1. How many of your programmers also work in the construction department How many of your graphics developers also work in the service department Does your firm manufacture the DDC product it installs Where is the DDC product manufactured Where is the DDC product manufacturer s head office Has your firm offered DDC products from manufacturers other than the manufacturer of your current product offering How long has your firm installed the products from the manufacturer of your current DDC product offering Where is your centre for advanced user training on DDC system programming and graphics production Provide an organizational chart of your construction department Separate sheet AJA revO 4208322 Page 12
2. implemented and how they are used Describe options on how alarms are can be filtered processed and distributed Provide a screen shot of a run time totalizer showing start and stop times durations and any other features 6 F D D AND DATA ANALYTICS The City seeks to improve energy efficiency and reduce operating costs by implementing automated measures to identify mechanical system operational faults Examples of a Fault Detection and Diagnostics FDD implementation may include for example 6 1 identifying air handler operation that has not taken full advantage of free cooling identifying excessive equipment runtime beyond present daily and weekly limits Valve leak by Damper operational fault Oscillating Control Loop Setpoint out of threshold range Statistical control accuracy index for terminal equipment Data Analysis Language To carry out the various required analyses a Data Analysis Language is required 1 2 3 Provide information on the language and programming environment for constructions rules for analyzing system operation Identify the manufacturer of the Data Analytics hardware and software Describe how the system may allow queries to be performed to facilitate data analysis without the need for manual data normalization manual interpolation to compensate for missing samples different sample frequencies or different sample timing Describe how date and time formats are handled when exporting to Ex
3. Anthony Jones amp Associates Inc CONSULTANTS SOFTWARE b 5178 EOI Direct Digital Controls Systems Strategic Plan Schedule A Technical Submission City of Richmond City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan TABLE OF CONTENTS So ee eae eee eee asec ncn cera occ ec E 3 1 Company inform tlon sisri a a e a a aee iania a S RAE E 4 I Service Organizatio soss erea e E E ES 4 1 2 Construction Organization ssssssissssiissiseiiiiisesiisssnisissiren celentiaceedisatacensaccoune rassid iisi 4 2 Programming Language siseicniscencisiirissiscenrosssrissniseienpds ir ssd teser iss EPPES EEAS E aera 5 21 Exampleof TCL or BPE sorcier E A E O ea ee 5 3 BACnet Compliance sss cciseccedisicseissasendacasacseausianssalsasagoccialeoeeasiouscad sasudeed ssassoaasaansbaceuonssacvasesoaaess 6 31 DDC P nels and NetWofk ssion israr sarin ane e ER Ea Ria aah 6 3 2 BACnet Intra System Communication ccescsssecsssccssncecssceesscceessceessccesssseesnenens 6 33 Nouba Controllers BC sssrs errn e Ea 6 3 4 Advanced Application Controllers AAC ssssesesssessssseessressressersseessseerssressresseseseeesseee 7 3 5 Field devices and Smart sensors and Actuators 0 essccesceceeeeeeeeeeeceteeeeoneescetseneeners 7 3 6 Operator Workstation sseressssssnesr ose eeewiceeo epee 7 4 Trend Logsand GraphS ssssiiinsisrinoiieei aeii eisie aans iaaiiai Kea a EESE na T7 5 Scheduling Alarm
4. proposed system 3 Identify which web browsers are supported for full functionality of the design 4 Identify any Flash Multimedia or third party plug ins or software dependencies required for the full functionality of the browser interface 4 TREND LOGS AND GRAPHS In reference to B AACs 1 Identify the minimum interval that timed trend logs can be performed e g 15 seconds between samples 2 Identify how many samples can be stored locally on the AAC for each trend log 3 Identify how many trend logs can be created on each model of AAC In reference to B BCs 4 Identify the minimum interval that timed trend logs can be performed e g 15 seconds between samples 5 Identify how many samples can be stored locally on the BC for each trend log 6 Identify how many trend logs can be created on each model of BC The sample frequency and number of samples identified must assume that 1 one trend log has been implemented for each input and output 7 Provide a description on the features and usage of your historical data trend logging tool 8 Describe which formats the data can be exported in 9 Describe how historical data is stored and which query protocols are supported AJA revO Page 7 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 5 SCHEDULING ALARM PROCESSING RUN ANALYSIS Describe how normal schedules annual holiday schedules and temporary schedules are
5. 00 AM and 4 00 PM and minimum weighted space temperature MWT is more than 4 Deg C below the building objective temperature BOT then start Pump 1 P1 As soon as Pump 1 has been on for 10 minutes turn on the boiler B1 If the day of year is before July 2 then factor A is equal to 1667 July 2 day of year 1368 otherwise the factor A is equal to 1661 day of year July 2 136 If the real time is greater than 8 00 AM minus a variable times the difference between setpoint and space temperature and if the real time is less than 3 30 PM and if outside air temperature is less than 10 Deg C then enable boiler 3 BACNET COMPLIANCE 1 3l Identify which of the BACnet Device Profiles are provided by the manufacturer of the proposed DDC system DDC Panels and Network Submit technical specifications for all Building Controllers B BC Advanced Application Controllers B AAC Application Specific Controllers B ASC Operator Workstations B OWS Advanced Operator Workstations AWS Operator Display B OD and other BTL Listed products offered by the manufacture of the proposed DDC system Include BACnet Protocol Implementation Conformance Statements PICS per Annex A of ANSI ASHRAE Standard 135 for all proposed components 3 2 BACnet Intra System Communication Describe if and how gateways are implemented in a typical network structure Describe BACnet protocols implemented over Ethernet for each Devic
6. Processing Run Analysis c ccceesceeesececeeececeeeeeceeeeeceeeeecseeessteeeesaes 8 6 F D D and Data Amallytics 0 0c ccc ceccccccesseceeseeesssecesssecssssecnessecseseecsaeecseseecseeeesseeeesaes 8 6 1 Data Analysis Language ssssessssessserssssessssssrssessserseesresseessrssessesssesesseesssesruseessersoesresses 8 6 1 1 Sample Analysis teesin desserer asarre OES eS EEEE ETES EEES EERS EEE 9 App ndix Poms for Part isa e acess enadeexvdeadsteoiuedquauceacesseneeasenededcuuesceuaaatuanesedumadaansdeatmeuduaas 10 6 2 Service Organization MOM 5 c sciets doststesepaa taetaneismpuds io egacssrcse ead eerste ewes 11 6 3 Construction Organization POI siscscccsdeseccnnssacsscasnsesenaseancaaeseacdoaseosasdcassarisanieaesversasadeatees 12 AJA revO Page 2 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan TECHNICAL SUBMISSION The Technical Submission for this Expression of Interest EOI is to include the following Sections titled and ordered as follows Section Description Organization Forms Service and Construction Use forms provided Section 2 Programming Language Example Include screen shots of the completed program sample implemented in the programming environment Section 3 BACnet Compliance Include a drawing of a sample network and provide manufacturer s PICS statements for each proposed component Section 4 Trend Capabilities Section 5 Sche
7. ber of service trucks in Metro Vancouver Name and telephone number of Controls Service Manager How are normal service requests handled Where is service dispatch office located How are after hours service requests handled Where is after hours service dispatch office located What is the service rate for DDC controls service during normal hours What is the service rate for DDC controls service for after hours What is your usual on site response time during normal hours What is your usual on site response time for after hours What is your hourly charge for remote Internet accessed service How many staff do you have dedicated to service sales Provide an organizational chart of your construction department Provide separate sheet AJA revO 4208322 Page 11 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 6 3 Construction Organization Form How many years experience does your local firm installing DDC System Technology In the last five years only in how many buildings has your firm installed DDC systems with a minimum of 200 hardware points per building How many programmers do you currently have on staff How many graphic developers do you currently have on staff How many construction electricians do you have on staff on average What are the terms of your standard product warranty
8. cel AJA revO Page 8 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 1 Provide screen shots of the symbolic or textual language and programming environment to implement the following analysis Use the following Data Inputs Outdoor air temperature OAT Average Perimeter Space Temperature STPAVG Air handler electrical current SFAMPS Perform the Following Bin Analysis Create OAT bin of 3 C starting at minus 3 0C to 30C Create Time of Day bins of one hour with 24 per day Take Average of operating fan current for each cross section of OAT and hourly bins Segregate Tuesday to Friday Saturday Sunday and Monday into four groups Prepare the Following Analysis Output or Similar Provide a graphical report showing average operating fan current by hour of day during Tuesdays to Fridays for each of the 27 OAT bins Provide a family of line graphs with hourly bins on the abscissa and average amps on the ordinate Each line graph is for an outdoor temperature bin AJA revO Page 9 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan APPENDIX FORMS FOR PART 1 AJA rev0 Page 10 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 6 2 Service Organization Form Number of mechanical service trucks in Metro Vancouver Number of DDC controls service trucks in Metro Vancouver Total num
9. duling Alarm Processing Run Analysis Section 6 FDD and Data Analytics Example Include screen shots of analysis environment showing sample analysis Section 7 Other Information as Desired by Respondent This could include information on lighting controls wireless devices etc e Submissions should include all Sections except Section 7 e Each Section to start at the top of a new page e The information requests in each Section are numbered Submissions should include a response to each numbered information request Each response should be provided in the order requested and should be identified with the item number Supporting brochures may be provided at the end of each Section if desired but should not separate the numbered responses e Submission should be delivered according to the method and format identified in any general conditions identified in the EOI AJA revO Page 3 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 1 COMPANY INFORMATION 1 1 Service Organization 1 2 Number of mechanical service trucks in Metro Vancouver Number of DDC controls service trucks in Metro Vancouver Total number of service trucks in Metro Vancouver Name and telephone number of Controls Service Manager How are normal service requests handled Where is service dispatch office located How are after hours service requests handled Where is after hours service dispatch office loca
10. e Profile offered Describe any limitations to functionality such as graphics editing and sequence of operation programming that are imposed when using the browser interface Provide a sample Network Architecture drawing that shows vendors complying panel types model numbers network connection network speed and protocol and sample point count ee Building Controllers BC 1 Verify that the proposed B BC conforms to BACnet Building Controller B BC device profile as specified in ANSI ASHRAE 135 BACnet Annex L and is listed as a certified B BC in the BACnet Testing Laboratories BTL Product Listing AJA revO Page 6 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 2 Describe where B BCs would typically be applied 3 4 Advanced Application Controllers AAC 1 Verify that the proposed B AAC conforms to BACnet Advanced Application Controller B AAC device profile as specified in ANSI ASHRAE 135 BACnet Annex L and is listed as a certified B AAC in the BACnet Testing Laboratories BTL Product Listing 2 Describe where B AACs would typically be applied 3 5 Field devices and Smart sensors and Actuators 1 Provide technical specifications for input and output field devices generally installed with the proposed system 3 6 Operator Workstation 1 Provide technical literature on the operator workstation 2 Provide PICS for the proposed B OWS B AWS and or B OD for the
11. ere is your centre for advanced user training on DDC system programming and graphics production Provide an organizational chart of your construction department AJA revO 4208322 Page 4 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan 2 PROGRAMMING LANGUAGE A textual programming language is defined herein to be comprised solely of ASCII characters numbers decimals mathematical operators Boolean operators and hierarchal designations A Block programming language is defined herein to be comprised or partially comprised of geometric shapes connected by lines to indicate calculations and program flow 1 Describe the general form of the user programming language such as Textual or Block 2 Briefly describe the programming environment that the City will use to create sequences of operation Provide a screen shot of the programming environment which will be used by the City 4 Upon request the submitter shall provide within 36 hours from request a web link to a functioning programming environment to allow the City to evaluate all aspects of the programming language and the software development environment for up to a two week period Provide Microsoft Remote Desktop access if the programming environment is not accessible through a Browser 5 Describe where the TCL or BPL programming language is stored and executed in both the case of the BC and AAC 6 Describe capabilities and limitations of
12. performing calculations using variables and points from multiple panels connected by the network 7 For TCL programming describe how nested IF THEN ELSE statements are constructed 8 Identify the location of your facilities where training in DDC sequence of operation programming graphics production and system operation will be performed 9 Identify licensing costs per seat for the programming language and environment 10 Identify costs per seat for the BOWS software license 11 Provide a soft copy of the programming language user s manual oad 2d Example of TCL or BPL 1 Provide the Textural Control Language TCL or Block Programming Language BPL code example with your submission to carry out the example strategy Provide this example code for each panel programming language and identify which panel model numbers use which language example Demonstrate precisely how the Control Language would be utilised to implement the following strategy Calculate the Minimum Weighted Temperature MWT by measuring 24 space temperature ST1 to ST24 Discard the four lowest space temperatures Take the 5th lowest space temperature STL5 Take the average of the balance of the 19 space temperatures sensors and multiply it by 0 66 STLAVG Calculate MWT by adding 33 of STLS and 66 STLAVG AJA revO Page 5 4208322 City of Richmond 5178 EOI Direct Digital Controls Systems Strategic Plan If real time RT is between 8
13. ted What is the service rate for DDC controls service during normal hours What is the service rate for DDC controls service for after hours What is your usual on site response time during normal hours What is your usual on site response time for after hours What is your hourly charge for remote Internet accessed service How many staff do you have dedicated to service sales Provide an organizational chart of your construction department Construction Organization How many years experience does your local firm installing DDC System Technology In the last five years only in how many buildings has your firm installed DDC systems with a minimum of 200 hardware points per building How many programmers do you currently have on staff How many graphic developers do you currently have on staff How many construction electricians do you have on staff on average What are the terms of your standard product warranty How many of your programmers also work in the construction department How many of your graphics developers also work in the service department Does your firm manufacture the DDC product it installs Where is the DDC product manufactured Where is the DDC product manufacturer s head office Has your firm offered DDC products from manufacturers other than the manufacturer of your current product offering How long has your firm installed the products from the manufacturer of your current DDC product offering Wh