Home
        Differential Pressure Field Unit User Guide
         Contents
1.                           saved  If  ENTER  is pressed while NO is being displayed the value is  NOT saved   The sensor should be at ZERO when YES is selected                              ENTER        Figure 7 1  Menu Map to Pressure Zero Setting    Rev 1210 27    AWS Wireless Differential Pressure Field Unit User Manual    7 2             a Measurement For various applications  the user may wish to display an offset value   rather than the actual value  To enter an offset  navigate to the OFFSET   Offset command  as shown in Figure 7 2  Then enter the offset to be added or  subtracted from the actual measured value       OPERATIONS SEQUENCE L NEXT      USER PROMPTED FOR    L PASSWORD                            OFFSET pewren  gt  INPUT T Jenter  gt  XXXXXX     NEXT    Figure 7 2  Menu Map to Offset Setting    7 3  Trimming the The Field Unit interface allows you to set a two point correction curve for  Measurement    the sensor  This process is often called  trimming  because the displayed  value is trimmed up or down to reflect the actual value being applied     To set a trim point  take the Field Unit offline and navigate to the TRIM  menu  as shown in Figure 7 3  and select the input to be trimmed  Then  select the point you wish to enter  After selecting the point  you will have  the option to trim the device or reset the trim  If NEW TRIM is selected   you will be prompted to enter the lower point first  Type the value and  If entering a two point trim via the NEXT and p
2.             RF ERR  SEN ERR  LOW BAT       YES                YES RF OK  RROR                 1    OPERATIONS SEQUENCE I          X                                                                 Figure 4 1  Field Unit Power UP and Operations LCD Sequences    Once      Field Unit 15 in the Operations Sequence  a user may access the  READ ONLY Sequence without a password by simply pressing the EN   TER button at any time  The Read Only Sequence  as shown in Figure 4 2   displays extra information about the current settings of the Field Unit that  are not seen during the Operations Sequence  but does not allow any  changes to be made to these settings     i                  1     OPERATIONS SEQUENCE XXXX XX UNITS YES                                 PEE 1                            MSG       ENTER RF ERR  NONE  E NO SEN ERR  i LOW BAT  j READONLY   RF OFF    NO RF             Figure 4 2  The Read Only Sequence    Rev 1210 15    AWS Wireless Differential Pressure Field Unit User Manual    4 2  Overall Configuration  Menu Map    The user must enter a four digit password to enter  the CONFIG and DIAGNSE  The FACTORY    menu is for factory use only  The default user  password is 0000  For more information on the  password see Section 4 4        4 3  Setting the Field Unit Tag  Name    A complete Field Unit Menu Map is shown in Appendix C  Below is an  overall view of the configuration menu to aid the user in setting up the  Field Unit for proper operation                  1    OPERA
3.          Load from File       Save to File     Figure 8 2  Orifice Flow    NOTE      Starred units are only available once the Density  check box has been selected        Section 8  Selecting and Configuring Operation Modes    In this mode  the user has the option of setting up volumetric or mass flow  calculations through an orifice plate  if the density units are selected and  entered mass flow calculations are available  The user must enter a differ   ential pressure value and a flow value corresponding to the pressure value   Using these two points  the PC will calculate the flow value that corre   sponds to the full scale pressure value of the Field Unit  1     FS Flow    Finally  the user also must enter a truncation point value  This information  is used to calculate flow in the units selected by the user     To set the Field Unit to this operation mode  you must go to the configura   tion menu of the Field Unit via the Software  For further instructions on  getting to the configuration menu see Section 9 2 of the Wireless Instru   mentation Manager User Manual     Once you have opened the configuration menu  select the Operation  Mode tab at the top of the menu and select Orifice Flow from the mode  menu  You should then see a menu like the one shown in Figure 8 2     Select the units that are appropriate for your application  All possible units  are listed below     Rev 1210 31       AWS Wireless Differential Pressure Field Unit User Manual    8 2  Orifice Flow  cont
4.          Percent Volume Flow may only be selected  from the Flow Units list  It does not appear in the    Flow list  Selecting Percent Volume Flow enables  the Square Root Function  See section 8 2 1 for  more information     8 2 1  Square Root Calculation    Differential Pressure Properties    9 44     Sampling Rates   Sampling Bands   Alarms    General   Range Operation Mode   Sensor Offset      Mode    Orifice Flow  v                   Differential Pressure  5 Psi   Flow  10 Cubic Feet   Sec  Full Scale Flow  Cubic Feet   Sec  Truncation Point  Cubic Feet   Sec    Flow Units     NOTE  Square root is ON                Load from File        Save to File    OK Cancel    Figure 8 3  Orifice Flow with Square  Root Calculation Enabled    32       Once engineering units have been selected  a 22 point sensor offset curve  can be enabled  it is disabled upon delivery from the factory  by selecting  the Sensor Offset tab within the configuration menu        When the Field Unit is in Orifice mode  a Square Root calculation is per   formed  You have the option to display the Square Root Calculation  If  this option is enabled  it will be displayed as Percent Square Root in WIM  and sent to a ModBus Register     To display the Square Root Calculation  first make sure you have selected  Orifice Flow from the mode menu  Then  from the Flow Units drop down  list  select Percent   Vol Flow  If the Density check box is selected  then  Percent   Mass Flow can also be selected from the Flow U
5.         1210            AS    WIRELESS SOLUTIONS       Differential Pressure Field Unit  User Guide       Adaptive Wireless Solutions Inc  577 Main St Phone   978  875 6000  Hudson  Ma 01749 www  adaptive wireless com               1 57  0405  0806  0810    3 31 2005 Updated Specs  cover  figures   amp           8   4 14 2005   Additional Maintenance to match other Guides    10 30 2008  Update Section 8 Drawing 6023 520 from Rev  C to Rev  E       User Manual    Differential Pressure Field Unit  Models WI DP I xxx    Versions 1 70 or later    Important Information to      User       Changes or modifications not expressly approved by Adaptive Wireless Solutions  may void the user   s authority to operate the equipment     This device complies with Part 15 of the FCC Rules  Operation is subject to the  following two conditions  1  this device may not cause harmful interference  and  2  this device must accept any interference received  including interference that  may cause undesired operation     This device is for mobile and fixed use only  not portable or body worn   A  separation distance of 20cm must be maintained at all times between the antenna  and the body of the user and bodies of nearby persons     This device has been designed to operate with an antenna having a maximum  gain of 9 dBd  Antenna having a higher gain is strictly prohibited per regulations  of Industry Canada  The required antenna impedance is 50 ohms     To reduce potential radio interference to other 
6.      Currently measured differential input level    Error Messages    If an error is detected with the operation of the Field Unit a message will  be displayed on the Field Unit LCD  a corresponding message may also  appear on the Base Radio LCD      There are few types of error messages  warning and fatal  Warning mes   sages are displayed as part of the normal cycling message sequence  These  are        LOW BAT   battery should be replaced as soon as possible                   can not detect Base Radio   e SFAULT  there is an open sensor or excitation wire detected   Also if a sensor value goes above below logical limits  The unit will  display 9999 99 for measurement  sensor fault mode   but will con   tinue sampling and recover if the problem desists       OVERRNG   the device is measuring a value above below sensor  dependent bound values  For example the Analog Input device will  report over range if measurement is above 105  range of the Analog  Input sensor  If the measurement goes above 150  full range  the unit  will go into Sensor Fault mode  In over range mode  the measurement  is continued to be displayed  with the  OVERRNG  message to re   mind the user that the specified range of the sensor and the calibrated  range of the device is being exceeded     Fatal error messages will replace the normal cycling message sequence  and will flash  A fatal message indicates the Field Unit is no longer operat   ing normally and requires repair  These are     RF ERR   fatal 
7.     Most often these problems can be avoided with some thought at the time  of installation  The practices noted below are generally recommended  but  they can only act as a guideline and cannot cover all possible variations   The final installation must be made at your discretion and approval  You  must be the judge of the actual installation     Dimensioned mechanical drawings for aid in mechanical installation are  located in Section 10  Technical Specifications    Correct positioning of the Field Unit will ensure the best performance of  the device  When planning the positioning of the Field Units there are a  few parameters that must be paid attention to     e The top of the Field Unit should point upwards  The bottom  of the Field Unit should NOT point directly at the Base  Radio and the Field Unit LCD should point away from the  Base Radio     e      Field Units should maintain an approximate spacing of at  least six feet apart from one another               line of sight range between a Field Unit and Base Radio  is 2000 feet at the 19 2K baud rate setting  Note that this  range is reduced by the amount of RF noise present   obstructions  and the material properties of the obstruction     e Only place the Field Unit in ambient operating temperatures  of  40  F to 185  F   40 C to 85          Figure 3 1 gives examples of incorrect setups according to the previously  mentioned parameters     Rev 1210    Section 3  Installation         Outside  Base Radio  range       Fi
8.   Pod  93       94  P dal  95       96      97   5  98  fe  99      100      102      103      104       ay d  57            253   Rev 1210    Appendix D  Modbus Register Definitions    specific gravity units     grams per cubic centimeter     kilograms per cubic meter     pounds per gallon      pounds per cubic foot     grams per milliliter     kilograms per liter      grams per liter      pounds per cubic inch     short tons per cubic yard     degrees twaddell      degrees baume heavy     degrees baume light     degrees API       percent       49    ABOUT         Adaptive Wireless Solutions develops  produces and supports  partner specific  high value industrial measurement and process  solutions that enable our end users to increase efficiency   through put and environmental compliance     AWS customers include large national companies in the oil and  gas  chemicals  pharmaceutical  food and beverage  primary  materials processing  and energy industries  In addition to the  wireless product line  AWS also offers a traditional wired line of  temperature  pressure and differential pressure instrumentation     In the process control field  where quality is taken for granted and  new technology is announced daily  we have deliberately  concentrated our efforts on the development of instrumentation  that makes business sense  The result is a product range that is  rugged  secure  and reliable and works in even the most  hazardous environments  We give companies the tools to red
9.   side  any zero drift caused by the over   pressure will be negligible after a fairly short period of time    about three  hours  If the sensor has suspected to have been over pressurized on the    side  over pressure equal to the static line pressure of the process should  be applied to        side and the zero allowed to neutralize for several  hours     1  Check overall installation to ascertain that all fittings  plugs  vents and  bolts are secure  leak free and ready for service    2       manifold and line shutoff valves  if installed  should be in the  closed position    3  Open manifold bypass valve and both line shutoff valves if installed   This will put a zero differential pressure across the sensor    4  Slowly crack open the   Upstream manifold block valve until the sen   sor 15 at line pressure  Then fully open this   Upstream manifold block  valve    5  Crack open        and   side vent plugs until all air is purged out of the   transmitter and the manifold  Close the vents tightly      Check ZERO output and adjust 1f necessary    7  Open the   Downstream manifold bock valve fully    8  Close the manifold bypass valve  The sensor is now in service     Os    Differential Pressure Sensors in flow service need to be periodically re    zeroed  The procedure for re zeroing assumes that the sensor in service   and that the line shut off valves are open  that the   and   manifold valves   are open and that the manifold bypass valve is closed  To then re zero the   tr
10.  50 AM  Device discovery      0 new devices found  0 devices removed         O Alarming Field Units       Figure 3 7  WIM Field Unit View    Select Wireless Data Loss Test    from the popup menu     The Wireless Data Loss Test window appears  see Figure 3 8  The name of  the Field Unit being tested appears in the title bar in parenthesis     Wireless Link Test  Unit 14041           Configure Test    Hours Minutes Seconds          Progress    Logging data    00 04 51 left    Link Quay  5 STARR                Figure 3 8  Wireless Data Loss Test    Rev 1210    3 2 2 3 Continued    Section 3  Installation    In the top of the window  you can configure the test to run for a specified  amount of time  The longer the test  the more data the test will have to do  an evaluation  Type the length of time that you want to run the test and  click Begin to start  Once the test starts  WIM will reconfigure the Field  Unit s Transmit Rate to the fastest possible for the selected Baud Rate   These rates are listed in Section 5 2  After the test has completed  it will  restore the previously configured Transmit Rate     During the test  the communications reliability is evaluated while the Field  Unit is running under normal operating conditions  As the test runs  a link  strength will be shown in the lower right hand corner of the window  5  STARR indicates the strongest link  while 1 STARR indicates the weakest  link  The Link Test will continue to be evaluated and the rating on the  screen 
11.  UI n E bs nde vene URS 9  3 5  Menu Map to Field Unit Link          10  3 0  Menu Map to Base Radio Link          ee pH dri b D pulp CHEER UMEN       11  3 7  WIM Field Unit  VIEW                                                       12  3 0  Wireless Data Loss MSU                                                                           12  4 1  Field Unit Power UP and Operations ICD Sequences                                     15  4 2  The Read Only SeQUEIGE    o rene nein ren                 15  4 3  Overall Configuration Menu                                                    16  AA  Setting a User Password                                         DIR REN 17  5 1  Menu Map to RF Channel            18  5 2  Menu Map to Baud Rate Setting uitae see                   19  5 3  Menu Map to RF ID                                                            19  bI  Incorrect Sampling ROG                                                                              e FR DIS a                    22  6 2  Correct Sampling I ale cute               ius                            22  6 3  Example of Abnormal Transmission Rate                                                        23  6 4  Example of Abnormal Transmission Rate                                                        24  6 5  Smart Rate Configuration Using                          25  6 6  Sampling and Transmission Rate Selection Using                                        26  6 7  Normal Upper and Lower Value Selection Usi
12.  can be found  in section 6 6 of this manual     Input   Volts   10          Abnormal Condition    Abnormal  Sample        Normal  Sample    Normal Upper  Value       Normal Sampling Rate of 15 Sec  Abnormal Sampling Rate of 5 Sec  Normal Upper Value of 2 5    Figure 6 4  Example of Abnormal Sampling Rate Setting    Rev 1210    6 5  Setting      Smart Rate  Threshold    Differential Pressure Properties   00009044  9 44       peration Mode   Sensor Offset  Sampling Bands   Alarms    General   Range    Sampling Rates      Update Rates  Normal Transmit Rate  10 Sec  Abnormal Transmit Rate  5 Sec  Normal Sampling  1 Sec  Abnormal Sampling  1 Sec    Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband              Enable Smart Smoothing       1 255 Seconds  Percent Sqr Rt    SmartRate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes by the amount set              v  Enable SmartRate       Send a sample when primary value Percent  changes by  L      Rt    Figure 6 5  Smart Rate Configuration Using    WIM                  Section 6  Configuring the Sampling and Transmission Rates    The Smart Rate is a feature used to trigger radio transmission of the  measured data sooner than the normal or abnormal rate specified by the  user  This feature is used to construct a more accurate graph of the  measured pro
13.  hour   MKS System     StdCuFtPerMin   123     standard cubic feet per minute   US System     CuFeetPerHour   130     cubic feet per hour      CuMeterPerMin   131     cubic meters per minute      BarrelPerSec   132     barrels per second   1 Barrel   42 US gallons  of   BarrelPerMin   133     barrels per minute      BarrelPerHr   134     barrels per hour      BarrelPerDay   135     barrels per day      GalPerHr   136     gallons per hour      ImpGalPerSec   137     imperial gallons per hour      LiterPerHr   138     liters per hour      GalPerDay   235     gallons per day       Rev 1210 47    AWS Wireless Differential Pressure Field Unit User Manual    48       Volume Units    Gallons  Liters  ImpGallons  CuMeters  Barrels  Bushels  CuYard  CuFeet  CuInch  BarrelsLiquid  Ez  NormalCuMeter  NormalLiter  StdCuFeet  HectoLiter          Feet   Meters   Inches   CM   MM  FtInSixteenths          Mass Units  Gram   KG   MetricTon  Pound  ShortTon  LongTon   Ounce       Length Units              ay    60     y  40   41   42   43   46   10   11   125  13   24     66   67   68   236           44   45   47   48   49   151     61   62   63   64   65   125        Mass Flow Units       GramPerSec  GramPerMin  GramPerHr  KGPerSec  KGPerMin  KGPerHr  KGPerDay  MetTonPerMin  MetTonPerHr  MetTonPerDay  PoundsPerSec  PoundsPerMin  PoundsPerHr  PoundsPerDay  ShTonPerMin  ShTonPerHr  ShTonPerDay  LongTonPerHr  LongTonPerDay    70   71   72   73   74   75   76   77   78   79   80   81   82   83   
14.  return from the sub menu     If both the NEXT and ENTER buttons are depressed at once  a message  on the LCD displaying OFF  will appear  If both buttons are released  upon appearance of this message the user will be returned to the scrolling  main screen  If both buttons are not released for the duration of the OFF   message the unit will power down and turn off  Note  If the unit is turned  off while entering values in a sub menu  those values will NOT be saved       As shown throughout the document  this mark indicates that these menu  options will automatically turn off if the Wireless Instrumentation Man   ager Software is used  All changes to these Field Unit menu options  should be made through software instead  This is to prevent simultaneous  changes from taking place  If you wish to discontinue use of the software  and want these menus re instated  you must contact your Adaptive Wire   less Solutions Sales Representative     44 Rev 1210    Appendix          Field Unit Displayed Message Definitions    This section covers the various messages  displayed on the Field Unit  LCD  that occur during operation of the device     Operations Sequence       RF Link Status      RF OK   Field Unit and Base Radio are communicating  properly      RF SYNC   Field Unit and Base Radio are attempting to  synchronize communications     RF OFF Field Unit s RF Channel is set to RF OFF    NORF  Field Unit and Base Radio have no communications  e Differential Pressure Input Level     XX XX
15.  same RF Channel and must be transmitting at the same Baud  Rate  While all Field Units and Base Radios are set to default configura   tions at the factory  if any configuration differences are present  the Base  Radio will not be able to communicate with the Field Units  The subsec   tions are as follows     5 1  RF Channel Selection  5 2  RF Baud Rate Selection  5 3  RF Identification Selection    The RF Channel defines a set of frequencies on which communication  takes place between the Base Radio and the Field Unit  Each RF Channel  has a different set of frequencies  thus allowing the user to have multiple  different wireless networks co existing throughout the same facility          Base Radios and Field Units can be set to one of 16 different RF chan   nels  The only Field Units recognized by a particular Base Radio are the  units that are on the same RF Channel as that Base Radio  This allows the  user to decide which Field Units communicate with each Base Radio     The RF Channel can be thought of as a set of walkie talkies  If both  walkie talkies are on channel one they can communicate  If    walkie   talkie is on channel one and the other is on channel two  they cannot com   municate  Likewise  if two walkie talkies are on channel one and two  other walkie talkies are on channel two  the walkie talkies on channel one  cannot hear what is being transmitted by the walkie talkies on channel  two     Each Field Unit comes from the factory with the RF Channel set to OF
16.  temperature induced density variations  between the legs  other density variations between  the measurement legs  The actual installation  must be made to minimize these errors        3 1 4  Installation in Steam  Service             Figure 3 3  Installation in a Steam  Application    Section 3  Installation    In liquid service  you want all of the impulse lines to be completely full of  liquid  It is generally best practice to place the process taps in the side of  the liquid process line  This minimizes the entrance of gas bubbles  which  tend to form at the top of the process line  It also tends to minimize the  entrance of sludge and particulates that tend to accumulate in the bottom  of the line     1  Tap into the side of the process line    2  Mount the transmitter beside or below the taps    3  Position the vents level with or above the point where the im   pulse lines connect to the transmitter  This will give the best way  to vent all ofthe air out of the impulse lines and flanges     Here you want the impulse lines and manifold to be full of gas  Placing  the taps 1n the top of the      generally prevents liquid from entering the  transmitter  Mounting the transmitter above the process piping allows any  liquid or condensate that does form in the impulse lines to drain back into  the process piping     1  Tap into the top of the line  2  Mount the transmitter above the taps    Steam service 1s slightly more complex  Here  you want to tap into the  side of the ste
17.  the Field Unit s diagnostic menu  see Figure  Field Unit 3 5      OPERATIONS SEQUENCE     emm   ENTER  5 STARR  Next 4 STARR  3 STARR  EXT     TEST   2 STARR    1 STARR  NO LINK       ENTER     Figure 3 5  Menu Map to Field Unit Link Test       Using the NEXT and ENTER buttons  navigate to Link Test  and press the  ENTER button to begin the test  The Field Unit will begin to test the link  in both directions  to and from the Base Radio   During this time  the word  TEST will appear on the LCD display  When the test is complete  the  Field Unit will display the quality of the link  Be aware that the Field Unit  uses the configured Baud Rate and transmission rate to perform this test   The length of time it will take to perform this test is dependent upon how  fast the device is normally transmitting     When enough messages have been observed  a link strength will be shown  on the display  5 STARR indicates the strongest link  while 1 STARR  indicates the weakest link  The Link Test will continue to be evaluated and  the rating on the screen may adjust itself  Keep      mind that the longer the  Link Test runs the more data the Field Unit will have to evaluate     The Field Unit installation site should strive to place the Field Unit in a  location where it receives the highest number possible  A stronger link  means less data re transmits and better battery life     When the Link Test is conducted from a Base Radio  it measures the link  strength between a selected Field Uni
18.  the strongest link  while 1 STARR  indicates the weakest link  The Link Test will continue to be evaluated and  the rating on the screen may adjust itself  Keep in mind that the longer the  Link Test runs the more data the Field Unit will have to evaluate     The Field Unit installation site should strive to place the Field Unit in a  location where it receives the highest number possible  A stronger link  means less data re transmits and better battery life     3 2 2 3  Conducting a Link Test from WIM To conduct a Link Test from WIM  make sure that WIM is running on the  PC attached to the Base Radio  Then go to the Field Unit view  and right   click on the Field Unit you want to test Received data transmission from   Figure 3 7      Rev 1210 11    AWS Wireless Differential Pressure Field Unit User Manual            Accutech Wireless Instrumentation Manager  Connected  in            Field Units  O All Field Units  3 Alaming Field Units   C Unconfigured Field Unis        Field Unit Groups      Base Radios      Field Unit Types    Total Field Units  1  Alarming Field Units  0  Waming Field Units  1    Selected Field Unit      Accutech Dual 4 20 mA Input    12    All Field Units    m ee                     Primary  amp  Secondary Values  00 14 041 Dusi 420 m   Input 1N1 35 00 m   51 0  Rename  Tasks    View Field Unit Data     Configuration     Export Dat     4 24 2006 10 34 38       Device  RF Channel   i  ONUNE  4 24 2006 10 34 33 AM  Field unit 14 041 ONUN   4 24 2006 10 34
19.  the tasks outlined     Section 3  Installation   This section covers general considerations regarding correctly commis   sioning the Field Unit as well as unique applications such a flow service  commissioning  Also covered in this section are mechanical installation  considerations  such as Field Unit placement     Section 4  General Configuration   In this section general configuration options such as password protection   and selecting a user password are discussed  Also covered 15 the setting of  a Field Unit tag name  resetting of all Field Unit settings  and a discussion  of the various messages that are displayed on the Field Unit LCD     Section 5  Configuring the RF Communications   This section covers the setup of the Field Unit RF Communications which  allow the Field Unit to achieve communication with the Base Radio  Pa   rameters discussed are the Field Unit RF ID  the RF channel setting and  Baud Rate     Section 6  Configuring the Sampling and Transmission Rates   This section aids the user in selecting the amount of time between each  sample of the process  and the time between each transmission of this  sample to the Base Radio  Also discussed is the use of setting an abnormal  threshold in which sampling and transmission times may change during a  period when the process variable is within the abnormal region     Section 7  Configuring the Process Variable  This section helps the user to zero the sensor  as well as discussing the  setting of a measurement o
20.  this to the user  The user will not be  allowed to leave this screen before the setting is corrected     To configure the Normal Upper and Lower Value menu options using the  Wireless Instrumentation Manager software  enter the configuration menu   See Section 9 2 of the Wireless Instrumentation Manager User Manual    Once in the configuration menu click on the Sampling Bands tab to bring  up the sampling band information as shown in Figure 6 7     To set a limit to the normal condition  enable the limit by clicking on the    Use Input 1 Limit check box  Then enter the value and time deadband for  the limit     Rev 1210                 7       Configuring      Process Variable    This section helps the user in the selection of engineering units  as well as  discussing the setting of a measurement offset and trimming the process  measurement  The subsections are as follows     7 1  Zeroing the Sensor   7 2  Setting a Measurement Offset  7 3  Trimming the Measurement  7 4 Entering a 22 Point Curve    7 1  Zeroing the Sensor Zeroing the sensor can only be performed from the Field Unit  You will  need to check the    position zero    reading on the transmitter  The Differ   ential Pressure Field Unit is a sensitive device  Its elevation and its orien   tation in the field may be different from the orientation in the factory  where it received its last configuration  To compensate for position  changes  you may need to perform a sensor position adjustment once the  unit is instal
21.  yourun the RSSI Diagnostics   See Section 3 2 1 Field  Unit RSSI Diagnostic     Rev 1210    Section 3    Installation    3 1  Mechanical Installation       Warning A    During installation do not apply force to the in     strument housing or antenna  Use a proper wrench  for all installations  Failure to use correct installa   tion procedures can cause damage to the Field  Unit     3 1 1  Field Unit Positioning          In this section  mechanical installation instructions are discussed for the  various setup capabilities of the Differential Pressure Field Unit  The  subsections are as follows     3 1 1  Field Unit Positioning   3 1 2  Installation in Liquid Flow Service  3 1 3  Installation in Gas Service   3 1 4  Installation in Steam Service    Each AWS Differential Pressure Field Unit is a rugged device which  provides optimal performance when installed with careful consideration  It  may be utilized in any ultrasound measurement service so long as care is  exercised to prevent exposing the sensing elements to excess stress or  temperature  Installation practices greatly affect the life that you can  expect from your AWS Differential Pressure Field Unit     Give careful consideration to the environment where you will be installing  your instrument  Avoid installations that expose the device to excess  temperature  high vibration  considerable shock  or exposure to dripping  condensate or corrosive materials  Also avoid installing the device in an  unserviceable location 
22. 0 Warning Statement   WARNING  EXPLOSION HAZARD   SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR  USE IN A HAZARDOUS LOCATION     CERTIFICATION DOCUMENT   NO CHANGES PERMITTED WITHOUT PRIOR CSA APPROVAL    NOTICE   This drawing and specifications  herein  are                    Adaptive Instruments Corp   proprietary property of ADAPTIVE INSTRUMENTS and    ghal not      reproduced in whole or in part as the basie  for manufacture or sale without prior written permission VS Installation Control Drawing     Wireless Sensors    from Adaptive Instruments   ACDSee EET     Rev 1210 41    AWS Wireless Differential Pressure Field Unit User Manual           INPUT CONNECTIONS    Wh   AM    WI GP 1  WAP    WLGL   Integral Sensor     no external connections Integral Sensor     no external connections  Pressure Senso   WI RT I           mem TEE   E J1  Terminal Board  Sensor Input J3  Terminal Board  Input Switches    Input  Swt                WI RT S  WI RT M  CO RT S  CO RT E              ture  WI GP S  WI AP S  WI GP M  WI AP M  WI GL M  WI GL S  WI GP E  WI AP E  WI GL E  WI DP E  WI GP EL  WI AP EL  WI GL EL  WI DP EL                      WI SES  WI SI M  WI SFE  WI SI EL  Dual Switch Input           o  Moi stamens Com  oma   ma      WS installation Contro  Drawing   Wireless Sensors    for manufacture or sale without prior written permission    from Adaptive Instruments    5 Drawing NO Sou  w   wa jw        2350                      42 Rev 1210    Section 10  Technical Specif
23. 5 an example of what happens when the Normal Sampling Rate  is too slow for the process being monitored  Notice how the rise in the    voltage level falls between two normal samples  and thus goes completely  64 Normal undetected   Sample    t    Figure 6 2 15 an example of what happens when      Normal Sampling Rate  15 correctly set for the device that is being monitored  Notice how this set     ting makes it possible to sample the rise in the voltage level                  1 00 2 00    Time  min   With a Normal The Wireless Instrumentation Manager software must be used to configure  Sampling Rate of 15 Seconds          this setting  An explanation of how to select the Normal Sampling Rate  Figure 6 2  Correct Sampling Rate using the Wireless Instrumentation Manager software can be found in sec     tion 6 6 of this manual     22 Rev 1210    Section 6  Configuring      Sampling and Transmission Rates    6 3  Selecting the Abnormal The Abnormal Transmission Rate is identical to the Normal Transmission  P Rate with one exception  The Abnormal Transmission Rate only applies  Transmission Rate while the Field Unit is in an abnormal condition  see Section 6 6   This    allows an increase or decrease in the frequency of information you receive  depending on the operating conditions of the process being monitored     In order to properly set the Abnormal Transmission Rate  determine how  often updates are needed from the Field Unit when the process being  monitored is operating und
24. 84   85   86   87   88     Rev 1210                                                                                                                                                                            gallons      liters      imperial gallons      cubic meters      barrels      bushels      cubic yards      cubic feet      cubic inches      liquid barrels      bbl lig   31 5 US gallons    normal cubic meter   MKS System     normal liter   MKS System     standard cubic feet   US System     hectoliters       feet      meters      inches      centimeters      millimeters      see Note 1 in HART document HCF SPEC 183       grams     kilograms     metric tons     pounds     short tons     long tons     ounce       grams per second     grams per minute     grams per hour     kilograms per second     kilograms per minute     kilograms per hour     kilograms per day     metric tons per minute     metric tons per hour     metric tons per day     pounds per second     pounds per minute          pounds per hour                                    pounds per day      short tons per minute     short tons per hour     short tons per day     long tons per hour     long tons per day          Density Units  SGU    GramPerCuCm    KGPerCuMeter    PoundsPerGal    PoundsPerCuFt  GramsPerML  KGPerLiter  GramsPerLiter  PoundsPerCuIn  ShTonPerCuYard  DegTwad  DegBaumHeavy    DegBaumLight    DegAPI         Analytical Units    Percent         Special Units  SpecialUnits      id  90      91  P  92
25. F   This means the Field Unit will not communicate to any Base Radio  To set  the Field Unit for communication  first determine the channel that you  want to use  Then follow the Field Unit menu map shown in Figure 5 1 to  configure the RF Channel     1    OPERATIONS SEQUENCE I   NEXT  REOR                  y    USER PROMPTED FOR      PASSWORD         ENTER          CHAN                RF CH16 _  Default of RF OFF  Figure 5 1  Menu Map to RF Channel Setting       Once in the RF Channel menu  increment it by pressing the NEXT button   When selecting this value  do not choose an RF Channel that is currently  being used by other AWS Wireless Systems as this can cause communica   tion problems     Rev 1210    5 2  Baud Rate Selection    If you change the baud rate of a Field Unit  you    must also change the baud rate of the Base Radio  and all other Field Units that are communicating  with that Base Radio        5 3  RF Identification  RF ID   Selection    Section 5  Configuring RF Communications    The RF Baud Rate refers to the speed at which the Base Radio and Field  Units communicate  The RF baud rate for the Base Radio and the Field  Unit must be the same in order for successful communication to occur   There are three selectable settings with the fastest update times and ranges  listed below        4 8    Rate of 4 8 Kbaud  Update every 20 seconds     Range of 3000ft  Line of Sight       192    Rate of 19 2 Kbaud  Update every 5 seconds     Range of 2000ft to 2500ft  Line 
26. NTER and NEXT buttons until the unit powers up    3  Hit the NEXT button until the CONFIG message appears then hit  ENTER    4  Enter the default password 0000 to enter the CONFIG menu    5  Enter the SET RF menu    6  Set RF CHAN setting equal to the Base Radio s RF Channel    7  Set BAUD RT setting equal to the Base Radio s Baud Rate    8   9   1    NOR    Set RF ID number to be a unique value between 1 and 100     Zero the sensor   0  Trim and Offset the measurement  if appropriate      Perform the following via the Wireless Instrumentation Manager software   Select mode of operation    Select appropriate engineering units    Enter appropriate calculation parameters    Select normal transmission rate    Select normal sampling rate    Select abnormal transmission rate    Select abnormal sampling rate    Set normal upper and lower values     GOO Ore OX       es    If the         OFF  message 15 being displayed on the Field Unit LCD  per   form the following        Set the RF CHAN setting equal to the Base Radio s RF  Channel     If a  NO RF  message is being displayed on the Field Unit LCD  check  the following     e 15      Field Unit set to the above listed configurations    e  Isthe Base Radio on    e Do      Field Unit and Base Radio settings match   See Sec   tion 5 of the Field Unit and Base Radio User Manuals    e Are the Base Radio and Field Units unable to communicate  due to obstructions or distance   See Field Unit Manual   Field Unit Placement section        Have
27. Please note that the password only protects the Field Unit from unauthor   ized configuration via the NEXT and ENTER buttons  The Wireless In   strumentation Manager requires a user login password to gain access to all  configuration parameters  However  user accounts are available and can be  set with different access levels and restrictions  For more information on  user accounts see the Wireless Instrumentation Manager User Manual  Section 8 4      To reset all Field Unit settings to their default state  the user must navigate  to the DEFAULT menu option in the CONFIG menu via the keypad     Once at the default menu option  pressing the ENTER button will display     RESET     on the LCD  which asks if you are sure you want to reset the  device to its default configuration  You will then be prompted with    NO     on the LCD  Pressing the ENTER button while    NO    is being displayed  will NOT reset the device  Pressing the NEXT button will display    YES     on the LCD  If you press the ENTER button while    YES    is being dis   played the device will be reset     Rev 1210 17                 5       Configuring      RF Communications    5 1  RF Channel Selection    Warning    During installation do not apply force to the in   strument housing or antenna  Use a proper wrench  for all installations  Failure to use correct installa   tion procedures can cause damage to the Field  Unit        In order for the Field Unit and the Base Radio to communicate  they must  be on the
28. Range  1       For example  if two Field Units are placed one foot apart and      first  Field Unit has an RF ID number of 027  that means it is in the 4th group   22 28   The second Field Unit must have an RF ID number that is in  another group  less than 22 or greater than 28   Setting the RF IDs of two  closely spaced Field Units so that the RF ID numbers are greater than 7  apart ensures that the Field Units are in different Base Radio sync groups   This allows the closely spaced Field Units to properly receive their  synchronization signal from the Base Radio and maintain their proper  communication and range     You can also ensure that closely spaced Field Units maintain their  synchronization with their Base Radio by simply assigning each of the two    closely spaced Field Units to talk to a different Base Radio     Either way  following this process will keep the Base Radio and Field  Units properly synchronized for long term communication     Rev 1210    3 1 2  Installation in Liquid  Flow Service       Figure 3 2  Installation in Liquid Flow  Application    3 1 3  Installation in Gas  Service    The piping between the process and the transmit   ter must accurately convey the process pressure to  the transmitter sensor  In transferring the pres   sure  there are several sources of error  These are   leaks  pressure loss due to friction  particularly if  purging is used in the application   gas that is  trapped in a liquid line  liquid that is trapped in a  gas line 
29. Seconds    LCD Message     Lower Limits       Use Input 1 Limit          This tab allows the user to set the  Sampling Bands  of the field unit   The unit uses Normal sampling transmission rates when the primary  values are within the bands  When the value is outside of the bands  it  is considered Abnormal and Abnormal rates are used        Load from File          Figure 6 7  Normal Upper and Lower Value    Selection Using WIM    26    To configure the Normal and Abnormal Sampling and Transmission menu  options using the Wireless Instrumentation Manager software  enter the  configuration menu  See Section 9 2 of the Wireless Instrumentation Man   ager User Manual   Once in the configuration menu click on the Sampling  Rates tab to bring up the sampling rate information  as shown in Figure  6 6     To select the Normal Transmission Rate  select one of the time periods  from the drop box  Next  select an Abnormal Transmission Rate in the  same manner  Note that the Normal and Abnormal Transmission Rate can  be the same     Once the transmission rates have been selected  the user should select the  desired sampling rates  Note that the sampling rate must be equal to or  faster than the associated transmit rate  For example  in Figure 6 6 the  Normal Transmission Rate is set to 10 seconds and the Normal Sampling  Rate is set to 1 second  This is a valid configuration     If the user incorrectly enters the Transmission and Sampling Rates  a mes   sage will be displayed explaining
30. TIONS SEQUENCE      NEXT  NEXT                           Nexr                   NExT   FACTORY                                  wae     USER PROMPTED FOR        PASSWORD  UF                                        Figure 4 3  Overall Configuration Menu           Each Field Unit has a user settable Field Unit Tag Name  This Tag Name  15 displayed upon Field Unit power up  and when the Read Only Sequence  is selected  The Tag Name is a 21 character string that is displayed in  three separate 7 character flashes on the Field Unit LCD     The user may choose from A Z  0 9  a dash         and an underscore     _       The underscore has a special meaning to the software inside the Field  Unit  For example  if you have a Tag Name that is only 5 characters long   then you do not want to wait for the rest of the 16 characters to be dis   played on the LCD  So if your Tag Name was                   you would want  to enter the Tag Name like this     TRAP1  n       The Tag Name is entered via the Wireless Instrumentation Manager  To  do so  when the software is in the Field Unit view  See Section 8 1 of the  Wireless Instrumentation Manager User Manual   right click the Field  Unit 1con  select Rename  then enter the Tag Name you wish the Field  Unit to have     This Tag Name will then be uploaded to the Field Unit and can be dis     played by pressing the ENTER button when the unit is in the Operations  Sequence  See Section 4 1 1 of this manual      Rev 1210    4 4  Setting a User Pas
31. am lines to keep from collecting sludge and particulates   Process steam temperatures almost always exceed the working tempera   tures for the differential pressure transmitter  To surmount this problem   allow the impulse lines to condense and cool the steam by exposing the  impulse lines to the general ambient temperature  Make the vertical sec   tion of the impulse lines long enough to make sure the steam condenses in  the impulse lines  A good rule of thumb is that each foot of condensate  line reduces the temperature by 20  F  Example  Saturated steam at 15  psig is approximately 250 F  To lower the temperature at the transmitter  to 200  F  take 50  F divided by 20  F per foot   2 5 feet of condensate pip   ing  Drain valves on the vertical portion of the condensate lines are gener   ally a good idea to help keep the system clean and free from a build up of  sludge     1  Tap into the side of the steam line    2  Run vertical impulse lines to allow the steam to condense and  cool  Mount the transmitter below the line taps but above the  drain valves    3  Fill the impulse lines with water when commissioning the  device     Rev 1210 7    AWS Wireless Differential Pressure Field Unit User Manual    3 2  Testing Communications Remember  proper placement of the Field Unit will optimize your RF  communication range and capabilities  Perhaps the best test to perform    before mechanically mounting the unit is a quick hand held test  There are  two types of tests you can condu
32. ansmitter use the following procedure    1  Open the manifold bypass valve fully    2  Close the   Downstream manifold block valve    3  Check the zero output and adjust if necessary  If you suspect gas or air  in the impulse lines  these should be purged    4  Open the   Downstream manifold block valve    5  Close the manifold bypass valve  The sensor is now in service     Rev 1210                 4       General Configuration    4 1  Field Unit Displayed  Messages    During configuration and testing  keep Field Units    at least six feet from the Base Radio and other  Field Units to ensure good communications        4 1 1  The Read Only Sequence    This section discusses the generalities for configuring the Field Unit via  the NEXT and ENTER buttons  The subsections are as follows     4 1  Field Unit Displayed Messages  4 1 1  The Read Only Sequence  4 2  The Overall Configuration Menu Map  4 3  Setting a Field Unit Tag Name  4 4  Setting a User Password  4 5  Resetting All Field Unit Settings    To turn the Field Unit on  press and hold both the NEXT and ENTER but   tons for a few seconds  Upon power up  the Field Unit will display the  Power Up Sequence  and then go into the Operations Sequence  These  Sequences are shown in Figure 4 1 below          If enabled              1    POWER UP SEQUENCE i       WI DP       VER X XX E E acd E XXXX XX       UNITS       b                                             RF  STATUS       RF               RF SYNC  RF OK    ERROR  MSG     
33. cess value vs  time than is possible with the fixed  transmission rates  while using less battery power     First you must decide the amount that the process variable must change  since the last data sample to trigger a new transmission of the process  value     If the process value changes by more than the entered Smart Rate amount  within the normal or abnormal sampling rate  whichever 1s active   then  the process variable is transmitted immediately  The normal abnormal  transmit clock is then reset upon this transmission  If no Smart Rate  amount exceeding change takes place in the next normal abnormal  sample  then the next transmission will be the normal abnormal transmit  rate period     The amount entered is in the same units as were selected by the user to be  displayed on the Field Unit  If the measured process value does not  change by more than the entered Smart Rate amount within the time  between the sampling rates  whichever is active   then the process value is  transmitted on the next transmit rate     If changes in the process value  which exceed the Smart Rate Amount   continue to occur  the process value is transmitted repeatedly     To configure the Smart Rate using the Wireless Instrumentation Manager  software  enter the configuration menu  See Section 9 2 of the Wireless  Instrumentation Manager User Manual   Once in the configuration menu  click on the Sampling Rates tab to bring up the sampling rate information  as shown in Figure 6 5     To enable t
34. ct  the RSSI  Received Signal Strength  Indicator  Diagnostic and the Link Test  The RSSI Diagnostic measures  the strength of the signal at the Field Unit  The Link Test measures the  throughput of data sent to and from the Field Unit  The Link Test may be  conducted from the Field Unit  Base Radio  or through WIM     The RSSI Diagnostic should be conducted first to determine if the Base  Radio is communicating with the Field Unit  Then the Link Test may be  performed to test the validity of the installation     To perform these tests you should have a good idea of where the Base  Radio will be placed  for more information see Section 3 of the Base Ra   dio User Manual   Place the Base Radio in the desired area and power on   Make sure that the Base Radio and Field Unit are on the same RF Channel  and Baud Rate  See Section 5   You may also have to increment the num   ber of Field Units with which the Base Radio is communicating  See the  Base Radio User Manual Section 4 3      Once both the Base Radio and Field Unit are set up to be on the same net   work  make sure communication is established by looking at the Field  Unit LCD for the  RF OK  message in the Read Only Sequence  see Sec   tion 4 1 1      After communications have been established  go to Section 3 2 1 for the  RSSI Diagnostic or Section 3 2 2 for the Link Test     3 2 1  Field Unit RSSI Diagnostic The Field Unit should be placed in RSSI Diagnostic mode to determine  the signal strength at the location of the 
35. date data faster than their communication  speed allows  Thus  if you selected the 19 2K Baud Rate setting  your fast   est transmission rate will be 5 seconds  The Field Unit automatically deter   mines these settings and adjusts the menu options accordingly  A complete  table of these parameters is shown in Section 6 2     In order to properly set the Normal Transmission Rate  you must first de   termine how often you need updates from the Field Unit  You have a se   lectable range of 1 5  10  15  20  40 seconds and 1 minute  The factory  default is 10 seconds     If all of the data does not get through  the data is resent the following sec   ond  This prevents data from being lost  However  if the Transmission  Rate is set to the maximum  1 second  76 8K baud   then the data cannot  be resent the following second because the next set of data must be sent in  order to meet the Transmission Rate     The Wireless Instrumentation Manager software must be used to configure  this setting  An explanation of how to select the Normal Transmission  Rate using the Wireless Instrumentation Manager software can be found in  Section 6 6 of this manual     Rev 1210 21    AWS Wireless Differential Pressure Field Unit User Manual    6 2  Selecting the Normal The Normal Sampling Rate is the interval in which the Field Unit reads          monitored process value  As previously mentioned       Field Unit is in  Sampling Rate    sleep    mode to save power during the operations sequence  This 
36. e exceeded the Normal Upper Value     The Wireless Instrumentation Manager software must be used to config   ure this setting  An explanation of how to select the Abnormal Transmis   sion Rate using the Wireless Instrumentation Manager software can be  found in section 6 6 of this manual     Input   Volts   10           Abnormal Condition    Abnormal  Transmission            Normal  Transmission    Normal Upper       Normal Transmit Rate of 1 Min  Abnormal Transmit Rate of 10 Sec  Normal Upper Value of 2 5    Figure 6 3  Example of Abnormal Transmission Rate Setting    Rev 1210 23    AWS Wireless Differential Pressure Field Unit User Manual    6 4  Selecting the Abnormal  Sampling Rate    If you do not need more or less frequent samples  and updates from a Field Unit for a given applica     tion  then there is no need to complete this section   Simply set the Normal Transmission and Sam   pling Rates to the desired speeds  and make sure  that the Normal Upper and Lower Values are  configured to Disabled     24       The Abnormal Sampling Rate is identical to the Normal Sampling Rate  with one exception  The Abnormal Sampling Rate only applies while the  Field Unit 15 in an abnormal condition  see 6 6 Selecting the Normal Up   per and Lower Values   This allows an increase or decrease of the fre   quency of information you receive depending on the operating conditions  of the process being monitored     In order to properly set the Abnormal Sampling Rate  determine how often  
37. eld Units too                      So          close together  79  See Section3 1 1 1   A      Sy     Base Radio Bottom  aimed at  Base Radio  Behind too  great of an  obstacle    Obstruction    Figure 3 1  Examples of Incorrect Field Unit Positioning    Because there are so many setup possibilities we cannot cover them all  A  correct setup would make sure that the above warnings are heeded  and  that the Field Unit and Base Radio are capable of communication  The  Testing Communications section will help you to determine 1f you have  selected the correct installation points and orientations for your applica   tion     Rev 1210    AWS Wireless Differential Pressure Field Unit User Manual    3 1 1 1  Technique for Close Positioning of  Field Units    Field Units may be placed closely together by carefully following this  procedure  If this procedure is not followed  the communication range of  the Field Units will be significantly reduced and the Field Units may  eventually lose communication with the Base Radio entirely  This  procedure is easy to implement  but please read carefully for a full  understanding     The Base Radio synchronizes with the Field Units in Synch Groups of 7   organized by their RF ID numbers  If you want to place two Field Units  closer than 6 feet  make sure that you have set them in different groups   Note that this only applies to Field Units that are communicating with the  same Base Radio  The groups are defined in the following table     RF ID 
38. ent   No revision to drawing without prior FM Approval   RTD  TC  and Contact Input process connections to a Simple Apparatus Only   Accutech WI RT S  CO RT S  WI TC S  WI GP S  WI AP S  WI SI S  WI GL S  WI RT M  CO RT M  WI TC M  WI   GP M  WI AP M  Wi SI M  WI GL M  WI AM  SW AM  WI AP I  WI GP I  WI RT I  and WI TC I MUST be installed to  a bonded process      Accutech WI Al  WI AV has an internal ground screw mounted in the enclosure and must be connected to IS ground      All conduit connections must be sealed within 18  per NEMA 4 Standards for models WI xx N  Wi xx NT  CO xx N  and                    OANA AWN    CERTIFICATION DOCUMENT     NO CHANGES PERMITTED WITHOUT PRIOR FM APPROVAL                  Adaptive Instruments Corp  10 24 03    Released               oun    40 Rev 1210       Section 10  Technical Specifications       CSA APPROVED INTRINSICALLY SAFE INSTALLATION CONTROL DRAWING    HAZARDOUS  CLASSIFIED  LOCATION UNCLASSIFIED LOCATION    Class I  Zone 0  Group        Class    Division 1  Groups A  B  C  and D  Class II  Division 1  Groups E      and G  Class 111    RTD  TC  Contact inputs      see Nole 8       Accutech WHAI  WI AV Entity Parameters   Ui  Vmax    30V   li  Imax    100mA          0 9W         0   Li 0    Notes    1  The Intrinsic Safety Entity concept allows the interconnection of a CSA Certified Associated Apparatus to a CSA  Certified Intrinsically Safe field device  each with entity parameters not specifically examined in combination as a  
39. equipment to be monitored     The RSSI Diagnostic  located in the Field Unit s diagnostic menu   displays the RF signal strength in one of seven ranges  The signal strength    E          im i d from is displayed on the LCD using a combination of     gt     and     characters   1e nits versions 1  an 1gher  e version        m  gt               number        only be checked when the Field Unit Full signal strength is displayed as     gt   gt   gt   gt  m  gt     while minimum signal  is powered up  See Figure 4 1  strength is displayed as        _       If the field unit is not       communicating with the Base Radio  ie  NO RF   all underscore  characters will      displayed                      The RSSI is measured every time the Field Unit receives a message from  the Base Radio  The signal strength of the received message from the Base  Radio is calculated during this time  The actual signal strength in dBm for  each range is shown below     E   105 dBm  amp   100 dBm  amp    95 dBm  amp     90 dBm  amp     85 dBm  amp    105 dBm    100 dBm    95 dBm  90 dBm  85 dBm  80 dBm  80 dBm       8 Rev 1210    3 2 1 Continued    While using slower baud rate increases  communication distance  it also increases the    minimum transmit rate  See Section 5 2 for a list  of the fastest transmit rates for each baud rate   This may not be suitable for your application        3 2 2 Link Test    The Link Test may only be conducted from Field  Units  Base Radios and WIM versions 1 7 and  high
40. er  However  a Link Test being run from  WIM version 1 7 may test communications with  Field Units older than version 1 7     The version number may only be checked when  the Field Unit is powered up  See Figure 4 1        Section 3  Installation    To place the Field Unit in RSSI Diagnostic mode follow the menu map  shown in Figure 3 4  Note that the RSSI menu is under the DIAGNSE  menu and not the CONFIG menu     ENTER      USER PROMPTED FOR    _ PASSWORD  UF       Figure 3 4  Menu Map to RSSI Mode    Now that the Field Unit is in the RSSI mode  bring the Field Unit close to  the equipment you wish to monitor  Look at the LCD  notice          gt     will  constantly fluctuate  You should estimate an average value based on these  fluctuations  The ideal signal integrity 15 seven arrows     Once you have verified that you are receiving a signal  you should check  to make sure the Field Unit is communicating properly with the Base  Radio  To do so exit the RSSI by pressing ENTER  and then navigate to  the EXIT  of the diagnostic menu and return to the Operations Sequence  shown in Figure 4 1 in Section 4 1     If you see a NO RF message  then you do not have satisfactory RF  communication with the Base Radio  If your application allows  move the  Field Unit to a different position and check again for communications  If  your application only allows you to mount at this particular point  you may  want to try a slower baud rate setting for an increased range     One final soluti
41. er normal conditions  The Field Unit has a se   lectable range of 1 5  10  15  20  40 seconds and 1 minute  Figure 6 3 is an    If the device is not configured to check for abnor     mal process conditions using Sample Bands   section 6 6   the Abnormal Transmission rate is      ak  not used and this section can be ignored  example of how the device switches transmission rates from Normal    Transmission Rate to Abnormal Transmission Rate  Note how the first       abnormal transmission is sent immediately when the Normal Upper Value  set point is exceeded  The next transmission will then follow this immedi   ate transmission by 10 seconds  or whatever the Abnormal Transmission  Rate is set to   The transmissions will continue at this interval until the  process value drops below the Normal Upper Value set point     Once the process value drops below this set point  another transmission is  sent to the Base Radio  The transmissions will then be sent at the Normal  Transmission Rate of one minute  the current setting for the Normal  Transmission Rate  from the time of the last abnormal transmission     The user should also note that the transmission time depends on the sam   pling rate  and when the process value is sampled  If the Normal Sampling  Rate 1s 30 seconds  then the process value may be above the Normal Up   per Value for up to 29 seconds before an abnormal condition is detected   This means that the transmission could be as late as 29 seconds after the  process valu
42. error within RF communications   SEN ERR    fatal error within the sensor electronics   SYS ERR    fatal error within the microprocessor system  RF CAL   fatal error within the RF calibration system    Rev 1210 45    Appendix                  c           NTER            ENTER                         Factory passwords will be hard    READ ONLY 1 coded  User password will be  Saas 0000 from factory                                           gt  RECHTE  RF OFF is Default    NEXT    ENTER NEXT         NEXT Default of 19 2K    NEXT    Default of 000    NEXT  m   NEXT    NEXT    ENTER  amp  NEXT  AT ANY TIME       If ENTER  is pressed while YES is being displayed the value is saved   If  ENTER  is pressed while NO is being displayed the value is NOT  saved   The sensor should be at ZERO when YES is selected    Note  If a menu is left  unchanged for 2 minutes then    the Field Unit will return to the  Operations Sequence       NEXT    IF  YES  IS  SELECTED  NEW  TRIM IS SAVED   IF    NO  IS      SELECTED  TRIM       POINT IS  DISCARDED     IF    YES    IS  PRESSED  TRIM IS  RESET    IF  NO  IS  PRESSED  NEW  TRIM IS  CANCELLED        46 Rev 1210    Appendix D       Modbus Register Definitions       Pressure Units          InH20At68F m1     inches of water at 68 degF     InHgAtOC   2     inches of mercury at 0 degC     FtH20At68F   3     feet of water at 68 degF     MMH20At68F   4     millimeters of water at 68 degF     MMHgAtOC   5     millimeters of mercury at 0 degF     PS   6     
43. ffset and trimming the process measurement     Section 8  Selecting and Configuring Operation Modes   In this section the four operation modes  pressure  orifice flow  open chan   nel flow  and level  of the Differential Pressure Field Unit are discussed in  order to aid the user in selecting the right mode for his or her application  and properly configuring the Field Unit for that specific application     Section 9  Maintaining the Field Unit  This section explains how the Field Unit should be cared for once it has  been placed into service and how to change the battery      Section 10  Technical Specifications   This section explains the technical specifications that are associated with  this device such as power characteristics  accuracy  and operating charac   teristics     Rev 1210    AWS Wireless Differential Pressure Field Unit User Manual    1 2  ABOUT THE DEVICE    1 3  UNPACKING    1 4  SOFTWARE  COMPATIBILITY    The AWS Differential Pressure Field Unit is a reliable Radio Frequency   RF  transceiver coupled with a differential pressure sensor that can be  used to monitor a variety of processes in hazardous and hard to reach ar   eas  The time and expense of running wires often makes it difficult to  measure parameters that have an economic impact on your plant opera   tion  but the Differential Pressure Field Unit allows you to quickly and  accurately monitor those devices at a fraction of the cost  which gives you  bigger and faster returns on your instrumentatio
44. g Bracket  The optional mounting bracket  DPB 2S  can be ordered separately     Rev 1210    Section 10  Technical Specifications                                          Dimensioned Mechanical Drawing    Rev 1210 39    AWS Wireless Differential Pressure Field Unit User Manual    FM APPROVED INTRINSICALLY SAFE INSTALLATION CONTROL DRAWING    HAZARDOUS  CLASSIFIED  LOCATION    Class    Zone 0  Group        Class 1  Division 1  Groups A  B  C  and D  Class Il  Division 1  Groups E      and     Class III    Ui  Vmax    30V  li  Imax    100mA  Pi   0 9W   Cis 0   Li 0    Notes    1  The Intrinsic Safety Entity concept allows the interconnection of two FM Approved intrinsically safe devices with entity  parameters not specifically examined in combination as a system when   Uo or Voc or Vt  lt  Vmax  lo or Isc or It  lt  Imax  Ca      Co          Ccable  La or Lo  gt  Li   Leable  Po  lt  Pi   Dust tight conduit seal must be used when installed in Class Il and Class    environments   Control equipment connected to the Associated Apparatus must not use or generate more than 250 Vrms or Vdc   Installation should be in accordance with ANSIISA RP12 6  Installation of Intrinsically Safe Systems for Hazardous   Classified  Locations  and the National Electrical Code    ANSI NFPA 70  Sections 504 and 505   The configuration of associated Apparatus must be FM Approved under Entity Concept   Associated Apparatus manufacturer s installation drawing must be followed when Installing this equipm
45. he Smart Rate  click the check box labeled Enable Smart  Rate  The user will then be allowed to enter a    delta     or amount changed     value which will trigger a transmission     Once a value has been entered  click OK to save and download the  configuration changes to the Field Unit     Rev 1210 25    AWS Wireless Differential Pressure Field Unit User Manual    6 6  Selecting Rates  Thresh   olds  and Deadbands via  the WIM    Differential Pressure Properties   00009044  9 44     General   Range   Operation Mode   Sensor Offset    Sampling Rates        Sampling Bands   Alarms  Update Rates   Normal Transmit Rate  10 Sec   Abnormal Transmit Rate  5 Sec   Normal Sampling  1 Sec   Abnormal Sampling  1 Sec    Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband              Enable Smart Smoothing       1 255 Seconds  Percent Sqr Rt    SmartRate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes by the amount set              Enable SmartRate          Load from File       Save to         OK Cancel    Figure 6 6  Sample and Transmission Rate  Selection Using WIM          Differential Pressure Properties   00009044  9 44   General   Range   Operation Mode   Sensor Offset    Sampling Rates Sampling Bands   Alarms  Upper Limits      Use Input 1 Limit                Value  Percent Sqr Rt  Time Deadband  
46. ialog box  Once in the  configuration dialog box  click the Sensor Offset tab to bring up the offset  information as shown for Level in Figure 7 4     Differential Pressure Properties   00009044  9 44     Sampling Rates l Sampling Bands   Alarms    General   Range   Operation Mode Sensor Offset    O Disable Sensor Offset Curve     Enable Sensor Offset Curve  Curve Parameters    Number of Pairs of Values  2    Indicated Actual Value Indicated Actual Value  Value Value    Point 0  Point 1                   1                                 values are in units of  Psi          Load      File  Save to File    0K Cancel    Figure 7 4  Setting a 22 Point Curve Using  WIM       Rev 1210 29    Section 8       Selecting and Configuring Operation Modes    8 1  Differential Pressure    Differential Pressure Properties    9 44     Sampling Rates   ling Band  Alarms  General   Range    Sensor Offset    Mode    Pressure    Pressure Units     NOTE  Square root is OFF             Load from       Save to         OK Cancel    Figure 8 1  Differential Pressure Setting  Using WIM    30       In this section the four operation modes  differential pressure  orifice flow   open channel flow  and level are discussed in order to aid the user in se   lecting the right mode for his or her application and properly configuring  the Field Unit for that specific application  The subsections are as follows     8 1  Differential Pressure  8 2  Orifice Flow   8 3  Open Channel Flow  8 4  Level    This mode si
47. ications    WI TC NT yy z  IC Temperature    CO RT N  CO RT NT  CO RT NT   Resistance Tape     WHGP S xxHAL  WI AP S xxHAL  Pressure Sensor       yy   Y6 Y9 2   Antenna cable length  max length 100 ft with bonded ground   NOTE  Devices connected to J3 and input wires must be of  Simple Apparatus  type     e e           VS Installation Control Drawing     Wireless Sensors    MEER RR    Rev 1210 43       Appendix A       Navigating User Menus    Pressing either the NEXT or ENTER buttons located on the front of the  Field Unit or Base Radio just below the Liquid Crystal Display  LCD   screen 15 all that 15 needed to navigate the respective menus  Pressing both  of these buttons for one second will turn the unit on     Pressing the NEXT button at any time while the Field Unit is cycling  through the normal messages causes the Field Unit to enter the setup  mode  The NEXT button is then used to step through menu options  and  the ENTER button is used to enter a sub menu of what is displayed on the  LCD at that time  If no button is pressed within a 30 second period the unit  goes back to the normal display mode     If you enter a sub menu that requires a numerical input  such as 001  the  left most 0 will be blinking  This indicates that pressing the NEXT button  will increment this value with each press from 0 to 9 and back to 0 again   Pressing the ENTER button will move to the next available value  If the  last value is blinking  pressing ENTER will save the entered values and 
48. ing the RF Communications  RF Channel Selection   RF Baud Rate Selection   RF Identification Selection   Configuring the Sampling and Transmission Rates  Selecting the Normal Transmission Rate  Selecting the Normal Sampling Rate   Selecting the Abnormal Transmission Rate  Selecting the Abnormal Sampling Rate  Setting the Smart Rate Threshold   Selecting Rates  Thresholds  and Deadbands via the Software  Configuring the Process Variable  Zeroing the Sensor   Setting a Measurement Offset   Trimming the Measurement   Entering a 22 Point Curve   Selecting and Configuring Operation Modes  Differential Pressure   Orifice Flow   Open Channel Flow   Level   Maintaining the Field Unit    9 1  Changing the Battery  Section 10  Technical Specifications  Dimensioned Mechanical Drawing  Appendix A  Navigating the Menus  Appendix B  Displayed Message Definitions  Appendix C  Field Unit Menu Map  Appendix D  Modbus Register Definitions    Rev 1210    oR BR                              14  15  15  16  16  17  17  18  18  19  19  Oon  21  22  23  24  25  26  27  27  28  28  29  30  30  31  33  35  36  36  37  39  44  45  46  47       IH    IV       Table of Figures    3 1  Example of Incorrect Field Unit Positioning                   eene 5  3 2  Installation in Liquid Flow                                                      2  3 3  Installation in a Steam Application                                                           7  3 4  Menu Map to RSSI                                eva UA NAES
49. led     For this step  power the unit and apply zero pressure  Be sure that the unit  15 installed in its final location or that it is oriented exactly as it will be in  its final installation  If you have a differential pressure device  you will  also need to go through a series of operations to fill the impulse lines to  the device  See Section 3 2  Commissioning      If you have a transmitter pressure reading of  zero    that is  the transmit   ter reading is within the specified accuracy of  0 07  of the full scale  value when zero pressure is applied   there is no need to zero the sensor   If your    zero    reading is outside of this value  you will need to execute the  position zero adjustment by following the menu map shown in Figure 7 1        When P ZERO is selected  the sensor is zeroed  However  the displayed  value 15 calculated relative to the offset point  The unit will display an  amount equal to the keypad configured offset added to the WIM   configured level offset  if applicable  If the intent is to have the unit dis   play    0          offsets must be zero before applying P ZERO     For example  1f 3 PSI of pressure 15 applied to a sensor  an offset of 5 PSI  15 entered into the keypad  and P ZERO 15 applied  the unit will display 5  PSI  If the pressure is then raised by 1 PSI to 4 PSI  the unit will display 6  PSI           PASSWORD UF                ENTER     If  ENTER  is pressed while YES is being displayed the value is  7                YES  NO     
50. may adjust itself for the specified amount of time     Rev 1210 13    AWS Wireless Differential Pressure Field Unit User Manual    3 3  Commissioning    3 3 1  Liquid Service  Commissioning Using a 3 Valve    3 3 1  Liquid Service Zeroing  Using a 3 Valve Manifold    In this section commissioning instructions are discussed for the various  setup capabilities of the Differential Pressure Field Unit  The subsections  are as follows     3 3 1  Liquid Service Commissioning Using a 3 Valve Manifold  3 3 2  Liquid Service Zeroing Using a 3 Valve Manifold    Be careful when commissioning your transmitter  Transient pressure shock  waves that can overpressure the sensor causing zero shifts  These are most  always generated on the upstream side of the instrument  By design  mini   mum zero shift is generated when the transmitter is over pressured on the    side  Sensors are protected for overpressure on either side to the full  pressure rating of the process flanges  However  stresses induced during  overpressure will cause a temporary zero shift  It is therefore recom   mended that during commissioning and zeroing  every attempt should be  made to prevent over pressuring the sensor on either side  The procedures  outlined below will allow commissioning and zeroing without over   pressurizing     In the event that the sensor is subject to significant over pressure  steps  must to taken to re establish the neutral instrument zero  If the sensor is or  has been over pressurized on      
51. mode    turns off most of the electronics on the unit  with the exception of the  LCD  in order to preserve battery life  The Field Unit will then    wake up     for every Normal Sampling Period and take the necessary process value  readings     Notice that the minimum speed of the Normal Sampling Rate is dependent  on the Normal Transmission Rate setting selected  see Section 6 1   The  Sampling Rate cannot be set slower than the Normal Sampling Rate  Thus   if you selected the Normal Transmit Rate setting to be 10 Seconds the  Normal Sampling Rate must be set to 10 Seconds or faster  A complete  table of these parameters is shown below     olts            p 500 750 feet 2000 2500 feet 3000 feet  P i 20 Seconds    10      Normal and Abnormal 1 Second or 5 Seconds or 20 Seconds or  Sample Normal and Abnormal Equalto Transmit   Equalto Transmit   Equalto Transmit  43  In order to properly set the Normal Sampling Rate determine how often  updates are needed from the Field Unit when the process being monitored             S Time  min   With a Normal 200 is operating under normal conditions  The Field Unit has a selectable  Sampling Rate of 30 Seconds range of 1 5  10  15  20  30  and 60 seconds depending on the Normal  Figure 6 1  Incorrect Sampling Rate Transmission Rate  The factory default is 1 second  However  the more  frequently the Field Unit wakes up to check the monitored device  the  TM faster you will use up the battery life ofthe Field Unit   npu  pis ie Figure 6 1 1
52. mply calculates and displays the differential pressure value  from the Differential Pressure sensor  To set the Field Unit to this opera   tion mode  you must go to the configuration menu of the Field Unit via  the Software  For further instructions on getting to the configuration  menu see Section 9 2 of the Wireless Instrumentation Manager User  Manual     Once you have opened the configuration menu  select the Operation  Mode tab at the top of the menu  You should then see a menu like the  one shown in Figure 8 1     To select the Differential Pressure mode  select Pressure in the Mode  drop down box  This will display another drop down box which will al   low the selection of differential pressure engineering units  You should  select the units that are appropriate for your application  All possible  units are listed below     Mm of HG  Mercury    0      Pounds per inf  PSD  pss         Once engineering units have been selected  a 22 point sensor offset curve  can be enabled  it is disabled upon delivery from the factory  by selecting  the Sensor Offset tab within the configuration menu     Rev 1210    8 2  Orifice Flow    Differential Pressure Properties    9 44     Sampling Rates   ling Band  Alarms  General   Range Sensor Offset    Mode    Orifice Flow                   Differential Pressure  5 Psi   Flow  10 Cubic Feet   Sec  Full Scale Flow  8 4929 Cubic Feet   Sec  Truncation Point  5 Cubic Feet   Sec    Flow Units  Cubic Feet   Sec    NOTE  Square root is ON       
53. n investments     The Field Units communicate in a secure  digital protocol over a band of  frequencies from 902MHz to 928MHz  This data communication tech   nique has been the backbone of the military s secure communications pro   tocols for many years  These devices require no wires  permits or licenses   and they are easily set up and installed right out of the box     You can use this device for long term monitoring in remote locations  for  short term data gathering on process conditions  or to quickly test the eco   nomic viability of a new installation     The purpose of this manual is to help you install and maintain your AWS  Differential Pressure Field Unit  BEFORE setting up and installing the  Field Unit please setup and configure the Base Radio     Remove the Packing List and check off the actual equipment received  If  you have any questions about your shipment  please call your Adaptive  Wireless Solutions Representative  Upon receipt of the shipment  inspect  the container for any signs of damage in transit  Especially take note of  any evidence of rough handling  Report any apparent damage immediately  to the shipping agent     Please note that sometimes units are assembled with accessories when  shipped  Inspect the shipment carefully if you think that something is  missing  This is rare  as we take considerable care to pack units for ship   ment  but it does sometimes happen  Please give us a call and we may be  able to resolve this matter quickly over the 
54. ng                                         26  7 1  Menu Map to Pressure Zero Setting    27  7 2  Menu Map to Offset                                             COS Db Nase bun Eds 28  7 3  Menu Map to Trim Set Ugo eio n ER SEU EPA CEPI o PER LAB COR RISE           28  7 4  Setting a 22 Point Curve Using      sess 20  8 1  Differential Pressure Using WM  sedaceneenxessnsuncunkus odia ohh E Ven uon Rs 30  8 2                Ae                                            31  8 3  Orifice Flow with Square Root Calculation                                                    32  8 4  Open Channel Flow Mode scisco    bro cO                                        33  8 5  Level                    ex eb UA E UU ERE ON AD eR PRX ORE ERO aeia 35  Dimensioned Mechanical Drawing vsscswsvesvisssdorsestavenddinetiocansssnnedsenvestevuareetssaanivess 39  Appendix C  Field Unit Menu Ma                                                                                                                                              46    Rev 1210                 1    Introduction    1 1  USING THIS MANUAL       This manual is designed to assist in installing  operating  and maintaining  AWS Model WI DP Differential Pressure Field Units  The manual is bro   ken into sections as follows     Section 2  Quick Start   This section summarizes what must be done in order to get the device in   stalled  configured and in operation quickly  However  it does not provide  detailed or how to information to perform
55. ng      Sampling and Transmission Rates    6 1  Selecting the Normal  Transmission Rate    The Differential Pressure Field Unit is very versatile with many program   mable features and can be used in numerous different applications  Be   cause no two applications are the same  some configuration is required for  each unit  This section will walk you through the initial configuration of  these sample and transmit settings  The subsections are as follows     6 1  Selecting the Normal Transmission Rate   6 2  Selecting the Normal Sampling Rate   6 3  Selecting the Abnormal Transmission Rate   6 4  Selecting the Abnormal Sampling Rate   6 5  Setting the Smart Rate Threshold   6 6  Selecting Rates  Thresholds  and Deadbands via the Software    The Normal Transmission Rate is the interval in which the Field Unit  transmits data to the Base Radio  The Field Unit is in a    sleep    mode to  save power during the operations sequence  This mode turns off most of  the electronics on the unit  with the exception of the LCD  in order to pre   serve battery life  The Field Unit will then    wake up    every Normal Sam   pling Period and take the necessary process value readings  The Field Unit  will then transmit these readings to the Base Radio on an interval deter   mined by the Normal Transmission Rate     Notice that the fastest update rate of the Normal Transmission Rate is de   pendent on the baud rate setting you selected earlier  see Section 5 2   The  transmission rates cannot up
56. ng a    LOW  BAT  message on the Field Unit  This is a simple process     1  Make sure you have the correct replacement battery     AWS model   WI BAT   TADIRAN    Lithium Inorganic Battery  non rechargeable   Size              3 6Volts   A TL2200 S    2  Power down the Field Unit by pressing and holding both the NEXT     Warning    and ENTER buttons for a few moments     When removing the housing do not 3  Remove the 4 set screws on the sides of the Field Unit housing with  twist or bend the green flex cable  Do  a standard screw driver   ing so may cause the tether to improp     erly seat next to the antenna and greatly 4  Remove the housing and locate the battery  Warning  When remov   reduce operable RF distances  Do not ing the housing do not twist or bend the green flex cable  Doing so  allow the housing to flop around while may cause the tether to improperly seat next to the antenna and  hanging by the tether  greatly reduce operable RF distances  Do not allow the housing to  flop around while hanging by the tether        5  Remove the old battery and replace it with the new battery positive  end first   Note that the positive end of the battery clip is the end  with the red wire      6  Plug the green wire flex cable back in 1f unplugged and replace the  housing  Then  screw the housing back on  and power up the unit by    pressing either of the buttons     7  Properly dispose of used battery     36 Rev 1210                 10       Technical Specifications    Differe
57. nits drop down  list to show the Square Root Calculation     Rev 1210    Section 8  Selecting and Configuring Operation Modes    8 3  Open Channel Flow This mode lets the user setup flow calculations for open channel flow   measurements for weirs  In order to make this calculation  the user must   Differential Pressure Properties    9  enter the density of the material  a differential pressure value and a match    Sampling Rates       i ing flow value  In addition  a truncation point value must be entered  Fi               Rim      nally       user must fill out the 22 point curve table indicating the rela   Mode    Open Channel Flow tionship between column height and flow rate        Flow    To set the Field Unit to this operation mode  you must go to the configura   tion menu of the Field Unit via the Software  For further instructions on  getting to the configuration menu see Section 9 2 of the Wireless Instru   1  10 Cie Si mentation Manager User Manual    Full Scale Flow  7 213 Cubic Feet   Sec  Truncation Point  5 Cubic Feet   Sec Once you have opened the configuration menu  select the Operation  Flow Units  Cubic Feet        Mode tab at the top of the menu and select Open Channel Flow from the  mode menu  You should then see a menu like the one shown in Figure 8 3                 Differential Pressure  5 Psi    Select the units that are appropriate for your application  All possible units  are listed below     T p  lt  lt   Figure 8 4  Open Channel Flow Mode    NOTE  S
58. ntial Pressure Input Characteristics                       Maximum Statie Pressure       WI DP I 100PSI   100    25 PSI 2000 PSI  WI DP I 300PSI   300    25 PSI 2000 PSI       Accuracy      0 2   of full scale reading including combined effects of temperature   hysteresis and repeatability  Stability  e Less than   0 25      of sensor URL per year at reference temperature          Return from Overpressure  e  0 04        Sensitivity in Reverse Pressure Direction  e Within 1 0   of forward direction    Mounting and Positioning Effect      1 5 In H O  correctable with position zero       Output Resolution  e See the Base Radio description for analog and digital output options    Operating Temperature Range   e  40  F to  220  F   40  C to  104  C  process connection temperature  steady state   e   A0 F to  185  F   40  C to  85  C  electronics       A F to  158 F   20 C to  70      display  full visibility    e  40  F to  185  F   40  C to  85  C  display  with reduced visibility    e Humidity Limits  0 to 100    Sampling and Transmission Characteristics  The Differential Pressure Field Unit samples differential pressure or flow at regular inter   vals  The data may then be transmitted to the Base Radio for centralized monitoring and  data acquisition  The user specifies how frequently the process is monitored and how of   ten data is transmitted    e Differential Pressure Flow     user designates low rate and high rate conditions    e Sampling rate     user selectable from 1 t
59. o 60 seconds  low rate  and from 1 to 30  seconds  high rate     e Transmission rate     user selectable from 1 second to 60 seconds  low and high  rate   Power Characteristics      Self contained power           Size 3 6 V lithium battery     Up to five year battery life  depends on sample rate and RF update rate   field replaceable    Rev 1210 37    AWS Wireless Differential Pressure Field Unit User Manual    38    RF Characteristics       902MHz   928 MHz Frequency Hopping Spread Spectrum  FHSS   FCC certified ISM  license free band    e Up to 3000  range from Base Radio with clear line of sight  500    to 1000    range with ob   structions              RF module in each field unit is individually tested and calibrated over the full tem   perature range to ensure reliable wireless operation    Self Diagnostics  Low battery alarm     indicates the need to replace the battery  approximately one month warning        Contains extensive self checking software and hardware that continuously monitors the  operation         sensor or device parameter out of spec is identified and reported    Materials of Construction              316 stainless steel base              316 stainless steel diaphragm  Hastelloy C is available upon special request               316 stainless steel flange and bolts  Hastelloy C is available upon special request   e DC 200 silicone sensor filling fluid  Florolube available upon special request      Weight approximately 6 2 Ibs  2 8 kgs      GE Lexan   co
60. of Sight    e  76 8K  Rate of 76 8 Kbaud  Update every 1 second     Range of 500ft to 750ft  Line of Sight     A faster RF Baud Rate allows the user to transmit more information in a  given period of time  but it will also limit the Field Unit s range  If you  need more distance out of your Field Units or are encountering difficulties  by frequently losing communications  then select a slower baud rate     Follow the Base Radio menu map shown in Figure 5 2 to configure the RF  Baud Rate  The factory default is the 19 2K Baud Rate          USER PROMPTED FOR      SSWOI i                a MuR RFC TEN    NEXT                BAU M 4 8K    ENTER NEXT   1 NEXT Default of 19 2K   NEXT                            Figure 5 2  Menu Map to Baud Rate Setting    Each Field Unit is identified by the Base Radio and WIM according to the  RF ID given to that particular unit  Two Field Units CANNOT have the  same RF ID and be on the same RF Channel  if you do not know the RF  Channel see section 5 1   If the Field Unit is in the Operations Sequence   pressing the ENTER button displays the Read Only Sequence on the LCD   The RF ID of that unit will be displayed in this format  ID 3          Field Units in your system are set to a default RF ID number upon ship   ment  For example  if you have ordered a Base Radio and three Field Units   the Field Units will be configured to RF ID s 0  0 and 0  You must set these  units to three different IDs between 1 and 100  The Field Units in this exam   ple c
61. on is to reposition the Base Radio  However  this may  affect communications with previously installed Field Units  and if so   may require the use of a second Base Radio for your application  To select  a better spot for the Base Radio  see Section 3 1 1 of the Base Radio User  Manual     The Link Test measures the wireless link performance of a Field Unit  running in its normal operating mode  Messages are sent from the Field  Unit to the Base Radio at a predefined interval called the Transmit Rate   see Section 6 1   Each message contains data for the previous time period   since the last transmit   The Link Test looks at the wireless performance  going in both directions  from the Field Unit to the Base Radio and vice  versa  and comes up with a rating  The result that appears on the display  shows the determined link strength     In order to perform this test  the Field Unit must be communicating on the  same channel and baud rate as the Base Radio  See Section 5 to configure  communications     The Link Test may be conducted from the Field Unit  Base Radio  or  through WIM  Running the Link Test from WIM 15 ideal for testing  communications for an installation with remote or hard to get to Field  Units  To conduct the Link Test from a Base Radio  see Section 3 2 2 2   To conduct the Link Test from WIM  see Section 3 2 2 3     Rev 1210 9    AWS Wireless Differential Pressure Field Unit User Manual       3 2 2 1  Conducting a Link Test from the The Link Test is located in
62. ould be set to RF IDs 1  2 and 3     First determine the RF ID s you d like to give each unit  Then follow the    menu map shown in Figure 5 3 to configure the RF ID  The factory default  is RF ID 0  which disables the RF communication of the unit     Rev 1210 19    AWS Wireless Differential Pressure Field Unit User Manual    5 3  Continued    20    1    OPERATIONS SEQUENCE I   NEXT           E sm    USER PROMPTED FOR      PASSWORD 1   enteR  gt  RE CHAN      NEXT    NEXT   ENT ID   L R  ID ers Default of 000    Figure 5 3  Menu Map to RF ID Setting    Once you have selected the RF ID you wish to use for this particular Field  Unit  exit the menus and return to the Operations Sequence     The Field Unit should now be successfully configured to the Base Radio   To check this  press ENTER while the Field Unit is in the Operations Se   quence for the Read Only Sequence to be displayed  You may see an RF  SYNC message displayed on the Field Unit LCD  This means that the  Field Unit and Base Radio are attempting to synchronize communications   If this 1s successful the RF Status will display an RF OK message  If this is  unsuccessful the RF Status will display a NO RF message     Also notice the two small arrows on either side of the LCD  if they are  fluctuating up and down  that indicates the Field Unit and Base Radio are  successfully communicating  If only one or none of the arrows are moving  then RF communication is unsuccessful     Rev 1210                 6       Configuri
63. phone     The carrier will not honor any claims for damage unless all shipping ma     terials are saved for their examination  If you find any damage while you  are examining and removing the contents  save the packing material and  the carton        Software for AWS 15 revised periodically  Internal device software may  contain portions that are not compatible with previous versions of the  Wireless Instrumentation Manager software     To ensure software compatibility  Wireless Instrumentation Manager soft   ware version 1 70 138 or later must be used  If you believe you are experi   encing software compatibility issues please call Adaptive Wireless Solu   tions Technical Tech support at  978  875 6000 or email techsup   port adaptive wireless com       Rev 1210    Section 2    Quick Start       Warning A    Warning  If the Field Units have been running for  an extended period of time with no signal from the    Base Radio  the Base Radio is off or not present    the Field Units will only search for the Base Radio  every one hour or so  Turning the Field Units off  and back on will cause them to begin searching  immediately           This section summarizes what must be done in order to get the device in   stalled  configured  and in operation quickly  However  it does not provide  detailed or how to information to perform the tasks outlined     Install the Field Unit in the desired location of operation    Turn on the Field Unit by simultaneously pressing and holding the   E
64. pounds per square inch      BAR  7     bars      MilliBAR   8     millibars      GMPerSqCm   9     grams per square centimeter     KGPerSqCm   10    kilograms per square centimeter     Pascals   11     pascals      KiloPascals   12     kilopascals      Torr   13     torricellis      Atmospheres   14     atmospheres      PSIA   175     pounds per square inch absolute     FtH20At4C   177    feet of water at 4 degC     MetHgAtO0C   179     meters of mercury at 0 degC     MegaPascals   237     megapascals      InH20At4C   238     inches of water at 4 degC     MMH20At4C   239     millimeters of water at 4 degC          Volumetric Flow Units          CuFtPerMin   15     cubic feet per minute      GalPerMin   16     gallons per minute      LiterPerMin   17     liters per minute      ImpGalPerMin   18     imperial gallons per minute      CuMeterPerHr z19     cubic meter per hour      GalPerSec   22     gallons per second      MillionGalPerDay   23     million gallons per day      LiterPerSec   24     liters        second      MillionLiterPerDay   25    million liters per day      CuFeetPerSec   26     cubic feet per second      CuFeetPerDay   27     cubic feet per day      CuMeterPerSec   28     cubic meters per second      CuMeterPerDay   29     cubic meters per day      ImpGalPerHr   30     imperial gallons per hour      ImpGalPerDay   31     imperial gallons per day     NormCuMeterPerHr   121    normal cubic meter per hour   MKS System     NormLiterPerHr   122     normal liter per
65. quare root is OFF                NOTE    For Open Channel Flow  a 22 point curve table  must be filled out for correct operation        Rev 1210 33    AWS Wireless Differential Pressure Field Unit User Manual    8 3  Open Channel Flow  cont      Once engineering units have been selected  a 22 point sensor offset curve  must be enabled  it is disabled upon delivery from the factory  by select   ing the Sensor Offset tab within the configuration menu        34 Rev 1210    8 4  Level    Differential Pressure Properties    Sampling Rates  General   Range    Mode    Fluid Level    Level     Density        Full Tank Pressure      9 44     Sensor Offset      Pounds   Cubic Foot       Tank Height   Tank Volume   Level Offset     Level Units     NOTE  Square root is OFF    Feet    Cubic Feet    Feet    Feet             Load from File       Save to            OK Cancel       Figure 8 5  Level Mode    NOTE    For Level  a 22 point curve table must be filled  out for correct operation        Section 8  Selecting and Configuring Operation Modes    In this mode  the user has the option of entering the density of material or  the full tank pressure  Also  the user must enter tank height and tank vol   ume  Finally  the user must select level units  which can be in units of  height  volume  or mass  The entered information is used to make level  calculations in the units selected by the user  For non uniform tanks  the  user must also fill out the 22 point curve table indicating the relation
66. ress ENTER  The Field Unit will prompt you to apply the indicated proc   c n       than ess value to the Field Unit  Apply the process value and press ENTER       Repeat the process for the higher point  After both points have been   trimmed  you can choose to save or discard the new trim                                                                                                                                                                             9000 00 enter    APPLY ENTER     1  pO E               cs Met                  1  1  pase eee 1    1       OPERATIONS SEQUENCE        CONFIG ENTER    gt   HIPNT jJ             0000 00 jewree  APPLY ENTER     I  rin eae a a ENTER       ee  ne ri     USER   t    SAVE         YES             IF YES  IS    PROMPTED   H     SELECTED  NEW    FOR    NEXT TRIM IS SAVED   PASSWORD   i IF  NO  IS              NEW TRIN  NO  ewe SELECTED  TRIM       POINT IS  SET RF nat DISCARDED  T  NEXT             IF YES IS      PZERO RESET     sewen     YES     PRESSED  TRIM IS  ENTER   T    RESET  NEXT      bri IF  NO  IS  x   PRESSED  NEW  OFFSET EXIT  NO HENTER  TRIM 18  CANCELLED  NEXT                   TRIM  Jewew  INPUT 1               NEXT    INPUT 2    NEXT             EXIT           Figure 7 3 Menu Map to Trim Setting    28 Rev 1210    7 4  Entering a 22 Point Curve    Section 7  Configuring the Process Variable    If you are running WIM  a 22 point sensor offset curve may be entered for  the Field Unit  To do so  open the configuration d
67. ship  between height and volume     To set the Field Unit to this operation mode  you must go to the configura   tion menu of the Field Unit via the Software  For further instructions on  getting to the configuration menu see Section 9 2 of the Wireless Instru   mentation Manager User Manual     Once you have opened the configuration menu  select the Operation  Mode tab at the top of the menu and select Fluid Level from the mode  menu  You should then see a menu like the one shown in Figure 8 4        Once engineering units have been selected  a 22 point sensor offset curve  must be enabled  it is disabled upon delivery from the factory  by select   ing the Sensor Offset tab within the configuration menu     Rev 1210 35                 9       Maintaining      Field Unit    The Differential Pressure Field Unit is extremely easy to maintain in that it  requires no periodic calibration or system checks  The Field Unit has a self   diagnostic that 15 constantly checking the internal system  If any errors  are found they are reported via the LCD  Base Radio or in the WIM  A  simple yearly visual inspection for the following is all that 15 needed     e 15 the Field Unit still securely fastened to the equipment be   ing monitored     e        there any visible corrosions  cracks or residue build ups  on the unit        Has anything about the application changed from the original  intended use     9 1  Changing the Battery The battery will need to be changed within one month of seei
68. sword    Differential Pressure Properties   00009044  9 44     Sampling Bands   Alarms    Range   peration Mode   Sensor   ffset      Description    Location     Date Installed     Comments     General    Monitored Equipment     Field Unit Password  0000    NOTE  Device is in Pressure mode and units are in Psi              Load from File        Save to         OK Cancel  Figure 4 4  Setting a User Password    4 5  Resetting All Field Unit  Settings    Resetting the Field Unit by using the DEFAULT    menu option will not reset the TRIM or OFFSET  values        Section 4  General Configuration    Each Field Unit has a password that will lock out undesired users from  making changes to the Field Unit  Any user may still view some of the  Field Unit settings by pressing the ENTER key during the Operations Se   quence and viewing the Read Only Sequence     The password is a four digit password  The factory default is 0000  If you  wish to select a different password  one may be entered via the Wireless  Instrumentation Manager software  To do so  enter the configuration menu   See Section 9 2 of the Wireless Instrumentation Manager User Manual    Once in the configuration menu  click on the General tab to display the  general information as shown in Figure 4 4     The Field Unit password for this device can be set by entering a four digit  number in the Field Unit Password field  Once a password has been en   tered  click OK to save and download the password to the Field Unit     
69. system when  Voc or Uo  lt  Vmax or Ui  Isc or lo  lt  Imax or li  Ca or       gt  Ci   Ccable  La or Lo 2 Li   Leable  Po  lt  Pi   Where two separate barrier channels are required  one dual channel or two single channel barriers may be used   where in either case  both channels have been Certified for use together with combined entity parameters that meet  the above equations    Dust tight conduit seal must be used when installed in Class Il and Class III environments    Control equipment connected to the Associated Apparatus must not use or generate more than 250 Vrms or Vdc   Installation should be in accordance with the Canadian Electrical Code  Part 1  Section 18    The configuration of associated Apparatus must be CSA Certified under the Entity Concept    Associated Apparatus manufacturer s installation drawing must be followed when installing this equipment    No revision to drawing without prior CSA Approval    Accutech WI RT S  CO RT S  Wi TC S  WI GP S  WI AP S  WI SI S  WI GL S  WI RT M  CO RT M  WI TC M  WI   GP M  WI AP M  WI SI M  WI GL M  WI AM  SW AM  WI AP I  WI GP I  WI RT I  and WI TC I MUST be installed to  a bonded  grounded  process    9  Accutech WI Al  WI AV has an internal ground screw mounted in the enclosure and must be connected to IS ground     ONDAN    Division 2 Waming Statement   WARNING  EXPLOSION HAZARD   DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN  SWITCHED OFF OR THE AREA IS KNOWN TO BE NON  HAZARDOUS    Division 1  Division 2  Zone 
70. t and the Base Radio  The Link Test  data must be configured to match the communication parameters of the  Field Unit from which you want to test  The Link Test is located in the  Base Radio s diagnostic menu  see Figure 3 6      3 2 2 2  Conducting a Link Test from the  Base Radio    To conduct a Link Test from the Base Radio  Navigate to Link Test  and  press the Enter button  Next enter the RF ID for the Field Unit that you  want to test  Then select the Normal Transmit rate that matches that of the  Field Unit  If the Field Unit is transmitting at a different rate than the one  you select in this menu  your results will be invalid     Once the Normal Transmit Rate is selected  the Link Test will  immediately start  The Base Radio will begin to test the link from the  Field Unit  During this time  the word TEST will appear on the LCD  display  When the test is complete  the Base Radio will display the quality  of the link  Be aware that the length of time it takes to perform this test is  dependent upon how fast the Field Unit is normally transmitting     10 Rev 1210    Section 3  Installation        1  3 2 2 2 Continued   OPERATIONS SEQUENCE         ENTER         yere                  ORE    L  1 5 SEC  10 SEC  15 SEC  20 SEC  40 SEC  1 MIN H  ENTER    5 STARR  4 STARR  3 STARR  2 STARR                1 STARR  NO LINK    Figure 3 6  Menu Map to Base Radio Link Test    When enough messages have been observed  a link strength will be shown  on the display  5 STARR indicates
71. uce  costs  save time  enhance safety  improve environmental  performance and cut waste     The next industrial revolution is right now  Let AWS show you  how to realize gains in operating efficiency     Visit us at  www adaptive wireless com  Or call us at  1  978  875  6000    Specifications subject to change without notice  Printed in USA  Copyright 2010 Adaptive Wireless Solutions    Adaptive Wireless Solutions Inc  577 Main St Phone   978  875 6000  Hudson  Ma 01749 Fax   978  568 9085    www adaptive wireless com    
72. updates are needed from the Field Unit when the process being monitored  15 operating under normal conditions  The Field Unit has a selectable  range of 1 5  10  15  20  40 seconds and 1 minute  Figure 6 4 is an exam   ple of how the device switches sampling methods from Normal Sampling  Rates to Abnormal Sampling Rates  Note how the first abnormal sample 15  taken a few seconds after the Normal Upper Value set point 15 exceeded   The next sample will then follow this sample by 5 seconds  or whatever  the Abnormal Sampling Rate is set to   These samples will continue at this  interval until the process value drops below the Normal Upper Value set  point     Once the process value drops below this set point the sampling rate will  return to the Normal Sampling Rate  Also  the Abnormal Sampling must  be equal to or faster than the Abnormal Transmission Rate     The user should also note that the transmission time depends on the sam   ple rate  and when the process variable is sampled  If the Normal Sam   pling Rate is 30 seconds  then the process variable may be above the Nor   mal Upper Value for up to 29 seconds before abnormal condition is de   tected  This means that the transmission could be as late as 29 seconds  after the process variable exceeded the Normal Upper Value     The Wireless Instrumentation Manager software must be used to config   ure this setting  An explanation of how to select the Abnormal Sampling  Rate using the Wireless Instrumentation Manager software
73. users  the antenna type and its gain  should be so chosen that the equivalent isotropically radiated power  EIRP  is not  more than that required for successful communication     The installer of this radio equipment must ensure that the antenna is located or  pointed such that it does not emit RF field in excess of Health Canada limits for  the general population  consult Safety Code 6  obtainable from Health Canada   s  website www hc sc gc ca rpb     FCC Certification    This product is a frequency hopping RF transceiver module for the 900MHz ISM  band  designed to meet FCC 15 247  and is used in industrial control and moni   toring applications     The antenna is factory installed and MUST NOT be removed or modified by  user        O Adaptive Wireless Solutions  2010   Printed in the USA    Rev 1210 I    Table of Contents    Section 1   1 1   1 2   13   1 4   Section 2   Section 3   3 1   3 2   33   Section 4   4 1   4 2   4 3   4 4   4 5   Section 5   5 1   5 2   5 3   Section 6   6 1   6 2   6 3   6 4   6 5   6 6   Section 7   7 1   7 2   73   7 4   Section 8   8 1   8 2   8 3   8 4   Section 9     Introduction   Using This Manual  About the Device  Unpacking   Software Compatibility  Quick Start    Installation   Mechanical Installation   Testing Communications   Commissioning   General Configuration   Field Unit Displayed Messages   Overall Configuration Menu Map   Setting the Field Unit Tag Name   Setting a User Password   Resetting      Field Unit Settings  Configur
74. ver  V 0 rating and UV stable    Operating Vibration and Shock Characteristics  e Certified per IEC EN00068 2 6  vibration  and 2 27  shock     Random Vibration Characteristics     Certified to withstand 6 g s  15 minutes        axis from 9     500 Hz    Electromagnetic Compatibility  CE Compliance     e Operates within specification in fields from 80 to 1 000 MHz with field strengths to 30  V m  Meets EN 50082 1 general immunity standard and EN 55011 compatibility emis   sions standard    Industrial Certification  Pending  e Rated for industrial use  40  F to 185  F   40   C to 85  C      Pending  FM NEMA 4X weather proof housing    e Pending  FM rated intrinsically safe for Class I II III  Division 1  Groups A  B  CD           amp  G  Class III II  Division 2  Groups A  B      D      amp  G     Intrinsic Safety Entity Parameters  Pending  e Maximum operating temperature   85  C    e Temperature Class T4    Configuration  The Wireless Instrumentation Manager is required for initial set up and ongoing configu   ration  Options include a 22 point custom curve capability     The Wireless Instrumentation Manager can also be used for monitoring of the process  information  The user can set thresholds to represent    alarm    or abnormal conditions     A local display provides        Integrated LCD display with membrane switch buttons  e Display provides pressure reading and error messages  if applicable    e Configure RF parameters locally using membrane switch buttons    Mountin
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Texte La République des Lettres  Kramer Electronics CON-COMP-F/M/RG-6  Fostex MR-8HD/CD Computer Drive User Manual    info  Régulateur pour chaudières à combustible solide FK  Data Sheet - Thermal Engineering Lab  User Manual - EagleTac.com  RP-6000MK6 取扱説明書      Copyright © All rights reserved. 
   Failed to retrieve file