Home
        Page 1 of 17 TITLE: QA APPROCAL: DATE: 1. REVISION Significant
         Contents
1.       2   Common          6 4 7 5     6 4 7 6     3   Normally Closed          Wire Slot Diagram  7 6 5 4  a 2 J   7  Normally Open  6  Common  5  Normally Closed                                           6 4 7 4 2  On the respective freezer unit  label each wire attached to contact  points with the wire slot location using electrical tape or other  labeling medium and a sharpie   6 4 7 4 2 1  Wrap each piece of tape around the respective wire   6 4 7 4 3  Label the white or blue alarm point wire with the alarm point ID   6 4 7 4 4  Identify the wires on all units     Disconnecting the Freezer Alarm  6 4 7 5 1  Prior to disconnecting the alarm  ensure that the location of the alarm  wires within the alarm plug are documented as described   6 4 7 5 1 1  On the respective freezer unit  verify that each wire is  labeled legibly with the wire slot location using labels  and a sharpie  Label any wires that are not already  legibly labeled using the black sharpie and labels   6 4 7 5 2  Place a sign on the door of the unit stating    FREEZER ALARM  DISCONNECTED  Do not use for sample storage     6 4 7 5 3  Using a suitable screwdriver  loosen the screws holding the alarm  wires to the contact points on the freezer unit and remove   6 4 7 5 3 1  If the unit has an adapter  usually green  unscrew and  disconnect prior to removing the wires   6 4 7 5 4  Connect the alarm wires removed from the unit   s contact points to  close the alarm circuit using a wire nut suitable for 18 gauge w
2.  3 1  Unplug the UPS in C158B from the electrical outlet  Record time   6 6 3 2  Monitor for Notification  Record Time  Acceptable if delay is  lt 3 minutes   6 6 3 3  Reconnect to main power   6 6 3 4  Acknowledge the alarm in the alarm system   6 6 3 5  Repeat Steps 6 6 3 1 6 6 3 4 for the UPS located in C135     6 6 4  Ultra Low Freezer Alarm for C135  MS B 46  SSF Annex   and UH5030 UH5049    CTSL     6 6 4 1  Program the high alarm set point of an empty backup freezer in C135 to    85  C    6 6 4 2  Record time when unit goes into alarm    6 6 4 3  Monitor for Notification  Record Time  Acceptable if delay is  lt 20 minutes    6 6 4 4  Re set high alarm set point to  60  C    6 6 4 5  Acknowledge the alarm in the alarm system    6 6 4 6  Repeat Steps 6 6 4 1 6 6 4 5 for a unit located in MS B 46 and again for a  unit located in either UH5030 or UH5049     6 6 5  Emergency LN2 Stop  E Stop   6 6 5 1  Activate E stop   6 6 5 2  Record time   6 6 5 3  Monitor for Notification  Record Time  Acceptable if delay is  lt 3 minutes   6 6 5 4  Re activate   6 6 5 5  Acknowledge the alarm in the alarm system     6 6 6  Low Oxygen Alarm   6 6 6 1  Reset alarm set points Al Adj and A2 Adj both to 20 9  on the unit  Refer  to PointGard II Operating Manual located in the Operations Manager   s  Office for instructions on how to do this     6 6 6 2  Record time when unit goes into alarm    6 6 6 3  Monitor for Notification  Record Time  Acceptable if delay is  lt 3 minutes    6 6 6 4  R
3.  6 4 5 9  Select OK    6 4 5 10  Right click on the contact   s name        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 10 of 17    6 4 5 11  Set up each device that needs to be utilized as a notification device   6 4 5 12  Select OK once completed   6 4 5 13  Repeat for each additional device  cell phone  pager  email  etc    6 4 5 14  To edit a device right click on the device   6 4 5 15  Select properties   6 4 5 16  Make changes and select OK   6 4 5 17  Add new user to any groups that are applicable   6 4 5 17 1  Right click on group name   6 4 5 17 2  Select Add Member   6 4 5 17 3  Enter a   in the Name field   6 4 5 17 4  Select Find Now   6 4 5 17 5  Left click on the device name that needs to be added   6 4 5 17 6  Select OK   6 4 5 18  Repeat to add as many devices as needed   6 4 5 19  Restart Reno to activate modifications     6 4 6  Creating a New Escalation List  6 4 6 1  Log in as administrator or user   6 4 6 2  Right click on Escalation List  Refer to point  6 4 6 3  Select New Escalation List   6 4 6 4  Enter a name for this escalation list in the name field   6 4 6 5  Complete the Emergency box by selecting the E button   6 4 6 6  Enter a   in the Name field   6 4 6 7  Select Find Now   6 4 6 8  Left click on the device name that needs to be added   6 4 6 9  Select OK   6 4 6 10  Select OK   6 4 6 11  Right click on new escalation list name   6 4 6 12  Select insert stage   6 4 6 13  Change field Type to Contact Group   6 4 6 14  Enter 
4.  SSF Siemens Alarm Response Guide  1 Page   APPENDIX G  SSF Siemens Alarm Notification Schema  Escalation Group Design  1 Page   APPENDIX H  SSF Siemens Alarm Escalation Schema  Settings for Escalation per Alarm Type  1  Page   APPENDIX I  Siemens Alarm Console Administrators  1 Page         SF 2 4 04 SOP for Alarm Systems Management and Response    Appendix A    Page lof 1    Components of the Insight Alarm System Software Systems     1 1  Insight Advanced Workstation    1 1 1     1 1 3     1 1 4     Graphical approach to manage and control a building from an easy to use  interface    1 1 1 1  Collect  view  analyze trend information    1 1 1 2  Store and retrieve long term information       RENO  Remote Notification Option     1 1 2 1  Permits user to configure level of detail in the alarm messages sent to  each contact person    1 1 2 2  Permits user to define group notifications    1 1 2 3  Permits user to define escalation lists for notification     APOGEE GO  Remote Acknowledging Option    1 1 3 1  Allows users control and access to Insight information via the  internet    1 1 3 2  Permits users to configure who can view notification points     High Speed Trunk Interface  1 1 4 1  Interfaces the serial data line to the APOGEE GO Automation  System        SF 2 4 SOP for Alarm Systems Management and Response Form Version 02    Appendix B    Toolbar Icons and Descriptions       5  eae Alarm Issue Management  Optional    Alarm Issue Management displays  point alarm issues d
5.  expand the tree   6 4 4 5  Left click on    Services    to view the drop down list    6 4 4 6  Right click on    Insight RENOServer       6 4 4 7  Left click on restart    6 4 4 8  Wait until information box is completed     6 4 5  Creating New Staff in RENO   6 4 5 1  Log in as administrator or user     6 4 5 2  Click on the RENO icon   6 4 5 3  Right click on contacts     E RERESET       Remote Notification       CRAE E GIE EE      E Corktacts    ADS Lreeves    DUPUIR610 dFish  DUPUIR610 mitchecm  Michek celphone  Michel Emal       Contact x    CTSI SSF Gp AS  CTSI SSF Gp A4      QD CTSI SSF Gp At   E   csi SSF Gp A2    Melissa Taylor             gP CTSI SSF Escalation At saa       1  CTSI SSF Gp Al     2  CTSI SSF Gp A2     3  CTSI SSF Gp AS  e    4  Repeat   Service Providers IT Allow this Contact to call into the System   Heart Beat  gig EUN Events Message Format      Concise fedt thes Message Fornat       The Poirt Bid  Floor  LGTO1 is in Alam Pricey 3       Verbose  edt this Message Format     Nod Ste Name       6 4 5 4  Select New Contact    6 4 5 5  Enter new contact   s name and initials    6 4 5 6  If privileges to acknowledge alarms are permitted  enter a user ID and  password  Note that the ID and password MUST contain only numerical  values  If privileges are not permitted  proceed to step 6 4 5 10   6 4 5 7  Check the box next to Allow this Contact to call into the system    6 4 5 8  Select the items that should be heard when the user calls in to the system   
6.  notify SSF Director   ALARN Refer to SOP SF 2 2     ee Report to SSF and determine cause    Eley Activation Activated Refer to SOP SF 2 2  Alarm Computer an Activated Report to SSF and determine cause     Battery Power  UPS        BLN Disconnect     Disconnected   gt  10 minutes have passed  without a notification that the BLN has  been reconnected  Notification per  Section 6 3 of this SOP      Report to SSF  Confirm all equipment is within normal parameters   Restart Siemens Alarm Computer    If this is ineffective in re establishing a connection  contact the  Siemens tech on call  1 800 832 6569        Field panel data  transmission failure           Field Panel Failure   gt  10 minutes have  passed without a notification that the BLN  has been reconnected  Notification per  Section 6 3 of this SOP         Report to SSF  Confirm all equipment is within normal parameters   Restart Siemens Alarm Computer    If this is ineffective in re establishing a connection  contact the  Siemens tech on call  1 800 832 6569        Reviewed by               Not an actual alarm point  This is a notification that is sent to the alarm printer and pagers and does not require the halting of RENO  nor the  acknowledgment of the notification on the Siemens console        SF 2 4 SOP for Alarm Systems Management and Response Form Version 04    Appendix G SSF Specific Alarm Settings    Escalation    Group    Group Level 2    Group Level 3    On  Call  Tech    Actions    All SSF    Investigator  pe
7. 4 2   6 5 1 2  Select the graphics icon   6 5 1 3  Double click on the room number in the tree where the point is located   6 5 1 4  Read value on graphics display        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 15 of 17     R3 SSF ROOM C135   View Insert Dynamic Tools Window Help    els x  fmf Elala el  Bi x                 Job   DEF_IUPUIR3B1I0_ SIEMENS  B SSF ROOM MS097   3 SSF EQUIPMENT TEMP    3 SSF ROOM C160B       6 5 2  Daily  monitor the alarm system for any alarm activity    6 5 2 1  Tear off the alarm print off from the previous day  initial and date it    6 5 2 2  If there were no alarms for that day  document on a piece of alarm printer  paper that there were no alarms for that day  initial and date it  Ensure that  documentation lists all dates for which there were no alarms  i e weekend   holiday dates     6 5 2 3  If it is discovered that an alarm printout was missed a certain day  an activity  report may be ran per Section 6 5 3 to determine if there were alarms during  that time    6 5 2 4  File alarm print offs activity reports in the OOS Alarms Deviations binder  located in the Operations Manager   s office     6 5 3  Running a report for a specific alarm point    6 5 3 1  Select the System Activity Log icon    6 5 3 2  Select Query    6 5 3 3  Select Query again  then Add    6 5 3 4  Under the Find Now section  in the Type dropdown  select object    6 5 3 5  Another screen appears and then select the alarm point s   select all point
8. 6 4 3 1 2  Select Account     6 4 3 1 3  Select New     6 4 3 1 4  Select Insight Account and a pop up screen appears     6 4 3  Setting up or deactivating a user   6 4 3 1  Log in as an administrator        6 4 3 1 1  Select the user account icon     Add Insight Account    Domain usoog v Preference    User Name   Display    System Name    Name  Full Name Anderson Thomas  Language English  United States     Initials gish        Default Graphic  H Supervised Settings    I User is a Supervisor  Access Groups    Security    Control for  CONFIGURE EDIT    EDIT   Supervised Settings      all Objects       According to Access Level BACnet Command Priority    defined for Access Groups  Command Settings       Apply   Cancel   Help       6 4 3 1 5  Enter the following in the pop up screen   6 4 3 1 5 1  User name  same as the login for Outlook   6 4 3 1 5 2  Full Name   6 4 3 1 5 3  Initials     6 4 3 1 6  Leave default graphics blank     6 4 3 1 7  Under Access Groups  assign the access level for all objects as one  of the following        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 7 of 17    6 4 3 1 7 1  Read Only  for non SSF staff who wish to be   involved for remote notification purposes only    6 4 3 1 7 2  Command  non SSF staff approved by management    6 4 3 1 7 3  Configure Edit  for SSF employees      6 4 3 1 8  Under Preference   6 4 3 1 8 1  Select Name   6 4 3 1 8 2  Select the APPLY button     6 4 3 1 9  For new SSF employees only  change access lev
9. 955PM 121754PM 12   RM _EQUPALME C135 1 3957PM 121754PM 1217   RW EQUIP ALM OCIS 13957PM 121753PM 12   RW _EQUIPALME C156 BOL44AM 121752PM 12  RW1_EQUIP ALM FCI RORODAM 121752PM 12   RIM _EQUPAMG CIS R0406AM 12   RIN EQUIP ALM HC1I58 RORS7AM 121752 PM 121752 PM  RI EQUIP ALMJT158 BOO26AM 121752 PM 121752 PM             B Fad Boose BPOSsh BOvdsev  W Noms  Beep Sert  DES  TIME 5 58 40 PM       6 2 1  Acknowledge the Alarm as directed by one of the alarm notification methods or as  defined below  NOTE  Acknowledging an Alarm confirms that you are  responding per applicable SOPs        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 4 of 17    6 2 1 1  Acknowledging Alarms  APOGEE GO for Insight  from the  IUPUIR3BIO computer   6 2 1 1 1  Login per 6 4 2     6 2 1 1 2  On the Insight software  select the Alarm Status icon    6 2 1 1 3  Look under the A column for no bell    6 2 1 1 4  Absence of the bell icon indicates an alarm point that is not  acknowledged    6 2 1 1 5  Left click on the alarm point that has not been acknowledged    6 2 1 1 6  Acknowledge the alarm by selecting the bell icon on the top    6 2 1 1 7  The alarm point resets and the bell reappears under the A column     S     6 2 1 2  Call in using a telephone to acknowledge alarms    6 2 1 2 1  Dial  317  274 2741    6 2 1 2 2  Enter user id and password  Assigned in section 6 4 5 6     6 2 1 2 3  Follow prompts to listen and stop the Remote Notification   escalation  RENO     6 2 1 2 4  Once at 
10. C158B and C135  SF 2 4 04 SOP for Alarm Systems Management and Response    Page 3 of 17    5 7  Screw Driver   5 8  Sharpie   5 9  Tape  electrical   5 10  Labels for alarm lines  5 11  Wire  18 gauge   5 12  Wire Cutters    6  PROCEDURE  6 1  Management of SSF Personnel    on call    status  6 1 1  SSF Personnel are    on call    from approximately 5 30 PM to 7 00 AM on work days  and 24 hrs on days SSF personnel are not scheduled to work and as needed to provide  24 hour 7 day per week coverage  If the on call person is unable to respond it is the  responsibility of this person to notify the director or  if unable to reach the director   notify other SSF staff to arrange for alarm response to be covered     6 1 2  SSF Management manages the on call schedule  Conflicts are referred to the SSF  Director     6 1 3  On call schedules are maintained on a shared SSF calendar and current contact  information is listed in Appendix D  template     6 2  SSF Personnel response to an alarm  Either in response to a page that is received displaying the  call back number of    274 2741    or to an email phone message that is received stating that there  is a point in alarm   Refer to the figure below as a reference for the screen display for points in  alarm     Alem Vew Hep     amp  z 2      4 27  B  8           r TUTTE ra FITI TYPU  RIN _EQUIPALMF CI5 942064M 104333AM 104833AM  RAIN _EQUIPALM ACIS B88 amM 908244M 908244M  RIO1_EQUIPALMI C156 B0343AM 121759PM 12178  AWM _EQUPALM BOIS 1 3
11. Page 1 of 17    See   N D   A N A E T  5   STANDARD OPERATING PROCEDURE    Indiana CTSI Specimen Storage Facility    Clinical and Translational Sciences Institute    TITLE  SOP FOR ALARM SYSTEMS MANAGEMENT AND RESPONSE    CHAPTER  2 Facility  SOP    SF 2 4 04    SUPERSEDES SOP    N A       Issue Date     Effective Date        AUTHORED BY  DATE     Indiana CTSI SSF Director    QA APPROCAL  DATE     1     Quality Compliance Specialist    REVISION   Significant changes incorporated in this version include    1 1  Modified Signatory Approval Section   1 2  Updated applicable graphics and icons to reflect new version of Siemens Insight software   Updated Appendix B accordingly    1 3  Extensively revised Section 6 2 to clarify the procedure for acknowledging alarms and to  incorporate the remote desktop feature as an option for logging into the  UPUIR3BIO alarm  computer    1 4  Added Section 6 3 to incorporate responses to BLN  internet  disconnections and field panel  transmission failure notifications  Updated Appendices C  F  and H accordingly    1 5  Updated Section 6 4 1 to include the restart of RENO when making system modifications    1 6  Modified Section 6 4 3 1 7 in order to clarify when to use each access level    1 7  Added Section 6 4 3 1 9 for assigning access levels to Insight applications    1 8  Extensively revised Section 6 4 3 2 to reflect procedural modifications for setting up an  administrator on the  UPUIR3BIO computer    1 9  Added Section 6 4 3 4 for dire
12. SOP is modified  prepare a new version of Appendix F  indicating any changes in applicable information and noting the new SOP  version in Section 1        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 5 of 17    6 2 2 4  If unable to access alarm remotely   REPORT TO SSF TO  INVESTIGATE     6 2 3  Review the Alarm Log  automatically printed for each alarm   describe response   record date time signature for response     6 2 4  Have alarm log reviewed by SSF Management  initial date    6 2 5  File in SSF Alarm Log Binder     6 3  SSF Personnel Response to a Building Level Network  BLN  disconnection or a field panel data  transmission failure notification  In response to an immediate page that is received displaying  the call back number of       666           6 3 1  NOTE  A BLN disconnection field panel transmission failure notification WILL NOT  trigger an actual alarm  it will only send a system message that is included on the alarm  printout  Thus  when personnel are alerted  the acknowledgement of an alarm and or  the stopping of RENO  as described in Section 6 2 1  are not applicable     6 3 2  When notification is received  wait approximately 5 to 10 minutes for a possible  reconnection  A reconnection is apparent if another page is received displaying the  call back number of    0        6 3 3  Ifthe there is a reconnection within approximately 10 minutes  no action is necessary     6 3 4  If there is no reconnection in approximately 10 minutes  REPOR
13. T TO SSF TO  INVESTIGATE     6 3 4 1  Refer to Appendix F for necessary actions   6 3 5  Document response on the alarm log per 6 2 3 6 2 5     6 4  Modifying the Alarm System    6 4 1  Complete the Alarm System Change Approval Log  Appendix E   6 4 1 1  Enter the date the change request is initiated   6 4 1 2  Enter the type and details of change requested  6 4 1 3  Justify the request  6 4 1 4  Submit for Approval  6 4 1 5  Obtain approval by the SSF Director   6 4 1 6  Complete the change per the applicable section below   6 4 1 7  RESTART RENO per Section 6 4 4   6 4 1 8  Have a different SSF staff member verify that the change was made   appropriately     6 4 2  Logging into the system   6 4 2 1  As an administrator   6 4 2 1 1  Enter your IU username  defined passphrase established when you  were provided administrator privileges and log on to  IUPUIR3BI0   6 4 2 1 2  The defined passphrase is neither automatically updated with your  standard IU log in credentials nor can it be reset   6 4 2 2  As an user   6 4 2 2 1  Log onto the IU ADS logon domain using your standard IU  credentials  username and current IU passphrase    6 4 2 2 2  The passphrase updates as your IU login credentials update        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 6 of 17    6 4 2 3  Select the Insight Icon           start E       6 4 2 4  Application opens to display the alarm status screen as the default with the  toolbar  See Appendix B for toolbar icon definitions    
14. a   in the Name field   6 4 6 15  Select Find Now   6 4 6 16  Left click on the group name that needs to be added   6 4 6 17  Select OK   6 4 6 18  Repeat until escalation list is complete   6 4 6 19  Restart Reno to activate modifications     6 4 7  Installation of alarm wires  6 4 7 1  One Unit  for units located in C135 and C156 only   Clarification  This is  the most common example on how to install alarm wires for one unit   Not all freezers have been found to be successfully alarmable using this  method  Refer to freezer user manual or a professional for assistance as  needed   6 4 7 1 1  Cut one strip of wire encased in white plastic long enough to reach  from the banana clip in the wall to the contact points on the unit   6 4 7 1 2  For both cut ends of wire  perform the following   6 4 7 1 2 1  Cut off about an inch in length of the white plastic  using wire cutters  exposing the inner wires  wrapped in foil   6 4 7 1 2 1 1  Do not cut through the inner wires   6 4 7 1 2 2    Remove the foil wrap  The four inner wires       SF 2 4 04 SOP for Alarm Systems Management and Response    Page 11 of 17    wrapped in colored plastic are now visible   6 4 7 1 2 3   GENTLY remove about 1   2 inch in length of both  the red and black plastic using wire cutters   exposing the bare wires inside   6 4 7 1 2 3 1  Do not cut through the inner wires   6 4 7 1 3  Insert one end of the red wire into the red connector point on the  banana clip   6 4 7 1 4  Insert the black wire of the s
15. a computer  acknowledge the alarm via accessing the  IUPUIR3BIO computer directly  Section 6 2 1 1   remotely   Section 6 2 1 4   or by accessing the Apogee Go Web Interface   Section 6 2 1 3      6 2 1 3  Access the Apogee Go Web Interface to acknowledge alarms   6 2 1 3 1  Log into the VPN for IU using the IU passphrase and login   6 2 1 3 2  Enter the intranet website at http  Aupuir3bio insightgo  6 2 1 3 3  Enter the domain name as iupuir3bio   6 2 1 3 4  Follow steps 6 2 1 1 2 thru 6 2 1 1 7     6 2 1 4  Access the  UPUIR3BIO computer via Remote Desktop Connection to  acknowledge alarms   6 2 1 4 1  Log into the VPN for IU using the IU passphrase and login   6 2 1 4 2  Open the    Remote Desktop Connection    program located in the   START menu    6 2 1 4 3  Enter the complete name of the computer  iupuir3bio ads iu edu  6 2 1 4 4  Log in to the computer per 6 4 2   6 2 1 4 5  Acknowledge the alarm per 6 2 1 1 2 thru 6 2 1 1 7     6 2 2  Access the alarm log remotely per the Apogee Go Web interface or the Remote  Desktop Connection to the IUPUIR3BIO computer and determine if a condition  exists that requires immediate action per the applicable SOP  Appendix F   6 2 2 1  Note  Appendix F serves as a quick reference guide only  Staff should  consult applicable facility equipment OOS SOPs for further details on  response to individual alarms     6 2 2 2  Appendix F must be re verified minimally each month and when referenced  SOPs are modified     6 2 2 3  If a referenced 
16. ame end into the black connector point  on the banana clip   6 4 7 1 5  Insert the other end of the red wire into the Normally Open  NO   contact point on the unit   6 4 7 1 5 1  If the unit has an adapter  usually green   unscrew  and disconnect prior to installing the wires   6 4 7 1 6  Insert the other end of the black wire into the Common  C  contact  point of the unit   6 4 7 1 6 1  If the unit has an adapter  usually green   screw  back into unit after installing the wires   6 4 7 2  Multiple Units  a k a  Daisy Chaining  for units located in C135 and C156 only    Clarification  This is the most common example on how to install alarm  wires for multiple units sharing a common alarm point  Not all freezers have  been found to be successfully alarmable using this method  Refer to freezer  user manual or a professional for assistance as needed   6 4 7 2 1  Cut one strip of wire encased in white plastic long enough to reach  from the banana clip in the wall to the contact points on the first  unit   6 4 7 2 2  For both cut ends of wire  perform the following   6 4 7 2 2 1  Cut off about an inch in length of the white plastic  using wire cutters  exposing the inner wires  wrapped in foil   6 4 7 2 2 1 1  Do not cut through the inner wires   6 4 7 2 2 2  Remove the foil wrap  The four inner wires  wrapped in colored plastic are now visible   6 4 7 2 2 3   GENTLY remove about 1   2 inch in length of both  the red and black plastic using wire cutters   exposing the bare wires i
17. and Response Form Version 02    Appendix E Siemens Alarm System Change Approval Log Page lof 1       Year Page of    Request Description of SSF Request Request Request Change    Rationale for    Initiation Alarm Modification Modification Submitted Approved Completed   Verified  Date Requested Initials Date _Initials Date _Initials Date   Initial Date                                                 SF 2 4 SOP for Alarm Systems Management and Response Form Version 03    Appendix F SSF Siemens Alarm Response Guide    Page lof 1       SOP Verification   do not exceed 1 Month     YEAR           SF 2 1 Mechanical Refrigeration  Unit Storage Room version       SF 2 2 LN2 System and Freezer  Room Operations version       SF 3 1 Mechanical Refrigeration  Units version       SF 3 2 LN2 Freezers version       Verified By  initials and date                                                                                      Alarm Point WEL  Expected Response  Mechanical Freezer ALARM Report to SSF   Ultra Low  Refer to SOP SF  3 1 and 1 10 Appendix D   Mechanical Freezer Report to SSF   Standard  ALARM Refer to SOP SF  3 1 and 1 10 Appendix D   Refrigerator Report to SSF   ALARM Refer to SOP SF  3 1 and 1 10 Appendix D   Liquid Nitrogen Report to SSF  Freezer ALARM Refer to SOP SF  3 2 and 1 10 Appendix D   Room Temperature     celine ae if not resolved  C135 and MS B046 ALARM Refer to SOP SF 2 4   Report to SSF  manually close the main LN2 valve or press E Stop    Low Oxygen Monitor and
18. changed to     Configure Edit       6 4 3 1 9 4  Click    edit    in the toolbar at the top of the screen  and select    access levels     Change privilege to     Configure Edit    and then click    OK       6 4 3 1 9 5  Alternately  each application privilege can be  changed individually by double clicking on the       SF 2 4 04 SOP for Alarm Systems Management and Response    Page 8 of 17    application and changing the privilege     6 4 3 2  To Set up an administrator on the  UPUIR3BIO computer   6 4 3 2 1  Current administrators may perform this function by logging in  using administrator credentials  Current administrators are listed  on Appendix I   6 4 3 2 2  From the start button  select control panel  system  advanced   user profiles and settings   6 4 3 2 3  Select the    click here    hyperlink   6 4 3 2 4  Select the    Users    folder   6 4 3 2 5  Click on    Action    in the toolbar at the top of the screen  then  select    New User      6 4 3 2 6  Fill out username  full name  and leave description blank   6 4 3 2 7  Assign password and confirm   6 4 3 2 8  Uncheck the box    User must change password at next login     and check the box    Password never expires      6 4 3 2 9  Click    Create     6 4 3 2 10  Double click on the newly created member   s name and select  the    Member of    tab   6 4 3 2 11  Select    Add     Add the following profiles  Administrators   Apogee Users  Distributed COM Users  Remote Desktop Users   and Users   6 4 3 2 11 1  To sele
19. ct these profiles  select    advanced    and then     find now      6 4 3 2 12  Select OK  and then    apply      6 4 3 2 13  Remove password protect setting from account   6 4 3 2 13 1 From the start button  select control panel  display   screen saver   6 4 3 2 13 2 Uncheck the box that states     On resume  password  protect      6 4 3 2 13 3 Click    Apply    and then    OK        6 4 3 3  Deactivating a User  6 4 3 3 1  Log in as an administrator or user   6 4 3 3 2  Right click on user account name   6 4 3 3 3  Select delete account   6 4 3 3 4  Select OK     6 4 3 4  To Remove an administrator from the  UPUIR3BIO computer    6 4 3 4 1  Current administrators may perform this function by logging in  using administrator credentials  Current administrators are listed on  Appendix I    6 4 3 4 2  From the start button  select control panel  system  advanced  user  profiles and settings    6 4 3 4 3  Select the    click here    hyperlink    6 4 3 4 4  Select the    Users    folder    6 4 3 4 5  Right click on the user that is to be removed    6 4 3 4 6  Click on delete and confirm deletion     6 4 4  Restart RENO  6 4 4 1  This section must be performed by a user logged in with administrator  privileges        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 9 of 17    6 4 4 2  On the Siemens Alarm Console  right click on My Computer   6 4 4 3  From the options that appear select    Manage       6 4 4 4  Select the         next to Services and Applications to
20. ctives on how to remove an administrator from the  IUPUIR3BIO computer    1 10  Modified Sections 6 4 7 1 and 6 4 7 2 to include a disclaimer on wiring units and to specify  locations where the referred directives are applicable    1 11  Added Section 6 4 7 3 to incorporate freezer wiring directives in the additional locations of  the SSF Annex and the CTSL labs    1 12  Modified Section 6 4 7 5 to incorporate the use of signage when a unit has been unalarmed  to  remove Section 6 4 7 5 4  and to add verification directives for the dis alarming of a unit   13  Updated Section 6 4 7 6 for the addition of verification directives when re alarming a unit    14  Added Section 6 4 7 7 to provide directives for alarm function verification if a unit has been  repaired  defrosted  or moved to a new location    15  Clarify Section 6 4 8 to describe that this service is provided by a skilled Siemens technician    16  Modified Section 6 5 2 to add that  alternately  a system report may be ran to confirm the  presence or absence of alarms for any given day    1 17  Updated Section 6 6 to add annual verifications for receiving a notification if internet  connectivity is lost and if field panel transmission is interrupted  Also  updated to add testing       SF 2 4 04 SOP for Alarm Systems Management and Response    1 18     1 19     1 20    Page 2 of 17    a unit in the annex  MS B 46  and the CTSL  UH5030 or UH5049   Original directives were  modified for clarity  Appendix C updated accord
21. e set alarm points Al Adj and A2 Adj to 19 5  and 19 0   respectively    6 6 6 5  Acknowledge the alarm in the alarm system        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 17 of 17    6 6 7  LN2 Freezer Alarm  6 6 7 1  Activate the alarm test feature on an SSF LN2 unit   6 6 7 2  Record time when unit goes into alarm   6 6 7 3  Monitor for Notification  Record Time  Acceptable if delay is  lt 20 minutes   6 6 7 4  Reset the alarm on the freezer   6 6 7 5  Acknowledge the alarm in the alarm system     6 6 8  Refrigerator and standard mechanical freezer  Not Applicable  6 6 9  Room C135 Temperature  Not Applicable  6 6 10  Room MS B 46 Temperature  Not Applicable    6 6 11  Record all actions and results for Alarm testing on Appendix C and attach alarm log  printout     7  REFERENCES  7 1  ISBER Best Practices  current version   7 2  Siemens Insight Rev 3 1 1 DVD    8  DOCUMENTATION  8 1  Records are maintained per SF 1 6 Controlled Document Management SOP   8 2  All Deviations are managed per the SF 1 9 Deviation Management SOP     9  APPENDICES  The current version of each of the following appendices is used to guide and or implement this SOP   APPENDIX A  Components of the Insight Alarm System  1 Page   APPENDIX B  Toolbar icons and descriptions  1 Page   APPENDIX C  Maintenance and Function Verification Log  1 Page   APPENDIX D  SSF Alarm Call Personnel Log  Template   1 Page   APPENDIX E  Siemens Alarm System Change Approval Log  1 Page   APPENDIX F 
22. els for all Insight  applications to    Configure Edit      6 4 3 1 9 1  Single click on the new username just created  from the username list  The access levels for the  Insight applications are viewable on the bottom   right portion of the screen            Inet Account   BUN Accourt  Access Groups  Scere Otse      ADS mamaca MI Name rah  Unites States   aSa t MI Nome Erh  Unies Stites   ADSNGVG F so  ty Cet G Fac i Ergo  United Sier   ADS NGVE F ochy Pager 5   ADSNGVE Lab Coordinates Pag NGIVE Lab Coordinate  Pa NGCP Nase  ADSNGVE Lab Coordinate  Pho NGB Lab Coordinate Ph NP Name          ADSense              Corel   CTS SSF Lab Phone  Owe   Geta Somme  DPURIEIOHGH  WUPUIR EO honoch   LPR E10 vahroby   APUR Ob amen Jamra Kamen  PUR O LOW Low level user account Low  LPIA 20  marmacce Mayk Cox MLC    DPURIKIOMEDLUM Modum ievel user sccourt MED Name E  4   n Coleen Michel OSO Nowe  hy       NORAD Lab Prone MP Nome  Sener Bldg Tech SBT  Name  Semenn indst Ire s Nane  LAUR E0 mahr Tasi Run TAA Name  uw 100  Name            JOIN GURL A D  CONFIGURE ADIT  CONFIGURE EDIT  CONFIGURE EDIT  CONFIGURE ADIT  CONNGURE ADIT  CONFIGURE ADIT  CONFIGURE EDIT  CONFIGURE EDIT  CONFIGURE ADIT  CONPIGURE ADIT    CONFIGURE ADIT      Custom Butter 01  Custom Bute  NO ACCESS     For Heip  press Fi    6 4 3 1 9 2  By default  the access levels for the Insight  applications are set to    No Access       6 4 3 1 9 3  Select all applications  CTRL   left mouse click   having privileges that are to be 
23. etected in your building system     a   Alarm Issue Management Editor  AIM   Optional    Alarm Issue Management  Editor allows you to define contacts and equipment information that is used when  assigning a contact to an alarm issue     A   Alarm Status   Alarm Status displays point alarms and Building Level  Network  BLN  or Automation Level Network  ALN  messages detected in your  building system     Y   Attribute Duplicator   Attribute Duplicator allows you to copy the properties of  a point to another point or a group of points  For example  a list of analog points will  have all their enhanced alarm definitions modified     a   Commander   Commander lets you take manual control of a point and  override any pre established automatic controls for the point     g   Database Transfer   Database Transfer provides a way for you to manually  upload and download the Insight system databases between the workstation and    the field panels     NJ   Point Editor   The Point Editor is used to enter point information into the  Insight system so that the Insight software can monitor and control the equipment  connected to the point        ke   Point Group Editor   The Point Group Editor is used to organize the points in  your system  Grouping points allows you create relationships and hierarchies  among the points           E    Point Summary Report   The Point Summary Report application allows you  to create three types of printed reports containing information about the points  with
24. ification Log    Page 1l of 1                                                                                                                                                                                                                                                           Complete annually and as otherwise indicated  Year   Difference Comments   Corrective  Type of Alarm or Time Time  Minutes  posers Initials  Actions  Notification Activated   Notified our Limit P Date  must be completed if not  ia ce acceptable   BLN  internet  connectivity   lt 1 Yes O No  disconnection   Field Panel  2  data transmission  lt 1 Yes O No  failure   Field Panel  3  data transmission  lt 1 Yes O No  failure   ae oe  lt 3 0 Yes O No  a 5 Room  lt 3 Yes O No  Ultra Low  Freezer  C135  eo Mes UNS  Ultra Low  Freezer  MS B   lt  20 Yes O No  46   Ultra Low  Freezer  UH5030  lt 20 Yes O No  OR UH5049   E Stop  lt 3 Yes O No  eee  lt 3 Yes O No  LN2 Freezer  lt 20 Yes O No  Reviewed By  Date         Not an actual alarm point  This is a notification that is sent to the alarm printer and pagers and does not  require the halting of RENO  nor the acknowledgment of the notification on the Siemens console     SF 2 4 SOP for Alarm Systems Management and Response Form Version 04       Appendix D  Alarm Call Personnel Log Template Page   of 1       Name Email Page   Cell Number Other                                     Effective Date        Obsolete Date        SF 2 4 SOP for Alarm Systems Management 
25. in the field panels and devices of your Building Automation System     el   Program Editor  Optional    The Program Editor is used to create control  programs with the Powers Process Control Language  PPCL      Page 1 of 1        Dynamic Plotter  Optional    Dynamic Plotter is used to plot point values in a  continuous graph  Historical trend point values  dynamic point value changes  or a  combination of historical and dynamic values can be used to analyze and report on    point activity     8    Event Builder   The Event Builder provides a mechanism to define Zones  and Events for your building system     A    Global Commander   The Global Commander allows you to issue a single  command to be applied to a selected group of points in the building system     Bi   Graphics   Graphics allows you to create and display color graphics of your  facility and equipment for point monitoring and commanding     E   Online Documentation Screen   The Online Documentation screen allows  you navigation capabilities  global searches to the Insight Main Help files  Insight  manuals  PDF   Technical Editor e mail address  and the Siemens Web site     E   Panel Point Log Report   The Point Log Report allows you to quickly create a  Point Log Report without creating a report definition in Report Builder     E   Point Detail   Point Details is used to view information about a logical point  defined in your building system     al   Remote Notification  Optional    Remote Notification allows the In
26. ingly    Added Section 6 6 10 to incorporate the SSF Annex room temperature as an alarm point  which is not applicable to the annual verification procedure    Replaced 2008 ISBER reference with that of    current version    to eliminate the need for SOP  revision when ISBER Best Practices are updated      Appendix E modified to include year and pagination     2  PURPOSE    2l     This Standard Operating Procedure  SOP  defines the procedures used in the Indiana CTSI  Sample Storage Facility  SSF  to set the alarming and notification parameters for notifying  personnel in response to out of specification conditions detected by the Siemens alarm system  and to define the procedure to be followed by SSF personnel when an alarm notification is  received  This procedure satisfies guidance set forth in ISBER    3  PRINCIPLE    3 1     Specimen storage facilities must provide continuous monitoring of critical systems in order to  safeguard the specimens and to remain in compliance with    Best Practice    guidances  This is  accomplished in the SSF via an electronic monitoring and alarm system designed and installed  by Siemens Building Technologies  The SSF alarm system utilizes Siemens    Insight software  with a Remote Notification Option  RENO  system and an acknowledging system called  APOGEE Go  All active alarms are identified according to parameters set by SSF in the RENO  alarm management console  The RENO Alarm transmits alarm notifications for each individual  alarm tag t
27. ire   6 4 7 5 5  Confirm that the alarm wires have been removed from the unit and  connected together correctly by viewing the alarm point on the  graphics of the Siemens Alarm Console per Section 6 5 1   6 4 7 5 5 1  The value of the alarm point should read    NORMAL      6 4 7 5 6  Document that freezer was disconnected on freezer maintenance log  and or Out of Specification Form  as applicable     Reconnect to Freezer Alarm   6 4 7 6 1  Remove wire nut  separate wires and straighten each wire    6 4 7 6 2  Reinsert the numbered wires to corresponding wire slots and tighten  the screw to secure the wires        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 14 of 17    6 4 7 6 3  Reinsert alarm adapter  if applicable  and tighten the screws to secure   6 4 7 6 4  Confirm that the alarm wires have been hooked up to the unit  correctly by viewing the alarm point on the graphics of the Siemens  Console per Section 6 5 1   6 4 7 6 4 1  The value of the alarm point should read    NORMAL      6 4 7 6 5  Document that freezer was reconnected on freezer maintenance log  and or Out of Specification Form  as applicable     6 4 7 7  Test Freezer Alarm Functionality  applicable if the unit has been defrosted   repaired  or moved to another location    6 4 7 7 1  Place unit in alarm by using the alarm test function on the unit  If the  alarm test function is not available  force unit in alarm by changing  unit temperature parameters   6 4 7 7 2 _ Verify that the unit wi
28. ll send an alarm to the Siemens system by  viewing the corresponding alarm point on the graphics of the Siemens  Console per Section 6 5 1   6 4 7 7 2 1  The value should read    ALARM     Record actions on the  freezer log  or the OOS form if applicable  to document  that alarm is activated when the unit exceeds the assigned  temperature set point  If alarm does not function as  intended  report to SSF Management   6 4 7 7 2 2  If unit parameters were altered  return them to their  previous settings   6 4 7 7 2 3  Verify that the alarm point has returned to    NORMAL     status by again viewing the graphics on the Siemens  Console   6 4 7 7 3  Remove the    FREEZER ALARM DISCONNECTED    signage from  the unit   s door once alarm wires have been successfully connected  and unit has been verified to send an alarm   6 4 7 7 4   Document that freezer alarm was tested and functions within normal  parameters on the freezer maintenance log and or Out of Specification  Form  as applicable   6 4 8  Activating an alarm point  6 4 8 1  Notify Seimens representative for new alarm point activation     6 4 9  SSF Siemens Alarm Notification Schema  Escalation Groups are defined in Appendix  G    6 4 10  SSF Siemens Alarm Escalation Schema  Settings for escalation per alarm type are  defined in Appendix H  Note  alarm parameters are per applicable equipment or  facility SOP     6 5  Monitoring  6 5 1  To view alarm points for monitoring   6 5 1 1  Log in as an administrator or a user per 6 
29. nside   6 4 7 2 2 3 1  Do not cut through the inner wires   6 4 7 2 3  Insert the end of the red wire into the red connector point on the  banana clip   6 4 7 2 4  Insert the other end of the red wire into the Normally Open  NO   contact point of unit  1   6 4 7 2 4 1  If the unit has an adapter  usually green   unscrew  and disconnect prior to installing the wires   6 4 7 2 5  For attaching another unit  cut another strip of wire encased in  white plastic long enough to reach between the contact points of  the previous unit and the one that is being added  stripping the  plastic as mentioned before  this time only stripping the black  wires on each end   6 4 7 2 6  Insert the end of the black wire into the Common  C  contact point  of the previous unit   6 4 7 2 6 1  If the unit has an adapter  usually green   screw  back into unit after installing the wires        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 12 of 17    6 4 7 2 7  Insert the other end of the black wire into the Normally Open  NO   contact point of the next unit   6 4 7 2 7 1  If the unit has an adapter  usually green   screw  back into unit after installing the wires     6 4 7 2 8  Repeat steps 6 4 7 2 5 thru 6 4 7 2 7  using additional white wires   as necessary until all units are alarmed  Then proceed to next step    6 4 7 2 9  When there are no more units to add to the daisy chain  cut a final  strip of wire encased in white plastic long enough to reach in  between the contact points 
30. o specific destinations defined by the SSF  Methods for alarm notification include  electronic messaging  pagers and phones  Effective systems for maintaining specimen integrity  also require that changes are incorporated by a thoughtful  defined  and recorded procedure and  alarms are responded to appropriately and  thus  these must also be defined     4  SCOPE    4 1     The SOP applies to SSF personnel assigned to install wiring  acknowledge and respond to the  SSF alarm system notifications and  as directly communicated to via SSF Personnel  applicable  investigator personnel  The alarm set point parameters are defined in the applicable equipment  or facility SOP  Response to Out of Specification Conditions is managed through SF 1 10 SOP  for Out of Specification Response and Notification Management  Applicable alarm points for  equipment monitored by the SSF alarm and monitoring system located within or outside of the  SSF Facility include      Mechanical Refrigeration Units     Liquid Nitrogen Freezers     Low Oxygen Alarm     Room C135 and MS B046 temperature     Electronic LN2    Stop    Activation     Uninterrupted Power Supplies     BLN Network Connections     Field Panel Transmission Error    5  MATERIALS  Components of the system are further described in Appendix A        5 1  Insight Advanced Workstation Alarm System  5 2  RENO Software System  5 3  APOGEE Go Software System  5 4  High Speed Trunk Interface  5 5  Computer and related equipment  5 6  UPS in rooms 
31. of the final unit and the banana clip in  the wall  stripping only the black wires on both ends    6 4 7 2 10  Insert an end of the black wire into the Normally Open  NO   contact point of the final unit    6 4 7 2 11  Insert the other end of the black wire into the black connector point    on the banana clip  See Figure 1            Freezer 2    6 4 7 3  One unit  for units located in MS B 46  UH5030  and UH5049    6 4 7 3 1  Alarm point wires having a blue plastic casing have been pre installed  in the wall by Campus Facility Services   6 4 7 3 2  Each blue wire contains only 2 wires  encased in white and black  plastic   6 4 7 3 2 1  Strip off the blue  white  and black colored casings of  the end of the wire per 6 4 7 1 2   6 4 7 3 2 2  Attach one wire to the Normally Open  NO  and the  other to the Common  C  contact points on the unit     6 4 7 3 3  The method of    Daisy Chaining    units is not necessary in these  locations due to the fact that there were enough alarm points wires  installed for the maximum number of units that the room can hold     6 4 7 4  Labeling the wires  6 4 7 4 1  On the back of the respective unit  a diagram indicates each of the  numbered wire slots available for connections  See Figure 2 and 3 for  the most common diagrams        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 13 of 17       Wire Slot Diagram             1 2 3                                4 5 6   Indicates slots with  no specification    1   Normally Open 
32. rsonnel    Personnel per       Phone pager  Notification    On  Call  Tech  amp   Back up    Submission    E mail Form    Investigator  Personnel per  Submission       Phone pager  Notification    All SSF  Personnel    Form    Investigator  Personnel per          Phone pager  Notification       Submission  Form          Intervals for  duplicate    group  notification    15 minutes    10 minutes    30 minutes    Loop back to Group 1 and Repeat until acknowledged       Escalation    total   of  duplicate  groups       Page lof 1    Elapsed  Time  between  Escalation  Groups    30 minutes    2 hours          SF 2 4 SOP for Alarm Systems Management and Response    Form Version 02    Appendix H  SSF Siemens Alarm Escalation Schema  Settings for Escalation Per Alarm Type Page lof 1             Alarm Point Alarm Delay Notification  Mecnanitapreezer 15 minutes Per Current Version of Appendix G of this SOP   Ultra Low    a Pree 15 minutes Per Current Version of Appendix G of this SOP  Refrigerator 15 minutes Per Current Version of Appendix G of this SOP  Liquid Nitrogen Freezer 15 minutes Per Current Version of Appendix G of this SOP       Room Temperature              C 135 and MS B 46 1 hour Per Current Version of Appendix G of this SOP  Low Oxygen Monitor 1 minute Per Current Version of Appendix G of this SOP  E Stop Activation 1 minute Per Current Version of Appendix G of this SOP  Sinton pice FOWer 1 minute Per Current Version of Appendix G of this SOP    Supplies       No escala
33. s if  in response to running a report for a missed daily alarm printout      6 5 3 6  Enter the date range  maximum range is 30 days     6 5 3 7  Run report     6 6  Verification     Annual or as otherwise indicated   6 6 1  BLN  internet connectivity  disconnection notification   6 6 1 1  Unplug the internet cable from the back of the alarm computer located in  C158B        SF 2 4 04 SOP for Alarm Systems Management and Response    Page 16 of 17    6 6 1 2  Record time    6 6 1 3  Monitor for Notification  Record time  Acceptable if delay is  lt 10 minutes   6 6 1 4  Plug the internet cable back into the alarm computer    6 6 1 5  Acknowledging the alarm is not applicable     6 6 2  Field panel data transmission failure notification for both the SSF Annex  Field Panel    2  and the CTSL  Field Panel  3     6 6 2 1  Disconnect the cable labeled    Network Cable Field Panel  2    from the field  panel located in the SSF Annex  MS B 46     6 6 2 2  Record time    6 6 2 3  Monitor for Notification  Record time  Acceptable if delay is  lt 10 minutes    6 6 2 4  Reconnect the cable to the field panel    6 6 2 5  Acknowledging the alarm is not applicable    6 6 2 6  Repeat Steps 6 6 2 2 6 6 2 5 for the field panel of the CTSL  disconnecting  the cable labeled    Network Cable Field Panel  3    located in the AOC of  University Hospital  UH5033    6 6 2 6 1  Contact IU Health Security at 317 944 8000 for access to   UH5033     6 6 3  UPS  Test UPS Alarm for both C158B and C135   6 6
34. sight  system to send alarm and event information to external devices  These devices are    alphanumeric pagers  numeric pagers  phones  or e mail addresses     El   Report Builder   The Report Builder is used to configure report definitions   When you select a report type  Report Builder opens the report definition for the  report you want to create     2   Report Viewer   The Report Viewer is used to display reports on the screen   to the printer or to file     m   Scheduler  Report Scheduling Optional    Scheduler provides a way for you  to schedule events  reports  and trend collection on the Insight calendar           m   System Activity Log  Optional    The System Activity Log allows you to view  the activities  which are logged in your system     al   System Profile   System Profile gives you graphical  system wide control for  defining  configuring  and maintaining your entire building control network       Time of Day  TOD    Time of Day  TOD  is used to automatically command  points based on a daily schedule or yearly calendar       Trend Definition Editor   The Trend Definition Editor allows you to define  trend points that will show how your building control equipment is operating over a  specified time period      User Accounts   User Accounts is used to manage access and security for  the Insight software and field panels on a specified BLN or ALN     SF 2 4 SOP for Alarm Systems Management and Response Form Version 03    Appendix C  Maintenance and Function Ver
35. tion  Notification sent to alarm printer and  BLN Disconnection  No delay on call pagers only  Notification of reconnection is  sent when connection is re established        No escalation  Notification sent to alarm printer and  No delay on call pagers only  Notification of reconnection is  sent when connection is re established     Field panel data  transmission failure                     Not an actual alarm point  This is a notification sent to the alarm printer and pagers and does not  require the halting of RENO since there is no escalation schema  nor the acknowledgement of the  notification on the Siemens console        SF 2 4 SOP for Alarm Systems Management and Response Form Version 04    Appendix I  Siemens Alarm Console Administrators Page lof 1    Current Administrators for the Siemens Alarm Console       Name Position                                  Effective Date     Obsolete Date           SF 2 4 SOP for Alarm Systems Management and Response Form Version 02    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
TA_2015_web - IUT de Lens  Washing Machine User`s Manual  A-dec 機器の保守点検チェックリスト  Masking Data Introduction The Mask Toolbar The Buttons  Conceptronic Multifunctional Printer Server  O.S. ブラシレスモーター 取扱説明書 警 告 ・注 意 安全上  生鮮野菜衛生管理ガイド-生産から消費まで-(平成15年、農林水産省  梁ロボ ケガキ名人  ADINA 85 M-LINE  8RDA06-2 - リズム時計工業株式会社    Copyright © All rights reserved. 
   Failed to retrieve file