Phoenix Contact 2736107 datasheet: pdf
Contents
1. DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A 4 2 Pin assignment of the power supply ULs E R D 6625A005 Figure 4 Pin assignment of the power supply U gt 4 3 Pin assignment of the power supply U of the outputs at A mm N l p Uar 24 V Unt 24 V S Us12 GND Unyo GND C 4 Uns GND Uns GND x os Unio 24 V Unio 24 V if f 6625A005 Figure 5 Pin assignment of the power supply U4 of the outputs 4 4 Pin assignment of the inputs and outputs Female input Female output _ Pe Temeer eomedtr Us 24 V Bf 6625A006 Figure 6 Pin assignment of the inputs and outputs 4 5 Assignment of the female input connectors NOTE Internal Two input signals can be connected to each J female input connector If both inputs of a female connector are used the other female connector must not be used 1 or 2 and 3 or 4 see Figure 7 L L 24 V Female connector 1 lt Female connector 2 Female connector 3 lt Female connector 4 Figure 7 Assignment of the female input connectors 6631_en_03 PHOENIX CONTACT 9 5 Local diagnostic and status indicators PB DIO 4 4 RJERCNIX 6631B003 Figure 8 Indicators and rotary encoding switches of the FLS PB M12 DIO 4 4 M12 2A Rotary en
2. OTE Ensure degree of protection To ensure IP65 IP67 protection cover unused female connectors with protective caps NOTE Avoid damage to the electronics Only supply the sensors with the voltage Us provided at the terminal points NOTE Avoid polarity reversal Avoid polarity reversal of the supply voltages U Us and U in order to prevent damage to the device NOTE Observe connection assignment Oo 000 0 When connecting the sensors and actuators observe the assignment of the connections to the PROFIBUS input and output data see Process data on page 14 6631_en_03 PHOENIX CONTACT 13 THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A 10 Process data 10 1 Assignment of the terminal points to the IN process data Byte bit view Byte 0 ee eee Bt o A a ce 1 0 Device npt ST 0 0 0o o 4 j 3s 2 1 A For bits 0 4 to 0 7 of the inputs the value is 0 10 2 Assignment of the terminal points to the OUT process data Bye Bid view et 7 6 i s 4 i 3s 2 14 0 Device oa x x gt x x i s 2 a The assignment of bits 0 4 to 0 7 of the outputs has no effect on the output state 11 Diagnostic data 11 1 Mapping of diagnostic data in PROFIBUS Diagnostic data Bit7 Bit Bits Bt4 Bt3 Bt2 Bitt Bto Remark seo x x x x x xX x x Statinstaust Byer x x x x x x x x Stationstatus X X swz x
3. THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A Fieldline Stand Alone device for PROFIBUS DP with four digital inputs and four digital outputs AUTOMATION Data sheet 6631 en_03 PHOENIX CONTACT 01 2009 1 Description This device is used to acquire and output digital signals Features Connection to PROFIBUS DP using M12 connectors B encoded Baud rate with up to 12 Mbaud autobaud Connection of digital sensors using M12 connectors Connection of digital actuators using M12 connectors each with a load capacity of 2 A nominal current Flexible power supply concept Diagnostic and status indicators Short circuit and overload protection of the outputs and sensor supply IP 65 IP 67 protection Make sure you always use the latest documentation It can be downloaded at www phoenixcontact com This data sheet is only valid in association with the FLS FLM SYS INST UM E and FLS FLM PB SYS PRO UME user manuals DO GD OO GD GD OGD OO OD Lconrac GDC INSPIRING INNOVATIONS THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A 2 Ordering data Products Description Type Order No Pcs PKt Fieldline Stand Alone device for PROFIBUS FLS PB M12 DIO 4 4 M12 2A 2736107 1 with four digital inputs and four digital outputs Accessories Description Type Order No Pcs PKt Protectiv
4. al inputs sensor supply 500 V AC 50 Hz 1 min FE digital outputs actuator supply 500 V AC 50 Hz 1 min Digital outputs actuator supply digital outputs actuator supply 500 V AC 50 Hz 1 min Approvals For the latest approvals please visit www download phoenixcontact com or eshop phoenixcontact com 6631_en_03 PHOENIX CONTACT T 4 Pin assignment 6631B002 Connections of the FLS PB M12 DIO 4 4 M12 2A Figure 2 4 1 Pin assignment of the PROFIBUS connection GH BUS IN OUT Cig 6625A004 Figure 3 PROFIBUS pin assignment M12 B encoded 6631_en_03 onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A Designation Meaning Oo FE Functional earth ground PROFIBUS IN BUS OUT PROFIBUS OUT Uis IN Power supply IN logic and sensors Us OUT Power supply OUT logic and sensors for additional devices INT to IN4 inputs 1104 OUT1 to Outputs 1 to 4 OUT4 Power supply IN of the outputs OUT1 to OUT4 with voltages U41411 and Unyo U OUT Power supply OUT for additional devices VP RxD TxD N A DGND RxD TXxD N A DGND ze rr ee ae RxD TxD P B RxD TxD P B Shield Shield a The thread is used for additional shielding PHOENIX CONTACT 8 onlinecomponents com THE ONLINE
5. coding switches The station address is set using rotary encoding switches X10 for tens and X1 for units The PROFIBUS master addresses the device by means of this station address a The valid value range is between 1 and 99 A new address value is only applied on device power up 6631_en_03 onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A PHOENIX CONTACT 10 THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A Designation Color Meaning OOOO U y O neo LED Bus error bus failure No cyclic data transmission PROFIBUS not connected master not active Incorrect settings configuration via master station address Synchronization or parameterization running Timeout elapsed Device is addressed by PROFIBUS and is in the cyclic process data exchange state Device supply not present In this state the UL LED is also off due to the missing 24 V communications power Green LED Communications power Communications power present OFF Communications power too low ea LED Power supply for IN1 to IN4 ON red red Power supply overloaded ont a Power supply present OFF Power supply too low C Sa indicators for the inputs S active OFF input not active Status indicators for the outputs See 50 active OFF Output not active Overload of outputs aam overloaded OFF Output not overloaded Power suppl
6. e caps for unused female connectors PROT M12 1680539 5 Protective caps for unused male connectors PROT M12 FS 1513596 5 5 pos shielded female connector M12 B encoded SACC M12FSB 5CON PG9 SH AU 1507777 1 for the incoming remote bus 5 pos shielded male connector M12 B encoded SACC M12MSB 5CON PG9 SH AU 1507764 1 for the outgoing remote bus PROFIBUS M12 T piece 12 Mbaud SAC M12T 2XM12 PB DP 1507780 1 PROFIBUS M12 termination resistor SAC 5P M12MS PB TR 1507803 1 Marking labels ZBF 12 UNBEDRUCKT 0809735 10 For additional accessories for connecting the sensors and actuators please refer to the Phoenix Contact PLUSCON catalog Documentation Description Type Order No Pcs Pkt Installation of devices in the Fieldline product range user manual FLS FLM SYS INST UME Configuring a PROFIBUS system using devices in the FLS FLM PB SYS PRO UME Fieldline product range user manual 3 Technical data 178 mm E ole N 2 ps aE oO HANI 5 168 mm 168 mm 6631C011 Figure 1 Dimensions of the device 6631_en_03 PHOENIX CONTACT 2 General data Order designation Order No Housing dimensions width x height x depth Weight Operating mode Connection method for sensors Connection method for actuators Permissible temperature operation Permissible temperature storage t
7. hom per channel 2A Total current 8 A observe derating Possible output current during short circuit 22 A maximum for 300 us a Please take this value into account when selecting the power supply unit Protection Short circuit overload a Single chip structure i e all channels are thermally isolated 6631_en_03 PHOENIX CONTACT 4 Digital outputs continued Derating at 100 simultaneity Nominal load per channel Ohmic Inductive Lamp Signal delay upon power up of Nominal ohmic load Nominal inductive load Nominal lamp load Signal delay upon power down of Nominal ohmic load Nominal inductive load Nominal lamp load Switching frequency with Nominal ohmic load THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A I A N A O 10 20 30 40 50 60 TA C 6631A012 48 W 48 VA 1 2 H 12 Q 48 W Approximately 200 us typical Depending on inductive time constant Approximately 200 us typical Approximately 250 us typical 150 ms 1 2 H 12 Q approximately depending on inductive time constant 250 us approximately 500 Hz maximum This switching frequency is limited by the number of bus devices the bus configuration the software used and the control or computer system used Nominal inductive load Nominal lamp load Overload response Restart frequency with ohmic overload 2 Q Response with inductive overload Reverse vo
8. ltage protection against short pulses Resistance to permanently applied reverse voltages Response upon power down Validity of output data after connecting the power supply power up Limitation of the voltage induced on circuit interruption Single maximum energy in free running Protective circuit type Overcurrent shutdown Output current when switched off Output current with ground connection interrupt when switched off 0 1 Hz 1 2 H 12 Q maximum 500 Hz Auto restart 45 Hz approximately Output may be damaged Protected against reverse voltages No The output follows the supply voltage without delay 5 ms typical 11 V approximately 1500 W Integrated free wheeling diode for each channel 2 6 A minimum 20 uA maximum 5 mA maximum Error messages to the higher level control or computer system Overload of outputs Yes master see Diagnostic data for device diagnostics on page 14 a If an error is triggered at the outputs by an overload the device switches off the corresponding output and sends an error message to the 6631_en_03 PHOENIX CONTACT 5 THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A Output characteristic curve when switched on typical Output current A Differential output voltage V 0 0 0 20 0 01 0 40 0 03 0 75 0 05 1 0 0 07 1 5 0 12 1 75 0 13 2 00 0 17 Output characteristic curve when switched off U axx 30 V DC typical Load resistance KO Ou
9. ransport Permissible humidity storage transport THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A FLS PB M12 DIO 4 4 M12 2A 2736107 60 mm x 178 mm x 49 3 mm 340 g approximately Process data mode with 8 bits 2 3 or 4 wire technology 2 or 3 wire technology 25 C to 60 C 25 C to 85 C 95 a For a short period slight condensation may appear on the outside of the housing Permissible air pressure operation Permissible air pressure storage transport Degree of protection Protection class Mechanical requirements Vibration test sinusoidal vibrations according to EN 60068 2 6 Shock test according to EN 60068 2 27 80 kPa to 106 kPa up to 2000 m above sea level 70 kPa to 106 kPa up to 3000 m above sea level IP65 IP67 according to IEC 60529 Class 3 according to VDE 0106 IEC 60536 5g load in each space direction 30g load half sinusoidal wave positive and negative in each space direction a For additional information about mechanical requirements and ambient conditions please contact Phoenix Contact Power supply Supply voltage Range Current consumption at U at 24 V DC Current consumption at Us at 24 V DC Current consumption at U axx at 24 V DC Digital inputs Number Input design Definition of switching thresholds Maximum low level voltage Minimum high level voltage Nominal input voltage Range Nominal input current Current flow Delay time Permis
10. sible cable length to the sensor 6631_en_03 24V DC 18 V DC to 30 V DC 40 mA typical 100 mA maximum 4 5 mA sensor current typical 700 mA maximum 6 mA actuator current typical 4 A maximum 4 According to IEC 61131 2 Type 1 Ul max lt 5 V UHmin gt 11 V 24 V DC 30 V DC lt Uj lt 30 V DC 5 mA Linear in the range 1 V lt U lt 30 V ton lt 3 1 ms typical torr 4 1 ms typical 100 m PHOENIX CONTACT 3 THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A Input characteristic curve Input voltage V Typical input current mA 30 lt Un lt 0 7 0 3 0 5 6 1 0 9 1 6 12 2 3 15 3 0 18 3 8 21 4 5 24 5 2 27 6 0 30 6 7 Sensor supply Minimum sensor voltage Us 1V Nominal current per channel 75 mA Nominal current per device 300 mA Overload protection Electronic per device Short circuit protection Electronic per device Error messages to the higher level control or computer system Sensor supply short circuit Yes Sensor supply overload Yes If an error is triggered by an overload or short circuit of the sensor supply the device switches off the sensor supply to all the channels and sends an error message to the master If the sensor supply Us is too low the device sends an error message to the master see Diagnostic data on page 14 Digital outputs Number 4 Nominal output voltage UouT Uaxx 1V Differential voltage at lhom lt 1V Nominal current l
11. tput voltage V oO 1 5 1000 0 9 100 0 1 10 0 01 1 0 001 Output characteristic curve for ground connection interrupt U Axx 30 V DC Load resistance kQ Output voltage V m 29 9 1000 28 8 100 25 0 10 13 6 1 3 8 Interface Bus system PROFIBUS DP Incoming bus Coupling of shield connection Directly to FE Transmission speed 12 Mbaud maximum Outgoing bus Coupling of shield connection Directly to FE Transmission speed 12 Mbaud maximum i For transmission speeds of more than 3 Mbaud T pieces with integrated series inductance must be used 6631_en_03 PHOENIX CONTACT 6 THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A Electrical isolation isolation of the voltage areas For device connection please note the instructions and regulations in the Installation of devices in the Fieldline product range user manual FLS FLM SYS INST UM E Separate potentials in the FLS PB M12 DIO 4 4 M12 2A I O device Test distance Test voltage 24 V supply bus logic bus connection 500 V AC 50 Hz 1 min 24 V supply bus logic FE 500 V AC 50 Hz 1 min 24 V supply bus logic digital inputs sensor supply 500 V AC 50 Hz 1 min 24 V supply bus logic digital outputs actuator supply 500 V AC 50 Hz 1 min Bus connection FE 500 V AC 50 Hz 1 min Bus connection digital inputs sensor supply 500 V AC 50 Hz 1 min Bus connection digital outputs actuator supply 500 V AC 50 Hz 1 min FE digit
12. x x x x x x x Station statuss sews x x x x x x x x Diagnostic master address Byes o 0 0 o 0 1 1 o HighIOnumber eyes fo 1 a 0 1 0 1 o lowlnumber Byes o 0 0 0 0 1 1 1 Diagnostichesder byes o 0 0 0 0 0 0 0 esma tyes o o o 0 0 0 0 0 Rema sew o 0 0 0 0 0 0 0 Pesma sven oJ o o 0 0 0 0 0 Rema see x x 0 0 o 0 0 0 Pesma a Bytes 0 to 6 are PROFIBUS standard Bytes 7 to 12 are device specific 11 2 Diagnostic data for device diagnostics C S e Mo M2 Reseved O O O O O ii ma Reema OOOO o SSS Status of the device supply U 1 if U too low Overload status of the sensor supply Us 1 if sensor supply is overloaded If a diagnostic event occurs the diagnostic data is sent to the master by means of a diagnostic telegram generated once by the device The current status of the data can be read by the device at any time 6631_en_03 PHOENIX CONTACT GmbH amp Co KG 32823 Blomberg Germany Phone 49 52 35 30 0 14 PHOENIX CONTACT P O Box 4100 Harrisburg PA 17111 0100 USA Phone 717 944 1300 www phoenixcontact com
13. y for OUT1 and OUT2 ON Power supply for OUT1 and OUT2 present Power supply for OUT1 and OUT2 too low ce LED Power supply for OUT3 and OUT4 ON Power supply for OUT3 and OUT4 present eps supply for OUT3 and OUT4 too low 6631_en_03 PHOENIX CONTACT 11 6 Internal basic circuit diagram PB IN PB OUT U OUT k g tt 7 BE Of 414 _ Orte Ed ES Ed E U OUT 6631A009 Figure 9 Internal wiring of the connections For information about the electrically isolated areas please refer to page 7 6631_en_03 onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A aN Functional earth ground Isolating transformer ENS PB PROFIBUS protocol chip bus logic ne including voltage conditioning Optocoupler LED Al fal E Transistor Input H H q4 Output Electrically isolated area PHOENIX CONTACT 12 onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS FLS PB M12 DIO 4 4 M12 2A 7 Connection example 6625B009 Figure 10 Typical connection of sensors and actuators Connection notes 9 Configuration data NOTE Meet noise immunity requirements 066Ahex Connect FE using a mounting screw or a cable pee ageless Ea connection to the FE connection latch when Output address area mounting on the side or on a non conductive surface N
Download Pdf Manuals
Related Search
Related Contents
HP ePrint & Share, das dieses Benutzerhandbuch - Hewlett rf and cavitation heads Minimate User manual les différentes visions des arômes alimentaires - Brunswick VKP 202-2 - Vaillant Generic ITS IP PBX User Manual 1/2009 user manual - VideoTesty.pl documento adicional - Inicio Profitez de la musique avec une Xperia/ un iPhone via un réseau Copyright © All rights reserved.