CFW-10 - Quick Start Guide
Contents
1. Note New CFW10 drives are shipped with parameters preset to factory defaults If you need to reload factory defaults at any time first set password parameter P000 5 then set factory default parameter P204 5 Keypad Start Stop Local Mode This operation mode is recommended for users who are operating the drive for the first time without additional control connections 1 Press the w start key The motor will accelerate from 0 0 to 3 00 Hz minimum speed P133 in the clockwise direction Note If the direction of rotation is not correct switch off the drive and wait until the capacitors discharge completely as long as 10 minutes and then swap any two wires at the motor output 2 Press the O key and hold it to increase motor speed maximum speed P134 Note On Plus versions use the keypad potentiometer located on the bottom right of the keypad to adjust speed 3 Press the w stop key The motor decelerates to 0 0Hz and stops with a display of rdY Keypad Operation and Parameter Setup LED Display indicates fault codes inverter status parameter Red LED When lit the display indicates the parameter number Key Description Switches the display between parameter number and content Increases Speed frequency number and value Green LED When lit the display indicates the parameter value Figure 2 Keypad Operation and Parameter number content Decreases
2. Publication Number QSOO5CFW10 1 4 to 1HP 1 6 to 4A 120V 1 4 to 3HP 1 6 to 10A 230V P Transforming Energy into Solutions 1 800 ASK 4WEG 275 4934 Power Connections The CFW10 Quick Start Guide is a supplement to help get the CFW10 started quickly using the most common installation and configuration options This CFW10 Quick Start Guide is not meant to replace the CFW10 User s Manual For detailed instructions safety precautions proper mounting installation configuration and operation please refer to the CFW10 User s Guide Warning Only qualified personnel should plan or implement the installation start up operation and maintenance of this equipment Personnel must read the entire CFW10 User s Guide before attempting to install operate or troubleshoot the CFW10 m oceen oem wes ces cewwees cons coetten Figure 1 Power and Grounding Connections Basic Wiring 1 Mount the CFW10 to a flat vertical surface Connect the incoming single phase power leads to the L L1 and N L2 connections on the power terminal and connect the GROUND lead to PE on the power terminal Refer to Figure 1 3 Connect the motor leads to the U V and W connections on the power terminal and connect the GROUND lead to PE on the power terminal Refer to Figure 1 Note Only three phase AC motors can be used 4 Apply power to the CFW10 drive The drive will run self diagnostics and if no problems are found it will display rdY
3. Speed Pot value must be 2 5KQ but lt 10KQ at 2W and is connected as shown in Figure 5 Fault Codes When a fault is detected the drive is disabled and the Fault Code is displayed Example E01 To restart the drive after a fault has occurred the drive must be reset Resetting the drive can be done by disconnecting and reapplying AC power oc oc Figure 4 3 Wire Start Stop Common Figure 5 Analog Input with Speed Pot power on reset by pressing the O RESET key manual reset automatic reset or via digital inputs For details on Reset and a full list and description of Fault Codes please read Chapter 7 in the CFW10 User s Guide SI Parameters Example e The following is a typical list of parameter changes that may be needed in addition to the factory default settings P204 5 P000 5 Parameter Access 5 Password P204 5 Loads Factory Default P100 5 Acceleration Time 5 seconds P101 10 Deceleration Time 10 seconds P133 3 00 Minimum Frequency 3 00 Hz P134 60 00 Maximum Frequency 60 00 Hz e Local Remote parameters allow the drive to be set up to operate from Keypad Remote Terminal or a programmed combination of keypad and terminal inputs P221 Local Speed Reference Selection P222 Remote Speed Reference Selection P229 Local Command Selection P230 Remote Command Selection P231 Forward Reverse Selection e Read Only Parameters P002 P040 can be us
4. Speed and Parameter number content Starts Stops the drive via the acceleration deceleration ramp and resets the drive after a fault Note Plus versions of the CFW10 have a speed potentiometer on the lower right side of the keypad which is used to increase decrease speed Display Display Description rdY Drive is ready to be enabled Sub Power supply voltage too low for drive operation dcb Drive in DC braking mode EPP Drive is loading factory setting The CFW10 does not require parameter programming prior to start up and is ready to operate with the factory default settings A parameter example is given below to familiarize the user with parameter navigation viewing and programming Action LED Display Description After power is applied to the drive the display shows the following message Press the Q key to view parameter number The red LED on the keypad will light to indicate parameter number Press the O or arrow keys to select a parameter Press the Q key to view the value of the parameter The green LED on the keypad will light to indicate parameter value D ER i LO Ca Oe CD i ico Drive is ready to be started Select the desired parameter This example uses parameter number P100 Acceleration Time This is the numerical value associated with the parameter For this example then P100 5 0 therefore the acceleration time is set for 5 seconds
5. shown in Figure 3 2 Wire Start Stop Remote Mode Parameters 1 Confirm DI4 is set to START STOP P266 4 2 Set P229 1 DIx if you want the 2 wire control in local mode 3 Confirm P230 1 DIx if you want the 2 wire control in remote mode Control Wiring Verify there is a jumper between XC1 1 general enable and XC1 5 or the drive will not work Jumper can be eliminated if DI1 is set to No Function P263 0 Start Stop switch is N O normally open and is connected as shown in Figure 3 Local Remote Start Stop General Enable 10 Nc 12 NO Figure 3 Local Remote and 2 Wire Start Stop z 3 Wire Start Stop Remote Mode Parameters 1 Set D11 Start to On P263 13 See note below 2 Set DI2 Stop to Off P264 14 3 Set D14 to No function P266 0 4 Set P229 1 DIx if you want the 3 wire control in local mode 5 Confirm P230 1 Dlx if you want the 3 wire control in remote mode Control Wiring Start and Stop are momentary push button switches and are connected as shown in Figure 4 Start is a N O normally open contact and Stop is a N C normally closed contact Note When initially setting DI1 to START P263 13 an E24 programming error will occur until DI2 is set to STOP P264 14 Operation from Remote Analog Input Speed Pot Parameters 1 Confirm P222 1 Remote Speed Ref Al1 Control Wiring
6. Press the O or arrow keys to change the parameter value Co G Set the new desired value In this example the acceleration time has been increased to 6 1 seconds Note To change parameter values you must first set the access parameter P000 5 Some parameter changes require the drive be stopped first Press the Q key to store the new value C3 The new value for P100 acceleration time is stored in memory Repeat this procedure for other parameters that may need to be changed Keypad Start Stop Local Mode continued 4 lf parameters were accessed or changed under Parameter Setup then the last parameter number or value will be displayed Scroll up or down with the O or keys to the read only parameter P002 Frequency Proportional Value for Speed and press the Q key to see the value 5 Return to step 1 and press the iZi start key to start the drive Local Remote Modes In the previous section the drive was operated from the keypad Local Mode If you wish to operate in remote mode you will need to add an external Local Remote switch Note To control speed in remote mode a speed potentiometer figure 5 can be added or the up and down arrow keys on the keypad can be used by setting P222 0 Plus versions can use the keypad speed potentiometer by setting P222 3 Parameters Confirm DI3 is set to Local Remote P265 6 Control Wiring Local Remote switch is N O normally open and is connected as
7. ed for monitoring and troubleshooting For a full list and description please read the CFW10 User s Guide By monitoring certain read only parameters drive operational values can be determined without the use of any other test equipment P002 Frequency Proportional Value Speed P003 Motor Current P004 used to monitor DC Link Voltage P005 Motor Frequency P007 Motor Output Voltage P014 Last fault These are just a few examples of drive set up and parameters Please read the CFW10 User s Guide for additional information Publication Numer QSOO5CFW10