Home
        SYSMAC CS/CJ-series CS1W-PRM21/CJ1W-PRM21
         Contents
1.         Help    OPERATE Command                   STOP   M UNFREEZE J UNSYNC  I FREEZE Iv SYNC  CLEAR    Destination  OFFLINE   N Group 1 T Group 5  I Group 2 I Group 6  I Group 3   Group   T Group 4   Group 8  P AllSlaves  Transmit       In order to change the network to OPERATE mode  i e  start I O data  exchange  press the OPERATE button  The OPERATE status of the Master  Unit can be retrieved from the Monitor   Master status tab in the same user  interface     The Unit   s operational mode can also be changed in indirect ways  i e  without  direct user or program interference     103    Operating the Network    Section 3 6       e Mode changes caused by Auto CLEAR  When the Auto CLEAR function has been enabled  and one or more of  the slave devices on the network stop I O data exchange  the Master  Unit   s operational mode will automatically change from OPERATE to  CLEAR  This is discussed in section 3 6 4 Using Auto CLEAR     e Mode changes caused by PLC mode changes  An operational mode change will take place if the PROFIBUS Master Unit  has been configured to change its operational mode together with the  PLC mode  i e  OPERATE when the PLC mode is set to RUN MONITOR  and CLEAR mode  when the PLC mode is changed to PROGRAM mode   Refer to section 3 4 1 Setting the Master Parameters for more informa   tion     3 6 3 Transmitting Global Control Commands    Global Control commands     O Data Synchronization    Note    Group Address Setting    Note    Setting the Group  A
2.         Reconstruct the network or cor   rect the routing tables so that  commands are set to within a 3   level network range        Check the command format and  set the correct command data        Check the routing tables        PROFIBUS parameter set  invalid     80  Bus param   eter error   00   7D  Slave   parameter error    e Check the parameter settings     e Re download the configuration  if necessary        Protocol error     00   7D  Fail   ing Master  Address    Check the master devices on the  network  and make sure they are  all working correctly        Duplicate master address     00   7D  Fail   ing Master  Address    Check the master devices on the  network and ensure that they  have unique device addresses        Hardware error     00       e Check the network wiring  and  make sure it is correct   Check for short circuits   Check the bus timing set  through CX Profibus   Check the HSA setting in CX   Profibus  and make sure it is  set to the master device with  the highest address on the net   work   Check if any other faulty  devices are on the same net   work   Verify that the Highest Station  Address setting includes any  other master address on the  bus        CPU Bus Unit fatal error     Error address in program     Restart the CPU Unit  If the prob   lem persists  replace the PROFI   BUS Master Unit           CPU Bus Unit memory error     Note 1     02  Network  Parameter     06  Error log     01  Read error   02  Write error           Restart the CPU
3.        0 0 0 0    0c e eee eee 6  Setting up a PROFIBUS DP Network                   00 00 2000 0005 7  1 2 1 Configuring the PROFIBUS Master                     0004  7  1 2 2 FDT DTM Technology               0 0 0 0  2 cece eee 7  1 2 3 GSD file Technology               0 0  eee eee eee 8  CX Profibus Configurator    0 0 0 0    0    eee cece eee eee 10  1 3 1 CxX Profibus Features    0 0 0 0    0  cece cee eee 10  1 3 2        Specifications    ec e sais sa eige ab is Ena EE EEG bet RE os 13    Overview of PROFIBUS    Section 1 1       1 1 Overview of PROFIBUS    1 1 1 Introduction  Standard EN50170    PROFIBUS FMS    PROFIBUS DP    PROFIBUS PA    Uniform Bus Access  Protocol    A Caution    PROFIBUS  PROcess FleldBUS  is an open fieldbus standard for a wide  range of applications in manufacturing  processing and building automation   The Standard  EN 50170  the Euronorm for field communications   to which  PROFIBUS adheres  guarantees vendor independence and transparency of  operation  It enables devices of various manufacturers to intercommunicate  without having to make any special interface adaptations     The PROFIBUS family comprises three mutually compatible versions   PROFIBUS FMS  PROFIBUS DP and PROFIBUS PA     FMS means Fieldbus Message Specification  This version is the general pur   pose solution for high level extensive and complex communication tasks   Powerful services open up a wide range of applications and provide great  flexibility     DP means Decentral
4.       Extended Diagnostics e Extended Diagnostics  Depending on the type of slave device  it may additionally send Extended  diagnostic bytes in a format defined in the PROFIBUS standard  The  Extended diagnostics usually contain device specific diagnostics informa   tion  The Extended diagnostics information is displayed in the Extended  Diagnostics tab of the Diagnostics User Interface     Updating the Diagnostics The Diagnostics User Interface contains two tabs  It also contains an Update  button  which will   when pressed   refresh the diagnostics data  by retrieving  it from the PROFIBUS Master Unit  A Green LED indicator in the lower left  corner will indicate whether or not the device is on line     Diagnostics Tab The Diagnostics tab displays basic diagnostics for the slave  An example of  the Diagnostic tab is shown below  The diagnostics information is displayed       70    Generic Slave Device DTM    Section 2 5       as red and green LED indicators  Red LED indicators refer to error events   Green LED indicator refer to status situations     Device  CJ1W PRT21 GSD File  OC_0602 gsd  Vendor  OMRON Corporation Ident Number  0x0602    Diagnostic   Extended Diagnostics         r Station Status      W Master lock Wa Slave deactivated    Parameter fault W Syne Mode  W Invalid slave response    Freeze Made  W Function not supported   Watchdog on    Extended diagnostics   Slave device    Configuration fault W Static diagnostics  W Station not ready WW Reparameterization r
5.       Open    Opens an existing Project        Save    Saves the displayed Project to a file        Save As       The Save as command is the same as Save  but the Filename Specifi   cation Window is always displayed        Export Project to HTML    Exports Project data in HTML format and launches the browser        Project Properties       Opens an edit window to add or edit Project information        Recently used File List    Lists the recently used Project files        Exit    Exits CX Profibus        Cut    Cuts devices and pastes them to the clipboard        Copy    Copies devices to the clipboard        Paste    Copies devices from the clipboard to the cursor position        Network view    Hides or un hides the Network view        Device Catalogue    Opens or closes the Device Catalogue        Tool Bar    Hides or un hides the Tool Bar        Status Bar    Hides or un hides the Status Bar        Error Logging    Hides or un hides the Error Logging window        FDT Monitoring    Hides or un hides the FDT Monitoring view        Device    Add Device       Opens up the Device Catalog Add window  from which devices can be  added to the selected network tree        Upload Parameters    Uploads the parameters from a device to its associated DTM        Download Parameters    Downloads the parameters from DTM to its associated device        Export to HTML    Exports the properties and parameters of the selected DTM  or the net   work to a HTML file and opens the default browse
6.      Master Setup Tab       Action to PLC Mode  Transition Box    Change PLC to RUN   MONITOR Mode    Change PLC to PROGRAM  Mode    Auto CLEAR Box    The Master Setup tab contains settings regarding the behaviour of the  PROFIBUS Master Unit itself  The Master Setup tab is shown below                  ioi xi  Device Setup Master Setup   Bus Parameters   Slave Area   Advanced   OK    m Action to PLC Mode Transition  Cancel    m ToRUN MONITOR Mode    r ToPROGRAM Mode  Help    C Keep Current Mode C Keep Current Mode       Goto OPERATE Mode     Goto CLEAR Mode       Auto Clear   r Support    Auto Clear Mode OFF IV Auto Addressing    Auto Clear Mode ON                The Action to PLC Mode Transition Box defines the behaviour of the Unit on  the PROFIBUS network  in case a PLC mode change occurs  The check  boxes define how the Unit should behave in case the PLC mode is changed  from RUN   MONITOR mode to PROGRAM mode  or vice versa  Refer to  section 1 1 7 Network Operation Modes for more information on PROFIBUS  operational modes     The table below defines the behaviour in case the PLC changes to RUN    MONITOR mode     Keep Current Mode Unit keeps the current mode if the PLC goes to RUN    MONITOR mode  e g  stay in CLEAR mode      The Unit goes to the OPERATE mode whenever the PLC  goes to the RUN   MONITOR mode           Go to OPERATE Mode   default setting     The table below defines the behaviour in case the PLC changes to PRO   GRAM mode     Keep Current Mode Unit keeps 
7.      e Personnel in charge of installing FA systems   e Personnel in charge of designing FA systems   e Personnel in charge of managing FA systems and facilities     General Precautions     N WARNING    The user must operate the product according to the performance specifica   tions described in the operation manuals     Before using the product under conditions which are not described in the  manual or applying the product to nuclear control systems  railroad systems   aviation systems  vehicles  combustion systems  medical equipment  amuse   ment machines  safety equipment  and other systems  machines  and equip   ment that may have a serious influence on lives and property if used  improperly  consult your OMRON representative     Make sure that the ratings and performance characteristics of the product are  sufficient for the systems  machines  and equipment  and be sure to provide  the systems  machines  and equipment with double safety mechanisms     This manual provides information for programming and operating OMRON  PROFIBUS Master Units  Be sure to read this manual before attempting to  use the Unit and keep this manual close at hand for reference during opera   tion     It is extremely important that all PLC Units be used for their specified pur   poses and under the specified conditions  especially in applications that can  directly or indirectly affect human life  You must consult your OMRON repre   sentative before using a PLC System in the above mentioned appli
8.     Note The Global Control command as set in the CIO words is transferred to the  Unit together with the I O data  but the Global Control command is sent over  the PROFIBUS network  following the I O data  The Freeze command forces  an immediate update of the PROFIBUS transmission buffers in the slave  device  with the last input value sampled  This input data is then transferred to  the PROFIBUS Master Unit  with the next I O data exchange cycle     105    Operating the Network    Section 3 6       Sync   Unsync commands    Sending a Global Control   Sync command to a slave device has the following  effect    e The slave device will update its physical outputs only once with the last  received PROFIBUS output data  despite new output data being received  from the PROFIBUS Master Unit     e If a new Global Control   Sync command is sent  the slave device will  update its physical outputs only once  with the most recent received out  put data    e If a Global Control   Unsync command is sent  the slave device will revert  back to its original situation  and transfer updated output information to  the Master Unit with each subsequent I O data exchange message     Note If a Global Control command contains both a Sync and an Unsync command     the Unsync will prevail     The figure shown below illustrates the Sync   Unsync feature as implemented  by the CS1 CJ1W PRM21 PROFIBUS Master Unit     Global Control Sync command Global Control Unsync command       PLC Cycle    PROFIBUS C
9.     There are two types of master devices     Class 1 Master  DPM1  A PROFIBUS DP Class 1 Master  DPM1  device is a central controller  which  exchanges information with the decentralized devices  i e  DP slaves  within a  specified message cycle     Class 2 Master  DPM2  PROFIBUS DP class 2 Master  DPM2  devices are programmers  configura   tion devices or operator panels  They are used during commissioning  for con   figuration of the DP system  or for operation and monitoring purposes     As of Unit Version 3 0 the CS1W PRM21 and the CJU1W PRM21 are PROFI   BUS DP Class 1 as well as Class 2 Master devices     Slave Devices Slave devices are peripheral devices  Typical slave devices include input out   put devices  valves  drives  and measuring transmitters  They do not have bus  access rights and they can only acknowledge received messages or send  messages to the master when requested to do so  Slave devices are also  called passive devices    Device Profile To enable the exchange of devices from different vendors  the user data has  to have the same format  The PROFIBUS DP protocol does not define the for   mat of user data  it is only responsible for the transmission of this data  The  format of user data may be defined in so called profiles  Profiles can reduce  engineering costs since the meaning of application related parameters is  specified precisely  Profiles have been defined for specific areas like drive  technology  encoders  and for sensors   actuators     PRO
10.     by the PROFIBUS Master Unit   Most likely causes     e Lost token messages  the token is not returned      To correct this     e Check the master devices on the network  and make sure they are all working cor   rectly   e After correction  switch the Unit to CLEAR   OPERATE mode again     Double master address error  ON   A second master device with the same network address has been detected on the   OFFLINE indicator will be ON  PROFIBUS network  The PROFIBUS Master Unit has switched to OFFLINE     To correct this     e Check the master devices on the network and ensure that they have unique  device addresses     e After correction  switch the Unit to CLEAR   OPERATE mode again     Hardware error  ON A hardware error has occurred in the PROFIBUS interface of the Unit  The PROFI    OFFLINE indicator will be ON  BUS Master Unit has switched to OFFLINE     Most likely causes   Faulty wiring           Broken messages    Short circuits  or   Faulty bus timings    A master device has been detected beyond the Highest Station Address  HSA      To correct this    Check the network wiring  and make sure it is correct    Check for short circuits    Check the bus timing set through CX Profibus    Check if any other faulty devices are on the same network    After correction  switch the Unit to CLEAR   OPERATE mode again   Auto Clear enabled  ON This combination indicates that one of the slave devices on the network failed  caus   CLEAR  ON ing an automatic transition to the CLEAR mod
11.    01 PLC Memory overlapping Input Output areas and or PROFI  Check the Input Output areas and  BUS DP V1 Status table are over  make sure they are not overlapping   lapping within the current Retry download   configuration    02 PLC Memory exceeds memory Input Output areas and or PROFI  Change the configuration to be   range BUS DP V1 Status table exceeds within the memory area and retry  memory range  combination of start   download   address and length     03 Slaves should have unique Unique bus addresses must be Change the addresses of the slaves  addresses assigned for each slave  and ensure no duplicates are   present  Retry download    04 DTM cannot be added to the net    The slave DTM cannot be con  Avoid using non PROFIBUS DP  work  it is nota PROFIBUS device   nected  e g  if adding HART device  DTMs    DTM DTM    05 Max  number of slaves configured    DTM can not be added  since the Do not add any more DTMs  If more   New slave cannot be added master has already the maximum are still needed  a second PROFI   number of slaves  125  assigned  BUS Master Unit on the same PLC  system may be solution    06 Slave address overlap detected    Changing the address of an existing   Automatically recovers    New address assigned   new slave results in an address overlap   address    07 Invalid data set received from a An internal error has occurred pre    Add a new slave DTM into the net   slave DTM  Slave parameter venting the master DTM to obtain work  or change the modules
12.    CX Profibus          CX Profibus provides the following additional support functions   e Context sensitive help functions    e Error logging    e Monitoring of FDT communication between DTMs    e Multi language support        13    CX Profibus Configurator    Section 1 3       CS1 CJ1W PRM21 DTM    Item  Device setup    Specification  Device setup allows the user to     e Select the PROFIBUS Master Unit   s unit number     e Configure the communication link between the PC and the Unit  This  function invokes the user interface of CX Server     e Test the Units communication link and read out the Unit   s information        Master setup    It allows enabling of Auto Addressing  to facilitate   O data mapping  as  well as defining the Unit   s behaviour in case of   e a network malfunction    e PLC mode changes between PROGRAM and RUN MONITOR mode        Bus parameter setup    The bus parameter setup allows the selection of baud rate and calcula   tion and editing of specific bus parameters        Slave area setup    The Slave area setup allows the user to define the I O Data mapping of  the I O Data from each of the slave devices on to PLC memory areas        Monitoring functions    Master status read out   Slave status and slave diagnostics read out   Read out of the Unit   s error log        Additional Master functions    Set remote slave address   Communication channels for PROFIBUS DP V1 MSAC1 messages   Communication channels for PROFIBUS DP V1 MSAC2 messages     Note 
13.    Operating the Network    Section 3 6       Note    3  Select the Online Operations tab     4  Select the commands to be transmitted  e g  Freeze  Sync  using the  checkboxes     Select the groups to transmit the Global Control command to     6  Press the Transmit button to transfer the command to the Unit   s CIO area   and to set bit 04 in the Software Switches 1 word     7  The Transmit button will be disabled until the command has been trans   mitted     The time between pressing the Transmit button in the CS1 CJ1W PRM21  Master DTM user interface and the Global Control command actually being  transmitted over the PROFIBUS network  will be  much  longer than when the  Global Control command is initiated from a PLC user program  due to the  additional communication between the PC and the PLC CPU     3 6 4 Using Auto CLEAR    Auto CLEAR Feature    Enabling Auto CLEAR    Transition Conditions    Note    Note    The CS1 CJ1W PRM21 PROFIBUS Master Units support the Auto CLEAR  function as defined in the PROFIBUS standard  This feature   when enabled    will switch the PROFIBUS Master Unit to CLEAR mode automatically  in case  one of the slave devices fails on the network  The purpose of this  is to force  the PROFIBUS network to a safe state     When in CLEAR mode  the PROFIBUS Master Unit will read each slave   s  input data  but not send output data  Depending on the slave device  the Mas   ter will instead send either empty output data messages or output data mes   sages 
14.    PRM21 DTM CX Gerver PRM21 Unit PROFIBUS  ee eee  lt         SS es TRR a  A    Read Acyclic Rea  i Response Acyclic Read      Response   Response          i       t i       PROFIBUS i PROFIBUS  Slave DTM I Slave Unit                   Note The CS1 CJ1W PRM21 master  communication  DTM will determine which  connection is initiated with the slave Unit  The default connection is PROFI   BUS DP V1 Class 2  If this is not supported by the slave  PROFIBUS DP V1  Class 1 messages will be send     Z  Caution Since using PROFIBUS DP V1 Class 2 messages are by definition aimed at  setting parameters in a slave device  it is highly recommended to make those  settings with the PROFIBUS Master Unit in CLEAR mode  to prevent undesir   able effects on I O data     As an example  the figure below shows the DTM of the GRT1 PRT PROFI   BUS Communication for SmartSlice I O Units  see Operation Manual WO4E     116    PROFIBUS DP VI Services o CS ection 3 8                EN L    The DTM is used to configure and monitor the GRT1 Series Smart        Slice I O Units           D   My Documents Example cpr      CX Profibus  File Edit View Device Tools Window Help    Dol tal  A    col    Efe  MyNetwork  i   ie 1   CUIW PRM21 PROFIBUS DP V1 Master     34   GRTI PRT SmartSlice I O Coupler          st  34   GRT1 PRT SmartSlice 1 0 Coupler   Configuration    PROFIBUS 1 0 Module    r Configuration      Slot   Product Name  a   gar o041 m  GRT1 0D441    GRT1 0D4 1 General Analog Input 0   Analog Input 1  
15.    e BF LED indicator is Flashing     e Slaves are sometimes briefly in and out of  data exchange     Verify that the Bus parameter sets are cor   rect  If necessary  increase Target Rota   tion Time and or Min  Slave Interval  parameters    Re download the configuration    If the problem persists  replace the Unit        A second master device  with its own slave  devices  is on the same network  interfering  with this Master Unit   e The baud rate settings of both masters is  different   The total Target Rotation Time set to both  masters is too small  i e  not the sum of  both individual time values      Verify that all masters on the network are  set to the same baud rate    Verify that the total Target Rotation Time  for all masters on the network is set to the  sum of all individual masters           Specific slave devices are configured and  allocated to the Master Unit  but the slave  which is not exchanging data may have been  disabled using the FINS STOP command        Use the FINS RUN command to enable the  slave devices        Troubleshooting the Network    Section 4 2       Problem    PROFIBUS Master Unit is  configured  All slaves were  in data exchange  but it has  now stopped     Probable cause    No power is supplied to the system  All LED  indicators on the system are OFF     Correction    Verify that power is supplied to the sys   tem        A PLC CPU error occurred   e The ERH indicator is ON  the other LED  indicators are OFF     e The ERR ALM LED indicat
16.   3 4 Configuring the Master          0 0    cee eee eee 87  3 5 I O Communication Characteristics     0 0    2 cece eee 94  3 6 Operating the NetWork sea e e E r ccc cece cee eee 102  3 7 Monitoring the Network         0 0    rraren erreen 108  3 8 PROFIBUS DP V1 Services      0 0    cece E E 116    SECTION 4   Troubleshooting and Maintenance                      119  Aa   JOVERVICW  fxs bie wk OVERS ees ees Be Eh Ris Bs RR SNe 120  4 2 Troubleshooting the Network          0 0    c cece ete ence eens 121  4 3 Troubleshooting Using the Error Log      0    0    eee ee 131    TABLE OF CONTENTS  Appendices    A Configurator Error and Warning Messages             00    0c eee eee eee    About this Manual    This manual describes the CX Profibus Configurator for the CS1W PRM21 and CJ1W PRM21  PROFIBUS DP and PROFIBUS DP V1 Master Units     This manual describes CX Profibus and the PROFIBUS Master and slave DTM supplied with it  how to  operate it  These software components are required to control and operate the CS1 CJ1W PRM21  PROFIBUS DP and PROFIBUS DP V1 Master units  For more information on the CS1 CJ1W PRM21  Master unit  refer to the CS1 CJ1W PRM21 PROFIBUS Master Units Operation Manual  W409 E2 L                   Note The basic functionality of PROFIBUS DP is sometimes referred to as PROFIBUS DP VO  In    this document the term PROFIBUS DP will be used to indicate the basic functionality     Please read this manual carefully so that you understand the information provided
17.   4 1 Overview    Troubleshooting the  Configuration Software    Troubleshooting the  network    120    The CS1 CJ1W PRM21 PROFIBUS Master Unit and the Configuration soft   ware package provides extensive means for troubleshooting  which can be  used to quickly determine errors in the Unit  in the configuration  in the net   work  and or in remote slave devices  allocated to the Unit  For troubleshoot   ing the Master units  refer to the CS1 CJ1W PRM21 PROFIBUS Master Units  Operation Manual  W409 E2 L                   The Configuration software  i e  CX Profibus  the PROFIBUS Master DTMs  and the Generic Slave DTM provide several mechanisms for error detection  and correction   e Errors occurring in CX Profibus are displayed in pop up message win   dows and or the error log window  The contents of the error log window  can be copied to the clipboard to allow analysis afterwards     e CX Profibus provides a FDT communication log window  which can be  copied to the clipboard  Analysis of this communication may provide addi   tional information in case errors occur     The PROFIBUS Master DTM and the Generic Slave DTM diagnostics infor   mation windows  which can display   e Indications of errors in the PROFIBUS interface of the Unit  e Indications of errors in the communication between the PROFIBUS Mas   ter Unit and remote slave devices   e Indications of errors in the remote slave devices  allocated to the PROFI   BUS Master Unit   The CX Profibus and DTM capabilities for t
18.   80   Slave station 80   95             Word n 6   111  110  109  108  107   106   105   104   103   102   101  100  99   98   97   96   Slave station 96   111    Word n 7 125  124  123  122  121 120  119  118 117  116 115  114 113 112  Slave station 112   125                                                             In the above figure  n is the start address of the memory locations  defined by  the Area and Start Address setting in the Acyclic Connection Abort Status  Box     CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3    Status   Controlled Unit operation  by    Acyclic Connection If the bit corresponding to a slave device address is ON  it indicates that  flags the PROFIBUS Master Unit has established a PROFIBUS DP V1 Class  2 type connection     If the bit corresponding to a slave device address is OFF  it indicates  that there is no open PROFIBUS DP V1 Class 2 type connection with  the specific slave device                       Acyclic Connection Abort The 8 word Acyclic Abort bit flags are shown below   Status Flags    1514131211109 8 765 43 2 1 0  5 14 13  12 11 10  9 8 7  6  51 41 3   2441  o   Slave station 00   15       Word n 8  Word n 9   31   30   29   28   27   26   25   24   23   22   21   20   19   18   17   16   Slave station 16   31          Word n 10   47   46   45   44   43   42   41   40   39   38   37   36   35   34   33   32   Slave station 32   47       Word n 11   63   62   61   60   59   58   57   56   55   54   53   52   51   50   49   48   
19.   GATHD41    GAT1ID4 1 1 0 Comment        GRT1 AD2  GRT1 DA2v Last Maintenance Date    2005701 m1 x  Adjustment           Emply Slot     r Function Choice     Empty Slot       Empty Slot J    MovingAverage    Peak Bottom I Comparator   Rate of Change  Empty Slot I Scaling M TopMVvalley M Cumulated Count    Emly Slat Range Data Allocation   Comparator   Top Valley   Cumulated Count            0000 Input Range  0001 Analog Datal Allocation  0002 Analog Data2 Allocation    Empty Slot          Help   NOTE  Input Flange isn t enabled     1  5Y   only by changing this parameter  lo 20m  Upload   Download Compe RESET or re start is required  E    Default Setting                                     117    PROFIBUS DP VI Services S CS ection 3 8       118    SECTION 4  Troubleshooting and Maintenance    This section describes the troubleshooting procedures and maintenance operations for the CS 1 CJ1W PRM21  needed to  keep the PROFIBUS network optimally working     4 1    4 3    Overview           4 2 Troubleshooting the Network           0  0 0  cece cee  Troubleshooting Parameter Download                  0000   Troubleshooting the Network using CX Profibus                 Troubleshooting I O Communication                     00   Troubleshooting Using the Error Log                0 00 00 00 eee ee eee  Error Log Overview          0 0 0 e eee eee eee    4 2 1  4 2 2  4 2 3    4 3 1  4 3 2    Error Codes    120  121  121  122  127  131  131  131    119    Overview    Section 4 1     
20.   In order to avoid unexpected results  the PLC user program may have to  be adapted as well     1  Auto Addressing will not change the allocation of I O modules to a certain  area  i e  a module allocated to Input Output area 2  will not be re allocated  to area 1  if Auto Addressing is enabled    2  Auto Addressing will not change the start address of the areas     3  Auto Addressing is by default enabled  when starting a new project  It is  however  disabled for existing projects to avoid unwanted re mapping     The figure below shows an example of the effects of Auto Addressing on   re allocation of I O modules  In the original I O configuration on the left  the  first slave   an OMRON CJ1W PRT21   consisted of two I O modules  In new  configuration one I O module was inserted  and subsequent modules were re   allocated in the process     it 4   CJ1W PRM21 PROFIBUS Master   Configuratio     Device Setup   Master Setup   Bus Parameters Slave Are          atl 1   CJ1W PRM21 PROFIBUS Master   Configuratio    Device Setup   Master Setup   Bus Parameters Slave An    Output Allocation   Input Allocation   Output Allocation   Input Allocation         Module Module  2 1 CJ1W PRT21 1 words 2 1 CJ1W PRT21 1 words  2 4 words 2 2 words   3 1 CPM14 PRT21 2 bytes 3 4 words   3 1 CPM14 PRT21 2 bytes               Output Area 1 Output Area 1   3200   2  1 words output 3200  2  1 words output   3201   2  4 words output 3201    2  2 words output   3202 4 words output 3202 2 words output   
21.   OMRON Corporation  OMRON Corporation    teH    Update   Install GSD Files         dd Device    A    Error Log         User   Administrator A       Error Log and FDT Monitoring view DTM view Status Bar    The main components in this window are  e The Network view   e The DTM   Catalogue view   e The Error Log view   e The FDT Monitoring view  not shown in the figure above      19    CX Profibus    Section 2 2       Network view    DTM   Device Catalogue  Window    Error Log view    FDT Monitoring view    Main Menu    20    e The Main menu   e The Tool Bar and the Status Bar     The Network view displays the structure of the PROFIBUS network in a tree  view format  The tree has at least three levels     e The Project Level   e The master level   e The slave level     The highest level of the tree is the project  The next level is the PROFIBUS  Master level  On this level one or more PROFIBUS Master devices can be  allocated  The third level contains the slave DTMs    The PROFIBUS network must be assembled in the Network view  i e  the var   ious DTMs are added to the network via this window  From the Network view  the individual DTM User Interfaces can be opened  and accessed     CX Profibus supports context menu in the Network view  which are made vis   ible when selecting a device DTM and right clicking the mouse  The contents  of the menu may depend on the functionality supported by the DTM     The DTM   Device Catalogue window will hold the Device Catalogue as well  as ev
22.   PROFIBUS Master Unit     The CS1 CJ1W PRM21 Master DTM Diagnosis User Interface provides the  means to control the Master Unit directly from CX Profibus  running on a PC     For access to the Unit   s controls  an online connection with the Unit has to be  established first  To achieve this perform the following sequence     1  To go online  select the DTM in the Network view  and perform one of the  following actions   e Select the Device   Go Online option from the main menu  or the DTM  context menu  or    e Select the A button from the Tool Bar     2  Acommunication channel will be opened through CX Server  The name of  the DTM in the Network view  will turn to Italic font  to indicate that the Unit  is on line    3  From the context menu  select the Diagnosis option  The DTM   s Diagnos   tics User Interface will be displayed     4  Select the Online Operations tab  for the Units controls     Controlling the CS1 CJ1W PRM21 PROFIBUS Master Unit from the CS1   CJ1W PRM21 Master DTM Diagnosis User Interface  may interfere with a  PLC user program running at the same time  This can result in unexpected  behaviour  It is recommended to change the PLC CPU mode to PROGRAM  mode to avoid this interference  during the use of the CS1 CJ1W PRM21  Master DTM Diagnosis User interface     Operating the Network    Section 3 6       3 6 2 Changing PROFIBUS Mode of the Master Unit    PROFIBUS DP Network  Modes    Normal Operating Modes    Changing the Mode from  the CS1 CJ1W PRM21  Mas
23.   Section 3 2       1 2 3       Note    Installing New GSD Files    1 2 3       Before starting the assembly of the network in CX Profibus  make the follow   ing preparation steps     1     Open the Device Catalogue  Either select the View   Device Catalogue  menu option  or press the fue  button in the Tool Bar  The opened Device  Catalogue is shown below                    aox  Device Types  Device  vesin  Dae  vendr 4l  Vendors H 58505 Mass Flow C 2 0 Brooks Instrument  Groups 2 ABB IMDPO1 v2 4 2000 07      Deutschmann Automation GmbH             Protocols 2 ABB ACPBDO NPBA     B 1998 08    ABB DRIVES      ABB PSR A 2000 07      ABB DRIVES   HA C200HwW PRT21 V1 0 2000 04     OMRON Corporation   Hi CB_AB32 DPS Version 1 001 1998 07     Hilscher GmbH   Hi CIF104P DPS Version 1 000 2002 06     Hilscher GmbH   2 CIF30 DPS    CIF104    Version 2 011 2000 03     Hilscher GmbH   HA CIFS0 DPS Version 1 000 2000 03     Hilscher GmbH      CIF60 DPS Version 1 000 2000 03     Hilscher GmbH   2 CIF80 DPS Version 1 000 2002 06     Hilscher GmbH  CIFPS1 DPS Version 1 010 2000 03    Hilscher GmbH   i CW PRM2I PRO    3 62 2003 10     OMRON Corporation     CJ1w PRT21 V1 0 2002 06     OMRON Corporation   t g COM C DPS Version 1 000 2002 06     Hilscher GmbH   k i Compact Slave Cont    32 0 2000 07     Asea Brown Boveri   _ CPM14 PRT21 V1 0 2002 03     OMRON Corporation   ig COM1 PRT21 V1 0 2000 04    OMRON Corporation   m CS1W PRM21 PRO    3 62 2003 10     OMRON Corporation     DARC w  DP Y1
24.   Set OPERATE switch in CIO Word n  see  Note  to force the Unit to the OPERATE  mode        129    Troubleshooting the Network    Section 4 2       Problem    PROFIBUS Master Unit is  configured  All slaves are in  data exchange  but the out   puts of some slave devices  are not updated     Probable cause    The specified slave devices may be in Sync  mode     Correction    Send a Global Control Unsync command to  the targeted slave or group of slaves  Use  either the Global Control feature in ClO  Words  refer to the CS1 CJ1W PRM21 Oper   ation Manual  W409 E2 L                      The specified slave device may have its  watchdog disabled and is disconnected from  the network  due to a cabling problem   e BF LED indicator is Flashing   e ClO Words n 9 to n 16  see Note  show  which slaves have problems   Use CX Profibus and DTMs to determine  slave diagnostics     Verify that the specified slave device is still  connected to the network        PROFIBUS Master Unit is  configured  All slaves are in  data exchange  but the  inputs of some slave  devices are not updated     The specified slave devices may be in  Freeze mode     Send a Global Control Unfreeze command to  the targeted slave or group of slaves  Use  either the Global Control feature in ClO  Words  refer to the CS1 CJ1W PRM21 Oper   ation Manual  W409 E2 L                         The specified slave device may have its  watchdog disabled and is disconnected from  the network  due to a cabling problem   e BF LED 
25.   Testing CX Server setup    92    Note    4  Select the Network Type to be used as connection between the PC and  the Unit  The available options may include other PLC systems or Commu   nication Units  which are setup to act as a gateway  Refer to CX Server  Runtime user Manual  W391  for details on configuring CX Server     Note 1  For further explanation  only the direct connections between the  PC and the PLC on which the Unit is attached are considered   These include ToolBus and SYSMAC WAY     2  Select the Settings button next to the Network Type selected  to  display the Network settings window  and select the Driver tab   Toolbus is shown as example below     3  Although SYSMAC WAY can be used for the majority of applica   tions  it is limited in a sense that it can not handle the absolute  maximum of I O configuration and parameters  i e  it can not han   dle a slave device which requires 244 I O modules and 244 pa   rameter bytes  Toolbus does not have that limitation     Network Settings  Toolbus  xj  Network Driver   Modem      Connection    Data a  Port Name  x  Data Bits   z       Baud Rate   115200 x  Parity None y  M Baud Rate Auto Detect Stop Bit fi z  Make Default         5  Make the necessary selections to facilitate communication between the  PC and the PLC CPU to which the PROFIBUS Master Unit is attached   and press the OK button     After making the settings  press the OK button to close the CX Server inter   face  In order to verify that the communic
26.   The Slave Area allocation tabs define how the I O data of each of the slave  devices is mapped on to the PLC memory  The Slave area tab contains two  tabs  one for Output Allocation and one for Input Allocation  Each tab contains  an overall module list  showing all the output or input data per slave  along  with the Module names  sizes  data types and start addresses  This data has  been transferred to the Master DTM by each of the allocated slave DTMs  If  no slave devices have been allocated  or configured  the list will be empty     The Module List Box list contains the following information  refer to figure  above  the table applies to the lists in the Input and Output Allocation tabs      Column Description     Addr  Station address on the network  obtained from the slave DTM   Index Index number of the I O module   Device Device name  obtained from DTM              Module System generated name   Size Module data size  unit of type mentioned in next column   Type Module data type  e g  Byte  Word etc              Addr Mapped address area in PLC memory  For example  ClO3200   equals CIO Area  start address 3200           Each Output Input Allocation tab also contains two areas on to which the I O  data can be mapped  The areas will in turn be mapped to the PLC memory   By default all data is mapped to Area 1  in order of ascending slave device  address     37    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Note 1  When mapping  the modules are copied from the m
27.   Unit must have been established     Opening the DTM In order to open the DTM Diagnostics User Interface perform the following  Diagnostics User Interface sequence     1 2 3    1  To go on line  perform one of the following actions   e Select the DTM in the Network view   e Select the Device   Go Online option from the main menu  or from the  DTM context menu  or  e Select the A button from the Tool Bar     2  Acommunication channel will be opened through CX Server  The name of  the DTM in the Network view  will turn to Italic font  to indicate that the Unit  is on line    3  Select the Device   Diagnosis option from the main menu  or from the  DTM context menu  The Diagnostics User Interface will now be displayed     43    CS1 CJIW PRM21 PROFIBUS Master DTM    Monitor Tab    Master Status Tab    Section 2 3    The figure below shows an example of the DTM Diagnostics User Interface     Monitor   Online Operations         m Master Status 1      OPERATE    sToP     CLEAR      OFFLINE      Data Exchange      Auto Clear Enabled    valid Configuration  Master Status 2     E Disturbed Bus Error      PROFIBUS Protocol Error    Slave Status   Error History      w 1   CJ1W PRM21 PROFIBUS Master   Diagnosis    r Refresh     Unit Status I Automatic     Unit Error       Master Error     Local Parameter Storage Error     Local Parameter Load Error      File Read Error     Unit Memory Error         Manual         Eror Log Updated  E Parameter Storage in Progress  Slave Status    oO Slave 
28.   When Auto Addressing is being enabled  a warning message is displayed   informing the user of the effects of enabling Auto Addressing     Enabling Auto Addressing has the immediate effect of re allocating I O mod   ules of an existing configuration  within each Input Output area  The I O mod   ules are re mapped according to the algorithm described above     Disabling Auto Addressing has no immediate effect on an existing I O map   ping   A disabled Auto Addressing feature has the following effects on I O mapping     e When adding new slave devices or new I O modules to an existing slave  configuration  the I O modules will be mapped to the first I O areas  but  the modules will be appended to the existing I O mapping     e When deleting a slave device from the network configuration  or deleting  I O modules from a slave device  the deleted I O modules will leave gaps  behind in the already existing I O mapping  If after deleting an I O module  a slave device still has more than one module configured  but these mod   ules are not in the same place  the DTM will attempt to remap them  together     Changing the address of a slave device  of which already an I O mapping  exists  has no effect on the existing mapping    Selecting an additional I O module for a slave device  in the presence of  already allocated I O modules  will cause a complete re map of all exist   ing modules if the total I O does not fit within the space it is already occu   pying  The modules are re mapped
29.   copying of new GSD  files into the GSD directory for the Generic Slave Device DTM  Selecting the  Install GSD Files    button displays the standard Windows File selection win   dow  After selecting the GSD file  and selecting the Open button in the File  selection window  the GSD file will be copied to the GSD file directory under  CX Profibus    After copying the GSD file  a warning window will be displayed  indicating that  the Device Catalogue needs to be updated  This can be accomplished by  selecting the Yes button in the warning window     1  Updating the Device Catalog after copying GSD file can only be done if  there is a new project opened  i e  with no DTMs allocated to the network   This is to prevent corruption of an existing network in case a GSD file is  removed or replaced     2  The Install GSD Files    option allows installation of more than one file at  the same time     2 2 5 Adding Devices to the Network    24    Setting up a network in CX Profibus involves adding and configuring single  device DTMs  The device DTMs as listed in the Device Catalogue can be  added to the network in three ways     e Using the context menu  A context menu will pop up when selecting the CS1 CJ1W PRM21    CX Profibus    Section 2 2       PROFIBUS Master DTM and right clicking the mouse  By selecting the  menu option Add Device  a simplified Device Catalogue is displayed   allowing only a selection of DTMs which can be added to the PROFIBUS  Master DTM     e Using the Drag  am
30.   e A failure during the reading process     e A faulty Memory Card     To correct this    e Check the Memory Card for faults    e Restart the PLC Unit  to re download the configuration    e If the problem persists  use CX Profibus to re download the configuration     Parameter error  ON An error has occurred initializing the PROFIBUS interface  after reading the parame    Valid Configuration Indicator will ter sets from the non volatile memory to the volatile memory     be OFF  Most likely cause   e A faulty parameters has been downloaded to the Unit        To correct this     e Check the parameter settings in CX Profibus and correct them if necessary  After  correction  perform a download of the new parameters to the Unit     Disturbed bus Error  ON An error has occurred in the PROFIBUS interface  with distorted messages received  by the PROFIBUS Master Unit     Most likely causes   e No or invalid termination or no inductors used at high baud rates   e Faulty wiring        To correct this   Check the termination on the appropriate devices   Restart the PLC Unit  to re download the configuration   If the problem persists  use CX Profibus to re download the configuration   If the problem persists  replace the PROFIBUS Master Unit           123    Troubleshooting the Network S    Section42       LED Indicators Description   Correction  PROFIBUS protocol error  ON An error has occurred in the PROFIBUS interface  with distorted messages received     OFFLINE indicator will be ON
31.  00 Release 1 00 1999 06      Ferrocontrol GmbH  amp  Co   LE EC1 DEB DPS Version 1 000 2002 07     Hilscher GmbH   2 ET 2005 IM 151 C    V0 2    2000 11     SIEMENS    Help   Update Install GSD Files                      Check the list of available DTMs  and verify that all the devices that need  to be added to the Network   both master and slave devices   are among  the DTMs in the list     If one or more of the DTMs is missing  these DTMs must first be installed  and the Device Catalogue updated     Non GSD file based DTMs are usually provided with their own setup pro   gram  Installation of these DTMs must be performed outside CX Profibus   e g  from Windows Explorer     In case of DTM installations outside CX Profibus  always initiate an update  of the Device Catalogue  before assembling a network  Without this up   date the newly installed DTM will not appear in the list of devices  To Up   date the Device Catalogue  press the Update button in the Device  Catalogue main window     An Update must also be performed when an already existing DTM is up   graded  Without the update  the old version number will still be shown in  the list  Failure to update the Device Catalogue in this case may also result  in undesired behaviour  when adding these DTMs to the Network     GSD file based DTMs can be installed from within the Device Catalogue main  window  To do so  follow the procedure below     1     Press the Install GSD File    button at the bottom of the Device Catalogue  m
32.  121    Troubleshooting the Network Section 4 2       4 2 2 Troubleshooting the Network using CX Profibus    CX Profibus  Troubleshooting    CX Profibus provides several means to troubleshoot either the CS1 CJ1W   PRM21 PROFIBUS Master Unit  the slave devices or the network  The means  all rely on features discussed in the previous section     Troubleshooting the  Master Unit    To troubleshoot the Master Unit or the network  the Master DTM Diagnosis  User Interface provides a help in determining problems  The figure below  shows the Monitor   Master Status tab of the Master DTM Diagnosis User    Interface     w 1   CJ1W PRM21 PROFIBUS Master   Diagnosis    Monitor   Online Operations         m Master Status 1      OPERATE    sToP     CLEAR      OFFLINE      Data Exchange        Auto Clear Enabled    Valid Configuration    Master Status 2    OD Disturbed Bus Error   PROFIBUS Protocol Error   O Double Master Address Error       Hardware Error    O Mode Command Error        Parameter Error             lave Status   Error History      r Refresh  V Automatic    Manual       m Unit Status     Unit Error       Master Error     Local Parameter Storage Error       Local Parameter Load Error      File Read Error      Unit Memory Error        Eror Log Updated  oO Parameter Storage in Progress    Slave Status    oO Slave Diagnostic Received  oO All Slaves in Data Exchange          The LED indicators shown in the  example  figure above are all related to bit  flags in the Unit Status Wor
33.  3201   2  2words output  3202 2 words output          3203   2  4 words output  3204 4 words output  3205 4 words output  3206 4 words output  3207   3  2 bytes output  No consiste   3208  10  1 words output    3209 x       Initial I O Configuration             atl 1   CJI1W PRM21 PROFIBUS DP   1 Master   Configuration i      Device Setup   Master Setup   Bus Parameters Slave Area   Advanced      Output Allocation   Input Allocation      Addr   Index  Device   Module  Sre  Type  Ads    1    OMRON Chiw PRT21 Word ele        2 T outpu E  3 4 words output 4 Wad ERTE                3 1 CPM14 PRT21 2 bytes output  No consis    2 Byte  ClIO3207  10 1 F150 PRT 1 words output 1 word  CI03208  in   r Output Area 1 7 Output Area 2  cio  Module Name  a  Module Name  a   3200   2  1 words output  3201 3401   2  2 words output  3202 3402 2 words output  3203   2  4 words output 3403  3204 4 words output 3404  3205 4 words output 3405  3206 4 words output 3406  3207   3  2 bytes output  No consiste  3407  3208  10  1 words output 3408  3209 z 3409 xl  Note  Auto addressing is disabled Output module 2 of slave device     2 was moved to Output area 2   location CIO 3401  leaving behind  a gap in Output area 1     Since gaps in the I O mapping are generally undesirable  the CS1 CJ1W   PRM21 Master DTM provides a means to remove all gaps  after finalizing the  I O mapping procedure  This removal is accomplished by compressing the I O  modules in a particular area     Compressing re allocates 
34.  Communication Group    A Caution    Global Control Messages    Selecting the Groups    48    The Online Operations tab is shown below         iix  Monitor Online Operations   Close    PROFIBUS Communication m Global Control Message                    Help    OPERATE  gt  Command                 STOP   M UNFREEZE     UNSYNC       FREEZE Iv SYNC  CLEAR    r Destinatin                 OFFLINE   IV Group 1 I Group 5       I Group 2 I Group 6  I Group 3 I Group   T Group 4   Group 8    P AllSlaves    Transmit               These buttons can be used to force the Unit to change its operating mode   The four operational modes are    e OFFLINE mode   e STOP mode    e CLEAR mode       OPERATE mode     The mode changes are implemented through FINS messages to the Unit   s  software switches in the CIO Memory Area  refer to the CS1 CJ1W PRM21  Operation Manual  W409 E2 L       When initiating a mode change  it may interfere with attempts from the PLC  Program to write to the same software switches  Care should be taken to  avoid these situations     Global Control messages  See section 3 6 3 Transmitting Global Control  Commands  can be initiated by the user from the Online Operations tab  The  user can select the Global Control commands     e Freeze    e Unfreeze   e Sync    e UnSync     All commands can be transmitted independent from each other  i e  all can be  send at the same time  However  their effects are not independent  as for  example sending Freeze and Unfreeze at the same 
35.  DTM    Section 2 3    LED Indicator Description    Master Status 1    OPERATE    Master Unit is in OPERATE mode        STOP    Master Unit is in STOP mode        CLEAR    Master Unit is in CLEAR mode        OFFLINE    Master Unit is in OFFLINE mode        Data Exchange    When set to ON  it indicates that the Master Unit is in Data Exchange with all its  allocated and enabled slave devices        Auto Clear enabled    Auto Clear function has been enabled in the downloaded configuration        Valid Configuration    The Master Unit contains a valid configuration        Master Status 2    Disturbed Bus error    When turned ON  the Disturbed Bus error indicates that distorted messages  have been received by the Unit  This may occur if the network is not properly  terminated or a cable is used  which is too long for the selected baud rate        PROFIBUS Protocol Error    When turned ON  the PROFIBUS Protocol Error indicates that an error has  occurred in the protocol handling  e g  a transmitted token frame could not be  read back  The Master Unit has switched to OFFLINE        Double Master address Error    Indicates that a second Master with the same address has been detected on the  Bus  The Master Unit has switched to OFFLINE        Hardware error    When turned ON  the Hardware Error indicates that an error has occurred on  the bus  e g  message exceeding 256 bytes  broken messages  faulty bus tim   ing  or devices beyond the HSA have been detected  The Master Unit has  sw
36.  DTM in the Network view     57    C200HW PRM21 PROFIBUS Master DTM Section 2 4       e Select the Device   Go Online option from the main menu  or from the  DTM context menu  or    e Select the A button from the Tool Bar     2  Acommunication channel will be opened through the CIF driver  provided  this driver has been assigned to the DTM  Refer to section 2 4 3 Connect   ing to the C200HW PRM21 on how to assign this driver  After going on line  The name of the DTM in the Network view  will turn to Italic font  to indicate  that the Unit is on line     3  Select the Device   Diagnosis option from the main menu  or from the  DTM context menu  The Diagnostics User Interface will now be displayed     The figure below shows an example of the DTM Diagnostics User Interface      inixi  m Master Operation Mode    p Master Status _    Bus Monitoring    Operate W Timeout W Fatal Error W Eror event  W Clear W Not Ready W Control Error Short Circuit Counter  0 Help    W Stop W Auto Clear Transmissions Rejected  W Offline   Slave Error Sends             r Station status    Oo Bi  2 3 O44    5 WE WD    s WD  G0 Ou OS2 G3 O44 O15 Oe WO  Ww wis  O82 O82   z   z OA OS WS   7   z WB  82 O81 O22 OB OH WS   s YW  WB WB  Ot OX   z OB OH WHE WH WT WR WA  On YH YVR   z OH VS WS WT WB Q5  On WH Ve YB WM WH WH Wr WB ws  GO O81   z OB OA OH   r OT OB wr  Os BOs OR   z OM   S WE WF Ww ws  G02 BOT   z   s OH   S   s WT WB WII  D100 iol H102   m Hiss Yi Wis Wir Wis wi09  Gio Bit Si2 Sis Sis S15 Ose S17
37.  Depending on the device  the se   quence may be checked by the slave device  If an incorrect sequence is  sent  the I O configuration is rejected  This is for example the case with the  OMRON PRT1 COM Multiple I O PROFIBUS DP Interface     3  A mandatory I O module sequence is sometimes indicated in the GSD file   by using non PROFIBUS standard GSD file keywords  i e  only interpreted  by a specific configurator   The Generic Slave DTM does not check such  keywords  In this case  refer to the manual of the specific device for details     82    Configuring the Slave Devices Section 3 3       4  Also in this window are the maximum values  which can be set  and the to   tals of I O data that actually have been set  If   while selecting I O modules    one of the maximum values is exceeded  a warning message will be dis     played   Example For the CJ1W PRT21  the first four I O modules have been selected  see fig   ure below   210 x   Device  CJ1W PRT21 GSD File  OC_0602 gsd  Vendor  OMRON Corporation Ident Number Ox0602    Configuration   Parameter   Group         r Device Settings  Station Address   2   IV Enable watchdog control Watchdog Interval   200 ms          m Module Configuration    Mak  length of input output data  360 Byte Length of input output data  60 Byte  Max  length of input data  200 Byte Length of input data  30 Byte  Maz  length of output data  200 Byte Length of output data  30 Byte  Max  number of modules  32 Number of modules  4    Available Modules     M
38.  PROFIBUS Master DTM has two main user interface components   e DTM Configuration User Interface  This user interface facilitates configuration of the Master Unit     e DTM Diagnostics User Interface  The DTM Diagnostics User Interface facilitates Unit status determination   slave status determination and changing the Unit s PROFIBUS opera   tional mode   This section provides an overview of the PROFIBUS Master DTM  and dis   cusses both user interfaces     2 3 1 Configuration User Interface    Opening the The configuration DTM is opened by  Configuration DTM e Selecting the Master DTM in the Network view  and double clicking the  left mouse button   e Selecting the Master DTM in the Network view  and right clicking the  mouse  From the context menu  select Configuration  The Master DTM  Configuration User Interface  which is displayed in the CX Profibus DTM  view is shown below     30                   CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3   ioi xi  Device Setup   Master Setup   Bus Parameters   Slave Area   Advanced   OK    omron Corea       Communication  e    ret_   r Settings  Station Address  fi  Unit Number  jo            Device Information    OMRON Corporation    Description        Firmware Version     Ident  Number  0742          Save         Note The Configuration User Interface for each of the two CS1 CJ1 PROFIBUS    Master DTM Configuration  User Interface    Configuration Interface  Buttons    A Caution    Master DTMs contains the same views and setting 
39.  PROFIBUS Master Unit  It allows  setting of the unit number to identify it on the PLC system and the device  address to identify it on the PROFIBUS network  It also will invoke the CX   Server interface to setup and test the communication between the PC and the  PLC to which the Unit is attached     The Device Setup tab has the following components        Settings Box The Settings box contains the setting the user must make before setting up  the communication and before testing the communication     Control Description  Station Address Address of the Unit in the PROFIBUS network  Default value is    1  but is should be changed if there is already another device  with that number     Unit Number This number must be the same as the number selected with the       Unit Number Selector switch on the front of the Unit  refer to the  CS1 CJ1W PRM21 Operation Manual  W409 E2      This num   ber is used in the communication between the PC and the PLC  to transmit the messages to the targeted PROFIBUS Master  Unit                      Configure Button The Configure button invokes the CX Server communications settings dia   log  CX Server is the driver software  providing the communication functional   ity between a PC and the PLC CPU  It is the basis for the OMRON   s CX Suite  programs     CX Server is provided with CX Profibus  but it may already be installed on the  PC  if other programs  for example CX Programmer have been installed     Note The CX Server is designed to manage th
40.  Rotation Time in ms     GAP Update The GAP update factor defines the amount of updates of the active devices  i e   Factor Master devices  list times during one token rotation cycle     To update the list  the Master device will transmit FDL_Status_request messages  to ascending device addresses until it finds a next Master device  or until it  reaches the Highest Station Address  See HSA below      Permissible values are in the range of 0 to 255     Max Retry Limit Maximum number of request transmission retries by this master if a device does  not reply to a request                       54    C200HW PRM21 PROFIBUS Master DTM Section 2 4       Item Description Unit   Editable  by User    Highest Station The HSA defines the Highest Station Address of Master devices on the network   Address of which the Master device will request the FDL status  when updating the active  device list  See GAP Update Factor     If new slaves are added to the network  this field shows the highest device  address The Master will periodically check whether new active devices have  been added between its own address and the Highest Station Address   Permissible values are in the range of 0 to 126    Data Control Time   The cycle time in which the master updates its Data Transfer List  in which it  keeps an overview of all slave states  Data Control Time is based on the  Watchdog time Twp  Data Control Time   6 Twp           Min  Slave Interval   The Minimum Slave Interval defines the poll cycle  i 
41.  The Unit may have been configured to  maintain its current mode  last mode was  OFFLINE  during download    The BF LED indicator is ON  A PROFIBUS  interface error has occurred  see Master  Status 2 error flags  CIO Word n 6  bit 00    03  see Note  for details     Determine the mode of the Unit  Check the  Master Status 1 Word  CIO Word n 5  bit 00  to bit 03  see Note   If Unit is in OFFLINE or  STOP mode     e Verify that the master does not use the  same address as another Master Unit on  the network  Otherwise  correct the Master  Unit   s PROFIBUS address    Verify that all Master Units on the network  use the same baud rate setting  Other   wise  correct the baud rate settings    Set CLEAR or OPERATE switch in ClO  Word n  see Note     Change the configuration to set the Unit  OPERATE mode when switching the PLC  to RUN MONITOR mode  see Master  DTM  Master Setup Tab   Download the  configuration  and switch the PLC to RUN   MONITOR mode           Network cabling is not correct   e BF LED indicator is ON     e Master Status 2 error flag may provide  more information  CIO Word n 6  bit 00    03  see Note     CIO Words n 9 to n 16 show which  slaves have problems        Verify that the network installation is correct   e Verify that all slaves are powered up and  functioning correctly   Verify that all slave devices are correctly  connected to the network   Verify that any repeaters used are func   tioning correctly   Check the cable length versus the  selected baud rat
42.  Unit  If the prob   lem persists  replace the PROFI   BUS Master Unit           The time information from the CPU Unit is used in the PROFIBUS Master    Unit     An error record is not created in non volatile memory when the error con     cerns an Error Log Write error     A 1    Number    Appendix A    Configurator Error and Warning Messages    Warning Messages    The table below lists the Warning messages which can be displayed by the PROFIBUS Master Unit DTM   These messages usually indicate that the user is about to perform an action  which will have significant impact   or an action which is only partly supported by the Unit  The user is given a chance to abort the function if the  impact is undesirable     Message    Change the PLC to PROGRAM  mode     Description    In order to start downloading a configuration  the   PLC must be set to PROGRAM mode  to prevent   I O data being exchanged with the Unit  during   the change of the configuration    e Yes Change state and download configura   tion     e No Stop download     When occurring  At the start of download   ing  in case the PLC is in  RUN MONITOR mode        DPV1 Slave slaves is assigned to  master  DPV1 slaves are not fully  supported     The PROFIBUS Master Unit supports only basic  DPV0 functions  This means that the DPV1 slave  can still be operated  but the DPV1 functionality  is not possible     e OK Close message box     At the start of download   ing  in case one of the  slaves is a DPV1 slave        Retu
43.  WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO  ADDRESS THE RISKS  AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED  FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM           PROGRAMMABLE PRODUCTS       OMRON shall not be responsible for the user s programming of a programmable product  or any  consequence thereof                    Disclaimers       CHANGE IN SPECIFICATIONS       Product specifications and accessories may be changed at any time based on improvements and other  reasons     It is our practice to change model numbers when published ratings or features are changed  or when  significant construction changes are made  However  some specifications of the products may be changed  without any notice  When in doubt  special model numbers may be assigned to fix or establish key  specifications for your application on your request  Please consult with your OMRON representative at any  time to confirm actual specifications of purchased products              DIMENSIONS AND WEIGHTS       Dimensions and weights are nominal and are not to be used for manufacturing purposes  even when  tolerances are shown              PERFORMANCE DATA       Performance data given in this manual is provided as a guide for the user in determining suitability and does  not constitute a warranty  It may represent the result of OMRON s test conditions  and the users must  correlate it to actual application requirements  Actual performance is subject to t
44.  a slave address to  that of another slave already assigned to the same Master Unit     Time  23 05 Date  04 Nov 03 1   CJ1 W PRM21 PROFIBUS Master Slaves should have unique addresses   Time  23 05 Date  04 Nov 03 1   CJ1W PRM21 PROFIBUS Master Slave address overlap detected  New address assigned  2    User  Administrator Us       26    By right clicking the mouse cursor in the Error Log view  a context menu is  displayed  This context menu provides the options listed below     CX Profibus       Section 2 2  Error Log view Context Menu  Menu item Description Equivalent menu command    Clear all entries Clears the entire Error Log view           Copy to clipboard Copies the entire contents of the Error Log view to the clipboard                     Hide Hides the Error Log view  View   Error Logging    FDT Monitoring view    Note    The FDT Monitoring view displays the communication between the FDT Con   tainer application  i e  CX Profibus  and any of the DTMs  The communication  is listed as a sequence of function calls from the CX Profibus to a DTM and  vice versa     The FDT Monitoring view is hidden by default  After starting CX Profibus  the  window will be displayed  by selecting the View   FDT Monitoring option from  the main menu     The purpose of the FDT Monitoring view is troubleshooting in case problems  occur with third party DTMs  The contents of the window can be copied to the  clipboard  to allow it to be pasted into another document or into an E mail   The mes
45.  before using CX   Profibus and the PROFIBUS Master Units  Start with the precautions in the following section  They  describe the operating environment and application safety measures which must be observed prior to  and when using the PROFIBUS Master Unit     The sections of this manual are as follows   Section 1 introduces PROFIBUS and Cx Profibus     Section 2 describes Cx Profibus and the DTMs in detail   Section 3 describes the operational aspects of CX Profibus   Section 4 provides procedures for troubleshooting the PROFIBUS network and the Units     The Appendices contain information supplementary to the information in the main body of the man   ual  They are referred to in the various sections as required     Contents  Describes the installation and operation of  the CS series PLCs     Products  SYSMAC CS series  CS1G H CPULILI E    Manual  CS series  Programmable Controllers  Operation Manual  CJ series  Programmable controllers  operation Manual  CS CJ series  Programmable Controllers  Programming Manual  CS CJ series  Programmable Controllers  Instructions Reference Manual  CX Programmer  Operation Manual       W339 E1                                SYSMAC Cu series  CJ1G CPU    W393 E1        Describes the installation and operation of  the CJ series PLCs                                   SYSMAC CS CJ series  CS1G H CPULIL E  CJ1G   CPU  SYSMAC CS   CS1G H CPU  CPU  SYSMAC WS02 CXP   CX Programmer    Describes the ladder diagram programming   W394 E1   instructio
46.  can be avoided by increasing the Watchdog Control Time in    107    Monitoring the Network    Section 3 7       Resume OPERATE mode    after Auto CLEAR    1 2 3       the Bus parameter set  see 3 4 2 Setting the Bus Parameters   Increasing  the Watchdog time will consequently increase the Data Control Time    The CS1 CJ1W PRM21 PROFIBUS DP does not automatically resume nor   mal operation after an Auto CLEAR has been initiated  In order to resume  normal I O data exchange  perform the following sequence     1  Determine which slave device failed during network startup or data ex   change  To do this  use the CS1 CJ1W PRM21 Master DTM Monitoring  User Interface or the slave DTM  see sections 3 7 1 Monitoring the Master  Unit and the Network and 3 7 2 Monitoring Slave Status  to determine the  slave and its type of failure    2  Remove the cause of the failure     3  Press the OPERATE Button in the Master Units Monitoring window     Alternatively  the Master can also be switched to OPERATE from the PLC pro   gram     3 7 Monitoring the Network    3 7 1 Monitoring the Master Unit and the Network    CS1 CJ1W PRM21 Master    DTM Diagnosis User  interface    108    1 2 3       Both the CS1 CJ1W PRM21 Master DTM and the Generic Slave DTM provide  special user interfaces to facilitate status debugging and diagnostics determi   nation  This section and the next will discuss the use and the features of these  diagnosis user interfaces     The CS1 CJ1W PRM21 Master DTM Diagnosis   Moni
47.  in the Network view     Open the device Catalogue  Either select the View   Device Catalogue  menu option  or press the fue  button in the Tool Bar     Select the device that must be added to the network    Select the Add Device button at the bottom of the Device Catalogue win   dow  The device DTM is added to the network    Note If a DTM is selected in the Device Catalogue  which can not be add     ed to the current location in the network  the Add Device button will  be disabled  which is shown as a grayed out button     Note When adding a CS1 CJ1W PRM21 Master DTM to the network  it is automat   ically assigned the PROFIBUS network address 1  This address can be    Note    changed  after opening the CS1 CJ1W PRM21 Master DTM     After adding the Master DTM to the Network view  repeat  one of  the proce   dures as outlined above to add slave DTMs to the Master DTM  In the proce     dures above  the highest level for adding slave DTMs is the Master DTM     When adding slave DTMs to the CS1 CJ1W PRM21 Master DTM  they are  automatically assigned their PROFIBUS network addresses  in ascending  order  i e  the first slave is assigned address 2  the second address 3  etc     The addresses can be changed in the slave DTM User Interface     The figure below shows an example network consisting of a CJ1W PRM21    PROFIBUS Master and three OMRON slave devices     oat  Unnamed      CX Profibus    File Edit View Device Tools Window Help    De tl  Z     MyNetwork  E  1   CJ1W PRM21 PRO
48.  is disabled  compressing the list can be accomplished  by pressing the Compress button  after all modifications to the mapping  have been made     The Advanced tab displays the settings required for PROFIBUS DP V1 Class  2 communication with Slave devices  The Advanced tab is shown below              al 1   CJ1W PRM21 PROFIBUS DP   1 Master   Configuration   5  x   Device Setup   Master Setup   Bus Parameters   Slave Area Advanced OK    m Acyclic Connections Abort Status Area Cancel    Area  cio  7  Help    Start Address  jo  Lenath  l 16 words          m Acyclic Slave Timeouts     200 x10 ms    All slaves              39    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Acyclic Connection Abort    Status Box    Note    Acyclic Connection Status    Flags    40    Note    The Acyclic Connection Abort status box contains settings  which allow the  user to define where in the PLC CPU memory the Connection Abort status bit  fields must be mapped  These bits indicated the open closed PROFIBUS DP   V1 Class 2 connections between the Master Unit and individual slave devices     The Acyclic Connection Abort status box contains the following information     Control Description    Selects the PLC memory area to which the Acyclic Con   nection Abort status bits will be mapped  Possible  options are  See Note    e Not Used  Default setting  Start Address and Length  will be set to 0    CIO    DM    Work   HR   EM Bank 0 to 12  Decimal    Start Address In this field the user can en
49.  is rejected by the slave device  The Parameter   request used LED indicator will also be ON    e Check the selected I O modules in the Slave DTM  Make sure they match the expected total  I O number and sequence    e Consult the operation manual of the slave device  Check if additional modules must be  selected  e g  empty i O modules for power modules in a modular slave         Extended diagnostics  received       The slave device has returned extended diagnostics information  This does not necessarily indi   cate a malfunction  The Master DTM does not display the extended diagnostics returned by a  slave device  Open the associated Slave DTM to check on the contents of the extended diag   nostis        125    Troubleshooting the Network    Section 4 2    LED Indicator Description   Correction    Function not supported    The Master Unit has sent a message to the slave device  which is not supported by that device        Invalid slave response    This bit is set by the Master Unit if the slave has returned an invalid response to a master  request message        Parameter fault    The parameters sent by the Master Unit are rejected by the slave device  The Parameter   request used LED indicator will also be ON    e Check the common parameter settings in the Slave DTM  Make sure the parameters are  within range  and match the physical configuration of the slave device    e Consult the operation manual of the slave device  Check if additional parameters must be  selected  e g  
50.  occurred during communication  between the master unit and the slave device as specified in the Station  Address field           Connected       When set to ON  this LED indicates that the C200HW PRM21 DTM is online  and exchanging data with the C200HW PRM21 PROFIBUS DP Master unit        59    C200HW PRM21 PROFIBUS Master DTM Section 2 4       2 4 3 Connecting to the C2Q00HW PRM21    Configuring  Communication    1 2 3       Downloading Parameters    60    For the purpose of downloading a configuration as well as monitoring the  C200HW PRM21 PROFIBUS DP Master DTM uses a dedicated serial driver  to connect to the Unit through one of the serial ports on the PC  To setup this  driver for communication to the Unit  perform the following procedure     Open the device   s context menu by    e Selecting the C200HW PRM21 Master DTM in the Network view  and    clicking the right mouse button     e Selecting the C200HW PRM21 Master DTM in the Network view and    from the main menu selecting Device     2  From the context menu select Additional Functions   Device Assign     ment  The driver window will open in the DTM view  as shown below     Device Assignment CIF Serial Driver i x     m Driver Description  Device Driver   OF Serial Driver    m Board Selection             Cancel         Name Type Version Date Error    rooms                  Conmectcoma    reme   E E T         _Conmectcom2    rems              fF   Connect com 3    roms   T E T E _ Connect com 4                  3  Ma
51.  of the  changes ignored the slave s parameter set  existing slave  with correct slave   parameter set    08 Set Parameters failed  Slave can    An internal error has occurred pre    Non recoverable  Master DTM tries  not be configured venting the master DTM from set  to assign a new bus address to the   ting changing the slave s bus slave DTM  but the slave DTM   s  address  database is locked    09 No slaves assigned  Download No slaves have been assigned to the   Retry download when at least one  aborted master  At least one slave must be   slave has been assigned    assigned    10 Slave s  has no modules  Down    A slave  or slaves  has no modules    Retry download when modules have  load aborted been added to the slave s  having   no modules    11 Configured EM bank  banks  is The configured EM bank  banks  are   Change the configuration to use only  not available in the connected not available in the connected PLC    memory areas available in the PLC  PLC Download aborted and retry download    12 Connected unit is busy  Download   Unit is busy with parameter storage    Retry download when parameter  aborted storage has finished    13 Slave configuration too big The total number of configured Reduce the configuration    parameter bytes and configuration  bytes does not fit into the FINS mes   sage for downloading   14 Maximum number of modules The total number of configured I O   Do not add any more modules to the       exceeded       modules over all allocated slave  de
52.  only View only Edit Edit Edit  settings    Go online Allowed Allowed Allowed Allowed Allowed  Monitoring Allowed Allowed Allowed Allowed Allowed    Change state and   Not allowed Not allowed Allowed Allowed Allowed  send commands    Export to HTML Allowed Allowed Allowed Allowed Allowed  Properties View only View only Edit Edit Edit   Open Allowed Allowed Allowed Allowed Allowed  Device settings View only View only Edit Edit Edit   Go online Allowed Allowed Allowed Allowed Allowed  Monitoring Allowed Allowed Allowed Allowed Allowed  Add DTMs Not allowed Not allowed Not allowed Allowed Allowed  Delete DTMs Not allowed Not allowed Not allowed Allowed Allowed  Properties View only View only Edit Edit Edit   Export to HTML Allowed Allowed Allowed Allowed Allowed  Change password   Not allowed Not allowed Not allowed Not allowed Allowed                            ke  Q  g  n  Oo     2   5  0  uw  O  fa  a                Generic  Slave DTM                Network       Management                         28    CX Profibus    Section 2 2       User Management    Changing Access Rights    Changing the Passwords    To change access rights or to change the passwords for the various access  levels  first login into the Administrator level  This allows you to select the  Tools   User Management option from the main menu in CX Profibus  Other  access levels do not have access to this menu option  The selection opens  the User Accounts window  as shown below     x    V Observer Change passw
53.  or dismounting the PROFIBUS Master Unit  Power Supply  Units  I O Units  CPU Units  or any other Units     e Assembling a Unit    e Setting DIP switches or rotary switches   e Connecting or wiring the cables    e Connecting or disconnecting connectors     Be sure that the terminal blocks  connectors  Memory Units  expansion  cables  and other items with locking devices are properly locked into  place  Improper locking may result in malfunction    Be sure that all the mounting screws  terminal screws  Unit mounting  screws  and cable connector screws are tightened to the torque specified  in the relevant manuals  Incorrect tightening torque may result in malfunc   tion    Leave the label attached to the Unit when wiring  Removing the label may  result in malfunction if foreign matter enters the Unit    Remove the label after the completion of wiring to ensure proper heat dis   sipation  Leaving the label attached may result in malfunction    Always use the power supply voltage specified in this manual   Double check all the wiring and connection of terminal blocks and con   nectors before mounting the Units    e Use crimp terminals for wiring  Do not connect bare stranded wires  directly to terminals     xvi    Application Precautions 5       e Observe the following precautions when wiring the communications  cable     e Separate the communications cables from the power lines or high ten   sion lines       Do not bend the communications cables       Do not pull on the communi
54.  provides all the options for configuration and monitoring of a device   which it can present to the user through its own user interface     The user interface for a DTM is provided using ActiveX windows  Control of  these windows is done by the DTM  but the FDT container application can  request specific user input from the DTM  based on which the DTM will pro   vide the necessary ActiveX windows  In general multi language user interface  windows  including DTM specific Help files are supported by the DTM     Data transfer to and from a DTM is provided using XML documents  The  XML documents are standardized for the communication between the FDT  container application and for communication between DTMs     An additional specification covers the definition of XML data formats for the  transfer of application specific data  such as PROFIBUS data     In general  a device configuration DTM is accompanied by a communication  DTM  This specific DTM facilitates device specific communication  e g  for  downloading a configuration to a PROFIBUS Master Unit and or for retrieving  monitoring information from PROFIBUS Master Unit  It may incorporate the  specific communication protocol  or rely on other available drivers     CX Profibus is a FDT container application  Together with this container appli   cation  OMRON provides five DTMs   e A DTM to facilitate configuration and operation of the CS1 CJ1W PRM21  PROFIBUS DP V1 Master Units  As of Unit version 2 0   e A DTM to facilitate c
55.  selecting the Auto Addressing check box   in the Master Setup tab  all slave I O data map    pings will be compressed in each of the I O map    pings  The slave I O mapping will be changed    e Yes Update slave I O module mapping and  check checkbox     Do not update slave I O module map  ping and uncheck checkbox     e No    When checking the  Auto Addressing check   box on the Master Setup  tab        Settings cannot be uploaded  unit  must be restarted  Would you like  to continue     The settings uploaded were not used by stack  e Yes  Restart the unit and upload the settings   e No  Do nothing     When attempting to  upload settings        Upload is not supported     Upload is not supported  e OK  Close message box     When attempting to  upload settings        After locking address it cannot be  changed any more  Would you  like to proceed     When sending Set Device Station Address com   mand with  Lock  check box is checked  the  address will be stored permanently in the Slave  device and can not be changed anymore    e Yes  Lock option is checked     e No  Lock option is unchecked     When    Lock    check box  in the Set Device Station  Address GUI is checked        DPV1 alarms are not supported  by the Master Unit and will be dis   abled     Alarm settings set by the Slave DTM are not sup   ported and will be reset     e OK  Close message box     Downloading settings  and one of the alarm bits  are set in Slave Parame   ter Set        Publisher functionality is no
56.  settings for either a PROFIBUS DP or a PROFIBUS PA  network  The following selections are possible from the drop down list   e PROFIBUS DP  Default bit rate  1500 kbit s   e PROFIBUS PA  Default bit rate  93 75 kbit s   Baud rate Defines the transmission rate on the PROFIBUS DP Network  The following baud  rate values are defined by the PROFIBUS DP standard   e 9 6 kBits s  19 2 kBits s  93 75 kBits s  187 5 kBits s  500 kBits s  1500 kBits s  default value   3000 kBits s  6000 kBits s  12000 kBits s  Slot Time The maximum time a Master Unit must wait for a response to a request message              Min  Station Delay   The minimum allowed time for a slave device before it will generate a response to  of Responders a request message        Max  Station Delay   The maximum allowed time for a slave device to generate a response to a   of Responders request message    Quiet Time The time a transmitting device must wait after the end of a message frame  before  enabling its receiver           Setup Time The time between an event and the necessary reaction   Station Address This value defines the device address of the C200HW PRM21 PROFIBUS  Master unit  Permissible values are in the range of 0 to 125     An attempt to change the address in to a value which is already occupied will  result in an error message     Target Rotation The anticipated time for one token cycle  including allowances for high and low  Time priority transactions  errors and GAP maintenance              Token
57.  slave diagnostics data  When continuing  sending I O data exchange data  the slave   s diagnostics data will not be  updated           Control Description   Continue if slave not The PROFIBUS Master Unit will continue to send I O data   responding exchange messages  when the slave device fails to  respond  The diagnostics data of the slave will not be  updated    Abort if slave not The PROFIBUS Master Unit will abort the data exchange   responding with the slave device  and continue to send diagnostics  request message to the slave  until it responds  The diag   nostics data of the slave will be updated accordingly        A slave   s failure to respond during I O data exchange will always be reported  to the PLC CPU  by resetting the corresponding Slave Data_Exchange Active  flags in the ClO Words  refer to the CS1 CJ1W PRM21 Operation Manual   W409 E2 L    If Auto CLEAR has been enabled  the failure to respond will  result in the PROFIBUS Master Unit switching to CLEAR mode  based on this  CIO flag                 The Diagnostics Update Delay defines the number of PROFIBUS DP cycles  during which the PROFIBUS Master Unit will ignore diagnostics message    67    Generic Slave Device DTM    Section 2 5       DPV1 Tab    68    Note    returned from the slave containing the Prm_Req flag  This flag indicates that  the Master Unit should re parameterize the slave  but in the case of reduced  performance slave devices  the returned flag also indicates that the slave  device is sti
58.  status bar will additionally  display a ix  symbol to indicate that new errors are available in the Error Log  view  Double clicking the symbol will open the Error Log view     2 2 3 Device Catalogue    Device Catalogue Main    Components    Invoking the Device  Catalogue    DTM view Layout    22    The Device Catalogue is one of the main components in CX Profibus  Its  main functions are    e to maintain a list of installed DTM and GSD files   e to provide convenient sorting and categorizing of the list   e to allow updating the list  after installation of new DTMs or GSD files   e to provide detailed information on selected DTMs  The main layout of the Device Catalogue is shown below     Device name File date           DTM categories Version number Vendor name    He Device Catalogue          t d  Device Types      d  Vendors   d  Groups      d  Protocols          585 2003 10 17   Bro      ABB IMDPO1 V2 4 2000 07 24 Deutschmann Automation Gmb   JZ ABB ACP6O0 NPBA     B 1998 08 12 ABB DRIVES      ABB PSR    2000 07 24 ABB DRIVES     C200HW PRT 21   1 0 2000 04 20 OMRON Corporation     CB_AB32 DPS Version 1 001 1998 07 01 Hilscher GmbH   a CIFIO4P DPS Version 1 000 2002 06 04 Hilscher GmbH   2 CIF30 DPS   CIF10    Version 2 011 2000 03 09 Hilscher GmbH   pa CIF50 DPS Version 1 000 2000 03 09 Hilscher GmbH      CIF60 DPS Version 1 000 2000 03 09 Hilscher GmbH   Re CIF80 DPS Version 1 000 2002 06 04 Hilscher GmbH     CIFPS1 DPS Version 1 010 2000 03 09 Hilscher GmbH   Be C w PR
59.  the CS1 CJ1W PRM21 Master DTM will calculate the bus param   eters  based on this information     Although the user can decide to modify some of these parameters  it is not  recommended to do that  Making the wrong configuration may lead to unex   pected behaviour     An example of the Bus Parameter tab is shown below                          a  1   CJ1W PRM21 PROFIBUS DP   1 Master   Configuration  iol x   Device Setup   Master Setup Bus Parameters   Slave Area   Advanced   OK    Baud Rate   g Eines Cancel    m Optimize Help      by standard     by user    Slot time    300 tBit Min Slave Interval        Min Station Delay of Responders  fi 1 tBit    Min Slave Interval        Max Station Delay of Responders  fis tBit Target Rotation Time    Quiet Time  0  Bit     Max Retry Limit D   Setup Time  1 tBit Highest Station Address  E   GAP Update Factor  1    Poll Timeout  10 ms  Data Control Time  140 ms  Watchdog Control  fo ms          The baud rate has been set to 1500 kBit s  The amount of slaves and the  amount of I O data  results in a poll cycle time of approximately 3 8 ms  Min  Slave Interval      After making the changes  select the Save button in the lower right corner of  the user interface to accept the changes  Next select the Slave Area tab to  display the I O Mapping     89    Configuring the Master    Section 3 4       3 4 3 Defining and Changing I O Mapping    Example    90    Note       The I O data of all slaves can be mapped on to the PLC memory areas   throug
60.  the network   of which the Master device will request the FDL status  when updating the active  device list  See GAP Update Factor     If new slaves are added to the network  this field shows the highest device  address  The Master will periodically check whether new active devices have  been added between its own address and the Highest Station Address  If any  devices are detected  GAP is updated     Permissible values are in the range of 0 to 126        GAP Update  Factor    The GAP update factor defines the amount of updates of the active devices  i e   Master devices  list times during one token rotation cycle    To update the list  the Master device will transmit FDL_Status_request messages  to ascending device addresses until it finds a next Master device  or until it  reaches the Highest Station Address  See HSA above      The GAP Update Factor is fixed to 1        Poll Timeout    The maximum time interval that this master device may need for the execution of  a master master function        Data Control Time    The cycle time in which the master updates its Data Transfer List  in which it  keeps an overview of all slave states  Data Control Time is based on the  Watchdog time Twp  Data Control Time   7 Twp        Watchdog Control    36       The Watchdog Control Time defines the time for a slave device to set its outputs  to a fail safe state  if during that time no communication between the Master  device and that slave device was detected  The Watchdog is automati
61.  to the new baud rate        Slot Time    The maximum time a Master Unit must wait for a response to a request message        Min  Station Delay  of Responders    The minimum allowed time for a slave device before it will generate a response to  a request message        Max  Station Delay  of Responders    The maximum allowed time for a slave device to generate a response to a  request message        Quiet Time    The time a transmitting device must wait after the end of a message frame  before  enabling its receiver        Setup Time    The time between an event and the necessary reaction        Min  Slave Interval    The Minimum Slave Interval defines the poll cycle  i e  the minimum time between  two consecutive Data_Exchange Cycles to the same slave device  The Minimum  Slave Interval must be smaller than the Target Rotation Time        Calculated Minimum Slave Interval in milliseconds        Target Rotation  Time    The anticipated time for one token cycle  including allowances for high and low  priority transactions  errors and GAP maintenance  Do not change the value  below the calculated value  to avoid bus communication interruptions        Max Retry Limit       Maximum number of request transmission retries by this master if a device does  not reply to a request              35       CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3  Item Description Unit   Editable  by User    Highest Station  Address    The HSA defines the Highest Station Address of Master devices on
62.  to the next available location in the  area  leaving behind a gap in the existing I O mapping  Subsequent I O  modules of other slave device will remain mapped as before the module  addition    When moving an I O module from one area to another  they can be  located anywhere with in the target area  They are not re mapped to the  start of that    When moving an I O module from one area to another  the module leaves  behind a gap in the I O mapping of the first area     1  Gaps in the I O mapping still contribute to the total size of an area  although  they do not contain valuable data  They therefore decrease the total I O ca   pacity of the CS1 CJ1W PRM21 PROFIBUS Master Unit  and unneces   sarily occupy PLC memory     2  Inthe I O data exchange with the PLC CPU  these gaps will contain zeros     I O Communication Characteristics Section 3 5       Example    Removing Gaps from the    I O Mapping    Compressing the I O    Mapping    1 2 3       The figure below illustrates the effects of re allocating I O modules  when Auto  Addressing has been disabled        ti 1   CJ1W PRM21 PROFIBUS DP   1 Master   Configuration      Device Setup   Master Setup   Bus Parameters Slave Area   Advanced      Output Allocation   Input Allocation       Bast  index   Device Mode lstre  Tye Jaon f        1 OMRON CJ1W PRT21 1 words output Word cosa  2 2 words output  pam   3 il CPM14 PRT21 2 bytes output  No consis   10 1 F150 PRT 1 words output              Module Name  3200   2  1 words output 
63.  will eventually lead to communication  problems    The marked parameters need to be recalculated  which can be accomplished  by pressing the Adjust button at the bottom right of the Bus Parameter tab   After re calculation the note symbol will disappear     Note In case of large networks  it may be required to increase the Watchdog time to  allow the network to become fully operational     Address Table Tab The Address Table tab displays the mapping of the I O data from to the allo   cated slave devices on to the internal I O memory of the Unit  The mapping  can be made automatically  but can also be changed by the user  before  downloading     The Address Table tab is shown below  containing example data        55    C200HW PRM21 PROFIBUS Master DTM Section 2 4            ti 1   C200HW PRM21   Configuration    O  x     Bus Parameters Address Table               CJ1W PRT21 1 word input output       2   2 CJ1W PRT21 2 word input output Iw 1   2 CJ1W PRT21 4 word input output Iw 3   2 CJ1W PRT21 8 word input output Iw T   3 CPM14 PRT21 2 byte output 15   3 CPM14 PRT21 2 byte input IB   4 BK3120 5 byte input output IB 16   4 BK3120 6 byte input output IB 19   4 BK3120 3 byte input output IB 22    Sort by station address C Sort by data address          Note The mapping in the Address Table tab does not define the mapping on to the  PLC memory areas  This is done by making the appropriate settings in the  unit   s DM areas  which are described in the C200HW PRM21 Operation Man   
64.  wis   1NI  D120 Pir Hi22 Hi Hi Wis                   C Not configured E  Running O Diagnosis E Not found H Ero  m Station Error   Station Address  4 Error event  No reaction of the remote station    Connected          The C200HW PRM21 DTM Diagnostics User Interface contains five fields of  information  These fields are described in the table below     LED Indicator   Description  Information Field    Operate Master Unit is in OPERATE mode  i e  the Master Unit exchanges I O data with  its slave devices     Clear Master Unit is in CLEAR mode  i e the Master Unit reads input data from the  assigned slave devices  but it sends zeros as output data to the slave devices     Stop Master Unit is in STOP mode  i e  the Master Unit may only communicate with  other Master devices and not with the assigned slave devices     Offline Master Unit is in OFFLINE mode  and not active on the PROFIBUS network              C  fo   2      g  fo  a  O  L   o  2  n           o  xe    e                 58    C200HW PRM21 PROFIBUS Master DTM    Section 2 4       Station Status    LED Indicator    Information Field    Timeout    Description    This indicator will be set to ON  when due to the number of rejected PROFIBUS  messages  the Master supervisory timeout has expired  This usually indicates a  short circuit in the PROFIBUS network  The amount of timeout events is dis   played in the Bus Monitoring field     The indicator will be set to ON upon the first occurrence of the timeout  It will not  b
65. 1  Adding records  131  Error log location  131  Error log records  131  Logged errors  131  Network  CS1 CJ1W PRM21 DTM  122  CX Profibus  using  122  I O communication  127  Slave devices  124  Overview  120  PROFIBUS DP V1 communication  130  PROFIBUS network  120    U    Unit number    See also CS1 CJ1W PRM21 DTM    V W    Warning messages  133    Wiring    144    Cable length  3    Index    Revision History    A manual revision code appears as a suffix to the catalog number on the front cover of the manual     Cat  No  WO5E EN 02    Revision code    The following table outlines the changes made to the manual during each revision  The page numbers of a  revision refer to the previous version     Revision Code Revised Content   July  2005 Initial version    May 2006 Changed document title    Page ix  Added note on terminology    Page ix  Added Warranty section    Page xv  Added precaution on slave configuration via PROFIBUS DP V1   Page 4  Updated text on version numbers    Page 6  Extended text on STOP mode capabilities    Page 8  Added GRT1 PRT DTM to bullet list    Page 10  Added GRT1 PRT DTM to bullet list    Page 11  Added Class 2 feature description to Master DTM   Page 11  Added description of GRT1 PRT DTM    Page 13  Added support for Class 2 messages to table   Page 29  Updated GUI image  new tab     Page 31  Added Ident number description to table    Page 31  Updated GUI image  new tab     Page 33  Updated GUI image  new tab     Page 35  Updated GUI image  new ta
66. 1 words output  3201   2  4 words output    3202 4 words output  3203 4 words output  3204 4 words output    3205   3  2 bytes output  No consiste   3206  10  1 words output   3207   3208    3209 xl          Initial I O configuration       i 1   CJ1W PRM21 PROFIBUS DP   1 Master   Configuration    4    Device Setup   Master Setup   Bus Parameters Slave Area   Advanced      Output Allocation   Input Allocation                Cl03400  C103200  e   ClO3401  Ci03204                       2  4 words output  3201 4 words output  3202 4 words output  3203 4 words output  3204  10  1 words output      2  1 words output  3401   3  2 bytes output  No consiste        3409 xl    The first Output modules  of slave device  2 and  3  were moved to Output area 2     97    I O Communication Characteristics Section 3 5       Enable Disable Auto    Addressing    1 2 3       Z  Caution    Note     O Mapping Without Auto    Addressing    98    Note    The example shows that the sequence of slave addresses is maintained  the  sequence of I O modules selected is maintained and the I O modules are allo   cated to the lowest address of the area     The Auto Addressing feature can be disabled in the CS1 CJ1W PRM21 Mas   ter DTM  In order to do that  perform the following sequence     1  Open the CS1 CJ1W PRM21 Master DTM   Configuration User Interface   2  Select the Master Setup tab     3  Enable Disable Auto Addressing by selecting deselecting the Auto Ad   dressing checkbox in the Support box     4
67. 2  Right click the mouse and a context menu will be displayed   3  From the menu select Add Device     4  A simplified Device Catalogue is displayed  The list only contains the de   vices which can be inserted at the selected network location  see figure be   low  only Master devices are listed      5  From the displayed list  select the device DTM to be added and select the  OK button  The Device DTM will be added to the network     Select Device xi       CJTW PRM21 PROFIBUS Master 3 62   2003 10 31   OMRON Corporation  CS1W PRM21 PROFIBUS Master 3 62   2003 10 31   OMRON Corporation          wa _   A    d    Setting up a network    Section 3 2          Using Drag  amp  Drop    1 2 3       Open the Device Catalogue  Either select the View   Device Catalogue  menu option  or press the Ml button in the Tool Bar     Select a device DTM in the Device Catalogue     Left click the mouse and Drag the mouse pointer to the desired location in  the network  i e  MyNetwork in the Network view     Release the mouse button and the device DTM will be added to that loca    tion    Note Master DTMs can only be added to the main branch of the Network   Slave Device DTMs can only be added to Master DTMs  Whether or  not a DTM can be added to the branch is indicated by the cursor     N indicates no addition  R indicates that addition is allowed     Using the Add Device Button       Example    1 2 3       1     Select the top of the network to which the DTM must be added  i e  select  MyNetwork
68. 3203 4 words output 3203   2  4 words output   3204 4 words output 3204 4 words output   3205  3  2bytes output  No consiste    3205 4 words output   3206 3206 4 words output   3207 3207     3  2 bytes output  No consiste     3208 3208          One I O module of two output  words was inserted  and re allocated  subsequent I O modules     Initial 1 O Configuration    Note The start address of Output area 1 in the example remains the same  after    Re allocating I O Modules    1 2 3       96    adding an I O module     After setting up the initial I O configuration  the I O modules can be re   mapped to the second Input Output area  This can be accomplished by using  drag  amp  drop to move the I O modules  To accomplish this  perform the follow   ing sequence     1  Open the CS1 CJ1W PRM21 Master DTM   Configuration User Interface     2  Select the Slave Area tab  The window shows two sub tabs  One for Output  Allocation and one for Input Allocation  The following points apply to each  of these tabs     3  After setting up the initial I O configuration  all I O modules will be shown  in the overall list in the upper half of the Slave Area tab  This is a pick list    I O Communication Characteristics Section 3 5       Auto Addressing and Re   allocating I O Modules    Example    from which modules can be selected  The allocated I O modules are listed  in area 1  the column on the left of the lower half of the window     Note The I O modules in the pick list  all remain there  T
69. 5 Adding Devices to the Network                  00 00000000   2 2 6 Saving and Opening Projects                  0 000000  e eee  2 2 7 Exporting toHTML          0    cect eee  2 2 8 Error Logging and FDT Monitoring                           2 2 9 Access Control and User Management                         CS1 CJ1W PRM21 PROFIBUS Master DTM                     0    2 3 1 Configuration User Interface                   000 000000005  2 3 2 Diagnostics User Interface                  0 00000 eee eee  2 3 3 Connecting to the CS1 CJIW PRM21                  000 2   C200HW PRM21 PROFIBUS Master DTM                      00    2 4 1 Configuration User Interface                    00 00000000   2 4 2 Diagnostics User Interface                0 0 0 0 eee eee  2 4 3 Connecting to the CLOOHW PRM21          0 0 00    eee  Generic Slave Device DTM            0    0 eee eee  2 5 1 Configuration User Interface                  0 000 000  2 5 2 Diagnostics User Interface                  0 00000     18  18  18  19  22  24  24  25  25  26  28  30  30  43  49  52  52  57  60  61  62  70    17    Installation Requirements       Section 2 1    2 1 Installation Requirements    2 2 CX Profibus    CX Profibus Configuration software is required to configure the PROFIBUS  Master before operating the network  Without a valid configuration the  PROFIBUS Master Unit will not be able to achieve data communication with  the slave devices on the network     The following are the minimum requirements for a P
70. 91  for details on configuring CX Server    Note 1  For further explanation  only the direct connections between the  PC and the PLC on which the Unit is attached are considered   These include ToolBus and SYSMAC WAY   2  Select the Settings button next to the Network Type selected  to  display the Network settings window  and select the Driver tab   Toolbus is shown as example below      Network Settings  Toolbus  x      Network Driver   Modem      Connection Data Format    Port Name  x  Data Bits fe 7  Baud Rate   115200 x  Parity   Nor e vy  1  lt        IV Baud Rate Auto Detect Stop Bits M    Make Default      Cancel Help         5  Make the necessary selections to facilitate communication between the  PC and the PLC CPU to which the PROFIBUS Master Unit is attached   and press the OK button     Testing CX Server Setup After making the settings  press the OK button to close the CX Server inter   face  In order to verify that the communication has been setup correctly  press  the Test button in the Device Setup tab of the DTM Configuration User Inter     50    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Note    Downloading Parameters    Monitoring    1 2 3       1 2 3       face  This will initiate a FINS command to read the Unit   s profile  i e  the name  of the Unit and the firmware version     If the communication has been setup correctly  the response of the FINS  command will yield the required information  which will be displayed in the  Device Information 
71. C to install the CX Profi   bus configurator software     e PC Pentium III or higher  500 MHz minimum  e Operating System  Windows 2000 SP2   Windows NT 4 0  SP6      Windows XP  e RAM  256 MB minimum  e Hard disk space  256 MB minimum  e Graphics resolution  1024 x 768 pixels minimum  e Serial port  RS 232C  COM1 to COM4 supported    e CD ROM drive    e Communication cable  Cable CS1W CN226 to connect to the peripheral  port on the CPU  Not included with CX Profibus     2 2 1 Starting CX Profibus    Starting CX Profibus    Login Window    Default Password    Z  Caution    Generating the Device  Catalogue    18    Select Program  OMRON  and CX Profibus  from the Start Menu if the  default program folder name is used     At startup  the CX Profibus splash screen will appear  on top of which a login  window as shown below will be displayed     CX Profibus Login x     User  Administrator S    Password   SS    Help Cancel            The Login window provides the selection of the access level as well as the  entry of the password belonging to the access level selected     The default password at the first start up of CX Profibus is    password    and is  applicable to all access levels  Type in    password     without the quotes  at the  password entry line and select OK     If access limitation to CX Profibus is required by the application  the password  should be changed as soon as possible  Changing passwords is only possible  on the Administrator level  Refer to Changing the P
72. CS1 CJ1W PRM21 Master DTM in the Network view and right   click the mouse to display the context menu     Select Download Parameters from the menu  to initiate a download  A  communication channel through CX Server will be opened automatically     When communication is achieved with the PLC  a warning window will be  displayed  notifying the user that the PLC will be switched to PROGRAM  mode  If the user confirms this  the download will continue     The downloading process is handled by the CS1 CJ1W PRM21 Master  DTM  The CS1 CJ1W PRM21 Master DTM will switch the Master Unit to  OFFLINE  commence the download  and after successful download  issue  a command to the Master Unit to store the parameter sets in the Unit  A  window is displayed to show the progress of the download     After storage has been completed  the CS1 CJ1W PRM21 Master DTM  will issue a command to restart the CS1 CJ1W PRM21 PROFIBUS Master  Unit  The new parameter sets will then become effective     After restarting the Unit  a warning window will be displayed  allowing the  user to switch the PLC CPU back to its original mode     When switching the PLC CPU back to its original mode  after download   the PROFIBUS Master Unit will behave according to the setting made in  the Master Setup Tab  see section 3 4 1 Setting the Master Parameters  lf  the Action to PLC mode change has been set to go to OPERATE mode   when the PLC switches to RUN MONITOR mode  the last action of the  download process may start up t
73. CX Profibus Ver  1 x    OPERATION MANUAL    WS02 9094G PROFIBUS Configurator  SYSMAC CS1W PRM21 PROFIBUS Master  SYSMAC CJ1W PRM21 PROFIBUS Master    CX Profibus Ver  1 x    Operation Manual  Revised May 29  2006    Notice   OMRON products are manufactured for use by a trained operator and only for the purposes described  in this manual     The following conventions are used to classify and explain the precautions in this manual  Always heed  the information provided with them     A DANGER Indicates information that  if not heeded  is likely to result in serious injury or loss of life      N WARNING Indicates information that  if not heeded  could possibly result in serious injury or loss of  life     Z  Caution Indicates information that  if not heeded  could possibly result in minor or relatively serious  injury  damage to the product or faulty operation     OMRON Product References    All OMRON products are capitalized in this manual  The first letter of the word Unit is also capitalized  when it refers to an OMRON product  regardless of whether it appears in the proper name of the prod   uct     The abbreviation Ch appears in some displays and on some OMRON products  It often means word  and is abbreviated as Wd in the documentation     The abbreviation PLC means Programmable Logic Controller     Visual Aids    The following headings appear in the left column of the manual to help you locate different types of  information     Note Indicates information of particular inte
74. DTM in the Network view   e Select the Device   Go Online option from the main menu  or the DTM  context menu  or  e Select the A button from the Tool Bar     2  Acommunication channel will be opened through CX Server  The name of  the DTM in the Network view  will turn to Italic font  to indicate that the Unit  is on line     3  From the context menu  select the Diagnosis option  The DTM   s Diagnos   tics User Interface will be displayed     51    C200HW PRM21 PROFIBUS Master DTM    Section 2 4       2 4 C200HW PRM21 PROFIBUS Master DTM    C200HW PRM21 Master  DTM    2 4 1    Master DTM Configuration  User Interface    Configuration Interface  Buttons    52    To allow configuration and data monitoring for a C200HW PRM21 from within  CX Profibus a C200HW PRM21 PROFIBUS DP Master DTM is available   which can be operated from CX Profibus   The C200HW PRM21 PROFIBUS DP Master DTM has two main user inter   face components   e DTM Configuration User Interface  This user interface facilitates configuration of the Master Unit   e DTM Diagnostics User Interface  The DTM Diagnostics User Interface facilitates Unit status determination   and the slave status determination   This section provides an overview of the C200HW PRM21 PROFIBUS DP  Master DTM  and discusses both user interfaces     Configuration User Interface    The configuration DTM is opened by  e Selecting the C200HW PRM21 Master DTM in the Network view  and  double clicking the left mouse button   e Selecting the Master 
75. DTM in the Network view  and right clicking the  mouse  From the context menu  select Configuration     The Master DTM Configuration User Interface  which is displayed in the CX   Profibus DTM view is shown below                       a5 x   Bus Parameters   Address Table    Profile   m Bus Parameters  Baud Rate  1500 kBit s 7  Station Address  1 4  Slot Time  300 tBit Target Rotation Time  A 11894 tBit  Min  Station Delay Time  11 tBit x 7 9293 ms  Max  Station Delay Time  150 tBit GAP Actualization Factor  10  Quiet Time  0 tBit Max  Retry Limit  1  Setup Time  1 tBit Highest Station Address  HSA   126  Bus Monitoring  Data Control Time  1200 ms J    Override slave specific Watchdog Control Time  Min  Slave Interval  2000 ps Watchdog Control Time  l 20 ms    Calculated Timing   Tidi  37 Bit I Auto Clear ON  Tid2  150 tBit Values marked with this symbol should be 3    B adjusted to changes in the topology  Adjust  OK   Cancel   Help               The Master DTM Configuration User Interface consist of two tabs   e Bus Parameters tab  e Address Table tab  The two tabs are discussed below   The Master DTM Configuration User Interface contains four general buttons     They are listed in the table below  together with the action taken when press   ing them     C200HW PRM21 PROFIBUS Master DTM Section 2 4    Button Action    Evaluate  and save the changes made  if any  and close the user  interface     Note If any invalid settings have been made  a warning message  will be display
76. Devices              0 00    e eee eee ee ees  3 3 1 Defining the I O configuration                   00     00008     3 3 2 Setting Parameters    3 3 3 Selecting the Group Assignment                      00000     Configuring the Master         3 4 1 Setting the Master Parameters                    00 00 0008   3 4 2 Setting the Bus Parameters                 00 00 0000 00008   3 4 3 Defining and Changing I O Mapping                      0    3 4 4 Configuring CX Server       0 0    ee ee eee  3 4 5 Downloading the Configuration                        008   I O Communication Characteristics           0 0 0 0  3 5 1 W O Data Configuration             0 0 0    eee    3 5 2 Mapping I O Data     3 5 3 Supported Data Types           00    0 2 eee eee eee    Operating the Network         3 6 1 User Access to the Network             0 00 00  0 eee ee eee  3 6 2 Changing PROFIBUS Mode of the Master Unit                  3 6 3 Transmitting Global Control Commands                       3 6 4 Using Auto CLEAR         0 0 00  ee eee    Monitoring the Network         3 7 1 Monitoring the Master Unit and the Network                    3 7 2 Monitoring Slave Status         00 0 0    0  eee eee eee  3 7 3 Using the Error Log      0    0    2c ee eee    PROFIBUS DP V1 Services    74  74  76  78  81  81  84  85  87  87  89  90  91  93  94  94  94  101  102  102  103  104  107  108  108  113  114  116    73    Introduction Section 3 1       3 1 Introduction    This section discusses the operat
77. Diagnostic Received  Oa Slaves in Data Exchange        15  x     Close    Help         44         Double Master Address Error       Hardware Error    O Mode Command Error        Parameter Error                The DTM Diagnostics User Interface contains two tabs     e The Monitor tab  This tab displays all Master Unit status and error information as well the  overall slave status information  which resides in the Master Unit    e The Online Operations tab  This tab contains controls to initiate state changes in the Master Unit as  well as transmit Global Control messages over the PROFIBUS network     The DTM Diagnostics User Interface   Monitor tab contains three sub tabs   e Master Status tab   e Slave Status tab   e Error History tab    Also  the Diagnostics data refreshing mode can be selected     e Automatic  The Diagnostics data is constantly retrieved from the Unit     e Manual  The Diagnostics data is retrieved only once from the Unit  when pressing  the Manual button     The Master Status tab  shown in the figure above  contains Diagnostics infor   mation regarding the Master Status  Each of the four status boxes  is related  to one of the Unit   s status words in the PLC CIO Area Memory  refer to the  CS1 CJ1W PRM21 Operation Manual  W409 E2 L     The status is indicated by red or green LED indicators  Red indicates an error  situation  green indicates a status indication  The LED indicators are listed in  the table below                 CS1 CJIW PRM21 PROFIBUS Master
78. FDT Monitoring view to the clip   board                 Hide Hides the FDT Monitoring view  View   FDT Monitoring    27    CX Profibus S Sc tion 2 2       2 2 9 Access Control and User Management    The FDT Standard defines four access levels and two attributes for FDT Con   tainer applications  which can be used to restrict access to the program or  certain features thereof for unauthorized personnel  The actual use of the  restrictions also depends on the application     CX Profibus implements the four levels as well as one of the attributes  These  levels are listed below    e Observer   e Operator   e Maintenance   e Planning Engineer   e Administrator  The access rights per level are defined in the table below     Function Observer Operator Maintenance Planning Administrator  Engineer    New file Allowed Allowed Allowed Allowed Allowed  Open file Allowed Allowed Allowed Allowed Allowed  Save File Not allowed Not allowed Not Allowed Allowed Allowed  Save As    Not allowed Not allowed Allowed Allowed Allowed  Properties View only View only Edit Edit Edit   Export to HTML Allowed Allowed Allowed Allowed Allowed  Open Allowed Allowed Allowed Allowed Allowed  Add GSD files Not allowed Not allowed Not allowed Allowed Allowed  Update Not allowed Not allowed Not allowed Allowed Allowed                   Project File             Catalogue   access    Device       Open Allowed Allowed Allowed Allowed Allowed  Master settings View only View only Edit Edit Edit    Communication View
79. FIBUS DP V1 PROFIBUS DP V1 is an extension to the PROFIBUS DP protocol standard  It  defines acyclic message services between a PROFIBUS DP V1 Master and a  PROFIBUS DP V1 slave device  These acyclic message services allow  exchange of extended parameter settings as well as extended diagnostics  and alarm information  during regular I O data exchange  PROFIBUS DP V1  devices must at least support PROFIBUS DP   PROFIBUS DP V1 services are designated as MSACn services  Master   Slave Acyclic  Class n   in which n designates the Master Class  i e  1 or 2    The CS1W PRM21 and the CJ1W PRM21 both support PROFIBUS DP V1  Class 1 Master functions as of Unit version 2 0        1 1 4 Bus Access Protocol    OSI Layer 2  Bus Access The PROFIBUS bus access protocol is implemented by OSI layer 2  This pro   Protocol tocol also includes data security and the handling of the transmission proto   cols and messages     Medium Access Control The Medium Access Control  MAC  specifies the procedures which determine  when a device is permitted to transmit data  A token passing procedure is  used to handle the bus access between master devices  and a polling proce   dure is used to handle the communication between a master device and its  assigned slave device s      Overview of PROFIBUS    Section 1 1       Token Passing    Polling Procedure    Multi peer Communication    Broadcast  Communication    Multicast Communication    The token passing procedure guarantees that the bus access right  the 
80. FIBUS Master     P 2 CJ1W PRT21   3 CPM1A PRT21   JEL 4 F150 PRT           77    Setting up a network    Section 3 2       Note that the slave DTMs all have the automatically assigned network  addresses  displayed to the left of the device name     3 2 2 Changing Device and DTM Addresses    Changing the Slave  Device Address    78    1 2 3       In order to achieve communication between the Master Unit and its allocated  slave devices  the latter must have the same physical network address as set  in the configuration  The network address on the slave devices are usually set    e through dip switches or rotary switches on the device  or    e remotely  using the dedicated Set_Slave_Add PROFIBUS service and  stored in the device     The physical address setting may differ from the slave DTM address  which  was automatically assigned by the Master DTM     Slave devices which are not equipped with switches to set the address  must  support the Set_Slave_Add PROFIBUS service  Typical device types sup   porting this address setting method are PROFIBUS PA devices or IP65  devices     The default address for these devices is 126  This allows them to communi   cate with a Master unit  with the purpose of changing the address  I O data  exchange with slave address 126 is not allowed  Usually  these slave devices  also provide a means to store the remotely set address in local non volatile  memory    As of Unit version 2 0  the CS1 CJ1W PRM21 PROFIBUS Master units sup   port the Set_Sla
81. HW PRM21 to PLC mem   ory mapping is limited to a total of 300 I O Words     56    C200HW PRM21 PROFIBUS Master DTM Section 2 4       Address Table Tab  Controls    Enable Auto Addressing    Changing Mapped  Addresses    Note    Sorting the Displayed  Modules    The Address Table Tab contains three controls  related to the I O mapping   The controls are discussed below     The C200HW PRM21 DTM provides Auto Addressing to facilitate easy map   ping of I O Modules  When enabled  the I O Modules are mapped in ascend   ing station address order  while preserving the Module sequence as selected  per Slave DTM     This means that when a new module is added for a particular slave device   the new module will be inserted in the already mapped I O Modules right after  the previous module of the same slave device  The consecutive modules   which were already mapped will move to higher addresses     In case Auto Addressing is not enabled  the user is allowed to change individ   ual mapped addresses by first double clicking the left mouse button on the  mapped address  after which the address can be manually changed  The  change will take effect  when selecting either the OK or the Apply button     1  In case a changed address overlaps another address in the I O Mapping   a warning message will be displayed indicating the location of the overlap   The overlap is however not automatically corrected     2  Incase the entered mapping address is located outside the range of inter   nal memor
82. M in the Network view    2  Right click the mouse to bring up the context menu    3  Select the Export to HTML option from the context menu     A window will pop up displaying the progress of the export process  When fin   ished  CX Profibus will launch the default browser to display the result  In this  case however  no links will be available to other DTMs in the network     2 2 8 Error Logging and FDT Monitoring    Error Log view    Purpose of the Error Log    Error Log Format    Error Log      CX Profibus provides two logging windows at the bottom of the application  window  Both windows are used for displaying events     The Error Log view displays error messages reported by the DTMs and by the  CX Profibus FDT container application  All messages include the Time and  Date of occurrence  as well as the DTM Name  as shown in the Network view     The purpose of the Error Log view is error reporting as well as troubleshoot   ing  The contents of the window can be copied to the clipboard  to allow it to  be pasted into another document or into an E mail  The errors themselves as  well as the sequence of errors may hold additional clues in case of problems     The format used in the Error Log view is  Time   lt Time gt  Date   lt Date gt     lt DTM name gt   lt message gt   The message displayed  originates from the DTM in which the error occurred     The figure below shows an example of an error message sequence  This  example sequence is generated after attempting to change
83. M21 PRO    3 62 2003 10 31 OMRON Corporation   E CJIw PRT21   1 0 2002 06 25 OMRON Corporation   2 COM C DPS Version 1 000 2002 06 04 Hilscher GmbH   2 COM DPS Version 2 010 2000 03 09 Hilscher GmbH   By Compact Slave Con    32 0 2000 07 24 Asea Brown Boveri   EL CPM14 PRT21 V1 0 2002 03 12 OMRON Corporation     COM1 PRT21 V1 0 2000 04 20 OMRON Corporation   Last CS1W PRM21 PRO    3 62 2003 10 31 OMRON Corporation of  E                               Help          Install GSD Files           Update Device Catalogue  Install a new GSD file    Add selected device to the network    The Device Catalogue window is opened by either selecting the jue  icon in  the CX Profibus toolbar or by selecting the View   Device Catalogue menu  option  Both options have toggle function  selecting one of them again will  close the Device Catalogue     The left view allows selection of specific groups of DTMs to be displayed  The  right view lists the DTMs  which are installed on the PC and which are avail     CX Profibus    Section 2 2       Note    DTM List Window    DTM Group Selection  Window    Note    Additional DTM  Information    able for setting up a network  A selection of DTMs is made by selecting a spe   cific group in the left view     The list makes no distinction between normal DTMs and GSD files which  have been loaded through the Generic Slave Device DTM     The list items in the right view are described in the following table     The Device column contains the names of the DTMs  
84. OM     A total of 80 error records can be logged in volatile memory     Up to 16 more serious system errors are also copied to non volatile memory     The error codes are described in the following table  The detailed error code  will provide detailed information on an error     Non   volatile    Detailed error code Correction    1st byte 2nd byte       Replace the PLC CPU Unit        CPU Unit service monitor error     Actual monitoring time ms  Hex    Check the operating environment        PLC Bus error     00 00 Replace the CPU Unit        Event time out    MRC SRC Replace the CPU Unit        CPU Unit memory error          01  Recreate the data specified by  the 2nd byte of the detailed error  code     02  Clear memory using proce   dure in the PLC operation manual     01  Read error   03  Routing  02  Write error   table                131    Error  code    Meaning    Destination address not in rout   ing tables  send failed     Detailed error code       1st byte 2nd byte    Commands  Bit 15        No routing table entry  send  failed     Bits 08 to 14   Bits 00 to 07    Responses       Routing table error  send failed     Bit 15   Bits 08 to 14   Bits 00 to 07       Too many relay points  send  failed        Header error  send failed        Unexpected routing error    Correction    Set the destination address in the  routing tables     Non   volatile       Set the local node  remote node  and relay nodes in the routing  tables        Create the routing tables cor   rectly
85. OU   Setup Time   1 Bit Highest Station Address  HSA  126   Bus Monitoring   Data Control Time   1200 ms      Override slave specific Watchdog Control Time   Min  Slave Interval   2000 ps Watchdog Control Time   ao ms  F P Ere    Bit I Auto Clear ON   HD e ea e a E          OK   Cancel   Apply Help            The Bus Parameters are settings  which define the communication behaviour  and timing on the PROFIBUS network  The Bus Parameters depend on the  selected baud rate  slave communication parameters as well as the number  of I O data bytes exchanged between the Master Unit and each of the slave  devices     The required combination of Bus Parameters is calculated by the program   based on the dependencies mentioned above  However  the user can change  selected Bus Parameter manually if the application requires this     53    C200HW PRM21 PROFIBUS Master DTM Section 2 4        N Caution Changing the calculated Bus Parameters manually is not recommended  and  should only be performed if this is really necessary  Changing the Bus Param   eters to an invalid combination  may result in Unit malfunctioning and unex   pected behaviour     Note The bus parameter calculations as performed by the C200HW PRM21 DTM  will differ from the calculations performed by the predecessor program  SyconDP  due to updated insights in bus calculation algorithms     The table below lists the parameters  shown in the Bus Parameter tab     Description Editable  by User    Profile Provides pre selected
86. PLC CPU     10    CX Profibus Configurator                 s   s    lt         s   sSsSsSSSSCSsSCQS ction 1 3       CS1 CJ1W PRM21 In addition to the PROFIBUS DP functions  the CS1 CJ1W PRM21 PROFI   PROFIBUS DP V1 DTM BUS DP V1 DTM provides     e A communication channel to the user to change a remote slave device  address  This channel has its own user interface    e Communication channels to facilitate data transfer  PROFIBUS DP V1  MSAC1 acyclic message transfer between a PROFIBUS DP V1 slave  device DTM and the physical slave device    e Communication channels to facilitate data transfer through PROFIBUS  DP V1 Class 2 acyclic message transfer between a PROFIBUS DP V1  slave device DTM and the physical slave device  This also allows direct  connection to third party PROFIBUS slave devices supporting PROFI   BUS DP V1 Class 2  e g  PROFIBUS PA devices     C200HW PRM21 DTM The C200HW PRM21 DTM allows configuration of the C200HW PRM21  PROFIBUS DP Master Unit  This predecessor of the CS1 CJ1W PRM21 can  be used on existing C200H PLC CPU Systems as well as CS1 PLC Systems   except for the CS1D    The C200HW PRM21 DTM consist of three parts    e The Settings DTM  which handles the settings for the C200HW PRM21  PROFIBUS DP Master Unit  including the bus parameters settings  and  the I O data mappings    e The Monitoring DTM  to handle the Units status monitoring  The DTM   s  user interface displays the Master status and Slave status    e The communication DTM  providing the i
87. S Master DTM    Section 2 3       Changing Mapped Data  Allocations    1 2 3       Note    Advanced Tab       4  Before Compressing  the Master DTM will display a warning message  prompting the user for confirmation of the action     By default  the data is mapped to Area 1 in both the Output and Input Alloca   tion tabs  It is however possible to map a part of the data to the second area in  the same tab  For example  an application may require to store all byte data in  one location and all word data in another     Moving data mapped in one Area to another Area is done from the module  list  The procedure is as follows     1  Find the module which must be mapped to a desired Area in the module  list  and select it     2  Left click the module and drag it  while holding the Left mouse button  to  the desired Area  This can be the end of the list or any empty space in the  list in which it will fit  See Note      3  Release the mouse button  The module data is copied in the desired Area  and appended to the already existing list  The same entry in the other list  is now deleted     4  Finally  the PLC memory address to which the module is mapped is now  updated in the module list     1  If Auto Addressing is enabled  see Master Setup tab in this section   any  empty spaces evolving out of moving of modules to another Area will be  removed by compressing the list  Modules located to a higher address will  be moved to a lower address to fill up the gap     2  If Auto Addressing
88. Setting of PROFIBUS DP Extension parameters    e Setting of PROFIBUS DP V1 dependent parameters        Group setting    The Group setup function allows definition of the group to which the  associated slave device will belong        Monitoring functions    The Monitoring functions provides a display of    Standard Slave diagnostics flags   Extended diagnostics messages           Support functions       Context sensitive help functions   Multi language support        CX Profibus Configurator              s    lt    s     s   sSsSsSsSSSsSCQS ction 1 3       Note For more information on the GRT1 PRT DTM  refer to the SmartSlice GRT1   series GRT1 PRT PROFIBUS Communication Unit Operation Manual   WO4E EN L                   15    SECTION 2  Configuration Software    This section contains the procedures for installing the configuration software  It also presents an overview of the  Configuration software and discusses the main aspects of defining a PROFIBUS configuration  A more detailed description  of the use of the Configuration software can be found in SECTION 3 Operation     2 1  2 2    2 3    2 4    2 5    Installation Requirements          00    cece eee teens  CX  Profibus ns  beeent Se DOES Saab ER RE Giets A eE Gute BORO RA  2 2 1 Starting CX Profibus            0 0 0    eee eee eee  2 2 2 CX Profibus Main Window                 00 0002 e eee eee  2 2 3 Device Catalogue            0 0    cee cee eee  2 2 4 Updating the Device Catalogue                       00000   2 2 
89. Slave station 48   63  Word n 12   79   78   77   76   75   74   73   72   71   70   69   68   67   66   65   64   Slave station 64   79  Word n 13   95   94   93   92   91   90   89   88   87   86   85   84   83   82   81   80   Slave station 80   95  Word n 14   111  110  109   108  107  106   105   104   103  102  101   100  99   98   97   96   Slave station 96   111    Word n 15 125  124  123  122  121 120  119  118 117  116 115  114 113 112  Slave station 112   125                                                                      Note In the above figure  n is the start address of the memory locations  defined by  the Area and Start Address setting in the Acyclic Connection Abort Status  Box     Controlled Unit operation  by  Acyclic Connection If the bit corresponding to a slave device address is ON  it indicates that  Abort flags the PROFIBUS Master Unit has aborted a PROFIBUS DP V1 Class 2  type connection   If the bit corresponding to a slave device address is OFF  it indicates  that no abort action of a PROFIBUS DP V1 Class 2 type connection  has been performed                       Slave Timeouts The Acyclic Slave Timeout defines the timeout value for PROFIBUS DP V1  Class 2 connections to slave devices  If a PROFIBUS DP V1 message is sent  to a specific slave device  the timeout is used to monitor the response from  the slave device  If a response is not received with the specified timeout inter   val  the connection will be aborted by the Master unit     The v
90. These functions are implemented as of Unit version 3 0        Support functions    e Context sensitive help functions   e Multi language support              O  o     a  a  z         oS  A  O    Bus parameter setup    The bus parameter setup allows the selection of baud rate and calcula   tion and editing of specific bus parameters        Address mapping setup    The address mapping setup shows an overview of the mapping of the     O data of each Slave on to the Unit   s memory  The mapping can be  accomplished automatically  but the function also allows editing of indi   vidual address mappings        Monitoring functions    e Master status read out   e Slave status read out        Support functions    e Context sensitive help functions   e Multi language support        Generic Slave DTM    14    General functions    The Generic Slave DTM reads the contents of a specific GSD file  located in a special sub directory  and displays the setup options to the  user  It supports   e GSD file revisions 1 and 2  PROFIBUS DP functionality     e GSD file revisions 3  PROFIBUS DP V1 functionality         I O configuration setup    The I O configuration setup function allows   e Selection of device address    e Enable disable watchdog    e Overview of available I O modules     e Selection of I O modules  including Addition  Insertion and Removal of  multiple modules        Parameter setup    The Parameter setup function       Setting of common as well as module dependent parameters      
91. Time of day format contains time since  midnight     Not Supported     Time of day format is transferred to PLC  memory as string of words        Time difference          Supported    Time difference format is the same as  Time of day format  but contains a time  difference        Not Supported     Time difference format is transferred to  PLC memory as string of words        101    Operating the Network    Section 3 6       3 6 Operating the Network    3 6 1    Access to the Unit    102    1 2 3        N Caution    User Access to the Network    There are several ways through which a user can have access to and control  over the PROFIBUS network   e Through a PLC user program  A PLC user program can set the operational mode of the Unit  send Glo   bal Control commands  read Master and slave status   diagnostics infor   mation  and access the Unit s Error Log  Furthermore  the I O data  transferred between the PROFIBUS network and the PLC memory  and  can be used by the user program     e Through CX Profibus  The CS1 CJ1W PRM21 Master DTM Diagnosis User Interface provides  the user with buttons to set the operational mode of the Unit  send Global   Control commands  read Master and slave status information  and access  the Unit   s Error Log    e Through any other CX Server based program  capable of accessing PLC  memory areas and communicating through FINS messages  e g  CX Pro   grammer  CX Supervisor  etc    This section will explore both means to control the CS1 CJ1W PRM21
92. W PRM21 DTM  Medium Access Control  4  Monitoring  CS1 CJ1 PRM21 Master Unit  6  Monitoring Time  6  Slave device  6  Monitoring slave status  113    Multicast communication  See Global Control    N    Network operation modes  CLEAR  6  OFFLINE  6  OPERATE  6  STOP  6    O P    OMRON  Copyright notice  iv  Operation modes  SeeNetwork Operation modes  6  OSI reference model  2  ISO 7498  2  Layer 1  Physical Layer  2  Layer 2  Data Link Layer  2    Layer 7  Application Layer  2  Password  Default  18    Polling procedure  5    Precautions  Application  xvi  General  xiv  Operating Environment  xv  Safety  xiv    PROFIBUS  Device profile  4  Master  Class 1 Master  DPM1   4  Class 2 Master  DPM2   4  Network  Changing mode  103  Indirect mode changes  103  Mode changes  103  Monitoring  108  Operational modes  6  User access  102  PROFIBUS DP  Decentralized Periphery  2  PROFIBUS DP V1  4  PROFIBUS FMS  Fieldbus Message Specification  2  PROFIBUS PA  Process Automation  2    PROFIBUS DP V1 services  116  Acyclic abort status  41  Acyclic connection status  40  Configuring using DTM  39  116    R    RS 485  Cable length  3  Transmission medium  3  Transmission speed  3    S    Safety Precautions  xiv  Setting up a network  74  Slave devices  4  Sync   See Global Control    T    Token passing  5  Trademarks  iv  Transmission medium  3  RS 485  3  Transmission speed  3    Troubleshooting  CS1 CJ1 PRM21 Master Unit  120    143       CX Profibus  120  Error codes  131  Error log  13
93. a  360 Byte Length of input output data  60 Byte  Max  length of input data  200 Byte Length of input data  30 Byte  Max  length of output data  200 Byte Length of output data  30 Byte  Max  number of modules  32 Number of modules  4    Available Modules     1 word In Out OxFO  2 words In Out OxF1  4 words In Out OxF3  8 words In Out OF   miords In Out NFF            ofl    1  4          Insert Append  Configured Modules     Slot   Module Name   Module Configuration Identifier    1 1 word In Out OxFO  2 2 words In Out OxF1  3 4 words In Out OxF3  4 8 words In Out OF        Remove             In general  the Configuration User Interface for the Generic Slave Device  DTM  contains three tabs  Above these tabs the Device  the Manufacturer  the  GSD file and the Unit   s PROFIBUS Ident number are displayed     The three tabs allow the user to set the slave parameters and configure the  I O for a standard PROFIBUS DP slave device  For slave devices which sup   port the extension PROFIBUS DP V1  to additional tabs will be displayed   These tabs are discussed later     The Configuration tab contains the Device settings and the I O module config   uration     The Device Settings contain the device address  i e  the Units PROFIBUS  address and the Watchdog time for the Unit  The device address is normally  set automatically by the Master DTM  when the slave DTM is added to its  tree  However  the user has the opportunity to change the address  The  changed address will be transferred 
94. ain window  refer to figure above   The standard windows File   Open  window will be displayed    In the File   Open window browse to the sub directory containing the GSD  file  select the  one or more  GSD file s  and press the Open button in the    75    Setting up a network    Section 3 2       3 2 1    Using the Context Menu    window  The GSD file s  will be copied to a sub directory of the CX Profi   bus directory     3  After completing the copy  a window will be displayed  asking the user per   mission for an update of the Device Catalogue  see figure below   If more  GSD files need to be installed  select the No button and continue with in   stallation of GSD file  Otherwise  select the Yes button     Question   CX Profibus x         To complete the import the device catalogue must be updated   sZ Do you wish to do this now         _ w       Note Updating the Device Catalogue may take several minutes  depending on the    number of installed GSD files     Adding Devices to the Network       76    1 2 3       If the Device Catalogue is up to date  it can be used to setup the network  Set   ting up a network in CX Profibus starts with adding single device DTMs to the  Network view  First the CS1 CJ1W PRM21 Master DTM must be added to the  main branch of the project Network  To do so  one of three procedures as out   lined below must be used to add the DTM     1  Select the top of the network to which the DTM must be added  i e  select  MyNetwork in the Network view     
95. all I O modules in an area as close to the start of  the area as possible  Compressing an area does not change the sequence of  the slave devices and or the I O modules  It only removes the unused memory  gaps  Compressing can be initiated for each area individually     In order to compress an area  perform the following sequence     1     Open the CS1 CJ1W PRM21 Master DTM   Configuration User Interface   and select the Slave Area tab     Select the Output Allocation tab or the Input Allocation tab  to display the  areas to compress     To compress the area  press the Compress button at the bottom     After finalizing the compress action  select the Save button at the lower  right corner  to save the changes made     99    I O Communication Characteristics Section 3 5       Note Compressing an Input Output area has no effect on the start address of the  area     Example The figure below  shows the effects on the previous example  after pressing  the Compress button in both Output areas                    saa  Device Setup   Master Setup   Bus Parameters Slave Area   Advanced   OK    Output Allocation   Input Allocation   Cancel       Addr   Index  Device    Module   p Hee    2 1 OMRON CJTW PRT21 1 words output 1 Word  Cl03200  2 2 words output 2 Word  CI03400  3 4 words output 4 Word CI03201  3 1 CPM14 PRT21 2 bytes output  No consis    2 Byte   CI03205  10 1 F150 PRT 1 words output 1 Word  CI03206  fs  m Output Area 1  r Output Area 2   3200   2  1 words output 3400   2  2 
96. alue can be set in the range of 1 to 32767  and is expressed in units of  10 ms   Additional functions Two additional functions are provided to the user  via the DTM context menu   e Slave DTM Address Assignment     e Set Device Station Address  only available on DTM version 0 2 0 0 or  higher and for CS1 CJ1W PRM21 Unit versions 2 0 or higher      To select these options perform the following steps     1 2 3    1  Select the Master DTM in the Network view     2  Right click the mouse  and select the Additional functions entry from the  context menu     3  Select the desired function     41    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3    Slave DTM Address    Assignment    Set Device Station  Address    42    1 2 3       Note    Selecting the Slave DTM Address Assignment displays a list of DTMs  assigned to the PROFIBUS Master DTM  together with their Station address               ioi xi  M DTM Station Address Assignment    lose     No   DTM Name  1 OMRON CJ1 W PRT21 2 Help    2 CPM14 PRT21 3  3 CQM1 PRT21 4  4 C200HW PRT21 5  5 F150 PRT 6  6 PRT1 COM 7  Status  a Address   19          zi Set               When assembling the network  the PROFIBUS Master DTM will automatically  assign a station address to each new slave DTM  The purpose of the Slave  DTM Address Assignment function is to allow the user to change the DTM  address of one or more devices  to make it the same as the actual physical  address of the device on the network     In order to change an address perfor
97. alue will be that number    The user can set the Length value to up to 7168 words     Occupied This field display the actual length of the data block  not  necessarily the same as the amount of data in it   This  length includes both data and any gaps between mod   ules  Gaps may only be there if Auto Addressing option  in the Master Setup tab is disabled   See also Note 2      Compress button Pressing the Compress button will compress the Area  list associated with it  i e  this action will remove all gaps  from the mapping list by moving all mapped I O modules  as close to the start of the memory area as possible    See Notes 3 and 4                        Note 1  Ifthe selected PLC memory area  on to which the data must be mapped is  not supported by the PLC CPU  a warning message will be displayed upon  downloading the configuration     2  If an invalid setting is made the Occupied length value will change its co   lour to red  indicating an invalid setting  In addition  a warning message will  be displayed  upon saving the changes  Invalid settings are for example   e The start address and length definitions of the data block will cause it  to exceed the area in the PLC    e The data mapping of two or more I O Areas  Output and or Input  will  be overlapping each other partly or totally in the PLC memory     3  The Compress button will be disabled  i e  grayed out  when Auto Ad   dressing  see Master Setup Tab on page 33  has been enabled     38    CS1 CJIW PRM21 PROFIBU
98. andard selections are  available   e 1 alarm of each selected type   2 alarms in total   4 alarms in total   8 alarms in total   12 alarms in total   16 alarms in total   24 alarms in total   32 alarms in total  Pull Plug alarm When set  this checkbox enables the signalling of a pull   plug alarm type  i e  the removal insertion of a hardware   O module           Process alarm When set  this checkbox enables the signalling of a pro     cess alarm type  i e  an alarm related to the process con   nected to the I O     Example  Upper Limit exceeded alarm    Diagnostic alarm When set  this checkbox enables the signalling of a diag   nostic alarm  i e  an alarm related to the functioning of a  specific I O module in a slot    Example  Short circuit detected    Manufacturer specific When set  this checkbox enables the signalling of a Manu   alarm facturer specific alarm    Status alarm When set  this checkbox enables the signalling of a Status  alarm  i e  an alarm related to an internal state change ina  module    Example  Change to Run state  Stop state    Update alarm When set  this checkbox enables the signalling of an  Update alarm  i e  an alarm indicating a change in the  parameters related to a specific module  either by local or  remote access                       Extra Alarm SAP For acyclic data exchange between a PROFIBUS DP V1 Master Unit  Class  1  and a PROFIBUS DP V1 slave device one specific SAP  Service Access  Point  the PROFIBUS definition for a message identifi
99. as provided by  the DTM or the GSD file  If the device is defined by a GSD file  the  Generic Slave Device DTM reads out the GSD file entry    Model  Name     The string provided by this variable is the name displayed in  the list        Version The version number defines the revision number of the device  If the    device is defined by a GSD file  the Generic Slave Device DTM reads  out the GSD file entry    Revision     The string provided by this variable is  the version number displayed in the list     Date For DTMs  Date is the date associated with the revision  For GSD file  based slaves  the date listed in this column is the date the GSD file  was last modified     Vendor The Vendor name is provided by the DTM or the GSD files                 The left view allows selection of specific groups of device DTMs with common  attributes  e g  Vendor name  Protocol type etc  If a group is selected  all  device DTMs which belong to that group will be listed in the right view  The  table below lists the possible groups that can be selected     List item Description   Sub groups  which can be selected are    e Communication DTMs  e g  PROFIBUS Master devices  e Gateways  e g  to another network type   e Modular devices   e Other devices  e g  slave devices    Vendors   Sub groups  which can be selected are all available vendors  This  information is provided by each DTM  It allows the user to select a  group of devices from one vendor    Groups Sub groups are the device types  e 
100. asswords for an explana   tion on how to change passwords     After entering the correct password  CX Profibus will start up and open  The  first time CX Profibus is started  the Device Catalogue will still be empty     CX Profilus ction 2 2       Therefore  the following window will be displayed on top of the CX Profibus  application window     Question   CX Profibus xi         DY Would you like to update the Device Catalogue      eae      Select Yes to generate the Device Catalogue for the first time  This action may  take several minutes depending on the number of installed DTMs     After updating the Device Catalogue  it will open in the CX Profibus applica   tion window     2 2 2 CX Profibus Main Window    The main application window of CX Profibus will open with a New Project   After the first start up  the Device Catalogue will be opened automatically  If  not  the Device Catalogue may be opened from the menu     The figure below shows the opened CX Profibus application window with a  Project already containing a network  and the Device Catalogue window  opened     Tool Bar Network view Device Catalogue       E  m  MyNetwork   1  CJ1W PRM21 PROFIBUS   T 2 C 1Ww PRT21     amp  3  CPMIAPRT21    CQM1 PRT21     C200H W PRT21     F150 PRT     PRT1 COM     He Device Catalogue    Device Types   Vendors m      BECKHOFF INDUSTRIE E      Groups P    V1      OMRON Corporation   Protocols OMRON Corporation  OMRON Corporation  OMRON Corporation  OMRON Corporation  OMRON Corporation
101. ast the common parameters  These  parameters apply to the whole slave device     e Module Parameters  Modular slaves often apply parameters related to a specific I O module   e g  the physical slave device consist of a number of hardware modules   each defining an amount of I O data  requiring its I O module selection  and requiring its own parameters     Configuring the Slave Devices Section 3 3    Example    Example    Note    The Parameter tab of the CJ1W PRT21 is shown in the figure below  It lists  the common parameters for the CJ1W PRT21     lox   Device  CJ1w PRT21 GSD File  OC_0602 gsd  Vendor  OMRON Corporation Ident Number  Ox0602    Configuration Parameter   Group      Module    Common hd      Parameters         Fail Safe support ON  default   Watchdog Base 10 ms  default   Output data on PROFIBUS fail Reset to 0  default   Output data format    Output to slave PLC area CIO area  ClOxxxx  ha  Output area start address   Action on slave PLC PROGRAM mode  Action on slave PLC 1 0 bus fail Work area  W xxx    Input data format Holding area fel   Input from slave PLC area D area KKK   Input area start address 0x0032   Slave PLC status indication PROFIBUS diagnostics only              CIO area  ClO xxx   Data Memory  Dxxxxx        T Decimal values       0K   Cancel   Apply   Help         In the figure above  the parameter captions are listed in the left column and  the options can be set in the right column  In order to change settings  double   click the required parame
102. ation has been setup correctly  press  the Test button in the Device Setup tab of the DTM Configuration User Inter   face  This will initiate a FINS command to read the Unit   s profile  i e  the name  of the Unit and the firmware version     If the communication has been setup correctly  the response of the FINS com   mand will yield the required information  which will be displayed in the Device  Information box  in the Description and Firmware Version fields  If the com   munication is not setup correctly  the two fields will contain three dashes  i e              and an Error message will be displayed in the Error Log view of CX Profi   bus  The communication settings must be changed to the correct value first   Refer to Appendix A Configurator Error and Warning Messages for more infor   mation on communication and download errors     Since CX Server is the common driver software for connection between PC   based CX  programs  e g  CX Programmer  CX Supervisor  etc   and the  CS1 CJ1 series PLC  all these programs can communicate simultaneously  with the PLC  However  the settings for CX Server made through each of  these programs have to be exactly the same  to allow simultaneous communi   cation     Configuring the Master    Section 3 4       3 4 5 Downloading the Configuration    Downloading Parameters In order to download the parameter sets to the CS1 CJ1W PRM21 PROFI   BUS Master Unit  the following sequence must be performed     1 2 3    1     Note 1     Select the 
103. ation to the Unit  perform the following proce     dure     LP    3     Open the CS1 CJ1W PRM21 Master DTM Configuration Interface  Device    Make sure that the Unit Number has been set to the unit number set on the  PROFIBUS Master Unit  through the rotary switch on the front     Select the Configure button to start CX Server     Up on pressing the Configure button  CX Server is launched and displays the  CX Server User Interface as shown below                       Device Name  PLO  m Device Type   EM x  Settings        Network Type     Toolbus x  Settings       re amment                     Cancel      x     In order to configure CX Server for communication with the Unit  perform the    following procedure     1     Select the type of PLC to which the Unit is attached  from the Device Type  drop down selection box     2  Press the Settings button next to the PLC type selected  The PLC settings    3     window  see figure below  is displayed     Device Type Settings  CJ1M   gt     General       gt  CPU Type  z  r Total Program Area Size    fir  Step  z   I Read Only    r Expansion Memory   None z   F Read Only                           File Memory   None x  I    Read Only     Timer   Clock        M Installed             Make Default      Cancel Help         In this window make the proper adjustments if necessary  The selections  made  must match the physical configuration of the PLC system  When  done  press the OK button     91    Configuring the Master    Section 3 4     
104. atus      OPERATE   Unit Error    sToP   Master Eror      CLEAR     Local Parameter Storage Error    OFFLINE     Local Parameter Load Error  O File Read Error     Data Exchange    Unit Memory Error       Auto Clear Enabled   Error Log Updated    Valid Configuration OD Parameter Storage in Progress  m Master Status 2 p Slave Status  O Disturbed Bus Error OD Slave Diagnostic Received  E PROFIBUS Protocol Error O All Slaves in Data Exchange       Double Master Address Error    Hardware Error       Mode Command Error      Parameter Error  Reading the Error Log The Error Log can now be retrieved from the Unit  and displayed through the    CS1 CJ1W PRM21 Master DTM Diagnosis User Interface  To retrieve and  view the Unit   s Error Log     1 2 3    1  Open the CS1 CJ1W PRM21 Master DTM Diagnosis User Interface     2  Select the Monitor   Error History Tab tab     3  If the Automatic checkbox in the Refresh box has not been selected  press  the Manual button to retrieve the Error Log contents from the Unit     As an example  the contents of the Error Log as it is displayed is shown in the  figure below  In this case a Hardware Error has been detected on the PROFI   BUS network     wti 1   CJ1W PRM21 PROFIBUS Master   Diagnosis       Monitor   Online Operations      Master Status   Slave Status Error History             Content  00219 O0x0000 PROFIBUS hardware error    Entry   Time  a 03 Mar 04 17 26 49       Note Reading the Error Log contents will not clear it   Clearing the Error L
105. b     Page 36  Renamed controls in table        Page 37  Added description of new DTM settings after note   Page 37  Corrected DTM version number in Additional Functions text     Page 63  Added note to Fail Safe Behaviour    Page 64  Added note on PROFIBUS DP V1 Class 1 to DPV1 Tab description   Page 83  Updated GUI image  new tab     Page 84  Updated GUI image  new tab     Page 86  Updated GUI image  new tab     Page 86  Updated GUI image  new tab     Page 86  Improved Caution text    Page 93  Updated GUI image  new tab     Page 95  Updated GUI image  new tab     Page 96  Updated GUI image  new tab     Page 112  Added Section 3 8    Page 121  Updated text above table    Page 121  Added baud rate to table as item to check correct    Page 124  Added section 4 2 4 related to PROFIBUS DP V1 Troubleshooting   Page 125  Added error log details when using routing tables    Page 127  Updated warning 03 description    Page 128  Added new warning 16    Page 128  Updated error 01 and 02 description              145       omron    Authorized Distributor           ne a          Cat  No  WO5E EN 02 Note  Specifications subject to change without notice  lees Netherlands  ay    
106. box  in the Description and Firmware Version fields  If  the communication is not setup correctly  the two fields will contain three  dashes  i e             and an Error message will be displayed in the Error Log view  of CX Profibus  The communication settings must be changed to the correct  value first     When CX Server has been setup correctly  it can be used for   e Configuration download   e Monitoring purposes  Since CX Server is the common driver software for connection between PC   based CX  programs  e g  CX Programmer  CX Supervisor  etc   and the  CS1 CJ1 series PLC  all these programs can communicate simultaneously  with the PLC  However  the settings for CX Server made through each of    these programs have to be exactly the same  to allow simultaneous communi   cation     In order to download the parameter sets to the PROFIBUS Master Unit  per   form the following sequence     1  Select the DTM in the Network view and right click the mouse to display  the context menu     2  Select Download Parameters from the menu  to initiate a download  A  communication channel through CX Server will be opened automatically     Alternatively  the following can be done   1  Select the DTM in the Network view and press the Download button in the  toolbar to start the download process     For monitoring  an online connection with the Unit must be made first  To  achieve this perform the following sequence   1  To go on line  perform one of the following actions   e Select the 
107. cally set for  all configured slaves  based on the value of Typ              CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Slave Area Tab       Allocation Areas    Module List Box    I O Mapping Areas    The Slave Area tab displays the mapping of the I O data from to the allocated  slave devices on to the PLC memory areas  The mapping can be made auto   matically  but can also be changed by the user  before downloading     The Slave Area tab is shown below  Only the Output Allocation tab is shown              a 1  CJ1W PRM21 PROFIBUS DP   1 Master   Configuration p   oj x   Device Setup   Master Setup   Bus Parameters Slave Area   Advanced   OK      Output Allocation   Input Allocation   Cancel    Help         1 OMRON CJ1W PRT21 1 words output 1 Word  CI03200  2 2 words output 2 Word  CI03201  3 4 words output 4 Word  CI03203  4 8 words output 8 Word  CI03207  3 i CPM14 PRT21 2 bytes output  No consis    2 Byte CI03215  4 1 COM1 PRT21 2 words output  No consi    2 Word  ClI03216  6 1 F150 PRT 1 words output 1 Word CI03218 xl         Output Area 1      p Output Area 2       CIO    ModuleName     C10    ModuleName  4      2  1 words output    2  2 words output  2 words output     2  4 words output  4 words output   4 words output   4 words output     8 words output   8 words output    8 words output xl zi  Area  clo v   Occupied 0020 Words   Area  clo v  Occupied  0000 Words    Start Address   2200 Start Address   3400    Length  100 Compress Length  100                 
108. cation  gaps are left behind     New I O modules are appended to the existing mapping   Changed I O modules will be re allocated to the end of the  list  Memory allocation gaps can be left behind        Auto Addressing  disabled          The Bus Parameters tab contains the parameters for the communication on  the PROFIBUS network  The Bus Parameters tab is shown below                       a 1   CJ1W PRM21 PROFIBUS DP   1 Master   Configuration  iol x   Device Setup   Master Setup Bus Parameters   Slave Area   Advanced   OK    Baud Rate  Cancel      Optimize Help      by standard  C by user  Slot time  l 300 tBit Min Slave Interval        Min Station Delay of Responders  fi 1 tBit    Min Slave Interval        Max Station Delay of Responders  fi 50 tBit Target Rotation Time   Quiet Time  0 tBit Max Retry Limit  1    Setup Time  1 tBit Highest Station Address   7      GAP Update Factor   Poll Timeout     Data Control Time     Watchdog Control              The Bus Parameters are a number of settings which define the communica   tion behaviour and timing on the PROFIBUS network  The Bus Parameters  depend on the selected baud rate  certain slave communication parameters  as well as the number of I O data bytes exchanged between the Master Unit  and each of the slave devices     The required combination of Bus Parameters is calculated by the program   based on the dependencies mentioned above  However  the user can change  selected Bus Parameter manually if the application require
109. cation Considerations       SUITABILITY FOR USE       OMRON shall not be responsible for conformity with any standards  codes  or regulations that apply to the  combination of products in the customer s application or use of the products     At the customer s request  OMRON will provide applicable third party certification documents identifying  ratings and limitations of use that apply to the products  This information by itself is not sufficient for a  complete determination of the suitability of the products in combination with the end product  machine   system  or other application or use     The following are some examples of applications for which particular attention must be given  This is not  intended to be an exhaustive list of all possible uses of the products  nor is it intended to imply that the uses  listed may be suitable for the products     e Outdoor use  uses involving potential chemical contamination or electrical interference  or conditions or  uses not described in this manual    e Nuclear energy control systems  combustion systems  railroad systems  aviation systems  medical  equipment  amusement machines  vehicles  safety equipment  and installations subject to separate  industry or government regulations    e Systems  machines  and equipment that could present a risk to life or property     Please know and observe all prohibitions of use applicable to the products     NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR  PROPERTY
110. cations     Safety Precautions    Z  WARNING    Z  WARNING     N WARNING     N WARNING    ZN Caution    Do not attempt to take any Unit apart while the power is being supplied  Doing  so may result in electric shock     Never touch any of the terminals while power is being supplied  Doing so may  result in serious electrical shock or electrocution     Do not attempt to disassemble  repair  or modify any Units  Any attempt to do  so may result in malfunction  fire  or electric shock     Do not touch the Power Supply Unit while power is being supplied or immedi   ately after power has been turned OFF  Doing so may result in electric shock     Tighten the screws on the terminal block of the AC Power Supply Unit to the  torque specified in the operation manual  Loose screws may result in burning  or malfunction     Operating Environment Precautions 4        N WARNING The CPU Unit refreshes I O even when the program is stopped  i e   even in     N WARNING    PROGRAM mode   Confirm safety thoroughly in advance before changing the  status of any part of memory allocated to I O Units  Special I O Units  or CPU  Bus Units  Any changes to the data allocated to any Unit may result in unex   pected operation of the loads connected to the Unit  Any of the following oper   ation may result in changes to memory status     e Transferring I O memory data to the CPU Unit from a Programming  Device     e Changing present values in memory from a Programming Device   e Force setting  resetting bi
111. cations cables    e Do not place heavy objects on top of the communications cables    e Be sure to wire communications cable inside ducts    e Use appropriate communications cables     e Take appropriate measures to ensure that the specified power with the  rated voltage and frequency is supplied in places where the power supply  is unstable  An incorrect power supply may result in malfunction    e Install external breakers and take other safety measures against short cir   cuits in external wiring  Insufficient safety measures against short circuits  may result in burning    e Double check all the wiring and switch settings before turning ON the  power supply    e Check the user program for proper execution before actually running it on  the Unit  Not checking the program may result in an unexpected opera   tion    e When configuring a slave device on the network using PROFIBUS DP V1  messaging services via the PROFIBUS Master Unit  make sure that the  PROFIBUS Master Unit is in the CLEAR state  to prevent unexpected  results when    e Confirm that no adverse effect will occur in the system before attempting  any of the following  Not doing so may result in an unexpected operation     e Changing the operating mode of the PC   e Force setting force resetting any bit in memory   e Changing the present value of any word or any set value in memory     e After replacing Units  resume operation only after transferring to the new  CPU Unit and or Special I O Units the contents of t
112. ce status  without having the user to  open all the slave DTMs  The overview is presented in the Monitoring   Slave  Status tab of the user interface  and displays only the standard PROFIBUS    Monitoring the Network S CS ection 3 7       diagnostics flags  An example is shown in the figure below  For the extended   non standard diagnostics see section 3 7 2 Monitoring Slave Status     wt 1   CJ1W PRM21 PROFIBUS Master   Diagnosis   5  x     Close    Help           Monitor   Online Operations         Master Status Slave Status   Enor History  FE  p Refres     I Automatic                         r Slave Status Flags       glee ch tei re AE     009 OOS CSOOOOO  113     OO0 0   202   O OO0C00CO  033 OOOCOO0C00CO  4493 QOOCOOC0O0CO  5053 OQOOOCOOCO00CO  5869 QOOOOO000O    Clear Diagnostics       Slave Diagnostic Data    Selected Slave  23 O New Diagnostics Received      Station non existent     Parameter request used      Station not ready     Static diagnostics        Configuration fault   Station type    Extended diagnostics received   Watchdog On       Function not supported    Freeze mode       Invalid slave response    Syne mode      Parameter fault    Station deactivated               Master lock     Extended diagnostics overflow          The upper half of the window   the Slave Status Flags box   presents the sta   tus of each slave device using coloured LED indicators  The colours are listed  in the table below     Indicator Slave Status  Colour    iors device does not ex
113. change Diagnostics with this Master  nit  i e    e Slave not allocated to this Master Unit  or   e Device is this Master Unit  or   e Device is another master device    Example figure  Slave device 0 is not allocated    The slave device is not communicating with the PROFIBUS Master    Unit  It may be disconnected  or the Master is in OFFLINE or STOP  mode        Example figure  Slave device 6 is not responding        The slave device is communicating with the PROFIBUS Master  Unit  but it is not in Data Exchange  due to incorrect parameter set   tings  See the slave diagnostics for more information     The slave device is in data exchange with the PROFIBUS Master  Unit  but it has reported diagnostics data  See the slave diagnostics  for more information     Example figure  Slave device 14 has returned diagnostics    The slave device is in data exchange with the PROFIBUS Master  Unit  No diagnostics reported    Example figure  Slave device 2 is in I O data exchange                 Any other colour than green or grey  indicates that new diagnostics have been  received from the associated slave device  since the last time the diagnostics  was monitored     111    Monitoring the Network    Section 3 7       Reading Standard Slave  Diagnostics    Clearing Diagnostics  Flags    112    Note    Note    The newly received diagnostics can be viewed  by clicking with the left mouse  button on the LED indicator  indicating diagnostics  The mouse pointer will  change in to a hand icon  w
114. containing all zeros     The Auto CLEAR function can only be enabled through CX Profibus  The con   trols to enable it can be found in the CS1 CJ1W PRM21 Master DTM   Master  Setup tab  see section 3 4 1 Setting the Master Parameters      The Auto CLEAR function will only be active if the Master Unit has been  switched to OPERATE mode     An automatic transition to CLEAR mode will take place in the following situa   tions     1  During network startup at least one slave device rejects its parameter or  I O configuration message or fails to respond  All slave devices which have  already reached data exchange with the Master will be switched to CLEAR  mode again  Also  slave device which remain in not ready state during a  time period which exceeds the Data Control Time  See section 3 4 2 Set   ting the Bus Parameters   will cause the Master Unit to switch to CLEAR  mode     2  After successful network start up  there is no I O data exchange with at  least one slave device for a period of time which exceeds the Data Control  Time     1  Slave devices which have either been disabled in the Master Unit  or slave  devices for which the Ignore Auto CLEAR flag has been set  see section  2 5 1 Configuration User Interface  Extensions Tab   will not cause a tran   sition to Auto CLEAR  not even when they fail on the network     2  Incase a slave device requires more time than the Data Control Time to  validate its parameter or configuration message  premature triggering of  Auto CLEAR
115. ction  Auto CLEAR  has been enabled  the PROFIBUS Master exits  its OPERATE state  switches the outputs of all assigned slaves to the fail safe  status and changes to the CLEAR state     Monitoring at the Slave Slave devices use a watchdog to detect failures of the master or the bus  If  data communication with the master does not occur within the set watchdog  time interval  a slave automatically switches its outputs to the fail safe mode     Also  access protection is provided for the inputs and outputs of the slaves  operating in multi master systems  Only authorized masters can access their  slaves     1 1 7 Network Operation Modes  PROFIBUS DP distinguishes four different network operation modes     OFFLINE e Communication with all PROFIBUS DP participants  masters and slaves   is stopped  The Master ceases to access the PROFIBUS network     STOP e Cyclic communication as well as PROFIBUS DP V1 Class 1 communica   tion between the master and its slaves is stopped  Only PROFIBUS DP   V1 Class 2 communication and communication between the master and  other masters is still possible     CLEAR e The master tries to set parameters  check the configuration  and perform  data exchange with its associated slaves  Data exchange involves reading  the inputs of the PROFIBUS DP slaves and writing zeros to the outputs of  the slaves     OPERATE e The master exchanges data with its assigned slaves  inputs are read and  outputs are written  Also  the master cyclically sends its local s
116. d  the Master Status Word 1  the Master Status  Word 2  and the Slave Status Word  refer to the CS1 CJ1W PRM21 Opera   tion Manual  W409 E2 L       The table below lists combinations of LED indicators with information on pos   sible problems                 122    Troubleshooting the Network o CS ection 4 2    LED Indicators Description   Correction    Local Parameter Storage Error An error has occurred  when writing the configuration to the non volatile memory    Valid Configuration Indicator will   To correct this    be OFF  e Restart the Unit    e Re download the configuration    e If the problem persists  replace the PROFIBUS Master Unit    Local Parameter Load Error An error has occurred  when loading the configuration from the non volatile memory   Valid Configuration Indicator will   t   the volatile memory at start up    be OFF  Most likely causes    e A failure or interruption during the writing process     e A faulty parameter setting  which makes initialization of the PROFIBUS interface  not possible        To correct this    e Check the parameter settings for incorrect values    e Restart the Unit    e Re download the configuration    e If the problem persists  replace the PROFIBUS Master Unit    File read error is ON An error has occurred  when loading the configuration from the non volatile memory     Valid Configuration Indicator will   tO the volatile memory at start up   be OFF  Most likely causes        e A failure or interruption during the writing process 
117. d device        The selected DTM is not suitable to  configure the connected PROFIBUS  Master     Error Messages   Communication    The table below lists the Error messages related to CX Server communication between the PROFIBUS Master  Unit DTM and the PLC     Message  Communication Failure with Unit       Description    The communication between the PC  and the Unit on the PLC could not be  achieved           Please use the DTM as specified in  the error message        Correction    Ensure there are no problems  with the connection between the  Personal Computer and the PLC   Ensure the Master Unit has been  correctly mounted  Make sure the  Device settings are correct   Perform one of the following suc   cessfully to confirm the problem  has been solved       Download configuration     Communication Test in Device  Settings tab     Update monitoring data  Slave  Diagnostics  clearing error log         Appendix       Number Message Description Correction    Communication Failure with PLC   The communication between the PC Ensure there are no problems  and the PLC could not be achieved  with the connection between the  Personal Computer and the PLC   Make sure the Device Settings  are correct    When problem has been  removed  disconnect and re con   nect  Perform one of the following  successfully to confirm the prob   lem has been solved       Update monitoring data  Slave  Diagnostics  clearing error log        Changing the master state    CX Server could not be config  C
118. dcast communication  See Global Control    Bus access protocol  4    C    C200HW PRM21 DTM  11  Address table tab  55  Adjusting bus parameters  55  Auto addressing  57  Bus parameter tab  53  Changing address mapping  57  CIF error messages  138  Configuration user interface  52  Configuring communication  60  Connecting  60  Diagnostics user interface  57  Downloading parameters  60  Memory layout  56  Monitoring  61  Sorting I O modules  57  Configuring the PROFIBUS Master  See C200HW PRM21 DTM  Configuration  See CS1 CJ1W PRM21 DTM  Configuration    CS1 CJ1W PRM21 DTM  10  Address  87  Auto addressing  89  Auto Update  109  Auto CLEAR  88  Bus parameter  89  Changing mode  103  Diagnosis User Interface  108  Downloading the configuration  93  Error Log  114  Access from PLC program  117    Index    Clearing  115  Concept  114  Detecting new errors  114  Reading  115  I O Mapping  90  Manual refresh  109  Master parameters  87  Master setup tab  87  Master Status  109  Monitoring  108  Reading the Master status  109  Set device station address  41  80  Slave DTM Address assignment  41  80  Slave status  110  Storing the configuration  93  Unit description  92  Unit firmware version  92  Unit number  87  Unit PLC behaviour  88    CX Profibus    Default password  18  Device Catalogue  See Device Catalogue  DTM view  20  Error Log view  20  FDT Monitoring view  20  Features  10  Generic slave DTM  See Generic slave DTM  Installation  Procedure  18  Requirements  18  Login win
119. ddress of a Slave Device    104    The CS1 CJ1W PRM21 PROFIBUS Master Units support the transmission of  Global Control commands  These messages are unconfirmed broadcast  messages  i e  the slave devices do not send a response message   which  can be used to synchronize I O data related events two more slave devices     Two types of synchronization can be achieved     1  Synchronization of input data  The inputs on one or more slave devices are read at the same time  The  synchronized data is transferred to the Master Unit during the next I O data  exchange cycle  The commands are defined as Freeze and Unfreeze     2  Synchronization of output data  The outputs on one or more slave devices are set at the same time  The  synchronized data has been transferred to the slave devices during the  previous I O data exchange cycle  The commands are defined as Sync  and Unsync     1  The CS1 CJ1W PRM21 PROFIBUS Master Unit also uses Global Control  commands to broadcast its own operational mode to other devices on the  network  These Global Control commands are sent automatically  without  user interference    e to all devices on the network  i e  not to specific groups    e always at the start of every I O data exchange cycle  and  e only when the Master Unit is either in OPERATE or in CLEAR mode    2  The user can only initiate transmission of Freeze Unfreeze and Sync Un   sync to either all slave devices or specific groups of slave devices  These  Global Control commands are trans
120. der CX Profibus   Upon updating the Device Catalogue  the Generic Slave Device DTM will  scan this sub directory and present an entry in the Device Catalogue for each  of the GSD files found     Upon adding the GSD based slave device to the network  an instance of the  Generic Slave Device DTM will be made in the PC memory  which will read  the GSD file contents  The instance of the Generic Slave Device DTM will pro   vide the user interface necessary to make the settings for the associated  slave device     61    Generic Slave Device DTM    Section 2 5       2 5 1 Configuration User Interface    Opening the  Configuration DTM    Configuration Tab       Device Settings    62    Note    The configuration DTM is opened by    e Selecting the slave DTM entry in the Network view  and double clicking  the left mouse button     e Selecting the slave DTM in the Network view  and right clicking the  mouse  From the context menu  select Configuration     The slave DTM Configuration User Interface  which is displayed in the CX   Profibus DTM view is shown below  The figure shows the user interface for an  OMRON CJ1W PRT21 PROFIBUS DP Slave Unit  By default the Configura   tion tab is opened      loxi  Device  CJTW PRT21 GSD File  OC_0602 gsd  Vendor  OMRON Corporation Ident Number 0x0602    Configuration   Parameter   Group               r Device Settings  Station Address  fe   IV Enable watchdog control Watchdog Interval   200 ms  m Module Configuration  Max  length of input output dat
121. dow  18  Main Menu  20  Main window  19  Master DTM  See C200HW PRM21 DTM  See CSI CJ1W PRM21 DTM  Network view  20  Specifications  13  Starting  18  Status Bar  22  Tool Bar  21    CX Server    Configuring  91  CPU selection  91  Network type  92  Testing the setup  92    D    Device address  78    Device Catalogue    Additional DTM Information  23  DTM group selection window  23  DTM view layout  22    141    Generating the Device Catalogue  18  Installing GSD files  24  Invoking  22  Main components  22  Open  75  Updating  24  Device DTM  7  Device profile  4  Diagnostic functions  5  Diagnostics  Channel Related  5  Device Related  5  Module Related  5    Diagnostics Update Delay  67  Downloading the configuration  12  DIM    non GSD based  75  PROFIBUS DP V1 services  11    E    EC Directives  Low voltage  EN 61131 2 1994 A12 2000  xviii    EMC Directives  EMI directive  xviii  EMS directive  xviii  Error codes  131    Error log  131  Adding records  131  Error codes  131  Error log location  131  Error log records  131  Logged errors  131  Error messages  Communication  136  Configuration  135  System  137    Error on Cyclic Data Exchange  67    F    Fail safe  6  67  FDT DTM  Communication DTM  8  Device DTM  7  DTM properties  8  DTM versus GSD file  9  FDT Container application  7  FDT DTM Concept  7  FDT DTM technology  7  User interface  8  XML based data transfer  8  Freeze  See Global Control    142    Index       G H    Generic Slave DTM  11  Extended diagnost
122. e   Slave Diagnostics received  ON   Check the Monitor   Slave Status tab  to see which slave failed   OPERATE  ON The Master Unit is still in OPERATE mode  but not exchanging data with all its slave  Slave Diagnostics received is    devices  One or more of the slave devices on the network failed   ON Check the Monitor   Slave Status tab  to see which slave failed   Data Exchange  OFF  Auto Clear enabled  OFF                Troubleshooting the Slave If the Master Status tab indicates problems related to slave devices  their sta   Devices tus can be obtained by checking the Slave Status tab  The figure below shows  this tab  As an example a failure of slave device 2 is shown     124    Troubleshooting the Network           sss    lt                                     lt   3 OR  lt   S  SS ction 4 2       wt 1   CJ1W PRM21 PROFIBUS Master   Diagnosis   0  x   Monitor   Online Operations   Close      Master Status Slave Status   Error History  sis  p Refresl          r Slave Status Flags    V Automatic       ge OOODOODOON Ten DOODOO  ss OOOOQOOOOO       Slave Diagnostic Data    Selected Slave  2 oO New Diagnostics Received      Station non existent     Parameter request used        Station not ready    Static diagnostics        Configuration fault   Station type     Extended diagnostics received   Watchdog On        Function not supported    Freeze mode        Invalid slave response      Syne mode        Parameter fault    Station deactivated        Master lock     Extended dia
123. e   Verify that any stubs used are not too  long   Verify that termination  resistors and  inductors  are properly set and used        127    Troubleshooting the Network    Section 4 2       Problem    PROFIBUS Master Unit is  configured  Some  but not  all slaves exchange data     128    Probable cause   Network cabling is not correct    e BF LED indicator is ON or Flashing    e Master Status 2 error flag may provide  more information  CIO Word n 6  bit 00    03  see Note     CIO Words n 9 to n 16 show which  slaves have problems     Correction  Verify that the network installation is correct   e Verify that all slaves are powered up and  functioning correctly   Verify that all slave devices are correctly  connected to the network   Verify that any repeaters used are func   tioning correctly   Check the cable length versus the  selected baud rate   Verify that any stubs used are not too  long   Verify that termination  resistors and  inductors  are properly set and used        Configuration is not correct    e BF LED indicator is Flashing    e CIO Words n 9 to n 16 show which  slaves have problems     Use CX Profibus and DTMs to determine  slave diagnostics     Verify that the configuration is correct    e Verify that address of targeted slave  device matches the configured address   Verify that the slave parameter and config   uration settings are correct    Verify that the watchdog setting for the  slave device is not too low        The configuration contains timing errors
124. e  the minimum time between  two consecutive Data_Exchange Cycles to the same slave device  The Minimum  Slave Interval must be smaller than the Target Rotation Time     Watchdog Control   Override slave specific Watchdog control time     This setting   when selected   allows the user to set one Watchdog Control Time  for the whole network and override the Watchdog Control Time provided by the  Slave DTM     The Watchdog Control Time defines the time for a slave device to set its outputs  to a fail safe state  if during that time no communication between the Master  device and that slave device was detected  The Watchdog is automatically set for  all configured slaves  based on the value of Typ              Calculated Timing   The Calculated Timing is the time that the Sender spends at idle after the receipt  of the last Bit of a telegram on the Bus  until the first Bit of a new telegram is sent  on the Bus     These values are calculated by the DTM and only displayed for information  purposes    Auto Clear ON When selected  the Unit transitions to the CLEAR mode in the event of a network  error  e g  because one or more configured slaves are not in the Data Exchange  mode                    Adjusting Bus Parameters If the bus configuration is changed and these changes have effects on the    Bus Parameters  a note symbol 4  appears next to the concerned parame   ters of which displayed values are not longer valid  Usually in these cases the  displayed values are too small and
125. e  which facilitates  the displaying of such extended diagnostics data strings   The presence of extended diagnostics as part of the diagnostics data mes   sage  is indicated by  e the LED indicator marked Extended Diagnostics received in the Master  DTM   Monitor tab  Slave Status tab  refer to section 3 7 1 Monitoring the  Master Unit and the Network      e the LED indicator in the Diagnostics tab of the slave Diagnostics User  Interface  see for example  the figure above      Also  if no extended diagnostics are available  the Extended Diagnostics tab  will be disabled  and inaccessible     To display the extended diagnostics  click on the Extended diagnostics tab in  the Slave Diagnostics User Interface     113    Monitoring the Network    Example    Section 3 7    The figure below shows an example of the extended diagnostics window  con   taining extended diagnostics data  The first row in the diagnostics window  shows the raw data bytes  the second and third row show the actual message  contained within the extended diagnostics message     2101 x   Device  CJ1W PRT21 GSD File  OC_0602 gsd OK    Vendor  OMRON Corporation Ident Number  0x0602   Help    Diagnostic Extended Diagnostics        Number   DiagnosticsMessage o o l  0x05  0x00  0x04  0x00  0x00  0x00  0x00  0x00  0x00  0x00  0x00  0x0     Device related  Non fatal PLC error   Device related  PLC in Monitor mode          Connected Update         3 7 3 Using the Error Log    Error Log Concept    Reading New Errors 
126. e Unit        Slave    Slave Diagnostics Received    When turned ON  it indicates that new slave diagnostics have been received           All Slaves in Data Exchange       When turned ON  it indicates that all slaves are in Data exchange with the Mas   ter Unit        45    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Slave Status Tab The Slave Status tab displays a comprehensive overview of the status of the  allocated slaves  An example of the Slave Status tab is shown below        taf  1   CJ1W PRM21 PROFIBUS Master   Diagnosis   0  x     Monitor   Online Operations   Close    Help      Master Status Slave Status   Error History  ast  m Refres           r Slave Status Flags    Automatic    012345  773 QOOOO00O  8083 OQOOOOO  933 O00000  100109 QDOOO00  110118 QOQOQOO00  12 18 QOOO000       6  O      QO  O    CLOSE    78  OO  OO  OO  OO  OO    OCOOCOO        Slave Diagnostic Data       Selected Slave  2 oO New Diagnostics Received       Station non existent     Parameter request used        Station not ready    Static diagnostics        Configuration fault   Station type     Extended diagnostics received   Watchdog On        Function not supported    Freeze mode       Invalid slave response    Syne mode       Parameter fault     Station deactivated        Master lock     Extended diagnostics overflow             LED Indicator Colours The LED indicators in the Slave Status Flags box  indicate per slave its status   using colours  Four colours are associated with stat
127. e a  default value and some are optional  The device data base file is divided into  three parts     e General specifications   This section contains the vendor name  the device name  hardware  and soft   ware release versions  device type and identification number  protocol specifi   cation and supported baud rates     e DP master related specifications   This section contains all parameters which only apply to DP master devices   e g  maximum memory size for the master parameter set  maximum number  of entries in the list of active devices  or the maximum number of slaves the  master can handle      e DP slave related specifications   This section contains all specification related to slaves  e g  minimum time  between two slave poll cycles  specification of the inputs and outputs  and  consistency of the I O data     For PROFIBUS DP V1 devices this section also specifies what services for  PROFIBUS DP V1 are supported     When comparing the two configuration technologies  a GSD file only provides  information on the device characteristics and configuration options  It has no  GUI of its own  nor can it connect to the device itself  A GSD file always  requires a separate configurator program to interpret the data  In the FDT   DTM concept all these device related functions are included in the DTM  The  DTM can be executed from any program  which provides FDT interfaces     Sending PROFIBUS DP V1 commands to a device from the configuration tool    is only possible using DTM 
128. e communication between the PC  and the PLC and also configure the connected PLC  CX Server currently sup   ports CS1G H  CS1H  CS1H H  CJ1G H  CJ1H H CJ1M and CS1G CJ1G  PLC types     Section 2 3 3 Connecting to the CS1 CJ1W PRM21 will provide more details  on how to configure CX Server     Test Button The purpose of the Test button is to test the communication setup  after CX   Server has been configured  If the PC and the PLC are connected  selecting  the Test button  will invoke a FINS request message to the PROFIBUS Mas   ter Unit via the PLC  to read its name and firmware version  If the request suc   ceeds  both will be displayed in the Device Information Box     If the FINS request fails  no response   an error message will be displayed in    the Error Log view  In this case the Firmware version field will revert back to  its default contents  i e                 Device Information Box The Device Information Box contains information obtained from the PROFI   BUS Master Unit  through the communication     OMRON Corporation   This is fixed text  indicating the Manufacturer of the PROFIBUS  Master Unit     Description This string will contain the name of the Unit  i e  CJ1W PRM21  or CS1W PRM21           Firmware Version This string displays the firmware version  currently in the  PROFIBUS Master Unit     Ident number The PROFIBUS Ident number  Hex  for the Unit   e CJ1W PRM21  07C4  e CS1W PRM21  0742             32    CS1 CJIW PRM21 PROFIBUS Master DTM    Section 2 3  
129. e reset  until power down        Not Ready    The Not Ready notification indicates that the application program has not  started or it has stopped the PROFIBUS DP Master  If this bit is set  the applica   tion is not ready to receive data        Auto Clear    Set to ON indicates that an Auto Clear event has occurred  i e  data exchange  with at least one of the slave devices has stopped  The Master Unit has been  switched to CLEAR mode        Slave Error    When set to ON  it indicates that at least one of the slaves has encountered an   error and is not exchanging I O data with the Master unit  Refer to the LED indi   cators in the Station status field to determine which slave devices encountered   the error        Fatal Error    A Fatal Error has occurred in the PROFIBUS DP Master unit  due to the large  amount of network errors  No further bus communication is possible        Control Error    The Control Error indicates that an error has been encountered in the down   loaded parameter set  No communication is possible        D    amp      je         O     a  5  a    Error Event    When set to ON  The Error Event indicates that the device has detected network  short circuits  The number of detected events is displayed in the Short Circuit  Counter  The bit will be set up on the first detected event and will not be reset   until power down or reset of the PROFIBUS DP Master unit        Short Circuit Counter    The Short Circuit Counter displays the number of short circuit er
130. e setting up the bus parameters  which define the baud rate and the bus  timing parameters     e downloading the configuration setup to the master device     The configuration process is usually facilitated by a special Computer based  program  often referred to as a configurator  The configurator requires special  configuration files  defining the configuration options for each device  which is  to participate in data exchange  The files must be provided by the manufac   turer of the device   Two types of configuration technology exist    e Configuration technology based on FDT DTM technology      Configuration technology based on GSD files    1 2 2 FDT DTM Technology    FDT DTM Technology  FDT DTM Concept    FDT Container Application    Device DTM    The newer configuration tools are based on FDT DTM technology     The FDT DTM concept specifies the interfaces between the engineering sys   tems called Field Device Tools  FDT   and the device specific software com   ponents called Device Type Managers  DTM      The FDT DTM concept separates the device dependent functionality  which is  in the DTM  from the application  It provides separate interfaces for device  configuration  monitoring and maintenance solutions  which before largely  depended on the manufacturer of the application  Because of this concept   FDT DTM technology is not limited to PROFIBUS applications  In concept   any type of network can be configured and accessed  provided the appropri   ate DTMs are availab
131. e the row selected in the  lower window  Append will add the module to the end of the selected  module list     1  The user can select multiple rows  in both windows  by simultaneously  holding the SHIFT or CTRL key on the keyboard and selecting the rows  using the left mouse button     2  The amount of I O modules and data which can be selected depends on  the slave device  The four rows of information above the module display  the maximum amounts as well as the selected totals     Removing one or more selected modules from the list is done by  e double clicking the left mouse button on the module in the lower window     e selecting the module in the lower window and click the Remove button  In  this case selecting multiple modules is also possible     63    Generic Slave Device DTM Section 2 5       Parameter Tab The Parameter tab lists all settings to be made for the Parameter message   The Parameter tab is shown below  Example shown is the Parameter tab for    an OMRON CJ1W PRT21 PROFIBUS DP Slave Unit           ti 2   CJ1W PRT21   Configuration    GSD File   Ident Number      15  x     CJ1W PRT21  OMRON Corporation    Device   Vendor     OC_0602 gsd  Ox0602    Common Parameters    Module Parameters    Group Tab    64    Note    Configuration Parameter   Group      Module     Parameters         Fail Safe support  Watchdog Base  Output data on PROFIBUS fail   Output data format   Output to slave PLC area   Output area start address   Action on slave PLC PROGRAM mode  Actio
132. ed  allowing cancellation of the command        Closes the user interface without saving     Note If any changes were made  a warning message is displayed   allowing cancellation of the command        Evaluate  and save the changes made  if any      Note If any invalid settings have been made  a warning message  will be displayed  allowing cancellation of the command           Launch context sensitive Help for the Active tab          Caution Saving the changes in the context of the buttons means that the changes    Bus Parameters Tab       made by the user are saved in the DTM only  i e  the changes are not perma   nently saved in the Project yet  This is indicated by the asterisk next to the  DTM in the Network view  The next time in the same session the GUI is  opened  the changes will still be there  In order to save the changes perma   nently  e g  to hard disk  Click the File   Save option from the main menu of  CX Profibus     The Bus Parameters tab contains the parameters for the communication on  the PROFIBUS network  The Bus Parameters tab is shown below       ti 4   C200HW PRM21   Configuration  O  x     Bus Parameters   Address Table                         Profile  PROFIBUS DP       m Bus Parameters          Baud Rate  1500 kBit s   Station Address  A    Slot Time        tBit Target Rotation Time      11894 tBit   Min  Station Delay Time  Hi tBit   7 9293 ms   Max  Station Delay Time   150 tBit GAP Actualization Factor  fo   Quiet Time  fo tBit Max  Retry Limit  T
133. eft mouse button     2  Select the Station Address field at the top of the Configuration tab  see fig   ure below  and change the value to 10     79    Setting up a network   Section 3 2       3  Select the OK or Apply button at the bottom of the window  The OK button  will close the DTM Configuration User Interface     io  x   Device  F150 PRT GSD File  OC_O5E4 gsd  Vendor  OMRON Corporation Ident Number Ox05E4     Configuration   Parameter   Group                     r Device Settings  Station Address   10   IV Enable watchdog control Watchdog Interval   200 ms          m Module Configuration    Max  length of input output data  74 Byte Length of input output data  8 Byte  Max  length of input data  64 Byte Length of input data  6 Byte  Max  length of output data  10 Byte Length of output data  2 Byte  Max  number of modules  1 Number of modules  1  Available Modules    Module Name Module Configuration Identifier a       Basic  Resp off  Out off 0xD2 0xE0  Basic  Resp on   Out off 0xD7 0xE0  Basic  Resp off  Out on OxDF 0xD4 0 E0  Basic  Resp on   Out on OxDF 0xDF 0xE0  Fynan Resn off Nut off TW  MF A          bi  b   Slot   Module Name Module Configuration Identifier    Basic  Resp off  Out off 0xD2 0xE0    Configured Modules                  OK   Cancel   Apply   Help            Note If  when pressing the Apply or OK button  no I O modules have been selected  as yet  a warning message will be displayed  The I O modules can be  selected later  Pressing the OK button with t
134. equested  W Station not existent WW Extended diagnostics overflow       Assigned Master Address  1    Device internal Ident Number  0x602       Update        Connected       The LED indicators are listed in the table below     Name Description    Master lock    The slave device has been parameterized by another master        Parameter fault    The last received parameter data from the Master Unit have been rejected  The parameter  data in the slave device differ from the parameter sent by the Master Unit        Invalid slave response    The slave has returned an invalid response to a Master request message        Function Not supported    The Master Unit has sent a message to the slave device  which is not supported by the  device        Extended diagnostics    The diagnostics message returned by the slave device contains extended diagnostics  i e  it  contains more than the mandatory 6 bytes        Configuration fault    The last received configuration data from the Master Unit have been rejected  The configura   tion data in the slave device differ from the configuration sent by the Master Unit        Station not ready    The slave device is not yet ready for data transfer  the parameters data and the configuration  data have been accepted         Station not existent    The slave does not respond to any of the request messages sent by the master  If set the  diagnostic bits contains the state of the last diagnostic message or the initial value        Slave deactivated    W
135. er  Double clicking a  file with the extension   CPR will invoke CX Profibus and open the selected  file     2 2 7 Exporting to HTML    Exporting Project to HTML    CX Profibus provides automatic generation of project documentation upon  command of the user  The documentation is generated in HTML format  and  can cover either single DTMs or the whole project  After generation of the  HTML document  it will automatically launch the default Internet browser  to  display the result     Exporting the project information to HTML can be achieved in two ways     e Select the main menu File   Export Project as HTML option   A window will pop up displaying the progress of the export process    e select Export to HTML option from the context menu  First select the project level in the Network view  then right click the  mouse to display the context menu  A window will pop up displaying the  progress of the export process     25    CX Profibus    Section 2 2       Exporting DTM  Information to HTML    1 2 3       After exporting the information  the default browser is launched  showing the  result of the export process  Links are available to open the information pages  for the individual DTMs     The extent of the information made available depends on the individual  DTMs  This can range from device type and version information up to all set   tings and selections made for the device     Exporting single DTM information to HTML is achieved by the following  sequence    1  Select the DT
136. er  is defined by the  PROFIBUS DP Extension standard  By default SAP 51 is used for acyclic  data exchange with the PROFIBUS DP V1 Master Unit  Class 1      69    Generic Slave Device DTM CS ection 2 5       For efficiency reasons however  acknowledgement of alarms  can be per   formed using a different  dedicated SAP or message identifier  SAP50  This  will allow other acyclic communication  e g  re parameterization of the slave  device  to continue without interference     Control Description    Alarm acknowledge via   When selected  the PROFIBUS DP V1 Master Unit will  SAP 51 acknowledge each received alarm using SAP 51 mes   sage identifier  default      Alarm acknowledge via   When selected  the PROFIBUS DP V1 Master Unit will  SAP 50 acknowledge each received alarm using SAP 50 mes   sage identifier              2 5 2 Diagnostics User Interface    The Generic Slave Device DTM provides a Diagnostics User Interface to dis   play diagnostics data sent by the slave device to the PROFIBUS Master Unit   In general a slave device can send two type of diagnostics     Basic Diagnostics e Basic Diagnostics  The first six bytes of each diagnostic message sent by a slave device  contain mandatory status and error flags  The flags are defined by the  PROFIBUS standard  Refer to the CS1 CJ1W PRM21 Operation Manual   W409 E2     for a detailed overview of diagnostics  The basic diagnos   tics information is displayed in the Diagnostic tab of the Diagnostics User  Interface           
137. er DTM will also check if the PLC memory areas  selected do exist in the PLC CPU model  connected to the Master Unit   e g  are any selected EM banks present     3  If any mapping error is discovered by the Master DTM  an error message  is displayed  and download is terminated     100    I O Communication Characteristics Section 3 5       3 5 3 Supported Data Types    The CS1 CJ1W PRM21 PROFIBUS Master Units perform an interface func   tion between a PROFIBUS network and the CS1 CJ1 PLC CPU  On both  sides of the interface different formats for data and data storages are used     To ensure that I O data transferred through the interface can be used on both  sides of the interface without additional formatting  the CS1 CJ1W PRM21  PROFIBUS Master Units perform the necessary data formatting  This ensures  that I O data in the PLC CPU memory can be processed by standard PLC  Instructions  and that the I O data transferred to   from the PROFIBUS DP  slaves over the network is compliant with the PROFIBUS DP definitions     The table below lists the I O data formats supported by both the PROFIBUS  network and PLC CPU     Data Type    PROFIBUS DP    CS CJ series PLC       Single 8 bit Integer  signed unsigned    Supported     Data is transmitted on a byte by byte  basis     Not supported    Minimum is 16 bit words  Two bytes will  be formatted in one word  Words con   taining odd bytes will be padded with  zeros        Single 16 bit Integer  signed unsigned    Supported     Data is 
138. ery opened DTM User Interface  The window is an MDI type window  or  Multiple Document Interface  One or more user interface windows can be  opened  re sized and moved inside this window     The Error Log view at the bottom of the CX Profibus application window dis   plays the error messages reported by DTMs to CX Profibus  A Time stamp  a  Date stamp and the DTM name are added to the message     The contents of the window can be cleared  or copied to the clipboard  to  allow pasting it into another document     The Error Log view is opened by default  when starting CX Profibus     The FDT Monitoring view at the bottom of the CX Profibus application window  displays the FDT DTM communication function calls between CX Profibus  and the DTMs  A Time stamp  a Date stamp  the type of information and the  DTM name are added to the message     The sequence of messages can be used to troubleshoot problems that may  occur when using third party DTMs in CX Profibus    The contents of the window can be cleared  or copied to the clipboard  to  allow pasting it into another document     The FDT Monitoring view is not opened by default  when starting CX Profibus   It can be opened through the View   FDT Monitoring menu option     The main menu of CX Profibus  provides all the necessary functionality to  handle a complete project  The table below lists the main menu and their sub  menu items     CX Profibus    Command  New    Short Key    Section 2 2    Description  Creates a new Project  
139. f output data  200 Byte Length of output data  0 Byte  Max  number of modules  32 Number of modules  0  Available Modules    Module Name Module Configuration Identifier a            1 word In Out OxFO  2 words In Out OxF1  4 words In Out OxF3  8 words In Out OxF   1A minrds In  Qut        X  fa  Insert Append      Configured Modules      Slot   Module Name Module Configuration Identifier             Remove            The DTM Configuration User Interface displays two lists   e The Available Modules list  which contains the I O modules the user can    select   e The Configured Modules list  which contains all the I O modules selected  by the user   Adding Inserting I O To select the I O modules  perform one of the following procedures   Modules e Select the I O module that needs to be added in the Available Modules    list  and double click it with the left mouse button  If more than one mod   ule must be added  repeat this step for the other modules     Select the I O module that needs to be added in the Available Modules  list  and press either the Insert or Append button  This method allows  selection of more than one module  by pressing either the Shift or the  Ctrl key on the keyboard  while selecting the modules     Note 1  When pressing the Insert button  the selected I O module will be inserted  above the selected module in the Configured Modules list     2  The selected I O modules are sent to the slave device  in the same se   quence as selected in the user interface 
140. from    the Error Log    114    1 2 3       The CS1 CJ1W PRM21 PROFIBUS Master Units are equipped with an error  logging mechanism  which will internally store error events  Most of the errors   which are stored in the Units Error Log are stored in volatile memory  i e   when power to the Unit is switched off  the errors are lost    Severe errors however  are also stored in non volatile memory  i e  these error  reports are still available after cycling the power down and up again  The  errors which can be logged are listed in section 4 3 2 Error Codes    The CS1 CJ1W PRM21 PROFIBUS Master Units can log up to 80 error  events  16 of which can be logged in non volatile memory     If a new error event is logged in the Error Log of the Unit  a bit flag can be  evaluated by the user  through the CS1 CJ1W PRM21 Master DTM Diagnosis  User Interface  In order to view the bit flag  perform the following actions     1  Open the CS1 CJ1W PRM21 Master DTM Diagnosis User Interface     2  Select the Monitor   Master Status tab   3  If the Automatic checkbox in the Refresh box has not been selected  press  the Manual button to refresh the status    The figure below shows as an example this Error Log Updated bit flag  indicat    ing that a new error event has been logged     Monitoring the Network o y Sections        oat 1   CJ1W PRM21 PROFIBUS Master   Diagnosis    Monitor   Online Operations      Master Status   Slave Status   Error History                        m Master Status 1 Unit St
141. functions to cre   ate  save and open project files  It facilitates user access control  which  limits of use to authorized personnel only  using password protection    e Additional functions  CX Profibus provides additional functions like print   ing  error logging  FDT Communication logging and help files     CS1 CJ1W PRM21 DTM The two CS1 CJ1W PRM21 DTMs provided to configure the CS1 CJ1W   PRM21 PROFIBUS Master Units and the CS1 CJ1W PRM21 PROFIBUS DP   V1 Master Units both provide the same basic PROFIBUS DP functions  These  DTMs consist of three parts     e The Settings DTM  which handles the configuration for the PROFIBUS  Master Unit  This includes the bus parameters settings  the I O data map   pings and Master specific settings  The Settings DTM provides its own  user interface    The Monitoring DTM  which handles the status monitoring and control  over the PROFIBUS Master Unit  when it is on line and communicating  over the PROFIBUS network  It provides its own user interface to read out  Master status flags and Error log  as well as Slave status flags and the  Slave diagnostics messages received by the Unit  It also allows the user  to send Global Control messages over the network and to change the  PROFIBUS Master Unit   s mode on the PROFIBUS network    The communication DTM  which provides the interface between the two  DTMs mentioned above and CX Server  CX Server  provided with the  CX Profibus package  is the driver for communication between the PC  and the 
142. g  digital I O  analog I O etc     Protocols   Sub groups which can be selected are all the communication protocols  found in the Device Catalogue                    1  The sub groups will be displayed by clicking on the   sign next to each  main group  2  Selecting the main group displays all devices in the group     In order to obtain more information of a specific DTM  right click the DTM in  the list  and from the pop up menu  select DTM Information  This opens a    23    CX Profibus    Section 2 2  window with additional DTM information  The figure below provides an exam   ple for the CJ1W PRM21 PROFIBUS Master DTM    xl       DTM Info            Name  c1w PRM21 PROFIBUS Master       Vendor  OMRON Corporation  Version   3  62    Date  2003 10 31       Close    2 2 4 Updating the Device Catalogue    Updating the Device  Catalogue    Installing GSD Files    Note    If a new DTM has been installed  it will not automatically be included in the  Device Catalogue  In order to add newly installed DTMs to the list  the Device  Catalogue must be updated by selecting the Update button at the bottom of  the window     Updating the Device Catalogue may take some time  depending on the  amount of DTMs installed  A dialogue window with a progress bar will be  shown during the update process  After updating the Device Catalogue  it will  be stored on hard disk  The next time CX Profibus is started the updated list  will be used     The Device Catalogue also allows the installation  i e
143. gnostics overflow             The LED indicators in the upper half of the Slave Status tab shown in the fig   ure above  indicates the status of the slave devices  by using different colours   see section 3 7 1 Monitoring the Master Unit and the Network  Slave Status  Overview      In case an LED indicator is either Red or Orange  additional information can  be obtained from the PROFIBUS Master Unit  by using the mouse pointer to  click on the coloured LED indicator  The basic diagnostics information  for the  selected slave device is retrieved from the Master Unit and displayed in the  lower half of the Slave Status tab  The table below lists the LED indicators   which are of interest for troubleshooting     LED Indicator Description   Correction    Station non existent    The slave device does not respond to any of the request messages sent by the Master Unit   e Make sure that the slave device is powered correctly   e Check the wiring and make sure that the slave device and the Master Unit are connected        Station not ready    The slave is communicating  but not ready for data transfer   e Check the slave device and make sure that it is working properly   e Check any loose modules  in case the slave device is a modular device     e Consult the operation manual of the slave device  Check if additional action must be taken to  initiate I O data exchange  e g  reset the device after a malfunction         Configuration fault    The I O configuration sent by the Master Unit
144. h the rotary switch on the front     3  Select the Configure button to start CX Server     Up on pressing the Configure button  CX Server is launched and displays the  CX Server User Interface as shown below     Change PLC x     Device Name    PLC                   r Device Type              en M   Settings       Network Type   Toolbus zy Settings       Comment   Carcel _     In order to configure CX Server for communication with the Unit  perform the  following procedure     1  Select the type of PLC to which the Unit is attached  from the Device Type  drop down selection box     49    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       2  Press the Settings button next to the PLC type selected  The PLC settings  window  see figure below  is displayed     Device Type Settings  CJ1M  xj    General         m CPU Type    is      m Total Program Area Size  10K  Step              T Read Only         Expansion Memory    x F Read Oniy    None           File Memory   None x  I    Read Only        Timer   Clock      Installed             Make Default         Cancel Help      3  In this window make the proper adjustments if necessary  The selections  made  must match the physical configuration of the PLC system  When  done  press the OK button    4  Select the Network Type to be used as connection between the PC and  the Unit  The available options may include other PLC systems or Commu   nication Units  which are setup to act as a gateway  Refer to CX Server  Runtime User Manual  W3
145. h two Output Ares and two Input Areas  The Output data can be distrib   uted over two Output Areas  each of which can be mapped on to PLC mem   ory  Similarly  the Input data can be distributed over two Input Areas  each of  which can be mapped on to PLC memory     The figure below shows the CS1 CJ1W PRM21 Master DTM   s Slave Area tab  for an example network with a CJ1W PRT21  a CPM1A PRT21  and an F150   PRT Vision system     oa 1   CJ1W PRM21 PROFIBUS DP   1 Master   Configuration  iol x     Device Setup   Master Setup   Bus Parameters Slave Area   Advanced   OK    Output Allocation   Input Allocation         Addr   Index   Device   ie  2    OMRON CJTW PRT21 1 words output D00000  2 words output D00100  4 words output D00102  8 words output D00001  CPM14 PRT21 2 bytes output  No consis    D00106  F150 PRT 1 words output D00009          r Output Area 2      2  1 words output   2  2 words output    2  8 words output 2 words output  8 words output   2  4 words output  8 words output 4 words output  8 words output 4 words output  8 words output 4 words output  8 words output   3  2 bytes output  No consiste     8 words output  8 words output   10  1 words output   xl      DM       Occupied  00010 Words   DM hd   Occupied  00007 Words  Start Address  jo Start Address  fi o0    Length  100 Compress Length  100                   By default all Output data is mapped on to Output Area 1  and all Input data is  mapped on to Input Area 1  Each of these Areas can be mapped on to PLC  
146. he DM Area  HR Area   and other data required for resuming operation  Not doing so may result  in an unexpected operation     e When transporting or storing the product  cover the PCBs with electrically  conductive materials to prevent LSIs and ICs from being damaged by  static electricity  and also keep the product within the specified storage  temperature range    e When transporting the Unit  use special packing boxes and protect it from  being exposed to excessive vibration or impacts during transportation    e Do not attempt to disassemble  repair  or modify any Units    e Do not attempt to remove the cover over the non used connector hole on  the front of the CS1W PRM21 Unit     xvii    Conformance to EC Directives 6       6 Conformance to EC Directives    6 1 Applicable Directives    6 2 Concepts    Note    e EMC Directives  e Low voltage directive EN 61131 2 1994 A12 2000    EMC Directives   OMRON Units complying with EC Directives also conform to related EMC  standards making them easier to incorporate in other Units or machines  The  actual products have been checked for conformity to EMC standards   See  the following note   Whether the products conform to the standards in the sys   tem used by the customer  however  must be checked by the customer     EMC related performance of OMRON Units complying with EC Directives will  vary depending on the configuration  wiring  and other conditions of the equip   ment or control panel in which OMRON devices are installed  T
147. he OMRON Warranty and  Limitations of Liability           ERRORS AND OMISSIONS       The information in this manual has been carefully checked and is believed to be accurate  however  no  responsibility is assumed for clerical  typographical  or proofreading errors  or omissions              xi    PRECAUTIONS    This section provides general precautions for using the PROFIBUS Master Units  Programmable Controllers and related  devices     The information contained in this section is important for the safe and reliable operation of the PROFIBUS Master  Units  You must read this section and understand the information contained before attempting to set up or operate  a PROFIBUS Master Unit and PLC system     1 Intended Audience          0    cece ene e een A ARRA xiv  2 General Precautions           0    eee eee eee E a xiv  3 Safety Precautions    0 0 0    eect ees xiv  4 Operating Environment Precautions               0 0 0 0  eee eee eee XV  5 Application Precautions              0 0    cee cece eee xvi  6 Conformance to EC Directives        0 0    cece eee eae xviii  6 1 Applicable Directives       u   un 0    eee eee eee xviii  6 2 CONCEDES af ta i a EEA Waka orice aah ARR RS xviii  6 3 Conformance to EC Directives         0 0 0 0 e eee eee eee xviii    xiii    Intended Audience       1    2    3    Xiv    Intended Audience    This manual is intended for the following personnel  who must also have a  knowledge of electrical systems  an electrical engineer or the equivalent 
148. he allocated I O  modules are copies of the modules selected from the pick list     4  In order to move an I O module from one area to another  select the mod   ule in the pick list     5  Hold the left mouse button and drag the I O module to the Input Output  area of choice  Release the left mouse button to drop the module in place     Note The area to place the module in must be empty  The area to put the  modules in does not need to be selected first     Auto Addressing  re allocates I O modules in all Input Output areas  If   after  setting up the initial I O configuration   two or more I O modules are moved  from one area to another  Auto Addressing maintains the same sequence  i e   the slave device with the lowest address and its I O modules in the selected  sequence are allocated before a slave device with a higher address     In the figure below two output modules from the initial I O configuration  top  window  have been re allocated to Output area 2  bottom window        1   CJIW PRM21 PROFIBUS DP   1 Master   Configuration  gt     Device Setup   Master Setup   Bus Parameters Slave Area   Advanced      Output Allocation   Input Allocation       Addr   Index  Device   Modue  sze  Type  a     2    o    1 OMRON CJ1W PRT21 1 words output 1 Word Cl03200  2 4 words output 4 word CI03201  3 1 CPM14 PRT21 2 bytes output  No consis    2 Byte CI03205  10 1 F150 PRT 1 words output 1 Word  CI03206  gl  r Output Area 1   p Dutput Area 2          cio  Module Name  a   3200   2  
149. he customer  must  therefore  perform final checks to confirm that units and the overall sys   tem conforms to EMC standards     Applicable EMS  Electromagnetic Susceptibility  and EMI  Electromagnetic  Interference standards in the EMC  Electromagnetic Compatibility  standards  are as follows        CS1W PRM21 EN 61000 6 2 2001 EN 61000 6 2 2001  CJ1W PRM21       6 3 Conformance to EC Directives    xviii    Units that meet EC directives also meet the common emission standard   EN50081 2   The measures necessary to ensure that the standard is met will  vary with the overall configuration  You must therefore confirm that EC direc   tives are met for the overall configuration  particularly any radiated emission  requirement  10 m      SECTION 1  Features and Specifications    This section provides an introductory overview of PROFIBUS  its functions and how to setup and configure a network  It  also addresses the PROFIBUS Master Units and the configurator  their features and specifications     1 1    1 2    1 3    Overview of PROFIBUS naun dure 0 0 00  c cette eee ees 2  L 1 1    Introductions  is  ean hack ee lees eb en ete ee ee 2  1 1 2 PROFIBUS Communication Protocol                     0   2  L 1 3  Device  Types    5 2 63    5dicn seb gabe seeds see Aaa eee 4  1 1 4 Bus Access Protocol       0 0 0    cece cee 4  1 1 5 Diagnostic functions              00 0  e eee eee eee 5  1 1 6 Protection Mechanisms            0 0 0 cece eee eee eee 6  1 1 7 Network Operation Modes      
150. he mouse will then transmit FINS mes   sages to retrieve the diagnostics data of the specified slave device   The retrieved information is displayed in the Slave Diagnostics Data area     The data displayed is the same as displayed with in the Diagnostics User  Interface of the Generic Slave DTM  Refer to section 2 5 2 Diagnostics User  Interface  for an explanation of the LED indicators        Error History Tab The Error History tab lists the contents of the Error Log stored in the PROFI   BUS Master Unit  The Error History tab is shown below    ox  Monitor   Online Operations   Close    Master Status   Slave Status Error History   sepa Help                    Detail _ Content    ime   M Automatic  03 Mar 04 17 26 49 00219 0x0000 PROFIBUS hardware error          0    Manual    Maximum Log Capacity  80 Clear             The Error Log entries are described in section 4 3 2 Error Codes  Refer to this  section for details        Clear Button Pressing the Clear Button  initiates an ERROR LOG CLEAR FINS command   All error messages in the Unit and the displayed list will be cleared    Online Operations The Online Operations tab is the second main tab in the DTM Diagnostics   Tab User Interface  It contains the necessary controls to    e Switch the Master Unit to PROFIBUS Operational modes    e Select one or more groups  and Global Control Commands and transmit  Global Control message over the PROFIBUS network     47    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       PROFIBUS 
151. he network  Therefore  if this is not de   sired  care must be taken to select the right setting     In case of a failure in the download process  refer to section 4 2 1 Trouble   shooting Parameter Download  to establish the cause and the remedy     93    I O Communication Characteristics Section 3 5       3 5 lO Communication Characteristics  3 5 1 I O Data Configuration    I O Data Configuration     O Data Range Supported    Each slave device defines its I O data size  sequence and format by means of  I O modules  each of which consists of one or more bytes  containing a  PROFIBUS defined coding scheme  The I O modules can define input data   or output data or both input and output data  The I O modules are used to  configure the I O data exchange process in the Master Unit and also to verify  the amount of I O data to be exchanged with the slave device     For modular slave devices the I O modules are selected by the user from a list  of available modules  The modules usually have to be consistent with the  physical I O of the slave device  For non modular slave devices there is only  one I O module  and can therefore not be selected by a user     The selected I O module bytes are sent over the PROFIBUS network to the  slave device at startup  using a Chk_Cfg message  The slave device has to  check and approve the I O modules sent by the Master Unit  before I O data  exchange can be established     The CS1 CJ1W PRM21 PROFIBUS Master Unit supports up to 4000 I O  modules  
152. he operating environment is within the specified condi   tions at installation time and remains that way during the life of the system   Follow all installation instructions and precautions provided in the operation  manuals     XV    Application Precautions 5       5 Application Precautions  Observe the following precautions when using the PROFIBUS Master Unit      N WARNING Failure to abide by the following precautions could lead to serious or possibly  fatal injury  Always heed these precautions     e Always connect to a class 3 ground  100 Q or less  when installing the  Units     ZN Caution Failure to abide by the following precautions could lead to faulty operation or  the PLC or the system or could damage the PLC or PLC Units  Always heed  these precautions     e Install double safety mechanisms to ensure safety against incorrect sig   nals that may be produced by broken signal lines or momentary power  interruptions     When adding a new device to the network  make sure that the baud rate  is the same as other nodes     When adding a new slave device to the network  make sure that the  PROFIBUS Master Unit is in the OFFLINE state  to prevent unexpected  results when starting up the slave device     Use specified communications cables     Do not extend connection distances beyond the ranges given in the spec   ifications     Always turn OFF the power supply to the personal computer  Slaves  and  Communications Units before attempting any of the following     e Mounting
153. he parameter settings must be performed carefully  In general  the slave  device will reject the parameter message  if it contains any faulty parameter   Consequently  the slave device will not reach I O data exchange with the  PROFIBUS Master     The parameter values are by default displayed in Hexadecimal format  By  checking the check box at the bottom  the values are converted to decimal  values     In the Group tab the user can define to which group the slave device will  belong  This group definition is used to define multi cast groups of slave    Generic SlaveDeviceDTM        C OOO CS ection 2 5       device to which a Global Control message can be transmitted  The window is  shown below     Selecting the Groups The user can check the check boxes for each group the slave device will  belong to  The group setting is transferred to the slave device as part of the  parameter message      lox  Device  CJ1W PRT21 GSD File  OC_0602 gsd  Vendor  OMRON Corporation Ident Number   0x0602    Configuration   Parameter Group         ri H I Group 5  T Group 2 I Group 6  I Group 3 I Group 7  I Group 4 I Group 8       The three tabs discussed above  allow for making all the standard PROFIBUS  DP settings for a slave device  For slave devices supporting PROFIBUS DP   V1  two additional tabs will show up  These tabs will appear  if the GSD file  parameter GSD_Revision is set to 3 or higher  The additional tabs are dis   cussed below     Extensions Tab The Extensions tab contains a numbe
154. he rotary switch on the front of the Unit     Note The device address is normally assigned automatically  Only in the case  where there are other devices in the network which have the same address   the device address of the CS1 CJ1W PRM21 Master DTM may need to be  changed     After making the changes  select the Save button in the lower right corner of  the user interface to accept the changes  Next select the Master Setup tab  to  display the Master Setup options     3 4 1 Setting the Master Parameters    Master Setup Tab The Master Setup tab defines    e the behaviour of the Master Unit  when the PLC CPU switches its mode  between RUN   MONITOR and PROGRAM mode     87    Configuring the Master    Unit Behaviour upon PLC  Mode Changes    Note    Auto CLEAR behaviour    88    Section 3 4    e The behaviour of the Master Unit in case an error occurs in one of the  slave devices allocated to the Master Unit     e The method of I O data mapping   The figure below shows the Master Setup tab                  ioi xi  Device Setup Master Setup   Bus Parameters   Slave Area   Advanced   OK    m Action to PLC Mode Transition Enel    To RUN MONITOR Mode    r To PROGRAM Mode E  el    C Keep Current Mode C Keep Current Mode    Goto OPERATE Mode   Goto CLEAR Mode  Auto Clear r Support    Auto Clear Mode OFF IV Auto Addressing       Auto Clear Made ON             The user can select the way the Unit will behave if the PLC mode is changed   The default settings are     e Set the Units ope
155. he warning  will apply the  changed device address     After changing the address in the slave DTM Configuration User Interface  the  updated address will be shown in the Network view  next to the device name     Changing the DTM The slave DTM address can also be changed via the Master DTM  To accom   a via the Master plish this  first open the Slave DTM Address Assignment table     1 2 3    1  Select the Master DTM in the Network view     2  Right click the mouse  and select the Additional functions entry from the  context menu     3  Select the Slave DTM Address Assignment function     80    Configuring the Slave Devices Section 3 3       The window as shown below will be displayed               ioi xi  M DTM Station Address Assignment 7  lose     No   DTM Name  1 OMRON CJ1W PRT21 2 Help    2 CPM14 PRT21 3  3 CQM1 PRT21 4  4 C200H W PRT 21 5  5 F150 PRT 6  6 PRT1 COM 7  Status  a Address   10  zi Set                In order to change the slave DTM address perform the following steps     1 2 3    1  Select the slave device in the list   2  Enter the new address in the field Address in the lower right corner of the  window     Press the Set button  The Status field will display the status of this service    After changing the slave DTM address  the new address will also be shown in  the Network view     3 3 Configuring the Slave Devices    After adding each of the slave DTMs to the network  configurations have to be  selected for each of them  Setting up a configuration invol
156. hen positioned over the LED indicator     Clicking the LED indicator with the left mouse button has the following effects    e The address of the associated slave device will be displayed in the Slave  Diagnostics Data box in the lower half of the window     e The standard diagnostics flags of the associated slave device will be dis   played  LED indicators representing a status are coloured green  LED  indicators representing a potential problem are coloured red     e The colour of the LED indicator for the specific slave device in the Slave  Status Flags box will change colour  if no new diagnostics is available  i e   a yellow LED will turn to green     e The New Diagnostics Received LED indicator in the Slave Diagnostics  Data box will be set to ON     If the Auto Update refresh mode has been selected  the New Diagnostics  Received LED indicator  will be ON only during one update cycle  provided no  new diagnostics are received after displaying     The standard diagnostics for a slave device displayed in the Slave Diagnostics  Data box can be used to    e Troubleshoot the device  the configuration or the network connection  Troubleshooting the device and the connection is discussed in section 4   2 2 Troubleshooting the Network using CX Profibus     e Determine the status of the slave device    e Determine if the slave device has reported extended diagnostics  If extended diagnostics have been reported to the Master Unit  the  Extended diagnostics received LED indicator w
157. hen set to ON  it indicates that the slave device has been disabled  i e  using the STOP  FINS command   The slave device is allocated to the Master Unit  but removed from cyclic  processing        Sync mode    When set to ON  the slave device has been set to the Sync mode  using the global com   mand        Freeze mode    When set to ON  the slave device has been set to the Freeze mode  using the global com   mand        Watchdog on    The watchdog has been enabled at the slave device  through the appropriate setting in the  parameterization message         Slave device    Indicates that the device is a slave device        Static diagnostics    When set  the slave device reports static diagnostics  i e  the error event is serious enough  that the diagnostics is continuously reported  No data exchange will be performed        Re parameterization  requested    When set  the slave indicates that it requires a new parameter setting  The slave device is  not in Data_Exchange with the Master Unit  The indicator remains ON as long as the slave  device has not been parameterized successfully        Extended diagnostics  overflow       The slave device has more diagnostics to report than it can fit into its transmission buffer   Diagnostics information is being lost        71    Generic Slave Device DTM    Section 2 5       Extended Diagnostics       Tab    72    The Extended Diagnostic tab contains any extended diagnostics reported by  the slave device  The figure below shows an exa
158. his Manual               cc ccc cccccccccccccee VII    PRECAUTIONS 2s ncu0s4 Satecedawsa diane dens eieda s   R    1 Itende Adini en oie ice ree eA Ria nak PRS Gea AEN ER xiv  2 General  Precautions rreren a a ent es  bse ata es Rud ee A A A Ra xiv  3 Safety Precautions  eere irere aeaoe ee eee a a eee a deka eed xiv  4 Operating Environment Precautions            0 0 00  XV  5 Application Precautions    sses o secer ee ce e Eees xvi  6 Conformance to EC Directives       0    0c suunnan nenene raaraa xviii    SECTION 1  Features and Specifications          essssssesssoseeeo    a n m    1 1  Overview of PROFIBUS          esan moan ee a ccc eee een eee  1 2 Setting up a PROFIBUS DP Network     0 0 0    cece  1 3 CX Profibus Configurator    1 0 0 0    eee eens 10    SECTION 2  Configuration Software            cccecceesceccceees 17    2 1 Installation Requirements        0 0    eee ene nee 18  222  CX  Prof DUS oaao ea envio aiin eA aoe eae nied a oak Gb eet thee A haere ete 18  2 3 CS1 CJ1W PRM21 PROFIBUS Master DTM               0 0 00    eee 30  2 4 C200HW PRM21 PROFIBUS Master DTM           0 0 0 0    e eee ee ee 52  2 5 Generic Slave Device DTM      6 0    cece eee nee eens 61    SECTION 3  Operation sesasi eo ceias eee kekeris see wert E TS    Bak     Introductions  sc bot tt hele sees eb deal buena lb a E E Sei dh stele Selphy Ble 74  3 2 Setting up a network 2 2 0 0 ce eee eee eee eee bene been beeeneees 74  3 3 Configuring the Slave Devices       2 0 0    cc cece eee 81
159. ics  113  Extensions  Alarm SAP  69  Alarms  69  Auto Clear behavior  66  Configuration processing  66  Diagnostics Update Delay  67  DPV 1 enable  69  Error on Cyclic Data Exchange  67  Fail safe behavior  67  Max  Alarm PDU length  69  Max  channel data length  69  Standard diagnostics  113    Generic slave DTM  Configuring  81  Group assignment  85  I O Configuration  82   Appending  82  Defining  81  Inserting  82  Removing  83  Parameters  84  Common  84  Module  84  Watchdog  83    Global Control  Commands  104  Freeze Unfreeze  48  104  105  I O synchronization  104  Selecting groups  in CX Profibus  48  Sync Unsync  48  104  106  Transmitting commands  106  CX Profibus  via  49  GSD file  DP master section  9  DP slave section  9  DTM versus GSD file  9  General section  9  GSD file technology  8  Installing new  75  Language  9    T O data  Configuration  94  Mapping  Algorithm  94  Area start address  100  Auto addressing    Default behaviour  95  Enable disable  98       Mapping without  98  Re allocating modules  behaviour when  97  Compressing  99  Concept  94  Re allocating modules  96  Removing gaps  99  Supported I O range  94  Types  101  Date Time  101  Floating point  101  Integer  101  Text string  101  Time difference  101  Time of day  101    Installing new GSD files  75    L M    Low voltage directive  xviii    Manual  About  vii  Revision history  145  Master devices  See PROFIBUS  Master  Master DTM  Configuration  7  See C200HW PRM21 DTM  See CS1 CJ1
160. ill be on     Refer to section 4 2 2 Troubleshooting the Network using CX Profibus for a  discussion on the errors reported by the slave and how to correct them     Since all slave devices will have to return their status in the diagnostics mes   sage after parameterization  all the LED indicators associated with the slave  devices allocated to the Master Unit  will indicate received diagnostics right  after network startup     If all slave devices have established I O data exchange with the Master Unit   this information may be less relevant  To detect new diagnostics  received dur   ing I O data exchange  the user can clear all current new diagnostics flags by  pressing the Clear Diagnostics button in the window  thus making it easy to  spot newly received  more relevant diagnostics afterwards     Pressing Clear Diagnostics button will cause all yellow LED indicators to turn  green     Monitoring the Network S CS ection 3 7       3 7 2 Monitoring Slave Status    The Generic Slave DTM provides a Diagnosis User Interface with two tabs     e Standard diagnostics tab  displaying the same information for the associ   ated slave device as in the Slave Diagnostics Data box in the Master DTM  Monitoring User Interface     e The Extended Diagnostics tab  displaying the extended diagnostics  reported by the slave device  The interpretation of this diagnostics infor   mation depends on the type of slave device     Standard Slave As an example  the standard slave device diagnostics inf
161. in the PLC  if default I O mapping  is used as shown above     Z  Caution The default mapping of areas on to the PLC memory is the same default map     ping as used in the CS1 CJ1W DRM21 Devicenet Master Slave Unit  Care  should be taken to avoid data overlap  if such a Unit is part of the same PLC  CPU system as the CS1 CJ1W PRM21 PROFIBUS Master Unit     The CS1 CJ1W PRM21 PROFIBUS Master Unit  will assemble the correct  PROFIBUS data messages from the storage order in the Input and Output  memory areas     The default allocation of I O modules  i e  I O modules are mapped in ascend   ing order of slave addresses and module selection  uses the concept of Auto  Addressing of the CS1 CJ1W PRM21 Master DTM  Auto Addressing will   re allocate I O modules according to the algorithm explained above in each  area    If a configuration has been selected  which is changed later   for example   by  adding an I O module to one of the slaves  the Auto Addressing feature will  add that module to the default area  between the already selected modules of  that particular slave device     95    I O Communication Characteristics    Section 3 5       Z  Caution When an I O module is added to or deleted from a configuration at a later    Note    Example    point in time  Auto Addressing will cause a change in the addresses of subse   quent I O modules in an Input Output area  This will cause I O data of  a part  of the  slave devices to be re mapped to different locations in the PLC mem   ory
162. indicator is Flashing   e ClO Words n 9 to n 16  see Note  show  which slaves have problems   Use CX Profibus and DTMs to determine  slave diagnostics     Note n   CIO 1500    25 x unit number         Verify that the specified slave device is still  connected to the network        4 2 4 Troubleshooting PROFIBUS DP V1 Communication    This section deals with troubleshooting the PROFIBUS DP V1 Communica   tion on the network from a behaviour point of view  The column on the left  describes the general perceived problem to the user  The columns on the  right list the possible causes and their remedies     Communication Problems    PROFIBUS Master Unit is  configured  Both the I O  Communication as the  PROFIBUS DP V1 Com   munication fail     Probable cause  A possible problem with the network     Correction    Please refer to sections 4 2 2 Troubleshoot   ing the Network using CX Profibus and or 4   2 3 Troubleshooting I O Communication        The I O Configuration is incorrect and the  slave device is not in data exchange with the  PROFIBUS Master Unit     Correct the I O Configuration if required        PROFIBUS Master Unit is  configured and the I O  Communication is operati   ional    The PROFIBUS DP V1  Communication fails     130    FINS commands can not be send to a  PROFIBUS Slave which has address value  zero     Change the address of the PROFIBUS Slave  and the PROFIBUS configuration if required        When communicating with the DTM or from  the PLC program  the prev
163. into driver has failed                                     Internal driver error   Could not create read thread   Could not create read event   Could not create write event   Could not create timer event   Error by writing data   Wrong COM state   COM state error is set   COM buffer setup failed   COM set timeout failed   Receive buffer overrun   Receive buffer full   Send busy   Error during close driver   COM port not opened   Invalid handle value   Invalid COM number   Size parameter invalid   Size parameter zero   Buffer pointer is NULL   Buffer too short   Setup error   Send message  timeout error   Could not send a message   Send message  no device connected  Error by send message  message receiving  Telegram collision   Telegram  no acknowledgement received  Telegram  noise                                                                                              138    Error Number    Appendix       Description  Telegram  data overrun       Telegram  parity error       Telegram  framing error       User  Telegram  unknown error       Timeout by receive a message             No message received    139    Appendix       140    A    About  Manual  vii    Acyclic Connection  Configuration  40  Connection Abort status flags  41  Connection status flags  40    Adding Devices to the Network  76    Auto addressing   See I O data  Mapping  Auto CLEAR  6  33   Behaviour  66   Enable  107   Feature  107   Resume OPERATE mode after  108   Transition conditions  107    B    Broa
164. ional aspects of using the PROFIBUS Mas   ter Unit and the configuration software  The section has been setup  to follow  the general process flow of setting up and configuring a network  downloading  the configuration  and operating the PROFIBUS network     Note 1  In case Error messages are displayed  while using CX Profibus  refer to  Appendix A Configurator Error and Warning Messages for more informa   tion on errors     2  This section does not discuss how to operate the C200HW PRM21  PROFIBUS DP Master Unit  For more information on how to operate this  type of unit  refer to the C200H series PROFIBUS DP Master Units Oper   ation Manual  W349 E2 L                   Example To illustrate the explanations  examples are marked with the word Example in  the side line     3 2 Setting up a network    Starting CX Profibus Setting up a network involves setting up a configuration in CX Profibus and  downloading it to the PROFIBUS Master Unit  To start CX profibus  select  Program  OMRON  and CX Profibus  from the Start Menu if the default pro   gram folder name is used   The Login Window will be displayed  Login as either Administrator or Plan   ning Engineer   Note The default password for all levels is    password        CX Profibus will now start  displaying the main window  as shown below     Sst  Unnamed   CX Profibus  Oy x   File Edit View Device Tools Window Help    plela   llal col              Error Log      ee    User   Administrator    A    74    Setting up a network  
165. ious PROFIBUS  DP V1 communication session may not have  been ended correctly    Corresponding PROFIBUS DP V1 Connec     tion bit  refer to Acyclic Connection Abort  Status Box on page 74  is still set     Put the DTM offline and online again to ini   tiate communication     If this does not clear the problem  put the  master in OFFLINE mode and back into the  original state           The PROFIBUS Slave may not support  PROFIBUS DP V1  class 1 or class 2         Please check the Slave   s Operation manual  or GSD file        Troubleshooting Using the Error Log    Section 4 3       4 3 Troubleshooting Using the Error Log    4 3 1    Logged Errors    Error Log Records    Error Log Location    4 3 2 Error Codes    Meaning    Unit     Watchdog timer error in CPU 00 00    Error Log Overview    The PROFIBUS Master Unit maintains an Error Log  which contains the  reports on specific error events     The following errors are recorded in the error log   e Errors in network operation  e Errors in data transfers  e Error in the CPU Unit    Each error is recorded as one record in an error log table  Each record con   tains    e A main error code   e A detailed error code   e A time stamp  from the clock in the CPU Unit     When an error is detected  the error codes and time stamp are recorded in an  error log record  which is stored in the error login volatile memory  i e  RAM  memory  inside the PROFIBUS Master Unit  Serious errors are also recorded  in non volatile memory  i e  Flash R
166. itched to OFFLINE        Mode Command Error    When set to ON  it indicates that two switches in the CIO switch word were set  simultaneously  refer to the CS1 CJ1W PRM21 Operation Manual   W409 E2                        Parameter error    The Parameter set error indicates if an error has been detected in the contents  of the Parameters set while configuring the PROFIBUS interface  using these  parameters        Unit Status    Unit Error    A Unit error indicates that a new error has been set in the Unit Status word  refer  to the CS1 CJ1W PRM21 Operation Manual  W409 E2 L                      Master Error    A Master Error indicates that a new error has been set in the Master Status 2  word  refer to the CS1 CJ1W PRM21 Operation Manual  W409 E2 L                      Local Parameter Storage Error    An error has occurred when storing the configuration to non volatile memory        Local Parameter Load Error    An error has occurred when loading the configuration from non volatile memory        File Read error    When turned ON  this LED indicates that a transfer from Memory Card to the  Unit has failed  The Unit must be re configured        Unit Memory error    When turned ON  it indicates that an error has occurred when writing the Error  Log to the Non volatile memory        Error Log Updated    The Error Log contains new entries  since the last time it was read or cleared        Parameter Storage in  Progress    Configuration Parameters are being transferred to or from th
167. itor User Interface can be updated either Automatically or Manually     e Automatic update  Select the Automatic checkbox in the upper right corner of the Monitor  tab  The refresh cycle will be approximately 0 5 to 1 second  depending  on the PC System  The Manual button will be disabled    e Manual update  Press the Manual button in the upper right corner of the Monitor tab  to  force a refresh of the window contents     The Master status sub tab displays the status of the Master Unit itself  The  LED indicators are directly related to the four CIO status words of the Unit   They can be used to    e Obtain the status of the Master Unit and the network   e Determine errors in the unit or the network   e Troubleshoot the Master Unit and the network     The Master Status 1 box indicates the Master Unit   s status  The Master Status  2 box and the Unit Status box all indicate errors  These LED indicators are  discussed in section 4 2 2 Troubleshooting the Network using CX Profibus     The Slave Status box indicates the overall status of the allocated slave  devices   Main indicators in this box are the LED indicators for operational status of the  Master Unit  They indicate whether the Master Unit is in   e OFFLINE mode    e STOP mode    e CLEAR mode  or in   e OPERATE mode    The Data Exchange LED indicates if I O data exchange is taking place with at  least one slave device     The Auto Clear enabled LED and Valid Configuration LED provide feedback  on the I O configuration d
168. its on the PLC CPU  showed unexpected behav   iour     The I O data mapping of the Master Unit may  overwrite either its won or other Unit ClO DM  Areas settings     Master Unit operational mode changes  unexpectedly    Global Control commands are transmitted  unexpectedly    Other Special I O Units or Special Bus  Units change behaviour unexpectedly     Verify the I O Mapping of the Master Unit    e Ensure that the I O data of the Master  Unit  does not overwrite its own CIO  words    Ensure that the I O data of the Master  Unit  does not overwrite ClO words or DM  words of other Special I O or Special CPU  Units  e g  Ethernet Units        The bus parameter used on the network are   wrong    e   O data exchange between the Master  Unit and the PLC stops     Verify that the correct bus parameters have  been used     e  If necessary  Restart the Unit and force it  to OFFLINE immediately  or    Disconnect the network cable first and  restart the Unit     Download the correct Bus parameters        PROFIBUS Master Unit is  configured  All slaves were  in data exchange  but all  outputs are now set to  zeros  Inputs can still be  read        The Master Unit is in CLEAR mode   The BST LED indicator is Flashing   The CLEAR switch has been set in the  Switch word 1  CIO Word n  bit 02  see  Note   The Unit has been configured for Auto   CLEAR and an error occurred on the Net   work with one or more slave devices        If Auto CLEAR is enabled  correct the net   work problem first  
169. ized Periphery  PROFIBUS DP is optimized for high  speed and low cost interfacing  It is specially designed for communication  between automation control systems and distributed I O at the device level     PA means Process Automation  It permits sensors and actuators to be con   nected to one common bus even in areas where intrinsically safe products are  required  It also permits data and power to be supplied over the bus using  2 wire technology according the international standard IEC 1158 2     PROFIBUS DP and PROFIBUS FMS use the same transmission technology  and uniform bus access protocol  Consequently  both versions can be oper   ated simultaneously on the same bus  FMS field devices  however  cannot be  controlled by DP masters and vice versa     It is not possible to exchange one of these family members by another family  member  This will cause faulty operation     The rest of this section describes the PROFIBUS DP Protocol architecture     1 1 2 PROFIBUS Communication Protocol    OSI reference model    ISO 7498    In general  the PROFIBUS communication protocol is based on the Open  System Interconnection  OSI  reference model in accordance with the inter   national standard ISO 7498  see the following illustration   The model defines  7 layers of communication functions  three of which   layers 1  2  and 7   are  used in PROFIBUS    e Layer 1  the Physical Layer of this model  defines the physical transmis   sion characteristics    e Layer 2  the Data Link Layer 
170. ke sure that the serial cable is attached between the PC   s Serial COM    Port  then in the driver window select the Connect button  associated with  the COM Port to which the C200HW PRM21 is connected    If connection is successful  the Error Field next to the selected button will  remain 0  The other fields will contain Name and Version information of the  firmware on board the C200HW PRM21 PROFIBUS DP Master Unit              Device Assignment CIF Serial Driver x   m Driver Description    i fe OK    Device Driver  OF Serial Driver  A Cancel    m Board Selection  Name Type Version Date Error       M com1  OPM  HMSDPM  voos fostoss fo E i  reme    oo  fo  0 Connect com 2  rea        T f20 Connect com 3  rooms    ff fat Connect CaM 4             In case of connection error  the Error Field will contain an error code  which  can be used to determine the communication problem  Refer to Appendix  A 5 C200HW PRM21 CIF Driver error messages for descriptions on most  common driver error numbers    To assign the driver to the selected port and C200HW PRM21  the check   box to the left of the COM Port must now be selected  after which the OK  button must be pressed to close the window     In order to download the parameter sets to the C2OOHW PRM21 PROFIBUS  DP Master Unit  perform the following sequence     Generic Slave Device DTM    Section 2 5       Monitoring    1 2 3       Note    1 2 3       1  Select the DTM in the Network view and right click the mouse to display  the contex
171. l    e switch its outputs to a known state     e signal its change of state in a diagnostics message  the next time the  Master addresses the slave     83    Configuring the Slave Devices Section 3 3       e request re parameterization from the Master  before resuming   O  data exchange   If disabled  the slave will remain in data exchange  even if the Master is not  communicating  thus maintaining its outputs in the latest known state   based on the last I O data exchange message   2  Watchdog Interval   This value is the watchdog timeout related to the Master Slave communi   cation time out     Note Enabling the Watchdog Control is highly recommended for safe operation of    Z  Caution    the network     In the current version of CX Profibus  the watchdog value for each of the  slave devices is overruled by the value determined by the Master DTM   Therefore  changing the value in the Generic Slave DTM has no effect     When done  making the I O configuration settings  press the Apply button at  the bottom of the window  Next  select the Parameter tab  to make the neces   sary parameter selections     3 3 2 Setting Parameters    84    The parameters are sent by the Master Unit to the slave device prior to estab   lishing I O data exchange  The slave device will reject incorrect parameters  and not establish I O data exchange  unless the parameters are changed     In general there will be two types of parameters     e Common Parameters  Most of the slave devices require at le
172. le     A FDT container application facilitates configuration of network devices and  parameterizing and or manipulating their operational modes  All device  dependent functionality is concentrated in the DTM     FDT container applications can be stand alone tools  or can be part of other  engineering tools such web browsers providing FDT interfaces Since FDT  standardizes the interfaces  it allows devices from different manufacturers to  be integrated in any automation system  regardless of the fieldbus system   CX Profibus is an example of a FDT container application  It is described in  detail in the following sections     DTMs are provided by the manufacturer of the device  A DTM is comparable  to a printer driver  which allows interactive configuration and diagnostics     Setting up a PROFIBUS DP Network Section 1 2       DTM Properties    ActiveX User Interface    XML based Data Transfer    Communication DTM    CX Profibus    The DTM provides not only the configuration  manipulation and monitoring  functions for a device including the user interface functions  it also provides  the connection technology to the device     In general  a DTM is a Microsoft COM component  which can be executed  from within a FDT container application  A DTM is not a stand alone tool  it  requires a FDT container application to be executed  The DTM provides a  number of interface functions  through which it can be controlled and  accessed in order to transfer data to or from the DTM     A DTM
173. ll processing the last received parameter message and has as yet  not approved nor rejected that message     During the Diagnostics Update Delay period the PROFIBUS Master Unit will  continue requesting its diagnostics data  Also during this period  the diagnos   tics data received from this slave will not be updated in the PLC CPU     PROFIBUS DP V1 defines extended communication functions between a  PROFIBUS DP V1 master and a PROFIBUS DP V1 slave device  These  extensions include   e Acyclic communications between master and slave  to allow re parame   terization  during I O data exchange   e Extended alarm reporting and acknowledgement     Settings related to these extensions are sent to the slave device through the  Set_Prm message     1  The PROFIBUS DP V1 settings in this tab refer to PROFIBUS DP V1  Class 1 communication only  For PROFIBUS DP V1 Class 2 communica   tion no specific settings are required    2  The CS1 CJ1W PRM21 PROFIBUS DP Master units will automatically  disable the DP V1 settings to avoid the slave devices to use PROFIBUS  DP V1 functions  Only the CS1 CJ1W PRM21 PROFIBUS DP V1 Master  Units will use the settings below     The DPV1 settings window is shown below      ioii  Device  BK3120 GSD File  BK3120 GSE  Vendor  BECKHOFF INDUSTRIE ELEKTRONIK Ident Number  OxBECE    Configuration   Parameter   Group   Extensions DPV1      ca    Max  channel data length  52  Max  alarm PDU length  58     Alarms    Alarm mode  1 alarm of each type x      P Pull Pl
174. m the following steps     1  Select the slave device in the list     2  Enter the new address in the field Address in the lower right corner of the  window     3  Press the Set button  The Status field will display the status of this service     The Set Device Station Address function is provided for slave devices of  which the PROFIBUS address is not set through switches  but by using the  PROFIBUS DP Set Slave Address service  Slave devices which support this  service also provide a means to store the address in internal non volatile  memory  In case this non volatile memory does not contain an entry  the  slave device will assume the default address 126     1  The PROFIBUS DP Set Slave Address service is supported by the CS1   CJ1W PRM21 Units as of Unit version 2 0     2  In order to be able to change a device   s address  the CS1 CJ1W PRM21  PROFIBUS Master DTM must be on line     Selecting the Set Device Station Address displays the window shown below              nH  1   CJ1W PRM21   1 PROFIBUS Master   Set Device Station Addr a  iol xj  m Perform the DP command  Set Device Station Address   lt  lt  lt         lose    Target Device    Address   126     Help    Ident number  hex   11234       New address   33  T Lock  Status  a             CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       In order to change the address of a slave device perform the following steps   Make sure that the DTM is on line with the CS1 CJ1W PRM21 Unit      1 2 3    1  Enter the device   s c
175. memory independently of each other     Changing the mapping can be achieved using drag  amp  drop  The module which  is mapped to Area 1 and which must be mapped to Area 2  can be copied  there by dragging it from the overall module list on top to Area 2     The I O mapping concept is discussed in section 3 5 2 Mapping I O Data     1  By default the Auto Addressing option will be enabled  see section 3 4 1  Setting the Master Parameters   If any I O modules are moved from one  Area to another  the I O modules in first Area are re mapped to close all  the gaps between mappings    2  Prior to download  the CS1 CJ1W PRM21 Master DTM will check the  mappings for possible Area overlaps  PLC memory overlaps and non ex   isting EM banks  If an error is detected  download will be aborted and the  necessary correction must be made first     Z  Caution When mapping the I O Areas  make sure that the I O data will not overlap the    Unit   s own CIO Area or one or more of the I O data areas of any other PLC  CPU or I O Unit  The CS1 CJ1W PRM21 Master DTM does not check this   Failure to avoid this  will lead to unpredictable behaviour of the Unit     Configuring the Master    Section 3 4       3 4 4 Configuring CX Server    Configuring  Communication    1 2 3       CX Server    Configuring CX Server    1 2 3       The CS1 CJ1W PRM21 Master DTM uses CX Server to connect to the Unit  for both downloading a configuration as well as monitoring the Master Unit  In  order to setup the communic
176. mitted separately from the automati   cally transmitted messages  at the end of the PROFIBUS I O data ex   change cycle     User initiated Global Control commands can be transmitted to either all slave  devices allocated to a Master Unit  or to one or more of up to eight groups of  slave devices  The group addresses are defined by up to eight bits in a group  address byte  which is part of the Global Control command     If a Global Control command is targeted to all slave devices  all the group bits  in the group address bytes are set to 0     In order for a specific slave device to belong to a certain group  the group  assignment for the slave has to be defined through the Generic Slave DTM  Configuration User Interface  A slave device can belong to one or more    Operating the Network   Section 3 6       groups at the same time  or to no specific group at all  The group assignment  is sent to the slave devices as part of the parameter message     To define the group assignment of a slave device  through the Generic Slave  DTM  refer to section 3 3 3 Selecting the Group Assignment     Freeze   Unfreeze Sending a Global Control   Freeze command to a slave device has the follow   commands ing effect    e The slave device will continue to read its physical inputs  but not send this  data to the PROFIBUS Master Unit    e Instead  it will continue to transfer the input data to the Master Unit from  the moment the Global Control   Freeze command was received    e If a new Global C
177. mory areas    e Availability of EM banks should any of the I O Areas be mapped to one of  the EM Banks  Availability of the EM banks depends on the PLC CPU  type    Anyone of these errors will abort the download process without conse   quences for the CS1 CJ1W PRM21 PROFIBUS Master Unit     The error messages associated with these failures are listed in Appendix A 2  Error Messages   Configuration  The list also provides remedies     If no errors occurred during the checking phase  the Master DTM will try to  establish communication with the CS1 CJ1W PRM21 PROFIBUS Master Unit  through CX Server  If this fails  an error message will be displayed  indicating  a communication problem  see Appendix A 3 Error Messages   Communica   tion   A failure to establish communication prior to download will have no con   sequences for the CS1 CJ1W PRM21 PROFIBUS Master Unit  The list  provided in Appendix A 3 Error Messages   Communication also provides  possible remedies     If none of the first two processes result in a failure  downloading will com   mence  As soon as downloading has started  the data in the volatile memory  of the CS1 CJ1W PRM21 PROFIBUS Master Unit will be overwritten     If a failure occurs during the download process  which prevents the Master  DTM from completing the process  the user must restart the Unit manually   Restarting the Master Unit will abort the download process in the Master Unit  and recover the previous configuration from its non volatile memory    
178. mple of Extended diagnos   tics     lolx   Device  CJ1W PRT21 GSD File  OC_0602 gsd OK    Vendor  OMRON Corporation Ident Number  0x0602  Help    Diagnostic Extended Diagnostics      0x05  0x00  0x04  0x00  0x00  0x00  0x00  0x00  0x00  0x00  0x00  0x0     Device related  Non fatal PLC error   Device related  PLC in Monitor mode          Connected Update         The first row of the Extended diagnostics window contains the raw data as  received from the slave device  Depending on the GSD file  it may provide  text strings for each Extended diagnostics events entry  i e  if the event occurs  and the diagnostics information is received by the DTM  it can display a text  string in stead of only the raw bytes  This makes troubleshooting the device  easier     If the strings are not supported  the user must determine the event from the  raw data bytes     SECTION 3    Operation    This section describes how to operate the CS1 CJ1W PRM21 PROFIBUS Master Unit in a Network  It will discuss setting  up a network  configuring all the connected devices and starting the network  Furthermore  it provides information the I O  data exchange performance and it also provides information on how to monitor a network  using the Unit and CX Profibus     3 1    3 2    3 3    3 4    3 7    Introduction               Setting up a network           3 2 1 Adding Devices to the Network                   0 0 0 00008   3 2 2 Changing Device and DTM Addresses                    4    Configuring the Slave 
179. n of CX Server  Make sure the correct CX Server  version is installed  Version must be  1 7 and up     Name of the function  called with   Container called a function with There must be problem in the con     improper parameters NULL pointer  tainer  Reinstall CX PROFIBUS  if  problem persists contact supplier                       137    Appendix       Number Message Description Correction    Received XML Document does Container called a function with an    There must be a problem in con    not fit it s XML schema improper XML document  tainer program  Reinstall CX PROFI   BUS  if problem persists contact  supplier     Ole Register Drop Target Failed An internal error has occurred  Reinstall CX PROFIBUS  if problem  persists contact supplier     Undefined control type An internal error has occurred  Reinstall CX PROFIBUS  if problem  persists contact supplier     Communication failure with the An internal error has occurred  Reinstall CX PROFIBUS  if problem  DTM persists contact supplier     GUI could not be closed An internal error has occurred  Reinstall CX PROFIBUS  if problem  persists contact supplier     A 5 C200HW PRM21 CIF Driver error messages    This section lists the most common error messages encountered with the serial communication driver for the  C200HW PRM21  Extended error messages are available through the Help files of the C200HW PRM21 DTM     Error Number Description    No COM port found or COM port already in use  COM port already opened  Function call 
180. n on slave PLC 1 0 bus fail   Input data format   Input from slave PLC area   Input area start address   Slave PLC status indication       ON  default   10 ms  default    Reset to 0  default    Motorola  default    CIO area  CIOxxxx    0x01 5e   Continue 1 0 data exchange  Stop 1 0 data exchange  Motorola  default    CIO area  ClOxxxx    0x0032    PROFIBUS diagnostics only    T Decimal values       OK   Cancel Apply   Help       The PROFIBUS DP parameter message contains a number of settings for the  slave device  It is transmitted to the slave device before the I O configuration  message  In most cases a slave device requires a block of Common Parame   ter settings  i e  settings which apply to the whole device     However  there are also more sophisticated   modular   devices which require  parameter settings per I O module selected  The specific parameters blocks  can be selected from the drop down list at the top of the Parameter tab  In the  figure above  the Common parameters are shown  This particular device does  not support module parameters  so the parameters shown are the only ones     The Parameter list consist of a left column containing the name of the Param   eter and a right column containing the settings options  In order to change the  parameter setting  double click the row  with the left mouse button  Depend   ing on the type of parameter and the selection options  either the field can be  edited directly  or a drop down list with options will appear     T
181. n the New Address field     3  Optionally  select the Lock checkbox  if the address change must be made  permanent     4  Press the Set button to invoke the PROFIBUS DP Set Slave Address ser   vice  The Status field will display the status of this service     Selecting the Lock option makes any future changes of the address impossi   ble  even after power down power up of the slave device     After successful completion of the address change  the device DTM address  in the Network view has to be changed as well     When assembling the PROFIBUS configuration in the Network view  the Mas   ter DTM automatically assigns addresses in ascending order to the slave  DTMs  If the physical address on the slave device differs from the DTM  address  the DTM address must be changed to match that setting     Changing the DTM address can be done in two ways   e Change the DTM address through the Generic Slave DTM  e Change the DTM address through the Slave DTM Address Assignment  table via the Master DTM     The first option  using the Generic Slave DTM is illustrated in the example  below     Assume that the F150 PRT Vision system in the previous example  has an  actual network address of 10  instead of 4  which was automatically assigned   In order to change the network address of the F150 PRT  or any other slave  device   perform the procedure outlined below     1  Open the Configuration User Interface for the slave device  by selecting it  in the Network view  and double clicking the l
182. nderstand this manual before using the product  Please consult your OMRON  representative if you have any questions or comments     Warranty and Limitations of Liability       WARRANTY       OMRON s exclusive warranty is that the products are free from defects in materials and workmanship for a  period of one year  or other period if specified  from date of sale by OMRON     OMRON MAKES NO WARRANTY OR REPRESENTATION  EXPRESS OR IMPLIED  REGARDING NON   INFRINGEMENT  MERCHANTABILITY  OR FITNESS FOR PARTICULAR PURPOSE OF THE  PRODUCTS  ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR  INTENDED USE  OMRON DISCLAIMS ALL OTHER WARRANTIES  EXPRESS OR IMPLIED              LIMITATIONS OF LIABILITY          OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL  INDIRECT  OR CONSEQUENTIAL DAMAGES   LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS   WHETHER SUCH CLAIM IS BASED ON CONTRACT  WARRANTY  NEGLIGENCE  OR STRICT  LIABILITY     In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which  liability is asserted     INNO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY  REPAIR  OR OTHER CLAIMS  REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS  WERE PROPERLY HANDLED  STORED  INSTALLED  AND MAINTAINED AND NOT SUBJECT TO  CONTAMINATION  ABUSE  MISUSE  OR INAPPROPRIATE MODIFICATION OR REPAIR        ix       Appli
183. ns supported by CS CU series  PLCs    Describes the ladder diagram programming  instructions supported by CS series and  CJ series PLCs    Provides information on how to use the CX   Programmer  programming software which  supports CS1 CJ1 series PLCs    Provides information on how to use the CX   Server communication driver software  which supports CS1 CJ1 series PLCs                                      J series W340 E1      E  CJ1G                                                                  E W414 E1                 CX Server  Run Time User Manual    CX Server W391 E2              CS1 CJ1W PRM21  Operation Manual    SYSMAC CS CJ series  CS1 CJ1W PRM21  PROFIBUS DP Master Units  Operation Manual    Provides information on how to install and  use the CS1 CJ1 PRM21 PROFIBUS Mas   ter units           W409 E2           C200H series PROFIBUS DP  Master Units  Operation Manual       C200HW PRM21 PROFI   BUS DP Master Unit       Describes the Installation and Operation of  the C200HW PRM21 PROFIBUS DP Mas   ter Units           W349 E2                 Vil     N WARNING Failure to read and understand the information provided in this manual may result in per   sonal injury or death  damage to the product  or product failure  Please read each section  in its entirety and be sure you understand the information provided in the section and  related sections before attempting any of the procedures or operations given     viii       Read and Understand this Manual    Please read and u
184. nterface between the two DTMs    mentioned above and the serial communication driver  to the C200HW   PRM21 PROFIBUS DP Master Unit     Note 1  This Operation Manual does not contain a detailed description of the  C200HW PRM21 Unit  only a description of the DTM  For more details on  the C200HW PRM21 refer to C200H series PROFIBUS DP Master Units  Operation Manual  W349 E2 L       2  The C200HW PRM21 Unit and DTM do not support PROFIBUS DP V1                 SmartSlice GRT1 series SmartSlice GRT1 series GRT1 PRT DTM allows configuration of the GRT1   GRT1 PRT DTM PRT PROFIBUS Communication Unit and SmartSlice I O Units  The DTM  provides the following user interfaces     e The Configuration User interface to define the I O configuration and  parameter setting for I O data exchange with the PROFIBUS Master Unit    e Configuration User Interfaces to configure individual SmartSlice I O Units  attached to the GRT1 PRT    e A monitoring User interface to monitor the status of the GRT1 PRT and  individual SmartSlice I O Units     Generic Slave DTM The Generic Slave DTM allows the handling of classic GSD files of up to GSD  revision 3 within CX Profibus  Upon allocating a slave device  for which only a  GSD file is available to a Master Unit in the network  this DTM will be invoked   This DTM consists of two parts     e The Settings DTM will provide the user interface to display the device   s  information and the selectable values  as defined in the GSD  After mak   ing the necessa
185. odule Name Module Configuration Identifier       1 word In Out OxFO  2 words In Out OxF1  4 words In Out OxF3    8 words In Out OxF 7   16 morde InN ha       Insert   Append                        Configured Modules          Slot   Module Name   Module Configuration Identifier    1 1 word In Out OxFO   2 2 words In Out OxF1   3 4 words In Out OxF3   4 8 words In Out OF           Remove            OK Cancel   Apply   Help         Removing I O Modules To remove I O modules from the Configured Modules list  perform one of the  following procedures   e Select the I O module that needs to be removed from the Configured  Modules list  and double click it with the left mouse button  If more than  one module must be added  repeat this step for the other modules   e Select the I O module that needs to be removed from the Configured  Modules list  and press either the Remove button  This method allows  selection of more than one module  by pressing either the Shift or the  Ctrl key on the keyboard  while selecting the modules     Watchdog Settings Apart from the I O module selection  the Configuration tab also contains the   settings for two other parameters    1  Enable Watchdog Control  This parameter will enable disable the monitoring of the Master Slave  communication in the slave device  If enabled  the slave will stop I O data  exchange with the Master  if the Master has not send any request mes   sage to the slave  within the configured Watchdog time  Furthermore  the  slave wil
186. odule list to the map   ping Area and not moved  This means that the module list acts as a re   source for the two Mapping Areas  below the module list     2  When adding removing slaves modules  and Auto Addressing has been  enabled  the modules in the Areas will be remapped  This usually results in  I O data being re mapped  Therefore it is recommended to select all slaves  and modules  before setting up the PLC memory mapping configuration      N Caution The default mapping of areas on to the PLC memory is the same default map   ping as used in the CS1 CJ1W DRM21 Devicenet Master Slave Unit  Care  should be taken to avoid data overlap  if such a Unit is part of the same PLC  CPU system as the CS1 CJ1W PRM21 PROFIBUS Master Unit     Mapping Area Controls Each mapping Area in the Allocation tab is equipped with four controls and an  information field located below the Area  The controls and information field  are listed and explained in the table below     Control Description    Selects the PLC memory area to which the associated  I O Area will be mapped  Possible options are     Not Used  List must be empty     CIO   DM   Work   HR   EM Bank 0 to 12  Decimal    See Note 1      Start Address In this field the user can enter the start address in the  PLC memory of the mapped data block     Length The length box allows the user to select the number of   visible rows  The minimum and the default value is 100  words  If more than 100 words are configured  the mini   mum Length v
187. of this model  defines the bus access proto   col  This protocol also includes data security and the handling of trans   mission protocols and telegrams    e Layer 7  the Application Layer of this model  defines the application func   tions  This Layer is only applicable to PROFIBUS FMS     Overview of PROFIBUS    Section 1 1       PROFIBUS DP    OSI Layer 1  2 and User  Interface    OSI Layer 1  Transmission  Medium    RS 485 Technology    RS 485 Transmission  Speed    Cable length    DP Profiles    DP Extensions  User Interface Layer DP Basic Functions     7  Application Layer    6  Presentation Layer   5  Session Layer NOT DEFINED   4  Transport Layer                3  Network Layer  2  Data Link Layer Fieldbus Data Link  FDL   1  Physical Layer RS485   Fibre Optics          In the rest of this manual  only PROFIBUS DP is considered     PROFIBUS DP uses layers 1 and 2  and the user interface  Layers 3 to 7 are  not defined for PROFIBUS DP  The user interface Layer defines the interface  functions for specific application areas  i e  the PROFIBUS DP basic functions  and communication profiles  This streamlined architecture ensures fast and  efficient data transmission  The application functions which are available to  the user  as well as the system and device behaviour of the various PROFI   BUS DP device types  are specified in the user interface     RS 485 transmission technology or fibre optics are available for transmission   RS 485 transmission is the most frequently 
188. og In order to clear the Error Log  perform the following actions     1 2 3    1  Open the CS1 CJ1W PRM21 Master DTM Diagnosis User Interface   2  Select the Monitor   Error History Tab tab   3  Press the Clear button in the lower right corner of the window     115    PROFIBUS DP VI Services S Section38       This will clear not only the Error Log stored in volatile memory  but also the  error log events stored in the non volatile memory     Note Clearing the Error Log is not possible  if an error  which was just added to the  Error Log is still active  The cause of the active error has to be removed first  before the Error Log can be cleared  Attempting to clear the Error Log  while  an error is still active  does not result in an Error message from the CS1   CJ1W PRM21 Master DTM     3 8 PROFIBUS DP V1 Services    Next to the cyclic I O data exchange  the CS1 CJ1W PRM21 PROFIBUS  Master Units are capable of communicating using acyclic DP V1 messages     Configuring and   The FDT DTM framework enables the configuration and monitoring of specific  Monitoring Slaves using parameters of PROFIBUS slaves  The DTMs support sending PROFIBUS  DTMs DP V1 Class 1  MSAC1  and Class 2  MSAC2  messages directly to the    slaves  The slave DTMs  provided by the Slave   s manufacturer  can therefore  perform application related configuration and monitoring                                                        Read Request Acyclic Redd Request Acyclic Read Request    MH  CS1 CJ1W  CS1 CJ1W
189. oint of view  The tables below describe the general per   ceived problem to the user  probable causes and probable remedies     Communication Problems    Problem    PROFIBUS Master Unit is  configured  but none of the  slaves are exchanging  data     Probable cause  No power is supplied to the system   e All LED indicators on the system are OFF     Correction    Verify that power is supplied to the sys   tem        A PLC CPU  startup  error occurred   e The ERH indicator is ON  the other LED  indicators are OFF     e The ERR ALM LED indicator on the PLC  CPU is ON     Determine error in the PLC CPU  Refer to  the CS1 Series CPU Unit Operation Man   ual  W339  or the CU Series CPU Unit  Operation Manual  W393          The stored configuration contains a check   sum error  storing configuration was inter   rupted or failed      e After restarting the Unit  the ERC LED  indicator is ON  and the PRM LED indica   tor is OFF    Unit Status error flag may provide more  information  CIO Word n 4  bit 06  bit 07   bit 09  see Note      Re download the configuration   If the problem persists  replace the Unit        The configuration contains timing errors    e After restarting the Unit  the ERC LED  indicator is ON  and the PRM LED indica   tor is OFF     Verify that the Bus parameter sets are cor   rect     e Re download the configuration   e Ifthe problem persists  replace the Unit        The PROFIBUS Master Unit is in either   OFFLINE or STOP mode    e The BST LED indicator is OFF 
190. onfiguration of CX Server failed  Make sure the settings within the  ured Device Set up tab are correct   Select the Test Button to check  this    Make sure the Personal Com   puter COM port selected within  the Device Set up Configuration  is not in use by another applica   tion  If it is close the connection  from within the other application   Restart CX PROFIBUS     Restart Personal Computer to  ensure COM port is released   Ensure the correct version of CX   Server is installed on the Personal  Computer  Refer to the Master  Manual for installation details     When the problem has been  removed  perform one of the fol   lowing successfully to confirm the  problem has been solved       Select the Configure Button in  the Device Set up tab      Select the Test Button in the  Device Set up tab    CX Server could not be initialized   Initialization of CX Server was not Ensure the correct version of CX   possible  Server is installed on the Personal  Computer  Refer to the Master  Manual for installation details                       A 4 Error Messages   System    The table below lists the Error messages related to the System on which the DTM is installed     Number Message Description Correction    Connected device can not be con    Incorrect firmware type  Make sure the unit connected is a  figured with this DTM CS1W PRM21 or CJU1W PRM21    Make sure the Unit number in the  Device set up corresponds to the   physical unit     Incorrect version of CX Server  Incorrect versio
191. onfiguration of the CS1 CJ1W PRM21 PROFIBUS  DP Master Units  Unit version 1 0   e A DTM to facilitate configuration of the C200HW PRM21 PROFIBUS  Master Unit  e A DIM to facilitate configuration of the SmartSlice GRT1 series  GRT1 PRT PROFIBUS Communication Unit   e A DTM to facilitate integration of GSD file based devices into CX Profibus   see section 1 2 3 GSD file Technology for more information     1 2 3 GSD file Technology    GSD file Technology    The older and most commonly used configuration technology is the based on  GSD files  General Slave Data file   A GSD file is a text file  containing the  characteristic features and configuration options of a device  The device data  base file of each device is loaded in the configurator and downloaded to the  master device     GSD files are usually supplied with a Unit  or can be downloaded from the  Internet  either from the manufacturer s site  or from the GSD library of the  PROFIBUS International at htto  Awww profibus com     Setting up a PROFIBUS DP Network    Section 1 2       GSD File Language    General Section    DP master Section    DP slave Section    DTM versus GSD File    The language used in the GSD file is indicated by the last letter of the file  extension    GS      Default   GSD  English   GSE  German   GSG  Italian   GSI   Portuguese   GSP  Spanish   GSS    The GSD files are prepared individually by the vendor for each type of device   according to a fixed format  Some parameters are mandatory  some hav
192. ontrol   Freeze command is sent  the slave device will  update its PROFIBUS input buffers only once  with the most recent physi   cal input data  and continue to transfer this data to the Master Unit with  subsequent I O data exchange messages    e If a Global Control   Unfreeze command is sent  the slave device will  revert back to its original situation  and transfer updated input information  to the Master Unit with subsequent I O data exchange messages     Note If a Global Control command contains both a Freeze and an Unfreeze com   mand  the Unfreeze will prevail     The figure shown below illustrates the Freeze   Unfreeze feature as imple   mented by the CS1 CJ1W PRM21 PROFIBUS Master Unit   Global Control Freeze command Global Control Freeze command    Global Control Unfreeze command                                            PLC Cycle Instruction Instruction Instruction Instruction  y Execution Execution Execution Execution       Freeze Unfreeze    transmitted transmitted  PROFIBUS AAN ASSN  Cycle SAAR SS  1  1  I  Slave Y    PROFIBUS x    Input Buffers       Slave Input  Refresh Cycle                Freeze command freezes Freeze command causes Unfreeze command cancels  slave input refresh process  immediate update of transmit Freeze command and causes  Last input data transferred to buffer  Last sampled data will be immediate update of transmit  transmit buffer will be transferred over PROFIBUS  buffer  Input refresh process  transferred over PROFIBUS  started again 
193. options     The Master DTM Configuration User Interface contains four tabs   e Device Setup tab  e Master Setup tab  e Bus Parameters tab  e Slave Area tab  The four tabs are discussed below     The Master DTM Configuration User Interface contains four general buttons   They are listed in the table below  together with the action taken when press   ing them     Button Action    Evaluate  and save the changes made  if any  and close the user  interface     Note If any invalid settings have been made  a warning message  will be displayed  allowing cancellation of the command     Closes the user interface without saving     Note If any changes were made  a warning message is displayed   allowing cancellation of the command     Launch context sensitive Help for the Active tab   Evaluate changes and save them        Cancel       Help  Save             Save in the context of the buttons means that the changes made by the user  are saved in the DTM only  i e  the changes are not permanently saved in the  Project yet  This is indicated by the asterisk next to the DTM in the Network  view  The next time in the same session the GUI is opened  the changes will  still be there  In order to save the changes permanently  e g  to hard disk   Click the File   Save option from the main menu of CX Profibus     31    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Device Setup Tab The Device setup tab  see figure above  provides the controls to achieve  communication between the PC and the
194. or on the PLC  CPU is ON     Determine error in the PLC CPU  Refer to  the CS1 Series CPU Unit Operation Man   ual  W339  or the CU Series CPU Unit  Operation Manual  W393          A Unit error occurred   e The ERC indicator is ON  the other LED  indicators are OFF     e The ERR ALM LED indicator on the PLC  CPU is ON     Restart the Unit  and read the error log to  determine the type of error        The PROFIBUS Master Unit is in either   OFFLINE or STOP mode    e The BST LED indicator is OFF   e The BF LED indicator is ON  A PROFIBUS  interface error has occurred  see Master  Status 2 error flags  CIO Word n 6  bit 00    03  see Note  for details     Determine the mode of the Unit  Check the  Master Status 1 Word  CIO Word n 5  bit 00  to bit 03  see Note   If Unit is in OFFLINE or  STOP mode     e Verify that the master does not use the  same address as another Master Unit on  the network  Otherwise  correct the Master  Unit   s PROFIBUS address    Set CLEAR or OPERATE switch in ClO  Word n  see Note         Network cabling is not correct   e BF LED indicator is ON     e Master Status 2 error flag may provide  more information  CIO Word n 6  bit 00      03  see Note      Verify that the network installation is correct   e Verify that the network is still in tact  and  connected to the Unit     e Verify that any repeaters used are func   tioning correctly        PROFIBUS Master Unit is  configured  After switching  the Master Unit to OPER   ATE  the Unit itself or other  Un
195. ord        IV Operator Change password        IV Maintenance Change password        I Planning Engineer Change password         Administrator Change password           Help Cancel         By selecting the check box next to a level  the Administrator can grant access  rights to CX Profibus  i e  the checked levels can start and access CX Profi   bus  If a check box is not selected  the corresponding level can not be used to  start CX Profibus  and it will not appear in the drop down list in the login win   dow    For example  in the window below the Observer and Maintenance levels are  unchecked     x    I Observer    IV Operator Change password          I Maintenance Change password    I Planning Engineer Change password        Administrator Change password             Change password          Help   Cancel         The next time CX Profibus is started  the Observer and Maintenance access  levels are not available in the login window  as shown below     CX Profibus Login xj  User  Administrator X      Administrator    Planning Engineer  Operator    Help Cancel            Password           The Administrator level has always access and can not be disabled in the  User Accounts window     In order to change a specific password  select the Change password button  in the User Account window  next to the related access level  The level must  be enabled by selecting the check box to the left of it  Pressing the Change  password button opens a window allowing the entry of a new passw
196. ord  As  an example the window below shows the Change password window for the    29    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Planning Engineer  You can now enter the new password  confirm it by re typ   ing the password and select the OK button to activate the new password     Planning Engineer Password x        New Password     Confirm New Password   17  i   ie      Note If access protection is not important for the application  you can define an  empty string as a password  i e  when entering the new password  simply  press the return button on your PC  When starting CX Profibus  the login win   dow can be passed by pressing the return button on your PC  without entering  a password     2 3 CS1 CJ1W PRM21 PROFIBUS Master DTM    CS1 CJ1W PRM21 Master To allow configuration and data monitoring from within CX Profibus two CS1   DTM CJ1 PROFIBUS Master DTMs are installed  together with CX Profibus  Each  DTM shows up in the Device Catalogue under two different names     DTM Name Functions    CS1W PRM21 PROFIBUS Master 1 0 Configuration of PROFIBUS DP    CJ1W PRM21 PROFIBUS Master and PROFIBUS DP V1 master Units  Monitoring of PROFIBUS DP and  PROFIBUS DP V1 master Units          CS1W PRM21 PROFIBUS DP V1 Master 1 0 Configuration of PROFIBUS DP       CS1W PRM21 PROFIBUS DP V1 Master  274 PROFIBUS DP V1 master Units  Monitoring of PROFIBUS DP and  PROFIBUS DP V1 master Units  Provide an Acyclic communication  channel with PROFIBUS DP V1 slave  devices           The
197. ormation window is  Diagnostics Example shown below  For more information regarding interpretation of the LED indica   tors  refer to section 3 7 1 Monitoring the Master Unit and the Network     2101 x   Device  CJ1W PRT21 GSD File  OC_0602 gsd OK    Vendor  OMRON Corporation Ident Number 0x0602    Help    Diagnostic   Extended Diagnostics      r Station Status          Wa Master lock W Slave deactivated     Parameter fault W Syne Mode   W Invalid slave response    Freeze Mode     Function not supported   Watchdog on     Extended diagnostics   Slave device   W Configuration fault Wa Static diagnostics   W Station not ready WW Reparameterization requested  W Station not existent Wa Extended diagnostics overflow    Assigned Master Address  1 Device internal Ident Number  0x602         Connected Update         Extended Slave Extended diagnostics data are often   not always   provided by a slave device  Diagnostics to indicate additional slave specific diagnostics  error and alarm information   which can not be contained in the standard data part of the diagnostics mes   sage  These extended diagnostics data bytes are sent by the slave in a diag   nostics message following the standard data part   For slave devices supporting extended diagnostics data  the associated GSD  files often   again  not always   provide language dependent text strings to  facilitate interpretation of the diagnostics codes  sent by the slave device   The Generic Slave DTM provides an easy to use interfac
198. ownloaded to the Unit     109    Monitoring the Network    Section 3 7       Example    Slave Status    Slave Status Overview    110    The figure below shows an example of the Master Status tab  in the case of a  fully functional network  i e  there are no errors and all slave devices are  exchanging I O data with the Master Unit     tat  1   CJ1W PRM21 PROFIBUS Master   Diagnosis   0  x     Monitor   Online Operations      Master Status   Slave Status   Error History         r Refresh             m Master Status 1   _ Unit Status              Boece    OPERATE    Unit Eror  O STOP  O  Master Error     CLEAR     Local Parameter Storage Error         OFFLINE      Local Parameter Load Error     File Read Error    Data Exchange      Unit Memory Error       Auto Clear Enabled      Error Log Updated    Valid Configuration oO Parameter Storage in Progress    Master Status 2 pSlave Status   O Disturbed Bus Error   Slave Diagnostic Received        All Slaves in Data Exchange    oO PROFIBUS Protocol Error       Double Master Address Error   CO  Hardware Error    O Mode Command Error        Parameter Error                   The Slave Diagnostics Received LED indicates if any of the allocated slave  device have returned diagnostics information to the Master Unit  In order to  determine which slave reported diagnostics  select the Slave Status tab next  to the Master status tab     The CS1 CJ1W PRM21 Master DTM Diagnosis User Interface provides a  comprehensive overview of the slave devi
199. p  Drop function  A Device DTM listed in the standard Device Catalogue window can be  dragged and dropped from the Device Catalogue to a desired position in  the Network view    e Using the Add Device button  A device DTM selected in the Device Catalogue can be added to a  selected Master DTM in the Network view by clicking the Add Device but   ton in the Device Catalogue window     2 2 6 Saving and Opening Projects    Note    A project  containing various DTMs can be saved and opened to and from  hard disk  Saving a project file is accomplished by selecting the File   Save or  File   Save As    menu option  This will display the standard Windows File  selection window  allowing the user to enter a file name     The Project File is saved with the extension   CPR     Saving the data is initiated from CX Profibus  but every DTM must support the  save function as well  The settings of each DTM are added to the Project file  by the DTM itself     A Project file can be opened using the File   Open menu option  This will  open the standard Windows File selection window  after which the Project file  can be selected and opened     When opening a Project file  the network tree view is constructed  However   for performance reasons  the DTMs are not directly instantiated  The advan   tage is that the tree view is constructed fast  but opening a DTM from the tree  view may take longer  depending on the performance of the PC used     A Project File can also be opened from Windows Explor
200. parameters associated with selected I O modules         Master lock    The slave device is parameterized and locked by another Master Unit on the network  The  Parameter request used LED indicator will also be ON     e Remove the slave device from either one of the two Master Units on the network   e Switch off the other Master Unit        Parameter request used    The slave device is not in I O data exchange with the Master Unit and has requested new   parameters    e Check the parameters and the I O configuration for the slave device and make sure they are  correct  Check the Parameter fault  Configuration fault and Master Lock LED indicators         Static diagnostics    The slave device is sending static diagnostics  and is not exchanging I O data  This usually indi    cates a problem at the slave device which prevents it from reading its inputs or setting its out    puts    e Check the slave device and make sure that it is working properly    e Check any loose modules  in case the slave device is a modular device    e Check the wiring of the I O at the slave device  Slaves can often detect short circuits on their  physical I O   Consult the operation manual of the slave device  Check if additional action must be taken to  initiate I O data exchange  e g  reset the device after a malfunction         Station type    This LED indicator only indicates the device type  i e  slave device  and does not indicate a  problem        Watchdog On    This LED indicator only indicates 
201. put Area 2  Out     put Area 1  Output Area 2       Each of the slave I O data mapping areas can be  compressed  by pressing the Compress button   This will result in the DTM filling up all the gaps in  the mapping  by moving I O data from higher  addresses closer to the start address of the map   ping area   e Yes   No    Compress memory area   Do nothing        When pressing the  Compress button in the  Slave Area tab  I O Allo   cation        133    Appendix       Number    Message     IO area  must be empty  Move all  modules into other area    Note  IO area    output area1   output area2  input areat     input area2    Description     Not used    item in the start address combo box in  output input allocation tabs can only be selected  if there are no I O module mapped in that area     e OK Close message box  Move modules  to other I O area first     When occurring    When selecting the    Not  Used    item from the  memory area box        Slave_User_data part of the  PROFIBUS slave parameter set  will be ignored  See slave  no     name     Note  no    slave address     name    slave DTM name    Slave_User_data part of the slave parameter set  will not be used  The additional user parameters  in the slave parameter set are not supported by   the PROFIBUS Master Unit     e OK Close message box    When adding a slave  DTM to the network   which defines additional  user parameters        Auto addressing will reallocate  slave I O mapping  Would you like  to proceed     When
202. r        Properties    Displays the properties of the selected DTM  or the network        User Management       Displays the user management  i e password management  window        Cascade    Cascades all open DTM User Interfaces        Tile Horizontally    Tiles all open DTM User Interfaces horizontally        Tile Vertically    Tiles all open DTM User Interfaces vertically        Close All    Closes all open DTM User Interfaces        Tool Bar    Contents    Opens the Help dialog and lists the Help file contents        Index    Opens the Help dialog and lists the Help Index           About CX Profibus                Opens the About dialog window for CX Profibus     The tool bar provides quick access buttons to the user for frequently used  menu commands  The table below lists the toolbar buttons     Description  Creates a new project     Equivalent menu command  File New       Opens an existing project file     File Open       Saves the displayed project to a file     File Save       Connects the configurator to the selected devices     Device Go Online          Downloads the parameters to the device        Device Download Parameters       21    CX Profibus    Section 2 2    Description Equivalent menu command    Uploads the parameters from the device     Device Upload Parameters       Opens the Device Catalogue     View Device Catalogue       Status Bar    The status bar displays the current user role  i e  the login level    In case the Error Log view has been closed  the
203. r defines how the CS1 CJ1W PRM21 PROFIBUS  Master Unit will behave in case one of its allocated slave devices fails during  I O data exchange  This option can be enabled if the application in which the  Master Unit is used warrants safety precautions to be taken to prevent unex   pected behaviour of the application     If Auto CLEAR has been enabled  the Master Unit will automatically transition  to the CLEAR state and set the allocated slave device outputs to the safe    Configuring the Master    Section 3 4       Auto Addressing    state  Refer to section 3 6 4 Using Auto CLEAR  for a description of how to  use the Auto CLEAR function     Auto Addressing defines whether or not the CS1 CJ1W PRM21 Master DTM  will automatically map the I O data in such a way that no gaps exist in the I O  data  If enabled  the user does not need to handle the exact mapping of I O  data on to the PLC memory areas  Refer to section 3 4 3 Defining and  Changing I O Mapping for more information on I O data mapping     After making the changes  select the Save button in the lower right corner of  the user interface to accept the changes  Next select the Bus Parameter tab to  display the Bus Parameters     3 4 2 Setting the Bus Parameters    Example    A Caution    The Bus Parameter setup tab contains all the settings required to setup the  communication cycles on the network  The settings depend on the selected  baud rate  the number of slaves  the amount of I O data per slave  etc     By default 
204. r of settings  which define additional  behaviour of the CS1 CJ1W PRM21 PROFIBUS Master Unit with respect to a  particular PROFIBUS DP V1 slave device  Although this specific behaviour is  defined in the PROFIBUS DP extensions standard  PROFIBUS DP V1  it  does not necessarily require PROFIBUS DP V1 capabilities from the PROFI   BUS Master Units  The Extension tab is shown below        65    Generic Slave Device DTM CS ection 2 5        o x   Device  BK3120 GSD File  BK3120 GSE  Vendor  BECKHOFF INDUSTRIE ELEKTRONIK Ident Number  OxBECE    Configuration   Parameter   Group Extensions  DPv1            Auto Clea Fail Safe Behaviour      Process Auto Clear    Send zeros in Clear Mode  f Ignore Auto Clear   Send no data in Clear Mode  JL  Configuration Data Convention    r Error on Cyclic Data Exchange  C DP  1 compliant    Continue if slave not responding    EN50170 compliant Abort if slave not responding       Diagnostics update delay  3 bus cycles       OK   Cancel Apply Help         Auto Clear Processing The Auto Clear processing box defines whether or not the PROFIBUS Master  Unit should ignore a failure of this particular slave  when Auto CLEAR has  been enabled in the Master Unit  See Auto CLEAR Box on page 33 in section  2 3 1 Configuration User Interface   When Ignore Auto CLEAR has been  selected  a failure of this particular slave device  i e  the slave device requests  new parameters  or fails to respond  will not activate the Auto CLEAR mode   The Master Unit will ho
205. ration message will contain stan   dard PROFIBUS DP Data type definitions as well as ven   dor specific data types and the slave device will perform  the check on this assumption              The Fail Safe Behaviour box defines whether or not the PROFIBUS Master  Unit will in CLEAR mode send an empty output data message to the slave  device or a data message containing zeros  Depending on the PROFIBUS DP  slave device  an empty data message  may be required  if the slave device  performs user specific functions in CLEAR mode  and during which the out   puts can not be set to zero     If the selected setting is not supported by the slave device  a parameter error  will be returned by the device     Control Description  Send zeros in Clear When in CLEAR mode  the PROFIBUS Master Unit will  mode send a full output data message to the slave device  but  the message will contain all zeros   Send no data in Clear When in CLEAR mode  the PROFIBUS Master Unit will  mode send an empty output data message  i e  no data bytes   only the message header  to the slave device              The Error on Cyclic Data Exchange settings box  defines the behaviour of the  PROFIBUS Master Units on the PROFIBUS network with respect to this par   ticular slave device  in case it fails to respond during I O data exchange   Depending on the setting  the Master Unit will either continue sending I O  data exchange messages to the slave device  or abort I O data exchange   and continue with requesting the
206. rational mode to CLEAR  i e  set all outputs to a safe  state   when switching the PLC CPU to PROGRAM mode     e Set the Unit s operational mode to OPERATE  i e  start I O data  exchange with the slave devices   when switching the PLC CPU to RUN    MONITOR mode     1  The advantage of this setting is that the user does not have program the  starting of the network  The disadvantage is that the moment at which the  network is started is out of direct control of the PLC user program  I O data  exchange is started  while the program may still be initializing its memory   Depending on the application this may have unexpected effects     2  To avoid potential problems at startup  it is recommended to set the net   work operational mode to    keep current mode    in case the PLC mode in  case the PLC mode changes to RUN   MONITOR and to set the operation   al mode to CLEAR in case the PLC mode changes to PROGRAM  This re   quires the PLC user program to switch the network to OPERATE  after  startup  Refer to section 3 6 2 Changing PROFIBUS Mode of the Master  Unit for a programming example     3  Aside effect of the default settings can be that the network is started right  after downloading the parameters to the CS1 CJ1W PRM21 PROFIBUS  Master Unit  After downloading the parameters  the CS1 CJ1W PRM21  Master DTM will restart the Unit and switch the PLC mode back from PRO   GRAM mode to the mode it had before downloading  This can be RUN    MONITOR mode     The Auto CLEAR behaviou
207. rea    e I O modules are mapped in ascending order according to slave device  address    e I O modules per slave device  are mapped in the order in which they were  selected  when setting up the slave device     Furthermore  Input area 1 is by default mapped to ClO 3300  whereas Output  area 1 is by default mapped to CIO 3200     I O Communication Characteristics Section 3 5       Example    Auto Addressing    Note    The default mapping algorithm is illustrated in the figure below  with the follow   ing configuration     e Slave device 1  One input output module  one output modules   e Slave device 2  One input module    e Slave device 3  One output module    e Slave device 4  Two input modules                                                                                                                 PLC CPU Unit PROFIBUS DP Master Unit Slave 1  Module 1  Slave 1  Module 2  Slave 3  Module 1  Output area       m Output area        CIO 3200  Output area 1    Output area 1  CIO 3400  Output area 2 Output area 2  Input area Input area  CIO 3300 Slave 1  Module 1  Slave 2  Module 1  Input areal   Input area 1 Slave 4  Module 1  Slave 4  Module 2  CIO 3500  Input area 2 Input area 2                                                                   1  The end address of each Input Output area in the PLC memory  depends  on the size of the allocated I O data     2  If more than 100 words of input or output have been configured for the  slave  overlap of memory areas will occur 
208. rest for efficient and convenient opera   tion of the product     1  2  3   Indicates various lists such as procedures  checklists etc     iii    Trademarks and Copyrights    PROFIBUS  PROFIBUS FMS  PROFIBUS DP  PROFIBUS DP V1  and PROFIBUS PA are trademarks  of PROFIBUS International    Microsoft  Windows  Windows NT  Windows 2000  Windows XP  Windows Explorer and ActiveX are  trademarks of Microsoft Corporation     Sycon and CIF are trademarks of Hilscher GmbH     Other product names and company names in this manual are trademarks or registered trademarks of  their respective companies     The copyright of the PROFIBUS Master Units belongs to OMRON Corporation        OMRON  2006    All rights reserved  No part of this publication may be reproduced  stored in a retrieval system  or transmitted  in any form  or  by any means  mechanical  electronic  photocopying  recording  or otherwise  without the prior written permission of  OMRON     No patent liability is assumed with respect to the use of the information contained herein  Moreover  because OMRON is con   stantly striving to improve its high quality products  the information contained in this manual is subject to change without  notice  Every precaution has been taken in the preparation of this manual  Nevertheless  OMRON assumes no responsibility  for errors or omissions  Neither is any liability assumed for damages resulting from the use of the information contained in  this publication     TABLE OF CONTENTS    About t
209. rn the PLC to  mode  mode     After download with PLC previously in RUN or  MONITOR the PLC can be returned to RUN or  MONITOR mode   e Yes Change state    e No PLC remains in PROGRAM mode    e Cancel PLC remains in PROGRAM mode     After completing the  download        PLC Memory  area overlapping   and or  exceeding memory range   Save anyway     One or more of the PLC Memory mappings is  incorrect  The I O data  a part of the I O data or  the PROFIBUS DP V1 Status Monitoring table is  mapped beyond an existing memory area  or two  or more mappings are overlapping in memory    e Yes Save settings    e No Do not save settings    e Cancel Do not save settings     Closing the Configura   tion User Interface with  invalid configuration or  saving invalid settings       Settings have been changed   Would you like to save     One or more settings have been changed  but  not yet saved    e Yes Save data and close DTM    e No Do not save data and close DTM    e Cancel Do not close the DTM     Closing the Configura   tion User Interface with   out saving the changes        Settings have been changed   Would you like to leave without  saving     Closing the GUI without saving the configuration   e Yes Do not save data and close DTM     e No Do not save data and do not close  DTM     Closing the Configura   tion User Interface with   out saving the changes           Compressing will re allocate slave  configuration in  memory area    Continue     Note  Memory Area    Input  Area 1  In
210. rofibus  Configurator    CX Profibus  Configurator                                                                                                                                                                                     CS Cu series een el a PG C200H series  PROFIBUS Host LINK usor PROFIBUS DP  Master Unit o3 Master Unit  o o a  A Configuration Port on  uE RL  P  eroro p   l     1  zH Master Unit  PROFIBUS Network PROFIBUS Network                                           CX Profibus Configurator    Section 1 3       1 3 2 Specifications    Functional Specifications    Item Specification    Model number    WS02 9094G       Hardware platform    Personal computer  IBM PC AT or compatible  Processor  Pentium 500 MHz or higher  Memory  256 Mbytes   Hard disk  A minimum of 256 Mbytes  CD ROM drive   Graphics resolution  800 x 600 pixels minimum  Serial port  RS 232C       Operating System    e MS Windows NT4 0  SP6   e MS Windows 2000  SP2   e MS Windows XP   Note Internet Explorer 5 01 is also required        Connection to CS1 CJ1W PRM21    Peripheral or RS 232C port of PC with PLC CPU  Serial communica   tions mode  Peripheral bus  Host Link  Toolbus  supported by CX   Server    Communication cable  Cable CS1W CN226 to connect to the periph   eral port on the CPU  Not included in package         Operating environment    Connection to C200HW PRM21    e RS 232C port of PC with Configuration port on the Unit        General Project functions    File handling  CX Profibus 
211. ror events on  the PROFIBUS network  which were detected by the Master Unit     Range of Value  0 to 65535       Transmission Rejected Count    The Transmissions Rejected Count displays the number of rejected messages   A possible reason for this is  that the Master itself can not receive the token any   more     Range of Value  0 to 65535       Station status    Any Slave Indicator    The LED indicators in the Station status field display the status of each slave  station on the network per address  The colour of the LED indicator indicates the  specific status of the slave device     e Grey  The slave device is not configured for this Master Unit   e Green  This slave device is exchanging I O data with the Master Unit     e Yellow  New Diagnostic is available from this slave device  Open the Slave  DTM to determine the actual Diagnostics data  Opening this DTM  will clear the LED indicator  and turn to another colour until the  next Diagnostics message is received from the specified slave  device    The slave device was configured  but not found on the network     The slave station has returned a Set_Prm or Chk_Cfg error and is  not in data exchange with the Master unit     e Blue   e Red        Station Error    Station Address    The Station address field displays the address of the first slave device  i e  with  the lowest address  which reported an error  The error is specified in the Error  Event field        Error Event    The Error Event field displays the error which
212. roubleshooting are extensively dis   cussed in SECTION 3 Operation     Troubleshooting the Network           ss   s    lt i                                          s                                             S SCS ction 4 2       4 2 Troubleshooting the Network    4 2 1 Troubleshooting Parameter Download    Errors in Slave Parameter  Sets    Errors when Establishing  Communication    Errors During Download    Recovery After Failing  Download    The PROFIBUS Master DTM provides clear error messages if downloading of  the parameters to the PROFIBUS Master Unit fails  Failure can be due to  either  e Errors or inconsistencies in the slave parameter sets  which are checked  prior to download   e The Master DTM being unable to establish communication with the CS1   CJ1W PRM21 PROFIBUS Master Unit   e A communication interruption of the process during download     The error messages displayed will provide a clear indication of the problem     A download initiated by the user  starts with a check on the slave parameter  sets  The Master DTM will check    e The total number of slave devices assigned  which must be at least one  slave device     e The total number of I O modules per slave  which must be at least one I O  module per slave    e The maximum size of the I O data size  which must not exceed 7168  words    e The maximum number of I O modules  which must not exceed 4000    e Any existing overlap in the I O Areas configured    e Any existing overlap in the allocated PLC me
213. ry configuration settings  and saving them  these will be  transferred to the Master DTM    e The monitoring DTM will provide a diagnostics interface to the user   allowing him to check the Slave   s status  This DTM obtains the necessary  information from the PROFIBUS Master Unit   s monitoring DTM     11    CX Profibus Configurator        ss   s   s    lt                 s                          S Section 1 3       Note The Generic Slave DTM provides parameter settings related to PROFIBUS  DP V1  However  it does not support PROFIBUS DP V1 communication     Downloading the After setting up the configuration  it must be downloaded to the PROFIBUS  Configuration Master Unit  The type of serial connection to use for downloading  depends  on the Unit     12    e CS1 CJ1W PRM21  Connection to the Unit is achieved through the serial  port of the PLC CPU  using CX Server  CX Server also allows routing the  download through multiple systems  if supported by these systems  The  CS1 CJ1W PRM21 does not support message routing    e C200HW PRM21  Connection to the C200HW PRM21 is achieved  through a serial RS 232c Connection between one of the PC   s Serial  COM Ports and the dedicated configuration connector at the front of the  Unit  For details  refer to the C200HW PRM21 Manual  W349 E2 2  The  figure below shows the connection methods  for both types     Serial connection to CS CJ series Serial connection to C200H series  PROFIBUS Master Unit PROFIBUS DP Master Unit          CX P
214. s this     CS1 CJIW PRM21 PROFIBUS Master DTM    Section 2 3       Baud rate    Z  Caution Changing the calculated Bus Parameters manually is not recommended  and  should only be performed if this is really necessary  Changing the Bus Param   eters to an invalid combination  may result in Unit malfunctioning and unex     pected behaviour     Note    When making changes to Bus Parameters  selecting the Optimize buttons     allows toggling between the optimized values and the changed values   Selecting an other baud rate after changing parameters  will reset the Bus    Parameters to default values for the new baud rate     The table below lists the parameters  shown in the Bus Parameter tab     Description    Defines the transmission rate on the PROFIBUS DP Network  The following baud  rate values are defined by the PROFIBUS DP standard     e 9 6 kBits s  19 2 kBits s  45 45 kBits s  93 75 kBits s  187 5 kBits s  500 kBits s  1500 kBits s  default value   3000 kBits s  6000 kBits s  12000 kBits s    Editable  by User       The Optimize setting defines whether parameters can be changed by the user   e By Standard   Forces the user to use the default  optimized  settings   e By User   Makes selected fields editable    Note 1  If the By User option is selected and changes have been made  it is  still possible to switch between Optimize settings  without the changes  being lost    2  If the By User option is selected and the baud rate is changed  the pa   rameters will be optimized
215. sages themselves as well as the sequence of messages may hold  additional clues in case of problems     The format used in the FDT Monitoring view is  Time   lt Time gt  Date   lt Date gt     lt Information Type gt   lt message gt     The message may include the name of the DTM involved in the communica   tion     The figure below shows an example of an FDT Monitoring message    sequence  This example sequence is generated when opening a CJ1W   PRM21 PROFIBUS Master Unit DTM     Error Log FDT Monitor      Time  23 09 Date  04 Nov 03 FDT Information   a  CJ1W PRM21 PROFIBUS Master  Call  DtmActiveControl Init function    Time  23 09 Date  04 Nov 03 FDT Information   s  CJ1 W PRM21 PROFIBUS Master  IDtmE vents  nFunctionChanged call received   Time  23 09 Date  04 Nov 03 FDT Information   s   CJ1 W PRM21 PROFIBUS Master  Call  IDtm GetFunctions function    Time  23 09 Date  04 Nov 03 Information   s   CJ1 W PRM21 PROFIBUS Master      DTM function  ID   1  execution finished     Time  23 09 Date  04 Nov 03 Information   aj DTM Proxy for ConfD TMCOM ConfD TMCOM     CJ1 W PRM21 PROFIBUS Master  disposed        User  Administrator A    By right clicking the mouse cursor in the FDT Monitoring view  a context  menu is displayed  This context menu provides the options listed below     FDT Monitoring view Context Menu    Menu item    Clear all entries Clears the entire FDT Monitoring view     Description Equivalent menu command       Copy to clipboard Copies the entire contents of the 
216. signed to groups 1  2 and 4        2   CJ1W PRT21   Configuration                After making the group assignment  press the OK button to save the changes  and close the DTM Configuration User Interface     86    Configuring the Master sss Section 3 4       3 4 Configuring the Master    Opening the Master DTM After configuring all the slave DTMs  the CS1 CJ1W PRM21 Master DTM  Configuration Interface must be configured  In order to open the Master DTM Configuration Interface  do either one of the following   e Select the CS1 CJ1W PRM21 Master DTM in the Network view and dou   ble click the left mouse button   e Select the CS1 CJ1W PRM21 Master DTM in the Network view  and  right click the mouse  From the context menu  select Configuration     The DTM Configuration User Interface is shown below                  1   C11w PRM21 PROFIBUS DP v1 Master Configuration  oix  Device Setup   Master Setup   Bus Parameters   Slave Area   Advanced   OK    omRon Cancel    m Communication  e    ra    m Settings    Station Address     m  Unit Number  p      Device Information    OMRON Corporation    Description     Firmware Version  l    Ident  Number                 Master Address In the first tab  the device address and the unit number must be set  The  device address can be set in the range from 0 to 125     Unit Number The setting of the unit number is required to setup communication with the  Unit through CX Server  The setting in the user interface must match the set   ting made with t
217. supports overall handling of project files as  well as network data    New  Start a new project    Open  Open an existing project file    Save  As   Save a project file    Export  Export project data to HTML    Properties Edit project property information        User management  Functionality of CX Profibus can be limited as  defined by several password protected access levels   e Administrator   Planning engineer   Maintenance   Operator   Observer       Network setup functions    CX Profibus provides network tree view  from which hierarchy between  Master and slave devices can clearly be distinguished        The following network functions are available    e Network DTMs  i e  devices  can be added or deleted  using drag and  drop from the Device Catalogue   Network DTMs can be copied and moved from one location to  another in the network view   DTM names can be edited by the user   Any change to the parameters of a DTM is clearly marked in the tree  view  until the project is downloaded to the Master Unit        Device Catalogue functions    The Device Catalogue maintains the installed device DTMs  After instal    lation of a new DTM  the user must refresh the database  The Device   Catalogue provides the following functions    e Update Device Catalogue    e Add device DTMs to the network directly    e Install a GSD file  This function allows copying of GSD files to a spe   cific directory  after which they are available for the Generic Slave  DTM        Support functions 
218. t menu     2  Select Download Parameters from the menu  to initiate a download  A  communication channel through the CIF driver will be opened     Alternatively  the following can be done   Select the DTM in the Network view and press the Download button in the  toolbar to start the download process     In case the driver assignment has not been done prior to attempting the  download  an error message will be displayed     For monitoring  an online connection with the Unit must be made first  To  achieve this perform the following sequence     1  To go on line  perform one of the following actions   e Select the DTM in the Network view   e Select the Device   Go Online option from the main menu  or the DTM  context menu  or  e Select the A button from the Tool Bar     2  A communication channel will be opened through the CIF Driver  The  name of the DTM in the Network view  will turn to Italic font  to indicate that  the Unit is on line     3  From the context menu  select the Diagnosis option  The DTM   s Diagnos   tics User Interface will be displayed     2 5 Generic Slave Device DTM    Most of the current PROFIBUS DP slave devices are supplied with a GSD file  in order to allow a configurator to setup a configuration for that particular slave  device  OMRON   s Generic Slave Device DTM is provided to allow integration  of the GSD file based configuration options into an FDT Container application   like CX Profibus     The GSD files are stored in a separate sub directory un
219. t sup   ported by the Master Unit and will  be disabled     Publisher functionality set by the Slave DTM is  not supported and will be reset     e OK  Close message box     Downloading settings  and bit is set in Slave  Parameter Set        Isochronous mode is not sup   ported by the Master Unit and will  be disabled     Isochronous mode set by the Slave DTM is not  supported and will be reset     e OK  Close message box     Downloading settings  and bit is set in Slave  Parameter Set        134       Acyclic Connection   Abort Status  Area and Acyclic Slave Timeout   settings are not supported by the  Master Unit and will be disabled        The connected Master Unit has version V2 00   The new features for version V3 00  and up  are  not supported by the Master Unit        Downloading settings to  Master Unit V2 00 with  Master DTM V3 00  or  up         Appendix       A 2 Error Messages   Configuration    The table below lists the Error messages which can be displayed by the PROFIBUS Master Unit DTM in case  there are configuration errors  Usually  these are detected either when entering  or up on download  The table  suggests corrections to the problems in the right most column     Number    Correction       Message    Description                                              00 Total I O area size exceeds maxi    The I O configuration exceeds the Change configuration to reduce the  mum maximum limit of 7168  or 7k  amount of I O data to 7168 words   words   maximum or less 
220. tatus to all  its assigned PROFIBUS DP slaves  using a broadcast message      The PROFIBUS Master Unit will always be in one of these four modes  Mode  transitions from one mode to another will be performed via intermediate  modes  For example  a mode transition from OFFLINE to OPERATE  will be  performed as OFFLINE STOP    CLEAR    OPERATE     Auto CLEAR If an error occurs during the data exchange phase of the master  the    Auto   CLEAR    function determines the subsequent actions  If this function has been  disabled  the master remains in the OPERATE mode  If the function has been  enabled  the master automatically changes the network to the CLEAR mode   in which the outputs of the assigned PROFIBUS DP slaves are switched to  zero  i e  the    fail safe    state  The master continues to read the inputs of the  slaves     Fail safe State    Setting up a PROFIBUS DP Network Section 1 2       1 2 Setting up a PROFIBUS DP Network  1 2 1 Configuring the PROFIBUS Master    Configuration Technology    In order to operate a PROFIBUS network  each master in the network needs  to be configured  This process of configuration involves  e setting up the network topology  i e  assigning the slave devices with  which the master will be exchanging data   e defining the parameterization data  which the master will send to each of  the slave devices  before process data exchange can commence    e defining the configuration data  i e  defining the process data  which will  be exchanged     
221. technology  The GSD file does not provide this  means     CX Profibus Configurator O Section 1 3       1 3 CX Profibus Configurator  1 3 1 CX Profibus Features    CX Profibus The PROFIBUS Master Unit requires a configuration before it can exchange     O data with the slave devices  For this purpose OMRON provides the CX   Profibus Configuration program  which runs under Microsoft Windows    NT  4 0  Windows    2000 or Windows    XP    Together with CX Profibus  OMRON provides five DTM COM Objects   e A DTM to configure the CS1 CJ1W PRM21 PROFIBUS DP V1 Master  e A DTM to configure the CS1 CJ1W PRM21 PROFIBUS DP Master  e A DTM to configure the C200HW PRM21 PROFIBUS DP Master  e A DTM to configure the SmartSlice GRT1 series GRT1 PRT   e A DTM to allow the handling of classic GSD files in CX Profibus  The following provides a quick overview of the functions     CX Profibus FDT _ CX Profibus provides an FDT environment in which DTMs can be executed   Container Application The main function of CX Profibus is to facilitate the DTMs and the data  exchange between them  It provides     e Network setup functions  A tree view shows the relations between the  DTMs  i e  the relation between the Master and slave devices    e Device Catalogue functions  A Device Catalogue containing the installed  DTMs is maintained  to which the user can add new DTMs or delete them   Device DTMs can be added to the network from this Catalogue    e Project maintenance functions  CX Profibus provides the 
222. ter DTM    Example    Indirect Mode Changes    The PROFIBUS standard defines four different network modes  in which a  Master Unit can operate  The modes are     e OFFLINE  The PROFIBUS Master Unit does not access the network  nor does it  respond to messages    e STOP  The PROFIBUS Master Unit is on line  but does not communicate with its  slave devices  It does communicate with other Master Units  in that it  passes the token message     e CLEAR  The PROFIBUS Master Unit is on line and communicates with its slave  devices  It will parameterize all allocated slave devices  but only read their  input data  The Master Unit does not send valid output data to the slave  devices  Instead it will send empty output data messages or messages  containing zeros       OPERATE  The PROFIBUS Master Unit is on line and communicates with its slave  devices  It will parameterize all allocated slave devices  and exchange all  I O data for which it has been configured     The OPERATE mode is the mode used for normal network operation  The  CLEAR mode is the mode used for situations which require a safety state to  fall back to  see section 3 6 4 Using Auto CLEAR      In order to change the Unit   s operational mode  open the CS1 CJ1W PRM21  Master DTM Diagnosis User Interface  The figure below shows this Online  Operations tab  Press the desired mode button in the upper left corner of the  window        aixi  Monitor Online Operations   Close    m PROFIBUS Communication Global Control Message
223. ter row with the left mouse button  Depending on the  parameter type  either a drop down lists will become available for selection or  a value can be entered     In the figure above  the parameter setting allowing the user to define the tar   get location of the output data in the PLC memory has been selected     Readable captions and or convenient selection items are not always provided  with the parameters  Depending on the slave device and the GSD file imple   mentation  setting the parameter values may require the help of the user doc   umentation for that slave     3 3 3 Selecting the Group Assignment    1 2 3       The group assignment is sent to the slave devices as part of the parameter  message  The group assignment is used as an address within the Global   Control command message  see section 3 6 3 Transmitting Global Control  Commands   to address a specific group of slaves  or all slaves  To set a slave  device   s group address  perform the following steps     1  Open the Configuration User Interface of the Generic Slave DTM the spe   cific slave device   2  Select the Group tab     3  Select the checkbox next to the group numbers for all the groups to which  the slave device will belong     4  Select the Apply button at the bottom of the User Interface     85    Configuring the Slave Devices o     Section33    Example Assigning slave devices to groups is application dependent  The figure below  shows the Group selection tab for the CJ1W PRT21  which has been  as
224. ter the start address in the  PLC memory of the mapped data block     Length The length value is a fixed number  The total number of  words is 16                 1  Ifthe selected PLC memory area  on to which the data must be mapped is  not supported by the PLC CPU  a warning message will be displayed upon  downloading the configuration    2  Ifan invalid setting is made the Length value will change its colour to red   indicating an invalid setting  In addition  a warning message will be dis   played  upon saving the changes  Invalid settings are for example   e The start address and length definitions of the data block will cause it  to exceed the area in the PLC       The mapping overlaps with one or more of the I O Areas  Output and   or Input  mappings     The 8 word Acyclic Connection bit flags are shown below     15 14131211109 8 765 43 2 1 0  Word n 15 14 13  12  11  10  9  8 7  6 5 4 3 2 41   0   Slave station 00   15    Word n 1   31   30   29   28   27   26   25   24   23   22   21   20   19   18   17   16   Slave station 16   31    Word n 2  47   46   45   44   43   42   41   40   39   38   37   36   35   34   33   32   Slave station 32   47                Word n 3   63   62   61   60   59   58   57   56   55   54   53   52   51   50   49   48   Slave station 48   63  Word n 4   79   78   77   76   75   74   73   72   71   70   69   68   67   66   65   64   Slave station 64   79    Word n 5   95   94   93   92   91   90   89   88   87   86   85   84   83   82   81 
225. that the Watchdog has been enabled at the slave device and  does not indicate a problem        Freeze mode    This LED indicator only indicates the slave device has received a Global Control Freeze com   mand and does not indicate a problem        Sync mode    This LED indicator only indicates the slave device has received a Global Control Sync com   mand and does not indicate a problem        Slave deactivated    This LED indicator indicates the slave device has been disabled in the Master Unit and does not  indicate a problem        Extended diagnostics  overflow    126       The slave device has more diagnostics to report than it can hold in its buffer  This is usually an  indication for problems   e Check the slave device   s extended diagnostics information  Open the associated Slave DTM  to check on the contents of the extended diagnostics  if this has been returned   Check the slave device and make sure that it is working properly   Check any loose modules  in case the slave device is a modular device   Check the wiring of the I O at the slave device  Slaves can often detect short circuits on their  physical I O   Consult the operation manual of the slave device  Check if additional action must be taken to  initiate I O data exchange  e g  reset the device after a malfunction         Troubleshooting the Network    Section 4 2       4 2 3 Troubleshooting I O Communication    This section deals with troubleshooting the I O communication on the network  from a behaviour p
226. the current mode if the PLC goes to PRO   GRAM modem  e g  stay in OPERATE mode      The Unit goes to the CLEAR mode whenever the PLC  goes to the PROGRAM mode        Go to CLEAR Mode   default setting        Auto CLEAR defines the Unit   s behaviour in case an error occurs in one of the  allocated slave devices  which causes it to stop data exchange with the Mas   ter Unit  If Auto CLEAR is enabled  the Unit will automatically transition to the  CLEAR state and force all its allocated slave devices to the    safe    state  i e  all  outputs are set to 0  using the Global Control CLEAR command     33    CS1 CJIW PRM21 PROFIBUS Master DTM    Section 2 3    Control Description    Auto CLEAR Mode ON    Selected Unit transitions to the CLEAR mode in the event  of a network error  e g  because one or more configured  slaves are not in the Data Exchange mode    Auto CLEAR Mode OFF   Selected Unit does not transition to CLEAR mode  but   default setting  attempts to re parameterize the slave device           Support Box    Bus Parameters Tab       34       The Auto Addressing in the Support Box defines the I O Mapping process  when adding removing I O modules or when editing an existing I O Mapping   Refer to section 3 5 2 Mapping I O Data for more details on I O mapping     Control Description    Auto Addressing enabled   I O data mapping will be done by the Master DTM by allo   cating the I O data in ascending order of slave device  address and selected I O modules  No memory allo
227. time results in an  Unfreeze command at the slaves     Specific groups to send the Global Control command to can be defined  by  selecting the appropriate checkbox  Selecting the All Slaves checkbox can    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       Transmit Global Control  Command    Z  Caution    will disable the individual check boxes  and result in a Global Control com   mand to all slave devices     In order to transmit the Global Control  press the Transmit button  The com   mand will be transmitted only once  Both the Global Control command con   tents  group select and the transmit command are transferred to the Unit  through its ClO words  refer to the CS1 CJ1W PRM21 Operation Manual   W409 E2 L                   When transmitting a Global Control command  it may interfere with attempts  from the PLC Program to write to the same software switches  Care should be  taken to avoid these situations     2 3 3 Connecting to the CS1 CJ1W PRM21    Configuring  Communication    1 2 3       CX Server    Configuring CX Server    1 2 3       The PROFIBUS Master DTM uses CX Server to connect to the Unit for both  downloading a configuration as well as monitoring the Master Unit  To setup  the communication to the Unit  perform the following procedure     1  Open the Master DTM Configuration Interface  Device Setup tab  see sec   tion 2 3 1 Configuration User Interface      2  Select the Unit Number  It must match the unit number set on the PROFI   BUS Master Unit  throug
228. to the Master DTM     Generic Slave Device DTM    Section 2 5       Module Configuration    Note    Note    Note    In case a changed address is invalid  for example if there is already another  slave device with the same new address  the Master DTM will set the number  back to its old value     The Watchdog value is the value used by the slave device to monitor commu   nication from the Master Unit  If no messages are sent to the slave by its Mas   ter within the Watchdog timeout time  the slave device will stop data  exchange and switch back to the fail safe mode     In the current version of CX Profibus  the Watchdog setting made in the  Generic Slave DTM is overruled by the Watchdog setting in the Master DTM   see also section 3 4 2 Setting the Bus Parameters      The I O module configuration defines the I O Data which the slave will be  exchanging with the Master Unit  when it is in data exchange mode  The  upper window in the Configuration tab contains all possible modules  which  are in the GSD file  The lower window holds all selected I O modules     The user has to select the modules  which are associated with the physical  configuration of the slave device  Selecting  i e  copying the module from the  upper window of the lower window can be done in several ways    e Double click the left mouse button on the selected module in the upper  window    e Select the module in the upper window and click the Insert button or  Append button  Insert will insert the module abov
229. token   is assigned to each master within a precisely defined time frame  The token  message  a special message for passing access rights from one master to the  next master  must be passed around the logical token ring   once to each  master   within a specified target rotation time  Each master executes this pro   cedure automatically     The polling or master slave procedure permits the master  currently in pos   session of the token  to access its assigned slaves  The figure below shows a  possible configuration The configuration shows three active devices  masters   and six passive devices  slaves      Token Passing              A  BS epee es  Active stations  Master devices  Polling  v PROFIBUS    A    Passive stations  Slave devices                      The three masters form a logical token ring  When an active device receives  the token message  it can perform its master role for a certain period of time   During this time it can communicate with all assigned slave devices in a mas   ter slave communication relationship  and a DPM2 master can take the initia   tive to communicate with DPM1 master devices in a master master  communication relationship     In addition to logical peer to peer data transmission  PROFIBUS DP provides  multi peer communication  broadcast and multicast      In the case of broadcast communication a master device sends an unac   knowledged message to all other devices  masters and slaves      In the case of multicast communication a master de
230. tor User Interface pro   vides a means to  e Monitor the CS1 CJ1W PRM21 Master Unit status   e Monitor an overview of the status of all allocated slave devices   e Monitor standard slave diagnostics   e Monitor the Unit   s Error Log  The Error Log is discussed in section 3 7 3 Using the Error Log     The information is obtained directly from the Master Unit  using FINS com   mands  The Master DTM reads the Units CIO words from the PLC memory   as well as the standard slave device diagnostics bytes as received by the  Master Unit     To open the CS1 CJ1W PRM21 Master DTM Diagnosis   Monitor User Inter   face  perform the following steps     1  Make sure the Master DTM is online with the Master Unit  To go on line   select the DTM in the Network view  and perform one of the following ac   tions    e Select the Device   Go Online option from the main menu  or the DTM  context menu  or    e Select the A button from the Tool Bar     2  Acommunication channel will be opened through CX Server  The name of  the DTM in the Network view  will turn to Italic font  to indicate that the Unit  is on line     Monitoring the Network    Section 3 7       Using Auto Update or  Manual Refresh    Reading the Master Unit   s  Status    Master Status 1    3  From the context menu  select the Diagnosis option  The DTM   s Diagnos   tics User Interface will be displayed     4  Select the Monitor tab  for status monitoring   The information displayed in the CS1 CJ1W PRM21 Master DTM Diagnosis    Mon
231. transmitted on a Most Signifi   cant Byte First basis     Supported     Single 16 bit integers are transferred to  memory words in PLC memory        Single 32 bit Integer  signed unsigned    Supported     Data is transmitted on a Most Signifi   cant Byte First basis     Supported     Data is stored with the Least Significant   Word at the lowest address        Floating point    Supported     Data is transmitted on a Most Signifi   cant Byte First basis     Supported     Data is stored with the Least Significant   Word at the lowest address        Visible string    Supported   Length of string is fixed by I O configura     tion  Data is transmitted on a left to right  basis  i e  first character is transmitted  first      Supported     First characters are stored at the lowest  address  String is padded with a zero  byte or a zero word  depending on the  number of characters        Byte string    Supported    Length of string is fixed by I O configura   tion  Data is transmitted on a left to right  basis  i e  first character is transmitted  first      Supported     First bytes are stored at the lowest  address  String is padded with a zero  byte or a zero word  depending on the  number of characters        Date   Clock time    Supported    Date Time format contains absolute time  with respect to start of century  Date   Time is coded in individual bytes     Not Supported     Date Time format is transferred to PLC  memory as string of words        Time of day    Supported     
232. ts from a Programming Device     e Transferring I O memory files from a Memory Card or EM file memory to  the CPU Unit     e Transferring I O memory from a host computer or from another PC ona  network     Execute online edits only after confirming that no adverse effects will be  caused by extending the cycle time  Otherwise  the input signals may not be  readable     4 Operating Environment Precautions     N Caution Do not operate the Unit in the following places     Z  Caution    e Locations subject to direct sunlight     e Locations subject to temperatures or humidities outside the range speci   fied in the specifications     e Locations subject to condensation as the result of severe changes in tem   perature     e Locations subject to corrosive or flammable gases    e Locations subject to dust  especially iron dust  or salt    e Locations subject to exposure to water  oil  or chemicals   e Locations subject to shock or vibration     Provide proper shielding when installing in the following locations   e Locations subject to static electricity or other sources of noise   e Locations subject to strong electromagnetic fields   e Locations subject to possible exposure to radiation   e Locations near to power supply lines     The operating environment of the PLC system can have a large effect on the  longevity and reliability of the system  Unsuitable operating environments can  lead to malfunction  failure and other unforeseeable problems with the PLC  system  Ensure that t
233. ual  W349 E2 L                   Address Table Tab The Address Table tab contains an overall module list  showing all input and  output data per slave  along with the Module names  sizes  data types and  start addresses  This data has been obtained by the Master DTM by each of  the allocated slave DTMs  If no slave devices have been allocated  or config   ured  the list will be empty     Memory Layout The Memory Layout box list contains the following information     Column Description     Addr  Station address on the network  obtained from the slave DTM   Device Name_  Device name  obtained from DTM   Module Name _   System generated name   IType Defines the Type of the Input       B  Input Byte type  e IW  Input Word type    lAddr  Word    Start Address of the Input data of the Module  relative to the start  of the internal memory of the Unit  containing the Input Data block   lAddr is expressed in Words    OType Defines the Type of the Output    e QB  Output Byte type   e QW  Output Word type   OAddr  Word    Start Address of the Output data of the Module  relative to the start  of the internal memory of the Unit  containing the Output Data  block  OAddr is expressed in Words                             Note 1  Modules consisting of one single byte will occupy a full word address     2  A total of up to 512 Input bytes and 512 Output bytes can be mapped on  to the Unit   s internal memory  Therefore  the maximum permissible ad   dress value is 255  Words   However  the C200
234. ug alarm      Manufacturer specific alarm  I    Process alarm  I Status alarm          T Diagnostic alarm I Update alarm      Extra Alarm SAP       Alarm Acknowledge via SAP 51  C Alarm Acknowledge via SAP 50             OK   Cancel Apply Help         Generic SlaveDeviceDTM      lt             OO CS ection 2 5       Enable DPV1 This checkbox enables or disables the DPV1 functions for the specific slave  device  The Master DTM will clear this setting prior to download     Max  Channel Data Length This parameter defines the maximum size in bytes of the acyclic message  exchanged with the PROFIBUS DP V1 Master Unit  The size ranges from 4  bytes to 244 bytes  The actual upper limit of the number is defined by the  buffer capacity of the slave device     Max  Alarm PDU Length This parameter defines the maximum size of an Alarm message sent from the  slave device to the PROFIBUS DP V1 Master Unit  The Master Unit uses this  number to reserve buffers to handle the alarms  The maximum alarm mes   sage size ranges from 4 bytes to 63 bytes    Alarms The Alarms box defines the types of alarms the slave device will report  as  well as the alarm handling capacity of the master device  The settings in this  box are conveyed to the slave device through the Set_Prm message sent by  the PROFIBUS DP V1 Master Unit     Control Description    Alarm mode The Alarm mode indicates to the slave device the amount  of alarms the PROFIBUS DP V1 Master Unit can process  simultaneously  The following st
235. urrent address and its PROFIBUS Ident Number   The PROFIBUS Ident Number can be found in the Generic Slave DTM or  through the device   s documentation  By default the device   s current ad   dress will be 126  If necessary  change this to the actual current address     2  Enter the new device address in the New Address field     3  Optionally  select the Lock checkbox  if the address change must be made  permanent     4  Press the Set button to invoke the PROFIBUS DP Set Slave Address ser   vice  The Status field will display the status of this service      N WARNING Selecting the Lock option makes any future changes of the address impossi   ble  even after power down power up of the slave device     Note After successful completion of the address change  the device DTM address  in the Network view has to be changed as well     2 3 2 Diagnostics User Interface    Diagnostics User Interface The PROFIBUS Master DTM provides a second user interface  to display the  Diagnostics information available in the PROFIBUS Master Unit  This infor   mation concerns    e Unit and PROFIBUS DP Interface status flags   e Slave status flags and common slave diagnostics   e The Units Error Log     Furthermore  the Diagnostics User Interface allows changing the Masters  PROFIBUS operational mode and the transmission of Global Control mes   sages     In order to access the Diagnostics User Interface  the DTM has to be on line   i e  a communication channel between the DTM and the PROFIBUS Master
236. us conditions  The LED  indicator colours are listed below     Indicator Slave Status  Colour    Associated device does not exchange Diagnostics with this Master  Unit  i e    e Slave not allocated to this Master Unit  or   e Device is this Master Unit  or   e Device is another master device     Red The slave device is not communicating with the Master Unit  It may  be disconnected  or the Master is in OFFLINE or STOP mode     Orange The slave device is communicating with the PROFIBUS Master  Unit  but it is not in Data Exchange  due to incorrect parameter set   tings  See the slave diagnostics for more information     Yellow The slave device is in data exchange with the PROFIBUS Master  Unit  but it has reported diagnostics data  See the slave diagnostics  for more information     Green The slave device is in data exchange with the PROFIBUS Master  Unit  No diagnostics reported                       Clear Diagnostics Button Pressing the Clear Diagnostics button will clear all new diagnostics data  flags in the Unit  If all slaves are in data exchange  pressing the button will  result in all LED indicators turning green     Retrieving Slave Provided that the Master Unit is not in OFFLINE or STOP mode  the diagnos   Diagnostics tics of a specific slave device can be obtained from the LED indicators  Mov   ing the mouse cursor over the LED  will change the cursor from a normal    46    CS1 CJ1W PRM21 PROFIBUS Master DTM Section 2 3       arrow pointer to a hand  Left clicking t
237. used transmission technology  Its  application area includes all areas in which high transmission speed and sim   ple inexpensive installation are required  PROFIBUS modules are intercon   nected by single twisted pair shielded copper wires     The RS 485 transmission technology is very easy to handle  Installation of the  twisted pair cable does not require expert knowledge  The bus structure per   mits addition and removal of devices or step by step commissioning of the  system without influencing the other devices  Later expansions have no effect  on devices which are already in operation     Transmission speeds between 9 6 kbit s and 12 Mbit s can be selected as  shown in the table below  One unique transmission speed must selected for  all devices on the bus when the system is commissioned        Baud rate  kbit s  Distance   segment  m                                      The maximum cable length values depend on the transmission speed  The  length can be increased by the use of repeaters  However  it is not recom   mended to use more than three repeaters in series in a PROFIBUS network     Overview of PROFIBUS Section 1 1       1 1 3 Device Types  PROFIBUS distinguishes between master devices and slave devices     Master Devices Master devices determine the data communication on the bus  A Master can  send messages without an external request  as long as it holds the bus  access right  the token   Masters are also referred to as active devices in the  PROFIBUS standard
238. ve_Add PROFIBUS service  which can be initiated from the  Master DTM  This service can be sent to any slave on the network  even if it is  not allocated to the Master DTM     In order to change a slave device   s address remotely  first make sure that the  Master DTM is on line with the Master  Next  open the Set Device Station  Address window     1  Select the DTM in the Network view     2  Right click the mouse  and select the Additional functions entry from the  context menu     3  Select the Set Device Station Address option  The window as shown below is displayed        tat  1   CJ1W PRM21 PROFIBUS DP   1 Master Set Device Station Adi  iol x   m Perform the DP command  Set Device Station Address                                          5  lose    Target Device    Help       Address     fi 26  Ident number  hex   fi 234   33  Lock    New address     r    Status  z                In order to change the address of a slave device perform the following steps     Setting up a network    Section 3 2       1 2 3        N WARNING    Note    Changing the Slave DTM    Address    Changing the DTM    address via the Generic    Slave DTM    Example    1 2 3       1  Enter the device   s current address and its PROFIBUS Ident Number   The PROFIBUS Ident Number can be found in the Generic Slave DTM or  through the device   s documentation  By default the device   s current ad   dress will be 126  If necessary  change this to the actual current address   2  Enter the new device address i
239. ves   e Selecting the proper I O modules  which define the I O data to be  exchanged when operational    e Setting up the device parameters  which will be send to the device to  make or verify its settings    e Selecting the group assignment  which defines the group of slave devices  each slave belongs to and to allow sending Global Control commands to  this particular group    All these settings will be downloaded to the Master Unit  which will send the  data to the individual slave devices over the PROFIBUS network     3 3 1 Defining the I O configuration    Opening the DTM In order to define the I O configuration  the DTM Configuration User Interface   aoe User must be opened  To do this  either   diii e select the device in the Network view and double click the left mouse but   ton     e select the device in the Network view  right click the mouse and select  Configuration from the context menu     81    Configuring the Slave Devices Section 3 3    Example The figure below  shows the DTM User Interface for the CJ1W PRT21  PROFIBUS DP slave device   210 x1  Device  CJ1W PRT21 GSD File  OC_0602 gsd  Vendor  OMRON Corporation Ident Number  Ox0602    Configuration   Parameter   Group         r Device Settings  Station Address  fe   IV Enable watchdog control Watchdog Interval   200 ms          m Module Configuration    Max  length of input output data  360 Byte Length of input output data  0 Byte  Max  length of input data  200 Byte Length of input data  0 Byte  Max  length o
240. vice sends an un   acknowledged message to a predetermined group of slave devices     1 1 5 Diagnostic functions    Extensive Diagnostics    Device Related  Diagnostics    Module Related  Diagnostics    Channel Related  Diagnostics    Extensive diagnostic functions defined in PROFIBUS DP enable the fast loca   tion of error at slave devices  Diagnostic messages are transmitted over the  bus and collected at the master  Three diagnostic message types are defined     e Messages concerning the general operational status of the whole device   e g  over temperature  low voltage     e Messages indicating that an error is present in a specific I O range of a  device  e g  an 8 bit output module     e Messages indicating an error at a given input or output  e g  short circuit  on Output 5     Overview of PROFIBUS Section 1 1       1 1 6 Protection Mechanisms    Monitoring Time PROFIBUS DP provides effective protection functions against parameteriza   tion errors or failure of the transmission equipment  Time monitoring is pro   vided both at the master and the slave devices  The monitoring interval is  specified when the system is configured     Monitoring at the Master The PROFIBUS Master monitors data transmission of the slaves with the  Data Control Timer  A separate control timer is used for each slave  This timer  expires if response data is not correctly transmitted by the slave within the  monitoring interval  The user is informed when this happens  If the automatic  error rea
241. vices can not exceed 4000        configuration     135    Appendix       Number    Message    PROFIBUS Master is not in cor   rect mode  Please set the PROFI   BUS Master in one of the following  modes  STOP  CLEAR or OPER   ATE     Description    The Set Device Station Address  command can not be executed  because the PROFIBUS Master is  not in correct mode  i e  the Master  Unit is OFFLINE     Correction    Set the PROFIBUS Master into one  of the following modes  STOP   CLEAR or OPERATE        Master Unit indicated failure of Set  Device Station Address     When sending Set Device Station  Address command  one of the fol   lowing problems occurred   e The slave has deactivated this  service   The slave has not responded to  the request   The slave does not have sufficient  memory space for the request  data     e Check target Slave device on the  PROFIBUS network     e Check specified Slave address   e Check Slave timeout parameter          New address    and or    Ident num   ber  hex   are is empty     No data is entered in the New  Address and Ident Number fields     Fill in both the  New address    and the     Ident number  hex   fields        Slave Master DTM does not  accept the specified address     The DTM has not accepted the new  address setting  Possible cause is  that the slave DTM data set has  been locked for parameter changes        A 3    136          Master Unit version and DTM ver   sion do not match  Please select  DTM that can be used with the  connecte
242. wever  service the slave device    This feature can be used with slaves which can fail during operation  but for  which failure it is not necessary to switch the entire network to Auto CLEAR  mode     Control Description       Process Auto CLEAR When Auto CLEAR has been enabled in the PROFIBUS  Master Unit  a failure of this particular slave will cause an  Auto CLEAR event     Ignore Auto CLEAR When Auto CLEAR has been enabled in the PROFIBUS  Master Unit  a failure of this particular slave will not cause  an Auto CLEAR event  The Master will however service  the slave device  e g  send new parameters            Configuration Data The Configuration Data Convention setting defines how the slave device will   Convention handle the special identifier format data parts of the Check I O configuration  message  The slave can perform the check either according to the original  PROFIBUS DP standard  or according to the PROFIBUS DP V1 standard   This allows PROFIBUS DP slaves to use either standard PROFIBUS DP data  types or extended PROFIBUS DP V1 data types     66    Section 2 5    Generic Slave Device DTM    Fail Safe Behaviour    Note    Error on Cyclic Data  Exchange    Note    Diagnostics Update Delay    Control Description    DPV1 Compliant The Check I O configuration message will contain PROFI   BUS DP V1 Data type definitions in the special identifier  format data parts and the slave device will perform the  check on this assumption     EN50170 Compliant The Check I O configu
243. which can define a total of up to 7168 words of input data and or  output data  The I O module selection made per slave by the user is also used  to setup the I O mapping  i e  the definition of which I O modules are mapped  to which PLC memory location     This section discusses the aspects of I O data exchange between the CS1   CJ1W PRM21 PROFIBUS Master Unit and the PLC CPU     3 5 2 Mapping I O Data    I O Mapping Concept    Default I O Mapping  Algorithm    94    The CS1 CJ1W PRM21 PROFIBUS Master Unit provides an I O mapping  concept  based on the I O module selection for each slave device  Each  selected I O module can   depending on whether it defines input and or output  data   be mapped to one of two input and or output areas  Each of the two  input and output areas can be mapped to any PLC memory area location   independent of each other  The I O mapping must be setup using the CS1   CJ1W PRM21 Master DTM  as provided with CX Profibus     Mapping the I O modules involves two steps    e Allocate each I O module to one or more of the Input Output areas    e Allocate each Input Output area to PLC memory   When setting up the network  i e  selecting the slave devices and I O modules  per slave  all input modules will   by default   be allocated to Input area 1  all    output modules will be allocated to Output area 1  The following rules apply  when allocating the I O modules to the areas     e I O modules are mapped starting at the lowest address of an Input Output  a
244. words output  3201   2  4 words output 3401 2 words output  3202 4 words output 3402  3203 4 words output 3403  3204 4 words output 3404  3205   3  2 bytes output  No consiste    3405  3206  10  1 words output 3406  3207 3407  3208 3408  3209 ha 3409 xl  Area   co T  Occupied  0007 Words Area  clo v   Occupied  0002 Words  Start Address   2200 Start Address   a400  Length  fico Compress   Length  fico Compress                     Save            Selecting the I O Area After finalizing the mapping of the I O modules on to the various I O areas  the  Start Address addresses to which the areas will be mapped in the PLC memory need to be  defined  To define the area mapping  perform the following settings     1 2 3    1  For each area  which contains I O modules  select the PLC memory area     2  For that area  set the address to which the first location of the Input Output  area will be mapped  The Input Output area will occupy the PLC memory  area  from this start address to ascending memory locations     3  The total size per Input Output area can be found for each area  next to the  PLC memory area selection box  see for example  the figure above  in  which Output area 1 occupies 6 words      Note 1  The CS1 CJ1W PRM21 Master DTM will check whether two or more se   lected mappings on to the PLC memory will be overlapping  In that case   the start address set  will be shown in red    2  Upon downloading the configuration to the CS1W CJ1W PRM21 PROFI   BUS Master Unit  the Mast
245. y  e g  an input address of 256 or higher   an error message is  displayed and the change is reverted     3  Enabling Auto Addressing again will result in all changes being lost  When  enabling Auto Addressing  a Warning message will be displayed  notifying  the user of these consequences     The I O Modules list can be sorted for more convenient views  Two options  are available     e Sort by station address  Sorting by station address groups all I O modules for each slave device  together  This view is more convenient in case Auto Addressing is  enabled     e Sort by data address  Sorting by data address lists the I O Modules in ascending order  Input  data first  This view is more convenient in case Auto Addressing is dis   abled and addresses have been changed manually     2 4 2 Diagnostics User Interface    Diagnostics User Interface    Opening the DTM  Diagnostics User Interface    1 2 3       The C200HW PRM21 PROFIBUS DP Master DTM provides a second user  interface  to display the Diagnostics information available in the Unit  This  information concerns    e Unit and PROFIBUS DP Interface status flags   e Slave status flags     In order to access the Diagnostics User Interface  the DTM has to be on line   i e  a communication channel between the DTM and the PROFIBUS DP Mas   ter Unit must have been established     In order to open the DTM Diagnostics User Interface perform the following  sequence     1  To go on line  perform one of the following actions   e Select the
246. ycle           Instruction  Execution    transmitted    Instruction  Execution    Instruction  Execution    Instruction  Execution                              Sync Sync    transmitted    Unsync  transmitted             Slave Output  Refresh Cycle    Transmitting Global     Control Commands using    CX Profibus    106             Sync command causes Sync command causes Unsyne command  immediate refresh of immediate refresh of cancels Sync command  slave outputs  and slave outputs with last and causes immediate  freezes slave output received PROFIBUS refresh of slave outputs  refresh process  output data  and with last received    PROFIBUS output data     Note The Global Control command as set in the CIO words is transferred to the    1 2 3       Unit together with the I O data  but the Global Control command is sent over  the PROFIBUS network  following the I O data  This means that the outputs of  the targeted slave device will be updated with the values sent to the slave  prior to the Global Control command     CX Profibus provides a means to transmit Global Control commands from the  PC  through the CS1 CJ1W PRM21 Master DTM Diagnosis User Interface    Online Operations tab  This means uses the same CIO words as described  above   To accomplish a Global Control command transmission  per from the follow   ing sequence     1  Make sure the CS1 CJ1W PRM21 Master DTM is online with the PROFI   BUS Master Unit     2  Open the CS1 CJ1W PRM21 Master DTM Diagnosis User Interface  
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
記 とまった君2号 一 取扱説明書 一  LokPilot Handbuch A5 V10  User Manual  612 - GEMÜ de válvulas  Bedienungsanleitung - T    Copyright © All rights reserved. 
   Failed to retrieve file