Contents
1. 16 7 Appendix 3 3300 Operation Quick Reference Guide Muting the Internal Buzzer Press Mute Buzzer Entering Access Level 2 Enter the 5 digit user code 1 3 4 4 2 The Level 2 Accessed indicator lights Returning to Access Level 1 Press button 4 the required number of times Silencing the Alarms From access level 2 press Silence Alarms A further activation will re sound the alarms Sounding the Alarms From access level 2 press Sound Alarms Resetting the Panel Determine the cause of the alarm before resetting the panel From access level 2 press Silence Alarms then press Reset Panel Testing the Indicators and Internal Buzzer From access level 2 press button 1 SECH 93 531 79 Issue 0 Page 23 of 24 O Protec Fire Detection PLC 2007 Protec Fire Detection PLC Protec House Churchill Way Nelson Lancashire BB9 6RT Telephone 44 0 1282 717171 Fax 44 0 1282 717273 Web www protec co uk Email sales protec co uk
2. 7 Protec 3300 NON ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Zone Location 3300 Fire Alarm Control Panel ENS4 Parts 2 and 4 1997 Fire Zones ed EI E 2 4 Fi ri O O O Mute e e 2 Fault Disablement Test Zones Buzzer Disablements Sil Aare e e Oo O 2 Fire Link Level 2 General Output General Alarm ire Operated Delay Fi Disablement Outputs Link Faults Sound Alarms d o o Oo O O O Genera System Alarm Power F Au ro x Repeat Fault Fault 24V Panel Fi aul Fault Fault Accessed Test Protec Fire Detection PLC Protec House Churchill Way Nelson Lancashire BB9 6RT Telephone 44 0 1282 717171 Fax 44 0 1282 717273 Web www protec co uk Email sales protec co uk vi Protec GE Document Revision Details Issue Modification Detail Author Date 0 Document Creation NH 12 02 07 DEE 93 531 79 Issue 0 Page 2 of 24 Protec Fire Detection PLC 2007 7 Protec Table of Contents 10 INTRODUCTION ae 5 2 0 USER RESPONSIBILITIES visse eek eden 6 2 1 Requirements of the Appointed Responsible Person 6 3 0 ROUTINE TESTING OF THE SYSTEM nrrrnnevnnnnvnnnnnnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnr 7 31 Dally Bon EE 7 CAELI IET eene erg geseid ae wen Saini dentate fala p badet bias ie 7 BS MODUS RE 7 3 4 Quarterly TEE 7 e WE el 8 36 5 Yeany TOST 8 4 0 ACCESS LEVELS AN EXPL
3. 93 531 79 Issue 0 Page 16 of 24 Protec Fire Detection PLC 2007 7 Protec 12 2 To Disable Alarm Outputs The 3300 can have alarm circuits 1 and 2 and or alarm circuits 3 and 4 disabled When an alarm circuit is disabled faults and activations on that circuit are inhibited 1 From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key switch depending on the model purchased The Level 2 Accessed indicator will illuminate 2 Using button 2 scroll to the Alarm Outputs indication Any current alarm disablements will be displayed on row 1 of the display on zones 1 and 2 Accept this option by pressing button 3 3 The Alarm Outputs indicator will flash showing this option has been accepted 4 Highlight the alarm circuit pair to be disabled by pressing button 2 e Highlight zone 1 indicator on row 2 if alarm circuits 1 and 2 are to be disabled e Highlight zone 2 indicator on row 2 if alarm circuits 3 and 4 are to be disabled 5 Press button 1 to show that it is to be disabled not disabled The relevant row 1 indicator will be illuminated if the alarm circuit is disabled 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the disablement set up and return to access level 2 8 The yellow General Disablement indicator will be illuminated steady as will the yellow Alarm Outputs indicator 12 3 To Disable Delays It is possible for the authorised
4. BS5839 Pt 1 2002 states that the owner of the fire alarm system must appoint a single named person to supervise all matters regarding the fire alarm system Below is a brief summary of the responsibilities expected of the appointed person Important Note It is advised that a full copy of BS5839 Pt 1 2002 is obtained and thoroughly read and understood 2 1 Requirements of the Appointed Responsible Person e Ensure the that the fire alarm equipment is checked at least once every 24 hours to ensure there are no faults on the system Report any faults to the site maintenance manager e Ensure that arrangements are in place for correct testing of the fire alarm system as specified in BS5839 Pt 1 2002 Section 6 Summarised in section 3 0 of this document e Ensure that the system event log is kept up to date and is available for inspection by any authorised person when required An example log book is included in appendix 15 0 of this document e Ensure that all occupants of the protected premises are trained how to use the system properly and that they are aware of what action to take in the event of an alarm e Ensure that false alarms are minimised e Ensure all detectors and manual call points remain un obstructed Detectors must have at least 500mm clear space preserved in all directions around them e Ensure that six spare manual call point frangible elements glass fronts and appropriate fitting tools are available as replacem
5. This sheet must be completed by the engineer in charge of commissioning the system It is the only record of how the system has been configured and as such should be safely stored for future reference ZONE DESCRIPTION LOCATION PROGRAMMING KE eee eee aM ELE re ae 2 ll RECH qM CONNECTION CONNECTED TO Global Fault Global Fire Class Change Remote Alarm Expansion Ports 4 93 531 79 Issue 0 Page 20 of 24 Protec Fire Detection PLC 2007 7 Protec 15 0 Appendix 2 3300 Event Log The person appointed in charge of the fire alarm system should complete the relevant section of this sheet whenever an event fire or fault occurs on the system Name of appointed responsible Gerson NEEN RENE E enne nenne Contact details of above perSoN x xraxnarannnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn Contact details of maintenance person company Fire Alarm System Event Log DATE TIME ZONE DETAILS ACTION REQUIRED COMPLETED NAME 93 531 79 Issue 0 Page 21 of 24 O Protec Fire Detection PLC 2007 7 Protec Fire Alarm System Event Log continued DATE TIME ZONE DETAILS ACTION REQUIRED COMPLETED NAME 93 531 79 Issue 0 Page 22 of 24 O Protec Fire Detection PLC 2007 7 Protec 16 0 16 1 15 2 16 3 16 4 16 5 16 6
6. Zone Fault Disablement test Indications S aH ystem System control Fault Ingicatons disablement push buttons Push buttons used for indications code entry lamp test and programming 93 531 79 Issue 0 Page 10 of 24 Protec Fire Detection PLC 2007 7 Protec 5 1 Testing the Indications Lamp Test To test the functionality of the front panel indicators 1 Ataccess level 1 enter the 5 digit user code 1 3 4 4 2 or turn the keyswitch depending on the model purchased The Level 2 accessed indicator will light 2 Press button 1 The 3300 will light each row on the display in turn and sound the internal buzzer 3 Confirm that each indicator is operational and that the buzzer can be heard clearly If a problem exists inform the site maintenance manager immediately 4 Return to access level 1 by pressing button 4 6 0 System Fire Indications The 3300 displays fire information on row 1 of the front panel display The following sections detail what each indicator means 6 1 General Fire Indicator Illuminated The 3300 has detected a fire on one of its zones or has been activated from another piece of equipment connected to its remote alarm input The building fire plan should be executed immediately 6 2 MCP Fire Indicator Illuminated A manual call point has been activated on one of the detection zones 6 3 Fire Zones 1 to 8 Flashing The 3300 has detected a fire on the relev
7. 3 4 4 2 or turn the key switch depending on the model purchased The Level 2 Accessed indicator will illuminate 2 Using button 2 scroll to the Alarm Outputs indication If the fire link is disabled the zone 4 indicator on row 1 will be illuminated Accept this option by pressing button 3 3 The Alarm Outputs indicator will flash showing this option has been accepted and any current settings in this option will be displayed on row 1 of the display on zone 4 4 Select the Disable Fire Link option by pressing button 2 until the indicator for zone 4 is illuminated 5 Press button 1 to show that the fire link is to be disabled not disabled 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the set up and return to access level 2 8 The Fire Link and General Disablement indicators will be Illuminated eme 93 531 79 Issue 0 Page 18 of 24 Protec Fire Detection PLC 2007 7 Protec 13 0 Testing Detection Zones To aid the required fire alarm test schedule to be performed the 3300 allows one zone at a time to be put into test mode In this mode upon an alarm on the test zone the 3300 activates the alarm outputs for 4 seconds then resets This allows a zone of detectors to be easily tested without having to reset the panel manually after each activation Note When a zone is in test mode the Global Fire Contacts and Fire Link if fitted are n
8. to program zone alarm delay and fire link disablements 12 1 To Disable Zones The 3300 can have one or more of its detector zones disabled When a zone is disabled faults and activations from that zone are inhibited 1 From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key switch depending on the model purchased The Level 2 Accessed indicator will illuminate 2 Press button 2 once The General Disablement indicator will illuminate steady to show the zone disablement option is selected the normal front panel display is temporarily replaced with the programming display Any current disablements will be displayed on row 1 of the display Accept the option by pressing button 3 3 The General Disablement indicator will flash showing this option has been accepted 4 Highlight the zone to be disabled by pressing button 2 until the required zone is reached 5 Press button 1 to show that the zone is to be disabled not disabled If disabled the relevant row 1 indicator will be illuminated 6 Follow the procedure above until all zones that are to be disabled have their row 1 indicators illuminated 7 Press button 3 to return to the selection menu 8 Press button 4 to accept and program the disablement set up and return to access level 2 9 The yellow General Disablement indicator will be illuminated steady as will the row 2 disablement indicator for the relevant zone s eme
9. user to override any delays zonal or fire link that may have been set up when the system was commissioned The procedure to do this is as follows 1 From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key switch depending on the model purchased The Level 2 Accessed indicator will illuminate 2 Using button 2 scroll to the Alarm Outputs indication Any current setting in this option will be displayed on row 1 of the display on zone 3 Accept this option by pressing button 3 3 The Alarm Outputs indicator will flash showing this option has been accepted 4 Select the delay override option by pressing button 2 until the row 2 indicator for zone 3 is illuminated 5 Press button 1 to show that delays are to be overridden not overridden If delays are overridden the zone 3 indicator on row 1 will be illuminated 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the set up and return to access level 2 8 The Output Delay indicator will be extinguished All delays zonal and fire link are now overridden M 93 531 79 Issue 0 Page 17 of 24 Protec Fire Detection PLC 2007 7 Protec 12 4 To Disable the Fire Link It is possible for the authorised user at access Level 2 to disable the Fire Link interface if fitted Disabling the interface inhibits Fire Link faults and activations 1 From access level 1 enter your 5 digit user code 1
10. 3 16 2 Entering EE 23 16 8 Returning to Access Level ek 23 16 4 Silencing the Aarme 23 16 5 Sounding the Alammes sss esses einen innen sirena senten tanen nennen 23 16 6 Heselting the Panel ranaun sm te edt ou oat pen a rueda tuae aee Run 23 16 7 Testing the Indicators and Internal BUzzer sisse nnne 23 CL 93 531 79 Issue 0 Page 4 of 24 Protec Fire Detection PLC 2007 7 Protec 1 0 Introduction The Protec 3300 Fire Alarm Control Panel has been designed and manufactured in the United Kingdom and complies fully with current standards dictating fire alarm system design practice EN54 parts 2 and 4 As the integrity and reliability of a fire alarm system is vital the 3300 monitors all critical paths for faults The detector and sounder wiring is constantly monitored to check it is correct and is not faulty The internal power supply regularly performs self checks to ensure it is in full working order and that the stand by batteries are in a good state Any faults detected are reported on the front panel display of the 3300 a fault output is also provided to be connected to external systems a remote monitoring centre for example to signal that the 3300 has a fault and attention is required The 3300 is also capable of distinguishing between automatic detector and manual manual call point zone activation Given this extra information the panel can
11. ANATION rrnnnvvnnnnvnnnnvnnnnnvnnnnvnnnnnnnnnnvnnnnnnnnnnvnnnnnnnnnnvnnnnnnnnnnvnnenennnr 9 4 1 Access Level 1 General User 9 42 Access Level 2 Authorised Ueerl sss seen 9 5 0 INDICATIONS AND CONTROLS renircreo inner nein eut coude eram xa n tan amu snek kndennndrennn 10 5 1 Testing the Indications Lamp Test 11 6 0 SYSTEM FIRE INDICATIONS rrnnnvnnnnvvnnnnvnnnnnvnnnnvnnnnvnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnenenr 11 6 1 General Fire Indicator Illuminated isses sese ener 11 6 2 MOP Fire Indicator Uiuminated einen innen nnne nnne tnnt 11 56 9 Fire ZONES Ee EE 11 6 4 Fire Zones 1 to 8 Illuminated Gresch 11 7 0 SYSTEM FAULT INDICATIONS eerie tete rue Rees duke Lou xxu EE Cu Eas a ome exu mae saa ne 12 Fe MEE GIUM 12 Z2 System Fa lls eee rael e Uh cane eb ier Dh envi ded dee deeg ege gedoe 12 73 Alarm Fauls ms 12 7 4 Power Supply Faute 12 Z Fre e 12 76 UX 2A TE 12 7 7 Hepeat Panel Faute 12 8 0 SYSTEM DELAYS Lu 13 90 COINCIDENCE ZONES Lunnan He xa ritene stendene nesten 13 10 0 RESPONSE TO AN ALARM nernanovnnnnvnnnnvnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnr 14 10 1 Automatic Detection SEENEN EEGENEN ae n n mue HORE Neen 14 10 2 Manual Detection SEE 14 10 3 Delayed ACUVALON EE 14 104 Silencing the AlAHINS E 14 10 5 Resetting The 3300 After An Alarm 14 10 6 New Zone I
12. ant zone This will always be accompanied by the General Fire indicator 6 4 Fire Zones 1 to 8 Illuminated Steady The 3300 has detected a fire on the relevant zone The fire has been accepted by a user pressing the Mute Buzzer button CL 93 531 79 Issue 0 Page 11 of 24 Protec Fire Detection PLC 2007 7 Protec 7 0 System Fault Indications When the 3300 has detected a fault in the critical operating path of the system it will display this on the front panel display The internal buzzer will also sound intermittently slowly The General Fault indicator will be illuminated and is always accompanied by other indicator s detailing the fault In general fault indicators flash until the fault is accepted by pressing the Mute Buzzer button the fault indicator then lights steady and the internal buzzer will be muted Further faults activate the buzzer again In the event of any fault the following action should be taken e Mute the fault by pressing the Mute Buzzer button on the panel e Note the fault down in the Log Book and take action to remedy the fault In all cases expert advice should be sought When the fault has been rectified the fault indicator will automatically extinguish The following sections give descriptions of each possible fault 7 1 Zone Faults The 3300 shows any faults on the detection zones on row 2 of the front panel display The General Fa
13. c 8 0 System Delays Delays may have been programmed in the 3300 to allow a predetermined time from a zone activation until e The alarm outputs and global fire contacts activate e The fire link activates This can be useful to allow time for the cause of the activation to be investigated by a responsible person If the cause of the activation is found to be legitimate the alarm outputs can be manually activated If the cause of the activation is found to be a false alarm the 3300 can be reset A delay time can be programmed into one or more zones The delay time set up on the 3300 applies to all zones and can be set to a maximum 10 minutes The fire link delay time is independent of the zone delay time and can be set up to a maximum of 10 minutes locally on the fire link interface The presence of a programmed delay is indicated by the Output Delay indicator being illuminated The 3300 system set up chart must be consulted to determine exactly which zones have been delayed and what the delay time is set to If the Silence Alarms button is pressed while a delay is running the alarm outputs will not be activated when the delay expires The global fire contacts however will still be activated Note Zone delays only pertain to automatic zone activations A manual activation on a zone will always override a programmed zone delay 9 0 Coincidence Zones At the time of commissioning one or more zones may have been pro
14. d failure of the normal power supply and then run in this mode for at least 1 hour e Visually inspect the stand by batteries and their connections Check that the batteries are capable of supplying the alarm sounders 3 4 Quarterly Test e Perform the monthly test recommended in 3 3 and e Ensure the system event log is up to date and all entries are correct Check that any faults noted have been rectified CL M 93 531 79 Issue 0 Page 7 of 24 Protec Fire Detection PLC 2007 vi Prote y 3 5 Annual Test e Perform the quarterly test recommended in 3 4 and e Test every detector manual call point and all auxiliary equipment for correct functionality 3 6 5 Yearly Test e Carry out a full wiring check in accordance with the testing and inspection requirements of the relevant National wiring regulations I E E regulations for the UK 93 531 79 Issue 0 Page 8 of 24 Protec Fire Detection PLC 2007 7 Protec 4 0 Access Levels An Explanation The 3300 has two access levels to allow users of different authorisation levels access to various parts of the sy
15. ents for use in the event a manual call point is activated 93 531 79 Issue 0 Page 6 of 24 Protec Fire Detection PLC 2007 7 Protec 3 0 Routine Testing of the System Recommendations for testing of the system are detailed in BS5839 Pt 1 2002 Section 6 The routine testing is briefly detailed below 3 1 Daily Inspection e Check that the Supply Present indicator is illuminated e Check for any faults on the system and report these to the site maintenance manager 3 2 Weekly Test Note During the test you may wish to temporarily place the zone to be tested into test mode e Perform an indicator test Lamp Test to check the integrity of the front panel indications and internal buzzer e Ensure no manual call points or detectors are obstructed e Operate a manual call point or detector during normal working hours to ensure the fire alarm system operates correctly e A different manual call point or detector on a different zone should be tested each week in this way all the devices on all the zones are tested e Ensure the system sounders are operational e Ensure the sounders are not operated for longer than 1 minute during testing Genuine alarms can then be distinguished by the occupants of the building 3 3 Monthly Test e Perform the weekly test recommended in 3 2 and e f an automatic generator is used as part of the mains failure back up system it should be started up once each month by simulate
16. ess level 2 The alarm outputs will be activated but the Global Fire Contacts and the Fire Link Interface WILL NOT be activated Lemmer 93 531 79 Issue 0 Page 14 of 24 O Protec Fire Detection PLC 2007 7 Protec 11 0 System Disablements Various disablements may be programmed into the 3300 by the authorised user In some situations it may be advantageous to turn off certain functions to suit specific site conditions The 3300 permits the following disablements to be made by the authorised user at access level 2 11 1 Zone Disablements Fires and faults from the disabled zone are inhibited 11 2 Alarm Disablements Activations and faults from the disabled alarm circuit are inhibited 11 8 Delay Disablement Any programmed zone or fire link delays are overridden Important Note Delays will have been programmed into the 3300 for valid reasons Please refer to the section on delays and consult the system set up record appendix 1 before making adjustments to this part of the system 11 4 Fire Link Disablement Activations and faults on the fire link output are inhibited Important Note Please refer to the section on the fire link and consult the system set up record appendix 1 before making adjustments to this critical part of the system 93 531 79 Issue 0 Page 15 of 24 Protec Fire Detection PLC 2007 7 Protec 12 0 Programming System Disablements It is possible for the authorised user at access level 2
17. grammed as coincidence zones This means that two or more of the coincidence zones must activate together before the 3300 will sound the alarms or activate the Global Fire Contacts If one coincidence zone is triggered the cause of the activation must be investigated if no action is taken within 2 minutes the 3300 will sound the alarms and activate the Global Fire contacts If the cause of the alarm is deemed to be false the 3300 should be reset The only way to determine if coincidence zones have been programmed into the system is by consulting the system set up chart appendix 1 of this document Note e A single activated coincidence zone will time out and sound the alarms after 2 minutes e Azone programmed as coincidence will be overridden by a manual call point activation on that zone Lee 93 531 79 Issue 0 Page 13 of 24 O Protec Fire Detection PLC 2007 7 Protec 10 0 Response to an Alarm 10 1 Automatic Detection If a smoke detector or heat detector operates on a zone of the 3300 this is known as an automatic operation The 3300 responds by Illuminating the General Fire indicator Flashing the relevant zone fire indicator Fast intermittent sounding of the internal buzzer Activating non disabled alarm outputs after a delay expiry if programmed Activating the Global Fire contacts Activating the Fire Link output if fitted and not disabled 10 2 Manual Detection If a Manual Call Point
18. is operated on the zone of a 3300 this is known as manual operation The 3300 responds by Illuminating the General Fire indicator Illuminating the MCP Fire indicator Flashing the relevant zone fire indicator Fast intermittent sounding of the internal buzzer Activating non disabled alarm outputs immediately Activating the Global Fire contacts Activating the Fire Link output if fitted and not disabled Overriding any zone delays that may be programmed Re sounding the alarms if the zone had previously experienced a silenced automatic activation 10 3 Delayed Activation Please see section 8 0 10 4 Silencing the Alarms The alarms and internal buzzer may be silenced by pressing Silence Alarms when in access level 2 10 5 Resetting The 3300 After An Alarm After the cause of the alarm has been determined and entered in the log by the authorised user the 3300 may be reset if required When in access level 2 press Silence Alarms then press Reset Panel The 3300 will reset any latched detectors on its zone connections Manual call points must be reset manually at the local location 10 6 New Zone Into Alarm If a new zone goes into alarm or a previously silenced zone triggered by an automatic device has a manual activation the 3300 will re activate the alarms and re sound the internal buzzer 10 7 Activating The Alarms Manually To evacuate the building press Sound Alarms when in acc
19. make decisions on the type of zone activation and take appropriate action for example a zone delay will be immediately overridden by a manual activation This manual includes a 3300 system set up sheet and a 3300 event log as appendices at the rear of the manual The system set up sheet must be completed by the commissioning engineer prior to handing the system over to the customer The system set up sheet details exactly how the system has been set up and programmed by the commissioning engineer and being the only such record should be kept in a safe place The 3300 event log must be completed by the authorised user of the system each time a 3300 event fire or fault occurs It is advisable to make copies of the blank event log to allow the log to be continued when the sheet included has been filled up Important Note There are no user serviceable parts inside the 3300 panel Any internal maintenance work MUST be carried out by a competent person trained to undertake such work A separate installation commissioning and maintenance manual is available Ce This product has been manufactured in conformance with the requirements of all applicable EU council directives 93 531 79 Issue 0 Page 5 of 24 Protec Fire Detection PLC 2007 7 Protec 2 0 User Responsibilities The registered owner of the fire alarm system has specific responsibilities regarding the installation testing and maintenance of the fire alarm system
20. nto Alarm suerte ern tn rn assu ER en eiua estu n Rune ots e ERN Renee drea ERR Rc 14 10 7 Activating The Alarms Manual 14 11 00 SYSTEM DISABLEMENTS 1ceiiiecrter crater karma nm cea ncm kann ima nam cuna cr R aan mk aU IR X Dm Pane DmAR AM ex A ac 15 11 1 Zone Ee ET 15 11 2 Alarm RRE TT 15 11 3 Delay WEE Ee 15 11 4 FireLinkDisablement ot e arve ded iaa aaae ai eaa Ria AE aaa ARAARA A 15 93 531 79 Issue 0 Page 3 of 24 Protec Fire Detection PLC 2007 7 Protec 12 0 PROGRAMMING SYSTEM DISABLEMENTS nernnnovennnvnnnnnvnnnnvnnnnnnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnr 16 12 1 JO Disable Zones orriei areire ien Eriein AREE itio sn E Oops add pL erat Eee as oda p eb ager dae Eo 16 12 2 To Disable Alarm Outputs sisse seinen nett nnn tronen ann rennene nenennnnnn 17 12 3 To HR 17 12 4 To Disable the Fire Link eese iiieese seinen EEEE EEEE nasi intra siint nna 18 13 0 TESTING DETECTION ZONES ernnnnvnnnnvnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnr 19 13 1 Programming a Zone into Test Mode 19 14 0 APPENDIX 1 3300 SYSTEM SETUP RECORD nsvnnnnvnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnr 20 15 0 APPENDIX 2 3300 EVENT LOG ertet nnt De suasana rie tea Loser uie eniin 21 16 0 APPENDIX 3 3300 OPERATION QUICK REFERENCE GUIDE eene 23 16 1 Muting the Internal Buzzer ee 2
21. ogramming a zone into test mode only one test zone at once is permitted Disablement of detector circuits Disablement of alarm circuits Disablement of any programmed delays detector and fire link Disablement of the fire link interface if fitted 93 531 79 Issue 0 Page 9 of 24 Protec Fire Detection PLC 2007 7 Protec 5 0 Indications and Controls The 3300 has a comprehensive front panel display enabling the state of the 3300 to be rapidly determined by inspection of the indications e Zone fires are displayed on row 1 of the display e Zone faults indicator flashing Zonal disablements indicator steady General Disablement indicator and zones in test mode indicator steady General Test indicator are shown on row 2 of the display e System disablements are shown on the right hand side of row 3 of the display e System faults are displayed on row 4 of the display Figure 5 0 illustrates the front panel indications Figure 5 0 3300 Front panel Indications and controls Zone Fire indications Fire Zones 0 0 Cm TIO Oo 0 0 C1 tanel 1 2 3 4 5 6 7 8 Buzzer Fault Disablement Test Zones 0 e or EODD UO XO o 9 i Disablements ce o 09000009 Supply Fire Link Level2 General Output General Alarm Present Operated Accessed Test Delay Disablement Outputs C o O Alarms General System Alarm Power Fire Aux Silenced Fault Fault Fault Supply Link 24V Fault Fault Fault
22. ot activated when the test zone goes into alarm Alarms on non test zones will prevent the 3300 resetting automatically 13 1 Programming a Zone into Test Mode 1 From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key switch depending on the model purchased The Level 2 Accessed indicator will illuminate 2 Scroll to the General Test indicator by pressing button 2 Any zones previously programmed into test mode will be displayed on line 1 of the display Accept the option by pressing button 3 3 The General Test indicator will flash to indicate this option has been accepted 4 Scroll to the detector zone to be put into test mode by pressing button 2 5 Press button 1 to set un set that zone into test mode The relevant row 1 indicator will be illuminated when the zone is in test mode 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the test set up and return to access level 2 The yellow General Test indicator will be illuminated steady showing that at least one zone has been programmed into test mode Any zones programmed into test mode will have their test indicator illuminated steady on row 2 of the display Important Note e Ensure zones are removed from test mode when testing of the system is complete Lee 93 531 79 Issue 0 Page 19 of 24 Protec Fire Detection PLC 2007 7 Protec 14 0 Appendix 1 3300 System Setup Record
23. stem The access levels and a description of functions available are given in the next sections 4 1 Access Level 1 General User Access level 1 allows the general user to view the status of the 3300 at any time Zone fire and fault states are clearly displayed as are any current system faults and disablements Full detail of the front panel display is given in the next section The following functions may be performed at access level 1 e Muting the 3300 internal buzzer e Accepting current fire and fault conditions e Entering access level 2 4 2 Access Level 2 Authorised User Access level 2 allows the authorised user access to various critical system functions To enter access level 2 from access level 1 enter the user code 1 3 4 4 2 on code entry models or turn the key on key switch models When the correct code has been entered or the key switch has been turned the Level 2 Accessed indicator will light showing that level 2 functions are available To return back to access level 1 press button 4 or return the key switch back to its normal position Note As a security measure on code entry models the 3300 will return back to access level 1 if no key activity has been detected for 2 minutes The following functions may be accessed at access level 2 Silencing an alarm condition Sounding the alarms Resetting the panel after an alarm activation Testing the front panel indications and internal buzzer Pr
24. ult indicator will be illuminated accompanied by the relevant zone indicator Pressing Mute Buzzer will mute the buzzer but WILL NOT make the zone indicator go steady 7 2 System Faults The 3300 performs many self tests to ensure the software is working correctly The fault should be cleared by pressing Silence Alarms then Reset Panel whilst in access level 2 If the fault re occurs with 3 minutes the 3300 has a microprocessor fault and the maintenance manager must be alerted 7 3 Alarm Faults A fault has been detected on one or more of the four sounder outputs One or more of the sounder circuits may no longer operate correctly 7 4 Power Supply Faults A fault has been detected in the power supply module of the 3300 This may be because the local mains supply has failed or because the internal stand by batteries or charger are faulty 7 5 Fire Link Fault A fault has been detected on the monitored fire link path This may be a wiring fault of the fire link interface fault The connection to the fire station link is no longer reliable Expert advice should be obtained immediately 7 6 Aux 24V Fault A fault has been detected with the Auxiliary 24V supply output of the panel 7 7 Repeat Panel Fault A fault has been detected on a 3300 repeat panel connected to the 3300 main panel or the wiring to the repeat panel is faulty 93 531 79 Issue 0 Page 12 of 24 Protec Fire Detection PLC 2007 7 Prote
Download Pdf Manuals
Related Search
Related Contents
SLT190 カタログ*EICT/EITCM含む(日本語版)258KB Luft-Hohlspannzylinder Air actuating cylinders Cylindres de Xantrex TC10TB User's Manual USER MANUAL - Appliances Online Spartan User Manual (web) P1 Riva2 530 670 Balanced Flue Instructions ECP-T03 - Lite 406 AF-Compact - Dallas Avionics Samsung ST45 Užívateľská príručka Copyright © All rights reserved.