User`s Manual

image

Contents

1. 11 230 presents output voltage is 230Vac Default 240 presents output voltage is 240Vac For 100 110 150 120 127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac Default 127 presents output voltage is 127Vac e 02 Frequency Converter enable disable Parameter 2 amp 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default Parameter 2 amp 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz Parameter 3 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable Default Parameter 2 amp 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting
2. 1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 2 Table of Contents 1 important Safety Warning usina la WADE RAWA MI KU 1 Mi ac non E o E O OO p r rr J rr r r hh prp rr O 1 2 Preparation ias 1 RT 1 1G O a aa Daai 1 1 5 Maintenance service and faults ccceceseseeseseeeeeceueueceeeueueueuaeaeanavavavavavavavavavavavars 2 2 IMStallaAUO Nana SetUD asar 3 2591 Rear pane VISWe tii iba 3 252 Sel p INSU PS us 7 SODA ON Sarna o oa a a 9 o54 BUON Opera Aaa 9 E A O 9 3 3 AUTIDIS Ala Misas aser 11 3 4 LED Gisplay WOFrGINGS IMA dad 11 Gas W keye sap e Pa n MD dante tat NA ENA DEN EET ENA DE ED TEE EIN 11 3 6 Operating Mode D sCl lDUOL s a ses xiyare darka d neNEna Za olana 1 ZUR e Taya p U R Tak AA DA DA 14 55 7 Faults Reference Cod incidir 15 G s WL IO IG Ca Te is yl Ac day ln ey nA bA a Ea r ka y dka y ERE Ab ean 15 Z TEOUDISShOOLU QO ii n so yal nn kalen a Y bebin ben benc Y ben n Mbeya na Y bebin Waa nee ene n ben ena 16 Ss Storage and Mantenan e SU DY DO a N iia 18 Os SPECINIEALIONS SWE TN MN acido 19 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1
3. 0 999 setting the backup time in minutes from 0 999 for general outlets on battery mode 0 When setting as 0 the backup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled Default 13 3 6 Operating Mode Description Operating mode LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving Frequency When input frequency is within 40 Hz to Converter mode 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply B power but still can charge batteries 14 3 7 Faults Reference Code Bus start fail Inverter voltage Low 13 x j 3 8 Warning indicator Sounding every second Over Charge Sounding every second
4. Output circuit breaker Output terminal O0 OAN AU AWN 2 2 Setup the UPS Step 1 External battery connection Only for long run model This UPS is not including batteries Please connect external batteries as below chart YA B i e O rg k jI Q 187 Q2 Q 2220 D e ed DAPR LIA RIAS I I y S I Gr 2 SISSI q I IIS SOR BOA 3293 NA ds POIS RAI 305305 A ji DOES ORO SODS T ERVAREN n BRL SEES AES SEES REST KG 203729 295298299 lU TO EXTERNAL BATTERY Step 2 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords e For 200 208 220 230 240VAC models The power cord is supplied in the UPS package e For 100 110 115 120 127VAC models The power cord is attached to the UPS The input plug is a NEMA 5 15P for 1K model and NEMA 5 20P for 2K model Step 3 UPS output connection e For socket type outputs simply connect devices to the outlets e For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm power cords for 3KVA 200 208 220 230 240VAC models Suggest using AWG12 10 or 3 3mm 5 3mm power cords for 3KVA 100 110 115 120 127VAC models Please also install a circuit breaker 40A between the mains and AC input of UPS in 3KVA 100 110 115 120127VAC models for safety operation c Upon completion of the wiring con
5. 1 Transportation e Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation e Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment e Do not install the UPS system near water or in moist environments e Do not install the UPS system where it would be exposed to direct sunlight or near heater e Do not block ventilation holes in the UPS housing 1 3 Installation e Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet e Please use only VDE tested CE marked power cables to connect the loads to the UPS system e When installing the equipment it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed
6. Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is working Battery information Indicates the Battery level by 0 25 26 50 51 75 and 76 100 RATT FAULT Indicates the battery is fault LOW BATT Indicates low battery level and low battery voltage Input amp Battery voltage information E ri Har i E Vde Indicates the input voltage or frequency or battery voltage a HE Vac Input voltage Vdc battery voltage Hz input frequency 10 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Sounding twice every second Continuously sounding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index mx Jn UT Tn Ilala IFA 2S Priun T T n 1 r ENA DIS ESC HLS LS BAT F p H U FE min ina r iv 3 5 UPS Setting There are three parameters to set up the Parameter 1 UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program Parameter 2 Parameter 3 e 01 Output voltage setting Parameter 3 Output voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 200 presents output voltage is 200Vac 208 presents output voltage is 208Vac 220 presents output voltage is 220Vac
7. P a Elo e O ct O gt i a a D om 4 ms Typical Pure Sinewave Time nverter to Bypass Waveform Batt Mode EFFICIENCY Numbers AAC BatteryNumbers J CU Lk _k_ LZ CB 1 0A 2 0A 4 0A 6 0 A PHYSICAL Standard Model Model Net Weight kg __2 Cd 12 142 ENVIRONMENT MANAGEMENT Optional SNMP Power management from SNMP manager and web browser Derate capacity to 80 of capacity in Frequency converter mode or when the output voltage is adjusted to 100 200 208VAC Long run model is only available in 200 208 220 230 240VAC systems Product specifications are subject to change without further notice 20
8. of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not dismantle the UPS system 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K NEMA Type Schuko Type RR CRO JEG CRISIS SII CRISIS RS CASAS 355535555555555 LOLI O OD ww in er O OR OO E MS bs India Type IEC Type NEMA Type Schuko Type Universal Type ese ese OS SISI RRA ROLLO IO B oe SERRE 3338388 Q ORO ROR
9. 3 5mA 1 4 Operation e Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads e The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet e In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance service and faults e The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel e Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Caution risk
10. OR ORO ASIS UDI YU S R eee AO NEMA Type Schuko Type Universal Type IEC Type Universal Type IEC Type Universal Type P 2 OAA Tsee Universal Type OOO OOO 84 998969161618 OOOO IEC Type Universal Type 0707070 495955555553 IES ARE OOOO HOOD ILO O O ati AAA 252825825555 2355553555558555 cono ES OFC 272 O O O Ope OO O HE PISA OSA SOO iA U i HO OG O Nue i i ORO y y ie ISLE D9 kw CO FEO SS 7 25255585852555 s5 OOOO dl gt 2 COK lt 0 Ly Y SOLON Universal Type vi EN FN PN R F PR nnn er Sr A ODO RRA CRO ORO ORC ORO OO 0 000 000 0 0 CD VW MN DAFO Q DA Sr cane wate la RE A R RERE n O O o O z S E 00000002 OLO2O020003 Universal Type O A e KO Y AE CRS cw o ET AI DO O ORORORORO a ORS ee ae OOO amp 2 LE P DT FICO DETER SR z 04344949 China Type AC input Input circuit breaker USB communication port RS 232 communication port SNMP intelligent slot option External battery connection only available for L model Output receptacles
11. Sounding every second Out of bypass voltage range Sounding every second Bypass frequency unstable Sounding every second Sounding every second Battery fault Sounding every second 15 4 Troubleshooting If the UPS system does not operate PL please solve the problem by TT the table below Symptom No indication and alarm even though the mains is normal The icon Aand flashing on LCD display and alarm is sounding every second Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding The icon A and OVER LOAD flashing on LCD display and alarm is sounding twice every second Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 14 and the icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 01 02 03 04 11 12 13 41 and 45 on LCD display and alarm is continuously sounding Possible cause __ cause The external or internal battery is incorrectly connected Battery voltage is too high or the charger is fault Battery voltage is too low or the charger is fault UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass After repetitive overloads the UPS is locked in the Byp
12. ass mode Connected devices are fed directly by the mains The UPS shut down automatically because of overload at the UPS output The UPS shut down automatically because short circuit occurs on the UPS output A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power 16 Remedy _____ connected well firmly connected to the mains The AC input is connected Plug AC input power cord to to the UPS output AC input correctly Check if all batteries are connected well Contact your dealer Contact your dealer UPS is overload Remove excess loads from UPS output Remove excess loads from UPS output Remove excess loads from UPS output first Then shut down the UPS and restart it Remove excess loads from UPS output and restart it Check output wiring and if connected devices are in short circuit status Contact your dealer Symptom Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value charged least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery 17 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperatu
13. figuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 4 Communication connection Communication port USB port RS 232 port Intelligent slot AFP gt To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port 7 Of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 5 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 6 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose
14. ility is normal Voltage igh Line Transfer igh Line Comeback requency Range hase ower Factor Z9 O 5 tQ D O y 110 130 UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal gt 130 UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal urrent Crest Ratio armonic Distortion lt 3 THD linear load lt 6 THD non linear load C Mode to Batt Mode IIO O TI TI J gt O 3 HE lt lu O o lt Y er r o Dd lt Q o DIF Pa iQ c y ct O 5 4 ms Typical Pure Sinewave A Qa gt a 0 ara Time nverter to Bypass Waveform Batt Mode FFICIENCY BATTERY ___jT LLb UZU gt y tO s s i i w i w lt w _ y _ i i Ttt jk Numbers J o 2 6 2 L E a an 7 Battery Numbers 2 1 1 1 1 1 1 1 PHYSICAL Standard Model Net Weight kgs OT O7 26 Model Net Weight kg 41 41 68 68 68 74 74 ENVIRONMENT 20 90 RH 0 40 C non condensing Less than 50dBA 1 Meter MANAGEMENT Supports Windows 2000 2003 XP Vista 2008 7 8 Linux Unix and MAC Power management from SNMP manager and web browser Long run model is only available in 200 208 220 230 240VAC systems Derate capacity to 80 of capacity in Frequency converter mode or when the output voltage is adj
15. range in parameter 3 is from 3V to 12V of the nominal voltage Default 6V LLS Low loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V e 06 Bypass enable disable when UPS is off Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default Parameter 2 amp 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 200 208 220 230 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage point For 200 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac Default 170Vac For 100 110 115 120 127 VAC models 95 110 setting the low voltage point in parameter 3 from 95Vac to 110Vac Default 95Vac e 8 Autonomy limitation setting e 00 Exit setting Parameter 3 Set up backup time on battery mode for general outlets
16. re has been exceeded the batteries must be replaced In this case please contact your dealer B Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 40 C 45 C Every 2 months 18 6 Specifications MODEL pK KK CAPACITY 1000 VA 800 W 2000 VA 1600 W 3000 VA 2400 W INPUT 85VAC 75VAC 65VAC 55VAC 5 or 160VAC 140VAC 120VAC 110VAC 5 Low Line Transfer Ambient Temp lt 35 C based on load percentage 100 80 80 70 70 60 60 0 95VAC 85VAC 75VAC 65VAC or 175VAC 155VAC 135VAC 125VAC 5 Low Line Comeback Ambient Temp lt 35 C based on load percentage 100 80 80 70 70 60 60 0 145 VAC 5 or 300 VAC 5 140 VAC 5 or 290 VAC 5 40Hz 70 Hz Single phase with ground gt 0 99 nominal voltage input voltage 100 110 115 120 127VAC or 200 208 220 230 240VAC 1 Batt Mode requency Range 47 53 Hz or 57 63 Hz Synchronized Range requency Range Batt Mode 50 Hz 0 25 Hz or 60Hz 0 3 Hz Ambient Temp lt 35 C 105 110 UPS shuts down after 10 minutes at battery mode or transfer to bypass when the ut
17. s button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute Select ON Mute and Select buttons simultaneously for 5 seconds Then UPS Button will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range ON Mute Button OFF Enter Button Select Button 3 2 LCD Panel Remaining Backup Time Info Fault Info Input amp Batter Mute Operation Voltage into f Output amp Battery A j i Voltage Info BATT FAULT Battery Info i T Load Info h Mode Operation Info Display Remaining backup time information S Indicates the remaining backup time in pie chart H Indicates the remaining backup time in numbers S IN H hours M minute S second Fault information N Indicates that the warning and fault occurs Indicates the warning and fault codes and the codes are listed in details in 3 5 section Mute operation Indicates that the UPS alarm is disabled Output amp Battery voltage information LI LI i vac Indicates the output voltage frequency or battery voltage Jon Lo Vac output voltage Vdc battery voltage Hz frequency Load aera Indicates the load level by 0 25 26 50 51 75 and 76 100 AD Indicates overload SHORT Indicates the load or the UPS output is short circuit Mode operation information e ooo Indicates the UPS connects to the mains rapa
18. usted to 100 200 208VAC Product specifications are subject to change without further notice MODEL KR KR KR INPUT 85VAC 75VAC 65VAC 55VAC 5 or 160VAC 140VAC 120VAC 110VAC 5 Low Line Transfer Ambient Temp lt 35 C based on load percentage 100 80 80 70 70 60 60 0 Voltage 95VAC 85VAC 75VAC 65VAC or 175VAC 155VAC 135VAC 125VAC 5 Range Low Line Comeback Ambient Temp lt 35 C based on load percentage 100 80 80 70 70 60 60 0 145 VAC 5 or 300 VAC 5 140 VAC 5 or 290 VAC 5 40Hz 70 Hz Single phase with ground gt 0 99 nominal voltage input voltage 100 110 115 120 127VAC or 200 208 220 230 240VAC 1 Batt Mode requency Range 47 53 Hz or 57 63 Hz Synchronized Range requency Range Batt Mode 50 Hz 0 25 Hz or 60Hz 0 3 Hz Ambient Temp lt 35 C 105 110 UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal igh Line Transfer igh Line Comeback requency Range hase ower Factor OUTPUT 110 130 UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal gt 130 UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal urrent Crest Ratio armonic Distortion lt 3 THD linear load lt 6 THD non linear load C Mode to Batt Mode TIO O Tm J gt O 3 RE lt J O O o lt Y FTIT o als DIF
19. your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 3 Operations 3 1 Button operation gt Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm When the UPS is on battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But it s not applied to the situations when warnings or errors occur Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON Mute button for 5 seconds to enter UPS self testing while in AC mode ECO mode or converter mode Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode Down key Press thi