Home

SMC Flex SMC-3 - Selection Guide

image

Contents

1. Rated IP65 Type 4 12 Enclosed Combination IP65 Type 4 12 Enclosed Combination Voltage Controller Current Controllers with Fusible Disconnect Controllers with Circuit Breaker V AC kW 50 Hz Hp 60 Hz Rating A Cat No Cat No 0 37 0 5 5 152H F5FBD 33 153H F5FBD 33 0 55 0 75 5 152H F5FBD 34 153H F5FBD 34 0 75 1 5 152H F5FBD 35 153H F5FBD 35 4 1 1 5 5 152H F5FBD 36 153H F5FBD 36 1 5 2 5 152H F5FBD 37 153H F5FBD 37 2 2 3 5 152H F5FBD 38 153H F5FBD 38 3 7 5 25 152H F25FBD 39 153H F25FBD 39 5 5 7 5 25 152H F25FBD 40 153H F25FBD 40 7 5 10 25 152H F25FBD 41 153H F25FBD 41 11 15 25 152H F25FBD 42 153H F25FBD 42 15 20 43 152H F43FBD 43 153H F25FBD 43 18 5 25 43 152H F43FBD 44 153H F43FBD 44 22 30 43 152H F43FBD 45 153H F43FBD 45 400 460 30 40 60 152H F60FBD 46 153H F60FBD 46 37 50 85 152H F85FBD 47 153H F85FBD 47 45 60 85 152H F85FBD 48 153H F85FBD 48 55 75 108 152H F108FBD 49 153H F108FBD 49 75 100 135 152H F135FBD 50 153H F135FBD 50 90 125 201 152H F201FBD 51 153H F201FBD 51 110 150 201 152H F201FBD 52 153H F201FBD 52 132 200 251 152H F251FBD 54 153H F251FBD 54 160 250 317 152H F317FBD 56 153H F317FBD 56 200 300 361 152H F361FBD 57 153H F361FBD 57 250 350 480 152H F480FBD 58 158H F480FBD 58 250 400 480 152H F480JBD 59 153H F480FBD 59 355 500 625 A 152H F625JBD 61 A 153H F625JBD 6
2. Controller Dimension Dimensions in inches mm Rating A Bulletin With Option Figure No A Width B Height C Depth D Mtg Dim E Mtg Dim F Mtg Dim Non Combination Controller 1 16 406 24 610 10 254 22 5 572 14 5 368 150 6 1 16 406 24 610 10 254 22 5 572 14 5 368 5 43 BP 1 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 150 150B NB NI 1 24 610 30 762 12 305 28 5 724 22 5 572 150 NB 6P_ 1t 30 762 38 965 14 356 36 5 927 28 5 724 150 16 406 24 610 10 254 22 5 572 14 5 368 1 24 610 30 762 12 305 28 5 724 22 5 572 60 BP 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 m 6 1 24 610 30 762 12 305 28 5 724 22 5 572 NB 4 24 610 30 762 12 305 28 5 724 22 5 572 150 150B NI 30 762 38 965 14 356 36 5 927 28 5 724 150 16 406 24 610 10 254 22 5 572 14 5 368 506 4 24 610 30 762 12 305 28 5 724 22 5 572 m BP 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 i50 NB 24 610 30 762 12 305 28 5 724 22 5 572 6 1 24 610 30 762 12 305 28 5 724 22 5 572 150 150B NB NI 6P_ 1t 30 762 38 965 14 356 36 5 927 28 5 724 24 610 30 762 12 305 28 5 724 22 5 572 150 BP 30 762 38 965 14 356 36 5 927 28 5 724 108 NB 1 30 762 38 965 14 356 0 75 19 36 5
3. 1 dn 14 100 Current Starts per Hour Curves SMC 3 Starts per hour 3 37 A 40 C 100 Duty Cycle 10 s 350 No Fan 60 Trip Class 15 1000 t sec Y 140 ia 120 50 m tor 100 40 T s L b p I 30 3 Wd E 60 i i o i amp 20 2 40 i Me NS 20 10 x E TEL 0 0 1 0 5 10 15 20 25 30 35 40 Current A 150 C3 C9 150 C16 C18 150 C25 C30 C037 SMC 3 Starts per hour 108 135 A 40C 100 Duty Cycle 20 sec 350 with standard fan 200 180 i N 160 i E 140 Y Y 120 x 100 DER 80 60 40 20 0 10 20 30 40 50 60 70 80 Current amps Allen Bradley 90 100 110 120 130 140 150 Cold Trip BN 00 1000 Current SMC 3 Starts per hour 3 37 A Trip Class 20 Cold Trip 1000 H Hot Trip 100 nm 10 Ei 1 100 Current 1000 SMC 3 Starts per hour 43 85 A 40C 100 Duty Cycle 20 sec 350 with standard fan 40 C 100 Duty Cycle 10 s 350 with Fan 200 180 1 b v Y i 160 E UN 140 TT X X 120 E g WA T S 100 E N 3 A 80 AX
4. 46 Approx Dimensions 50 Enclosed Options 42 Accessories This catalog is based on the minimum information needed to select an SMC soft starter for applications with low starting torque requirements For product selection involving loads with high starting torque requirements large fan rock crusher chipper etc use of the free tools available from the Rockwell Automation Website is recommended http www ab com industrialcontrols products solid state motor control software Standards Compliance UL 508 CSA C22 2 No 14 EN IEC 60947 1 EN IEC 60947 4 2 Modes of Operation Soft Start Current Limit Start Selectable Kickstart Soft Stop Note For detailed information about the different modes of operation see page 4 Description of Features Electronic Motor Overload Protection The SMC 3 controller incorporates as standard electronic motor overload protection This motor overload protection is accomplished electronically with the use of current transformers on each of the three phases The controller s overload protection is programmable providing the user with flexibility The overload trip class selection consists of either OFF 10 15 or 20 The trip current is easily selected by adjusting the rotary potentiometer to the motor full load current rating Trip reset is selectable to either automatic or manual mode Note Trip rating is 12096 of dial setting Over temperature The SM
5. Surcharge for special voltages up to 20 pcs no surcharge for quantities greater than 20 pcs a www ab com catalogs amp 9 Allen Bradley 43 Publication 150 SGOO9F EN P Bulletin 150 SMC 3 Smart Motor Controllers Typical Wiring Diagrams Two Wire Configuration IEC NEMA r q Li FT gt i 11 1 273 L2 3 H3 H2 L3 5 EUX HA L SMC 3 TC Aere Trans POWER CONNECTIONS xi X2 Pe vals Sound y E1 Power T H3H2 Connections ER E STOP H1 XX H4 a Stop TRANS rato I Xx YY iD T TWO WIRE DEVICE M Two Wire 4 Device y T 85A m DIN diN2 o97 998 013 oddl APARECIA OVLD Fault AUX 1 1 Oai O42 OIN IN2 97 98 13 L SMC 3 Control Terminals 3 Im OVLD FAULT AUX 1 SMC 3 CONTROL TERMINALS i S al Three Wire Configuration IEC NEMA r q 77 SS 1 m lu 1172 Lam a L2 3 T2 4 MTR Lo ll A T3 6 E SMC 3 H3 H2 POWER CONNECTIONS Wed TC Trans X1 X2 Ground O wo iH E1 Power H3 H2 Connections E STOP VOGN TRANS GRD gt 81 E 7 Esp STOP OPTION olo SB EJ Stop Option SB3 EN Start j r
6. A Separate 120V or 240V single phase is required for fan operation 36 www ab com catalogs Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type Controllers For use with Delta Connected Motors Continued Rated Voltage V AC 230 Motor FLA rating should fall within specified current range for unit to operate properly A Separate 120V or 240V single phase is required for fan operation Open Type Motor Current A Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 C3NBD 1 7 5 1 0 25 1 1 1 24V AC DC 150 C3NBR 100 240V AC 50 60 Hz 150 C9NBD 5 1 16 1 1 4 1 45 24V AC DC 150 C9NBR 100 240V AC 50 60 Hz 150 C16NBD 9 1 27 6 2 2 0 5 341 5 24V AC DC 150 C16NBR 100 240V AC 50 60 Hz 150 C19NBD 10 9 32 8 2 2 0 5 3 10 24V AC DC 150 C19NBR 100 240V AC 50 60 Hz 150 C25NBD 14 3 43 4 11 Sia lD 24V AC DC 150 C25NBR 100 240V AC 50 60 Hz 150 C30NBD 17 3 52 4 15 5 15 24V AC DC 150 C30NBR 100 240V AC 50 60 Hz 150 C37NBD 21 64 5 5 18 5 7 5 20 24V AC DC 150 C37NBR 100 240V AC 50 60 Hz 150 C43NBD 25 74 5 5 22 7 5 25 24V AC DC 150 C43NBR 100 240V AC 50 60 Hz 150 C60NBD 34 6 104 7 5 30 15 40 24V AC DC 150 C60NBR 100 240V AC 50 60 Hz 150 C85NBD 50 147
7. 30 762 38 965 14 356 36 5 927 28 5 724 201 PEN 6_ 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 152H 152B 153H 153B BP NB N 36 914 51 1295 14 356 49 5 1257 34 5 876 30 762 38 965 14 356 36 5 927 28 5 724 251 Tu 6_ 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 152H 152B 153H 153B BP NB N 36 914 51 1295 14 356 49 5 1257 34 5 876 36 914 51 1295 14 356 49 5 1257 34 5 876 153H 6_ 4 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 BPNB 36 914 60 1524 14 356 58 5 1486 34 5 876 317 153B 36 914 60 1524 14 356 58 5 1486 34 5 876 38 965 60 1524 17 431 1 75 45 61 69 1567 152H 152B 2 33 88 861 6 38 965 60 1524 17 431 1 75 45 61 69 1567 152H 152B 153B NB NI 3 40 1016 84 2134 18 457 36 914 51 1295 14 356 49 5 1257 34 5 876 153H 6_ i 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 BP 36 914 60 1524 14 356 58 5 1486 34 5 876 361 153B 36 914 60 1524 14 356 58 5 1486 34 5 876 152H 152B 38 965 60 1524 17 431 1 75 45 61 69 1567 2 33 88 861 152H 6 38 965 60 1524 17 431 1 75 45 61 69 1567 152H 152B 153H 153B NB NI 3 40 1016 84 2134 18 457 E j 36 914 51 1295 14 856 49 5 1257 34 5 876 6 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 153H 153B BPNI 1t 36 914 60 1524 14 356 58 5 1486 34 5 876 38 965 60
8. 100 240V AC 50 60 H 150 C60NBD 150 C60FBD 380 400 20 60 30 15 40 Z 415 460 24V AC DC 150 C60NBR 100 240V AC 50 60 Hz 150 C85NBD 150 C85FBD 28 3 85 45 25 60 24V AC DC 150 C85NBR 100 240V AC 50 60 Hz 150 C108NBD 150 C108FBD 27 108 55 50 75 24V AC DCA 150 C108NBR 100 240V AC 50 60 Hz 150 C135NBD 150 C135FBD 34 135 75 60 100 24V AC DCA 150 C135NBR 100 240V AC 50 60 Hz 150 C201NBD 150 C201FBD 67 201 95 110 75 150 24V AC DCA 150 C201NBR 100 240V AC 50 60 Hz 150 C251NBD 150 C251FBD 84 251 95 132 100 200 24V AC DCA 150 C251NBR 100 240V AC 50 60 Hz 150 C317NBD 150 C317FBD 106 317 95 160 125 250 24V AC DCA 150 C317NBR 100 240V AC 50 60 Hz 150 C361NBD 150 C361FBD 120 361 110 200 250 300 24V AC DCA 150 C361NBR 100 240V AC 50 60 Hz 150 C480NBD 150 C480FBD 160 480 160 250 300 400 24V AC DCA 150 C480NBR Motor FLA rating should fall within specified current range for unit to operate properly These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string A Separate 120V or 240V single phase is required for fan operation 34 www ab com catalogs Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed I
9. 100 240V AC 50 60 Hz 150 C3NBD 150 C3FHD UU 24V AC DC 150 C3NBR Ove 100 240V AC 50 60 Hz 150 CONBD 150 C9FHD P diac 24V AC DC 150 C9NBR eae in 100 240V AC 50 60 Hz 150 C16NBD 150 C16FHD 2505 mE 24V AC DC 150 C16NBR 63 46 j 100 240V AC 50 60 Hz 150 C19NBD 150 C25FHD De n 24V AC DC 150 C19NBR 100 240V AC 50 60 Hz 150 C25NBD 150 C25FHD 9 2 25 3 7 5 24V AC DC 150 C25NBR 100 240V AC 50 60 Hz 150 C30NBD 150 C30FHD 10 30 3 7 5 24V AC DC 150 C30NBR 100 240V AC 50 60 Hz 150 C37NBD 150 C37FHD 12 3 37 5 10 24V AC DC 150 C37NBR 100 240V AC 50 60 Hz 150 C43NBD 150 C43FHD 14 3 43 5 10 24V AC DC 150 C43NBR 100 240V AC 50 60 Hz 150 C60NBD 150 C60FHD 20 60 7 5 15 24V AC DC 150 C60NBR 100 240V AC 50 60 Hz 150 C85NBD 150 C85FHD 28 3 85 10 25 24V AC DC 150 C85NBR 100 240V AC 50 60 Hz 150 C108NBD 150 C108FHD 27 108 20 30 24V AC DCA 150 C108NBR 100 240V AC 50 60 Hz 150 C135NBD 150 C135FHD 34 135 25 40 24V AC DCA 150 C135NBR 100 240V AC 50 60 Hz 150 C201NBD 150 C201FHD 67 201 40 60 24V AC DCA 150 C201NBR 100 240V AC 50 60 Hz 150 C251NBD 150 C251FHD 84 251 50 75 24V AC DCA 150 C251NBR 100 240V AC 50 60 Hz 150 C317NBD 150 C317FHD 106 317 60 100 24V AC DCA 150 C317NBR 100 240V AC 50 60 Hz 150
10. Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation technical support for further guidance These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string A Separate 120V or 240V single phase power supply is required for fan operation Line and load termination are provided as standard Available in IP54 Type 12 enclosure only www ab com catalogs 10 Publication 150 SG009F EN P Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 Type 4 12 Controllers For use with Line Connected Motors Continued Enclosures other than those listed are available consult your local Rockwell Automation sales office or Allen Bradley distributor Open Type Line Connected IP65 Type 4 12 Enclosed Rated Voltage Motor Current Max kW Max Hp Motors Non Combination Controllers V AC A t 50 Hz 60 Hz Control Power Cat No Cat No n 3 100 240V AC 50 60 Hz
11. Rated Impulse Voltage 2 5 kV 4 kV Dielectric Withstand 1500V AC 2000V Overvoltage Category Il lb Operating Frequency 50 60 Hz 50 60 Hz Input onstate voltage minimum during start IN1 IN2 85V AC 19 2V DC 19 2V AC Input onstate current IN1 IN2 9 8 mA 120V AC 19 6 mA 240V AC 7 3 mA 24V AC DC Input offstate voltage maximum IN1 IN2 40V AC 17V DC 12V AC Control Circuit Input offstate current input offstate voltage IN1 IN2 10 mA 12 mA 215 mA 6 120V AC 180 mA 240V AC 800 mA 6 24V DC 660 mA O 3 37 A 24V AC 43 85A 200 mA 120V AC 100 mA 240V AC 700 mA 24V AC DC Control Power with Fan during start Fan Power Control Power 108 135 A 20VA 201 251 A OVA 200 mA 120V AC 120 mA 240V AC 600 mA 24V AC DC 317 480 A 60VA Control Power without Fan during start 3 37A 205 mA 6 120V AC 145 mA poires 705 mA 24V DC 580 mA Controller Rating A Steady State Heat Dissipation W Overload Current Range A 3 11 1 8 9 12 3 9 16 14 5 3 16 19 15 6 3 19 25 17 9 2 27 7 30 19 10 30 37 24 12 3 37 WO 43 34 14 3 43 Steady State Heat Dissipation and Overload Current Range 60 50 20 60 85 82 28 3 85 108 62 27 108 135 75 34 135 201 129 67 201 251 147 84 251 317 174 106 317 361 194 120 361 480 239 160 480 Auxiliary Contacts UL CSA NEMA IEC Rated Operational Voltage 250V AC 30V DC 250V 30V DC Rated Insulation Voltage 250V 250V Rated Impulse Voltage 2 5 kV 4kV Dielec
12. 1 NN ie 60 c t Ss U EN 40 e w 20 150 043 5 150 080 SR 1 A 0 l 51 150 085 O 5 10 15 20 25 30 35 40 O 10 20 30 40 50 60 70 80 90 Current A Current amps 150 03 C9 150 015 C19 150 025 C30 C37 SMC 3 Starts per hour 201 480 A 40C 10096 Duty Cycle 20 sec 35096 with standard fan 315 4 150 C201 C251 150 265 a 0 640 215 5 2 165 5 S 415 4 65 NA 15 60 160 260 360 460 Eos Current Amps 150 F135 www ab com catalogs Publication 150 SGOO9F EN P 49 Bulletin 150 SMC 3 Smart Motor Controllers Approximate Dimensions Dimensions in millimeters inches Dimensions are not intended to be used for manufacturing purposes All dimensions are subject to change Open Type H A lt ja G 1 04 1g I Or F mo B E a amp D GS e e el 4 e Y I I Controller Mounting Weight Rating A A B C D E F G Hole Size kg Ibs 11 37 44 8 1 49 64 139 7 5 1 2 100 4 21 64 35 1 3 8 132 5 13 64 46 4 1 81 2 1 16 4 6 0 18 0 86 1 9 43 85 72 2 83 206 8 11 130 5 12 55 2 17 198 7 8 102 4 02 2 1 16 5 3 0 21 2 25 5 0 108 135 196 4 7 74 443 7 17 47 205 2 8 08 166 6 6 56 367 14 45 7 5 0 295 15 33
13. 100 TD ob S co S Coast to Rest g LU eS mn M LM Automatic Zero Time s Speed Shut Off Accu Stopt This option is used in applications requiring controlled position stopping During stopping braking torque is applied to the motor until it reaches preset slow speed 796 or 1596 of rated speed and holds the motor at this speed until a stop command is given Braking torque is then applied until the motor reaches zero speed Braking current and slow speed current are user programmable Slow speed can be programmed for either 796 low or 1596 high 100 3 Braking RO Slow Speed S Slow Speed Braking o Bee L Coas to Rest P SA lt Start gt Run Brake x pee Times s Slow Speed with Brakingt Slow Speed with Braking is used on applications that require slow speed in the forward direction for positioning or alignment and also require braking control to stop Slow speed adjustments are 796 low or 1596 high of rated speed Slow speed acceleration current slow speed running current and braking current are all adjustable 100 5 Braking 3 gt Coast to Rest 7 or 10 o 15 s 7 NC N Slow gt Start Run Stop gt Speed Time s Not intended to be used as an emergency stop Refer to the applicable standards for emergency stop requirements www ab com catalogs Publication 150 SGOO9F EN P Bul
14. 135 90 78 125 24V AC DCA 150 C135NCR 100 240V AC 50 60 Hz 150 C201NCD 150 C201FCD 67 201 75 182 100 200 24V AC DCA 150 C201NCR 100 240V AC 50 60 Hz 150 C251NCD 150 C251FCD 84 251 90 160 125 250 24V AC DCA 150 C251NCR 100 240V AC 50 60 Hz 150 C317NCD 150 C317FCD 106 317 100 200 200 300 24V AC DCA 150 C317NCR 100 240V AC 50 60 Hz 150 C361NCD 150 C361FCD 120 361 132 250 200 350 24V AC DCA 150 C361NCR 100 240V AC 50 60 Hz 150 C480NCD 150 C480FCD 160 480 200 315 250 500 24V AC DCA 150 C480NCR Motor FLA rating should fall within specified current range for unit to operate properly These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to appropriate option code to the catalog string A Separate 120V or 240V single phase is required for fan operation Allen Bradley www ab com catalogs Publication 150 SGOO9F EN P he enclosure add the 35 Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type Controllers For use with Delta Connected Motors Rated Voltage V AC 200 208 Motor FLA rating should fall within specified current range for unit to operate properly Open Type Motor Current A Max kW
15. 200 600V AC 1600V 500V 1600V Operating Freguency 50 60 Hz 50 60 Hz 1 37 A AC 53b 3 5 15 3585 43 60 A AC 53b 4 5 30 1770 Power Circuit mE 85A AC 53b 4 5 30 3570 ndi 108A AC 53b 4 5 30 1770 ategory 135A AC 53b 3 5 30 1770 201 251A AC 53b 3 5 30 1770 317 480 A m AC 53b 3 5 30 1770 Number of Poles Equipment designed for 3 phase only Rated Impulse Voltage 6 kV DV DT Protection 1000V us Overvoltage Category Hi Type 1A SCPD Performance nie High Capacity Time Dela Non Time Delay Thermal Magnetic Circuit Breaker 9 ls CUM y SCPD List Avaliable Fault Fuse Alt Avaliable Fault Breaker A Available pau Mex Fuse A 3 5 kA 12 5 kA 15 70 kA 6 9 5 kA 30 5 kA 30 70 kA 15 16 5 kA 60 5 kA 60 70 kA 30 19 5 kA 70 5 kA 70 70 kA 40 25 5 kA 100 5 kA 100 70 kA 50 30 10 kA 110 10 kA 110 70 kA 60 37 10 kA 125 10 kA 125 70 kA 60 Line Device 43 10 kA 150 10 kA 150 70 kA 90 Operational 60 10 kA 225 10 kA 225 70 kA 125 Current Rating A 85 10 kA 300 10 kA 300 70 kA 175 108 10 kA 400 10 kA 300 70 kA 200 135 10 kA 500 10 kA 400 70 kA 250 201 18 kA 600 18 kA 600 70 kA 350 251 18 kA 700 18 kA 700 70 kA 400 Short Circuit 317 30 kA 800 30 kA 800 69 kA 500 Protection 361 30 kA 1000 30 kA 1000 69 kA 600 480 42 kA 1200 42 kA 1200 69 kA 800 5 1 5 kA 15 5 kA 15 70 kA 10 16 5 kA 60 5 kA 60 70 kA 30 27 6 5 kA 70 5 kA 70 70 kA 60 32 8 5 kA 125 5 kA 125 70 kA 70 43 5 kA 150 5 kA 150 70 kA 90 52 10 kA 200 10 kA 200 70 kA
16. 927 28 5 724 EE 30 762 38 965 14 356 36 5 927 28 5 724 NB NI 36 914 51 1295 14 356 49 5 1257 34 5 876 a 24 610 30 762 12 305 28 5 724 22 5 572 BP 30 762 38 965 14 356 36 5 927 28 5 724 135 150B 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 150 NB 30 762 38 965 14 356 36 5 927 28 5 724 150B NB NI 36 914 51 1295 14 356 49 5 1257 34 5 876 150 30 762 38 965 14 356 36 5 927 28 5 724 201 1 0 75 19 150 150B NB NI BP 6_ 36 914 51 1295 14 356 49 5 1257 34 5 876 150 30 762 38 965 14 356 36 5 927 28 5 724 251 1 0 75 19 150 150B NB NI BP 6_ 36 914 51 1295 14 356 49 5 1257 34 5 876 150 NB NI BP 6_ y 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 150B NB NI BP 6_ 36 914 60 1524 14 356 58 5 1486 34 5 876 36i 150 NB NI BP 6_ 4 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 150B NB NI BP6 36 914 60 1524 14 356 58 5 1486 34 5 876 150 36 914 51 1295 14 356 49 5 1257 34 5 876 480 1 0 75 19 150 150B BPNB NI 36 914 60 1524 14 356 58 5 1486 34 5 876 em 35 889 91 5 2324 20 508 Bus BPNB 60 1524 91 5 2324 20 508 ymn 60 1524 91 5 2324 20 508 NB 90 2286 91 5 2324 20 508 mu 35 889 91 5 2324 20 508 70 BPNB 4 60 1524 91 5 2324 20 508 o m 60 1524 91 5 2324 20 508 NB 90 2286 91 5 2324 20
17. l da Sa dint Sino A 98 A 4 A1 OA2 dt IN2 97 998 13 14 H OVLD Fault AUX 1 OVLD FAULT AUX 1 SMC 3 Control Terminals SMC 3 CONTROL TERMINALS El L J 44 El www ab com catalogs Publication 150 SGO09F EN P Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Typical Wiring Diagrams Isolation Contactor Configuration IEC NEMA IC r 4 Lit Tue L zl L2 3 T2 4 L3 5 T3 6 Loy Ea SMC 3 ol o Power connections Yy Mc s So TC LEP Trans xi x2 A A El z Ground Power i H3 H2 Connections HI H4 NOM E Stop Trans Ground sB1 E rele D xi x2 i E St ii Stop Option Start alo o o o M Li sp E Stop Option p 4 sB3 F KM Start i da das bt ON 997 098 413 T m a dim m E iis 5 O44 OVLD Fault AX OVLD Faul AURA SMC 3 Control Terminals i SMC 3 Control Terminals zl E1 Reversing Configuration Note Minimum Off time equals 1 0 s IEC NEMA re F ES r J AU peti T1 2 J L 123
18. sch ab 100 240V AC 50 60 Hz 150 F60NBD 150 F60FHD 7 24V AC DCA 150 F60NBR T EE 25 100 240V AC 50 60 Hz 150 F85NBD 150 F85FHD B 24V AC DCA 150 F85NBR i 100 240V AC 50 60 Hz 150 F108NBD 150 F108FHD U 24V AC DCA 150 F108NBR 100 240V AC 50 60 Hz 150 F135NBD 150 F135FHD 34 135 Z 40 24V AC DCA 150 F135NBR en 100 240V AC 50 60 Hz 150 F201NBD 150 F201FHD v 24V AC DCA 150 F201NBR 200 208 m 100 240V AC 50 60 Hz 150 F251NBD 150 F251FHD 7 24V AC DCA 150 F251NBR 100 240V AC 50 60 Hz 150 F317NBD 150 F317FHD 106 317 E 100 24V AC DCA 150 F317NBR 100 240V AC 50 60 Hz 150 F361NBD 150 F361FHD 120 361 125 24V AC DCA 150 F361NBR 100 240V AC 50 60 Hz 150 F480NBD 150 F480FHD 160 480 150 24V AC DCA 150 F480NBR 110 120V AC 50 60 Hz 150 F625NBE 150 F625JHE 208 625 200 230 240V AC 50 60 Hz 150 F625NBA 150 F625JHA 110 120V AC 50 60 Hz 150 F780NBE 150 F780JHE 260 780 250 230 240V AC 50 60 Hz 150 F780NBA 150 F780JHA 110 120V AC 50 60 Hz 150 F970NBE 323 970 350 230 240V AC 50 60 Hz 150 F970NBA 110 120V AC 50 60 Hz 150 F1250NBE 416 1250 400 230 240V AC 50 60 Hz 150 F1250NBA Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given wh
19. 15 45 20 50 24V AC DC 150 C85NBR 100 240V AC 50 60 Hz 150 C108NBD 47 187 55 20 60 24V AC DCA 150 C108NBR 100 240V AC 50 60 Hz 150 C135NBD 59 234 75 25 19 24V AC DCA 150 C135NBR 100 240V AC 50 60 Hz 150 C201NBD 116 348 110 75 125 24V AC DCA 150 C201NBR 100 240V AC 50 60 Hz 150 C251NBD 145 435 132 100 150 24V AC DCA 150 C251NBR 100 240V AC 50 60 Hz 150 C317NBD 183 549 160 125 200 24V AC DCA 150 C317NBR 100 240V AC 50 60 Hz 150 C361NBD 208 625 200 150 250 24V AC DCA 150 C361NBR 100 240V AC 50 60 Hz 150 C480NBD 277 831 250 200 300 24V AC DCA 150 C480NBR Allen Bradley www ab com catalogs Publication 150 SGO09F EN P 37 Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type Controllers For use with Delta Connected Motors Continued Rated Voltage V AC 380 400 415 460 Motor FLA rating should fall within specified current range for unit to operate properly A Separate 120V or 240V single phase is required for fan operation 38 Open Type Motor Current A Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 C3NBD 1 7 5 1 0 55 2 2 0 5 2 24V AC DC 150 C3NBR 100 240V AC 50 60 Hz 150 C9NBD 5 1 16 2 2 4 5 2 4 5 24V AC DC 150 C9NBR 100 240V AC 50 60 Hz 150 C16NBD 9 1 27 6 4 11 5
20. 15 24V AC DC 150 C16NBR 100 240V AC 50 60 Hz 150 C19NBD 10 9 32 8 4 15 5 15 24V AC DC 150 C19NBR 100 240V AC 50 60 Hz 150 C25NBD 14 3 43 5 5 22 7 5 20 24V AC DC 150 C25NBR 100 240V AC 50 60 Hz 150 C30NBD 17 3 52 15 22 7 5 30 24V AC DC 150 C30NBR 100 240V AC 50 60 Hz 150 C37NBD 21 64 7 5 30 10 40 24V AC DC 150 C37NBR 100 240V AC 50 60 Hz 150 C43NBD 25 74 11 37 10 50 24V AC DC 150 C43NBR 100 240V AC 50 60 Hz 150 C60NBD 34 6 104 15 55 20 75 24V AC DC 150 C60NBR 100 240V AC 50 60 Hz 150 C85NBD 50 147 22 5 25 100 24V AC DC 150 C85NBR 100 240V AC 50 60 Hz 150 C108NBD 47 187 90 40 150 24V AC DCA 150 C108NBR 100 240V AC 50 60 Hz 150 C135NBD 59 234 132 50 150 24V AC DCA 150 C135NBR 100 240V AC 50 60 Hz 150 C201NBD 116 348 160 150 250 24V AC DCA 150 C201NBR 100 240V AC 50 60 Hz 150 C251NBD 145 435 250 200 350 24V AC DCA 150 C251NBR 100 240V AC 50 60 Hz 150 C317NBD 183 549 315 250 450 24V AC DCA 150 C317NBR 100 240V AC 50 60 Hz 150 C361NBD 208 625 355 300 500 24V AC DCA 150 C361NBR 100 240V AC 50 60 Hz 150 C480NBD 277 831 450 350 700 24V AC DCA 150 C480NBR www ab com catalogs Publication 150 SGO09F EN P Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type Controllers For use with Delta Connected Motors Continued Rated Voltage V AC 500 575 Motor FLA
21. 1524 17 431 1 75 45 61 69 1567 2 8 33 88 861 BP 38 965 60 1524 17 431 1 75 45 61 69 1567 480 Aen NB 3x8 40 1016 84 2134 18 457 4 4 20 508 91 5 2324 20 508 153H 153B BPNB NI 3x4 40 1016 84 2134 18 457 152B BP NB NI 6_ 3x 40 1016 84 2134 18 457 152H 152B BPNB NI 4 35 889 91 5 2324 20 508 152B 55 1397 91 5 2324 20 508 152H 152B 153H 153B NB 105 2664 91 5 2324 20 508 625 T 4 55 1397 91 5 2324 20 508 BP 70 1778 91 5 2324 20 508 153H 153B 65 1651 91 5 2324 20 508 152H 152B 55 1397 91 5 2324 20 508 780 152H 152B BPNI 70 1778 91 5 2324 20 508 u u 152H 152B 153H 153B NB 105 2664 91 5 2324 20 508 153H 153B 65 1651 91 5 2324 20 508 Assumed line voltage to be 480V AC Different voltage may necessitate a bigger enclosure size Consult your local Rockwell Automation sales office or Allen Bradley distributor 350 Hp max 8 150 Hp 208V AC 350 Hp G480V 400 450 Hp 600V 200 Hp 240V AC 400 Hp 480V 500 Hp 600V 28 www ab com catalogs Allen Bradley Publication 150 SGOO9F EN P Bulletin 150 SMC Flex Smart Motor Controllers Approximate Dimensions
22. 153H F201FAD 49 75 100 251 152H F251FAD 50 153H F251FAD 50 90 125 317 152H F317FAD 51 153H F317FAD 51 110 150 361 152H F361FAD 52 153H F361FAD 52 132 200 480 152H F480JAD 54 153H F480FAD 54 185 250 625 152H F625JAD 56 153H F625JAD 56 220 300 780 152H F780JAD 57 153H F780JAD 57 These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string t The nominal current rating for the combination package may differ from the controller based on the horsepower Consult your local Rockwell Automation sales office or Allen Bradley distributor Provided with Class J or L fuse clips as standard Available in IP54 Type 12 enclosure only Allen Bradley www ab com catalogs Publication 150 SG009F EN P 17 Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Combination Line Connected Controllers IP65 Type 4 12 Enclosed with Fusible Disconnect or Circuit Breaker Cont These controllers include line and load terminations Enclosures other than those listed are available consult your local Rockwell Automation sales office or Allen Bradley distributor All Bulletin 153 catalog numbers are supplied with thermal magnetic circuit breakers The fusible disconnects do not come with fuses
23. 2000 m 6560 ft Humidity 5 9596 non condensing Pollution Degree 2 Mechanical Operational All 1 0 G Peak 0 15 mm 0 006 in displacement Resistance to Vibration 5 480A 2 5 G Peak 0 38 mm 0 015 in displacement Non Operational 625 1250A 1 0 G Peak 0 15 mm 0 006 in displacement 5 85A 15G Operational 108 480A 5 5 G 625 1250A 4G Resistance to Shock 5 85A 30G Non Operational 108 480A 25G 625 1250A 12G Power Poles 5 85A Heatsink thyristor modular design Power Poles 108 1250A Heatsink hockey puck thyristor modular design Construction Control Modules Thermoset and Thermoplastic Moldings Metal Parts Plated Brass Copper or Painted Steel Cable size Line Upper 2 5 95 mm 14 3 0 AWG Line Lower 0 8 2 5 mm 18 14 AWG 5 85 A Load Upper 2 5 50 mm 14 1 AWG Load Lower 0 8 2 5 mm 18 14 AWG Tightening torque 14 7 Nem 130 Ib in Power Terminals Terminals 108 135 A One M10 x 1 5 diameter hole per power pole 201 251 A Two M10 x 1 5 diameter holes per power pole 317 480 A Two M12 x 1 75 diameter holes per power pole 625 1250 A Two 13 5 mm 0 53 in diameter holes per power pole Power Terminal Markings NEMA CENELEC EN50 012 Control Terminals M3 screw clamp Clamping yoke connection Other EMC Emission Levels DuC m IU Clas
24. 201 251 225 8 86 560 22 05 265 3 10 45 150 5 91 504 1 19 85 11 5 0 45 30 4 67 317 480 290 11 42 600 23 62 298 11 73 200 7 87 539 2 21 23 LE 11 5 0 45 45 8 101 Minimum Enclosure Size 4 a c ec IL Controller Rating A B Height A Width C Depth Fan Requirements 1 37 A 305 12 224 9 152 6 none 43 85 A 406 16 305 12 203 8 none 108 135 A 762 30 610 24 305 12 none 201 251A 965 38 762 30 356 14 none 317 480A 1295 51 914 36 356 14 none www ab com catalogs Publication 150 SGOO9F EN P 50 Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Approximate Dimensions Enclosed Type Line Connected Controllers F Cc 4 Figure 1 Wall Mount i Figure 3 Floor Mount Figure 4 Floor Mount Controller Dimension Dimensions in inches mm Rating A Bulletin With Option Figure No A Width B Height C Depth D Mtg Dim E Mtg Dim F Mtg Dim SMC 3 Non Combination Controller sae 456 4 8 203 12 305 6 152 2 44 62 10 43 265 3 0 76 6P 12 305 12 305 6 152 2 41 61 10 43 265 7 0 178 gt 8 203 14 356 8 203 2 44 62 12 40 315 3 0 76 6P 16 406 14 3
25. 25 152H F25FHD 36 153H F25FHD 36 2 25 152H F25FHD 37 153H F25FHD 37 3 25 152H F25FHD 38 153H F25FHD 38 5 25 152H F25FHD 39 153H F25FHD 39 5 25 152H F25FHD 40 153H F25FHD 40 10 43 152H F43FHD 41 153H F43FHD 41 15 60 152H F60FHD 42 153H F60FHD 42 20 85 152H F85FHD 43 153H F85FHD 43 290 25 85 152H F85FHD 44 153H F85FHD 44 30 108 152H F108FHD 45 153H F108FHD 45 40 135 152H F135FHD 46 153H F135FHD 46 50 201 152H F201FHD 47 153H F201FHD 47 60 201 152H F201FHD 48 153H F201FHD 48 75 251 152H F251FHD 49 153H F251FHD 49 100 317 152H F317FHD 50 153H F317FHD 50 125 361 152H F361FHD 51 153H F361FHD 51 150 480 152H F480FHD 52 153H F480FHD 52 200 625 A 152H F625JHD 54 A 153H F625JHD 54 250 780 152H F780JHD 56 153H F780JHD 56 0 37 0 5 5 152H F5FAD 33 153H F5FAD 33 0 55 0 75 5 152H F5FAD 34 153H F5FAD 34 0 75 1 5 152H F5FAD 35 153H F5FAD 35 1 1 1 5 25 152H F25FAD 36 153H F25FAD 36 1 5 2 25 152H F25FAD 37 153H F25FAD 37 2 2 3 25 152H F25FAD 38 153H F25FAD 38 3 7 25 152H F25FAD 39 153H F25FAD 39 5 5 7 5 25 152H F25FAD 40 153H F25FAD 40 1 5 10 43 152H F43FAD 41 153H F43FAD 41 11 15 43 152H F43FAD 42 153H F43FAD 42 15 20 60 152H F60FAD 43 153H F60FAD 43 230 18 5 25 85 152H F85FAD 44 153H F85FAD 44 22 30 85 152H F85FAD 45 153H F85FAD 45 30 40 108 152H F108FAD 46 153H F108FAD 46 37 50 135 152H F135FAD 47 153H F135FAD 47 45 60 201 152H F201FAD 48 153H F201FAD 48 55 75 201 152H F201FAD 49
26. 50 60 Hz 150 F970NCA 110 120V AC 50 60 Hz 150 F1250NCE 533 1600 1100 1600 230 240V AC 50 60 Hz 150 F1250NCA Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation technical support for further guidance A Separate 120V or 240V single phase power supply is required for fan operation www ab com catalogs 16 Publication 150 SG009F EN P Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Combination Line Connected Controllers IP65 Type 4 12 Enclosed with Fusible Disconnect or Circuit Breaker IP65 Type 4 12 Enclosed Combination IP65 Type 4 12 Enclosed Combination Verna Controller Current Controllers with Fusible Disconnect Controllers with Circuit Breaker V AC kW 50 Hz Hp 60 Hz Rating A Cat No 4 Cat No 0 5 5 152H F5FHD 33 153H F5FHD 33 0 75 5 152H F5FHD 34 153H F5FHD 34 1 5 152H F5FHD 35 153H F5FHD 35 1 5
27. 50 Hz Max Hp 60 Hz Control Power Cat No iacob 100 240V AC 50 60 Hz 150 C3NBD ME 24V AC DC 150 C3NBR 100 240V AC 50 60 Hz 150 C9NBD 5 1 16 1 5 8 24V AC DC 150 C9NBR 100 240V AC 50 60 Hz 150 C16NBD 9 1 27 6 33 0 5 24V AC DC 150 C16NBR 100 240V AC 50 60 Hz 150 C19NBD 10 9 32 8 3 10 24V AC DC 150 C19NBR 100 240V AC 50 60 Hz 150 C25NBD 14 3 43 3 10 24V AC DC 150 C25NBR 100 240V AC 50 60 Hz 150 C30NBD 17 3 52 5 10 24V AC DC 150 C30NBR 100 240V AC 50 60 Hz 150 C37NBD 21 64 5 20 24V AC DC 150 C37NBR 100 240V AC 50 60 Hz 150 C43NBD 25 74 7 5 20 24V AC DC 150 C43NBR 100 240V AC 50 60 Hz 150 C60NBD 34 6 104 15 30 24V AC DC 150 C60NBR 100 240V AC 50 60 Hz 150 C85NBD 50 147 15 40 24V AC DC 150 C85NBR 100 240V AC 50 60 Hz 150 C108NBD 47 187 20 60 24V AC DCA 150 C108NBR 100 240V AC 50 60 Hz 150 C135NBD 59 234 20 75 24V AC DCA 150 C135NBR 100 240V AC 50 60 Hz 150 C201NBD 116 348 75 100 24V AC DCA 150 C201NBR 100 240V AC 50 60 Hz 150 C251NBD 145 435 100 150 24V AC DCA 150 C251NBR 100 240V AC 50 60 Hz 150 C317NBD 183 549 100 200 24V AC DCA 150 C317NBR 100 240V AC 50 60 Hz 150 C361NBD 208 625 125 200 24V AC DCA 150 C361NBR 100 240V AC 50 60 Hz 150 C480NBD 277 831 200 300 24V AC DCA 150 C480NBR
28. 508 Extra capacity transformer may require a larger enclosure consult your local Rockwell Automation sales office or Allen Bradley distributor 1 kVA control transformers or larger extra capacity transformers may require a larger enclosure consult your local Rockwell Automation sales office or Allen Bradley distributor www ab com catalogs Allen Bradley oe 29 Publication 150 SGOO9F EN P Bulletin 150 SMC 3 Smart Motor Controllers Overview Motor Controller ef dr eee SLY LY LY are as follows Soft Start Current Limit Start 1 480 A Range Built In SCR Run Bypass Delta Compatibility Bulletin 150 Smart Motor Controllers SMC 3 Smart The SMC 3 is a compact simple to use solid state motor controller designed to operate 3 phase motors It features a built in overload y relay and a built in SCR bypass contactor on all three phases allowing a smaller footprint than other soft starters on the market This product is designed for many applications including compressors chillers pumps conveyors and crushers Modes of operation for the controller Soft Stop Kick Start The controllers offer two voltage ranges 200 480V AC and 200 600V AC All voltage ranges will operate at either 50 or 60 Hz Built In Electronic Motor Overload Protection Table of Contents Cat No Explanation 31 Product Selection 32 Typical Wiring Diags 44 Specifications
29. A Electrostatic Discharge 8 kV Air Discharge EMC Immunity Levels Radio Frequency Electromagnetic Field Per EN IEC 60947 4 2 Fast Transient Per EN IEC 60947 4 2 Surge Transient Per EN IEC 60947 4 2 Line Delta 5 dab 1 7 9 25 5 25 8 6 43 43 8 6 43 14 8 75 60 12 60 20 8 104 85 17 85 29 4 147 108 27 108 47 187 135 34 135 59 234 Current Range A 201 67 201 116 348 Overload Characteristics 251 84 251 145 435 317 106 317 183 549 361 120 361 208 625 480 160 480 277 831 625 208 625 283 850 780 260 780 300 900 970 323 970 400 1200 1250 416 1250 533 1600 Trip Classes Trip Current Rating Number of Poles 10 15 20 and 30 117 of Motor FLC 3 Certifications 26 Open Type Controllers www ab com catalogs Publication 150 SGOO9F EN P CE Marked Per Low Voltage Directive 73 23 EEC 93 68 EEC UL Listed File No E96956 Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Approximate Dimensions Approximate Dimensions and Shipping Weights Open Type Controllers Dimensions are in millimeters inches Dimensions are not intended for manufacturing purposes Rating A Height Width Depth Weight us 321 150 203 5 7 kg e 12 6 5 9 8 0 12 6 lbs 443 7 196 4 205 2 15 0 kg 108 135 17 47 7 74 8 08 33 lbs 560 225 253 8 30 4 kg 201 251 22 05 8 86 9 99 67 lbs 600 290 276 5 45 8 kg 317 480 23
30. C361NBD 150 C361FHD 120 361 75 125 24V AC DCA 150 C361NBR 100 240V AC 50 60 Hz 150 C480NBD 150 C480FHD 160 480 100 150 24V AC DCA 150 C480NBR Motor FLA rating should fall within specified current range for unit to operate properly These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to appropriate option code to the catalog string A Separate 120V or 240V single phase is required for fan operation 32 Publication 150 SGOO9F EN P www ab com catalogs he enclosure add the Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 NEMA 4 12 Controllers For use with Line Connected Motors Continued Rated Voltage V AC 230 Open Type Line Connected IP65 Type 4 12 Enclosed Motor Current Max kW 50 Max Hp 60 Motors Non Combination Controllers A t Hz Hz Control Power Cat No Cat No 100 240V AC 50 60 Hz 150 C3NBD 150 C3FAD 1 449 0 55 0 5 24V AC DC 150 C3NBR 100 240V AC 50 60 Hz 150 C9NBD 150 C9FAD 3 9 22 0 75 2 24V AC DC 150 C9NBR 100 240V AC 50 60 Hz 150 C16NBD 150 C16FAD 5 3 16 4 15 5 24V AC DC 150 C16NBR 100 240V AC 50 60 Hz 150 C19NBD 150 C25FAD 6 3 19
31. F25NBR 100 240V AC 50 60 Hz 150 F43NBD 150 F43FAD 8 6 43 11 15 24V AC DCA 150 F43NBR 100 240V AC 50 60 Hz 150 F60NBD 150 F60FAD 12 60 15 20 24V AC DCA 150 F60NBR 100 240V AC 50 60 Hz 150 F85NBD 150 F85FAD 17 85 22 30 24V AC DCA 150 F85NBR 100 240V AC 50 60 Hz 150 F108NBD 150 F108FAD 27 108 30 40 24V AC DCA 150 F108NBR 100 240V AC 50 60 Hz 150 F135NBD 150 F135FAD 34 135 37 50 24V AC DCA 150 F135NBR 100 240V AC 50 60 Hz 150 F201NBD 150 F201FAD 67 201 55 75 230 24V AC DCA 150 F201NBR 100 240V AC 50 60 Hz 150 F251NBD 150 F251FAD 84 251 75 100 24V AC DCA 150 F251NBR 100 240V AC 50 60 Hz 150 F317NBD 150 F317FAD 106 317 90 125 24V AC DCA 150 F317NBR 100 240V AC 50 60 Hz 150 F361NBD 150 F361FAD 120 361 110 150 24V AC DCA 150 F361NBR 100 240V AC 50 60 Hz 150 F480NBD 150 F480FAD 160 480 132 200 24V AC DCA 150 F480NBR 110 120V AC 50 60 Hz 150 F625NBE 150 F625JAE 208 625 200 250 230 240V AC 50 60 Hz 150 F625NBA 150 F625JAA 110 120V AC 50 60 Hz 150 F780NBE 150 F780JAE 260 780 250 300 230 240V AC 50 60 Hz 150 F780NBA 150 F780JAA 110 120V AC 50 60 Hz 150 F970NBE 323 970 315 400 230 240V AC 50 60 Hz 150 F970NBA 110 120V AC 50 60 Hz 150 F1250NBE 416 1250 400 500 230 240V AC 50 60 Hz 150 F1250NBA Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits
32. F780NCA 150 F780JCA 110 120V AC 50 60 Hz 150 F970NCE 323 970 710 1000 230 240V AC 50 60 Hz 150 F970NCA 110 120V AC 50 60 Hz 150 F1250NCE 416 1250 900 1300 230 240V AC 50 60 Hz 150 F1250NCA Rated Voltage Motor Current Open Type Line Connected Motors x V AC A t Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 27 108 90 100 100 240V AC 50 60 Hz 150 F108NZD 34 135 132 175 100 240V AC 50 60 Hz 150 F135NZD 67 201 160 200 100 240V AC 50 60 Hz 150 F201NZD 84 251 200 250 100 240V AC 50 60 Hz 150 F251NZD 106 317 315 400 100 240V AC 50 60 Hz 150 F317NZD 120 361 355 450 100 240V AC 50 60 Hz 150 F361NZD 160 480 450 600 100 240V AC 50 60 Hz 150 F480NZD 690 YS 110 120V AC 50 60 Hz 150 F625NZE 208 625 630 800 230 240V AC 50 60 Hz 150 F625NZA 110 120V AC 50 60 Hz 150 F780NZE 260 780 800 1000 230 240V AC 50 60 Hz 150 F780NZA 110 120V AC 50 60 Hz 150 F970NZE 323 970 1000 1300 230 240V AC 50 60 Hz 150 F970NZA 110 120V AC 50 60 Hz 150 F1250NZE 416 1250 1200 1600 230 240V AC 50 60 Hz 150 F1250NZA Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage s
33. Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 150 SGOO9F EN P March 2013 Supersedes Publication 150 SGOO9E EN P October 2011 Copyright 2013 Rockwell Automation Inc All rights reserved Printed in the U S A
34. SA 2 3 2 8 Nem 20 25 inelbs 2 5 95 mm2 14 3 0 AWG Line Power Terminals Cable Size _ PA 11 3 12 4 Nem 100 110 inelbs Igteringr Lorqua 108 135 A 23 Nem 200 inelbs 201 251A Two M10 x 1 5 diameter holes per power pole 317 480A Two M12 x 1 75 diameter holes per power pole 2 5 16 mm2 14 6 AWG Bom 2 3 2 5 Nem 20 22 5 inelbs 2 5 50 mm2 14 1 AWG Load Power Terminals ER 43 BSA 11 3 12 4 Nem 100 110 inelbs 9 9 tora 108 135 A 23 Nem 200 inelbs 201 251A Two M10 x 1 5 diameter holes per power pole 317 480A Two M12 x 1 75 diameter holes per power pole Cable Size 0 2 2 5 mm2 24 14 AWG Control Terminals All Tightening Torque 0 5 0 9 Nem 4 4 8 0 inelbs Other UL CSA NEMA IEC mm Conducted Radio Frequency Emissions Class A EDDAU Radiated Emissions Class A Electrostatic Discharge 4 kV Contact and 8 kV Air Discharge 8 kV Air Discharge EMC Immunity Levels Radio Frequency Electromagnetic Field Per EN IEC 60947 4 2 Fast Transient mm Per EN IEC 60947 4 2 Surge Transient Per EN IEC 60947 4 2 48 www ab com catalogs Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers S pecifications SMC 3 Overload Trip Curves Trip Class 10 Cold Trip Hot Trip 100 t sec
35. and Communication Modules Description Cat No Hand Held LCD Display Full Numeric Keypad x 20 HIM A3 Human Interface Modules CD Display Programmer Only 20 HIM A5 Door Mounted Remote Panel Mount LCD Display Full Numeric Keypad 20 HIM C3S Human Interface Modules CD Display Programmer Only HIM includes 3 m cable 20 HIM C5S PowerFlex HIM Interface Cable 1 m 39 in 20 HIM H10 Cable Kit Male Female 0 33 m 1 1 ft 1202 H03 Human Interface Module Cable Kit Male Female 1 m 3 3 ft 1202 H10 Interface Cables Cable Kit Male Female 3 m 9 8 ft 1202 H30 Cable Kit Male Female 9 m 29 5 ft 1202 H90 DPI SCANport One to Two Port Splitter Cable 1203 S03 Description IP30 Type 1 For Use With RS485 DF1 Communication Adapter 20 COMM S PROFIBUS DP Communication Adapter 20 COMM P ControlNet Communication Adapter Coax 20 COMM C Interbus Communication Adapter 20 COMM I Communication Modules Modbus TCP Communication Adapter Bulletin 150 SMC Flex 20 COMM M DeviceNet Communication Adapter 20 COMM D EtherNet IPTM Communication Adapter 20 COMM E HVAC Communication Adapter 20 COMM H ControlNet Communication Adapter Fiber 20 COMM Q DriveTools Programming Software WIN NT 2000 XP 9303 4DTEO1ENE DriveTools Sp Programming Software WIN NT 2000 XP 9303 4DTSO1ENE AnaCANda RS 232 to DPI PC Interface Serial 1203 SSS DPI to USB PC Interface Reauires a 20 HIM H10 cab
36. consists of either OFF 10 15 20 or 30 protection The trip current is programmed by entering the motor full load current rating service factor and selecting the trip class Thermal memory is included to accurately model motor operating temperature Ambient temperature insensitivity is inherent in the electronic design of the overload www ab com catalogs 6 Publication 150 SG009F EN P Undervoltage Protection The SMC Flex controller s undervoltage protection will halt motor operation if a drop in the incoming line voltage is detected The undervoltage trip level is adjustable as a percentage of the programmed line voltage from 0 9996 To eliminate nuisance trips a programmable undervoltage trip delay time of 0 99 seconds can also be programmed The line voltage must remain below the undervoltage trip level during the programmed delay time Overvoltage Protection If a rise in the incoming line voltage is detected the SMC Flex controller s overvoltage protection will halt motor operation The overvoltage trip level is adjustable as a percentage of the programmed line voltage from 0 199 To eliminate nuisance trips a programmable overvoltage trip delay time of 0 99 seconds can also be programmed The line voltage must remain above the overvoltage trip level during the programmed delay time Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Overview Stall Protection and Jam Detection Motors can e
37. control wiring can be tested for fault conditions by using the Push to Test function Hold down the Reset button for 7 s to activate the fault Aux 97 98 and shut down the SMC 3 To clear either push the Reset button or cycle control power to the device LED Description Number of Flashes Overload Overtemperature Phase Reversal Phase Loss Open Load Phase Imbalance Shorted SCR Test NOGORON Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Catalog Number Explanation Cat No Explanation Open and Non Combination Bulletin Number Solid State Controller Controller Type SMO 3 Combination Bulletin Number Solid State Controller with Fusible Disconnect Solid State Controller with Circuit Breaker Controller Type SMO 3 Allen Bradley Ampere Ratings Code Description Ampere Ratings Code Description Enclosure Type N Open E NEMA 4 12 IP65 Input Line Voltage Open Type Code Description B 200 460V AC 3 Phase 50 60 Hz 200 600V AC 3 Phase 50 60 Hz Non Combination Enclosed Only 200 208V AC 3 Phase 50 60 Hz 230V AC 3 Phase 50 60 Hz 400 460V AC 3 Phase 50 60 Hz 500 575V AC 3 Phase 50 60 Hz e Input Line Voltage Open Type Code Description 200 208V AC 3 Phase 50 60 Hz 230V AC 3 Phase 50 60 Hz 400 460V AC 3 Phase 50 6
38. corresponding option module is selected Example Cat No 150 F108FBDB 1XB V Bypass contactor and overload are not included with this option A NB or BP needs to be added to the catalog string to add these devices www ab com catalogs Publication 150 SG009F EN P Allen Bradley 19 Bulletin 150 SMC Flex Smart Motor Controllers Modifications Accessories Enclosed Options Continued Option NEMA Bypass Contactor and Overload Relay Description 5 43 A Cat No Modification 60 85 A 108 135 A NB 201 251A 317 361A 480A NEMA Isolation Contactor 5 43 A 60 85 A 108 135 A 201 251A NI 317 361A 480A MCS Bypass Contactor and Overload Relay Accessories Protective Modules 5 43 A 60 85 A 108 135 A 201 251A 317 361A 480A Protective modules must not be placed on the load side of a device when using an inside the delta connection or with Pump Braking or Linerar Speed control PROTECTIVE MODULE AX 150 F HAL L3 Field Modification Current Rating A Description Cat No 5 85 150 F84 480V Protective Module UM 90 520 150 F84L 5 85 150 F86 600V Protective Module 90 520 150 F86L The same protective module mounts on the line or load side of the SMC Flex For applications requiring both line and load side protection two protective mod
39. rating should fall within specified current range for unit to operate properly Open Type Motor Current A Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 C3NCD 1 7 5 1 0 75 3 1 3 24V AC DC 150 C3NCR 100 240V AC 50 60 Hz 150 C9NCD 5 1 16 3 7 5 3 10 24V AC DC 150 C9NCR 100 240V AC 50 60 Hz 150 C16NCD 9 1 27 6 D D 1b 7 5 20 24V AC DC 150 C16NCR 100 240V AC 50 60 Hz 150 C19NCD 10 9 32 8 5 5 22 7 5 30 24V AC DC 150 C19NCR 100 240V AC 50 60 Hz 150 C25NCD 14 3 43 7 5 22 10 40 24V AC DC 150 C25NCR 100 240V AC 50 60 Hz 150 C30NCD 17 3 52 11 30 15 50 24V AC DC 150 C30NCR 100 240V AC 50 60 Hz 150 C37NCD 21 64 11 37 15 60 24V AC DC 150 C37NCR 100 240V AC 50 60 Hz 150 C43NCD 25 74 15 45 20 60 24V AC DC 150 C43NCR 100 240V AC 50 60 Hz 150 C60NCD 34 6 104 22 50 30 100 24V AC DC 150 C60NCR 100 240V AC 50 60 Hz 150 C85NCD 50 147 30 90 40 150 24V AC DC 150 C85NCR 100 240V AC 50 60 Hz 150 C108NCD 47 187 132 50 150 24V AC DCA 150 C108NCR 100 240V AC 50 60 Hz 150 C135NCD 59 234 160 60 200 24V AC DCA 150 C135NCR 100 240V AC 50 60 Hz 150 C201NCD 116 348 250 250 300 24V AC DCA 150 C201NCR 100 240V AC 50 60 Hz 150 C251NCD 145 435 315 250 400 24V AC DCA 150 C251NCR 100 240V AC 50 60 Hz 150 C317NCD 18
40. up to speed fault alarm network N O N C Auxiliary Contacts or external bypass N O only Helps reduce fluid surges in centrifugal pumping systems during starting and stopping Pump Control period Starting time is adjustable from 0 30 s Stopping time is adjustable from 0 120 s Provides motor braking without additional equipment for applications that require the motor to stop quickly Braking current is adjustable from 0 400 of the motor s full load current rating SMB Smart Motor Braking Optional Features Provides controlled position stopping During stopping braking torque is applied to the Braking Control motor until it reaches preset slow speed 796 or 1596 of rated speed and holds the motor AGO SOR at this speed until a stop command is given Braking torque is then applied until the motor reaches zero speed Braking current is programmable from 0 450 of full load current Slow Speed with Used on applications that require slow speed in the forward direction for positioning or Braking alignment and also require braking control to stop Wiring Diagram Line Controller poet L1A T2 3 Phase L2 3 T24 Motor Input Power L3 5 T36 SMC Flex Controller J Branch T md cc m Protection AMA k pi e Fan Stop Option Input 1 gt k ToLo St
41. 0 A 40 Hp 6 460V AC F85 85 A 60 Hp 6 460V AC F108 108 A 75 Hp 460V AC F135 135 A 100 Hp 460V AC F201 201 A 150 Hp 460V AC F251 251 A 200 Hp 460V AC F317 317 A 250 Hp 460V AC F361 361 A 300 Hp 460V AC F480 480 A 400 Hp 460V AC F625 625 A 500 Hp 460V AC F780 780 A 600 Hp 460V AC 8 www ab com catalogs Allen Bradley Publication 150 SGOO9F EN P Horsepower Cat Hp Cat Hp Cat Hp Cat Hp Cat Hp No Rating No Rating No Rating No Rating No Rating Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 Type 4 12 Controllers For use with Line Connected Motors Enclosures other than those listed are available consult your local Rockwell Automation sales office or Allen Bradley distributor Open Type Line Connected IP65 Type 4 12 Enclosed Rated Voltage Motor Current Max kW Max Hp Motors Non Combination Controllers V AC A 50 Hz 60 Hz Control Power Cat No Cat No 4 100 240V AC 50 60 Hz 150 F5NBD 150 F5FHD i n 24V AC DCA 150 F5NBR de cab 5 100 240V AC 50 60 Hz 150 F25NBD 150 F25FHD T m 24V AC DCA 150 F25NBR dns f 100 240V AC 50 60 Hz 150 F43NBD 150 F43FHD BE 7 24V AC DCA 150 F43NBR m
42. 0 C108 C135 1 150 TC1 Terminal Cover MC We AW Y SW IEC line or load terminal covers for 108 480 A devices 150 C201 C251 1 150 TC2 A 1 10 ME AU O Dead front protection 150 C317 C480 1 150 TC3 Terminal Lug Kits 108 480 A m Total No of Line Controller Terminal Lugs Current Possible Each Side Rating A t Wire Size Line Side Load Side Pkg Qty Cat No 108 135A 6 250 MCM AWG 3 3 TN 201 251A 16 mm 120 mm 6 6 WEHR b 3 Pp D 4 500 MCM AWG f e 317 480A 25 mm 240 mm 6 6 199 LG1 Line and Load terminals are provided as standard on enclosed SMCs 1 85 A units have box lugs standard No additional lugs are required A When a multi conductor lug is required refer to the Instruction Sheet for appropriate lug catalog number Marking Tags and Covers Description For Use With Pkg Qty Marking Tag Sheet 160 perforated paper labels each 6 x 17 mm to be used 150 C 150 D 100 FMP with a transparent cover 4 Transparent Cover To be used with marking tag sheets TF GER 100 OENE Remote Reset Solenoid Description For Use With Pkg Qty Cat No issemo ES Remote Reset Solenoid for remote reset of electronic 193 T all 150 C 193 ER19 CES overload amp Voltage Suffix Code Available Coil Voltages 12 600V 50 Hz 12 600V 60 Hz Standard Coil Voltages Voltage 24 48 110 115 120 220 240 50 Hz J D A 60 Hz J D A DC Z24 Z48 Z01
43. 0 F1250NBA Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation technical support for further guidance These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string A Separate 120V or 240V single phase power supply is required for fan operation Line and load termination are provided as standard Available in IP54 Type 12 enclosure only www ab com catalogs Allen Bradley os 11 Publication 150 SGOO9F EN P Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 Type 4 12 Controllers For use with Line Connected Motors Continued Enclosures other than those listed are available consult your local Rockwell Automation sales office or Allen Bradley distributor Open Type Line Conne
44. 0 Hz Enclosure Type Code Description NEMA Type 4 12 IP65 NEMA Type 12 IP54 NEMA Type 3R IP44 www ab com catalogs Publication 150 SG009F EN P 500 575V AC 3 Phase 50 60 Hz Control Voltage 100 240V AC 24V AC DC Open Type only g Options see page 42 for a full listing Line Mounted Protective 8L Module Enclosed Type only Load side MOVs are not available when used with inside the delta connections MOVs can be field installed for open type units Options see page 42 for a full listing Line Mounted Protective 8L Module Enclosed Type only Load side MOVs are not available when used with inside the delta connections Horsepower Cat Hp Cat Hp Cat Hp Cat Hp Cat Hp No Rating No Rating No Rating No Rating No Rating 31 Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 NEMA 4 12 Controllers For use with Line Connected Motors Rated Voltage V AC 200 208 Open Type Line Connected IP65 Type 4 12 Enclosed Motor Current Max kW 50 Max Hp 60 Motors Non Combination Controllers A t Hz Hz Control Power Cat No Cat No is
45. 00 361 30 kA 1000 30 kA 1000 69 kA 600 480 42 kA 1200 42 kA 1200 69 kA 800 625 42 kA 1600 42 kA 1600 74 kA 1600 780 42 kA 1600 42 kA 2000 74 kA 1600 970 85 kA 2500 85 kA 2500 85 kA 2500 1250 85 kA 3000 85 kA 3200 85 kA 3000 8 7 5 kA 35 5 kA 35 70 kA 17 5 43 5 kA 150 5 kA 150 70 kA 90 74 10 kA 300 10 kA 300 70 kA 150 104 10 kA 400 10 kA 400 70 kA 200 147 10 kA 400 10 kA 400 70 kA 200 187 10 kA 600 10 kA 500 70 kA 300 234 10 kA 700 10 kA 700 70 kA 400 Delta Device Operational 348 18 kA 1000 18 kA 1000 70 kA 600 Short Circuit Current Rating A 435 18 kA 1200 18 kA 1200 70 kA 800 Protection 549 30 kA 1600 30 kA 1600 69 kA 1000 625 30 kA 1600 30 kA 1600 69 kA 1200 831 42 kA 1600 30 kA 1600 69 kA 1600 850 42 kA 1600 42 kA 2000 74 kA 1600 900 42 kA 1600 42 kA 2000 74 kA 1600 1200 85 kA 3000 85 kA 3200 85 kA 3000 1600 85 kA 3000 85 kA 3200 85 kA 3000 SCPD Performance 690V Type 1 SCCR List pins Max Standard Available Faut Max poi d North n a 6 9 gRB 73xxx400 108 70 kA A070URD33xxx500 G GURDA920x500 135 70 kA AO7OURD33xxx500 Due 00 201 70 kA A070URD33xxx700 Fr ne 251 70 kA AO70URD33xxx700 aT 6 9 gRB 73xxx800 w 317 70 kA A070URD33xxx900 G G FID3 00900 361 70 kA AO70URD33xxx900 De non A070D33xxx1250 9 URD 73xxx1250 480 JURA A100URD73xxx1250 6 6URD33xxx1250 625 70 kA A070URD33xxx1400 6 6URD33xxx1400 780 70 kA A070URD33xxx1400 6 6URD33xxx1400 Two fuses in parallel Two fuses in parallel 370 85 kA AO7OURD33xxx1250 6 6URD33xxx1250 Two fu
46. 1 450 600 780 A 152H F780JBD 62 A 153H F780JBD 62 0 55 0 75 5 152H F5FCD 34 153H F5FCD 34 0 75 1 5 152H F5FCD 35 153H F5FCD 35 41 15 5 152H F5FCD 36 153H F5FCD 36 1 5 2 5 152H F5FCD 37 153H F5FCD 37 2 2 3 5 152H F5FCD 38 153H F5FCD 38 3 7 5 25 152H F25FCD 39 153H F25FCD 39 5 5 7 5 25 152H F25FCD 40 153H F25FCD 40 7 5 10 25 152H F25FCD 41 153H F25FCD 41 11 15 25 152H F25FCD 42 153H F25FCD 42 15 20 43 152H F43FCD 43 153H F43FCD 43 18 5 25 43 152H F43FCD 44 153H F43FCD 44 22 30 43 152H F43FCD 45 153H F43FCD 45 22 40 43 152H F43FCD 46 153H F43FCD 46 500 575 37 50 60 152H F60FCD 47 153H F60FCD 47 45 60 85 152H F85FCD 48 153H F85FCD 48 55 75 85 152H F85FCD 49 153H F85FCD 49 75 100 108 152H F108FCD 50 153H F108FCD 50 90 125 135 152H F135FCD 51 153H F135FCD 51 110 150 201 152H F201FCD 52 153H F201FCD 52 132 200 201 152H F201FCD 54 153H F201FCD 54 160 250 251 152H F251FCD 56 153H F251FCD 56 200 300 317 152H F317FCD 57 153H F317FCD 57 250 350 361 152H F361FCD 58 153H F361FCD 58 295 400 480 A 152H F480JCD 59 153H F480FCD 59 315 450 480 A 152H F480JCD 60 153H F480FCD 60 315 500 480 A 152H F480JCD 61 153H F480FCD 61 450 600 625 A 152H F625JCD 62 A 153H F625JCD 62 560 800 780 A 152H F780JCD 65 A 153H F780JCD 65 These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string The nominal current rating for the com
47. 100 64 10 kA 250 10 kA 250 70 kA 100 Delta Device 74 10 kA 250 10 kA 250 70 kA 150 Operational 104 10 kA 400 10 kA 300 70 kA 225 Current Rating 147 10 kA 400 10 kA 400 70 kA 300 A 187 10 kA 600 10 kA 500 70 kA 400 234 10 kA 700 10 kA 700 70 kA 400 348 18 kA 1000 18 kA 1000 70 kA 600 435 18 kA 1200 18 kA 1200 69 kA 800 549 30 kA 1600 30 kA 1600 69 kA 1000 625 30 kA 1600 30 kA 1600 69 kA 1200 831 42 kA 1600 30 kA 1600 69 kA 1600 831 42 kA 1600 42 kA 1200 69 kA 1600 Non time delay fuses K5 Consult local codes for proper sizing of short circuit protection Type 1 performance protection indicates that under a short circuit condition the fused or circuit breaker protected starter shall cause no danger to persons or installation but may not be suitable for further service without repair or replacement A For short circuit current rating SCCR for enclosed panel with external bypass or isolation contactor see the Industrial Controls catalog website www ab com catalogs Allen Bradley www ab com catalogs 46 Publication 150 SGOO9F EN P Bulletin 150 SMC 3 Smart Motor Controllers Specifications Electrical Ratings UL CSA NEMA IEC Rated Operational Voltage 10 1596 100 240V AC 24V AC DC 100 240V 24V AC DC Rated Insulation Voltage 250V 250V
48. 120V AC 50 60 Hz 150 F970NBE 400 1200 400 400 230 240V AC 50 60 Hz 150 F970NBA 110 120V AC 50 60 Hz 150 F1250NBE 533 1600 500 600 230 240V AC 50 60 Hz 150 F1250NBA Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation technical support for further guidance A Separate 120V or 240V single phase power supply is required for fan operation 14 www ab com catalogs Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type Controllers For use with Delta Connected Motors Continued Rated Voltage V AC 400 415 460 Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Open Type Motor Current A Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 F5NBD 1 7 8 7 4 5 24V AC DCA 150 F5NBR 100 240V AC 50 60 Hz 150 F25NBD 8 7 48 22 30 24V AC DCA 150 F25NBR 100 240V AC 50 60 Hz 150 F43NBD 14 9 74 37 50 24V AC DCA 150 F43NBR 100 240V AC 50 60 Hz 150 F60NBD 20 8 104
49. 14 5 368 152H Any 1 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 AEN Any 1x 16 406 4 610 9 229 0 75 19 22 5 572 14 5 368 85 Any 1t 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 153H Any 1 16 406 4 610 9 229 0 75 19 22 5 572 14 5 368 108 152H 153H Any 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 135 152H 153H Any 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 ai 152H 153H 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 152H 152B 153H 153B Any 1 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 25 152H 153H 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 152H 152B 153H 153B Any 1 36 914 1 1295 14 356 0 75 19 49 5 1257 34 5 876 Rd 1 36 914 1 1295 14 356 0 75 19 49 5 1257 34 5 876 BPNB 1 36 914 0 1524 14 356 0 75 19 58 5 1486 34 5 876 225 153B 1 36 914 60 1524 14 356 0 75 19 58 5 1486 34 5 876 152H 152B 2 38 965 60 1524 17 431 33 88 861 1 75 45 61 69 1567 152H BP 2 38 965 60 1524 17 431 33 88 861 1 75 45 61 69 1567 152H 152B 153H 153B NB NI 3 40 1016 4 2134 18 457 ar 1 36 914 1 1295 14 356 0 75 19 49 5 1257 34 5 876 BPNB 1 36 914 0 1524 14 356 0 75 19 58 5 1486 34 5 876 did 153B 1 36 914 0 1524 14 356 0 75 19 58 5 1486 34 5 876 152H 152B 2 38 965 60 1524 17 431 33 88 861 1 75 45
50. 150 F5NBD 150 F5FBD o 24V AC DCA 150 F5NBR 5 25 11 15 100 240V AC 50 60 Hz 150 F25NBD 150 F25FBD B 24V AC DCA 150 F25NBR 100 240V AC 50 60 Hz 150 F43NBD 150 F43FBD 8 6 43 22 30 24V AC DCA 150 F43NBR 100 240V AC 50 60 Hz 150 F60NBD 150 F60FBD 12 60 30 40 24V AC DCA 150 F60NBR 100 240V AC 50 60 Hz 150 F85NBD 150 F85FBD 17 85 45 60 24V AC DCA 150 F85NBR 100 240V AC 50 60 Hz 150 F108NBD 150 F108FBD 27 108 55 75 24V AC DCA 150 F108NBR 100 240V AC 50 60 Hz 150 F135NBD 150 F135FBD 34 135 75 100 24V AC DCA 150 F135NBR 100 240V AC 50 60 Hz 150 F201NBD 150 F201FBD 67 201 110 150 24V AC DCA 150 F201NBR 400 415 460 100 240V AC 50 60 Hz 150 F251NBD 150 F251FBD 84 251 132 200 24V AC DCA 150 F251NBR 100 240V AC 50 60 Hz 150 F317NBD 150 F317FBD 106 317 160 250 24V AC DCA 150 F317NBR 100 240V AC 50 60 Hz 150 F361NBD 150 F361FBD 120 361 200 300 24V AC DCA 150 F361NBR 100 240V AC 50 60 Hz 150 F480NBD 150 F480FBD 160 480 250 400 24V AC DCA 150 F480NBR 110 120V AC 50 60 Hz 150 F625NBE 150 F625JBE 208 625 355 500 230 240V AC 50 60 Hz 150 F625NBA 150 F625JBA 110 120V AC 50 60 Hz 150 F780NBE 150 F780JBE 260 780 450 600 230 240V AC 50 60 Hz 150 F780NBA 150 F780JBA 110 120V AC 50 60 Hz 150 F970NBE 323 970 560 800 230 240V AC 50 60 Hz 150 F970NBA 110 120V AC 50 60 Hz 150 F1250NBE 416 1250 710 1000 230 240V AC 50 60 Hz 15
51. 153H C9FCD 37 9 2 2 3 152H C9FCD 38 153H C9FCD 38 9 3 7 5 152H C9FCD 39 153H C9FCD 39 16 5 5 7 5 152H C16FCD 40 153H C16FCD 40 16 7 5 10 152H C16FCD 41 153H C16FCD 41 25 11 15 152H C25FCD 42 153H C25FCD 42 30 15 20 152H C30FCD 43 153H C30FCD 43 37 18 5 25 152H C37FCD 44 153H C37FCD 44 500 575 43 22 30 152H C43FCD 45 153H C43FCD 45 43 30 40 152H C43FCD 46 153H C43FCD 46 60 37 50 152H C60FCD 47 153H C60FCD 47 85 45 60 152H C85FCD 48 153H C85FCD 48 85 55 75 152H C85FCD 49 153H C85FCD 49 108 75 100 152H C108FCD 50 153H C108FCD 50 135 90 125 152H C135FCD 51 153H C135FCD 51 201 132 200 152H C201FCD 54 153H C201FCD 54 251 160 250 152H C251FCD 56 153H C251FCD 56 317 200 300 152H C317FCD 57 153H C317FCD 57 361 250 350 152H C361FCD 58 153H C361FCD 58 480 315 500 E 152H C480JCD 61 153H C480FCD 61 t These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string Available in IP54 Type 12 enclosure only www ab com catalogs Publication 150 SG009F EN P 41 Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Modifications Accessories Enclosed Options Cat No Option Description Modification Push Buttons Start Stop Push Button 1 Selector Switch Hand Off Auto S
52. 251 75 152H C251FHD 49 153H C251FHD 49 317 100 152H C317FHD 50 153H C317FHD 50 361 125 152H C361FHD 51 153H C361FHD 51 480 150 152H C480FHD 52 153H C480FHD 52 3 0 37 0 5 152H C3FAD 33 153H C3FAD 33 9 0 55 0 75 152H C9FAD 34 153H C9FAD 34 9 0 75 1 152H C9FAD 35 153H C9FAD 35 9 1 1 1 5 152H C9FAD 36 153H C9FAD 36 9 1 5 2 152H C9FAD 37 153H C9FAD 37 16 2 2 3 152H C16FAD 38 153H C16FAD 38 25 3 7 152H C25FAD 39 153H C25FAD 39 30 5 5 7 5 152H C30FAD 40 153H C30FAD 40 37 7 5 10 152H C37FAD 41 153H C37FAD 41 43 11 15 152H C43FAD 42 153H C43FAD 42 230 60 15 20 152H C60FAD 43 153H C60FAD 43 85 18 5 25 152H C85FAD 44 153H C85FAD 44 85 22 30 152H C85FAD 45 153H C85FAD 45 108 30 40 152H C108FAD 46 153H C108FAD 46 135 37 50 152H C135FAD 47 153H C135FAD 47 201 55 75 152H C201FAD 49 153H C201FAD 49 251 75 100 152H C251FAD 50 153H C251FAD 50 317 90 125 152H C317FAD 51 153H C317FAD 51 361 110 150 152H C361FAD 52 153H C361FAD 52 480 147 200 152H C480JAD 54 153H C480FAD 54 t These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string Available in IP54 Type 12 enclosure only www ab com catalogs 40 Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Combination Enclosed IP65 NEMA 4 12 Controllers with Fusible Disconnect
53. 3 549 400 300 500 24V AC DCA 150 C317NCR 100 240V AC 50 60 Hz 150 C361NCD 208 625 450 350 600 24V AC DCA 150 C361NCR 100 240V AC 50 60 Hz 150 C480NCD 277 831 560 400 900 24V AC DCA 150 C480NCR A Separate 120V or 240V single phase is required for fan operation Allen Bradley www ab com catalogs Publication 150 SGO09F EN P 39 Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Combination Enclosed IP65 NEMA 4 12 Controllers with Fusible Disconnect or Circuit Breaker IP65 Type 4 12 Enclosed IP65 Type 4 12 Enclosed Combination Controllers with Combination Controllers Rated Voltage Current Fusible Disconnect with Circuit Breaker V AC Rating A kw Hp Cat No Cat No 3 0 5 152H C3FHD 33 153H C3FHD 33 9 0 75 152H C9FHD 34 153H C9FHD 34 9 3 152H C9FHD 35 153H C9FHD 35 9 1 5 152H C9FHD 36 153H C9FHD 36 16 2 152H C16FHD 37 153H C16FHD 37 16 3 152H C16FHD 38 153H C16FHD 38 25 152H C25FHD 39 153H C25FHD 39 37 7 5 152H C37FHD 40 153H C37FHD 40 43 10 152H C43FHD 41 153H C43FHD 41 200 208 60 15 152H C60FHD 42 153H C60FHD 42 85 20 152H C85FHD 43 153H C85FHD 43 85 25 152H C85FHD 44 153H C85FHD 44 108 30 152H C108FHD 45 153H C108FHD 45 135 40 152H C135FHD 46 153H C135FHD 46 201 60 152H C201FHD 48 153H C201FHD 48
54. 4 2 5 24V AC DC 150 C19NBR 100 240V AC 50 60 Hz 150 C25NBD 150 C25FAD 9 2 25 5 5 Be ee 24V AC DC 150 C25NBR 100 240V AC 50 60 Hz 150 C30NBD 150 C30FAD 10 30 7 5 5 10 24V AC DC 150 C30NBR 100 240V AC 50 60 Hz 150 C37NBD 150 C37FAD 12 3 37 7 5 5 10 24V AC DC 150 C37NBR 100 240V AC 50 60 Hz 150 C43NBD 150 C43FAD 14 3 43 11 5 15 24V AC DC 150 C43NBR 100 240V AC 50 60 Hz 150 C60NBD 150 C60FAD 20 60 15 7 5 20 24V AC DC 150 C60NBR 100 240V AC 50 60 Hz 150 C85NBD 150 C85FAD 28 3 85 22 15 90 24V AC DC 150 C85NBR 100 240V AC 50 60 Hz 150 C108NBD 150 C108FAD 27 108 30 20 40 24V AC DCA 150 C108NBR 100 240V AC 50 60 Hz 150 C135NBD 150 C135FAD 34 135 37 25 50 24V AC DCA 150 C135NBR 100 240V AC 50 60 Hz 150 C201NBD 150 C201FAD 67 201 55 40 75 24V AC DCA 150 C201NBR 100 240V AC 50 60 Hz 150 C251NBD 150 C251FAD 84 251 75 50 100 24V AC DCA 150 C251NBR 100 240V AC 50 60 Hz 150 C317NBD 150 C317FAD 106 317 90 60 125 24V AC DCA 150 C317NBR 100 240V AC 50 60 Hz 150 C361NBD 150 C361FAD 120 361 110 75 150 24V AC DCA 150 C361NBR 100 240V AC 50 60 Hz 150 C480NBD 150 C480FAD 160 480 132 100 200 24V AC DCA 150 C480NBR Motor FLA rating should fall within specified current range for unit to operate properly These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circ
55. 55 75 24V AC DCA 150 F60NBR 100 240V AC 50 60 Hz 150 F85NBD 29 4 147 75 100 24V AC DCA 150 F85NBR 100 240V AC 50 60 Hz 150 F108NBD 47 187 90 150 24V AC DCA 150 F108NBR 100 240V AC 50 60 Hz 150 F135NBD 59 234 132 150 24V AC DCA 150 F135NBR 100 240V AC 50 60 Hz 150 F201NBD 116 348 160 250 24V AC DCA 150 F201NBR 100 240V AC 50 60 Hz 150 F251NBD 145 435 250 350 24V AC DCA 150 F251NBR 100 240V AC 50 60 Hz 150 F317NBD 183 549 315 450 24V AC DCA 150 F317NBR 100 240V AC 50 60 Hz 150 F361NBD 208 625 355 500 24V AC DCA 150 F361NBR 100 240V AC 50 60 Hz 150 F480NBD 277 831 450 700 24V AC DCA 150 F480NBR 110 120V AC 50 60 Hz 150 F625NBE 283 850 500 700 230 240V AC 50 60 Hz 150 F625NBA 110 120V AC 50 60 Hz 150 F780NBE 300 900 500 700 230 240V AC 50 60 Hz 150 F780NBA 110 120V AC 50 60 Hz 150 F970NBE 400 1200 710 1000 230 240V AC 50 60 Hz 150 F970NBA 110 120V AC 50 60 Hz 150 F1250NBE 533 1600 900 1400 230 240V AC 50 60 Hz 150 F1250NBA Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation technical support for further guidance A Separate 120V or 240V single phase power supply is required for fan operation Allen Bradley www ab com catalo
56. 56 8 203 4 38 111 12 40 315 7 0 178 108 135 150 Any 1 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 150 q 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 150 150B BP NB NI 6P 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 150 Any 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 six nm i 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 150B NI 6P 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 BPNI 6P 36 914 60 1524 14 356 0 75 19 58 5 1486 34 5 876 aab 150 36 914 51 1295 14 356 0 75 19 49 5 1257 34 5 876 150 150B BP NB NI 6P 36 914 60 1524 14 356 0 75 19 58 5 1486 34 5 876 www ab com catalogs Allen Bradley ui 51 ublication 150 SGO09F EN P Bulletin 150 SMC 3 Smart Motor Controllers Approximate Dimensions Controller Dimension Dimensions in inches mm Rating A Bulletin With Option Figure No A Width B Height C Depth D Mtg Dim E Mtg Dim F Mtg Dim SMC 3 Combination Controller 3 37 152H 153H Any 1 16 406 14 356 8 203 4 38 111 12 40 315 7 0 178 43 152H Any 1 16 406 4 356 8 203 4 38 111 12 40 315 7 0 178 153H Any 1 16 406 4 610 10 254 0 75 19 22 5 572 14 5 368 en 152H 153H Any 1 16 406 4 610 9 229 0 75 19 22 5 572
57. 61 69 1567 152H BP 2 38 965 60 1524 17 431 33 88 861 1 75 45 61 69 1567 152H 152B 153H 153B NB NI 3 40 1016 4 2134 18 457 T 1 36 914 1 1295 14 356 0 75 19 49 5 1257 34 5 876 BP 34 40 1016 4 2134 18 457 480 152H 153B Any 3 40 1016 4 2134 18 457 152H 4 20 508 91 5 2324 20 508 152H 152B BPNB 4 35 889 91 5 2324 20 508 Rating 20 Hp 208V 25 Hp 240V 50 Hp O 480V 60 Hp 9 600V Rating 25 Hp G208V 30 Hp G240V 60 Hp 480V 75 Hp 600V 200 Hp O 240V AC 400 Hp G480V 500 Hp 600V www ab com catalogs 50 No Allen Bradley ublication 150 SGO09F EN P Bulletin 150 SMC 3 Smart Motor Controllers E www ab com catalogs Allen Bradley oo 53 Publication 150 SGOO9F EN P SMC Allen Bradley Rockwell Software Rockwell Automation and LISTEN THINK SOLVE are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road
58. 62 11 42 10 89 101 lbs 1041 1 596 9 346 2 179 kg pane 41 0 23 5 13 63 395 Ibs 1041 1 596 9 346 2 224 kg FOIS 41 0 23 5 13 63 495 Ibs Enclosed Type Line Connected Controllers Factory installed options may affect enclosure size requirements Exact dimensions can be obtained after order entry Please consult your local Rockwell Automation sales office or Allen Bradley distributor Dimensions are in millimeters inches Dimensions are not intended for manufacturing purposes C 4 E BE tU SS Figure 1 Wall Mount Figure 2 Wall Mount LIFTING ANGLE Figure 3 Floor Mount Figure 4 Floor Mount E www ab com catalogs Allen Bradley na 27 Publication 150 SGOO9F EN P Bulletin 150 SMC Flex Smart Motor Controllers Approximate Dimensions Dimensions in inches mm Controller Dimension Rating A Bulletin With Option Figure No A Width B Height C Depth D
59. 7 85 129 108 91 135 104 Steady State Heat 201 180 Dissipation with Control Controller Rating A 251 198 and Fan Power Watts 317 225 361 245 480 290 625 446 780 590 970 812 1250 1222 Auxiliary Contacts 19 20 Aux 1 29 30 Aux 2 31 32 Aux 3 33 34 Aux 4 Type of Control Circuit Electromagnetic relay Number of Contacts 1 Type of Contacts programmable N O N C Type of Current AC Rated Operational Current 3 120V AC 1 5 A 240V AC Conventional Thermal Current AC DC 5A Make Break VA 3600 360 AC 15 DC Utilization Category PTC Input Ratings Response Resistance 3400 Q 150 Q Reset Resistance 1600 O 100 Q Short Circuit Trip Resistance 25Q 10Q Max Voltage at PTC Terminals Rprc 4 KQ 7 5V Max Voltage at PTC Terminals Rprc open 30V Max No of Sensors 6 Max Cold Resistance of PTC Sensor Chain 1500 Q 800 ms Response Time Tach Input Heatsink fans can be powered by either 110 120V AC or 220 240V AC Allen Bradley www ab com catalogs Publication 150 SGOO9F EN P 0 5V DC 4 5V DC 10096 Speed 25 Bulletin 150 SMC Flex Smart Motor Controllers Specifications Environmental Operating Temperature Range 5 50 C 23 122 F open 5 40 C 23 104 F enclosed Storage and Transportation Temperature Range 20 475 C 4 167 F Altitude
60. C 3 monitors the SCR temperature by means of internal thermistors When the power poles maximum rated temperature is reached the microcomputer switches off the SMC a TEMP fault is indicated via LED and the 97 98 fault contact closes Phase Reversal Protection When enabled via a DIP switch 3 phase input power will be verified before starting If input power phasing is detected to be incorrect the start will be aborted and a fault indicated Phase Loss Open Load The unit will not attempt a start if there is a single phase condition on the line This protects from motor burnout during single phase starting www ab com catalogs 30 Publication 150 SG009F EN P Certifications cULus Listed Open Type File No E96956 Guides NMFT NMFT7 CSA Certified File No LR 1234 CE Marked Open Type per EMC and Low Voltage Directive CCC Certified Phase Imbalance The unit monitors for imbalance between phase currents To prevent motor damage the unit will trip if the difference between the minimum phase current and the maximum phase current exceeds 6596 for 3 s and a fault will be indicated Shorted SCR Prior to every start and during starting the unit will check all SCRs for shorts and unit load connections to the motor If there is a shorted SCR in the SMC 3 and or open load the start will be aborted and a shorted SCR or open load fault will be indicated This prevents damage from phase imbalance Push to Test The unit with
61. D 8 7 43 10 24V AC DCA 150 F25NBR 100 240V AC 50 60 Hz 150 F43NBD 14 9 74 20 24V AC DCA 150 F43NBR 100 240V AC 50 60 Hz 150 F60NBD 20 8 104 30 24V AC DCA 150 F60NBR 100 240V AC 50 60 Hz 150 F85NBD 29 4 147 40 24V AC DCA 150 F85NBR 100 240V AC 50 60 Hz 150 F108NBD 47 187 60 24V AC DCA 150 F108NBR 100 240V AC 50 60 Hz 150 F135NBD 59 234 75 24V AC DCA 150 F135NBR 100 240V AC 50 60 Hz 150 F201NBD 116 348 100 24V AC DCA 150 F201NBR 100 240V AC 50 60 Hz 150 F251NBD 145 435 150 24V AC DCA 150 F251NBR 100 240V AC 50 60 Hz 150 F317NBD 183 549 200 24V AC DCA 150 F317NBR 100 240V AC 50 60 Hz 150 F361NBD 208 625 200 24V AC DCA 150 F361NBR 100 240V AC 50 60 Hz 150 F480NBD 277 831 300 24V AC DCA 150 F480NBR 110 120V AC 50 60 Hz 150 F625NBE 283 850 300 230 240V AC 50 60 Hz 150 F625NBA 110 120V AC 50 60 Hz 150 F780NBE 300 900 300 230 240V AC 50 60 Hz 150 F780NBA 110 120V AC 50 60 Hz 150 F970NBE 400 1200 400 230 240V AC 50 60 Hz 150 F970NBA 110 120V AC 50 60 Hz 150 F1250NBE 533 1600 500 230 240V AC 50 60 Hz 150 F1250NBA technical support for further guidance A Separate 120V or 240V single phase power supply is required for fan operation Allen Bradley www ab com catalogs Publication 150 SGOO9F EN P Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type Controllers For u
62. Mtg Dim E Mtg Dim F Mtg Dim SMC Flex Combination Controller 16 406 24 610 10 254 22 5 572 14 5 368 5 25 152H 152B 153H 153B 1 0 75 19 BBNB NI 6 24 610 30 762 12 305 28 5 724 22 5 572 16 406 24 610 10 254 22 5 572 14 5 368 43 152H 152B 153H 153B BP 6_ 1 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 NI NB 30 762 38 965 14 356 36 5 927 28 5 724 153H 153B 16 406 24 610 10 254 22 5 572 14 5 368 T 152H 153H 153B 6 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 152H 152B 24 610 30 762 12 305 28 5 724 22 5 572 152H 152B 153H 153B NI NB 30 762 38 965 14 356 36 5 927 28 5 724 153H 153B 16 406 24 610 10 254 22 5 572 14 5 368 152H 152B 24 610 30 762 12 305 28 5 724 22 5 572 85 152H 153H 153B 6_ a 24 610 30 762 12 305 0 75 19 28 5 724 22 5 572 BP 24 610 30 762 12 305 28 5 724 22 5 572 BP 6_ 30 762 38 965 14 356 36 5 927 28 5 724 152H 152B 153B BPNB NI 30 762 38 965 14 356 36 5 927 28 5 724 30 762 38 965 14 356 36 5 927 28 5 724 152H 153H 108 6_ 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 152H 152B 153H 153B BP NB N 36 914 51 1295 14 356 49 5 1257 34 5 876 30 762 38 965 14 356 36 5 927 28 5 724 152H 153H 135 6_ 1 30 762 38 965 14 356 0 75 19 36 5 927 28 5 724 152H 152B 153H 153B BP NB N 36 914 51 1295 14 356 49 5 1257 34 5 876
63. P65 NEMA 4 12 Controllers For use with Line Connected Motors Continued Rated Voltage V AC 500 575 Open Type Line Connected IP65 Type 4 12 Enclosed Motor Current Max kW 50 Max Hp 60 Motors Non Combination Controllers A t Hz Hz Control Power Cat No Cat No 100 240V AC 50 60 Hz 150 C3NCD 150 C3FCD 1 449 1 5 0 75 2 24V AC DC 150 C3NCR 100 240V AC 50 60 Hz 150 C9NCD 150 C9FCD 3 9 5 5 d 5 24V AC DC 150 C9NCR 100 240V AC 50 60 Hz 150 C16NCD 150 C16FCD 5 3 16 75 6 010 24V AC DC 150 C16NCR 100 240V AC 50 60 Hz 150 C19NCD 150 C25FCD 6 3 19 11 7 5 15 24V AC DC 150 C19NCR 100 240V AC 50 60 Hz 150 C25NCD 150 C25FCD 9 2 25 15 7 5 20 24V AC DC 150 C25NCR 100 240V AC 50 60 Hz 150 C30NCD 150 C30FCD 10 30 18 5 10 25 24V AC DC 150 C30NCR 100 240V AC 50 60 Hz 150 C37NCD 150 C37FCD 12 3 37 22 15 90 24V AC DC 150 C37NCR 100 240V AC 50 60 Hz 150 C43NCD 150 C43FCD 14 3 43 22 15 40 24V AC DC 150 C43NCR 100 240V AC 50 60 Hz 150 C60NCD 150 C60FCD 20 60 37 20 50 24V AC DC 150 C60NCR 100 240V AC 50 60 Hz 150 C85NCD 150 C85FCD 28 3 85 55 30 75 24V AC DC 150 C85NCR 100 240V AC 50 60 Hz 150 C108NCD 150 C108FCD 27 108 75 60 100 24V AC DCA 150 C108NCR 100 240V AC 50 60 Hz 150 C135NCD 150 C135FCD 34
64. Selection Guide amp Allen Bradley SMC 3 and SMC Flex Smart Motor Controllers LISTEN SONE Rockwell i Allen Bradley Rockwell Software Automation Bulletin 150 Reduced Voltage Starters Product Overview Modes of Operation Bulletin 150 Solid State Reduced Voltage Starters The Allen Bradley SMCTM Smart Motor Controller product line offers a broad range of products for starting and stopping standard 3 phase squirrel cage induction motors and wye delta motors Tu TA SMC Flex SMC 3 200 690V 200 600V Features 1 1250 A 1 480 A Soft Start S S Kickstart S Current Limit S Dual Ramp Start Full Voltage DN ON nN no Energy Saver Soft Stop Pump Control Preset Slow Speed nn on Linear Acceleration Deceleration Torque Control SMBTM Smart Motor Braking Accu Stop Slow Speed with Braking Integrated Bypass Contactor o o o o o o o Integrated Motor Overload Protection Single phase Operation DPI Communication oo Metering Real Time Clock Motor Winding Heater Function Qs Diagnostic Faults and Alarms Motor and Starter Individual Bit Enable of Faults and Alarms Automatic Tuning of Motor Parameters Parameter Configuration Programming Human Interface Module HIM O Parameter Configruation Module Configuration Software Drives o E
65. art Option Input 2 rele O 0 4 oe 111 12 13 14 15 16 17 18 19 20 21 22 SMC Flex p Control Terminals Aux 1 23 24 25 26 27 28 29 30 31 32 33 34 LILI LT ug lp tj PTC TACH Ground Aux 2 Aux 3 Aux 4 Input Input Fault Customer supplied 99 www ab com catalogs Allen Bradley Publication 150 SGOO9F EN P Bulletin 150 SMC Flex Smart Motor Controllers Specifications Electrical Ratings Device Rating UL CSA NEMA IEC 480V 200 480V AC 1596 10 200 415V Rated Operation Voltage 600V 200 600V AC 15 1096 200 500V 690V 230 600V AC 1596 10 230 690V Y 15 10 480V 500V Rated Insulation Voltage 600V N A 500V 690V 690V 480V Rated Impulse Voltage 600V N A 6000V 690V 480V Dielectric Withstand 600V 2200V AC 2500V 690V Power Circuit 480V 1400V 1400V MUT Inverse 600V 1600V 1600V 690V 1800V 1800V Operating Frequency All 50 60 Hz Utilization Category 5 480 A MG 1 AC 53B 3 0 50 1750 625 1250 A MG 1 AC 53B 3 0 50 3550 5 85A IP20 Urbe me Against Electrical 49g A80 A N A IP2X with terminal covers 625 1250 A IPOO open device 480V amp 600V RC Snubber Network DV DT Protection 690V None i 480V amp 600V Metal Oxide Vari
66. bination package may differ from the controller based on the horsepower Consult your local Rockwell Automation sales office or Allen Bradley distributor Provided with Class J or L fuse clips as standard Available in IP54 Type 12 enclosure only www ab com catalogs 18 Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Control Options open and enclosed Cat No Description Modification Pump Control Provides smooth motor acceleration and deceleration reducing surges caused by the starting and stopping of centrifugal pumps Starting time is adjustable from 0 30 s and stopping time is adjustable from 0 120 s Braking Control Provides Smart Motor Braking SMB Accu Stop and Slow Speed with Braking Dx Enclosed Options Cat No Option Description Modification Start Stop Push Button 1 Start Stop Push Button with H O A Selector Switch 1F Soft Stop Push Buttont 1XA Push Buttons Pump Stop Push Buttont 1XB Slow Speed Push Buttont 1XC Brake Push Buttont 1XD Accu Stop Slow Speed Push Buttont 1XE Hand Off Auto Selector Switch 3 Selector Switch SMC Off Bypass Selector Switch 3B V Transformer Pilot Light Green Power On Indicator 4G Pilot Lights Transformer Pilot Light Red Run Indicator 4R Push to Test Pilot L
67. cted IP65 Type 4 12 Enclosed Rated Voltage Motor Current Motors x Non Combination Controllers V AC A t Max kW 50 Hz Max Hp 60 Hz Control Power Cat No Cat No 4 58 25 3 100 240V AC 50 60 Hz 150 F5NCD 150 F5FCD a 24V AC DCA 150 F5NCR 100 240V AC 50 60 Hz 150 F25NCD 150 F25FCD 5 25 15 20 24V AC DCA 150 F25NCR 100 240V AC 50 60 Hz 150 F43NCD 150 F43FCD 8 6 43 22 40 24V AC DCA 150 F43NCR 100 240V AC 50 60 Hz 150 F60NCD 150 F60FCD 12 60 37 50 24V AC DCA 150 F60NCR 100 240V AC 50 60 Hz 150 F85NCD 150 F85FCD 17 85 55 75 24V AC DCA 150 F85NCR 100 240V AC 50 60 Hz 150 F108NCD 150 F108FCD 27 108 75 100 24V AC DCA 150 F108NCR 100 240V AC 50 60 Hz 150 F135NCD 150 F135FCD 34 135 90 125 24V AC DCA 150 F135NCR 100 240V AC 50 60 Hz 150 F201NCD 150 F201FCD 67 201 132 200 24V AC DCA 150 F201NCR 500 575 100 240V AC 50 60 Hz 150 F251NCD 150 F251FCD 84 251 160 250 24V AC DCA 150 F251NCR 100 240V AC 50 60 Hz 150 F317NCD 150 F317FCD 106 317 200 300 24V AC DCA 150 F317NCR 100 240V AC 50 60 Hz 150 F361NCD 150 F361FCD 120 361 250 350 24V AC DCA 150 F361NCR 100 240V AC 50 60 Hz 150 F480NCD 150 F480FCD 160 480 315 500 24V AC DCA 150 F480NCR 110 120V AC 50 60 Hz 150 F625NCE 150 F625JCE 208 625 450 600 230 240V AC 50 60 Hz 150 F625NCA 150 F625JCA 110 120V AC 50 60 Hz 150 F780NCE 150 F780JCE 260 780 560 800 230 240V AC 50 60 Hz 150
68. d Mounted Protective 625 A 500 Hp 460V AC 8B Modules enclosed only 780 A 600 Hp 460V AC Load side MOVs are not available with Pump 970 A 800 Hp 460V AC and Braking options or on delta connected 1250 A 1000 Hp 460V AC motors MOVs can be field installed for open type units Combination 1 52H F480 a b a Bulletin Number Description Solid State Controller with Fusible Disconnect Solid State Controller with Fusible Disconnect and Isolation Contactor C Enclosure Type F NEMA Type 4 12 IP65 J NEMA Type 12 IP54 e Control Options Code Description Standard Pump Control Braking Control Solid State Controller with Circuit Breaker Solid State Controller with Circuit Breaker and Isolation Contactor g Options see page 19 for a full listing Line Voltage 120V AC Control Voltage Code Description 8L Code Description 200 208V AC 3 phase 50 and 60 Hz 8M 230V AC 3 phase 50 and 60 Hz 8B Line and Load Mounted Protective 400 460V AC 3 phase 50 and 60 Hz Modules 500 575V AC 3 phase 50 and 60 Hz Load side MOVs are not available with Pump and Braking options or when used with inside the delta connections Line Mounted Protective Module Load Mounted Protective Module Controller Ratings F5 5 A 3 Hp 460V AC 25 A 15 Hp 460V AC F43 43 A 30 Hp 6 460V AC F60 6
69. ed during the acceleration ramp time which is user adjustable 100 Initial Torque Ramp Time Percent Voltage lt Sat 994 Rn FrF Time in Seconds Selectable Kickstart The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started It is intended to provide a current pulse for a selected period of time o 100 Kickstart 3 i o gt g initial 5 Torque n Start a Run gt Time s Current Limit Start This method provides current limit start and is used when it is necessary to limit the maximum starting current The starting current is user adjustable The current limit stating time is user adjustable Dual Ramp Start This starting method is useful on applications with varying loads starting torque and start time requirements Dual Ramp Start offers the user the ability to select between two separate start profiles with separately adjustable ramp times and initial torque settings 100 o _Initial gt Torque s 2 gt _Initial 8 Torque D 1 n lt Start 1 Run 1 gt lt Start 2 Run 2 Time s Full Voltage Start This method is used in applications requiring across the line starting The SMC controller performs like a solid state contactor Full inrush current and locked rotor torque are realized The SMC ma
70. elector Switch 3 Pilot Light Transformer Pilot Light Red Run Indicator 4R Control Circuit Transformer Control Circuit Transformer fused primary and secondary 6P 480V Line Side Protective Module 3 480 A aL 600V Line Side Protective Module 3 480A 480V Load Side Protective Module 43 480 A Protective Module 8M 600V Load Side Protective Module 43 480 A 480V Both Line and Load Side Protective Module 43 480 A 88 600V Both Line and Load Side Protective Module 43 480 A 1 N O auxiliary contact for 3 480 A units 90 Auxiliary Contacts 2 N O auxiliary contacts for 3 480 A units 900 1 N O and 1 N C auxiliary contacts for 3 480 A units 901 N O disconnect auxiliary mounted on the operating mechanism 98 Disconnect Auxiliary N C disconnect auxiliary mounted on the operating mechanism 99 5 43 AS 60 85 AS NEMA Bypass Contactor 108 135 AS NB and Overload Relay 201 251 A 317 361A 480A 5 43 AS 60 85 AS MCS Bypass Contactor 108 135 AS BP and Overload Relay 201 251A 317 361A 480A Available only as a modified standard Accessories Auxiliary Contact Blocks Description N O N C Connection Diagram Cat No Y non 150 CA10 4 Auxiliary Contact Blocks for side mounting with x sequence terminal designations 150 CA20 B 1 and 2 pole 150 CA01 cy Quick and easy mounting without tools Farmer 150 CA11 Y One block per device only Form C Fans Description For Use With Pkg Q
71. en using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation technical support for further guidance These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string A Separate 120V or 240V single phase power supply is required for fan operation Line and load termination are provided as standard Available in IP54 Type 12 enclosure only www ab com catalogs Publication 150 SG009F EN P 9 Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 Type 4 12 Controllers For use with Line Connected Motors Continued Enclosures other than those listed are available consult your local Rockwell Automation sales office or Allen Bradley distributor Open Type Line Connected IP65 Type 4 12 Enclosed Rated Voltage Motor Current Max kW Max Hp Motors Non Combination Controllers V AC A 50 Hz 60 Hz Control Power Cat No Cat No 1 5 14 1 100 240V AC 50 60 Hz 150 F5NBD 150 F5FAD e 24V AC DCA 150 F5NBR 100 240V AC 50 60 Hz 150 F25NBD 150 F25FAD 5 25 5 5 eb 24V AC DCA 150
72. gs Publication 150 SGOO9F EN P 15 Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type Controllers For use with Delta Connected Motors Continued Rated Voltage Open Type V AC Motor Current A Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 F5NCD 1 7 8 7 5 5 7 5 24V AC DCA 150 F5NCR 100 240V AC 50 60 Hz 150 F25NCD 8 7 48 15 40 24V AC DCA 150 F25NCR 100 240V AC 50 60 Hz 150 F43NCD 14 9 74 45 60 24V AC DCA 150 F43NCR 100 240V AC 50 60 Hz 150 F60NCD 20 8 104 55 100 24V AC DCA 150 F60NCR 100 240V AC 50 60 Hz 150 F85NCD 29 4 147 90 150 24V AC DCA 150 F85NCR 100 240V AC 50 60 Hz 150 F108NCD 47 187 132 150 24V AC DCA 150 F108NCR 100 240V AC 50 60 Hz 150 F135NCD 59 234 160 200 24V AC DCA 150 F135NCR 100 240V AC 50 60 Hz 150 F201NCD 116 348 250 300 24V AC DCA 150 F201NCR 500 575 100 240V AC 50 60 Hz 150 F251NCD 145 435 315 400 24V AC DCA 150 F251NCR 100 240V AC 50 60 Hz 150 F317NCD 183 549 400 500 24V AC DCA 150 F317NCR 100 240V AC 50 60 Hz 150 F361NCD 208 625 450 600 24V AC DCA 150 F361NCR 100 240V AC 50 60 Hz 150 F480NCD 277 831 560 900 24V AC DCA 150 F480NCR 110 120V AC 50 60 Hz 150 F625NCE 283 850 560 900 230 240V AC 50 60 Hz 150 F625NCA 110 120V AC 50 60 Hz 150 F780NCE 300 900 630 900 230 240V AC 50 60 Hz 150 F780NCA 110 120V AC 50 60 Hz 150 F970NCE 400 1200 800 1300 230 240V AC
73. ight Red Run Indicator 5R Control Circuit Transformer fused primary and secondary 6P Additional 100VA Control Circuit Transformer fused primary and secondary 6PX Control Circuit Transformer 1000VA Control Circuit Transformer fused primary and secondary 6PK 1600VA Control Circuit Transformer fused primary and secondary 6PL 2000VA Control Circuit Transformer fused primary and secondary 6PM 480V Line Side Protective Module 600V Line Side Protective Module a isis Medulss 480V Load Side propels Module 8M 600V Load Side Protective Module 480V Both Line and Load Side Protective Modules 600V Both Line and Load Side Protective Modules e Human Interface Module Door mounted Full Numeric Type 4 12 HC3 RS 485 208 DeviceNet 20D Communication Module Ethernet IP 20E Control Net 20C ProfiBUS 20P N O disconnect auxiliary mounted on operating mechanism 98 Disconnect Auxiliary N C disconnect auxiliary mounted on operating mechanism 99 E me Internal N O circuit breaker auxiliary 98X Circuit Breaker Auxiliary Internal N C circuit breaker auxiliary 99X Service Entrance Label Service Entrance Label SEL Oil Pump Starter Bulletin 509 NEMA Size 1starter and Bulletin 592 solid state overload OPS Add the designated letter to the end of the cat no Example To add the Pump Control option Cat No 150 F361NBDB or Cat No 152H F361FBDB 57 t Option push buttons are available only when the
74. informative text Controller set up can be performed quickly and easily without the use of a reference manual Parameters are arranged in an organized four level menu structure for ease of programming and fast access to parameters Keypad Programming Programming of parameters is accomplished through a five button keypad on the front of the SMC Flex controller The five buttons include up and down arrows an Enter button a Select button and an Escape button The user needs only to enter the correct sequence of keystrokes for programming the SMC Flex controller Auxiliary Contacts Four fully programmable hard contacts are furnished as standard with the SMC Flex controller Aux 1 Aux 2 Aux 3 Aux 4 N O N C Normal Up to Speed External Bypass Fault Alarm Network Network 1 0 The SMC Flex can have up to two inputs and four outputs controlled via a communication network The output contacts use the auxiliary contacts Ground Fault Input The SMC Flex can monitor for ground fault conditions An external core balance current transformer is reguired for this function See SMC Flex User Manual for additional information Tach Input A motor tachometer is reguired for the Linear Speed Start mode Please see the Specifications section on page 22 for tachometer characteristics PTC Input A motor PTC input can be monitored by the SMC Flex In the event of a fault the SMC Flex will shut down and indicate a motor PTC fault www ab c
75. ions requiring an extended coast to rest The voltage ramp down time is user adjustable The load will stop when the voltage drops to a point where the load torque is greater than the motor torque 100 pc 2 E Coast to Rest E L gt h a op amp Initial X 5 Torque N a E Start Run Soft Stop Time s Pump Control Start and Stopt This option is used to reduce surges during the starting and stopping of a centrifugal pump by smoothly accelerating and decelerating the motor The microprocessor analyzes the motor variables and generates commands which control motor torque and reduce the possibility of surges occurring in the system 100 Motor Speed Pump Start Run gt Pump Stop Time s Allen Bradley SMB Smart Motor Braking This option provides motor braking for applications that require the motor to stop faster than a coast to rest Braking control with automatic zero speed shut off is fully integrated into the compact design of the SMC controller This design facilitates a clean straight forward installation and eliminates the requirement for additional hardware such as braking contactors resistors timers and speed sensors The microprocessor based braking system applies braking current to a standard squirrel cage induction motor The strength of the braking current is user programmable
76. le to connect to the SMC Flex Allen Bradley www ab com catalogs Publication 150 SG009F EN P USB 1203 USB 21 Bulletin 150 SMC Flex Smart Motor Controllers Specifications Specifications Functional Design Specifications installati Power Wiring Standard squirrel cage induction motor or a Wye Delta six lead motor nstallation Control Wiring 2 and 3 wire control for a wide variety of applications Keypad Front keypad and backlit LCD display Setup Software Parameter values can be downloaded to the SMC Flex Controller with DriveTools programming software and the Cat No 20 COMM DPI communication module Communications One DPI provided for connection to optional human interface and communication modules Soft Start Current Limit Start Dual Ramp Starting and Stopping Modes Full Voltage Linear Speed Acceleration Standard Features Preset Slow Speed Soft Stop Power loss line fault voltage unbalance excessive starts hour phase reversal Protection and Diagnostics undervoltage overvoltage controller temp stall jam open gate overload underload communication fault Meterin Amps volts kW KWH MW MWH elapsed time power factor motor thermal capacity 9 Usage Alarm Contact Overload underload undervoltage overvoltage unbalance jam stall and ground fault Status Indication Stopped starting stopping at speed alarm and fault Four fully programmable contacts as normal
77. letin 150 SMC Flex Smart Motor Controllers Overview y y FS RQ OL NN fap ge OU single controller 1 1250 A Range Seven Standard Start Modes Features E Built in SCR Bypass Run Contactor N Protection CT on each Phase Metering resistive loads Bulletin 150 SMC Flex Smart Motor Controller The SMC Flex controller provides microprocessor controlled starting for standard 3 phase squirrel cage induction or Wye Delta 6 lead motors Seven standard modes of operation are available within a Options Include Pump Control and Braking Control a e Built in Electronic Motor Overload The SMC Flex controller is available for motors rated 1 1250 A 200 480V AC 200 600V AC or 230 690V AC 50 60 Hz In addition to motors the SMC Flex controller can be used to control Table of Contents Features this page Cat No Explanation 8 Product Selection 9 Options Accessories Specifications 22 Approx Dims 27 DPI Communication LCD Display Keypad Programming Four Programmable Auxiliary Contacts This catalog is based on the minimum information needed to select an SMC soft starter for applications with low starting torque requirements For product selection involving loads with high starting torque requirements large fan rock crusher chipper etc use of the free tools available from the Rockwell Automation Website is rec
78. of 0 99 seconds Voltage Unbalance Protection Voltage unbalance is detected by monitoring the 3 phase supply voltage magnitudes in conjunction with the rotational relationship of the three phases The controller will halt motor operation when the calculated voltage unbalance reaches the user programmed trip level The voltage unbalance trip level is programmable from 0 25 unbalance Excessive Starts Per Hour The SMC Flex controller allows the user to program the allowed number of starts per hour up to 99 This helps eliminate motor Stress caused by repeated starting during a short time period Metering Power monitoring parameters include 3 phase current Power Factor e 3 phase voltage Motor thermal capacity usage Power in kW or mW Elapsed time Power usage in KWH or mWH Note The motor thermal capacity usage allows the user to monitor the amount of overload thermal capacity usage before the SMC Flex controller s built in electronic overload trips Built in DPI Communication Capabilities A serial interface port is provided as standard which allows connection to a Bulletin 20 Human Interface Module and a variety of Bulletin 20 COMM Communication Modules This includes Allen Bradley Remote 1 0 DeviceNet ControlNet Ethernet ProfiBUS Interbus and RS485 DF1 Allen Bradley LCD Display The SMC Flex controller s three line 16 character backlit LCD display provides parameter identification using clear
79. om catalogs Publication 150 SGOO9F EN P Bulletin 150 SMC Flex Smart Motor Controllers Catalog Number Explanation Open and Non Combination 150 F135 F B D B 8L a C Control Voltage Bulletin Number Enclosure Type Code Description Code Description Code Description D 100 240V AC 5 480 A units Solid State Controller NEMA Type 4 12 IP65 24V AC DC 5 480 A units Open Only Enclosed Solid State Controller with Non Combination Only 110 120V AC 625 1250 A units Isolation Contactor NEMA Type 12 1P54 230 240V AC 625 1250 A units Open e Controller Ratings Code Description Input Line Voltage Options Select Only One 5 A 3 Hp 460V AC 25 A 15 Hp G 460V AC Description Standard 43 A 30 Hp amp 460V AC B 200 460V AC 3 phase 50 and 60 Hz Pump Control 60 A 40 Hp 460V AC 200 575V AC 3 phase 50 and 60 Hz Braking Control 85 A 60 Hp G 460V AC 230 690V AC 3 phase 50 and 60 Hz g 108 A 75 Hp 460V AC Open Only 108 A and above 135 A 100 Hp 460V AC Non Combination Enclosed Only see page 19 for a full listing 201 A 150 Hp Q 460V AC 200 208V AC 3 phase 50 and 60 Hz E Description 8L Line Mounted Protective Module 317 A 250 Hp 460V AC 400 460V AC 3 phase 50 and 60 Hz enclosed only 361 A 300 Hp 460V AC 500 575V AC 3 phase 50 and 60 Hz Load Mounted Protective Module eM enclosed only 480 A 400 Hp 460V AC i ai asda FI ine and Loa
80. ommended http www ab com industrialcontrols products solid state motor control software Standards Compliance UL 508 CSA C22 2 No 14 EN IEC 60947 1 EN IEC 60947 4 2 Modes of Operation The SMC Flex controller provides the following modes of operation as standard Soft Start Selectable Kickstart Current Limit Start Dual Ramp Start Full Voltage Start Linear Speed Acceleration Preset Slow Speed Soft Stop Certifications cULus Listed Open Type File No E96956 Guides NMFT NMFT7 CSA Certified File No LR 1234 CE Marked CCC Certified Optional Modes of Operation Pump Control Start and Stop Braking Control SMB Smart Motor Braking Slow Speed with Braking Accu Stop Note For detailed information about the different modes of operation see page 4 Description of Features Electronic Motor Overload Protection The SMC Flex controller incorporates as standard electronic motor overload protection This overload protection is accomplished electronically with an Pt algorithm When coordinated with the proper short circuit protection overload protection is intended to protect the motor motor controller and power wiring against overheating caused by excessive overcurrent The SMC Flex controller meets applicable requirements as a motor overload protective device The controller s overload protection is programmable providing the user with flexibility The overload trip class
81. or Circuit Breaker Continued IP65 Type 4 12 Enclosed IP65 Type 4 12 Enclosed Combination Controllers with Combination Controllers Rated Voltage Current Fusible Disconnect with Circuit Breaker V AC Rating A kW Hp Cat No Cat No 3 0 37 0 5 152H C3FBD 33 153H C3FBD 33 3 0 55 0 75 152H C3FBD 34 153H C3FBD 34 3 0 75 1 152H C3FBD 35 153H C3FBD 35 9 1 1 1 5 152H C9FBD 36 153H C9FBD 36 9 1 5 2 152H C9FBD 37 153H C9FBD 37 9 2 2 3 152H C9FBD 38 153H C9FBD 38 16 3 7 5 152H C16FBD 39 153H C16FBD 39 16 5 5 7 5 152H C16FBD 40 153H C16FBD 40 25 7 5 10 152H C25FBD 41 153H C25FBD 41 30 11 15 152H C30FBD 42 153H C30FBD 42 37 15 20 152H C37FBD 43 153H C37FBD 43 460 43 18 5 25 152H C43FBD 44 153H C43FBD 44 43 22 30 152H C43FBD 45 153H C43FBD 45 60 30 40 152H C60FBD 46 153H C60FBD 46 85 37 50 152H C85FBD 47 153H C85FBD 47 85 45 60 152H C85FBD 48 153H C85FBD 48 108 55 75 152H C108FBD 49 153H C108FBD 49 135 75 100 152H C135FBD 50 153H C135FBD 50 201 110 150 152H C201FBD 52 153H C201FBD 52 251 132 200 152H C251FBD 54 153H C251FBD 54 317 160 250 152H C317FBD 56 153H C317FBD 56 361 200 300 152H C361FBD 57 153H C361FBD 57 480 250 400 152H C480JBD 59 153H C480FBD 59 3 0 55 0 75 152H C3FCD 34 153H C3FCD 34 3 0 75 1 152H C3FCD 35 153H C3FCD 35 9 1 1 1 5 152H C9FCD 36 153H C9FCD 36 9 1 5 2 152H C9FCD 37
82. rasa es ll Lgs 136 a pas 1156 R SMC 3 1 Power connections H3_H2 Hi xi x AA AS A Groun IH H3 H2 Ho E Stop H1 HA Tcr Trans i Ground Bp or X x2 E Stop FOR t REV R m Lo E Power E ur o o N a Connections s art i EN TT R t KM2 KMI KM2N KMf F KM1 KM2 T Vedat A2 ONI N2 997 098 o13 oddl EJ al da da SINt OIN2 997 998 013 oddl OVLD Faut AUX 1 E el UU J L SMC 3 Control Terminals 4 OVLD Fault AUX 1 a AA J www ab com catalogs Allen Bradley 45 Publication 150 SG009F EN P Bulletin 150 SMC 3 Smart Motor Controllers Specifications Standard Features Selectable Start Times 2 5 10 15 20 25 or 30s Selectable Initial Torque 096 2596 3596 and 6596 of locked rotor torque Selectable Current Limit 15096 25096 35096 and 45096 of full load current Selectable Kick Start 45096 FLA 0 0 5 1 0 or 1 5 s Selectable Soft Stop Off 10096 20096 or 30096 of the start time setting when wired Electrical Ratings UL CSA NEMA IEC 200 480V AC 200 480V 400V Rated Operation Voltage 200 600V AC 500V 500V Rated Insulation Voltage 600V AC 500V Dielectric Withstand 2200V AC 2500V Repetitive Peak 200 480V AC 1400V 200 480V 1400V
83. se with Delta Connected Motors Continued Rated Voltage V AC 230 Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Open Type Motor Current A Max kW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 F5NBD 1 7 8 7 2 2 2 24V AC DCA 150 F5NBR 100 240V AC 50 60 Hz 150 F25NBD 8 7 48 11 15 24V AC DCA 150 F25NBR 100 240V AC 50 60 Hz 150 F43NBD 14 9 74 22 25 24V AC DCA 150 F43NBR 100 240V AC 50 60 Hz 150 F60NBD 20 8 104 30 40 24V AC DCA 150 F60NBR 100 240V AC 50 60 Hz 150 F85NBD 29 4 147 45 50 24V AC DCA 150 F85NBR 100 240V AC 50 60 Hz 150 F108NBD 47 187 55 60 24V AC DCA 150 F108NBR 100 240V AC 50 60 Hz 150 F135NBD 59 234 75 75 24V AC DCA 150 F135NBR 100 240V AC 50 60 Hz 150 F201NBD 116 348 110 125 24V AC DCA 150 F201NBR 100 240V AC 50 60 Hz 150 F251NBD 145 435 132 150 24V AC DCA 150 F251NBR 100 240V AC 50 60 Hz 150 F317NBD 183 549 160 200 24V AC DCA 150 F317NBR 100 240V AC 50 60 Hz 150 F361NBD 208 625 200 250 24V AC DCA 150 F361NBR 100 240V AC 50 60 Hz 150 F480NBD 277 831 250 350 24V AC DCA 150 F480NBR 110 120V AC 50 60 Hz 150 F625NBE 283 850 250 350 230 240V AC 50 60 Hz 150 F625NBA 110 120V AC 50 60 Hz 150 F780NBE 300 900 250 350 230 240V AC 50 60 Hz 150 F780NBA 110
84. ses in parallel Two fuses in parallel 1238 BW AO7OURD33xxx1250 6 6URD33xxx1250 Consult local codes for proper sizing of short circuit protection Non time delay fuses K5 5 480V 8 7 831 A devices Class L 625 1250V 850 1600 A devices High capacity fault rating when used with time delay class CC J or L fuses Type 1 performance protection indicates that under a short circuit condition the fused or circuit breaker protected starter shall cause no danger to persons or installation but may not be suitable for further service without repair or replacement A For short circuit current rating SCCR for enclosed panel with external bypass or isolation contactor see the Industrial Controls catalog website www ab com catalogs www ab com catalogs 24 Publication 150 SGOO9F EN P Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Specifications Electrical Ratings 120 240V AC Transformer 75 VA 24V AC Transformer 130 VA Inrush Current 5A Inrush Time 250 ms 1 480A Transient Watts 60 W Control Module 24V DC Transient Time 500 ms Power Steady State Watts 24 W Requirements Minimum Allen Bradley 1606 XLP50E Power Supply 625 1250 A 751 VA recommended 800 VA 5 135 A 20 VA Heatsink Fanta 317 480 6D VA 625 1250 A 150 VA 5 70 25 70 43 81 60 9
85. stors 220 Joules Transient Protection 690V None Rated icinal Vai 5 480A 100 240V AC or 24V AC DC a ET 110 120V AC and 230 240V AC Rated Insulation Voltage All N A 240V Rated Impulse Voltage All N A 3000V Dielectric Withstand All 1600V AC 2000V Control Circuit Operating Frequency All 50 60 Hz Input onstate voltage minimum 85V AC 19 2V DC 20 4V AC Input onstate current 20 mA 120V AC 40 mA 6 240V AC 7 6 mA 6 24V AC DC Input offstate voltage maximum 50V AC 10V DC 12V AC Input offstate current input offstate lt 10 mA AC 3 mA DC voltage 690V power is only available with 100 240V control Allen Bradley www ab com catalogs Publication 150 SGOO9F EN P 23 Bulletin 150 SMC Flex Smart Motor Controllers Specifications Electrical Ratings SCPD Performance 200 600V Type 14A SCCR List Max Standard Max Standard Max Standard Max Circuit Max High Max Fuse A Available Fault Fuse Alt Available Fault Breaker A Fault 8 5 5 kA 20 5 kA 20 70 kA 10 25 5 kA 100 5 kA 100 70 kA 50 43 10 kA 150 10 kA 150 70 kA 90 60 10 kA 225 10 kA 225 70 kA 125 85 10 kA 300 10 kA 300 70 kA 175 108 10 kA 400 10 kA 300 70 kA 200 135 10 kA 500 10 kA 400 70 kA 225 Line Device Operational 201 18 kA 600 18 kA 600 70 kA 350 Current Rating A 251 18 kA 700 18 kA 700 70 kA 400 317 30 kA 800 30 kA 800 69 kA 5
86. t Electromagnetic relay TB 23 24 Number of Contacts 1 Normal Up to Speed Type of Contacts Normally Open N O TB 33 34 Type of Current AC DC Normal Up to Speed Rated Operational Current max 1 5 A 120V AC 0 75A 240V AC 1 17 A 24V DC Conventional Thermal Current in 25A Make Break VA 1800 180V AC 28V DC resistive Type of Control Circuit B300 R300 AC 15 DC 13 Type of Control Circuit Electromagnetic relay Number of Contacts 1 TB 11 12 Type of Contacts Normally Closed N C Normal Up to Speed Type of Current AC DC Rated Operational Current max 3 A 120V AC 1 5A 240V AC 1 17 A 24V DC Conventional Thermal Current An 5A Make Break VA 3600 360VA 28VA DC resistive Overvoltage category ll when either control or auxiliary circuit is wired to a SELV or PELV circuit Environmental Operating Temperature Range 5 50 C 23 122 F open 5 40 C 23 104 F enclosed Storage and Transportation Temperature Range 25 485 C 13 185 F Altitude 2000 m 6560 ft Humidity 5 9596 non condensing Pollution Degree 2 Type of Protection Resistance to Vibration Operational Mechanical Ratings IP2X 1 0 G Peak 0 15 mm 0 006 in displacement Non Operational 2 5 G Peak 0 38 mm 0 015 in displacement i Operational 15G Resistance to Shock Non Operational 30G 2 5 25 mm2 14 4 AWG
87. tarting mode Contact Rockwell Automation technical support for further guidance These controllers require a separate 100 240V 50 60 Hz single phase control source To add a control circuit transformer to the enclosure add the appropriate option code to the catalog string A Separate 120V or 240V single phase power supply is required for fan operation Line and load termination are provided as standard To be used only in a Y type system Available in IP54 Type 12 enclosure only io www ab com catalogs Allen Bradley Publication 150 SGOO9F EN P Open Type Controllers For use with Delta Connected Motors Rated Voltage V AC 200 208 Controllers rated 108 A and greater are not equipped with line and load terminal lugs See page 20 for terminal lug kits Motor FLA rating should fall within specified current range for unit to operate properly Special consideration should be given when using a motor with a potentially high starting current greater than ten times motor FLA with the SMC Flex in the Full Voltage starting mode Contact Rockwell Automation Bulletin 150 SMC Flex Smart Motor Controllers Product Selection Open Type Motor Current A Max KW 50 Hz Max Hp 60 Hz Control Power Cat No 100 240V AC 50 60 Hz 150 F5NBD SE 24V AC DCA 150 F5NBR 100 240V AC 50 60 Hz 150 F25NB
88. tric Withstand 1500V AC 2000V Overvoltage Category Il Ile Operating Frequency 50 60 Hz 50 60 Hz Utilization Category D300 D300 AC 15 DC Type of Control Circuit Electromagnetic relay Number of Contacts 1 Type of Contacts Normally Open N O LEID Type of Current AC DC Rated Operational Current max 0 6 A 120V and 0 3 A 240V Conventional Thermal Current in 1A Make Break VA 432 72 TB 13 14 Aux 1 Normal Up to Speed Type of Control Circuit Electromagnetic relay Number of Contacts 1 Type of Contacts Normally Open N O Type of Current AC DC Rated Operational Current max 0 6 A 120V and 0 3 A 240V Conventional Thermal Current Jin 1A Make Break VA 432 72 Overvoltage category ll when either control or auxiliary circuit is wired to a SELV or PELV circuit Allen Bradley www ab com catalogs Publication 150 SGOO9F EN P 47 Bulletin 150 SMC 3 Smart Motor Controllers Specifications Electrical Ratings Side Mount Auxiliary Contacts UL CSA NEMA IEC Rated Operational Voltage 250V AC 30V DC 250V AC 30V DC Rated Insulation Voltage 250V 250V AC Rated Impulse Voltage 2 5 kV 4 KV Dielectric Withstand 1500V AC 2000V AC Overvoltage Category Il lb Operating Frequency 50 60 Hz 50 60 Hz Utilization Category C300 R150 AC 15 DC 13 Type of Control Circui
89. ty Cat No a Optional 150 C3 37 150 CF64 150 C43 85 150 CF147 Fan 150 C108 150 C135 1 41391 801 03 Field installed Replacement 150 C201 150 C251 41391 801 01 150 C317 C480 41391 801 02 Connecting Modules Description For Use With Pkg Qty Cat No Connects 140 M C to 150 C3 25 1 ce Connecting modules to 140 M Electrical interconnection between SMC 3 and 140 M i to 1 150 CD25 Motor protector and SMC must be mounted separately Connects 140 M F to 150 C3 37 1 150 CF45 Connects 100 C09 23 to Connecting modules to 100 C 150 C3 19 1 150 Cl23 Electrical interconnection between SMC 3 and 100 C Contactor and SMC must be mounted separately Fe d to 1 150 CI37 42 www ab com catalogs Publication 150 SGOO9F EN P wy Allen Bradley Bulletin 150 SMC 3 Smart Motor Controllers Accessories Protective Modules Protective modules must not be placed on the load side of a device when using an inside the delta connection Description For Use With Pkg Qty Cat No 150 C3 37NB 1 150 C84 480V Protective Module 150 C43 85NB line and or load 1 150 C84P 150 C108 480NB line and or load 1 150 F84L 150 C3 37NC 1 150 C86 600V Protective Module 150 C43 85NC line and or load 1 150 C86P 150 C108 480NC line and or load 1 150 F86L IEC Terminal Covers Description For Use With Pkg Qty Cat No MEE 15
90. uit transformer to appropriate option code to the catalog string A Separate 120V or 240V single phase is required for fan operation Allen Bradley www ab com catalogs Publication 150 SG009F EN P he enclosure add the 33 Bulletin 150 SMC 3 Smart Motor Controllers Product Selection Open Type and Non Combination Enclosed IP65 NEMA 4 12 Controllers For use with Line Connected Motors Continued Open Type Line Connected IP65 Type 4 12 Enclosed Rated Voltage Motor Current Max KW 50 Max Hp 60 Motors Non Combination Controllers V AC A t Hz Hz Control Power Cat No Cat No 100 240V AC 50 60 Hz 150 C3NBD 150 C3FBD 1 3 1 1 0 5 1 5 24V AC DC 150 C3NBR EE 100 240V AC 50 60 Hz 150 C9NBD 150 C9FBD ur ERE 24V AC DC 150 C9NBR 100 240V AC 50 60 Hz 150 C16NBD 150 C16FBD 5 3 16 7 5 5 10 24V AC DC 150 C16NBR 100 240V AC 50 60 Hz 150 C19NBD 150 C19NBR 6 3 19 7 5 5 10 24V AC DC 150 C19NBR 100 240V AC 50 60 Hz 150 C25NBD 150 C25NBR 9 2 25 11 7 5 15 24V AC DC 150 C25NBR 100 240V AC 50 60 Hz 150 C30NBD 150 C30FBD 10 30 15 7 5 20 24V AC DC 150 C30NBR 100 240V AC 50 60 Hz 150 C37NBD 150 C37FBD 12 3 37 18 5 10 25 24V AC DC 150 C37NBR 100 240V AC 50 60 Hz 150 C43NBD 150 C43FBD 14 3 43 22 10 30 24V AC DC 150 C43NBR
91. ules must be ordered Terminal Lug Kits 108 1250 A Total No of Line Controller Terminal Lugs Current Possible Each Side Rating A Wire Size Line Side Load Side Pkg Qty Cat No 108 135A 3 3 201 251A 6 mm 120 mme 6 6 s 317 480A Y y iir 6 6 199 LG1 625 780 2 0 500 MCM AWG 6 6 3 100 DL630 970 4 0 500 MCM AWG 3 3 100 DL860 2 0 500 MCM AWG 3 3 100 DL630 12504 4 0 500 MCM AWG 3 3 100 DL860 Line and Load terminals are provided as standard on enclosed SMCs 5 85 A units have box lugs standard No additional lugs are required The 1250 A device requires 1 100 DL630 and 1 100 DL860 per connection A When a multi conductor lug is required refer to the User Manual for appropriate lug catalog number 20 Publication 150 SGOO9F EN P www ab com catalogs Allen Bradley Bulletin 150 SMC Flex Smart Motor Controllers Accessories IEC Terminal Covers Field Modification Descriptions Package Quantity Cat No uM M S obs ii an covers for 108 and 135 A devices 1 150 TC1 NA i WM Y FAC RE pd us covers for 201 251 A devices 1 150 TC2 EE 1 In og WE IEC line or load terminal covers for 317 480 A devices Dead front protection L dues 8 5 85 A units have terminal guards standard No additional terminal guards are required Human Interface
92. xperience locked rotor currents and develop high torque levels in the event of a stall or a jam These conditions can result in winding insulation breakdown or mechanical damage to the connected load The SMC Flex controller provides both stall protection and jam detection for enhanced motor and system protection Stall protection allows the user to program a maximum stall protection delay time from 0 10 seconds The stall protection delay time is in addition to the programmed start time and begins only after the start time has timed out If the controller senses that the motor is stalled it will shut down after the delay period has expired Jam detection allows the user to determine the motor jam detection level as a percentage of the motor s full load current rating To prevent nuisance tripping a jam detection delay time from 0 0 99 0 seconds can be programmed This allows the user to select the time delay required before the SMC Flex controller will trip on a motor jam condition The motor current must remain above the jam detection level during the delay time Jam detection is active only after the motor has reached full speed Underload Protection Utilizing the underload protection of the SMC Flex controller motor operation can be halted if a drop in current is sensed The SMC Flex controller provides an adjustable underload trip setting from 0 9996 of the programmed motor full load current rating with an adjustable trip delay time
93. xplorer and Drives Executive Digital I O Expansion ModuleS Ground Fault CT PTC ModuleS Network Communications O ur Inside Delta Connection S S Standards Compliance CE Marked per Low Voltage Directive 73 23 EEC 93 68 EEC S S CSA Certified File No LR 1234 UL Listed File No E96956 Product Selection Page 6 Page 30 S Standard Feature O Optional Feature Starter does not include a configuration device as standard Option using a Bulletin 1410 motor winding heater With removable terminal block Starter ships with 2 DC inputs and 2 relay outputs as standard The starter is fully solid state no integral bypass An external bypass contactor can be added as an option amp Note Information for this product line is available on the Industrial Controls catalog web site www ab com catalogs A Note Information for this product line is available in publication 150 SG010 or on the Industrial Controls catalog web site www ab com catalogs E www ab com catalogs Allen Bradley He os 3 Publication 150 SGOO9F EN P Bulletin 150 Reduced Voltage Starters Modes of Operation Modes of Operation The SMC controllers provide the following modes of operation Soft Start This method covers the most general applications The motor is given an initial torque setting which is user adjustable From the initial torque level the output voltage to the motor is steplessly increas
94. y be programmed to provide full voltage start in which the output voltage to the motor reaches full voltage 100 Percent Voltage Time s Linear Speed Acceleration With this type of acceleration mode a closed loop feedback system maintains the motor acceleration at a constant rate The required feedback signal is provided by a DC tachometer coupled to the motor tachometer supplied by user 0 5V DC 4 5V DC 100 speed Kickstart is available with this mode www ab com catalogs 4 Publication 150 SGOO9F EN P _ 600 S 100 S lb a 9 T o B ba AO 2 D 2 o E AS ed ied a et O A RARA o 5 a e 50 4 Start Run lt Stop gt Star Time s Time s Allen Bradley Bulletin 150 Reduced Voltage Starters Modes of Operation Preset Slow Speed This method can be used on applications that require a slow speed for positioning material The Preset Slow Speed can be set for either Low 796 of base speed or High 1596 of base speed Reversing is also possible through programming Speeds provided during reverse operation are low 1096 of base speed or high 2096 of base speed 10096 jo e 2 ao 5 Forward 2 15 High 7 Low 10 Low Start Run 20 High Reverse Time s Soft Stopi The Soft Stop option can be used in applicat