Home
STT 3000 Smart Temperature Transmitter Specifications
Contents
1. Ordering Example STT350 0 EPME 0000 0000000 000 0000 0000 STT 3000 Smart Temperature Transmitter Warranty Remedy Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship Contact your local sales office for warranty information If warranted goods are returned to Honeywell during the period of coverage Honeywell will repair or replace without charge those items it finds defective The foregoing is Buyer s sole remedy and is in lieu of all other warranties expressed or implied including those of merchantability and fitness for a particular purpose Specifications may change without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use While we provide application assistance personally through our literature and the Honeywell web site it is up to the customer to determine the suitability of the product in the application Fieldbus is a trademark from Foundation Fieldbus Specifications are subject to change without notice For More Information Learn more about how STT 3000 Smart Temperature Transmitter can provide true differential temperature measurement visit our website www honeywellprocess com stt 3000 temperature transmitters or contact your Honeywell account manager Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix Arizona 85027 Tel 1 800 423 9883 or 1 800 343
2. 2 000Vdc for 1 minute Withstands dielectric test of 700Vac rms or 1 000 Vdc for 1 minute Common Mode Rejection 120dB 1 million to 1 from 50Hz to 50kHz Series Mode Rejection 40dB 100 to 1 for 50 or 60Hz 0 5Hz with internal software filter set to local power line frequency EMC compliance In compliance with 89 336 EEC Electro Magnetic Compatibility EMC Directive STT 3000 Smart Temperature Transmitter Parameter RFI Rejection 0 1 of span at 30V m over 20 to 1 000MHz in explosion proof housing with shielded cables Stability Time Drift 0 05 of maximum span per year Autocalibration against internal reference every second Physical Mounting and Construction Parameter Description Mounting DIN rail top hat or G rail Explosion Proof Flameproof housing with surface mounting or 2 inch pipe mounting IP 66 NEMA 4X Rating The FM CSA explosion proof housing meets the applicable requirements of NEMA 7 and 9 Wiring Screw Terminals M3 5x6 7mm nickel coated brass Accepts up to 12AWG 16AWG recommended Net Weight Transmitter for DIN rail mount 0 5kg 1 1 pounds Transmitter in EP or XC housing 1 6kg 3 6 pounds Transmitter indicator in housing 2 4kg 5 2 pounds Materials of construction Transmitter module Aluminum housing with baked on polyester paint cover Noryl terminal block EP housing Aluminum housin
3. 0228 www honeywellprocess com ENOI 6083 April 2012 2011 Honeywell International Inc Honeywell
4. honeywell com or TAC hfs tac support honeywell com NORTH AMERICA Honeywell Process Solutions Phone 1 800 423 9883 Or 1 800 343 0228 Email Sales ask ssc honeywell com or TAC hfs tac support honeywell com SOUTH AMERICA Honeywell do Brasil amp Cia Phone 55 11 7266 1900 FAX 55 11 7266 1905 Email Sales ask ssc honeywell com or TAC hfs tac support honeywell com STT 3000 Smart Temperature Transmitter 8 Model Selection Guides are subject to change and are inserted into the specifications as guidance only Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at http npsweb honeywell com Cultures en US Products Instrumentation ProductModelSelectionGuides default htm Honeywell Model Selection Guide STT 3000 Temperature Transmitter Model Selection Guide Models STT350 amp STT35F Fieldbus Instructions e Select the desired Key Number The arrow to the right marks the selection available e Make one selection from each table using the column below the proper arrow e Adot e denotes unrestricted availability Aletter denotes restricted availability e Restrictions follow Table VII Key Number STs f 7 f I i Il IV v i VI i Vil KEY NUMBER C O OO Descrip SSC Sete ction Avaitnbity STT350 Smart Temperature Transmitter Module 4 20MADE ia ST1T350 ee ee All modules carry the f
5. the event of primary LAS loss e Integral Digital Meter available without the need for an additional bus connection or power e Fieldbus Simulate link available for loop commissioning troubleshooting Honeywell ay Figure 1 STT35F module and Transmitter in Field Mount Housing with display indicator e Includes Flash Memory for ease of software upgrade over the Fieldbus for changes or improvements in this emerging technology e Post read validation of the measured signal before providing fresh output e Includes sensor break detection on all input wires e Configuration of the STT35F Function Blocks and the Fieldbus Application Parameters can be done with the National Instruments Configuration Toolkit or any other Fieldbus Foundation registered configurator e Single model accepts input signals from a choice of primary sensors to satisfy varying applications requirements with minimum transmitter inventory e Added Smart features include reading of the highest and lowest inputs external cold junction compensation temperature at an isothermal block and engineering units displayed in degrees C F K or R plus milliVolt and Ohms STT 3000 Smart Temperature Transmitter STT Features continued e Smart transmitter personality with local or remote interfacing means significant manpower efficiency improvements in commissioning start up and ongoing maintenance functions Write protect link included
6. to safeguard configuration settings e Suitable for DIN rail mounting or remote field mounting in a flameproof housing e Unique patented thermocouple tip resistance measurement gives predictive warning of imminent sensor failure for preventative maintenance e Provides true differential temperature measurement of thermocouple or RTD inputs by individual linearization of each sensor reading and then computing the difference e Suitable for true 4 wire Pt100 measurement or 3 or 2 wire e Write protect link included to safeguard configuration settings e Supports dual thermocouple sensor inputs for redundant sensor operation e Surge lightning protection options can be installed internally in housing or externally in conduit e Standard digital cold junction compensation function provides accurate and reliable temperature measurement over a wide ambient operating range e The STT35F FOUNDATION Fieldbus Temperature Transmitter is approved for use in systems powered by FISCO and FNICO power supplies FISCO Intrinsically Safe and FNICO Nonincendive parameters in addition to Entity parameters are included on the Control Drawing and in the User s Manual Description The STT35F transmitters are suitable as a direct replacement for any conventional or Smart temperature transmitter in use today Their memory contains the characteristics of most commonly used temperature sensors This means that you can use the Fieldb
7. 0 0 5 500 to 1760 932 to 3200 IEC 584 1 ITS 90 S 0 08 50 to 1760 58 to 3200 0 5 500 to 1760 932 to 3200 IEC 584 1 ITS 90 T 0 14 250 to 400 418 to 752 0 2 100 to 400 148 to 752 IEC 584 1 ITS 90 NiNiMoly 0 03 0 to 1300 32 to 2372 0 3 780 to 1300 1436 to G E IPTS 68 Radiamatic 0 6 420 to 1800 788 to 3272 0 7 780 to1800 1436 to Honeywell RH milliVolts 0 01 20 to 120mV 8V 10 to 45 mV Ohms 0 01 0 to 20009 0 150 to 2000Q Note that the above Accuracy values are available merely by selecting the sensor type and range i e without user calibration Improvements of up to 2 times can be obtained for the accuracy by calibrating to the required LRV URV values with simulated inputs from a calibrator box All STT35F units pass through 20 hours of Environmental Stress Screening ESS by fast cycling between 40 and 85 C to ensure maximum product reliability During this ESS process the ambient temperature compensation coefficients are determined for individual units and burned in transmitter memory to provide maximum performance over a wide range of operating conditions STT 3000 Smart Temperature Transmitter Specifications Operating Conditions Parameter Reference Rated Condition Operative limits Transportation and conditions storage Ambient temperature 23 C 2 40 to 85 C 40 to 85 C 50 to 100 C 73 F 4 40 to 185 F 40 to 185 F 58 to 212 F Humidity Rack Mounting RH 10 to 55
8. 5 to 95 5 to 100 5 to 100 Mounted in EP RH 10 to 55 5 to 100 5 to 100 5 to 100 housing Power supply Current draw 18mA constant current draw Supply Voltage and load Resistance 9 0 to 35Vdc at the transmitter terminals Dependent on number type of bus devices Vibration Maximum of 4g over 15 to 200Hz restricted to 3g with indication meter Shock Maximum of 40g Short term operative limit of 50 C 58 F Additional Specifications Cold Junction Accuracy Total Reference Accuracy 0 25 C Digital Accuracy of input CJ Accuracy T Cs only example transmitter with thermocouple Type J sensor and 0 to 200 C range Total Reference Accuracy 0 2 0 25 0 45 C Digital Ambient Temperature Effect per 10 C change from 20 C reference RTDs or Ohms 0 029 of reading T Cs or mV 0 042 of reading Cold Junction Rejection Effect 60 1 for changes from 23 C ambient Total Output Ambient Temperature Effect ATE Digital ATE CJ rejection effect T Cs only Power Supply Voltage Effect 0 005 of span per Volt Parameter Description Adjustment Range No limits to adjustments between the Maximum range and 1 eng unit e g 1 C Damping time constant Adjustable from 0 to 102 seconds digital damping Input to output galvanic isolation Input amp output common mode isolation Meets dielectric strength test of 1400Vac rms 50 60Hz
9. Conformance Origin D 0098 RD A SoG TABLE VI Additional Features No Selection Red Epoxy Painted Housing Cap Red Epoxy Painted Explosion Proof Housing Note 6 316 Stainless Steel Explosion Proof Housing Note 6 Optional Extended Warranty Pricing Table A Table VI Table Il EPOQ EPME EPSM EPFM Note 5 Installation Guide chosen Operator s Manuals and chosen Certificates are automatically shipped w ith unit See 13 STT OE 7 for additional manuals and alternate shipping Note 6 Must be ordered with Table II EP _ _ STO7 STT 3000 Smart Temperature Transmitter 10 34 44 16U 02 Issue 36 Page 3 of 4 Availability STT35 _ TABLE VII Safety Approval Body Selection Appearing on Housing Nameplate a Approval Body Body Approval Type Type Location or Classification Selection o F EE approval body certifications included OO e lafinsically Sefe Class T Ill Div 1 Groups AB C D E F G FISCO Field Device STT35F Only 1C Nonincendive Class I Div 2 Groups A B C D Suitable for Class Il Ill Div 2 Groups F G Outdoor Location Enclosure ps 4X FM Approvals Nonincendive Class I Div 2 Groups A B C D Suitable for Class Il Ill Div 2 Groups F G Outdoor Location Enclosure Type 4X Intrinsically Safe Class Il Ill Div 1 Groups A B C D E F G FISCO Field Device STT35F Only 1G Nonincendive Class I Div 2 Groups A B C D Explosion Proof Class I Div 1 Groups B C D Dust Ign
10. Technical Information STT 3000 Smart Temperature Transmitter Specifications Foundation Fieldbus Model STT35F ENOI 6083 April 2012 Introduction Honeywell s microprocessor based STT35F Smart Temperature Transmitters convert a primary temperature sensor input into a standard FOUNDATION Fieldbus output signal on a 2 wire signal plus power multidrop connection These universal temperature input models readily accept signals from a wide variety of industry standard thermocouples T Cs or resistance temperature detectors RTDs as well as basic milliVolt or Ohms sensors The output signal is either proportional to the measured variable or linerarized to temperature The STT35F output conforms to the low speed H1 of the Fieldbus Physical Layer specification IEC 61158 2 1993 The other protocol layers conform to the FOUNDATION Fieldbus section of the 8 part IEC 61158 standard This is supported by all the worldwide instrumentation suppliers and enables multidrop field instruments to be powered via a single wire pair and communicate measurement control configuration and diagnostic data at 31 25kbps STT Features e Includes Fieldbus Foundation standard Function blocks to ensure full interoperable operation Analog Input Al Control Bloc PID Resource Block RB and Transducer Block XB e Includes Link Master capability to assume Link Active Scheduler LAS role of controlling the deterministic message communications in
11. ded well Flanged well or Socket well with or without thermowell lag extensions Flange Types Raised Face Flat Faced and Ring Type Joint flange availability in 1 1 5 2 or 3 sizes Flange ratings ANSI 150 300 600 900 and 1500 ratings STT 3000 Smart Temperature Transmitter Module front view EP Housing side view Clearance for cap removal 86 mm 67mm 2 64 72 6 mm 2 86 80 2 mm 3 16 Module DIN clip DIN RAIL Housing with integral meter Clearance for cap removal EP Housing and Mounting Bracket Figure 3 STT350 Transmitter and Optional Flameproof Housing Dimensions reference only mm inches Sales and Service For application assistance current specifications pricing or name of the nearest Authorized Distributor contact one of the offices below ASIA PACIFIC TAC hfs tac support honeywell com Australia Honeywell Limited Phone 61 7 3846 1255 FAX 61 7 3840 6481 Toll Free 1300 36 39 36 Toll Free Fax 1300 36 04 70 China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 South Korea Honeywell Korea Co Ltd Phone 822 799 6114 Fax 822 792 9015 EMEA Honeywell Process Solutions Phone 80012026455 or 44 0 1202645583 FAX 44 0 1344 655554 Email Sales SC Cp apps salespa62
12. ell pricing Note 2 With a housing 20 characters max of customer information is available on the nameplate at no charge See 13 STT OE 5 for ordering instructions Note 3 Remote Meter available as Model RMA300 See Price Page 13 RM 1 Note 4 Replaces Selection US STT 3000 Smart Temperature Transmitter 9 34 44 16U 02 Issue 36 Page 2 of 4 Availability STT35 _ TABLE IV Optional Equipment Selection 0 F No Mounting Arrangement Supplied Mounting DIN Rail Mounting via 2 Clips to Top Hat or G Rail Arrangement Carbon Steel Mounting Bracket for 2 Pipe Stainless Steel Mounting Bracket for 2 Pipe No Adaptor s Supplied 1 2 NPT Conduit Connection 316 SS Conduit Entry EExd IIC Approved 2 Adaptors 172 NPT to 3 4 NPT No Lightning Protection Supplied Lightning Protection External Lightning Protection Mountable to Housing Internal Surge Lightning Protection None English Version for STT35F Only English Version for STT350 Only French Version Spanish Version Operator User Manual TABLE V Optional Extended Warranty Coverage amp Certificates Standard Warranty Additional Warranty 1 year Additional Warranty 2 years Additional Warranty 3 years Lifetime Warranty 15 years No Transmitter Configuration Calibration Certificate Onti neaineat Transmitter Configuration Calibration Certificate ptional Certificate D 0097 RD A Note 2 No Certificate of Conformance Origin __0 Certificate of
13. g with baked on epoxy polyester hybrid paint cover beige XC housing Aluminum housing with baked on 2 coats epoxy resin cover beige ST02 housing Aluminum housing with baked on 2 coats epoxy resin cover red 316 Stainless Steel housing available as a special Dimensions See Fig 3 Sensor cable entry EP XC or STO2 housing 1 2 NPT electrical connection with optional adapters for M20x1 5 or 3 4 inch NPT STT 3000 Smart Temperature Transmitter Physical Mounting and Construction Thermowell amp Probe Availability STT35F can be supplied integrally mounted with any of the previously listed standard resistance temperature devices RTDs and thermocouple TCs elements Probe Types 1 4 Rigid or spring loaded RTDs or T Cs in Inconel or Stainless Steel sheaths in standard lengths from 3 to 24 other lengths by request Standard or heavy duty service Locally mounted to the STT350 housing or remotely mounted into explosion proof mounting heads With or without probe lag hardware Hex nipple Straight nipple or Double lag and Union connections Single or dual element availability grounded or ungrounded Additionally the following types of Thermowells can also be provided as an integral thermal solution Thermowell Materials Carbon Steel 304SS 316SS 316L SS 446SS Hastelloy B Hastelloy C Monel Inconel 600 other materials by request Thermowell Types Threa
14. ition Proof Class Il Ill Div 1 Groups E F G Intrinsically Safe Class I Il Ill Div 1 Groups A B C D E F G 2J intins caly Sate Class T il Div 1 Groups AB C D E F G FISCO Field Device STT35F Only 1J FISCO Field Device STT35F Only Suitable for Class Il Ill Div 2 Groups F G Outdoor Location Enclosure Type 4X Intrinsically Safe Class I Il Ill Div 1 Groups A B C D E F G FISCO Field Device STT35F Only 2G Suitable for Class I Div 2 Groups A B C D Exia IIC T4 T5 T6 Intrinsically Safe Ell 1G FISCO Field Device STT35F 3S Zone 0 1 Only Module Flameproof Zone 1 12 G Pag T5 T6 Enclosure rated IP fi a Ex nA T5 T6 Zone 2 FISCO Field Device ic STT35F Only Honeyw ell Module to be installed in enclosure rated IP 54 minimum Non Sparking Zone 2 Multiple Marking Int Safe Zone 0 1 or Flameproof Zone 1 or Non Sparking Zone 2 Instrinsically Safe SA Zone 0 1 Exia IIC T4 Ta 70 C BR Exd IIC T6 Ta 50 to 80 C T5 Ta 50 to Flameproof 85 C INMETRO BR Exia IIC T6 Ta 50 to 40 C T5 Ta 50 to Brazil cally Sat 55 C T5 Ta 50 to 85 C ntrinsically Safe _ ER Exia lIC T6 Ta 50 to 40 C T5 Ta 50 to 50 C T5 Ta 50 to 85 C Exia IIC T4 T5 T6 Exd IIC T5 T6 ExnA IIC T5 T6 continued on next page STT 3000 Smart Temperature Transmitter 11 34 44 16U 02 Issue 36 Page 4 of 4 Availability STT35 _ TABLE VII CON T Safety Ap
15. ngs etc STT 3000 Smart Temperature Transmitter 3 Performance under Rated Conditions Input Digital Maximum Range Limits Digital Normal Range Limits Standards Type Accuracy for Accuracy Maximum for Normal Range Limits Range Limits RTD of Max Span C F C C F Pt100 0 01 200 to 850 328 to 562 0 1 200 to 450 328 to 842 1EC751 1986 0 00385 Pt200 0 01 200 to 850 328 to 562 0 1 200 to 450 328 to 842 1EC751 1986 0 00385 Pt500 0 02 200 to 850 328 to 562 0 1 200 to 450 328 to 842 1EC751 1986 0 00385 Pt100J 0 01 200 to 640 328 to 184 0 1 200 to 450 328 to 842 JISC 1604 81 0 00392 Ni500 0 04 80 to 150 112 to 302 0 1 50 to 150 58 to 302 Honeywell Type A Cu 10 0 37 20 to 250 4 to 482 1 0 20 to 250 4 to 482 General Electric Cu 25 0 19 20 to 250 4 to 482 0 5 20 to 250 4 to 482 General Electric T C B 0 14 200 to 1820 392 to 3308 1 0 550 to 1820 1022 to 3308 IEC 584 1 ITS 90 Cc 0 03 0 to 2300 32 to 4172 0 6 0 to 1650 32 to 3002 IPTS 68 D 0 03 0 to 2300 32 to 4172 0 6 330 to 1370 626 to 2498 IPTS 68 E 0 04 200 to 1000 328 to 1832 0 2 0 to 1000 32 to 1832 IEC 584 1 ITS 90 J 0 04 200 to 1200 328 to 2192 0 2 0 to 800 32 to 1472 IEC 584 1 ITS 90 K 0 04 200 to 1370 328 to 2498 0 3 120 to 1370 191 to 2498 IEC 584 1 ITS 90 N 0 06 200 to 1300 328 to 2372 0 3 0 to 1300 32 to 2372 IEC 584 1 ITS 90 R 0 09 50 to 1760 58 to 320
16. ollow ing approvals See Approvals Table VII for more information All modules carry CE Mark and are in compliance with ail EN 50081 2 and 50082 2 Russian Certificate of Pattern Approval No 2064 of Jan 1988 Use of STT350 35F within Class Ilor Ill Division 1 or 2 Groups E F and G requires the use of explosion proof field mount housing option TABLE Sensor Probe and Thermowell Accessories No Integral Sensor Probe or Thermowell Supplied Oo fee TABLE Il Transmitter Housing and Integral Meters Select approval body certification in Table VII No Housing Supplied Aluminum with a Beige Epoxy Polyester Hybrid Coating For Stainless Steel or Red Epoxy Painted Housing select Table II EP _ _ and appropriate Table VI code No Meter Supplied Integral Meter Analog Meter for Field Mount Housing Note 3 Digital Meter for Field Mount Housing Fieldbus Digital Meter for Field Mount Housing Explosion Proof Field Mount Housing Note 2 TABLE Ill Configuration amp Tagging None Factory Default Configuration Supplied Configuration Transmitter Configuration see 13 STT OE 5 for choices Transmitter Configuration Fieldbus No Tagging Requested Customer Tagging 316 SS Wired on Customer I D Tag 4 lines Note 4 28 characters per line customer specified information 316 SS Wired on Customer I D Tag blank Note 1 Specify 8 digit customer I D when probe w ell selected See Price Pages 13 TP 1 to 16 for sensor w
17. proval Body Selection Appearing on Housing Nameplate J Exia IIB or IIC T6 Ta 50 C to 40 C Exia IIB or IIC T5 Ta 50 C to 50 C Exia IIB or IIC T4 Ta 50 C to 85 C FISCO Field Device STT35F Only Module only IP 20 Intrinsically Safe Zone 0 1 Exd IIC T6 Ta 50 C to 80 C Exd IIC T5 Ta 50 C to 85 C Flameproof Zone 1 Exia IIB or IIC T6 Ta 50 C to 40 C Intrinsically Safe Exia IIB or IIC T5 Ta 50 C to 50 C Zone 0 1 Exia IIB or IIC T4 Ta 50 C to 85 C FISCO Field Device STT35F Only Enclosure IP 66 67 See ATEX installation requirements in Operator s Manuals EN1I 6162 amp EN1 6196 The user must determine the type of protection required for installation of the equipment The user shall then check the box V adjacent to the type of protection used on the equipment certification nameplate Once a type of protection has been checked on the nameplate the equipment shall not be reinstalled using any of the other certification types RESTRICTIONS Restriction Letter Available Only With Not Available With Table Selection Table C SSSelection Ss Notes See 13 STT 9 and User s Manual for part numbers See 13 STT OE 5 for OMS Order Entry Information including tagging transmitter configuration manuals certificates draw ings and SPINS To request a quotation for a non published special fax RFQ to Marketing Applications at 602 313 6155
18. us configuration tool to configure the transmitter for any of these sensors and it will automatically correct for their associated non linearity The transmitter module can also be installed on a standard DIN rail to EN50022 or remotely mounted in a flameproof housing designed for either surface or two inch pipe stand mounting Transmitters can be preconfigured at the factory to your exact specifications or they will be shipped with factory default configuration ready to accept your own configuration The H1 low speed FOUNDATION Fieldbus protocol is aimed at the replacement of 4 20mA conventional or Smart transmitters by multidrop digital field devices with signal and power carried over a single wire pair and also meeting intrinsic safety requirements Transmitters can be preconfigured at the factory to your exact specifications or they will be shipped with factory default configuration ready to accept your own configuration Configuration of the field devices and the bus operating parameters can be performed from the system console or from Windows 95 or NT PC based configuration tools such as the National Instruments Configurator The driving force behind Fieldbus is increased field intelligence and capabilities and these results in a wide range of available configuration selections such as the gain integral derivative settings in the PID control block or its mode of operation Manual Automatic or cascade or built in alarm setti