Home

Quick Start Unit Software Setup

image

Contents

1. Setup to navigate to Setup screen Ensure that Auto Start En Harmonic Correct En and PWR Fact Correct En buttons are off blue color If they are ON green press them to toggle to OFF blue Press Save Settings Press Status to navigate to Status screen Press Home to navigate to Home screen HI ACTI 1 Hr ten See Note 9 I ik Loads NOTE Built In Sensor Wiring Error Detection The active filter has an automatic sensor wiring error detection algorithm built in to the controls If a sensor wiring error is detected please reference the Sensor Error Auto Detection section of the full user manual available at www transcoil com 3 Home screen check Compare Freq to expected line frequency Compare Supply Voltage to expected line voltage Current expected to be zero because unit is not running and CT inputs are shorted If status indicates a Fault press Stop button to reset condition 4 Status screen check Press Status to navigate to Status screen Compare Volts to expected line voltage Compare Freq to expected line frequency Current expected to be zero if unit is not running and CT inputs are shorted 5 Phase rotation check Warning Press Phase to Neutral Voltage Plot Check that the current peaks follow the following sequence from left to right Phase A green Phase B blue Phase C red Equip
2. GA All of these sources of power must be disconnected before working on the HGA After switching off the power always allow 5 minutes for the capacitors in the HGA and in the drive to discharge before working on the HGA the drive the motor or the connecting wiring It is good practice to check with a voltmeter to make sure that all sources of power have been disconnected and that all capacitors have discharged before beginning work NOTE Full User Manual e For the full user manual and other supporting documentation please go to a a FD http www transcoil com 7 N 5 http www transcoil com 1 Verify unit external connections Phase A B C power connection with positive A B C phase rotation expected CT H1 Terminal is pointing toward the source CT feedback on phases A amp C to TB 1 Leave CT shorting bars in place on TB 1 With the HGA circuit breaker open energize the source to the HGA Close the HGA circuit breaker Fans and HMI should come on in lt 5 seconds HMI will start on Home screen Load s have an integral 5 line reactance or equivalent dc bus choke Warning Hazardous voltages are present when unit is energized Language Selection The active filter supports several languages including English French and Spanish Press Setup to navigate to Setup screen and press the Language Setup button Select language setting from the language setup pop up screen 2 Converter check 1 Press
3. HARMONICGUARD ACTIVE Active Harmonic Filter Quick Start Unit Software Setup TCI LLC W 132 N10611 Grant Drive Germantown Wisconsin 53022 Phone 414 357 4480 Fax 414 357 4484 Helpline 800 TCI 8282 Web Site http www transcoil com TCI LLC No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means mechanical electronic photocopying recording or otherwise without the prior written permission of TCI LLC The information in this manual is subject to change without notice Every precaution has been taken in the preparation of this manual TCI LLC assumes no responsibility for errors or omissions Neither is any liability assumed for damages resulting from the use of the information contained in this publication Be sure to read understand and follow all safety instructions Only qualified electricians should carry out all electrical installation and maintenance work on the HarmonicGuard Active Filter HGA All wiring must be in accordance with the National Electrical Code NEC and or any other codes that apply to the installation site Disconnect all power before working on the equipment Do not attempt any work on a powered Active Harmonic Filter The HGA drive motor and other connected equipment must be properly grounded The HGA may receive power from two or more sources Three phase power is connected to the main input terminals of the H
4. ment is phase rotation sensitive if phase rotation is incorrect power down unit and rewire to adjust phase rotation by swapping two incoming phase connections Improper operation will occur when input voltage phase rotation is incorrect Turn off Unit and chec k 3 phase AC input voltage wiring for A B C phase rotation or missing phase connection Filter Status Filter Current Used 50 supply oltacg J 494 Ye T its Ag d a Current Fa F Ower 0 00 i M eg ative Factor equals Lag LinesLoad Status Power Factor 0 00 Current om a Stopped Line Lo ad Current F lot Converter Current F lot 6 Converter check 2 Total Press Setup to navigate to Setup screen ar 5E PMS Ensure that Auto Start En Harmonic ee eee ee z 7 7 Link oltaqe we OC Correct En and PWR Fact Correct En Heer erp A buttons are off blue color os x Press Status to navigate to Status screen eae 50 Press Run to start unit operation Weer 5 7 Remove CT shorting bars Warning Press Stop to turn off unit Disconnect power from cabinet o Turn off the built in door breaker AND o Turn off the upstream feeder breaker Lethal voltages may be present Wait 5 A minutes for DC bus voltage to drop to safe levels Warning Check for voltage in cabinet with a DMM before working inside cabinet Open the cabinet door and remove shorting bars from CTs con
5. nable Autostart Warning When Auto Start is enabled unit may operate without operator input e Press Save Settings to save settings and restart converter e Let the unit come on automatically about 30 s 11 Final check Navigate to Status screen volts VAC RMS Navigate to Line Load status Current 755 Arms Note the corrected voltage current power and Power 17 GAEE THD Apparent Power e A A Power Factor THD H Y THD mrima oy E TCI LLC W 132 N10611 Germantown Wisconsin 53022 Phone 414 357 4480 Fax 414 357 4484 Helpline 800 TCI 8282 Web Site http www transcoil com 2013 TCI LLC Publication No 28666 Effective 10 29 13 Revision A Printed in USA
6. nected to TB 1 8 Current polarity 1 Power up unit From Home screen press Run to turn on unit Press Status to navigate to Status screen Select Vline Iline screen Note Lightly loaded conditions less than 20 CT rating will not have enough current to show up on line plot Check that Phase A to Neutral voltage peak lines up with Phase A current use zoom if necessary Check that Phase C to Neutral voltage peak lines up with Phase C current Power system down and check CT installation location and orientation if Phase A plots differ significantly from Phase C plots Warning Improper operation and damage may occur if CTs are installed incorrectly 9 Current Polarity 2 Tora Navigate to Status screen alts VAC PMS Navigate to Line Load status Current o7 4 Res Verify that Volts Current Power ata 126 Rae I THD and V THD match expected values Apparent Power BESIEN evs for the power system Power Factor If they do not verify CTs are correctly installed THD o Warning v THD 2E E Improper operation and damage may I THO Ret Ra occur if CTs are installed incorrectly l Stopped 10 Final setup Press Setup to navigate to Setup screen Press Harmonic Correct En to enable harmonic correction If unit is sized with sufficient capacity to provide power factor correction press PF Correct En Press Auto Start En to e