHz Amplitude 10 Vrms Modulation 80 AM 1000 Hz sine wave Procedure The test object is supplied with power via a coupling decoupling network The test signal is coupled to the power lines and signal lines via coupling networks or via an EM clamp The coupling impedance is 150 Q The test object is switched ON during the exposure The test object is observed during the exposure and a functional check is performed after the exposure Results No malfunction was observed during the exposure and the functi
3. SUO Iko DANAK 19 12336 DELTA T202349 Page 24 of 45 Severity control unit and level sensor Magnetic field strength 30 A m Test frequency 50 Hz Procedure The test is performed in three orthogonal orientations The test object is energised and in normal operational mode during the exposure The test object is observed during the exposure and a functional check 1s performed after the exposure Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure Performance criterion A Voltage dips and interruptions The purpose of the test is to verify the immunity of the test object to fluctuations on AC power input Product application standard EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Reference standard IEC 61000 4 11 2001 Testing and measurement techniques Power frequency magnetic field immunity test Severity control unit and level sensor including all cables Line 0 of nominal for 1 cycle Line 40 of nominal for 10 cycles 50 Hz Line 70 of nominal for 25 cycles 50 Hz Line 0 of nominal for 250 cycles Procedure SUO Iko DANAK 19 12336 DELTA T202349 Page 25 of 45 The test object is energised and in normal operational mode during the exposure The test object is observed during the exposure and a functional check is performed after the ex
4. AgroTech Table 5 Results from testing the basic alarm function in small scale slurry container Slurry type 1 1 60 TS Small leakage Medium leakage Large leakage 7 mm minut 43 mm minut 130 mm minut Small leakage Medium leakage Large leakage TS refers to total solids a measure of the dry matter content of the slurry Based on the results in Table 5 it is concluded that LevelTec is functioning as claimed by PlusTec with respect to threshold value for reporting leakage Table 6 presents the measured time from the threshold value in slurry level has been reached to an SMS message is received by the person responsible for the tank Table 6 Measured time from the threshold value in slurry level is reached to an SMS message is received Test Type of leakage Decrease in slurry Time from leakage to reception no simulation level mm of alarm SMS One single leakage 1 min 30 sec M n po mem Bl on po Mm Leakage part 1 25 No alarm after 15 min 4 Leakage part 2 40 38 sec Total leakage 65 5 Leakage part 2 30 44 sec Total leakage 50 NNE Leakage part 2 30 55 sec Total leakage 55 Based on the test results in Table 6 it is concluded that an alarm SMS is received with in 2 minutes after the threshold value of 50 mm decrease in slurry level has been reached This is according to the claim by the proposer LevelTec Test Report 7 AgroTech k AgroTech DANETV Full tank warning an
5. 07 meter from the slurry level to the artificial rim of the slurry tank Tank overflow 0 450 meter In the time from LevelTec registers that the 0 02 alarm meter threshold value is reached to the SMS warning message is received on the mobile phone the slurry level continues to raise That is the reason why the slurry level has reached the artificial rim of the slurry tank when the SMS alarm message was received It is seen from Table 7 that both the full tank warning message and the tank overflow alarm message were received Thus these functions are working as claimed by the technology supplier Alarm function in case of failing power supply LevelTec online monitoring system has to be in operation 24 hours per day throughout the year to give the desired security Thus a stable power supply is required Still it is an advantage if the slurry tank owner receives a message in case the power supply is failing This can be secured by installing a battery that makes it possible for LevelTec to send an SMS alarm message The technology supplier claims that LevelTec has this function This is tested as part of this verification In table 8 the results from this test are shown LevelTec Test Report 8 AgroTech k AgroTech DANETV Table 8 Results from testing LevelTec in case of failing power supply Time when power supply was disconnected Time for reception of SMS alarm 12 03 2012 07 38 12 03 2012 07 39 15 03 20
6. 11 2 30 0 Led 101 0 222 00 VERTICAL 199 300000 26 90 10 2 20 D Sad 400 0 42 00 HORIZONTAL SUO Iko SUO Iko DELTA EUT Manufacturer Operating Condition Test Site Operator Test Specification Comment Start of Test Level dBuV m LevelTec DANETV Ant 4 m horizontal EMC 5 HEN T202349 EN55022 B Sheet 4 22 03 2012 Frequency Hz MES RE 4mh 30 1000 MaxPk MES RE 30 1000 QP 4m QPk X MES Maximering fin QP 22 03 2017 11 34 LIM RE EN 55022 B QP Radiated Emission DANAK 19 12336 DELTA T202349 Page 40 of 45 200M 300M 500M 700M 1G SUO Iko DELTA EUT Manufacturer Operating Condition Test Site Operator Test Specification Comment Start of Test Level dBy V 80 70 DANAK 19 12336 DELTA T202349 Page 41 of 45 LevelTec DANETV Line no Neutral 230 VAC EMC 5 HEN T202349 EN55022 B Sheet 5 22 03 2012 90 10 150k 300k n 60 1 1 A 30 a WET p il Ty 2 s ZNE NN LM CUN A nll al tt TE PT ETT iy LLLI dL dL LLL TT UA 500k 10M ee m MES CE 0 15 30 PK AV Avg MES CE 0 15 30 PK MaxPk LIM CE EN 55022 B AV Conducted Emission LIM CE EN 55022 B QP Conducted Emission 22 03 2012 11 45 CE DANAK 19 12336 DELTA T202349 Page 42 of 45 DELTA EUT LevelTec Manufacturer DANETV Operating Condition Line no Line 1 230 V
7. 13 3 4 Amendments to and deviations from test plan 13 4 REFERENCE Surin TE E EE E M NM INE 14 RENDRA EEEE Eiai 15 Terms and iulio p eee nE EEEE EA EEE E E Esi PEENES 15 APPRENDRE ee een ee eee 18 Test data report PR ER RE Re 18 APRENDA ee EESE E EAA EEN ENE NER 20 DELTA Test Report Environmental Testing of LevelTec Online Monitoring System 20 t AgroTech DANETV 1 INTRODUCTION This test report is prepared as part of the the verification of LevelTec online monitoring system for slurry storage tanks following the AgroTech Test Centre Quality Manual 1 1 Name and contact of proposer LevelTec is developed and produced by PlusTec Aps Mads Bjerresvej 8 DK 7500 Holstebro Denmark Website www plustec dk Contact person of PlusTec Aps J rgen Seerup E mail js plustec dk Phone 45 96 10 40 80 Mobil phone 45 20 32 66 54 1 2 Name of test body and test responsible The test activities were coordinated by DANETV Test Centre AgroTech Agro Food Park 15 DK 8200 Aarhus N Denmark Test responsible for the performance test was Seren G Rasmussen AgroTech Phone 45 87 43 84 22 E mail sgr agrotech dk Test responsible for the environmental test was Susanne Otto DELTA Phone 45 72 19 41 13 E mail suo delta dk 1 3 Reference to test plan and specific verification protocol This test report was made to meet the requirements defined in the verification protocol and test plan for LevelTe
8. Conducted radio frequency control unit SUO Iko DANAK 19 12336 DELTA T202349 Page 35 of 45 i e PV E V E Photo 13 Burst fast transients Photo 14 Surge voltage SUO Iko DANAK 19 12336 DELTA T202349 Page 36 of 45 IN Photo 15 Radiated emission Pp he P Photo 16 Conducted emission SUO Iko DANAK 19 12336 DELTA T202349 Page 37 of 45 Photo 17 Power frequency H field Immunity SUO Iko DANAK 19 12336 DELTA T202349 Page 38 of 45 Annex 3 Measurement curves Emission SUO Iko DANAK 19 12336 DELTA T202349 Page 39 of 45 DELTA EUT LevelTec Manufacturer DANETV Operating Condition Ant 1 m vertical Test Site EMC 5 Operator HEN T202349 Test Specification EN55022 B Comment Sheet 3 Start of Test 22 03 2012 Level dBu V m 30M 50M 70M 100M 200M 300M 500M 700M 1G Frequency Hz X MES Maximering fin QP MES RE 30 1000 QP 1m QPk MES RE 1mv 30 1000 MaxPk LIM RE EN 55022 B QP Radiated Emission MEASUREMENT RESULT Maximering fin QP 22 03 2012 11 33 Frequency Level Transd Limit Margin Height Azimuth Polarisation MHz dBuV m dB dBuV m dB cm deg 94 600000 29 60 10 0 30 50 0 4 101 0 242 00 VERTICAL 119 300000 23 40 12 1 30 0 6 6 118 0 261 00 VERTICAL 141 900000 28 20 122 30 0 1 8 101 0 348 00 VERTICAL 148 100000 2 1 10 11 8 30 0 29 104 0 338 00 VERTICAL 159 300000 28 90
9. T202349 Page 2 of 45 Environmental Testing of LevelTec Online Monitoring System 3 pcs of LevelTec Online Monitoring Systems complete with level sensor and cabling serial nos 2011 1201 011 2011 1201 025 and 2011 1201 023 Detailed information is given in Section 2 The test objects were received 23 February 2012 DANAK 19 12336 T202349 22 March 14 June 2012 Plus Tec ApS Mads Bjerres Ve 8 7500 Holstebro Denmark Mr J rgen Seerup E mail JS plusel dk Tel 45 96 10 40 80 Plus Tec ApS DANETV Doc D 5 Environmental test specification for LevelTec Slurry Surveillance System Danske Landbrugsmaskinfabrikanters Palidelig Jordbrugselektronik Maj 1989 Nordtest ELEC 016G 1990 No malfunctions were detected However please note the observation made after impact Section 4 6 The criteria for compliance are listed in Section 3 2 Anders B Kentved Henrik Egeberg Nielsen Poul N rgaard Olling Truelsen DANAK 19 12336 DELTA T202349 Page 3 of 45 Date 15 August 2012 Responsible Susanne Otto B Sc E E B Com Org DELTA SUO Iko 1 1 1 2 2 1 222 3 1 3 2 3 3 3 4 4 1 4 2 4 3 4 4 4 5 4 6 4 7 4 8 4 9 4 10 4 11 4 12 4 13 4 14 4 15 4 16 SUO Iko Table of contents Summary of test Introduction Conclusion Test objects Test objects Auxiliary equipment General test conditions Test setup Criteria for compliance Functional test Standard env
10. Yes no for the tank in case of failing power suppl Alarm is forwarded to a new person in case the communication to Yes no the first person did not result in actions that reset the alarm The LevelTec system is automatically switched on following a Yes no manual switching i i The performance test was done using a small scale slurry container with the LevelTec installed Leakages were simulated by opening a tap installed in the bottom of the slur ry container Figure 1 shows the small scale slurry container used for the performance test of LevelTec Figure 1 The small scale slurry container used for the performance test of LevelTec On the left photo the LevelTec control unit is seen as a grey box installed on the end of the slurry container By undertaking the performance test at a biogas plant using slurry from many different farms it was possible to test the LevelTec Online Monitoring System using different LevelTec Test Report 4 AgroTech k AgroTech DANETV slurry types The performance of LevelTec was tested and verified using five difference slurry types matrices An overview of the five slurry types is given in Table 2 below Table 2 Overview of the five slurry types used for the performance test of LevelTec Mixture of sow and piglet slurry Mixed pig slurry with fodder residues Mixed pig slurry Fattening pig slurry 2 3 2 Environmental test methods Table 3 shows for each environmental tes
11. of the test object during the exposure A visual inspection is performed after the exposure Result No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspection performed after the exposure Impact surface point operational The main purpose of this test is to verify the ability of the test object to operate during impacts likely to occur during normal use Reference specification IEC 60068 2 63 1991 Test Eg Impact spring hammer 4 1 SUO Iko DANAK 19 12336 DELTA T202349 Page 14 of 45 Severity Impact energy i 1J Number of impacts 3 at each point Impact points Relevant accessible surfaces Procedure The test object is placed on a rigid plane test surface The test object is switched ON and the functional check monitors the operation of the test object during the exposure A visual inspection is performed after the exposure Result No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspection at standard atmospheric conditions except for cracking of black plastic part Cable bending The main purpose of this test is to verify the mechanical integrity of cable connections during conditions of cable bending likely to occur during normal use Product application standard Danske Landbrugsmaskinfabrikanters P lidelig jordbrugselektronik Maj 1989 Nordtest ELEC 016G S
12. the involved test staff it was not possible to follow the time schedule described in the test plan Consequently the test report was de layed LevelTec Test Report 13 AgroTech AgroTech DANETV 4 REFERENCES 1 AgroTech 2009 AgroTech Test Centre Quality Manual Not published 2 Plus Tec 2011 Product Sheet for LevelTec In Danish 2 pp 3 Plus Tec 2011 User Manual for LevelTec In Danish 18 pp 4 dig Tele 2011 Product sheet for DLG slurry tank monitoring system In Dan ish 1 p LevelTec Test Report 14 AgroTech c DANETV ee Low AgroIech APPENDIX A Terms and definitions LevelTec Test Report 15 AgroTech t AgroTech DANETV Analytical labor Independent analytical laboratory used to analyse test samples atory Application The use of a product specified with respect to matrix target effect and limitations DANETV Danish center for verification of environmental technologies DANETV test Preliminary name for the verification bodies in DANETV with a verification center and a test sub body Effect The way the target is affected Environmental Ready to market or prototype stage product process system or service product based upon an environmental technology Environmental The practical application of knowledge in the environmental area technology Evaluation Evaluation of test data for a technology product for performance and data quality In
13. 12 10 48 15 03 2012 10 50 15 03 2012 13 42 15 03 2012 13 43 It is concluded from the test that the alarm function in case of failing power supply is working as claimed by the technology supplier Alarm forwarding function If a potential leakage is registered from the slurry storage tank it is crucial that the SMS alarm message is actually received by a person who can take immediate actions to stop the leakage and minimize the risk for pollution of nearby streams and lakes There is a risk that the person to whom the SMS alarm message Is sent will not see this im mediately Perhaps the person has put the mobile phone away or the mobile phone has run out of battery According to the technology supplier LevelTec will send an SMS alarm message to an other mobile phone number if LevelTec is not reset 5 minutes after the SMS alarm message is sent And if there is still no reaction from the receiver of the second SMS message an SMS alarm message is send to a third mobile number LevelTec can for ward the SMS alarm message to up to five mobile numbers If there is still no action taken LevelTec sends SMS messages to the first mobile number again This function has been tested as part of the verification A leakage has been simulated in the small scale slurry container When the SMS alarm messages were received re setting the LevelTec was omitted The time for reception of the SMS alarm messages were registered The test was repeated twice and t
14. 9 Nordtest ELEC 016G Reference standard IEC 60529 2001 Degrees of protection provided by enclosures IP Code Severity control unit including sensor cable Water IP X4 protected against splashing water Severity level sensor including sensor cable Water IP X7 immersion Procedure The test object is switched OFF during the exposure A functional test and a visual inspection with special attention to any water inside the product are performed after the exposure Result Neither ingress of water nor malfunction was observed after the exposure 4 5 4 6 SUO Iko DANAK 19 12336 DELTA T202349 Page 13 of 45 Transient shock operational The purpose of this test is to verify the ability of the test object to withstand shocks likely to occur during normal use Reference specification IEC EN 60068 2 57 1999 Test Ff Time history method Severity control unit Peak acceleration 10 20 g Frequency range RRS level 5 25 Hz 12 dB oct 25 250 Hz 50 g Number of shocks 3 per axis Number of axes 3 mutually orthogonal Severity level sensor Peak acceleration 40 80g Frequency range RRS level 10 100 Hz 12 dB oct 50 500 Hz 200 g Number of shocks 3 per axis Number of axes i 3 mutually orthogonal Procedure The test object mounted on a fixture representing normal use is placed on the vibrator table The test object is switched ON and the functional check monitors the operation
15. AC Test Site EMC 5 Operator HEN T202349 Test Specification EN55022 B Comment Sheet 6 Start of Test 22 03 2017 Level dBy V a o Ande t WAR m a LARA T ANM TRA WA wa 500k 1M 2M 3M SM 7M Frequency Hz 150k 300k MES CE 0 15 30 PK AV Avg MES CE 0 15 30 PK MaxPk LIM CE EN 55022 B AV Conducted Emission LIM CE EN 55022 B QP Conducted Emission 22 03 2012 11750 CE SUO Iko DANAK 19 12336 DELTA T202349 Page 43 of 45 Annex 4 Test setup and functional test procedure SUO Iko DANAK 19 12336 DELTA T202349 Page 44 of 45 Funktionstest der skal v re 230 VAC pa enheden forst 1 Tjek at sensoren er under ca 1 m 1000 mm vand i r ret husk at tolerancen er 50 mm 5 cm sa der er lidt at give af 2 Send en SMS med LEVEL til enhedens tlf nummer Den skal svare med et level pa omkring 1000 mm 3 Tr k sensoren et godt stykke 20 cm eller s dan noget op ad vandet og hold den der 30 60 sek 4 Tjek at du modtager en SMS med LAEKAGE ALARM 5 Tjek at de to hvide ledninger bliver kortsluttet rel erne med et multimeter 6 Put sensoren ned 1 vandet igen 1 m vand 7 Tjek at de hvide ledninger stadig er kortsluttede 8 Tryk pa den store bla Reset knap og tjek at de hvide ledninger ikke er kortsluttede mere 9 H ld lidt mere end 5 cm ekstra vand 1 r ret dvs lidt over den ekstra streg jeg har tegnet 10 Tjek at du
16. OK no SMS alarm message is sent even though 0 30 meter slurry is drained off the slurry container LevelTec is still switched off Reception of SMS message confirming that LevelTec is now switched on again The tap is opened to decrease the slurry level in the slurry container Reception of SMS alarm message Result 3 OK the alarm function of LevelTec has been automatically switched on again after 1 hour SMS alarm messages are now sent when a de crease in slurry level is registered Based on the results in Table 10 it is concluded that the functions of manual switching off and automatic switching on are working as claimed by the technology supplier In Table 11 the results of the performance test are summarised Table 11 Summary of the performance test of LevelTec Parameter Verified value Threshold value for reporting leakage measured as decrease in slur 0 05 meter ry level Time from threshold value in slurry level has been reached to SMS Maximum 2 minutes message is received by the person responsible for the tank Warning and alarm messages are received by the tank responsible Yes these functions person in case of slurry tank overflow work as claimed An alarm is registered and communicated to person responsible for Yes this function the tank in case of failing power supply works as claimed Alarm is forwarded to a new person in case the communication to the Yes this function first person did not result in a
17. OWER AMPLIFIER 800 4200 OPHIR RF 5161F MHz 15 WATTS 49514 BURST CABLE 1 m DELTA RG223 U 49531 COAX RF DIODE DETECTOR NEG HEWLETT PACKARD 8471D OUTPUT CS TEST 49562 ESD GENERATOR AIR AND SHAFFNER NSG438 CONTACT DISCHARGE 49617 HIGH POWER RF AMPLIFIER 80 1000 TESEQ CBA1G 500 MHz 500 W EVFGT 50 EL DYN LONG STROKE SHAKER LING DYNAMICS V875 440 1127205 ACCELEROMETER BR EL amp KJ R 4371 95 22585 ACC PRE AMP BR EL amp KJ R 2626 43236 VIBR CONTROLLER LDS DACTRON LAS 200 EVEGT 47 CLIMATIC CHAMBER DELTA VKF875 3 EVFGT 34 WATER TEST FACILITY DELTA EVFGT 34 SUO Iko DANAK 19 12336 DELTA T202349 Page 28 of 45 Annex 2 Photos SUO Iko DANAK 19 12336 DELTA T202349 Page 29 of 45 E Photo 2 Climatic tests dry heat cold and humidity level sensor SUO Iko DANAK 19 12336 DELTA T202349 Page 30 of 45 LEVELT C i Photo 4 Transient shock control unit SUO Iko DANAK 19 12336 DELTA T202349 Page 31 of 45 Photo 5 Transient shock level sensor Photo 6 Cable bending SUO Iko DANAK 19 12336 DELTA T202349 Page 32 of 45 Photo 7 Impact control unit Photo 8 Impact level sensor after impact SUO Iko DANAK 19 12336 DELTA T202349 Page 33 of 45 Photo 9 ESD control unit j Photo 10 ESD level sensor SUO Iko DANAK 19 12336 DELTA T202349 Page 34 of 45 Photo 11 Radiated RF immunity Photo 12
18. Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure Performance criterion B Radiated emission The purpose of the test is to verify that the unintentional E field emissions from the test object in normal operating mode is below the specified limits Product application standard EN 61000 6 3 2006 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environments Reference standard CISPR 16 2 3 2006 Specification for radio disturbance and immunity measuring apparatus and methods Part 2 3 Methods of measurement of disturbance and immunity Radiated disturbance measurements Severity control unit and level sensor including all cables Frequency range i 30 1000 MHz Limits quasi peak 30 230 MHZ 30 dBuV m 230 1000 MHZ 37 dBuV m Procedure The electromagnetic field is measured with antennas at a distance of 10 m The test object is switched ON and in normal operational mode during the measurement Results The radiated emissions were within the specified limits Test record sheets of the radiated emission measurements are enclosed in Annex 3 4 14 4 15 SUO Iko DANAK 19 12336 DELTA T202349 Page 22 of 45 Conducted emission The purpose of the test is to verify that the unintentional emissions conducted back on the AC power mains are below the specifi
19. ables The test object is switched ON during the exposure The test object is observed during the exposure and a functional check is performed after the exposure Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure Performance criterion B Surge voltage The purpose of the test 1s to verify the immunity of the test object to switching and lightning induced transients Applicable to AC DC power inputs as well as I O cabling which exceeds 30 m Product application standard EN 61000 6 1 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Reference standard IEC 61000 4 5 2005 Testing and measurement techniques Surge immunity test Severity control unit and level sensor including all cables longer than 3 m Amplitude power ports l 2 kV line to earth IkV line to line Amplitude signal ports 1 kV line to earth SUO Iko Voltage rise time Voltage decay time DANAK 19 12336 DELTA T202349 Page 20 of 45 1 2 us open circuit 50 us open circuit 4 13 SUO Iko DANAK 19 12336 DELTA T202349 Page 21 of 45 Procedure The impedance of the test generator is 2 for line to line coupling and 12 Q for line to earth coupling The test object is switched ON during the exposure The test object is observed during the exposure and a functional check is performed after the exposure
20. ata report LevelTec Test Report 18 AgroTech Ok AgroTech DANETV All relevant data from the performance test is presented in section 3 1 1 and section 3 1 3 Data from the environmental test are presented in section 3 1 2 and in Appendix C LevelTec Test Report 19 AgroTech DANETV 7 AgroTech APPENDIX C DELTA Test Report Environmental Testing of LevelTec Online Monitoring System LevelTec Test Report 20 AgroTech We help ideas meet the real world DELTA Test Report LL EL NM l p SS jac MRA i DANAK Ll ne TN TEST Reg no 19 i j Ws Environmental Testing of LevelTec Online Monitoring System Performed for Plus Tec ApS DANAK 19 12336 Project no T202349 Page 1 of 45 including 4 annexes 15 August 2012 DELTA Venlighedsvej 4 2970 Hgrsholm Denmark Tel 45 72 19 40 00 Fax 45 72 19 40 01 www delta dk VAT No 12275110 This report is issued under the rules of DANAK Danish Accreditation and ILAC International Laboratory Accreditation Cooperation including its MRA Mutual Recognition Arrangement Further information can be found at www danak dk and www ilac org The report must not be reproduced except in full without the written approval of DELTA Version m Title Test objects Report no Project no Test period Client Contact person Manufacturer Specifications Results Test personnel SUO Iko DANAK 19 12336 DELTA
21. bject to withstand the environmental conditions without impairment of the function Further a visual inspection with the un aided eye is performed after each exposure in order to detect mechanical damages or deteriorations The functional test procedure is given in Annex 4 3 4 SUO Iko DANAK 19 12336 DELTA T202349 Page 9 of 45 Standard environment Normal environmental condition Temperature 15 C 35 C Humidity 25 RH 75 RH Air pressure 86 kPa 106 kPa 860 mbar 1060 mbar Power supply voltage Um 3 Zo 4 1 4 2 SUO Iko DANAK 19 12336 DELTA T202349 Page 10 of 45 Test and results Dry heat operational The purpose of this test is to verify the ability of the test object to operate according to specifications at the upper temperature limit of the use environment Product application standard Danske Landbrugsmaskinfabrikanters P lidelig jordbrugselektronik Maj 1989 Nordtest ELEC 016G Reference standard IEC EN 60068 2 2 2007 Test Be Dry heat for heat dissipating specimen with gradual change of temperature Severity control unit Temperature 70 C Duration 16 hours Severity level sensor Temperature 40 C Duration 16 hours Procedure The test object is switched ON during the exposure A functional check is performed during the last part of the exposure at the high temperature Further a visual inspection is performed after returning to standard at
22. c online monitoring system used for slurry storage tanks 1 4 Deviations to test plan Due to many other ongoing tasks of the involved test staff it was not possible to follow the time schedule described in the test plan Consequently the test report was de layed 2 TEST DESIGN The test was divided into two main parts 1 Performance test undertaken by AgroTech test staff 2 Environmental test undertaken by test staff from DELTA LevelTec Test Report 2 AgroTech k AgroTech DANETV The main purpose of the performance test was to demonstrate that the alarm function of the online monitoring system is functioning as described by the technology supplier i e that the alarm is triggered when it is supposed to be triggered However the test should also demonstrate that number of false alarms is reduced to a minimum This is partly because it is inconvenient and time consuming for the owner of the slurry stor age tank to react on such false alarms In addition if the LevelTec system is sending a lot of false alarms there is a risk the slurry storage tank owner or the person responsi ble to react on alarms will not take action if he she believes that there is no problem The main purpose of the environmental test was to verify the ability of the LevelTec to withstand or operate within specified tolerances while being exposed to the environ mental conditions likely to be encountered during normal use 2 1 Technolo
23. charges are applied to conductive surfaces and coupling planes Air discharges are applied to insulating surfaces The test object is switched ON during the exposure The test object is observed during the exposure and a functional check is performed after the exposure Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure Performance criterion B 4 9 4 10 SUO Iko DANAK 19 12336 DELTA T202349 Page 16 of 45 Radiated RF immunity The purpose of the test is to verify the immunity of the test object to fields generated by intentional transmitters radio TV cell etc Product application standard EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Reference standard IEC 61000 4 3 2006 Testing and measurement techniques Radiated radio frequency electromagnetic field immunity test Severity control unit and level sensor including all cables Frequency range 80 1000 MHz 1000 20000 MHz 2000 2700 MHz Field strength 10 V m 3 V m 1 V m Modulation 80 AM 1000 Hz sine wave Procedure The test is performed in an anechoic room The field is generated using linearly polarised broadband antennas The test object is switched ON during the exposure The test object is observed during the exposure and a functional check is performed after the exposure Results
24. ctions that reset the alarm works as claimed The LevelTec system is automatically switched on following a manu Yes this function al switching off e g during emptying of storage tank works as claimed Note Under assumption of satisfactory mobile phone connection coverage 3 1 2 Environmental test results Table 12 shows for each environmental test parameter the results of the environmental test activities LevelTec Test Report 10 AgroTech AgroTech DANETV Table 12 Results from evaluation of environmental test parameters No Parameter Resut 1 Dry heat opera No malfunction was observed during the exposure Further no tional damages or deteriorations were observed during the visual inspec tion at standard atmospheric conditions 2 Cold operational No malfunction was observed during the exposure Further no including cold damages or deteriorations were observed during the visual inspec start up tion at standard atmospheric conditions 3 Humidity No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspec tion at standard atmospheric conditions Water operation Neither ingress of water nor malfunction was observed after the al exposure Transient shock No malfunction was observed during the exposure Further no operational damages or deteriorations were observed during th
25. d tank overflow alarm functions Leakages from slurry storage tanks can result from tank overflow This will occur if slur ry is pumped from the animal housing system to a storage tank which is already full It is claimed by the technology producer that LevelTec can be used to prevent this situ ation According to the user manual an SMS warning message is sent to the tank own er when the level reaches 0 10 meter from the rim of the storage tank The tank owner has to reset LevelTec after reception of an SMS warning message If the slurry level continues to raise LevelTec sends an SMS alarm message when the slurry level reaches 0 02 meter from the rim of the storage tank As part of this verification the full tank warning and the tank overflow alarm functions were tested The tests were performed using the small scale slurry container First the height of the container was artificially set to 0 45 meter This was done by sending SMS commandos to LevelTec Then slurry was led to the slurry container and SMS messages were waited for Table 7 shows the results from these tests Table 7 Results from testing the full tank warning and tank overflow alarm functions LevelTec when SMS was received Full tank 0 380 meter In the time from LevelTec registers that the 0 10 warning meter threshold value is reached to the SMS warning message is received on the mobile phone the slurry level continues to raise That is the reason why there is only measured 0
26. dependent persons qualified on a technology in verification The type of material that the product is intended for Method Generic document that provides rules guidelines or characteristics for tests or analysis Performance The effects foreseen by the vendor on the target s in the matrix of in claim tended use Performance Parameters that can be documented quantitatively in tests and that pro parameters vide the relevant information on the performance of an environmental technology product Detailed description of the use of a standard or a method within one body The party producing the product Standard Generic document established by consensus and approved by a recog nized standardization body that provides rules guidelines or characteris tics for tests or analysis The property that is affected by the product Test center test Sub body of the test center that plans and performs test sub body LevelTec Test Report 16 AgroTech DANETV AgroTech Test center verification sub body Test testing Verification LevelTec Test Report Sub body of the test center that plans and performs the verification Determination of the performance of a product for parameters defined for the application Evaluation of product performance parameters for a specified application under defined conditions and adequate quality assurance 17 AgroTech i E DANETV Ms G Agrolech APPENDIX B Test d
27. e g using an excavator before slurry is pumped to the tank Alternatively the pressure sensor can be raised so that it is now place 0 40 0 50 meter from the bottom of the tank However if the pressure sensor is raised LevelTec has to be cali brated again 3 2 Test performance observation All relevant observations made during testing are described in section 3 1 3 3 Test quality assurance summary including audit results The test followed the AgroTech Test Centre Quality Manual which is ISO 9001 compli ant but not certified The test report have been subject to internal review by the verification responsible from AgroTech Test Centre Torkild S Birkmose In addition Anders Bonde Kentved DELTA has reviewed the test results of the environmental test activities performed by DELTA No system audit was done for this verification External review of the test report was done by Jergen Hviid Knowledge Centre for Ag riculture Agro Food Park 15 DK 8200 Aarhus N The stability of the test equipment was controlled continuously by supervision and re cording of data Procedures for ensuring that test facilities and equipment are calibrat ed and fit for the purposes are described in the Quality Manual for the Laboratories of AgroTech Data management including filing and archiving procedures are described in the Agro Tech Test Centre Quality Manual 3 4 Amendments to and deviations from test plan Due to many other ongoing tasks of
28. e visual inspec tion performed after the exposure Impact surface No malfunction was observed during the exposure Further no point operational damages or deteriorations were observed during the visual inspec i tion at standard atmospheric conditions except for cracking of black olastic part 7 Cable bending No malfunction was observed during the exposure Further no M damages or deteriorations were observed during the visual inspec tion at standard atmospheric conditions Electrostatic dis No malfunction was observed during the exposure and the function M charge of the test objects was OK after the exposure Performance criteri on B Ca cease eee munity of the test objects was OK after the exposure frequency of the test objects was OK after the exposure ents of the test objects was OK after the exposure of the test objects was OK after the exposure sion sion H field immunity of the test objects as OK after exposure interruptions of the test objects was OK after the exposure Based on the environmental test activities it is concluded that the test object LevelT ec online monitoring system complete with pressure sensor and cabling meets the rele vant requirements of the reference standards reference specifications Full infor mation about the environmental test is included in the DELTA Test Report Environ mental Testing of LevelTec Online Monitoring System performed for Plus Tec ApS see Appendix C 3 1 3 Addi
29. ed limits Product application standard EN 61000 6 3 2006 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commercial and light industrial environments Reference standard CISPR16 2 1 2008 Specification for radio disturbance and immunity measuring apparatus and methods Part 2 1 Methods of measurement of disturbances and immunity Conducted disturbance measurements Severity control unit and level sensor including all cables Frequency range 0 15 30 MHz Limits quasi peak 0 15 0 5 MHz 66 56 dBuV 0 5 5 MHz i 56 dBuV 0 5 30 MHz 60 dBuV Procedure The radio frequency voltage is measured at the power supply terminals of the test object by a receiver through an artificial mains network The test switched ON during the measurement Results The conducted emissions were within the specified limits Test record sheets of the conducted emission measurements are enclosed in Annex 3 Power frequency H field immunity The purpose of the test is to verify the immunity of the test object to low frequency magnetic fields Product application standard EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments DANAK 19 12336 DELTA T202349 Page 23 of 45 Reference standard IEC 61000 4 8 2001 Testing and measurement techniques Power frequency magnetic field immunity test SUO Iko 4 16
30. ej 4 DK 8380 Trige Denmark Contact person of test site is Arne Jensen Phone 45 20 21 33 70 E mail amj baanlev dk By doing the performance test activities at a biogas plant it was possible to simulate leakages from a slurry tank under controlled conditions The environmental test was undertaken in the laboratories of DELTA Venlighedsvej 4 DK 2970 Hersholm Denmark Contact person of test site is Susanne Otto Phone 45 72 19 41 13 E mail suo delta dk LevelTec Test Report 3 AgroTech FR AgroTech DANETV 2 3 Test methods 2 3 1 Performance test methods No standardized methods for undertaking performance test of online monitoring sys tems for slurry storage tanks have been identified Therefore test methods have been developed specifically for the present testing of the LevelTec system The performance test was planned and undertaken with the aim to verify the 6 perfor mance parameters described in Table 1 Table 1 Overview of the 6 performance parameters for the verification of LevelTec Parameter Value Threshold value for reporting leakage measured as decrease in 0 05 meter slurry level Time from threshold value in slurry level has been reached to 2 minutes SMS message is received by the person responsible for the tank Warning and alarm messages are received by the tank responsi Yes no ble person in case of slurry tank overflow An alarm is registered and communicated to person responsible
31. everity cable level sensor end Number of bendings 2500 per plane Force SN Procedure The sensor 1s fixated The bending angle is limited to the maximum achievable during normal use A visual inspection is performed after the exposure Result No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspection at standard atmospheric conditions 4 8 SUO Iko DANAK 19 12336 DELTA T202349 Page 15 of 45 Electrostatic discharge The purpose of the test is to verify that electrostatic discharge occurring on the equipment or in its vicinity does not affect its performance or causes malfunction or permanent damage It is also a test of proper grounding or shielding inside the test object Product application standard EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Reference standard IEC 61000 4 2 2001 Testing and measurement techniques Electrostatic discharge immunity test Severity control unit and level sensor Air discharge 2 4 and 8 kV Contact discharge 2 4 and 8 kV Energy storage capacitance 150 pF Discharge resistance 330 Polarity and Number of discharges i 10 per polarity at each test point Procedure The discharges are applied only to such points and surfaces of the test object which are accessible to personnel during normal use Contact dis
32. following generic acceptance criteria for compliance were in force during the EMC immunity testing Performance Criterion A For continuous phenomena The EUT shall continue to operate as intended during and after the test No degradation of performance or loss of function is allowed as defined in the relevant equipment standard and in the technical specification published by the manufacturer Performance Criterion B For transient phenomena The EUT shall continue to operate as intended after the tests No degradation of performance or loss of function is allowed as defined in the technical specification published by the manufacturer During the test degradation or loss of function or performance which is self recoverable is however allowed but no change of actual operating state or stored data is allowed Performance Criterion C Temporary degradation or loss of function or performance is allowed during and after the test provided the function is self recoverable or can be restored by the operation of the controls as defined in the relevant equipment standard and in the technical specification published by the manufacturer Functional test A functional check demonstrating compliance with the requirements stated by Plus Tec ApS is performed before the actual testing 1s started The functional check is performed before in some cases during and after each environmental exposure in order to verify the ability of the test o
33. gy description LevelTec Online Monitoring System includes a pressure sensor cabling and a control unit with a GSM modem for communication between LevelTec and mobile phones The pressure sensor and cable are placed in a PVC tube mounted on a galvanised steel frame installed on the inner side of the storage tank wall The pressure sensor is kept in a fixed position approximately 0 20 meter above the bottom of the slurry tank Even small changes in the slurry level are measured by the pressure sensor A de crease in the slurry level results in a lower pressure and vice versa LevelTec is pro grammed so that when a sudden pressure decrease is measured a SMS message is sent to the owner of the slurry tank or another person responsible for the slurry tank The purpose of the SMS message is to make it possible to take immediate actions in case of leakages Thereby it is possible to avoid or minimize pollution of nearby streams and lakes The LevelTec Online Monitoring System is intended for storage tanks for all types of livestock slurry and for digested biomass from biogas plants Normally the total solids content of such matrices is within the range of 2 0 10 0 96 The overall purpose of LevelTec is to 1 detect a potential risk for leakage and 2 to re port this electronically to the slurry storage tank owner or another person responsible for the tank 2 2 Test sites The performance test was undertaken at Baanlev Biogas Plant Bjergagerv
34. he results are presented in table 9 Table 9 Results from testing the SMS alarm forwarding function of LevelTec Time from reception of the first SMS alarm Event message number 2 number 1 again It is concluded that the alarm forwarding function is working as described by the tech nology supplier Automatic switching on LevelTec after manual switching off Sometimes slurry is pumped from the storage tank to a slurry trailer to be applied on the field or to be moved to another tank or transported to a biogas plant This will cause the slurry level to decrease and an SMS alarm message will be generated even though there is no leakage To avoid SMS alarm messages in such situations it is possible to switch off the Level Tec alarm function for a certain number of hours This is done by sending an SMS message to LevelTec In the SMS message it is specified for how many hours Level Tec should be switched off According to the technology supplier LevelTec will auto matically switch on again after the specified number of hours This function is tested and the results are presented in Table 10 LevelTec Test Report 9 AgroTech AgroTech DANETV Table 10 Results from testing the automatic switching on LevelTec after manual switching off 8 41 An SMS command is sent to LevelTec to switch off the alarm function for 1 hour GYLLEOFFO 1 drained off the slurry container LevelTec has been switched off Result 2
35. installed only 0 20 meter from the bottom of the slurry tank there is a risk that the pressure sensor will be covered by sand and this could potentially give problems for the performance of the LevelTec As part of this verification the function of LevelTec was tested in a situation where the pressure sensor was covered Figure 2 shows the test set up Figure 2 Photo 1 shows the LevelTec pressure sensor installed in the small scale slurry container used for the performance test Photo 2 shows the LevelTec sensor covered by sand Photo 3 show how the sand is placed around the LevelTec sensor after the slurry container was filled with slurry and emptied again It is seen that the sand is still laying around the sensor LevelTec Test Report 12 AgroTech t AgroTech DANETV It was concluded from the test activities that uncertainties in the pressure measure ments can occur when the LevelTec sensor is fully covered by a thick layer of sand Thus in such situations there is a risk that LevelTec will not detect a sudden decrease in the slurry level and send a SMS alarm message To avoid this situation it is recommended the slurry tank owner to check the thickness of the sand layer once a year immediately after the storage tanks has been emptied in connection with land application of slurry If the bottom layer has become so thick that there is a risk the pressure sensor will be covered actions should be taken to remove the sand
36. ironment Test and results Dry heat operational Cold operational including cold start up Humidity Water operational Transient shock operational Impact surface point operational Cable bending Electrostatic discharge Radiated RF immunity Conducted radio frequency Burst Fast transients Surge voltage Radiated emission Conducted emission Power frequency H field immunity Voltage dips and interruptions Annex List of instruments Annex 2 Photos Annex 3 Measurement curves Emission Annex 4 Test setup and functional test procedure DANAK 19 12336 DELTA T202349 Page 4 of 45 Page Un I N WO O0 O0 O0 KH 10 10 10 11 12 13 13 14 15 16 16 18 19 21 22 22 24 26 28 38 43 1 1 1 2 SUO Iko DANAK 19 12336 DELTA T202349 Page 5 of 45 Summary of test Introduction The testing is performed according to DANETV Doc D 5 Environmental test specification of LevelTec Slurry Surveillance System The specification 1s based on the manufacturer s product sheet on site inspection at a farm at Rostved Danske Landbrugsmaskinfabrikanters Palidelig jordbrugselektronik Maj 1989 Nordtest ELEC 016G 1990 and SPM 179 Acceleration factors and accelerated life testing 2011 The purpose of the environmental testing 1s to verify the ability of the test object to withstand or operate within specified tolerances while being exposed to the environmental conditions likely to be encou
37. is allowed 2 4 Test schedule The test schedule for the performance test is presented in table 4 below Table 4 Test schedule for the performance and environmental testing of LevelTec 2012 Week no 19 14 15 16 17 18 19 20 21 22 1 ee ee eee ee Period for testing X XX Test report quality assurance X Test report final version Ix 56 78 940 ti 2 X Practical planning X X X j Lo Lx RE 3 TEST RESULTS 3 1 Test data summary 3 1 1 Performance test results Detection and reporting a decrease in slurry level of 0 05 meter A number of test activities have been performed to verify the basic alarm function of the LevelTec Online Monitoring System To detect a decrease in slurry level and when the threshold value is reached to report this via a SMS message Leakages of different sizes are simulated by opening the tap to different extent In tests to simulate large leakages the tap was full open and in tests to simulate small leakages the tap was open to a very small extent As part of the test the time from the leakage started until the alarm SMS was received on the mobile phone was measured Also the decrease in slurry level from the leakage started until reception of the SMS message was measured Results from these test ac tivities are presented in Table 5 LevelTec Test Report 6 AgroTech DANETV di
38. modtager en SMS med TANK FULD 11 Tjek at de to hvide ledninger bliver kortsluttet rel erne med et multimeter 12 T m det ekstra vand af igen sa der bliver 1 m vand i r ret igen 13 Tjek at de to hvide ledninger ikke er kortsluttede mere enheden resetter selv 14 Udfyld arket med resultater som vi snakkede om 1 dag Ovenst ende er jo et komplet funktionstjek Som vi aftalte skal det k res for og efter alle testene og der hvor du synes det passer Undervejs i alle de forskellige forstyrrelser skal enheden bare st klar og male Hvis en forstyrrelse giver mere end 50 mm st j vil der blive sendt en besked til dig og rel erne vil tr kke Dette er jo selvf lgelig meget U NSKET for brugeren og skal derfor tjekkes noteres Der b r nok sidde et multimeter fast pa de to hvide ledninger som man kan holde je med undervejs SUO Iko DANAK 19 12336 DELTA T202349 Page 45 of 45 Test set up outside climatic test chamber with level sensor inside climatic test chamber SUO Iko
39. mospheric conditions Result No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspection at standard atmospheric conditions Cold operational including cold start up The purpose of this test is to verify the ability of the test object to initiate normal operation and operate according to specifications at the lower temperature limit of the use environment Product application standard Danske Landbrugsmaskinfabrikanters P lidelig jordbrugselektronik Maj 1989 Nordtest ELEC 016G 4 3 SUO Iko DANAK 19 12336 DELTA T202349 Page 11 of 45 Reference standard IEC EN 60068 2 1 2007 Test Ad Cold for heat dissipating specimen with gradual change of temperature Severity control unit Temperature i 25 C Duration 16 hours Severity level sensor Temperature 5 C Duration i 16 hours Procedure The test object is switched OFF during the exposure except for the last hour where the test object is switched ON and a functional check is performed Further a visual inspection is performed after returning to ambient temperature Result No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspection at standard atmospheric conditions Humidity The purpose of this test is to verify the ability of the test object to operate under and withstand the deteriorative effects of high
40. nic unit and sensor and a PVC tube The level sensor and cable are protected in a PVC tube mounted on a galvanised steel frame mounted inside the slurry tank see Fig 1 and 2 The control unit is mounted on the outside of the slurry tank For further details please refer to the manufacturer s specifications in Annex 1 Fig 1 LevelTec system 2 1 2 2 SUO Iko LCL LCL LL LL LL LAS LA LL LL LL ALL ELLE LL LL LL LL LL Leg h DANAK 19 12336 DELTA T202349 Page 7 of 45 Fig 2 Mounting of LevelTec pressure sensor Test objects Test objects 2 1 1 Name of test object Model type Part no Serial no Manufacturer Supply voltage Comments Auxiliary equipment Auxiliary equipment 2 2 1 Name of auxiliary equipment Model type Part no Serial no Manufacturer Supply voltage Comments 3 pcs of LevelTec Online Monitoring Systems complete with level sensor and cabling 2011 1201 011 2011 1201 025 and 2011 1201 023 Plus Tec ApS 230 VAC Various mobile phones For communication with LevelTec Online Monitoring system 3 1 3 2 3 3 SUO Iko DANAK 19 12336 DELTA T202349 Page 8 of 45 General test conditions Test setup A photo of the test setup is enclosed in Annex 4 Criteria for compliance No change of the actual operational states of the test object is allowed However temporary change is allowed during the power supply failure test In addition the
41. ntered during normal use The selection of the severity of each of the tests 1s based on the following conditions The test aims to produce the same failure mechanisms as may be encountered during use Only a few samples of the test objects are exposed to each test Thus variations in tolerances have to be taken into account The verbal description of the use environment see Section 2 1 The compliance of the LevelTec Online Monitoring System to electrical safety as well as the compliance of the GSM module to the RTTE directive is not covered Conclusion The test object mentioned in this report meets the relevant requirements of the specification standards stated below DANETV Doc D 5 Environmental test specification for LevelTec Slurry Surveillance System However please note the observation made after impact Section 4 6 The test results relate only to the objects tested SUO Iko DANAK 19 12336 DELTA T202349 Page 6 of 45 Test objects The LevelTec measures the level of the slurry tank by means of a pressure sensor A text message is transmitted to mobile phones at the occurrence of a sudden drop in slurry level or a full tank in order to protect nearby lakes or streams Further the LevelTec currently transmits data for monitoring and documentation The LevelTec system comprises a control unit a level pressure sensor a fixture for the sensor a supply cable and a signal cable connecting electro
42. on of the test objects was OK after the exposure Performance criterion A Burst Fast transients The purpose of the test is to verify the immunity of the test object to switching and transient noise Applicable to AC DC input and I O cabling greater than 3 m Product application standard EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for industrial environments Reference standard IEC 61000 4 4 2004 Testing and measurement techniques Section 4 Electrical fast transient burst immunity test Severity control unit and level sensor including all cables greater than 3 m Amplitude 2 kV on power lines 1 kV on signal lines and earth lines Pulse rise time 5 ns Pulse duration 50 ns Generator impedance 50 Q Repetition rate l 5 kHz 4 12 SUO Iko DANAK 19 12336 DELTA T202349 Page 19 of 45 Burst duration 15 ms Burst period time 300 ms Procedure Power port The test object is supplied with power via a transient coupling network The test signal is successively coupled to each power line and protective earth with reference to the ground plane The test signal is injected on the power lines for 5 minutes using each coupling mode and each polarity and then on the signal lines for 5 minutes using each polarity Signal lines The test signal is injected on the signal lines using a capacitive coupling clamp The clamp is successively used on selected signal c
43. posure Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure Performance criterion B 0 of nominal for 1 cycle C remainder of exposures DANAK 19 12336 DELTA T202349 Page 26 of 45 Annex 1 List of instruments SUO Iko DANAK 19 12336 DELTA T202349 Page 27 of 45 List of instruments NO DESCRIPTION MANUFACTURER TYPE NO 20232 HELMHOLZ COIL LARGE EC PK 20646 PWR ATT 6 dB 75W DC 2GHz BIRD ELECTRONIC 8308 60 N CORPORATION 29691 0 01 20 GHz SYNTH SWEEPER HEWLETT PACKARD 83620A 29694 1 12 GHz HORN ANTENNA LOGIMETRICS AN 8200 F 29806 BROADBAND POWER AMPLIFIER 10 AMPLIFIER RESEARCH 75A220 kHz 220 MHz 75 W 29815 3 LINE CDN NETWORK IEC 61000 4 MEB M3 6 29846 RF GENERATOR 9 kHz 2 4 GHz MARCONI 2024 29859 AC SOURCE W HEWLETT PACKARD 6842A HARMONIC FLICKER TEST OPTION 29891 GENERAL IMMUNITY SOFTWARE VBN PRTST KURVEPROG VERS 06 29911 DIGITAL MULTIMETER W HPIB HEWLETT PACKARD 34401A 29913 ELECTRICAL FAST TRANSIENT EM TEST EFT 500 BURST GENERATOR 29914 ELECTRONIC SURGE GENERATOR EM TEST VCS 500 29985 BILOG ANTENNA 26 2000 MHz SCHAFFNER CHASE 6140A 49002 SINGLE CHANNEL POWER METER ROHDE amp SCHWARZ NRVS DISPLAY UNIT 49159 HF GENERATOR MARCONI 2024 49390 RF COUPLER 2 18 GHz 30 dB MIDWEST MICROWAVE CPL 5028 30 INTERNATIONAL LTD NNN 79 49403 RF P
44. t parameter the reference standard or refer ence specification used Table 3 Overview of the 16 parameters included in the of environmental test of LevelTec and the corre sponding reference standard or reference specification used mL ERR specification 6 Impact surface point operational IMEEM EM Performance criterion B IMEEM M Performance criterion A Performance criterion A Performance criterion B Performance criterion B CISPR 16 2 3 2006 Conducted emission CISPR 16 2 1 2008 Performance criterion A Performance criterion B During the EMC immunity testing the following generic acceptance criteria for compli ance were in force e Performance Criterion A For continuous phenomena The EUT shall continue to operate as intended during and after the test No degradation of performance or loss of function is allowed as defined in the relevant equipment standard and in the technical specification published by the manufacturer LevelTec Test Report 5 AgroTech k AgroTech DANETV e Performance Criterion B For transient phenomena The EUT shall continue to operate as intended after the tests No degradation of performance or loss of function is allowed as defined in the technical specification published by the manufacturer During the test degradation or loss of function or performance which is self recoverable is however allowed but no change of actual operation state or store data
45. temperature humidity and cold condition Product application standard Danske Landbrugsmaskinfabrikanters P lidelig jordbrugselektronik Maj 1989 Nordtest ELEC 016G Reference standard cyclic test control unit and level sensor IEC 60068 2 30 2005 Test Db Damp heat cyclic 12 12 hours cycle Variant 1 Severity and procedure Lower temperature i 25 C Humidity range at lower temperature 95 100 RH Upper temperature i 55 C Humidity range at upper temperature 90 96 WRH Number of cycles 6 4 4 SUO Iko DANAK 19 12336 DELTA T202349 Page 12 of 45 Procedure The test object is switched OFF during the exposure except for the first hour of upper temperature in the second and the sixth cycle where the test object 1s switched ON and the functional check monitors the operation of the test object After this the test object is switched OFF again After recovery for hour at laboratory temperature a functional check and a visual inspection are performed Result No malfunction was observed during the exposure Further no damages or deteriorations were observed during the visual inspection at standard atmospheric conditions Water operational The purpose of this test 1s to verify the ability of the test object to operate according to specifications when exposed to water in the use environment Product application standard Danske Landbrugsmaskinfabrikanters P lidelig jordbrugselektronik Maj 198
46. tional test parameters LevelTec Test Report 11 AgroTech DANETV mk AgroTech User manual The LevelTec user manual is 18 pages and formulated in Danish The manual is read and evaluated as part of this verification According to the user manual switching off the LevelTec alarm function can be done using two commands ALARMOFFXX and GYLLEOFFXX XX refers to the number of hours the alarm function shall be switched off However during the test it was only the command GYLLEOFFXX that actually switched off the alarm function It is recom mended that the user manual is updated accordingly Moreover it is recommended that the user manual is updated so it includes instructions for calibration of LevelTec In addition In general the user manual contains full information and it is clearly formulated Testing the function of LevelTec when the pressure sensor is covered by sand Normally slurry contains a certain amount of sand e g from the fodder or from the wheels of the machines moving in and out of the livestock housing systems Especially large amounts of sand are found in slurry from cow housing systems where sand is used as bedding material for the cows During storage the sand will sediment in the slurry storage tank under the formation of a base layer in the bottom of the tank Over time this sand layer will accumulate since it is difficult to pump this out even after mixing the storage tank Thus since the pressure sensor is