1. PENDIX PLC MEMORY In this Appendix DLOS PLC Memoty css n mk RE ER Cabo eee eee ys F 2 Appendix F PLC Memory B DLO5 PLC Memory When designing a PLC application it is important for the PLC user to understand the different types of memory in the PLC The DL05 PLC uses two types of memory RAM and EEPROM RAM is Random Access Memory and EEPROM is Electrically Erasable Programmable Read Only Memory The PLC program is stored in EEPROM and the PLC V memory data is stored in RAM There is also a small range of V memory that can be copied to EEPROM which will be explained later The V memory in RAM can be configured as either retentive or non retentive Retentive memory is memory that is configured by the user to maintain values through a power cycle or a PROGRAM to RUN transition Non retentive memory is memory that is configured by the PLC user to clear data after a power cycle or a PROGRAM to RUN transition The retentive ranges can be configured with either the handheld programmer d using AUX57 or DirectSOFT 5 PLC Setup The contents of RAM memory can be written to and read from for an infinite number of times but RAM requires a power source to maintain the contents of memory The contents of RAM are maintained by the internal power supply 5VDC only while the PLC is powered by an external source normally 120VAC When power to the PLC is turned off the contents of RAM are maintained by a Super Capacitor If the Super
2. Capacitor ever discharges the contents of RAM will be lost The data retention time of the Super Capacitor backed RAM is 3 weeks maximum and 4 1 2 days minimum at 60 C The contents of EEPROM memory can be read an infinite number of times but there is a limit to the number of times it can be written to typical specification is 100 000 writes EEPROM does not require a power source to maintain the memory contents It will retain the contents of memory indefinitely PLC user V memory is stored in both volatile RAM and non volatile EEPROM memory Data being stored in RAM uses V400 V677 V1200 V7377 and V10000 V17777 which is volatile Data stored in EEPROM uses V7400 V7577 and V700 V777 V7600 V7777 and V36000 V37777 are non volatile Data values that must be retained for long periods of time when the PLC is powered off should be stored in EEPROM based V memory Since EEPROM is limited to the number of times it can be written to it is suggested that transitional logic such as a one shot be used to write the data one time instead on each CPU scan Data values that are continually changing or which can be initialized with program logic should be stored in RAM based V memory F 2 l DL05 Micro PLC User Manual 6th Edition Rev C Appendix F PLC Memory ELE MM Non volatile V memory in the DL05 There are 2 types of memory assigned for the non volatile V memory area The
3. y are RAM and flash ROM EEPROM They are sharing the same V memory addresses however you can only use the MOV instruction D2 HPP and DirectSOFT 5 to write data to the flash ROM When you write data to the flash ROM the same data is also written to RAM If you use other instructions you can only write data to RAM When you read data from the non volatile V memory area the data is always read from RAM Writing data Reading data RAM Flash ROM RAM Flash ROM V7400 V7577 V7400 V7577 V7400 V7577 V7400 V7577 ra Other instructions MOV MOV There is no way to read data OUT OUTD D2 HPP D2 HPP from the Flash ROM directly DirectSOFT 5 DirectSOFT 5 After a power cycle the PLC always copies the data in the flash ROM to the RAM If you use the instructions except for the MOV instruction to write data into the non volatile V memory area you only update the data in RAM After a power cycle the PLC copies the previous data from the flash memory to the RAM so you may think the data you changed has disappeared To avoid trouble such as this we recommend that you use the MOV instruction RAM Flash ROM V7400 1111 V7400 1111 LD K2222 OUT V7400 V7400 2222 V7400 1111 Not changed Cycle power Copy V7400 1111 V7400 1111 This appears to be previous data returning DL05 Micro PLC User Manual 6th Edition Rev C F 3

Download Pdf Manuals

image

Related Search

Related Contents

Via Secura 42  4 P. 79~111  防水スマートフォン収納スピーカー    Da-Lite Contour Electrol    SA15-3166 明電小規模監視制御システム ESC    Powermate VPF1080318 Parts list  Controles do usuário  

Copyright © All rights reserved.
Failed to retrieve file