SolaHD IntelliSlot Relay Card User Manual

image

Contents

1. IntelliSlot Relay Card User Manual IS RELAY i D vw EMERSON SOLAND Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com 1 0 Introduction The IntelliSlot relay card IS RELAY provides contact closure for remote monitoring of alarm conditions in your SolaHD UPS The IntelliSlot relay card is easy to install and integrates with other relay contact monitoring systems This advanced power management device is designed to function in units with a IntelliSlot port such as S4KC Series S5K Series Please visit our Web site for the curent list of suppored products On supported units the inverter shut off command can be controlled from the computer directly connected to the UPS via the factory installed DB9 connector and will conserve battery power after the workstation shutdown is complete The IntelliSlot relay card is rated for 24 V ac V dc at 1 A 1 1 Inspecting Shipment on Receipt Upon accepting shipment inspect the packaging and product for any damaged or missing parts If any damage is observed report it to the shipping company and your local SolaHD representative immediately If any components are missing contact your local SolaHD representative for replacement Items included with the shipment are IntelliSlot relay card protected by an anti static bag User manual Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr c
2. ax 888 723 4773 Web www clrwtr com Email info clrwtr com 3 0 PIN Configuration The IntelliSolt relay card has two terminals blocks TB1 green numbered 1 9 and TB2 black numbered 10 18 as shown in Figure 2 TB2 black Figure 2 PIN location amp numbering Please refer to the UPS User manual for the UPS terminal block configuration The PIN functions in Table 1 apply only to the SolaHD units listed in Section 1 0 Introduction Table 1 IntelliSlot Relay Card PIN Configuration en Function om 4 common towsatey 4 eommen vrsreak KN 6 use cosetinourstane 7 Jcommen ontey 8 onpatey Closedif n Battery power uy fairey 9 J nBattem Closed ifrot On Battery power utility 10 sanalGround UseforPSAnyModeshutdown 11 __ SianalGround ose for ops Any Mode Shutdown 14 summaan cosedifsummanyAlam occurs 45 common Summa fam fo 16 fOnuPS Closed if ON UPS inverter power LR a On Bypass Closed if On Bypass Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com 4 0 Jumper Setup The IntelliSlot relay card has five jumpers P3 through P7 as shown in Figure 2 Each jumper connects two PINs Front of card Jumper P6 Jumper P5 Jumper P4 BIEREN 4 Rv Jumper P3 j WEEER POWER amp Ee DY Jumper P7 L Figure 3 Jumper location amp numbering By default al
3. l five jumpers have shunts installed The two PINs are shunted together to provide the functions shown in Table 2 allowing relay commons to be tied together NOTE The jumpers should be removed if there are any external voltage sources that may intentionally or inadvertently be connected to the relay Removing the shunt from any two PINs breaks the connection between the relay commons so they are not tied together Table 2 Jumper Connections On Bypass Summary Alarm Jumper Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com
4. om 2 0 Installation 2 1 Required Parts amp Tools NOTE Make sure you have the following parts and tools before you begin the installation IntelliSlot relay card provided 2 medium Phillips or small flathead screwdriver 2 2 Installation Instructions 1 Turning off the UPS prior to installation is suggested although not required 2 Locate the IntelliSlot port See examples in Figure 1 Refer to the UPS user manual for port location and orientation 3 Remove the two retaining screws from the IntelliSlot port cover plate see Figure 1 Save the screws for reassembly in Step 5 4 Insert the IntelliSlot relay card Make sure the holes are aligned with those on the UPS Initially the card should slide in freely as you carefully align the screw holes As you feel it click into place press firmly to ensure solid seating in the slot 5 Use the screwdriver to secure the IntelliSlot relay card to the UPS chassis with the two retaining screws removed in Step 3 Make sure the screws are snug not tight to avoid damage to the device EITT Ei PRESS TO RESET 20A 125V IntelliSlot Relay Card Remove screws Figure 1 Installation 6 Use these guidelines for terminal block specifications Acceptable wire size 24 16 AWG Wire strip length 0 24 0 28 in 6 7 mm Please proceed to Sections 3 0 Pin Configuration and 4 0 Jumper Setup to configure the terminal blocks and jumpers Phone 800 894 0412 F

Download Pdf Manuals

image

Related Search

Related Contents

Bedienungsanleitung  TE-905 service manual.cdr  

Copyright © All rights reserved.
Failed to retrieve file