1. 1 Call us at 877 297 6937 or write to us at Cyber Power Systems USA Inc 4241 12th Ave E STE 400 Shakopee MN 55379 or send us an e mail message at claims cpsww com for instructions 2 When you contact CyberPower identify the Product the Purchase Date and the item s of Connected Equipment Have information on all applicable insurance or other resources of recovery payment that are available to the Initial Customer and Request a Claim Number 3 You must provide a dated Proof of Purchase receipt or other proof of the original purchase and provide a description of the defect 4 Pack and ship the product with a dated Proof of Purchase receipt to CyberPower and if requested the item s of Connected Equipment a repair cost estimate for the damage to the Connected Equipment and all claim forms that CyberPower provides to you Show the Claim Number on the shipping label or include it with the product You must prepay all shipping costs you are responsible for packaging and shipment and you must pay the cost of the repair estimate How Long Do Have To Make A Claim All claims must be made within ten days of the occurrence What Will We Do To Correct Problems CyberPower will inspect and examine the Product If the Product is defective in material or workmanship CyberPower will repair or replace it at CyberPower s expense or if CyberPower is unable to or decides not to repair or replace the Product if defective within a reaso
2. The UPS will not turn on The Unit te nol conngcIegig The unit must be connected to a 110 120v outlet an AC outlet l i The battery is worn out Contact CyberPower Systems about replacement batteries at tech cpsww com Mechanical problem Contact CyberPower Systems at tech cpsww com The serial cable or USB cable Connect the cable to the UPS unit You must use the cable that is not connected came with the unit The cable is connected to the Try another port of your computer PowerPanel Personal wien Pon Edition is inactive Shutdown your computer and turn the UPS off Wait 10 seconds and turn the UPS back on This should reset the unit The UPS does not perform expected runtime The unit is not providing battery power The serial cable is not the cable that was provided with the unit You must use the cable included with the unit for the software Additional troubleshooting information can be found at www cyberpowersystems com support htm CYBERPOWER GREENPOWER UPS TECHNOLOGY GreenPower UPS The CyberPower GreenPower UPS cuts UPS energy costs by up to 75 compared to the conventional UPS circuits Conventional UPS systems pass power through a transformer to provide normal output voltage to protected devices By contrast the GreenPower UPS circuitry bypasses the transformer when utility power is normal significantly increasing the power efficiency of the UPS As a result a GreenPower UPS produces less he
3. CyberPower Smart App Sinewave Series PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA User s Manual K01 0000071 01 IMPORTANT SAFETY WARNINGS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate CAUTION The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection DO NOT plug the UPS into an outlet that is not grounded If you need to de energize this equipment turn off and unplug the UPS CAUTION DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT CyberPower Systems does not sell products for life support or medical applications DO NOT use in any circumstance that would affect operation or safety of any life support equipment with any medical applications or patient care CAUTION The battery can energize hazardous live parts inside even when the AC input power is disconnected CAUTION For pluggable equipment the socket outlet shall be installed near the equipment and shall be easily accessible CAUTION To prevent the risk of fire or electric shock install in a temperature and humidity controlled indoor area free of conductive contaminants Please see specifications for acceptable temperature and humidity range CAUTION To reduce the ris
4. 4 LCD Display Toggle Button The button can be used to toggle between different data displays on the LCD 5 Battery Backup Protected Outlets Provides eight battery powered surge protected and AVR outlets for connected equipment and ensures temporary uninterrupted operation of connected equipment during a power failure Critical Non critical When the UPS is overloaded the circuit breakers will be tripped to interrupt the power supply to the uncritical outlets while continuing to supply the critical outlets As well as the battery capacity depletes under the threshold value the uncritical outlets will be shut down and provide energy for critical outlets The threshold can be determined and set by users Non critical outlets can also be turned on off manually through the software package provided 6 Input Power Cord Heavy duty extra long power cord 7 Output Circuit Breaker Resettable circuit breakers provide output outlets protection from overload 8 Input Circuit Breaker Resettable circuit breakers provide Input optimal overload Protection 9 USB port USB communication port for management software 10 Protected Communication Ports RJ11 RJ45 Ports protect standard single line modem fax telephone line or network cable 11 Site Wire Fault Indicator This LED will illuminate to warn the user that a wiring problem exists within the AC receptacle such as a bad
5. battery reaches low capacity OVER LOAD icon This icon appears and an alarm sounds to indicate the battery supplied outlets are overloaded To clear the overload unplug some of your equipment from the battery supplied outlets until the icon turns off and the alarm stops FAULT icon This icon appears if there is a problem with your UPS BATT CAPACITY meter This meter displays the approximate charge level in 20 increments of the UPS s internal battery During a blackout or severe brownout the UPS switches to battery back up power the BATT CAPACITY icon appears and the charge level decreases LOAD CAPACITY This meter displays the approximate output load level in 20 increments of the UPS s battery outlets LOAD CAPACITY aa BATT CAPACITY A ee oe ol NORMAL BATTERY AV R SILENT LOAD FAULT Wy p Dulu ka bh Dal The LCD display indicates a variety of UPS operational conditions All descriptions apply when the UPS is plugged into the AC outlet and turned on or when the UPS is on battery LCD STATUS AND SETUP FUCTIONS 1 General Mode a Press the Display button to check the status of the UPS ff item SY nit If the machine is in the Battery Mode it enters the status of Mute If the machine is in the Line Mode it proceeds Self Test c If the Display toggle remains untouched for over 30 seconds the LCD 4 Load in backlight will turn off automatically Estimate Run Time 2 Set up Mode 6 Load Capa
6. ground or reversed wiring If illuminated disconnect all equipment and contact an electrician to ensure outlet is properly wired 12 Coax Cable DSS Surge Protection The Coax Cable DSS surge protection ports will protect any cable Modem CATV converter or DSS receiver 13 Serial Port I Serial port allows connection and communication between the UPS and the computer 14 Serial Port Il Serial Port Il relays information to equipment that can utilize a contact closure UPS 15 SNMP HTTP Network slot Remove the cover panel to install optional RMCARD that allows remote monitoring and control of your UPS on a network 16 EPO Emergency Power Off Port The EPO interface enables connection to an EPO master switch 17 Ground Stud Use the Ground Stud to ground the UPS 18 External Battery Pack Connector Provides a connection for additional CyberPower external battery packs for extended runtime BATTERY REPLACEMENT Contact your dealer or email tech cpsww com Refer to replacement battery pack number RBP852 for PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA For model PR1000LCDRT2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA can support model BP48V75ART2UTAA for external battery pack Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery Service the battery under the supervision of personnel knowledgeable of batteries and their precautions Servicing the battery should only be performed by traine
7. laser printers appliances aquariums medical or life support devices etc What Other Limitations Apply 1 This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets including compliance with electrical and safety codes of the most current electrical code without the use of any adapters or other connectors 2 The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not daisy chained together in serial fashion with any extension cords another Product or device similar to the Product surge suppressor or power tap Any such installation voids the Limited Warranty 3 The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license instruction manual or warnings provided with the Product and the equipment connected to it 4 The Product must have been used at all times within the limitations on the Product s VA capacity What are the Limitations The sole and exclusive remedies of the Initial Customer are those provided by this Warranty The Product was designed to eliminate disrupting and damaging effects of momentary less than 1ms voltage spikes or impulses from lightning or other power transients If it can be shown that a voltage spike lasting longer than 1ms has occurred the
8. 0 XP Vista Manual Self Test Auto Charger Auto Restart es COM Interface True RS232 x1 Dry connector x1 Built in USB Interface SNMP HTTP Network Slot Any of the Following 1 Loss of or damage to data records or software or the restoration of data or records or the reinstallation of software 2 Damage from causes other than AC Power Line Transients spikes or surges on properly installed grounded and code compliant 120 volt power lines in the United States and Canada transients surges or spikes on standard telephone land lines PBX telephone equipment lines or Base 10T Ethernet lines when properly installed and connected This exclusion applies for example to fluctuations in data transmission or reception by CATV or RF transmission or fluctuations or by transients in such transmission 3 Damage from any circumstance described as excluded above with respect to the Product 4 Damages from fire flood wind rain rising water leakage or breakage of plumbing abuse misuse or alteration of either the product or the Connected Equipment 5 CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee CyberPower excludes any liability for direct indirect special incidental or consequential damages whether for damage to or loss of property EXCEPT FOR AND ONLY FOR the specific limited agreement of CyberPower to provide certain warranty benefits regarding Connected Equipme
9. at and uses less energy reducing energy costs When utility power is abnormal the GreenPower UPS operates like a normal UPS Since utility power operates me ei normally 88 of the time the GreenPower UPS operates primarily in its cost cutting bypass mode J LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARNTEE Read the following terms and conditions carefully before using the CyberPower PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA the Product By using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected Equipment Guarantee together referred to as this Warranty If you do not agree to the terms and conditions of this Warranty you should return the Product for a full refund prior to using it Who is Providing this Warranty CyberPower Systems USA Inc CyberPower provides this Limited Warranty What Does This Warranty Cover This warranty covers defects in materials and workmanship in the Product under normal use and conditions It also covers equipment that was connected to the Product and damaged because of the failure of the Product What is the Period of Coverage This warranty covers the Product for three years and connected equipment for as long as you own the Product Who Is Covered This warranty only covers the original purchaser Coverage ends if you sell or otherwise transfer the Product How Do You Get Service
10. city Step 1 The machine enters Set Up Mode after holding the Display toggle for 10 Battery Capacity seconds Icon 3 4 5 6 7 8 lights to indicate Set Up Mode Step 2 By pressing the Display toggle users can switch between setup 8 Centigrade L9 Fahrenheit lop functions User configurable functions are as follows a Delay Time The time delay between switching from Battery Mode to Line Mode There are 9 different settings The default setting is 0 minutes b Battery Pack Numbers This function provides the estimated UPS runtime using various numbers of battery packs The default setting is 0 c Static Frequency Tolerance There are 6 settings The default setting is 6 Functional description The setting may be adjusted to the quality of the electricity in use d Slew rate also called Dynamic Frequency Tolerance There are 5 different settings The fault value is 4Hz sec Functional Description Slew Rate indicates the tolerance of a device in accepting frequency variance The lower Slew Rate results in less tolerance but better protection for the connected loads e Battery Shutdown Voltage This function adjusts the UPS shutdown point according to the battery voltage b Press and hold the Display toggle for 4 seconds The settable items are sorted by unit as in the following table Step 3 Press and hold the toggle for 4 seconds When the icons blink the value of O tems m each item can be cha
11. connect either the serial cable or the USB cable to the corresponding ajin port on the UPS and the computer Note if the USB port is used the serial port will be disabled To control mt Binal multiple computers install PowerPanel Business Edition Agent on the computer connected with the USB cable s and PowerPanel Business Edition Slave on the remaining computers 3 With the UPS unit off and unplugged connect your computer monitor and any externally powered data storage device Hard drive Tape drive etc into the battery power supplied outlets DO NOT plug a laser printer copier space heater vacuum paper shredder or other large electrical device into the UPS The power demands of these devices will overload and possibly damage the unit 4 To protect a fax telephone modem line or network cable connect a telephone cable or network cable from the wall jack outlet to the IN jack of the UPS Then connect a telephone cable or network cable from the OUT jack on the UPS to the modem computer telephone fax machine or network device 5 Plug the UPS into a 2 pole 3 wire grounded receptacle wall outlet Make sure the wall branch outlet is L g protected by a fuse or circuit breaker and does not service equipment with large electrical demands e g air charge the battery js conditioner refrigerator copier etc Avoid using extension cords 6 Depress the power switch to turn the unit on The Power On indicator light wil
12. d personnel Replacement of batteries located in an OPERATOR ACCESS AREA CAUTION When replacing batteries replace with the same number of the following battery HR9 12 BB for PR1I000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA CAUTION Risk of Energy Hazard 12 V maximum 9Ampere hour battery HR9 12 Before replacing batteries remove conductive jewelry such as chains wrist watches and rings High energy through conductive materials could cause severe burns CAUTION Risk of battery explosion if battery is replaced by an incorrect type Dispose of used battery according to the instructions CAUTION To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code ANSI NFPA 70 CAUTION Use only the specified CyberPower replacement battery or battery pack See your dealer for details CAUTION The battery may present a risk of electrical shock Do not dispose of batteries in a fire as they may explode Follow all local ordinances regarding proper disposal of batteries CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to the skin and eyes and may be toxic CAUTION A battery may present a high risk of short circuit current and electrical shock Take the following precautions before replacing the battery 1 Remove all watches rings or other metal objects 2 Only use tools with insulated hand
13. ection and provides battery backup during power outages The PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA ensures consistent power to your computer system and its included software will automatically save your open files and shutdown your computer system during a utility power loss AUTOMATIC VOLTAGE REGULATOR AVR The PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA stabilizes inconsistent utility power The incoming utility power may be damaging to important data and hardware but with Automatic Voltage Regulation the computer will not experience damaging voltage levels An Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent computer safe 110v 120v The unit powerful sealed lead acid batteries will provide power only if the incoming voltage drops below 80v or increases above 150v SYSTEM BLOCK DIAGRAM Filter Suppressor Charger AC DC Input Output Inverter gt Normal Mode Battery Mode HARDWARE INSTALLATION GUIDE 1 Your new UPS may be used immediately upon receipt However recharging the battery for at least four hours is recommended to ensure that the battery s maximum charge capacity is achieved Charge loss may occur during shipping and storage To recharge the battery simply leave the unit plugged into an AC outlet The unit will charge in both the on and off position RS J l E 2 If you plan to use the included software
14. k of electric shock do not remove the cover except to service the battery There are no serviceable parts inside except for the battery CAUTION To avoid electrical shock turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer component CAUTION DO NOT USE WITH OR NEAR AQUARIUMS To reduce the risk of fire do not use with or near aquariums Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out CAUTION For model PR1000LCDRT2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA For use in a computer room as defined in the standard for the Protection of Electronic Computer Data Processing Equipment ANSI NFPA 75 INSTALLING YOUR UPS SYSTEM UNPACKING Inspect the UPS upon receipt The box should contain the following 1 UPS Unit 1 User s Manual for UPS 2 Rack mount Brackets 2 Stands 2 Skids 1 Telephone Cable black 1 Emergency Power Off Cable gray 1 PowerPanel Business Edition Software CD 2 Serial Interface Cable DB 9 1 USB A B type cable 1 Warranty Registration Card OVERVIEW The PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA provides battery backup automatic voltage regulation AVR and optimal performance of computers and other network equipment by ensuring consistent sinewave power The PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA features 2060 Joules of surge prot
15. l illuminate If an overload is detected an audible alarm will sound and the unit will emit one long beep To correct this turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets Wait 10 seconds Make sure the circuit breaker is depressed and then turn the UPS on 7 Your UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically recharge 8 To maintain optimal battery charge leave the UPS plugged into an AC outlet at all times 9 To store your UPS for an extended period cover it and store with the battery fully charged Recharge the battery every three months to ensure battery life 10 Professional Rack Mount UPS provide one serial port one dry contact port and one USB port to allow communication between the UPS and computers or equipment The dry contact port Serial Port Il signals information for equipment that can utilize a dry contact UPS The primary computer with PowerPanel Business Edition installed connected to Serial Port or the USB port is the computer that you use to control the UPS When there is a power failure the primary computer which connects to Serial Port or the USB port will start to shutdown after a user controlled delay PowerPanel Business Edition Agent software will save and close any open files prior to shutting the system down and signal any configured slaves to shutdown 11 EPO Emergency Power Off Po
16. les 3 Do not lay tools or metal parts on top of battery or any terminals 4 Wear rubber gloves and boots 5 Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance applicable to a UPS and a remote battery supply not having a grounded circuit BATTERY REPLACMENT PROCEDURE 1 Remove the six retaining screws and remove the front panel 2 Remove the two retaining screws of the cable protection cover then remove the cover 3 Remove the two retaining screws of the cable connectors 4 Disconnect the black and red cable 5 Remove the three retaining screws 6 Pull out the old battery pack and replace Reassemble the retaining screws covers black and red cable and front panel in the reverse sequence of the above steps Recharge the unit for 4 8 hours to ensure maximum UPS battery runtime LCD STATUS DEFINITION INPUT voltage meter INPUT voltage meter This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet The INPUT voltage readout can be used as a diagnostic tool to identify poor quality input power The AVR in this UPS continuously conditions the power to a stable 110 120V output to connected equipment In the event of a complete power loss severe brownout or ove
17. n is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation WARNING This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits The Class A digital apparatus meets all requirements of the Canadian Interference Causing Equipment Regulation Cet appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada
18. nable time CyberPower will refund to you the full purchase price you paid for the Product purchase receipt showing price paid is required If it appears that our Product failed to protect any equipment plugged into it we will also send you forms for making your claim for the connected equipment We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value NOT REPLACEMENT COST of the equipment at of the time of the damage We will use Orion Blue Book or another a third party valuation guide or eBay craigslist or other source to establish that amount Our maximum liability is limited to 400 000 for PR1000LCDRT XL2UaTAA PR1500LCDRT XL2UTAA PR2200LCDRTXL2UTAA Who Pays For Shipping We pay when we send items to you you pay when you send items to us What Are Some Things This Warranty Does Not Cover 1 This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of the failure or the restoration of data or records or the reinstallation of software 2 This Warranty does not cover or apply to misuse modification operation or storage outside environmental limits of the Product or the equipment connected to it nor for damage while in transit or in storage nor if there has been improper operation or maintenance or use with items not designed or intended for use with the Product such as
19. nged by slightly pressing the toggle l i Step 4 To save the value and return to general mode press and hold the toggle for Delay Time 4 seconds Battery Pack Numbers o S Static Frequency Tolerance Note If the machine is left idle for over 30 seconds during setup it will turn off the backlight and return to general mode automatically Battery Shutdown Voltage Note If user wants to return to general mode without saving changes there are two methods 1 Wait for the backlight to turn off 2 Press and hold the Display toggle for 10 seconds TROUBLE SHOOTIMG Turn the UPS off and unplug at least one piece of equipment Wait 10 seconds reset the circuit breaker by depressing the button and then turn the UPS on l Batteries are discharged Recharge the unit for at least 4 hours Outlet do not provide power to equipment Unit has been damaged by a Contact CyberPower Systems about replacement batteries at surge or spike tech cpsww com Uncritical outlets have turned off automatically due to an overload Circuit breaker has tripped due to an overload Push the toggle button to make the uncritical outlets turn on Battery not fully charged Recharge the battery by leaving the UPS plugged in Battery is degraded Contact CyberPower Systems about replacement batteries at tech cpsww com TE poit Swiieh Is Gesigned Turn the UPS off Wait 10 seconds and then turn the to prevent damage by rapidly turning it off and on UPS on
20. nt under this Warranty loss of profits business interruption or loss of information or data NOTE Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages so the above limitation may not apply to you 6 The Product is not for use in high risk activities or with aquariums The Product is not designed or intended for use in hazardous environments requiring fail safe performance or for use in any circumstance in which the failure of the Product could lead directly to death personal injury or severe physical or property damage or that would affect operation or safety of any medical or life support device collectively High Risk Activities CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums CyberPower does not authorize use of any Product in any High Risk Activities or with Aquariums ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT What is the Fine Print The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded CyberPower is the warrantor under this Limited Warranty For further information please feel free to contact CyberPower at Cyber Power Systems USA Inc 4241 12th Ave E STE 400 Shakopee MN 55379 call us at 877 297 6937 or send us an e mail message at claims cpsww com FCC Notice This device complies with part 15 of the FCC Rules Operatio
21. occurrence will be deemed outside TECHNICAL SPECIFICATIONS the rated capabilities of the Product and the Limited Warranty is void CyberPower Does Not Cover or Undertake Any Liability in Any Event for PR1000LCDRTXL2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA Capacity VA 1000 1500 2150 Capacity Watts 750 1125 1650 nput Plug Type NEMA 5 15P NEMA 5 20P nput Voltage Range 80Vac 150Vac Input Frequency Range 50 60HZ 3Hz auto sensing Output On Battery Output Voltage Pure Sine Wave at 120Vac 5 On Battery Output Frequency 50 60HZz 0 1Hz Transfer Time Typical 4 ms Overload Protection On Utility Circuit Breaker On Battery Internal Current Limiting Surge Protection and Filtering Internet Ready DSL Phone FAX Modem Protection Physical Output Receptacles 8 NEMA 5 20R Dimensions in 2U Rack 17 1 x 18 9 x 3 5 2U Rack 17 1 x 15 3 x 3 5 Weight Ib 68 76 77 RJ11 RJ45 One In One Out w o lt Sealed Maintenance Free Lead Acid Battery Extension Runtime Yes Hot Swappable External Battery Yes Warning Diagnostics ndicators Power On Wiring Fault LCD Display Using Battery AVR Load Level Battery Level Audible Alarms On Battery Low Battery Overload Environmental Operating Temperature Operating Relative Humidity Communication PowerPanel Business Edition Management Self Test 12V 9 0AHx4 32 F to 104 F 0 C to 40 C 0 to 95 Non Condensing Windows 98 ME NT 200
22. r voltage the UPS relies on its internal battery back up to supply a consistent 110 120V output OUTPUT voltage meter This meter measures in real time the AC voltage that the UPS system is providing to the computer such as normal line mode AVR mode and battery back up mode Note The OUTPUT voltage readout displays the status of the battery back up outlets ESTIMATE RUN TIME This displays the run time estimate of the UPS with the current battery capacity and load NORMAL icon This icon appears when the UPS is working under normal conditions BATTERY icon During a severe brownout or blackout this icon appears and an alarm sounds two short beeps followed by a pause to indicate the UPS is operating from its Internal batteries During an extended brownout or blackout that drains the battery a continuous alarm will sound and the BATT CAPACITY readout will show a single shaded segment equaling 20 battery capacity remaining indicating the UPS batteries are nearly out of power If this occurs it is recommended that you save your files and manually power down your equipment immediately Automatic Voltage Regulation AVR icon This icon appears whenever your UPS is automatically correcting low AC input line voltage without using battery power This is a normal automatic operation of your UPS and no action is required SILENT MODE icon This icon appears whenever the UPS is in silent mode The buzzer does not beep during silent mode until the
23. rt The feature is used with EPO controllers Use the provided gray cable to connect to an EPO contact switch Follow the appropriate circuit diagram below to wire the cable to match your EPO configuration For model PR1000LCDRT2UaTAA PR1500LCDRTXL2UTAA PR2200LCDRTXL2UTAA EPO function is provided in the UPS EPO remote switch which is a Push Back button installed computer room outside by a phone line and not connected any other equipment AAAH computer and peripherals OPTION 1 USER SUPPLIED NORMALLY CLOSED SWITCH 4 5 JUMPER 5 RJ11 N C EPO SWITCH PLUG N O EPO SWITCH RJ11 PLUG NO CONNECTION Install PowerPanel Business Edition software on the primary computer connected to the UPS with either a serial cable or a USB cable The equipment can read information from dry contact Dry connect is controlled by the PowerPanel Software Primary Computer please go to www cyberpowersystems com for free download Install PowerPanel Business Edition NOTE Both USB and Serial can not be used simultaneously When you first receive the unit plug in the unit to fully Unplug the unit and turn Power Off when first connecting your BASIC OPERATION FRONT REAR PANEL DESCRIPTION O 1 Power Switch Master on off switch for equipment connected to the UPS 2 Power On Indicator Indicates the power is on 3 LCD Module Display LCD shows all the UPS information with icons and messages