Home
EasyCheck 3000
Contents
1. If any faults or an wrong input has taken place than a fault message will appear See next page Version 2 1 11 EasyCheck 3000 12 3 1 Potential error messages Here are a few error messages which could pop up during operation Press Esc Cause Source detector or target detector not found Remedy Quit action check correct fit of detector or adapter and try again Cause Source detector or target detector not found Remedy Quit action check correct fit of detector or adapter and try again Version 2 1 12 Source and target detector are not the same type Only detectors of the same type can be cloned Quit action and repeat with equal detector types It was not possible to program the target detector Quit action and try again If still no success than the target detector is faulty In this case please contact the detector manufacturer Cause Unknown type of source or target detector Remedy No copy possible with an unknown detector Version 2 1 13 EasyCheck 3000 12 4 12 4 1 Main Menu 4 Detector Setup Pressing the key 4 on page 2 of the main menu will open the sub menu 4 Detector Setup This menu is divided into 4 sub menu items Version 1 10 on the 12 04 06 Display page 1 Display page 2 Detector Setup 1 Change Life sign Pressing the key 1 in the Detector Setup menu will start the search for the connected detector if still unknown t
2. detector address detector type serial number software date inspection date calibration date sensitivity level with respective sensitivity indices and the current smoke pollution and temperature rates e change the detector address communication address e _ change the sensitivity level e switch on or off life signs LED flashing of a detector e copy the detector clone Keyboard 0 9 Number Clr Clear Ent Enter Esc Escape Men Mainmenu T Page up 4 Page down Display The display is a four line text display with 20 characters per line The arrows up and down on the right hand side of the display indicate that the display cannot show everything on 1 display page i e the key indicates the preceding page and the J key the following page If both arrows are shown at the same time this means that there is at least one preceding and one following page Accompanying signals A short high tone confirms a permitted or a correct keystroke a short low tone indicates a non permitted keystroke or a faulty input To list all accompanying signals would not make sense as they are only meant to support intuitive operation When working with the device the different tones will be memorised with time and the operator develops a feeling for working with the EasyCheck 3000 These signals can also be deactivated in the EasyCheck Setup menu item 4 Version 2 1 5 EasyCheck 3000
3. Joo aw detectomat 10 When an external power unit is used the batteries are electronically separated from the device so that the power supply is taken over by the power unit so the batteries do not discharge any further In addition the cut off timers are switched off as well i e the device does not switch off automatically and the background light if switched on in the first place remains switched on for as long as the device is run on a power unit In case the device is exclusively operated with a power unit for a longer period of time it is advisable to remove the batteries from the device in order to prevent leakage and thus damage to the Easy Check This applies to empty batteries and discharged storage batteries in general It is not possible to recharge accumulator batteries in this device Input jack The input jack is located at the front of this device This is to connect loop elements which do not have a terminal base via the provided adapter cable It is important to make sure that there is no detector in the terminal base during programming with the input jack In this case always the element with the lowest address will be displayed That s why it is important that only ONE element is connected at a time ATTENTION NEVER apply current into the input jack This would cause irreparable damage to the EasyCheck 3000 Switch on The device is switched on by pressing the key 0 keep pressed for longer
4. 7 Batteries Primary battery 3 x AA or Accumulator cell 3x AA NiCd or better NiMH It is recommended to use only high quality batteries with this device as these show very little self discharge and high durability as well as a low risk of leakage It is also possible to use NiCd or NiMH storage batteries although these have a much higher self discharge rate than primary cells batteries In any case it has to ensured that always three cells or storage batteries of the same kind are inserted Batteries must NEVER be mixed i e be of different types different capacity or different charge status In order to avoid leakage and any resulting damage to the EasyCheck it is advisable to replace empty batteries or discharged storage batteries immediately with new ones ATTENTION Take the old batteries out and wait about 20 seconds The internal condensers need to be discharged totally so that a reset can take place If new batteries are placed to early than the EasyCheck will not start but the batteries will still be discharged 8 External power unit The device can be operated with an external power unit Art No 50925 or any other power unit equipped with a tubular plug In this case it is absolutely necessary that the power unit meets the following requirements Tubular plug outer diameter 3 5mm Inner diameter 1 3mm Voltage 9V 14V unregulated Power at least 150mA better 200mA Version 2 1 6 a
5. for the connected AOM 3301 if still unknown the display will show the message searching address and subsequently call up the following text on the display To turn the external sounder beacon on change value to 1 and press Ent Potential error messages No AOM 3301 connected or PL detector still connected on the reverse side Make sure that only the AMD 3301 is connected and try again AOM 3301 address not found Check connection and try again Version 2 1 18 I Joo Se detectomat 12 5 EasyCheck Setup Pressing the key 5 on page 2 of the main menu will open the sub menu 5 EasyCheck Setup This is only possible on the second page if main menu item 4 and 5 are visible This menu is divided in 5 sub menu items Version 1 10 from the 12 04 06 The display shows the following text Display page 2 To return back to the main menu press the Esc or Men key If settings have been changed the question whether the changes are to be saved permanently in the EEPROM of the EasyCheck i e will stay on even after the device has been switched off has to be answered before the return to the main menu will proceed Display text Pressing the Ent key results in a confirmation so that the changes are saved permanently Afterwards the function automatically returns to the main menu Pressing the Esc key results in an interruption so that the changes are only
6. new can be changed Version 2 1 16 J Joo aw detectomat Once the required value is keyed in this needs to be confirmed by pressing the Ent key causing Easy Check to change the OTi detector mode to the desired mode To return into the Detector Setup menu press Esc or to return into the Main menu press the key Men The value can also be increased by using the T key or decreased using the 4 key The following table shows the possible settings 0 Moist detection a Cigar smoke detection OFF 1 Moist detection Cigar smoke detection OFF 2 Moist detection Cigar smoke detection ON 3 Moist detection 7 Cigar smoke detection ON Default setting is 0 ATTENTION Values can be entered from 0 3 Entries beyond this margin will not be accepted and will produce a corresponding fault message on the display Pressing the Clr key will delete an entry if a typing error has occurred Pressing the Ent key directly without entering a new value after the Clr key i e if there is an empty space next to new will lead to the same result as if the value 0 had been entered The value 0 is the default setting for OTi detectors Therefore the value 0 will always appear next to new initially Version 2 1 17 EasyCheck 3000 12 4 4 Detector Setup 4 Ext Signaller AOM 3301 Pressing the key 4 in the Detector setup menu will start the search
7. press Esc or to return into the Main menu press the key Men Version 2 1 15 EasyCheck 3000 12 4 3 ATTENTION The sensitivity can only be changed if a PL detector is connected which has a higher or equal application version than 37 All other detectors or loop elements will show a corresponding fault message in the display Pressing the Esc or the Men key instead of the Ent key will cause an immediate return to the main menu and the sensitivity level remains unchanged Values can be entered from 1 5 Entries beyond this margin will not be accepted and will produce a corresponding fault message on the display Pressing the Clr key will delete an entry if a typing error has occurred pressing the Ent key directly without entering a new value after the Clr key i e if there is an empty space next to new will lead to the same result as if the value 0 had been entered which in turn leads to a corresponding fault message on the display The value 3 is the default setting for PL detectors Therefore the value 3 will always appear next to new Detector Setup 3 Change OTi Mode Pressing the key 3 in the Detector Setup menu will start the search for the connected OTi detector if still unknown the display will show the message searching address and subsequently call up the following text on the display By keying in a figure the value next to
8. than 1 second The display will show the following text accompanied by 4 tones in rising sequence if acknowledgement tones are turned on The bottom line indicates the number of the current software version and date of the EasyCheck This text remains on the display for about 5 seconds can be cut off by using any key and will be followed subsequently by the main menu Version 2 1 7 EasyCheck 3000 11 12 Switching off Switching off is also carried out by pressing key 0 keep pressed for longer than 1 second The display will the show the words switched off for about 2 seconds accompanied by 4 tones in falling sequence if acknowledgement tons are on Main menu The main menu is divided in 5 sub main menus at Version 1 11 dated 18 01 07 Display page Display page 2 ATTENTION The display examples shown above refer to a PL3300 OT detector if not noted different Version 2 1 8 aie Joo 7 detectomat 12 1 Main menu 1 Show Data Pressing the key 1 in the main menu will start the search of the address from the connected detector display text searching address subsequently the detector data will be read out display text reading data and finally the following text will be shown on the display for example Display page 1 Display page 2 Display page 3 Display page 4 On the fourth page the data is refreshed every seco
9. Esc key instead of the Ent key will cause an immediate return to the Setup menu and the AutoPowerOff time remains unchanged Pressing the Men key instead of the Ent key will cause an immediate return to the Main menu and the AutoPowerOff time remains unchanged The values 1 15 can be entered Any entries beyond this margin will not be accepted and produce a corresponding message on the display Pressing the Clr key will delete the entry if a typing error has occurred If pressing the Ent key directly without entering a value after the Clr key i e if there is an empty space next to new the value 0 is assumed and a corresponding message appears on the display Setup 2 Back light Pressing the key 2 in the menu settings will change the illumination The following text will appear on the display The entry is effected in the same way as in e g Change Address Version 2 1 21 EasyCheck 3000 The function back light is the second of three functions to save the batteries This function is used to set the time for the background light in the display in seconds Each pressing down of a key will restart the time setting if e g the time set is 20 seconds than the light will switch off 20 seconds after the last key press in order to save the batteries When the device is delivered the lighting is pre set to 0 switched off this also applies when the factory settings ha
10. If so than repeat the entry with the correct value Pressing the Ent key directly without entering a new value after the Clr key i e if there is an empty space next to new will lead to the same result as if the value 0 had been entered which leads to a corresponding message on the display cf comment 2 Version 2 1 10 Se detectomat 12 3 Main menu 3 Clone Detector Pressing the key 3 in the main menu will lead to the copy menu Here you can copy important system files from one detector to another clone detector This is very handy to swap an old loop element i e detector if to dirty against a new one without messing up the running system i e detector PL 3300 OT parameters like loop address life sign and sensitivity will be copied from a old detector to a new one The display will show the following text After inserting the source detector or loop element and pressing the Ent key the address and settings will be read out As soon as finished the following text will appear Now the new detector target can be attached After pressing Ent the loop address will be read continued with a compatible check Is everything ok than the new software will be installed on this detector or loop element and receipted with to high bleeps if acknowledgement tones are not turned off ATTENTION Copying is only possible with O T OT and OTi detectors with Appl Vers 37 or higher
11. Joo detectomat EasyCheck 3000 Manual addressing and programming tool User manual Version 2 1 Art 31482 EasyCheck 3000 detectomat GmbH An der Strusbek 5 D 22926 Ahrensburg User manual no Headquarter Hotline Phone Fax Phone Fax 53210 49 0 4102 2114 60 49 0 4102 2114 670 49 0 1805 2114 60 49 0 4102 2114 9670 0 14ct Min German network Mobile fee can vary Version 2 1 08 05 2008 Version 2 1 Pe Jod er detectomat 1 Declaration of the instruction manual 4 1 1 Purpose of the instruction manual 4 1 2 Notes of the instruction manual 4 2 General safety instructions 4 2 1 Intended application 4 3 Product Information 5 4 Keyboard 5 5 Display 5 6 Accompanying signals 5 7 Batteries 6 8 External power unit 6 9 Input jack 7 10 Switch on 7 11 Switch off 8 12 Main menu 8 12 1 Main menu 1 Show Data 9 12 2 Main menu 2 Change Address 10 12 3 Main menu 3 Clone Detector 11 12 4 Main Menu 4 Detector Setup 14 12 5 EasyCheck Setup 19 13 Further special features 26 Version 2 1 3 EasyCheck 3000 Declaration of the instruction manual 1 1 Purpose of the instruction manual This instruction manual applies to technical qualified users who are skilled for installation service and maintenance of the EasyCheck 3000 As an operator you are obliged to read and understand the instruction manual especially the section Safety This instruct
12. arried out when the device is switched on If the battery voltage is low a message will appear on the display after the device was switched on and the start text will display If the battery voltage is too low a message will appear no matter where you are in the EasyCheck after this message the device will switch off ATTENTION In this case remove the batteries from the device and exchanged them for new ones to avoid a total discharge as empty cells are prone to leaking and may damage the device Version 2 1 26
13. e Men key will result in a return to the main menu and the setting will not be changed cf leave setting The values 0 or 1 may be entered Entries beyond this margin will not be accepted and produce a corresponding message on the display Pressing the Clr key will delete the entry if a typing error has occurred Pressing the Ent key directly without entering a value after the Clr key i e if there is an empty space next to new the value 0 is assumed and the acknowledgement tones are turned off Version 2 1 24 Se detectomat 12 5 5 Setup 5 Factory Settings Pressing the key 5 in the setup menu will result in calling up the function factory setting The following text will appear on the display This function is used to restore to factory settings APO 3 minutes APO Auto Power Off Illumination 0 turned off Language English Acknowledgement tones 1 switched on Pressing the Ent key results in a confirmation so that the current setting is overwritten by the factory setting as described above Afterwards the device automatically returns to the main menu Pressing the Esc key results in interrupting the process so that the current setting remains intact Version 2 1 25 EasyCheck 3000 13 Further special features The third of the three battery protection functions is monitoring the condition of the battery battery voltage This monitoring can only be c
14. he display will show the message searching address and subsequently call up the following text on the display By keying in the figure 0 or 1 the value next to new can be changed Once the desired value is keyed in this must be confirmed by pressing the Ent key causing EasyCheck to write the new life sign into the detector To return into the Detector Setup menu press Esc or to return into the Main menu press the key Men The value can also be increased by using the T key or decreased using the 4 key Version 21 14 Se detectomat 12 4 2 Detector Setup 2 Change Sensitivity Pressing the key 2 in the Detector Setup menu will start the search for the connected detector if still unknown the display will show the message searching address and subsequently call up the following text on the display By keying in a figure the value next to new can be changed Once the desired value is keyed in it must be confirmed by pressing the Ent key causing EasyCheck 3000 to write the new sensitivity level into the detector The value can also be increased by using the T key or decreased using the 4 key In this way it is particularly easy and comfortable to change the sensitivity of several detectors up and downwards This is also the reason why you need to press Esc or Men to leave this item To return into the Detector Setup menu
15. ion manual contains all relevant information s for operation It should help you to work with the EasyCheck 3000 safely and efficiently 1 2 Notes of the instruction manual The following conventions are applied in this instruction manual e Lists with numerations apply to information and are not work steps e Numbered listings contain a sequence of steps or hierarchical ordered information e Text within quotations point to a menu selection e _ Keyboard commands are enclosed in square brackets i e CLR General safety instructions The EasyCheck 3000 meets the present state of the art and the applicable safety regulations Nerveless danger could occur from the misuse of this device e for the EasyCheck 3000 and other material assets of the operator e for the efficient use of the EasyCheck 3000 2 1 Intended application The EasyCheck 3000 is exclusively designed and produced for manual programming for all loop3000 devices For specified normal operation it is also important to e follow the safety instructions in this manual e follow the maintenance instructions in this manual detectomat GmbH is not liable for defects which occur due to incorrect usage of the EasyCheck 3000 Version 2 1 4 Pe Joo aw detectomat Product Information This device has been developed for detectors and all other loop elements in the detect 3000 series in order to provide a simple way in which to e display detector data like
16. nd and displayed Only with O T OT and OTi detectors from Appl V37 upwards Version 2 1 9 EasyCheck 3000 12 2 Main menu 2 Change Address Pressing the key 2 in the main menu will start the search for the address of the connected detector if still unknown the display will show the text searching address and subsequently indicate the following text To change the address enter the desired number Please make sure not to assign two detectors with the same address Confirm the new address with the Ent key The EasyCheck 3000 will write the new address into the detector and subsequently return to this point in the menu with the new value The value next to new can also be increased step by step with the T key or decreased with the J key The is an very comfortable way to address several detectors one after the other in increasing or decreasing sequence This is also the reason why this item of the menu can only be left with the Esc or Men key ATTENTION Pressing the Esc or the Men key instead of the Ent key will cause an immediate return to the main menu and the detector address will remain unchanged Addresses can be assigned between 1 and 126 0 or entries higher then 126 are not possible and will produce a corresponding fault message on the display Pressing the Clr key will delete an entry if a mistype has occurred and the Ent key has not been pressed yet
17. nge the language 0 gt German 1 gt English When first delivered the device is pre set to english this also applies when the factory settings have been restored ATTENTION Pressing the Esc key instead of the Ent key will result in a return to the setup menu and the language will not be changed cf leave setting Pressing the Men key instead of the Ent key will result in a return to the main menu and the language will not be changed cf leave setting The values 0 or 1 may be entered Entries beyond this margin will not be accepted and produce a corresponding message on the display Pressing the Clr key will delete the entry if a typing error has occurred Pressing the Ent key directly without entering a value after the Clr key i e if there is an empty space next to new the value 0 is assumed and consequently 0 is set German Version 2 1 23 EasyCheck 3000 12 5 4 Setup 4 Ack tones Pressing the key 4 in the EasyCheck Setup menu will call up the function to turn acknowledgement tones on and off The following text will appear on the display When first delivered the acknowledgement tones are on this also applies when the factory setting has been called up ATTENTION Pressing the Esc key instead of the Ent key will result in a return to the setting menu and the setting will not be changed cf leave setting Pressing the Esc key instead of th
18. saved until the device is switched off Version 2 1 19 EasyCheck 3000 ATTENTION Even if the term permanently saved is used in this context this does not mean that no changes can be carried out any more It is meant that all settings remain after a battery change or loss of current All settings can be changed at any time again 12 5 1 Setup 1 AutoPowerOff Pressing the key 1 in the menu Setup switches to AutoPowerOff menu The following text will be seen on the display The entry is effected in the same way as in e g Change Address The APO function AutoPowerOff is one of three functions to save the batteries The APO function causes the EasyCheck to switch off automatically after a certain pre set time in minutes in order to save the batteries The time pre set restarts after each press down of a key if e g the APO is set at 5 minutes than the device will switch off automatically 5 minutes after the last key has been pressed When the device is first delivered the APO is set at 3 minutes it also reverts back to this when the factory settings are restored The maximum AutoPowerOff time is defined to 15 minutes All other values above 15 will provide an Error Message on the display Version 2 1 20 Ye Joo Sa detectomat 12 5 2 ATTENTION If the device is externally powered the APO is disabled i e the device will not switch off automatically Pressing the
19. ve been restored ATTENTION As the background light puts a great strain to the batteries about 45mA when the light is on as against about 6mA when it is switched off the background lighting should be set to 0 switched off if possible If the device is externally powered by means of a tubular plug the switch off function for the background light is disabled The light does not switch off automatically if it is switched on Pressing the Esc key instead of the Ent key will result in a return to the Setup menu and the lighting will not be changed Pressing the Men key instead of the Ent key will result in a return to the Setup menu and the lighting will not be changed The values 0 40 can be entered Entries beyond this margin will not be accepted and produce a corresponding message on the display Pressing the Clr key will delete the entry if a typing error has occurred Pressing the Ent key directly without entering a value after the Clr key i e if there is an empty space next to new the value 0 is assumed and set light switched off Version 2 1 22 Pe Joo sie detectomat 12 5 3 Setup 3 Sprache Pressing the key 3 in the EasyCheck Setup menu will call up the function to change the language The following text will appear on the display The entry is effected in the same way as e g for change detector address This function allows to cha
Download Pdf Manuals
Related Search
Related Contents
MANUAL DE SERVIÇO Brazilian Model Systron Donner -- TL8 Sanyo 24THS32 User's Manual Manualistica Ils retrouvent du travail LG 55LA860W 55" Full HD 3D compatibility Smart TV Black Yamaha CD-S3000 Philips AK 703 User's Manual Gendarme Gendarme adjoint OPERATOR`S MANUAL MANUEL de L`UTILISATEUR MANUAL del Copyright © All rights reserved.