1. personnel The UPS has its own internal energy source battery The output receptacles may be alive even when the UPS is not connected to the mains Do not dispose of batteries in a fire the battery may explode Do not open or mutilate the battery or batteries released electrolyte is harmful to the skin and eyes A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on batteries Remove watches rings or other metal objects DUse tools with insulated handles TUV Safety statement German ACHTUNG 1 Der Arbeitsplatzbezogene Schalldruckpegel diese Ger tes nach DIN 45635 betr gt 70dB A oder weniger 2 Dieses Ger t ist durch Elektrofachkr fte zu installieren 3 Bei der Installation dieses Ger tes ist darauf zu achten da die Ableitstr me der USV und der angeschlossenen Verbraucher den Maximalwert von 3 5mA nicht berschreiten 4 Die Ger testeckdose mu nahe dem Ger t angebracht und leicht zug nglich sein 5 Die USV enth lt Spannungen die m glicherweise gef hrlich sind Alle Reparaturen sollten nur von ausgebildeten Monteuren durchgef hrt werden Die USV hat eine interne Stromversorgung batterien Die Ausgangsanschl sse k nnen daher unter Strom stehen auch wenn die USV nicht an das Versorgungsnetz angeschlossen ist 6 Werfen sie niemals die Batterien in das Feuer die Batterien k nnten explodieren 7 ffnen od
2. EFFEKTA UPS Series MI technical description Uninterruptible power Supply e EFFEKTA Product description MI Series 400 VA 1200 VA MIRM Series 600 VA 1200 VA EFFEKTA UPS Series MI technical description CONTENTS 1 Introduction 2 Description and Indicators 5 3 Accessories 6 4 Installation T 5 Operation 7 6 Maintenance 8 7 Specifications 8 8 Troubleshooting guide 9 9 MI Block Diagram 9 Stand 08 2005 Seite 2 techbes_dt_MI_MIRM_050824 doc Anderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description T V Safety statement English CAUTION l 2 3 The sound pressure level at the operators position according to IEC 704 1 1982 is equal or less than 70dB A This unit should be installed from service personnel With the installation of this equipment it should be prevented that the sum of the leakage current of the UPS and the connected consumer does not exceed 3 5mA 4 The socket outlet shall be near the equipment and easily accessible The UPS contains voltage which are potentially hazardous All repairs should be performed by qualified service
3. UPS also provides the telephone surge protector to protect the telecommunication equipment Stand 08 2005 Seite 4 techbes_dt_MI_MIRM_050824 doc Anderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description 2 Description and Indicators 2 1 Front and rear panel descriptions O 6 lol Om NA QU EN PEN ZAS e 5 FN A y WY E ANA STE QE alo le A il LYS e Ed hil F i REAR VIEW OF 300 400VA REAR VIEW OF 500 600VA REAR VIEW OF 800 1000 1200VA DN 2 D A gt A CT A 77 KE REAR VIEW OF RMIGOOVA Can AE N O V vV REAR VIEW OF RMIL200VA LINE On line mode BATT INV mode ON OFF TEST SILENT key FAULT UPS in faulty or overload condition Communication port Output sockets Phone jack for telephone line surge protection option Inlet with fuse holder and spare fuse Input Breaker NO 08 E e U o a Stand 08 2005 Seite 5 techbes_dt_MI_MIRM_050824 do
4. c Anderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description 2 2 Indicators and buzzer LINE BATT FAULT Condition Continuously Twice in every 10 sec Twice in every 10 sec No load shutdown after 30 5 sec Twice in every 1 sec Low battery warning INV shutdown with restart timer on 3 Accessories 1 One user s manual 2 One AC power cord 3 One IEC cord optional with IEC outlet 4 One spare fuse 5 One bundle software package option 6 One telephone cable option with telephone line surge protector Stand 08 2005 Seite 6 techbes_dt_MI_MIRM_050824 doc Anderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description 4 Installation 4 1 Install the UPS in a protected area with adequate air flow and free of excessive dust Do not operate the UPS where the temperature and humidity are outside the specified limits 4 2 Check if the voltage as shown on the model label on the rear cover corresponds to your local power supply If it does not consult your dealer 4 3 Initial battery charging The UPS is shipped from the factory with its internal battery in a fully charged state However the battery may be lose some power during shipping and storage The battery should be recharged before conducting the following test for proper operation and to assure that UPS will provide expected run time The battery is automatically charge by the UPS whenever it is plugged in no need to
5. er besch digen Sie nicht die Batterien ausflie endes Elektrolyt ist sch dlich f r Haut und Augen 8 Eine Batterie kann eine Gefahr eines elektrischen Schlages und sehr gro er Kurzschlu str me beinhalten Folgende Vorkehrungen sollten getroffen werden wenn Sie mit der Batterie arbeiten Entfernen Sie Uhren Ringe und andere metallische Objekte Verwenden Sie Werkzeug mit isolierten Griffen 9 Dieses Ger t ist nur durch unterwiesenes Personal zu bedienen Stand 08 2005 Seite 3 techbes_dt_MI_MIRM_050824 doc Anderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description 1 Introduction The product is STANDBY UPS with the newest technology and powerful function All these series are with AVR function allows wide input voltage range including on line voltage boost up and buck down An ideal protection equipment for critical connected loads It is based on microprocessor controls with utility power connected the charging is ongoing no need to switch ON the UPS Also at back up mode UPS can be automatically turned OFF if none of the connected loads is operating to save the battery energy Self testing function is included to verify both the operations of the UPS and the condition of the battery The UPS provides communication signal through RS232 with user s computer allows to monitoring the condition of the UPS The intelligent UPS provides you with the ability of perfect protection of your critical devices The
6. otal loading can not exceed 180W for PF 1 or 300VA for PF 0 6 Stand 08 2005 Seite 7 techbes_dt_MI_MIRM_050824 doc nderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description 5 6 Loading condition Turn on the equipment s which connected with the UPS one by one to reduce the inrush current at the turn on moment Operating at overload state shown at the table below Over 110 Over 130 Over 200 Normal operation _ shut down within 30sec shut down within 2sec Short circuit protection Note Charge over night after discharge the battery 6 Maintenance The unit is designed for easy maintenance Only a little care must be taken Vacuum the dust from the ventilation openings Clean the unit with a damp cloth Storage Recharge the UPS every 90 days if the UPS was in the storage state 7 Specifications NOTE Engineering specification M1300 M1400 M1500 M1600 MIS00 M11000 M1200 RMI600 RMI1200 POWER RATING 180W 240w 300W 360w 480w 600W 720w 330W 660w VOLTAGE 170 280V FREQUENCY 45 65Hz CURRENT 1 8A 2 44 3 04 3 6A 47A 59A 71A 3 6A TAA VOLTAGE 230V CURRENT 1 3A 17A 22A 2 64 5 3A 2 6A 5 3A 266V OUTPUT ACTPONT BOOST 198V FREQUENCY 50 60Hz Auto select Waveform Step wave Overload Over 130 delay 30 seconds Transfer Line Battery Under 5 millisecond Total efficienc
7. rn to service no output alarm beeps continuously condition or equipment 9 MI Block Diagram r p 150 Ly TRANSFORMER gt 0 P RELAY SUPPRESSORS JACK I P CHG Inv 4 CONT JACK O P BATT Stand 08 2005 Seite 9 techbes_dt_MI_MIRM_050824 doc Anderungen und Irrtum vorbehalten
8. start up the UPS You can be sure that the battery is fully recharged if the UPS were left plugged over 8 hours 4 4 Connecting equipment s to the UPS To ensure that your computer equipment will be protected during a utility failure and that you receive expected run time it is important that you determine the total power loading of the equipment you wish to protect by the UPS The power requirements of your equipment should be less than or equal to the capacity of the UPS Once you have determined that your equipment and the UPS are compatible put your equipment s plug into the UPS s rear panel output sockets 5 Operation 5 1 5 2 5 3 54 5 5 Turning on the UPS Press and hold the TEST button till the first beeps sound over and then the UPS is ready to work Otherwise the UPS will not work as if misstouch the switch only for a very short time Turning off the UPS Press and hold the TEST button till the alarm beeps then all the LEDs go off and the UPS has been turned off Silent mode On BATTERY mode press the TEST button to stop the alarm until the low battery state the alarm will be active again Self test Press the TEST button on LINE mode could force the UPS to enter the self test sequence It returns to LINE mode after pass the test Load level Normally the POWER FACTOR of the UPS is designed at about 60 That is if we put a 300VA for example the t
9. y Over 94 Standard battery voltage 24VDC 12VDC Battery Quantity 1 2AH Charging current 0 40A Temperature 0 40 C 0 95 non condensing Environments Humidity Dimensions WxHxD Weight W Batterykg N W G W CE Marking TUV GS Marking C Tick AS NZS 3548 Characteristics subject to change without prior notice NOTE For reference Safety CE electrical rate Special specification NOTE The GS mark does not imply for the RMI600 1200 Standard LVD EN 50091 1 1 EN 62040 1 IEC 60950 EMC EN 50091 2 EN 62040 2 C Tick AS NZS 3548 Stand 08 2005 Seite 8 techbes_dt_MI_MIRM_050824 doc nderungen und Irrtum vorbehalten EFFEKTA UPS Series MI technical description 8 Troubleshooting guide PROBLEM POSSIBLE CAUSE ACTION The UPS can only work on 1 A loose power plug 1 Re plug the power core tightly battery mode even if the utility 2 Fuse burn out 2 Replace the fuse The UPS working normally Bad battery Return to service but with a short backup time and can not be charged fully Press down the sw but nollInternal fuse burn out Return to service response with the UPS Fault condition after press the UPS Failure Return to service ON OFF key Working at normal LINE mode 1 Bad connection of 1 Check the batt Cable but shutdown immediately as batt Cable 2 Charge the batt Over 12 transfer to battery mode 2 battery empty hours 3 Charger failure 3 Retu