        HVAC PRO User`s Manual Appendix C: HVAC PRO Modules
         Contents
1.   0  Bias    100        Dead Dead  band   band             Bias Setpoint  50   0   50  of PB  50  of PB   Bias is active  below setpoint   50BIAS  Figure 4  50  Bias  Setpoint  Bias  100     0     100  of PB    100BIAS    Figure 5  100  Bias    SINGLE POINT CMD    The SINGLE POINT CMD maintains the min on  min off  and max  cycles attributes associated with a single Maintained or Momentary  BO     If the BO HW type is MAINTAINED  then only one BO is  commanded either On or off     If the BO HW type is MOMENTARY  then two sequentially  addressed BOs are involved  The first BO is the On point  the second  BO is the Off point  If the On point   s value is set to 1  then the On  point will be commanded On for 1 5 seconds  If the On point   s value is  set to zero  then the Off point will be commanded On for 1 5 seconds     SQUARE ROOT    STAGE DIAG    SUBTRACT    TIME COMP    Appendix C  HVAC PRO Modules 21    Output   SQRT Input     The STAGE DIAG module operates on the principal that when a piece  of equipment is activated  a measurable reaction takes place  An  example would be if a stage of electric heat is turned on  a rise in the  discharge air temperature should be detected  providing feedback that  the heat had in fact turned on  This module monitors a binary value   When the binary value turns on  the module reads and stores the  Monitored Value and starts a timer  As the timer expires  the  Monitored Value is read again and compared with the stored value     If the diff
2.  Auto Zero Duration has  expired  Each sensor is then read and the associated Al  Analog Input   offset table entry is updated so that the sensor value reads 0 005 units   The Auto Zero Duration time should be sufficient for the controlled  device to close and the control variable to reach a steady state  allow  for any input filtering      Trigger Conditions for Auto Zero   Auto Zero command forces Auto Zero to execute regardless of  conditions    Auto Zero enable must be On for the following conditions to trigger  Auto Zero    e Flow sensor goes negative as a result of drift     e Auto Zero Enable has been On for at least one hour and actual  flow is below the 1 3 Maximum Flow Setpoint     e Twenty four hours has passed since the last Auto Zero and actual  flow is below the 1 3 Maximum Flow Setpoint     Output    Input 1   Input 2         Input N    Number of Inputs    The reliability of the AVERAGE operands is evaluated so that the  average is only computed on the operands that are reliable  If all  operands are unreliable  the average is still computed with unreliable  values and the result is also flagged as unreliable     The BINARY UPDATE module causes the binary inputs to read into  memory which can be referenced by other logic modules  If the BI   Binary Input  is overridden  the override value will be read into  memory instead of the actual hardware input value     First BO   1   First BO  First BO   2   First BO       First BO   N   First BO    Each BO  Binary Outp
3.  Proportional Band  Deadband    Integration Gain Time  Bias    Pterm  Iterm  Output    Definition   Process variable   The target value for the input controller  Defined in the same units as the Input    The area around the setpoint where no output change  is required    Integral time  defined in units of tics  where 1 5 seconds  equals one tic    A user defined value   See following paragraph for  definition      The part of the output due to the proportional Error  The part of the output due to integration  The command value to the controlled device    The following table illustrates how the output of the PI controller is    calculated     Table 6  Pl Output    Procedure  Pterm   100    Err PBand    Description  Calculate proportional part    Output   Pterm   Iterm   Bias Add proportional part  last Iterm  and Bias    If  Output  gt  100    Output   100    Else If  Output  lt  0    Output   0    If  IT  gt  0     Limit the Output at 100     Limit the Output at 0     If the User defined Integral time is  gt  O    Iterm   Last Iterm   Pterm IT Calculate the next Iterm    The Bias is a user defined parameter and is normally defaulted to zero   The Bias is the value that the output should be at if proportional only  control is selected and the input is at the setpoint  The value used for  Bias will depend on the application  The following graphs show a bias  of 0   30   60   and 100      20 Appendix    100     Dead  band    100  of PB  Bias  0        Setpoint  OBIAS    Figure 3
4. BI UPDATE  BO HW MUX  BO SW MUX  IF SKIP  OS RESET    6 Appendix       ABS VALUE    ADD    AND    AUTO ZERO    IF  Input  gt   0     Output   Input    ELSE    Output     Input    Output   Input 1   Input 2    ANALOG OUTPUT    The ANALOG OUTPUT module causes the Analog Output  AO   values to be converted from 0  to 100  into 0 counts to 255 counts     IF  Input 1   1  AND  Input 2   1     Output   1  ELSE  Output   0    The AUTO ZERO module becomes activated under the following    conditions     Table 3  Auto Zero    Condition   Input   Sensor Count  Sensor Input 1 2   N  Auto Zero Command    Auto Zero Enable  Actual Flow   Max Flow   Min Flow   Auto Zero Duration    Output  Auto Zero Status    Function    Defines number of sensors to be auto zeroed   Inputs from sensors    An N2 or Zone Bus command that activates the Auto Zero  command without delay     Allows Auto Zero to execute conditionally   Calculated flow from sensor   Maximum design flow   Minimum design flow    Time required for full travel of the actuator plus some  additional time to ensure positive shutoff     Indicates Auto Zero is active  used by other modules for  initiating auto zero commands     AVERAGE    Bl UPDATE    BIN COMMAND    Appendix C  HVAC PRO Modules 7    Once activated  the AUTO ZERO module sets the Auto Zero Status to  On for the Auto Zero Duration  Other modules may use the Auto Zero  status to turn off an output and command an actuator to zero percent   The flow is presumed to be zero when the
5. ENS 16  A O O 17  A A ane 17  SINGLE Plica 17  SINGLE POINT CMD aria A taa 20  SQUARE ROQ T                                               21  gp czib ct                                                            21  SUB Ti Tio 21  TIME COMP M                    e cents nsnene lacs SN ones 21  is CIP PU O O E eine o OP o REO se        22      Indicates those sections where changes occurred since the last printing     Appendix C  HVAC PRO Modules 3    HVAC PRO Modules    Introduction    HVAC PRO    applications are composed of the modules listed in this  document  The basic function of each block is described  including  how the outputs of the block are related to the inputs     4 Appendix       Key Concepts    Table 1 and Table 2 list the modules included in this section   Descriptions of each module follow     Table 1  Basic Modules    Module Category  Math    Logical    Compare    Calculations    Multiplex    Miscellaneous    Module Name  ADD   DIVIDE  MULTIPLY  SUBTRACT  AND   NOT   OR   XOR  COMPARE  NEG COMPARE  TIME COMPARE  AVERAGE   MAX SELECT  MIN SELECT  BINARY MUX  FAILSOFT   MUX   ABS VALUE  FLT TO INT  SQUARE ROOT    Appendix C  HVAC PRO Modules 5       Table 2  Complex Modules    Module Category Module Name  Direct Slot Outputs AUTO ZERO  BIN COMMAND  BO SEQUENCE  FAST BO  HEATPUMP  INCR W FB  INCR WO FB  SINGLE POINT CMD  STAGE DIAG  Time Based Modules DELAY  DERIVATIVE  HTG CLG PI  SINGLE PI  Calculations CFM CALC  ENTHALPY  RAMP  RESET  OS Modules ANALOG OUT  
6. FANS 637 5  1637 5  Appendix Section    AS ta Issue Date 0400  CONTRSLS    APPLICATION NOTE    Appendix C  HVAC PRO Modules       HVAC PRO Modules sosi iio terio ito iicos 3  INTO AU CIO ee SAM I AUN ne   3  Key CONCCDIS 1D AA AA EA AA er tir far tnt dei dent rs nes dress  s  4  ABS VALUE rta A eke i Pe as aa oo 6  PDD  eos ec A LM oa Dedo e ease 6  ANALOG OUTPUT ita a A SG ea 6  AND aves fo setae eta  etie o Shaw  Sh wana ets 6  AUTO ZERO isa stow P PEE 6  AVERAGE eo 7  BLUPDATE  cotos feaceniseuentnsesceniadvceels da rates ann rendent Raid 7  BIN COMNIAND  corr A A EA EA res c   7  INSECTS 8  BON MUX  emp a Sea Ec MP 8  eRlilelIezm                                                                        8  BOS WI TN  Seca            eee 9  CEM CADO ido 9  COMPARE sat 9  DELLA Vota A Sane AAA A A A Pace Gown BS 9  DERIVATIVE  coto ta dios 10  DIVID   02 a A E PE a A Ne AS 10  ENTHALP Y EEE EE EA ad 11  FAILSOF Tira A aes ERA 11  FAST  BO EU ER EE 12      Indicates those sections where changes occurred since the last printing        2000 Johnson Controls  Inc  www johnsoncontrols com  Code No  LIT 6375190    2    Appendix  A A 12  HEATPUMP E E E E 12  TO OO a EE E E T 13  IF SKIP ERREUR 14  INCR W PB ta 14  INCR WO M 15  MAX SELEC Ta AA A ot 15  A H  n 15  UBI 15  MUX err pna a REE EE EA E EN AEAEE RE OAD EREE 16  NEG COMPARE asian anti 16  e P              one    e 16  COT                                                                          16  DS DESEE  ni IINE E NNI EMIN
7. d pass through the program     IF  On BO not equal to Last Commanded State   Last Commanded State   On BO  IF  On BO   1   Pulse the On BO  ELSE  Pulse the Off BO    This module converts a floating point value to an integer value with a  range of 0 to 32767  Values are truncated if necessary     The HEATPUMP module controls a Heat Pump based on the Heating  Command and Cooling Command generated by other logic  i e   the  HTG CLG PI module  A heat pump achieves heating or cooling with a  single compressor and a reversing valve     The HEATPUMP module maintains the min on  min off  and max  cycles attributes associated with the Compressor BO and the  Reversing Valve BO  Each slot number provided in the HEATPUMP  module points to a Compressor Reversing Valve BO pair  The module  allows the Number of Compressors to be specified  This value is  usually set to 1 or 2     The mode of the HEATPUMP is set to cooling when the Cooling  Command is non zero and the Heating Command is zero  The mode is  set to heating when the Heating Command is non zero and the Cooling  Command is zero     A critical module performed by HEATPUMP is control of the  Reversing Valve  When switching from Heating Mode to Cooling  Mode  the compressors must be off long enough for the refrigerant to  settle before switching the flow with the Reversing Valve BO  The  Reversing Valve Delay provides the number of 1 5 second tics to wait  after the compressors have been turned off before commanding the  Reversing Va
8. e for the input is 6 seconds   The PID output is then calculated as   Output   Single PI Output   D Term    Note    The DERIVATIVE module does not accept an input   setpoint  and deadband like the SINGLE PI module does   The Error now must be calculated with separate logic using  the SUBTRACT module     Output   Input 1   Input 2    ENTHALPY    FAILSOFT    Appendix C  HVAC PRO Modules 11    T   Temperature   RH   Relative Humidity  Units   1  Metric    Units   0  English     IF  units   1  METRIC     Kcal Kg    S1   0 000416  T    0 00227 T    0 323 T   3 77  Enthalpy   0 1   S1   0 0597 RH   0 24 T    IF  units     0   IF  temperature    70 0  ENGLISH low temps   btu Ib    ELSE    S1    0 071   S2   0 241  T   S3   0 000071 T    0 0043 T   0 12   S4   0 000003 T   0 00011   Enthalpy   S1   S2   S3 RH   S4 RH   ENGLISH hi temps      btu lb   S1   0 0   S2   0 2399 T   S3   0 000107 T    0 00927 T   0 293   S4   0 000005 T   0 0003   Enthalpy   S1   S2   S3 RH   S4 RH     IF Status input OR Controlled input are unreliable    ELSE    Failsoft Output   Failsoft Value    Failsoft Output   Controlled Input Value    12 Appendix    FAST BO    FLT TO INT    HEATPUMP    The FAST BO module provides control for two Momentary BOs  having consecutive addresses  The first BO is pulsed for   50 milliseconds for On operation  The second BO is pulsed for  50 milliseconds for Off operation     The Last Commanded State is saved to prevent the FAST BO from  pulsing the desired BO every 1 5 secon
9. erence is less than the Delta  the stage is not working  correctly and the Alarm is activated  If the difference is greater than  the Delta  the Alarm is deactivated     WHEN  Monitored BO TURNS ON   INITIAL VALUE   Monitored Value  WHEN  Timeout tics have passed   IF ABS INITIAL Value   Monitored Value   lt  Delta  Alarm   1  ELSE  Alarm   0    Output   Input 1   Input 2    IF  Actual Time  gt   Start Time  AND  Actual Time  lt  Stop Time   Output   1   ELSE  Output   0    When the Actual Time is in between the Start Time and the Stop Time   the output is 1  Valid values are 00 00 to 23 59  The output is 1 if the  Start Time and Stop Time are equal     22 Appendix    XOR  IF  Input 1   Input 2   Output   0  ELSE  Output   1    Appendix C  HVAC PRO Modules 23    Notes    24 Appendix       Notes  JeHNSON  CONTRSLS  Controls Group  507 E  Michigan Street www johnsoncontrols com  P O  Box 423 Release 8 0    Milwaukee  WI 53201 Printed in U S A     
10. irection from drive open to drive close  both BOs  will be commanded Off for 1 5 seconds  A Failsoft feature allows the  INCR W FB to drive the BOs to a desired state when the Setpoint   Feedback or Deadband becomes unreliable  When the Failsoft  command is 1  the Close BO is commanded On  otherwise the Open  BO is commanded On     The INCR W FB also allows Full Open and Full Close override  commands  If the Full Open value is 1  the Open BO will be  commanded On  If the Full Close value is 1  the Close BO will be  commanded On  If both Full Open and Full Close are 1  the output is  determined by the Failsoft command     INCR WO FB    MAX SELECT    MIN SELECT    MULTIPLY    Appendix C  HVAC PRO Modules 15    The difference between INCR WO FB and INCR W FB is that the  INCR WO FB calculates its own feedback signal based on the stroke  time of the actuator  For example  with a stroke time of 100 tics  the  INCR WO FB would drive the Open BO for 40 tics  60 seconds  to  achieve a setpoint of 40  after restart with a deadband of zero  If the  setpoint changed to 50   the INCR WO FB would drive the Open BO  for only 10 tics  15 seconds      Since the INCR WO FB calculates its own feedback the actual  position needs to be synchronized upon controller reset  A restart  variable is commanded to zero upon controller reset  The INCR WO  FB then commands the output to the Failsoft command for the number  of tics found in Stroke Time  For example  if stroke time was 100 tics  and the Fai
11. lsoft command was 0  the INCR WO FB would command  the Open BO for 100 tics  150 seconds   During this time  the restart  value is set to 1  When the calibration is complete  the restart value is  set to 2     UNT VAV  Variable Air Volume  firmware Revision D02 or later  or  AHU firmware revision C06 or later employs logic that overdrives the  incremental actuator 1 5 times its stroke time when the command  equals 0  or 100      All other features operate the same as in the INCR W FB     This module selects the maximum value from a list of N input values   If all inputs are unreliable  then it selects the maximum of the  unreliable data  If at least one value is reliable  the maximum value is  selected from only the reliable inputs     This module selects the minimum value from a list of N input values   If all inputs are unreliable  then it selects the minimum of the  unreliable data  If at least one value is reliable  the minimum value is  selected from the reliable points     Output   Input 1   Input 2    16 Appendix    MUX  IF Selector   1  Output Value   Input 1 Value  Output Reliability   Input 1 Reliability  ELSE  Output Value   Input 2 Value  Output Reliability   Input 2 Reliability    NEG COMPARE  IF  Input 1  lt  Input 2   Output   1  IF  Input 1  gt   Input 2   Differential    Output   0    NOT  IF  Input 1   1   Output   0  ELSE  Output   1    OR  IF  Input 1   1  OR  Input 2   1   Output   1  ELSE  Output   0    OS RESET    The OS RESET module causes the executio
12. lve BO  The Reversing Valve Cmd tells the module how  to command the Reversing Valve BO to switch to the correct mode     HTG CLG PI    Appendix C  HVAC PRO Modules 13    The HEATPUMP module determines the percentage of Heating  Command or Cooling Command at which to turn on each compressor  by dividing 100  by the Number of Compressors  A Vernier similar  to the BO SEQUENCE module is calculated internally to determine  the duty cycle of each compressor  For example  with two compressors  defined and the Cooling Command at 40   the first compressor would  be on 80  of the time and Compressor 2 would be off  When the  Cooling command is above 50   Compressor 1 is on continuously and  Compressor 2 is cycled     The duty cycle of each compressor is usually altered internally to  maintain the correct min on  min off  and max cycles defined in the  BO database record  The Cycles per Hour value supplied to the  HEATPUMP module is also recalculated internally to maintain these  delays     For an explanation of the terminology involved with the PI module   such Proportional Band  Integration Time  and Offset  see the Single  PI Module description     The HTG CLG PI combines heating and cooling PI loops into a single  module     The SINGLE PI module is invoked with the combined Cooling and  Economizer variables  The Cooling Sensor and Cooling Setpoint from  the HTG CLG PI are passed directly to the SINGLE PI module  The  Cooling proportional band and the Economizer proportional band a
13. n of the logic modules to  start over at the first module after a 1 5 second delay  This is always  the last module loaded     RAMP    RESET    SINGLE Pl    Appendix C  HVAC PRO Modules 17    The RAMP module allows an output point to track an input point in  incremental steps over time  A fast and slow step size are allowed   When the output is near zero  the Slow Step size is used to increment  the output every 1 5 seconds until it reaches the input  During the time  the Slow Step is being used  the Step Flag will be set to 1  When the  output becomes greater or equal to the input  the Fast Step increment is  used and the Step Flag is set to zero     Anytime the difference between the input and the output is less than  the current step size  the output will be set exactly equal to the input     Anytime the output gets near zero  below 0 001   the step size will  change back to the slow step size  Disable the slow step feature by  making the Fast Step equal to the Slow Step  The reliability of the  output is based on the reliability of the input and any math errors that  may occur when incrementing the output value     Output     Input   Input Setpoint      Output Prop Band Input Prop Band      Output Setpoint    The output is limited to the output setpoint when the input falls below  the input setpoint  Likewise  the output is limited to the end of the  output proportional band when the input goes above the input  proportional band     The reliability of the output is based 
14. o On occurs  the internal On counter is reset  to zero  Every 1 5 second tic  the On counter is incremented until it  reaches the Delay On value  Note that the On counter will reset to zero  if the input drops back to off  This means that the output will not be  commanded On unless the input has been on    continuously    for Delay  On tics     10 Appendix    DERIVATIVE    DIVIDE    When the input transition to off occurs  the internal Off counter is reset  to zero  Every 1 5 second tic  the Off counter is incremented until is  reaches the Delay Off value  Note that the Off counter will reset to  zero if the input jumps back to on  This means that the output will not  be commanded Off unless the input has been off    continuously    for  Delay Off tics     The DERIVATIVE module combines the output from a SINGLE PI  module with a derivative term  which is proportional to the change in  Error over time     The SINGLE PI module defined Error  Proportional Term  P Term    Integral Term  I Term  as     Error   Input   Setpoint   P Term     100     Error   Prop Band      I Term    P Term   Integral Gain    Last I Term  PI Output   P Term   I Term    The DERIVATIVE module defines the Delta Error and Derivative  Term  D Term as     Delta Error   Error Now   Error Last Time    D Term    100     Delta Error   Prop Band         Factor    Derivative Gain  Delta Time     Delta Time   6 0  This is the actual run time of 1 5 seconds times the  default filter of 4      The default sample rat
15. on the reliability of the input and  any math errors that may occur when incrementing the output value     The SINGLE PI module provides closed loop control  The PI stands  for Proportional and Integral  The proportional control is achieved by  calculating the difference between the input and the desired setpoint  If  the difference is greater than the deadband  the output is commanded  to a value  which is proportional to the difference divided by the  proportional band     With Proportional Only  the output would increase up to 100  as the  input moved from the edge of the deadband up to the width of the  proportional band     In other words  when the Error  which is equal to the Input minus the  Setpoint  see Table 4   is equal to the Proportional Band  the Pterm  output is equal to 100      Proportional Only control causes an instantaneous response in the  output based on the change in ERROR     18    Appendix    With Proportional Only control  the controlled variable will never be  equal to the setpoint as a result of the device being manipulated by the  controller  By definition  when ERROR is equal to zero  the control  output will equal zero  or some other arbitrarily chosen offset value   Thus  some ERROR must persist in order to hold a non zero output   and continue to remain in control  A properly tuned P only loop will  eventually find equilibrium with some error from setpoint  termed  proportional offset     Integration is used to eliminate the proportional offse
16. re  combined before passing to the SINGLE PI  The output from the  SINGLE PI is used to calculate the Cooling output and the  Economizer output     The SINGLE PI module is invoked with the combined Heating and  Preheat variables  If the Cooling Sensor and Heating Sensor are the  same  then the integral terms are adjusted to provide correct operation   If the Heating Deadband is non zero then the Heating Setpoint is  calculated as an offset from the Cooling Setpoint  otherwise the  Heating Setpoint is passed on directly to the SINGLE PI module     The Heating proportional band and the Preheat proportional band are  combined before passing to the SINGLE PI  The output from the  SINGLE PI is used to calculate the Heating output and the Preheat  output     14 Appendix    Heating Preheat Economizer Cooling    100 0      Output  Command    0 0         Htg  Econ Prop Band   Clg Prop Band    Heating Prop Band   Preheat Prop Band   Deadband    Clg      Deadband  Htg Setpoint Clg Setpoint    HTGCLGPI    Figure 1  HTG CLG PI Module    IF SKIP  IF  Input 1   1     SKIP the next logic module function     INCR W FB    The INCR W FB module  INCREMENTAL WITH FEEDBACK  is a  simple control loop that monitors the offset between a Setpoint AO  and a calculated feedback signal  The output drives an incremental  actuator  which consists of an Open BO and a Close BO     IF  Setpoint   Feedback  gt  Deadband     Open BO   On  IF  Feedback   Setpoint  gt  Deadband   Close BO   On    When switching d
17. st stage can also be enabled  When all of the BOs  have been turned off  the first stage is recalculated to be the next stage   each time up to the last stage and then beginning again at the original  first stage  Rotation is not allowed when Vernier is enabled     The BO Sequencer maintains the interstage delays  min on  min off   max cycles attributes associated with each BO stage     An Instant OFF feature can be enabled with UNT  Unitary  firmware  Revisions B00 or higher  or AHU  Air Handling Unit  firmware  Revisions C06 or higher  All of the BO stages are turned off and the  Vernier is set to zero when the Instant Off command is turned on     BO SW MUX    CFM CALC    COMPARE    DELAY    Appendix C  HVAC PRO Modules 9    The BO SW MUX module combines the binary output values  generated by other logic modules with the Overrides received from  N2 or Zone Bus  The value received in the override has priority over  the values generated by other logic modules     Note that this module does not have any effect on the modules that  reference BO slots directly as listed below     e BIN COMMAND  e BO SEQUENCE    e FASTB  e HEAT PUMP  e INCR W FB    e INCR WO FB  e SINGLE POINT CMD    Velocity   4005   SQRT  Air Pressure K constant   CFM   Velocity   Duct Area    IF  Input 1  gt  Input 2     Output   1  IF  Input 1  lt   Input 2   Differential    Output   0    IF  Input is ON  for Delay On    Output   On  IF  Input is OFF  for Delay Off  Output   Off    When the input transition t
18. t inherent with  Proportional Only control  By taking the sum of the error over time  and adjusting the output proportionally  the output can increase or  decrease to overcome the proportional offset  Assuming the ERROR  remains constant  the Integration time  TI  is the time it takes the  Integral term to contribute an amount to the total PI output equal to the  Proportional term     The selection of the Integration time requires a knowledge of the time  it takes for the process variable to respond to the controlled device  If  too large a value is chosen  the loop will react very slowly  making it  look like Proportional Only  If too small a value is chosen  the loop  will react too quickly  making it unstable  resulting in cycling        Error             Iterm Output                  z Integral    PI Output Pterm Output                     CONSTERR    Figure 2  Response of PI Module to a Constant Error  Calculate Error   ERROR   Input   Setpoint    Determine if the error is below the deadband  above the deadband  or  within the deadband     Table 4  Single Pl    ERROR  If  ERROR  lt   Deadband     Appendix C  HVAC PRO Modules 19       Explanation  If the Al is below the setpoint by more    ERROR   ERROR   Deadband than the deadband   Else If  ERROR  gt  Deadband  If the Al is above the setpoint by more  ERROR   ERROR   Deadband  than the deadband   Else Otherwise the Al is within the    ERROR   0 0    deadband     Table 5  Single Pl Terminology    Term   Input   Setpoint 
19. ut  is commanded to the value of the first BO   The BINCOMMAND maintains the interstage delays  min on   min off  and max cycles attributes associated with each BO     8 Appendix    BINARY MUX  IF Selector   1  Output   Input 1  ELSE  Output   Input 2    BO HW MUX    The BO HW MUX module causes the binary output values to be made  available to the hardware driver firmware  The BO HW MUX module  is tied directly to the hardware output     BO SEQUENCE    The BO SEQUENCE monitors an analog output to control several  stages of BOs     The interstage spacing is calculated by dividing 100  by the number  of stages  The first stage may be specified and may be different from  the other evenly spaced stages  For instance  with four stages total  the  interstage spacing would be every 25   The first stage may be moved  from 25  to a different value like 10   Note the first stage percent  may not be specified when Vernier is enabled     Vernier output can be enabled  When the Vernier is enabled  the  interstage spacing is calculated as if one extra stage was present    For instance  with four stages total  the interstage spacing with Vernier  is 20   The Vernier is set to zero when a stage is turned on  and ramps  up to 100  just before the next stage is turned on  With four stages  and the Monitored AO at 70   the first three stages would come on at  20   40   and 60   The Vernier would be at 50  since it is half way  to the next stage  which will come on at 80      Rotation of the fir
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Guía rápida  Snapper E11305 User's Manual  McAllen Software User Manual  Avocent Cyclades-PR4000 Home Theater Server User Manual  SIMULACIÓN NUMÉRICA DE FLUJO  Toshiba XD2000 2,000 ANSI Lumens/XGA 1,024x768 pixels/2.5 kg  Samsung Lavatrice WF1802XEC User Manual  iDataFax Troubleshooting  Cenni problematiche sicurezza macchine utensili  NewAge Products 36172 Instructions / Assembly    Copyright © All rights reserved. 