USER MANUAL - Integra Tech
Contents
1. SKF amp 3KF CN 1305 EPRO 1K 3K 20 USER MANUAL EPR0 1K 3K 1KF 3KF 17 ESPECIFICACIONES 1K 1 5K 2K 3K ONLINE UPS 1K 3K Capacity Capacidad VA Capacity Capacidad W INPUT ENTRADA Range Rango Vac Models 120V Range Rango Vac Models 220V Freq Range Rango Frecuencia Phase Fases Power Factor Factor de Potencia Input THDi THDi de Entrada Slew Rate Seguimiento de F OUTPUT SALIDA Voltage Output Voltaje de Salida AC Output Regulation Rango de Salida Frequency Frecuencia Batt Mode Current Crest Ratio Factor de Cresta Harmonic Distortion Dist Arm nica THDv AC to Inverter Tiempo AC a Inversor Waveform Forma de Onda Freq Conversion Conversi n Frec EPO Apagado Emergencia Progammable Outputs Salidas Prog EFFICIENCY EFICIENCIA Eco Mode AC Mode Modo AC Battery Mode Modo Bater a OVERLOAD SOBRECARGA AC Mode Modo Normal Shortcircuit Cortocircuitos Battery Mode Modo Bateria 1000VA 800W 1500VA 1200W 2000VA 1600W 3000VA 2400W Model 120V 80Vac 150Vac 100 load Model 120V 50Vac 150Vac 50 load Model 220V 160Vac 300Vac 100 load Model 220V 110Vac 300Vac 50 load 40 Hz 0Hz Single phase with ground 1 fase Tierra gt 0 99 100 load lt 7 100 load 1Hz s N1 Model 120V 110 115 120 127Vac Model 220V 208 220 230 240Vac 1 N3 50 Hz 0 25 Hz
2. USER MANUAL EPR0 1K 3K 1KF 3KF ENGLISH USER MANUAL MODELS 120V 220V EPRO 1K 1 5K 2K 3K EPRO 1KF 2KF 3KF EPRO 1KF CN 2KF CN 3KF CN ONLINE DOUBLE CONVERSION UPS Technical information on this manual is property of INTEGRA This manual Information cannot be copied or distributed totally or partially without written approval of INTEGRA INTEGRA can introduce modifications in their products or manuals without further notice INTEGRA is not responsible of mistakes or missing information in this manual INTEGRA is not responsible for wrong use a third part can do of this information Trademarks and logos in this manual are property of their owners www integra ups com 1305 EPRO 1K 3K 1 me POSE ld USER MANUAL EPRO 1K 3K 1KF 3KF This manual covers 3 UPS families related to EPRO UPS 1KVA to 3KVA EPRO 1K 1 5K 2K 3K Online double conversion UPS IGBT technology with full set of functions and capabilities This model includes special functions like Frequency conversion EPO Emergency Power OFF Programmable Outlets Inverter Technology Half Bridge Common Neutral Main Features of Half Brdige Common Neutral UPS Output Neutral is connected to Input Neutral in normal Online mode That makes voltage between output Neutral and Ground is similar to N G voltage at input side This is a perfect online UPS for PC related applications PCs Workstations Servers etc Not suitable fo
3. 60Hz 0 3 Hz 3 1 100 load lt 3 Linear Load Carga Lineal lt 6 No Linear Load Carga no Lineal 0 ms Pure Sinewave Sinusoidal Pura Y Y Y Y Y Y Y Y gt 93 gt 93 gt 93 gt 93 gt 85 gt 85 gt 88 gt 88 gt 83 gt 83 gt 83 gt 83 100 110 Full Protection for all outlets Protecci n en todas las salidas 100 110 waming alarma 110 130 30s shutdown gt 130 1s shutdown waming alarma 110 130 1min bypass gt 130 1s bypass BATTERIES BATERIAS Type Tipo Sealed Lead Acid VRLA AGM Sellada de Libre Mantenimiento VRLA AGM Cap Qty 12V 7AH x 3 12V 9AH x 3 12V 7AH x 6 12V 9AH x 6 Recharge Time Recarga 4 Hours for 90 capacity 4 Horas para recuperar el 90 de carga Charging Voltage Voltaje de Carga 41Vdc 41Vdc 82Vdc 82Vdc Charging Amps Corriente de Carga 1 0 A Max EXT BATT CABINETS Optional BATERIAS EXTERNAS opcionales Standard EXT BATT pack X X 12V 9Ah x 12 12V 9Ah x 12 INDICATORS INDICADORES LCD ALARM ALARMAS Alarm Beep Alarma Sonora www integra ups com UPS status Load level Battery Input Output voltage Discharge timer and Fault conditions Estado del UPS Consumo Baterias Voltaje Entrada Salida Autonomia Diagnostico Fallas Battery Mode Low batt Overload UPS Failure Modo Bateria Baja bateria Sobrecargas Falla 1305 EPRO 1K 3K 21 USER MANUAL EPR0 1K 3K 1KF 3KF 17 ESPECIFIC
4. ECO disable OFF 05 ECO Input Range Configuration This function allows to set HIGH limit HLS and LOW limit LLS for ECO mode Hi limit and Low limit define the acceptable voltage input range in ECO mode If during ECO mode input voltage is out of acceptable input range UPS will change to normal ONLINE mode 06 Bypass Enable or Disable This function allows to enable or disable BYPASS mode If Bypass mode is enable UPS will enter in BYPASS when UPS is connected to AC input service without selecting ON push button ENX Bypass enable DIS Bypass disable 07 By Pass Input Range Configuration This function allows to set HIGH limit HLS and LOW limit LLS for BYPASS mode Hi limit and Low limit define the acceptable voltage input range in BYPASS mode If during BYPASS mode input voltage is out of acceptable range UPS will power off 08 Programmable Outlets Enable or Disable This function allows to enable or disable programmable outlets Programmable outlets are those that can be programmed to power off after reaching configured time even battery level is OK _ JENA to enable programmable function DIS to disable programmable function 09 Programmable Outlets Timer setting 0 999 T o configure timer limit in minutes for powering off programmable outlets no matter batteries level is still OK 10 Max backup Time Timer setting 0 999 To configure maximum backup time in minutes for general AC o
5. Frecuiencia Cuando el voltaje de salida se ajusta a 208Vac en los modelos de 220Vac se pierde un 20 de capacidad de salida Maximum working altitud is 4 000m Over 1 000m output derates 1 every 100m Altura m xima de operaci n es 4 000m Sobre los 1 000m la potencia de salida disminuye un 1 cada 100m Intelligent SNMP Port www integra ups com 1305 EPRO 1K 3K 22 afitegra USER MANUAL EPRO 1K 3K 1KF 3KF 17 ESPECIFICACIONES 1KF 2KF amp 1KF CN 2KF CN 3KF CN Capacity Capacidad VA Capacity Capacidad W INPUT ENTRADA Range Rango Vac Models 120V Range Rango Vac Models 220V Freq Range Rango Frecuencia Phase Fases Power Factor Factor de Potencia Input THDi THDi de Entrada Slew Rate Seguimiento de F Surge Immunity Level OUTPUT SALIDA Voltage Output Voltaje de Salida AC Output Regulation Rango de Salida Frequency Frecuencia Batt Mode Current Crest Ratio Factor de Cresta Harmonic Distortion Dist Armonica THDv AC to Inverter Tiempo AC a Inversor Waveform Forma de Onda Freq Conversion Conversion Frec EPO Apagado Emergencia Progammable Outputs Salidas Prog EFFICIENCY EFICIENCIA Eco Mode AC Mode Modo AC Battery Mode Modo Bater a OVERLOAD SOBRECARGA AC Mode Modo Normal Output Shortcircuit Cortocircuito en Salida Battery Mode Modo Bater a BATTERIES BATERIAS Type Tipo Cap amp
6. ONLINE UPS UPS outlets are supplied by AC power generated by UPS inverter circuit offering a clean power to your devices b ECO Mode Under this mode UPS works as OFF LINE UPS UPS outlets are supplied by AC input source UPS supervises input source to switch to ONLINE mode only when input source is out of range This is not a recommendable mode for those critical applications that require ONLINE UPS Default mode set as factory is NORMAL MODE Online UPS C Output Voltage It can be configured to any of 4 available values In 120Vac Models 110Vac 115Vac 120Vac 127Vac In 220Vac Models 208Vac 220Vac 230Vac 240Vac d Output Frequency It can be selected to 50Hz or 60Hz Default configuration allows auto selection to match with frequency of input AC source NOTE When conversion frequency mode is activated UPS power capacity could be reduced e Programmable Outputs There are 2 groups of outlets e Standard Outlets They work as expected in any UPS This kind of outlets under battery keep powered until batteries reach very low level or up to UPS receives power off command from software e Programmable Outlets If programmable outlets function is configured programmable outlets can be powered off by internal timer before UPS detects very low battery level Most common application for programmable outlets is for connecting non critical devices to them so that backup time can be longer for those critical devices connected in standard outl
7. Qty Recharge Time Recarga Charging Voltage Voltaje de Carga Charging Amps Corriente de Carga 1KF amp 1KF CN 2KF amp 2KF CN 3KF amp 3KF CN 1000VA 2000VA 3000VA 800W 1600W 2400W Model 120V 80Vac 150Vac 100 load Model 120V 50Vac 150Vac 50 load Model 220V 160Vac 300Vac 100 load Model 220V 110Vac 300Vac 50 load 40 Hz 70Hz Single phase with ground 1 fase Tierra gt 0 99 100 load lt 7 100 load 1Hz s gt 7KV EN61000 4 5 N1 Model 120V 110 115 120 127Vac Model 220V 208 220 230 240Vac 1 N3 50 Hz 0 25 Hz 60Hz 0 3 Hz 3 1 100 load lt 3 Linear Load Carga Lineal lt 6 No Linear Load Carga no Lineal 0 ms Pure Sinewave Sinusoidal Pura N N N N N N N N N gt 93 gt 93 gt 93 gt 89 gt 90 gt 89 gt 86 gt 89 gt 88 100 110 warning alarma 110 130 1min bypass gt 130 1s bypass Full Protection for all outlets Protecci n en todas las salidas 100 110 warning alarma 110 130 30s shutdown gt 130 1s shutdown Sealed Lead Acid VRLA AGM Sellada de Libre Mantenimiento VRLA AGM 12V 9AH x 2 12V 9AH x 4 12V 9AH x 6 4 Hours for 9096 capacity 4 Horas para recuperar el 9096 de carga 27 4Vdc 54 7Vdc 82 1Vdc 1 0A Max EXT BATT CABINETS Optional BATERIAS EXTERNAS opcionales Standard EXT BATT pack INDICATORS INDICADORES LCD ALARM ALARMAS Alarm Beep Alarma Sonora
8. Range Vac BYPASS mode BAN Input Range Vac BYPASS mode running time for general outlets Programmable Outlets Input Range Hz BYPASS mode Enable Disable Max running time for PROG AH setting for batteries Outlets Max running time for general N G Voltage Control Enable Disable outlets www integra ups com 1305 EPRO 1K 3K 12 afitegra USER MANUAL EPRO 1K 3K 1KF 3KF MODEL EPRO F CN 1KF CN 2KF CN amp 3KF CN ocreens for 230V models 120V models have their own screens showing values typical for 120V systems D5 HLS ebt 4 www integra ups com 01 Output Voltage Configuration Output voltage value can be selected from 4 available values For 220V Models 208V 220V 230 V or 240Vac For 120V Models 110V 115V 120V or 127Vac 102 Input Acceptable Voltage Range Defines acceptable input to allow UPS to go to normal ONLINE mode HLS High Limit For 220V models from 260V to 300V For 120V models from 130V to 150V LLS Low Limit For 220V models from 160V to 190V For 120V models from 80V to 95V 03 ECO Enable or Disable This function allows to enable or disable ECO mode ENA ECO enable ON DIS ECO disable OFF 104 ECO Input Range Configuration This function allows to set HIGH limit HLS and LOW limit LLS for ECO mode Hi limit and Low limit define the acceptable voltage input range in ECO mode I
9. STAND BY mode Acoustic alarm is activated as continuous iin d Warning message N 20 is indicated on LCD To disable EPO mode and recovering normal mode contact switch or jumper in EPO port must be closed and UPS must be powered by selecting ON push button www integra ups com 1305 EPRO 1K 3K 7 me 9 USER MANUAL EPRO 1K 3K 1KF 3KF OPTIONAL KIT FOR EXTERNAL BATTERIES PACKS There is a connector optional kit available for EPRO amp EPRO F series that allows connection of external battery packs to the UPS This optional kit can be get as option to be connected in UPS rear panel This kit offers a DC connector for the rear panel and attached cable to be connected to internal batteries In that way internal batteries will be available to be connected to external batteries by DC connector INSTRUCTIONS TO CONNECT EXTERNAL BATTERIES If UPS already has DC connector installed for External Batteries EXBATT follow instructions of this section If not install connection kit according to its manual IMPORTANT Every UPS model has its own DC connector kit with different size and color This avoids to connect the wrong EXBATT to your UPS User must be sure about the kind of EXBATT to be connected to UPS In case of doubts we recommend to revise product label and instructions of this manual MODELO VOLTAJE DC MODELO VOLTAJE DC EPRO 1KF 24 Vdc EPRO 1KF CN 24 Vdc EPRO 2KF 48 Vdc E
10. support equipments microwave ovens vacuum cleaners refrigerators or any other appliance to this UPS WARNING UPS must be checked repaired and maintained by qualified personnel only This product is locked by screws WARNING ELECTRIC SHOCK RISK Inside the UPS there are dangerous high voltages even when disconnected of power line due to internal batteries WARNING In case of emergency turn off the UPS pressing Power Button unplug it and call technical support Laser Printers Scanners and Copiers are high peak power devices Make sure your UPS output capacity in watts can manage peak consumption of connected loads NEVER connect output NEUTRAL with system GROUND This will damage UPS after few weeks If load requires OV between NEUTRAL and GROUND an isolation transformer must be installed at UPS output Then you can connect NEUTRAL and GROUND in the secondary of the transformer DISPOSAL We strongly recommend disposing this UPS according to regulations in your country to prevent possible environmental damages besides some parts might be recycled K BATTERY WARNING DO NOT dispose batteries in fire as it might explode DO NOT try to open batteries there are dangerous liquids inside www integra ups com 1305 EPRO 1K 3K 3 USER MANUAL EPR0 1K 3K 1KF 3KF 2 SAFETY QUALITY PERFORMANCE STANDARDS SAFETY LOW VOLTAGE DIRECTIVE 2006 95 EC w ww UPS Part 1 1 General amp Safety UPS in accessible areas IEC
11. 60Hz siempre que la frecuencia de entrada se mantenga entre 40 y 70 Hz Derate capacity to 60 of total capacity when Frequency converter mode is activated When the output voltage is adjusted to 208VAC in 220Vac models output capacity derates to 80 La capacidad en VA Watts se degrada y baja hasta el 60 en modo Convertidor de Frecuiencia Cuando el voltaje de salida se ajusta a 208Vac en los modelos de 220Vac se pierde un 20 de capacidad de salida Maximum working altitud is 4 000m Over 1 000m output derates 1 every 100m Altura maxima de operaci n es 4 000m Sobre los 1 000m la potencia de salida disminuye un 1 cada 100m Intelligent SNMP Port www integra ups com 1305 EPRO 1K 3K 24
12. A 31 41 Half Pallet Medio Pallet NA 12pcs 12pcs Full Pallet Pallet Completo NA 24pcs 24 OPERATIONAL CONDITIONS CONDICIONES DE OPERACION Rel Humidity Humedad Relativa lt 95 RH non condensing no condensante Temperature Temperatura 0 40 C Noise Level Ruido Producido lt 45dBA o 1m COMMUNICATION COMUNICACION Smart RS 232 amp USB Windows family Linux Unix Mac 05 LAN Card SNMP type optional Comunicacion con LAN mediante SNMP opcional AS400 Interface optional comm Card Interfaz con AS400 tarjeta opcional Technical specifications can be modified to comply with special requirements Las especificaciones pueden bajo requerimiento adaptarse a proyectos especiales Technical specifications may change without further notice Por motivos comerciales o t cnicos las especificaciones pueden cambiar sin previo aviso N1 Output voltage is selectable by LCD El Voltaje de salida es configurable entre 4 alternativas seleccionables en el LCD N2 Backup time for programable outlets is configurable in minutes by LCD to offer longer time to critical loads connected to normal outlets La autonomia de las salidas programables es configurable en min en el LCD para dejar mayor autonomia para las salidas normales N3 Converter Mode Function allows to set output frequency at constant value 50Hz or 60Hz when input Frequency is within 40 70 Hz El modo de Conversion de Frecuencia permite fijar la salida a 50 o
13. ACIONES 1K 1 5K 2K 3K ONLINE UPS 1K 3K PRODUCT FEATURES CARACTERISTICAS DEL PRODUCTO DxWxH Prof Ancho Altura mm 397x145x220 397x145x220 421x190x318 421x190x318 Net Weight Peso Neto kgs 13 14 26 20 UPS MODEL 230Vac EUROPE Standard Outlets Salidas Est ndar SCHUKO x 1 SCHUKO x 1 SCHUKO x 2 SCHUKO x 2 Prog Outlets Salidas prog N2 SCHUKO x 1 SCHUKO x 1 SCHUKO x 2 SCHUKO x 2 UPS MODEL 120Vac AMERICA Standard Outlets Salidas Est ndar NEMA 15 x2 NEMA 15 x2 NEMA 20 x4 NEMA x 3 TB Prog Outlets Salidas prog N2 NEMA 15 x2 NEMA 15 x2 NEMA 20 x4 NEMA 20 x 3 External Battery Cabinet Tower DxWxH Prof Ancho Altura NA NA 421x190x318 421x190x318 Net Weight Peso Neto kgs NA NA 29 39 PACKING EMPAQUE UPS Tower Type Unit CARTON DxWxH mm 472x230x340 472x230x340 560x320x470 560x320x470 Unit Gross Weight Peso Bruto 14 Kg 15 Kg 29 Kg 30 Kg Half Pallet Medio Pallet 30pcs 30pcs 12pcs 12pcs Full Pallet Pallet Completo 50pcs 50pcs 24pcs 24pcs External Battery Cabinet Unit CARTON DxWxH mm NA NA 560x320x470 560x320x470 Unit Gross Weight Peso Bruto NA NA 31 41 Half Pallet Medio Pallet NA NA 12pcs 12pcs Full Pallet Pallet Completo NA NA 24pcs 24pcs OPERATIONAL CONDITIONS CONDICIONES DE OPERACI N Rel Humidity Humedad Relativa lt 95 RH non condensing no condensante Temperature Temperatura 0 40 C Noise Level Ruido Producido lt 45dBA 1m COMMUNICATION COMU
14. EN 62040 1 ELECTROMAGNETIC COMPATIBILITY EMC DIRECTIVE 2004 108 EC UPS Part 2 Electromagnetic Compatibility IEC EN 62040 2 Low Freq Conducted Disturbances amp Signals IEC EN 61000 2 2 Electrostatic discharge immunity Test IEC EN 61000 4 2 Level 3 Radiated radio Frequency immunity IEC EN 61000 4 3 Level 3 Electrical Fast Transient burst immunity IEC EN 61000 4 4 Level 4 Surge immunity IEC EN 61000 4 5 Level 4 Conducted Immunity IEC EN 61000 4 6 Power frequency magnetic field immunity IEC EN 61000 4 8 Voltage Dips Short Interruptions amp Voltage Variations Immunity IEC EN 61000 4 11 UPS Part 3 Methods of operation specifications and test requirement IEC EN 62040 3 IT Equipments SAFETY Part 1 General Requirements IEC EN 60950 1 IP PROTECTION IP20 static Manufactured under ISO 9001 QUALITY MANAGEMENT 2000 Manufactured under ISO 14001 ENVIRONMENTAL MANAGEMENT 2004 Any modification made by user or operator may affect compliance of the safety and performance certifications listed above UPS manufacturer is not responsible of any modification made on the product or its accessories after it is manufactured This product is designed to operate in domestic and commercial environment www integra ups com 1305 EPRO 1K 3K 4 ae Quiere USER MANUAL EPRO 1K 3K 1KF 3KF 9 PRODUCT DESCRIPTION This is an online double conversion UPS designed to work under harsh environments that offers sophi
15. Enable Voltage between UPS output N G similar than input DIS Disable Output NEUTRAL isolated from input NEUT RAL Voltage in output N G could rise 1305 EPRO 1K 3K 13 afitegra USER MANUAL EPRO 1K 3K 1KF 3KF MODEL EPRO F 1KF 2KF amp 3KF ocreens for 230V models 120V models have their own screens showing values typical for 120V systems fe HLS 280 DY HLS D5 HLS cou www integra ups com 01 Output Voltage Configuration Output voltage value can be selected from 4 available values For 220V Models 208V 220V 230 V or 240Vac For 120V Models 110V 115V 120V or 127Vac 102 Input Acceptable Voltage Range Defines acceptable input to allow UPS to go to normal ONLINE mode HLS High Limit For 220V models from 260V to 300V For 120V models from 130V to 150V ILLS Low Limit For 220V models from 160V to 190V For 120V models from 80V to 95V 03 ECO Enable or Disable This function allows to enable or disable ECO mode ENA ECO enable ON DIS ECO disable OFF 04 ECO Input Range Configuration This function allows to set HIGH limit HLS and LOW limit LLS for ECO mode Hi limit and Low limit define the acceptable voltage input range in ECO mode If during ECO mode input voltage is out of acceptable input range UPS will change to normal ONLINE mode 05 Bypass Enable or Disable This function allo
16. NICACION Smart RS 232 amp USB Windows family Linux Unix Mac 0S LAN Card SNMP type optional Comunicaci n con LAN mediante SNMP opcional AS400 Interface optional comm Card Interfaz con AS400 tarjeta opcional Technical specifications can be modified to comply with special requirements Las especificaciones pueden bajo requerimiento adaptarse a proyectos especiales Technical specifications may change without further notice Por motivos comerciales o t cnicos las especificaciones pueden cambiar sin previo aviso N1 Output voltage is selectable by LCD El Voltaje de salida es configurable entre 4 alternativas seleccionables en el LCD N2 Backup time for programable outlets is configurable in minutes by LCD to offer longer time to critical loads connected to normal outlets La autonomia de las salidas programables es configurable en min en el LCD para dejar mayor autonomia para las salidas normales N3 Converter Mode Function allows to set output frequency at constant value 50Hz or 60Hz when input Frequency is within 40 70 Hz El modo de Conversi n de Frecuencia permite fijar la salida a 50 o 60Hz siempre que la frecuencia de entrada se mantenga entre 40 y 70 Hz Derate capacity to 60 of total capacity when Frequency converter mode is activated When the output voltage is adjusted to 208VAC in 220Vac models output capacity derates to 80 La capacidad en VA Watts se degrada y baja hasta el 60 en modo Convertidor de
17. PRO 2KF CN 48 Vdc EPRO 3KF 72 Vdc EPRO 3KF CN 72 Vdc MODELO VOLTAJE DC EPRO 1K 36 Vdc EPRO 1 5K 36 Vdc EPRO 2K 72 Vdc EPRO 3K 72 1 Place EXBATT close to the UPS 2 We recommend to measure DC voltage on both EXBATT and UPS before making any connections Input breaker on EXBATT must be in ON position before measuring DC voltage Verify both voltages are similar according to above tables 3 Turn OFF input breaker in all EXBATT to be connected Connect UPS to first EXBATT using EXBATT cable included in EXBATT box 4 Connect second EXBATT to first EXBATT in similar way 9 After connecting all EXBATT Turn ON all input breakers on EXBATT EXBATT 1 EXBATT 2 EXBATT n COMUNICATION PORTS Models F and F CN come with USB port inserted in intelligent slot If a different communication port is required as RS232 LAN Card etc you must remove USB port to connect new port Models 1K 3K already include RS232 USB on rear panel Intelligent slot is only required for connecting LAN card Relay card etc www integra ups com 1305 EPRO 1K 3K 8 ae Quiere USER MANUAL EPRO 1K 3K 1KF 3KF 9 CONFIGURATION Any configuration modification must be applied with UPS connected to AC line but in OFF or STAND BY mode This UPS can be configured to work under some different modes Some important functions can also be configured in CONFIGURATION MODE a Normal Mode Also known as AC MODE Under this mode UPS works as
18. abnormal situation at UPS output UPS mode is indicated graphically e Normal e Bypass e ECO e Battery qu Vac 1 ES Vac Vdc Vdc uz 3 digits at right indicates output values 3 digits code at left show input values www integra ups com 1305 EPRO 1K 3K 11 LA SEL USER MANUAL EPRO 1K 3K 1KF 3KF 9 UPS CONFIGURATION Configuration menu is activated by selecting SELECT push button at front panel during 5 seconds or longer UPS must be connected to input AC source but in stand by mode powered off When entering in configuration mode you will see EXIT screen identified as 00 You can navigate in configuration menu by using keys in front panel Each configuration screen is identified by 2 digits number 01 02 etc On each screen 2 parameters are indicated PAR 1 and PAR 2 IMPORTANT NOTE EVERY UPSFAMILY HAS ITS OWN CONFIGURATION MENU WITH DIFFERENT FUNCTIONS AND OPTIONS CONFIGURATION MENU BY MODEL EPRO F 1KF 2KF 3KF EPRO F CN 1KFCN 2KFCN 3KFCN ESC screen ESC screen ESC screen Bd Lx Dwewer inc hacia Input Range for normal mode Input Range Vac for normal mode na T Tn Input Range Vac for ECO mode Input Range Vac for ECO mode EN Input Range Vac for ECO mode BYPASS Mode Enable Disable BYPASS Mode Enable Disable EN BYPASS Mode Enable Disable Input Range Vac BYPASS mode Input
19. ackout is detected e Configurable scheduled shutdown and Auto tests Some UPS models include software CD inside the box For others software downloading is available from our website Download always software user manual and follow it carefully during software installation 14 BATTERIES MAINTENANCE AND CARE When battery backup time is noticeable shorter it is time to replace batteries To get longer lifetime we recommend applying a deep discharge every 3 months Operation temperature should be below 25 C IMPORTANT RECHARGING PLAN DURING LONG STORAGE When UPS is storage periodic recharge must be performed as indicated in below table Long storage without recharging will damage batteries This kind of problem is not covered by original product warranty Storage Temperature Recharge Frequency Recharge Time 25 C to 30 C 30 C to 45 C www integra ups com 1305 EPRO 1K 3K 18 Quissra USER MANUAL EPRO 1K 3K 1KF 3KF 15 WARRANTY AND SUPPORT Support If a failure or problem is detected please check troubleshooting section in user manual If problem cannot be solved please contact authorized service center or authorized dealer Batteries Rechargeable batteries can be charged and discharged hundreds of times However they will eventually wear out This is not a defect or failure so that batteries wear out is not covered by this warranty Battery lifetime will depend of operative conditions like working temp
20. be storage longer than 18 months Problems on batteries caused by this kind of long storage are not covered by this warranty 9 This warranty does not cover product failures caused by installations modifications or repair performed by non authorized person If product is open by not authorized technician warranty will be considered void This warranty does not cover failure caused by inadequate installation or maintenance misuse accidents fire or floods 10 This product can include protection devices like input fuse or input breaker Activation of this kind of devices is not a failure it is caused by an improper product installation Input fuse or breaker reset or replacement is not covered by this warranty 11 This warranty does not cover damages produced during transportation from user to technical service caused by improper packing of the product by user 12 Warranty terms and conditions cannot be modified or extended by third parties without written approval of INTEGRA Limited Warranty PRO 11 INTEGRA does not warrant that the operation of this product will be uninterrupted or error free during its lifetime If product fails to work the maximum liability of INTEGRA under this limited warranty is expressly limited to the lesser of the price you have paid for the product or the cost of repairing or replacement of any hardware components that malfunction in conditions of normal use n no event will INTEGRA be liable for any damages cause
21. ctivate Auo Test function OFF ENTER a POWER OFF Keep selected during 2 seconds to power off UPS b ENTER Enter function works under configuration mode only It works as confirmation or selection key for accepting current option on LCD SELECT a PARAMETERS AND VALUES It is used to show on LCD UPS input and output values as AC Input DC battery voltage Input Frequency UPS output output frequency etc b CONFIGURATION MENU Keep selected during 5 seconds or longer lt ON MUTE gt SELECT BY PASS MODE Under normal mode by selecting these 2 keys at the same time during 5 seconds or longer UPS changes from normal mode to bypass mode www integra ups com 1305 EPRO 1K 3K 5 ae 9 USER MANUAL EPRO 1K 3K 1KF 3KF 4 INSTALATION WARNINGS It is not allowed to connect output Neutral line to input Neutral line This practice can damage UPS This kind of damage is not covered by warranty FIG 1 NEVER CONNECT OUTPUT NEUTRAL TO INPUT NEUTRAL AC INPUT L N G PROHIBITED WARNING To avoid UPS permanent damage never connect output neutral to input neutral ADVERTENCIA Para evitar da o permanente en el UPS nunca conecte el neutro de salida al neutro de entrada For all full bridge models 1KF 3KF amp 1KF CN to 3KF CN it is not allowed to connect output Neutral to system Ground This practice will generate internal damage in the UPS In full bridge UPS outp
22. d by the product or the failure of the product to perform including any lost profits or savings or special incidental or consequential damages INTEGRA is not liable for any claim made by a third party to INTEGRA or to final user INTEGRA is not responsible for damage that occurs as a result of your failure to follow the instructions intended for this hardware product INTEGRA is not responsible for damage that occurs as a result of your failure to follow the instructions intended for this hardware product www integra ups com 1305 EPRO 1K 3K 19 aie ass USER MANUAL EPRO 1K 3K 1KF 3KF 16 REAR PANEL 1 Programable Outltes 8 RS 232 2 Standar UPS Outlets 9 SNMP Smart Port 3 AC Input 10 External Battery Connector EXBATT 4 Input Breaker 11 AC Output Terminal Block 5 RJ45 Surge Protected Sockets 12 Output Breaker 6 Emergency Power Off Connector 7 USB 13 AC Input Terminal Block 220V SCHUKO CE 7 7 120V NEMA 220V SCHUKO CE7 7 1201 NEMA lt lt ee A SS Z MS a 2 2 p a t a i A s E APT X 2 SKF CN NOTE NEMA 220V models have same rear panel than NEMA 120V models www integra ups com
23. er cord is connected into UPS Check input power cord connection 1 beep 4s however AC input source is OK E outlet UPS cannot be powered on even AC input is OK Beep alarm is active 1 beep s amp LCD shows CO EF UPS cannot be powered on even AC input is ON push button is not been selected Push ON button during 2 seconds or OK properly longer 1 beep s alarm is active and LCD shows Input Line and Neutral are swapped Rotate UPS plug at wall socket to allow A correct line neutral connection This A UP suggestion is only valid for Schuko power plug type 1 beep s alarm is active and LCD shows Internal or external batteries are not Check battery connection AN properly connected Code 27 Very high voltage at batteries or Batteries and charger must be inspected BATT FAULT charger failure by qualified personnel EPO function is active Re establish emergency power off switch and set UPS in normal mode Active Continuous beep Code 28 Very low voltage at batteries or charger Batteries and charger must be inspected failure by qualified personnel Active FAULT Continuous beep UPS overloaded Disconnect devices from UPS outlets Intermittent A OVER LOAD until solving overload 2 beeps per second UPS overloaded UPS has changed to Disconnect devices from UPS outlets Intermittent AN OVER LOAD BYPASS mode to avoid internal until solving overload 2 beeps p
24. er second damage By Pass activated After repetitive small overloads UPS Disconnect devices from UPS outlets has changed to BYPASS mode until solving overload Then power off UPS and re star again Code 43 UPS has been automatically powered Disconnect devices from UPS outlets OVER LOAD off because overload until solving overload Then power ON Active Continuous beep SHORT UPS has been automatically powered Check short circuit problem in devices Active on LCD off because short circuit detected at connected to UPS Continuous beep output Any of following codes indicated on LCD Internal Ups failure detected UPS Call service support 1 2 3 4 11 12 130 41 working in any of following modes Continuous beep 1 UPS output powered in BYPASS mode 2 UPS outlets powered off Very short backup time Batteries can be discharged because Let UPS recharge batteries during 6 recent use hours before check backup time again Battery can be degraded because long Batteries must be replaced by new lifetime batteries www integra ups com 1305 EPRO 1K 3K 17 ie Qro USER MANUAL EPRO 1K 3K 1KF 3KF 13 SOFTWARE Our control software offers huge capabilities to monitor your UPS and configure key shutdown parameters Also event and data log are available in software options Main software features are e Friendly human interface to UPS e Controlled files saving and OS shutdown when bl
25. erature type and frequency of discharging cycles Higher the temperature shorter will be the lifetime Frequent and deep discharging cycles also will short lifetime For critical applications batteries should be revised and replaced periodically Long storage longer than 6 months without required recharging will wear out batteries This situation is not covered by this limited warranty since this is not considered as a defect Check recharging instructions on user manual Conditions Limited Warranty PRO 11 1 Subject to the conditions of this limited warranty this product is warranted to be free from defects in materials and workmanship at the time of INTEGRA supplies the product n Europe warranty time is 2 years on electronic parts and 2 year on internal batteries from INTEGRA invoice date n America warranty time is 2 years on electronic parts and 1 year on internal batteries from INTEGRA invoice date standard warranty times could vary depending on country region or extended by purchasing warranty options Please check warranty conditions by country region in our web www integra ups com 2 f during the warranty period this product fails to operate under normal use and service due to defects in materials or workmanship authorized distributor or service center will at their option either repair or replace the product in accordance with terms and conditions stipulated herein Transportation expenses are not covered by this limited
26. ets 6 OPERATION This is UPS is ONLINE DOUBLE CONVERSION type and it has been designed to offer the most clear power without switching transitions or dead times In that way your hardware but also your valuable data will be safe when your PC related equipment is connected to EPRO series UPS Power output is sine wave type same as supplied by AC main source Depending of AC input source this UPS can work under one of two following modes Stand By Mode UPS goes to Stand By mode when it is just connected to AC input source BYPASS mode must not be previously activated If BYPASS is activated UPS will go to BYPASS mode just after UPS is connected to input source Normal AC Mode Online It is the default mode when AC input source is OK and ON button is selected If ON button is not selected UPS will remain in stand by mode or bypass if bypass has been configured as ENABLE Under normal online mode power output is generated by UPS inverter Inverter takes power from AC DC converter feed by AC input source AC input source is only used under this mode to recharging batteries when necessary Battery Mode Also known as Inverter Mode It is the mode when AC input source is out of range or black out is detected by the UPS Under this mode power output is generated by UPS inverter that takes power from batteries There is no dead time transition time is ZERO ms related to switching from normal mode to battery mode since load is always powered fr
27. f during ECO mode input voltage is out of acceptable input range UPS will change to normal ONLINE mode 05 Bypass Enable or Disable This function allows to enable or disable BYPASS mode If Bypass mode is enable UPS will enter in BYPASS when UPS is connected to AC input service without selecting ON push button ENA Bypass enable DIS Bypass disable 06 By Pass Input Range Configuration This function allows to set HIGH limit HLS and LOW limit LLS for BYPASS mode _ Hi limit and Low limit define the acceptable voltage input range in BYPASS mode If during BYPASS mode input voltage is out of acceptable range UPS will power off 07 Max backup Time Timer settin 10 999 To configure maximum backup time in minutes for general AC outlets This function allows to power off ALL outlets when reaching configured time even batteries charging level is above minimal Factory setting is 999 minutes 08 Bypass frequency range setting This function allows to configure HIGH limit HLS and LOW limit LLS of input FREQUENCY range in BYPASS mode If during BYPASS mode input frequency is out of acceptable range UPS will power off 09 Battery Setting AH If original batteries are replaced by different AH value user must use this menu to set the AH value of the new batteries installed 1110 Control Setting for N G Voltage This function allows UPS to control voltage between output NEUT RAL and GROUND ENA Control
28. nt AC voltage systems and offering options for AC outlets a 220V 230V 240Vac Outlets Schuko Europe Outlets NEMA countries with 220Vac in Latin America Outlets IEC b 110V 120V 127Vac Outlets NEMA for USA amp other 120Vac countries in Latin America Outlets IEC All units can work in both 50Hz and 60Hz www integra ups com 1305 EPRO 1K 3K 2 ae POSE ld USER MANUAL EPRO 1K 3K 1KF 3KF 1 SAFETY INSTRUCTIONS WARNING This product has been designed to operate safely and reliably for years Nevertheless as it is an electrical device it is required to read and understand this manual Keep manuals as references for future consults WARNING This product has been designed to be used indoors protected of water direct sun light and extreme temperatures This device must not be used outdoors close to moisture of heat sources WARNING Do not set objects on this UPS Handle with care Do not block UPS ventilation WARNING Make sure to connect this unit to proper power line according to selected model The UPS Technical Specs sticker shows power rating information DO NOT connect this UPS to any of its own power outlets WARNING UPS must be installed following instruction from this manual The manufacturer is not liable for any damage that might rise from misusing this unit or defective installation WARNING Only computer related equipment can be connected to this UPS DO NOT connect medical equipments life
29. nterference 1 Plug input AC power cord to an appropriate power outlet with Line Neutral Ground contacts e Some models come with input power cord with appropriate plug for your country e 3KVA 120V could come with input terminal block For 3KVA 120V models input cable to be connected to input Terminal Block must be AWG12 or wider for lengths shorter than 50 feet 15m Wire size is strongly affected by length and temperature Input wire must be selected and installed by qualified personnel according to local regulations 2 First time leave UPS recharging batteries during 6 hours before connecting your devices to the UPS to let batteries recover charging level to offer full battery backup time 3 Connect your devices to be protected to UPS outlets Take care to not overload UPS output by connecting devices with higher power ratings than UPS power capacity Laser printers scanners and copiers frequently have two different power ratings in stand by power ratings are very low compared with consumption rating during operation If this kind of products will be connected to the UPS operation power rating must be considering to size total power consumption to be connected to UPS 4 EPO Function Emergency Power Off function allows to power off UPS outlets when EPO input is open When EPO port is closed EPO function is disable When EPO function is activated UPS will perform following actions EPO Power Off all outlets a LN b Switch to
30. om inverter This is main characteristic of an ONLINE UPS BYPASS Mode Bypass is a working state where UPS supply outlets directly from input AC source In this mode Inverter does not supply outlets from inverter Bypass mode can be forced by user from Online mode by selecting ON amp SELECT buttons at same time during 5 minutes It can be also activated by configuring BYPASS as enable in configuration menu and connecting UPS to AC source without activating ON button Bypass mode can be also forced in automatic way by UPS in case it detects external overload or internal failure ECO Mode This UPS also offer a third operation mode name ECO MODE Under this mode selectable by LCD configuration menu UPS works as OFF LINE UPS Load is powered from AC input and UPS only switch to battery mode when input is out of range or in black out Status Transition time from ECO mode to Battery mode is not zero Typically is about 4ms that is why ECO Mode is not recommended for Critical applications www integra ups com 1305 EPRO 1K 3K 9 Qquissra USER MANUAL EPRO 1K 3K 1KF 3KF 7 OPERATION MODES AND LCD Operation Mode LCD UPS ON Input AC source OK UPS output generated by inverter ONLINE UPS in ON ECO mode activated Input AC source is OK UPS output feed from AC input to save energy UPS in ON ECO mode activated Input AC source out of acceptable range UPS output generated by inverter CF f
31. r managing high inductive loads This kind of loads generates unbalance in DC bus of UPS Error 04 Not compatible with loads based on half wave rectified power supplies They generate unbalance in UPS bus Error 04 EPRO 1KF 2KF 3KF Online double conversion UPS IGBT technology with full set of standard functions and capabilities Inverter Technology Full Bridge isolated neutral Main Features of Full Brdige UPS Output Neutral is not connected to Input Neutral in normal Online mode That generates a floating voltage between output Neutral and Ground higher than N G voltage at input side This is a perfect online UPS for PC related applications PCs Workstations Servers etc Suitable for managing high inductive loads Compatible with loads based on half wave rectified power supplies EPRO 1KF CN 2KF CN 3KF CN Online double conversion UPS IGBT technology with full set of standard functions and capabilities Inverter Technology Full Bridge Common Neutral Main Features of Full Brdige Common Neutral UPS Output Neutral is connected to Input Neutral in normal Online mode That makes voltage between output Neutral and Ground is similar to N G voltage at input side This is a perfect online UPS for PC related applications PCs Workstations Servers etc Suitable for managing high inductive loads Compatible with loads based on half wave rectified power supplies This 3 families are available for differe
32. sticated features and high reliability It works generating a high quality and uninterrupted pure sine wave output It is perfect to protect hardware and your valuable data in workstations multi PCs systems or critical servers This UPS is 10096 compatible with low quality AC input sources like those based on power plants UPS parameters can be configured either by front panel LCD or remotely by software All key system values can be also supervised by either LCD or by control software Additionally to high quality uninterrupted output this product is able to protect your hardware from electrical surges and dangerous spikes by powerful surge suppression stage based on MOV technology Output voltage or frequency can be selected according to the model In terms of communication you have a wide range of alternatives like RS 232 USB Ethernet LAN or AS 400 interface some of them are optional Please follow carefully this manual during installation configuration start up and required maintenance to enjoy of this excellent and modern UPS FRONT PANEL PUSH BUTTON FUNCTIONS nli ON MUTE OFF ENTER SELECT 1 ON MUTE a POWER ON Keep selected during 2 seconds or longer b BEEP MUTE In battery mode Keep selected during 5 seconds or longer to Mute acoustic alarm beep Some alarms cannot be muted as Bypass Warning or ERROR alarms AUTO TEST In normal mode Keep selected during 5 seconds or longer to a
33. unction enabled to generate output frequency FREQUENCY CONVERTER as selected FUNCTION When AC input source is out of range Ups goes to battery mode to supply output from taking BATTERY MODE energy from batteries If UPS is overloaded by big consuming load connected at UPS output UPS changes to BYPASS mode feeding outlets from input AC BYPASS source This mode can be set also by front panel by selecting ON MUTE SELECT at same time UPS is OFF No power in UPS outlets STAND BY Input AC source is OK Batteries are been charged MEANING www integra ups com 1305 EPRO 1K 3K 10 ae USER MANUAL 1 3 1KF 3KF 8 LCD DESCRIPTION ae A e 1 UNA 1 LI 7 Li Hz meum OUTPUT OVER 0 E13 LS u BYPASS am 5 jum t s 4 mms rr Indicates battery charging level by 4 segments bar 76 100 51 75 26 50 0 25 BATT FAULT y LOW BATT indicate abnormal battery situation Indicates UPS time under battery mode H hours M minutes S seconds Alert triangle symbol indicates alarm or error Two 2 digits code indicates error alarm code This symbol indicates buzzer alarm state active or muted Indicates power supplied by UPS by 4 segment bar 15 100 50 75 25 50 0 25 OVERLOAD SHORT indicate
34. ut Neutral is not same than input Neutral so a floating voltage will be generated between N G at output side of the UPS This voltage is not harmful for your equipment connected to UPS If you need OVac in N to G for your equipment please check recommendation of FIG 3 FIG 2 NEVER CONNECT OUTPUT NEUTRAL TO GROUND IN FULL BRIDGE UPS UPS AC INPUT L N G pa JNE A AT PROHIBITED WARNING To avoid UPS permanent damage never connect output neutral directly to ground for UPS with inverter full bridge type as 1KF 3KF amp 1KF 3KF CN ADVERTENCIA Para evitar da os permanentes en el UPS nunca conecte el neutro de salida a tierra en UPS con tecnologia de inversor full bridge como las familias 1KF 3KF amp 1KF 3KF CN www integra ups com 1305 EPRO 1K 3K 6 me 9 USER MANUAL 1K 3K 1KF 3KF If your system requires output of UPS has N G voltage close to OVac we suggest to install an isolation transformer at the UPS output Neutral line of secondary of the transformer can be connected to Ground See FIG 3 FIG 3 UPS WITH EXTERNAL OUTPUT ISOTX AC INPUT L N G INSTALATION Install this unit in any protected environment with a dust free air flow Also corrosive vapours and conductive contaminants must be avoided Do not use UPS outdoors or where either temperature or humidity exceeds tech specs Install UPS at least 10 inches away from your monitor to avoid magnetic i
35. utlets This function allows to power off ALL outlets when reaching configured time even batteries charging level is above minimal Factory setting is 999 minutes www integra ups com 1305 EPRO 1K 3K 15 ae Quiere USER MANUAL EPRO 1K 3K 1KF 3KF 10 ERROR CODES FALURE ERROR y CObE 1 0N 01 C HiBUSVotage o 1 1 O LowBUSVolagg 1 1 1 08 J BusUnlaned ee O Short circuitin BUS 05 f J Soft start Inverter Failure 11 Inverter Hi Voltage ASS ACEITE 13 Battery Very High Voltage Battery Very Low Voltage Over Temperature Overload UPS power output capacity has been exceeded Inverter cannot 43 Supply output 11 ALARMS ON LCD Overload hi power consumption detected at UPS output J mr FAN failure 1 s 1 5 P Ns gt gt 3 RARA gt gt BEEP ALARM Battery Mode 1 Beep every 4 seconds Battery Low 1 Beep per second Output Overload 2 Beeps per second UPS Failure Continuous Beep By Pass Mode 1 Beep every 10 seconds www integra ups com 1305 EPRO 1K 3K 16 gt USER MANUAL EPRO 1K 3K 1KF 3KF 12 TROUBLESHOOTING Input power cord is not connected Check input power cord connection LCD does not show input voltage value AC input failure alarm active Input pow
36. warranty 3 Warranty is valid only if the original invoice issued by INTEGRA specifying date of purchase serial number and name of the dealer is presented with the product to be revised INTEGRA and authorized partners reserve the right to refuse warranty service if any of this information has been removed changed or missing in original invoice document 4 If product is repaired or replaced repaired or replaced product will be warranted for the remaining time of the original warranty or for 90 days on repaired part from date of repair whichever is longer 5 INTEGRA or their distribution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out of warranty a reparation proposal will be sent to the user for his approval If proposal is not accepted service center will keep product available for the user during 60 continuous days After this period product would be disposed and user will not be able to rise any claim 7 Rechargeable batteries like included in this product will definitively wear out even under normal operation This is not a defect or failure so it is not covered by this warranty 8 This warranty does not cover batteries wear out caused by improper or long storage over 6 months without required recharging indicated in product manual Even performing recharging procedure this product cannot
37. ws to enable or disable BYPASS mode If Bypass mode is enable UPS will enter in BYPASS when UPS is connected to AC input service without selecting ON push button ENA Bypass enable DIS Bypass disable 06 By Pass Input Range Configuration This function allows to set HIGH limit HLS and LOW limit LLS for BYPASS mode Hi limit and Low limit define the acceptable voltage input range in BYPASS mode If during BYPASS mode input voltage is out of acceptable range UPS will power off 1305 EPRO 1K 3K 14 ae sr USER MANUAL EPRO 1K 3K 1KF 3KF MODEL EPRO 1K 1 5K 2K amp 3K screens for 230V models 120V models have their own screens showing values typical for 120V systems 101 Output Voltage Configuration Output voltage value can be selected from 4 available values For 220V Models 208V 220V 230 V or 240Vac For 120V Models 110V 115V 120V or 127Vac 7 102 CF Enable or Disable This function enables or disables Frequency Conversion function CF allows UPS to supply output with different frequency value than detected at its input CF ENA CF function enable CF DIS CF function disable 03 CF Frequency value in Hz Output frequency can be configured for battery mode BAT 50 50Hz or BAT 60 60Hz If CF function is enable output frequency can be set in normal mode CF 50 50Hz or CF 60 60Hz 04 ECO Enable or Disable This function allows to enable or disable ECO mode ENA ECO enable ON DIS
38. www integra ups com X 12V 9Ah x 8 12V 9Ah x 12 UPS status Load level Battery Input Output voltage Discharge timer and Fault conditions Estado del UPS Consumo Baterias Voltaje Entrada Salida Autonomia Diagnostico Fallas Battery Mode Low batt Overload UPS Failure Modo Bateria Baja bateria Sobrecargas Falla 1305 EPRO 1K 3K 23 afitegra USER MANUAL EPRO 1K 3K 1KF 3KF 17 ESPECIFICACIONES 1KF 2KF 3KF 1KF CN 2KF CN 3KF CN 1KF amp 1KF CN PRODUCT FEATURES CARACTERISTICAS DEL PRODUCTO 2KF amp 2KF CN SKF amp 3KF CN DxWxH Prof Ancho Altura mm 397x145x220 397x145x220 421x190x318 Net Weight Peso Neto kgs 12 17 20 UPS MODEL 230Vac EUROPE Standard Outlets Salidas Est ndar SCHUKO x 3 SCHUKO x 3 SCHUKO x 4 Prog Outlets Salidas prog N2 NA NA NA UPS MODEL 120Vac AMERICA standard Outlets Salidas Est ndar NEMA 20 x4 NEMA 20 x4 NEMA x 6 TB Prog Outlets Salidas prog N2 NA NA NA External Battery Cabinet Tower DxWxH Prof Ancho Altura NA 421x190x318 421x190x318 Net Weight Peso Neto kgs NA 29 39 PACKING EMPAQUE UPS Tower Type Unit CARTON DxWxH mm 472x230x340 472x230x340 560x320x470 Unit Gross Weight Peso Bruto Kg 13 19 30 Half Pallet Medio Pallet 30pcs 30pcs 12pcs Full Pallet Pallet Completo 50pcs 50pcs 24pcs External Battery Cabinet Unit CARTON DxWxH mm NA 560x320x470 560x320x470 Unit Gross Weight Peso Bruto Kg N
Download Pdf Manuals
Related Search
Related Contents
Pour le savoir, consultez le mode d`emploi et la liste des communes. Hotpoint 9537 Washer User Manual Black Flag HG-11036 Instructions / Assembly Poste de contrôle FireLock® I-751-FRE - Sincomavi Personal Audio System User Manual Standard Brookhouse NMEA 0183 multiplexer ISS Toolkit Philips DVD940 User's Manual Copyright © All rights reserved.