Home

Micro Motion® 9739 MVD Transmitters Configuration and Use Manual

image

Contents

1. A PC B HART interface c 250 600 Q resistance D Transmitter Notes e This figure shows a serial port connection A USB port connection is also available 2 To connect to a point in the local HART loop attach the leads from the signal converter to any point in the loop and add resistance as necessary See Figure 3 3 ProLink IlI must be connected across a resistance of 250 600 Q 30 Micro Motion 9739 MVD Transmitters Quick start with ProLink II Figure 3 3 ProLink Il connection to local HART loop N Ap Ei KKE 5 26 27 A PC B HART interface C Any combination of resistors R1 R2 and R3 as necessary to meet HART communication resistance requirements D DCS or PLC E Transmitter Notes e This figure shows a serial port connection A USB port connection is also available 3 To connect to a point in the HART multidrop network attach the leads from the signal converter to any point in the loop and add resistance as necessary See Figure 3 4 ProLink II must be connected across a resistance of 250 600 Q Configuration and Use Manual 31 Quick start with ProLink II Figure 3 4 ProLink II connection to multidrop network D ee z A HART interface to PC B 250 600 Q resistance C Devices on the network D Master device Notes e This figure shows a seria
2. Procedure Set Frequency Output Maximum Pulse Width as desired The default value is 277 milliseconds You can set Frequency Output Maximum Pulse Width to 0 milliseconds or to a value between 0 5 milliseconds and 277 5 milliseconds The transmitter automatically adjusts the value to the nearest valid value Tip Micro Motion recommends leaving Frequency Output Maximum Pulse Width at the default value Contact flow support emerson com before changing Frequency Output Maximum Pulse Width 7 2 3 Configure Frequency Output Polarity Display OFF LINE MAINT OFF LINE CONFG IO FO POLAR ProLink II ProLink Configuration Frequency Freq Output Polarity Field Communicator Configure Manual Setup Inputs Outputs Frequency Output FO Settings FO Polarity Frequency Output Polarity controls how the output indicates the ON active state The default value Active High is appropriate for most applications Active Low may be required by applications that use low frequency signals Configuration and Use Manual 127 Integrate the meter with the control system Procedure Set Frequency Output Polarity as desired The default setting is Active High Options for Frequency Output Polarity Options for Frequency Output Polarity are shown in Table 7 6 Table 7 6 Options for Frequency Output Polarity Polarity Reference voltage OFF Pulse voltage ON Active High As determined by power supply pull up resisto
3. gt Analog output Frequency Primary secondary output Tertiary variable PV SV is Scaling method Lower range value Freq factor Upper range value Rate factor AO cutoff Pulses per unit AO added damp Units per pulse LSL Freq pulse width USL Last measured value timeout Min span Freq fault action AO fault action Freq output polarity AO fault level Last measured value timeout Discrete output Discrete input Sensor simulation Discrete output Assignment Enable disable DO1 assignment Polarity DO1 polarity Mass flow DO1 fault action Wave form Fixed value Period Minimum Maximum Density Wave form Fixed value Period Minimum Maximum Temperature Wave form Fixed value Period Minimum Maximum 234 Micro Motion 9739 MVD Transmitters Using ProLink II with the 9739 MVD transmitter Figure D 4 Configuration menu continued ProLink gt Configuration Special units Sensor Events Discrete events Base mass unit Sensor s n Event 1 2 Event name Base mass time Sensor model Variable Event type Mass flow conv fact Sensor matl Type Process variable Mass flow text Liner matl Setpoint Low setpoint A Mass total text Flange High setpoint B Base vol unit Base vol time Gas Vol flow conv fact Gas Vol flow text Gas Vol total text Polled variables Variable mapping Alarm System
4. Polled variable 1 2 PVis Alarm W amp M approval Polling control SVis Severity Reset options External tag TVis Variable type QVis Current value Configuration and Use Manual 235 Appendix E Using the Field Communicator with the 9739 MVD transmitter Topics covered in this appendix Basic information about the Field Communicator Menu maps for the Field Communicator E 1 Basic information about the Field Communicator The Field Communicator is a handheld configuration and management tool that can be used with a variety of devices including Micro Motion transmitters It provides complete access to transmitter functions and data Field Communicator documentation Most of the instructions in this manual assume that you are already familiar with the Field Communicator and can perform the following tasks Turn on the Field Communicator e Navigate the Field Communicator menus e Establish communication with HART compatible devices e Send configuration data to the device e Use the alpha keys to enter information If you are unable to perform these tasks consult the Field Communicator manual before attempting to use the Field Communicator The Field Communicator manual is available on the Micro Motion documentation CD or the Micro Motion web site Field Communicator device descriptions DDs In order for the Field Communicator to work with your device the appropriate device description DD
5. If the Severity is Information or Ignore outputs are not affected They continue to report process data 160 Micro Motion 9739 MVD Transmitters Transmitter operation When the transmitter detects that the alarm condition has cleared e First status flag is set to Inactive Second status flag is unchanged Unacknowledged e For Fault alarms only Outputs return to reporting process data Operator action is required to change the second status flag however alarm acknowledgement is not necessary 8 5 Start and stop totalizers and inventories Display See Section 8 5 1 ProLink Il ProLink Totalizer Control Start ProLink Totalizer Control Stop Stop Totalizers Field Communicator Service Tools Variables Totalizer Control All Totalizers Start Totalizers Service Tools Variables Totalizer Control All Totalizers Stop Totalizers 8 5 1 Start and stop totalizers and inventories using the display Prerequisites To start and stop the totalizers and inventories using the display this feature must be enabled Procedure e To stop all totalizers and inventories using the display a Scroll until the word TOTAL appears in the lower left corner of the display Important Because all totalizers are started or stopped together it does not matter which total you use to start or stop the totalizers Select Scroll until STOP appears beneath the current totalizer value Select Select again to
6. A le Micro Motion WH EMERSON Process Management
7. Configuration and Use Manual 27 Quick start with ProLink Il Figure 3 1 ProLink II connection to service port A PC B 25 to 9 pin adapter if necessary or RS 232 to USB adapter if necessary C RS 232 to RS 485 signal converter D Transmitter Notes e This figure shows a serial port connection A USB port connection is also available 4 Start ProLink Il Choose Connection Connect to Device 6 Set Protocol to Service Port Tip Service port connections use standard connection parameters and a standard address You do not need to configure them here 7 Set the COM Port value to the PC COM port that you are using for this connection 8 Click Connect If the connection is successful e The status bar in the main window is updated to show an active connection e The Process Variables window or Commissioning Wizard window is displayed 28 Micro Motion 9739 MVD Transmitters Quick start with ProLink Il If an error message appears e Switch the leads and try again Ensure that you are using the correct COM port e Check the physical connection between the PC and the transmitter 3 2 3 Make a HART Bell 202 connection Prerequisites You will need the following e An installed licensed copy of ProLink II An available serial or USB port One of the following types of signal converters RS 232 to Bell 202 signal converter USB to Bell 202 signal con
8. To set the meter factor using the display OFF LINE MAINT CONFG UNITS MTR F To set the meter factor using ProLink Il ProLink Configuration Flow e To set the meter factor using the Field Communicator Configure Manual Setup Measurements Flow 9 3 Perform a standard D1 and D2 density calibration Density calibration establishes the relationship between the density of the calibration fluids and the signal produced at the sensor Density calibration includes the calibration of the D1 low density and D2 high density calibration points You can calibrate for density using ProLink II or the Field Communicator Important Micro Motion flowmeters are calibrated at the factory and normally do not need to be calibrated in the field Calibrate the flowmeter only if you must do so to meet regulatory requirements Contact Micro Motion before calibrating the flowmeter Tip Micro Motion recommends using meter validation and meter factors rather than calibration to prove the meter against a regulatory standard or to correct measurement error 168 Micro Motion 9739 MVD Transmitters Measurement support 9 3 1 Perform a D1 and D2 density calibration using ProLink Il Prerequisites e During density calibration the sensor must be completely filled with the calibration fluid and flow through the sensor must be at the lowest rate allowed by your application This is usually accomplished by closing the shutoff valve
9. ACK ALL Yes No lt No Active unacknowledged alarms Yes No 2T Csa OO Oak Yes No Select Scroll 8 4 2 View or acknowledge status alarms with ProLink II You can view or acknowledge alarms two ways using the Status window or the Alarm Log window You can view alarms in both windows but you cannot acknowledge alarms from within the Status window You must view alarms in the Alarm Log window to acknowledge the alarm Configuration and Use Manual 159 Transmitter operation Procedure To view the current status of all possible alarms select ProLink Status To view status indicators in an alarm category click on one of three tabs in the Status window Critical Informational or Operational The Status window displays the current status of all possible alarms including Ignore alarms on the three panels A tab is red if one or more status indicators in that category is on e A green LED indicates an Inactive alarm e A red status indicator indicates an Active alarm To view and acknowledge active and inactive Fault and Information alarms select ProLink lt Alarm Log To acknowledge an alarm check the ACK check box The transmitter automatically filters out Ignore alarms Entries in the alarm log are divided into two categories High priority and Low priority These priorities correspond to the default severity levels for the type of alarm Within each category e A red LED in
10. Done Done 9 5 Perform temperature calibration Temperature calibration establishes the relationship between the temperature of the calibration fluids and the signal produced by the sensor Prerequisites The temperature calibration is a two part procedure temperature offset calibration and temperature slope calibration The two parts must be performed without interruption in the order shown Make sure that you are prepared to complete the process without interruption You must use ProLink II to calibrate for temperature 174 Micro Motion 9739 MVD Transmitters Measurement support Important Consult Micro Motion before performing a temperature calibration Under normal circumstances the temperature circuit is stable and should not need an adjustment Procedure See Figure 9 5 for the procedure to perform a temperature calibration using ProLink II Figure 9 5 Temperature calibration using ProLink II Temperature Offset calibration Temperature Slope calibration Fill sensor with low Fill sensor with high temperature fluid temperature fluid Wait until sensor achieves Wait until sensor achieves thermal equilibrium thermal equilibrium ProLink Menu gt ProLink Menu gt Calibration gt Calibration gt Temp offset cal Temp slope cal Enter temperature of low Enter temperature of high temperature fluid temperature fluid Calibration in Progress Calibration in Progress light turns red light turns red
11. eee cee cece cece cence cence cee eeeeeeeeeeaeeeeaeeeeeaeeeeaeeeeeaeeeeaaeeeseeeeeas 41 3 5 Perform a loop t St iraisser taneazers viaeaonv aad aaanns RENAA 41 3 6 Trim MA outputs 0 2 cc ccc ee cee ceee eee eee tett cece eee cate ee ce eeecaeeeeaaeeecaeeeeaeeeesaeeeeaeeeesaeees 43 3 7 Z ra the MOWIMELESN sais caus ioe deeeee dws dees boas cease dene aar A EAEE Ea N ENAA 43 3 8 Test or tune the system using sensor simulation 2 0 0 eeeeeeeteeeeeeeeaneeeees 44 3 9 Back up transmitter Configuration ceecceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaaaeeeeeeaaeees 46 3 10 Enable disable HART security ccc eee ee ee te etter teeter eee aa tree ee aaaeeeeeeiaeeeeeeeaa 47 Chapter 4 Quick start with the Field Communicator cccccccsccececececccececccececescssscsssscesscess 49 4 1 Apply pOWET eee 49 4 2 Connect with the Field Commu nicator c cceeeeeeeeeeeeeeeeeeeeeaeeeeeeeeeeaaes 49 4 3 Configuration tips and tricks 0 0 cece cece eeeee cece ee eeeeeeeaaeeeeeeeaaeeeeeeeaaeeeeeaaaeeeees 52 4 4 Configure the primary mA output to report mass flow rate in a user selected Measurement Unit ecceeee ce eeee cence ee eee cee ence ae ee eeaeeeeaeeeeeaeeeeseeeeeaeeeeaeeeesseeeeas 53 4 5 PertormailoOp test errietan ete bedvad cease a E EEE EAA OE 54 4 6 Trim MA outputs esnneeneenesee cece eee eee ee cece eee ttt cece eee SEESE EESE E EAEE EEEE EEEE EE EEEE EEn 55 4 7 Z to the MOWIMCLESM sersa
12. receiving device Check flow direction See Section 10 22 Bad output circuit Verify that the receiving device and the Incorrect internal external power wiring between the transmitter and the configuration receiving device Incorrect pulse width configuration Verify which wiring terminals are configured for frequency output Output not powered Perform a loop test Wiring problem Verify that the power configuration for the frequency output internal vs external Check the pulse width See Section 10 20 Configuration and Use Manual 189 Troubleshooting Table 10 7 Frequency output problems and recommended actions continued Problem Possible causes Recommended actions Consistently incorrect frequency F measurement Incorrect flow measurement unit Section 10 20 configured e Verify that the measurement units are configured correctly for your application pine Beueney RF radio frequency interference e Check for radio frequency interference output i from environment See Section 10 12 10 8 Use sensor simulation for troubleshooting e Output not scaled correctly Check the frequency output scaling See You can use sensor simulation to help distinguish between legitimate process noise and externally caused variation For example consider a receiving device that reports an unexpectedly erratic flow value If sensor simulation is enabled and the observed flow rate does not match the simulated value the sou
13. increase the distance between the pump and sensor Drive board or module failure Erratic drive gain Table 10 9 Possible causes and recommended actions for erratic drive gain Possible cause Recommended actions Wrong K1 characterization constant for sensor Verify the K1 characterization parameter Polarity of pick off reversed or polarity of drive reversed Contact Micro Motion Slug flow Check for slug flow See Section 10 24 Foreign material caught in flow tubes e Purge the flow tubes e Replace the sensor 10 25 1 Collect drive gain data Prerequisites You will need either ProLink II or a Field Communicator to collect the drive gain data 196 Micro Motion 9739 MVD Transmitters Troubleshooting Procedure 1 Navigate to the drive gain data e If you are using ProLink II choose ProLink Diagnostic Information e If you are using a Field Communicator choose 3 Service Tools 4 Maintenance 5 Diagnostic Variables 2 Observe and record drive gain data over an appropriate period of time under a variety of process conditions 10 26 Check the pickoff voltage Collecting pickoff voltage data To know whether your pickoff voltage is unusually low you must collect pickoff voltage data during the problem condition and compare it to pickoff voltage data from a period of normal operation Table 10 10 Possible causes and recommended actions for low pickoff voltage Faulty wiring runs between the sensor and tr
14. Activate Scroll Select Scroll This operator sequence is a safety precaution designed to protect the transmitter from accidental configuration changes caused by unintentional activation of the off line menu Important If you have enabled a display password the Scroll Select Scroll operator sequence is disabled You are required to enter a password before you can continue The default password is 1234 Activate Scroll until OFF LINE CONFG appears on the display then activate Select 2 Set Mass Flow Measurement Unit as desired d When COMFIG UNITS appears on the display activate Select When UNITS MASS appears on the display activate Select Activate Scroll to view the options for Mass Flow Measurement Unit When you see the measurement unit you want to use activate Select If STORE YES flashes on the display activate Select Activate Scroll until UNITS EXIT appears on the display then activate Select 3 Set mA Output Process Variable to Mass Flow Rate a b c d Activate Scroll until CONFIG IO appears on the display then activate Select When AO 1 appears on the display activate Select When AO 1 SRC appears on the display activate Select Activate Scroll to view the options for mA Output Process Variable options When you see MFLOW activate Select If STORE YES flashes on the display activate Select 4 Set Lower Range Value LRV Micro Motion 9739 MVD Transmitters Quick start with the displ
15. Field Communicator Configure Manual Setup nputs Outputs Discrete Output The discrete output is used to report specific flowmeter or process conditions The discrete output parameters control which condition is reported and how it is reported Configuration and Use Manual 129 Integrate the meter with the control system The discrete output parameters include e Discrete Output Source e Discrete Output Polarity e Discrete Output Fault Action e Discrete Output Power Source Postrequisites Important Whenever you change a discrete output parameter verify all other discrete output parameters before returning the flowmeter to service In some situations the transmitter automatically loads a set of stored values and these values may not be appropriate for your application 7 3 1 Configure Discrete Output Source Display OFF LINE MAINT OFF LINE CONFG I0 DO SRC ProLink II ProLink Configuration Discrete Output Discrete Output DO Assignment Field Communicator Configure Manual Setup lnputs Outputs Discrete Output DO Assignment Discrete Output Source controls which flowmeter condition or process condition is reported via the discrete output Procedure Set Discrete Output Source to the desired option The default setting for Discrete Output Source is Flow Direction Options for Discrete Output Source Options for Discrete Output Source are shown in Table 7 8 Table 7 8 Options for Discrete O
16. Flow Volume Flow Unit Volume Flow Measurement Unit specifies the unit will be used for the volume flow rate The unit used for the volume total and the volume inventory is derived from this unit Prerequisites Before you configure Volume Flow Measurement Unit be sure that Volume Flow Type is set to Liquid Procedure Set Volume Flow Measurement Unit to the desired unit The default setting for Volume Flow Measurement Unit is L s liters per second Tip If the measurement unit you want to use is not available you can define a special measurement unit Options for Volume Flow Measurement Unit for liquid applications The transmitter provides a standard set of measurement units for Volume Flow Measurement Unit plus one user defined special measurement unit Different communications tool use different labels for the units Options for Volume Flow Measurement Unit are shown in Table 5 2 70 Micro Motion 9739 MVD Transmitters Configure process measurement Table 5 2 Options for Volume Flow Measurement Unit for liquid applications Label Unit description ProLink Il Cubic feet per second ft3 sec Cubic feet per minute ft3 min Cubic feet per hour ft3 hr Cubic feet per day ft3 day Cubic meters per second m3 sec Cubic meters per minute m3 min Cubic meters per hour m3 hr Cubic meters per day m3 day U S gallons per second US gal sec U S gallons per minute US gal min U S gallons per hour US gal hr U S gallons per day U
17. Make a connection from ProLink II to your transmitter 2 Choose ProLink Configuration Device Restore Factory Configuration 3 In the Configuration window click the Device tab 40 Micro Motion 9739 MVD Transmitters Quick start with ProLink II 4 Click Restore Factory Configuration 5 Click OK 3 4 Configure the primary mA output to report mass flow rate in a user selected measurement unit This procedure shows you how to perform these tasks using ProLink II For all other configuration tasks including other options for the mA output see the configuration sections of this manual Note This procedure assumes that you are starting from the factory default configuration Procedure 1 Start ProLink II and connect to your transmitter 2 Set the measurement unit for mass flow rate a Choose ProLink Configuration b In the Configuration window click the Flow tab c Select a measurement unit from the Mass Flow Units list then click Apply 3 Configure the mA output In the Configuration window click the Analog Output tab Select Mass Flow Rate from the Primary Variable Is list c Enter appropriate values for Lower Range Value LRV and Upper Range Value URV Lower Range Value specifies the value of Mass Flow Rate to be represented by an output level of O mA or 4 mA Upper Range Value specifies the value of Mass Flow Rate to be represented by an output level of 20 mA Click OK to apply the changes and close the
18. Manual Setup Inputs Outputs Discrete Output Flow Switch Setpoint Flow Switch is used to indicate that the flow rate measured by the configured flow variable has dropped below the configured setpoint The flow switch is implemented with a user configurable hysteresis Procedure 1 Set Discrete Output Source to Flow Switch if you have not already done so 2 Set Flow Switch Variable to the flow variable that will be used to control the flow switch 3 Set Flow Switch Setpoint to the flow rate below which you want the flow switch to turn on 4 Set Hysteresis to the percentage of variation above and below the setpoint that will operate as a deadband Hysteresis defines a range around the setpoint within which the flow switch will not change The default is 5 The valid range is 0 1 to 10 5 If you assign flow switch to the discrete output you must also configure Flow Switch Variable Flow Switch Setpoint and Hysteresis 6 If your transmitter is configured with two discrete outputs you can assign flow switch to both of them However they will share the settings for Flow Switch Variable Flow Switch Setpoint and Hysteresis Configuration and Use Manual 131 Integrate the meter with the control system Example For example if Flow Switch Setpoint 100 g sec and Hysteresis 5 and the flow rate drops below 95 g sec the discrete output will turn ON It will stay ON until the flow rate rises above 105 g sec At this
19. Table C 2 Display codes for process variables meo wees SC CS C SSSSCSCSCS S SCSSSCSC d or _ Boerstenpere SSSSCSCSC SCSCSCSCSCSCSS CO ear emase SSSSCSC C SCSCSSSSSSSCSCSCSCS SCSCS CAE C SSSS Sid SSCS Configuration and Use Manual 219 Using the transmitter display Table C 2 Display codes for process variables continued Gas standard volume inventory PO Gas standard volume total PO Case temperature T Series sensors only Pp NET M Net mass flow rate Concentration measurement application only NET V Net volume flow rate Concentration measurement application only NETMI Net mass inventory Concentration measurement application only NETVI Net volume inventory Concentration measurement application only PWRIN Input voltage Refers to power input to the core processor RDENS Density at reference temperature Concentration measurement application only RPO_A Right pickoff amplitude SGU Specific gravity units ee STD V Standard volume flow rate Concentration measurement application only STDVI Standard volume inventory Concentration measurement application only TCDENS Temperature corrected density Petroleum measurement application only TCORI Temperature corrected inventory Petroleum measurement application only TCORR Temperature corrected total Petroleum measurement application only TCVOL Temperature corrected volume Petroleum measurement application only C 4 Codes and abbrev
20. The density of the D3 fluid may be either greater or less than the density of water e For D4 density calibration the D4 fluid must meet the following requirements Minimum density of 0 6 g cms Minimum difference of 0 1 g cm between the density of the D4 fluid and the density of the D3 fluid The density of the D4 fluid must be greater than the density of the D3 fluid Minimum difference of 0 1 g cm3 between the density of the D4 fluid and the density of water The density of the D4 fluid may be either greater or less than the density of water Before performing the calibration record your current calibration parameters If the calibration fails restore the known values Configuration and Use Manual 173 Measurement support Procedure To perform a D3 calibration or D3 and D4 calibration see Figure 9 4 Figure 9 4 D3 or D3 and D4 density calibration using the Field Communicator D3 calibration D4 calibration Clase shutoff valve Fill sensor with D3 fluid Fill sensor with D4 fluid downstream from sensor On Line Menu gt Service Tools gt Service Tools gt Maintenance gt Maintenance gt Density Calibration Density Calibration Dens Pt 3 T Series Calibration method Calibration method executes executes Enter density of D4 fluid Enter density of D3 fluid Calibration in Progress Calibration in Progress message message Density Calibration Density Calibration Complete message Complete message
21. To connect directly to the transmitter connect the leads on your signal converter to terminals 26 RS 485 A and 27 RS 485 B on your transmitter See Figure 3 5 Figure 3 5 ProLink II connection to transmitter terminals A PC B 25 to 9 pin adapter if necessary C RS 485 to RS 232 signal converter D Transmitter 4 To connect to a point in the RS 485 network connect the leads on your signal converter to any point in the network and add resistance as necessary See Figure 3 6 34 Micro Motion 9739 MVD Transmitters Quick start with ProLink II Figure 3 6 ProLink II connection to an RS 485 network using HART PC 25 to 9 pin adapter if necessary RS 485 to RS 232 signal converter 120 Q 1 2 watt terminating resistors at both ends of the segment if necessary DCS or PLC Auto detect communication moe nm w gt Transmitter Notes e This figure shows a serial port connection A USB port connection is also available 5 To connect to a point in a multidrop network attach the leads from the signal converter to any point in the wire See Figure 3 7 Configuration and Use Manual 35 Quick start with ProLink Il Figure 3 7 ProLink II connection to a multidrop network A HART interface to PC B Devices on the network C Master device Start ProLink Il Choose Connection Connect to Device If necessary set
22. You can configure the speed of the transmitter s response to changes in process data The following parameter is used to control the speed of the transmitter s response e Response Time 6 4 1 Configure Response Time Display Not available ProLink II ProLink Configuration gt Device Response Time Field Communicator Not available Response Time controls the rate at which the transmitter updates its outputs to reflect changes in process data Procedure Set Response Time as desired Normal default Transmitter outputs track process data at the standard speed Special Transmitter outputs track process data as fast as possible Tip If you set Response Time to Special additional process noise will be present in the transmitter outputs Configuration and Use Manual 107 Configure device options and preferences 6 5 Configure alarm handling Display Not available ProLink II ProLink Configuration Alarm Field Communicator Configure Alert Setup Alert Severity Alarm handling parameters control the transmitter s response to a variety of process and device conditions Alarm handling parameters include e Fault Timeout e Status Alarm Severity 6 5 1 Configure Fault Timeout Display Not available ProLink II ProLink Configuration Alarm Alarm Field Communicator Configure Alert Setup lt Alert Severity Fault Timeout For certain alarms only Fault Timeout cont
23. condition tied to DO is false the circuit provides a pull up to a site specific voltage to a maximum of 30 V 132 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system 7 3 3 Configure Discrete Output Fault Action Display Not available ProLink II ProLink Configuration Discrete Output Discrete Output DO Fault Action Field Communicator Configure Manual Setup nputs Outputs Discrete Output DO Fault Action Discrete Output Fault Action controls the behavior of the discrete output if the transmitter encounters an internal fault condition Note If Last Measured Value Timeout is set to a non zero value the transmitter will not implement the fault action until the timeout has elapsed Ad Do not use Discrete Output Fault Action as a fault indicator Because the discrete output is always ON or OFF you may not be able to distinguish its fault action from its normal operating state Procedure Set Discrete Output Fault Action as desired The default setting is None Options for Discrete Output Fault Action Options for Discrete Output Fault Action are shown in Table 7 10 Table 7 10 E for Discrete Output Fault Action OoOo ode OS Discrete output behavior Field Communi ProLink II cator Polarity Active High Polarity Active Low Ups ale Upscale Fault discrete output is ON Fault discrete output is OFF site specific voltage 0 V No fault discrete output is No fault d
24. contact flow support emerson com Procedure 1 Enable pressure compensation 2 Enter Flow Factor for your sensor Flow Factor is the percent change in the flow rate per PSI Flow Factor for your sensor is provided on the sensor product data sheet When entering the value reverse the sign Example If the flow factor is 0 000004 per PSI enter 0 000004 per PSI 3 Enter Density Factor for your sensor Density Factor is the change in fluid density in g cm PSI Density Factor for your sensor is provided on the sensor product data sheet When entering the value reverse the sign Example If the density factor is 0 000006 g cm PSI enter 0 000006 g cm3 PSI 4 Enter Calibration Pressure for your sensor 90 Micro Motion 9739 MVD Transmitters Configure process measurement Calibration Pressure is the pressure at which your sensor was calibrated and therefore defines the pressure at which there will be no pressure effect Calibration Pressure for your sensor is provided on the sensor calibration sheet If the data is unavailable enter 20 PSI 5 Decide how pressure data will be provided to the transmitter and perform the required setup e If you will poll an external pressure device set up polling for pressure e If you will use a static pressure value set Pressure Units to the units you are using enter External Pressure and ensure that polling for pressure is disabled e If you will use digital communications or a d
25. must be installed The 9739 MVD transmitter requires the following HART device description DD v2 To view the device descriptions that are installed on your Field Communicator 1 At the HART application menu press Utility Available Device Descriptions 2 Scroll the list of manufacturers and select Micro Motion then scroll the list of installed device descriptions If Micro Motion is not listed or you do not see the required device description download the appropriate device description from the Micro Motion web site and upgrade your Field Communicator Configuration and Use Manual 237 Using the Field Communicator with the 9739 MVD transmitter Field Communicator menus and messages Most of the menus in this manual start with the On Line menu Ensure that you are able to navigate to the On Line menu As you use the Field Communicator with a Micro Motion transmitter you will see a number of messages and notes This manual does not document all of these messages and notes Important The user is responsible for responding to messages and notes and complying with all safety messages E 2 Menu maps for the Field Communicator Figure E 1 On Line menu Overview 1 Check Status 2 Primary Purpose Variables 3 Shortcuts Configure 1 Manual Setup 2 Alert Setup Service Tools 1 Alerts 2 Variables 3 Trends 4 Maintenance 5 Simulate 238 Micro Motion 9739 MVD Transmitters Figure E 2 Overview m
26. 54 It should vary between 0 mA or 4 mA and 20 mA according to the mass flow rate of your process Perform a loop test A loop test is a way to verify that the transmitter and the receiving device are communicating properly A loop test also helps you know whether you need to trim mA outputs Performing a loop test is not a required procedure However Micro Motion recommends performing a loop test for every input or output available on your transmitter Procedure 1 Test the mA output a Press Service Tools Simulate Simulate Outputs mA Output Loop Tests and select 4 mA b Read the mA current at the receiving device and compare it to the transmitter output The readings do not need to match exactly If the values are slightly different you can correct the discrepancy by trimming the output c Select 20 mA d Read the mA current at the receiving device and compare it to the transmitter output The readings do not need to match exactly If the values are slightly different you can correct the discrepancy by trimming the output Test the secondary mA output Press Service Tools Maintenance Simulate Outputs mA Output 2 Loop Test and repeat the loop test for the secondary mA output Test the frequency output Note If the Weights amp Measures application is enabled on the transmitter it is not possible to perform a loop test of the frequency output even when the transmitter is unsecured a Press Serv
27. AMS Suite Intelligent Device Manager or the Smart Wireless THUM Adapter Use of AMS or the Smart Wireless THUM Adapter is not discussed in this manual For your reference the AMS interface is similar to the ProLink II interface For more information on the Smart Wireless THUM Adapter refer to the documentation available at www micromotion com This manual provides basic information on using the transmitter display ProLink II and the Field Communicator For more information on using ProLink II see the ProLink Il user manual available on the Micro Motion web site www micromotion com or on the Micro Motion user documentation CD For more information on using Field Communicator see the Field Communicator documentation available on the Micro Motion web site www micromotion com 1 4 Additional documentation and resources Micro Motion provides additional documentation to support the installation and operation of the 9739 MVD transmitter See Table 1 2 for the documentation resources available to support the 9739 MVD transmitter All documentation resources are available on the Micro Motion web site at www micromotion com or on the Micro Motion user documentation CD Table 1 2 Additional documentation and resources Sensor Sensor documentation Transmitter installation Micro Motion 9739 MVD Transmitters Installation Manual Hazardous area installation See the approval documentation shipped with the transmitter or download the app
28. Calibration in Progress Calibration in Progress light turns green light turns green Done Configuration and Use Manual 175 Chapter 10 Troubleshooting Topics covered in this chapter Transmitter status LED states Status alarms Flow problems Density problems Temperature problems Milliamp output problems Frequency output problems Use sensor simulation for troubleshooting Check power supply wiring Check sensor to transmitter wiring Check grounding Check for radio frequency interference Check HART communication loop Check HART Address and Loop Current Mode Check HART burst mode Check mA output trim Check Lower Range Value and Upper Range Value Check mA Output Fault Action Check Frequency Output Mode Check Frequency Output Maximum Pulse Width and Frequency Output Scaling Method Check Frequency Output Fault Action Check Flow Direction Check cutoffs Check for slug flow Check the drive gain Check the pickoff voltage Check for electrical shorts 10 1 Transmitter status LED states If the transmitter status LED indicates a status change refer to the status alarms for more information about the actions recommended to address the problem 9739 MVD LED states The 9739 MVD transmitter has a status LED located on the user interface Configuration and Use Manual 177 Troubleshooting Table 10 1 Solid green Normal operation 9739 MVD status LED st
29. Configuration window Optional Choose ProLink Output Levels and observe the mA output reading It should vary between 0 mA or 4 mA and 20 mA according to the mass flow rate of your process 3 5 Perform a loop test 9739 MVD Transmitter ProLink Test Fix Milliamp 1 ProLink Test Fix Milliamp 2 ProLink Test Fix Freq Out ProLink Test Fix Discrete Out ProLink Test Read Discrete Input ProLink Test Read Milliamp Input A loop test is a way to verify that the transmitter and the receiving device are communicating properly A loop test also helps you know whether you need to trim mA outputs A loop test is a way to verify that the transmitter and the receiving device are communicating properly A loop test also helps you know whether you need to trim mA outputs Performing a loop test is not Configuration and Use Manual 41 Quick start with ProLink Il 42 a required procedure However Micro Motion recommends performing a loop test for every input or output available on your transmitter Procedure 1 Test the mA output g Choose ProLink Test Fix Milliamp 1 Enter 0 mA or 4 mA in Set Output To Click Fix mA Read the mA current at the receiving device and compare it to the transmitter output The readings do not need to match exactly If the values are slightly different you can correct the discrepancy by trimming the output Click UnFix mA Enter 20 mA in Set Output To Click Fix mA Read the
30. Contact Micro Motion Micro Motion 9739 MVD Transmitters Table 10 2 Status alarms and recommended actions continued A006 A008 A009 A010 A011 Transmitter not configured Density overrange Transmitter initializing warming up Calibration failure Calibration too low Configuration and Use Manual Calibration factors have not been entered and the sensor type is incorrect The measured density has exceeded 0 to 10 g cms Transmitter is in power up mode Mechanical zero the resulting zero was greater than 3 us Temperature Density calibration many possible causes Mechanical zero corresponds with high reverse flow a zero magnitude absolute value greater than 3 us Temperature Density calibration many possible causes Troubleshooting Verify characterization parameters Contact Micro Motion If other alarms are present resolve those alarm conditions first If the current alarm persists continue with the recommended actions Verify process conditions checking especially for air in the flow tubes tubes not filled foreign material in the tubes or coating in the tubes Check for slug flow See Section 10 24 If accompanied by an A003 alarm check for electrical shorts See Section 10 27 Verify characterization parameters Check the drive gain and the pickoff voltage See Section 10 25 and Section 10 26 Perform a density calibration Contact Micro Motion Allo
31. Conversion factor a special unit Flow text Total text text Volume flow cutoff Flow direction Absolute Value Bidirectional Forward Negate Bidirectional Negate Forward Reverse Density measurement unit Slug flow low limit Slug flow high limit Temperature C measurement unit oF R Kelvin Temperature damping Flow factor Pressure compensation Density factor Calibration pressure 6 Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi parameter Display ProLink II cator API table type L Degrees API reference temperature 60 F L Relative Density Specific Gravity reference temperature 60 F Petroleum kg m3 at user defined measurement reference temperature application if Temperature __ available API Units Generalized Crude or JP4 API Chapter 11 1 A Tables Generalized Products API Chapter 11 1 B Tables User Defined TEC API Chapter 11 1 C Tables measurement application if Derived variable available Weights amp Totalizer reset options Measures application if available Not resettable from display or digital communications Resettable from digital communications only Resettable fro display and digital communications Resettable from display only Language Q English Tra
32. Fault Action ProLink II Field Communicator Frequency output behavior Upscale Upscale Goes to configured Upscale value e Range 10 Hz to 15000 Hz e Default 15000 Hz None default None default Tracks data for the assigned process variable A If you set mA Output Fault Action or Frequency Output Fault Action to None be sure to set Digital Communications Fault Action to None If you do not the output will not report actual process data and this may result in measurement error or unintended consequences for your process A If you set Digital Communications Fault Action to NAN you cannot set mA Output Fault Action or Frequency Output Fault Action to None If you try to do this the transmitter will not accept the configuration 7 2 5 Configure Frequency Output Power Source Display OFF LINE MAINT OFF LINE CONFG gt IO FO POWER ProLink II ProLink Configuration Frequency Power Type Field Communicator Configure Manual Setup lnputs Outputs Frequency Output FO Settings Power Source Use Frequency Output Power Source to set the output power source for the frequency output The power configuration must match the wiring for the frequency output Procedure Set Frequency Output Power Source as desired External The output is powered by an external power source 7 3 Configure the discrete output Display OFF LINE MAINT OFF LINE CONFG I0 DO ProLink II ProLink Configuration Discrete Output
33. If the HART security switch is set to ON HART protocol cannot be used to perform any action that requires writing to the transmitter For example you cannot change the configuration reset totalizers or perform calibration using the Field Communicator or ProLink II with a HART connection When the HART security switch is set to OFF no functions are disabled Procedure 1 To connect to the HART clips a Remove the transmitter housing cover b Attach the leads from the Field Communicator to the HART clips on the face of the transmitter and add resistance as necessary The Field Communicator must be connected across a resistance of 250 600 Q Tip HART connections are polarity insensitive It does not matter which lead you attach to which terminal 50 Micro Motion 9739 MVD Transmitters Quick start with the Field Communicator Figure 4 1 Field Communicator connection to HART clips A Field Communicator B 250 600 Q resistance C Transmitter 2 To connect to a point in the local HART loop attach the leads from the Field Communicator to any point in the loop and add resistance as necessary See Figure 4 2 The Field Communicator must be connected across a resistance of 250 600 Figure 4 2 Field Communicator connection to local HART loop A Field Communicator B 250 600 Q resistance C Transmitter terminals Configuration and Use Man
34. Optical switch indicator for Scroll Scroll optical switch HART clips Unused zs aA mon w gt Service port clips Select optical switch Optical switch indicator for Select Unit of measure Status LED Current value Z22eF7 214 Micro Motion 9739 MVD Transmitters Using the transmitter display Figure C 2 Transmitter without display Zero button HART security switch Unused HART clips Service port clips Status LED 7m mgp nH G gt C 2 Access and use the display menu system Prerequisites To access the display menu system operator access to either the Off Line menu or the Alarm menu must be enabled To access the complete menu system operator access must be enabled for both Tip The display menu system does not provide complete configuration administrative or maintenance functions For complete transmitter management you must use another communications tool Procedure 1 At the transmitter display activate the Scroll and Select optical switches simultaneously until the display changes You will enter the Off Line menu at any of several locations depending on several factors e Ifan alarm is active and access to the Alarm menu is enabled you will see SEE ALARM Use the Scroll and Select optical switches to navigate to your destination in the display menu system e Use Scroll to move through a list of options e Use Select to choose the current option If CODE appears o
35. Specify Base Time Unit Base Time Unit is the existing time unit that the special unit will be based on 3 Calculate Volume Flow Conversion Factor as follows a x base units y special units b Volume Flow Conversion Factor x y 4 Enter the Volume Flow Conversion Factor 5 Set Volume Flow Label to the label to be used for the volume flow unit 6 Set Volume Total Label to the label to be used for the volume total and volume inventory unit The special measurement unit is stored in the transmitter You can configure the transmitter to use the special measurement unit at any time Example Defining a special measurement unit for volume flow You want to measure volume flow in pints per second 1 Set Base Volume Unit to Gallons gal 2 Set Base Time Unit to Seconds sec 3 Calculate the conversion factor a 1 gal sec 8 pints sec b Volume Flow Conversion Factor 1 8 0 1250 4 Set Volume Flow Conversion Factor to 0 1250 5 Set Volume Flow Label to pints sec 6 Set Volume Total Label to pints 72 Micro Motion 9739 MVD Transmitters Configure process measurement 5 3 3 Configure Volume Flow Cutoff Display Not available ProLink II ProLink Configuration Flow Vol Flow Cutoff Field Communicator Configure Manual Setup Measurements Flow Volume Flow Cutoff Volume Flow Cutoff specifies the lowest volume flow rate that will reported as measured All volume flow rates below this cutoff will be reported
36. Troubleshooting Table 10 2 Status alarms and recommended actions continued AES Secondary MA uput Check process conditions Actual saturated E conditions may be outside of the normally expected conditions for which the output is configured Verify process conditions checking especially for air in the flow tubes tubes not filled foreign material in the tubes or coating in the tubes Verify that the measurement units are configured correctly for your application Purge the flow tubes Check the settings of Upper Range Value and Lower Range Value See Section 10 17 ATIS PE MA Output Check that the transmitter is in loop test ixed mode Exit mA output trim Check that the output has been fixed via digital communication AlS External input erfor Uaa ae Verify the external device operation external device has Verify the wiring between the transmitter failed No response and the external device received from polled device Verify the HART polling configuration The mA input Verify the mA input configuration connection to an external device has failed No response received from the external device A116 API temperature F a outside standard range Verify process conditions Verify the configuration of the petroleum measurement table type and temperature Ply a Genel put or Verify process conditions imits Verify the configuration of the petroleum measurement table type and density ATG Discrete output 1 fixeu Vi et
37. You are responsible for following all safety and wiring instructions documented in the transmitter installation manual plus any additional site requirements You can wire the 9739 MVD transmitter to the following sensors ELITE H Series T Series and F Series e Model D and Model DL e Model DT with user supplied metal junction box with terminal block Each wire of the 9 wire cable is inserted into the corresponding terminal at the sensor and transmitter matching by color see Table B 1 Table B 1 Sensor and transmitter terminal designations wirecolor sensorteminai __ ransmitertrminal Funaion C 0 Oranwres i e EC C CC CS C CC T wooo e o e S B 3 Power supply terminals A Refer to the Micro Motion 9739 MVD Transmitters Installation Manual for all safety and detailed wiring information for the 9739 MVD transmitter You are responsible for following all safety and wiring instructions documented in the transmitter installation manual plus any additional site requirements Configuration and Use Manual 209 Transmitter components and installation wiring Figure B 2 Power supply terminals A External ground terminal B Power supply conduit opening c L L1 for AC for DC D N L2 for AC for DC E Power ground terminal B 4 Input output I O terminals A Refer to the Micro Motion 9739 MVD Transmitters Installation Manual for all safety and detailed wiring information for the 9739 MVD transmitt
38. and URV are shown in Table 7 2 120 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Table 7 2 Default values for Lower Range Value LRV and Upper Range Value URV All mass flow variables 200 000 g sec 200 000 g sec All liquid volume flow variables 0 200 I sec 0 200 I sec Gas standard volume flow 423 78 SCFM 423 78 SCFM 7 1 3 Configure AO Cutoff Display Not available ProLink II ProLink Configuration Analog Output Primary Secondary Output AO Cutoff Field Communicator Configure Manual Setup Inputs Outputs mA Output 1 mA Output Settings MAO Cutoff Configure Manual Setup Inputs Outputs mA Output 2 mA Output Settings gt MAO Cutoff AO Cutoff Analog Output Cutoff specifies the lowest mass flow rate volume flow rate or Gas Standard Volume flow rate that will be reported through the mA output Any flow rates below the AO Cutoff will be reported as 0 Restriction AO Cutoff is applied only if mA Output Process Variable is set to Mass Flow Rate Volume Flow Rate or Gas Standard Volume Flow Rate If mA Output Process Variable is set to a different process variable AO Cutoff is not configurable and the transmitter does not implement the AO cutoff function Procedure Set AO Cutoff as desired The default values for AO Cutoff are as follows e Primary mA output 0 0 g s e Secondary mA output Not A Number Tip For most applications the default value of
39. and reported The volume flow measurement parameters include e Volume Flow Type Volume Flow Measurement Unit Volume Flow Cutoff Restriction You cannot implement both liquid volume flow and gas standard volume flow You must choose one or the other 5 3 1 Configure Volume Flow Type for liquid applications Display OFF LINE MAINT OFF LINE CONFG VOL VOL TYPE LIQUID ProLink II ProLink Configuration Flow Vol Flow Type Liquid Volume Field Communicator Configure Manual Setup Measurements Gas Standard Volume Volume Flow Type Liquid Volume Flow Type controls whether liquid or gas standard volume flow measurement will be implemented Configuration and Use Manual 69 Configure process measurement Restriction If you are using the petroleum measurement application you must set Volume Flow Type to Liquid Gas standard volume measurement is incompatible with the petroleum measurement application Restriction If you are using the concentration measurement application you must set Volume Flow Type to Liquid Gas standard volume measurement is incompatible with the concentration measurement application Procedure Set Volume Flow Type to Liquid 5 3 2 Configure Volume Flow Measurement Unit for liquid applications Display OFF LINE MAINT OFF LINE CONFG UNITS VOL ProLink II ProLink Configuration Flow Vol Flow Units Field Communicator Configure Manual Setup Measurements
40. as 0 Procedure Set Volume Flow Cutoff to the desired value The default value for Volume Flow Cutoff is 0 0 L s The lower limit is 0 The upper limit is the sensor s flow calibration factor in units of L s multiplied by 0 2 Interaction between Volume Flow Cutoff and AO Cutoff Volume Flow Cutoff defines the lowest liquid volume flow value that the transmitter will report as measured AO Cutoff defines the lowest flow rate that will be reported via the mA output If mA Output Process Variable is set to Volume Flow Rate the volume flow rate reported via the mA output is controlled by the higher of the two cutoff values Volume Flow Cutoff affects both volume flow values reported via outputs and volume flow values used in other transmitter behavior e g events defined on volume flow AO Cutoff affects only flow values reported via the mA output Example Cutoff interaction with AO Cutoff lower than Volume Flow Cutoff Configuration e mA Output Process Variable for the primary mA output Volume Flow Rate e Frequency Output Process Variable Volume Flow Rate AO Cutoff for the primary mA output 10 liters second e Volume Flow Cutoff 15 liters second Result If the mass flow rate drops below 15 liters second volume flow will be reported as 0 and 0 will be used in all internal processing Example Cutoff interaction with AO Cutoff higher than Volume Flow Cutoff Configuration e mA Output Process Variable for the pri
41. as measured Modbus scaled integers are reported as Max Int Totalizers stop incrementing Blown erg jnlzersr law t Flow rates are reported as 0 Other process variables are reported as measured Totalizers stop incrementing None d fault None aefaut All process variables are reported as measured Totalizers increment if they are running A If you set mA Output Fault Action or Frequency Output Fault Action to None be sure to set Digital Communications Fault Action to None If you do not the output will not report actual process data and this may result in measurement error or unintended consequences for your process A If you set Digital Communications Fault Action to NAN you cannot set mA Output Fault Action or Frequency Output Fault Action to None If you try to do this the transmitter will not accept the configuration Configuration and Use Manual 145 Integrate the meter with the control system 7 7 Configure events Display Not available ProLink II ProLink Configuration Events Field Communicator Configure Alert Setup Discrete Events An event occurs if the real time value of a user specified process variable moves past a user defined setpoint Events are used to provide notification of process changes or to perform specific transmitter actions if a process change occurs The 9739 MVD transmitter supports two event models e Basic event model Enhanced event model 7 7 1 Configure a basic even
42. by saving the current configuration to a file on the PC If the calibration fails restore the known values Procedure To perform a D3 calibration or D3 and D4 calibration using ProLink Il see Figure 9 3 172 Micro Motion 9739 MVD Transmitters Measurement support Figure 9 3 D3 or D3 and D4 density calibration using ProLink II D3 calibration D4 calibration Close shutoff valve Fill sensor with D3 fluid Fill sensor with D4 fluid downstream from sensor ProLink Menu gt ProLink Menu gt Calibration gt Calibration gt Density cal Point 3 Density cal Point 4 Enter density of D3 fluid Enter density of D4 fluid Do Cal Calibration in Progress Calibration in Progress light turns red light turns red Calibration in Progress Calibration in Progress light turns green light turns green Close Done Done 9 4 2 Perform a D3 and D4 density calibration using Field Communicator Prerequisites e During density calibration the sensor must be completely filled with the calibration fluid and flow through the sensor must be at the lowest rate allowed by your application This is usually accomplished by closing the shutoff valve downstream from the sensor then filling the sensor with the appropriate fluid For D3 density calibration the D3 fluid must meet the following requirements Minimum density of 0 6 g cm3 Minimum difference of 0 1 g cm between the density of the D3 fluid and the density of water
43. connection request With this auto detect feature you do not need to enter some HART communication parameters Procedure Set HART Address to a value between 0 and 15 HART Address must be unique on the network The default address 0 is typically used unless you are in a multidrop environment Tip Devices using HART protocol to communicate with the transmitter may use either HART Address or HART Tag Software Tag to identify the transmitter You may configure either or both as required by your other HART devices 7 6 3 Configure Modbus RS 485 communications Display Not available ProLink II ProLink Configuration Device Digital Comm Setting Field Communicator Configure Manual Setup lnputs Outputs Communications Setup RS 485 Port Modbus RS 485 communications parameters control Modbus communication with the transmitter s RS 485 terminals Modbus RS 485 communications parameters include e Modbus Address Slave Address e Disable Modbus ASCII Floating Point Byte Order e Additional Communications Response Delay Important To minimize configuration requirements the 9739 MVD transmitter uses an auto detection scheme when responding to a connection request With this auto detect feature you do not need to enter some Modbus communication parameters Restriction To configure Floating Point Byte Order or Additional Communications Response Delay you must use ProLink II Procedure 1 Se
44. downstream from the sensor then filling the sensor with the appropriate fluid e D1 and D2 density calibration require a D1 low density fluid and a D2 high density fluid You may use air and water The calibrations must be performed without interruption in the order shown Make sure that you are prepared to complete the process without interruption e Before performing the calibration record your current calibration parameters You can do this by saving the current configuration to a file on the PC If the calibration fails restore the known values Restriction For T Series sensors the D1 calibration must be performed on air and the D2 calibration must be performed on water Tip For T Series sensors only you have the option to perform a D3 and D4 calibration to improve the accuracy of the density measurement if the fluid density is outside of the 0 8 g cm to 1 2 g cm density range If you choose to perform the D3 and D4 calibration do not perform the D1 and D2 calibration Procedure To perform a D1 and D2 calibration see Figure 9 1 Configuration and Use Manual 169 Measurement support Figure 9 1 D1 and D2 density calibration using ProLink II D2 calibration Fill sensor with D2 fluid ProLink Menu gt Calibration gt Density cal Point 2 Enter density of D2 fluid Calibration in Progress light turns red Calibration in Progress light turns green D1 calibration Fill s
45. i Micro Motion 9739 MVD Transmitters Default values and ranges Table A 1 Transmitter default values and ranges continued Besems oo O SS SooS C e E a e o aseve fe OO SSS Eo o E Primary variable variable Mass flow o S Quaternary variable Volume flow o variable 200 00000 ee fURV 200 00000 g s AO cutoff 0 00000 g s AO added damping 0 00000 sec 200 g s Read only LSL and USL are calculated mA output 200 g s based on the sensor size and characterization parameters AO fault level downscale fault level downscale 0 0 3 6 mA Last measured value timeout measured value timeout a Tertiary variable Tertiary variable Mass flow flow Frequency factor 1 000 00 Hz 10 000 00 Hz Rate factor 16 666 66992 g s Frequency pulse width 0 50 duty 0 01 655 35 Frequency cycle millisec output Scaling method method Freq Flow _ 1k Frequency fault level upscale 15 000 Hz 10 0 15 000 oe Frequency output polarity output polarity Active high Last measured value timeout 0 0 60 0 sec Pe Configuration and Use Manual 205 Default values and ranges Table A 1 Transmitter default values and ranges continued Assignment Forward Re verse output rover items i Polarity Active High O ressonen ne CS Discrete input Update period 200 100 10 000 milliseconds milliseconds Variable 3 Volume flow rate Fe 0 Fvaranies Te
46. mA current at the receiving device and compare it to the transmitter output The readings do not need to match exactly If the values are slightly different you can correct the discrepancy by trimming the output Click UnFix mA 2 Test the secondary mA output Choose ProLink Test Fix Millamp 2 and repeat the loop test for the secondary mA output 3 Test the frequency output Note If the Weights amp Measures application is enabled on the transmitter it is not possible to perform a loop test of the frequency output even when the transmitter is unsecured a b c d Choose ProLink Test Fix Freq Out Enter the frequency output value in Set Output To Click Fix Frequency Read the frequency signal at the receiving device and compare it to the transmitter output Click UnFix Freq 4 Test the discrete output o moapop Choose ProLink Test Fix Discrete Output Select On Verify the signal state at the receiving device Click UnFix Select Off Verify the signal state at the receiving device Click UnFix 5 Read the discrete input a b c Set the remote input device so that the desired signal is sent to the transmitter Choose ProLink Test Read Discrete Input Verify the signal state at the transmitter Micro Motion 9739 MVD Transmitters 6 Quick start with ProLink II d Repeat the procedure for the other signal state Read the mA input a Set the remote input device so
47. mode Zero calibration failure Fault condition if fault indicator is set to upscale or downscale LRV and URV are not set correctly Milliamp output problems and recommended actions Possible causes Recommended actions Check the power supply and power supply wiring See Section 10 9 Check the Fault Action settings See Section 10 18 Measure DC voltage across output terminals to verify that the output is active Check the mA output wiring Contact Micro Motion Check the power supply and power supply wiring See Section 10 9 Check the Fault Action settings See Section 10 18 Check the mA output wiring Contact Micro Motion Verify process conditions Check the settings of Upper Range Value and Lower Range Value See Section 10 17 Check the Fault Action settings See Section 10 18 Verify that the receiving device and the wiring between the transmitter and the receiving device Check the HART address and Loop Current Mode See Section 10 14 Check the loop test mode Check HART burst mode configuration See Section 10 15 If related to a zero calibration failure cycle power to the meter and retry the zeroing procedure Check the Fault Action settings See Section 10 18 Check the settings of Upper Range Value and Lower Range Value See Section 10 17 Micro Motion 9739 MVD Transmitters Troubleshooting Table 10 6 Milliamp output problems and recommended actions continued Prob
48. parts from the documents shipped with your sensor or from a code in the sensor model number 114 Micro Motion 9739 MVD Transmitters Configure device options and preferences To interpret the model number refer to the product data sheet for your sensor 2 Set Sensor Material to the appropriate option 6 6 6 Configure Sensor Liner Material Display Not available ProLink II ProLink Configuration Sensor Sensor Matl Field Communicator Configure Manual Setup Info Parameters Sensor Information Tube Lining Sensor Liner Material provides a place to store the type of material used for your sensor liner in transmitter memory Sensor Liner Material is not used in transmitter processing and is not required Procedure 1 Obtain your sensor s liner material from the documents shipped with your sensor or from a code in the sensor model number To interpret the model number refer to the product data sheet for your sensor 2 Set Sensor Liner Material to the appropriate option 6 6 7 Configure Sensor Flange Type Display Not available ProLink II ProLink Configuration Sensor Flange Field Communicator Configure Manual Setup Info Parameters Sensor Information Sensor Flange Sensor Flange Type provides a place to your sensor s flange type in transmitter memory Sensor Flange Type is not used in transmitter processing and is not required Procedure 1 Obtain your sensor s flange type from the
49. plus a minus sign to indicate a negative number e They can contain a decimal point The decimal point does not count as a digit The decimal point must be positioned so that the precision of the value does not exceed four When you first enter the configuration screen the current configuration value is displayed in decimal notation and the active character is flashing If the value is positive no sign is displayed If the value is negative a minus sign is displayed Procedure e To change the value a Activate Select until the digit you want to change is active flashing Select moves the cursor one position to the left From the leftmost position Select moves the cursor to the rightmost digit b Activate Scroll to change the value of the active digit c Repeat until all digits are set as desired To change the sign of the value e If the current value is negative activate Select until the minus sign is flashing then activate Scroll until the space is blank e lf the current value is positive and there is a blank space at the left of the value activate Select until the cursor is flashing under the blank space then activate Scroll until the minus sign appears e lf the current value is positive and there is no blank space at the left of the value activate Select until the cursor is flashing under the leftmost digit then activate Scroll until the minus sign appears To move the decimal point a Activate Select u
50. plus one user defined special measurement unit Different communications tool use different labels for the units Options for Mass Flow Measurement Unit are shown in Table 5 1 Table 5 1 Options for Mass Flow Measurement Unit Unit description Display ProLink II Grams per second G S g s Grams per minute G MIN g min G H g hr KG MIN kg min T MIN mTon min T D mTon day LB MIN lbs min LB H Ibs hr Pounds per day LB D Ibs day Short tons 2000 pounds ST MIN sTon min per minute Configuration and Use Manual 65 Grams per hour Kilograms per second Kilograms per minute Kilograms per hour Kilograms per day Metric tons per minute Metric tons per hour Metric tons per day Pounds per second Pounds per minute Pounds per hour ee Cc __ O Configure process measurement Table 5 1 Options for Mass Flow Measurement Unit continued Unit description Display ProLink II Field Communicator Short tons 2000 pounds ST H sTon hr STon h per hour Short tons 2000 pounds ST D sTon day STon d per day Long tons 2240 pounds LT H ITon hr LTon h per hour Long tons 2240 pounds LT D ITon day LTon d per day Define a special measurement unit for mass flow Display Not available ProLink II ProLink Configuration Special Units Field Communicator Configure Manual Setup Measurements Special Units Mass Special Units A special measurement unit allows you to report process data totalizer data and inventor
51. terminal at a time place a DMM lead on the terminal and the other lead on the sensor case With the DMM set to its highest range there should be infinite resistance on each lead If there is any resistance at all there is a short to case 6 Test the resistance of junction box terminal pairs a Test the brown terminal against all other terminals except the red one b Test the red terminal against all other terminals except the brown one Test the green terminal against all other terminals except the white one c d Test the white terminal against all other terminals except the green one D Test the blue terminal against all other terminals except the gray one mh Test the gray terminal against all other terminals except the blue one g Test the orange terminal against all other terminals except the yellow and violet ones h Test the yellow terminal against all other terminals except the orange and violet ones i Test the violet terminal against all other terminals except the yellow and orange ones There should be infinite resistance for each pair If there is any resistance at all there is a short between terminals Postrequisites To return to normal operation 1 Plug the terminal blocks into the terminal board 2 Replace the transmitter housing cover 3 Replace the lid on the sensor junction box Note When reassembling the meter components be sure to grease all O rings Configuration and Use Manual 199 App
52. that the desired signal is sent to the transmitter b Choose ProLink Test Read MA Input Postrequisites 3 6 If the mA output readings were slightly off at the receiving device you can correct this discrepancy by trimming the output If the mA output reading was significantly off 200 microamps or if at any step the reading was faulty verify the wiring between the transmitter and the remote device and try again If the mA input reading was slightly off at the transmitter trim and calibrate the input at the remote input device Trim mA outputs Trimming the mA output establishes a common measurement range between the transmitter and the device that receives the mA output Trimming the mA outputs is not a required procedure However if there is a small discrepancy in the mA reading between the transmitter and the receiving device trimming the output will correct this Note Any trimming performed on the output should not exceed 200 microamps If more trimming is required contact Micro Motion customer support Procedure 1 Choose ProLink Calibration Milliamp 1 Trim to start the mA trim procedure 2 Follow the instructions in the guided method to trim the mA output 3 Choose ProLink Calibration Milliamp 2 Trim to start the trim procedure for the secondary mA output 4 Follow the instructions in the guided method to trim the mA output 3 7 Zero the flowmeter Prerequisites To prepare for the zero pr
53. the values are slightly different you can correct the discrepancy by trimming the output f At the transmitter activate Select Test the secondary mA output Choose OFFLINE MAINT SIM lt AO2 SIM and repeat the loop test for the secondary mA output Test the frequency output a Choose OFFLINE MAINT SIM FO SIM and select the frequency output value The frequency output can be set to 1 10 or 15 kHz Note If the Weights amp Measures application is enabled on the transmitter it is not possible to perform a loop test of the frequency output even when the transmitter is unsecured Dots traverse the display while the output is fixed b Read the frequency signal at the receiving device and compare it to the transmitter output c At the transmitter activate Select Test the discrete output a Choose OFFLINE MAINT SIM DO SIM and select SET ON Dots traverse the display while the output is fixed b Verify the signal state at the receiving device c At the transmitter activate Select d Scroll to and select SET OFF e Verify the signal state at the receiving device f At the transmitter activate Select Read the discrete input a Set the remote input device so that the desired signal is sent to the transmitter b At the transmitter choose OFFLINE MAINT SIM and select READ DI c Verify the signal state at the transmitter d Repeat the procedure for the other signal state Read the mA input a Set the remo
54. totalizers individually from the display When you use the display to start or stop totalizers all totalizers are started or stopped together e You cannot start or stop inventories separately from totalizers When a totalizer is started or stopped the associated inventory is also started or stopped If the petroleum measurement application is installed on your computer the operator must enter the off line password to perform this function even if the off line password is not enabled Procedure 1 Enable or disable Totalizer Start Stop as desired Configuration and Use Manual 103 Configure device options and preferences Enabled Operators can start and stop totalizers and inventories from the display if at least one totalizer is configured as a display variable Disabled default Operators cannot start and stop totalizers and inventories from the display 2 Ensure that at least one totalizer has been configured as a display variable This function is accessed from a totalizer value on the display To ensure that the operator can start and stop totalizers and inventories at least one totalizer must be shown on the display 6 2 2 Enable or disable Totalizer Reset from the display Display OFF LINE MAINT OFF LINE CONFG DISPLAY TOTALS RESET ProLink II ProLink Configuration Display Display Options Display Totalizer Reset Field Communicator Not available You can control whether or not the operator wi
55. variety of process fluids Table 5 12 describes the standard concentration curves available from Micro Motion along with the density and temperature measurement units used in calculation and the unit used to report concentration data If these curves are available on your transmitter you can set Active Curve to any one of them Table 5 12 Standard concentration curves and associated measurement units Curve name Description Density unit Temperature Concentration unit unit Deg Balling Curve represents percent extract by g cm3 Balling mass in solution based on Balling For example if a wort is 10 Balling and the extract in solution is 100 sucrose the extract is 10 of the total mass Deg Brix Curve represents a hydrometer scale g cm3 Brix for sucrose solutions that indicates the percent by mass of sucrose in solution at a given temperature For example 40 kg of sucrose mixed with 60 kg of water results in a 40 Brix solution Deg Plato Curve represents percent extract by g cm3 mass in solution based on Plato For example if a wort is 10 Plato and the extract in solution is 100 sucrose the extract is 10 of the total mass HFCS 42 Curve represents a hydrometer scale g cm3 for HFCS 42 high fructose corn syrup solutions that indicates the percent by mass of HFCS in solution HFCS 55 Curve represents a hydrometer scale g cm3 k for HFCS 55 high fructose corn syrup solutions that indicates the perc
56. whichever comes first Procedure 1 Check whether slug flow alarms have been generated If the transmitter is not generating slug flow alarms then slug flow is not the source of your problem 2 Check the process for cavitation flashing or leaks 3 Check the configured slug flow limits and duration A slug flow duration of 0 0 seconds will cause flow outputs to report zero flow as soon as slug flow is detected If you are experiencing slug flow alarms and no flow output this maybe resolved by increasing the slug flow duration Tip The default high slug flow limit 5 0 g cm is appropriate for most applications 4 Monitor the density output under normal process conditions It may be necessary to adjust the slug flow limits and duration to account for the normal density variation in your process 10 25 Check the drive gain Collecting drive gain data To know whether your drive gain is excessive or erratic you must collect drive gain data during the problem condition and compare it to drive gain data from a period of normal operation Configuration and Use Manual 195 Troubleshooting Excessive drive gain Table 10 8 Possible causes and recommended actions for excessive drive gain Slug flow Check for slug flow See Section 10 24 Plugged flow tube Purge the flow tubes Replace the sensor Cavitation or flashing Increase inlet or back pressure at the sensor If a pump is located upstream from the sensor
57. 5 Configure process measurement Topics covered in this chapter Characterize the flowmeter Configure mass flow measurement Configure volume flow measurement for liquid applications Configure gas standard volume flow measurement Configure Flow Direction Configure density measurement Configure temperature measurement Configure pressure compensation Configure the petroleum measurement application Configure the concentration measurement application 5 1 Characterize the flowmeter Display Not available ProLink II ProLink Configuration DensityProLink Configuration Flow Field Communicator Configure Manual Setup Characterize Characterizing the flowmeter adjusts the transmitter s measurement algorithms to match the unique traits of the sensor it is paired with The characterization parameters also called calibration parameters describe the sensor s sensitivity to flow density and temperature Depending on your sensor type different parameters are required Values for your sensor are provided by Micro Motion on the sensor tag or the calibration certificate Note If your sensor and transmitter were ordered together the transmitter has already been characterized at the factory However you should still verify characterization parameters Configuration and Use Manual 61 Configure process measurement Procedure 1 Specify Sensor Type e Straight tube T Series e Curved tube all s
58. 6 10 24 Effect of Density Damping on volume measurement Density Damping affects liquid volume measurement Density Damping does not affect gas standard volume measurement Interaction between Density Damping and Added Damping Density Damping controls the rate of change in the density process variable Added Damping controls the rate of change reported via the mA output If mA Output Process Variable is set to Density and both Density Damping and Added Damping are set to non zero values density damping is applied first and the added damping calculation is applied to the result of the first calculation 5 6 4 Configure Density Cutoff Display Not available ProLink II ProLink Configuration Density Low Density Cutoff Field Communicator Configure Manual Setup Measurements Density Density Cutoff Density Cutoff specifies the lowest density value that will reported as measured All density values below this cutoff will be reported as 0 Configuration and Use Manual 87 Configure process measurement Procedure Set Density Cutoff to the desired value The default value for Density Cutoff is 0 2 g cm The range is 0 0 g cm to 0 5 g cm Effect of Density Cutoff on volume measurement Density Cutoff affects liquid volume measurement If the density value goes below Density Cutoff the volume flow rate goes to 0 Density Cutoff does not affect gas standard volume measurement Gas standard volume values are always ca
59. 65 Measurement support Prerequisites Identify the meter factor s that you will calculate and set You may set any combination of the three meter factors mass flow volume flow and density Note that all three meter factors are independent The meter factor for mass flow affects only the value reported for mass flow e The meter factor for density affects only the value reported for density The meter factor for volume flow affects only the value reported for volume flow or gas standard volume flow Important To adjust volume flow you must set the meter factor for volume flow Setting a meter factor for mass flow and a meter factor for density will not produce the desired result The volume flow calculations are based on original mass flow and density values before the corresponding meter factors have been applied If you plan to calculate the meter factor for volume flow be aware that validating volume in the field may be expensive and the procedure may be hazardous for some process fluids Therefore because volume is inversely proportional to density an alternative to direct measurement is to calculate the meter factor for volume flow from the meter factor for density See Section 9 2 1 for instructions on this method Obtain a reference device external measurement device for the appropriate process variable Important For good results the reference device must be highly accurate Procedure 1 Determine t
60. AO Cutoff should be used Contact Micro Motion Customer Service before changing AO Cutoff Cutoff interaction When mA Output Process Variable is set to a flow variable mass flow volume flow or gas standard volume flow AO Cutoff interacts with Mass Flow Cutoff Volume Flow Cutoff or Gas Standard Volume Flow Cutoff The transmitter puts the cutoff into effect at the highest flow rate at which a cutoff is applicable Configuration and Use Manual 121 Integrate the meter with the control system Example Cutoff interaction Configuration e mA Output Process Variable Mass Flow Rate e Frequency Output Process Variable Mass Flow Rate e AO Cutoff 10 g s e Mass Flow Cutoff 15 g s Result If the mass flow rate drops below 15 g s all outputs representing mass flow will report zero flow Example Cutoff interaction Configuration e mA Output Process Variable Mass Flow Rate e Frequency Output Process Variable Mass Flow Rate e AO Cutoff 15 g s e Mass Flow Cutoff 10 g s Result e lf the mass flow rate drops below 15 g s but not below 10 g s The mA output will report zero flow The frequency output will report the actual flow rate lf the mass flow rate drops below 10 g s both outputs will report zero flow 7 1 4 Configure Added Damping Display Not available ProLink II ProLink Configuration Analog Output Primary Secondary Output AO Added Damp Field Communicator Configure Manual Setu
61. CDEN API Temp Corrected Density TCVOL TC Vol API Temp Corrected Volume Flow AVE D API Avg Density ED Std Vol flo ED Net Mass flo ED Net Vol flo ED Concentration ED Dens Baume API Avg Temperature AVE T RDENS a STD V NET M NET V CONC BAUME CM Density Reference CM Density Fixed SG units CM Std Vol Flow Rate CM Net Mass Flow Rate CM Net Vol Flow Rate CM Concentration CM Density Fixed Baume Units 119 Integrate the meter with the control system 7 1 2 Configure Lower Range Value LRV and Upper Range Value URV Display OFF LINE MAINT OFF LINE CONFG IO AO 1 2 4 mA OFF LINE MAINT OFF LINE CONFG IO AO 1 2 20 mA ProLink II ProLink Configuration Analog Output Primary Secondary Output Lower Range Value ProLink Configuration Analog Output Primary Secondary Output Upper Range Value Field Communicator Configure Manual Setup lInputs Outputs mA Output X mA Output Settings PV SV LRV Configure Manual Setup Inputs Outputs mA Output X mA Output Settings PV SV URV The Lower Range Value LRV and Upper Range Value URV are used to scale the mA output i e to define the relationship between mA Output Process Variable and the mA output level The mA output uses a range of 4 20 mA or 0 20 mA to represent mA Output Process Variable Between LRV and URV the mA output is linear with the process variable If the process variable d
62. Configuration and Use Manual P N MMI 20016855 Rev AA June 2010 Micro Motion 9739 MVD Transmitters Configuration and Use Manual Configuration Operation ww Maintenance A Micro Metion EMERSON Process Management Micro Motion customer service Location Telephone Number U S A 800 522 MASS 800 522 6277 toll free Canada and Latin America 1 303 527 5200 U S A Asia Japan 3 5769 6803 All other locations 65 6777 8211 Singapore Europe U K 0870 240 1978 toll free All other locations 31 0 318 495 555 The Netherlands Customers outside the U S A can also send an email to flow support emerson com Copyrights and trademarks 2010 Micro Motion Inc All rights reserved The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co Micro Motion ELITE MVD ProLink MVD Direct Connect and PlantWeb are marks of one of the Emerson Process Management family of companies All other trademarks are property of their respective owners Contents l Getting starte dispis E A 1 Chapter 1 B tore yot DOGMA soriccsbecccecetecsscecetaccstededecestczedocsdiatvdevaswiexciesacdedsessens csteuecuevecececseeaboces 3 1 1 Safety IMNESSAGES oi ciciectes eetieis teeta icde da dibiet fase tertadeine Hie dtbbertaadedee rebate 3 1 2 Obtain version information cccceceeeeeeeeeeeeeeeeeceeeeeaeeeeaeeeeaeeesaeeesaeeeesaeees 3 1 3 Available communications tools 2 ccc
63. Display OFF LINE MAINT OFF LINE CONFG gt IO DI ProLink II ProLink Configuration Discrete Input Field Communicator Configure Manual Setup Inputs Outputs Discrete Input The discrete input is used to initiate one or more transmitter actions from a remote input device The discrete input parameters include e Discrete Input Action e Discrete Input Polarity 7 4 1 Configure Discrete Input Action Display OFF LINE MAINT OFF LINE CONFG IO DI DI ACT ProLink II ProLink Configuration Discrete Input Assignment Field Communicator Configure Alert Setup Discrete Events Assign Discrete Action Discrete Input Action controls the action or actions that the transmitter will perform when the discrete input transitions from OFF to ON 134 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system A Before assigning actions to an enhanced event or discrete input check the status of the event or the remote input device If it is ON all assigned actions will be performed when the new configuration is implemented If this is not acceptable wait until an appropriate time to assign actions to the event or discrete input Procedure Set Discrete Input Action as desired The default setting is None Options for Discrete Input Action Options for Discrete Input Action are shown in Table 7 11 Table 7 11 Options for Discrete Input Action or Enhanced Event Action Reset volume t
64. Display Variables 11 15 Set Up Decimal Places 1 For Process Variables 2 For Totalizer Variables 3 For Diagnostic Variables Figure E 7 Configure menu Manual Setup Inputs Outputs mA Output 1 1 Primary Variable 2 mA Output Settings 3 MA01 Fault Settings mA Output Settings 1 PV LRV 2 PV URV 3 PV Min Span 4 PV LSL 5 PV USL 6 PV MAO Cutoff 7 PV Added Damping mA Fault Settings 1 MAO Fault Action 2 MAO Fault Level mA Output 2 1 Secondary Variable 2 mA Output Settings 3 MAO2 Fault Settings mA Output Settings 1 SV LRV 2 SV URV 3 SV Min Span 4 SV LSL 5 SV USL 6 SV MAO Cutoff 7 SV Added Damping mA Fault Settings 1 MAO Fault Action 2 MAO Fault Level __ Additional _ options Frequency Output 1 FO Settings 2 FO Fault Parameters 3 FO Scaling FO Settings 1 Third Variable 2 Max Pulse Width 3 FO Polarity 4 Power Source FO Fault Parameters 1 Third Variable 2 FO Fault Action 3 FO Fault Level FO Scaling 1 FO Scaling Method 2 TV Frequency Factor 3 TV Rate Factor 4 Set FO Scaling Configuration and Use Manual 243 Using the Field Communicator with the 9739 MVD transmitter Figure E 8 Configure menu Manual Setup Inputs Outputs continued Discrete Output Discrete Input Milliamp Input 1 DO Assignment 1 Polarity 1 mA Input URV 2 DO Polarity 2 mA Input LRV 3 DO Fault Action 3 mA Input Variable Assignment 4 Flow Switch Source 4 mA
65. Input Level 5 Flow Switch Setpoint Communications Map Variables 1 HART Communications 1 Primary Variable 2 HART Burst Mode 2 Secondary Variable 3 Setup RS 485 Port 3 Third Variable 4 Fourth Variable HART Communications HART Address Tag Device Identification HART Burst Mode Burst Mode Burst Option Field Device Var 1 Field Device Var 2 Field Device Var 3 Field Device Var 4 Setup RS 485 Port Protocol Modbus Slave Address 244 Micro Motion 9739 MVD Transmitters Using the Field Communicator with the 9739 MVD transmitter Figure E 9 Configure menu Alert Setup Input Output Fault Action Alert Severity Discrete Events 1 Discrete Event 1 2 Discrete Event 2 3 Discrete Event 3 1 MA Output 1 1 Fault Timeout 2 MA Output 2 2 Set Alert Severity 3 FO Fault Parameters 3 View Alert Severity 4 Discrete Event 4 5 Discrete Event 5 6 Assign Discrete Action 7 Read Discrete Action 8 Review Discrete Actions 4 Discrete Output 5 Digital Communications 1 2 3 4 5 Discrete Event x 1 Discrete Event Var 2 Discrete Event Type 3 Setpoint A 4 Setpoint B Figure E 10 Service Tools menu top level Alerts Variables Trends 1 Refresh Alerts 1 Variable Summary 1 Process Variables 2 Alert Name 2 Process Variables 2 Diagnostic Variables 3 Additional Information for 3 Mapped Variables Above 4 External Variables 5 Totalizer Control 6 Outputs Maintenance Simulate 1 Routine Maintenance 1 Simulate Outputs 2 Ze
66. KHZ Scroll Scroll Seron m k d y SET 4 mA SET 4 mA SET 10 KHZ Scroll Scroll Scroll S S SET 12 mA SET 12mA SET 15 KHZ Scroll Scroll Scroll TA eS as o C e Ca me a EEE Y SET 22 mA SET 22 mA Scroll Scroll z y EXIT EXIT 228 Micro Motion 9739 MVD Transmitters Figure C 9 Offline menu Simulation loop testing continued Using the transmitter display Scroll and Select simultaneously for 4 seconds OFF LINE MAINT OFF LINE SIM cont Select dO SIM Scroll Scroll Configuration and Use Manual Read DI Scroll gt Read MAI Actual reading EXIT 229 Using the transmitter display Figure C 10 Offline menu Zero A f Scroll and Select simultaneously A for 4 seconds OFF LINE MAINT Select Scroll ZERO Select a CAL ZERO Scroll RESTORE ZERO Scrol EXIT Select Select ZERO YES 0 000 CUR Z Yes Scroll Scroll Select p e mE Scroll CAL FAIL CAL PASS Y RESTORE ZERO Scroll RESTORE EXIT 230 Micro Motion 9739 MVD Transmitters Appendix D Using ProLink II with the 9739 MVD transmitter Topics covered in this appendix Basic information about the ProLink II software tool Menu maps for ProLink II D 1 Basic information about the ProLink II software tool ProLink II is a software too
67. Mass totalizer Display Variable 3 Volume flow Display Variable 4 Volume totalizer 100 Micro Motion 9739 MVD Transmitters Configure device options and preferences 6 1 3 Configure the precision of process variables shown on the display Display Not available ProLink II ProLink Configuration Display Display Precision Field Communicator Configure Manual Setup Display Set Up Decimal Places For Process Variables For each process variable Display Precision controls the number of digits to the right of the decimal place that are shown on the display You can set Display Precision independently for each process variable Display Precision does not affect the value of the process variable reported via other methods or used in calculations Procedure 1 Select a process variable 2 Set Display Precision to the precision to be applied when this process variable is shown on the display For temperature and density process variables the default value is 2 For all other process variables the default value is 4 The range is 0 to 5 Tip The lower the precision the larger a process change must be in order to be reflected in the displayed value Do not set Display Precision too low or too high to be useful 6 1 4 Configure the refresh rate of data shown on the display Display OFF LINE MAINT OFF LINE CONFG gt DISPLAY RATE ProLink II ProLink Configuration Display Display Options Upd
68. OFF LINE MAINT OFF LINE CONFG UNITS DENS ProLink II ProLink Configuration Density Density Units Field Communicator Configure Manual Setup Measurements Density Density Unit Density Measurement Unit specifies the unit that will be used for density measurement Procedure Set Density Measurement Unit to the desired option The default setting for Density Measurement Unit is g cm3 grams per cubic centimeter Options for Density Measurement Unit The transmitter provides a standard set of units for Density Measurement Unit Different communications tools use different labels Options for Density Measurement Unit are shown in Table 5 9 84 Micro Motion 9739 MVD Transmitters Configure process measurement Table 5 9 Options for Density Measurement Unit Unit description Display ProLink II Specific gravity unit not SGU SGU SGU temperature corrected Field Communicator Grams per cubic G CM3 centimeter g cm3 g Cucm Grams per liter G L G mL KG L KG M3 kg m3 kg Cum Pounds per U S gallon LB GAL Ibs Usgal Ib gal 5 6 2 Configure slug flow parameters Display Not available ProLink II ProLink Configuration Density Slug High Limit ProLink Configuration Density Slug Low Limit ProLink Configuration Density Slug Duration Q Q m Grams per milliliter g ml kg l g mL Kilograms per liter kg L Kilograms per cubic meter Field Communicator Configure Manual
69. OL TYPE GAS ProLink II ProLink Configuration Flow Vol Flow Type Std Gas Volume Field Communicator Configure Manual Setup Measurements Gas Standard Volume Volume Flow Type GSV Volume Flow Type controls whether liquid or gas standard volume flow measurement will be implemented Restriction If you are using the petroleum measurement application you must set Volume Flow Type to Liquid Gas standard volume measurement is incompatible with the petroleum measurement application 74 Micro Motion 9739 MVD Transmitters Configure process measurement Restriction If you are using the concentration measurement application you must set Volume Flow Type to Liquid Gas standard volume measurement is incompatible with the concentration measurement application Procedure Set Volume Flow Type to Gas Standard Volume 5 4 2 Configure Standard Gas Density Display Not available ProLink II ProLink Configuration Flow Std Gas Density Field Communicator Configure Manual Setup Measurements Gas Standard Volume Gas Density Standard Gas Density is used to convert the measured flow data to reference standard values Prerequisites Ensure that Density Measurement Unit is set to the units you will use for Standard Gas Density Procedure Enter the appropriate Standard Gas Density value for the gas you are measuring Tip ProLink II provides a Gas Wizard that you can use to calculate the stand
70. S gal d Million U S gallons per day mil US gal day Liters per second l sec L s Liters per minute l min Million liters per day mil day d Imperial gallons per UKGPS Imp gal sec Impgal s second Imperial gallons per minute Imp gal min Imperial gallons per hour Imp gal hr Imperial gallons per day Imp gal day Barrels per second barrels sec Barrels per minute barrels min Barrels per hour barrels hr Barrels per day barrels day Beer barrels per second Beer barrels sec Beer barrels per minute Beer barrels min Beer barrels per hour Beer barrels hr Beer barrels per day Beer barrels day Configuration and Use Manual 71 Configure process measurement Define a special measurement unit for volume flow Display Not available ProLink II ProLink Configuration Special Units Field Communicator Configure Manual Setup Measurements Special Units Volume Special Units A special measurement unit allows you to report process data totalizer data and inventory data in a unit that is not hard coded in the transmitter A special measurement unit is calculated from an existing measurement unit using a conversion factor Restriction Although you cannot define a special measurement unit using the display you can use the display to select an existing special measurement unit and to view process data Procedure 1 Specify Base Volume Unit Base Volume Unit is the existing volume unit that the special unit will be based on 2
71. Scroll until the mass totalizer value appears b Select c Scroll until RESET appears beneath the current totalizer value d Select e Select again to confirm Scroll to EXIT g Select To reset the volume liquid or gas totalizers using the display a Scroll until the volume totalizer value appears b Select c Scroll until RESET appears beneath the current totalizer value d Select e Select again to confirm f Scroll to EXIT g Select 162 Micro Motion 9739 MVD Transmitters Transmitter operation 8 7 Reset mass and volume inventories using ProLink II Prerequisites To reset the mass and volume inventories you must enable this feature in the ProLink II Preferences window To enable inventory reset using ProLink II do the following 1 Click View Preferences 2 Check the Enable Inventory Totals Reset checkbox 3 Click Apply Procedure To reset all inventories simultaneously click ProLink Totalizer Control Reset Inventories e To reset the mass inventory click ProLink Totalizer Control Reset Mass Inventory To reset the volume liquid inventory click ProLink Totalizer Control Reset Volume Inventory To reset the volume gas inventory click ProLink Totalizer Control Reset Gas Volume Inventory Configuration and Use Manual 163 Chapter 9 Measurement support Topics covered in this chapter Options for measurement support Validate the meter Perform a st
72. Setup Measurements Density Slug Low Limit Configure Manual Setup Measurements Density Slug High Limit Configure Manual Setup Measurements Density Slug Duration The slug flow parameters control how the transmitter detects and reports two phase flow Procedure 1 Set Slug Low Limit to the lowest density value that is considered normal in your process Values below this will cause the transmitter to perform the configured slug flow action Typically this value is the lowest density value in the normal range of your process Tip Gas entrainment can cause your process density to drop temporarily To reduce the occurrence of slug flow alarms that are not significant to your process set Slug Low Limit slightly below your expected lowest process density You must enter Slug Low Limit in g cm3 even if another unit has been configured for density measurement The default value for Slug Low Limit is 0 0 g cm The range is 0 0 g cm to 10 0 g cm Configuration and Use Manual 85 Configure process measurement 2 Set Slug High Limit to the highest density value that is considered normal in your process Tip To reduce the occurrence of slug flow alarms that are not significant to your process set Slug High Limit slightly above your expected highest process density Values above this will cause the transmitter to perform the configured slug flow action Typically this value is the highest density value
73. To configure pressure measurement units Using the display choose OFF LINE MAINT OFF LINE CONFG gt UNITS gt PRESS Using ProLink II choose ProLink Configuration Pressure Pressure Units Using the Field Communicator press Configure Manual Setup Measurements External Compensation Pressure Unit e To configure temperature measurement units see the section on configuring the temperature measurement unit 7 5 2 Configure Lower Range Value LRV and Upper Range Value URV Display OFF LINE MAINT OFF LINE CONFG IO MAI AI 4 mA OFF LINE MAINT OFF LINE CONFG IO MAI Al 20 mA ProLink II ProLink Configuration Milliamp Input Lower Range Value ProLink Configuration Milliamp Input Upper Range Value Field Communicator mA Input LRV Configure Manual Setup Inputs Outputs Milliamp Input mA Input LRV mA Input URV Configure Manual Setup nputs Outputs Milliamp Input mA Input URV The Lower Range Value LRV and Upper Range Value URV are used to scale the readings received from the external measurement device i e to define the relationship between mA input Process Variable and the mA input level received Between LRV and URV the mA input is linear with the process variable If the process variable drops below LRV or rises above URV the transmitter posts an external input error Prerequisites Verify that you have set the measurement units for the pressure or temperature to match
74. V s percent of range and the PV s actual range ProLink II mA level in each burst e g 25 11 0 mA range current Field Communicator Dynamic vars amp PV The transmitter sends PV SV TV and QV values in measurement units current ProLink II and the PV s actual milliamp reading in each burst e g 50 g s 23 C Process 50 g s 0 0023 g cm 11 8 mA variables current Field Communicator Transmitter vars The transmitter sends four user specified process variables in each ProLink II burst Fld dev var Field Communicator 3 Set or verify the burst output variables e If you are using ProLink II and you set Burst Mode Output to Transmitter Vars ProLink II set the four process variables to be sent in each burst ProLink Configuration Device Burst Setup Burst Var 1 4 e If you are using the Field Communicator and you set Burst Mode Output to Field Device Vars set the four process variables to be sent in each burst Configure Manual Setup Inputs Outputs Communications HART Burst Mode Field Device Var 1 4 e If you set Burst Mode Output to any other option verify that the HART variables are set as desired Configure HART variables PV SV TV QV Display N A ProLink II ProLink Configuration Variable Mapping Field Communicator Not available The HART variables are a set of four variables predefined for HART use The HART variables include the Primary Variable PV Secon
75. a he e Check that the transmitter is in loop test i mode A120 i pahaan unable Verify the configuration of the to fix curve data concentration measurement application Configuration and Use Manual 183 Troubleshooting Table 10 2 Status alarms and recommended actions continued A121 Concentration Verif diti Measurement erify process conditions extrapolation alarm Verify the configuration of the concentration measurement application A132 Simulation mode Simulation mode is N ti ired active enabled acum ewe e Disable sensor simulation A133 PIC UI EEPROM error The transmitter display i A141 DDC trigger s have completed Density FD calibration in progress Allow the procedure to complete Density 2nd point calibration in progress Allow the procedure to complete A Density 3rd point N Density 4th point calibration in progress Allow the procedure to complete N A Mechanical zero N A Flow is in reverse gt N ti ired direction o action required 10 3 Flow problems N A Density 1st point calibration in progress Co Allow the procedure to complete N Table 10 3 Flow problems and recommended actions Problem Possible causes Recommended actions Steady non zero flow rate under no flow conditions Misaligned piping especially in new Verify characterization parameters installations If the flow reading is not excessively high Open or leaking valve zero the meter Zeroing with a high false flow r
76. agnostic Variables 1 Temperature 1 Sensor Model 2 Temp Cal Factor 2 Drive Gain 3 Input Voltage 4 LPO Amplitude 5 RPO Amplitude 6 Board Temperature 7 Tube Frequency 8 Live Zero Figure E 13 Service Tools menu Simulate Simulate 1 Simulate Outputs 2 Simulate Sensor Simulate Outputs Simulate Sensor 1 mA Output 1 Loop Test 2 mA Output 2 Loop Test 3 Frequency Output Test 4 Discrete Output Test 1 Simulate Primary Purpose Variables Configuration and Use Manual 247 2010 Micro Motion Inc All rights reserved P N MMI 20016855 Rev AA For the latest Micro Motion product specifications view the PRODUCTS section of our web site at www micromotion com Micro Motion Inc USA Worldwide Headquarters 7070 Winchester Circle Boulder Colorado 80301 T 1 303 527 5200 1 800 522 6277 F 1 303 530 8459 Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T 31 0 318 495 555 F 31 0 318 495 556 Micro Motion United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U K T 44 0870 240 1978 F 44 0800 966 181 Micro Motion Asia Emerson Process Management 1 Pandan Crescent Singapore 128461 Republic of Singapore T 65 6777 8211 F 65 6770 8003 Micro Motion Japan Emerson Process Management 1 2 5 Higashi Shinagawa Shinagawa ku Tokyo 140 0002 Japan T 81 3 5769 6803 F 81 3 5769 6843
77. ake a service port connection Prerequisites You will need the following e An installed licensed copy of ProLink II e An available serial or USB port One of the following types of signal converters RS 232 to RS 485 signal converter USB to RS 485 signal converter e Adapters as required e g 9 pin to 25 pin Important The SP Service Port clips on the display of the 9739 MVD transmitter are directly connected to the RS 485 terminals 26 and 27 of the transmitter If you have wired the transmitter for RS 485 digital communications you must directly connect to the transmitter using the RS 485 terminal block connections or disconnect the RS 485 terminal connections to use the Service Port connections Procedure 1 Attach the signal converter to your PC s serial or USB port 2 Atthe transmitter remove the housing cover to access the transmitter display A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To access transmitter information ina hazardous environment use a communication method that does not require removing the transmitter housing cover 3 Connect the leads on your signal converter to the SP Service Port clips A and B on the face of the transmitter See Figure 3 1 Tip Usually but not always the black lead is RS 485 A and the red lead is RS 485 B
78. alarm log until it is acknowledged If the slug flow condition does not clear before Slug Duration expires outputs that represent flow rate report a flow rate of 0 If Slug Duration is set to 0 0 seconds outputs that represent flow rate will report a flow rate of 0 as soon as slug flow is detected 86 Micro Motion 9739 MVD Transmitters Configure process measurement 5 6 3 Configure Density Damping Display Not available ProLink II ProLink Configuration Density Density Damping Field Communicator Configure Manual Setup Measurements Density Density Damping Damping is used to smooth out small rapid fluctuations in process measurement The Damping Value specifies the time period in seconds over which the transmitter will spread changes in the reported process variable At the end of the interval the reported process variable will reflect 63 of the change in the actual measured value Tips A high damping value makes the process variable appear smoother because the reported value must change slowly A low damping value makes the process variable appear more erratic because the reported value changes more quickly Procedure Set Density Damping to the desired value The default value is 1 6 seconds The range is 0 to 10 24 seconds When you enter a value for Flow Damping the transmitter automatically rounds it down to the nearest valid value The valid values for Flow Damping are 0 0 04 0 08 0 1
79. andard D1 and D2 density calibration Perform a D3 and D4 density calibration T Series sensors only Perform temperature calibration 9 1 Options for measurement support Micro Motion provides several measurement support procedures to help you evaluate and maintain your flowmeter s accuracy The following methods are available e Meter validation compares flowmeter measurements reported by the transmitter to an external measurement standard Meter validation requires one data point e Calibration establishes the relationship between a process variable and the signal produced at the sensor You can calibrate the flowmeter for zero density and temperature Density and temperature calibration require two data points low and high and an external measurement for each Tip Micro Motion recommends using meter validation and meter factors rather than calibration to prove the meter against a regulatory standard or to correct measurement error 9 2 Validate the meter Meter validation compares flowmeter measurements reported by the transmitter to an external measurement standard If the transmitter mass flow volume flow or density measurement is significantly different from the external measurement standard you may want to adjust the corresponding meter factor The flowmeter s actual measurement is multiplied by the meter factor and the resulting value is reported and used in further processing Configuration and Use Manual 1
80. ansmitter Verify wiring between sensor and transmitter Process flow rate beyond the limits of the sensor Verify that the process flow rate is not out of range of the sensor Slug flow Check for slug flow See Section 10 24 No tube vibration in sensor Check for plugging Ensure sensor is free to vibrate no mechanical binding Verify wiring Test coils at sensor See Section 10 27 1 Moisture in the sensor electronics Eliminate the moisture in the sensor electronics The sensor is damaged Contact Micro Motion 10 26 1 Collect pickoff voltage data Prerequisites You will need either ProLink II or a Field Communicator to collect the pickoff voltage data Configuration and Use Manual 197 Troubleshooting Procedure 1 Navigate to the picikoff voltage data e If you are using ProLink Il choose ProLink Diagnostic Information e If you are using a Field Communicator choose Service Tools Maintenance Diagnostic Variables 2 Observe and record data for both the left pickoff and the right pickoff over an appropriate period of time under a variety of process conditions 10 27 Check for electrical shorts Table 10 11 Possible causes and recommended actions for electrical shorts Possible cause Recommended action Moisture inside the junction box Make sure the junction box is dry and no corrosion is present Liquid or moisture inside the sensor case Contact Micro Motion Internally shorted feedthrough Contact M
81. ansmitters Figure C 7 Offline menu configuration display Using the transmitter display OFF LINE MAINT Select Scroll Select ma Scroll Select Scroll H CONFG DISPLAY Select TOTALS RESET TOTALS STOP Scroll DISPLAY OFFLN Scroll DISPLAY ALARM ear DISPLAY ACK Scroll AUTO SCRLL Scroll b d OFFLINE PASSW Scroll DISPLAY RATE _ Serot DISPLAY BKLT Scroll DISPLAY LANG EXIT If you disable access to the offline menu the offline menu will disappear as soon as you exit To re enable access you must use ProLink II or the Field Communicator If Auto Scroll is enabled a Scroll Rate screen is displayed immediately after the Auto Scroll screen If Offline Password is enabled a Change Password screen is displayed immediately after the Offline Password screen Configuration and Use Manual 227 Using the transmitter display Figure C 8 Offline menu Simulation loop testing Scroll and Select simultaneously for 4 seconds Scroll OFF LINE MAINT Select Scroll Select Scroll OFF LINE SIM Select AO 1 SIM AO 2 SIM FO SIM Select Select Select E S SET 2 mA SET 2 mA SET 1
82. ansmitters Troubleshooting A If the transmitter is in a hazardous area do not reapply power to the transmitter with the housing cover removed Reapplying power to the transmitter while the housing cover is removed could cause an explosion 7 Use a voltmeter to test the voltage at the transmitter s power supply terminals The voltage should be within specified limits For DC power you may need to size the cable 10 10 Check sensor to transmitter wiring Prerequisites You will need a copy of the installation manual for your transmitter Procedure 1 Before opening the wiring compartments disconnect the power source Ay If the transmitter is in a hazardous area wait five minutes after disconnecting the power 2 Verify that the transmitter is connected to the sensor according to the information provided in your transmitter installation manual Verify that the wires are making good contact with the terminals Check the continuity of all wires from the transmitter to the sensor 10 11 Check grounding Prerequisites You will need a copy of your sensor installation manual and your transmitter installation manual Procedure Refer to the sensor and transmitter installation manuals for grounding requirements and instructions 10 12 Check for radio frequency interference Perform the actions described here if you suspect your frequency or discrete output is being affected by radio frequency interference RFI Possible sou
83. arameter Display ProLink Il cator Y Lo Fault Level mA Output 2 Added damping Fault action QO Upscale Downscale L Internal zero L None Fault level 7 v Scaling method Q Fregency Flow Q Pulses Unit QO Units Pulse Pulse width Q Active High QO Active Low Polarity Frequency Q Active High output O Active Low Fault action Q Upscale QO Downscale Q Internal zero L None Fault level Power type J Internal Q External 10 Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi parameter ProLink Il cator Assignment Q Calibration in progress Discrete event 1 Discrete event 2 Discrete event 3 Discrete event 4 Discrete event 5 Event 1 Event 2 Fault condition indication Flow switch indication Discrete output CucoOOcoOCODUOOSO Forward Reverse indication Polarity Q Active High QO Active Low Fault action Q Upscale QO Downscale Q None Polarity Q Active High Q Active Low Assignment QO Start zero Discrete input Start stop totalizers Q Reset mass total m Reset gas standard volume total Reset all totals Reset API temperature corrected volume total Power type Q Internal Q External Configuration and Use Manual 11 Before you begin Table 1 3 9739 MVD transmitter configuration setti
84. ard Volume Measurement Unit Unit description Display ProLink II Field Communicator Normal cubic meters per NM3 S Nm3 sec Not available second Normal cubic meters per NM3 MN Nm3 min Not available minute Normal cubic meters per NM3 H Nm3 hr Not available hour Normal cubic meters per NM3 D Nm3 day Not available NLPS NLPM NLPH NLPD SCFS NLPS NLPM NLPH NLPD SCFS Normal liter per second Not available Normal liter per minute Not available Normal liter per hour Not available Normal liter per day Not available Standard cubic feet per Not available second Standard cubic feet per SCFM SCFM Not available minute Standard cubic feet per SCFH SCFH Not available hour Standard cubic feet per SCFD SCFD Not available Standard cubic meters per SM3 S Sm3 S Not available second Standard cubic meters per SM3 MN Sm3 min Not available minute Standard cubic meters per SM3 H Sm3 hr Not available hour Standard cubic meters per SM3 D Sm3 day Not available day Standard liter per second SLPS SLPS Not available Standard liter per minute SLPM SLPM Not available 76 Micro Motion 9739 MVD Transmitters Configure process measurement Table 5 3 Options for Gas Standard Volume Measurement Unit continued Unit description Display ProLink Il Field Communicator Standard liter per hour SLPH SLPH Not available Standard liter per day SLPD SLPD Not available Define a special measurement unit for Gas Stand
85. ard Volume flow Display Not available ProLink II ProLink Configuration Special Units Field Communicator Configure Manual Setup Measurements Special Units Volume Special Units A special measurement unit allows you to report process data totalizer data and inventory data in a unit that is not hard coded in the transmitter A special measurement unit is calculated from an existing measurement unit using a conversion factor Restriction Although you cannot define a special measurement unit using the display you can use the display to select an existing special measurement unit and to view process data Procedure 1 Specify Base Gas Standard Volume Unit Base Gas Standard Volume Unit is the existing Gas Standard Volume unit that the special unit will be based on 2 Specify Base Time Unit Base Time Unit is the existing time unit that the special unit will be based on 3 Calculate Gas Standard Volume Flow Conversion Factor as follows a x base units y special units b Gas Standard Volume Flow Conversion Factor x y Enter the Gas Standard Volume Flow Conversion Factor Set Gas Standard Volume Flow Label to the label to be used for the Gas Standard Volume flow unit Set Gas Standard Volume Total Label to the label to be used for the Gas Standard Volume total and Gas Standard Volume inventory unit The special measurement unit is stored in the transmitter You can configure the transmitter to use the specia
86. ard density of your gas if you do not know it 5 4 3 Configure Gas Standard Volume Flow Measurement Unit Display OFF LINE MAINT OFF LINE CONFG UNITS VOL ProLink II ProLink Configuration Flow Std Gas Vol Flow Units Field Communicator Configure Manual Setup Measurements Gas Standard Volume Gas Vol Flow Unit Gas Standard Volume Flow Measurement Unit specifies the unit will be used for the gas standard volume flow rate The unit used for the gas standard volume total and the gas standard volume inventory is derived from this unit Prerequisites Before you configure Gas Standard Volume Flow Measurement Unit be sure that Volume Flow Type is set to Gas Standard Volume Procedure Set Gas Standard Volume Flow Measurement Unit to the desired unit The default setting for Gas Standard Volume Flow Measurement Unit is SCFM standard cubic feet per minute Configuration and Use Manual 75 Configure process measurement Tip If the measurement unit you want to use is not available you can define a special measurement unit Options for Gas Standard Volume Flow Measurement Unit The transmitter provides a standard set of measurement units for Gas Standard Volume Flow Measurement Unit plus one user defined special measurement unit Different communications tool use different labels for the units Options for Gas Standard Volume Flow Measurement Unit are shown in Table 5 3 Table 5 3 Options for Gas Stand
87. ariables If the value is not correct 1 Verify the HART tag of the external device 2 Verify that the external device is powered up and online 3 Verify the HART mA connection between the transmitter and the external measurement device Configuration and Use Manual 151 Operations maintenance and troubleshooting Chapters covered in this part Transmitter operation Measurement support Troubleshooting Chapter 8 Transmitter operation Topics covered in this chapter Record the process variables View process variables View transmitter status View and acknowledge status alarms Start and stop totalizers and inventories Reset mass and volume totalizers Reset mass and volume inventories using ProLink II 8 1 Record the process variables Micro Motion suggests that you make a record of specific process variable measurements including the acceptable range of measurements under normal operating conditions Making a record of the variable measurements will help you recognize when the process variables are unusually high or low and may help you better diagnose and troubleshoot application issues Procedure Record the following process variables under normal operating conditions Process variable Typical Typical high low O a e a a e T A O T A Peme OOO o SSS S bwan S S 8 2 View process variables Display Scroll to the desired process variable or if AutoScroll is enabled you can wait unti
88. ate Period Field Communicator Configure Manual Setup Display Update Period Update Period controls how often the display is refreshed with current data Configuration and Use Manual 101 Configure device options and preferences Procedure Set Update Period as desired The default value is 200 milliseconds The range is 100 milliseconds to 10 000 milliseconds 10 seconds 6 1 5 Enable or disable automatic scrolling through the display variables Display OFF LINE MAINT OFF LINE CONFG DISPLAY AUTO SCRLL ProLink II ProLink Configuration Display Display Options Display Auto Scroll Field Communicator Not available You can configure the display to show a single display variable indefinitely until the operator activates Scroll or to scroll through the configured display variables and display each one for a user defined number of seconds Procedure 1 Enable or disable Auto Scroll as desired Enabled The display will automatically scroll through the list of display variables showing each display variable for the number of seconds specified by Scroll Rate The operator can move to the next display variable by activating Scroll Disabled default The display will show Display Variable 1 and will not scroll automatically The operator can move to the next display variable by activating Scroll 2 If you enabled Auto Scroll set Scroll Rate as desired The default value is 10 seconds Tip Yo
89. ates Solid yellow Low severity alarm Alarm condition that will not cause measurement error outputs continue to report process data Solid red High severity alarm Alarm condition that will cause measurement error outputs in fault 10 2 Status alarms Table 10 2 Status alarms and recommended actions Continuity failure of Check the drive gain and the pickoff A003 Sensor failure A004 Temperature sensor failure A005 Input overrange 178 drive circuit LPO or RPO or LPO RPO mismatch when driving Combination of A016 and A017 The measured flow has exceeded the maximum flow rate of the sensor AT greater than 200 us voltage See Section 10 25 and Section 10 26 Check the wiring between the sensor and transmitter See Section 10 10 Check for electrical shorts See Section 10 27 Check sensor tubes Check the sensor wiring See Section 10 27 1 Check the wiring between the sensor and transmitter See Section 10 10 Verify temperature characterization parameters Temp Cal Factor Verify process conditions Contact Micro Motion If other alarms are present resolve those alarm conditions first If the current alarm persists continue with the recommended actions Verify process conditions Check for slug flow See Section 10 24 Check the drive gain and the pickoff voltage See Section 10 25 and Section 10 26 Check for electrical shorts See Section 10 27 Check sensor tubes
90. ations applying power to the unit while housing covers are removed or loose can cause an explosion Procedure Turn on the electrical power at the power supply The flowmeter will automatically perform diagnostic routines For transmitters with a display the status LED will turn green and begin to flash when the startup diagnostics are complete If the status LED exhibits different behavior an alarm condition is present Postrequisites Allow the electronics to warm up for approximately 10 minutes before relying on process measurements Although the sensor is ready to receive process fluid shortly after power up the electronics can take up to 10 minutes to warm up completely 3 2 Connect with ProLink II A connection from ProLink II to your transmitter allows you to read process data configure the transmitter and perform maintenance and troubleshooting tasks Configuration and Use Manual 25 Quick start with ProLink Il Prerequisites You must have the following version of ProLink II installed on your computer v2 91 or later 3 2 1 ProLink II connection types The 9739 MVD transmitter has several connections options for communicating via ProLink II You choose a connection type based on what you need to accomplish with the transmitter and the digital communications you are using The 9739 MVD transmitter supports the following ProLink II connection types Service port connections HART Bell 202 connections HART RS 485 co
91. ay Lower Range Value specifies the value of Mass Flow Rate to be represented by an output level of 0 mA or 4 mA a Activate Scroll until AO 14 mA or AO 10 mA appears on the display then activate Select b Define each character in Lower Range Value including the sign Use Select to highlight a specific character Use Scroll to set the value of the character c When you have set all characters as desired activate Scroll and Select simultaneously until SAVE YES flashes on the display then activate Select to write the value to transmitter memory 5 Set Upper Range Value URV Upper Range Value specifies the value of Mass Flow Rate to be represented by an output level of 20 mA a b Activate Scroll until AO 120 mA appears on the display then activate Select Define each character in Upper Range Value including the sign Use Select to highlight a specific character Use Scroll to set the value of the character When you have set all characters as desired activate Scroll and Select simultaneously until SAVE YES flashes on the display then activate Select to write the value to transmitter memory Activate Scroll until AO EXIT appears on the display then activate Select 7 Return the display to normal operation displaying process data a b c d Activate Scroll until IO EXIT appears on the display then activate Select Activate Scroll until CONFIG EXIT appears on the display then activate Select Activate Scroll u
92. be a four digit value with a precision of three i e values between 0 000 and 9 999 Activate Select to move the cursor to the rightmost digit in the mantissa Activate Scroll until the desired character is displayed Activate Select to move the cursor one digit to the left Activate Scroll until the desired character is displayed Activate Select to move the cursor one digit to the left 9 29 5 o Activate Scroll until the desired character is displayed Activate Select to move the cursor one digit to the left 7 Q Activate Scroll until the desired character is displayed 4 Enter the sign a Activate Select to move the cursor one digit to the left b Activate Scroll until the desired character is displayed For positive numbers select a blank space 5 To save the displayed value to transmitter memory activate Scroll and Select simultaneously and hold until the display changes e Ifthe displayed value is the same as the value in transmitter memory you will be returned to the previous screen e lf the displayed value is not the same as the value in transmitter memory SAVE YES flashes on the display Activate Select 6 Optional Switch back from exponential notation to decimal notation a Activate Select until the E is flashing b Activate Select until d is displayed c Activate Select C 3 Display codes for process variables Table C 2 lists and defines the codes used for process variables on the display
93. be able to use a single command to acknowledge all alarms from the display Procedure Enable or disable Acknowledge All Alarms as desired Enabled default Operators can use a single display command to acknowledge all alarms at once Disabled Operators cannot acknowledge all alarms at once They must acknowledge alarms individually Note To acknowledge alarms from the display the operator must have access to the alarm menu whether Acknowledge All Alarms is enabled or disabled 6 3 Configure security for the display menus Display OFF LINE MAINT OFF LINE CONFG DISPLAY OFFLN ProLink II ProLink Configuration Display Display Options Display Offline Menu Field Communicator Not available You can control operator access to different sections of the display off line menu and you can control whether or not a password is required at specific entry points Procedure 1 To control operator access to the maintenance section of the off line menu enable or disable Off Line Menu Configuration and Use Manual 105 Configure device options and preferences om o O Enabled default Operator can access the maintenance section of the off line menu This access is required 106 for configuration and calibration but is not required to view alarms Disabled Operator cannot access the maintenance section of the off line menu To control operator access to the alarm menu enable or disable Alarm Menu own
94. ceeeeeeeeeeeeeee ce eeeeaeeeeaeeeesaeeesaeeeeeneeeeas 3 1 4 Additional documentation and reSOUICES cece cee eeee cece eee eeeeeeeeeeeeeeeaeeeeeeeeaaeees 4 1 5 9739 MVD transmitter configuration Worksheet 0 ccceeeeeeeneeeeeeeeaaeeeeeeeaaeeees 4 Chapter 2 Quickstart withthe display sssssssecscacsisccssasassdssdesssscaseacasscsdssnscausissesscessascasecsesssssacsseses 19 2 1 Apply POWER rer iaaea aeania shes aaa A I EE ESTAA C E Aa aaa 19 2 2 Configuration tips and trikS ccc eee ee cence cece ee anina 19 2 3 Configure the primary mA output to report mass flow rate in a user selected Measurement Unit ccc ccee cece cece cence eee ee cee eect ae ee eeaeeeeaeeeeeaeeeeaaeeesaeeeeaeeeeseeeee 20 2 4 Pertorim aloOp tSt vies scscessed cone onia aa r cataazers Vike none cataaaads TAEAE 21 2 5 Zero the flOwMetel cccceeeceeeeee ce eeee ee eeeceeeeeeeeeecaeeeeaeeeesaeeeeaeeeesaeeeeaeeeesaeees 23 Chapter 3 Quickstart with Prolink I scpucccesessuadcesesviacenunspaacesvosbuasesonvacseesonb duecespebdaavsassedecenseapdanass 25 3 1 Apply pOWET 2cccceeeeceeeeee eee ceeeeee ae ttrt tt tnr tAr EEEE NEE AE EEE SEEE EEEE EEEE E EEEE EE EEEE EEEE 25 3 2 Connect with Prokink Iien iinan anaE AEAEE AEEA E AAE EESAN 25 3 3 Configuration tips and tricks 00 0 0 eee eeeee cece eeeeeeeeaeeeeeeeaaeeeeeeeaaeeeeeaaaeeees 40 3 4 Configure the primary mA output to report mass flow rate in a user selected Measurement Unit
95. col When the HART security switch is set to ON HART protocol cannot be used to perform any action that requires writing to the transmitter For example you cannot change the configuration reset totalizers perform calibration etc using the Field Communicator or ProLink II with a HART Bell 202 or HART RS 485 connection When the HART security switch is set to OFF no functions are disabled Important The HART security switch does not affect Modbus communications A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To access the HART security switch in a hazardous environment be sure to remove power from the transmitter before removing the housing cover and setting the HART security switch Procedure 1 Remove power from the transmitter 2 Remove the transmitter housing cover 3 Move the HART security switch to the desired position see Figure 4 4 Figure 4 4 HART security switch on blank display A HART security switch B Unused 58 4 Replace the transmitter housing cover Restore power to the transmitter Micro Motion 9739 MVD Transmitters Reference information for commissioning Chapters covered in this part Configure process measurement Configure device options and preferences Integrate the meter with the control system Chapter
96. confirm Scroll to EXIT e To start all totalizers and inventories using the display mogao og a Scroll until the word TOTAL appears in the lower left corner of the display Important Because all totalizers are started or stopped together it does not matter which total you use to start or stop the totalizers b Select Scroll until START appears beneath the current totalizer value Select Configuration and Use Manual 161 Transmitter operation e Select again to confirm f Scroll to EXIT 8 6 Reset mass and volume totalizers Display See Section 8 6 1 ProLink II ProLink Totalizer Control Reset Mass Total ProLink Totalizer Control Reset Volume Total ProLink Totalizer Control Reset Gas Volume Total ProLink Totalizer Control Reset Field Communicator Service Tools Variables Totalizer Control Mass Mass Total Service Tools Variables Totalizer Control Gas Standard Volume Volume Total Service Tools Variables Totalizer Control Gas Standard Volume GSV Total Service Tools Variables Totalizer Control All Totalizers Reset All Totals 8 6 1 Reset mass and volume totalizers using the display Prerequisites To reset the totalizers using the display this feature must be enabled and the appropriate process variable Mass Total Volume Total or Gas Volume Total must be configured as a display variable Procedure e To reset the mass totalizer using the display a
97. d Use Manual 123 Integrate the meter with the control system The default value is 2 0 mA The range is 1 0 mA to 3 6 mA Options for mA Output Fault Action and mA Output Fault Level Options for mA Output Fault Action and mA Output Fault Level are shown in Table 7 4 Table 7 4 Options for mA Output Fault Action and mA Output Fault Level Communica ProLink II mA Output Fault Level mA output behavior Upscale Upscale 21 24 mA Goes to the configured fault level Default 22 mA Downscale default Downscale default Goes to the configured fault level 0 0 3 6 mA Default 2 0 mA Internal Zero Intrnl Zero Not applicable Goes to the mA output level associated with a process variable value of 0 zero as determined by Lower Range Value and Upper Range Value settings None None Not applicable Tracks data for the assigned process variable no fault action A If you set mA Output Fault Action or Frequency Output Fault Action to None be sure to set Digital Communications Fault Action to None If you do not the output will not report actual process data and this may result in measurement error or unintended consequences for your process A If you set Digital Communications Fault Action to NAN you cannot set mA Output Fault Action or Frequency Output Fault Action to None If you try to do this the transmitter will not accept the configuration 7 2 Configure the frequency output ProLink II ProLink Configuration Frequency Fie
98. d acknowledge status alarms To view and acknowledge status alarms you can use the transmitter display ProLink II or the Field Communicator The transmitter maintains two status flags for a status alarm e The first status flag indicates Active or Inactive e The second status flag indicates Acknowledged or Unacknowledged An alarm is Active when the transmitter detects that the alarm condition exists An alarm is Inactive when the transmitter detects that the alarm condition has cleared When an alarm is posted it is set to Unacknowledged Operator action is required to change the status from Unacknowledged to Acknowledged whether or not the alarm is still active Configuration and Use Manual 157 Transmitter operation 8 4 1 View or acknowledge status alarms with the display All active Fault or Information alarms are listed in the display alarm menu The transmitter automatically filters out Ignore alarms Prerequisites Operator access to the alarm menu must be enabled default setting If operator access to the alarm menu is disabled you must use ProLink II or the Field Communicator to view or acknowledge status alarms Procedure To view or acknowledge status alarms follow the procedure in Figure 8 2 158 Micro Motion 9739 MVD Transmitters Transmitter operation Figure 8 2 Using the display to view and acknowledge the status alarms Scroll and Select simultaneously for 4 seconds Is ACK ALL enabled Yes
99. d ranges for the most commonly used parameters are provided in Appendix A 4 4 Configure the primary mA output to report mass flow rate in a user selected measurement unit Note This procedure assumes that you are starting from the factory default configuration Procedure 1 Make a connection from the Field Communicator to your transmitter 2 Navigate to the On Line Menu 3 Set the measurement unit for mass flow rate a Press Configure Manual Setup Measurements Flow Mass Flow Unit b Select the desired measurement unit from the list c Press the left arrow until you are returned to the Manual Setup menu 4 Configure the mA output a Press Inputs Outputs mA Output 1 Primary Variable b Select Mass Flow Rate from the list c Press ENTER until you are returned to the mA Output 1 menu d Press mA Output Settings e Press PV LRV and enter an appropriate value for Lower Range Value LRV Lower Range Value specifies the value of Mass Flow Rate to be represented by an output level of 0 mA or 4 mA f Press ENTER g Press PV URV and enter an appropriate value for Upper Range Value LRV Upper Range Value specifies the value of Mass Flow Rate to be represented by an output level of 20 mA h Press ENTER 5 Optional Press Overview Shortcuts Variables Outputs Current mA output 1 and observe the mA output reading Configuration and Use Manual 53 Quick start with the Field Communicator 4 5
100. dary Variable SV Tertiary Variable TV and Quaternary Variable QV You can assign specific process variables to the HART variables and then use standard HART methods to read or broadcast the assigned process data 140 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Options for HART variables Options for HART variables are shown in Table 7 12 Table 7 12 Options for HART variables Process variable Mass flow rate Line Gross Volume flow rate Temperature Density Drive gain Mass total Line Gross Volume total Mass inventory Line Gross Volume inventory Raw Tube frequency Meter temperature T Series LPO amplitude RPO amplitude Board temperature External pressure External temperature Gas standard volume flow rate Gas standard volume total Gas standard volume inventory Live zero API density API volume flow rate API volume total API volume inventory API average density API average temperature API CTL CM density at reference temperature CM specific gravity CM standard volume flow rate CM standard volume total CM standard volume inventory CM net mass flow rate Configuration and Use Manual 141 Integrate the meter with the control system Table 7 12 Options for HART variables continued Prosare o o Cd Cd Ci C a E E CE a A a ewe Sd Interaction of HART variables and transmitter outputs The HART variables are automatically reported thr
101. dicates an Active alarm e A green LED indicates an Inactive alarm that has not been acknowledged 8 4 3 View alarms using the Field Communicator Procedure e Press Service Tools Alerts to view the active Fault and Informational alarms The transmitter automatically filters out Ignore alarms e Press Service Tools Alerts Refresh Alerts to refresh the view of the active alarms e Press Service Tools Alerts and select the individual alarm to view and acknowledge the alarm 8 4 4 Interaction of transmitter fault actions and Alarm Severity level When an alarm condition occurs the transmitter responds by reporting a status alarm Each status alarm has an alarm Alarms are classified into three severity levels Fault Information and Ignore Severity level controls how the transmitter responds to the alarm condition You can change the Alarm Severity for some alarms The transmitter maintains two status flags for each alarm e The first status flag indicates Active or Inactive e The second status flag indicates Acknowledged or Unacknowledged When the transmitter detects an alarm condition the following occurs An alarm is posted for the corresponding alarm First status flag is set to Active Second status flag is set to Unacknowledged e The transmitter checks the severity level for the specific alarm If Severity is Fault outputs go to their configured Fault Action after the configured fault timeout has expired
102. ding to event status 6 Optional Specify the action or actions that the transmitter will perform when the event occurs To do this e With ProLink Il ProLink Configuration Discrete Input e With the Field Communicator Configure Alert Setup Discrete Events Assign Discrete Action Options for Enhanced Event Action Options for Enhanced Event Action are shown in Table 7 16 Table 7 16 Options for Discrete Input Action or Enhanced Event Action Reset volume total volume total Reset volume total RESET VOL si VOL RESET VoL Reset Volume Total Volume Total Reset volume total volume total Reset gas standard volume RESET GSVT eset Youre Teel _ Gas Std Volume Reone standard volume a ae ca Reset all totais all totals RESET ALL ALL Reset All Totais All Totals Reset totas totals Reset temperature TCVOL Reset API Ref Vol Total Reset corrected volume corrected volume total total Reset CM reference RESET STD V Reset CM Ref Vol Total ae total Sa CM net mass total a NET M Reset ee Net Mass Total Reset CM net volume total CM net volume total PRESETNETV NET V Reset CM Net Vol Total CM Net Vol Total Increment CM matrix INCr CURVE Increment Current CM Curve A Before assigning actions to an enhanced event or discrete input check the status of the event or the remote input device If it is ON all assigned actions will be performed when the new configuration is implemented If th
103. display reports Auto zero complete if the zero was successful or Auto zero failed if it was not 4 8 Test or tune the system using sensor simulation Sensor simulation allows you to set specific values or value ranges for mass flow density and temperature The transmitter will report the specified values and take all appropriate actions e g apply a cutoff activate an event or post an alarm You can use this feature to test the system s response to a variety of process conditions including boundary conditions problem conditions or alarm conditions or to tune the loop When you enable sensor simulation the simulated values are stored in the same memory locations used for process data from the sensor Therefore the simulated values will be used throughout transmitter functioning For example sensor simulation will affect All mass flow temperature or density values shown on the display or reported via outputs or digital communications e The mass total and mass inventory values All volume calculations and data including reported values volume totals and volume inventories All mass temperature density or volume values logged to Data Logger Sensor simulation does not affect any diagnostic values Unlike actual mass flow and density values the simulated values are not temperature compensated adjusted for the effect of temperature on the sensor s flow tubes Important Do not enable sensor simulation unless you
104. documents shipped with your sensor or from a code in the sensor model number To interpret the model number refer to the product data sheet for your sensor 2 Set Sensor Flange Type to the appropriate option Configuration and Use Manual 115 Chapter 7 Integrate the meter with the control system Topics covered in this chapter Configure the mA outputs Configure the frequency output Configure the discrete output Configure the discrete input Configure the mA input Configure digital communications Configure events Set up polling for pressure Set up polling for temperature 7 1 Configure the mA outputs Display OFF LINE MAINT OFF LINE CONFG IO AO 1 OFF LINE MAINT OFF LINE CONFG IO AO 2 ProLink II ProLink Configuration Analog Output Field Communicator Configure Manual Setup lInputs Outputs mA Output 1 Configure Manual Setup Inputs Outputs mA Output 2 The mA output is used to report a process variable The mA output parameters control how the process variable is reported Your transmitter has two mA outputs The mA output parameters include e mA Output Process Variable e Lower Range Value LRV and Upper Range Value URV AO Cutoff e Added Damping e AO Fault Action and AO Fault Value Configuration and Use Manual 117 Integrate the meter with the control system Postrequisites Important Whenever you change an mA output parameter verify all other mA outp
105. e device options and preferences Topics covered in this chapter Configure the transmitter display Enable or disable operator actions from the display Configure security for the display menus Configure the speed of the transmitter s response to changes in process data Configure alarm handling Configure informational parameters 6 1 Configure the transmitter display Display OFF LINE MAINT OFF LINE CONFG DISPLAY ProLink II ProLink Configuration Display Field Communicator Configure Manual Setup Display The transmitter display parameters control the process variables shown on the display and a variety of other display behaviors The transmitter display parameters include e Display Language e Display Variables e Display Precision e Update Period e Auto Scroll and Auto Scroll Rate e Backlight e LED Blinking 6 1 1 Configure the language used for display menus and process data shown on the display Display OFF LINE MAINT OFF LINE CONFG gt DISPLAY LANG ProLink II ProLink Configuration Display Display Language Field Communicator Not available Configuration and Use Manual 99 Configure device options and preferences Display Language controls the language used for process data and menus on the display Different languages are available depending on your transmitter model and version Procedure Set Display Language to the desired option 6 1 2 Configure the process variab
106. e you like in transmitter memory Date is a static value and is not updated by the transmitter Date is not used in transmitter processing and is not required Procedure Enter any desired Date in the form mm dd yyyy If you are using ProLink Il you can access a calendar tool from the Device panel to select and enter the data To access the calendar tool click Down Arrow in the Date field 6 6 4 Configure Sensor Serial Number Display Not available ProLink II ProLink Configuration Sensor Sensor S N Field Communicator Configure Manual Setup Info Parameters Sensor Information Transmitter Serial Number Sensor Serial Number provides a place to store the serial number of the sensor component of your flowmeter in transmitter memory Sensor Serial Number is not used in transmitter processing and is not required Procedure 1 Obtain the serial number from your sensor tag 2 Enter the serial number in the Sensor Serial Number field 6 6 5 Configure Sensor Material Display Not available ProLink II ProLink Configuration Sensor Sensor Matl Field Communicator Configure Manual Setup Info Parameters Sensor Information Tube Wetted Material Sensor Material provides a place to store the type of material used for your sensor s wetted parts in transmitter memory Sensor Material is not used in transmitter processing and is not required Procedure 1 Obtain the material used for your sensor s wetted
107. eading can result in a zero failure Bad sensor zero Check for open or leaking valves or seals Check for mounting stress on the sensor e g sensor being used to support piping misaligned piping Contact Micro Motion 184 Micro Motion 9739 MVD Transmitters Troubleshooting Table 10 3 Flow problems and recommended actions continued Problem Possible causes Recommended actions Erratic non zero flow rate under no flow conditions Leaking valve or seal Slug flow Plugged flow tube Incorrect sensor orientation Wiring problem Vibration in pipeline at rate close to sensor tube frequency Damping value too low Mounting stress on sensor Sensor cross talk Configuration and Use Manual Verify that the sensor orientation is appropriate for your application refer to the sensor installation manual Check the drive gain and the pickoff voltage See Section 10 25 and Section 10 26 For installation with 9 wire cabling verify that the 9 wire cable is correctly grounded Check the wiring between the sensor and transmitter See Section 10 10 For sensors with a junction box check for moisture in the junction box Purge the flow tubes Check for open or leaking valves or seals Check for sources of vibration Verify damping configuration Verify that the measurement units are configured correctly for your application Check for slug flow See Section 10 24 Check for radio frequency interfere
108. eceeeeeeeeeeeeeeeeeeeeeeeeeeeees 213 C 2 Access and use the display Menu system 0 00 2 eee ee eee eetneeeeeeaaaeeeeeeaaaeeeees 215 C 3 Display codes for process variables ccccecceeeceeeeeceeeeeeeeeeseaeeeeaeeeesaees 219 C 4 Codes and abbreviations used in display MENUS 0 ceceeeeeeeeeeeeeeeeeeeeeneees 220 C 5 Menu maps for the transmitter display cccsceeceeeeecee teeta eeeeaeeeeaeeeeeaeees 223 AppendixD Using ProLink Il with the 9739 MVD transmitter sssssssscscssssssssceeeeesssssssseeeeeees 231 D 1 Basic information about the ProLink II software tool eesseeeeeeeeeeeeees 231 D 2 Menu maps Tor Procink Il v cccicasesatdztanstadstiansraceddaandaddabanacederaanndend naaancendannnndens 232 Appendix E Using the Field Communicator with the 9739 MVD transmitter ssssscccssssssereeee 237 E 1 Basic information about the Field Communicator ccceeeeeeeeeeeeeeeeees 237 E 2 Menu maps for the Field Communicator cccceeeeeeeeeeeeeeeeeeeeeeaeeeeaeees 238 iii Getting started Chapters covered in this part Before you begin Quick start with the display Quick start with ProLink II Quick start with the Field Communicator Chapter 1 Before you begin Topics covered in this chapter Safety messages Obtain version information Available communications tools Additional documentation and resources 9739 MVD trans
109. eck the configuration of the LRV and URV 10 18 Check mA Output Fault Action Procedure 1 Check the status alarms for fault conditions If no fault conditions are present the source of the problem is something other than the mA fault configuration 2 Check the configuration of mA Output Fault Action 10 19 Check Frequency Output Mode Frequency Output Mode is used only to defined the relationship between two frequency outputs If your transmitter is not configured for two frequency outputs Frequency Output Mode is not causing your output problem Configuration and Use Manual 193 Troubleshooting Procedure Verify the configuration of Frequency Output Mode 10 20 Check Frequency Output Maximum Pulse Width and Frequency Output Scaling Method Procedure 1 Verify the configuration of Frequency Output Scaling Method The scaling method should be set as required by your frequency receiving device If you change the scaling method you may need to configure additional frequency output parameters 2 Verify the configuration of Frequency Output Maximum Pulse Width For most applications the default frequency pulse width is appropriate This corresponds to a 50 duty cycle 10 21 Check Frequency Output Fault Action Procedure 1 Check the status alarms for fault conditions If no fault conditions are present the source of the problem is something other than the frequency output fault configuration 2 Check the config
110. ected volume total Reset CM reference volume total Reset CM net mass total Reset CM net volume total Increment CM matrix Polled variable 1 External Tag Variable type 0 External pressure 0 External temperature Q None Polling control Q None QL Poll As Primary Q Poll As Secondary Polled variable 2 External Tag Variable type Q External pressure 0 External temperature L None Polling control Vv vA Q None Q Poll As Primary Q Poll As Secondary Ooo ee e oC oC a ae Pf of 18 Micro Motion 9739 MVD Transmitters Chapter 2 Quick start with the display Topics covered in this chapter Apply power Configuration tips and tricks Configure the primary mA output to report mass flow rate in a user selected measurement unit Perform a loop test Zero the flowmeter 2 1 Apply power Prerequisites Before you apply power to the flowmeter close and tighten all housing covers A To prevent ignition of flammable or combustible atmospheres make sure all covers are tightly closed For hazardous area installations applying power to the unit while housing covers are removed or loose can cause an explosion Procedure Turn on the electrical power at the power supply The flowmeter will automatically perform diagnostic routines For transmitters with a display the status LED will turn green and begin to flash when the startup diagnostics are complete If the status LED e
111. ee Section 10 12 Contact Micro Motion Verify characterization parameters Verify that the measurement units are configured correctly for your application Zero the meter Check grounding See Section 10 11 Check for slug flow See Section 10 24 Verify that the receiving device and the wiring between the transmitter and the receiving device Check the wiring between the sensor and transmitter See Section 10 10 Micro Motion 9739 MVD Transmitters 10 4 Table 10 4 Problem Inaccurate density reading Unusually high density reading Unusually low density reading 10 5 Table 10 5 Temperature reading significantly different from process temperature Temperature reading slightly different from process temperature Density problems Density problems and recommended actions Troubleshooting Possible causes Recommended actions Problem with process fluid Bad density calibration factors Wiring problem Bad flowmeter grounding Slug flow Sensor cross talk Plugged flow tube Incorrect sensor orientation RTD failure Physical characteristics of sensor have changed Plugged flow tube Incorrect K2 value Slug flow Incorrect K2 value Temperature problems Verify process conditions Verify characterization parameters Check the wiring between the sensor and transmitter See Section 10 10 Check grounding See Section 10 11 Check for slug flow See Section 10 24 If two sensors w
112. eeeeaeeesaaeeesaeeenaeees 190 10 10 Check sensor to transmitter wiring ccecee cece cette eect ee eeeeeeeeeeeeeeeeaaaeeeeeeanaees 191 TOT CHECK GQrOUNGING irasara a AAAA 191 10 12 Check for radio frequency interference ce eeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaneees 191 10 13 Check HART communication lOOp 2 ccceeeeceeeeeeeeeeceaeeeeeeeesaaeeseaeeeesaees 192 10 14 Check HART Address and Loop Current Mode 2 cccceeeeceeeeeeeeeeeeaeeeeaeeeesaeees 192 10 15 Check HART burst MOde 0 c ccecceeeeceeeeee eee cae eeeeaeeesaaeeeeaeeesaaeeeeaeeeeaaeees 193 10 16 Check MA output trim ecenin anina EE 193 10 17 Check Lower Range Value and Upper Range Value cceeeeeeeeeeeeeeeeeeeeeeeeeeeeaneees 193 10 18 Check mA Output Fault ACON ciscccesncedsatasectssearrncbecdanddacstiantvenss saadetadanedadadanantieds 193 10 19 Check Frequency Output Mode cecceeeeceeeeeeeeecaeeeeeaeeesaaeeeeaeeesaaeeeeaeeeeeaeees 193 10 20 Check Frequency Output Maximum Pulse Width and Frequency Output Scaling Me thOG acrana E conneenanmeadierd dvednoetiedaddesticenaeeriededecdsaedes 194 10 21 Check Frequency Output Fault Action cceceeeeeeecee cece ee eeceeeeeeaeeeseaeeeeaeeeeeaeees 194 10 22 Check Flow Direction ras ssteissi rrain love suns chaeedoue resi tune soeeaedad ieee seeteagnaasebaaeeans 194 10 23 Check cutoffs 2 2 2 c ccc c eee eee cece cece ence eee ee cae ee ee ae ee caae
113. eees 138 7 7 CONTIQUIPE SVENS is terlenesetitdsesscestenesecddbbenenaadegersblodewetsuddedbersbdMabianadidgbtenudad 146 7 8 Set up polling for PreSSure ccccececeeeeeeeeeeeeeeeee ae eeeeeeeeeaeeeeeeeeeeaeeeeeeeeeeas 148 7 9 Set up polling for temperature 0ccccceeceeeeeeeeeeee ee eeeeeeeeeaeeeeeeeeeaaeeeeseeeeas 150 Operations maintenance and troubleshooting sscccccccccccccccsssssssssssssessscceees 153 Chapter 8 MGA STMICECH OR ELAMOMN ciscscecsesse2 edasersectcsscasasessnees cosancecodssdsbesacesapeuss eesaansseyesdsatusacedonss 155 8 1 Record the process variables ccccececeeeeeceeeeeeeeeeceaeeeeaeeeeeaeeeeaeeeenaeees 155 8 2 View process variables c ccccceeeeceeeeeeeeeceeeeee ce eeceeeeeaeeeeeeeeeeaaeesseneeeas 155 8 3 View transmitter Status seai cece cece nett reer aa Ka NA ATAKAA 157 8 4 View and acknowledge status AlarMs ccceeeeeeeeeeeeeeeeaaeeeeeeaaaeeeeeeaaeneeees 157 8 5 Start and stop totalizers and inventories cccececceeeee neces eeeeeeeeeeeeeeeees 161 8 6 Reset mass and volume totaliZers eeeeceeeeee eee teeter eee eeeeeeaaeeeeeeeaaeeeeeeeaa 162 8 7 Reset mass and volume inventories using ProLink Il 163 Chapter 9 Measurement SUPPOIt sccccssssssscssssssscccscssssccssssssscccsssssccacsssssscacssssseeanesseseseneess 165 9 1 Options for measurement SUPPOTt 0 ec cece ee ee eeeee eee ee eeeee ae eeeeeeeeeaee
114. eeeseneees 165 9 2 Validate the Meter cccccccecceeceeeeeeceeeeee ae eeeeeeeeaeeeeeeeeeeaeeeeeaeeeeaaeeeeaeeesaaes 165 9 3 Perform a standard D1 and D2 density calibration ecceeeeeeeeee seen 168 9 4 Perform a D3 and D4 density calibration T Series sensors only 0 171 9 5 Perform temperature Calibration 2 c ccecceeeeceeeeeeeeecaaeeeeaeeeeeaeeeeaeeeesaeees 174 Chapter 10 Troubleshooting ssiscsiecssscdstecies cisiecbssecetedsessaetecarscsatesssssdncedsassssctuacacducdesesesdontcdessdsie 177 10 1 Transmitter status LED states cece cece etter eee ee ee eeeeeeeeeeeeeeaaaeeeeeeaaeees 177 10 2 Status alarms cece cece cece cece cence cence cae cess ttrt cae eeeeaeeesaaeeeeaeeesaaeeesaeeessaeees 178 10 3 FloW problems iisecdiccs eetedaegs na phate anes a E E a a a A 184 10 4 Density problemS eeeesseesserreessrrrisserrrssenrsraannttnaannnnaannntaaaantnaaaanaaaannannaana 187 10 5 Temperature problems ccccccecceeeeceeeeeeeeeceeeeeeeeeeseaeeeeaeeeseeeeeeaeeeesaaees 187 10 6 Milliamp output problems ccccccececeeeeeeeeee cee eeeeeeeeseaeeeeaeeesaaeeesaeeeesaeees 188 10 7 Frequency output problems ccccecseeeceeeeeceeeeeeeeeecaaeeeeaeeeseaeeeeaeeeesaeees 189 10 8 Use sensor simulation for troubleshooting cceeeeeeeeeeeeeeeeeeeeeeneeeeeeeaneees 190 10 9 Check power supply wiring 2 0cecc cece cee eece eee cee eeeeaeeecaa
115. eesaeeesaaeeeeaeeesaaeeesaeeeesaeees 194 10 24 Check Tor slug OW isc cicicceceeten eee enka decent cdeee eens cote tae eect nda cece aad cease eae 195 10 25 Check the drive gain 0 cece ce cece eeeee eect eee ee eres ee eeeeeeeeeeeeeeeeseeeeeeeeaaeeeeeeaaaeees 195 10 26 Check the pickoff Voltage 0 cee ce cece eeee rere ee te nesses i 197 10 27 Check for electrical shorts cccecceeee cence ee eeee cee eeeeeeeecaaeeeeaeeesaaeeeeaeeeesaeees 198 Appendices SNE FEOF ENC sissiets cinsteseri core Gidacasiasseacciarccarardeiecceiemaasi a emcees 201 Appendix A Default Valles and FANG CS 52i lt cenccesccdccesvasandasavavaadenssiscacossstauddsnsehaentensniauecscandeensssoe dacs 203 A 1 Default values ANd raNnGeS cceceeee ene eeeee eee eeeeeee ae eeeeeeaaaeeeeeeaaeeeeeeeaaeeeeeeeaa 203 Appendix B Transmitter components and installation WirinG scecsssssscsereecesssssesseeesessesees 207 B 1 Transmitter COMpPONENS cccceeceeee cece a a 207 B 2 Transmitter to SeENSOr WITING ceeee cece eeeee cece ee eeeeeee cae eeeeeaaeeeeeeaaaeeeeeaaaeeeees 209 B 3 Power supply terminals 02 ccceceeeeecee cece eeeecaeeeeeaeeeeeaeeeeaeeeeaaeeeeaeeeesaeees 209 B 4 Input output I O terminals ssena EASA EEE a 210 Appendix C Using the transmitter displayscicsscccsceccssccsccsessiccecsssessccasssecscsasdscecesassssssssedestecesessteeses 213 C 1 Components of the transmitter interface cccec
116. ement The concentration measurement parameters control how the transmitter calculates concentration from temperature and density data Configuration and Use Manual 93 Configure process measurement The concentration measurement parameters include Active Curve Derived Variable Restriction The concentration measurement parameters are available only if the concentration measurement application has been purchased and is enabled on your transmitter Prerequisites Before you can configure concentration measurement e The concentration measurement application must be enabled on your transmitter e The curve you want to use must be available on your transmitter Note Curves can be made available on your transmitter either by loading an existing curve or by configuring a new curve Up to six curves can be available on your transmitter but only one can be used for measurement at any given time See Micro Motion Enhanced Density Application Theory Configuration and Use Manual for information on loading or configuring a curve Procedure 1 Identify the curve you want to use 2 Set Density Measurement Unit to match the density unit used by your curve 3 Set Temperature Measurement Unit to match the temperature unit used by your curve 4 Set Derived Variable to one of the derived variables available with your curve Tip Select a Derived Variable that will provide the concentration measurement process var
117. ement Tag on newer curved tube sensors all sensors except T Series MODEL S N FLOW CAL 19 0005 13 DENS CAL 12502142824 44 D1 0 0010 K1 142502 000 D2 0 9980 K2 14282 000 TC 4 44000 FD 310 TEMP RANGE TO C TUBE CONN x CASE Pe CALIBRATION FACTORS REFERENCE NAXIMUM PRESSURE RATING AT ane MAXIMA PRESSURE RATING AT 256 KOCORDING To ALISE ate 5 OR NER S RATING Figure 5 3 Tag on older straight tube sensor T Series MODEL T100T628SCAZEZZZZ S N 1234567890 FLOW FCF X XXXX FT X XX X XX FFQ X XX XXXXX K1 XXXXX XXX XXXXX K2 XXXXX XXX XX FD XX XX XX DFQ1 XX XX DFQ2 X XX TEMP RANGE XXX TO XXX C TUBE CONN CASE XXXX XXXXX XXXX XXXXXX MAXIMUM PRESSURE RATING AT 25 C ACCORDING TO ASME B31 3 se MAXIMUM PRESSURE RATING AT 25 C ACCORDING TO ANSI ASME B16 5 OR MFR S RATING Figure 5 4 Tag on newer straight tube sensor T Series MODEL T100T628SCAZEZZZZ S N 1234567890 X XX DFQ1 TEMP RANGE XXX TO XXX C TUBE CONN CASE XXXX XXXXX XXXX XXXXXX FLOW FCF XXXX XX XX X XX FFQ X XX XXXXX K1 XXXXX K2 X XX FD XXXXX XXX XXXXX XXX XX XX XX XX DFQ2 X XX MAXIMUM PRESSURE RATING AT 25 C ACCORDING TO ASME B31 3 MAXIMUM PRESSURE RATING AT 25 C ACCORDING TO ANSI ASME B16 5 OR MFR S RATING Configuration and Use Manual 63 Configure process measurement Density calibration parameters D1 D2 K1 K2 FD DT TC If your sensor tag does not
118. endices and reference Appendix A Default values and ranges Topics covered in this appendix Default values and ranges A 1 Default values and ranges See Table A 1 for the default values and ranges for the most frequently used transmitter settings Table A 1 Transmitter default values and ranges Eondon ___ damping 0 8 sec 2 40 96 User entered value is corrected to nearest lower value in list of preset values For gas applications Micro Motion recommends a minimum value of 2 56 ess townie __ flow cutoff 0 0 g s Recommended setting is 5 of the sensor s rated maximum flowrate Volume flow cutoff 0 0 L s 0 0 x L s x is obtained by multiplying the flow calibration factor by 0 2 using units of L s e a A Meter factors Configuration and Use Manual 203 Default values and ranges Table A 1 Transmitter default values and ranges continued Density Slug flow Temperature Pressure T Series sensor 204 Density damping 1 28 sec 0 0 40 96 User entered value is corrected sec to nearest value in list of preset Density cutoff 0 2 g cms 0 0 0 5 e 1 j Temp Coefficient Coefficient Slug flow low limit CE 0 g cm a 0 10 0 g cm Slug flow high limit 5 0 g cm3 0 0 10 0 g cm Temperature damping 4 8 sec 0 0 38 4 sec User entered value is corrected to nearest lower value in list of preset values Temperature calibration factor i oe 00 ae Pressure units
119. ensor with D1 fluid ProLink Menu gt Calibration gt Density cal Point 1 Enter density of D1 fluid Do Cal Do Ca Calibration in Progress light turns red Close shutoff valve downstream from sensor Yy Calibration in Progress light turns green Done 9 3 2 Perform a D1 and D2 density calibration using Field Communicator Prerequisites e During density calibration the sensor must be completely filled with the calibration fluid and flow through the sensor must be at the lowest rate allowed by your application This is usually accomplished by closing the shutoff valve downstream from the sensor then filling the sensor with the appropriate fluid e D1 and D2 density calibration require a D1 low density fluid and a D2 high density fluid You may use air and water e The calibrations must be performed without interruption in the order shown Make sure that you are prepared to complete the process without interruption e Before performing the calibration record your current calibration parameters If the calibration fails restore the known values Restriction For T Series sensors the D1 calibration must be performed on air and the D2 calibration must be performed on water 170 Micro Motion 9739 MVD Transmitters Measurement support Tip For T Series sensors only you have the option to perform a D3 and D4 calibration to improve the accuracy o
120. ensors except T Series 2 Set the flow characterization parameters Be sure to include all decimal points For straight tube sensors set FCF Flow Cal or Flow Calibration Factor FTG and FFQ e For curved tube sensors set Flow Cal Flow Calibration Factor 3 Set the density characterization parameters For straight tube sensors set D1 D2 DT DTG K1 K2 FD DFQ1 and DFQ2 For curved tube sensors set D1 D2 TC K1 K2 and FD TC is sometimes shown as DT 5 1 1 Sources and formats for characterization parameters Different sensor tags display characterization parameters differently and older sensors may not have all the required parameters on the tag Sample sensor tags Sample sensor tags are shown in the following illustrations Figure 5 1 Older curved tube sensors all sensors except T Series e Figure 5 2 Newer curved tube sensors all sensors except T Series e Figure 5 3 Older straight tube sensors T Series e Figure 5 4 Newer straight tube sensors T Series Figure 5 1 Tag on older curved tube sensors all sensors except T Series Sensor S N Meter Type Meter Factor Flow Cal Factor 19 0005 13 Dens Cal Factor 12500142864 44 Cal Factor Ref to 0 C TEMP eC TUBE CONN eMAX PRESSURE RATING AT 25 C ACCORDING TO ASME B31 3 eMAX PRESSURE RATING AT 25 C ACCORDING TO ANSI ASME B16 5 OR MFR S RATING 62 Micro Motion 9739 MVD Transmitters Figure 5 2 Configure process measur
121. ent by mass of HFCS in solution Configuration and Use Manual 95 F C F C C Configure process measurement Table 5 12 Standard concentration curves and associated measurement units continued Curve name Description Density unit Temperature Concentration unit unit mn Derived variables and calculated process variables HFCS 90 Curve represents a hydrometer scale for HFCS 90 high fructose corn syrup solutions that indicates the percent by mass of HFCS in solution 5 10 3 When you configure the concentration measurement application your choice of Derived Variable determines the process variables that will be calculated by the application Table 5 13 lists the options for Derived Variable and the set of process variables that are calculated for each option Table 5 13 Derived variables and calculated process variables Calculated process variables Standard volume flow rate Net volume flow rate Net mass flow rate Concen tration Density at reference tempera ture Specific gravity Derived Variable Description Mass unit volume corrected to a given reference temperature Density at reference temperature The ratio of the density of a process fluid at a given temperature to the density of water at a given temperature The two given temperature conditions do not need to be the same Specific gravity Mass concentration derived from reference density 96 T
122. enu Using the Field Communicator with the 9739 MVD transmitter Check Status 1 Refresh Alerts 2 Dev Status 3 Comm Status Indentification 3 Final Asmbly Num 4 Transmitter Serial Num 5 Date 6 Descriptor 7 Message Primary Purpose Variables Mass Flow Rate Volume Flow Rate Density Mat of Construction 1 Tube Wetted Mat 2 Tube Lining 3 Sensor Flange Licenses 1 Features Shortcuts 1 Device Information 2 Totalizer Control 3 Zero Calibration 4 Variables 5 Trends 6 Meter Verification Device Information 1 Identification 2 Mat of Construction 3 Revisions 4 Licenses Revisions 1 Universal 2 Field Device 3 DD Revision 4 Xmtr Software Rev 5 ETO Number Configuration and Use Manual 239 Using the Field Communicator with the 9739 MVD transmitter Figure E 3 Configure menu top level Manual Setup Alert Setup 1 Characterize 1 Inputs Outputs Fault Actions 2 Measurements 2 Alert Severity 3 Display 3 Discrete Events 4 Inputs Outputs 5 Info Parameters 240 Micro Motion 9739 MVD Transmitters Using the Field Communicator with the 9739 MVD transmitter Figure E 4 Configure menu Manual Setup Characterize Characterize 1 Sensor Type 2 Sensor Tag Parameters Sensor Type 1 Curved Tube 2 Straight Tube Sensor Type traight Tube Sensor Tag Parameters Sensor Tag Parameters 1 Flow Parameters 2 Density Parameters Flow Parameters Density Paramete
123. er You are responsible for following all safety and wiring instructions documented in the transmitter installation manual plus any additional site requirements 210 Micro Motion 9739 MVD Transmitters Transmitter components and installation wiring Figure B 3 IJO terminals Bk ee SS ROMNWOOO VU 21 22 23 24 25 26 27 Table B 2 I O terminals and functions Primary variable PV mA output Primary variable PV mA output Secondary variable SV mA output Secondary variable SV mA output Discrete input Zero RS 485 I O A shared with Service port A on the user interface RS 485 I O B shared with Service port B on the user interface DC power to pressure or DP transmitter mA input from pressure or DP transmitter Configuration and Use Manual 211 Appendix C Using the transmitter display Topics covered in this appendix Components of the transmitter interface Access and use the display menu system Display codes for process variables Codes and abbreviations used in display menus Menu maps for the transmitter display C 1 Components of the transmitter interface See Figure C 1 to view a transmitter with a display See Figure C 2 to view a transmitter without a display Configuration and Use Manual 213 Using the transmitter display Figure C 1 Transmitter with display LCD display Process variable HART security switch Unused
124. event occurs is ON if the real time value of a user specified process variable moves above HI or below LO a user defined setpoint or in range IN or out of range OUT with respect to two user defined setpoints You can define up to five enhanced events For each enhanced event you can assign one or more actions that the transmitter will perform if the enhanced event occurs Procedure 1 Select Event 1 Event 2 Event 3 Event 4 or Event 5 from Event Name 2 Specify Event Type The event will occur if the value of the assigned process variable x is greater than the setpoint Setpoint A endpoint not included x gt A The event will occur if the value of the assigned process variable x is less than the setpoint Setpoint A endpoint not included x lt A The event will occur if the value of the assigned process variable x is in range i e between Setpoint A and Setpoint B endpoints included A lt x lt B The event will occur if the value of the assigned process variable x is out of range i e less than Setpoint A or greater than Setpoint B endpoints included x lt Aorx2 gt B 3 Assign a process variable to the event 4 Set values for the required setpoints For HI or LO events set Setpoint A For IN or OUT events set Setpoint A and Setpoint B Configuration and Use Manual 147 Integrate the meter with the control system 5 Optional Configure a discrete output to switch states accor
125. f the density measurement if the fluid density is outside of the 0 8 g cm to 1 2 g cm density range If you choose to perform the D3 and D4 calibration do not perform the D1 and D2 calibration Procedure To perform a D1 and D2 calibration see Figure 9 2 Figure 9 2 D1 and D2 density calibration using Field Communicator D1 calibration Fill sensor with D1 fluid On Line Menu gt Service Tools gt Maintenance gt Density Calibration Dens Pt 1 Calibration method executes Close shutoff valve downstream from sensor Enter density of D1 fluid D2 calibration Fill sensor with D2 fluid Service Tools gt Maintenance gt Density Calibration Dens Pt 2 Calibration method executes Enter density of D2 fluid OK Calibration in Progress Calibration in Progress message message Density Calibration Complete message Complete message Lok Done 9 4 Perform a D3 and D4 density calibration T Series sensors only For T Series sensors the optional D3 and D4 calibration could improve the accuracy of the density measurement if the fluid density is outside of the 0 8 g cm to 1 2 g cm density range Configuration and Use Manual 171 Measurement support If you perform the D3 and D4 calibration note the following Do not perform the D1 and D2 calibration e Perform the D3 calibration if you have one calibrated fluid e Perform both the D3 and D4 calibrations if you have two cal
126. ferences The informational parameters include e Device parameters Descriptor Message Date e Sensor parameters Sensor Serial Number Sensor Model Number Sensor Material Sensor Liner Material Sensor Flange Type 6 6 1 Configure Descriptor Display Not available ProLink II Not available Field Communicator Configure Manual Setup Info Parameters Transmitter Info Descriptor Descriptor provides a place to store any phrase you like in transmitter memory You can use Descriptor to describe your transmitter or flowmeter Descriptor is not used in transmitter processing and is not required Procedure Enter any desired phrase Descriptor can contain a maximum of 16 characters 6 6 2 Configure Message Display Not available ProLink II Not available Field Communicator Configure Manual Setup lInfo Parameters Transmitter Info Message Message provides a place to store any phrase you like in transmitter memory You can use Message to describe your transmitter or flowmeter Message is not used in transmitter processing and is not required Procedure Enter any desired phrase Message can contain a maximum of 32 characters Configuration and Use Manual 113 Configure device options and preferences 6 6 3 Configure Date ProLink II Not available Field Communicator Configure Manual Setup Info Parameters Transmitter Info Date Date provides a place to store any dat
127. flow the mA output is 4 mA e Under conditions of forward flow up to a flow rate of 100 g s the mA output varies between 4 mA and 20 mA in proportion to the flow rate e Under conditions of forward flow if the flow rate equals or exceeds 100 g s the mA output will be proportional to the flow rate up to 20 5 mA and will be level at 20 5 mA at higher flow rates Example Flow Direction Forward and Lower Range Value lt 0 Configuration e Flow Direction Forward e Lower Range Value 100 g s e Upper Range Value 100 g s Configuration and Use Manual 81 Configure process measurement Result e Under conditions of zero flow the mA output is 12 mA e Under conditions of forward flow for flow rates between 0 and 100 g s the mA output varies between 12 mA and 20 mA in proportion to the absolute value of the flow rate e Under conditions of forward flow if the absolute value of the flow rate equals or exceeds 100 g s the mA output is proportional to the flow rate up to 20 5 mA and will be level at 20 5 mA at higher flow rates e Under conditions of reverse flow for flow rates between 0 and 100 g s the mA output varies between 4 mA and 12 mA in inverse proportion to the absolute value of the flow rate e Under conditions of reverse flow if the absolute value of the flow rate equals or exceeds 100 g s the mA output is inversely proportional to the flow rate down to 3 8 mA and will be level at 3 8 mA at hi
128. fter every power cycle A108 Event 1 triggered Informational Applies only to basic events A109 Event 2 triggered Informational Applies only to basic events A110 Frequency output saturated Informational Can be set to either Informational or Yes Ignore but cannot be set to Fault A111 Frequency output fixed i Informational Can be set to either Informational or Ignore but cannot be set to Fault A113 Secondary mA output saturated Informational Can be set to either Informational or Ignore but cannot be set to Fault A114 Secondary mA output fixed Informational Can be set to either Informational or Ignore but cannot be set to Fault A115 External input error Informational Yes A116 API temperature outside standard range Informational Applies only to transmitters with the petroleum measurement application A117 API density out of limits Informational Applies only to transmitters with the petroleum measurement application A118 Discrete output 1 fixed Informational Can be set to either Informational or Ignore but cannot be set to Fault A120 Concentration measurement unable to fix curve data Informational Applies only to transmitters with the concentration measurement application A121 Concentration measurement extrapolation alarm Informational Applies only to transmitters with the concentration measurement application Configu
129. g e If Frequency Factor is greater than 10 000 Hz reconfigure the receiving device for a lower pulses unit setting Tip If Frequency Output Scale Method is set to Frequency Flow and Frequency Output Maximum Pulse Width is set to a non zero value Micro Motion recommends setting Frequency Factor to a value less than 200 Hz Example Configure Frequency Flow You want the frequency output to report all flow rates up to 2000 kg min The frequency receiving device is configured for 10 pulses kg Solution FrequencyFactor RateFactor xN FrequencyFactor a x 10 FrequencyFactor 333 33 Set parameters as follows e Rate Factor 2000 e Frequency Factor 333 33 126 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system 7 2 2 Configure Frequency Output Maximum Pulse Width Display Not available ProLink II ProLink Configuration Frequency Freq Pulse Width Field Communicator Configure Manual Setup Inputs Outputs Frequency Output FO Settings Max Pulse Width Frequency Output Maximum Pulse Width is used to ensure that the duration of the ON signal is great enough for your frequency receiving device to detect The ON signal may be the high voltage or 0 0 V depending on Frequency Output Polarity as shown in Table 7 5 Table 7 5 Interaction of Frequency Output Maximum Pulse Width and Frequency Output Polarity Polarity Pulse width Active High Active Low
130. gher absolute values Example Flow Direction Reverse Configuration e Flow Direction Reverse e Lower Range Value 0 g s e Upper Range Value 100 g s Result e Under conditions of forward flow or zero flow the mA output is 4 mA Under conditions of reverse flow for flow rates between 0 and 100 g s the mA output level varies between 4 mA and 20 mA in proportion to the absolute value of the flow rate e Under conditions of reverse flow if the absolute value of the flow rate equals or exceeds 100 g s the mA output will be proportional to the absolute value of the flow rate up to 20 5 mA and will be level at 20 5 mA at higher absolute values Flow Direction and frequency outputs Frequency outputs are affected by Flow Direction only if Frequency Output Process Variable is set to a flow variable Frequency output levels for different combinations of Flow Direction and actual flow direction are shown in Table 5 5 Table 5 5 Effect of the Flow Direction parameter and actual flow direction on frequency outputs 1 Refer to the digital communications status bits for an indication of whether flow is positive or negative 82 Micro Motion 9739 MVD Transmitters Configure process measurement Flow Direction and discrete outputs Discrete outputs are affected by Flow Direction only if Discrete Output Source is set to Flow Direction Discrete output states for different combinations of Flow Direction and actual flow directi
131. gure HART Bell 202 communications ProLink II ProLink Configuration Device Digital Comm Settings Field Communicator Configure Manual Setup nputs Outputs Communications HART Communications HART Bell 202 communications parameters support HART communication with the transmitter s primary mA terminals over a HART Bell 202 network The HART Bell 202 communications parameters include e HART Address Polling Address e Loop Current Mode ProLink II or mA Output Action Field Communicator e Burst Parameters optional e HART Variables optional 138 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Procedure 1 Set HART Address to a value between 0 and 15 HART Address must be unique on the network The default address 0 is typically used unless you are in a multidrop environment Tip Devices using HART protocol to communicate with the transmitter may use either HART Address or HART Tag Software Tag to identify the transmitter You may configure either or both as required by your other HART devices 2 Check the setting of Loop Current Mode mA Output Action and change it if required Enabled The primary mA output reports process data as configured Disabled The primary mA output is fixed at 4 mA and does not report process data Tip Whenever you use ProLink II to set HART Address to 0 ProLink II also enables Loop Current Mode Whenever you use ProLink II to
132. he display Activate Scroll Enter a floating point value using exponential notation Exponential notation is used to enter values that are larger than 99999999 or smaller than 9999999 Exponential values entered via the display must be in the following form SX XXXEYY In this string e S Sign A minus sign indicates a negative number A blank indicates a positive number e X XXX The four digit mantissa e E The exponent indicator e YY The two digit exponent Procedure 1 Switch from decimal notation to exponential notation a Activate Select as required until the rightmost digit is flashing b Activate Scroll until E is displayed c Activate Select Tip If you have modified the value in decimal notation without saving the changes to transmitter memory the changes will be lost when you switch to exponential notation Save the decimal value before switching to exponential notation 2 Enter the exponent The first character may be a minus sign or any digit between 0 and 3 The second character may be any digit between 0 and 9 a Activate Select to move the cursor to the rightmost character on the display b Activate Scroll until the desired character is displayed c Activate Select to move the cursor one position to the left d Activate Scroll until the desired character is displayed 3 Enter the mantissa 218 Micro Motion 9739 MVD Transmitters Using the transmitter display The mantissa must
133. he meter factor as follows a Use the flowmeter to take a sample measurement b Measure the same sample using the reference device c Calculate the meter factor using the following formula 166 Micro Motion 9739 MVD Transmitters Measurement support NewMeterFactor ConfiguredMeterFactor x pele eae et FlowmeterMeasurement 2 Ensure that the calculated meter factor is between 0 8 and 1 2 inclusive If the meter factor is outside these limits contact Micro Motion Customer Service 3 Configure the meter factor in the transmitter To set the meter factor using the display OFF LINE MAINT CONFG UNITS MTR F e To set the meter factor using ProLink II ProLink Configuration Flow To set the meter factor using the Field Communicator Configure Manual Setup Measurements Flow Configure Manual Setup Measurements Density Example Calculating the meter factor for mass flow The flowmeter is installed and validated for the first time The mass flow measurement from the transmitter is 250 27 lb the mass flow measurement from the reference device is 250 Ib A mass flow meter factor is determined as follows 250 MeterFactormassriow 1 X MH 0 9989 250 27 The first meter factor for mass flow is 0 9989 One year later the flowmeter is validated again The flowmeter mass measurement is 250 07 Ib the reference device measurement is 250 25 Ib A new mass flow meter factor is determined as follo
134. he percent mass of solute or of material in suspension in the total solution derived from reference density Micro Motion 9739 MVD Transmitters Configure process measurement Table 5 13 Derived variables and calculated process variables continued Derived Variable Mass concentration derived from specific gravity Volume concentration derived from reference density Volume concentration derived from specific gravity Concentration derived from reference density Concentration derived from specific gravity Density at reference tempera Description ture The percent mass of solute or of material in suspension in the total solution derived from specific gravity The percent volume of solute or of material in suspension in the total solution derived from reference density The percent volume of solute or of material in suspension in the total solution derived from specific gravity volume weight or number of moles of solute or of material in suspension in proportion to the total solution derived from reference density The mass volume weight or number of moles of solute or of material in suspension in proportion to the total solution derived from specific gravity Configuration and Use Manual Standard volume flow rate Calculated process variables Concen tration Specific gravity Net mass flow rate Net volume flow rate 97 Chapter 6 Configur
135. iables that you want to use If you are using one of the standard curves from Micro Motion set Derived Variable to Mass Conc Dens If you are using a custom curve see the reference information for your curve 5 Set Active Curve to the curve you identified in Step 1 6 Optional If you want the concentration measurement application to use temperature data from an external temperature sensor a Set Temperature Source to External b Setup polling for temperature or configure the mA input to receive temperature data from an external measurement device You can now configure your transmitter to report and handle concentration process variables in the same way that it reports and handles other process variables 94 Micro Motion 9739 MVD Transmitters Configure process measurement 5 10 1 Concentration measurement application The concentration measurement application calculates concentration data from process temperature and density Micro Motion provides a set of concentration curves that calculate concentration data for several standard industry applications and process fluids If desired you can configure a custom curve for your process fluid or purchase a custom curve from Micro Motion Note The concentration measurement application is also known as the enhanced density application 5 10 2 Standard curves for the concentration measurement application The standard curves available from Micro Motion are applicable to a
136. iations used in display menus Table C 3 lists and defines the codes and abbreviations used in the display menus 220 Micro Motion 9739 MVD Transmitters Table C 3 Codes and abbreviations used in display menus Code or abbreviation Definition ACK ALARM Acknowledge alarm ACK ALL Acknowledge all alarms Action ADDR Address AO 1 SRC Fixed to the process variable assigned to the primary output Analog output 1 primary mA output Analog output 2 secondary mA output AUTO SCRLL Auto Scroll Backlight B LIGHT CAL Calibrate Channel A Channel B Channel C CHANGE PASSW CHANGE CODE Change password or passcode Configuration Core processor Current zero CUSTODY Custody transfer XFER Discrete event DENS Density DGAIN DRIVE Drive gain Discrete input Disable Discrete output 1 Discrete output 2 Display Event 1 or Event 2 Enable ENABLE ACK Enable acknowledge all ENABLE ALARM Enable alarm menu Configuration and Use Manual Using the transmitter display Comment or reference Change the password or passcode required for access to display functions Events configured using the enhanced event model Select to disable Events configured using the basic event model Select to enable Enable or disable the ACK ALL function Access to alarm menu from display 221 Using the transmitter display Table C 3 Codes and abbreviations used in display menus continued Code or abbreviati
137. ibrated fluids other than air and water The calibrations must be performed without interruption in the order shown Make sure that you are prepared to complete the process without interruption 9 4 1 Perform a D3 and D4 density calibration using ProLink Il Prerequisites e During density calibration the sensor must be completely filled with the calibration fluid and flow through the sensor must be at the lowest rate allowed by your application This is usually accomplished by closing the shutoff valve downstream from the sensor then filling the sensor with the appropriate fluid e For D3 density calibration the D3 fluid must meet the following requirements Minimum density of 0 6 g cm3 Minimum difference of 0 1 g cm between the density of the D3 fluid and the density of water The density of the D3 fluid may be either greater or less than the density of water e For D4 density calibration the D4 fluid must meet the following requirements Minimum density of 0 6 g cms Minimum difference of 0 1 g cm between the density of the D4 fluid and the density of the D3 fluid The density of the D4 fluid must be greater than the density of the D3 fluid Minimum difference of 0 1 g cm between the density of the D4 fluid and the density of water The density of the D4 fluid may be either greater or less than the density of water Before performing the calibration record your current calibration parameters You can do this
138. ical switch Select Optical switch Scroll qa mMm og nH BD gt Optical switch indicator turns red when Scroll activated 156 Micro Motion 9739 MVD Transmitters Transmitter operation 8 3 View transmitter status Display See Section 8 3 1 ProLink II Prolink Status Field Communicator Overview Check Status 8 3 1 View transmitter status using the status LED The status LED is located on the user interface module of the transmitter Procedure View the status LED on the user interface module of the transmitter e For transmitters with a display you can view the status LED with the transmitter housing cover in place e For transmitters without a display the transmitter housing cover must be removed to view the status LED A If the transmitter is in a hazardous area do not remove the housing cover while power is supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To view transmitter status in a hazardous environment use a communication method that does not require removing the transmitter housing cover To interpret the status LED see Table 8 1 Table 8 1 9739 MVD status LED states Solid green Normal operation Solid yellow Low severity alarm Alarm condition that will not cause measurement error outputs continue to report process data Solid red High severity alarm Alarm condition that will cause measurement error outputs in fault 8 4 View an
139. ice Tools Simulate Simulate Outputs Frequency Output Test and choose the frequency output level b Read the frequency signal at the receiving device and compare it to the transmitter output c Choose End Test the discrete output Press Service Tools Simulate Simulate Outputs Discrete Output Test a b Choose Off 9 Verify the signal state at the receiving device d Choose On e Verify the signal state at the receiving device Micro Motion 9739 MVD Transmitters Quick start with the Field Communicator f Choose End Postrequisites If the mA output readings were slightly off at the receiving device you can correct this discrepancy by trimming the output e If the mA output reading was significantly off 200 microamps or if at any step the reading was faulty verify the wiring between the transmitter and the remote device and try again e If the mA input reading was slightly off at the transmitter trim and calibrate the input at the remote input device 4 6 Trim mA outputs Trimming the mA outputs is not a required procedure However if there is a small discrepancy in the mA reading between the transmitter and the receiving device trimming the output will correct this Note Any trimming performed on the output should not exceed 200 microamps If more trimming is required contact Micro Motion customer support Procedure 1 Press Service Tools Maintenance Routine Maintenance Tr
140. icro Motion Faulty cable Replace the cable Improper wire termination Verify wire terminations inside sensor junction box The Micro Motion document titled 9 Wire Flowmeter Cable Preparation and Installation Guide may offer some assistance 10 27 1 Check the sensor coils for 9 wire transmitter Procedure 1 Disconnect power to the transmitter A If the transmitter is in a hazardous area wait 5 minutes Remove the transmitter housing cover Unplug the terminal blocks from the terminal board Using a digital multimeter DMM check the pickoff coils listed in Table 10 12 by placing the DMM leads on the unplugged terminal blocks for each terminal pair Record the values Table 10 12 Coils and test terminal pairs Resistance temperature detector All Yellow to violet RTD Lead length compensator LLC All except T Series and CMF400 Yellow to orange 198 Micro Motion 9739 MVD Transmitters Troubleshooting There should be no open circuits that is no infinite resistance readings The left pickoff and right pickoff readings should be the same or very close 5 Q If there are any unusual readings repeat the coil resistance tests at the sensor junction box to eliminate the possibility of faulty cable The readings for each coil pair should match at both ends 5 Test the terminals in the sensor junction box for shorts to case a Leave the terminal blocks disconnected b Remove the lid of the junction box c Testing one
141. im mA output 1 to start the mA trim procedure Follow the instructions in the guided method to trim the mA output Choose Service Tools Maintenance Routine Maintenance Trim mA output 2 to start the trim procedure for the secondary mA output 4 Follow the instructions in the guided method to trim the mA output 4 7 Zero the flowmeter Prerequisites To prepare for the zero procedure 1 Allow the flowmeter to warm up for at least 20 minutes after applying power 2 Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature 3 Stop flow through the sensor by shutting a valve downstream from the sensor 4 Ensure that flow has completely stopped through the sensor and that the sensor is completely full of process fluid 5 Check the flow rate If the flow rate is close to zero you should not need to zero the flowmeter Important The meter was zeroed at the factory and should not require a field zero Configuration and Use Manual 55 Quick start with the Field Communicator Note Do not zero the flowmeter if a high severity alarm is active Correct the problem then zero the flowmeter You may zero the flowmeter if a low severity alarm is active Procedure To initiate the flowmeter zero press Service Tools Maintenance Zero Calibration Perform Auto Zero The display will report Calibration in progress When the calibration is complete the
142. in the normal range of your process You must enter Slug High Limit in g cm3 even if another unit has been configured for density measurement The default value for Slug High Limit is 5 0 g cm3 The range is 0 0 g cm to 10 0 g cms 3 Set Slug Duration to the number of seconds that the transmitter will wait for a slug flow condition to clear before performing the configured slug flow action The default value for Slug Duration is 0 0 seconds The range is 0 0 seconds to 60 0 seconds Slug flow detection and reporting Slug flow is typically used as an indicator of two phase flow gas in a liquid process or liquid in a gas process Two phase flow can cause a variety of process control issues By configuring the slug flow parameters appropriately for your application you can detect process conditions that require correction Tip To decrease the occurrence of slug flow alarms lower Slug Low Limit or raise Slug High Limit A condition of slug flow occurs whenever the measured density goes below Slug Low Limit or above Slug High Limit If this occurs A slug flow alarm is posted to the active alarm log All outputs that are configured to represent flow rate hold their last pre slug flow value for the configured Slug Duration If the slug flow condition clears before Slug Duration expires e Outputs that represent flow rate revert to reporting actual flow The slug flow alarm is deactivated but remains in the active
143. ions Procedure 1 Select a status alarm 2 Set Status Alarm Severity as desired Actions when alarm is detected Alarm posted to Alert List Outputs go to configured fault action after Fault Timeout has expired if applicable Digital communications go to configured fault action after Fault Timeout has expired if applicable Status LED changes to red or yellow depending on alarm severity Actions when alarm clears Outputs return to normal behavior Digital communications returns to normal behavior Status LED changes behavior returns to green may or may not flash Informational Actions when alarm is detected Alarm posted to Alert List e Status LED changes to red or yellow depending on alarm severity Actions when alarm clears e Status LED changes behavior returns to green may or may not flash Ignore No action Status alarms and options for Status Alarm Severity Each status alarm has a default Status Alarm Severity Some status alarms can be configured for other severity levels Configuration and Use Manual 109 Configure device options and preferences Status alarms default severity settings and related information are listed in Table 6 1 Table 6 1 Status alarms and Status Alarm Severity Default severity Alarm Status message code A003 Sensor failure Fault A004 Temperature sensor failure Fault A005 Input overrange Fault A006 Transmitter not configu
144. irect analog current to write pressure data to the transmitter set Pressure Units to the units to be used and ensure that polling for pressure is disabled Then ensure that the appropriate value is written to transmitter memory at appropriate intervals e If you will use an external measurement device configure the mA input to External Pressure You must also enable External Pressure Compensation and set the Pressure Units to the units set at the external measurement device 5 9 Configure the petroleum measurement application Display Not available ProLink II ProLink Configuration API Setup Field Communicator Configure Manual Setup Measurements Petroleum Measurement The petroleum measurement parameters control the values that will be used in the transmitter s petroleum measurement application The petroleum measurement parameters include e API Table Type e Thermal Expansion Coefficient TEC if required by API Table Type e Reference Temperature if required by API Table Type Restriction The petroleum measurement parameters are available only if the petroleum measurement application has been purchased and is enabled on your transmitter Procedure 1 Select API Table Type 2 If you set API Table Type to 53A 53B 53D or 54C set Reference Temperature to the appropriate value for your application Enter the value in C 3 If you set API Table Type to 6C 24C or 54C set Thermal Expansion Coefficient to
145. is is not acceptable wait until an appropriate time to assign actions to the event or discrete input 7 8 Set up polling for pressure Display Not available ProLink II ProLink Configuration Polled Variables External Pressure Field Communicator Configure Manual Setup Measurements External Compensation External Polling 148 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system The transmitter can poll an external pressure device for current pressure data The pressure value is used only for pressure compensation If you are not implementing pressure compensation do not set up polling for pressure Tip To obtain value from pressure compensation the external measurement device must be reliable and accurate Prerequisites Polling requires HART protocol over the Bell 202 physical layer Ensure that the primary mA output on your transmitter has been wired for HART protocol and that the external measurement device is accessible over the HART network Procedure 1 Select Polled Variable 1 or Polled Variable 2 2 Set Polling Control Polling Control determines how the transmitter will access the external measurement device Primary The transmitter is the only device that will access the external measurement device as a primary master Secondary Another device on the network will access the external measurement device as a primary master Tip If you set up polling f
146. iscrete output is controlled by its assignment controlled by its assignment D D ad ila Fault discrete output is OFF Fault discrete output is ON 0 V site specific voltage No fault discrete output is No fault discrete output is controlled by its assignment controlled by its assignment None default None default Discrete output is controlled by its assignment Fault indication with the discrete output To indicate faults via the discrete output set parameters as follows e Discrete Output Source Fault e Discrete Output Fault Action None Configuration and Use Manual 133 Integrate the meter with the control system Note If Discrete Output Source is set to Fault and a fault occurs the discrete output is always ON The setting of Discrete Output Fault Action is ignored 7 3 4 Configure Discrete Output Power Source Display OFF LINE MAINT OFF LINE CONFG IO DO POWER ProLink II ProLink Configuration Discrete Output Power Type Field Communicator Configure Manual Setup lInputs Outputs Discrete Output Power Source Use Discrete Output Power Source to set the output power source for the discrete output The power configuration must match the wiring for the discrete output Procedure Set Discrete Output Power Source as desired Internal The output is powered by the transmitter External The output is powered by an external power source 7 4 Configure the discrete input
147. ith similar frequency are too near each other separate them Purge the flow tubes Verify characterization parameters Purge the flow tubes Check for coating in the flow tubes Verify process conditions Verify characterization parameters Check the wiring between the sensor and transmitter See Section 10 10 Check for tube erosion especially if the process fluid is abrasive Temperature problems and recommended actions Possible causes Recommended actions e RTD failure e Wiring problem Sensor leaking heat Configuration and Use Manual Refer to status alarms especially RTD failure alarms Disable external temperature compensation Verify temperature calibration Check the wiring between the sensor and transmitter See Section 10 10 Perform temperature calibration 187 Troubleshooting 10 6 Milliamp output problems Table 10 6 Problem No mA output Loop test failed mA output below 4 mA Constant mA output mA output consistently out of range 188 Wiring problem Circuit failure Power supply problem Incorrect internal external power configuration Output not powered Wiring problem Circuit failure Process condition below LRV LRV and URV are not set correctly Fault condition if fault indicator is set to internal zero or downscale Open in wiring Bad mA receiving device Bad output circuit Non zero HART address mA output 1 Output is fixed in text
148. ity base or known thermal expansion coefficient 2 2 2 2 Generalized crude and JP4 Generalized products 3A 3B 3D 4C 53A 53B 53D Lubricating oils 54C Liquids with a constant density base or known thermal expansion coefficient 5 10 Observed density and observed temperature Observed density and observed temperature Observed density and observed temperature User supplied reference density or thermal expansion coefficient and observed temperature Observed density and observed temperature Observed density and observed temperature Observed density and observed temperature User supplied reference density or thermal expansion coefficient and observed temperature 60 F non configurable 60 F non configurable 60 F non configurable 60 F non configurable 15 C configurable 15 C configurable 15 C configurable 15 C configurable Relative density Range 0 6110 to 1 0760 Relative density Range 0 6535 to 1 0760 Relative density Range 8520 to 1 1640 Relative density Base density Range 610 to 1075 kg m3 Base density Range 653 to 1075 kg m3 Base density Range 825 to 1164 kg m3 Base density in kg m3 Configure the concentration measurement application Display Not available ProLink II ProLink Configuration CM Setup Field Communicator Configure Manual Setup Measurements Concentration Measur
149. k start with ProLink Il Tip If you do not know the transmitter s RS 485 communication settings you can connect through the service port which always uses default settings or use another communications tool to view or change the settings 8 Set the COM Port value to the PC COM port that you are using for this connection 9 Click Connect If the connection is successful The status bar in the main window is updated to show an active connection e The Process Variables window or Commissioning Wizard window is displayed If an error message appears e Switch the leads and try again e Ensure that you are using the correct COM port e Check the physical connection between the PC and the transmitter e For long distance communication or if noise from an external source interferes with the signal install 120 Q 72 W terminating resistors in parallel with the output at both ends of the communication segment 3 3 Configuration tips and tricks Review these tips before beginning configuration 3 3 1 HART security HART security may be enabled on the 9739 MVD transmitter To configure the transmitter using HART protocol you must disable HART security 3 3 2 Default values and ranges Default values and ranges for the most commonly used parameters are provided in Appendix A 3 3 3 Restore the factory configuration Restoring the factory configuration returns the transmitter to a known operational configuration Procedure 1
150. l available from Micro Motion It runs on a Windows platform and provides complete access to transmitter functions and data ProLink Il documentation Most of the instructions in this manual assume that you are already familiar with ProLink II or that you have a general familiarity with Windows programs If you need more information on than this manual provides see the ProLink II manual In most ProLink II installations the manual is installed with the ProLink II program Additionally the ProLink II manual is available on the Micro Motion documentation CD or the Micro Motion web site ProLink Il features ProLink II offers a number of special features including e The ability to save the transmitter configuration set to a file on the PC and reload it or propagate it to other transmitters e The ability to log specific types of data to a file on the PC e A commissioning wizard A proving wizard These features are documented in the ProLink Il manual They are not documented in the current manual ProLink Il messages As you use ProLink II with a Micro Motion transmitter you will see a number of messages and notes This manual does not document all of these messages and notes Important The user is responsible for responding to messages and notes and complying with all safety messages Configuration and Use Manual 231 Using ProLink II with the 9739 MVD transmitter D 2 Figure D 1 Menu maps for ProLink II Main men
151. l measurement unit at any time Example Defining a special measurement unit for Gas Standard Volume flow You want to measure Gas Standard Volume flow in thousands of standard cubic feet per minute 1 Set the Base Gas Standard Volume Unit to SCFM Configuration and Use Manual 77 Configure process measurement 2 Set the Base Time Unit to minutes min 3 Calculate the conversion factor a 1 thousands of standard cubic feet per minute 1000 cubic feet per minute b Gas Standard Volume Flow Conversion Factor 1 1000 0 001 4 Set Gas Standard Volume Flow Conversion Factor to 0 001 5 Set Gas Standard Volume Flow Label to KSCFM 6 Set Gas Standard Volume Total Label to KSCF 5 4 4 Configure Gas Standard Volume Flow Cutoff Display Not available ProLink II ProLink Configuration Flow Std Gas Vol Flow Cutoff Field Communicator Configure Manual Setup Measurements Gas Standard Volume GSV Cutoff Gas Standard Volume Flow Cutoff specifies the lowest volume flow rate that will reported as measured All volume flow rates below this cutoff will be reported as 0 Procedure Set Volume Flow Cutoff to the desired value The default value for Gas Standard Volume Flow Cutoff is 0 0 The lower limit is 0 0 There is no upper limit Interaction between Gas Standard Volume Flow Cutoff and AO Cutoff Gas Standard Volume Flow Cutoff defines the lowest Gas Standard Volume flow value that the transmitter will report as meas
152. l port connection A USB port connection is also available 4 Start ProLink Il 5 Choose Connection Connect to Device 6 Set Protocol to HART Bell 202 Tip HART Bell 202 connections use standard connection parameters You do not need to configure them here 7 lf you are using a USB port connection enable Converter Toggles RTS 8 Set Address Tag to the HART polling address configured in the transmitter 32 Micro Motion 9739 MVD Transmitters Quick start with ProLink II Tips e If this is the first time you are connecting to the transmitter use the default address 0 e If you are not ina HART multidrop environment the HART polling address is typically left at the default value If you are unsure of the transmitter s address click Poll ProLink II will search the network and return a list of the transmitters that it detects 9 Set the COM Port value to the PC COM port that you are using for this connection 10 Set Master as appropriate Secondary Use this setting if another HART host such as a DCS is on the network Primary Use this setting if no other host is on the network The Field Communicator is not a host 11 Click Connect If the connection is successful The status bar in the main window is updated to show an active connection e The Process Variables window or Commissioning Wizard window is displayed If an error message appears Ensure that you are using the cor
153. l the process variable is displayed ProLink II ProLink Process Variables Field Communicator Overview Shortcuts Variables Process Variables Configuration and Use Manual 155 Transmitter operation Process variables provide information about the state of the process fluid such as flow rate density and temperature as well as running totals Process variables can also include data about flowmeter operation such as drive gain and pickoff voltage This information can be used to understand and troubleshoot your process Procedure View the desired process variable s If you are using the transmitter display by default the display shows the mass flow rate mass total volume flow rate volume total temperature density and drive gain If desired you can configure the display to show other process variables such as totalizers and inventories The display reports the abbreviated name of the process variable for example DENS for density the current value of that process variable and the associated unit of measure for example G CM3 If Auto Scroll is enabled the display cycles through the configured display variables showing each display variable for a user specified number of seconds Figure 8 1 identifies the features of the transmitter display Figure 8 1 Transmitter display features Process variable Current value Unit of measure Optical switch indicator turns red when Select activated Opt
154. lculated from the measured density value 5 7 Configure temperature measurement Display OFF LINE MAINT OFF LINE CONFG UNITS TEMP ProLink II ProLink Configuration Density Low Density Cutoff Field Communicator Configure Manual Setup Measurements Temperature The temperature measurement parameters control how temperature data from the sensor is reported Temperature data is used to compensate flow measurement for the effect of temperature on the sensor tubes The temperature measurement parameters include e Temperature Measurement Unit e Temperature Damping 5 7 1 Configure Temperature Measurement Unit Display OFF LINE MAINT OFF LINE CONFG gt UNITS TEMP ProLink II ProLink Configuration Temperature Temp Units Field Communicator Configure Manual Setup Measurements Temperature Temperature Unit Temperature Measurement Unit specifies the unit that will be used for temperature measurement Procedure Set Temperature Measurement Unit to the desired option The default setting is Degrees Celsius Tip If you are configuring the mA input to receive temperature data from an external measurement device you must set the measurement unit to match the temperature measurement unit at the external measurement device Options for Temperature Measurement Unit The transmitter provides a standard set of units for Temperature Measurement Unit Different communications tools use differe
155. ld Communicator Configure Manual Setup Inputs Outputs Frequency Output The frequency output is used to report a process variable The frequency output parameters control how the process variable is reported 124 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system The frequency output parameters include e Frequency Output Process Variable e Frequency Output Scaling Method e Frequency Output Maximum Pulse Width e Frequency Output Polarity e Frequency Output Fault Action and Frequency Output Fault Value e Frequency Output Power Source Postrequisites Important Whenever you change a frequency output parameter verify all other frequency output parameters before returning the flowmeter to service In some situations the transmitter automatically loads a set of stored values and these values may not be appropriate for your application 7 2 1 Configure Frequency Output Scaling Method Display OFF LINE MAINT OFF LINE CONFG IO FO SCALE ProLink II ProLink Configuration Frequency Scaling Method Field Communicator Configure Manual Setup Inputs Outputs Frequency Output FO Scaling Frequency Output Scaling Method defines the relationship between output pulse and flow units Set Frequency Output Scaling Method as required by your frequency receiving device Procedure 1 Set Frequency Output Scaling Method Frequency Flow default Frequency calculated from flowra
156. le the effect of damping the process variable is calculated first and the added damping calculation is applied to the result of that calculation Example Damping interaction Configuration e Flow Damping 1 second e mA Output Process Variable Mass Flow Rate e Added Damping 2 seconds Result A change in the mass flow rate will be reflected in the mA output over a time period that is greater than 3 seconds The exact time period is calculated by the transmitter according to internal algorithms which are not configurable 7 1 5 Configure mA Output Fault Action and mA Output Fault Level Display Not available ProLink II ProLink Configuration Analog Output Primary Secondary Output AO Fault Action ProLink Configuration Analog Output Primary Output AO Fault Level Field Communicator Configure Manual Setup lInputs Outputs mA Output 1 MA01 Fault Settings Configure Manual Setup lInputs Outputs mA Output 2 MA02 Fault Settings mA Output Fault Action controls the behavior of the mA output if the transmitter encounters an internal fault condition Note If Last Measured Value Timeout is set to a non zero value the transmitter will not implement the fault action until the timeout has elapsed Procedure 1 Set mA Output Fault Action to the desired value The default setting is Downscale 2 If you set mA Output Fault Action to Downscale set mA Output Fault Level as desired Configuration an
157. lem Possible causes Recommended actions Consistently incorrect mA measurement Incorrect flow measurement unit configured Verify that the measurement units are configured correctly for your application Output not trimmed correctly Check the mA output trim See Section 10 16 Incorrect process variable configured LRV and DRY aie not set comectly Verify the process variable assigned to the mA output Check the settings of Upper Range Value and Lower Range Value See Section 10 17 mA output correct at lower current but incorrect at higher current mA loop resistance may be set too Verify that the mA output load high resistance is below maximum supported load see the installation manual for your transmitter 10 7 Frequency output problems Table 10 7 Frequency output problems and recommended actions Possible causes Recommended actions Process condition below cutoff Verify that the process conditions are below the low flow cutoff Reconfigure the low flow cutoff if necessary No frequency output Fault condition if fault indicator is set to internal zero or downscale Check the Fault Action settings See Slug flow Section 10 18 Flow in reverse direction from configured flow direction parameter Verify that the totalizers are not stopped A stopped totalizer will cause the Bad frequency receiving device frequency output to be locked Output level not compatible with Check for slug flow See Section 10 24
158. les that are shown on the display Display Not available ProLink II ProLink Configuration Display Display Var X Field Communicator Configure Manual Setup Display Set Up Display Variables Display Variables controls the process variables shown on the display The display can scroll through up to 15 process variables in any order You can configure the process variables to be displayed and the order in which they will appear You can repeat variables and you can leave slots empty Restrictions e You cannot set Display Variable 1 to None Display Variable 1 must always be set to a process variable e If you have fixed Display Variable 1 to the primary mA output you cannot change the setting of Display Variable 1 using this method To change the setting of Display Variable 1 you must change the configuration of mA Output Process Variable for the primary mA output Note If you have configured a volume process variable as a display variable and you subsequently change the setting of Volume Flow Type the display variable is automatically changed to the equivalent process variable For example if Display Variable 2 was set to Volume Flow Rate it will be changed to Gas Standard Volume Flow Rate Procedure 1 Select a slot 2 Set Display Variable to the variable that you want to appear in that slot Example Display variable configuration Display variable Process variable assignment Display Variable 2
159. ll be able to reset totalizers from the display Restrictions Totalizer Reset does not apply to inventories Operators cannot reset inventories from the display even if Totalizer Reset is enabled e You cannot use the display to reset all totalizers as a group From the display you must reset totalizers individually e lf the petroleum measurement application is installed on your computer the operator must enter the off line password to perform this function even if the off line password is not enabled Procedure 1 Enable or disable Totalizer Reset as desired Enabled Operators can reset a totalizer from the display if the appropriate totalizer is configured as a display variable Disabled default Operators cannot reset totalizers from the display 2 Ensure that the totalizers to be reset from the display have been configured as display variables 104 Micro Motion 9739 MVD Transmitters Configure device options and preferences This function is accessed from the totalizer value on the display If the appropriate totalizer is not configured as a display variable the operator will not be able to reset it 6 2 3 Enable or disable the Acknowledge All Alarms display command Display OFF LINE MAINT OFF LINE CONFG DISPLAY ALARM ProLink II ProLink Configuration Display Display Options Display Ack All Alarms Field Communicator Not available You can control whether or not the operator will
160. mary mA output Volume Flow Rate e Frequency Output Process Variable Volume Flow Rate AO Cutoff for the primary mA output 15 liters second Volume Flow Cutoff 10 liters second Configuration and Use Manual 73 Configure process measurement Result lf the volume flow rate drops below 15 liters second but not below 10 liters second The primary mA output will report zero flow The frequency output will report the actual flow rate and the actual flow rate will be used in all internal processing If the volume flow rate drops below 10 liters second both outputs will report zero flow and 0 will be used in all internal processing 5 4 Configure gas standard volume flow measurement Display OFF LINE MAINT OFF LINE CONFG VOL VOL TYPE GAS ProLink II ProLink Configuration Flow Vol Flow Type Field Communicator Configure Manual Setup Measurements Gas Standard Volume The gas standard volume flow measurement parameters control how gas standard volume flow is measured and reported The gas standard volume flow measurement parameters include e Volume Flow Type e Standard Gas Density e Gas Standard Volume Flow Measurement Unit e Gas Standard Volume Flow Cutoff Restriction You cannot implement both liquid volume flow and gas standard volume flow You must choose one or the other 5 4 1 Configure Volume Flow Type for gas applications Display OFF LINE MAINT OFF LINE CONFG VOL V
161. me data is calculated from the damped mass flow data rather than the measured flow value Interaction between Flow Damping and Added Damping Flow Damping controls the rate of change in flow process variables Added Damping controls the rate of change reported via the mA output If mA Output Process Variable is set to Mass Flow Rate and both Flow Damping and Added Damping are set to non zero values flow damping is applied first and the added damping calculation is applied to the result of the first calculation 5 2 3 Configure Mass Flow Cutoff ProLink II ProLink Configuration Flow Mass Flow Cutoff Field Communicator Configure Manual Setup Measurements Flow Mass Flow Cutoff Mass Flow Cutoff specifies the lowest mass flow rate that will reported as measured All mass flow rates below this cutoff will be reported as 0 Procedure Set Mass Flow Cutoff to the desired value The default value for Mass Flow Cutoff is 0 0 g s The recommended setting is 0 05 of the sensor s rated maximum flow rate Effect of Mass Flow Cutoff on volume measurement Mass Flow Cutoff does not affect volume measurement Volume data is calculated from the actual mass data rather than the reported value Interaction between Mass Flow Cutoff and AO Cutoff Mass Flow Cutoff affects all reported values and values used in other transmitter behavior e g events defined on mass flow AO Cutoff affects only mass flow values reported via the mA o
162. mended actions continued A105 The density h lg tow eas a Check for slug flow See Section 10 24 user defined slug density limits A106 Burst mode enabled The device is in HART N ti ired burst mode o action required If desired you can reconfigure the alarm severity level to Ignore A107 Power reset occurred The transmitter has N ti ired been restarted a a If desired you can reconfigure the alarm severity level to Ignore A108 Event 1 triggered No action required Review event configuration if you believe the event was triggered erroneously A109 Event 2 triggered No action required Review event configuration if you believe the event was triggered erroneously A110 Frequency output The calculated saturated frequency output is outside of the linear range Check process conditions Actual conditions may be outside of the normally expected conditions for which the output is configured Check the frequency output scaling See Section 10 20 Verify process conditions checking especially for air in the flow tubes tubes not filled foreign material in the tubes or coating in the tubes Verify that the measurement units are configured correctly for your application Purge the flow tubes A111 Frequency output fixed User has fixed the PORRER frequency output Check that the transmitter is in loop test mode Check that the output has been fixed via digital communication 182 Micro Motion 9739 MVD Transmitters
163. minute e Gas Standard Volume Flow Cutoff 10 SLPM Result Ifthe Gas Standard Volume flow rate drops below 15 SLPM but not below 10 SLPM The primary mA output will report zero flow The frequency output will report the actual flow rate and the actual flow rate will be used in all internal processing Ifthe Gas Standard Volume flow rate drops below 10 SLPM both outputs will report zero flow and 0 will be used in all internal processing 5 5 Configure Flow Direction Display Not available ProLink II ProLink Configuration Flow Flow Direction Field Communicator Configure Manual Setup Measurements Flow Flow Direction Flow Direction controls how conditions of forward flow and reverse flow affect flow measurement and reporting Flow Direction is defined with respect to the flow arrow on the sensor Forward flow positive flow moves in the direction of the flow arrow on the sensor e Reverse flow negative flow moves in the direction opposite to the flow arrow on the sensor Procedure Set Flow Direction as desired 5 5 1 Options for Flow Direction Flow Direction controls how the outputs report flow and how the totalizers and inventories increment totals Configuration and Use Manual 79 Configure process measurement Table 5 4 Options for Flow Direction 5 5 2 Effect of Flow Direction on transmitter outputs and totalizers Flow Direction and mA outputs mA outputs are affected by Flo
164. mitter configuration worksheet 1 1 Safety messages Safety messages are provided throughout this manual to protect personnel and equipment Read each safety message carefully before proceeding to the next step 1 2 Obtain version information To configure use and troubleshoot the transmitter you may need to know the version information of your transmitter software ProLink II software application and or HART device description Procedure See Table 1 1 for information on how to obtain the version information Table 1 1 Methods to obtain version information With display With ProLink II With Field Communicator Transmitter software OFF LINE MAINT VER View lnstalled Overview Shortcu Options Software Revisions ts Device Informa tion Revisions Xmtr Software Rev ProLink II Not applicable Help About ProLink II Not applicable HART device description Not applicable Not applicable Overview Short cuts Device Informa tion Revisions DD Re vision 1 3 Available communications tools You can use a variety of communications tools to interface with the 9739 MVD transmitter Configuration and Use Manual 3 Before you begin The following communications tools are supported e Transmitter display if the transmitter was ordered with a display e ProLink II software v2 91 or later e Field Communicator DD v2 or later Tip You may be able to use other tools from Emerson Process Management such as
165. mulated values and make any appropriate changes to the transmitter configuration or to the system 7 Modify the simulated values and repeat 8 When you have finished testing or tuning disable sensor simulation 3 9 Back up transmitter configuration ProLink II provides a configuration upload download function which allows you to save configuration sets to your PC This allows you to back up and restore your transmitter configuration and is also a convenient way to replicate a configuration across multiple devices Procedure Choose File Load from Xmtr to File to save the transmitter configuration to your PC 46 Micro Motion 9739 MVD Transmitters Quick start with ProLink Il 3 10 Enable disable HART security You use the HART security switch located on the transmitter display to disable configuration of the transmitter using HART protocol When the HART security switch is set to ON HART protocol cannot be used to perform any action that requires writing to the transmitter For example you cannot change the configuration reset totalizers perform calibration etc using the Field Communicator or ProLink II with a HART Bell 202 or HART RS 485 connection When the HART security switch is set to OFF no functions are disabled Important The HART security switch does not affect Modbus communications A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removi
166. n eh vies densa aa a a aaia a ia a aa aai 55 4 8 Test or tune the system using sensor simulation 0 eee eect cece eee tneeeeeeeaneeeees 56 4 9 Enable disable HART security ccceceeeeeeeeeeee eee eeeeeeeeeeeeeeeeeeeeeeaaeeeeeeeaaeees 58 ll Reference information for COMMISSIONING ssssssssssssssssscsssccsceccececcsccccsceseseees 59 Chapter 5 Configure process M ASUPEMENL ceceseccscccsscsscssssccccececececescececeeecessscsescessesecess 61 5 1 Characterize the flowmeter 2 0cccceeeeeceeeeeeeeee ce eeeeeeeeeseeeeeeeeesaeeeeeeeeesaes 61 5 2 Configure mass flow measurement cee cece ee eteeeeeee ee eeeeeeeaaeeeeeeeaaeeeeeeeaaeeeees 64 5 3 Configure volume flow measurement for liquid applications ce 69 5 4 Configure gas standard volume flow measurement 22 ceeeeeeeeeeeeeeeeeeee es 74 5 5 Contigure Flow Direction 2 cscietesecnetedeccateiedeceseetidecedgunsdvesdestsleczdeeneteenseunsteelpaensteeds 79 5 6 Configure density measurement ee eceeeeee cece teeeeeee ee eeeeeeeaaeeeeeeeaaeeeeeaaaaeeees 84 5 7 Configure temperature MEASUFEMENT cece eeeeeee cece eeeeeeeeeaaeeeeeeeaaeeeeeeeaaeeeees 88 5 8 Configure pressure COMPENSATION 00 ccccceceeceeeee ce eeeeeeeeeaeeeeeeeeeesaeeeeeeeeeaaes 90 5 9 Configure the petroleum measurement application c cceeeeeeeeeeeeeeeeee es 91 5 10 Configure the concentration measuremen
167. n the display when you make a choice enter the value that is configured for Off Line Password Configuration and Use Manual 215 Using the transmitter display a With the cursor flashing on the first digit activate Scroll until the correct digit is displayed then activate Select b Repeat this process for the second third and fourth digits Tip If you do not know the correct value for Off Line Password wait 30 seconds The password screen will time out automatically and you will be returned to the previous screen 4 If Scroll flashes on the display activate the Scroll optical switch then the Select optical switch and then the Scroll optical switch again The display will prompt you through this sequence The Scroll Select Scroll sequence is designed to protect the display from accidental activation of the off line menu It is not designed as a security measure 5 To exit a display menu and return to a higher level menu e Activate Scroll until the EXIT option is displayed then activate Select e lf the EXIT option is not available activate Scroll and Select simultaneously and hold until the screen returns to the previous display 6 To exit the display menu system you can use either of the following methods e Exit each menu separately working your way back to the top of the menu system e Wait until the display times out and returns to displaying process variable data C 2 1 Optical switches The transmit
168. nce See Section 10 12 If two sensors with similar frequency are too near each other separate them Contact Micro Motion 185 Troubleshooting Table 10 3 Flow problems and recommended actions continued Problem Possible causes Recommended actions Erratic non zero flow rate when flow is steady Inaccurate flow rate or batch total 186 Slug flow Damping value too low Plugged flow tube Excessive or erratic drive gain Output wiring problem Problem with receiving device Wiring problem Bad flow calibration factor Inappropriate measurement unit Bad sensor zero Bad density calibration factors Bad flowmeter grounding Slug flow Problem with receiving device Wiring problem Verify that the sensor orientation is appropriate for your application refer to the sensor installation manual Check the drive gain and the pickoff voltage See Section 10 25 and Section 10 26 For installation with 9 wire cabling verify that the 9 wire cable is correctly grounded Check the wiring between the sensor and transmitter See Section 10 10 For sensors with a junction box check for moisture in the junction box Purge the flow tubes Check for open or leaking valves or seals Check for sources of vibration Verify damping configuration Verify that the measurement units are configured correctly for your application Check for slug flow See Section 10 24 Check for radio frequency interference S
169. ng the housing cover while power is supplied to the unit could cause an explosion To access the HART security switch in a hazardous environment be sure to remove power from the transmitter before removing the housing cover and setting the HART security switch Procedure 1 Remove power from the transmitter 2 Remove the transmitter housing cover 3 Move the HART security switch to the desired position see Figure 3 10 Figure 3 10 HART security switch on blank display A HART security switch B Unused 4 Replace the transmitter housing cover 5 Restore power to the transmitter Configuration and Use Manual 47 Chapter 4 Quick start with the Field Communicator Topics covered in this chapter Apply power Connect with the Field Communicator Configuration tips and tricks Configure the primary mA output to report mass flow rate in a user selected measurement unit Perform a loop test Trim mA outputs Zero the flowmeter Test or tune the system using sensor simulation Enable disable HART security 4 1 Apply power Prerequisites Before you apply power to the flowmeter close and tighten all housing covers A To prevent ignition of flammable or combustible atmospheres make sure all covers are tightly closed For hazardous area installations applying power to the unit while housing covers are removed or loose can cause an explosion Procedure Turn on the electrical power at the power
170. ngs continued Confi Configurable with with Configuration parameter Process variable Q External pressure Q Internal pressure U None Lower range value LRV Upper range value URV Enable Disable mA input HART Address or Modbus Address Loop current mode ProLink II or mA output ac tion Field Com municator Modbus ASCII Enable Disable Burst mode Enable Disable Burst mode output Dynamic variables and PV current Primary variable PV current and percentage of range Read device variables with status Transmitter variables HAR TVaNabIBS Primary variable PV Secondary variable SV Tertiary variable TV Quaternary variable QV 12 ProLink Il Field Communi cator Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration parameter Display Field Communi ProLink II cator Digital Communications Fault Actions Downscale Settings Upscale Report NAN Not A Number Flow Rates go to zero value zero flow Flow Rates go to zero value zero flow Density and Temperature go to zero No Action Output assignment Type Event 1 Q High alarm Low alarm Setpoint Output assignment Type Q High alarm U Low alarm Setpoint Event Type HI Discrete Event 1 Process Variable Setpoi
171. nnections Modbus RS 485 7 bit connections Modbus ASCII Modbus RS 485 8 bit connections Modbus RTU When selecting a connection type consider the following 26 Service port connections use standard connection parameters that are already defined in ProLink II and therefore you do not have to configure them HART Bell 202 connections use standard HART connection parameters that are already defined in ProLink II The only parameter you must configure is the transmitter address The service port terminals A and B and the RS 485 terminals 26 and 27 use the same internal wiring If you have wired the transmitter for RS 485 digital communications you cannot make a service port connection Service port connections require access to the service port terminals which are located on the transmitter display and only accessible after removing the housing cover Accordingly service port connections should be used only for temporary connections and may require extra safety precautions Modbus connections including service port connections are typically faster than HART connections When you are using a HART connection ProLink II will not allow you to open more than one window at a time This is done to manage network traffic and optimize speed You cannot make a service port connection while an active connection exists between the transmitter and Modbus host Micro Motion 9739 MVD Transmitters Quick start with ProLink II 3 2 2 M
172. nsmitter display French Q U German Q Spanish Configuration and Use Manual 7 Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi parameter ProLink II cator Display variables Var1 Var2 Var3 Var4 Var5 Var6 Var7 Vars Var9 Var10 Var11 Var12 Var13 Var14 Var15 ff Update period 100 milliseconds to 10 000 milliseconds range default is 200 milliseconds Auto scroll U Enable J Disable Auto scroll rate default is 10 seconds Backlight QO On QO Off Totalizer start stop Q Enabled Q Disabled Totalizer reset Q Enabled Q Disabled 8 Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Configurable with Field Communi ProLink II cator Configuration parameter Display Acknowledge all alarms Q Enabled QO Disabled ffline menu Q Enabled Q Disabled Alarm password Q Enabled Q Disabled Response time Q Normal L Special Informational parameters Lower range value LRV Upper range value URV Mass flow cutoff Added damping mA Output 1 Fault action Q Upscale Downscale Internal zero None Configuration and Use Manual 9 Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Configurable with Configuration Field Communi p
173. nt 3 2 5 Make a Modbus RS 485 connection Prerequisites You will need the following e An installed licensed copy of ProLink II An available serial or USB port One of the following types of signal converters RS 232 to RS 485 signal converter USB to RS 485 signal converter e Adapters as required e g 9 pin to 25 pin Procedure 1 Attach the signal converter to your PC s serial or USB port 2 At the transmitter remove the housing cover to access the RS 485 terminal connections A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To access transmitter information in a hazardous environment use a communication method that does not require removing the transmitter housing cover 3 To connect directly to the transmitter connect the leads on your signal converter to terminals 26 RS 485 A and 27 RS 485 B on your transmitter See Figure 3 8 Configuration and Use Manual 37 Quick start with ProLink Il Tip Usually but not always the black lead is RS 485 A and the red lead is RS 485 B Figure 3 8 ProLink II connection to transmitter terminals 20 A PC B 25 to 9 pin adapter if necessary cC RS 485 to RS 232 signal converter D Transmitter 4 To connect to a point in RS 485 network connect the leads on your signal con
174. nt A Setpoint B Configuration and Use Manual 13 Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi parameter Display ProLink II cator Action Q None default Start Sensor Zero Start stop all totalizers Reset mass total Reset volume total Reset gas standard volume total Reset all totals Reset temperature corrected volume total Reset CM reference volume total Reset CM net mass total Reset CM net volume total Increment CM matrix Ooo ae O W OO Y Event Type HI Discrete Event 2 OUT 14 Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi parameter Display ProLink II cator Action Q None default Start Sensor Zero Start stop all totalizers Reset mass total Reset volume total Reset gas standard volume total Reset all totals Reset temperature corrected volume total Reset CM reference volume total Reset CM net mass total Reset CM net volume total Increment CM matrix Ooo re re re E OOO Y Event Type HI Discrete Event 3 OUT Configuration and Use Manual 15 Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi pa
175. nt labels 88 Micro Motion 9739 MVD Transmitters Configure process measurement Options for Temperature Measurement Unit are shown in Table 5 10 Table 5 10 Options for Temperature Measurement Unit Description Display ProLink Il Field Communicator 97 2 Configure Temperature Damping Display Not available ProLink II ProLink Configuration Temperature Temp Damping Field Communicator Configure Manual Setup Measurements Temperature Temp Damping Damping is used to smooth out small rapid fluctuations in process measurement The Damping Value specifies the time period in seconds over which the transmitter will spread changes in the reported process variable At the end of the interval the reported process variable will reflect 63 of the change in the actual measured value Tips A high damping value makes the process variable appear smoother because the reported value must change slowly A low damping value makes the process variable appear more erratic because the reported value changes more quickly Procedure Enter the desired value for Temperature Damping The default value is 4 8 seconds The range is 0 0 seconds to 38 4 seconds When you enter a value for Temperature Damping the transmitter automatically rounds it down to the nearest valid value Valid values for Temperature Damping are 0 0 6 1 2 2 4 4 8 38 4 Effect of Temperature Damping Temperature Damping affects the respon
176. ntil OFF LINE EXIT appears on the display then activate Select Activate Scroll until EXIT appears on the display then activate Select Tip Another way to exit the off line menu is to rely on the time out feature If you have not used the off line menu for approximately 60 seconds the display will automatically return to normal operation 2 4 Perform a loop test A loop test is a way to verify that the transmitter and the receiving device are communicating properly A loop test also helps you know whether you need to trim mA outputs Performing a loop test is not a required procedure However Micro Motion recommends performing a loop test for every input or output available on your transmitter Procedure 1 Test the mA output a Choose OFFLINE MAINT gt SIM A01 SIM and select SET 4 MA or another mA output value Dots traverse the display while the output is fixed Read the mA current at the receiving device and compare it to the transmitter output The readings do not need to match exactly If the values are slightly different you can correct the discrepancy by trimming the output Configuration and Use Manual 21 Quick start with the display 22 c At the transmitter activate Select d Scroll to and select SET 20 MA Dots traverse the display while the output is fixed e Read the mA current at the receiving device and compare it to the transmitter output The readings do not need to match exactly If
177. ntil the decimal point is flashing Activate Scroll The decimal point is removed from its current position c Activate Select and watch the position of the decimal point As the cursor moves to the left the decimal point will flash between each pair of digits up to a maximum precision of four four digits to the right of the decimal point Tip If the position is not valid the decimal point is not displayed Continue to activate Select until the decimal point appears at the right of the displayed value d When the decimal point is in the desired position activate Scroll Configuration and Use Manual 217 Using the transmitter display The decimal point is inserted at its current position To save the displayed value to transmitter memory activate Scroll and Select simultaneously and hold until the display changes If the displayed value is the same as the value in transmitter memory you will be returned to the previous screen If the displayed value is not the same as the value in transmitter memory SAVE YES flashes on the display Activate Select To exit the menu without saving the displayed value to transmitter memory activate Scroll and Select simultaneously and hold until the display changes If the displayed value is the same as the value in transmitter memory you will be returned to the previous screen If the displayed value is not the same as the value in transmitter memory SAVE YES flashes on t
178. o 0 0625 5 Set Mass Flow Label to oz sec 6 Set Mass Total Label to oz 5 2 2 Configure Flow Damping Display Not available ProLink II ProLink Configuration Flow Flow Damp Field Communicator Configure Manual Setup Measurements Flow Flow Damping Damping is used to smooth out small rapid fluctuations in process measurement The Damping Value specifies the time period in seconds over which the transmitter will spread changes in the reported process variable At the end of the interval the reported process variable will reflect 63 of the change in the actual measured value Tips A high damping value makes the process variable appear smoother because the reported value must change slowly A low damping value makes the process variable appear more erratic because the reported value changes more quickly Procedure Set Flow Damping to the desired value The default value is 0 8 seconds The range is 0 to 10 24 seconds When you enter a value for Flow Damping the transmitter automatically rounds it down to the nearest valid value The valid values for Flow Damping are 0 0 04 0 08 0 16 10 24 Tips For gas applications Micro Motion recommends setting Flow Damping to 2 56 or higher Configuration and Use Manual 67 Configure process measurement Effect of Flow Damping on volume measurement Flow Damping effects volume measurement for both liquid volume and gas standard volume Volu
179. o O Enabled default Operator can access the alarm menu This access is required to view and acknowledge alarms but is not required for configuration or calibration Disabled Operator cannot access the alarm menu Note The status LED on the transmitter face shows whether or not alarms are active but does not show specific alarms Enable or disable Off Line Password as desired Enabled Operator is prompted for the off line password at entry to the maintenance section of the off line menu Disabled default No password is required for entry to the maintenance section of the off line menu Enable or disable Alarm Password as desired Enabled Operator is prompted for the off line password at entry to the alarm menu Disabled default No password is required for entry to the alarm menu If both Off Line Password and Alarm Password are enabled the operator is prompted for the off line password at the top of the off line menu and is not prompted thereafter Optional Set Off Line Password to the desired value The default value is 1234 The range is 0000 to 9999 Micro Motion 9739 MVD Transmitters Configure device options and preferences Tip Record your password for future reference 6 4 Configure the speed of the transmitter s response to changes in process data Display Not available ProLink II ProLink Configuration Device Response Time Field Communicator Not available
180. ocedure 1 2 Allow the flowmeter to warm up for at least 20 minutes after applying power Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature 3 Stop flow through the sensor by shutting a valve downstream from the sensor Ensure that flow has completely stopped through the sensor and that the sensor is completely full of process fluid Check the flow rate If the flow rate is close to zero you should not need to zero the flowmeter Configuration and Use Manual 43 Quick start with ProLink Il Important The meter was zeroed at the factory and should not require a field zero Note Do not zero the flowmeter if a high severity alarm is active Correct the problem then zero the flowmeter You may zero the flowmeter if a low severity alarm is active Procedure 1 2 3 8 Choose ProLink Calibration Zero Calibration Modify Zero Time if required Zero Time controls the amount of time the transmitter takes to determine its zero flow reference point A long zero time may produce a more accurate zero reference but is more likely to result in a zero failure This is due to the increased possibility of noisy flow which causes incorrect calibration A short zero time is less likely to result in a zero failure but may produce a less accurate zero reference The default Zero Time is 20 seconds For most applications the defaul
181. on Definition Comment or reference ENABLE AUTO Enable Auto Scroll Enable or disable the Auto Scroll function ENABLE OFFLN Enable off line Access to off line menu from display ENABLE Enable password Enable or disable password PASSW protection for display functions ENABLE RESET Enable totalizer reset Enable or disable totalizer reset from display ENABLE START Enable totalizer start Enable or disable totalizer start stop from display EVNT1 Event 1 Event configured using the basic event model only EVNT2 Event 2 Event configured using the basic event model only EXTRN External FAC Z Factory zero FCF Flow calibration factor FL SW Flow switch FLSWT FLDIR Flow direction Frequency output FO FREQ Frequency factor ee E E Eo A E a Eoo rs ee E E E a E Language Write protect Loop current Meter factor Modbus ASCII Modbus RTU mA output 1 primary mA output mA output 2 secondary mA output Mass flow 222 Micro Motion 9739 MVD Transmitters Using the transmitter display Table C 3 Codes and abbreviations used in display menus continued Code or abbreviation Definition Comment or reference NFLOM Simulation Used for loop testing not simulation mode Simulation mode is not accessible via the display sea o OFF LINE Off line maintenance MAINT COO C C e ve fes S very vey SSCS weon fome SSCS SSSCSC SY va fomen SS wero Swem ooo S E e C 5 Menu maps for the t
182. on are shown in Table 5 6 Table 5 6 Effect of the Flow Direction parameter and actual flow direction on discrete outputs Actual flow direction Forward OFF OFF Reverse OFF OFF Bidirectional OFF OFF Absolute Value OFF OFF Negate Forward ON FF Negate Bidirectional O OFF Flow Direction and digital communications Digital communications values for different combinations of Flow Direction and actual flow direction are shown in Table 5 7 Table 5 7 Effect of the Flow Direction parameter and actual flow direction on flow values reported via digital communications Flow Direction and flow totals Totalizer and inventory behaviors for different combinations of Flow Direction and actual flow direction are shown in Table 5 8 Configuration and Use Manual 83 Configure process measurement Table 5 8 Effect of the Flow Direction parameter and actual flow direction on flow totals Flow Direction setting Zeroflow Reverse o 5 6 Configure density measurement Display OFF LINE MAINT OFF LINE CONFG UNITS DENS ProLink II ProLink Configuration Density Field Communicator Configure Manual Setup Measurements Density The density measurement parameters control how density is measured and reported The density measurement parameters include e Density Measurement Unit e The slug flow parameters Slug High Limit Slug Low Limit Slug Duration 5 6 1 Configure Density Measurement Unit Display
183. or both temperature and pressure use the same Polling Control option for both If you do not Primary will be used for both devices ProLink II only Click Apply to enable the polling controls Enter the device tag of the external measurement device Set Process Variable to Pressure Postrequisites Verify that the transmitter is receiving the external data To do this e Using ProLink II click ProLink Process Variables and check the External Pressure value e Using the Field Communicator select Overview Primary Purpose Variables If the value is not correct 1 Verify the HART tag of the external device 2 Verify that the external device is powered up and online 3 Verify the HART mA connection between the transmitter and the external measurement device Configuration and Use Manual 149 Integrate the meter with the control system 7 9 Set up polling for temperature Display Not available ProLink II ProLink Configuration Polled Variables External Temperature Field Communicator Configure Manual Setup Measurements External Compensation External Polling The transmitter can poll an external temperature device for current temperature data The external temperature value is used only by the petroleum measurement application or the concentration measurement application If you do not have one of these applications do not set up polling for temperature Tip To obtain value from using an external tempe
184. otal volume total RESET VOL si VOL Reset Volume Total Volume Total Reset volume total volume total Reset voure eet _ gas standard volume COC GSVT eset Voune Teel _ _ Gas Std Volume Best voure eet _ standard volume total Total total Reset all totais all totals Reset all totals RESET ALL ALL RESET ALL Reset All Totas All Totals Reset totas totals Reset temperature TCVOL estos o API Ref Vol Total feces _ corrected volume corrected volume total total Reset CM reference RESET STD V Reset CM Ref Vol Total CEN total e CM net mass total Sa NET M EERE CM Net Mass Total Reset CM net volume total CM net volume total RESETNETV e NET V Reset CM Net Vol Total CM Net Vol Total Increment CM matrix INCr CURVE Increment Current CM Curve A Before assigning actions to an enhanced event or discrete input check the status of the event or the remote input device If it is ON all assigned actions will be performed when the new configuration is implemented If this is not acceptable wait until an appropriate time to assign actions to the event or discrete input 7 4 2 Configure Discrete Input Polarity Display OFF LINE MAINT OFF LINE CONFG IO DI DI POLAR ProLink II ProLink Configuration Discrete Input DI1 Polarity Field Communicator Configure Manual Setup Inputs Outputs Discrete Input Polarity Configuration and Use Manual 135 Integrate the meter with the cont
185. ough specific transmitter outputs as described in Table 7 13 Table 7 13 HART variables and transmitter outputs Primary Variable PV Primary mA output If one assignment is changed the other is changed automatically and vice versa Secondary Variable SV Secondary mA output If one assignment is changed the other is changed automatically and vice versa If your transmitter is not configured for a secondary mA output the SV must be configured directly and the value of the SV is available only via digital communications Tertiary Variable TV Frequency output If one assignment is changed the other is changed automatically and vice versa Quaternary Variable QV Not associated with an The QV must be configured directly and the value of the output QV is available only via digital communications 7 6 2 Configure HART RS 485 communications Display Not available ProLink II ProLink Configuration Device Digital Comm Setting Field Communicator Configure Manual Setup Inputs Outputs Communications Setup RS 485 Port HART RS 485 communications parameters support HART communication with the transmitter s RS 485 terminals HART RS 485 communication parameters include e HART Address Polling Address 142 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Important To minimize configuration requirements the 9739 MVD transmitter uses an auto detection scheme when responding to a
186. p lInputs Outputs mA Output 1 mA Output Settings PV Added Damping Configure Manual Setup Inputs Outputs mA Output 2 mA Output Settings gt PV Added Damping Added Damping controls the amount of damping that will be applied to the mA output It affects the reporting of mA Output Process Variable through the mA output only It does not affect the reporting of that process variable via any other method e g the frequency output or digital communications or the value of the process variable used in calculations Note Added Damping is not applied if the mA output is fixed for example during loop testing or if the mA output is reporting a fault Added Damping is applied while sensor simulation is active Procedure Set Added Damping to the desired value The default value is 0 0 seconds 122 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system When you specify a value for Added Damping the transmitter automatically rounds the value down to the nearest valid value Valid values are shown in Table 7 3 Table 7 3 Valid values for Added Damping Valid values for Added Damping 0 0 0 1 0 3 0 75 1 6 3 3 6 5 13 5 27 5 55 0 110 220 440 Interaction of damping parameters When mA Output Process Variable is set to a flow variable density or temperature Added Damping interacts with Flow Damping Density Damping or Temperature Damping If multiple damping parameters are applicab
187. point it turns OFF and will remain OFF until the flow rate drops below 95 g sec 7 3 2 Configure Discrete Output Polarity Display Not available ProLink II ProLink Configuration Discrete Output DO1 Polarity Field Communicator Configure Manual Setup lInputs Outputs Discrete Output DO Polarity Discrete outputs have two states ON active and OFF inactive Two different voltage levels are used to represent these states Discrete Output Polarity controls which voltage level represents which state Procedure Set Discrete Output Polarity as desired The default setting is Active High Options for Discrete Output Polarity Options for Discrete Output Polarity are shown in Table 7 9 Table 7 9 Options for Discrete Output Polarity neve High internal When asserted condition tied to DO is true the circuit provides a pull up to 15 V When not asserted condition tied to DO is false the circuit provides 0 V Eee When asserted condition tied to DO is true the circuit provides a pull up to a site specific voltage maximum 30 V When not asserted condition tied to DO is false the circuit provides 0 V Active Low Interia When asserted condition tied to DO is true the circuit provides 0 V When not asserted condition tied to DO is false the circuit provides a pull up to 15 V External eae When asserted condition tied to DO is true the circuit provides 0 V When not asserted
188. put Process Variable The transmitter provides a basic set of options for mA Output Process Variable plus several application specific options Different communications tools use different labels for the options Options for mA Output Process Variable are listed in Table 7 1 Table 7 1 Options for mA Output Process Variable Label Process variable Display ProLink II Field Communicator Mass flow rate MFLOW Mass Flow Rate Volume flow rate VFLOW Volume Flow Rate Vol flo 118 Micro Motion 9739 MVD Transmitters Table 7 1 Process variable Gas standard volume flow rate Temperature Density External pressure External temperature Petroleum measurement Temperature corrected density Petroleum measurement Temperature corrected standard volume flow rate Drive gain Petroleum measurement Average corrected density Petroleum measurement Average temperature Concentration measurement Density at reference Concentration measurement Specific gravity Concentration measurement Standard volume flow rate Concentration measurement Net mass flow rate Concentration measurement Net volume flow rate Concentration measurement Concentration Concentration measurement Baume Configuration and Use Manual Integrate the meter with the control system Options for mA Output Process Variable continued Label Display ProLink Il Field Communicator GSV F Gas Std Vol Flow Rate Gas vol flo T
189. r and load see the installation manual for your transmitter Active Low As determined by power supply pull up resistor and load see the installation manual for your transmitter 7 2 4 Configure Frequency Output Fault Action and Frequency Output Fault Level Display Not available ProLink II ProLink Configuration Frequency Freq Fault Action ProLink Configuration Frequency Freq Fault Level Field Communicator Configure Manual Setup Inputs Outputs Frequency Output FO Fault Parameters FO Fault Action Configure Manual Setup lInputs Outputs Frequency Output FO Fault Parameters FO Fault Level Frequency Output Fault Action controls the behavior of the frequency output if the transmitter encounters an internal fault condition Note If Last Measured Value Timeout is set to a non zero value the transmitter will not implement the fault action until the timeout has elapsed Procedure 1 Set Frequency Output Fault Action as desired The default value is Downscale 0 Hz 2 If you set Frequency Output Fault Action to Upscale set Frequency Fault Level to the desired value The default value is 15000 Hz The range is 10 Hz to 15000 Hz Options for Frequency Output Fault Action Options for Frequency Output Fault Action are shown in Table 7 7 128 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Table 7 7 Options for Frequency Output
190. r process can tolerate the effects of the simulated process values Procedure 1 Navigate to the sensor simulation menu Service Tools Simulate Simulate Sensor 2 Enable sensor simulation 3 For mass flow set Wave Form as desired and enter the required values 56 Micro Motion 9739 MVD Transmitters Quick start with the Field Communicator Sawtooth P Sim Ramp Low Point Sim Ramp High Point Sim Ramp Period Sim Ramp Low Point Sim Ramp High Point Sim Ramp Period 4 For density set Wave Form as desired and enter the required values Fi Tri riangular wave Sim Ramp Low Point Sim Ramp High Point Sim Ramp Period Sine wave Sim Ramp Low Point Sim Ramp High Point Sim Ramp Period 5 For temperature set Wave Form as desired and enter the required values Fi Tri nangular wave Sim Ramp Low Point Sim Ramp High Point Sim Ramp Period Sine wave Sim Ramp Low Point Sim Ramp High Point Sim Ramp Period 6 Observe the system response to the simulated values and make any appropriate changes to the transmitter configuration or to the system Configuration and Use Manual 57 Quick start with the Field Communicator 7 Modify the simulated values and repeat 8 When you have finished testing or tuning disable sensor simulation 4 9 Enable disable HART security You use the HART security switch located on the transmitter display to disable configuration of the transmitter using HART proto
191. rameter Display ProLink II cator Action Q None default Start Sensor Zero Start stop all totalizers Reset mass total Reset volume total Reset gas standard volume total Reset all totals Reset temperature corrected volume total Reset CM reference volume total Reset CM net mass total Reset CM net volume total Increment CM matrix Ooo ae O ae OOO Event Type HI Discrete Event 4 QO OUT 16 Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Confi Configurable with with Configuration Field Communi parameter Display ProLink II cator Action Q None default Start Sensor Zero Start stop all totalizers Reset mass total Reset volume total Reset gas standard volume total Reset all totals Reset temperature corrected volume total Reset CM reference volume total Reset CM net mass total Reset CM net volume total Increment CM matrix Ooo ae re re OO Y e Event Type HI Discrete Event 5 QO OUT Configuration and Use Manual 17 Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Configurable with Configuration Field Communi parameter Display ProLink Il cator Action CL None default Start Sensor Zero Start stop all totalizers Reset mass total Reset volume total Reset gas standard volume total Reset all totals Reset temperature corr
192. ransmitter display Figure C 3 Offline menu top level Scroll and Select simultaneously for 4 seconds SEE ALARM scoi OFF LINE MAINT Select Scroll lt Select je Scroll j4 SWREV H scoi CONFG scon gt SiM H Scon gt ZERO H soon EXIT Configuration and Use Manual 223 Using the transmitter display Figure C 4 Offline menu version information Scroll and Select simultaneously for 4 seconds OFF LINE MAINT Transmitter software version displayed 224 Micro Motion 9739 MVD Transmitters Using the transmitter display Figure C 5 Offline menu configuration units and IJO Scroll and Select simultaneously for 4 seconds OFF LINE MAINT Select a Scroll Select reef Select Select AO1 Select Either Vol or GSV is displayed depending y on the Volume Flow Type AO2 i d MAI Scroll EXIT Configuration and Use Manual 225 Using the transmitter display Figure C 6 Offline menu configuration meter factors volume OFF LINE MAINT Select Scroll Select Scroll CONFG VOL Select VOL TYPE GAS FACTOR MASS FACTOR VOL VOL TYPE LIQUD FACTOR EXIT 226 Micro Motion 9739 MVD Tr
193. rately concatenate the two values to form the single parameter value Example Concatenating FCF and FT FCF X XXXX FT y yy Flow calibration parameter X XxXxxy YyYy 5 2 Configure mass flow measurement Display OFF LINE MAINT OFF LINE CONFG UNITS MASS ProLink II ProLink Configuration Flow Field Communicator Configure Manual Setup Measurements Flow The mass flow measurement parameters control how mass flow is measured and reported The mass flow measurement parameters include e Mass Flow Measurement Unit Flow Damping Mass Flow Cutoff 64 Micro Motion 9739 MVD Transmitters Configure process measurement 5 2 1 Configure Mass Flow Measurement Unit Display OFF LINE MAINT OFF LINE CONFG UNITS MASS ProLink II ProLink Configuration Flow Mass Flow Units Field Communicator Configure Manual Setup Measurements Flow Mass Flow Unit Mass Flow Measurement Unit specifies the unit will be used for the mass flow rate The unit used for mass total and mass inventory is derived from this unit Procedure Set Mass Flow Measurement Unit to the desired unit The default setting for Mass Flow Measurement Unit is g s grams per second Tip If the measurement unit you want to use is not available you can define a special measurement unit Options for Mass Flow Measurement Unit The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit
194. ration and Use Manual 111 Configure device options and preferences Alarm data in transmitter memory For each alarm occurrence that is posted information is maintained in three different ways in transmitter memory Alert List e Alert Statistics Recent Alerts Table 6 2 describes these three types of alarm data structures Table 6 2 Alarm data in transmitter memory Transmitter action if condition occurs Alert List List of Cleared and regenerated with every transmitter power cycle All currently active alarms P y All previously active alarms that have not been acknowledged as determined by the alarm status bits Alert Statistics One record for each alarm by alarm Not cleared maintained across number that has occurred since transmitter power cycles the last master reset Each record contains A count of the number of occurrences Timestamps for the most recent posting and clearing Recent Alerts 50 most recent alarm postings or Not cleared maintained across alarm clearings transmitter power cycles 6 6 Configure informational parameters Display Not available ProLink II ProLink Configuration Sensor Field Communicator Configure Manual Setup Info Parameters The informational parameters can be used to identify or describe your flowmeter They are not used in transmitter processing and are not required 112 Micro Motion 9739 MVD Transmitters Configure device options and pre
195. rature value the external measurement device must be reliable and must provide more accurate data than is available from the sensor Prerequisites Polling requires HART protocol over the Bell 202 physical layer Ensure that the primary mA output on your transmitter has been wired for HART protocol and that the external measurement device is accessible over the HART network Procedure 1 Select Polled Variable 1 or Polled Variable 2 2 Set Polling Control Polling Control determines how the transmitter will access the external measurement device Primary The transmitter is the only device that will access the external measurement device as a primary master Secondary Another device on the network will access the external measurement device as a primary master Tip If you set up polling for both temperature and pressure use the same Polling Control option for both If you do not Primary will be used for both devices 3 ProLink II only Click Apply to enable the polling controls 150 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system 4 Enter the device tag of the external measurement device 5 Set Process Variable to Temperature Postrequisites Verify that the transmitter is receiving the external data To do this e Using ProLink II click ProLink Process Variables and check the External Temperature value Using the Field Communicator select Overview Primary Purpose V
196. rce of the problem is likely to be somewhere between the transmitter and the receiving device Important When sensor simulation is active the simulated value is used in all transmitter outputs and calculations including totals and inventories volume flow calculations and concentration calculations Do not enable simulation mode unless your application can tolerate these effects and be sure to disable simulation mode when you have finished testing 10 9 Check power supply wiring Prerequisites To verify wiring you will need a copy of the installation manual for your transmitter To check power supply wiring for the 9739 MVD transmitter you must remove the electronics module from the transmitter housing base Procedure 1 Before inspecting the power supply wiring disconnect the power source A If the transmitter is in a hazardous area wait five minutes after disconnecting the power 2 Verify that the correct external fuse is used An incorrect fuse can limit current to the transmitter and keep it from initializing Ensure that the power supply wires are connected to the correct terminals 4 Verify that the power supply wires are making good contact and are not clamped to the wire insulation 5 Inspect the voltage label on the inside of the field wiring compartment The voltage supplied to the transmitter should match the voltage specified on the label 6 Reapply power to the transmitter 190 Micro Motion 9739 MVD Tr
197. rces of RFI include a source of radio emissions or a large transformer pump or motor that can generate a strong electromagnetic field Procedure e Eliminate the RFI source e Move the transmitter e Use shielded cable for the frequency output e Terminate the shielding at the output device If this is impossible terminate the shielding at the cable gland or conduit fitting e Do not terminate the shielding inside the wiring compartment e 360 degree termination of shielding is unnecessary Configuration and Use Manual 191 Troubleshooting 10 13 Check HART communication loop Prerequisites You will need the following A copy of your transmitter installation manual A Field Communicator Optional the HART Application Guide available at www hartcomm org Procedure 1 Verify that the loop wires are connected as shown in the wiring diagrams in the transmitter installation manual If your HART network is more complex than the wiring diagrams in the transmitter installation manual contact either Micro Motion or the HART Communication Foundation Disconnect the primary mA output wiring from the transmitter Install a 250 Q resistor across the transmitter s primary mA output terminals Check the voltage drop across the resistor 4 20 mA 1 5 VDC If voltage drop is less than 1 VDC add resistance to achieve a voltage drop of greater than 1 VDC Connect a Field Communicator directly across the resistor and attemp
198. rect COM port e Verify the HART polling address e Check the physical connection between the PC and the transmitter Increase or decrease resistance 3 2 4 Make a HART RS 485 connection Prerequisites You will need the following e An installed licensed copy of ProLink II An available serial or USB port One of the following types of signal converters RS 232 to RS 485 signal converter USB to RS 485 signal converter e Adapters as required e g 9 pin to 25 pin Configuration and Use Manual 33 Quick start with ProLink Il Important If the HART security switch is set to ON HART protocol cannot be used to perform any action that requires writing to the transmitter For example you cannot change the configuration reset totalizers or perform calibration using the Field Communicator or ProLink II with a HART connection When the HART security switch is set to OFF no functions are disabled Procedure 1 Attach the signal converter to your PC s serial or USB port 2 At the transmitter remove the housing cover to access the RS 485 terminal connections A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To access transmitter information ina hazardous environment use a communication method that does not require removing the transmitter housing cover 3
199. red Fault A008 Density overrange Fault A009 Transmitter initializing warming Fault au Cc Tw A010 Calibration failure Fault A011 Calibration too low Fault A012 Calibration too high Fault A013 Zero too noisy Fault A014 Transmitter failed Fault A016 Line temperature out of range Fault A017 Meter RTD temperature out of range EEPROM checksum error Fault A018 Fault A019 RAM or ROM test error Fault A020 Calibration factors unentered Fault A021 Incorrect sensor type Fault A027 Security breach Fault A100 Primary mA output saturated A Informational Can be set to either Informational or Ignore but cannot be set to Fault Primary mA output fixed Informational Can be set to either Informational or Ignore but cannot be set to Fault A102 Drive overrange Informational Yes A104 Calibration in progress Informational Can be set to either Informational or Ignore but cannot be set to Fault 110 Micro Motion 9739 MVD Transmitters Configure device options and preferences Table 6 1 Status alarms and Status Alarm Severity continued Alarm Status message Default code severity Configurable A105 Slug flow Informational Yes A106 Burst mode enabled i Informational Can be set to either Informational or Ignore but cannot be set to Fault A107 Power reset occurred Informational Normal transmitter behavior occurs a
200. ro Note Do not zero the flowmeter if a high severity alarm is active Correct the problem then zero the flowmeter You may zero the flowmeter if a low severity alarm is active Procedure 1 Initiate flowmeter zero by choosing OFFLINE MAINT gt ZERO CAL ZERO and select CAL YES Dots traverse the display while flowmeter zero is in progress 2 Read the zero result on the display The display will report CAL PASS if the zero was successful or CAL FAIL if it was not If the zero fails restore the factory zero if available 2 5 1 Restore factory zero Procedure Restore the factory zero with the display Configuration and Use Manual 23 Quick start with the display OFFLINE MAINT RESTORE ZERO RESTORE YES 24 Micro Motion 9739 MVD Transmitters Chapter 3 Quick start with ProLink Il Topics covered in this chapter Apply power Connect with ProLink II Configuration tips and tricks Configure the primary mA output to report mass flow rate in a user selected measurement unit Perform a loop test Trim mA outputs Zero the flowmeter Test or tune the system using sensor simulation Back up transmitter configuration Enable disable HART security 3 1 Apply power Prerequisites Before you apply power to the flowmeter close and tighten all housing covers A To prevent ignition of flammable or combustible atmospheres make sure all covers are tightly closed For hazardous area install
201. ro Calibration 2 Simulate Sensor 3 Density Calibration 4 Temperature Calibration 5 Diagnostic Variables Configuration and Use Manual 245 Using the Field Communicator with the 9739 MVD transmitter Figure E 11 Service Tools menu Variables Totalizer Control 4 Variable Summary 1 All Totalizers 2 Mass 3 Gas Standard Volume Process Variables 1 Mass Flow Rate 2 Volume Flow Rate 3 GSV Flow Rate 1 Start Totalizers 4 Density 2 Stop Totalizers 5 Temperature 3 Reset All Totals 4 Mass Total 5 Volume Total 6 GSV Total All Totalizers Mapped Variables Mass 1 Mass Flow Rate 2 Mass Total 3 Mass Inventory External Variables Fesat To 1 External Temperature A 2 External Pressure Volume 1 GSV Flow Rate 2 GSV Total 3 GSV Inventory if Volume Flow Type GSV 4 Reset Total GSV variables are displayed Outputs 1 Current mA output 1 2 Current mA output 2 3 Frequency 4 DO State 246 Micro Motion 9739 MVD Transmitters Using the Field Communicator with the 9739 MVD transmitter Figure E 12 Service Tools menu Maintenance Routine Maintenance Zero Calibration Density Calibration 1 Trim mA Output 1 1 Mass Flow Rate 1 Density 2 Trim mA Output 2 2 Volume Flow Rate 2 Dens Pt1 Air 3 Zero Time 3 Dens Pt2 Water 4 Zero Value 4 Dens Pt3 T Series 5 Standard Deviation 5 Dens Pt4 T Series 6 Perform Auto Zero 6 Flowing Dens FD 7 Restore Factory Zero Temperature Calibration Di
202. rol system The discrete input has two states ON and OFF Discrete Input Polarity controls how the transmitter maps the incoming voltage level to the ON and OFF states Procedure Set Discrete Input Polarity as desired The default setting is Active Low 7 5 Configure the mA input ProLink II ProLink Configuration Milliamp Input Field Communicator Configure Manual Setup Inputs Outputs Milliamp Input The mA input is used to receive pressure or temperature data from an external measurement device The milliamp input parameters include mA Input Process Variable e Lower range value LRV e Upper range value URV 7 5 1 Configure mA Input Process Variable Display OFF LINE MAINT OFF LINE CONFG IO MAI Al SRC ProLink II ProLink Configuration Milliamp Input PV Field Communicator Configure Manual Setup Inputs Outputs Milliamp Input mA Input Variable Assignment mA Input Process Variable specifies the type of process data that you are receiving from the external measurement device Procedure 1 Set the mA Input Process Variable as desired External pressure The remote device measures pressure External temperature The remote device measures temperature 136 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system The default setting is None 2 Configure the transmitter s measurement units to match the measurement units used by the remote device e
203. rols how long the transmitter will delay before performing fault actions The fault timeout period begins as soon as the transmitter detects the alarm condition During the fault timeout period the transmitter continues to report its last valid measurements If the fault timeout period expires and the alarm is still active fault actions are performed If the alarm condition clears before the fault timeout expires no fault actions are performed For all other alarms the fault action is performed as soon as the alarm is detected Restriction Fault Timeout is applied only to the following alarms listed by Status Alarm Code A003 A004 A005 A008 A016 A017 A033 Procedure Set Fault Timeout as desired The default value is 0 seconds The range is 0 seconds to 60 seconds If you set Fault Timeout to 0 the transmitter will perform fault actions as soon as the alarm is detected 6 5 2 Configure Status Alarm Severity Display Not available ProLink II ProLink Configuration Alarm Severity Field Communicator Configure Alert Setup Alert Severity Set Alert Severity Status Alarm Severity controls which set of fault actions the transmitter will perform when it detects an alarm 108 Micro Motion 9739 MVD Transmitters Configure device options and preferences Restrictions e For some alarms Status Alarm Severity is not configurable For some alarms Status Alarm Severity can be set only to two of the three opt
204. ropriate documentation from the Micro Motion web site at www micromotion com Transmitter electronics module upgrade Micro Motion 9739 MVD Transmitter Electronics Module Installation Guide 1 5 9739 MVD transmitter configuration worksheet Use the 9739 MVD transmitter configuration worksheet for both planning and recording the transmitter configuration Additionally the configuration worksheet shows the parameters that are accessible from the different communications tools Choose a communications tool that provides access to the parameters that you plan to configure 4 Micro Motion 9739 MVD Transmitters Before you begin Table 1 3 9739 MVD transmitter configuration settings Confi Configurable with with Configuration Field Communi parameter Display ProLink II cator Sensor Type ap O T Series Straight Tube Q Other Curved Tube Flow calibration v v factor C re Se ee a ee e o Density M v temperature coefficient DT Temperature calibration factor Mass flow measurement unit C a T special unit Flow text Total text Volume type Pre Q Liquid Volume L Std Gas Volume Standard Gas Density Volume flow measurement unit S S S S Configuration and Use Manual 5 Before you begin Table 1 3 9739 MVD transmitter configuration settings continued Configurable with Configuration Field Communi parameter Display ProLink II cator Base mass unit Base time unit If volume flow is
205. rops below LRV or rises above URV the transmitter posts an output saturation alarm Note If you change LRV and URV from factory default values and you later change mA Output Process Variable LRV and URV will not be reset to the default values For example if you configure mA Output Process Variable as mass flow and change the LRV and URV for mass flow then you configure mA Output Process Variable as density and finally you change mA Output Process Variable back to mass flow LRV and URV for mass flow are reset to the configured values Procedure 1 Set LRV as desired LRV is the value of mA Output Process Variable represented by an output of 0 or 4 mA The default value depends on the setting of mA Output Process Variable Enter LRV in the measurement units that are configured for mA Output Process Variable 2 Set URV as desired URV is the value of mA Output Process Variable represented by an output of 20 mA The default value depends on the setting of mA Output Process Variable Enter URV in the measurement units that are configured for mA Output Process Variable Note You can set URV below LRV For example you can set URV to 50 and LRV to 100 Default values for Lower Range Value LRV and Upper Range Value URV Each option for mA Output Process Variable has its own LRV and URV If you change the configuration of mA Output Process Variable the corresponding LRV and URV are loaded and used Default values for LRV
206. rs 1 Flow FCF 2FTG 3 FFQ Configuration and Use Manual 241 Using the Field Communicator with the 9739 MVD transmitter Figure E 5 Configure menu Manual Setup Measurements Flow 1 Flow Direction 2 Flow Damping 3 Mass Flow Cutoff 4 Mass Flow Unit 5 Volume Flow Cutoff 6 Volume Flow Unit 7 Mass Factor 8 Volume Factor Density 1 Density Unit 2 Density Damping 3 Density Cutoff 4 Density Factor 5 Slug Low Limit 6 Slug High Limit 7 Slug Duration Temperature 1 Temperature Unit 2 Temp Damping Displayed only if Volume Flow Type Liquid Special Units 1 Mass Special Units 2 Volume Special Units External Compensation 1 Pressure Unit 2 Enable Press Comp 3 Flow Cal Pressure 4 Static Pressure 5 Flow Press Factor 6 Dens Press Factor 7 Enable Ext Temp 8 External Temperature 9 External Polling External Polling 1 Poll Control 2 Ext Dev Tag 1 3 Ext Dev Tag 2 4 Polled Variable 1 5 Polled Variable 2 Gas Standard Volume 1 Volume Flow Type 2 Gas Density 3 GSV Cutoff 4 Gas Vol Flow Unit 5 Base Volume Unit 6 Base Volume Time 7 Gas Vol Flow Conv 8 Gas Vol Flow Label 9 Gas Vol Total Label 242 Micro Motion 9739 MVD Transmitters Using the Field Communicator with the 9739 MVD transmitter Figure E 6 Configure menu Manual Setup Display 1 Update Period Set Up Display Variables 1 Display Variables 1 5 2 Display Variables 6 10 3
207. rweraure a SSSSCSC S a SS S Fvaranieis woe it SSCSC S oily oazes sabes OOO O C a SSS S C a SSS S sonene Jeera t SS Poise one password sabes OO oiiayaiern mens a SSSSSC S oie ectrowiedgeaaiams navies __ SSSS S LE a moso o i SSS 206 Micro Motion 9739 MVD Transmitters Appendix B Transmitter components and installation wiring Topics covered in this appendix Transmitter components Transmitter to sensor wiring Power supply terminals Input output I O terminals B 1 Transmitter components You may need to identify the transmitter components for certain operational or troubleshooting tasks See Figure B 1 Configuration and Use Manual 207 Transmitter components and installation wiring Figure B 1 9739 MVD transmitter components Removable housing cover Electronics module Intrinsically safe sensor wiring terminals Non intrinsically safe output wiring terminals Conduit opening for sensor wiring Conduit opening for power supply wiring Conduit opening for output wiring EOT MO O B gt Housing base User interface with or without display options 208 Micro Motion 9739 MVD Transmitters Transmitter components and installation wiring B 2 Transmitter to sensor wiring A Refer to the Micro Motion 9739 MVD Transmitters Installation Manual for all safety and detailed wiring information for the 9739 MVD transmitter
208. ry the procedure Cycle power to the meter then retry the procedure Remove or reduce sources of electromechanical noise e g pumps vibration pipe stress then retry the procedure Cycle power to the meter then retry the procedure Cycle power to the meter Contact Micro Motion Check the sensor wiring See Section 10 27 1 Verify process conditions Contact Micro Motion Check the sensor wiring See Section 10 27 1 Verify process conditions Temperature should be between 200 F and 400 F Verify characterization parameters Contact Micro Motion Cycle power to the meter Contact Micro Motion Cycle power to the meter Contact Micro Motion Verify characterization parameters Verify characterization parameters Micro Motion 9739 MVD Transmitters Table 10 2 Status alarms and recommended actions continued A027 Security breach A029 Internal communica tion failure A030 Hardware software incompatible A100 Primary mA output saturated A101 Primary mA output fixed A102 Drive overrange A103 Data loss possible A104 Calibration in progress Configuration and Use Manual Transmitter electronics failure The loaded software is not compatible with the programmed board type The calculated amount of current output is outside of the linear range Non zero HART address configured or user has fixed the mA output The drive power current voltage is at its maxim
209. se speed for temperature compensation Temperature compensation adjusts process measurement to compensate for the effect of temperature on sensor tube stiffness Configuration and Use Manual 89 Configure process measurement Temperature Damping affects petroleum measurement process variables only if the transmitter is configured to use temperature data from the sensor If an external temperature value is used for petroleum measurement Temperature Damping does not affect petroleum measurement process variables Temperature Damping affects concentration measurement process variables only if the transmitter is configured to use temperature data from the sensor If an external temperature value is used for concentration measurement Temperature Damping does not affect concentration measurement process variables 5 8 Configure pressure compensation Display Not available ProLink II ProLink Configuration Pressure Pressure Compensation Field Communicator Configure Manual Setup Measurements External Compensation Pressure compensation adjusts process measurement to compensate for the pressure effect on the sensor s flow tubes Pressure effect is defined as the change in the sensor s sensitivity to flow and density associated with the difference between calibration pressure and process pressure Tip Not all sensors or applications require pressure compensation If you are uncertain about implementing pressure compensation
210. set HART Address to any other value ProLink II also disables Loop Current Mode This is designed to make it easier to configure the transmitter for legacy behavior Be sure to verify Loop Current Mode after setting HART Address 3 Optional Enable and configure Burst Parameters Tip In typical installations burst mode is disabled Enable burst mode only if another device on the network requires burst mode communication 4 Optional Configure HART Variables Configure Burst Parameters Display N A ProLink II ProLink Configuration Device Burst Setup Field Communicator Configure Manual Setup Inputs Outputs Communications HART Burst Mode Burst mode is a specialized mode of communication during which the transmitter regularly broadcasts HART digital information over the primary mA output The burst parameters control the information that is broadcast when burst mode is enabled Tip In typical installations burst mode is disabled Enable burst mode only if another device on the network requires burst mode communication Configuration and Use Manual 139 Integrate the meter with the control system Procedure 1 Enable Burst Mode 2 Set Burst Mode Output Primary Variable The transmitter sends the primary variable PV in the configured ProLink II measurement units in each burst e g 14 0 g s 13 5 g s 12 0 g s PV Field Communicator PV current amp of The transmitter sends the P
211. show a D1 or D2 value For D1 enter the Dens A or D1 value from the calibration certificate This value is the line condition density of the low density calibration fluid Micro Motion uses air If you cannot find a Dens A or D1 value enter 0 001 g cms For D2 enter the Dens B or D2 value from the calibration certificate This value is the line condition density of the high density calibration fluid Micro Motion uses water If you cannot find a Dens B or D2 value enter 0 998 g cm If your sensor tag does not show a K1 or K2 value e For K1 enter the first 5 digits of the density calibration factor In the sample tag in Figure 5 1 this value is shown as 12500 For K2 enter the second 5 digits of the density calibration factor In the sample tag in Figure 5 1 this value is shown as 14286 If your sensor does not show an FD value contact flow support emerson com If your sensor tag does not show a DT or TC value enter the last 3 digits of the density calibration factor In the sample tag in Figure 5 1 this value is shown as 4 44 Flow calibration parameters FCF FT Two separate values are used to describe flow calibration a 6 character FCF value and a 4 character FT value Both values contain decimal points During characterization these are entered as a single 10 character string that includes two decimal points This parameter is called either Flowcal or FCF If your sensor tag shows the FCF and the FT values sepa
212. supply The flowmeter will automatically perform diagnostic routines For transmitters with a display the status LED will turn green and begin to flash when the startup diagnostics are complete If the status LED exhibits different behavior an alarm condition is present Postrequisites Allow the electronics to warm up for approximately 10 minutes before relying on process measurements Although the sensor is ready to receive process fluid shortly after power up the electronics can take up to 10 minutes to warm up completely 4 2 Connect with the Field Communicator Prerequisites The following HART device description DD must be installed on the Field Communicator DD v2 A connection from the Field Communicator to your transmitter allows you to read process data configure the transmitter and perform maintenance and troubleshooting tasks Configuration and Use Manual 49 Quick start with the Field Communicator You can connect the Field Communicator to the HART clips on the transmitter to any point in a local HART loop or to any point in a HART multidrop network A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To access transmitter information in a hazardous environment use a communication method that does not require removing the transmitter housing cover Important
213. t Display Not available ProLink II ProLink Configuration Events Field Communicator Configure Alert Setup Discrete Events A basic event is used to provide notification of process changes A basic event occurs is ON if the real time value of a user specified process variable moves above HI or below LO a user defined setpoint You can define up to two basic events Event status can be queried via digital communications and a discrete output can be configured to report event status Procedure 1 Select Event 1 or Event 2 from Event Number 2 Specify Event Type The event will occur if the value of the assigned process variable x is greater than the setpoint Setpoint A endpoint not included x gt A The event will occur if the value of the assigned process variable x is less than the setpoint Setpoint A endpoint not included x lt A 3 Assign a process variable to the event 146 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system 4 Seta value for the setpoint Setpoint A 5 Optional Configure a discrete output to switch states according to event status 7 7 2 Configure an enhanced event Display Not available ProLink II ProLink Configuration Discrete Events Field Communicator Configure Alert Setup Discrete Events Discrete Events 1 5 An enhanced event is used to perform specific transmitter actions if the event occurs An enhanced
214. t Disable Modbus ASCII as desired Configuration and Use Manual 143 Integrate the meter with the control system The primary reason to disable Modbus ASCII support is to allow you to use the full range of Modbus addresses that are available for your Modbus connections 1 to 127 If Modbus ASCII support is enabled you are limited to using the following Modbus addresses 1 15 32 47 64 79 and 96 110 2 Set Modbus Address to a value between 1 and 127 excluding 111 111 is reserved for the service port 3 Set Floating Point Byte Order to match the byte order used by your Modbus host fo en PEE The bit structure of bytes 1 2 3 and 4 is shown in Table 7 14 Table 7 14 Bit structure of floating point bytes 1 SEEEEEEE S Sign E Exponent 2 EMMMMMMM E Exponent M Mantissa 4 Optional Set Additional Communications Response Delay in delay units A delay unit is 2 3 of the time required to transmit one character as calculated for the serial port currently in use and the character transmission parameters Valid values range from 1 to 255 Additional Communications Response Delay is used to synchronize Modbus communications with hosts that operate at a slower speed than the transmitter The value specified here will be added to each response the transmitter sends to the host Tip Do not set Additional Communications Response Delay unless required by your Modbus host 7 6 4 Configure Digital Communica
215. t Zero Time is appropriate Click Perform Auto Zero to initiate the zero procedure The Calibration in Progress light will turn red during the zero procedure At the end of the procedure e The Calibration in Progress light will return to green if the zero was successful e The Calibration Failure light will turn red if the zero procedure failed In case of failure you have two options Restore Prior Zero Restore Prior Zero restores the flowmeter to the zero value it had just prior to starting the zero procedure If you close the Flow Calibration window you will no longer be able to restore the prior zero Restore Factory Zero Restore Factory Zero is available only if you ordered a transmitter and a sensor together Test or tune the system using sensor simulation Sensor simulation allows you to set specific values or value ranges for mass flow density and temperature The transmitter will report the specified values and take all appropriate actions e g apply a cutoff activate an event or post an alarm You can use this feature to test the system s response to a variety of process conditions including boundary conditions problem conditions or alarm conditions or to tune the loop 44 Micro Motion 9739 MVD Transmitters Quick start with ProLink II When you enable sensor simulation the simulated values are stored in the same memory locations used for process data from the sensor Therefore the simulated values will be
216. t application 0 cseeeeeeeeeeeeees 93 Chapter 6 Configure device options and preferences ssssssscccceccssssscsssceececssssscseeeeeesssseseceees 99 6 1 Configure the transmitter display 0 ceeeeeeeeneeeeeeee ee eeeeeeeaaeeeeeeeaaeeeeeeaaaeeeees 99 6 2 Enable or disable operator actions from the display cceeceeeeeeeeeneeeeeeeeee 103 6 3 Configure security for the display MENUS ceeeeeeeeeeeeeeeeeeeeeeeeeneeeeeeenneees 105 6 4 Configure the speed of the transmitter s response to changes in process CALA ss aioi aaa i aa a aa a a 107 6 5 Configure alarm handling seses asana A TERET 108 6 6 Configure informational parameters ceceeeceeeeeeeeeeeeeeeeeeeeeeeeeeaeeeeeeeeanaees 112 Chapter 7 Integrate the meter with the control system seessesssseossssssssssssssssssssesesssssssssssssese 117 7 1 Configure the MA OUTPUTS cic cc2 cecie cece ccnececee ens conte eens cece deta AE EEEa 117 7 2 Configure the frequency OUtDUt ee eeeeeee cece cette tree eee eeeeeeeeeeeeeeaaeeeeeeaaaaees 124 7 3 Configure the discrete OUtDUt 0 ce eeeeeee eter cette iin 129 7 4 Configure the discrete inDUt cece cece eeeee eect ee eeeeeeeeeeeeeeeeeeeeeeeeeaaeeeeesaaaeees 134 7 5 Configure the MA MPU o ccc secie coe nents ceeteens ceed ineen nen chap cece endne cece aE 136 7 6 Configure digital COMMUNICATIONS cee eeee cece eeeee eect eee eeeeeeeeeeeeeeaeeeeeeeaaa
217. t to communicate poll If communication with the transmitter cannot be established the transmitter may need service Contact Micro Motion 10 14 Check HART Address and Loop Current Mode The default HART Address is 0 This address is appropriate unless the transmitter is in a multidrop environment If the HART Address is configured to a value other than 0 some configuration tools will automatically change Loop Current Mode as well If Loop Current Mode is Disabled the primary mA output will not report process variable data or indicate fault conditions 192 Micro Motion 9739 MVD Transmitters Troubleshooting Procedure 1 Set HART Address as appropriate for your HART network 2 Set Loop Current Mode to Enabled 10 15 Check HART burst mode Procedure 1 Check to see if burst mode is enabled or disabled 2 If burst mode is enabled disable it 10 16 Check mA output trim There are four mA output trim values a 4 mA and a 20 mA trim value for each mA output 9739 MVD transmitters have a 4 and 20 mA trim value for each mA output Verify the configuration of all the trim values Procedure Verify the trim values for the mA output Note Micro Motion does not recommend attempting to trim an mA output if the reading is off by more than 200 microamps If this is the case contact Micro Motion Customer Service 10 17 Check Lower Range Value and Upper Range Value Procedure 1 Verify current process conditions 2 Ch
218. te Pulses Unit A user specified number of pulses represents one flow unit Units Pulse A pulse represents a user specified number of flow units 2 Set additional required parameters e If you set Frequency Output Scaling Method to Frequency Flow set Rate Factor and Frequency Factor e If you set Frequency Output Scaling Method to Pulses Unit define the number of pulses that will represent one flow unit e If you set Frequency Output Scaling Method to Units Pulse define the number of units that each pulse will indicate Configuration and Use Manual 125 Integrate the meter with the control system Frequency Flow The Frequency Flow option is used to customize the frequency output for your application when you do not know appropriate values for Units Pulse or Pulses Unit If you specify Frequency Flow you must provide values for Rate Factor and Frequency Factor Rate Factor The maximum flow rate that you want the frequency output to report Above this rate the transmitter will report A110 Frequency Output Saturated Frequency Factor A value calculated as follows FrequencyFactor RateFactor xN where T Factor to convert selected time base to seconds N Number of pulses per flow unit as configured in the receiving device The resulting Frequency Factor must be within the range of the frequency output 0 to 10 000 Hz e If Frequency Factor is less than 1 Hz reconfigure the receiving device for a higher pulses unit settin
219. te input device so that the desired current is sent to the transmitter b At the transmitter choose OFFLINE MAINT SIM and select READ MAI Micro Motion 9739 MVD Transmitters Quick start with the display c Verify the current value Postrequisites lf the mA output readings were slightly off at the receiving device you can correct this discrepancy by trimming the output e If the mA output reading was significantly off 200 microamps or if at any step the reading was faulty verify the wiring between the transmitter and the remote device and try again e If the mA input reading was slightly off at the transmitter trim and calibrate the input at the remote input device 2 5 Zero the flowmeter Zeroing the flowmeter establishes the flowmeter s point of reference when there is no flow Prerequisites To prepare for the zero procedure 1 Allow the flowmeter to warm up for at least 20 minutes after applying power 2 Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature 3 Stop flow through the sensor by shutting a valve downstream from the sensor 4 Ensure that flow has completely stopped through the sensor and that the sensor is completely full of process fluid 5 Check the flow rate If the flow rate is close to zero you should not need to zero the flowmeter Important The meter was zeroed at the factory and should not require a field ze
220. ter has two optical switches Scroll and Select To activate an optical switch block the light by holding your thumb or finger in front of the opening A If you are in a hazardous environment do not remove the transmitter housing cover Removing the transmitter housing cover in a hazardous environment can cause an explosion or other damage You can operate the optical switches through the lens The optical switch indicator lights up when the transmitter senses that an optical switch has been activated See Table C 1 Table C 1 Optical switch indicator and optical switch states Optical switch indicator State of optical switches Solid red Either the Scroll or the Select optical switch is activated Flashing red Both optical switches are activated C 2 2 Enter a floating point value The display allows you to enter a maximum of 8 characters including the sign The decimal point is not counted as a character Exponential notation is used to enter values that require more than 8 characters 216 Micro Motion 9739 MVD Transmitters Using the transmitter display Enter a floating point value using decimal notation Decimal notation allows you to enter values between 9999999 and 99999999 You can use the decimal point to enter values with a precision of 0 through 4 4 digits to the right of the decimal point Decimal values entered via the display must meet the following requirements e They can contain a maximum of 8 digits or 7 digits
221. ter serial number Floating pt ordering Add comm resp delay Restore Factory Configuration Digital comm settings Fault setting HART address Loop current mode HART device ID Modbus address Enable write protection Response Time Update rate Update rate 100 Hz variable Burst setup Enable burst Burst cmd Burst var 1 4 Vol flow type K2 Std gas vol flow cutoff FD Std gas flow units D1 Std gas density D2 Temp coeff DT Gas wizard Mass factor l zoen i aaor T Series Device Display FTG Model Var1 Var15 M FFQ Manufacturer K Plow switch variable DTG Tag Display precision Flow switch setpoint Flow switch hysteresis DEAT Dato Svar DFQ2 Hardware Rev Number of decimals K3 Distributor D3 Descriptor Display language D4 Software Rev K4 Message Display options Sensor type Display start stop totalizers Option board Display totalizer reset Display auto scroll Display offline menu Display offline password Display alarm menu Display ack all alarms Display backlight on off Display alarm screen password Display status LED blinking Offline password Auto scroll rate Update period Backlight Intensity 233 Using ProLink II with the 9739 MVD transmitter Figure D 3 Configuration menu continued Additional configuration options
222. the appropriate value for your application 4 Optional Set the temperature unit configured on the transmitter to the temperature unit used by your API reference table Configuration and Use Manual 91 Configure process measurement Tip Although configuring the temperature unit to match the temperature units used by your API reference table is not required Micro Motion recommends it 5 Optional If you want to use temperature data from an external temperature sensor a Set Temperature Source to External b Depending on your external setup do one of the following Set up polling for temperature e Use digital communications to write temperature data to the sensor at appropriate intervals e Configure the mA input to receive temperature data from an external measurement device You can now configure your transmitter to report and handle petroleum measurement process variables in the same way that it reports and handles other process variables 5 9 1 Petroleum measurement application The petroleum measurement application enables Correction for the effect of Temperature on volume of Liquids CTL by calculating and applying a Volume Correction Factor VCF to volume measurement Internal calculations are performed in compliance with American Petroleum Measurement API standards API reference tables are used to control how CTL is calculated Your selection of API Table Type specifies the type of process fluid that the calcula
223. the connection parameters to match the HART RS 485 parameters configured in your transmitter To minimize configuration requirements the 9739 MVD transmitter uses an auto detection scheme when responding to a connection request The transmitter will accept all connection requests within the limits described in Table 3 1 Table 3 1 Auto detection limits Address Responds to e Service port address 111 e Configured HART address default 0 e Configured Modbus address default 1 Standard rates between 1200 and 38 400 9 Set the COM Port value to the PC COM port that you are using for this connection 36 Micro Motion 9739 MVD Transmitters Quick start with ProLink Il 10 Set Master as appropriate Secondary Use this setting if another host such as a DCS is on the network Use this setting if no other host is on the network The Field Communicator is not a host 11 Click Connect If the connection is successful e The status bar in the main window is updated to show an active connection The Process Variables window or Commissioning Wizard window is displayed If an error message appears Ensure that you are using the correct COM port e Check the physical connection between the PC and the transmitter e For long distance communication or if noise from an external source interferes with the signal install 120 Q 72 W terminating resistors in parallel with the output at both ends of the communication segme
224. the units configured at the external measurement device For example if the external measurement device is set to send pressure data in PSI you must set the pressure measurement units to be PSI at your transmitter Procedure 1 Set LRV as desired Tip Set the LRV to match the lower range value at the remote device 2 Set URV as desired Configuration and Use Manual 137 Integrate the meter with the control system Tip Set the URV to match the upper range value at the remote device 7 6 Configure digital communications ProLink II ProLink Configuration Device Digital Comm Settings Field Communicator Configure Manual Setup Inputs Outputs Communications The digital communications parameters control how the transmitter will communicate using digital communications The 9739 MVD supports the following types of digital communications e HART Bell 202 over the primary mA terminals e HART RS 485 over the RS 485 terminals e Modbus RS 485 over the RS 485 terminals e Modbus RTU via the service port Note The service port responds automatically to a wide range of connection requests It is not configurable Important The service port clips on the user interface of the 9739 MVD transmitter are directly connected to RS 485 terminals 26 and 27 If you wire the transmitter for RS 485 digital communications you cannot use the service port clips for communication with the transmitter 7 6 1 Confi
225. tions Fault Action Display Not available ProLink II ProLink Configuration Device Digital Comm Settings Digital Comm Fault Setting Field Communicator Configure Alert Setup lInputs Outputs Fault Actions Digital Communications Digital Communications Fault Action specifies the values that will be reported via digital communications if the transmitter encounters an internal fault condition 144 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Procedure Set Digital Communications Fault Action as desired The default setting is None Options for Digital Communications Fault Action Options for Digital Communications Fault Action are shown in Table 7 15 Table 7 15 Options for Digital Communications Fault Action ProLink II Field Communicator Description ae pe Process variable values indicate that the value is greater than the upper sensor limit Totalizers stop incrementing D D ae REE AE Process variable values indicate that the value is greater than the upper sensor limit Totalizers stop incrementing zero METONO Flow rate variables go to the value that represents a flow rate of 0 zero Density is reported as 0 Temperature is reported as 0 C or the equivalent if other units are used e g 32 F Drive gain is reported as measured Totalizers stop incrementing Not a N mber NAN Neco Numer Process variables are reported as IEEE NAN Drive gain is reported
226. tions will assume and the CTL source data the reference temperature and the density unit that the calculations will use Depending on your selection of API Table Type you may or may not need to specify Reference Temperature and Thermal Expansion Coefficient See Table 5 11 for a listing of the API reference tables and related information Table 5 11 API reference tables associated process fluids and associated calculation values Reference Table name Process fluid CTL source data temperature Density unit Generalized crude Observed density 60 F non and JP4 and observed configurable temperature Range 0 to 100 Degrees API Generalized Observed density 60 F non products and observed configurable temperature Range 0 to 85 Degrees API Liquids with a User supplied 60 F non constant density reference density or configurable base or known thermal expansion thermal expansion coefficient coefficient and observed temperature Degrees API Lubricating oils Observed density 60 F non and observed configurable Degrees API temperature Range 0 to 40 92 Micro Motion 9739 MVD Transmitters Table 5 11 Configure process measurement API reference tables associated process fluids and associated calculation values continued Reference Table name Process fluid CTL source data temperature Density unit Generalized crude and JP4 Generalized products Lubricating oils Liquids with a constant dens
227. u License Load from Xmtr to File Save to Xmtr from File Connect to Device Connect to Densitometer Viscometer Disconnect Preferences Meter Verification Data Logger Commissioning Wizard Options e ProLink Il Language e Error Log On Use External Temperature Enable Inventory Totals Reset Enable External Pressure Compensation Copper RTD Installed options Configuration Output Levels Process Variables For information about using Data Status Logger see the ProLink II manual Alarm Log Diagnostic Information Calibration Test Totalizer Control Core Processor Diagnostics PPI Variables Batcher Controls NOC well performance measurement Marine Bunker Transfer 232 Micro Motion 9739 MVD Transmitters Figure D 2 Configuration menu Using ProLink II with the 9739 MVD transmitter Flow Flow direction Flow damp Flow cal Mass flow cutoff Mass flow units Vol flow cutoff Vol flow units Density Density units Density damping Slug high limit Slug low limit Slug duration Low density cutoff K1 Temperature Temp units Temp cal factor Temp damping External temperature External RTD Pressure Flow factor Dens factor Cal pressure Pressure units External pressure Configuration and Use Manual Transmit
228. u may need to apply the Auto Scroll setting before you can access Scroll Rate 6 1 6 Enable or disable the display backlight Display OFF LINE MAINT OFF LINE CONFG DISPLAY BKLT ProLink II ProLink Configuration Display Display Options Display Backlight On Off Field Communicator Not available You can enable or disable the backlight on the display s LCD panel 102 Micro Motion 9739 MVD Transmitters Configure device options and preferences Procedure Enable or disable Backlight as desired The default setting is Enabled 6 2 Enable or disable operator actions from the display Display OFF LINE MAINT OFF LINE CONFG DISPLAY ProLink II ProLink Configuration Display Display Options Field Communicator Not available You can control whether or not the operator will be able to perform specific actions from the transmitter display You can Enable or disable Totalizer Start Stop Enable or disable Totalizer Reset e Enable or disable Acknowledge All Alarms 6 2 1 Enable or disable Totalizer Start Stop from the display Display OFF LINE MAINT OFF LINE CONFG gt DISPLAY TOTALS STOP ProLink II ProLink Configuration Display Display Options Display Start Stop Totalizers Field Communicator Not available You can control whether or not the operator will be able to start and stop totalizers and inventories from the display Restrictions e You cannot start and stop
229. ual 51 Quick start with the Field Communicator 3 Toconnect to a point in the HART multidrop network attach the leads from the Field Communicator to any point on the network See Figure 4 3 Figure 4 3 Field Communicator connection to multidrop network A Field Communicator B 250 600 Q resistance C Devices on the network D Master device 4 Turn on the Field Communicator and wait until the main menu is displayed 5 If you are connecting across a multidrop network a Set the Field Communicator to poll The device returns all addresses that are valid b Enter the appropriate HART address The default HART address is 0 However for multidrop operation the HART address must be unique on the network 6 Optional To navigate to the Online menu press HART Application 2 Online Most configuration maintenance and troubleshooting tasks are performed from the Online menu Tip You may see messages related to the DD or active alerts Press the appropriate buttons to ignore the message and continue 4 3 Configuration tips and tricks Review these tips before beginning configuration 52 Micro Motion 9739 MVD Transmitters Quick start with the Field Communicator 4 3 1 HART security HART security may be enabled on the 9739 MVD transmitter To configure the transmitter using HART protocol you must disable HART security 4 3 2 Default values and ranges Default values an
230. um Totalizers are not properly saved A calibration procedure is in process Troubleshooting Check the HART device ID The weights and measures security seal has been broken An authorized procedure is required to reestablish security Cycle power to the meter Contact Micro Motion Cycle power to the meter Contact Micro Motion Check the settings of Upper Range Value and Lower Range Value See Section 10 17 Check process conditions Actual conditions may be outside of the normally expected conditions for which the output is configured Verify process conditions checking especially for air in the flow tubes tubes not filled foreign material in the tubes or coating in the tubes Verify that the measurement units are configured correctly for your application Purge the flow tubes Check that the transmitter is in loop test mode Exit mA output trim Check the HART polling address Check that the output has been fixed via digital communication Check the drive gain and the pickoff voltage See Section 10 25 and Section 10 26 Check for electrical shorts See Section 10 27 Check the power supply and power supply wiring See Section 10 9 Contact Micro Motion Allow the procedure to complete For zero calibration you may abort the calibration set the zero time parameter to a lower value and restart the calibration 181 Troubleshooting Table 10 2 Status alarms and recom
231. uration of Frequency Output Fault Action 10 22 Check Flow Direction The interaction of the flow direction parameter flow values reported by the transmitter and flow totals reported by the transmitter is complex For the simplest operation actual process flow should match the flow arrow printed on the side of the sensor case Procedure 1 Verify the actual direction of process flow through the sensor 2 Verify the configuration of Flow Direction 10 23 Check cutoffs There are separate cutoff parameters for mass flow volume flow including gas standard volume flow and density Furthermore there is an independent cutoff for each mA output The interaction between cutoffs sometimes produce unexpected results Procedure Verify the configuration of the cutoffs 194 Micro Motion 9739 MVD Transmitters Troubleshooting Tip For typical applications Micro Motion recommends setting Flow Cutoff to the zero stability of your sensor multiplied by 10 10 24 Check for slug flow The default slug flow limits are appropriate for most applications Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility of the transmitter reporting slug flow conditions If slug limits have been configured and slug flow occurs a slug flow alarm will be generated Outputs that are configured for flow rate hold their last known value until the slug flow clears or up to the configured slug flow duration
232. ured AO Cutoff defines the lowest flow rate that will be reported via the mA output If mA Output Process Variable is set to Gas Standard Volume Flow Rate the volume flow rate reported via the mA output is controlled by the higher of the two cutoff values Gas Standard Volume Flow Cutoff affects both gas standard volume flow values reported via outputs and gas standard volume flow values used in other transmitter behavior e g events defined on gas standard volume flow AO Cutoff affects only flow values reported via the mA output Example Cutoff interaction with AO Cutoff lower than Gas Standard Volume Flow Cutoff Configuration e mA Output Process Variable for the primary mA output Gas Standard Volume Flow Rate e Frequency Output Process Variable Gas Standard Volume Flow Rate e AO Cutoff for the primary mA output 10 SLPM standard liters per minute e Gas Standard Volume Flow Cutoff 15 SLPM Result If the Gas Standard Volume flow rate drops below 15 SLPM volume flow will be reported as 0 and 0 will be used in all internal processing 78 Micro Motion 9739 MVD Transmitters Configure process measurement Example Cutoff interaction with AO Cutoff higher than Gas Standard Volume Flow Cutoff Configuration e mA Output Process Variable for the primary mA output Gas Standard Volume Flow Rate e Frequency Output Process Variable Gas Standard Volume Flow Rate e AO Cutoff for the primary mA output 15 SLPM standard liters per
233. used throughout transmitter functioning For example sensor simulation will affect All mass flow temperature or density values shown on the display or reported via outputs or digital communications The mass total and mass inventory values e All volume calculations and data including reported values volume totals and volume inventories All mass temperature density or volume values logged to Data Logger Sensor simulation does not affect any diagnostic values Unlike actual mass flow and density values the simulated values are not temperature compensated adjusted for the effect of temperature on the sensor s flow tubes Important Do not enable sensor simulation unless your process can tolerate the effects of the simulated process values Procedure 1 Click ProLink Configuration Sensor Simulation 2 Enable sensor simulation 3 For mass flow set Wave Form as desired and enter the required values tooth Sauipe Period Minimum Maximum lie Period Minimum Maximum 4 For density set Wave Form as desired and enter the required values Configuration and Use Manual 45 Quick start with ProLink Il Triangular wave Period Minimum Maximum Sine wave Period Minimum Maximum 5 For temperature set Wave Form as desired and enter the required values Triangular wave Period Minimum Maximum Sine wave Period Minimum Maximum 6 Observe the system response to the si
234. ut parameters before returning the flowmeter to service In some situations the transmitter automatically loads a set of stored values and these values may not be appropriate for your application 7 1 1 Configure mA Output Process Variable Display OFF LINE MAINT OFF LINE CONFG IO AO 1 SRC OFF LINE MAINT OFF LINE CONFG IO AO 2 SRC ProLink II ProLink Configuration Analog Output Primary Secondary Output PV SV Is Field Communicator Configure Manual Setup lInputs Outputs mA Output 1 Primary Variable Configure Manual Setup lInputs Outputs mA Output 2 Secondary Variable mA Output Process Variable controls the variable that is reported over the mA output Prerequisites If you plan to configure an output to report volume flow ensure that you have set Volume Flow Type as desired Liquid or Gas Standard Volume If you plan to configure an output to report a concentration measurement process variable ensure that the concentration measurement application is configured so that the desired variable is available If you are using the HART variables be aware that changing the configuration of mA Output Process Variable will change the configuration of the HART Primary Variable PV and or the HART Secondary Variable SV Procedure Set mA Output Process Variable as desired Default settings are as follows e Primary mA output Mass Flow Rate e Secondary mA output Density Options for mA Out
235. utput Example Cutoff interaction Configuration e mA Output Process Variable for the primary mA output Mass Flow Rate e Frequency Output Process Variable Mass Flow Rate AO Cutoff for the primary mA output 10 grams second e Mass Flow Cutoff 15 grams second Result If the mass flow rate drops below 15 grams second mass flow will be reported as 0 and 0 will be used in all internal processing 68 Micro Motion 9739 MVD Transmitters Configure process measurement Example Cutoff interaction Configuration mA Output Process Variable for the primary mA output Mass Flow Rate e Frequency Output Process Variable Mass Flow Rate e AO Cutoff for the primary mA output 15 grams second e Mass Flow Cutoff 10 grams second Result e f the mass flow rate drops below 15 grams second but not below 10 grams second The primary mA output will report zero flow The frequency output will report the actual flow rate and the actual flow rate will be used in all internal processing If the mass flow rate drops below 10 grams second both outputs will report zero flow and 0 will be used in all internal processing 5 3 Configure volume flow measurement for liquid applications Display OFF LINE MAINT OFF LINE CONFG UNITS VOL ProLink II ProLink Configuration Flow Field Communicator Configure Manual Setup Measurements Flow The volume flow measurement parameters control how liquid volume flow is measured
236. utput Source Field Communi Discrete output Option Display ProLink Il cator Condition voltage Discrete Event Discrete Event x Discrete Event x Site specific 1 5 3 Event 1 2 4 Event 1 Event 1 Site specific Event 2 Event 2 Event 1 or Event 1 or OFF Ov Event 2 Event 2 2 Assumes that Discrete Output Polarity is set to Active High If Discrete Output Polarity is set to Active Low reverse the voltage values 3 Events configured using the enhanced event model 4 Events configured using the basic event model 130 Micro Motion 9739 MVD Transmitters Integrate the meter with the control system Table 7 8 Options for Discrete Output Source continued Field Communi Discrete output Option Display ProLink Il cator Condition voltage Flow Switch FL SW Flow Switch Flow Switch FON Site specific ei JorF pov ON OFF Flow Direction FLDIR Forward Re Forward Re e Progress Progress Progress FF Fault FAULT Fault Condition Fault Site specific ia Configure Flow Switch parameters Display OFF LINE MAINT OFF LINE CONFG 10 DO CONFIG FL SW ProLink II ProLink Configuration Flow Flow Switch Setpoint ProLink Configuration Flow Flow Switch Variable ProLink Configuration Flow Flow Switch Hysteresis Field Communicator Configure Manual Setup lInputs Outputs Discrete Output DO Assignment Configure Manual Setup lInputs Outputs Discrete Output Flow Switch Source Configure
237. verter e Adapters as required e g 9 pin to 25 pin Important If the HART security switch is set to ON HART protocol cannot be used to perform any action that requires writing to the transmitter For example you cannot change the configuration reset totalizers or perform calibration using the Field Communicator or ProLink II with a HART connection When the HART security switch is set to OFF no functions are disabled You can connect ProLink II to the HART clips on the transmitter to any point in a local HART loop or to any point in a HART multidrop network A If the transmitter is in a hazardous area do not remove the housing cover while power is being supplied to the unit Removing the housing cover while power is supplied to the unit could cause an explosion To access transmitter information in a hazardous environment use a communication method that does not require removing the transmitter housing cover Procedure 1 To connect to the HART clips a Remove the transmitter housing cover b Attach the leads from the signal converter to the HART clips on the face of the transmitter and add resistance as necessary See Figure 3 2 ProLink Il must be connected across a resistance of 250 600 Q Tip HART connections are polarity insensitive It does not matter which lead you attach to which terminal Configuration and Use Manual 29 Quick start with ProLink Il Figure 3 2 ProLink II connection to HART clips
238. verter to any point in the network and add resistance as necessary See Figure 3 9 Restriction The Modbus host must not be communicating with the transmitter when you make the ProLink II connection To make the connection wait until the host communication is complete or terminate the host connection 38 Micro Motion 9739 MVD Transmitters Quick start with ProLink II Figure 3 9 ProLink Il connection to RS 485 network PC 25 to 9 pin adapter if necessary RS 485 to RS 232 signal converter 120 Q 1 2 watt terminating resistors at both ends of the segment if necessary DCS or PLC must not be communicating with the transmitter during the ProLink II connection mon w gt Transmitter 5 Start ProLink Il 6 Choose Connection Connect to Device 7 f necessary set the connection parameters to match the Modbus RS 485 parameters configured in your transmitter To minimize configuration requirements the transmitter uses an auto detection scheme when responding to a connection request The transmitter will accept all connection requests within the auto detection limits see Table 3 2 Table 3 2 Auto detection limits Address Responds to e Service port address 111 e Configured HART Address default 0 e Configured Modbus Address default 1 Standard rates between 1200 and 38 400 Configuration and Use Manual 39 Quic
239. w Direction only if mA Output Process Variable is set to a flow variable The effect of Flow Direction on mA outputs depend on the Lower Range Value configured for the mA output e If Lower Range Value is set to 0 see Figure 5 5 e If Lower Range Value is set to a negative value see Figure 5 6 Figure 5 5 Effect of Flow Direction on the mA output Lower Range Value 0 Flow Direction Forward Flow Direction Reverse Negate Forward Flow Direction Absolute Value Bidirectional Negate Bidirectional x Reverse fow f Forward flw gt 4 Reverse tow Forward flow gt Reverse fow f Forara flow gt Notes e Lower Range Value 0 e Upper Range Value x 80 Micro Motion 9739 MVD Transmitters Configure process measurement Figure 5 6 Effect of Flow Direction on the mA output Lower Range Value lt 0 Flow Direction Forward Flow Direction Reverse Negate Forward I I 0 x x lt Reverse flow __ Forward flow gt 4 Reverse fow f Fornara flow gt Flow Direction Absolute Value Bidirectional Negate Bidirectional 0 lt Reverse fow Forward flow p gt Notes e Lower Range Value x e Upper Range Value x Example Flow Direction Forward and Lower Range Value 0 Configuration e Flow Direction Forward e Lower Range Value 0 g s e Upper Range Value 100 g s Result e Under conditions of reverse flow or zero
240. w the meter to warm up Verify that the tubes are full of process fluid Check the wiring between the sensor and transmitter See Section 10 10 If this alarm appears during zeroing verify that there is no flow through the sensor then retry the procedure Cycle power to the meter then retry the procedure Verify that there is no flow through the sensor then retry the procedure Cycle power to the meter then retry the procedure 179 Troubleshooting Table 10 2 Status alarms and recommended actions continued A012 Calibration too high A013 Zero too noisy A014 Transmitter failed A016 Line temperature out of range A017 Meter RTD temperature out of range A018 EEPROM checksum error A019 RAM or ROM test error A020 Calibration factors unentered A021 Incorrect sensor type 180 Mechanical zero corresponds with high forward flow the resulting zero was greater than 3 us Temperature Density calibration many possible causes Mechanical zero Unstable value exists Many possible causes The value computed for the resistance of the Line RTD is outside limits The value computed for the resistance of the Meter Case RTD is outside limits The flow calibration factor and or K1 has not been entered since the last master reset The sensor is recognized as a straight tube but the K1 value indicates a curved tube or vice versa Verify that there is no flow through the sensor then ret
241. ws MeterFactormassFliow 0 9989 x Eaa 0 9996 250 07 The new meter factor for mass flow is 0 9996 9 2 1 Alternate method for calculating the meter factor for volume flow The alternate method for calculating the meter factor for volume flow is used to avoid the difficulties that may be associated with the standard method This alternate method is based on the fact that volume is inversely proportional to density It provides partial correction of the volume flow measurement by adjusting for the portion of the total offset that is caused by the density measurement offset Use this method only when a volume flow reference is not available but a density reference is available Procedure 1 Calculate the meter factor for density using the standard method see Section 9 2 2 Calculate the meter factor for volume flow from the meter factor for density 1 MeterFactoryoiume 2 MeterFactorpensity Configuration and Use Manual 167 Measurement support Note The following equation is mathematically equivalent to the first equation You may use whichever version you prefer DensityrFiowmeter MeterFactorvyoume ConfiguredMeterFactorpensity X DensityreferenceDevice 3 Ensure that the calculated meter factor is between 0 8 and 1 2 inclusive If the meter factor is outside these limits contact Micro Motion Customer Service 4 Configure the meter factor for volume flow in the transmitter
242. xhibits different behavior an alarm condition is present Postrequisites Allow the electronics to warm up for approximately 10 minutes before relying on process measurements Although the sensor is ready to receive process fluid shortly after power up the electronics can take up to 10 minutes to warm up completely 2 2 Configuration tips and tricks Review these tips before beginning configuration 2 2 1 Access to OFFLINE menu Access to the OFFLINE menu may be disabled To configure the transmitter using the display you must enable access to the OFFLINE menu Configuration and Use Manual 19 Quick start with the display 2 2 2 Default values and ranges Default values and ranges for the most commonly used parameters are provided in Appendix A 2 3 20 Configure the primary mA output to report mass flow rate in a user selected measurement unit This procedure shows you how to perform these tasks using the display For all other configuration tasks including other options for the mA output see the configuration sections of this manual Note This procedure assumes that you are starting from the factory default configuration Procedure 1 Navigate to the configuration menu a d At the transmitter display activate the Scroll and Select optical switches simultaneously until SEE ALARM appears on the display Activate Scroll repeatedly until OFF LINE MAINT appears on the display then activate Select
243. y data in a unit that is not hard coded in the transmitter A special measurement unit is calculated from an existing measurement unit using a conversion factor Restriction Although you cannot define a special measurement unit using the display you can use the display to select an existing special measurement unit and to view process data Procedure 1 Specify Base Mass Unit Base Mass Unit is the existing mass unit that the special unit will be based on 2 Specify Base Time Unit Base Time Unit is the existing time unit that the special unit will be based on 3 Calculate Mass Flow Conversion Factor as follows a x base units y special units b Mass Flow Conversion Factor x y 4 Enter Mass Flow Conversion Factor 5 Set Mass Flow Label to the label to be used for the mass flow unit 6 Set Mass Total Label to the label to be used for the mass total and mass inventory unit The special measurement unit is stored in the transmitter You can configure the transmitter to use the special measurement unit at any time 66 Micro Motion 9739 MVD Transmitters Configure process measurement Example Defining a special measurement unit for mass flow You want to measure mass flow in ounces per second 1 Set Base Mass Unit to Pounds Ib 2 Set Base Time Unit to Seconds sec 3 Calculate Mass Flow Conversion Factor a 1 lb sec 16 oz sec b Mass Flow Conversion Factor 1 16 0 0625 4 Set Mass Flow Conversion Factor t

Download Pdf Manuals

image

Related Search

Related Contents

TD2 Forensic 1:2 Duplicator  Liste des marchés conclus en 2012  CamPart Travel CH-0596  GESTÃO FINANCEIRA E DE VENDAS  Manuale utente  Rio Grande Games Antike 19 User's Manual  Manual de instalación, funcionamiento y  TEGAM INC. MODEL DSRS-5DA DECADE SYNCO/RESOLVER  T'nB CIPC8 serial cable  Télécharger le pdf  

Copyright © All rights reserved.
Failed to retrieve file