        User manual geoTHERM 6-10 kw user manual Size 3.73 MB
         Contents
1.         24  5 10 2 Activating emergency mode                              25  5 10 3 Errors malfunctions that you can remedy     25  5 10 4 Warning messages                                                 5 10 5 Temporary malfunctions   5 10 6 Blocking error                                          6 Warranty and customer service                  27  yA    1 111      ee 28  74 Technical datansiirrossa 28  7 2 Data badge       Operating Manual geoTHERM VWS 0020045200_00    General information    The Vaillant geoTHERM heat pumps in this manual are  referred to in general as heat pumps and are available  in the following models                    Type name Article number  VWS 61 2 230V 0010005501  VWS 81 2 230V 0010005502  VWS 101 2 230 V 0010005503          Table 0 1 Type designations and article numbers    The heat pumps state of the art appliances  which have been constructed in accordance  with recognised safety regulations     Conformity with the applicable standards has  been demonstrated      DACH  seal of approval    VDE seal and Tested Safety       With the CE mark  we confirm as equipment manufac   turers that the appliances in the geoTHERM range satis   fy the requirements of the Directive on Electromagnetic  Compatibility  Council Directive 89 336 EC   The appli   ances meet the basic requirements of the Low Voltage  Directive  Council Directive 73 23 EEC     Furthermore  the appliances satisfy the requirements of  EN 14511  Heat pumps with electrically driven compre
2.    For the owner    Operating manual    geoTHERM       Heat pump VWS    6668 B B GB    Contents                     General information                                                    3  Data Dadga ia iee AEA E ARER Liisa 3  1 Notes on this manual                                        1 1 Storage of the documents                                      1 2 Symbols used                                  1 3 Applicability of the manual  2 Safety instructions                                           2 1 COOlANES snina  2 2 Prohibition on alterations  3 Notes on operation                                            5  3 1 Intended use                                                              5  32 Requirements of the installation site                  6  33 Cleaning and care                                                    6  3 4 Checking the operational condition of   the heatrpunmbpbDa uya ana a aniaya 6  3 4 1 Filling pressure of the heating system               6  3 4 2 Filling level and filling pressure of the   brine  circuit unine 6  3 4 3 Accumulation of condensate    condensation water                                               7  3 5  Energy SAVING tipSaissisiiisssisereccrsirssiensrecsrsssissss 7  3 5 1 General energy SAVING tips                                    7  3 5 2 Economising by the correct use   of the control system                                               3 6 Recycling and disposal  3 6 1 APpliANC  ni    ccccesesseesssseteseeees  3 6 2  Packagin
3.   Operating Manual geoTHERM VWS 0020045200_00       Display shown       Holiday programming  for cpl  System        6       Period of time  1  gt 06 01 08  2 14 01 08  Room Temp  setpoint    08 01 08  30 01 08    12  C           gt Set start day          Description       For the controller and its connected system compo   nents it is possible to programme two holiday peri   ods with the introduction of the date  Moreover  the  desired target room temperature can be set for holi   days  i e  regardless of the preset timer programme   After the holiday time has elapsed  the controller au   tomatically goes back to the previously selected op   erating mode  The holiday program can be activated  only in auto and eco operating mode    Connected cylinder charging circuits or circulation  pump circuits are automatically switched to OFF op   erating mode during the holiday timer programme     Connected cylinder charging circuits or circulation  pump circuits are automatically switched to OFF op   erating mode during the holiday timer programme   Prolonged periods of absence can be set in the dis   play  Programme holidays   The target temperature  during this period should be selected to be as low as  possible    During this period hot water generation is not in  operation     Factory setting    Period 1   01 01 2003    01 01 2003    Period 2   01 01 2003    01 01 2003    Room Temp  set   point 15  C             Basic data El 7  Date 21 04 08   Day of week Mo   Time 09 35        gt 
4.  compressor is kept  running or at standstill     5 3 3 Charging principle buffer cylinder   The buffer cylinder is controlled depending on the sup   ply set target temperature  The heat pump heats when  the temperature of the buffer cylinder head tempera   ture sensor VF1 is smaller than the set target tempera   ture  It continues to heat until the buffer cylinder floor  temperature sensor RF1 has reached the set target tem   perature plus 2K    In the connection to a hot water cylinder charging the  buffer cylinder is also charged when the temperature of  the head temperature sensor VF1 is less than 2K higher  than the set target temperature  premature reheating    VF1 lt  T VL set   2K     5 3 4 Resetting to factory settings       Caution    Inadvertent deletion of specific settings   When you reset the control system to  the default settings  specific system  settings can be deleted and the system  can shut down  The system does not  suffer damage          In the basic display on the graphic display press both  dials at the same time for min  5sec     After that you can select whether to reset only the  timer programme or all values to the default settings     5 3 5 Controller structure   The top level display is a graphics display  It is the  starting point for all the available displays  This display  reappears automatically if you do not actuate any of the  dials for a long time when setting values     Controller operation is subdivided into four levels     The operato
5.  electric power from the heat pump in   stallation  then switch off the circuit  breaker on your heating system     Cr    5 9 Inspection   An annual inspection maintenance of the unit by a spe   cialist is a prerequisite for continuing operational safety   reliability and a long working life        Danger    Inspections Maintenance work not car   ried out can result in damage to proper   ty and personal injury    Have the inspection  maintenance and  repairs carried out only by a recognised  expert technician company        Only genuine Vaillant spare parts may be used for in   spections  maintenance and repair work to ensure the  perfect long term working order of all functions of your  Vaillant appliance and to prevent the approved series  condition from being changed    Any spare parts which might be required are listed in  the relevant current spare parts catalogues   Information can be obtained from Vaillant Customer  Service Centres     24    5 10 Troubleshooting and diagnosis   5 10 1 Error messages on the controller   Error messages appear ca  20 seconds after the error  has occurred on the display and are written in the error  memory of the controller when the error has been  present for ca  3min  where the engineer can view it at  a later date                 Error History H  Fault number  gt 1  Fault code 41  16 02 08 07 18   Error CH circuit   Sensor T3 heat source       Fig  5 3 Error message in the error memory Menu I1    The geoTHERM control system has various 
6.  general behaviour        Ventilate correctly    Do not leave windows or French windows tilted open   but rather open the windows wide 3 or 4 times a day  for 15 minutes and turn down the thermostatic valves  or room thermostats while ventilating      Do not block the radiators to ensure that heated air  can circulate in the room      Use a ventilation system with heat recovery    The optimum exchange of air in the building is always  guaranteed by the use of a ventilation system with  heat recovery  windows no longer need to be opened  for ventilation purposes   If necessary  the air flow can  be matched to your individual requirements with the  ventilation unit s remote control        Check that windows and doors are airtight  Keep shut   ters and blinds closed at night  so that as little heat as  possible is lost      If a VR 90 remote control unit is installed as an acces   sory  do not obstruct it with furniture  etc   so that it  can measure the circulating room air unhindered        Think when using water  for example  take a shower  instead of a bath  promptly renew the seals on drip     ping taps     3 5 2 Economising by the correct use of the control  system  Further economies can be made by the correct use of  the control system on your heat pump   The control of the heat pump helps you to make savings  by     The correct selection of the heating flow temperature   Your heat pump controls the heating flow tempera   ture depending on the room temperature you have  s
7.  is constantly  measured  If the heat source outlet temperature falls  below a specific value  the compressor temporarily  shuts off with the error message 20 or 21  If these er   rors occur three times in a row there is a fault induced  shutdown    For the geoTHERM VWS heat pumps you can set the  value  Default setting  10  C  for the freezing protection  in the installation assistant A4     Operating Manual geoTHERM VWS 0020045200_00    4 4 Design of the geoTHERM heat pump   The heat pump is available in the following models    The heat pump are  above all  different from each other  in their output                 Type name Heating output  kW   VWS 61 2 230V 6 0   VWS 81 2 230V 8 1   VWS 101 2 230V 10 5             Table 4 1 Type summary                            Fig  4 3 Front view    Key to Fig  4 3  1 Label with heat pump type designation  2 Operating panel    Operating Manual geoTHERM VWS 0020045200_00                                  Fig  4 4 Rear view    Key to Fig  4 4   Return to domestic hot water cylinder  Coolant to heat pump   Coolant from heat pump  Transportation handles   Cable duct for electrical connections  Heating return   Heating feed    NOUR WN    11    5 Operation  5 1 Familiarising yourself with and operating the  controller   All programming of the heat pump is carried out by  means of the two dials El and     on the controller    The dial Elis used to select the parameter  by pressing   and to alter the parameter    by turning   The dial El is use
8.  temp  difference   20K difference  means deactivated     22 Frost protection heat source over  source outlet  Source outlet temperature too low    lt parameter freezing protection in menu A4    27 Coolant pressure too high  The integrated high pressure switch tripped at  30 bar  g    The heat pump cannot be restarted until after  60 min  at the earliest    28 Coolant pressure too low  The integrated low pressure switch tripped at  1 25 bar  g     29 Coolant pressure outside the range    If the error occurs twice in a row the heat pump  cannot be started until after 60 min  at the earliest           Table 5 6 Temporary malfunctions    25                                                                      5 10 6 Blocking error Fault code  Error text description es hia  Errors could occur which result in the shutdown of the 72 Flow temperature too high for un   _  heat pump derfloor heating  E Flow temperature is for 15 min   Fault code  Error text description ieee higher than a set value  max  HK  mo e temp    compr  hysteresis   2K    32 Error heat source sensor T8 possible    81 Coolant pressure too high  Sorte cut inthe Sensor Error 27 has occurred three times      in a row  33 Error heat circuit pressure sensor 83 Coolant pressure too low check  short circuit in the pressure sensor heat source  34 Error brine pressure sensor possible re ee nas occurred threetime    short circuit in the pressure sensor 84 Coolant pressure outside the  range  40 Error comp outlet sensorT1 p
9.  temperature of 35  C  Fig  7 1 Example of an identification plate titi Thermal output with a brine tem   B5 W55 perature of 5  C and a heating flow    temperature of 55  C    C     CE mark  VDE GS mark    Read the Operating and Installation  Manual                 IP 20 Humidity protection class  Ensure proper disposal at the end  x of its useful life  not household  waste     OTOT    seria  Number  21054500100028300006000001N4    Table 7 2 Explanation of symbols          30 Operating Manual geoTHERM VWS 0020045200_00    Vaillant Ltd  Nottingham Road E Belper    Derbyshire B DE561JT  Telephone 0845 602 2922 W www vaillant co uk E info vaillant co uk    0020045200_00 GB 082008    
10.  that the domestic hot water  cylinder is being heated or that the heat pump   is in the ready state  The temperature in the  domestic hot water cylinder is also displayed           Table 5 1 Settable parameters in the operator level    Operating Manual geoTHERM VWS 0020045200_00       Display shown             Mon  21 04 08 16 49 Eli  Current flow temp  28  C  CH pressure 1 2bar  Brine pressure 1 4 bar    Heating only comp     Warning message            Warning message       Description    Energy input display   Shows the energy extracted from the environment for each of the  12 months of the current year  black bar   White filled bars represent  the future months of the year  the height of the bar corresponds to  the yield for the month in the previous year  comparison possible    On commissioning  the height of the bars is zero for all months  as no  information is available yet    The scaling  in the example  4000 kWh  adapts automatically to the  month s highest value    Top right the total of the environmental yield since commissioning is  displayed  in the example  13628 kWh            Day  date  time as well as flow temperature  heating system pressure  and heat source pressure are displayed   Current flow temp  Current flow temperature in the unit   Heating system pressure  Pressure sensor heating circuit   Pressure heat source  Pressure of the heat source  pressure sensor   heat source circuit  brine pressure    Heating only comp   this status message provides infor
11. 0           gt Select weekday block                You can set the heating times for each heating cir   cuit in the  HK2 Timer programme  menu    Up to three heating times can be programmed per  day or block  The control system operates according  to the heating curve and the room setpoint tempera   ture     The set back times can be dispensed with  depending  on the tariff agreement with power company  VNB   or the construction of the house    Power companies offer their own discounted tariffs  for heat pumps  It can make sense on economic  grounds to make use of the more favourable off   peak power    In low energy houses  in Germany standard as from  1st February 2002 energy conservation regulation   the room temperature reduction can be dispensed  with owing to low heat losses    The desired set back temperature must be set in  menu 2     Mon   Sun    0 00   24 00          Table 5 1 Settable parameters in the operator level  ctnd      Operating Manual geoTHERM VWS 0020045200_00       Display shown                         Description    Factory setting             3 j i i Mon   Fri  DHW loading E  5 You can set the times at which the domestic hot Eo 2 SO BES   Time programme water cylinder is heated in the  WW Timer Pro    gt Mon gramme   menu  Sat      Up to three times can be programmed per day or  1 06 00 22 00 N Wen prog per ay ae  2   i  3 8 9 9 Su   f   7 30   22 00   gt Select weekday block  The hot water generation should only be active at  times when really hot wa
12. 0020046310  Other applicable documents are all the manuals that  describe the operation of the heat pump  as well as  other manuals for all the accessories used     1 1 Storage of the documents   Please store this operating manual and all related docu   ments in such a way that they are available whenever  required    You can store the documents inside the pillar cover                             Lah ee          Fig  1 1 Removing the pillar cover    1 2 Symbols used   The following hazard classification symbols are used for  information  activities and energy saving tips in this  operating manual        Danger   Immediate risk of serious injury or death          Danger   Danger of burning and scalding           Caution   Potentially dangerous situation for the  product and environment           Note   Useful information and instructions        oy  gt  P P    This symbol points you to energy saving tips  You can  put this setting into effect by means of the heat pump  control system  among other things     e Symbol for a necessary task         1 3 Applicability of the manual   This operating manual applies exclusively to units with  the following article numbers    0010005501   0010005502   0010005503   The part number of your unit can be obtained from the  identification plate     2 Safety instructions    Observe the following safety instructions and regula    tions when operating the heat pump    e Take advantage of the extensive instruction in the  operation of the heat pum
13. 01 2 230 V  Article number g 0010005501 0010005502 0010005503  Height without connections mm 1200   Width mm 600   Depth without pillars mm 650   Depth with pillars mm 840   Weight     with packaging kg 156 163 167     without packaging kg 141 148 152     ready for operation kg 147 155 160   Rated voltage s      Heating circuit Compressor 1 N PE 230V 50 Hz     Control circuit 1 N PE 230 V 50 Hz     Auxiliary heating 1 N PE 230 V 50 Hz   Fuse  slow blow   Connected mains supply   Alternative operation  Supply status 4kW  A 16 20 25 25   Parallel operation A 25 35 35 50   Dual circuit supply WP charge rate     Individual compressor A 16 25 25    booster heating 2 4kW individual A 16 20 16 20 16 20  Dual circuit supply special charge rate     Alternative operation  Supply status 4kW  A 16 20 25 25 25 25  Parallel operation A 25 35 35 50 35 50    pumps and controllers A 4 4 4  Start up current     without start up current limiter A 58 76 97    with start up current limiter A  lt  45  lt  45  lt  45  Rated power     min  for B 5W35 kW 1 4 1 8 2 4    max  for B20W60 kW 2 8 4 0 4 9    Auxiliary heating kW 2 4 2 4 2 4  EN 60529 level of protection   IP 20   Hydraulic connections     Heating circuit flow and return mm G11 4   diameter 28     Heat source flow and return mm G11 4   diameter 28   Heat source circuit  brine circuit      Brine type    Ethylene glycol 30      max  operating pressure MPa  bar  0 3  3      min  inlet temperature e    10     max  inlet temperature SG 20     No
14. C presents no danger in normal  use and under normal conditions   With improper use  however  it can  cause injury and damage     Cr          2 2 Prohibition on alterations  Danger   Inappropriate alterations can cause inju   ries     Under no circumstances should you  attempt to make changes or alterations  to the heat pump or other parts of the  heating and hot water system yourself     The prohibition applies to         the geoTHERM heat pumps        the vicinity of the geoTHERM heat pumps        the supply lines for water and power    For alterations to the heat pump or its peripherals  you  must call on a qualified engineer    Do not damage or remove seals or locking devices on  components  Only suitably qualified heating engineer  or our customer service may remove sealed compo   nents     Operating Manual geoTHERM VWS 0020045200_00    3 Notes on operation    The Vaillant geoTHERM heat pumps are state of the art  appliances which have been constructed in accordance  with recognised safety regulations and must be installed  by a qualified expert technician in compliance with the  existing regulations  rules and directives        Danger    Risk to life as a consequence of using  unqualified   personnel    Installation  inspection and repair may  only be carried out by a qualified engi   neer  In particular  working on the elec   trical components and on the coolant  circuit requires an appropriate qualifica   tion        3 1 Intended use   The Vaillant heat pumps are buil
15. Settable values       You can set the current date  the day of the week  and the current time  if DCF radio clock reception is  not possible  in the  Basic Data  menu    These settings apply to all connected system compo   nents           Code layer        8       Code number     0000           gt Set figures                To access the Code level  Installer level   the appro   priate code must be entered    To view setting parameters without entering the  code  you must press the dial F once  You can then  view all parameters of the code level by turning the  dial El but not change them  As operator  without en   tering the code  you can view all menus in the code  level however not modify them                    Caution  Do not try to access the code level by   making arbitrary entries in the code level  Uninten   tional modification of the system specific parame   ters can cause malfunctions or damage to the heat    pump           Table 5 1 Settable parameters in the operator level  ctnd      Operating Manual geoTHERM VWS 0020045200_00    21    5 6 Installer Menu    Special functions can be selected only from the basic  display  To do so press the left hand dial El    You must turn the dial tJ to alter the parameter    The following special functions can be selected                      Energy saving function  Press dial E  1 x  e Party function  Press dial E  2 x    One time charging  Press dial El 3 x             To activate one of the functions  you merely have to  sel
16. ating Manual geoTHERM VWS 0020045200_00 15    5 5 Displays in the user level    The individual menus on the controller are described    and explained below        Display shown             Description    Graphics display  Top level display    You can read off the instantaneous state of the system from this dis   play  This is always shown if you have not actuated either of the dials  for a long time while another display is showing                       Outside temperature  here 10  C      Source inlet temperature  Temperature sensor   in the example 9   C     Under the arrow the output of the heat source   in the example 10 KW  is displayed    The extent of darkening of the arrow graphically  shows the energy efficiency of the heat pump  under the given operating conditions     The output of the heat source must not be equa   ted with the heating output    The heating output corresponds to approx  the  output of the heat source   compressor output     When the compressor or the electric auxiliary  heating is switched on  the arrow is shown filled      gt  gt  gt  Left and right flash when the compressor is  switched on and energy is consequently being  taken from the environment and fed to the heat   ing system      gt  gt  gt  Right flashes when energy is being fed to the  heating system  e g  only from the electric auxil   iary heating      The heat pump is in the CH mode  Moreover   the heating flow temperature is displayed  in the  example 30  C      The symbol indicates
17. d to select the menu  by  turning  and to activate special functions  by pressing                        Vaillant          Basic data    Date  Day of week  Time                      Fr  16 55                   Fig  5 1 Operating overview    Key  1 Menu name  2 Cursor indicates the selected parameter  3 Menu number  4 Dialt   position parameter  turn   select parameter  press   5 Dial El   select menu  turn   activate special operation  press   6 Information line  in the example a handling request                       Typical operating process  operator level     O  Q                Turn the dial E until the menu  required has been selected           Turn the dial H until the  parameter to be modified  has been selected                       Press the dial H to mark the  parameter to be modified   The parameter background  is darkened                    Turn the dial H to modify the  parameter setting value                 Press the dial E to mark the  setting value to be accepted        fiai    o N             Operating Manual geoTHERM VWS 0020045200_00    5 2 Setting menus and parameters       setting to date    modified setting                   Select menu                                                      gt Set weekday                               Holiday programming El 6 Basic data     7  for cpl  System  Or  Period of time Biel dist  Setect Date  gt 21 04 08     Turn the ial  Selec  1  gt 06 01 08 08 01 08 menu e g  from menu Day of week Mo  2 14 01 08 30 01 08 6 t
18. e must be dimensioned such that the   heat pump can be properly installed and maintained    e Ask your heating engineer which currently applicable  national building regulations must be observed    The installation site must be dry and generally frost    proof     3 3 Cleaning and care  Do not use any scouring or cleaning agents that could  damage the cladding        Note   Clean the exterior of your heat pump  with a damp cloth and a little soap     Cr       3 4 Checking the operational condition of the  heat pump   In contrast to heaters based on fossil fuels  no expen   sive maintenance work is necessary for the Vaillant    geoTHERM heat pump        Note    Have your installation checked regularly  by an expert technician company to  ensure efficient operation of your heat  pump     C       3 4 1 Filling pressure of the heating system   The filling pressure of the heating installation should be  checked at regular intervals  The filling pressure of the  heating installation can be checked from the reading on  the heat pump controller  see sect  5 5   It should be be   tween 1 and 2bar  If the water pressure falls below  O 5bar  the heat pump will be shut down automatically  and an error message will be displayed     Caution    Risk of damage from water escaping  from leaks in the system    Close the cold water stop valve in the  event of leaks in the hot water pipework   In the event of leaks in the heating  installation switch off the heat pump to  avoid any further leaki
19. ect it  In the energy saving function it is additionally  necessary to enter the time until which the energy  saving function  regulation to set back temperature  is    to apply     The basic display appears either after the function has  elapsed  reaching the time  or by pressing the dial E   again        Display shown Description          We 16 02 08 9 35    Saving function        Energy saving enabled        gt Select end time       With the saving function you can set back the heating times for a set   table period     Enter the time for the end of the saving function in the format hh mm   hour minute            We 16 02 08 9 35       Party function enabled          Party function    With the party function you can continue the heating and hot water  times beyond the next switch off time up to the next heating start   The party function can only be used for the heating circuits or hot  water circuits for which the operating mode  Auto  or  ECO  is set              We 16 02 08 9 35       one time  DHW tank loading enabled                   One time charging   This function allows you to charge the hot water cylinder once  re   gardless of the current time program           Table 5 2 Special functions    22    Operating Manual geoTHERM VWS 0020045200_00         Reset to default setting  Keep dial El and dial H  pressed for longer than 5 seconds  After that you can  select whether to reset only the timer programme or  all values to the default settings              Display s
20. et  Therefore select a room temperature that is just  sufficient for your comfort  for example 20  C  Every  degree over and above that means an increase in en   ergy consumption of around 6  per annum   For floor heating use heating curves of  lt  0 4  For radi   ator heating  we recommend that they are laid out to  manage with a maximum flow temperature of 50  C  at the lowest outside temperature  this corresponds  to heating curves of  lt  0 7   An appropriate setting of the hot water temperature   Only heat hot water as much as is required for con   sumption  Any further heating results in unnecessary  power consumption  and hot water temperatures of    more than 60  C also lead to increased lime scale pro   duction  We recommend that hot water generation be  achieved without the electric auxiliary heating  by this  method  the maximum hot water temperature is de   termined by the high pressure cut out in the heat  pump cooling circuit  This cut out corresponds to a  maximum hot water temperature of approx  58  C   Setting of individually suited heating times    Select the correct operating mode    For the times that you are asleep or away  we recom   mend that you switch the heating to set back mode   Heat uniformly    By means of a meaningfully constructed heating pro   gramme  you can arrange for all the rooms in your  house to be uniformly heated in accordance with your  pattern of use    Set the thermostatic valves    You can adjust the room temperature to suit your 
21. f the transport packaging to  the qualified servicing company which installed the  appliance     3 6 3 Coolants  The Vaillant heat pump is filled with R 407 C coolant        Danger   Risk of injury from freezing as a result  of contact with the R 407 C coolant     Escaping coolant can cause freezing if  the exit point is touched    Do not inhale gases or vapours emanat   ing from leaks in the coolant circuit   Avoid contact with the skin and eyes   The disposal of coolant must only be  by qualified specialists           Cr Note   R 407 C presents no danger in normal    use and under normal conditions  With  improper use  however  it can cause inju   ry and damage        Operating Manual geoTHERM VWS 0020045200_00    4 Equipment and functional  description    4 1 Functional principle   Heat pump systems consist of separate circuits in which  liquids or gases transport the heat from the heat source  to the heating system  As these circuits operate with  differing media  brine water  coolant and heating  water   they are coupled to one another by means of  heat exchangers  In these heat exchangers the heat  passes from a medium at a high temperature to a medi   um at a lower temperature     The Vaillant geoTHERM heat pump uses geothermal  energy as its heat source        1 4 Electrical energy     D       FS    I                              hi    5     gt   gt              Fig  4 1 Using a geothermal heat source    The system consists of separate circuits which are cou    pled w
22. g aseisiin  36 3  COOlAMES nenen eenen a Qua a Ei  4 Equipment and functional description           9  4 1 Functional principle                                                 9  4 2 Operation mode of the coolant circuit               9  43 Automatic auxiliary functions                             10  4 4 Design of the geoTHERM heat pump                  11  5 Operation  k S N k Sl Su 2   12  5 1 Familiarising yourself with and   operating the controller                                        12  5 2 Setting menus and parameters                           13  5 3 Description of the controller     5 3 1 Possible system circuits                                         5 3 2 Energy balance Controller                                     5 3 3 Charging principle buffer cylinder                     14  5 3 4 Resetting to factory settings                              14  5 3 5 Controller structure                                                14  5 3 6 Setting energy saving functions                         14  54  Flow diagralfiuzu sl n snieni 15  5 5 Displays in the user level                                     16  5 6 Installer Menu                                                         22  5 7 Starting up the heat pump                                 24  5 8 Shutting down the heat pump                           24  5 9   ns petti Messner k a a au a a 24  2       5 10 Troubleshooting and diagnosis                          24  5 10 1 Error messages on the controller             
23. hown Description       We 21 04 08 9 35 The default settings are re established        Caution  Ensure that a qualified technician performs the default set     Factory setting    ie     ting reset  The system specific settings are reset  The system can be    Cancel NO YES hut d Th t d t suffer d  Time programme NO YES snu own  e system aoes not sutter damage   Everything NO YES    Press both dials for at least 5 seconds to request the menu default  setting               gt Settable values                Table 5 3 Re establishing the default setting    Operating Manual geoTHERM VWS 0020045200_00 23    5 7 Starting up the heat pump   The start up of your heat pump was carried out after  installation by your expert technician company    A repeated start up will not even be necessary in the  event that your heat pump disconnects from the mains  unexpectedly  for example as a result of a voltage drop   power cut  circuit breaker defective  circuit breaker de   activated   Your geoTHERM heat pump has an automat   ic reset function  i e  the heat pump reverts automatical   ly to its starting condition  provided no fault is present  in the heat pump itself  Find out what to do in the event  of a fault in Chap  5 10     5 8 Shutting down the heat pump   A shutdown of the heat pump is only possible via the  operating panel by deactivating heating and hot water  generation in the respective menus  see Sect  5 4  User  Level Displays          Note    Should it be necessary to remove all 
24. in   dividual requirements and ensure effective operation  of your heating installation using the thermostatic  valves in combination with a room temperature regu   lator  weather compensator     The operating times of the circulation pump can thus  be optimally matched to the actual need    Consult a qualified engineer  He will adjust your heat   ing installation to suit your personal requirements   You will find these and other energy saving tips in  Chap  5 5  The controller settings that can potentially  save energy are described there     3 6 Recycling and disposal   Both your heat pump and all its accessories and associ   ated transport packaging consist overwhelmingly of raw  materials that can be recycled  and thus have no place  in your household waste        Cr Note   Please observe the applicable national    legal regulations   Make sure the old appliance and any  accessories are disposed of properly           Caution   Environmental hazard due to improper  disposal     The disposal of coolant must only be  by qualified specialists        3 6 1 Appliance  If your heat pump is identified with this sym   bol  it does not belong with your household  waste at the end of its useful life   As this heat pump is not covered by the law  regarding the marketing  return and environ   mentally friendly disposal of electrical and electronic  equipment  ElektroG in Germany   free disposal at a  municipal collection point is not provided     3 6 2 Packaging   Leave the disposal o
25. ing circuit should only be carried out by  authorised specialists     Operating Manual geoTHERM VWS 0020045200_00 29    7 2 Data badge Explanation of the symbols on the identification plate    O Rated voltage   compressor  O A   Rated voltage   pumps   controller  VWS 61 2 230 V    IT FR NO LV LT EE ES UK  TU Rated voltage   auxiliary heating  IP 20     J 1 N PE 230V 50Hz P    Vaillant GmbH Remscheid   Germany    Serial No  21054500100028300006000001N1       Rated maximum power  O AJ 1 N PE 230V 50Hz Max  LU UNPE 290V 50Hz Rated power   compressor  pumps  PC  O w and controller  P 68 kW  Max    POQ 28 kW P LLL Rated power   auxiliary heating  PLO 7       l Start up current without start up  current limiter    l  oo A E ford Start up current with start up  current limiter             I    xt _ MPa  bar     Service water tank capacity                                        Z   R407 C Permissible rated overpressure  X 19 kg  2 9  29  MPa  bar    Coolant type  O X Filling quantity   COP BO W35 4 2 za  Permissible rated overpressure  COP BENIS   Performance figure at a brine tem    BO W35 6 0 kW COP BO W35 perature of 0  C and a heating flow   B5 W55 is w temperature of 35  C       Performance figure at a brine tem   COP B5 W55 perature of 5  C and a heating flow  temperature of 55  C   N4    Thermal output with a brine tem        k     01                                   lt C sy UNN    x 210545001000283000060000                 BO W35 perature of O  C and a heating flow  N   dii
26. ion against loss of brine   An analogue pressure sensor monitors possible low  brine pressure and switches the heat pump off if the  brine pressure is ever less than 0 2 bar on the pressure  gauge and error 91 is displayed on the error memory   The heat pump switches on again when the brine pres   sure rises above 0 4 bar gauge pressure    If the brine pressure drops below O 6bar on the pres   sure gauge for more than one minute a warning appears  in menu El                 Floor protection circuit for all hydraulics without  buffer cylinder  e g  in hydraulic plans 1 and 3    If the measured flow temperature in the underfloor  heating circuit continuously exceeds a value for more  than 15 minutes  the heat pump switches off and issues  an error message 72  When the heating flow tempera   ture falls below this value again and the error has been  reset the heat pump switches back on    Caution    Danger of damage to the floor    Set the value for the floor protection cir   cuit ensuring that it is not high enough  to damage the floor as a result of exces   sively high temperatures        Phase monitoring   The sequence and existence of phases  clockwise rotat   ing field  on the 400 V voltage supply are continuously  monitored during commissioning and operation  If the  sequence is not correct or if a phase breaks down  the  heat pump is switched off due to the error to avoid  damage to the compressor     Freezing protection function   The outlet temperature of the heat source
27. ith one another by means of heat exchangers    These circuits are      The heat source circuit  by means of which the energy   from the heat source is transported to the coolant cir    cuit    The coolant circuit  which releases its heat to the   heating water circuit by means of evaporation    compression  liquefaction and expansion      The heating water circuit  which supplies the heating  and the hot water generator for the domestic hot  water cylinder     Operating Manual geoTHERM VWS 0020045200_00    4 2    Operation mode of the coolant circuit           Cold water   gt     Heating system            Additional  heating                           Domestic  hot water cylinder             Switching valve       Heating water pump Heating water circui          4 3 t  Condenser 2        I Expansion valve Compressor  ID Coolant circuit  4 Evaporator    Bri     pump 4 Heat source circuit    Heat source          Fig  4 2 Mode of operation of the heat pump    The coolant circuit is connected by means of the evapo   rator  1  to the geothermal heat source  from which it  extracts thermal energy  At the same time  the physical  state of the coolant changes  it evaporates  The coolant  circuit is connected by means of the condenser  3  to  the heating system  to which it releases the heat again   In so doing  the coolant becomes liquid again  it con   denses    As thermal energy can only pass from a body at a  higher temperature to a body at a lower temperature   the coolant in the e
28. ity hot water priority     see the following tables  column  emergency operation      5 10 3 Errors malfunctions that you can remedy       Possible cause Remedy    Dirt in the heating  Bleeding heating  circuit     Faulty pump     Malfunction sign    Noise in the heating  circuit        Air in the heating  circuit     Table 5 4 Other malfunctions    5 10 4 Warning messages   The following warning messages do not cause a mal   function in the operation of the heat pump  The heat  pump is not shut down    Take note of the error code and text and discuss this  during the next inspection with the expert technician        Fault code    Error text description        Overheating on compressor pressure side    36 Low brine pressure             Table 5 5 Warning messages  no shutdown    Operating Manual geoTHERM VWS 0020045200_00       5 10 5 Temporary malfunctions   The heat pump is shut down temporarily and starts up  again independently when the cause of the fault is re   moved    Depending on the error the heat pump switches back on  automatically after 5 or 60 minutes    Take note of the error code and text and discuss this  during the next inspection with the expert technician                 Fault code  Error text description   20 Frost protection heat source monitoring source  outlet  Temperature difference of the heat source  gt  set  value  permitted temp  difference   This error message is deactivated as standard and  can only be activated via vrDIALOG parameter   permitted
29. malfunction  types      Malfunction of components which are connected via  eBUS    Temporary shutdown   The heat pump remains in operation  The error is dis   played and disappears independently when the cause  of the fault is removed      Fault induced shutdown   The heat pump is shut down  It can only be restarted  after the cause of the fault has been removed by the  expert technician and the error reset    Moreover  other errors malfunctions can occur on  the unit or system        Caution    Heat pump malfunction    Immediately notify your expert techni   cian if error messages appear on the dis   play on the operating panel which are  not listed in tables 5 4 to 5 7    Do not attempt to remove the source   of the malfunction yourself           Note    Not all of the following listed malfunc   tions have to be dealt with by an expert  technician    If you are unsure whether you can reme   dy the fault yourself or not or if the  error occurs repeatedly contact your  expert technician or Vaillant customer  service     Cr       Operating Manual geoTHERM VWS 0020045200_00    5 10 2 Activating emergency mode   Depending on the type of malfunction the expert techni   cian can set the heat pump to continue operation in  emergency mode  via an integrated electric auxiliary  heating  until the cause of the error is remedied  and ei   ther for heating operation  display  heating priority     for hot water operation  display  hot water priority   or  for both  display  heating prior
30. mation on the  current operating status   The following are possible    Heating only comp    Heating comp  amp  ZH   CH  ZH only   CH Comp amp aux off   WW Comp amp aux off   WW  Comp only   WW  ZH only   Peak Rate  WW   Peak Rate  Stand by   Acceleration mode   Frost prot  Heating   Frost prot  Cylind    Legionella protect    Automatic pump spin   Floor drying   Venting mode   Fault shutdown  heating   Error shutdown  heating   Fault shutdown  DHW   Error shutdown  DHW   Malfunction   Blocking error   Operation interlock   CH Comp overrun   WW Comp overrun   CH return too high    Under critical operating conditions a warning message is displayed in  both lower display lines  These lines are empty when the operating  conditions are normal        Table 5 1 Settable parameters in the operator level  ctnd      Operating Manual geoTHERM VWS 0020045200_00    17          Display shown       HK2  Parameters    E  2        gt Auto  Set value day  Night set back temp     Operating mode heating 3       22  C  15  C        gt Select operating mode                   Description Factory setting    Room set target    The room set target temperature is the tempera  temp   20  C    ture to which the heating should be regulated in the  operating mode  Heat  or during the time slots     Note  Select a room temperature that is just  high enough to ensure your personal well being   e g  20  C   Each degree over and above the set  value means an increase in energy consumption  of around 6  per an
31. minal flow rate dT 3K I h 1453 1936 2530    Residual head dT 3K mbar 381 332 263    Nominal flow rate dT 4K I h 1090 1452 1898    Residual head dT 4K mbar 461 429 380    Electrical power consumption   pump W 132 132 132  CH circuit     max  operating pressure MPa  bar  0 3  3      min  flow temperature e   25     max  flow temperature   C 62     Nominal flow rate dT 5K I h 1061 1375 1803    Residual head dT 5K mbar 382 339 254    Nominal flow rate dT 10K I h 517 697 848    Residual head dT 10K mbar 486 468 450    Electrical power consumption   pump Ww 93 93 93  refrigerant circuit     Coolant type i R 407 C     Quantity kg 1 9 2 2 2 05     Number of revolutions EX valve   9 0 9 0 9 0     Permissible operating overpressure MPa  bar  2 9  29      Compressor type    Scroll     Oil   Ester     Oil filling quantity 1 3 1 45 1 45    Table 7 1 Technical data    28    Operating Manual geoTHERM VWS 0020045200_00          Description Unit VWS 61 2 230 V  VWS 81 2 230 V  VWS 101 2 230 V  Heat pump performance data    BOW35 dT5     Heating output     Power consumption     Performance figure COP    B5W55     Heating output     Power consumption     Performance figure COP  Internal sound level   Conforms to safety regulations    Low Voltage Directive 73 23 EWG  EMC Directive 89 336 EWG   EN 60335   ISO 5149       Table 7 1 Technical data  cont         Caution    A R 407 C is a chlorine free coolant which  does not affect the ozone layer  Never   theless  any servicing work on the cool     
32. ng    Have the leaks repaired by an expert  technician           Note    The cold water stop valve is not part of  the heat pump scope of supply  It is fit   ted on site by your heating engineer  He  will explain the location and handling of  the component to you     Cr       3 4 2 Filling level and filling pressure of the brine  circuit   Check the brine level or pressure in the brine circuit at   regular intervals  The filling pressure of the brine circuit     Pressure Heat Source   can be checked from the rea    ding on the heat pump controller  see sect  5 5     It should be between 1 and 2 bar  If the brine pressure   falls below 0 2 bar  the heat pump will be shut down   automatically and an error message will be displayed        Caution    Risk of damage from brine escaping from  leaks in the system    In the event of leaks in the brine circuit  switch off the heat pump to avoid any  further leaking    Have the leaks repaired by an expert  technician           Caution    The brine circuit must be filled with the  correct quantity of fluid  otherwise the  system can be damaged     If the filling level of the brine has fallen so far that it is  no longer visible in the expansion tank  you must have  the brine refilled        Operating Manual geoTHERM VWS 0020045200_00       DL          Fig  3 1 Filling level of the brine expansion tank    It is normal for the filling level of the brine to fall a little  in the first month after the start up of the system  The  filling le
33. num     Set back temp    15  C    The set back temperature is the temperature to  which the heating is regulated during the set back  period  An individual set back temperature can be  set for each heating circuit     The set operating mode determines under which  conditions the assigned heating circuit or hot water  circuit should be regulated     The following operating modes are available for  heating circuits    Auto  The operation of the heating circuits alter   nates between the Heating and Energy Saving oper   ating modes in accordance with a settable timer pro   gramme    Eco  The operation of the heating circuits alternates  between the Heating and Off operating modes in ac   cordance with a settable timer programme  The  heating circuit is switched off during the set back  period provided the frost protection function  which  depends on the outside temperature  is not  activated    Heating  The heating circuit operates at the room  set target temperature regardless of any settable  timer programme    Energy sav  The heating circuit operates at the set   back temperature regardless of any settable timer  programme    Off  The heating circuit is off  provided that the frost  protection function  depending on the external tem   perature  is not activated     Note   Additional heating circuits are displayed  depending  on the system configuration        Table 5 1 Settable parameters in the operator level  ctnd      Operating Manual geoTHERM VWS 0020045200_00          Di
34. o7  Time 09 35  Room Temp  setpoint 12  C   gt Set start day  gt Set day  i 7 Select parameter  3  Basic data E 7 Basic data     7  4O   AAA   Date  gt 21 04 08 Sa Faia lect tne    Pate 21 04 08     Turn the ial  select the  Day of week Mo parameter to be modified Day of week  gt Mon  Time 09 35 e g  from line 1 day to line    Time 09 35  2 weekday  in this exam   ple continue to turn   gt Set day 3 snap in points    gt Set weekday  P Modify parameter weekday    7  Base data E  from Monday to Tuesday  Basle dara E           Dat 21 04 08 G   ate  04  DS S Date 21 04 08  Day of week  gt Mon   Push the    dial  Day of week  gt Tues  Time 09 35 Select parameter  Time 09 35           O   WY  gt Set weekday            Turn the    dial   Modify parameter           pi  ve      Push the      dial     B                Accept modification           5 3 Description of the controller    5 3 1 Possible system circuits    The heating engineer will have set all the operating pa   rameters to preset values during commissioning  so that  the heat pump can function optimally  However  you can  individually set and adapt the operating modes and  functions afterwards     Operating Manual geoTHERM VWS 0020045200_00    The controller can control the following system circuits     a heating circuit      an indirectly heated hot water storage tank      a hot water circulation pump      a buffer circuit     In order to extend the system a buffer circuit can be  used to connect up to six additional mixe
35. ossible Error 29 has occurred three times  MENN in a row  Short circuit in the sensor 90 Heating system pressure too low  _  41 Error heat source sensor T3 possible Pressure  lt 0 5 bar  s Heat pump switches off and starts  Short circuit in the sensor up automatically when the pres   sure increases to over 0 7 bar  42 Error HP return sensor T5 possible      91 Brine pressure too low possible  Short circuit in the sensor Pressure  lt 02 Dar    Heat pump switches off and starts  43 Error HP flow sensor T6 possible up automatically when the pres   Shert Cieeuit in thessensor sure increases to over 0 4bar  n 96 Error pressure sensor possible  44 Error external sensor AF possible refrigerant circuit  shorkateut inthe sentor short circuit in the pressure sensor  97 No power for compressor possible  45 Error DHW tank sensor SP possible  Short circuit in the sensor Table 5 7 Fault induced shutdown  ctnd    46 Error HB flow sensor VF1 possible e Consult your expert technician about doing this   Short circuit in the sensor  Cr Note   47 Error HB return sensor RFI possible Only an expert technician can remedy  the fault and reset the error code   Short circuit in the sensor  48 Error flow sensor VF2 WW operation ue f  asih Once the expert technician has remedied the error and  Short circuit in the sensor reset the error he can restart the heat pump   52 Sensors are not suited to the  hydraulic plan  60 Frost protection heat source moni   possible  toring source outlet  Error 20 has occu
36. p provided by your specia   list technician    e Carefully read through this operating manual    e Only carry out activities that are described in this  operating manual        Danger    Risk of burning as a result of contact  with heat pump components    High temperatures can appear on heat  pump components    Do not touch any uninsulated pipes on  the heat pump    Do not remove any of the cladding  sections  apart from the pillar cover   see Ch  1 1         2 1 Coolants   The heat pump is delivered with an operational filling of  R 407 C coolant  This is a chlorine free coolant which  does not affect the Earth s ozone layer  R 407 C is nei   ther a fire hazard nor an explosion risk        Caution    This appliance contains R 407 C coolant   The coolant must not be allowed to es   cape into the atmosphere  R 407 Cis a  fluorinated greenhouse gas covered by  the Kyoto Protocol  with a GWP of 1653   GWP   Global Warming Potential    Before the appliance is disposed of  the  coolant it contains must be completely  drained into a suitable vessel so that it  can then be recycled or disposed of in  accordance with the regulations        Operating Manual geoTHERM VWS 0020045200_00       Danger    Risk of injury from freezing as a result  of contact with the R 407 C coolant   Escaping coolant can cause freezing if  the exit point is touched    Do not inhale gases or vapours emana   ting from leaks in the coolant circuit   Avoid contact with the skin and eyes           Note    R 407 
37. r circuit mod   ules VR 60  accessories  each with two mixer circuits   The controller on the operating panel of the heat pump  is used to programme the mixer circuits     In order to operate under comfortable conditions you    can connect the remote control units VR 90 for the first  eight heating circuits     13    5 3 2 Energy balance controller   The energy balance controller is only applicable to hy   draulics without buffer cylinder    For economical and fault free operation of a heat pump   it is important to regiment the starting of the compres   sor  The start up of the compressor is the point at which  the highest loading occurs  With the help of the energy  balance controller it is possible to minimise starts of the  heat pump without compromising the comfort of a  pleasant room atmosphere    As with other weather controlled heating controllers the  controller determines a supply set target temperature  by capturing the outside temperature through a heating  curve  The energy balance calculation is carried out  based on this supply set target temperature and the  supply real temperature the difference of which is  measured per minute and added up     1 degree minute    min    1K temperature difference in  the supply from 1 Minute  K   Kelvin     The heat pump starts up at a defined heat deficit and  only switches off again when the supplied heat is equal  to the heat deficit    The larger the preset negative numerical value is  the  longer the periods for which the
38. r level is specified for the operator    In Sect  5 4 all of the controller s displays are shown as  a flow diagram  A detailed description of the displays is  contained in Sect  5 5     The code level  menu C1   C9  D1   D5  11   15 and A1   A9   is reserved for the engineer and protected by a code to  protect it from unintentional modification    As the operator you can scroll through the menus of the  code level and view the system specific setting parame   ters however without changing the values    In the menus C1 to C9 the engineer sets system specific  parameters    The menus D1 to D5 enable the engineer to operate and  test the heat pump in the diagnosis mode    In menus l1 to I5 you are given general information on  the settings of the heat pump    Menus A1 to A9 take the engineer through the installa   tion menu to put the heat pump into operation     The display and selection of special function  e g  the  energy saving function  is also possible for the operator   Instructions are given in Sect  5 6 as to how to activate  the special functions     The fourth level contains functions for the optimisation  of the system and can only be set by the engineer using  vrDIALOG 810 2     5 3 6 Setting energy saving functions   Also described in Chap  5 5 are heat pump settings that  will enable a reduction in your energy costs  This is  achieved by optimum setting of the heat pump s weath   er controlled energy balance controller     This symbol points you to these energy 
39. rmation under the  heat pump is thus possible    4 3 Automatic auxiliary functions   Frost protection   The controller is equipped with a frost protection func   tion  This function ensures that your heating installation  is protected from frost in all operating modes    If the outside temperature falls below a value of 3  C  a  set back temperature is automatically programmed for  each heating circuit     Cylinder frost protection   This function starts automatically when the actual tem   perature of the cylinder falls below 10  C  The cylinder is  then heated to 15  C  This function is also active in the   Off  and  Auto  operating modes  regardless of the  timer programmes     Checking the external sensors   The hydraulic basic circuit given by you during commis   sioning determines the required sensors  The heat pump  constantly checks automatically that all sensors are in   stalled and functioning     Protection from loss of heating water   An analogue pressure sensor monitors possible low  water pressure and switches the heat pump off if the  water pressure on the pressure gauge reads less than  0 5 bar and switches it back on when the water pressure  is over 0 7 bar on the pressure gauge     Pump seizing and valve seizing protection   To prevent the sticking of the heating  circulation and  brine pump or of the hot water diverter valve UV1  the  pumps and the valve  which have not been in operation  for 24 hours  are switched on every day for approx   20sec     Protect
40. rred three times in  a row  62 Frost protection heat source moni   possible  toring source outlet  Error 22 has occurred three times  in a row             Table 5 7 Error shutdown    26 Operating Manual geoTHERM VWS 0020045200_00    6 Warranty and customer service    Vaillant provide a full parts and labour warranty for  this appliance    The appliance must be installed by a suitably competent  person in accordance with the Gas Safety  Installation  and Use  Regulations 1998  and the manufacturer s  instructions    In the UK  CORGI registered installers undertake the  work in compliance with safe and satisfactory stan   dards    All unvented domestic hot water cylinders must be  installed by a competent person to the prevailing build   ing regulations at the time of installation  G3     Terms and conditions apply to the warranty  details of  which can be found on the warranty registration card  included with this appliance  Failure to install and com   mission this appliance in compliance with the manufac   turer s instructions may invalidate the warranty  this  does not affect the customer s statutory rights      Vaillant Service   To ensure regular servicing  it is strongly recommended  that arrangements are made for a Maintenance Agree   ment  Please contact Vaillant Service Solutions    0870 6060 777  for further details     Operating Manual geoTHERM VWS 0020045200_00    27    7 Appendix    7 1 Technical data          Description Unit VWS 61 2 230 V  VWS 81 2 230 V  VWS 1
41. s   sors  heating  specifications for appliances for space  heating and for warming drinking water  as well as   EN 378  safety and environmentally related specifica   tions for refrigerating systems and heat pumps      Data badge   An identification plate is attached to the baseplate on  the inside of the geoTHERM heat pump  The type desig   nation is located at the top on the grey frame of the  pillar  see also Fig  4 3  Item 1   In Chapter 7 2 of the  Appendix there is a picture of an identification plate for  the benefit of technically interested customers  and a  table explaining the symbols shown on it     Operating Manual geoTHERM VWS 0020045200_00    1 Notes on this manual    The following information is intended to help you  throughout the entire documentation  Further docu   ments apply in combination with this operating manual   We accept no liability for any damage caused by failure  to observe these instructions     Other applicable documents for the expert technician   Installation instructions No  838408 as well as all the  accessories instructions listed therein    The following information is intended to help you  throughout the entire documentation  Further docu   ments apply in combination with this operating manual   We accept no liability for any damage caused by fail   ure to observe these instructions     Other applicable documents  For the owner of the system   Warranty card No  802922  For the heating engineer   geoTHERM installation instructions No  
42. saving tips     Operating Manual geoTHERM VWS 0020045200_00    5 4 Flow diagram             Reset to default  settings  We 16 02 08    Graphics display    Factory setting  Cancel NO YES       Time programme NO YES  Everything NO YES     gt  Select    a Foe geil                Installer Menu  We 16 02 08 9 35     Q   B  gt  Sparen aktiviert for  gt  12 00     gt  Select stop time       We 16 02 08  O   B Party function enabled  E       Mo 21 04 08 16 49 al                           Flow Temp  CH 28  C We 16 02 08  System pressure 1 2bar    Brine pressure 1 4bar Z N One time    CH  Comp only      e DHW tank loading enabled  ess L      a DDE L   O               HK2 B 2  Parameters            merno mode x Domestic hot water  u Time programme  Set value day 20  C   Night set back temp  15  C  gt Mo     gt Select operation mode       g Basic data 87  Date 21 04 08  Day of week  gt Mo  Time 09 35     gt  Set day of the week    Domestic hot water  Parameters Circulation pump    Operation mode DHW Time programme ra SN 2  I  gt Mo   P     Min  DHW temp   Current DHW temp      gt Select operation mode       Code layer    Code Nummer    gt 0000  Hard co   HK2    Time programme      Holiday programming     gt Mo for cpl  System SY  90 00 24 00 Periods WY  e        gt Adjust numeric character    1  gt 06 01 08 08 01 08  2 14 01 08 31 01 08  Room Temp  setpoint 12   C       gt Set starting day    Code level only for  expert technicians             Fig  5 2 Displays in the User level    Oper
43. splay shown       DHW loading  Parameters    E  4       Auto  60  C    Operating mode WW  Max  DHW temp    Min  DHW temp  44  C  Cylinder temp  REAL 51  C    Auto  60  C  44  C   51  C           gt Select set target temperature          Description    For connected domestic hot water cylinders and the  circulation circuit the operating modes Auto  On and  Off are possible     The maximum WW temperature determines the  temperature to which the domestic hot water cylin   der should be heated    The minimum WW temperature determines the  limit below which the domestic hot water cylinder is  heated    Note  The maximum WW temperature is only dis   played when the auxiliary hot water heating is ena   bled    Without electric auxiliary heating  the WW tempera   ture is limited by the pressure sensor control shut   off in the cooling circuit and cannot be adjusted   Cylinder temp  REAL  Current temperature in the  domestic hot water cylinder     We recommend that hot water generation be  achieved without the electric auxiliary heating by  this method  the maximum WW temperature is de   termined by the high pressure cut out in the heat  pump cooling circuit  This cut out corresponds to a  maximum hot water temperature of 58  C  In order  to keep the heat pump starts to an absolute mini   mum as low a min  hot water temperature as possi   ble should be selected     Factory setting       Min  hot water  temp  44  C          HK2  Time programme    E5        gt Mon  1 00 00  2  3    24 0
44. t and designed accor   ding to accepted safety rules and regulations  Neverthe   less  there is still a risk of injury or death to the user or  others or of damage to the device and other property  in the event of improper use or use for which it is not  intended    This unit is not intended for use by persons  including  children  having limited physical  sensory or mental  capacities or who have inadequate experience and or  knowledge  unless they are supervised by a person  responsible for their safety or have been given instruc   tions by him regarding the operation of the unit   Children must be supervised to ensure that they do  not play with the unit    The units are intended as heat generators for closed  hot water central heating installations and for hot wa   ter preparation  Any other use or extended use is con   sidered to be improper  The manufacturer or supplier  is not liable for any resulting damage  The user alone  bears the risk    It is also considered as intended use to observe        the operating and installation instructions       all other applicable documents       adherence to the inspection and care conditions        Danger    Risk to life as a consequence of improper  use of the installation    There is a risk of death or serious injury  to the user or third parties or of damage  to the device and other property in the  event of improper use or use for which it  is not intended        3 2 Requirements of the installation site   The installation sit
45. ter is to be run  Please set  this timer programme to your minimum require   ments   As an example  for working people a window from  6 00   8 00hrs  and a second window from 17 00    23 00hrs can minimise the energy consumption due  to hot water generation   Circulation pump E 5 You can set the times at which the circulation pump on  Time programme is to be operational in the  Circulation Pump Timer           Programme  menu  Sat   gt Mon   a      Up to three times can be programmed per day or  1 06 00 22 00 block  7 30   23 30  i i If the hot water operating mode  see menu E 3  is Sy  3  gt            gt Select weekday block                set to  ON   the circulation pump runs continuously   7 30   22 00    The timer programme circulation pump should cor   respond to the timer programme hot water  if nec   essary the time slots could be selected even more  restrictively    If the desired hot water temperature is obtained  quickly enough without switching on the circulation  pump  the circulation pump can likewise be deacti   vated    In addition  you can briefly activate the circulation  pump by means of electronic pushbutton switches  mounted in the immediate vicinity of the taps and  connected to the heat pump  the same idea as stair   well lighting   The operating times of the circulation  pump can thus be optimally matched to the actual  need    Consult your expert technician about doing this           Table 5 1 Settable parameters in the operator level  ctnd      20  
46. vaporator must have a lower tem   perature than the geothermal heat source  On the other  hand  the temperature of the coolant in the condenser  must be higher than that of the heating water in order  to be able to release the heat to it     These different temperatures are produced in the  coolant circuit by means of a compressor  2  and an  expansion valve  4   which are situated between the  evaporator  1  and the condenser  The coolant flows in  vapour form from the evaporator  1  into the compres   sor  where it is compressed  This causes the pressure  and temperature of the coolant vapour to rise sharply   After this process it flows through the condenser  where  it releases its heat to the heating water by condensa   tion  It flows as a liquid to the expansion valve  where  it expands significantly and in so doing loses much of  its pressure and temperature  This temperature is now  lower than that of the outside air which flows through  the evaporator  1   The coolant can thus take up more  heat in the evaporator   1  turning into vapour in the    process and flowing to the compressor  The cycle starts  again    If required  the electric auxiliary heating can be  switched in by the integrated controller    To prevent the formation of condensate in the interior  of the unit  the pipes of the heat source circuit and the  coolant circuit are insulated  Should condensate appear   however  it is collected in a pan inside the unit and di   verted away underneath it  Drop fo
47. vel can also vary depending on the temperature  of the heat source  However it should never sink so far  that it is no longer visible in the expansion tank        Caution    Risk of damage    The filling of the brine circuit in your  heat pump installation may only be  undertaken by authorised specialists   Check the filling level of the brine circuit  at regular intervals and inform your  expert technician company if the filling  level in the brine expansion tank is too  low        3 4 3 Accumulation of condensate  condensa    tion water   The evaporator  the brine pumps and the pipes in the  heat source circuit  as well as some components in the  coolant circuit  are insulated in the interior of the heat  pump  so that no condensate can accumulate  If conden   sate should ever accumulate in small amounts this will  be collected by the condensate basin  The condensate  basin is located on the inside  in the lower part of the  heat pump  As a result of the heat generated inside the  heat pump  the condensate in the condensate pan eva   porates  Small amounts of the accumulating condensate  can be drained off under the heat pump  In small  amounts  accumulating condensate should not be seen  as a fault in the heat pump     Operating Manual geoTHERM VWS 0020045200_00    3 5 Energy saving tips   Below you will find important tips to help you operate  your heat pump system in an energy and cost saving  manner     3 5 1 General energy saving tips   You can even save energy by your
    