Home
WebCTRL v5 - Air Systems
Contents
1. essssss 205 Step 1 Create a spreadsheet esee eene nnnann 205 Step 2 Create a macro eseseesssesesesee eene e nennen nnns nnns anna aita sain sana 205 Step 3 Run the macto EE 206 Chapter 24 System database maintenance essere eese eeen eene nn nnne nnns 207 To back TR EE EE 207 To compact and defragment cecceccecceeeeceeeeeseeeeeseeseeeeeseeeeseseeseseeseeseseesssnseneats 207 To minimize the database size re 208 WebCTRL v5 User Manual Chapter 1 What s new in v5 What s new in WebCTRL Feature Downloading see page 43 Improved download performance Devices page see page 46 Locked values see page 33 Improved trend collection 2011 Automated Logic Corporation Improvement The downloading interface and functionality has changed as follows Downloading moved from the CFG tree to the NET tree Click the Downloads action button The Downloads page see page 44 was redesigned to provide more flexibility and more feedback on the download tasks WebCTRL can download up to 5 routers simultaneously The Memory download option see page 44 is now called All Content and includes the names of source files equipment View bacview and driver Using this information the new Devices page can show file discrepancies between the database and controller This feature also accommodates Field Assistant You ca
2. 78 To view alarms in WebCTRL ss 79 To acknowledge alarms esee 80 To delete HE 81 To receive audible notification of alarms eee 82 Setting up alarm actions 82 To assign alarm actions to alarm sources eene 82 Alarm STT EE 83 UE 87 Propagate TO SOMO enert eiut rnnt recenter geed 88 Run External Program 88 Send Alphanumeric Page sesenta 89 Send E UE EN Send SNMP Trap 94 Write Pr perty s 95 Write to Database iae rnaen a aaa aaa a aiaa a an laaa 96 Write to File APAPA EATE E E A A E A EA 100 Setting up an alarm source in WebCTRL essen 101 To set up edit or disable alarm sources 102 Tosimulate arn alarm 55 52er neo insu o arator esos e aeneae s baisses 104 To view all instances of an alarm source 104 CUSLOMIZING ALANS mL 104 El 104 Alarm categories ns 106 If you upgraded alarms from v2 0 or earlier SEENEN 107 USING f ld COUCS 108 Format TED m MM 108 Field Code 110 Chapter Reports aE 113 To run a CT PN 116 To create an Equipment Summary report 116 To create an Equipment Values report ss 117 To create an Trend Samples
3. ES VI chabie El Static Pressure Cc Static Pressure Ban 2 37 ir Static Setpoint 840 2 1 v Code Point type Al Analog Input ANI Analog Network Input ANI2 Analog Network Input 2 ANO Analog Network Output ANO2 Analog Network Output 2 AO Analog Output AV Analog Value BAI BACnet Analog Input BALM BACnet Alarm BAO BACnet Analog Output BAV BACnet Analog Value BBI BACnet Binary Input BBO BACnet Binary Output BBV BACnet Binary Value BFM Floating Motor Bl Binary Input BLSTAT LogiStat Zone Sensor with Optional OAT Display 2011 Automated Logic Corporation 37 WebCTRL v5 User Manual 38 Code BMSV BNI BNI2 BNO BNO2 BO BPTA BPWM BRS BRSF BTLO BTRN BV DI DO EVT LAN AI LAN AO LAN DI LAN DO LSTAT POLLAVG POLLMAX POLLMIN POLLTOT PTA TLO Point type BACnet Multi State Value Binary Network Input Binary Network Input 2 Binary Network Output Binary Network Output 2 Binary Output Pulse to Analog Input Pulse Width Output RS Sensor RS Sensor Fan Timed Local Override Trend Log Binary Value Digital Input Digital Output BACnet Alarm LAN Analog Input LAN Analog Output LAN Digital Input LAN Digital Output LogiStat Zone Sensor Average Analog Properties Maximum Analog Properties Minimum Analog Properties Total Analog Properties Pulse to Analog Input Timed Local Override 2011 Automated Logic Corporation WebCTRL v5 User Manual Logic pages The Logic page
4. Los Logic pages see page 39 Logic pages show the control program for a piece of equipment Use the sequence of control and yellow status values on the Logic pages for troubleshooting your mechanical equipment Microblock pop ups To open a microblock pop up where you can view and change properties e Click a microblock on a Logic page e Click the bold underlined microblock name on a Properties page e Right click a value and then select Details 32 2011 Automated Logic Corporation WebCTRL v5 User Manual Graphics pages You can view and adjust your system from Graphics pages which include navigation maps floor plans and equipment e Button Input field Drop down list Some typical controls that may appear on a graphics page are Button or switch to turn equipment on or off Input field to set a property value Drop down list to select a state Interactive room sensor to override an unoccupied schedule Setpoint graph to adjust setpoints Trend graph to view trend information Link to jump to another WebCTRL page or to the Internet NOTES Right click a value then select Details to view and change properties in the microblock pop up Right click a value then select Global Modify see page 41 to view and change the property in other control programs A yellow dashed box around a value indicates the value is locked ois On If a graphic is larger than the action pane right click the g
5. 2011 Automated Logic Corporation 91 WebCTRL v5 User Manual 92 Field Attach Report Perform Action NOTES Notes Select to attach a WebCTRL report to the e mail then select the Report and the Format NOTE The Report Name field shows a custom report only if it was created at the current system level Run as shows the name and login name of the operator creating the alarm action The report will be run using the privileges and report options of this operator TIP You may want to create a new operator with limited privileges for this purpose By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you wan
6. TRUE above the line client mssoapinit URL Step 3 Run the macro NOTE WebCTRL Server must be running 1 In Excel click Tools gt Macro gt Macros 2 Select the TestSoapRead sub routine 3 Click Run The macro will write the values into the WebCTRL database and field controllers NOTE Follow the steps below if you get an error message when you run the macro a In Excel select Tools gt Macro gt Visual Basic Editor b Inthe Visual Basic editor select Tools gt References c Select the Microsoft Soap Type Library v3 0 and click OK 2011 Automated Logic Corporation 201 WebCTRL v5 User Manual Example using Web services to retrieve trend data Follow the process below to retrieve a collection of zone temperature samples and put it in an Excel spreadsheet Step 1 Create a spreadsheet 1 Enter the following information the spreadsheet uses to log in to the WebCTRL system o WebCTRL Server IP address or the server network name Cell A1 in this example o Operator name for logging in to WebCTRL Cell A2 in this example o Operator s WebCTRL password Cell A3 in this example Enter the GQL path to the trend object you want to retrieve Cell A5 in this example NOTE You can also use a global path or a global reference name such as zone_1 Define the sample s start time Cell A6 and end time Cell A7 and the maximum number of samples to take Cell A9 The text in Cell A11 indicates where the results will
7. Synchronize Tells WebCTRL to wait for the external program to finish running before initiating the next Run External Program alarm action Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package Send Alphanumeric Page The Send Alphanumeric Page alarm action sen
8. client ClientProperty ServerHTTPRequest TRU above the line client mssoapinit URL Step 3 Run the macro NOTE WebCTRL Server must be running 1 To launch and run the macro click Tools 2 Click Macro Macros 3 Select the evalTrends sub routine 4 Click Run The macro will retrieve the data and place it in the spreadsheet NOTE Follow the steps below if you get an error message when you run the macro a In Excel select Tools gt Macro gt Visual Basic Editor b Inthe Visual Basic editor select Tools gt References c Select the Microsoft Soap Type Library v3 0 and click OK 204 2011 Automated Logic Corporation WebCTRL v5 User Manual Example using Web services to retrieve a WebCTRL report Follow the procedure below to retrieve a WebCTRL Point List report and put it in an Excel spreadsheet Step 1 Create a spreadsheet 1 Enter the following information the spreadsheet uses to log in to the WebCTRL system o WebCTRL Server IP address or the server network name Cell A1 in this example o Operator name for logging in to WebCTRL Cell A2 in this example o Operator s WebCTRL password Cell A3 in this example 2 Enter the path to the WebCTRL report Cell A5 in this example NOTE You can also use a global path or a global reference name such as zone 1 QD BeON A B 192 168 162 170 administrator abc Arees geographic chiller point list report The macro will write the report data t
9. 84 Field Notes Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group lt your new group gt is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group lt your new group gt is Unoccupied Available only if you have the Advanced Alarming package Using the WebCTRL Alarm Notification Client application The WebCTRL Alarm Notification Client application must be running on each client computer that should receive popup notificat
10. FB NY a NOTE You can display icons and hover text in the GEO tree that show where privileges have been assigned See Tree icons and hover text page 22 To delete a local privilege set assignment On the GEO or NET tree select the location where the assignment was made Click Privileges Select the assignment under Privilege Set Assignments at this Level Click Delete Click OK a fF N 2011 Automated Logic Corporation 133 WebCTRL v5 User Manual Restricting access in the system Restricting an operator s access to areas of the system You can give an operator access to only a specific area of the system All other areas will be either grayed out or not visible when the operator logs in to WebCTRL EXAMPLE If you give an operator the Access Geographic Locations privilege only at the first floor of the system shown below he will see a navigation tree like the one on the left The areas above the first floor are visible because he needs them to navigate to the first floor but grayed out because he cannot access them The operator does not see Dallas New York or San Francisco because he can t access them and does not need them to navigate Restricted access Full system oi World Corporation B Atlanta R amp D Facility lE Basement First Floor Second Floor Third Floor OA Conditions a orid Corporatior E At anta R amp D Fa GR First Floor ie Administration amp Main Conf
11. the 64 bit install does not include Local Access support The 32 bit install that supports all connection types can be used on a 64 bit operating system NOTE MS Access is not available on a 64 bit installation of WebCTRL If your system uses an Access database and you want to upgrade to the 64 bit version of WebCTRL v5 you must migrate your Access database to a different type of database before upgrading WebCTRL v5 User Manual Feature HyperTerminal replaced by PuTTY in Help Feature Microblock Common Properties Editor ZN microblock rules Integrator microblock is non volatile Always upload feature in BACnet Analog Value Parameter microblock BACnet PID microblock 20 state BACnet Multi state Value Parameter and 20 state BACnet Multi state Value Status microblocks OCL microblock system variable for weekday Wildcard instead of Device ID in BACnet addresses Improvement Windows operating systems after XP do not include the HyperTerminal application You can download the external application PuTTY to communicate locally with controllers Most HyperTerminal instructions in Help have been replaced with PuTTY instructions For HyperTerminal instructions see Communicating using HyperTerminal What s new in EIKON LogicBuilder Improvement You can view or edit common properties for the 1 0 Network Display and BACnet microblocks in a control program A ZN control program can now have e Amaximum of
12. 13 or 9 FP BIN D WO N Oo WebCTRL v5 User Manual Condition Indicated In equipment when running WebCTRL Design Server In a controller non operational or no communications In equipment a hardware or software error In a controller a download is required or is already in progress In equipment a controller has stopped Control program error NOTE If a zone controlled by a U line controller shows coral on a floorplan the controller may be offline Heating or cooling alarm Maximum cooling Maximum heating Moderate cooling Moderate heating Unoccupied inactive Occupied active Free cooling In a controller operational or operational read only In equipment No heating or cooling Five conditions may affect a zone s thermographic color Setpoint adjust Timed local override TLO Optimal start Demand level Hysteresis In the examples below a zone s heating occupied setpoint is 70 and its cooling occupied setpoint is 74 2011 Automated Logic Corporation 25 WebCTRL v5 User Manual 26 If you normally see green gray gray yellow green when the zone temp is 72 5 73 unoccupied TT unoccupied 75 73 5 but someone adjusts the setpoints for example with a setpoint adjust of two degrees the new setpoints would be 68 and 72 someone presses the Override button on a room sensor to use the occupied setpoints the zone is in optimal sta
13. Group the left of the icons Alarm incident group All alarms related to a particular incident For example an alarm and its return to normal form an alarm incident group Status table Gives the status of alarms at the current location Here and in the entire system Total This table shows the number of alarms that need a return to normal need to be acknowledged or are closed 2011 Automated Logic Corporation 79 WebCTRL v5 User Manual Field Notes Alarm icon Indicates the alarm category o Access Control Q Lighting I Module Alarm L Fire General Alarm D System Error e B HVAC 1 General Message Unknown Critical alarms The category icon plus For example vel e e Maintenance alarms The category icon plus 1 For example OL Occurred The date and time the alarm was generated To Do Acknowledge indicates the alarm needs to be acknowledged Waiting for normal indicates the alarm requires a return to normal A checkmark indicates the alarm is closed Details The alarm message NOTE An alarm that requires a return to normal appears in red text until the alarm condition returns to normal Navigation buttons Use these buttons to move through the alarm list To the end of the list One alarm at a time One page at a time Additional Actions You can e acknowledge or delete multiple alarms simultaneously e search for an alarm generated on a particular date and time NOTES e Alarms generated by WebCTR
14. Operator groups are useful if you have multiple operators who need the same privilege set or you have positions with high turnover rates You can assign an operator to a group when you enter the operator or when you create the operator group NOTE When using hierarchical servers you must create identical operators on each server in order to navigate across servers Default operators WebCTRL is installed with the following default operators Operator Has To log in Administrator Almost all privileges Type Administrator inthe Name field then click Log in Anonymous The Standard privilege set that Click Log in contains only viewing privileges 2011 Automated Logic Corporation 127 WebCTRL v5 User Manual To ensure system security log in as the Administrator then do one of the following e Assign the Admin privilege set to another operator then delete the Administrator operator e Assign a password to the Administrator operator CAUTION Passwords can be forgotten To ensure access to the administrative functions of WebCTRL assign the Admin privilege set to at least two operators If you want to prevent Anonymous access to your system delete the Anonymous operator To add or edit an operator 1 Onthe CFG tree select Operators 2 Click Add to enter a new operator or select an operator to edit his settings 3 Enter information on this page as needed The only required fields are Name and Login Name See t
15. Used only with the Write to Database alarm action You must include this field code in the Database Insert String The time when the alarm returned to normal The setpoint value from the alarm source Valid only for alarm type FLOATING LIMIT The formatted alarm short text The display name of the site the alarm came from The display name of the alarm source that generated the alarm The description of the alarm source that generated the alarm For advanced users displays the database item indicated by lt path gt relative to the alarm source for example lt path gt equipment display name The easiest way to display the path is to use Global Modify The system folder name The current state of the alarm source for example Normal Fault Off normal High limit Low limit 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 9 Reports Use WebCTRL reports to monitor and troubleshoot your system In WebCTRL you can e View preconfigured reports e Create custom reports See the table below for a list of all reports The Reports button drop list varies depending on whether you selected the GEO or NET tree and if you have created any custom reports at or above the selected location A report shows data for the selected item and all of its children NOTE You can display icons and hover text in the GEO tree that show where custom reports have been created See Tree icons and hover
16. alarms or trends for that microblock in the same way that you would make changes on a regular Properties page see page 36 Alarms page see page 101 or Trends page see page 65 4 Click OK or Apply NOTE Right click a value then select Global Modify see page 41 to view and change the property in other control programs 2011 Automated Logic Corporation 39 WebCTRL v5 User Manual Using a Logic page to troubleshoot WebCTRL monitors your system and provides feedback Interpreting the feedback on a Logic page is a powerful troubleshooting tool If you find an unexpected value on a Properties page or a Logic page work your way backward right to left through the sequence in the control program to discover what caused that value See Microblock reference to understand what each microblock in the sequence is doing Unexpected feedback Space temperature reads excessively high or low Equipment displays an unexpected color effective setpoints are different than the programmed setpoints Gaps in trend data on trend graph WebCTRL is not receiving alarms from a BACnet alarm microblock Output should be off but the equipment is on Sensor value on the Properties page does not match the reading from handheld sensor 40 Possible cause e The sensor has a short or open circuit Verify wires are properly connected at the sensor and controller e Asensoris missing or configured incorrectly on its Properties
17. edit and delete alarm messages and actions edit all properties on the System Settings page add edit delete and download schedules add edit and delete schedule groups add edit and delete categories edit Trends Display Setup and Trends Print Setup on the CFG tree edit Alarm Template and Reporting Action Templates acknowledge all non critical alarms acknowledge all critical alarms force non critical alarms to return to normal force critical alarms to return to normal delete non critical alarms delete critical alarms run the Location Audit Log and System Audit Log reports mark equipment for download and initiate a download issue the Shutdown manual command that shuts down WebCTRL Server 125 WebCTRL v5 User Manual 126 This Functional privilege allows an operator to Engineer System e login and make database changes in SiteBuilder e use the copy notify reload and revert manual commands e access the Configure and Set up Tree right click menus in WebCTRL e Add text in the Notes field on an equipment s Properties page Access Commissioning Tools access e Equipment Checkout e Airflow Configuration e Trend Report and Graphic categories that require this privilege e Discovery tool Maintain Graphs and Reports add edit and delete trend graphs and reports Maintain Connections edit Connections page properties Remote File Management access files using a WebDAV utility Remote Data
18. latched_data_digital x location_path long_message message_details message_prefix message_text new_state new_value object_ID out_of_service overridden 2011 Automated Logic Corporation WebCTRL v5 User Manual Description The exceeding value from the alarm source Valid only for alarm type OUT OF RANGE The status of the fault condition from the alarm source The feedback value from the alarm source Valid only for alarm type COMMAND FAILURE Additional text recorded in the alarm by the device The previous state of the alarm source The operator who forced the alarm to return to normal The time in the controller when the alarm was generated The in alarm status from the alarm source The time the alarm s entire incident group closed x ranges from 1 to 5 The display name of the alarm source that generated the alarm x ranges from 1 to 5 The display name of the alarm source that generated the alarm Displays all the path display names from root to source The formatted alarm long text displayed by double clicking the alarm on the Alarms page The message details displayed on the Alarms page View tab The message prefix displayed on the Alarms page View tab The message text displayed on the Alarms page View tab The status of new state from the alarm source The new value from the alarm source Valid only for alarm type CHANGE OF VALUE
19. see page 43 NOTE You can click Delete Unused in the Control Programs section to delete all unattached control programs and any supporting files with the same name from the programs folder To edit a control program on a WebCTRL client On a WebCTRL client you can get a copy of a control program from the server edit it then put it back on the server 172 To get the control program zl Oo oO 5 WD Right click the equipment on WebCTRL s GEO or NET tree then select Configure In the Control Programs section click Edit Existing Click Save Browse to the folder you want to put the file in Click Save Click Close Click Close again To put the edited control program back on the server oc fF WD Right click the equipment on WebCTRL s GEO or NET tree then select Configure In the Control Programs section click Add New Browse to select the control program Click Open Click Continue Click Close Click Close again 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 19 Working with drivers in WebCTRL A controller s driver is defined in SiteBuilder when the system is engineered but you can make the following changes to a driver in WebCTRL e Change or upgrade a driver See topic below e Reload a driver if it becomes corrupt for example a driver page is missing in WebCTRL On WebCTRL s NET tree right click the controller or driver then select Reload Driver Changes y
20. 2 Make changes on the Settings or Contact Info tab See table below 3 Click OK Field Notes Change password Enable this field then type your current and new passwords Starting Location and The location and page WebCTRL will display after you log in Starting Page Language The language and formatting conventions you want to see in WebCTRL NOTES e If you will be using a language other than English see Setting up your system for non English languages page 181 for additional requirements e f support for your selected language is removed in SiteBuilder WebCTRL will automatically assign the System language to you Automatically collapse Expands only one tree branch at a time trees Play sound at browser Select the Non critical alarms or Critical alarms checkbox if you want when server receives the system to audibly notify you when that type of alarm is received If you want to use a custom sound file au or wav 1 Putthe file in the webroot _common lvi5 sounds folder 2 Inthe Sound File field replace warning bell au or critical bell au with the name of your sound file NOTE You can put your sound file anywhere under the WebCTRLX x folder but be sure to change the path in the Sound File field 130 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 11 Advanced security Optional WebCTRL Pa NOTE Tosee if your system has this optional package click Ex then select About You have this package if En
21. 2011 Automated Logic Corporation 139 WebCTRL v5 User Manual 140 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 13 Manual commands To run a manual command 1 Click the menu button Le then select Manual Command 2 Type the manual command in the dialog box then click OK TIP Ctri M also opens the dialog box You must have the Manual Commands Console Operations privilege to access the manual commands dialog box The descriptions below tell you if you need an additional privilege to run the corresponding command Command Description addon Opens a dialog box where you can upload start stop or remove an add on program such as Tenant Override Billing arcnet Run this command each time you plug a device such as a laptop into a controller using an ARCNET card The arcnet command configures WebCTRL to recognize your device as the WebCTRL server Run this command from the equipment controller or network level on the NET tree autopilot location Displays the full path for the current location and copies the path to the Windows clipboard You can then paste the path into the autopilot xml file that runs WebCTRL s autopilot See Running WebCTRL s autopilot page 149 bbmd commands You must have the Manual Commands Adv Network privilege to run bbmd commands bbmd read lt IP address gt Reads the BBMD table of the controller at the given IP address For example to display the BBMD table in the BACne
22. Bundled Resources 4 Click di locate and select the translation file s for this control program then click Open NOTES o Do not add equipment xx native files that you created for multiple control programs o You can use Ctrl click or Shift click to select multiple files 5 Save the control program The translation files are embedded in the control program the original files are no longer necessary 2011 Automated Logic Corporation WebCTRL v5 User Manual Extension codes and encoding Language Extension codes Encoding English _en IS0 8859 1 French fr FR IS0 8859 1 German _de IS0 8859 1 Japanese ja EUC JP Korean _ko EUC KR Russian ru KOI8 H Spanish _es ISO 8859 1 Swedish _SV ISO 8859 1 Simplified Chinese _zh GB2312 Traditional Chinese _zh_TW Big5 Thai _th TIS620 Vietnamese Vi Cp1258 Encoding is used when you create the translation file Creating graphics for a non English system Use ViewBuilder to create graphics for a single language system Use WebCTRL extensions for FrontPage to create graphics for a multi language system Creating a non English graphic in ViewBuilder NOTES e The names of your view file and any inserted image files must contain only ASCII characters e Graphics created in ViewBuilder do not use translation files Type non English terms directly into the graphic in ViewBuilder Before you begin adding objects to a graphic 1 Select Configure View Properties 2 Inthe Language fiel
23. Double click Text on the graphic Type the key term in the Key field Enter the location of the translation file in the Resource field See step 4 above Click OK a fF N Creating a non English system in SiteBuilder To set language preferences 1 In SiteBuilder select Configure gt Preferences 2 Select the Language tab 3 Under Supported Languages select each language that your system will display NOTE Each language you select requires a language pack See Installing a language pack page 181 Select the system language under System See System Language page 188 Click OK Save your database 2011 Automated Logic Corporation 187 WebCTRL v5 User Manual To create your system To create your system in each language that the system will display 1 2 o Oo P In SiteBuilder select Configure gt Preferences Select the Font tab To the right of each language that your system will display click Default and select the appropriate font for that language from the drop down list Click the Language tab Select a language in the Current Session field Click OK Create your system Save your database If your system will display multiple languages a Select Configure gt Preferences select the Language tab and select another language in the Current Session field b Re enter all node names and display names in the current language c Save your database d Repeat steps a through c f
24. Field Assistant Select the checkbox to use the Alarm Notification Client application See Alarm Popup page 82 If the server has more than one network interface adapter type the IP address of the server s network connection that the Alarm Notification Client application will connect to Change this field if the Alarm Notification Client application will use a port other than 47806 on the server Shows any workstation whose Alarm Notification Client is actively connected to this server For troubleshooting you can download a zip file that contains logs of system activity Notes Records operator activities and some system activities such as opening and closing the database or automatic deletions in a text file The default file is auditlog txt stored in WebCTRL webroot lt system_name gt You can change the file name and include a different path To prevent the file from growing too large as new data is appended 161 WebCTRL v5 User Manual Field Log audit data to database Delete database entries older than days Log errors for invalid URLs Security Policy Allow remote file management Return operators to previous locations when server reconnects Log off operators after _ _ HH MM of inactivity Lock out operators for minutes after __ failed login attempts Use advanced password policy Do not synchronize operator and privileges Notes you can archive the data to another text file by
25. Global Copy see page 41 to copy trend properties to other pieces of equipment that use the same control program e Runa Trend Usage report see page 113 to view trend data Graphing data for multiple points You can graph multiple trend points simultaneously to help monitor and troubleshoot your system AHU 1 Temps A comparison trend graph can display up to four graphs on the page Each graph can display up to 4 similar points 4 binary points or 4 analog points NOTES e Before you create a comparison trend graph you must enable trending for the individual points you want to include in the graph See To collect trend data for a point page 65 e You can display icons and hover text in the GEO tree that show where trend graphs for multiple points have been created See Tree icons and hover text page 22 2011 Automated Logic Corporation 67 WebCTRL v5 User Manual To create a comparison trend graph You can select up to 16 trends to view then save them for graphing again later 1 2 3 In the GEO tree select the area or equipment where you want to view the graph Click the Trends button drop down arrow then select New Graph Select up to 16 trends from the selection tree NOTES o Use Ctri click Shift click or both to select multiple items o The tree shows only points that have trending enabled See To collect trend data for a point page 65 Click View Optional Click Save to name and save the t
26. Historian Store Trends Now Every __ trend samples write to historian Trend samples accumulated since last notification Last Record Written to Historian Keep historical trends for days Delete Notes Records the point s value only when the value changes by at least the amount of the COV Increment NOTE Use this method for a binary point or for an analog point that has infrequent changes in value Type the maximum number of samples to be stored in the controller NOTES e Trending consumes memory in the controller The amount of memory available depends on the type of controller Each trended point consumes 48 bytes of memory plus 10 bytes for each trend sample Each trend microblock consumes 416 bytes of memory plus 10 bytes for each trend sample e Click Reset to delete all samples currently stored in the controller e Changing the value in Allocate memory for trend samples in the controller will delete all of the point s trend samples currently stored in the controller Click the Store Trends Now button before changing the value to transfer the trend data from the controller to the system database The sample and memory allocation fields together define trend data storage in the controller in terms of hours EXAMPLE f you set these fields so that samples are collected every 5 minutes for a maximum of 120 samples the controller will store 600 minutes 5 x 120 or 10 hours of trend data Select this field to s
27. Hold down Ctrl while rolling your mouse wheel to zoom in or out on the contents of the action pane e Right click the action pane and select Scale to 10096 to restore the contents to their original size e fa graphic does not fit in the action pane right click it and select Scale to Fit to make it fit the action pane Select Scale to 100 to return it to its original size Using right click menus You can right click the following items to select options A tree item The action pane A property di World Corporation E I Bldg B Help A Basement Print B First Floor i k Configure Copy E f Ctrl C Module Status Ger Gage Ctr V Scale to Fit Ctri S Ctrl 0 ect Scale to 100 Ctrl 0 Ctrl Click Tree Display Options i Alt Click Reload Control Program Copy Control Program Properties Copy Path To print the action pane Click to print the contents of the action pane Set the print orientation to Landscape in the Print dialog box 24 2011 Automated Logic Corporation Colors and status in WebCTRL The following colors indicate equipment status throughout WebCTRL on floor plans equipment property pages and some reports Color Color Name Mustard Purple Charcoal Coral Red Orange Dark blue Yellow Light blue Gray White Light green Green Colors and setpoints Thermographic colors indicate how much a zone s actual temperature differs from its setpoints Status Code none O or 15 14
28. Name The name that appears in the Graphics button drop down list Category The name of the category that multiple graphics may be sorted into in the Graphics button drop down list NOTE Changes to Display Name or Category apply only to WebCTRL and are not retained if you export source files Reference Name The name that is used to create links to the graphic in ViewBuilder Included in download Equipment graphics only Select to have the view file included in an All Content download so that it can be uploaded by Field Assistant The graphic will have beside it in the Attached list Requires 4 x or later drivers You can click Delete Unused at the bottom of the Views section to delete all unattached graphic files from your system To edit a graphic on a WebCTRL client 34 On a WebCTRL client you can get a copy of a graphic from the server edit it then put it back on the server To get the graphic 1 2 At the bottom of the Views section click Edit Existing On WebCTRL s GEO tree right click the item that the graphic is attached to then select Configure 3 Select the graphic you want to edit 2011 Automated Logic Corporation WebCTRL v5 User Manual Click Save Browse to the folder you want to put the file in Click Save Click Close Click Close again oN Oo P To put the edited graphic back on the server On WebCTRL s GEO tree right click the item that the graphic is attached to then select Configure At
29. Spanish This_value Este valor es present_value Zone_temp Temperatura de zona If WebCTRL will be displayed in multiple non English languages create a translation file for each language To create and implement a translation file 184 Create your translation file in a text editor such as Microsoft Word that supports the character encoding you need 1 Type one key term and language equivalent per line left justified starting in column 1 Do not put spaces on either side of the equal sign 2 Save the file using the appropriate file name and location in the table below If key terms are used in the file name is File location Asingle control program lt any_name gt _xx native Any location Multiple control programs equipment_xx native WebCTRL webroot lt system_name gt resources A single graphic name xx native WebCTRL webroot graphic lt system_name gt graphics IvI5 Multiple translations_xx native WebCTRL webroot graphics lt system gt resources xx the language extension code See Extension codes and encoding below If you are using o the English character set save the file as Text only o anon English character set save the file as Encoded text See your application s help for information on saving files as encoded text When prompted for the language and encoding see Extension codes and encoding below 3 Open the control program in EIKON LogicBuilder then select Control Program gt
30. Tuning and Logic Parameters Edit Manual Override Parameters Edit Point Setup Parameters allows an operator to e Add edit and delete operators operator groups and privilege sets e Update WebCTRL Server with service packs and patches e Register the WebCTRL software See To register your WebCTRL software page 167 e Enable and set up advanced security features see page 131 optional package such as location dependent operator access and a configurable password policy e Add and remove WebCTRL web applications such as EnergyReports allows an operator to access but not edit pages from the GEO tree pages from the NET tree pages from the GRP tree pages from the CFG tree alarms logic pages anything in a category that has the same privilege assigned to it See To create a custom privilege below allows an operator to edit properties such as occupied and unoccupied heating and cooling setpoints demand level setpoint offsets thermographic color band offsets heating and cooling capacities and design temperatures color hysteresis and learning adaptive optimal start capacity adjustment values gains limits trip points hysteresis color bandwidths design temperatures and optimal start stop locks on input output and network points point number type range and network source and destination 2011 Automated Logic Corporation This Parameter privilege Edit Restricted
31. a database are contiguous As records are added deleted and modified the records become scattered in the database This condition called fragmentation can slow down system performance and increase the database size Compact the database to correct this situation The files on the server s hard drive can also become fragmented Defragment the hard drive to correct this situation You should compact and defragment on a regular schedule such as once a month But you may need to do these more often depending on how often the data or files change TIP To minimize the effects of fragmentation you should maintain at least 2096 free disk space on the server 2011 Automated Logic Corporation 207 WebCTRL v5 User Manual Compacting the database MSDE MySQL MS SQL Server Oracle and PostGreSQL databases are compacted dynamically compacting occurs in the background when a database is open To compact an MS Access database Shut down WebCTRL Server and SiteBuilder Click Start gt Control Panel Double click Administrative Tools Double click Data Sources ODBC On the User DSN tab click MS Access Database then click Configure Click Compact Under Directories select your system s folder under webroot Under Database Name select core mdb then click OK Under Format select Version 4 x then click OK 2 o O0 0 BR WO DN a 0 When asked if you want to replace the database click Yes 1 When compacting finis
32. alarm source has an alarm message category and template defined in EIKON LogicBuilder You can change messages and categories in WebCTRL Alarm messages An alarm message is the information WebCTRL displays on the Alarms page View tab for an alarm An alarm message can consist of three parts Prefix and Text make up the alarm message you see without double clicking the alarm Message Prefix optional Text alarm or return Details optional Text defined in the control program You can edit Text only at the alarm source in EIKON LogicBuilder 104 2011 Automated Logic Corporation WebCTRL v5 User Manual Prefix and Details are hierarchical They apply at the location where they are added and to all its children For example you could enter Details at the system level to show the acknowledge time for alarms in the HVAC Critical category The acknowledge time would then be in any HVAC critical alarm message in the system NOTE An alarm action can have a different message from the alarm message seen on the View tab To edit the message for a particular alarm action see Setting up alarm actions page 82 To edit the message for an alarm source 1 2 On the GEO tree select the alarm source microblock Click Alarms then select the Messages tab NOTE Sample Alarm Message and Sample Return Message show the messages as they are currently defined Do the following as needed o Edit the Text for Alarm or Return Yo
33. any open WebCTRL pages You must have the System Shutdown privilege to run this command storetrends Uploads trend data from the controller s to the database for all equipment at and below the selected item on the GEO tree This command stores trend data for points that have Trend Historian enabled 146 2011 Automated Logic Corporation Command timesync updatedriver commands updatedriver updatedriver net updatedriver all whereami whoson zap 2011 Automated Logic Corporation WebCTRL v5 User Manual Description Synchronizes the time on all controllers at the current location and below to the time on the server Run this command only from a location in the NET tree NOTE For CMnet networks executing a timesync on a controller sends the timesync to its gateway and all the controllers under that gateway You must have the Manual Commands Adv Network privilege to run this command You must have the Engineer System privilege to run updatedriver commands Updates the selected controller to the latest version of its driver Updates the selected controller to the latest version of its driver and any other controllers on the same network that use that driver Updates the selected controller to the latest version of its driver and all other controllers in the system that use that driver Displays the full path for the current location and gives the display and reference names of the action button ca
34. array of the raw values for the given expressions c String getDisplayValue String expression Returns the display value for the given expression d String getDisplayValues String expressions Returns an array of the display values for the given expressions e setValue String expression String rawVal String reason Sets the given raw value for the expression f setValues String expressions String rawVals String reason Sets an array of the given raw values for the expressions g setDisplayValue String expression String displayVal String reason Sets the given display value for the expression h setDisplayValues String expressions String displayVals String reason Sets an array of the given display values for the expressions Parameters e expression For Methods a through d its the GQL expression to be evaluated For points expression only needs to refer to the microblock present value is assumed For Methods e through h its the GQL expression for which new value is to be set e rawVal The raw value for instance 1 indicating a On status e displayVal The display value for instance On indicating On status e reason Reason for the change raw value versus display value For a binary input that is on the raw value would be 1 For an operator whose default language is English the display value would be On The display value is in the operator s default language
35. be listed after the macro is run A B 192 168 162 170 administrator abc fvav zone temp trend log 1 13 07 8 00 AM 1 13 07 5 00 PM OO MO RO is 100 10 11 Results 12 The macro will retrieve the trend data and write the time of each sample in column A and the corresponding zone temperature in column B Step 2 Create a macro The macro will retrieve the values from your system s trend log and put them in the spreadsheet 202 The following steps correspond to the numbered parts of the code shown below 1 2 Name the subroutine evalTrends that will retrieve the trend data from WebCTRL Define which spreadsheet cells contain the host WebCTRL server user WebCTRL operator password WebCTRL operator s password 2011 Automated Logic Corporation WebCTRL v5 User Manual 3 Add this section to define the data read from the GQL expression for the trend in cell A5 This retrieves trends from startDate to endDate LimitFromStart to retrieve maxRecords from beginning if true from end if false MaxRecords the maximum numbers of records to retrieve expression the expression to evaluate 4 Identify the Web services program that allows the Excel spreadsheet to retrieve the data from the WebCTRL server over the network or Internet Enter the code to authenticate the user Enter the error handling code Add this code to retrieve the trend data and displayed it on Oo OC This displays an error chec
36. be logged off without warning ao a fF oO N In WebCTRL press Ctrl m Type whoson inthe manual command field Obtain the ID number of the operator you want to log off Press Ctrl m Type logoffuser x where x is the ID number Click OK To shut down a system 1 2 3 In WebCTRL Server select Server gt Shut Down Optional Select a delay option then edit the Notification message Click Shut Down NOTE You can also type shutdown in the manual command dialog box in WebCTRL to shut down the server 30 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 5 Working with equipment You can view and adjust equipment operation from the following pages Graphics pages see page 33 You can view and adjust your essential building controls on most Graphics pages e Thermographic floor plans indicate the temperature of zones compared to their effective setpoints e Equipment graphics show the current status of mechanical equipment and often include an adjustable setpoint control or other editable properties 2011 Automated Logic Corporation 31 WebCTRL v5 User Manual Properties pages See page 36 e oe Een Each piece of equipment and each microblock ne See has a Properties page You can view and adjust E Tempers Comet more equipment properties on a Properties m lm CAPI Lee come unanime 4e TY namen page than on its corresponding Graphics page femmen eT ie eem
37. but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package Setting up an alarm source in WebCTRL The application engineer usually sets up alarm sources in EIKON LogicBuilder In WebCTRL you can e Edit an alarm source s settings from EIKON LogicBuilder or set up a new alarm source to generate alarms e Setup all alarms for a piece of equipment at once on the Alarm Sources tab of the equipment s Properties page e Simulate an alarm to test its setup Two types of microblocks generate alarms in control programs e Alarm microblocks include logic that takes into account conditions such as space occupancy e O point microblocks can generate an alarm when the present value exceeds defined limits analog or when the present value changes to an off normal state binary This type of microblock is typically set up for analog points to generate alarms for sensor failure 2011 Automated Logic Corporation 101 WebCTRL v5 User Manual Alarm microblocks and 1 0 microblocks can have similar
38. fa Elem School 1 d r Elem School 2 d r Elem School 3 High Schools Middle Schools Scheduling Groups Add Folder E Elementary Schools g Elem School 1 Add Group fi Elem School 2 fi Elem School 3 E High Schools m EH g High School 1 d High School 2 E Middle Schools OS Middle School 1 dg Middle School 2 2011 Automated Logic Corporation WebCTRL v5 User Manual To create folders and add groups to them On the GRP tree select Scheduling Groups Click Add Folder Type a name for the new folder in the Name field Optional Change the default Reference name Click OK Repeat steps 1 4 for each folder that you want to add o Om 5 KN Do one of the following to add a group to a folder o Ifyou have already created the group drag and drop it into the appropriate folder in the tree on the Scheduling Groups page then click OK o Select the folder in the tree on the Scheduling Groups page click Add Group enter a Name for it then click OK NOTE You can also add a folder to a folder or drag and drop a folder into another folder To edit or delete a schedule 1 Doone of the following o On the GEO tree select the tree item where the schedule was defined o On the GRP tree expand Scheduling Groups then select the group you want to edit the schedule for Click Schedules then Configure Select the schedule you want to edi
39. links shown above Ele Edit Format View Help extra login links properties Notepad ole E pagi linkl text ALC Home linkt url http www automatedlogic com link2 text ALC Dealer website link2 url http accounts automatedlogic com link3 textzALC Technical Support link3 url mailto alctechsupt automatedlogic com 2011 Automated Logic Corporation 169 WebCTRL v5 User Manual 2 Save the file with the following name and location File name extra login links properties Location WebCTRLx x webroot lt system_name gt To add text to the login page 1 Inatext editor such as Notepad type the text that you want on the login page Example to add text shown above 2 legal_disclaimer txt Notepad Ele Edit Format View Help unauthorized use is prohibited Usage may be subject to security testing and monitoring Misuse is subject to criminal prosecution 2 Save the file with the following name and location File name legal disclaimer txt Location WebCTRLx x webroot lt system_name gt 170 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 18 Working with control programs in WebCTRL A control program is typically defined in SiteBuilder when the system is engineered but you can make the following changes to a control program in WebCTRL These changes require you to download All Content to the controller see page 43 e Select a different control program See top
40. mum cb d een to 3rd party nebwork A single equipment networks that does not use f controller BACnet MODBUS LON BACview6 m nes displays values and ZN ZN RS Pro allows editing of RS Standard properties 2011 Automated Logic Corporation WebCTRL v5 User Manual The WebCTRL client uses Internet Explorer to access WebCTRL Server as a website Access and security options in WebCTRL may include WebCTRL client outside dial up networking WebCTRL Server Java Platform WebCTRL clients internal network WebCTRL client outside Internet connection I P Router Firewall Network security Transport Layer Security Secure Layer Virtual P etwork N N QD x A WebCTRL clients outside wireless browsers WebCTRL editions WebCTRL supports e Unlimited simultaneous users e Multiple operating systems and databases e Built in alarming trending and reporting e International languages International English Korean Traditional and Simplified Chinese Spanish French German Russian Swedish Thai e Third party integration e WAP enabled devices e Secure server access using TLS SSL e Optional WebCTRL packages listed below WebCTRL 500 supports all the same features and options as WebCTRL in systems with fewer than 500 points NOTE Points include all input and output points tied into the system regardless of vendor 2011 Automated Logic Corporation 17 WebCT
41. names So when you are going to enable an alarm source first look for an alarm microblock in the GEO or NET tree This type of microblock Appears in the GEO or NET tree as HI ZONE TEMP Zone Temp To set up edit or disable alarm sources To set up edit or disable a single alarm source 1 On the GEO or NET tree select the alarm source microblock 2 Click Alarms then select the Enable Disable tab 3 Make changes to the fields as needed The fields can vary for different types of alarm sources See table below 4 Click OK TIP To set up all the alarms for a piece of equipment at once click Properties then select Alarm Sources Field Notes Potential alarm source Select the checkbox to enable the alarm source to generate alarms Clear the checkbox to disable the alarm source Alarm Select to have the alarm source generate an alarm when the specified conditions occur e Fora binary input enter the conditions for generating an alarm e Foran analog input type the low and high limits that when exceeded will generate an alarm Deadband The amount inside the normal range by which an alarm condition must return before a return to normal notification is generated EXAMPLE 215 Deadban n Low s 25 10 Deadband Alam is generated e Return to Normal is generated NOTE If the Status checkbox is selected the alarm condition currently exists 102 2011 Automated Logic Corporation Field Retu
42. on mismatch on the System Settings gt Communications page to have WebCTRL upload automatically e Clear Always upload properties from controllers to WebCTRL Server on mismatch so that you can evaluate every mismatch to determine the correct value When a mismatch occurs 1 On WebCTRL s NET tree select the controller s network 2 Click Devices 2011 Automated Logic Corporation WebCTRL v5 User Manual 3 On the Manage tab select a controller with a mismatch 4 Do one of the following Click Upload to upload parameters from the controller to WebCTRL Server Click Download to download parameters from WebCTRL Server to the controller NOTE Click the mismatch message in the Status column to view details Setpoints Use setpoints to set temperature values that control the HVAC equipment WebCTRL displays green when a zone is within the desired temperature range determined by the heating and cooling setpoints e Programmed setpoints are set and changed by operators See To change programmed setpoints page 49 e Effective setpoints reflect the impact of other system conditions on the programmed setpoints such as setpoint adjustments demand reduction adjustments and hysteresis Effective setpoints control the equipment Besides manually adjusting setpoints you can use the following cost saving strategies see page 137 to adjust setpoints automatically e Optimal Start e Demand Control e Setpoint Optimization To
43. other schedules BACnet limits the number of priority indices to sixteen Color of the schedule bar on the Schedules page The Weekly type is available for Index O only The Allow Wildcards and Partial Day options affect all selected schedule types The default schedule used when this category is selected Create the schedule by adding segments for each state until every hour in the 24 hour schedule is covered by a segment EXCEPTION If you selected Partial Day in the Schedule Types field you do not have to add segments for the entire 24 hour period 63 WebCTRL v5 User Manual To view edit or delete a schedule category 64 1 2 3 4 On the CFG tree click the plus sign to the left of the Categories folder then click Schedule In the Schedule Categories table select the category you want to edit or delete Edit the fields in the Category Details section or click Delete Click OK 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 7 Trends WebCTRL can read and store equipment status values over time and then display this information in a graph to help you monitor the equipment s operation You can collect trend data for any BACnet input or output point in WebCTRL The controller reads values for a point at intervals that you define and then stores that data in the controller Because a controller has limited memory for storing trend data you can set up historical trending to ar
44. prompted to trust this certificate Type yes To set up a dial up networking connection WebCTRL can use a dial up internet connection through a modem to deliver e mail for the Send E mail or Send Alphanumeric Page alarm action To set up the dial up connection 1 Setup your modem to dial out to your Internet Service Provider See your modem documentation 2 Onthe WebCTRL server open Internet Explorer 2011 Automated Logic Corporation 93 WebCTRL v5 User Manual ao a P Q Select Tools gt Internet Options On the Connections tab click Setup Follow the instructions in the wizard See Windows Help for assistance In a text editor such as Windows Notepad open WebCTRLx x webroot lt system gt system properties At the end of the file type the following line repactions connection name lt name of connection gt where lt name of connection gt is the ISP name you entered in the wizard in step 2 Open Internet Explorer then select Tools gt Internet Options gt Connections tab If the box under Dial up and Virtual Private Network settings shows more than one connection select the connection that you just created then click Set Default 10 Select Always dial my default connection Send SNMP Trap 94 Optional WebCTRL Pa NOTE Tosee if your system has this optional package click EA then select About You have this package if Enabled Features shows Adv Alarming The Send SNMP Trap alarm action sends an SN
45. purchase an optional package at http orders automatedlogic com Select Options under Software Products To obtain an updated license and then apply it in WebCTRL Go to http accounts automatedlogic com http accounts automatedlogic com Select Support gt Software Licenses gt WebCTRL 2 5 and later BAS License Manager Select filter criteria to narrow the list of licenses then click Filter in the upper right hand corner Select the appropriate row Select the checkbox for agree to the terms of use Click Download License then save the license file to a disk or to your hard drive To replace your license in WebCTRL select CFG License Administration Browse to the license file Click Apply O N OO Oc FF WO MN 0 Restart WebCTRL Server using the rebootserver manual command see page 141 TIP Back up your system see page 207 before replacing your license in WebCTRL 2011 Automated Logic Corporation WebCTRL v5 User Manual Adding links or text to WebCTRL s login page You can add links or text such as a disclaimer to WebCTRL s login page WebCTRL Licensed to Automated Logic for at Automated Logic Corporate Offices Links Text To add links to the login page 1 Ina text editor such as Notepad type 2 lines for each link that you want on the login page Line 1 link text lt the link text that is to appear on the login page gt Line 2 link url lt the link s address gt Example to add
46. require an acknowledgement Analog inputs and outputs that have low and high limit alarm properties Click the plus sign to the left of Out of Range to make changes to the alarm messages displayed on the Alarms page gt View tab Short text is the message displayed when the alarm is not expanded Long text is the message displayed when the alarm is double clicked and expanded Binary inputs and alarm microblocks See Out of Range above to change the alarm messages To add a field code to any of the message text fields 1 Selecta field code to copy it 2 Clickin the appropriate text field where you want the field code 3 Press Ctrl V to paste the field code e Text displayed on the Alarms page gt View tab e Alarm information archived to a text file when an alarm is deleted You can customize the setup of each of these items by appending field codes For example to have the message in an alarm action include the device that generated the alarm append the Device field code to the action s message Format field codes You can type a formatting command after a field code to format the field code in one of the following three ways e Format a number field code Example e Format a date time field code Example MM dd yyyy hh mm ss e Left right or center align a field code and set the field width 2011 Automated Logic Corporation A formatting command must have the following syntax fieldcode format_type s
47. right click Command Prompt then select Run as administrator Select Yes in the User Account Control message In the Command Prompt window type cd path to the WebCTRL install directory For example type cd c WebCTRL5 2 Press Enter Type WebCTRL Service exe install Press Enter 2011 Automated Logic Corporation 177 WebCTRL v5 User Manual To start WebCTRL Server as a Windows service 1 Click the Windows Start button then select Control Panel 2 Double click Administrative Tools then Services 3 Inthe Services Local list double click WebCTRL 4 Inthe WebCTRL Properties dialog box select Automatic in the Startup type drop down list 5 Optional If you want to be able to access WebCTRL Server on the server computer s desktop select Allow service to interact with desktop on the Log On tab NOTES o Ifyou do not select this checkbox the computer screen will give no indication that WebCTRL Server is running you must view the computer s Services page to see if it is running o This checkbox applies only to a user logged in on the server A Windows Remote Desktop user cannot access WebCTRL Server running as a service o Ifyou select this checkbox you cannot use the instructions below to set up printing to a network printer Ask your Network Administrator to set up Local System account to use a network printer o Ifyou select this checkbox and WebCTRL is to run email alarm actions ask your Network Administrator to
48. s Out of Service checkbox on the Properties page is enabled Occurs if you attempt to upload a controller with a pre 4 x driver 4T WebCTRL v5 User Manual Blue messages Download All Please download all content to the Content controller Controller Replaced This controller has been replaced by 4 x driver only another controller of the same type in the field Program Mismatch Content differences detected Upload 4 x driver only all content from the controller or download all content to the controller Driver Parameter Driver parameter differences Mismatch detected Upload parameters from the controller or download parameters to the controller Parameter Control Program parameter Mismatch differences detected Upload parameters from the controller or download parameters to the controller Download To download parameters highlight Parameters row and select Parameters from the Download Action menu and click Download Download Schedule To download schedules highlight row and select Schedules from the Download Action menu and click Download General messages v This controller is ok Cancelled The last operation on this controller was cancelled To resolve a mismatch 48 A mismatch occurs when a value in a controller does not match the value in WebCTRL Server Use either of the following methods to handle mismatches in your system e Select Always upload properties from controllers to WebCTRL Server
49. selecting an archive frequency in the Archive log file contents field The archive file is auditlog_yyyy_mm_dd txt where yyyy_mm_dd is the creation date of the archive file This file is created in the same location as auditlog txt NOTE If you do not archive the log file contents you should manually delete the oldest entries Records audit data in a database named audit mdb that can be accessed by third party software NOTE For Access or MSDE the database is automatically created An Access database is named audit mdb a MSDE database is named audit mdf For MySQL SQL Server PostgreSQL or Oracle you must create the database manually Automatically deletes entries in the database that are older than the number of days you specify Enable this field to write to the core txt log any time an external source sends a request to the WebCTRL Server NOTE Regular maintenance scans by external software can cause the log files to grow large See Location dependent operator access page 131 for information on Change Policy Lets you access the system using WebDAV Returns operators to current tree locations when the server reconnects The system automatically logs off an operator who has had no activity in the system for the time period specified This is a default setting for the system The System Administrator can change this setting for an individual operator on the Operators page Clear Lockouts removes lockouts for all u
50. set up Local System account to send emails 6 Click Start 7 Click OK NOTES To shut down the WebCTRL service return to the WebCTRL Properties dialog box and click Stop If WebCTRL Server does not start when you click Start you may have a Windows permissions problem Follow the procedure below in To set up the WebCTRL service for network printing to set up the Windows user name and password To set up the service for network printing If WebCTRL runs as a service on a computer that is using a network printer you must set up the Windows user name and password for the service The Print alarm action requires this setup to be able to print 1 Open the Windows Control Panel 2 Select Administrative Tools gt Services 3 Double click WebCTRL Service x x 4 Onthe Log On tab select This account 5 Browse to the computer s domain then select the user that the service will log in as NOTE Contact your network administrator if you need help determining the domain 6 Type the user s password in the Password and Confirm password fields 2011 Automated Logic Corporation WebCTRL v5 User Manual To remove WebCTRL Server service On Windows 2003 and XP 1 Click the Windows Start button then click Run 2 Browse to the WebCTRLx x folder select WebCTRL Service exe the service install file then click Open 3 At the end of the path type space remove EXAMPLE c NWebCTRL5 2NWebCTRL Service exe remove 4 Click OK On Wind
51. step 4 above 2011 Automated Logic Corporation 85 WebCTRL v5 User Manual 86 To install the WebCTRL Alarm Notification Client application Follow the steps below on each client computer that should receive alarm popups PREREQUISITE Enable support for Alarm Popup client in System Settings See above topic 1 2 On the CFG tree click Client Installs Select the appropriate Alarm Popup Application based on whether your client computer is 32 bit or 64 bit Click Run then follow the on screen instructions to install the WebCTRL Alarm Notification Client application After you click Done the application starts automatically In the Settings dialog box enter appropriate values You can also click 1 to open this box See the table above for a description of each setting NOTE You can lock the Settings so that a user cannot edit them See To lock a client s Settings feature below Click OK Minimize the WebCTRL Alarm Notification Client window To lock a client s Settings feature To prevent a user from editing the Settings 1 R 1 2 3 Right click Alarm Notification Client in the Windows Start menu Select Properties On the Shortcut tab type lockconfig atthe end of the Target path Alarm Notification Client 5 2 Properties General Shortcut Compatibilty Securty g Alarm Notification Client 5 2 exe SCH Target type Application Target location webctil popup Target Alan
52. text page 22 This preconfigured allows you to report Schedules Schedule Instances Find every schedule with its location that is entered at and below a selected tree item This report can help you discover newly added and conflicting schedules Effective Schedules View all equipment that may be scheduled and the net result of all schedules in effect for a selected date and time Commissioning Test amp Balance View the results of VAV box commissioning Running this report automatically uploads calibration parameters to WebCTRL Equipment Checkout View the information on the Equipment Checkout tab of the equipment s Properties page during commissioning Also find equipment that has not been fully commissioned Alarms Alarms View sort and filter the information on the Alarms gt View tab see page 78 2011 Automated Logic Corporation 113 WebCTRL v5 User Manual This preconfigured report Alarm Sources Alarm Prefixes amp Details Alarm Actions Equipment Point List Locked Values Network IO Trend Usage Parameter Mismatch Security Location Audit Log System Audit Log Network Equipment Status Controller Status allows you to Create a summary of potential alarm sources as configured on the Alarms gt Enable Disable tab see page 101 Create a summary of the information configured on the Alarms gt Messages tab see page 104 Create a summary of the informati
53. work Creating a custom schedule category 1 Create the custom schedule category in EIKON LogicBuilder See To use custom alarm and schedule categories in EIKON LogicBuilder Help 2 In EIKON LogicBuilder select the new category from the Schedule Category droplist in a Time Clock microblock 3 Create the same custom schedule category in WebCTRL The Reference Name must be identical to the category s name in EIKON LogicBuilder See To add a custom schedule category in WebCTRL below To add a custom schedule category in WebCTRL TIP Study the default Occupancy category to understand the various properties you need to set when adding a new schedule category PREREQUISITES e Add the custom schedule category in EIKON LogicBuilder See To use custom alarm and schedule categories in EIKON LogicBuilder Help e n EIKON LogicBuilder select the new category from the Schedule Category droplist in a Time Clock microblock 1 On the WebCTRL CFG tree click the plus sign to the left of the Categories folder then click Schedule Click Add Category Enter values or add items for the fields in each section of the page See table below NOTE The fields that you see depend on selections you made in previous sections Category Details fields 4 Click OK 62 2011 Automated Logic Corporation Field Reference Name Schedule Category Description Allowed Type Default Value Allowed Values Allowed Value Description Pa
54. 350 microblocks previously 200 e Upto 2 PID microblocks in addition to the zone controller microblock previously 1 PID The integrator microblock now retains its output magnitude through a power loss controller reset or controller restart Using a combination of logic that writes critical parameters within a control program to a BACnet Analog Value Parameter microblock and a new property of the BACnet Analog Value Parameter microblock you can retain critical values through a power loss through a controller restart and if the reference name of the microblock is unchanged through a memory download This new microblock provides improved PID algorithm and BACnet accessibility These 2 new microblocks support up to 20 states To be consistent with the System Variable microblock the weekday system variable has changed to WKDAY where Monday 1 to Sunday 7 The previous weekday system variable WDAY will continue to work in existing control programs using Sunday 1 to Saturday 7 Use an in a Network Input or Total Analog microblock s address to have the microblock automatically locate the nearest device that contains the object specified in the address This feature eliminates the need for specific device addresses when retrieving values from common objects For example control programs on a campus that need oa_temp can automatically retrieve the value from the nearest device that contains that object name 2011 Automa
55. 4 Marker display color RGB 00FF30 DM RGB FF921 css Sample series ees CE Default settings on Trends Display Setup and Trends Print Setup pages If you make changes to the Trends Display Setup and Trends Print Setup pages and then find you need to return them to their original settings refer to the images below that show the default settings Trends Display Setup Trend Colors Display colors Background 000000 Mi Main Title Color Grid 303030 D Axis co0000 B Y label 00E0E0 X label DODODO Main title DODODO Y title 00E0E0 TrendBG 000000 M E Graph 1 Data Series 1 Data Series 2 Data Series 3 Data Series 4 Line style Solid Tight Dots Short Dashes Long Dashes Line display color FFFFOO 00A4A7 pl FF8924 E 2FACFF IN Marker display color 00FF30 EX FF92E4 9CAFFF FFBO78 Marker type LargePoint Cross X Square Sample series as CE 74 2011 Automated Logic Corporation WebCTRL v5 User Manual Trends Print Setup Main Title Color Y axis title color 15 43 15 154330 15 43 45 9 ug2000 9 ug2000 9 Aug 2000 IN Bl E n _ H To copy a trend graph s properties You can use Global Copy see page 41 to copy trend properties to other pieces of equipment that use the same control program To add edit or delete a trend category A point trend graph is in the Enabled or Disabled category in the Trends butto
56. 5 User Manual Start up Commissioning and Service Tools Use To Field Assistant Service or start up and commission a piece of equipment or a partial network of controllers Test amp Balance Calibrate airflow in VAV zone controllers commission air terminals and override reheat and terminal fans Virtual BACview Let your laptop serve as a local interface to a single piece of equipment F World Corp El Site E BACnet Network mms Router 172 16 1 1 Driver zu Router 172 16 1 1 E DI Controller 172 16 1 E Controller 172 16 1 Configure Help 6 7 8 3 0 bd m E e 6 e e CR 20 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 3 Getting to know the workspace System wide alarms button Green no alarms Yellow non critical alarms Red critical alarms Click to display alarms Back button Print button Show Auto hide navigation pane Navigation tree Action buttons Help button all World Corporation Atlanta R amp D Facility Bj Basement B First Floor BB Lobby E North offices B South offices B Core offices H Roof 6 OA Conditions Electric meter SX Dallas Training Center Menu commands Menu button Click to display menu Navigation pane Indicates error on pag
57. 68 162 170 2 administrator 3 abc 4 5 n points m 21 locked TRUE Fan needs maintenance B o_points mO21 locked_ value On Fan needs maintenance 7 Step 2 Create a macro The macro will write the values from the spreadsheet to the WebCTRL system The following steps correspond to the numbered parts of the code shown below 1 Name the subroutine testSoapWrite that will set the value in WebCTRL 2 Define which spreadsheet cells contain the host WebCTRL server user WebCTRL operator password WebCTRL operator s password 3 Identify the Web services program that allows the spreadsheet to access the WebCTRL server over the network or Internet Enter the code to authenticate the user Enter the error handling code 2011 Automated Logic Corporation 197 WebCTRL v5 User Manual 198 6 Enter the code that uses the setValue method to set the raw value 7 Enter the code that uses the setDisplayValue method to set the display value 8 This displays an error checking statement if an error is found in the data Sub testSoapWrite 0 2 host Range A1 Value user Range A2 Value passwd Range A3 Value Dim changeReason As String 3 Dim client As MSSOAPLib30 SoapClient30 Set client CreateObject MSSOAP SOAPClient30 URL http amp host amp common webservices Eval wsdl client mssoapinit URL client ConnectorProperty WinHTTPAuthScheme 1 client ConnectorProperty AuthUs
58. AUTOMATEDLOGIC CORPORA T 1150 Roberts Boulevard Kennesaw Georgia 30144 770 429 3000 Fax 770 429 3001 www automatedlogic com WebCTRL v5 User Manual Rev 3 28 2011 A Verify that you have the most current version of this document Go to http accounts automatedlogic com then select Support gt Download gt Documents gt Manuals Contents Chapter 1 What s new in UE 7 What Sinew in WEDCIRL AEEA E EE 7 What s new in EIKON LogicBuilder 10 What s new in SiteBuilder sise 11 What s new in ViewBuilder ss 12 What s new Other tools visceiccescsecsssccsssscsssseseseassesscesssasssssasesesusessicsnsasesesacesesacesssedersaces 13 Chapter 2 What DAD d OCI KEE 15 A typical WebCTRL system cssssssssssscssssssssssesssssssssserssesensssccssssensseesssssensssesssseessaess 16 WebCTRL editions iscissaiccaicsscessiccssecesssacosssesesesasesscconsvaadesesecedacesssusasasesosesesesacesnsesesnsets 17 WebGIRE TEE 18 Chapter 3 Getting to know the workspace eese eere eene enne nn nennen nnne nnne nnn 21 Navigating E EE 22 Tree icons and hover text E 22 To show hide the navigation pane us 24 Zooming and resizing in the action pane eseeseeseeeeeeeeeeeeeeeeeseeeeeseeseesseseeseeaseneaneatens 24 Using right Click menus scie nn a 24 To print the action pane s r is sise 24 Colors and status in WebCTRL eseesss
59. Access SOAP retrieve WebCTRL data through an Enterprise Data Exchange SOAP application Do not audit changes made not have his SOAP Web services changes recorded in the Audit using SOAP Web services Log Manual Commands Console access the manual command dialog box and issue basic manual Operations commands Manual Commands File IO execute manual commands that access the server s file system Manual Commands Adv Network execute manual commands that directly access network communications Manual Commands Unrestricted execute manual commands that bypass all safeguards and may cause unpredictable results if used incorrectly To create a custom privilege You can assign a privilege to a Graphic Property Trend or Report category so that only operators with that privilege can access the category You assign a category privilege on the page where you create or edit categories If all the other privileges are too widely used to accomplish the results you want you can assign one of the five Access User Category privileges to the operator s and category For example your system has two graphics categories HVAC and Lighting Security You want HVAC technicians to see only the HVAC graphics and security personnel to see only the Lighting Security graphics To do this Assign To Results Access User HVAC graphics category and The security personnel cannot see the HVAC Category 1 HVAC technicians only graphics because they do not ha
60. Alarms logged to the database e State text and object names downloaded to the field e The login page NOTE Language also refers to formatting conventions For example English uses the date format mm dd yy but English International uses the date format dd mm vy 160 2011 Automated Logic Corporation Field Use a single alarm template for CMnet alarms All Source Files Alarm Popup Restrict to IP Address Port Current client connections Select a week of logs to review Security tab Field Log audit data to file 2011 Automated Logic Corporation WebCTRL v5 User Manual Notes If your system is an upgraded legacy system do one of the following e Select this checkbox to have alarms for CMnet equipment use only the alert auto alarm template e Disable this checkbox to allow multiple alarm templates Use to export source files to a zip file that can be imported into Field Assistant If the technician using Field Assistant changes or adds files he can export them from Field Assistant so that they can then be imported in WebCTRL or SiteBuilder Source files include Control programs equipment files only Drivers Graphics view files only BACview files NOTE If import detects a difference between a database file and an import file with the same name import does not overwrite the database file A message lists any file differences so that you can resolve them See Commissioning equipment using
61. CHED UIC ccs sacs sos cee rc erttcdesedeseundutesetesesecctesedeienesatesedecesetctesedsieneye 56 To apply a schedule to equipment 56 To apply a schedule to a group of items 57 To edit or delete a schedule Us 59 Effective Schedules orent ri remo e nr nti tr a e rrr ra eo rs 60 Using schedule categories sine 62 Creating a custom schedule category 62 To add a custom schedule category in WebCTRL esss 62 To view edit or delete a schedule category 64 Chapter P nn et 65 To collect trend data for a point 65 Graphing data for multiple points ss 67 To create a comparison trend graph 68 To edit a comparison trend graph 68 To delete a comparison trend graph 69 Using trend Sra PMS woe 69 TO View a trend Srah tee vs cesccatecavecesecatesevecesecatesatscenecatecarscesttericatece 69 Tools for viewing trends eeeeeeeeeeeneenenenneneennnnnnnnnnnnnnns 70 To print a trend graph ss 71 To transfer trend data to a table format 71 Customizing graph appearance sisi 72 To edit graph properties sise 72 To edit colors line styles and marker types 73 To copy a trend graph s properties ss 75 To add edit or delete a trend category esses 75 Chapter CN 77 Viewing acknowledging and deleting alarms
62. CTRL 2 5 and later BAS License Manager Select filter criteria to narrow the list of licenses then click Filter in the upper right hand corner Select the appropriate row Fill in the blank fields in the License Registration Area Click Register License Select the checkbox for I agree to the terms of use Click Download License then save the license file to a disk or to your hard drive o N Oo FPF WO ND a Apply your license in WebCTRL o During the WebCTRL installation The installation requests the location of your license file Browse to location where you saved it in step 4 above o After the installation a In WebCTRL select CFG gt License Administration b Browse to the license file c Click Apply d Restart WebCTRL Server using the rebootserver manual command see page 141 NOTES e Do not edit any part of this registered license file Editing a license file invalidates the license e Store the license in a safe location 2011 Automated Logic Corporation 167 WebCTRL v5 User Manual To replace the license when adding features You can add any of the following optional WebCTRL packages to your WebCTRL system e Enterprise integration Web services XML SOAP data retrieval e Advanced security Location dependent operator access configurable password policies and required operator comments verification for system changes e Advanced reporting Custom reports e Additional alarm actions You can
63. Changes NOTE To modify several properties in multiple control programs at the same time use Global Copy To use Global Copy 42 Use Global Copy to copy any or all of the following from one control program to other equipment using the same control program Embedded trend graph settings Custom trend graphs Custom reports Other editable properties to other pieces of equipment using the same control program On the GEO or NET tree right click the piece of equipment that has the properties you want to copy then select Copy Control Program Properties In the Global Copy dialog box select the items that you want to copy Select the area on the tree containing similar control programs that you may want to copy these properties to then click Search All instances at that level and below are listed in the expanded lower window 2011 Automated Logic Corporation WebCTRL v5 User Manual Select or clear checkboxes as needed Do one of the following o Select the Skip bad values checkbox to copy all values except a bad value it cannot be copied because you do not have the necessary privilege the property to be copied is undefined etc o Clear the checkbox to prevent any values from being copied if a bad value is found 6 Click Apply Changes then close the Global Copy dialog box Downloading to controllers If you make any of the following changes you must download the new data from WebCTRL Server to the affected con
64. Cnet object names The Immediate Triggered Write property was removed from ANO2 and BNO2 microblocks These microblocks automatically write their value as soon as they are enabled Improvement The new Environmental Index source tree allows you to drag and drop zones that use standard reference names to calculate the Environmental Index A site now defaults to the WebCTRL server s time zone but you can select a different time zone if needed You can search your system database for any information that you can access from an item s Properties dialog box The Replicate dialog boxes were redesigned If multiple pieces of equipment use the same control program and you change the attached view s for one a Synchronize Views dialog box appears showing all equipment using the same control program You can then easily select other equipment that requires the same view change When you attach a view in SiteBuilder you can edit the view s navigation properties that were defined in ViewBuilder You can now create up to 20 custom source trees 11 WebCTRL v5 User Manual Feature Connect strings for MySQL Oracle PostgreSQL or SQLServer databases Support for lighting control Download Source Files Export and import source files SSL certificate management What s new in ViewBuilder Feature Drawing tools Lighting graphics 12 Improvement The connect strings were broken into fields in SiteBuilder to simplify se
65. E To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group lt your new group gt is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group lt your new group gt is Unoccupied Available only if you have the Advanced Alarming package 2011 Automated Logic Corporation 87 WebCTRL v5 User Manual Propagate To Server The Propagate To Server alarm action sends the selected alarm to the parent server in a system with hierarchical servers Field Notes Message text The alarm message that is sent to the parent server Append Field Code Add field codes see page 108 to include live data in the Message text field Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm esc
66. L Server appear at the system level e Alarms generated by controllers appear at the system level on the GEO tree but in the network hierarchy on the NET tree To acknowledge alarms To acknowledge a single alarm 1 On the Alarms page select the View tab 2 Select an alarm that shows Acknowledge in the To Do column 3 Click the Acknowledge button beneath the list 80 2011 Automated Logic Corporation WebCTRL v5 User Manual To acknowledge all alarms in the selected categories 1 Onthe Alarms page select the View tab 2 Click Additional Actions 3 Click All under Acknowledge alarms in selected categories TIP Acknowledging many alarms simultaneously can take a long time Acknowledge alarms as they occur to avoid long waits To delete alarms To delete a single alarm 1 Onthe Alarms page select the View tab 2 Select an alarm 3 Click Delete To delete multiple alarms in the selected categories 1 Onthe Alarms page select the View tab 2 Click Additional Actions 3 Click the appropriate button under Delete alarms in selected categories o Closed Incidents deletes all closed incident groups An incident group is considered closed when all alarms in the group are closed o All System deletes all system alarms o All deletes all alarms at the selected location and below NOTES e To have WebCTRL automatically delete alarm incident groups a specified number of days after the groups close select this option on
67. MP trap in response to receiving an alarm Traps contain the text created in the Text to send as the SNMP Trap field in the alarm action dialog box You can configure up to five SNMP servers to receive traps NOTES WebCTRL supports SNMP v1 Each SNMP server you want to receive these traps must have SNMP monitoring equipment installed If problems arise with your SNMP connection or receiving traps contact your IS department This alarm action uses Port 162 to send SNMP traps To use a different port open WebCTRLx x webroot lt system_name gt system properties in a text editor such as Notepad In the line snmp trap port 162 delete at the beginning of the line and change 162 to the port you want to use If you make this change while WebCTRL Server is running you must restart it to have the change take effect Field Notes Network Address The network address of the SNMP server receiving the SNMP trap Community Name The community name that the SNMP server belongs to Comment The physical location of the SNMP server This field is optional 2011 Automated Logic Corporation WebCTRL v5 User Manual Field Notes Trap number If the network administrator has configured trap numbers type a unique number from 1 to 127 NOTE The same trap number is used for all messages from this alarm action Text to send as the 255 character limit Type punctuation spaces or returns after the entries SNMP Trap to format the message You can
68. Managing files on a remote WebCTRL server 151 Methods for using WebDAV iris 151 To use WebDAV with Internet Explorer 151 Chapter 16 Using wireless devices with WebCTRL ener 153 Supported WebCTRL features eessssesssssseeeeeeeeeee nennen nnne nnns 153 To dial up a System using WAP nennt 154 Tonavigate the SyStem 5 5 EES 155 To view and e dE EE 156 To view and edit equipment properties 156 Chapter 17 Setting up a system in WeDCTRL s scssescsssssnseesssessnseessseesnseeessessnseeessenenseneseeess 157 Editing the GEO or NET tree in WebCTRL rire 157 To importa CHPPINE 158 El 160 cre 160 Security ta D 161 Communications tab 163 SchedulediTaSkKS tab wiv dee eit iere trecenti a iii iret 164 MEDeEuAcumeD M 165 Web Applications tab esseeeeeeeeeeeeenenennnennnn nennen 166 To Set up site properties n erneuert ra noon tourne saa nouas onk atur inn 167 To register your WebCTRL software 167 To replace the license when adding features esse 168 Adding links or text to WebCTRL s login page een 169 To add links to the login page eene 169 To add text to the login page 170 Chapter 18 Working with control programs in WebCTRL nine 171 To select a different control progr
69. Notification Client 5 2 exe lockconfig L 2011 Automated Logic Corporation Print WebCTRL v5 User Manual The Print alarm action prints alarm information Field Text Printing Graphics Printing Text to Print Perform Action Notes Select to use the WebCTRL server s local dot matrix printer Text Printing will not print to a network printer In the Printer Name field type the computer port that the printer is connected to In the Line Width field tyoe the number of characters to be printed per line Prints multiple alarms per page Select to use the WebCTRL server s default printer local or network printer Prints one alarm per page to the WebCTRL server s default printer Use punctuation spaces or returns after the entries to format the text To add live data to the text select field codes See page 108 from the Append Field Code list By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPL
70. Object ID of the alarm source The status of out of service from the alarm source The status of overridden from the alarm source 111 WebCTRL v5 User Manual Field Code Name Program ID Receive Time Recipient Device ID Record Type Reference Path Reference Value Referenced Bitstring Report Text RTN Time Setpoint Value Short Message Site Source Source description Source Path System Directory To State 112 Field Code program_id receive_time device_id record_type reference_path reference_value referenced_bitstring report_text RTN_time setpoint_value short_message site source source description source lt path gt system_dir to_state Description The address of the control program that generated the alarm BACnet program address format device ID program number example 240219 5 SuperVision program address format site gateway controller fb example 1 2 13 5 The time at the workstation when the alarm was received The device ID of the device where the alarm came from The type of alarm for example BACnet SuperVision System Path to alarm source Available in all alarm actions The reference value from the alarm source Valid only for alarm type FLOATING LIMIT The value of the referenced bitstring value from the alarm source Valid only for alarm type CHANGE OF BITSTRING
71. Parameters Edit Category Assignments Edit History Value Reset Edit Trend Parameters Edit Calibration Parameters Edit Hardware Controller Parameters Edit Critical Configuration Edit Area Name Edit Control Program Name Edit Alarm Configuration InterOp Privilege 1 10 This Functional privilege Manage Alarm Messages and Actions Maintain System Parameters Maintain Schedules Maintain Schedule Group Members Maintain Categories Maintain Trends Display and Print Setup Maintain Alarm Templates Acknowledge Non Critical Alarms Acknowledge Critical Alarms Force Normal Non Critical Alarms Force Normal Critical Alarms Delete Non Critical Alarms Delete Critical Alarms Execute Audit Log Report Download Controllers System Shutdown 2011 Automated Logic Corporation WebCTRL v5 User Manual allows an operator to edit properties such as properties the installer restricted with this privilege Alarm Graphic Trend and Report category assignments elapsed active time and history resets and runtime hours enable trend logging log intervals and log start stop times point calibration offsets driver properties critical properties the installer protected with this privilege area display names control program display names enabling disabling alarms and editing alarm messages actions categories and templates those protected by password levels 1 10 in SuperVision allows an operator to add
72. RL In WebCTRL right click the equipment in the GEO or NET tree select Configure then select the Icon 2011 Automated Logic Corporation WebCTRL v5 User Manual Optional icons You can display the following icons to denote locations in the GEO tree where items were created or assigned e Schedules ET Trend Graphs Alarm Actions Mi Schedule Groups EH Reports 9 Privileges To turn on optional icons 1 Right click the GEO tree 2 Select Tree Display Options 3 Select the desired Tree Icons 4 Click OK Optional hover text If you turn on hover text you can hold the cursor over a system area or equipment icon to display information about its item The information displayed depends on which hover text options you select of World Corporation DE Headquarters D EE Headquarters Schedules Ignore above this level Occupancy Monday Friday Reports Equipment Summary Third Floor 1801 To turn on hover text 1 Right click the tree 2 Select Tree Display Options 3 Select the desired Tree Hover Text 4 Click OK 2011 Automated Logic Corporation 23 WebCTRL v5 User Manual To show hide the navigation pane Click CH toggle the navigation pane between shown or hidden When the navigation pane is hidden move the cursor across the left edge of the browser to show the navigation pane Click and drag the right edge of the navigation pane to adjust its width Zooming and resizing in the action pane e
73. RL v5 User Manual Optional WebCTRL packages Package Advanced Reporting see page 113 Advanced Security see page 131 Advanced Alarming see page 82 Enterprise Integration see page 191 Capabilities Configurable report designer for making environmental reports Available report types e Equipment Values Trend Samples Location dependent operator access Configurable password policies Audit Log reports Requirement of operator comments and operator verification prior to accepting system changes The following alarm actions e Send SNMP trap e Write property e Write to database In addition to running an alarm action when an alarm or return to normal occur alarm actions can be set to run e After a delay period e Based on a schedule group s occupancy status Web services XML SOAP data retrieval e Add on web applications such as EnergyReports NOTE An optional package is enabled when you install the license that provides the optional package see page 167 WebCTRL tools A WebCTRL system includes the following tools 18 Design Tools Use EIKON LogicBuilder ViewBuilder ViewBuilder for WAP SiteBuilder Third Party BACnet Utility To Create control programs and Properties pages Create graphics and BACview screens Customize pages for WAP enabled devices Create and modify the system database and associate control programs and graphics with equipment Use discovered BACnet informati
74. RL v5 User Manual To edit colors line styles and marker types You can change colors line styles and marker types for both point trend graphs and custom trend graphs The changes you make apply to all graphs in the system and become the default settings for future trend graphs 1 Onthe CFG tree select Trends Display Setup to change the settings for displaying trend graphs or select Trends Print Setup to change the settings for printing trend graphs 2 Follow the appropriate instructions below Click OK To change a color Click the colored box to the right of the graph element that you want to change then select the new color in the color palette Or you can type the hexadecimal value in the RGB field Trends Display Setup H Trend Colors Display colors Background 000000 WM Grid 303030 Bil Axis coo000 Bil line style marker type For a point trend graph select the new line style and marker type under Graph 1 Data Series 1 For a custom trend graph 1 Click the plus sign to the left of the graph you want to change 2 The four Data Series refer to the 4 points that you can include on a custom trend graph Under the appropriate Data Series select the new line style and marker style you want 2011 Automated Logic Corporation 73 WebCTRL v5 User Manual Trend BG color RGB 000000 M Default gre E Graph1 Data Series 1 Data Serie Ti ot Line display color RGB FFFFOO _ RGB 00A
75. Self contained modular applications that can be run over the Internet and can be integrated into other applications A standardized method for combining remote applications distributed over the Internet so that they may work together for a common purpose Application to application interfaces Using Web services you can retrieve information or set values for items accessible through WebCTRL s GEO or NET tree You can retrieve trend data reports present values setpoints and any other BACnet object property information from a remote WebCTRL server and import the information into a SOAP client such as Microsoft Excel You can also set present values setpoints and any other object property information on a remote WebCTRL server The Web services examples we provide use Microsoft Excel as the SOAP client but you can use other software packages NOTE To use Web services with Microsoft Excel or Microsoft Word You should be comfortable writing Visual Basic scripts and setting up macros You must install the Soap Toolkit found at http download microsoft com download xml Install 3 0 W982KMeXP EN US SoapToolkit30 EXE 2011 Automated Logic Corporation 191 WebCTRL v5 User Manual WebCTRL privilege requirements You should create a WebCTRL operator and a privilege set whose specific purpose is Web services The privilege set must have the following privileges Remote Data Access Access Geographic Locations or Network Locations as ne
76. TATE_ TEXT_ values generation_time location_path to_state report_text NOTES You can add field codes see page 108 to the Insert String using the Append Field Code list If you add a timestamp type field code for example generation_time you should have the data go into a timestamp data type field in the custom database Otherwise you must use field code formatting see page 108 to format the time Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Cr
77. You initiated the download and the controller is waiting for its turn to download Failed The download failed See If a controller fails to download page 46 cae On Hold Indicates either of the following The controller requires a download You clicked Hold to stop a pending e download e Click o in the upper left hand corner to view a log of download activity in the current session Copy to Clipboard lets you copy the text to paste it into another application e Toremove an item from the download list right click the item then select Remove selected tasks To download from a Properties page If a controller requires a download a red download message and a Download button appear at the top of the Properties page for the controller the equipment or a microblock Click the button to start the download Downloading from the Properties page downloads All Content to the controller 2011 Automated Logic Corporation 45 WebCTRL v5 User Manual If a controller fails to download A controller that fails to download appears on the Downloads page with this icon W 1 Review the reason for the failure o Hold your cursor over the failed task to see hover text giving the reason o Click Win the upper left hand corner of the page to see information on all failed downloads Copy to Clipboard lets you copy the text to paste it into another application 2 Correct the problem that caused the failure 3 Select the controlle
78. a user without warning the user Typea whoson manual command to view the IDs of logged in operators then type logoffuser x where xis a the user s ID These commands place the controller for the selected tree item on the list to download at a later time The download list can be viewed at NET Downloads 143 WebCTRL v5 User Manual Command markdownload markdownload p markdownload s memory memory free modstat commands modstat modstat 8 lt device instance number gt modstat mac lt network number gt lt media type gt lt mac address gt notify 144 Description Marks for an All Content download that includes parameters schedules and BBMDs if applicable Marks for a Parameters download Marks for a Schedules download Shows the amount of server memory allocated for WebCTRL and the amount being used by WebCTRL Releases unused server memory then shows the memory usage by WebCTRL before and after the release These commands display a Modstat report NOTE It is not necessary to download a controller before running a Modstat on it Binding takes place when you run the modstat Displays status of the controller at the current location including e Hardware components of the device e Software components of the device e Error conditions that may exist in the device e Date and time the device is using Displays status for a specific controller in the IP network using the controller
79. able below 4 Click OK Field Login Name Change password Force User to Change Password at login Exempt From Password Policy Logoff options Personal Information Starting Location and Starting Page Notes The name the operator must type to log in to the system This name must be unique within the system Enable this field then type the current and new passwords NOTE An operator can change his password on the My Settings page see page 130 Forces the operator to change his password immediately after his next login NOTE Use this field with the Change Password field to create a temporary password that the operator must change after his next login If the advanced password policy is enabled in System Settings on the Security tab see page 161 select this option if you do not want the policy to apply to this operator If the automatic logoff feature is enabled in System Settings on the Security tab see page 161 select one of the 3 logoff options You can enter contact information for this operator NOTE An operator can enter contact information on the My Settings page see page 130 The location and page WebCTRL will display after the operator logs in 2011 Automated Logic Corporation WebCTRL v5 User Manual Field Notes System wide To assign a privilege set to the operator select the privilege set s checkbox Privilege Sets NOTES e Click Show current privileges only to see only the se
80. abled Features shows Adv Security Location dependent operator access Optional WebCTRL Packag NOTE Tosee if your system has this optional package click L ze then select About You have this package if Enabled Features shows Adv Security With the Advanced Security package you can set up operator access to your system to be location dependent This type of operator access lets you assign privileges to an operator only at locations in the system where he needs them For example you could assign an operator mechanic privileges in one building in a system view only privileges in another building and no privileges in a third building New and converted WebCTRL systems default to location independent operator access in which an operator s privileges apply throughout the system You should understand this type of operator access before switching to location dependent See Operator access page 123 for more information on location independent operator access NOTE When using hierarchical servers the security policy and privilege sets are local to each server so you can have location independent security on one server but not on another To switch to location dependent access CAUTIONS e Create a backup of your system before you begin Switching to location dependent operator access changes the configuration of operators and privilege sets If you need to revert to location independent operator access your previous configuration can
81. age 150 before starting the autopilot 1 Start WebCTRL Server 2 Run the autopilot bat file that you created in step 1 of To set up WebCTRL s autopilot page 149 NOTES To stop the autopilot do one of the following o Close the browser o Close the Command Prompt window that is running the autopilot bat file to stop the autopilot but leave WebCTRL running in the browser If the autopilot does not start open autopilot log to see the error To run autopilot with Windows Vista To run the autopilot with the Windows Vista operating system you must add the WebCTRL URL to Internet Explorer s trusted sites 1 2 zl oO 0 P 150 In Internet Explorer select Tools gt Internet Options On the Security tab select the Trusted Sites icon then click the Sites button Under Add this Web site to the zone type the url that autopilot uses to start your system See step 3 in To set up WebCTRL s autopilot page 149 Clear the checkbox beside Require server verification https for all sites in this zone Click Add Click OK to close both windows Close Internet Explorer to have the changes take effect 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 15 Managing files on a remote WebCTRL server WebCTRL supports WebDAV a network protocol designed for managing remote server files through an Internet connection By using WebDAV you can access the Internet from anywhere in the world and mana
82. alation e fthealarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package Run External Program 88 The Run External Program alarm action starts a program or batch file on the server Field Notes Command Line The path of the executable file on the WebCTRL server followed by the path of the output file EXAMPLE c windows notepad exe c WebCTRL webroot alarms txt 2011 Automated Logic Corporation WebCTRL v5 User Manual Field Notes Append Field Code Add field codes see page 108 to the Command Line field EXAMPLE c reports run_report bat Generation_time To_State This starts a batch file on the server and uses the alarm s generation time and state as values
83. all categories and all alarm sources on the Templates tab To add an alarm template 1 Onthe CFG tree select Alarm Templates 2 Click Add 3 Select Source based a v2 5 template or Stand alone a pre v2 5 template then click OK 4 Edit the template fields as needed See table below 5 Click OK Field Template Type Notes Reference Name All Must be unique in the database be lowercase and not contain any spaces This name must be identical to the name of the template in EIKON LogicBuilder Display Name All The name WebCTRL will display for this template Alarm Message Source based The message text displayed on the View tab or in the alarm action when an Alarm requires acknowledgement 2011 Automated Logic Corporation 107 WebCTRL v5 User Manual Field Return Message Fault Message Critical Acknowledgement Required Out of Range Change of State Copy Field Code to Clipboard Using field codes Template Type Source based Source based Stand alone Stand alone Stand alone Stand alone Stand alone Use field codes to insert live data into e The message on an alarm action Notes The message text displayed on the View tab or in the alarm action when a return to normal requires acknowledgement The message text displayed on the View tab or in the alarm action when a Fault requires acknowledgement Select if this is a template you will use with a critical alarm Select which alarm states
84. am 171 To edit a control program on a WebCTRL client 172 Chapter 19 Working with drivers in WebCTRL sn 173 To change or upgrade a driver 173 Chapter 20 Working with BACview files in WebCTRL ensure eren 175 To select a different bacview file eeeeeeeeneeneneneennnnnnnnnnnnn 175 To edit a bacview file on a WebCTRL client 176 Chapter 21 Running WebCTRL Server as a Windows service nn 177 To install WebCTRL Server service sisi 177 To start WebCTRL Server as a Windows service eene 178 To set up the service for network printing 178 To remove WebCTRL Server service ss 179 To determine if WebCTRL Server service is installed 179 Chapter 22 Setting up a system for non English languages eene 181 Installing a language pack sis 181 Preparing your workstation for non English text 181 Creating control programs and translation files for a non English system 183 To enter a key term in EIKON LogicBuilder eneee 183 Ur ERN CC 183 To create and implement a translation file 184 Creating graphics for a non English system 185 Creating a non English graphic in ViewBuilder 185 Creating a graphic for a multi language system using WebCTRL extensions for Fron
85. ant to replace event templates follow the on screen instructions 7 If asked if you want to overwrite components follow the on screen instructions 8 WebCTRL lists any conflicts and problems that were found during the import Make any needed corrections in SiteBuilder NOTE Click Copy to Clipboard and then paste the list into another program such as Notepad for viewing or printing 9 Click Next 2011 Automated Logic Corporation WebCTRL v5 User Manual 10 Click Finish 11 Do any of the following that apply If you imported Another site into the system Asecond BACnet IP network into a site Any controllers that use the SiteBuilder option Automatically Configure My BBMDs Any controllers that use manually configured BBMD tables 2011 Automated Logic Corporation Do the following in SiteBuilder Change the new site s BACnet IP network number to be the same as the other BACnet IP network s iB XYZ system EE Site 1 o S BACnet IP A 2400 EE Site 2 4 HS BACnet IP A 2406 Change this address to 2400 Move the items under the new network to the original BACnet IP network then delete the new network diB XYZ System H EE Site ci E BACnet IP 1 em LGR1000 Driver ARC156 S BACnet IP 2 Ej mmu LGR250 19 Driver ARC156 N A N A Do the following in WebCTRL Download All Content to all ALC IP routers in the system Download Parameters to any co
86. anual 58 Type a name for the new schedule group in the Name field Optional Change the default Reference name A group s reference name must be unique throughout the system Click OK Click Go On the Members page select the areas equipment or other groups that you want to add to the group from the tree on the right Use Ctri click Shift click or both to select multiple items 8 Click Add TIP Use the Raise and Lower buttons to reorder items in the Members list Changing the order is for your viewing convenience and does not affect the system 9 Click OK 10 Click the Schedules button then Configure 11 Add a schedule to the group See To apply a schedule to equipment page 56 NOTE When using hierarchical servers you can place a server link in a schedule group on the parent server This automatically creates a schedule group with the same name on the child server s This group includes only the top most area node of the child server However from the child server you can edit the group to add other members To organize groups using folders You can create folders and sort your groups into them to organize the GRP tree For example a large school system that has a group for each school may want to create an Elementary School folder a Middle School folder and a High School folder and put the appropriate groups in each folder Scheduling Groups all Office Park 9 Scheduling Groups Elementary Schools
87. aphic Locations and Maintain Schedules at each location that is a member of the schedule group e f you switch to location dependent operator access in a system that has operators and privileges set up WebCTRL splits any existing privilege set containing local and system wide privileges into two separate privilege sets one local and one system wide Operators system wide privilege sets still apply throughout the system The operators local privilege sets are automatically assigned at the system level You can then reassign the local privilege sets to the operators at the locations where they need them To add a privilege set Adding a privilege set using location dependent operator access is the same as using location independent operator access except that you must select whether you are adding a system wide or local privilege set See Privilege sets page 124 To assign privilege sets to an operator Assign a system wide privilege set to an operator on the Operators page in the same way you would assign privilege sets in a system using location independent operator access See Operators and Operator Groups page 127 Assign a local privilege set to an operator at locations on the GEO or NET tree where he needs the privileges Select a location on the GEO or NET tree Click Privileges Click Add Select the operator or operator group Click OK Select the privilege set s that you want the operator to have Click OK Oo O
88. arm source is assigned to an alarm category in EIKON LogicBuilder but you can change the category assignment in WebCTRL WebCTRL has a number of default alarm categories but you can create custom categories if needed To assign alarm sources to a different category 1 On the GEO or NET tree select the area equipment or controller containing the alarm sources 2 Click Alarms then select the Category tab 3 In step 1 select the category that currently contains the alarm sources NOTE n step 1 and step 2 Ctrl click Shift click or both to select multiple items or select the Select All checkbox In step 2 select the alarm sources whose category you want to change In step 3 select a category from the drop down list then click Change Click OK To add a custom alarm category PREREQUISITE Add the custom alarm category in EIKON LogicBuilder See To use custom alarm and schedule categories in EIKON LogicBuilder Help 1 Onthe CFG tree click the plus sign to the left of Categories 2 Click Alarms 3 Click Add See table below 4 Click OK Field Notes Reference Must be unique in the database be lowercase and not contain any spaces This Name name must be identical to the name of the custom alarm category that you added in EIKON LogicBuilder Icon 1 Find or create a 32 x 32 pixel icon gif file that represents the new category For example 2 Store the gif file in the WebCTRLx x webroot _common IvI5 graphics e
89. assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package Write to Database Optional WebCTRL Packa NOTE To see if your system has this optional package click Es then select About You have this package if Enabled Features shows Adv Alarming The Write to Database alarm action stores alarm information in a table in the WebCTRL alarm database or in a custom database Third party applications can access the alarm information for building maintenance management or alarm analysis For example an application can perform actions such as triggering a stored procedure or running a report 96 2011 Automated Logic Corporation WebCTRL v5 User Manual Writing to the WebCTRL alarm database When you add the Write to Database alarm action by default WebCTRL writes alarm information to the write_db_ra table in the WebCTRL alarm database The following table describes the information that WebCTRL writes to the database and gives the column name and data type you will need in order to access the alarm informatio
90. ate with WebCTRL extensions for FrontPage See page 185 e To edit existing control programs or translation files see Editing translation files control programs or graphics page 189 To enter a key term in EIKON LogicBuilder In EIKON LogicBuilder s Property Editor type before each key term Property Page Text Show Property Page Text BThis value Property Page Text NOTES e Type only the key term in EIKON LogicBuilder Expressions such as present_value are put in the translation file as part of the translated text See EXAMPLES in Translation files below e Key terms can contain only alphanumeric characters and underscores no spaces and cannot start with a number Translation files Translation files are used to translate key terms in control programs and graphics created with WebCTRL extensions for FrontPage see page 186 A translation file contains key terms and their language specific equivalents For a non English system you must create an English translation file and a non English translation file for each of the following Each control program Key terms used in multiple control programs Each graphic created with WebCTRL Extensions for FrontPage Key terms used in multiple graphics 2011 Automated Logic Corporation 183 WebCTRL v5 User Manual EXAMPLES Translation files Key term Language specific equivalent English This_value This value is present_value Zone_temp Zone temperature
91. ated Logic Corporation 53 WebCTRL v5 User Manual 54 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 6 Schedules Using schedules your equipment can maintain one set of setpoints during occupied periods to provide comfort and it can maintain a different set of setpoints during unoccupied periods to reduce energy consumption Schedules are WebCTRL s most effective cost saving strategy see page 137 You can apply a schedule to a tree item or to a group of tree items E When you apply a schedule to a tree item the schedule affects School equipment at and below the area or equipment where the E Building A schedule was added Lobby Health Center Main Office Main Conf Room Break Room Rest Rooms Room 1 Room 2 Room 3 E When you apply a schedule to a schedule group the schedule School affects all pieces of equipment in the group Bf Building A Lobby For example a school board meets every third Tuesday of the H Hgallh Canter month and uses the lobby main conference room break room 7 and rest rooms You can create a schedule group to control Sa Gs BEUR these different areas with a single schedule Break Room Rest Rooms H B Room 1 H B Room 2 H B Room 3 NOTES e When multiple schedules affect a tree item the combined result is the Effective Schedule see page 60 e Do not include preheating or precooling time in your schedules Optimal Start see page 49 anoth
92. ation Notes Enable this field to put restrictions on passwords An operator s login name and password must be different when this policy is enabled After you change the password policy any operator whose password doesn t meet the new requirements will not be locked out of the system but will be prompted to create a new password You can require that passwords contain any or all of the following Numbers Special characters any keyboard character that is not a number or letter Letters uppercase lowercase or both Enter a number to limit how often users can change their passwords When set to O users can change them as often as they want Enter a number between 1 and 20 Enter O to reuse passwords without a delay Enable to set the number of days an operator can use his password before the system requires him to change it Enter a number between 1 and 999 Click this button to force every user s password to expire Each user will be prompted to change their password when they next attempt to log in to WebCTRL 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 12 Cost saving strategies HVAC equipment runs in order to maintain adequate temperature for zones Some zones like classrooms must maintain a comfortable temperature only while people occupy them When a zone is no longer occupied you can define different setpoints that require less energy to maintain Use WebCTRL Schedules
93. axed Relaxed heating cooling setpoint setpoint 66 00 80 00 Demand 3 Demand 2 Demand 1 Occupied Unoccupied ALARH COOL IDEAL HARH ALARH To define Demand Control properties 1 On the GEO or NET tree select the electric meter 2 Click Properties 3 Expand the Demand Level Parameters section 4 Type the Start Time and End Time to define the time period that you want demand control to be in effect for this zone 5 Type kilowatts per hour kW hr in the Level columns to define the amount of power that the demand must exceed before WebCTRL calls for a higher demand level 2011 Automated Logic Corporation WebCTRL v5 User Manual NOTE Levels are defined in the electric meter control program in EIKON LogicBuilder You can test the Demand Levels by locking the meter to a value In the example below during Period 4 defined as 12 00 noon to 16 00 4 00 p m if the demand exceeds 800 kW hr WebCTRL will use Demand Level 1 setpoints If the demand exceeds 1000 kW hr WebCTRL will use Demand Level 2 level setpoints and so on Setpoint Optimization Setpoint Optimization also known as Trim and Respond saves energy by calculating the setpoint of a piece of equipment based on the number of heating or cooling requests it receives from other equipment You must put a Setpoint Optimization microblock in a control program to receive Total Average Minimum or Maximum microblock outputs from linked equipment 2011 Autom
94. ay a different language You can also set up multiple languages so different operators can view the system in different languages Follow the procedures below to display WebCTRL in non English languages Install a language pack see page 181 Prepare your workstation for non English text see page 181 Create control programs and translation files see page 183 Create graphics see page 185 Create your system in SiteBuilder see page 187 ao a fF NY Set an operator s language in WebCTRL see page 188 Installing a language pack A language pack translates the text in the WebCTRL interface WebCTRL is installed with an English language pack To download other language packs 1 Go to http accounts automatedlogic com http accounts automatedlogic com 2 Select Support gt Download 3 Under Software Updates select Language Packs for the version you need 4 Follow the instructions under To install this language pack NOTE If you create a system by copying an existing system that uses language packs install the same language packs on the new system Preparing your workstation for non English text Set up your workstation so you can type international fonts from your keyboard 1 Install the appropriate fonts for the languages you will be using In the Windows Control Panel open Fonts select File Install new fonts 2011 Automated Logic Corporation 181 WebCTRL v5 User Manual 2 Inthe Control Panel o
95. bCTRL v5 User Manual Chapter 17 Setting up a system in WebCTRL Editing the GEO or NET tree in WebCTRL In WebCTRL you can edit the GEO or NET tree that was originally set up in SiteBuilder The system database is updated immediately Right click an item in the GEO tree then select Set up Tree Click GEO or NET to display the tree you want to edit Click this Or use this button shortcut X Ctri X E Ctrl V y Up arrow or Drag and drop in new location A Down arrow or Drag and drop in new location EA Delete Double click the tree item 2011 Automated Logic Corporation To Add an area as a child of the selected area GEO tree only Import a clipping that was saved in SiteBuilder See To import a clipping page 158 below Cut a selected item so it can be pasted in another location in the tree GEO tree only Paste an item that was previously cut from another location in the tree The item will be pasted as a child to the selected item GEO tree only Move the selected item up the tree to a new location GEO tree only Move the selected item down the tree to a new location GEO tree only Rename the selected item Delete the selected item The item and all of its children will be deleted Edit the item s features such as e names e view See To attach a graphic in WebCTRL page 33 e control program See Working with control programs in WebCTRL page 171 WebCTRL
96. ccess 131 157 160 location independent operator access 123 131 logging in e 27 123 127 130 logging out 30 127 141 161 Logic pages 31 39 49 124 login 27 82 127 160 169 191 login name e 127 128 login failed 160 161 logoff 128 maintenance e 207 manual commands 141 Manual Commands Console Operations privilege 124 141 markdownload manual commands e 141 memory e 65 menu button e 21 menu commands 21 microblock paths e 41 microblock pop up e 31 33 36 39 141 microblock properties 31 33 36 39 41 microblocks e 31 33 36 39 minimize database size e 208 mismatch 48 141 160 163 modems 82 101 141 modstat e 141 modstat manual commands 141 module memory e 65 MSDE database 161 207 multi state schedule category e 62 My Settings 82 130 131 MySQL database 161 207 N NAT 82 navigation pane e 21 24 navigation tree e 21 navigation WebCTRL 21 network number e 163 node name 160 non English system 181 Normal mode 27 Notify all users 30 notify manual command 141 O operator access 123 131 135 operator groups 123 127 operators 123 127 128 131 133 optimal start 49 137 Oracle database 161 207 P parameters e 44 2011 Automated Logic Corporation paramupload manual command 141 password 27 123 127 128 130 135 password policy 128 135 160 161 paths 41 Permissions e 7 Postgr
97. change programmed setpoints 1 Navigate to a setpoint control in one of the following places o The zone temperature section of a Properties page o The setpoint microblock pop up on a Logic page o A Graphics page Click a setpoint trend graph control to access the editable setpoint bar 2 Ona programmed setpoint bar click the segment or the gap between segments you want to change 3 Type new values in the Heating and Cooling fields TIP You can click and drag a segment or a gap between segments to change setpoints 4 Click OK Optimal Start Optimal Start gradually moves the unoccupied setpoints toward the occupied setpoints as the occupied time approaches The actual equation that a controller uses to calculate Optimal Start is nonlinear An approximation of the equation is shown below 2011 Automated Logic Corporation 49 WebCTRL v5 User Manual design temp OAT calculated capacity Je Zone temperature amp y design temp 65 ne P x capacity at 65 Ut cupied mh w K Refining Optimal Start saves energy in the following ways e Removing guesswork from preheating or precooling zones e Ensuring that zones reach the ideal comfort range just as people arrive e Preventing equipment from running unnecessarily during unoccupied periods You can adjust the Optimal Start routine in the control program s Zone Setpoint microblock 1 Inthe GEO tree select the equipment that you want
98. chive the trend data from the controller to the WebCTRL database A trend graph can display data from both the controller and the database To collect trend data for a point PREREQUISITE Assign an input or output number to the point in EIKON LogicBuilder or WebCTRL Before you can look at a trend graph for a point you must enable trending for that point and then tell WebCTRL how you want the controller to collect the point s data 1 On the GEO tree select the equipment that has the point you want to trend 2 Click the Trends button drop down arrow select Disabled Points then select the point 3 Click the Enable Disable tab then select Enable Trend Log to have the controller collect trend data 4 Enter information in the appropriate fields See table below 5 Click OK TIP You can set up all trends for a piece of equipment at once on the Trend Sources tab of the equipment s Properties page Field Notes Sample every _ _ _ Records the point s value at this interval hh mm ss NOTE Set trend intervals for U line controllers to one minute or greater U line controllers are designed to meet low end high volume terminal control applications and are not suited to very short trend intervals 2011 Automated Logic Corporation 65 WebCTRL v5 User Manual 66 Field Sample on COV change of value Allocate memory for __ samples in the controller Stop When Full Enable trend log at specific times only Enable Trend
99. criteria WebCTRL can perform the following alarm actions Alarm Popup Print Propagate To Server Run External Program Send Alphanumeric Page Send E Mail e Write to File If your system has the Advanced Alarming package WebCTRL can also perform the following alarm actions e Send SNMP Trap e Write Property e Write to Database See the following topics for a description of each alarm action To assign alarm actions to alarm sources 82 To assign alarm actions to multiple alarm sources Although you can assign an alarm action to a single alarm source you typically assign an action to multiple alarm sources at the area or equipment level The alarm action applies to all instances of the alarm sources at the selected location and below Click an action s Edit button to make any changes To assign an alarm action to alarm sources 1 Onthe GEO or NET tree select the area equipment or controller containing the alarm sources 2 Click Alarms then select the Actions tab 2011 Automated Logic Corporation WebCTRL v5 User Manual 3 Follow the 3 steps on the screen NOTE Use Ctri click Shift click or both to select multiple items Click Add Set up the alarm action by editing the fields on the alarm action page See the appropriate alarm action below for field descriptions 6 Click OK After you have assigned alarm actions to an alarm source simulate the alarm see page 104 to check your work If an alarm actio
100. customize this text by selecting field codes see page 108 from the Append Field Code list Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the work hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package Ask your network administrator for this information Write Property Optional WebCTRL Packa NOTE Tosee if yo
101. d select the language you want to use 3 Click OK 2011 Automated Logic Corporation 185 WebCTRL v5 User Manual To set the default font If your system has language packs installed you can select a language to be the default language for all new graphics that you create in ViewBuilder You can then change the language selection for an individual graphic in its View Properties To set the default language 1 Select Configure Preferences 2 Select the Languages tab 3 Select the checkbox for the default language ViewBuilder uses the defined font for all text in your graphic The default is Arial Unicode MS because it supports all languages and is the only font that ensures controls and labels in your graphic will align correctly in WebCTRL If you do not see Arial Unicode MS in the Font column install it if possible using the following instructions If you cannot install it use the font shown or click on it to see other fonts that you can select To install the Arial Unicode MS font Arial Unicode MS is only supplied with Microsoft Office Although Office may be installed on your computer the font may not be installed Insert your Microsoft Office CD in the computer Select Start gt Control Panel In the Control Panel select Add Remove Programs Make sure Change or Remove Programs in the upper left corner is selected Select Microsoft Office XP or Microsoft Word 2002 Click Change In the Setup window select A
102. dard format However you can change the format and how much data is displayed on the graph Legend OA Temp Y axis label Y axis Grid Title Temperatures RA Temp MA Temp X axis time a A N Click OK Field Font size Enable Grid Autoscale x axis X initial range Autoscale y axis Y axis minimum and maximum Graphs Points for custom graphs only On the GEO tree select the equipment that has the trend graph properties you want to configure Click the Trends button drop down arrow then select the trend you want to change Click the Configure tab Edit the graph properties as needed See table below Notes Lets you change the font size of the graph s title and other text Show or hide the graph s grid Gathers the most recent 2000 data samples and then autoscales the x axis to include the complete time range of all the samples If you do not autoscale the x axis type in this field how far back WebCTRL should go to display data For example if you want to see trend data from a week ago type 7 in the Days field Gathers the trend data from the controller and then autoscales the y axis to include the complete range of values If you do not autoscale the y axis type the minimum and maximum value that you want the graph to display Add or delete graphs from the page Add or delete points from the graph selected in the Graphs table 2011 Automated Logic Corporation WebCT
103. dd or Remove Features Click Next 9 Expand Office Shared Features oN o Oc FF WO N 10 Expand International Support 11 Click the icon next to Universal Font 12 Select Run all from My computer 13 Click Update 14 Restart ViewBuilder if it was open Creating a graphic for a multi language system using WebCTRL extensions for FrontPage 186 When you create a graphic using WebCTRL extensions for FrontPage you enter a key term instead of text in the graphic When the graphic is displayed in WebCTRL the key term is replaced with its equivalent in the translation file for the current operator language See Creating control programs and translation files page 183 2011 Automated Logic Corporation WebCTRL v5 User Manual To enter a key term for an image area label 1 Double click the image area label 2 Enter a key term in the Label Text field NOTE Use only alphanumeric characters and underscores no spaces Do not start a key term with a number Select Label Text is resource key Do one of the following o Ifthe translation file for the graphic is in WebCTRL webroot lt system_name gt graphics IvI5 leave the Resource field blank o Ifthe translation file is in WebCTRL webroot lt system_name gt resources enter the following in the Resource field resources lt translation file prefix gt EXAMPLE resources translation 5 Click OK To enter a key term for other text Click the International Text button A
104. dded manually not through an automated process To edit or delete a custom report 1 Selectthe item in the GEO or NET tree where the report was created 2 Click the Reports button drop down arrow then select the report you want to edit or delete Do one of the following o Editthe report then click OK o Click the menu button EA then select Delete To organize custom reports You can organize your custom reports by creating report categories that appear in the Reports button drop down list Custom report category Custom report To add or edit a report category 1 On the CFG tree click H to the left of the Categories folder then click Report 2 Click Add or select a category to edit it 3 Type the Category Name and Reference Name 4 Select a privilege so that only operators with that privilege can access reports in the category 5 Click OK NOTE To delete a category select the category click Delete then click OK 2011 Automated Logic Corporation 121 WebCTRL v5 User Manual To use custom reports from v2 5 or earlier 122 If you upgrade WebCTRL from a version that had custom reports created with e Spreadsheet Report Designer or Formula One you can continue to view and edit those reports in WebCTRL Copy the following files from WebCTRL2 5 webroot WEB INFNib or WebCTRLS3 ONib to WebCTRLx x bin lib in your new version of WebCTRL f1j9_de jar f1j9_es jar f1j9_fr jar f1j9 it jar f1j9 ko jar f1j9 zh
105. down manual command 27 141 site properties 167 SiteBuilder 18 SNMP 82 SOAP 16 124 191 source files 7 44 spreadsheet data retrieval 191 SSL 153 191 starting location 128 130 starting page 128 starting the WebCTRL Server e 27 starting WebCTRL e 27 static BACnet bindings e 160 163 status values e 31 65 synchronize time e 160 164 167 system database e 27 157 back up 207 database type 160 207 defragment e 207 maintenance e 207 minimize size e 208 system language 160 system maintenance 207 system name e 160 System Settings 160 System wide alarms button e 21 system wide privileges 128 131 132 T tab e 21 TCP ports 83 91 TCP IP 16 Test amp Balance 13 thermographic colors 25 Third Party BACnet Utility 13 third party integration e 13 time format 12 hour or 24 hour e 160 time synchronization e 160 164 167 time zone 164 165 167 timesync manual command 141 TLS SSL ev 153 191 translation file 183 189 trend data 40 65 67 69 164 191 Trend Samples report 113 119 trends e 7 41 65 copying 67 enabling historian 65 historical 65 69 164 208 trend graph 67 69 72 viewing e 69 troubleshooting 31 39 40 U upload 46 48 163 211 WebCTRL v5 User Manual 212 V ViewBuilder 18 ViewBuilder for WAP e 18 W WAP e 153 WAP devices e 153 Web applications 7 166 WebCTRL action pane e 21 WebCTRL client 16 27 WebCTRL Desig
106. ds a page to one or more alphanumeric pagers or sends text messages to cell phones The pager or phone must be able to accept e mail Field Notes To Type the address es that you want to send the alarm to To enter multiple addresses type a space or press Enter after each address From Enter a valid address if required by your mailserver 2011 Automated Logic Corporation 89 WebCTRL v5 User Manual 90 Field Notes Mail Host The SMTP mailserver s address This can be an IP address or a system name such as mail mycompany com Specify Mail User For Select if your mailserver requires a username and password Mail Host Authentication Send mail as MIME Select if your mailserver allows only MIME attachments attachment Message Text Use punctuation spaces or returns after the entries to format the text To add live data to the text select field codes See page 108 from the Append Field Code list Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during th
107. e View buttons Geographic tree e Network tree e Groups tree Configuration tree NOTES e After you log in to WebCTRL you will see the page defined as your starting location on the My Settings page To change your opening page see To change My Settings page 130 e Privileges control what an operator can see or do in WebCTRL If you cannot see or do something that you read about in Help ask your System Administrator to check your privileges 2011 Automated Logic Corporation 21 WebCTRL v5 User Manual Navigating the system NOTE Use only the WebCTRL interface to navigate through WebCTRL do not use the browser s navigation buttons To navigate to an item in the system 1 Select an item in the GEO or NET tree NOTE The GRP and CFG trees are used to set up your system 2 Use the action buttons and their drop down menus to navigate to specific types of information about the selected tree item 3 Use the tabs to filter the information further To navigate using links Use links to jump to related pages On a Graphics page On a Properties page Name AHU1 1801 salut 1801 Control Progr oec Roter Lon ron 1 mei Last Parameter Change Thu Mar 30 10 16 14 EST Tree icons and hover text 22 The navigation tree displays an icon to the left of each item to denote the type of item For example oli System Sa Area Equipment You can select custom equipment icons in EIKON LogicBuilder or in WebCT
108. e 1 Select the Alert Text field code 2 After alerttext type one of the following normalshort normallong alarmshort alarmlong For example alerttext alarmlong A single ASCII character Often used for form feeds and other printer escape sequences For example C 65 displays A The commanded value from the alarm source Valid only for alarm type COMMAND FAILURE The deadband value from the alarm source Valid only for alarm type OUT OF RANGE The operator who deleted the alarm The time the alarm was deleted The display name of the device where the alarm came from The display name of the equipment where the alarm came from The error limit from the alarm source Valid only for alarm type FLOATING LIMIT The exceeded limit value from the alarm source Valid only for alarm type OUT OF RANGE 2011 Automated Logic Corporation Field Code Name Exceeding Value Fault Feedback Value Field Message From State Generation Operator Generation Time In Alarm Incident Closed Time Latched Data Value Analog Latched Data Value Digital Location Path Long Message Message Details Message Prefix Message Text New State New Value Object ID Out of Service Overridden Field Code exceeding_value fault feedback_value field_message from_state generation_operator generation_time in_alarm incident_closed_time latched_data_analog x
109. e Specify Custom Database checkbox on the Alarms page Actions tab then enter information in the remaining fields See table below Field Text to write to the database Database Connect String Database Login and Password Notes The text is made up of field codes see page 108 that add live data to the text You can select additional field codes from the Append Field Code list NOTE To write the text in this field to the custom database you must include the Report Text field code report_text in the Database Insert String field described below For database type SQL Server MySQL PostgreSQL Oracle The connect string format is jdbc odbc odbc alias jdbc mysql host port instance jdbc postgresql lt host gt lt port gt lt instance gt jdbc oracle thin lt host gt lt port gt lt instance gt where lt host gt is the database server name IP address lt port gt is the port number for the database lt instance gt is the database name in the database server lt odbc_alias gt is the name of the ODBC data source The login and password to connect to the database 2011 Automated Logic Corporation WebCTRL v5 User Manual Field Notes Database Insert Use the following format String Insert into lt TABLE_NAME gt column1 name column2 name values lt field_code1 gt lt field_code2 gt Example Insert into WebCTRL_ALARMS TIME_ LOCATION_ TO_S
110. e range Select the time range to run the report for 2011 Automated Logic Corporation WebCTRL v5 User Manual Type of Column Data Trend Display Select the type of calculation to show in the column Calculation Average or Total Data is named Select this checkbox if similar points have different names differently in some _ in different control programs Then add each of the names equipment to the Name to use list For example if a point is named Zone Temp in one control program and Zone Temperature in different control program add both names to the list Trend to use Select the name of the point to show in the column Set Click to have all columns in the report use the same time range Time Range Select the time range to run the report for Equipment Display Select Color Display Name Display Path Notes Prime Variable or Reference Name to show in the column Expression Data is named Select this checkbox if similar points have different names differently in some in different control programs Then add each of the names equipment to the Name to use list For example if a point is named Zone Temp in one control program and Zone Temperature in different control program add both names to the list Expression Type the GQL expression relative to the current control program The GQL expression must return a string value To display the Notes on an equipment s Properties page type notations in this field To create an Tre
111. e and delete SSL certificates simplifying the process of certificate creation and deletion Improvement New tools let you draw vector lines and shapes The ViewBuilder library now has graphics for lighting 2011 Automated Logic Corporation What s new Other tools Use Field Assistant Third Party BACnet Utility Test amp Balance Redesigned 2011 Automated Logic Corporation WebCTRL v5 User Manual To Service or start up and commission a piece of equipment or a partial network of controllers Use discovered BACnet information to choose and address microblocks for third party BACnet integration Calibrate airflow in VAV zone controllers commission air terminals and override reheat and terminal fans 13 WebCTRL v5 User Manual 14 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 2 What is WebCTRL WebCTRL is a web based building automation system that can be accessed from anywhere in the world through Internet Explorer without the need for special software on the workstation Through Internet Explorer you can perform building management functions such as adjust setpoints and other control parameters set and change schedules graphically trend important building conditions view and acknowledge alarms run preconfigured and custom reports on energy usage occupant overrides tenant billing and much more dE Prestige Corp EE Bf First Floor Wi Second Flo
112. e and specify the expressions to get Enter the code to get the values and insert them into the spreadsheeet on o Om fF This displays an error checking statement if an error is found in the data Sub testSoapRead host Range Al Value user Range A2 Value passwd Range A3 Value Dim changeReason As String 3 Dim client As MSSOAPLib30 SoapClient30 Set client CreateObject MSSOAP SOAPClient30 URL http amp host amp common webservices Eval wsdl client mssoapinit URL client ConnectorProperty WinHTTPAuthScheme 1 client ConnectorProperty AuthUser user client ConnectorProperty AuthPassword passwd 5 On Error GoTo err M VB arrays start at index 0 and are declared by the maximum index M some the next line declares an array of two strings at indices 0 and 1 Dim expressions 2 As String Dim values 2 As String Dim result As String expressions 0 Range A5 Value expressions 1 Range A6 Value expressions 2 Range A7 Value 200 2011 Automated Logic Corporation WebCTRL v5 User Manual result client getValues expressions 7 Range B5 result 0 Range B6 result 1 Range B7 result 2 GoTo done err Range D amp i Value ert Description done End Sub NOTE If you have problems connecting to WebCTRL using Visual Basic add the following line client ClientProperty ServerHTTPRequest
113. e computer 5 Enter a Name and Password To set up a computer and browser to view WebCTRL NOTES e WebCTRL Server must be running before operators can log in from client browsers e To view trends client computers need Sun s Java VM plugin In WebCTRL go to the CFG tree Client Installs page for a link to the Java website 2011 Automated Logic Corporation 27 WebCTRL v5 User Manual 28 Browser settings Accept First party and Third party cookies Automatically check for newer versions of stored pages Load ActiveX Control Disable the Image Toolbar IE6 Select Play animations in web pages Do not save passwords if the computer is used by multiple operators Disable all the options on the Explorer Bar Disable browser s pop up blockers Disable external toolbar pop up blockers Hide the browser s toolbars Maximize the browser window Computer settings Set the monitor s screen resolution to a minimum of 1024 x 768 with 24 or 32 bit color quality Where to change setting Tools gt Internet Options gt Privacy tab gt Advanced button Tools gt Internet Options gt General tab gt Browsing history gt Settings button Tools gt Internet Options gt Security gt Custom Level gt Activex controls enable all of the following settings Download signed ActiveX controls gt Prompt Download unsigned ActiveX controls gt Disable Run ActiveX controls and plug ins gt Enable Sc
114. e control programs or graphics Click OK Save the control program The translation files are bundled with the control program the original files are no longer necessary NOTE If you need to change a translation file after you save the control program see To edit a bundled resource page 189 2011 Automated Logic Corporation 189 WebCTRL v5 User Manual Copying translation files to another system To copy most translation files from one system to another you copy the files in the source system and paste them into the same folders in the destination system However if your source system and destination system have translation files with the same name copying and pasting would overwrite the file s in the destination system In this case 1 Open the source system s translation file in a text editor then copy the key terms and translations 2 Open the destination system s translation file in a text editor then paste into it the key terms that you copied Remove any duplicate key terms 190 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 23 Web services Optional WebCTRL Pack 7 NOTE Tosee if your system has this optional package click CH then select About You have this package if Enabled Features shows Enterprise Using Web services to retrieve or change data Web services are A class of data exchange using XML extensible markup language and SOAP simple object access protocol
115. e for second sample 10 02 2002 10 23 00 AM gt Time for third sample 76 2 gt Trend data value for third sample Parameters e user WebCTRL operator login Id This user should have the Remote Data Access privilege e password Password for the above WebCTRL user e trendLogPath The full GQL path to the point or trend log node whose trend data is desired For example mxm ai_interval or mxm ai_interval trend_log e STime Start Time Returns trend data values starting with this time e eTime End Time Returns trend data values until this time e limitFromStart If maxRecords is gt 0 use True to retrieve maxRecords from the start sTime if specified or the first record in the database use False to retrieve maxRecords from the end eTime if specified or the last record in the database e maxRecords Maximum number of records desired Use a number gt 0 to limit records use O to retrieve unlimited records If using O you must specify sTime and eTime limitFromStart will be ignored 2011 Automated Logic Corporation WebCTRL v5 User Manual NOTES e sTime and eTime format MM dd yyyy hh mm ss aa Example 10 02 2002 10 22 00 AM e f you do not want to specify a start time or end time use NULL or an empty string for the sTime or eTime In this case maxRecords must be gt 0 EXAMPLES e STime 04 07 2007 12 00 00 AM eTime NULL limitFromStart True maxRecords 10 The first 10 records starting on 4 7 07 a
116. e second Tuesday of every month NOTE Wildcard schedules do not work with ALC legacy equipment WebCTRL will let you know if you apply a schedule to legacy equipment Continuous Continuously between specified times on two separate dates Dated Weekly Weekly between a start date and an end date For example the summer break in the school year NOTE To use a Dated Weekly schedule with an ExecB controller you must use the 1 7 1 032 or later ExecB driver NOTES e To have all new schedules and schedule changes in the system download automatically click Show Advanced under the Add button then select Automatically Download Schedules If you want to manually download schedules see Downloading system changes to controllers page 43 e When you apply a schedule to an item in the GEO tree the schedule affects that item and all children of that item If you do not want an item to be affected by schedules from a higher level click Show Advanced under the Add button then select Ignore Schedules above this level To apply a schedule to a amp roup of items You must create a group then add members areas equipment or other groups to the group before you can apply a schedule to it 1 Onthe GRP tree select Scheduling Groups Optional If you have created folders to organize your groups select the appropriate folder See To organize groups using folders below 2 Click Add Group 2011 Automated Logic Corporation 57 WebCTRL v5 User M
117. e to the router or the network on the NET tree You must have the Manual Commands Adv Network privilege to run this command Ping to verify communication between to IP devices You cannot ping devices on non IP networks To run this command type ping hostname where hostname is the IP address or device name For example ping 192 168 168 1 will ping the IP address 4 times or ping 192 168 168 1 t will ping the IP address constantly Restarts WebCTRL Server You must log back in to WebCTRL if you want to continue You must have the System Shutdown privilege to run this command Rebuilds a Properties page Use if you make changes to control program property text in EIKON LogicBuilder Reloads a control program Use if you make changes to control program logic in EIKON LogicBuilder You must have the Engineer System privilege to run this command Restarts the current controller You must have the Manual Commands Adv Network privilege to run this command Overrides the address configuration of the Rnet host controller to allow a subsequent All Content or Parameters download Run this command if you experience communication problems with the controller because the controller s network number does not agree with SiteBuilder s network number Run this command from a control program device or driver Resets the selected driver or control program to its default values Sets the current page as the default view for the s
118. e unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it Create a schedule for the group Set the occupied hours to be the same as the work hours Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package NOTE You should not assign this alarm action to frequently occurring alarms as this may cause problems on your network or the Internet To set up a dial up networking connection WebCTRL can use a dial up internet connection through a modem to deliver e mail for the Send E mail or Send Alphanumeric Page alarm action To set up the dial up connection 1 Setup your modem to dial out to your Internet Service Provider See your modem documentation 2011 Automated Logic Corporation WebCTRL v5 User Manual On the WebCTRL server open Internet Explorer Select Tools gt Internet Options On the Connections tab click Setup Follow the instructions in the wizard See Windows Help for assistance ao a fF ND In a text editor s
119. eSQL e 161 207 Print alarm action 82 178 printing 24 priority level 56 privilege set 123 124 127 131 132 assigning to an operator e 128 129 133 privileges 41 123 124 131 132 Propagate To Server alarm action e 82 properties 36 39 41 Properties pages 31 36 43 45 protocol e 16 R rebootserver manual command 141 rebuild manual command 141 reload control programs 141 171 reload manual command 141 remote data retrieval 191 202 remote file management 151 161 reports e 7 113 categories 121 custom 113 116 117 119 121 122 reset to defaults 39 restartmodule manual command 141 right click menus e 24 rnet here manual command 141 Run External Programs alarm action 82 S schedule 43 44 55 56 62 137 categories 62 deleting expired schedules e 160 164 208 groups 7 57 occupancy 56 62 reports 113 setting up e 55 56 viewing 56 secure socket layer SSL 153 191 Security Assignments Report e 131 Send Alphanumeric Page alarm action 82 Send E mail alarm action e 82 91 Send SNMP Trap alarm action e 82 sequence of control e 31 Server e 16 27 service packs and patches 124 setdefault manual command 141 setgcm manual command 141 setpoint optimization 49 137 shortcuts mouse and keyboard 70 157 Show Auto hide button e 21 2011 Automated Logic Corporation WebCTRL v5 User Manual showhistory manual command 141 shut
120. eate the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied 5 Available only if you have the Advanced Alarming package 2011 Automated Logic Corporation 99 WebCTRL v5 User Manual Write to File The Write to File alarm action can do either of the following e Record alarm information in a standard ASCII text file that you can view and edit using a text editor such as Windows Notepad e Write a WebCTRL report to a file Field File Name Write as File Append Text to write to the file Write as Report 100 Notes Path name for the file you want to write to such as c WebCTRLx x webroot alarms txt e If you do not specify a path the file is written to the system folder e If you type a path that does not exist WebCTRL will create the necessary folders e You can write to one of the following a file on the server anetworked computer if you map the network drive Use the drive mapping in the path from the server to the computer e The path name may contain field codes see page 108 Select to record alarm information in a text file Select to append new alarm information to the end of the file instead of writing over existing data NOTE Because you can append new alarm information to the end of the file this file can become very large You must back up and delete this file frequently if you are usi
121. eded Access Network items as needed Any privileges needed for the specific task Every change made through Web services is recorded in the Audit Log If you do not want these changes recorded in the Audit Log add the following privilege to the privilege set Do not audit changes made using SOAP Web Services WebCTRL data access using SOAP NOTE The operator attempting to use SOAP must have the Remote Data Access privilege 192 You can use the following services with WebCTRL data Eval Returns the value for the given GQL Expression Trend Returns trend data for a specified point Report Returns the WebCTRL report in CSV or HTML format System Returns a path to a folder in the system folder where a web application can store data so that it is backed up with other system files The information below gives the WSDL methods and parameters for each service NOTE You may discover other methods in our web services that are not listed below but these are for internal use only and not intended for use by our customers 2011 Automated Logic Corporation WebCTRL v5 User Manual 1 Eval See Example using Web services to set a value page 197 Example using Web services to retrieve values page 199 WSDL http lt WebCTRL_server gt _common webservices Eval wsdl Methods a String getValue String expression Returns the raw value for the given expression b String getValues String expressions Returns an
122. elected action button and the selected tree location You must have the Engineer System privilege to run this command 145 WebCTRL v5 User Manual Command Description setgcm Initializes any LANgate gateway from a converted SuperVision system After downloading to the LANgate run setgcm if you e Added a controller to a CMnet where the address is set higher than any other address on the CMnet e Changed the 3 letter system name e Changed the dead module timeout value on the System Settings page e Changed the site number in SiteBuilder previously referred to as the line number setgcm sends the following information from the WebCTRL database to the LANgate e Maxnet the highest addressed controller plus one e 3 letter system name e Site number e Dead module timeout value NOTES e You can send this command over network direct or modem connections but not over a direct network access port e In SuperVision the command set the workstation phone number in the LANgate You must now type the LANgate s phone numbers on the LANgate s parameter pages e You must have the Manual Commands Adv Network privilege to run this command showhistory Gives historical information on the system such as when it was created and updated You must have the Manual Commands Unrestricted privilege to run this command shutdown Shuts down WebCTRL Server This stops communication between the server and the client but does not close
123. eport to run CSV or html 4 System WSDL http lt WebCTRL_server gt _common webservices System wsdl Method String getWebAppStorageDirectory String webAppName Returns a path to a folder in the system folder where a web application can store data The web application is responsible for creating the folder Parameter webAppName A name unique to the web application 196 2011 Automated Logic Corporation WebCTRL v5 User Manual Example using Web services to set a value Follow the process below to change a BACnet Binary Point s e Raw value in the WebCTRL database and controller e Display value shown in WebCTRL Step 1 Create a spreadsheet 1 Enter the following information the spreadsheet uses to log in to the WebCTRL system o WebCTRL Server IP address or the server network name Cell A1 in this example o Operator name for logging in to WebCTRL Cell A2 in this example o Operator s WebCTRL password Cell A3 in this example 2 Enter the GQL path to the property whose raw value you want to set Cell A5 then enter the raw value Cell B5 NOTE You can use an absolute path such as trees geographic points io_points m001 or a global reference name 3 Enter the GQL path to the property whose display value you want to set Cell A6 then enter the display value B6 4 Ifyou need to comply with 21 CFR Part 11 see page 135 enter the reason the values are being changed Cell C5 and C6 A 1 192 1
124. eports button drop down arrow then select New Report 3 Select Equipment Summary 4 Optional Select a Category NOTE The Category field is visible only if you have defined report categories See To organize custom reports page 121 Type a name for the report Click Create On the Design tab define the title layout and the Maximum number of rows N o OI To create a CSV Comma Separated Values file after you run the report select Support CSV text format See To create a PDF Excel spreadsheet or CSV file page 121 Select or clear the Optional Sections checkboxes as needed 10 Optional Select Show only equipment for specific control programs at or below this location then type the names of the control programs 2011 Automated Logic Corporation WebCTRL v5 User Manual 11 Select Available Points that you want to include in the report Use Ctrl click Shift click or both to select multiple items 12 Click Add 13 Click OK 14 Click Run NOTE To run this report later go to the location where the report was created Click the Reports button drop down arrow select the report then click Run To create an Equipment Values report Optional WebCTRL Package NOTE To see if your system has this optional package click Es then select About You have this package if Enabled Features shows Adv Reporting An Equipment Values report allows you to compare point information To create an Equipment Values rep
125. er user client ConnectorProperty AuthPassword passwd 5 On Error GoTo err i 5 6 expression Range A amp i Value newValue Range B amp i Value changeReason Range C amp i Value client setValu xpression newValue changeReason 1 6 7 expression Range A amp i Value newValue Range B amp i Value changeReason Range C amp i Value client setDisplayValue expression newValue changeReason GoTo done 8 err Range D amp i Value err Description done End Sub NOTE If you have problems connecting to WebCTRL using Visual Basic add the following line Gl client ClientProperty ServerHTTPRequest TRU above the line client mssoapinit URL 2011 Automated Logic Corporation WebCTRL v5 User Manual Step 3 Run the macro NOTE WebCTRL Server must be running 1 2 3 Example In Excel click Tools gt Macro gt Macros Select the TestSoapWrite sub routine Click Run The macro will write the values into the WebCTRL database and field controllers NOTE Follow the steps below if you get an error message when you run the macro a In Excel select Tools gt Macro gt Visual Basic Editor b Inthe Visual Basic editor select Tools gt References c Select the Microsoft Soap Type Library v3 0 and click OK using Web services to retrieve values Follow the process below to read the value of BACnet Binary Inputs Step 1 C
126. er computers 3 Inthe row that begins with lt script replace the highlighted text shown below with the information needed to start your system Leave a blank space between each field script url http someurl user admin password pwdi123 fullscreen true loop true NOTES o The Attribute list near the top of the file describes each field o To prevent exposing someone s password in this file create a generic user and password in WebCTRL 4 Each pair of rows beginning with navigate and delay define a page in WebCTRL and how many seconds WebCTRL should display the page Follow the steps below to replace each navigate line with information specific to your system Add or delete rows as needed a In WebCTRL go to the page you want to display b Press Ctrl m c Type autopilot location d Click OK The path to the WebCTRL page is displayed and is copied to the Windows clipboard 2011 Automated Logic Corporation 149 WebCTRL v5 User Manual e Inthe autopilot xml file highlight a navigate row then press Ctrl V to replace the highlighted text with the copied WebCTRL path NOTE To have the autopilot run a report define the path to the report s View tab In the lt delay row below each path change 20 to the number of seconds you want to display the WebCTRL page 6 Save the file To run WebCTRL s autopilot NOTE If your computer is running Windows Vista see To run autopilot with Windows Vista p
127. er cost saving strategy automatically calculates and controls precise preheating and precooling routines e Ifyou are using hierarchical servers when you add or change a schedule on the parent server the schedule is automatically downloaded to the corresponding location on the child server s 2011 Automated Logic Corporation 55 WebCTRL v5 User Manual To view schedules 1 Select a GEO tree item Click Schedules then the View tab Optional Click an Effective bar to view all the schedules that contribute to the resulting schedule If the item has multiple schedules the schedule closest to the Effective bar has the highest priority You set a schedule s priority when you create the schedule NOTES e You can display icons and hover text in the GEO tree that show where schedules have been created See Tree icons and hover text page 22 e You can also view schedules on the following detailed printable schedule reports These reports are accessible from the Schedules page Reports tab or from the Reports button drop down menu This report allows you to Schedule Instances Find every schedule with its location that is entered at and below a selected tree item This report can help you discover newly added and conflicting schedules Effective Schedules View all equipment that may be scheduled and the net result of all schedules in effect for a selected date and time See Effective Schedules page 60 Setting up schedule
128. erence ie D AHU 1 Accounting Cafeteria a E Electric Meter DEL Dallas Training Center New York Headquarter San Francisco Medical Restricting all operator access to a location To remove all operators local privileges from a location so that you can assign access only to a specific operator s navigate to the location select Privileges then clear the checkbox Inherit security privileges from above this level Security Assignments Report A Security Assignments Report shows an operator s local and system wide privileges and privilege sets at a specific location 1 Selectthe location on the GEO or NET tree 2 Click the Reports button drop down arrow then select Security gt Security Assignments 3 Onthe Options tab select an operator 4 Click Run 134 2011 Automated Logic Corporation WebCTRL v5 User Manual Recording reasons for edits 21 CFR Part 11 Optional WebCTRL Packag NOTE Tosee if your system has this optional package click EA then select About You have this package if Enabled Features shows Adv Security The Advanced Security package provides support for 21 CFR Part 11 With this feature enabled WebCTRL can require an operator to record a reason for changing an equipment property before WebCTRL accepts the change WebCTRL s Audit Log report then displays the operator s name and the recorded reason for making the change NOTE You cannot use WAP enabled devices to change equipmen
129. escription done End Sub NOTE If you have problems connecting to WebCTRL using Visual Basic add the following line client ClientProperty ServerHTTPRequest TRUE above the line client mssoapinit URL Step 3 Run the macro NOTE WebCTRL Server must be running 206 1 2 3 4 To launch and run the macro click Tools Click Macro gt Macros Select the TestReport subroutine Click Run The macro will retrieve the data and place it in the spreadsheet NOTE Follow the steps below if you get an error message when you run the macro a In Excel select Tools gt Macro gt Visual Basic Editor b Inthe Visual Basic editor select Tools gt References c Select the Microsoft Soap Type Library v3 0 and click OK 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 24 System database maintenance You should perform the following system maintenance on a regular basis To back up a system The type of database your system uses determines the method you use to back up the system For MS Access or MSDE 1 Shut down WebCTRL Server and SiteBuilder 2 In the WebCTRLx x webroot folder copy your system folder 3 Paste the copy to a new location TIP Zip the copy before transporting it over a network or to a CD For MySQL MS SQL Server Oracle or PostGreSQL Use the database management system s backup method To compact and defragment In a new WebCTRL system the records in
130. et Specification For example Tenant Billing is override war To deploy a web application from your WebCTRL system 1 Save the web application s war file to your computer 2 Onthe System Settings gt Web Applications tab click Browse and open the war file 3 Click Add Web Application After a few seconds the message Web Application has been successfully deployed is displayed 4 Click OK The web application appears in the table at the top of the page The information in each column is described below NOTE To update a web application select Remove Leave data in the Commands column for that application follow steps 4 through 6 above then restart the WebCTRL Server Column Webapp Path Running Sessions Commands Webapp Data Directory Webapp Directory Notes To open the web application in a web browser append this path to your WebCTRL system s address For example to start Tenant Billing enter http lt system_name gt override or http system IP address override Shows the status of the web application This column must show running for you to open the web application in a browser Shows the number of web browsers that are currently connected to the web application Use these commands to stop or start the application remove the application and its data or remove just the application NOTE If you click one of the Remove commands you must follow the procedure above to deploy the applicati
131. for these occupied unoccupied zones so that equipment runs only as needed to reduce energy consumption but not comfort Other zones like computer server rooms and production floors must maintain particular cooling and heating setpoints 24 hours a day 7 days a week Schedules would have no cost saving effect on them Use one of the other cost saving strategies to reduce energy consumption and equipment repairs for these kinds of zones You can realize the greatest savings by using Schedules Then fine tune Optimal Start Demand Control and Setpoint Optimization Each strategy depends on a particular microblock Microblock Strategy Description Schedules Define when a building or zone is occupied and see page 55 whether or not equipment should run depending on the occupied setpoints Optimal Start Ensures that a zone s ideal comfort range is reached see page 49 just as the zone becomes occupied Demand Control Relaxes heating or cooling setpoints when a certain see page 52 level of energy use is reached in order to avoid peak demand ratchet or time of use electric charges Setpoint Optimization Calculates a piece of equipment s setpoint based on Trim and Respond the number of heating or cooling requests it receives see page 53 from other equipment 2011 Automated Logic Corporation 137 WebCTRL v5 User Manual 138 2011 Automated Logic Corporation WebCTRL v5 User Manual Advanced topics and features
132. ge your system files residing on a distant WebCTRL server Methods for using WebDAV e A third party WebDAV client application such as WebDrive allows you to open remote files in addition to managing them e Perform remote file management o With Internet Explorer by opening the remote system as a web folder o With Microsoft Windows file explorer by adding a network connection in file explorer NOTE These functions may not be available on all versions or combinations of Windows operating systems or Internet Explorer To use WebDAV with Internet Explorer PREREQUISITES On your client computer you must e Be running WebCTRL v2 0 or later on the WebCTRL server NOTE Your WebCTRL system must be running on the remote server for WebDAV to work you can then access the webroot folder for the system You cannot edit the WebCTRL database when using WebDAV e Onthe WebCTRL Systems Settings page Security tab enable Remote File Management e Have Remote File Management privilege assigned in your privilege set e Have a password for the person logging in the password field cannot be empty 2011 Automated Logic Corporation 151 WebCTRL v5 User Manual To use WebDAV from a client computer 1 2 3 On the Internet Explorer menu bar select File gt Open In the Open dialog box select Open as Web Folder In the Open field type the IP address of your WebCTRL server webdav For example http 172 16 2 163 webdav NOTE On a Window
133. gory in the Category field 4 Click OK Properties pages Properties pages are automatically generated from control programs created in EIKON LogicBuilder Use Properties pages to e View the status of a piece of equipment See Colors and status in WebCTRL page 25 e View or change the equipment or microblock properties currently stored in the controller e Commission equipment To view or edit properties 1 Select a piece of equipment or a microblock on the GEO or NET tree then click Properties NOTE You must resolve any condition described in red text at the top of the page before a Properties page can obtain current information from its controller 2 To change a property Click or to show or hide a section as needed Click microblock name to Select Select item Change open its pop up where you or clear in drop down text in can change properties checkbox list text field 3 Click OK 36 2011 Automated Logic Corporation WebCTRL v5 User Manual NOTES e Right click a value then select Details to view and change properties in the microblock pop up e Right click a value then select Global Modify see page 41 to view and change the property in other control programs e A yellow dashed box around a value indicates the value is locked BBO On Point types A point name on the Properties page is followed by a code that tells you the point type The table below describes each code
134. he column and how you want it to look See table below 15 Optional Use the Add Delete and arrow buttons below the report preview to manipulate the columns 16 Click OK 17 Click Run NOTE Torun this report later go to the location where the report was created Click the Reports button drop down arrow select the report then click Run Type of Column Data Point Trend Sample 118 Displays point data in the column Display Data is named differently in some equipment Point to use Display Data is named differently in some equipment Trend to use Set Time Range Select the property to show in this column Select this checkbox if similar points have different names in different control programs Then add each of the names to the Name to use list For example if a point is named Zone Temp in one control program and Zone Temperature in different control program add both names to the list Select the name of the point to show in the column Select First Minimum Maximum or Last recorded trend value Select this checkbox if similar points have different names in different control programs Then add each of the names to the Name to use list For example if a point is named Zone Temp in one control program and Zone Temperature in different control program add both names to the list Select the name of the point to show in the column Click to have all columns in the report use the same tim
135. he control program in the Geographic tree then select Reload Control Program If you changed a translation file located in WebCTRL webroot lt system_name gt resources right click each applicable graphic in the Geographic tree then select Rebuild Graphic Resources To edit a bundled resource EIKON LogicBuilder bundles embeds the translation file s for a control program into the equipment file See steps 3 through 5 in To create and implement a translation file page 184 To edit a bundled translation file 1 2 3 4 5 6 Open the control program in EIKON LogicBuilder Select Control Program gt Bundled Resources Select the file then click k to save it to your hard drive Edit the translation file In the Bundled Resources dialog box in EIKON LogicBuilder click and select the edited file Click OK to overwrite the existing file Editing an EIKON for WebCTRL control program in EIKON LogicBuilder To edit a non English control program that you created in EIKON for WebCTRL 1 2 3 In EIKON LogicBuilder open the eiw or equipment file then make your edits Select Control Program gt Bundled Resources Verify that the list shows all translation files specifically for the control program Use the plus or minus button to add or delete translation files NOTE This list shows the translation files in the WebCTRL webroot lt system_name gt programs folder This list should not include translation files for multipl
136. hes click OK NOTE Compacting a database may take several minutes to several hours depending on its size 12 Repeat steps 5 10 to compact audit mdb events mdb and trends mdb Defragmenting the server s hard drive For all database types use a defragmentation utility such as Windows Disk Defragmenter or Norton SystemWorks NOTE If you are using a single computer as both the WebCTRL server and the client you must defragment the disk more often than the disk of a dedicated server especially if people access the Internet from this computer To minimize the database size The larger a database is the less responsive it may become Deleting closed alarm incident groups expired schedules and expired historical trends on a regular basis will reduce the database size You can set WebCTRL to automatically delete these See System Settings Scheduled Tasks tab page 164 in WebCTRL Help 208 2011 Automated Logic Corporation A Access database 207 Access User Category privilege 124 action button e 21 action pane e 21 Admin privilege set 124 127 advanced password policy 7 135 160 161 Advanced reporting actions e 82 advanced security 131 135 alarm actions 77 82 101 104 113 alarm categories 110 alarm messages 82 104 110 124 131 157 Alarm Notification Client 7 83 Alarm Popup alarm action 82 83 160 alarm source 101 alarm templates e 104 110 124 131 157 160 alarms e 77 acknowledg
137. ic below e Reload a revised control program located in webroot lt system gt programs In WebCTRL s GEO tree right click the equipment then select Reload NOTE If you change a control program in EIKON LogicBuilder and it does not display correctly in WebCTRL Ctri right click WebCTRL s action pane then select Refresh To select a different control program Right click the equipment on WebCTRL s navigation tree then select Configure 2 If the system has other control programs of this type select which control programs you want to change Change this control program only Change for all control programs of this type on this network only Change for all control programs of this type NOTES o Ifyou are changing an IP router s control program the second option will change all control programs of this type only on the IP network o Ifyou are changing a control program on the network below an IP router the second option will not change control programs of this type in the router 2011 Automated Logic Corporation 171 WebCTRL v5 User Manual 3 Do one of the following If the control program is In the Control Program drop down list Select the control program Click OK Click Add New Browse to select the control program Click Open Click Continue Click Close Click Close again Not in the Control Program drop down list gt e pm TD 4 Download All Content to the controller
138. ients below Browse To Which page you want to see first in WebCTRL when browsing to the equipment Internet Explorer Whether or not browsing to the equipment opens a new browser window Notification e Ifyou want to hear a sound when an alarm occurs Sounds e Which sound you want to hear for each type of alarm NOTE A Connection Failure occurs when the Alarm Notification Client loses communication with WebCTRL Server e Whether you want the sound to continue until silenced NOTE If multiple types of alarms occur simultaneously the application plays the sound of the most critical alarm Connection Failure first then Critical then Normal To set up WebCTRL Server to support Alarm Popup clients 1 On WebCTRL s CFG tree select System Settings 2 Onthe General tab select Enable support for Alarm Popup clients to connect to this server 3 If the server has more than one network interface adapter type in the Restrict to IP Address field the IP address that the Alarm Notification Client application will connect to You must specify the same IP address in the Server field in the WebCTRL Alarm Notification Client 4 Use the default port or specify a different port You must specify the same port in the Port field in the WebCTRL Alarm Notification Client NOTE If the WebCTRL Alarm Notification Client application is not on the local network and will access WebCTRL alarms through a NAT router you must port forward the TCP port you defined in
139. ieved at the beginning of occupancy Learned cooling and The rate in F hr that the zone temperature can change by heating or heating capacity cooling at an outside temperature of 65 F Actual or The actual heating or cooling capacity of the equipment at an outside adjusted capacity temperature of 65 F 2011 Automated Logic Corporation 51 WebCTRL v5 User Manual Demand Control 52 Demand Control is a cost saving strategy that saves energy while maintaining comfort in the following ways e Controlling energy use to avoid peak demand ratchet or time of use utility charges e Maintaining ventilation at relaxed setpoints rather than shutting down equipment as with load shedding or duty cycling Before you can use Demand Control effectively you must e Obtain details regarding past energy usage and peak demand ratchet and time of use charges from your energy provider e Understand the demand profiles of the zones you are controlling Demand Control can be customized at the zone level For example you may relax the setpoints in some zones like break rooms and closets by a few degrees but you may not want to relax setpoints in computer rooms at all Zone Setpoint microblocks that have a Demand input use a demand control strategy to conserve energy by relaxing setpoints as the demand level rises In EIKON LogicBuilder you define the amount that setpoints will be adjusted or relaxed based on the demand level Rel
140. if your system has the optional Advanced Reporting package NOTE The Send E mail alarm action see page 91 can run any WebCTRL report and attach it to the email The Write to File alarm action see page 100 can run any WebCTRL report and save it as a file For both alarm actions the report can be a PDF HTML Excel or CSV file 2011 Automated Logic Corporation 115 WebCTRL v5 User Manual To run a report 1 Select an item on the GEO or NET tree Click the Reports button drop down arrow then select a report On the Options tab define the layout and content of the report NOTES o Changing the size and orientation of the printed page also changes the report layout on the View tab o Tocreate a CSV Comma Separated Values file after you run the report select Support CSV text format See To create a PDF Excel spreadsheet or CSV file page 121 o WebCTRL saves report options for the current operator When that operator logs in again WebCTRL uses the same options Click Run Click PDF if you want to print the report To create an Equipment Summary report 116 An Equipment Summary report can provide the following information for equipment at or below the location where the report is created Color Active alarm Locked values Current value of selected points Effective schedule To create an Equipment Summary report 1 Onthe GEO or NET tree select the location where you want to view the report 2 Click the R
141. in your WebCTRL username then select OK o Tap in your WebCTRL password then select Login 2011 Automated Logic Corporation To navigate the System WebCTRL v5 User Manual Navigating through the WAP interface is the same as navigating through the WebCTRL GEO tree the WAP screen is similar to the WebCTRL navigation pane B A C Technologies ibAtlanta R amp D Facility HOME MENU CLR 1 Dasc Zoer om 5 kc Guno Atlanta R amp D di BAC Technologies c QR Atlanta R amp D Facility Floor 1 amp amp oa conditions amp electric meter 4 electric meter HOME MENU CLR Dasec Soer 5 ac Guno WebCTRL automatically generates default WAP interface pages However you can create custom pages using ViewBuilder for WAP After you log in the first screen shows the system level The name at the top of the screen is the name of the current level To navigate deeper into the system select an item by either pressing its number on the keypad or by scrolling through the list and then selecting OK To navigate to other areas of the system see below Select 1 Menu Navigation Alarms Properties Back Go to Root Logout 2011 Automated Logic Corporation Action Navigate up one level Return to the navigation tree area and equipment level only List the alarms at the current level area and equipment level only Show properties at the point level and show properties at the area and equipme
142. ing 78 alarm actions e 82 archiving deleted alarms 160 164 changing settings e 77 deleting 78 164 sounds for alarms e 130 viewing e 78 arcnet manual command 141 audible sounds for alarms e 130 audit log 7 124 131 135 160 automatic logoff 30 127 160 161 automatically collapse trees 130 autopilot 149 B Back button e 21 backing up database 207 BACnet alarm recipient intance 160 BACnet binding conflicts 160 163 BACnet devices 16 BACnet Discovery e 7 BACnet routers 16 BACnet IP 157 BACview 16 18 BACview files 175 BBMD 44 141 bbmd manual commands 141 binary schedule category e 62 browser e 15 16 27 2011 Automated Logic Corporation WebCTRL v5 User Manual C category 21 124 alarm e 77 78 82 104 110 categories 62 graphic e 33 trend e 72 category privilege 123 124 changing modes e 27 checkurls manual command 141 clipping 157 CMnet equipment 158 colors e 25 colors in WebCTRL 21 25 compact the database 207 comstat 141 control programs 36 39 41 171 controllers 15 27 copy manual command 141 copying a path e 41 cost saving strategies 137 CSV Comma Separated Values e 116 121 custom reports e 41 113 116 117 119 121 122 D database system e 27 back up 207 database type 160 207 defragment e 207 maintenance e 207 minimize size e 208 date format 160 Daylight Saving Time 160 165 167 defragmenti
143. ions Keep the application minimized to the right side of the Windows task bar The window will pop up with a message whenever an alarm occurs Select an alarm message then click B to open a browser window displaying the piece of equipment that generated the alarm A grayed out alarm indicates that it was acknowledged in WebCTRL If the Alarm Notification Client is set up to play a continuous alarm sound you can silence an alarm by clicking Silence by pressing Ctri S or by acknowledging the alarm in WebCTRL Browse to source equipment Alarm message Alarm Notification Client alle Oct 14 2004 7 35 56AM OFF NORMAL Standard Eventi indicates an alarm condition Thu Oct 14 07 36 22 GMT 05 00 2004 Connected to 172 16 6 51 2011 Automated Logic Corporation WebCTRL v5 User Manual Button Notes Opens a browser window that displays the equipment that generated the alarm Copies the selected alarm information to the clipboard E Removes the alarm information from the alarm popup list Removing items from this list has no effect on the alarms list in WebCTRL View information about the server connection We m X On this tab You define Server The WebCTRL server and port and the WebCTRL operator name and Connection password NOTE The default port is TCP 47806 If you change this you must also change the Port field in WebCTRL s System Settings See To set WebCTRL Server to support Alarm Popup cl
144. king statement if an error is found in the data Sub evalTrends e host Range Al Value user Range A2 Value passwd Range A3 Value 3 startDate Format Range A6 Value mm dd yyyy hh mm ss AMPM endDate Format Range A7 Value mm dd yyyy hh mm ss AMPM limitFromStart Range A8 Value MaxRecords Range A9 Value expression Range A5 Value 4 Dim client As MSSOAPLib30 SoapClient30 Set client CreateObject MSSOAP SOAPClient30 URL http amp host amp common webservices Trend wsdl client mssoapinit URL client ConnectorProperty WinHTTPAuthScheme 1 client ConnectorProperty AuthUser user client ConnectorProperty AuthPassword passwd 6 On Error GoTo err Dim resultl As String 2011 Automated Logic Corporation 203 WebCTRL v5 User Manual 7 resultl client getTrendData expression startDate endDate limitFromStart maxRecords Dim i row index size As Integer index 0 Rem results is time value string pairs Rem compute size result is 0 based so add one to UBound to get size size UBound resultl 1 2 For i 1 To size row i 11 Range a amp row resultl index Range b amp row resultl index 1 index index 2 Next GoTo done 8 err Range a10 err Description done End Sub NOTE If you have problems connecting to WebCTRL using Visual Basic add the following line Gl
145. lected privilege sets e A grayed out privilege set with a group name beside it indicates the operator is inheriting that privilege set from the group To delete an operator 1 Onthe CFG tree select Operators 2 Select the operator 3 Click Delete 4 Click OK To add or edit an operator group 1 Onthe CFG tree select Operator Groups 2 Click Add to create a new operator group or select an operator group to edit it 3 Type the Display Name and Reference Name for the operator group 4 Under Members select the operators and or groups that you want to add to the new group 5 Under Privilege Sets select the privilege sets that you want to assign to the new group 6 Click OK TIP WebCTRL has a permanent default group called Everybody that every operator is automatically a member of You can assign privilege sets to this group To delete an operator group 1 Onthe CFG tree select Operator Groups 2 Select the operator group 3 Click Delete 4 Click OK CAUTION When you delete an operator group its individual members lose the privilege sets that were assigned to the group 2011 Automated Logic Corporation 129 WebCTRL v5 User Manual To change My Settings On the My Settings page you can change settings such as your e Password e Viewing preferences e Contact information NOTE The System Administrator can also change these settings on the Operators page To change your settings 1 On the CFG tree select My Settings
146. licts WebCTRL waits two days after a schedule expires to delete it Stores trend data in the WebCTRL database for the time you specify This is a default setting that you can change when you set up trends for an individual point Deletes trend data that has been in the database longer than then time you specified in the previous field 2011 Automated Logic Corporation Field Enable time synchronization of controllers daily at Daylight Saving tab WebCTRL v5 User Manual Notes Automatically synchronizes the time on all equipment to the time on the server adjusting for different time zones and Daylight Saving Time We recommend that you enable this field CAUTIONS To prevent time sync problems when the transition to and from Daylight Saving Time occurs set the time sync to occur at least 1 hour after the last controller in the system is adjusted for DST For example your server and part of your system is in the Eastern Standard Time zone but you also have controllers in the Pacific Time zone Your server is adjusted for DST at 2 00 a m Eastern Standard Time but the controllers in the Pacific Time zone are not adjusted until 3 hours later So you would set the time sync to occur daily at 6 00 a m or later Make sure that your server s time and time zone setting are correct Make sure that each site s time zone setting is correct in SiteBuilder NOTES You can disable this function for an individual site on
147. lowing 3 schedules e Full calendar year Normal Weekly Monday Friday 6am 5pm Summer months Holiday Continuous 12am June 1st 11 59pm August 31st e Work days in summer months Override Dated Weekly Monday Thursday 9 am 2 pm f you do not see one of the types listed above go to CFG Categories Schedule Select the Occupancy category then the Priority Under Schedule Types select the missing type then click OK Using the Priority and Type options you can often accomplish the effective schedule you need in several different ways For example the effective schedule resulting from the 3 schedules described above for Type could also be accomplished with the following schedules School year Normal Dated Weekly Monday Friday September 1st May 31st 6 am 5 pm Summer months Normal Dated Weekly Monday Thursday June 1st August 31st 9 am 2 pm 2011 Automated Logic Corporation 61 WebCTRL v5 User Manual Using schedule categories Occupancy is WebCTRL s only default schedule category Occupancy is a binary schedule category that allows a zone or piece of equipment to be defined as On when a Space is occupied and Off when it is unoccupied You can add custom schedule categories to handle other conditions if the equipment s control program includes a Time Clock microblock For example you can add a multi state schedule category to control lights on during work hours off at night and dim for janitorial
148. ment amounts are defined for thermographic colors in the control program s Zone Setpoint with Learning Adaptive Optimal Start microblock For example the heating capacity for a zone is 5 per hour When the zone becomes occupied the zone temperature is 1 below the occupied setpoint indicating a need for additional heat Because the zone temperature was low by 1 the learned heating capacity will be decreased by the Less than Heating setpoint value If the value is 0 06 the learned heating capacity will be adjusted to 4 94 for the next optimal start period The setpoint adjustment will begin sooner in the next unoccupied period If you need to change the adjustment values in the Learning Adaptive Optimal Start routine 1 Inthe GEO tree select the equipment that you want to change 2 Click Properties 3 Adjust the color fields between the Zone Set Points graph and the Effective Set Points graph CAUTION When using Learning Adaptive Optimal Start be sure that all equipment is properly maintained so that your system doesn t learn to compensate for dirty filters or loose fan belts TIP After your system has run for at least a year you may want to turn off learning in your control program and change the Heating Capacity and Cooling Capacity in your control program to match the learned heating or cooling capacity shown on the Properties page Fields Notes Color fields The amount of adjustment the system makes for the color that is ach
149. n Server 7 29 WebCTRL extensions for FrontPage 183 185 WebCTRL navigation 21 WebCTRL navigation tree e 21 WebCTRL Server e 7 16 27 changing systems e 27 restarting 27 shutting down e 27 starting e 27 WebCTRL Server BACnet device instance e 160 WebCTRL tools e 18 WebDAV 151 161 WebPRTL 16 whoson manual command 141 Windows service e 27 177 Write Property alarm action e 82 Write to Database alarm action e 82 Write to File alarm action e 82 100 Z zones e 31 49 2011 Automated Logic Corporation
150. n arrow then select the trend graph 3 Click the menu button CH then select Delete Using trend graphs In WebCTRL you can view and print trend graphs You can also copy the trend data to a spreadsheet program To view a trend graph 1 Onthe GEO tree select the equipment whose trend s you want to view 2 Click the Trends button drop down arrow then select the graph you want to view 3 Select the View tab NOTES e A large marker indicates a point that is in alarm in fault out of service or has been overridden Ctrl click the marker to view details 2011 Automated Logic Corporation 69 WebCTRL v5 User Manual e A dotted vertical line indicates o Trend Historian has been enabled or disabled o The trend object ID of a third party trend source has been changed For information only you do not need to do anything o Equipment received a time synchronization from its network router or from WebCTRL Ctrl click the line to view the time correction o Trend Log has been enabled or disabled e Ctri click a dotted vertical line to view details Tools for viewing trends 70 Right click anywhere on a trend graph to access most of the tools described below Shortcut Tool Arrow keys Pan Page Down Zoomin Page Up Zoom out Home Zoom to extents End Reset view Esc Undo J Set start date History Only Auto Update M Point Markers Ctrl C Copy data to clipboard Refresh the display gather trend data Dis
151. n drop down menu You can add categories for your custom trend graphs 1 On the CFG tree click the plus sign to the left of the Categories folder then select Trend 2 Click Add or select a category to edit 2011 Automated Logic Corporation 75 WebCTRL v5 User Manual 3 Type the Category Name and Reference Name 4 Select a privilege so that only operators with that privilege can access trends in the category 5 Click OK NOTE To delete a category select the category click Delete then click OK 76 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 8 Alarms Alarm A message sent from an alarm source usually a microblock in a control program to WebCTRL to notify you that certain conditions exist such as a piece of equipment has stopped running or a temperature is too high When WebCTRL receives an alarm it displays information about the alarm on the Alarms page WebCTRL can also perform alarm actions to inform personnel of the condition and to record information about the alarm An alarm source can also send a return to normal message when the alarm condition returns to its normal state Alarm process starts here alarm source West Mn av JOTT Vt Alarm sources and the alarms they generate are assigned to categories such as HVAC Critical or HVAC Maintenance to help you work with related alarms 2011 Automated Logic Corporation 77 WebCTRL v5 User Manual The application enginee
152. n fails WebCTRL receives an alarm for the failed action NOTES e Click View Selected Sources to view or change settings for each alarm e You can display icons and hover text in the GEO tree that show where alarm actions have been created See Tree icons and hover text page 22 To assign an alarm action to a single alarm source 1 Onthe GEO or NET tree select the alarm source microblock 2 Click Alarms then select the Actions tab 3 Click the drop down arrow to select an alarm action then click Add 4 Set up the alarm action by editing the fields on the alarm action page See the appropriate alarm action below for field descriptions 5 Click OK Alarm Popup The Alarm Popup alarm action pops up a message on any computer that is running the WebCTRL Alarm Notification Client application Field Notes To Operator Select individual operators or operator groups who should receive alarm To Group notification Generate alarm if Select this checkbox to send a System Info alarm to WebCTRL Server if the delivery fails popup recipient is not currently running the Alarm Notification Client application Message text Use punctuation spaces or returns after the entries to format the text To add live data to the text select field codes see page 108 from the Append Field Code list Append Field Code Add field codes see page 108 to the message text if desired 2011 Automated Logic Corporation 83 WebCTRL v5 User Manual
153. n from a third party application Description Column Name Data type Alarm generation time EVENT_TIME_ Datestamp Path to the alarm source SOURCE PATH String Example slm m073 Display name path to the alarm source DISPLAY NAME String Example Atlanta Office R amp D Facility Second Floor VAV 2 1 Zone Temp Alarm state EVENT STATE String Example OFF NORMAL LOW LIMIT HIGH LIMIT Alarm text as defined in the Text to write to the RA TEXT String database field on the alarm action page You can add live data to the text by selecting field codes see page 108 from the Append Field Code list Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e If the alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not assign members to it 2 Create a schedule for the group Set the occupied hours to be the same as the w
154. n operator must enter his user name and password This password requirement can be enhanced by using WebCTRL s advanced password policy see page 135 available with the optional Advanced Security package Restricting operator access To restrict access to your system you can Restrict an operator s privileges Use location dependent operator access See page 131 available with the optional Advanced Security package Change a microblock s Editing Privilege from Preset to a specific privilege The microblock s properties will be editable only by an operator that has that privilege CAUTION Each microblock property has a default Editing Privilege represented by the Preset option that is appropriate for that property Changing Preset to a specific privilege changes every property in the microblock to the same privilege which may produce undesirable results 2011 Automated Logic Corporation 123 WebCTRL v5 User Manual Privilege sets A privilege set is a group of one or more privileges see page 124 The Administrator creates privilege sets and assigns them to operators and operator groups Privileges This privilege System Administration Privilege This Access privilege Access Geographic Locations Access Network Items Access Groups Access Config Items Access Alarms Access Logic Pages Access User Category 1 5 This Parameter privilege Edit Setpoint Parameters Edit Setpoint Tuning Parameters Edit
155. n see who downloaded a controller on the Controller Status Report or on the controller s Properties page WebCTRL can now perform a memory download to at least 5 controllers on separate networks simultaneously and schedule downloads to at least 10 controllers on separate networks simultaneously Anew management tool that allows you to View network controller communication status Resolve database controller mismatches View controller information such as model address driver and control program Find ALC devices on a network that are not in your system database Locked values on Graphics and Properties pages have a yellow dashed box around them Trend services have been improved to allow concurrent data collection through multiple BACnet routers N WebCTRL v5 User Manual Feature Controller Status Report see page 113 Tree display options see page 22 Schedule Group folders see page 57 WebCTRL Design Server see page 29 Location Audit Log and System Audit Log reports see page 113 Advanced Password Policy see page 135 System Settings gt Security tab gt Permissions see page 161 System Settings gt Web Applications tab see page 166 Alarm Notification Client see page 83 Edit Setpoint Tuning Parameters privilege see page 124 Remotely change the IP configuration of a BACnet IP controller Disabling Local Access HTTP Proxy and HTTP Tunnel in System Settings Improvemen
156. n select the point graph or custom graph you want to print 3 Select the View tab to display the graph 4 Click the print button Si To transfer trend data to a table format You can copy the trend data currently displayed in the graph and paste it into a spreadsheet application such as Microsoft Excel On the GEO tree select the equipment Click the Trends button drop down arrow then select the point graph or custom graph Select the View tab to display the graph Right click somewhere in the graph then select Copy data to clipboard Click OK ao a Aa oO N Start your spreadsheet program and paste the trend data into your spreadsheet ES Microsoft Excel Baak KI Eje gdt Yew Insert Format Joos Qata Window Dci SR A Ba o Wr 5 F9 X fe A B C D E 1 Time MA Temp RA Temp SA Temp 2 37792 21 62 81 2 54 7 3 37792 21 63 81 3 549 4 3779221 63 815 55 2 37792 22 62 81 2 55 1 B 3779222 53 81 1 548 7379222 64 812 547 7 Convert the trend data in the Time column to a readable date time format using the spreadsheet application s formatting options For example in Microsoft Excel highlight the cells you want to format and choose Format gt Cells On the Number tab choose Time from the Category list and select the type of format you want to see 2011 Automated Logic Corporation 71 WebCTRL v5 User Manual Customizing graph appearance To edit graph properties 72 Each point trend graph has a stan
157. nd Samples report Optional WebCTRL Packag NOTE To see if your system has this optional package click EA then select About You have this package if Enabled Features shows Adv Reporting A Trend Samples report provides trend values for a particular time frame To create an Trend Samples report 1 On the GEO or NET tree select the location where you want to view the report 2 Select the Reports button drop down arrow then select New Report 3 Select Trend Samples 2011 Automated Logic Corporation 119 WebCTRL v5 User Manual 10 11 12 13 14 15 16 17 18 19 Optional Select a Category NOTE The Category drop down list is only visible if you have defined report categories See To organize custom reports page 121 Type a name for the report Click Create On the Design tab click next to Page to verify or change the page size and orientation NOTE Changing the size and orientation of the printed page also changes the report layout on the View tab Click next to Rows Select a Time Range from the drop down list then refine that option by selecting an option from the drop down list s to the right Define the trend data NOTES o Calculate values for missing samples calculates a value based on the two closest values to the time interval o Find the closest sample displays the value closest to the time interval selected Optional Select the Highlight alternate rows checkbox to make the repo
158. ng the database 207 demand control 49 137 Design mode e 27 device ID 163 Devices page e 7 46 dial up connection e 91 disconnect manual command 141 display name e 33 download 7 25 43 46 48 56 124 131 141 157 163 165 171 173 175 download manual commands 141 download options e 44 Downloads page e 7 44 driver e 124 141 165 173 209 WebCTRL v5 User Manual 210 E editing a graphic 34 EIKON LogicBuilder 18 36 39 49 62 77 101 104 141 171 181 energy consumption e 49 137 Equipment Summary report 113 116 Equipment Values report 113 117 error indicator e 21 errors e 25 29 150 event recipient instance 160 extensions for FrontPage 183 185 F Field Assistant 7 13 44 floorplans e 25 font e 72 181 187 G global copy 41 42 65 72 141 global modify 33 36 39 41 110 go manual commands e 141 graphics e 18 22 33 181 attaching graphic files 33 157 category e 35 124 editing 34 size 24 33 Graphics button 33 35 Graphics pages e 31 33 49 H Help button e 21 hierarchical servers e 55 127 131 160 historical trends 65 160 164 208 HTTP 160 index 62 Internet browser e 15 16 27 IP address 141 160 K keyboard shortcuts e 70 157 L labels e 39 language pack 181 languages 130 181 license 167 links e 22 29 33 169 local access port e 7 local privileges 131 134 location dependent operator a
159. ng this alarm action with many alarms Use punctuation spaces or returns after the entries to format the text To add live data to the text select field codes See page 108 from the Append Field Code list Select to write a WebCTRL report to a file then select the Report and the Format NOTE The Report Name field shows a custom report only if it was created at the current system level Run as shows the name and login name of the operator creating the alarm action The report will be run using the privileges and report options of this operator TIP You may want to create a new operator with limited privileges for this purpose 2011 Automated Logic Corporation WebCTRL v5 User Manual Field Notes Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57
160. ngs Enabling support for Alarm Popup clients moved from System Settings gt Other Applications tab to the General tab The permissions granted by the Edit Setpoint Parameters privilege were split between that privilege and the new Edit Setpoint Tuning Parameters privilege You can now change the IP configuration of a device in WebCTRL To limit access to your system you can disable a controller s Local Access port from communicating with WebCTRL Field Assistant or Test and Balance running on a laptop Requires the v4 x driver These options were removed Use Field Assistant instead 2011 Automated Logic Corporation Feature Download Source Files System Settings gt General tab gt Export All Source Files see page 160 BACnet Discovery WAP pages Internet Explorer support Reset to Defaults 64 bit operating system 2011 Automated Logic Corporation WebCTRL v5 User Manual Improvement Available only with a v4 x or later driver If Field Assistant will be used with your WebCTRL system it needs each controller s equipment bacview and driver source files plus any view files marked to be included in download e Select the new Download Source Files option on the controller s Properties page to have WebCTRL download the source files so that Field Assistant can upload them This option depends on the controller s available memory e Do not select this option if you know the controller does not ha
161. not be automatically restored e f you change the policy after you create and assign privilege sets to operators you may need to reconfigure your operators privileges 2011 Automated Logic Corporation 131 WebCTRL v5 User Manual 132 To switch to location dependent operator access 1 On the CFG tree select System Settings 2 Select the Security tab 3 Click Change Policy 4 Follow the on screen instructions Privileges and privilege sets When using location dependent operator access privileges are either system wide or local System wide privileges allow an operator to perform functions throughout the entire system such as accessing the Configuration tree or performing a system shutdown Local privileges allow an operator to perform functions in a specific area of the system such as editing setpoints or viewing alarms Assigning any local privilege to an operator also allows him to change his password and set preferences on the My Settings page on the CFG tree You assign system wide privileges to system wide privilege sets and local privileges to local privilege sets Use the following table in planning which privileges to assign to a privilege set For a description of each privilege see Privileges page 124 System wide privileges Access Groups Access Config Items Maintain System Parameters Maintain Schedule Group Members Maintain Categories Maintain Trends Display and Print Setup Maintain Alarm Tem
162. nt levels if custom pages have been attached Return to the previous page Return to the top of the GEO tree Log out of WebCTRL 155 WebCTRL v5 User Manual To view and edit Alarms ao a fF Ga N Select 1 List 2 Navigation 3 Ack All 4 Del All Closed 5 Del All Select Menu Navigate to the area you want to view alarms for Select Alarms to view all alarms at this area Select an alarm then click OK to view or edit its details Select Actions to view a list of actions for the alarm Select the action to be done then select OK Action List all alarms at the current area or equipment level Return to the navigation tree Acknowledge all alarms at the current level Delete all closed alarms at the current level Delete all alarms at the current level To view and edit equipment properties NOTE If WebCTRL requires reasons for changes to equipment See page 135 you cannot edit equipment properties using WAP 1 Navigate to a point or BACnet object to view 2 Edit any properties in brackets NOTE You may need to scroll down the screen to view them all For example from the BACnet analog input point level you can view the following Select Value Lock At Alarm 156 Action Present value for that point Locked override status for that point True locks the present value to the At value Locked override value Alarm state for that point 2011 Automated Logic Corporation We
163. nt using Field Assistant To download from the Downloads page The Downloads page shows any controllers that WebCTRL marked for download But if needed you can add other controllers to the list To download 1 Onthe NET tree select an item to download controllers at and below that item 2 Click Downloads 3 Click to the left of a Location to see controllers that require a download 44 2011 Automated Logic Corporation WebCTRL v5 User Manual 4 Optional To add controllers to the list a Click Add b Select the controller s NOTE Use Ctrl click or Shift click to select multiple controllers c Select a Download Option see page 44 d Click Add then click Close 5 Select the controllers that you want to download NOTES o Use Ctri click Shift click or the Select All checkbox to select multiple controllers o A network s controllers download in the order shown To change the order select a controller s then drag and drop or click Move to Top or Move to Bottom EXCEPTION If a controller s router requires a download it will download first regardless of it s position on the Download page 6 Click Start NOTES Click Hold to stop pending e downloads Active downloads d cannot be stopped Up to 5 routers can download simultaneously A controller is removed from the list when its download is complete Icons in the Tasks column indicate the following Active WebCTRL is downloading to the controller Pending
164. ntrollers that you moved Download BBMDs to the routers Update the routers BBMD tables See To set up BBMD s using WebCTRL or To set up BBMD s using the BBMD Configuration Tool in WebCTRL Help 159 WebCTRL v5 User Manual System Settings The System Settings page contains information that you must enter before WebCTRL can run properly To access System Settings 1 Onthe CFG tree select System Settings 2 Click each tab then enter the necessary information Tab details are described below General tab The General tab presents the following system information System Directory Name System Date and Time Path to the Web Root Directory Database Type You can edit or use the following fields and buttons Field Notes Time Sync Click to synchronize the time on all controllers in the system to the time on the server Time Format Select one of the following for the system s time e 12 hour clock Example 4 34 pm e 24 hour clock Example 16 34 Date Format Select the format you want the system to use Node Name Display Depth The number of levels displayed in paths in WebCTRL For example if Node Name Display Depth is set at 2 a typical path might be NAHU 1NRA Temp 3 a typical path might be Atlanta R amp D First FloorNAHU 1 NOTE Changing this field does not take effect until you restart WebCTRL Server System Language The language to be used for e The default language for new operators e
165. o Cell B1 Step 2 Create a macro The macro will retrieve the report data and add it to the spreadsheet The following steps correspond to the numbered parts of the code shown below 1 2 o c0 P Name the sub routine TestReport that will retrieve the report Define which spreadsheet cells contain the host WebCTRL server user WebCTRL operator password WebCTRL operator s password Identify the Web services program that allows the Excel spreadsheet to retrieve the report from the WebCTRL server over the network or Internet Enter the code to authenticate the user Enter the error handling code Enter the code to run the report This displays an error checking statement if an error is found in the data 2011 Automated Logic Corporation 205 WebCTRL v5 User Manual Sub TestReport host Range Al Value user Range A2 Value passwd Range A3 Value Dim client As MSSOAPLib30 SoapClient30 Set client CreateObject MSSOAP SOAPClient30 URL http amp host amp common webservices Report wsdl client mssoapinit URL client ConnectorProperty WinHTTPAuthScheme 1 client ConnectorProperty AuthUser user client ConnectorProperty AuthPassword passwd On Error GoTo err location Range A4 Value report Range A5 Value result client runReport location report csv Range Bl Value result GoTo done errs Range B1 Value err D
166. ock properties ss 41 To use Global Modify 41 To USE Global COPY a E 42 Downloading to controllers 43 Download Options ss 44 To download from the Downloads page 44 To download from a Properties page ss 45 If a controller fails to download 46 2011 Automated Logic Corporation All rights reserved throughout the world Automated Logic Corporation the Automated Logic logo WebCTRL EIKON BACview SuperVision and InterOp are registered trademarks and Alert is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Checking controller status 46 KT 47 To resolve a mismatch wisiscesacecesesacesecesecasesssacesesacesscasacadesesavecesecesssasecasesesacess 48 SEIN oTo TII gece Eeer Ee Eeer 49 To change programmed setpoints 49 WIIEIESrum 49 Demand Control sise 52 Setpoint Optimization 53 Chapter 6 SCheGUleS isciscivscrsasvecssvisesvssvasivcsociciossacvevadcusuavedeieisusssndussoassadeversanvdindeasaavescavisdsedine 55 To view schedules ctscccatcdedecstcvetecstsuktessscavnscsudensedsacesdsdecsusnsusnseetassecustectsdesoniaestslacer tees 56 Setting UP S
167. ols 1 Open WebCTRLx x webroot lt system_name gt system properties in a text editor such as Notepad 2 Inthe line mail transport protocol SMTP delete at the beginning of the line and change SMTP to SMTPS or STARTILS If you make this change while WebCTRL Server is running you must restart it to have the change take effect Before WebCTRL sends an email using SSL WebCTRL requests an SSL certificate from the mailserver If the certificate that WebCTRL receives is in its list of trusted certificates WebCTRL sends the email If the certificate is not in the list WebCTRL generates a system alarm indicating that the email alarm action failed If this occurs you will need to add the mailserver s certificate to WebCTRL s list of trusted certificates 1 Geta copy of the certificate file from the mailserver Ask your Network Administrator for help 2 Putthe file on the WebCTRL server 3 From the WebCTRL server s Start menu select Run 4 Inthe Open field type the following command C WebCTRL lt x x gt java lt operating system gt jre bin keytool exe import trustcacerts alias smtpserver keystore webserver keystores certkeys file lt file path gt replacing lt x x gt with the system s version number operating system with the WebCTRL folder name for the operating system you are running file path with the full path and file name of the certificate file 5 The information for the smtpserver key is displayed and you are
168. on again CAUTIONS If you click Remove All you will lose all data associated with the web application This displays the size and location of the web application data For example the data for Tenant Billing is stored in WebCTRLx x webroot lt system_name gt webapp_data override Shows the location of the installed web application 2011 Automated Logic Corporation WebCTRL v5 User Manual To set up site properties 1 Onthe NET tree select the site 2 Click Properties 3 Configure site properties Field Notes Enable Timesync Daily synchronizes the time in the site s controllers with the server s time adjusting for different time zones and Daylight Saving Time Synchronization occurs each day at the time specified in the field Enable time synchronization of controllers daily at on the System Settings Scheduled Tasks tab see page 164 CAUTION Make sure that your server s time and time zone setting are correct Also make sure that the site s time zone setting is correct in SiteBuilder Group Cache The designated router where colors are cached when peer caching is enabled Controller in SiteBuilder To register your WebCTRL software To register your software you must obtain a registered license from ALC and then apply it in WebCTRL You can apply it when you install WebCTRL or at a later time Go to http accounts automatedlogic com http accounts automatedlogic com Select Support Software Licenses Web
169. on configured on the Alarms gt Actions tab See page 82 View the details of all points Verify that all points have been checked out during commissioning Also create custom lists for other contractors For example create a list of BACnet IDs or Web services links Find all locked points and locked values NOTE Locks in the Airflow microblock are not reported Verify the programming and status of all network points especially useful for commissioning controllers used for third party integration Creates a summary of the information configured on the Trends gt Enable Disable tab See page 65 Discover where your system has parameter mismatches that need to be resolved NOTE You must have the Advanced Security package to run these reports View chronological lists of location based changes the operators that made them and the reasons for the changes This report includes changes such as property edits downloads driver changes and view changes View chronological lists of system wide changes the operators that made them and the reasons for the changes This report includes changes such as any change made in the CFG tree login logout and scheduled processes like deleting expired trends Display the thermographic color status and prime variable of each control program Discover network communication problems Shown as purple squares on the report that need troubleshooting The report also shows boot and driver ve
170. on to choose and address microblocks for third party BACnet integration 2011 Automated Logic Corporation WebCTRL v5 User Manual o File Edit Reorder Control Program Options Microblocks Custom Microblocks Favorites Tools Window Help x Jenee KRG Variable Air Volume aan an Date 06 09 PM File Control Program BACnet Objects Help Discovered BACnet Objects Device I Liszt Tuna Ahiact Masco Mint Mocerintion Hhisotmotnes Dien deer blaran Cai OURDE EH ViewBuilder For WAP CES File Edit Insert Configure Help Jw 9 ViewBuilder creating b vav_box view File Edit Configure Tools Window Help ANI Demand Leve SiteBuilder world corporation Not Assigned File Edit Tree View Configure Action Tools Help Jeu gt Location ahu_1 changetree network p GO B Network Cool Source Heat Source Demand Source World Corporation S World Corporation E A Headquarters B E ALC E First Floor Ej S BACnet IP FB au Emm LGR1000 H D Zone 1 Driver H Flow Control E ARCnet 1 SS Zone Temp HK 5E6104a Discharge Temp i8 Driver Damper B anui Damper E Ed 2N551 Cool Request ie Driver iti FFA Zone 1 gt Modified BOO 223 364 2011 Automated Logic Corporation 19 WebCTRL v
171. ontrollers The Status column shows a description of the controller s current state Hold your cursor over that description to see hover text with a more detailed description If multiple conditions exist WebCTRL displays the message with the highest priority The table below shows all possible messages The message color indicates the following Green In process Red An error occurred Blue Requires action from the user Status column message Green messages Downloading Uploading Pending Red messages Connection Error Connection Disabled Out of Service Communications Error Not Uploadable Download Failed Error Hover text message The controller is downloading communications may be disabled The controller is uploading communications may be disabled This controller is waiting to be processed The connection for this controller failed to start The connection for this controller has been disabled This controller is out of service Cannot communicate with this controller This controller is not configured for content upload Message depends on the cause of the failure An unknown error has occurred 2011 Automated Logic Corporation Notes Occurs if the connection is misconfigured or failed to start Occurs if someone stopped the connection This includes stopping a connection using the No Connect connection or running WebCTRL Design Server The controller
172. or Bi Third Floor Bi Fourth Floor Bj Roof Chiller LZ Boiler 02 Conditions H fl Electric Meter F3 f Environmental Index 9 15 4m 9 30 AM 9 45 AM 10 00 AM 2011 Automated Logic Corporation 15 WebCTRL v5 User Manual A typical WebCTRL system 16 WebCTRL uses a network of microprocessor based controllers to control heating air conditioning lighting and other facility systems A web based server communicates with these controllers and generates web pages that the user can access through Internet Explorer WebCTRL allows you to gather information change operating properties run reports and perform other building management functions on a single building an entire campus or a network of facilities that stretch around the globe A typical WebCTRL system may include WebCTRL clients WebCTRL access WebCTRL Server as a website Server using ard web browser such runs WebCTRL as Internet Explorer Server application Web services ows other Protocols ALC Legacy and trend data from on licensing WML WAP Ethernet TCP 1P 4 LGR router roule mmunications Detwe BACnet E networks ARCNET156K baud AAR routes communications between ARCNET networks 4 ME LGR communicates ff with non BACnet systems and ZN line LN I devices routes 4 ME line multi I equipment E controller e communications SE line
173. or each additional language the system will display System language The system language is used for The default language for new operators Alarms sent to the database State text and object names downloaded to the field The default login page All other information is displayed in the operator s language which may be different than the system language See Setting an operator s language in WebCTRL page 188 You can change the language shown on WebCTRL s login page by selecting a different language from the list below the Password field To set an operator s language in WebCTRL An operator can change their language preference in WebCTRL 1 2 3 188 On the CFG tree select My Settings Under Preferences select the Language in the drop down list Click OK 2011 Automated Logic Corporation WebCTRL v5 User Manual Editing translation files control programs or graphics for a non English system If you add or edit a key term in a control program or graphic be sure to make the same change in the translation file See Creating control programs and translation files page 183 If you make changes after attaching a control program or graphic in SiteBuilder do one of the following If you changed text only in a control program or its translation file right click the control program in the Geographic tree then select Rebuild Equipment Pages If you changed logic in the control program right click t
174. ork hours 3 Create the alarm action that you want WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package 2011 Automated Logic Corporation 97 WebCTRL v5 User Manual 98 NOTES e To keep the database table from growing too large you must delete old entries using a third party database application You cannot view edit or delete entries from WebCTRL e f your system uses an Access or MSDE database you cannot open the database in a third party application while WebCTRL or SiteBuilder is running Writing to a custom database WebCTRL can write alarm information to the following types of custom databases The custom database does not have to be the same type as the WebCTRL database SQL Server MySQL PostgreSQL Oracle You may create a table in an existing third party database or create a new database Using your database management tool create a table in your custom database that includes fields for each alarm field code to be written to the table Each field length in the table should be as long as the longest value to be written to that field To set up WebCTRL to write to a custom database instead of the WebCTRL alarm database select th
175. ort 1 Onthe GEO or NET tree select the location where you want to view the report 2 Click the Reports button drop down arrow then select New Report 3 Select Equipment Values 4 Optional Select a Category NOTE The Category drop down list is only visible if you have defined report categories See To organize custom reports page 121 Type a name for the report Click Create 7 On the Design tab click next to Page to verify or change the page size and orientation NOTE Changing the size and orientation of the printed page also changes the report layout on the View tab Click next to Rows Do one of the following o Select Show only equipment for specific control programs at or below this location then type the control program names o On the selection tree select the pieces of equipment you want to view in the report Use Ctrl click Shift click or both to select multiple items Then click Add Optional Select the Highlight alternate rows checkbox to make the report easier to analyze 10 Click Next or next to Columns 11 Verify or change the report Title Page units of measure for defining column widths and Outer border characteristics 2011 Automated Logic Corporation 117 WebCTRL v5 User Manual 12 Select a column in the report preview NOTE The selected column is light purple 13 Under Column Header define how you want the column header to look 14 Under Column Data define the data you want in t
176. ou made on the driver pages in WebCTRL remain in effect After you make these changes you must download All Content to the affected controller s see page 43 NOTE You can also make these changes in SiteBuilder See To change or upgrade a driver in SiteBuilder Help To change or upgrade a driver 1 On WebCTRL s NET tree right click the controller then select Configure 2 If other controllers in the system use this driver select which controllers you want to change This controller only All controllers on this network that use same driver version Al controllers in the system that use same driver version 3 Doone of the following If the driver is In the Driver Version drop down list Not in the Driver Version drop down list 2011 Automated Logic Corporation gt mp oo 79 FT Select the driver Click OK Click Add Browse to select the driver Click Open Click Continue Click Close Click Close again 173 WebCTRL v5 User Manual 4 Download All Content to the controller see page 43 NOTE You can click Delete Unused in the Controller section to delete all unused drivers in WebCTRLx x webroot lt system_name gt drivers 174 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 20 Working with BACview files in WebCTRL To use a BACview to view or edit a controller s property values you must download a bacview file to the controlle
177. ows 7 Vista 2008 and 2008 R2 1 2 3 In the Windows Start menu right click Command Prompt then select Run as administrator Select Yes in the User Account Control message In the Command Prompt window type cd path to the WebCTRL install directory For example type cd c WebCTRL5 2 Press Enter Type WebCTRL Service exe remov Press Enter To determine if WebCTRL Server service is installed If you do not know if the service was previously installed follow the appropriate steps below On Windows 2003 and XP 1 2 From the Windows Start menu open Command Prompt In the Command Prompt window type cd path to the WebCTRL install directory For example type cd c WebCTRL5 2 Press Enter Type WebCTRL Service exe check Press Enter On Windows 7 Vista 2008 and 2008 R2 1 2 In the Windows Start menu right click Command Prompt then select Run as administrator Select Yes in the User Account Control message 2011 Automated Logic Corporation 179 WebCTRL v5 User Manual 3 Inthe Command Prompt window type cd path to the WebCTRL install directory gt For example type cd c WebCTRL5 2 4 Press Enter Type WebCTRL Service exe check Press Enter 180 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 22 Setting up a system for non English languages English is WebCTRL s default language but you can set up your system to displ
178. p localhost logoffuser markdownload commands 2011 Automated Logic Corporation WebCTRL v5 User Manual Description Goes to the point in the system that is referenced For example go oa conditions or go vav 1 m28 Takes you from a piece of equipment on the GEO tree to the same equipment on the NET tree Takes you from a piece of equipment on the NET tree to the same equipment on the GEO tree Takes you to the controller for a point or piece of equipment on the NET tree Takes you to the network the selected object s controller is associated to Goes to the microblock pop up for the microblock that is referenced You must run this command from the microblock s equipment in the navigation tree For example go logicpopup lstat Goes to a device in the NET tree For example to go to device 301205 referenced in a dead module alarm type go 301205 Goes to a device and object in the GEO or NET tree For example go 300550 A1 3 Goes to an object for the current device in the GEO or NET tree For example if a module alarm reports a control program Locked 1 0 Alarm and references an error in program 11 click the link to go to the device then go to the object by typing go PRG 11 site gateway controller program Goes to the item that the s g m p address references Use this command for legacy equipment only For example go 2 1 4 1 Shows the IP address of the WebCTRL server Logs off
179. page NOTE Equipment operates using effective setpoints e Check hysteresis e Check Demand Level e Check Optimal Start e Check Timed Local Override TLO e Check Setpoint Adjust Usually gaps result if network communication was disrupted or a point was temporarily disabled If the gap is not the result of interrupted communication send reports more frequently Open the trend microblock that displayed the gap in data then decrease the notification threshold so that it is approximately 4096 of the buffer size allocated memory size for that microblock Locate the microblock on the Logic page If the color square on the microblock is black the alarm is disabled To enable it 1 Click the microblock 2 Inthe microblock pop up click the Alarms button 3 On the Enable Disable tab select Potential alarm source The On Off Auto OOA switch on the controller for that equipment may be locked in the On Hand position Calibrate the sensor Check to see if the output point is locked on 2011 Automated Logic Corporation WebCTRL v5 User Manual Changing multiple microblock properties Two WebCTRL features Global Modify and Global Copy allow you to view and change multiple microblock properties at the same time TIP Click ES to copy a microblock s reference path to the clipboard so you can paste it into another field or application To use Global Modify Use the Global Modify feature to View a microblock s f
180. pen Regional and Language Options then select the Input language 3 Install an Input Method Editor IME for non alphanumeric characters To view of change the languages and methods you can use to enter Select one of the installed input languages to use when you start your computer English United States US r Installed services Select the services that you want for each input language shown in the Est Use the Add and Remove buttons to modify this list EN English United States amp Handwriting Recognition Drawing Pad White Anywhere Willing Pad a Handwntng recognition Speech See your operating system s Help for more information 182 2011 Automated Logic Corporation WebCTRL v5 User Manual Creating control programs and translation files for a non English system To have WebCTRL display a control program s user defined text such as microblock names and property text in a non English language you must 1 Create the control program using key terms instead of the text 2 Create translation files of key terms and their language specific equivalents In WebCTRL the key term is replaced with its equivalent in the translation file for the current operator language If a WebCTRL Properties page Logic page or graphic shows key term the key term is missing from the translation file NOTES e You also use key terms and translation files with graphics that you cre
181. plates Acknowledge Non Critical Alarms Acknowledge Critical Alarms Force Normal Non Critical Alarms Force Normal Critical Alarms Delete Non Critical Alarms Delete Critical Alarms Execute Audit Log Report Download Controllers System Shutdown Engineer System Access Commissioning Tools Maintain Graphs and Reports Maintain Connections Remote File Management Remote Data Access SOAP Do not audit changes made using SOAP Web services Manual Commands Console Operations Manual Commands File IO Manual Commands Adv Network Manual Commands Unrestricted NOTES Local privileges Access Geographic Locations Access Network Items Access Alarms Access Logic Pages Access User Category 1 5 Edit Setpoint Parameters Edit Setpoint Tuning Parameters Edit Tuning and Logic Parameters Edit Manual Override Parameters Edit Point Setup Parameters Edit Restricted Parameters Edit Category Assignments Edit History Value Reset Edit Trend Parameters Edit Calibration Parameters Edit Hardware Controller Parameters Edit Critical Configuration Edit Area Name Edit Control Program Name Edit Alarm Configuration InterOp Privilege 1 10 Manage Alarm Messages and Actions Maintain Schedules 2011 Automated Logic Corporation WebCTRL v5 User Manual e For an operator to add edit or delete schedule groups he must have the system wide privilege Maintain Schedule Group Members He must also have the local privileges Access Geogr
182. play a specific sample s data Notes If you display more than one graph panning up and down affects only one graph at a time Panning left to right affects all graphs You can also Alt click and drag inside the graph You can also use the key on the numeric keypad the X key or drag a rectangle around area You can also use the minus key on the numeric keypad or the Z key Shows all the data you have viewed in the current session of a particular trend graph Resets the display to its default setting You can also use the Enter or R key Undo up to 10 changes to your view Enter the date you want the trend to jump to The trend displays the same time range for the new date Press the J key again to hide the date fields Displays only the historical data on the graph The trend graph polls for data every 10 seconds Press U again to stop updating Shows a marker for each data point in the graph Copies only the data from the time range that is currently displayed Click Trends Ctri click a sample to view the point name time and date the sample was read the exact point value and if the point is in alarm is in fault out of service or has been overridden Click anywhere to clear the details 2011 Automated Logic Corporation WebCTRL v5 User Manual To print a trend graph 1 On the GEO tree select the equipment that has the trend s you want to print 2 Click the Trends button drop down arrow the
183. r The bacview file is typically defined in SiteBuilder and downloaded with the initial download to the controller but you can select a different file in WebCTRL To select a different bacview file On WebCTRL s NET tree right click the controller then select Configure 2 If other controllers in the system use this bacview file select which controllers you want to change re This controller only Allcontrollers on this network that use same bacview version Al controllers in the system that use same bacview version 3 Do one ofthe following If the bacview file is Select the file Click OK Click Add Browse to select the bacview file Click Open Click Continue Click Close Click Close again In the BACview file drop down list Not in the BACview file drop down list D Q 9 CG DC 4 Download All Content to the controller see page 43 NOTE You can click Delete Unused in the Bacview section to delete all unused BACview files in e WebCTRLx x webroot lt system_name gt views e WebCTRLx x webroot lt system_name gt programs 2011 Automated Logic Corporation 175 WebCTRL v5 User Manual To edit a bacview file on a WebCTRL client On a WebCTRL client you can get a copy of a bacview file from the server edit it then put it back on the server To get the bacview file On WebCTRL s NET tree right click the controller that uses the bacview file then select Configure Unde
184. r BACview click Edit Click Save Browse to the folder you want to put the file in Click Save Click Close Click Close again Oo oO 5 ND a To put the edited file back on the server On WebCTRL s NET tree right click the controller that uses the bacview file then select Configure Under BACview click Add Browse to select the bacview file Click Open Click Continue Click Close Click Close again zl OO Oo DN a 176 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 21 Running WebCTRL Server as a Windows service Run WebCTRL Server as a Windows service if you want WebCTRL Server to automatically start up when the server computer is restarted NOTE If your WebCTRL system uses a non MS Access database located on the same computer as WebCTRL Server you must set up Windows to delay starting WebCTRL Server until the database service has started See Microsoft s How to delay loading of specific services http support microsoft com kb 193888 To install WebCTRL Server service NOTE If you think the service was previously installed see To determine if WebCTRL Server service is installed page 179 On Windows 2003 and XP 1 Click the Windows Start button then click Run 2 Browse to the WebCTRLx x folder select WebCTRL Service exe the service install file then click Open 3 Click OK On Windows 7 Vista 2008 and 2008 R2 1 2 3 In the Windows Start menu
185. r on the Downloads page then click Start Checking controller status On WebCTRL s NET tree you can select a network router site or the system and then click the Devices button to View the status of controllers see page 47 View controller information such as address model driver and view files included in download Download or upload to resolve a mismatch see page 48 Troubleshoot network communication Download or upload files for Field Assistant NOTES 46 Use Ctrl click Shift click or the Select All checkbox to select multiple controllers Click Hold to stop pending eo downloads or uploads Active downloads amp or uploads i cannot be stopped Icons in the Tasks column indicate the following d Active WebCTRL is downloading to the controller d Active WebCTRL is uploading from the controller e Pending You initiated the download and the controller is waiting for its turn to download Failed The download failed See f a controller fails to download page 46 y On Hold Indicates you clicked Hold to stop a pending e download Click o in the upper left hand corner to view a log of activity on the Devices page in the current session Copy to Clipboard lets you copy the text to paste it into another application 2011 Automated Logic Corporation Status messages WebCTRL v5 User Manual In WebCTRL s NET tree you can select a router network site or the system to view the status of c
186. r usually sets up alarm sources in EIKON LogicBuilder In WebCTRL you e View acknowledge and delete alarms received by WebCTRL see page 78 e Set up the alarm actions that WebCTRL performs see page 82 e Edit alarm sources that were set up in EIKON LogicBuilder or set up new alarm sources to generate alarms see page 101 e Customize alarms by changing the category or message see page 104 NOTE Besides the alarms that you set up WebCTRL has built in system and equipment alarms Viewing acknowledging and deleting alarms In WebCTRL you can view acknowledge and delete alarms received by WebCTRL Select an item in the tree to see all alarms at that level and below it Click the system wide alarms button to view all alarms in the system The color of this button signifies one of the following conditions e Red Critical alarms need to be acknowledged e Yellow Non critical alarms need to be acknowledged e Green No alarms need to be acknowledged System wide alarm button ased You must acknowledge alarms that have been set up to require acknowledgement You should delete alarms from your system as WebCTRL closes them because large quantities of stored alarms can reduce the efficiency of your system WebCTRL closes an alarm when all of the following have occurred e You acknowledge the alarm if required e WebCTRL receives a return to normal if required e WebCTRL performs all alarm actions To save alarm informa
187. raphic and select Scale to Fit to see the whole graphic Right click and select Scale to 100 to return the graphic to its original size When using Scale to 100 hold down Ctrl while rolling the mouse wheel to zoom in and out ona graphic To attach a graphic in WebCTRL 1 On WebCTRL s navigation tree right click the item that you want to attach a graphic to then select Configure Equipment graphic only If the system has other control programs of this type select which control programs you want to change Change this control program only Change for all control programs of this type on this network only Change for all control programs of this type 2011 Automated Logic Corporation 33 WebCTRL v5 User Manual NOTES o If the control program is in an IP router the second option will change the graphic for all control programs of this type only on the IP network If the control program is on the network below an IP router the second option will not change the graphic for the router s control programs of this type 3 Do one of the following If the graphic is In the Views Available list Not in the Views Available list NOTES a Select the graphic then click Attach b Click OK a Click Add New b Browse to select the view file c Click Open d Click Continue e Click Close f Click Close again e Select a graphic in the Attached list to edit the graphic s O O Display
188. reason can be used if you need to comply with 21 CFR Part 11 see page 135 2011 Automated Logic Corporation 193 WebCTRL v5 User Manual 194 NOTE Methods b d f and h above process multiple expressions If an expression causes an error only that expression returns an error The remaining expressions are processed as intended e For an expression that gets a value an error is indicated by ERROR error message Correctly processed expressions return a value e Foran expression that sets a value an error is indicated by ERROR Correctly processed expression return OK Trend See Example using Web services to retrieve trend data page 202 WSDL http lt WebCTRL_server gt _common webservices Trend wsdl Method getTrendData String trendLogPath String sTime String eTime boolean limitFromStart int maxRecords Retrieves trend records for a given point or a trend log A series of time value pairs representing trend samples is returned The first element of the array is the time for the first sample second element of the array is the trend data value for the first sample The third element is time for second sample fourth element is trend data value for second sample etc The returned array is in the following format 10 02 2002 10 22 00 AM Time for first sample 76 1 gt Trend data value for first sample 10 02 2002 10 22 30 AM gt Time for second sample 76 1 gt Trend data valu
189. reate a spreadsheet 1 2 Enter the following information the spreadsheet uses to log in to the WebCTRL system o WebCTRL Server IP address or the server network name Cell A1 in this example o Operator name for logging in to WebCTRL Cell A2 in this example o Operator s WebCTRL password Cell A3 in this example Enter the GQL paths to the properties whose values you want to get Cells A5 A6 and A7 NOTE You can use an absolute path such as trees geographic points io points mOO1 or a global reference name O NOO B ON A B 192 168 162 170 administrator abc vavl zone temp present value fvav2 zone temp present value vav3 zone temp present value The macro that will retrieve the values will write them to cells B5 B6 and B7 2011 Automated Logic Corporation 199 WebCTRL v5 User Manual Step 2 Create a macro The macro will read the values from the WebCTRL system and write them to the spreadsheet The following steps correspond to the numbered parts of the code shown below 1 Name the subroutine testSoapRead that will retrieve the values from WebCTRL 2 Define which spreadsheet cells contain the host WebCTRL server user WebCTRL operator password WebCTRL operator s password 3 Identify the Web services program that allows the spreadsheet to access the WebCTRL server over the network or Internet Enter the code to authenticate the user Enter the error handling code Enter the code to allocat
190. rend graph configuration so the graph will be accessible from the Trends button To edit a comparison trend graph 68 1 2 3 4 On the GEO tree select the tree item where the trend was created Click the Trends drop down arrow then select the trend graph Select the Configure tab Follow the instructions below for the edits you want to make To add another graph to a trend graph page 1 2 3 4 Click the Add button below the Graphs list Type a Y axis label Add up to 4 points See below Click OK To add a point to a trend graph 1 2 3 Select the graph in the Graphs list Click the Add button below the Points list Select a point from the Data source tree NOTES o The tree shows only points that have trending enabled See To collect trend data for a point page 65 o Each graph can display up to 4 similar type points all binary or all analog Click OK 2011 Automated Logic Corporation WebCTRL v5 User Manual To delete a point from a trend graph 1 Select the graph in the Graphs list 2 Select the point in the Points list 3 Click the Delete button below the Points list 4 Click OK To delete a graph from a comparison trend graph page 1 Select the graph you want to delete in the Graphs list 2 Click the Delete button below the Graphs list 3 Click OK To delete a comparison trend graph 1 On the GEO tree select the tree item where the trend was created 2 Click the Trends drop dow
191. report 119 To create a PDF Excel spreadsheet or CSV file 121 To edit or delete a custom report 121 T rganizec stom DEES eege ege eege ee 121 To use custom reports from v2 5 or earlier esee 122 Chapter 10 Operator access secci icccecccssccetsncedsnccesccessentecoecssaceveceasscceescassnstensuctesacessaetsvascdeccess 123 NEE 124 ee 124 To add or edit a privilege set 127 To delete a privilege set 127 Operators and operator groups sisi 127 To add or edit an operator 128 To delete an operator 129 To add or edit an operator group 129 To delete an operator group 129 To Change My Settings rerit ierat retener e rire sese cas eres ens 130 Chapter 11 Advanced security 1 2 1eee eene eren e nnne enne n nnne nnne nnnm annn nuam na nnunun 131 Location dependent operator access ss 131 Recording reasons for edits 21 CFR Part 11 135 Advanced password policy 135 Chapter 12 Cost saving strategies nn 137 Advanced topics and features 139 Chapter 13 Manual commands inner 141 Chapter 14 Running WebCTRL s autopilot memes 149 To set up WebCTRL s autopilot ss 149 To run WebCTRL s autopilot ss 150 To run autopilot with Windows Vista ss 150 Chapter 15
192. res of WebCTRL You can Navigate through the GEO tree View and manage Alarms for the current location Receive an e mail alarm message View and edit abbreviated Properties pages for areas and equipment View and edit abbreviated Properties pages for microblocks You cannot View and manage Schedules View and edit items under the CFG tree Configure and view Reports View Graphics pages Send manual commands 2011 Automated Logic Corporation 153 WebCTRL v5 User Manual To dial up a System using WAP Dialing up a WebCTRL system using a WAP device differs from dialing a telephone number Each service has a slightly different method The following method for connecting to a WebCTRL server using WAP is similar to the Sprint PCS Wireless mobile phone process 1 Turn onthe WAP device 2 Select Wireless Web 3 Select Launch Browser 4 Select Menu You can also select WebCTRL bookmark if one has been saved a Select Goto Tap in the WebCTRL IP address for example 192 168 168 1 NOTE If you do not see the WebCTRL login tap in the IP address again and do the following If your WAP device supports append these characters to the end of the address WML browsers t w Applies to most older pre 3G WAP devices XHTMLMP browsers t xmp Applies to most newer 3G WAP devices XHTML browsers t X Atext only interface for PC s or PDA s EXAMPLE 192 168 168 1 t xmp 7 Login to your WebCTRL system o Tap
193. ript ActiveX controls marked safe for scripting gt Enable Tools gt Internet Options gt Advanced tab gt Multimedia section Tools gt Internet Options gt Advanced tab gt Multimedia section Tools gt Internet Options gt Content tab gt AutoComplete gt Settings button View gt Explorer Bar Tools gt Pop up Blocker gt Turn Off Pop Up Blocker Varies View gt Toolbars F11 on your keyboard or use the minimize maximize button in the top right corner of the browser window Start gt Control Panel gt Display gt Settings tab 2011 Automated Logic Corporation WebCTRL v5 User Manual Browser settings Where to change setting Disable navigation sounds Start gt Control Panel gt Sounds and Audio Devices gt Sounds tab Sounds and Audio Devices Properties Ax Volume Sounds Audo Voice Hardware sound scheme is a set of sounds apoled to events in Windows and programs You can select an existing scheme or save one you have modihed Sound scheme v To change sounds click a program event in the following ket and then select sound to apply You can save the changes as new sound scheme Program events E Fax error Fax line tings Fax sent Move Menu Heen o TK WebCTRL cannot function without this setting To run without connecting to the controllers To verify links between graphics and to set up properties schedules alarms and trends before you connect
194. rmat_type1 style format_type2 style EXAMPLE To format the alarm date and time center it and set the field at 20 characters the field code is generation_time D MM dd yyyy hh mm ss C 20 NOTE You must enter the date time or number formatting command before the alignment field width command 2011 Automated Logic Corporation 109 WebCTRL v5 User Manual Field Codes 110 Field Code Name Acknowledge Operator Acknowledge Time Alarm Category Alarm Template Alarm Type Alarm Value Alert Text Character Command Value Dead Band Deletion Operator Deletion Time Device Equipment Error Limit Exceeded Limit Field Code acknowledge_operator acknowledge_time event_category event_template event_type alarm_value alerttext c command value deadband deletion_operator deletion_time device equipment error_limit exceed_limit Description The operator who acknowledged the alarm The time when the operator acknowledged the alarm The alarm category that the alarm is assigned to The alarm template that the alarm is assigned to The alarm type of the alarm source for example CHANGE OF VALUE CHANGE OF STATE The alarm value For a converted SuperVision system if the option Create a single alarm template was selected during upgrade Retrieves alarm message text from cmnet alert text properties To use this field cod
195. rn to Normal Alarm requires acknowledgement Return requires acknowledgement Classified as critical Event State BACnet Configuration Dial on alarm Notification Class WebCTRL v5 User Manual Notes Select to have the alarm source generate a return to normal when the alarm condition returns to a normal state Select to have WebCTRL require that an operator acknowledge the alarm Select to have WebCTRL require that an operator acknowledge the return to normal This property determines the color of the system wide alarm button when the alarm comes in amp Critical Non critical The current state of the alarm source can be Normal value is normal Off normal the value is not normal binary only Fault the alarm source microblock may be misconfigured High Limit the value exceeds the normal range analog only Low Limit the value is below the normal range analog only Select to have this alarm immediately delivered through a modem connection NOTE When monitoring your system through a modem connection non critical alarms are stored in the gateway until one of the following happens e acritical alarm occurs e the gateway is contacted by WebCTRL e the gateway buffer is full at which time all alarms are sent to WebCTRL Do not change this field To set up edit or disable multiple alarm sources simultaneously 1 On the GEO or NET tree area equipment or controller containing the alarm
196. rsion download information and if controller has 4 x or later driver the report shows the serial number and Local Access port status 2011 Automated Logic Corporation WebCTRL v5 User Manual This preconfigured allows you to report Add in reports Install the following 2 reports if you need them 1 On the CFG tree select Reports Administration 2 Click Add browse to WebCTRLx x extras web reports then select a report 3 Click OK Historical Trends Report View historical trend information for the selected GEO tree item including the point that was trended the number of trend samples collected and the date and time of the first and last sample Equipment Sources Report View heat and or cool sources the paths to the equipment and the names of the control programs This custom report allows you to Equipment Summary View the following information for equipment at or below the location where the report was created e Color e Active alarm e Locked values e Current value of selected points e Effective schedule See To create an Equipment Summary report page 116 Equipment Values Compare point information See To create an Equipment Values report page 117 NOTE This report is available only if your system has the optional Advanced Reporting package Trend Samples View trend values for a particular time frame See To create an Trend Samples report page 119 NOTE This report is available only
197. rt and is ramping up to its occupied setpoint in the few hours before occupancy the zone s electric meter is in demand level 2 with relaxed setpoints of 68 and 76 cooling began when the temperature rose above 74 and the temperature has not yet dropped beyond the 1 hysteresis to 73 then you will see yellow green an occupied color green yellow 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 4 Running WebCTRL Server WebCTRL Server accesses and maintains the system database that is viewed and edited from client browsers WebCTRL Server s Current Users Connections and Output tabs allow you to monitor the status of the system Output information is continually archived to WebCTRLx x logs WEBSERVER log To run a system WebCTRL Server must be running before operators can log in from client browsers 1 Select Start gt Programs gt WebCTRL x x gt WebCTRL Server TIP If you use WebCTRL as a Windows service your computer can automatically start WebCTRL Server every time the computer starts See Running WebCTRL as a Windows service page 177 2 Start the Internet browser on one or more client computers 3 Verify that your browser is set up for displaying WebCTRL See To set up a browser to view WebCTRL page 27 4 Typethe WebCTRL server s address in the browser s Address field NOTE You can type http localhost if the WebCTRL Server and browser are running on the sam
198. rt easier to analyze Click Next or next to Columns Verify or change the report Title Page units of measure for defining column widths and Outer border characteristics Select a column in the report preview NOTE The selected column is light purple In the top 2 boxes define the Column Header and the Column Data In the bottom 2 boxes define the appearance of the header and data cells NOTE Select General from the Format drop down list unless you want to define the number of places to the right of the decimal point for the displayed value Optional Use the Add Delete and arrow buttons below the report preview to manipulate the columns Click OK Click Run NOTE To run this report later go to the location where the report was created Click the Reports button drop down arrow select the report then click Run 120 2011 Automated Logic Corporation WebCTRL v5 User Manual To create a PDF Excel spreadsheet or CSV file PREREQUISITE FOR CSV TEXT You must enable Support CSV text format on the Options tab before you run the report 1 Runa report 2 Click PDF Excel or CSV Text 3 For Excel or CSV Text click Open to view the file or Save to save it NOTE If you need a digitally signed PDF to comply with 21 CFR Part 11 open the PDF in a program that supports digital signing such as Adobe Acrobat then sign the PDF WebCTRL does not support digital signing because 21 CFR Part 11 requires that the signature be a
199. s To apply a schedule to equipment 56 Schedules in WebCTRL are typically based on zone occupancy See Using schedule categories page 62 if you want to create a schedule based on conditions other than occupancy 1 Onthe GEO tree select the area or equipment you want to schedule 2 Click Schedules then Configure 3 Click Add 4 Select a Priority A schedule s priority determines whether affected zones will use occupied or unoccupied setpoints Select For Normal A typical occupied period Holiday An unoccupied period that overrides a Normal schedule Override An occupied period that overrides a Holiday schedule 5 Select a Type See table below 2011 Automated Logic Corporation WebCTRL v5 User Manual 6 Type a schedule name in the Description field 7 Enter desired values in the fields below Description 8 On the graph change the schedule s default time segment shown as a colored bar by doing one of the following o Click the segment then type Start and End times in the fields above the segment o Click and drag either end of the segment or the entire segment 9 Optional Click Show Advanced below the schedule bar to add one or more separate segments to the schedule 10 Click OK Type Schedule runs Weekly Every week on the specified days Date On a single specified date Date Range Between two specified dates Date List On multiple specified dates Wildcard According to a repeating pattern For example th
200. s ID Your location in the system does not have to be the controller you are querying For example modstat 8 489202 Displays a Modstat for a specific controller in the system using the controller s MAC address Network number is the number of the network this controller is on as specified in SiteBuilder media type is the type of network the controller is on MAC address can be either the controller address or the IP address and depends on the controller s media type For example modstat mac 48161 arcnet 2 or modstat mac 888 bacnet ip 172 16 101 119 Sends a message to all operators currently logged in to the system For example The server is going to shut down in 5 minutes Please log off To run this command type notify your message The message must use only alphanumeric characters You must have the Admin privilege set or the Engineer System privilege to run this command 2011 Automated Logic Corporation Command paramupload ping rebootserver rebuild reload restartmodule rnet here revert setdefault 2011 Automated Logic Corporation WebCTRL v5 User Manual Description Uploads parameters editable properties to WebCTRL Server from the equipment or driver at the current location and below If you want to upload editable properties for all equipment on a floor navigate to the floor level on the GEO tree If you want to do this for everything under a particular router Such as an navigat
201. s XP machine you may need to include the HTTP port number in your URL For example http 172 16 2 163 80 webdav Type your WebCTRL user name and your password NOTES o The user name must not end with a space when using WebDAV o The password field must contain a valid password must not contain a space and must not be blank Browse to Web Folders to remotely view and manage your WebCTRL files 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 16 Using wireless devices with WebCTRL WebCTRL supports Wireless Application Protocol WAP a communications protocol that allows you to access your system through a wireless device such as a mobile phone WebCTRL supports WAP enabled browsers on 2G and 3G devices on the Sprint PCS network and Pocket Internet Explorer on devices running Windows Mobile for Pocket PC 2003 or later Using a WAP device you can access the Internet and remotely manage certain aspects of your system WebCTRL currently supports only English alphanumeric characters NOTES e Navigation buttons and how the information is presented varies among WAP devices e To use WAP through a Secure Sockets Layer SSL you must use a certificate from a trusted Certificate Authority CA Ask your phone company which Certificate Authorities they support See To set up TLS SSL using a self signed certificate in WebCTRL Help Supported WebCTRL features The WAP interface supports the following featu
202. s jar f1j9 zht jar f1j9swing jar fijtextures jar Then follow the steps below to make the reports appear in the Reports button drop down list To add a new e Spreadsheet report 1 Goto CFG gt Reports Administration and add the report 2 Inthe GEO tree where you want to be able to access the report click the Reports button down arrow then select New Report 3 Select Other then select a report type from that drop down list Name the report then click Create NOTE Report Designer is licensed to Automated Logic Corporation by Actuate Corporation for WebCTRL v2 5 and earlier 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 10 Operator access Privileges control the parts of a WebCTRL system an operator can access Privileges also control what an operator can do and what he can change To set up operator access to your system 1 2 3 Log into WebCTRL as the Administrator See Operators and operator groups page 127 Define privilege sets by job function See Privilege sets page 124 Enter each operator in the system by assigning him privilege sets and entering settings that apply only to him If you need to assign the same privilege set to multiple operators you can create an operator group and assign the privilege set to the group See Operators and operator groups page 127 An operator can change many of his operator settings on the My Settings page See page 130 To access WebCTRL a
203. s the key has a problem such as it does not apply or has expired See the Notes column for an explanation The fields on this tab let you define controller communication with WebCTRL Server and BACnet network communication Field WebCTRL Server BACnet Device Instance and BACnet Alarm Recipient Instance Always upload properties from controllers to WebCTRL server on mismatch Ignore incoming alarms from sources not in this database BACnet Settings Use Static BACnet Bindings 2011 Automated Logic Corporation Notes The BACnet identifier for the system s server and the alarm recipient You enter these system properties in SiteBuilder Automatic uploads are listed in the Audit Log If you do not select this field properties must be manually uploaded or downloaded by the operator when a mismatch occurs NOTE If an automatic upload fails and the operator chooses to do nothing at that time the upload will be attempted again when he returns to the page where he encountered the mismatch WebCTRL Server will ignore alarms from third party devices not in the database or devices from other WebCTRL systems on the same network Native WebCTRL system only If selected WebCTRL uses information in its database to bind to BACnet devices rather than using BACnet s Who Is I Am Who Is Router To l Am Router To broadcasts to resolve BACnet network and 163 WebCTRL v5 User Manual Log BACnet Binding Conflicts Scheduled Ta
204. sers NOTE Restarting WebCTRL Server will remove lockouts A feature of the Advanced Security package that provides additional security See Advanced password policy page 135 If using hierarchical servers WebCTRL automatically synchronizes the operator privilege settings on the child servers with those on the parent server You have the following options e Enable this checkbox on all servers to stop the synchronization process e Enable this checkbox on a child server to remove it from the synchronization process so that you can manage that server s settings locally 2011 Automated Logic Corporation Field Synchronize Now Permissions Communications tab WebCTRL v5 User Manual Notes Click this button on the parent server for immediate synchronization of operator privilege settings When control programs views and bacview files are created by an original equipment manufacturer OEM they cannot be used ina WebCTRL system without the creator s permission However the creator can produce a key for a system with a different license that will grant permission to the key s recipient If you receive a key put it in the WebCTRL X X resources keys folder The table in the Permissions section of the Security page shows all keys in the that folder To activate a key click Add then browse to the key To delete a key from your system select the key in the table then click Delete Red text in the table indicate
205. shows the control program for a piece of equipment WebCTRL updates the live data yellow text every few seconds and whenever you click the Logic button The control program uses exact property values for its calculations but values are rounded to 2 decimal places when displayed on the Logic page TIP Click anywhere on the Logic page then use the Page Up Page Down and arrow keys to scroll through the page NOTE If you find an unexpected value on a Properties page or a Logic page you can use the Logic page to troubleshoot To view a Logic page 1 Select a piece of equipment in the GEO or NET tree 2 Click Logic 3 Click a microblock to view its details To locate a microblock section or label 1 Right click the Logic page then select Jump To 2 Doone of the following o On the Microblock or Section tab select an item to have WebCTRL locate and highlight the item o On the Label tab select a label to have WebCTRL display a reduced logic page outlined in yellow that shows all instances of the label A red box indicates an output label a yellow box indicates an input label Click a red or yellow box to jump to that label in the full size logic page NOTE You can also click a label on the full size logic page to display the reduced logic page To change properties alarms or trends 1 Click a microblock on the equipment s Logic page 2 Inthe microblock pop up click the Properties Alarms or Trends button 3 Change properties
206. sks tab Field Automatically delete alarm incident groups which have been closed for more than ___ days Archive alarm information upon alarm deletion Archive file Archive file format Automatically delete expired schedules daily at Keep historical trends for days Remove expired historical trends daily at device bindings dynamic binding If not selected WebCTRL uses BACnet dynamic binding for communication between devices Leave this field at its default setting unless you are doing one of the following e Select this checkbox if your system uses NAT routing e Clear this checkbox to use BACnet Discovery or for third party BACnet integration When checked WebCTRL logs binding conflicts that result from duplicate network numbers or device IDs Notes Alarm incident groups are all alarm actions such as Off Normal Fault and Return to Normal that are triggered by a single alarm NOTE Alarms in an incident group are not deleted until all alarms in the group have been closed Writes alarm information to a text file The default file is eventdel txt stored in WebCTRL webroot lt system_name gt You can change the file name and include a different path The alarm information to be written to the archive file To add information select field codes in Append Field Code To delete field codes highlight them in the Archive file format box and press Delete To ensure there are no time zone conf
207. sources 2 Click Alarms then select the Enable Disable tab 3 In step 1 select the categories that contain the alarm sources NOTE n step 1 and step 2 Ctrl click Shift click or both to select multiple items or select the Select All checkbox 4 Instep 2 select the alarm sources 5 Make appropriate changes in step 3 6 Click OK NOTE Click View Selected Sources to view or change settings for each alarm 2011 Automated Logic Corporation 103 WebCTRL v5 User Manual To simulate an alarm To test the setup of an alarm source and its alarm actions See page 82 you can simulate an alarm or its return to normal On the GEO tree select the alarm source but not whose alarm you want to simulate Click Alarms then select the Enable Disable tab Select the Enable checkbox next to Alarm or Return to Normal Click Simulate next to Alarm or Return to Normal a fF O N Select the equipment on the tree then select the View tab to see the alarm To view all instances of an alarm source To find all instances of an alarm source at and below a selected area 1 Onthe GEO or NET tree select an area 2 Select the Message Actions Enable Disable or Category tab 3 Select an alarm source from the list in step 2 4 Click View Selected Sources Each path in the dialog box links to the alarm source microblock NOTE You may be able to change settings that relate to the tab you selected Customizing alarms Each
208. ssseseeseeeene enne nnne nnne nnne nennen 25 Colors and setpoints wvissecscecsccsesesesesscessiceasssesecesesesatesnsasesssessseresesecesnsesssnsesnsetesesatesasess 25 Chapter 4 Running WebCTRL Setver 1e eeeeeeeenn eren nn nnn nnn annu nanus annua 27 TO TUNA EE 27 To set up a computer and browser to view WebCTRL csssscesseesesseeseeeseeeeeesneeaes 27 To run without connecting to the controllers eene 29 To switch to a different system 29 To send a message to logged in operators 30 To log off an Operator eene tee eie cete cel 30 To Shut down a SYSTEM rers rotos neonato aito ra ae tna eara kun annsna sinasina anaana 30 Chapter 5 Working with equipment e1e eene eene enne nennen nnn nnn nnn nnne 31 Graphics E F A A titer teer rete enit ee reve rv Re pr rie rien A Te TER EET 33 To attach a graphic in WebCTRL eene 33 To edit a graphic on a WebCTRL client 34 To organize multiple graphics for a tree item eese 35 Null 36 To view or edit properties 36 Point E 37 LOBSICDaBes ini chico Le e Ad I LIED CA 39 To VieW a Logic page oerte eter 39 To locate a microblock section or label 39 To change properties alarms or trends eese 39 Using a Logic page to troubleshoot eene 40 Changing multiple microbl
209. t This report now includes a controller s download information and if the controller has the 4 x or later driver the serial number and Local Access port status You can display icons in the GEO tree to denote locations where items such as schedules or alarm actions were created or assigned You can also turn on hover text so that when you hold the cursor over a system area or equipment icon information about the tree item is displayed You can create folders and sort your groups into them to organize the GRP tree WebCTRL Server no longer has a Normal mode and Design mode WebCTRL Server and WebCTRL Design Server are now 2 separate applications on the Start Menu The Audit Log report is now 2 reports one with location based changes and one with system wide changes The System Settings gt Security tab has 2 new options e Cannot be changed more than once every__ days e Force expiration button When control programs views and bacview files are created by an original equipment manufacturer OEM they cannot be used in a WebCTRL system without the creator s permission However the creator can produce a key for a system with a different license that will grant permission to the key s recipient If you receive a key you can activate it on the System Settings gt Security tab You can deploy a web application from your WebCTRL system It now has a continuous sound and silencing feature You can now lock a client s Setti
210. t 12 00 00 AM will be returned e sTime NULL eTime NULL limitFromStart False maxRecords 10 The most recent 10 records in the database will be returned e sTime 204 07 2007 12 00 00 AM eTime 04 10 2007 11 59 00 PM limitFromStart False maxRecords 0 All records in the database between 04 07 2007 12 00 00 AM and 04 10 2007 11 59 00 PM will be returned 3 Report See Example using Web services to retrieve a report page 205 WSDL http lt WebCTRL_server gt _common webservices Report wsdl Methods a String runReport String location String reportName String extension Runs the named report at the given location and returns the result as a large string with embedded carriage returns b String runReportCsvLines String location String reportName Runs the named report at the given location and returns an array of individual CSV lines The caller must still parse each line 2011 Automated Logic Corporation 195 WebCTRL v5 User Manual Parameters location The location to run the report at in the database reportName The name of a built in report or the reference name of a custom report Built in report names schedule instance effective schedule point list report locked value network io test and balance equipment checkout audit log alarms alarm source network status module version security assignment alarm messages alarm actions trend usage parameter mismatch extension Type of r
211. t WebCTRL to perform during work hours Under Perform Action select If schedule group your new group is Occupied 4 Create the alarm action that you want WebCTRL to perform during after hours Under Perform Action select If schedule group your new group is Unoccupied Available only if you have the Advanced Alarming package e You should not assign this alarm action to frequently occurring alarms as this may cause problems on your network or the Internet e This alarm action uses SMTP TCP Port 25 to send emails To use a different port open WebCTRLx x webroot lt system_name gt system properties in a text editor such as Notepad In the line mail server port 25 delete at the beginning of the line and change 25 to the port you want to use If you make this change while WebCTRL Server is running you must restart it to have the change take effect 2011 Automated Logic Corporation WebCTRL v5 User Manual To secure mailserver communication using Secure Sockets Layer SSL By default the Send E mail alarm action uses the SMTP protocol to send the email as clear text over TCP IP You can switch to one of the following protocols to secure email communication between the WebCTRL server and the mailserver SMTPS Sends email using SSL a communication protocol that provides data encryption STARTTLS Sends email using SSL but does not begin encryption until WebCTRL issues STARTTLS command To use one of these protoc
212. t device router at IP address 154 16 12 101 type bbmd read 154 16 12 101 bbmd update lt network Selects BBMDs on the specified network and marks them for number gt download If no network is entered at the end of the command all networks in the system are scanned For example if the network number is 888 type bbmd update 888 2011 Automated Logic Corporation 141 WebCTRL v5 User Manual Command bbmd view lt network number gt bbmd write lt table file gt lt IP address gt bbmd clear lt IP address gt bbmd dump lt network gt lt file gt checkurls checkurls p checkurls v commstat copy disconnect download commands download m download p download s 142 Description Views the list of BBMDs that have been selected for the network number at the end of the command Assumes the update has been run For example bbmd view 888 Writes the BBMD table into the controller at the given IP address See To set up BBMD s using WebCTRL For example to write the BBMD table in dallasbbmd bdt into the BACnet device router at IP address 154 16 12 101 type bbmd write dallasbbmd bdt 154 16 12 101 Clears the BBMD for the specified controller For example bbmd clear 154 16 12 101 Writes to a file the BBMD from the specified controller For example bbmd dump 888 dallasbbmd bdt 1 Finds all network point exp expressions for the selected item in the GEO or NET tree 2 Converts
213. t or delete kh N Edit the fields you want to change or click Delete 5 Click OK NOTE WebCTRL automatically deletes expired dated schedules from the database at 3 30 AM every day But expired schedules remain in the controller until the next time schedules are downloaded to the controller You can change the deletion time on the Scheduled Tasks tab of the System Settings page see page 160 2011 Automated Logic Corporation 59 WebCTRL v5 User Manual Effective Schedules 60 The effective schedule that you see on the Schedules View tab can be the result of multiple overlapping schedules Schedule created at system level Schedule created at child level Week BAC Technologies Effective schedule Click to see the schedules above that result in the effective schedule The following schedule features can influence an item s effective schedule Feature Description Hierarchy A schedule applied to an item on WebCTRL s tree affects that item and all of its children A child item s effective schedule could be the result of multiple schedules applied at different levels above it To change a child item s effective schedule e Adda schedule at the child that overrides the current schedule See the Priority feature below e Setthe child to ignore the parent schedules To do this select the child item in the tree then go to Schedules Configure Select the schedule click Show Advanced then select Ignore Sched
214. t that requires operators to log changes To set up equipment to require reasons for changes 1 In WebCTRL s GEO or NET tree right click the equipment then select Configure 2 Select the Require operator to record any changes to equipment checkbox 3 Click OK or Apply NOTE You can also turn this setting on in SiteBuilder in the equipment s Properties dialog box To view reasons for changing equipment properties 1 In WebCTRL select a piece of equipment that requires reasons for change 2 Click the Reports button drop down arrow select Security gt Audit Log 3 Onthe Options tab under Display the following columns select the Reason checkbox 4 Click Run Advanced password policy Optional WebCTRL Packag NOTE Tosee if your system has this optional package click Le then select About You have this package if Enabled Features shows Adv Security With the Advanced Security package you can set up a WebCTRL password policy to meet your security needs 1 On the CFG tree select System Settings 2 Select the Security tab 3 Enter information in the fields described below NOTE See System Settings page 160 for information on all the other fields 2011 Automated Logic Corporation 135 WebCTRL v5 User Manual 136 Field Use advanced password policy Passwords must contain Cannot be changed more than once every days May not be reused until different passwords are used Expire after days Force expir
215. tPage 186 Creating a non English system in SiteBuilder eee 187 To set language preferences eseeeeeeeeennnnnnennnnnn 187 To create your system ss 188 SVSLEMMANSUASC RP E ee 188 To set an operators language in WebCTRL eene 188 Editing translation files control programs or graphics for a non English system 189 To edit a bundled resource 189 Editing an EIKON for WebCTRL control program in EIKON LogicBuilder 189 Copying translation files to another system eeeesss 190 Chapter 23 Web EE 191 Using Web services to retrieve or change data 191 WebCTRL privilege requirements 192 WebCTRL data access using SOAP eene 192 Example using Web services to set a value eene 197 Step 1 Create a spreadsheet 197 Step2 reat a MACIO M 197 St p 3 RUM the Macro irri eiecit metres inl rennes nes 199 Example using Web services to retrieve values 199 Step 1 Create a spreadsheet 199 Step2 Create a MAOO EE 200 Step 3 Run the macro EE 201 Example using Web services to retrieve trend data 202 Step 1 Create a spreadsheet eene nnnann 202 Step 2 Create a macro EE 202 Step 3 Run the macro riii ires dE 204 Example using Web services to retrieve a WebCTRL report
216. ted Logic Corporation Feature Edit gt Third Party BACnet Addresses Device Alias microblock and Device Alias field in Display microblocks Mark certain properties as Read only Remove all Property Page Text Keep historical trends for ___ days Use unitary naming Immediate Triggered Write What s new in SiteBuilder Feature Environmental Index source tree Use Server s Time Zone Find feature Replicate feature Synchronize views View Properties Custom source trees 2011 Automated Logic Corporation WebCTRL v5 User Manual Improvement You can edit the addresses that you created with the Third Party BACnet Utility Or you can convert a control program into an integration program by changing 1 0 microblocks to Network or Display microblocks and setting the microblock addresses These allow the use of Network I O and Display microblocks in the same program and efficient re use of programs for multiple instances of third party equipment You can right click some properties in EIKON LogicBuilder and select Make Editable or Make Read Only to determine that property s functionality in WebCTRL You can use this Tools menu add on to remove property page text for all microblocks in a control program You can now define this setting in EIKON LogicBuilder for 1 0 and Log microblocks Previously this was only in WebCTRL You can set your control program to use unitary naming to omit __ at the end of BA
217. tegory instance and tab If the selected tree location differs from the location shown in the action pane for example a point trend page whereami returns information on both locations Use this command when you create links in ViewBuilder Shows the list of users currently logged in to the WebCTRL system the IP addresses from where they are logged on what kind of interface they are using for example Ivl5 for an Internet browser on a computer and how long it has been since they have actively interfaced with the WebCTRL system Restarts the current controller You must have the Manual Commands Adv Network privilege to run this command 147 WebCTRL v5 User Manual 148 2011 Automated Logic Corporation WebCTRL v5 User Manual Chapter 14 Running WebCTRL s autopilot To monitor your WebCTRL system you can run the autopilot to display specified WebCTRL pages at regular intervals You can run the autopilot on the WebCTRL server or on one or more client computers Each computer can display a different set of pages To set up WebCTRL s autopilot 1 Copy the WebCTRLx x autopilot folder from the WebCTRL system to any location on the computer where you will be running the autopilot 2 Ina text editor such as Windows Notepad open the autopilot xml file in the new folder you created in step 1 CAUTION Do not open or edit the original autopilot xml file in the WebCTRL system Keep this file to set up the autopilot on oth
218. the Scheduled Tasks tab in System Settings see page 160 e Also on the Scheduled Tasks tab in System Settings you can set WebCTRL to archive alarm information to a text file as alarms are deleted e An alarm source may be set up to generate an alarm and a return to normal If an alarm occurs but WebCTRL never receives the return to normal you can click Force Normal so that WebCTRL can close the alarm Force Normal has no affect on the alarm condition that generated the alarm 2011 Automated Logic Corporation 81 WebCTRL v5 User Manual To receive audible notification of alarms You can set up WebCTRL to play an audio file on your workstation when it receives a critical or non critical alarm 1 Onthe CFG tree select My Settings 2 On the Settings tab select Non critical alarms or Critical alarms to be notified of each type of alarm 3 In the Sound File field type the path to the sound file When an alarm triggers the audio file to play you can temporarily silence the sound by clicking the menu button Le and selecting Silence The alarm is silenced for a period of about five minutes or until another alarm that triggers a sound is received Setting up alarm actions Alarm Action An action that WebCTRL performs to notify personnel of an alarm or to record information about the alarm You can assign alarm actions to an alarm source a category of alarm sources alarm sources from a certain location or a combination of these
219. the bottom of the Views section click Add New Browse to select the view file Click Open Click Continue Click Close Oo O FB MN 2 Click Close again To organize multiple graphics for a tree item If a single tree item has multiple graphics and you want to change the default graphic that was defined in SiteBuilder display the graphic in WebCTRL then run the setdefault manual command see page 141 In WebCTRL you can create categories and assign graphics to them so that the Graphics button drop down menu has the graphics arranged by category This is typically done in ViewBuilder or SiteBuilder See To define WebCTRL navigation in ViewBuilder Help and To attach graphic files in SiteBuilder Help To add or edit a Graphics category in WebCTRL 1 On WebCTRL s CFG tree click the plus sign to the left of the Categories folder then select Graphic Click Add or select a category to edit Type the Category Name and Reference Name Optional Select a privilege so that only operators with that privilege can access graphics in the category 5 Click OK NOTE To delete a category select the category click Delete then click OK 2011 Automated Logic Corporation 35 WebCTRL v5 User Manual To assign a graphic to a category in WebCTRL 1 On WebCTRL s GEO tree right click the item that the graphic is attached to then select Configure 2 Under Views select the graphic in the Attached list 3 Select the cate
220. the exp expressions to bacnet equivalent expressions that the controllers use 3 Compares the equivalent bacnet expressions to the bacnet expressions currently downloaded in the controllers 4 Displays any mismatches Does the same as checkurls then adds any mismatches to the download queue as parameter downloads Does the same as checkurls but displays the exp and bacnet expressions for all network points that were checked Gives a complete set of diagnostic information for all defined connections as well as information regarding all modems in the system Displays a global copy utility that allows you to selectively copy trend graphs custom reports and all editable properties from the selected equipment to other equipment in the system with the same control program See To use Global Copy page 42 Disconnects you from a BACnet dial up session if you are the last active operator Each of these commands performs an immediate download to a controller for the selected control program device or driver Downloads all content including parameters schedules and BBMDs if applicable Downloads parameters only Downloads schedules only 2011 Automated Logic Corporation Command go commands go lt refname or path gt go net go geo go device go network go logicpopup lt refname gt go lt device ID gt go lt device ID gt lt object ID gt go lt object ID gt go s g m
221. the site s Properties page See To set up site properties You can also perform time synchronizations using the timesync manual command See page 141 On this tab you can adjust the settings for Daylight Saving Time Click Update to automatically set the table s Begin and End dates for the next ten years based on the system s timezone This marks all controllers with ExecB drivers for a Parameters download If the updated dates are incorrect If you clicked Update but the dates are incorrect your system s Java timezone data may be out of date Do the following 1 Goto the Oracle Java SE Download site http java sun com javase downloads Click Continue Restart WebCTRL Server o oco BR o NM 2011 Automated Logic Corporation Download the JDK DST Timezone Update Tool tzupdater zip In WebCTRL go to System Settings gt Daylight Saving then click Import Browse to the tzupdater zip file select it then click Open On the System Settings gt Daylight Saving tab click Update 165 WebCTRL v5 User Manual Web Applications tab Optional WebCTRL Packag NOTE Tosee if your system has this optional package click Es then select About You have this package if Enabled Features shows Enterprise 166 A web application such as Tenant Billing is an application that retrieves and uses data from a WebCTRL system web application is a standard Web Application Archive war file as described in the Java Servl
222. tion before deleting select Alarms gt Reports tab gt Alarms gt click Run button 78 2011 Automated Logic Corporation WebCTRL v5 User Manual To view alarms in WebCTRL 1 Onthe GEO or NET tree select the system level an area or a piece of equipment NOTE The WebCTRL tree is limited to ten levels When an alarm source is deeper than ten levels the alarm is reassigned to the system level 2 Click Alarms then select the View tab 3 Select the alarm categories that you want to view Use Ctri click Shift click or both to select multiple categories or select the Select All checkbox The alarms list displays all alarms received for the selected location and below See table below 4 Double click an alarm to see more information Double click again to hide this information NOTE This information includes a path to the alarm source Each section of the path is a link to that location For example in the path West Wing RTU 1 SSP_LO West Wing links to the West Wing graphic RTU 1 links to the equipment graphic and SSP_LO links to microblock s Properties page Field Notes View By Select one of the following options to sort the alarms list Date Displays all alarms based on the time the alarm was generated with the most recent alarm at the bottom of the list To Do Displays only alarms that are waiting on one or more actions to complete before they are closed Incident Groups the alarms in an alarm incident group with a bracket to
223. to change 2 Click Properties 3 Adjust the following fields located below the setpoint graph Field Heating Capacity Cooling Capacity Heating Design Temp Cooling Design Temp Notes The maximum rate in F hr that the zone temperature could be changed by heating or cooling if the outside temperature were 65 F For example if it takes 2 hours for a zone to warm up from 65 F to 72 F the heating capacity is 3 5 F hr NOTE Use 5 hr as a starting point if you are unsure of actual capacities The most extreme outside winter and summer temperatures at which the equipment must run 100 of the time to maintain the zone temperature at a comfortable level ASHRAE determines design temperatures based on the geographic location of the building NOTE The Zone Setpoint with Learning Adaptive Optimal Start microblock automatically adjusts the heating and cooling capacities to optimize efficiency 50 2011 Automated Logic Corporation WebCTRL v5 User Manual Learning Adaptive Optimal Start If you are using the Learning Adaptive Optimal Start feature and a zone does not reach the ideal temperature range by the time occupancy begins or reaches it too soon then the heating or cooling capacities of the equipment are automatically adjusted up or down for the next unoccupied period When the Learning Adaptive Optimal Start routine runs adjustments are made based on the color that is achieved when occupancy begins Adjust
224. to the network run the WebCTRL Design Server instead of WebCTRL Server Then view WebCTRL in a browser as you would if running WebCTRL Server NOTES e Question marks and purple thermographic color indicates correct microblock paths Missing data or dark yellow thermographic color indicate errors e f your Start Menu does not show the WebCTRL Design Server you are using a Tools Only installation of WebCTRL To switch to a different system Design engineers working on multiple projects can switch systems in WebCTRL Server 1 In WebCTRL Server select Server gt Change Active System 2 Select a different system it must be in the webroot folder and mode 3 Click Select 2011 Automated Logic Corporation 29 WebCTRL v5 User Manual To send a message to logged in operators Notification messages are delivered immediately to WebCTRL client browsers You can send multiple messages but the operator must click Ok for the first message before the next message can be delivered If the browser window is minimized the message is not visible 1 2 3 4 In WebCTRL Server click the Current Users tab Click the Notify button ES beside the user you want to send a message to Or click Notify All Users Type a Notification message Click OK NOTE You can also type notify followed by the message inthe manual command dialog box in WebCTRL to send a message to all logged in operators To log off an operator NOTE The operator will
225. top trend sampling when the maximum number of samples is reached Collects trend data for the specific period of time you define in the time and date fields Archives trend data to the system database Writes all trend data in the controller to the system database without having to enable trend historian Writes all trend data in the controller to the system database each time the controller collects the number of samples that you enter in this field This number must be greater than zero and less than the number entered in the field Allocate memory for samples in the controller The number of trends specified must be accumulated at least once before the historical trends can be viewed Shows the number of samples stored in the controller since data was last written to the database Shows the number of trend samples that were last written to the database This is based on the date that the sample was read Set this field to O to use the system default defined in System Settings see page 160 Deletes all trend samples stored in the database for the item selected in the GEO tree 2011 Automated Logic Corporation WebCTRL v5 User Manual Field Notes BACnet Configuration The Object Name is a unique alphanumeric string that defines the BACnet object Although the Object Name field can be edited it is not recommended The Notification Class is set to 1 to receive alarms generated by ALC controllers NOTES e You can use
226. trollers In WebCTRL e Change or reload a control program e Change or reload a driver e Change a schedule NOTE A schedule change automatically downloads unless you clear its Automatically Download Schedules checkbox on the schedule s Configure tab under Show Advanced e Change a BACview file Select or deselect a view file s Included in download option Add a device Add equipment Change or reload a control program Set an object instance Change or reload a driver Assign or unassign equipment Select or deselect a view file s Included in download option In SiteBuilder WebCTRL automatically marks the affected controllers as requiring a download You can download these controllers from the Downloads page see page 44 or the Properties page see page 45 for the controller the equipment or a microblock When WebCTRL marks a controller for download it determines what information needs to be downloaded based on the type of information that changed See Download Options page 44 NOTES e A property change in WebCTRL is automatically downloaded while WebCTRL is communicating with the controller If the download fails WebCTRL adds the controller to the Downloads page with the reason for the failure e To see who downloaded a controller last go to the NET tree select the controller then do one of the following o Goto Reports Network Controller Status then click Run o View Downloaded by on the Properties page o Click Mod
227. ttern Priority Description Index Color Schedule Types Default Schedule 2011 Automated Logic Corporation WebCTRL v5 User Manual Notes Must be unique in the database be lowercase and not contain any spaces This name must be identical to the name of the custom schedule category that you added in EIKON LogicBuilder The name used in the WebCTRL interface Replace Undefined with one of the following e Boolean binary on off true false condition e Multi State list of integer defined states For example 1 off 2 on 3 dim Displays what schedule value is in effect for times not specified by the schedule To set this value in the Allowed Values table select the value that you want to use as the default then click the Make Default OK button If you selected Boolean above select True Value or False Value If you selected Multi State click the Add Value button to create each schedule state The name used in the WebCTRL interface Type none dark or common lvl5 graphics patterns xxx gif where xxx gif is any gif file in the webroot _common lvi5 graphics patterns folder none dark vert gif The name used in the WebCTRL interface Represents this priority s relative level of importance within this schedule category WebCTRL automatically assigns the priority index which is zero for the first priority level The higher the index value the higher the priority of the schedule type relative to
228. tup of the databases When adding an LX6 controller in SiteBuilder a Panel Properties tab appears where you select the lighting control panel s model Available only with a v4 x or later driver If Field Assistant will be used with your WebCTRL system it needs each controller s equipment bacview and driver source files plus any view files marked to be included in download e Select the new Download Source Files option to have WebCTRL download the source files so that Field Assistant can upload them This option depends on the controller s available memory e Do not select this option if you know the controller does not have enough memory or you want faster uploads in Field Assistant You will need to export the files from SiteBuilder or WebCTRL so that they can be imported into Field Assistant NOTES e You can set this option at the site level so that it is the default for every new controller that you add You can then change the setting for individual controllers e If you select this field but the controller does not have enough memory the download in WebCTRL will fail You can then disable this option on the controller s Properties page in WebCTRL and download again From SiteBuilder or WebCTRL you can export source files to a zip file that can be imported into Field Assistant And you can export source files from Field Assistant and import them into WebCTRL or SiteBuilder SiteBuilder now has the ability to mak
229. tyleS LL WebCTRL v5 User Manual Use the table below to determine the format type and style for a formatting command Q format_type To format a N number To format D date time To set alignment and field width L for left align R for right align C for center align Using multiple formatting commands 2 style The actual formatting such as The basic format uses the pound sign to represent a number See Other numerical formatting System Options http java sun com j2se 1 4 2 docs api java tex t DecimalFormat html The actual formatting such as MM dd yyyy hh mm ss See Date time formatting System Options http java sun com j2se 1 4 2 docs api java tex t SimpleDateFormat html Indicate the field width by number of characters Example To always truncate an alarm value to two digits to the right of the decimal the field code is alarm_valueXN For example 78 9935 becomes 78 99 To show the date and time when an alarm is generated in a format like 03 15 2004 10 50 43 the field code is generation_time D MM dd yyyy hh mm ss To left align the name of the device that generated the alarm and set the field width to 15 characters the field code is device L 15 You can type multiple formatting commands for a field code For example you can format a number and then set the alignment and field width The syntax for multiple formatting commands is fieldcode fo
230. u can add live data to the text by selecting field codes see page 108 from the Append Field Code list o Click the Edit button to edit Message Prefix or Message Details o In the drop down list to the right of Message formation select Add new prefix to beginning of message or Add new details to end of message then click Add Click OK To add a Prefix or Details for multiple alarm sources 1 2 N oOo A In the GEO or NET tree select the area equipment or controller containing the alarm sources Click Alarms then select the Messages tab In step 1 select the categories that contain the alarm sources whose messages you want to edit NOTE In step 1 and step 2 Ctri click Shift click or both to select multiple items or select the Select All checkbox In step 2 select the alarm sources In step 3 select Add new prefix to beginning of message or Add new details to end of message Click Add Type text and add field codes as needed Click OK 2011 Automated Logic Corporation 105 WebCTRL v5 User Manual Alarm categories 106 Alarm categories sort related alarm sources and their alarms into groups such as HVAC Critical and Access Control General Alarm categories let you e View acknowledge or delete selected categories of alarms received by WebCTRL see page 78 e Assign alarm actions see page 82 to selected categories of alarm sources e Set up alarm sources See page 101 in selected categories Each al
231. uch as Windows Notepad open WebCTRLx x webroot lt system gt system properties 7 Atthe end of the file type the following line repactions connection name lt name of connection gt where lt name of connection gt is the ISP name you entered in the wizard in step 2 Open Internet Explorer then select Tools gt Internet Options gt Connections tab If the box under Dial up and Virtual Private Network settings shows more than one connection select the connection that you just created then click Set Default 10 Select Always dial my default connection Send E mail The Send E mail alarm action sends a message to one or more e mail accounts The alarm action can also run a report and attach it to the e mail as a PDF HTML or Excel file Field Notes To Type the address es that you want to send the alarm to To enter multiple addresses type a Space or press Enter after each address From Enter a valid address if required by your mailserver Mail Host The SMTP mailserver s address This can be an IP address or a system name such as mail mycompany com Specify Mail User For Select if your mailserver requires a username and password Mail Host Authentication Send mail as MIME Select if your mailserver allows only MIME attachments attachment Message Text Use punctuation spaces or returns after the entries to format the text To add live data to the text select field codes See page 108 from the Append Field Code list
232. ule Status on the Properties page 2011 Automated Logic Corporation 43 WebCTRL v5 User Manual Download Options When WebCTRL marks a controller for download it determines what information needs to be downloaded based on the type of information that changed Below are the options that can be downloaded This option Downloads All Content Only the executable portion of the driver and control programs The names of all equipment bacview and driver source files The names of any view files that are marked to be included in a download Parameters Schedules NOTE An All Content download also Synchronizes the controller s time to WebCTRL Overwrites trends in the controller Restarts the controller Only Schedules All schedules that are not set for automatic download Only Parameters All editable properties Only BBMDs BBMD tables bdt file that you have updated but have not yet written to the controller NOTES e An All Content download clears trend history and alarm data from the affected controllers At the beginning of the download process trends that have the Trend Historian enabled are saved to the system database e f Field Assistant will be used with your system you can choose to have the All Content option download the full source files instead of only their names In WebCTRL s NET tree select a controller then enable Download Source Files on the Properties page See Commissioning equipme
233. ules above this level You can then add a different schedule for the child tB B A C Technologies Bg Atlanta E A ABC Corporation EY Basement 1801 E Bf First Floor 1801 EBT Second Floor 1801 G Third Floor 1801 B 0 Conditions 1801 LO 3 Electric Meter 1801 BER LMN Corporation EEL XYZ Corporation Description Normal Week Override Hide Advanced Automatically Download Schedules M Ignore Schedules above this level Any schedule change that you make to an item affects it and all of its children 2011 Automated Logic Corporation WebCTRL v5 User Manual Feature Description Priority You must assign one of the following priorities to every schedule Use For Normal Atypical occupied period Holiday An unoccupied period that overrides a Normal schedule Override An occupied period that overrides a Holiday time EXAMPLE For a school you define e Normal schedule that has it occupied every Monday Friday 6 am 5 pm e A Holiday unoccupied schedule for the week of Spring Break e An Override schedule on the first day of Spring Break from 9 am 1 pm for the cafeteria only where a teacher s meeting will be held Type You must assign one of the following types to every schedule Weekly Wildcard Date Continuous Date Range Dated Weekly Date List See To apply a schedule to equipment page 56 for a description of each type EXAMPLE For a school you define the fol
234. ull path control program name and the privileges required to change its properties View or change a single property in several control programs at one time View errors on graphics and Properties pages Browse to any page that displays the property you want to view or change Do one of the following to access Global Modify o Right click the property then select Global Modify o Alt click the property Make changes to the Control Program field if needed NOTES o Use wildcards in the Control Program field to broaden the search For example vav matches vav vavi vavx vav12345 vav z matches vavz vav1z vavxz vav12345z vav 1 2 matches vav12 vavabc1xyz2 vav matches vav141 vav12 vavzz but does not match vav vav1 vav123 matches any control program o Click Show Advanced to view the location value and privileges associated with this property Select the tree item under which you want to search for every occurrence of that microblock in other control programs Click Find All Select the properties in the list that you want to change 2011 Automated Logic Corporation 41 WebCTRL v5 User Manual 7 8 9 Do one of the following o Type a New Value to the right of each selected item a o Type a number in the Set All To field b o Type a number in the Change All By field c If you typed a value in b click Set All To If you typed a value in c click Change AII By Click Apply
235. ur system has this optional package click Le then select About You have this package if Enabled Features shows Adv Alarming The Write Property alarm action writes a specified value to a BACnet property You typically set up 2 alarm actions the first writes a value when the alarm occurs and the other writes a value when the return to normal occurs 2011 Automated Logic Corporation 95 WebCTRL v5 User Manual Field Notes Expression Type the target property s expression Value to Write Type the value you want to write to the microblock property Type 0 or 1 fora binary property Append field code to Select field codes see page 108 to add this information to the Value to value Write field Perform Action By default WebCTRL performs an alarm action when the alarm source generates an alarm and when it returns to normal Under Perform Action you can choose to run the alarm action e Only when the alarm source generates an alarm or when it returns to normal e After a specified amount of time if the alarm has not been acknowledged or has not returned to normal Use this option for alarm escalation e Ifthe alarm occurs during the occupied hours defined for a schedule group or run if the alarm occurs during the unoccupied hours defined for a schedule group EXAMPLE To have WebCTRL perform one alarm action during work hours and a different alarm action after work hours 1 Create a schedule group see page 57 but do not
236. v5 User Manual CAUTIONS e Make a backup of your system before making changes e Make changes carefully as they cannot be undone NOTES e You can also right click items in the Set up Tree dialog box to perform the above tasks e You can perform some of the above actions on multiple tree items simultaneously Use Ctrl click Shift click or both to select multiple items To import a clipping You can export a clipping a portion of a system in SiteBuilder and then import it in WebCTRL The following items are imported e One or more selected Geographic and Network tree items including attached control programs graphics and drivers e Reports e Alarm templates and categories e Location dependent security information e Schedules and schedule group membership including the entire schedule group and schedules if it does not exist in the target system e Alarm actions e Alarm message prefixes and suffixes e Source tree relationships including source tree rules if the source tree does not exist in the target system To import a clipping 1 Right click an item in the GEO tree then select Set up Tree Click the Import clipping button 2 3 Browse to and select the clipping you want to import then click Next 4 Optional If necessary you can change the location path where the clipping will be imported Select the system fragment then select the import location in the tree below Click Next 5 6 If asked if you w
237. ve enough memory or you want faster uploads in Field Assistant You will need to export the files from WebCTRL or SiteBuilder so that they can be imported into Field Assistant NOTES e If you select this field but the controller does not have enough memory the download in WebCTRL will fail You can then disable this option and download again e You can exclude a view file from being downloaded From WebCTRL or SiteBuilder you can export source files to a zip file that can be imported into Field Assistant And you can export source files from Field Assistant and import them into WebCTRL or SiteBuilder This feature is now a page under the Devices button on the NET tree And you can now export the BACnet information to a discovery file that can be opened in the new Third Party BACnet Utility or in EIKON LogicBuilder The default WAP pages generated by WebCTRL have been redesigned to be more useful and easier to navigate WebCTRL now supports IE9 but no longer supports IE6 NOTE If your system has legacy graphics and you are running IE9 you may see a strange font on the graphics pages in WebCTRL To correct upgrade your InterOp graphics in SiteBuilder This will change the font to Courier New This menu option was removed from the right click menu You can use the revert manual command instead WebCTRL has a 64 bit install for large systems that can use the increased capability inherent in a 64 bit operating system However
238. ve Access User Category 1 Access User Lighting Security Graphics The HVAC technicians cannot see the Category 2 category and Lighting Security graphics because they do not Security personnel only have Access User Category 2 2011 Automated Logic Corporation WebCTRL v5 User Manual To add or edit a privilege set 1 Onthe CFG tree select Privilege Sets 2 Click Add to create a new privilege set or select a privilege set to edit 3 Typethe Name and Reference Name for the privilege set 4 Select the checkbox beside each privilege you want to include in the privilege set 5 Click OK CAUTION Include all required access privileges in a privilege set For example if you add Acknowledge Non Critical Alarms to a privilege set also add Access Alarms to that privilege set TIP To create a privilege set that is similar to an existing set select the existing set then click Add The privileges that are initially selected are identical to those of the existing set To delete a privilege set 1 Onthe CFG tree select Privilege Sets 2 Selectthe privilege set to be deleted 3 Click Delete 4 Click OK 5 Click OK again Operators and operator groups The Administrator see Default operators below sets up each operator in WebCTRL by entering the necessary settings and assigning one or more privilege sets to the operator Operator groups give you the ability to assign privilege sets to a group of operators instead of the individual operators
239. vent_categories folder 3 Type common lvl5 graphics event categories file name gt gif in the Icon field 2011 Automated Logic Corporation WebCTRL v5 User Manual If you upgraded alarms from v2 0 or earlier All v2 5 and later alarms use one template called Universal This template lets you define your alarm message text the critical setting and the required acknowledgements at the alarm source in EIKON LogicBuilder or WebCTRL Templates in upgraded systems If you upgraded your system from v2 0 or earlier the alarm sources retained their existing templates and existing alarm settings If the existing alarm sources contain little or no customization to the alarm settings Automated Logic Corporation recommends that you change all of the alarms to use the Universal template If the alarm sources had customized alarm settings continue using the existing templates To assign a different template to alarm sources PREREQUISITE The Alarms Template tab must be visible If it s not on the CFG tree select Privilege Sets then select the Maintain Alarm Templates checkbox 1 Onthe GEO tree select the piece of equipment containing the alarm sources to be changed 2 Click Alarms then select the Template tab 3 Follow the 3 steps on the screen NOTE Use Ctrl click Shift click or both to select multiple items 4 Click Change 5 Click OK TIP To change all alarms in the system simultaneously go to the system level and then select
Download Pdf Manuals
Related Search
Related Contents
Samsung SM-G313HU manual de utilizador Charger Samsung CH-W224 User Manual - Graupner SAARC Advertised Tender Inquiry Document for arbeiten Manual fogões elétricos p embtir 2 placas para site.cdr Copyright © All rights reserved.