Gateway M-Bus from/to Modbus TCP Server
Contents
1. 106 mm 63 mm 4 17 inch 2 56 inch Housing PVC Weight 200g Approx Figure 11 Mechanical dimensions scheme for HD67044M 160 ADFweb com Srl IT31010 Mareno Treviso User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 25 of 27 95 mm 3 74 inch 4 17 inch 2 36 inch Housing PVC Weight 200g Approx Figure 10 Mechanical dimensions scheme for HD67044M 40 HD67044M 80 gt R Eg oN coa bA E 106 mm 75 mm 4 17 inch 2 95 inch Housing PVC Weight 200g Approx Figure 12 Mechanical dimensions scheme for HD67044M 250 INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 26 of 27 Industrial Electronic Devices ORDER CODES Order Code HD67044M Gateway M Bus to Modbus TCP Server up to 20 slaves connected to M Bus Order Code HD67044M 40 Gateway M Bus to Modbus TCP Server up to 40 slaves connected to M Bus Order Code HD67044M 80 Gateway M Bus to Modbus TCP Server up to 80 slaves connected to M Bus Order Code HD67044M 160 Gateway M Bus to Modbus TCP Server up to 160 slaves connected to M Bus Order Code HD67044M 250 Gateway M Bus to Modbus TCP Server up to 250 slaves connected to M Bus ACCESSORIES Order Code AC34107 Null Modem Cable Fem Fem DSub 9 Pin 1 5 m Order Code AC34114 Null Modem Cable Fem Fem DSub 9
2. HD67507 Gateway Modbus TCP Server to RTU Master www adfweb com product HD67507 HD67510 Gateway Modbus TCP Client to RTU Slave www adfweb com product HD67510 ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31
3. Modbus Re Scale it is necessary to insert the value of Modbus Register that contains the value of measure scale If the scale is not necessary you have to insert the number O in this field It is possible to insert from Modbus Register 1 to 60000 In the field Storage Number if it is necessary it is possible to insert the value of storage counter of that variable With this field the slave can indicate and transmit various stored counter states or historical values in the order in which they occur Inthe field Tariff if it is necessary it is possible to insert the value of the tariff of that variable The Tariff is used for indicates from which device the data come Inthe field VIFE it is possible to select a sub type of Type of Data cancet ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 12 of 27 Industrial Electronic Devices If the field Use Five Modbus Register and the Type of Data is Time Point it is possible to read the information of Year Month Day Hour Minutes on five consecutive Modbus registers without decoding the data if not selected the values are the same of the reply of the slave device so coded with a determinate structure You have to insert the first Modbus Register If the field Fro
4. Pin 5 m Order Code AC34001 Rail DIN Power Supply 220 240V AC 50 60Hz 12 V AC Order Code AC34002 Rail DIN Power Supply 110V AC 50 60Hz 12 V AC ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 27 of 27 Industrial Electronic Devices WARRANTIES AND TECHNICAL SUPPORT For fast and easy technical support for your ADFweb com SRL products consult our internet support at www adfweb com Otherwise contact us at the address support adfweb com RETURN POLICY If while using your product you have any problem and you wish to exchange or repair it please do the following 1 Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem 2 Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or exchanged and returned within three weeks If the product is no longer under warranty you will receive a repair estimate PRODUCTS AND RELATED DOCUMENTS Part Description URL HD67120 Converter Ethernet to RS232 RS485 www adfweb com product HD67120 HD67119 Converter USB 2 0 to RS485 Isolated www adfweb com product HD67119
5. _ External Temperature C _ Pressure bar _Averaging Duration _Actuality Duration _ Type of data in VIFE _ Time Point _VIF is in ASCII _ Unit for H C A _ Fabrication No _ Enhaced Identification _ Bus Address ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices VIFE __ Not Selected _ Credit of the nominal local legal currency units _ Debit of the nominal local legal currency units _ Access Number transmission count _ Medium as in fixed header _ Manufacturer as in fixed header _ Parameter set identification _ Model Version _ Hardware Version _ Firmware Version _ Software Version _ Customer Location __ Customer _ Access Code User _ Access Code Operator _ Access Code System Operator _ Access Code Developer _ Password _ Error flags binary _ Error mask _ Digital Output binary _ Digital Input binary _ Baudrate Baud _ response delay time bittimes _ Retry _ First storage for cyclic storage _ Last storage for cyclic storage _ Size of storage block _ Storage interval sec s day s __ Storage interval month s __ Storage interval year s _ Duration since last readout sec s day s _ Start date time of tariff _ Duration of tariff nn 01 11 min to day _ Period of tariff sec s to day s ADFweb com Srl IT31010 Mareno Treviso User Manual M Bus from to Modbus TCP Ser
6. in Integer Identification Num not checked None Type 1 1000 0x1234 1000 0x5678 1001 0x5678 1001 0x1234 Identification Number Secondary Address 12345678 Address Register 1000 Convert BCD in Integer Identification Num checked None Type 1 1000 OxOOBC 1000 0x614E 1001 0x614E 1001 0x00BC ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 20 of 27 Aib Industrial Electronic Devices To know the meaning of value read in the Modbus Re Scale field you must follow this table x Value read in Modbus Re Scale Description Range Coding Range Energy 0e Wh 0 001 Wh to 10000 Wh Energy 10 J 0 001 kJ to 10000 kJ Volume 10 m 0 001 I to 10000 Mass oe kg 0 001 kg to 10000 kg x 0 Seconds F x 1 Minutes Cus Ua x 2 Hours x 3 Days Operating Time coded like On Time Power 19 W 0 001 W to 10000 W Power 10 J h 0 001 kJ h to 10000 kJ h Volume Flow 10 78 m h 0 001 I h to 10000 I h Volume Flow Ext io 2 m min 0 0001 l min to 1000 l min Volume Flow Ext io m s 0 001 ml s to 10000 ml s Mass Flow 10 7 kg h 0 001 kg h to 10000 kg h Flow Temperature 10 oC 0 001 C to 1 C Return Temperature 10 oC 0 001 C to 1 C Temperature Difference 10 7 K 1 mK
7. 1 100 INIT Waiting FIRMWARE Waiting PROJECT Waiting Figure 6 Update Device windows ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 23 of 27 Industrial Electronic Devices 3 Note L HD67044M xxx device a Warning If the Fig 20 appears when you try to do the Update before require assistance try these points Check if the serial COM port selected is the correct one When you install a new version of the software it is better if the first time you do the update of the Firmware in the Ver 1 100 Check if the serial is connected between the PC and the device _ Try to repeat the operations for the updating SW67044 Serial Update If you are using a dongle try with a native COM port or change the dongle l Try with another PC Sete FIRMWARE PROTECTION A Warning PROJECT PROTECTION With all codes of HD67044M you have to use the software SW67044 www adfweb com download filefold SW67044 zip Figure 7 Protection window ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 i User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 24 of 27 Industrial Electronic Devices CHARACTERISTICS OF THE CABLE Rs232 The con
8. C and 18 35V DC The consumption depends to the code of the device For more details see the two tables below User Manual Document code M M Bus from to Modbus TCP Server N67044M_ENG Revision 1 030 Page 6 of 27 VAC N VDC Vmin Vmax Vmin Vmax 15V 21V 18V 35V Consumption at 24V DC Device No Load W VA Full Load W VA HD67044 HD67044 40 HD67044 80 HD67044 160 HD67044 250 4 5 3 5 14 30 This value is with all the Slave M Bus devices of the code 20 40 80 160 250 connected to the line Caution Not reverse the polarity power ADFweb com Srl IT31010 Mareno Treviso HD67044 xxx INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 7 of 27 Industrial Electronic Devices SET COMMUNICATION PARAMETERS Configurable Parameters Baud Rate Parity Fixed Parameters 1 Bit Start 8 Bit Data 1 Bit Stop The Baud Rate and the Parity of M Bus are configurable with the software CONFIGURATION You need Compositor SW67044 software on your PC in order to perform the following Define the parameter of Modbus TCP line Define the parameter of M Bus line Define which Modbus register contain the M Bus information Update the device 44 4 FUNCTION MODES For the device HD67044M i
9. D to makes the requests and then insert the Primary Address from 1 to 250 or the Secondary Address from 0 to 99999999 of M Bus device in the field ID Node M Bus In the field Description it is possible to write a short description of the node In the field Node State it is possible to insert an address Modbus that contain the Status of the M Bus device If you don t need to know this put this register at 0 In the field Identification Number it is possible to insert an address Modbus that contain the Identification Number of the M Bus device You have to read two consecutive registers for knowing the value If you don t need to know this put this register at 0 If the field Convert BCD in Integer Identification Num is checked the gateway converts the Identification Number that is normally expressed in BCD in a Integer In the field Swap Identification Num it is possible to select the swap mode of the Identification Number If swap isn t necessary you have to select None otherwise see the section Swap Identification page 20 of this document for select the swap mode If the field Send SND_NKE is checked the Gateway send the SND_NKE frame to start the communication In the field Send Reset App Is checked the gateway send the Application Reset command to the slave In the field Variables List it is possible to select which type of variables def
10. D67053M Gateway M Bus Concentrator www adfweb com Product HD67054M Gateway M Bus Slave Modbus RTU master www adfweb com Product HD67059M 232 Do you need to choose a device do you want help Ask it to the following link www adfweb com Cmd helpme www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices INDEX UPDATED DOCUMENTATION REVISION LIST WARNING TRADEMARKS INDEX CONNECTION SCHEME CHARACTERISTICS POWER SUPPLY SET COMMUNICATION PARAMETERS CONFIGURATION FUNCTION MODES USE OF COMPOSITOR SW67044 NEW PROJECT OPEN PROJECT SET COMMUNICATION M BUS UPDATE DEVICE CHARACTERISTICS OF THE CABLE MECHANICAL DIMENSIONS ORDER CODES ACCESSORIES WARRANTIES AND TECHNICAL SUPPORT RETURN POLICY PRODUCTS AND RELATED DOCUMENTS ADFweb com Srl IT31010 Mareno Treviso Page WO WMAOANNNAUWNNNNN User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 2 of 27 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is gt Updated gt Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Document Code go to web page www adfweb com download and search for the corresponding code on the page Click on the proper Do
11. Gateway In the field Subnet Mask insert the Subnet Mask k92 jes Jo Ifthe field Gateway is checked it is possible to insert in the field under the IP Address of the gateway used for going out to the net TCP Port 502 Inthe field TCP Port insert the number of the port used for communicate 4 M Bus The means of the fields for M Bus are Sa IE 38400 m Inthe field Baudrate the velocity of the M Bus line in use is defined Parity In the field Parity the parity of the M Bus line is defined If the field M Bus Poll on request is checked the Gateway makes the request only if a Modbus register is requested otherwise if Cyclic request is checked the Gateway makes M Bus Poll on request the request in M bus network each time the time defined under passes Cyclic request In the field Delay insert a time expressed in seconds This time is used for the Cyclic f request Delay s J OK X Cancel Figure 4 Set Communication window ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices M BUS By Pressing the M Bus button from the main window for SW67044 SECTION NODES In the section Nodes it is possible to create the nodes of M Bus line In order to create a new node it is necessary to select which address use selecting Primary ID or Secondary I
12. M iuit the node or the variable and then press the DELETE ITEM M Bus network ID 10534069 Integral button VAR Fabrication Number VAR Energy Wh UOSOTO VAR Volume m3 UOSOTO VAR Volume Flow m3 h UOSOTO VAR Flow Temperaure C UOSOTO IVAR Return Temperature C VAR Temperature Difference k UOSOTO VAR Operating Time hours UOSOTO VAR Operating Time days UOSOTO VAR Time Point time date UOSOTO VAR Volume m3 U1SOTO VAR Volume m3 U2SOTO VAR Firmware Version UOSOTO VAR Software Version UOSOTO ID 28456571 Hall ID 3 First Floor DELETE ITEM Nodes Variables ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 16 of 27 Industrial Electronic Devices Possible choices for the fields used to create a variable Type of Data Function Field _ Energy Wh _ Instantaneous Value _Energy J _Minimum Value _ Volume m Maximum Value _ Mass Kg _ Value During Error State _ On Time _ Operating Time _ Power W Dimension bit _ Power J h _8 _ Volume Flow m h _16 _Volume Flow Ext m min _ 24 _Volume Flow Ext m s _ 32 _ Mass Flow Kg h _ 32 real _ Flow Temperature C _ 48 Return Temperature C _ 64 _ Temperature Difference K _ Variable Length
13. ars in the left side of the window In order to modify a created node it is necessary to select the desired node change the wrong items and then press the MODIFY NODE button ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 11 of 27 Industrial Electronic Devices SECTION VARIABLES By TYPE Selecting the desired node it is possible to add a variable In order to create a new variable it is necessary to fill these items VAR Operating Time days UOSOTO VAR Time Point time date UOSOTO By Preble Vaat gt To use the created variable the field Enable Variable a oad a ea i must be checked If you have created a variable but for the VAR Firmware Version U0SOTO eee k P x VAR Software Version UOSOTO TA G moment it is unused it is possible to uncheck the field E ARGETA B Function Field SSS A Enable Variable without delete it Ekin 1 Frot Hoor Dimension bit 32 i H i i i i i VAR POSEANO S0 TD Length Variable Len g In the field Description it is possible to write a VAR Energy U0 S1 TO a E E description of the variable it isn t a necessary information VA ona pede 5 n E 2 ys odbus Register it helps the readability of the tree of network VAR Tim
14. cument Code and download the updates To obtain the updated documentation for the product that you own note the Document Code Abbreviated written Doc Code on the label on the product and download the updated from our web site www adfweb com download REVISION LIST Revision Date Author Chapter Description 1 010 25 03 2010 FI All New software version 1 200 1 020 30 03 2010 Ft All Revision 1 021 22 10 2010 FI All Revision 1 030 04 03 2011 FI All Software changed v1 300 WARNING ADFweb com reserves the right to change information in this manual about our product without warning ADFweb com is not responsible for any error this manual may contain TRADEMARKS All trademarks mentioned in this document belong to their respective owners INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices CONNECTION SCHEME Order Code HD67044M User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 3 of 27 Connector4 Ethernet Port RJ45 Plug Connectors3 Port RS232 D SUB9 Male PIN2 RX PIN3 TX PINS Gnd_232 Green Used for Link Ethernet OO OOOGOOBOOO000 Programmation Port 18 VAC M Bus 18 30 VDC Connector o connect the device to the COM port of a PC in order to set it you have to use the programming cable AC34107 or a cable made as showed here RS232 Connector Ethern
15. e Point UO S8 TO io The field Type of Data is used to select the unit of pao aetna measure VAR Volume U0 S9 TO Tariff 5 In the field VIF ASCII String insert the string of VIF It TEE Vire Not Seleded 1s is possible to use this field only if the Type of Data is VIF VAR Volume Flow UO SO TO Time Point i i M VAR Power U0 SO TO E Use five Modbus Register IS In ASCII 4 VAR Flow Temperature UO SO TO g 3 ie In the field Function Field it is necessary to select the ile eae e EE a type of data VAR Time Point UO S17 TO j pi Paai i VAR Time Point UO S32 TO Ell Front BGDto Integer The field Dimension is used to select the dimension of UAR Enara BORE TS iin S AE the variable 8 16 24 32 32 real 48 64 bit Variable VAR Energy UO S32 TO Ist MODIFY VARIABLE Length VAR ELOA ES TAJER In the field Length Variable Len insert the length of VAR Energy UO 533 TO Ist m VAR Time Point UO S34 TO the data in the case of the dimension is Variable Length VAR Energy UO S34 TO Min In the field Unit if it is necessary it is possible to select ey acon the unit of that variable The Unit is used for indicates from which device the data come Inthe field Modbus Register it is necessary to insert the value of Modbus Register that contains the data of the M Bus device It is possible to insert from Modbus Register 1 to 60000 Inthe field
16. e value of measure scale If the scale is not necessary you have to insert the number O in this field It is possible to insert from Modbus Register 1 to 60000 K cancer If the field Use Five Modbus Register and the Type of Data is Time Point it is possible to read the information of Year Month Day Hour Minutes on five consecutive Modbus registers without decoding the data if not selected the values are the same of the reply of the slave device so coded with a determinate structure page 22 for more information You have to insert the first Modbus Register If the field From BCD to Integer is checked the Gateway converts the BCD value of variable in Integer format This happens only if the variable is in BCD format if it isn t nothing changes If the field SWAP is checked the byte of data of that variable are swapped Example from 0x01020304 to 0x04030201 In the field Position insert the number of the variable that you want on Modbus ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices Example 0x68 Start Byte OxBD L Fied OxBD L Field 0x68 Start Byte 0x08 C Field 0x02 A Field 0x72 CI Field 0x71 Identification Number Byte 4of4 0x65 Identification Number Byte 30f4 0x45 4 Identification Number Byte 20f4 0x28 Identification N
17. et OV Ground V Positive wire Connector2 When receive Unpolarized A M Bus reply Yes Jumper M Bus Boot Mode No Jumper Normal Mode Figure 1 Connection scheme for HD67044M ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 4 of 27 Industrial Electronic Devices X Change state when receive Order Code HD67044M 40 a Modbus TCP request Order Code HD67044M 80 ji Connector4 Connector3 Order Code HD67044M 160 Ethernet Port Port RS232 D SUB9 Male Order Code HD67044M 250 RJ45 Plug Led3 Green Link Ethernet PINS Gnd_232 COD QPQOOODDODOOQQO sed for Programmation Port 18 VAC M Bus 18 30 VDC Connector To connect the device to the COM port of a PC in order to set it you have to use the programming cable AC34107 or a cable made as showed here Ethernet RS232 Port CABLE Side B FEM OV Ground V Positive wire V AC min 15V max 21V V DC min 18V max 35V Ne Connector2 Unpolarized M Bus Yes Jumper Boot Mode No Jumper Normal Mode Figure 2 Connection scheme for HD67044M xxx ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 5 of 27 Ind
18. evice configuration can also be imported or exported To clone the configurations of a Programmable M Bus to Modbus TCP Server Gateway in order to configure another device in the same manner it is necessary to maintain the folder and all its contents To clone a project in order to obtain a different version of the project it is sufficient to duplicate the project folder with another name and open the new folder with the button Open Project When a new project is created or an existent project is open it will be possible to access the various configuration sections of the software e Set Communication e M Bus e Update Device ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 9 of 27 Industrial Electronic Devices SET COMMUNICATION This section define the fundamental communication parameters of two Buses Modbus and M Bus SET COMMUNICATIO By Pressing the Set Communication button from the main window for SW67044 Fig 3 the Ethernet window Set Communication appears Fig 4 FRIN The window is divided in two sections one for the Modbus TCP Ethernet and the other for the M Bus l oz fxss e lps SubNet Mask The means of the fields for Ethernet are ass f2ss_ f2s5_ fo Inthe field IP Address insert the IP address of the device El
19. ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 1 of 27 Industrial Electronic Devices User Manual Revision 1 030 English Gateway M Bus from to Modbus TCP Server to connect a Modbus TCP Client Order Code HD67044M HD67044M 40 HD67044M 80 HD67044M 160 HD67044M 250 for Website information www adfweb com Product HD67044M for Price information www adfweb com Price HD67044M www adfweb com Price HD67044M 40 www adfweb com Price HD67044M 80 www adfweb com Price HD67044M 160 Similiar www adfweb com Price HD67044M 250 Benefits and Main Features Very easy to configure Up to 250 standard M Bus devices connected to the Gateway Power Supply 15 21V AC or 18 35V DC Industrial temperature range 30 C 70 C 22 F 158 F ADFweb com Srl IT31010 Mareno Treviso INFO Cen E J HD67044M HD67044M xxx For other M Bus products see also the following link Converter M Bus to www adfweb com Product HD67021 RS232 www adfweb com Product HD67022 RS485 www adfweb com Product HD67030 Ethernet Analyzer amp Scanner M Bus www adfweb com Product HD67031 Extender and Repeater M Bus www adfweb com Product HD67032 Gateway M Bus Modbus RTU www adfweb com Product HD67029M 232 on RS232 www adfweb com Product HD67029M 485 on RS485 Gateway M Bus PROFIBUS www adfweb com Product H
20. inition to use If is selected By Type it is necessary to fill all fields in the section User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 10 of 27 Fig 3 the window M Bus Network appears Fig 5 M Bus Network Description Integral E4 ID 10534069 Integral VAR Fabrication Number Nodes D Primary ID Secondary ID VAR Energy Wh UOSOTO ID Node M Bus 10534069 VAR Volume m3 UOSOTO VAR Volume Flow m3 h UOSOTO VAR Flow Temperaure C UOSOTO Node State 97 Identification Number 98 Variables VAR Return Temperature C UOSOTO VAR Temperature Difference k UOSOTO VAR Operating Time hours UOSOTO VAR Operating Time days UOSOTO VAR Time Point time date UOSOTO VAR Volume m3 U1SOTO VAR Volume m3 U2SOTO VAR Firmware Version UOSOTO VAR Software Version UOSOTO ID 28456571 Hall ID 3 First Floor E Convert BCD in Integer Identification Num Swap Identification Num Type 1 X E Send SND_NKE E Send Reset App By Position z Valiables List MODIFY NODE Delete Items X CANCEL Figure 5 M Bus Network window Variables with the correct values otherwise if By Position is selected you can insert the progressive number of the variable that you need page 14 for more information After that pressing the ADD NODE button a new node appe
21. m BCD to Integer is checked the Gateway converts the BCD value of variable in Integer format This happens only if the variable is in BCD format if it isn t nothing changes If the field Convert in Float is checked the Gateway converts the data into Float type Every variable occupies two consecutive Modbus Registers and the first one is the one defined in Modbus Register In this case the float value is multiplied by the Modbus Re Scale automatically Having completed this fields to add the variable the button ADD VARIABLE must be pressed In order to modify a created variable it is necessary to select the desired variable change the wrong items and then press the MODIFY VARIABLE button ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices SECTION VARIABLES BY POSITION Selecting the desired node it is possible to add a variable In order to create a new variable it is necessary to fill these items To use the created variable the field Enable Variable must be checked If you have created a variable but for the moment it is unused it is possible to uncheck the field Enable Variable without delete it In the field Description it is possible to write a description of the variable it isn t a necessary information it helps the readability of the tree of network User Manual M Bus from to Modbus TCP Ser
22. mulation of abs value only if negative contributions upper lower limit value of exceeds of lower upper limit Date time of begin end of first last lower upper limit exceed ADFweb com Srl IT31010 Mareno Treviso User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 18 of 27 Duration of limit exceed Duration of first last Date time of first last begin end Multiplicative currection factor Additive correction constant unit of VIF offset Moltiplicative correction factor 10 3 future value next VIFE s and data of this block are manufacturer specific None Too many DIFE s Storage number not implemented Unit number not implemented Tariff number not implemented Function not implemented Data class not implemented Data size not implemented Too many VIFE s Illegal VIF Group Illegal VIF Exponent VIF DIF mismatch Unimplemented action No data available undefined value Data overflow Data underflow Data error Premature end of record INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 19 of 27 Industrial Electronic Devices Swap Identification This field is used for select the Swap mode of Identification Number At the moment there are these possibilities None Type l Examples Identification Number Secondary Address 12345678 Address Register 1000 Convert BCD
23. nection from RS232 socket to a serial port example one from a personal computer must be made with a NULL MODEM cable a serial cable where the pins 2 and 3 are crossed It is recommended that the RS232C Cable not exceed 15 meters NULL MODEM CABLING si N N m 0 sj o in E gt CABLE CABLE Side A Side B FEM FEM Figure 8 Null modem cabling M Bus A two wire standard telephone cable JYStY N 2 0 8 mm is used as the transmission medium for the M Bus The maximum distance between a slave and the repeater is 350m this length corresponds to a cable resistance of up 299 This distance applies for the standard configuration having Baud rates between 300 and 9600 Baud and a maximum of 250 slaves The maximum distance can be increased by limiting the Baud rate and using fewer slaves but the bus voltage in the space state must at no point in a segment fall below 12V because of the remote powering of the slaves In the standard configuration the total cable length should not exceed 1000m in order to meet the requirement of a maximum cable capacitance of 180nF Taken from M Bus specifics ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices MECHANICAL DIMENSIONS 000000000 0090004 95 mm 3 74 inch 4 17 inch 2 36 inch Housing PVC Weight 200g Approx Figure 9 Mechanical dimensions scheme for HD67044M 95 mm 3 74 inch
24. r Industrial Electronic Devices UPDATE DEVICE Section Update device Fig 6 In order to load the parameters or update the firmware in the gateway follow these instructions Turn off the Device Connect the Null Modem Cable form your PC to the Gateway Insert the Boot Jumper For more info see Fig 1 Select the COM port and press the Connect button Turn on the device Check the BOOT Led It must blink quickly For more info see Fig 1 Press the Next button Select which operations you want to do You can select only Firmware only Project or both of them Press the Execute update firmware button to start the upload When all the operations are OK turn off the device Disconnect the Boot jumper Disconnect the RS232 Cable Turn on the device At this point the configuration firmware on the device is correctly updated Document code MN67044M_ENG Revision 1 030 Page 22 of 27 Follow this step to update the HD67044 from RS232 1 Turn OFF the Device 2 Insert the Boot Jumper see the manual 3 Select the COM port and press the connect button com Connect 4 Turn ON the Device 5 Check the BOOT led It must blink quickly X Cancel Next I gt Update Device Options wt Firmware wt Read Firmware when finish ff Project wt Read Project when finish Execute update firmware Ver
25. t is possible to update the microprocessor program Therefore there are two functions to select from the boot jumper NORMAL MODE factory setting without BOOT jumper with this setting the HD67044M is able to function as an adapter M Bus to Ethernet BOOT MODE with BOOT jumper the boot mode is activated when the HD67044M is turned on Eventual program updates are available on the site www adfweb com When the run LED blinks at frequency of about 1 second the device functions in Normal Mode otherwise if the run LED blinks more quickly the device is in Boot Mode ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 8 of 27 Industrial Electronic Devices USE OF COMPOSITOR SW67044 To configure the Gateway use the available software that runs ADFweb com Compositor SWE 1044_M with Windows called SW67044 It is downloadable on the site www adfweb com and its operation is described in this document Step 1 4 New project Ay Open project When launching the SW67044 the right window appears Fig 3 Step 2 Set Communication Step 3 l M Bus Step 4 ET Update Device www ADFweb com Figure 3 Main window for SW67044 NEW PROJECT OPEN PROJECT The New Project button creates the folder which contains the entire device configuration A d
26. to 1000 mK External Temperature 10 oC 0 001 C to 1 C Pressure 10 3 bar 1 mbar to 1000 mbar Averaging Duration coded like On Time Actuality Duration coded like On Time x 0 Date Data type G Tineret x 1 Time amp Date Data o F Unit for H C A dimensionless ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 21 of 27 Industrial Electronic Devices Data type F 96 Bye oi 913 pi 911 94 o9 98 98 9 921 290 919 918 gly pile 931 930 9 9 pyr aa 926 925 974 Min 0 59 Hour 0 23 Day 1 31 Month 1 12 Year 0 99 Ti Summer Time 0 Reserved 0 Data type G N E E 915 oi 913 gE 911 94 99 98 Day 1 31 Month 1 12 Year 0 99 For example if you have defined Type of Data Energy J Function Field Instantaneous Value Dimension 32 bit Modbus Register 150 Register 151 declared implicitly because the dimension is 32 bit Modbus Re Scale 152 After the request in Modbus register 150 you read 0x0004 in 151 you read 0x5678 and in register 152 is write Ox0006 The value obtained is 284280 x10 J ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Serve
27. umber Byte 10f4 0x4D Manufacturer Byte 20 Ox6A Manufacturer Byte 1of2 0x81 Version 0x04 Medium Ox3E Access Number 0x00 Signature Byte 2of2 0x00 Signature Byte 1of2 0x04 DIF 0x79 VIF Identification 0x00 Data Byte 40f4 0x00 Data Byte 30f4 0x00 Data Byte 20f4 0x00 Data Byte 1of4 0x04 DIF 0x06 VIF Energy 0x00 Data Byte 40f4 0x00 Data Byte 30f4 0x00 Data Byte 20f4 0x00 Data Byte 10f4 0x44 DIF 0x06 VIF Energy 0x00 Data Byte 40f4 0x00 Data Byte 30f4 0x00 Data Byte 20f4 0x00 Data Byte 10f4 A Other Variables 0x55 Check Sum 0x16 Stop Byte User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Identification Number or Secondary Address putted in the selected register if Identification Number is checked Fixed Data Header First Variable O Second Variable Third Variable G ADFweb com Srl IT31010 Mareno Treviso Node State is checked Status of the meter putted in the selected register if Revision 1 030 Page 14 of 27 To be use in the Position field INFO www adfweb com Phone 39 0438 30 91 31 ily User Manual M Bus from to Modbus TCP Server Document code MN67044M_ENG Revision 1 030 Page 15 of 27 Industrial Electronic Devices SECTION DELETE ITEMS If it is necessary to delete a node or a variable you have to select i
28. ustrial Electronic Devices CHARACTERISTICS The HD67044M is a Gateway M Bus to Modbus TCP Server It allows the following characteristics Baud Rate and Parity changeable with software Mountable on Rail DIN Power Supply 15 21V AC or 18 35V DC Temperature range 30 C to 70 C 4 4 4 At the Adapters can be connected up to 250 standard M Bus devices This number depends of the code expressed by the xxx number HD67044 support up to 20 M Bus devices HD67044 40 support up to 40 M Bus devices HD67044 80 support up to 80 M Bus devices HD67044 160 support up to 160 M Bus devices HD67044 250 support up to 250 M Bus devices 4 4 4 In the case of HD67044 160 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet back A plate To avoid obstructions to the airflow around the unit it is recommended to not cover the paths of air In the case of HD67044 250 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet back plate These units have a fan in the top of the enclosure To avoid obstructions to the airflow around the unit it is recommended to not cover the paths of air Take care to not cover the fan It is recommended to put the device into a ventilated cabinet ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices POWER SUPPLY The devices can be powered at 15 21V A
29. ver Document code MN67044M_ENG M Bus Network ID 10534069 Integral Fabrication Number Energy Wh UOSOTO Volume m3 UOSOTO Volume Flow m3 h UOSOTO Flow Temperaure C UOSOTO Return Temperature C UOSOTO Temperature Difference k UOSOTO Operating Time hours UOSOTO Operating Time days UOSOTO Time Point time date UOSOTO Volume m3 U1SOTO Volume m3 U2SOTO Firmware Version UOSOTO Revision 1 030 Page 13 of 27 V Enable Variable Nodes Description Energy Wh UOSOTO Dimension bit 32 Length Variable Len o Modbus Register 302 Variables Modbus Re Scale 0 Time Point E Use five Modbus Register YY Jo MM 0 HH 0 MM 0 Delete Items El From BCD to Integer The field Dimension is used to select the dimension of i the variable 8 16 24 32 32 real 48 64 bit Variable iao oasen wal 50n vosoTo F Convert in Float Length ID 3 First Floor Position 2 In the field Length Variable Len insert the length of the data in the case of the dimension is Variable Length In the field Modbus Register it is necessary to insert the value of Modbus Register that contains the data of the M Bus device It is possible to insert from Modbus Register 1 to 60000 Inthe field Modbus Re Scale it is necessary to insert the value of Modbus Register that contains th
30. ver Document code MN67044M_ENG Revision 1 030 Page 17 of 27 Period of tariff months s Period of tariff year s dimensionless no VIF Volts Ampere Reset counter Comulation counter Control signal Day of week Week number Time point of day change State of parameter activation Special supplier information Duration since last comulation hour s year s Operation time battery hour s year s Date and time of battery change Energy MWh Energy GJ Volume Mass Volume 0 1 feet 3 Volume 0 1 american gallon Volume 1 american gallon Volume flow 0 001 american gallon min Volume flow 1 american gallon min Volume flow 1 american gallon h Power MW Power GJ h Flow Temperature Return Temperature Temperature Difference External Temperature Cold Warm Temperature Limit F Cold Worm Temperature Limit C Cumul count max power INFO www adfweb com Phone 39 0438 30 91 31 Industrial Electronic Devices per second per minute per hour per day per week per month per year per revolution measurement increment per input pulse on input channel increment per output pulse on output channel per liter per m 3 per kg per K Kelvin per kWh per GJ per kW per K 1 Kelvin liter per V Volt per A Ampere multiplied by sek multiplied by sek V multiplied by sek A start date time of VIF contains uncorrected unit instead of corrected unit Accumulation only if positive contributions Accu