Home
SmartLine - Honeywell Process Solutions
Contents
1. HART DP SP Adjustable from 0 to 32 seconds in 0 1 increments Default 0 50 seconds HART Temperature Damping limit is 0 to 102 HART FLOW Damping limit is 0 to 100 DE DP SP 0 0 16 0 32 0 48 1 2 4 8 16 32 seconds Default 0 48 seconds DE for Temperature PV Damping time 0 0 3 0 7 1 5 3 1 6 3 12 7 25 5 51 1 102 3 DE for Flow PV Damping time 0 0 50 1 2 3 4 5 10 50 100 Vibration Effect SMA845 SMG870 Less than 0 1 of URL w o damping Per IEC60770 1 field or pipeline high vibration level 10 2000Hz 0 21 displacement 3g max acceleration Electromagnetic Compatibility EN 61326 1 Isolation 2000 Vdc 1400Vrms Galvanic Isolation between inputs and outputs Maximum Lead Wire Resistance Thermocouples 50 ohms leg Pt100 Pt200 Pt500 and Pt1000 RTDs 50 ohms leg Pt25 RTD 10 ohms per leg Ambient Temperature Effect Digital Accuracy For RTD Inputs 0 0015 C C For T C Inputs 0 005 C C Temperature Sensor Burnout Burnout detection is user selectable Upscale or down scale with critical status message For RTD type inputs broken wire wires will be indicated Lightning Protection Option Leakage Current 10uA max 42 4VDC 93C Impulse rating 8 20uS 5000A gt 10 strikes 10 1000uS 200A gt 300 strikes 10000A 1 strike min Materials Specifications SMV 800 Smart Pressure Transmitter See model selection guide for availability rest
2. Note 1 50 C to 85 C Enclosure Type 4X IP66 IP67 All All Canadian Registration Number CRN All models except and have been registered in all provinces and territories in Canada and are marked CRN 0F8914 5C 12 SMV 800 Smart Pressure Transmitter Approval Certifications Continued MSG COMM FIELD AMBIENT TEMP CODE AGENCY TYPE OF PROTECTION OPTION PARAMETERS Ta Flameproof Certificate SIRA 15ATEX2039X All 50 2 o Il 1 2 G Ex d IIC T4 Note 302C to 85 C II 2 D Ex tb IIIC T 85 C IP 66 Intrinsically Safe 4 20 mA c ATEX Certificate SIRA 15ATEX2039X DE HART Note 2 50 C to 70 C II 1 G Ex ia IIC T4 Nonincendive Certificate SIRA 15ATEX4040x 4 20 MA Note 1 50 C to 85 C ertificate DE HART ote o II 3 G Ex nA IIC T4 Enclosure IP66 IP67 All All All Flameproof Certificate SIR 15 0022X All 50 2 o Ga Gb Ex d IIC T4 Note 1 50 C to 85 C Ex tb IIIC T 85 C IP 66 Intrinsically Safe D IECEx Certificate SIR 15 0022X em Note 2 50 C to 70 C World Ex ia IIC T4 ee Nonincendive ery i 20 m r A Certificate SIR 15 0022X DE HART Note 1 50 C to 852C Ex nA IIC T4 Enclosure IP66 IP67 All All All Notes 1 Operating Parameters Voltage 11 to 42 V DC Current 4 20 mA Normal 3 8 23 mA Faults 2 Intrinsically Safe Entity Parameters Analog DE HART Entity Values Vmax Ui 30V Imax li 225 mA Ci
3. 0 to 100 Vac Region Min Pressure mmHg absolute Atmospheric 25 2 short term inH O absolute Atmospheric 13 1 short term HART Models 10 8 to 42 4 Vdc at terminals IS version limited to 30v Supply Voltage 0 to 1440 ohm as shown in Figure 2 Load Resistance DE Models 15V to 42 4 Vdc at terminals IS version limited to 30V XP and Non Sparking Non Incentive 42 Volts 0 to 900 ohm as shown in Figure 2 Maximum Allowable Working Pressure MAWP Standard SMV 800 products are rated to SMA810 100 psiA 7 0 BarA Maximum Allowable Working SMA845 1500 psiA 104 BarA Pressure MAWP depends on Approval Agency and transmitter SMG870 4500 psiG 310 BarG materials of construction 1 2 3 4 LCD Display operating temperature 20 C to 70 C 4 F to 158 F Storage temperature 30 C to 80 C 22 F to 176 F For CTFE fill fluid the rating is 15 to 110 C 5 to 230 F Short term equals 2 hours at 70 C 158 F MAWP applies for temperatures 40 C to 125 C 40 F to 257 F Static Pressure Limit is de rated to 3 000 psi 207 BarA for 26 C to 40 C 14 8 F to 40 F Use of graphite o rings de rates transmitter to 3 625 psi Use of 12 process adaptors with graphite o rings de rates transmitter to 3 000 psi Consult factory for MAWP of SMV 800 transmitters with CRN approval A ee ee ae earn ee a a Note A minimum of 250 ohms of loop resis
4. Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 South Korea Honeywell Korea Co Ltd Phone 822 799 6114 Fax 822 792 9015 44 0 1344 656000 Email Sales FP Sales Apps Honeywell com ort honeywell com AMERICA S Honeywell Process Solutions Phone TAC 1 800 423 9883 or 215 641 3610 Sales 1 800 343 0228 Email Sales FP Sales Apps Honeywell com or TAC hfs tac support honeywell com Specifications are subject to change without notice For more information To learn more about SmartLine Transmitters visit www honeywellprocess com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston TX 77042 Honeywell Control Systems Ltd Honeywell House Skimped Hill Lane Bracknell England RG12 1EB Shanghai City Centre 100 Jungi Road Shanghai China 20061 www honeywellprocess com 34 SM 03 92 October 2015 Honeywell 2015 Honeywell International Inc
5. and the handheld communicator 2 Analog Output Accuracy is applicable to the 4 to 20 mA Signal output 3 For TC inputs CJ accuracy of 0 25 C shall be added to digital accuracy to calculate the total digital accuracy 4 These input types are not available on DE units Total analog accuracy is the sum of digital accuracy and 0 005 of span Ambient Temperature Effect Digital Accuracy For RTD Inputs 0 0015 C C For T C Inputs 0 005 C C Output D A 0 0005 of span C PV4 Mass Flow Reference Accuracy 0 6 over 20 1 flow range calculated every 500ms Flow performance specifications assume dynamic compensation and is applicable for SMA845 and SMG870 2 Applicable standards and installations per ASME MFC 3M or ISO 5167 1 for un calibrated orifice Bigger than 2 8 inch Pipe Diameter 0 2 lt beta lt 0 6 Orifice DP Turn down 16 1 Reference accuracy does not include RTD sensor accuracy SMV 800 Smart Pressure Transmitter Operating Conditions All Models Reference Rated Condition Operative Limits Transportation and Parameter Condition Storage C oF C oF C oF C oF Ambient Temperature SMA810 SMA845 SMG870 25 1 774 2 40 to 85 40 to 185 40 to 85 40 to 185 55 to 120 67 to 248 Meter Body Temperature SMA810 SMA845 SMG870 25 1 77 2 40 to 110 40 to 230 40 to 125 40 to 257 55 to 120 67 to 248 Humidity RH 10 to 55 0 to 100 0 to 100
6. customer tag Tag One Wired Stainless Steel Tag Up to 4 lines 26 char line Two Wired Stainless Steel Tag Up to 4 lines 26 char line Unassembled Conduit Plugs amp Adapters No Conduit Plugs or Adapters Required 1 2 NPT Male to 3 4 NPT Female 316 SS Certified Conduit Adapter 1 2 NPT 316 SS Certified Conduit Plug M20 316 SS Certified Conduit Plug Minifast 4 pin 1 2 NPT not suitable for X Proof applications 4 d s 5 c Unassembled Conduit Plugs amp Adapters Minifast_ 4 pin M20 not suitable for X Proof applications None No additional options NACE MR0175 MR0103 1SO15156 FC33338 Process wetted parts only NACE MR0175 MRO103 1SO15156 FC33339 Process wetted and non wetted parts EN10204 Type 3 1 Material Traceability FC33341 Certificate of Conformance F3391 Calibration Test Report amp Certificate of Conformance F3399 Certifications amp Certificate of Origin F0195 Warranty Over Pressure Leak Test Certificate 1 5X MAWP F3392 Cert Clean for O2 or CLzservice per ASTM G93 Extended Warranty Additional 1 year Extended Warranty Additional 2 years Extended Warranty Additional 3 years Extended Warranty Additional 4 years Extended Warranty Additional 15 years IXa Se ON SS aS er ee eS ee ed a T SBN CRN umbor availa _ ee ms a E Sa a a Sct onion option omnis group SSCS SMV 800 Smart Pressure Transmitter Model Selection Guide FIELD INSTALLABLE ACCESSORY PARTS Integrally Mounted Advan
7. options o RTD 2 3 4 wires PT25 PT100 PT200 PT500 PT1000 o Universal Input RTD PT25 PT100 PT200 PT500 PT1000 and Thermocouple Type B E J K N R S T Mass Flow Calculation Mass Flow Compensation can be selected for Standard Compensations by user for Gas Liquid and Steam without limitation on primary elements Mass Flow Compensation can be selected for Dynamic Compensation by the user from ASME MFC 3M IS05167 Gost 8 586 for Orifice Plate Nozzle and Venturri AGA3 for Orifice and Calculation Support for Averaging Pitot Tube VCone Wafer Cone Wedge and Integral Orifice and Conditional Orifice are also available Mass Flow Calculations also support user Fixed Input Parameters for Customizing the Calculations SMV 800 Smart Pressure Transmitter System Integration o SmartLine communications protocols all meet the most current published standards for HART DE o Integration with Honeywell s Experion PKS offers the following unique advantages Messaging amp Maintenance Mode Indication Tamper reporting O O o FDM Plant Area Views with Health summaries o All SMV 800 units are Experion tested to provide the highest level of compatibility assurance Automatic Density Compensation Using the configuration software the SMV can be configured with the primary element type and the physical parameters of the fluid measured This method dynamically compensates for fluid characteristics such as discharge coef
8. 4 2nF Li OUH Pi 0 9W SMV 800 Smart Pressure Transmitter 13 Mounting amp Dimensional Drawings millimeters inches Reference Dimensions Figure 4 Mounting Configurations H 128 9 W OPTIONAL DISPLAY OR 116 0 W O OPTIONAL DISPLAY 4 57 62 6 W OPTIONAL DISPLAY con 63 3 246 2 49 OR 52 7 W O OPTIONAL DISPLAY 2 08 2x 127 0 CLEARANCE FOR ENDCAP REMOVAL MANIPULATION r n i eS N HHY R 155 VASE GN Ih 2x 20 20 oR al 795 Q ns t ey Pj f 198 8 A mas a i ROTATIONAL LOCK 116 5 o 4 59 EXTERNAL GROUND SIDE CONNECTION VENT ORAN 36 8 OPTIONAL 1 45 PLUG t L Figure 5 Typical mounting dimensions for reference 14 SMV 800 Smart Pressure Transmitter Model Selection Guides are subject to change and are inserted into the specifications as guidance only Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at www honeywellprocess com en US pages default aspx Model Selection Guide Model SMV800 Multivariable Pressure Transmitter Model Selection Guide 34 SM 16 92 Issue 1 Instructions Make selections fromall Tables Key through IX using column belowthe proper arrow Asterisk indicates availability Letter a refer to restrictions highlighted in the restrictions table Tables delimited with dashes List Price Price equals the sum of prices foral
9. O o Modular design characteristics Communications Output Options Span amp Range Limits o 4 20mA DC Analog Model URL LRL Max Span Min Span o Honeywell Digitally Enhanced DE PV1 DP H20 mbar H20 mbar H20 mbar H20 mbar Single or Multivariable SMA810 25 62 50 25 62 5 25 62 50 1 0 2 5 62 50 cee 62 50 ee o HART version 7 0 SMA845 400 1000 400 1000 400 1000 1 0 2 5 SMG870 400 1000 400 1000 400 1000 1 0 2 5 All transmitters are available with the above listed Pv2 SP psiA bara psiA bara psiA bara psiA bar communication protocols SMA810 100 7 0 0 0 100 7 0 5 0 35 SMA845 1500 104 0 0 1500 104 30 2 1 PV2 SP psig barg psig barg psig barg psig barg SMG870 4500 310 14 7 1 4500 310 60 4 2 Description Honeywell s SMV 800 Smart Multivariable Flow Transmitter extends our proven smart technology to the measurement of three separate process variables with the ability to calculate compensated mass or volume flow rate as a fourth process variable according to industry standard methods for air gases steam and liquids Unique Indication Display Advanced Graphics LCD Display Features Modular may be replaced in the field 0 90 180 amp 270 degree position adjustments Standard and custom measurement units available Up to eight display screens with 3 formats are possible L
10. RTD 4Wire RTD Figure 3 Temperature sensor Wiring Diagram SMV 800 Smart Pressure Transmitter Approval Certifications 11 MSG CODE AGENCY TYPE OF PROTECTION COMM OPTION FIELD PARAMETERS AMBIENT TEMP Ta FM Approvals Explosionproof Class I Division 1 Groups A B C D Dust Ignition Proof Class Il Ill Division 1 Groups E F G T4 Class Zone 1 2 AEx d IIC T4 Class Il Zone 21 AEx tb IIIC T 85 C IP 66 All Note 1 50 C to 85 C Intrinsically Safe Class Il Ill Division 1 Groups A B C D E F G T4 Class 1 Zone O AEx ia IIC T4 4 20 mA DE HART Note 2 50 C to 70 C Nonincendive Class l Division 2 Groups A B C D locations Class 1 Zone 2 AEx nA IIC T4 4 20 mA DE HART Note 1 50 C to 85 C Enclosure Type 4X IP66 IP67 All All Canadian Standards Association CSA Explosion Proof Certificate 70007689 Class I Division 1 Groups A B C D Dust Ignition Proof Class Il Ill Division 1 Groups E F G T4 Ex d IIC T4 Ex tD A21 T 95 C IP 66 All Note 1 50 C to 85 C Intrinsically Safe Certificate 70007689 Class l Il Ill Division 1 Groups A B C D E F G T4 Ex nA IIC T4 4 20 mA DE HART Note 2 50 C to 70 C Nonincendive Certificate 70007689 Class l Division 2 Groups A B C D T4 Ex nA IIC T4 4 20 mA DE HART
11. SmartLine Honeywell Preliminary Technical Information Cs P SMV SmartLine Multivariable Transmitter Specification 34 SM 03 92 October 2015 Introduction The SMV 800 combines sensor technologies for differential pressure static pressure and temperature with the latest microprocessor technology to provide highly accurate compensated flow measurement When paired with the other SmartLine unique features the SMV 800 delivers the highest levels of safety reliability and efficiency available The SmartLine family is also fully tested and compliant with Experion PKS providing the highest level of compatibility assurance and integration capabilities Best in Class Features Accuracy up to 0 0400 for Differential pressure Accuracy up to 0 0375 for Static pressure Accuracy up to 0 1 Deg C for Temperature Mass Flow Reference Accuracy up to 0 6 Automatic static pressure amp temperature compensation Rangeability up to 400 1 O O 0 0 0 0 0 Compensated flow response time of up to 2x per second Multiple local display capabilities External zero span amp configuration capability Polarity insensitive electrical connections Figure 1 SMV 800 Multivariable Transmitters feature field proven piezoresistive sensor technology Comprehensive on board diagnostic capabilities o Oo 0 0 90 Integral Dual Seal design for highest safety based on ANSI NFPA 70 202 and ANSI ISA 12 27 0 World class overpressure protection o
12. arge PV with Bar Graph or PV with Trend Graph Configurable screen rotation timing 3 to 30 sec o Display Square Root capabilities may be set separately from the 4 20mA dc output signal o Multiple language capability EN GE FR IT SP RU TU CH amp JP Oo 0 0 Q O Diagnostics SmartLine transmitters all offer digitally accessible diagnostics which aid in providing advanced warning of possible failure events minimizing unplanned shutdowns providing lower overall operational costs Configuration Tools Integral Three Button Configuration Option Suitable for all electrical and environmental requirements SmartLine offers the ability to configure the transmitter and display via three externally accessible buttons except for the flow related parameters Zero span capabilities are also optionally available via these buttons with or without selection of a display option Hand Held Configuration SmartLine transmitters feature two way communication and configuration capability between the operator and the transmitter This is accomplished via Honeywell s field rated Multiple Communication Configurator MCT404 The MCT404 is capable of field configuring HART SMV Devices for all parameters other than flow configuration can be ordered for use in intrinsically safe environments All Honeywell transmitters are designed and tested for compliance with the offered communication protocols and are designed to operate with any properl
13. ced Indicator Kit EN DE FR ES IT RU TU compatible with all Electronic Modules Integrally Mounted Advanced Indicator Kit EN CH JP compatible with all Electronic Modules Terminal Strip w o Lightening Protection for HART or DE Modules Terminal Strip w Lightning Protection Kit for HART or DE Modules Terminal Strip w o Lightening Protection FFB Profibus Module Terminal Strip w Lightning Protection Kit for FFB Profibus Module HART Electronics Module HART Electronics Module w connection for external configuration buttons DE Electronics Module DE Electronics Module w connection for external configuration buttons PAPER MANUALS Paper Manual SMV 800 Smart Transmitter User Manual English Paper Manual SMV 800 Smart Transmitter HART DE Communications Manual English 17 50049846 506 50087087 503 50086421 501 50086421 503 50086421 507 50086421 509 50098718 501 50098718 502 50098718 503 50098718 504 Part Number 34 SM 25 03 34 SM 25 06 Sales and Service For application assistance current specifications pricing or name of the nearest Authorized Distributor contact one of the offices below ASIA PACIFIC Honeywell Process Solutions TAC hfs tac EMEA Honeywell Process Solutions Phone 80012026455 or support honeywell com Australia Honeywell Limited Phone 61 7 3846 1255 FAX 61 7 3840 6481 or Toll Free 1300 36 39 36 TAC Toll Free Fax hfs tac su 1300 36 04 70 China PRC
14. d spans and reference conditions of 25 C 77 F 0 static pressure 10 to 55 RH and 316SS barrier diaphragm 3 Static Line Pressure effect for SMA810 is span 25 psi SMV 800 Smart Pressure Transmitter Performance Specifications Digital PV3 Temperature Reference Accuracy conformance to 3 Sigma Table III Input Maximum Range Limits Digital Min Span Stability Standards Type Accuracy ULR year RTD o o o o 2 3 4 wire s P i 2 Pt25 200 to 850 328 to 1562 0 50 1 0 0 01 IEC751 1990 0 00385 Pt100 200 to 850 328 to 1562 0 10 1 0 0 01 IEC751 1990 0 00385 Pt200 200 to 850 328 to 1562 0 20 1 0 0 01 IEC751 1990 0 00385 Pt500 200 to 850 328 to 1562 0 12 1 0 0 01 IEC751 1990 0 00385 Pt1000 200 to 500 328 to 932 0 10 1 0 0 01 IEC751 1990 0 00385 Thermo oC oF oC couples B 200 to 1820 392 to 3308 0 60 1 0 0 01 IEC 584 1 ITS 90 E 200 to 1000 328 to 1832 0 20 1 0 0 01 IEC 584 1 ITS 90 J 200 to 1200 328 to 2192 0 25 1 0 0 01 IEC 584 1 ITS 90 K 200 to 1370 328 to 2498 0 25 1 0 0 01 IEC 584 1 ITS 90 N 200 to 1300 328 to 2372 0 40 1 0 0 01 IEC 584 1 ITS 90 R 50 to 1760 58 to 3200 0 50 1 0 0 01 IEC 584 1 ITS 90 S 50 to 1760 58 to 3200 0 50 1 0 0 01 IEC 584 1 ITS 90 T 250 to 400 418 to 752 0 20 1 0 0 01 IEC 584 1 ITS 90 Notes 1 Digital Accuracy is accuracy of the digital value accessed by the Host system
15. de w Vent Side w Center Vent End w Vent Matches Head Material Stainless Steel Only Matches Head Material Stainless Steel Only Matches Head Material Single Ended Single Ended Dual Ended Dual Ended End w Center Vent Dual Ended Side w Vent amp End w Plug Teflon or PTFE Glass Filled Viton or Fluorocarbon Elastomer Graphite e Vent Drain Type Location f Gasket Material Except Carbon Steel Heads shall use 316SS Vent Drain Plugs amp Adapters when required SMV 800 Smart Pressure Transmitter Model Selection Guide Head Connect Orientation Approvals a Electronic Housing Material amp Connection Type b Output Protocol c Customer Interface Selections a Application Software b Output Limit Failsafe amp Write Protect Settings c General Configuration 2 Left side Right side as view ed from Standard Reversed 90 Standard High Side Left Low Side Right Std Head Orientation Low Side Left High Side Right Std Head Orientation High Side Left Low Side Right 90 Head Rotation No Approvals Required FM Explosion proof Intrinsically Safe Non incendive amp Dustproof CSA Explosion proof Intrinsically Safe Non incendive amp Dustproof ATEX Explosion proof Intrinsically Safe amp Non incendive IECEx Explosion proof Intrinsically Safe a
16. down Stability Accuracy URL LRL Ratio URL Year Span 25 in HO 62 5mbar 25 in H O 62 5mbar 1 in H 0 2 5mbar os owes oe 0 0400 SMAB45 400 in H 0 1000mbar 400 in H O 1000mba 1 in H O 2 5mbar 400 1 0 0625 SMG870 SMA810 100 psiA 7 bara 0 psiA O bara 5 psiA 0 35 bara 20 1 0 125 0 0375 SMA845 1500 psiA 104 bara 0 psiA O bara 30 psia 2 1 bara 50 1 0 008 i SMG870 4500 psig 310 barg 14 7 psig 1 0 barg 60 psig 4 2 barg 0 025 Zero and span may be set anywhere within the listed URL LRL range limits Differential Static Digital Accuracy at Specified Span Temperature and Static Pressure Combined Zero amp Span conformance to 3 Sigma TABLE Il Accuracy Temperature Effect Static Line Pressure of Span Span 50 F Effect Span 1000psi For Spans c URL Below SMA810 25 in H2O 0 100 0 1000 0 180 0 080 SMA845 400 in H2O 0 015 0 025 25 0 075 0 0250 0 200 0 025 SMG870 400 in H2O Fase amen er oom 0 0125 0 025 eee ee Differential PV2 Static n a Turn Down Effect Temp Effect Static Effect eG felon blr o Span per 1000 psi Span Span per 28 C 50 F Typical Calibration Frequency PV1 and PV2 calibration verification is recommended every four 4 years Notes 1 Digital terminal based accuracy Includes the combined effects of linearity hysteresis and repeatability Analog output adds 0 005 of span error 7 For zero base
17. e via the DD DTM tools or integral display as shown below Critical Diagnostics Non critical Diagnostics HART DD DTM Tools Display HART DD DTM Tools Display e Sensor Critical Fault e Meter Body and or e Local Display e Display Setup a Body Comm e Fixed Current Mode e Analog Out Mode and or and or e Sensing Sec NC Fault Temp cal Correct Temp Input and or DP Zero Correct and or e Temp Sensor Comm DP Span Correct and or SIL Diag Failure or e Comm Module Meter Body Input p msp vcc fault e Sensor Over Temperature e Temp Module Temp and or ere c e Meter Body Temp onfig Data Corrupt e DAC Failure e PV Out Of Range e PV Out Of Range e DAC Failure e Comm Module Temp e No Fact Calib e Pressure Fac Cal and or e Temp Fac Cal Button Button e CJ Out of Limit e CJ Range e AO Out of Range N A e Sensor Input Open e Temp Input and or e Temp Input TB6 e Loop Current Noise N A e Sensor Unreliable Comm e Meter Body Comm and or e Temp Comm e Tamper Alarm N A e No DAC Calibration N A e Low Supply Voltage e Supply Voltage e Flow Calculation Details Flow Divide by 0 and or Flow Sart of Neg and or Flow Direction and or Flow SP PT Comp e DP SP PT FLOW DP Simulation and or Simulation Mode SP Simulation and or PT Simulation and or Flow Simulation Other Certification Options o NACE MRO175 MRO103 IS015156 N A Mode 10 SMV 800 Smart Pressure Transmitter Temperature Sensor Wiring Diagram Strap Link Single 3 2 Wire RTD Wire
18. ficients gas expansion factors density and viscosity as well as installation issues like upstream pipe size using the above referenced algorithms Basic Flow Density Compensation This conventional calculation method is based on flow factors being manually entered Modular Design To help contain maintenance amp inventory costs all SMV 800 transmitters are modular in design supporting the user s ability to replace meter bodies indicators or change electronic modules without affecting overall performance or approval body certifications Each meter body is uniquely characterized to provide in tolerance performance over a wide range of application variations in temperature and pressure and due to the Honeywell advanced interface electronic modules may be swapped without losing in tolerance performance characteristics Modular Features o Meter body replacement Replaceable electronics comm modules Add or remove integral indicators Add or remove lightning protection terminal connection oo O Field replaceable in all electrical environments including IS except flameproof without violating agency approvals See Model Selection Guide With no performance effects Honeywell s unique modularity results in lower inventory needs and lower overall operating costs 4 SMV 800 Smart Pressure Transmitter Performance Specifications Digital Reference Accuracy conformance to 3 Sigma TABLE Maximum Reference Turn
19. l selections made Key Number ll Ul v v wi vi X x xi _1 _ 1 _ _ 1 l 1 0000 Ism____ __ _H Selection Availability 25 to 25 In H20 62 5 to 62 5 mbar 400 to 400 In H20 1000 to 1000 mbar 400 to 400 In H20 1000 to 1000 mbar Temperature Single Input RTD 2 3 4 Wire Sensor Input Single Input Universal Digital Output 316L Stainless Steel Hastelloy C 276 Monel 400 Plated Carbon Steel Tantalum Gold Plated Stainless Steel Gold Plated Hastelloy C 276 Gold Plated Monel 400 316L Stainless Steel Hastelloy C 276 Monel 400 316 Stainless Steel Tantalum Gold Plated Stainless Steel Gold Plated Hastelloy C 276 Gold Plated Monel 400 Hastelloy C 276 Hastelloy C 276 Tantalum Gold Plated Hastelloy C 276 Monel 400 Gold Plated Monel 400 0 to 100 psia 0 to 7 bara 0 to 1500 psia 0 t0104 bara 14 7 to 4500 psig 1 to 310 barg Measurement Range a Process Wetted Heads amp Diaphragm Materials Monel 400 Silicone Oil 200 Fluorinated Oil CTFE Silicone Oil 704 Neobee M 20 c Process None None 1 4 NPTF female thread Std Materials to Match Head amp Head Bolt Materials Selections Carbon Steel 316 SS Grade 660 NACE A286 with NACE 304 SS Nuts Grade 660 NACE A286 Bolts amp Nuts Monel K500 Super Duplex B7M b Fill Huid d Bolt Nut Materials Head Type Single Ended None None Vent Drain Location Vent Material Si
20. mp Non incendive Material Connection Lhining Protection 1 2 NPT M20 1 2 NPT M20 1 2 NPT M20 1 2 NPT M20 HART Protocol None None Yes Zero Span Only None None EN DE FR IT ES RU TU Yes EN DE FR IT ES RU TU None EN CH JP Yes EN CH JP Polyester Powder Coated Aluminum 316 Stainless Steel Grade CF8M Analog Output Indicator None None Advanced Advanced Advanced Advanced Diagnostics Honeywell Std 3 8 20 8 mAdc Honeywell Std 3 8 20 8 mAdc Honeywell Std 3 8 20 8 mAdc Honeywell Std 3 8 20 8 mAdc Factory Standard Standard Diagnostics Write Protect Fail Mode Disabled High gt 21 0mAdc Disabled Low lt 3 6mAdc Enabled High gt 21 0mAdc Enabled Low lt 3 6mAdc Custom Configuration Unit Data Required from customer he customer connection perspective 3 NAMUR Output Limits 3 8 20 5mAdc can be configured by the customer or select custom configuration Table Vc Model Selection Guide SMG870 SMA845 of Calibrations z a Accuracy and PV1 PV2 amp PV3 Factory Std PV1 PV2 amp PV3 Single Calibration Calibration Standard PV1 PV2 amp PV3 Custom Unit Data Required PV1 PV2 amp PV3 Custom Unit Data Required PV1 amp PV2 Dual Calibration Bracket Type Material None None Angle Bracket Carbon Steel a Mounting Angle Bracket 304 SS Bracket Angle Bracket 316 SS Flat Bracket Carbon Steel Flat Bracket 304 SS Flat Bracket 316 SS Customer Tag Type b Customer No
21. rictions with various models Parameter Description Barrier Diaphragms Material 316L SS Hastelloy C 276 Monel 400 Tantalum Gold plated 316L SS Gold plated Hastelloy C 276 Gold plated Monel 400 Process Head Material 316 SS Carbon Steel Zinc plated Hastelloy C 276 Monel 400 Vent Drain Valves amp Plugs 316 SS Hastelloy C 276 Monel 400 Head Gaskets Glass filled PTFE standard Viton and graphite are optional Meter Body Bolting Carbon Steel Zinc plated standard Options include 316 SS NACE A286 SS bolts Monel K500 Super Duplex and B7M Optional Adapter Flange and Bolts Adapter Flange materials include 316 SS Hastelloy C 276 and Monel 400 Bolt material for flanges is dependent on process head bolts material chosen Standard adaptor o ring material is glass filled PTFE Viton and graphite are optional Mounting Bracket Carbon Steel Zinc plated 304 Stainless Steel or 316 Stainless Steel Fill Fluid Silicone Oil DC200 Silicone Oil 704 NEOBEE M 20 or CTFE Chlorotrifluoroethylene Electronic Housing Pure Polyester Powder Coated Low Copper lt 0 4 Aluminum Meets Type 4X IP66 amp IP67 All stainless steel housing is optional Mounting Can be mounted in virtually any position using the standard mounting bracket Bracket is designed to mount on 2 inch 50 mm vertical or horizontal pipe See Figure 4 Proces
22. s Connections Va NPT or 42 NPT with adapter meets DIN requirements Wiring Accepts up to 16 AWG 1 5 mm diameter Dimensions See Figure 5 Net Weight 8 3 pounds 3 8 Kg With Aluminum Housing 1 Vent Drains are sealed with Teflon Hastelloy C 276 or UNS N10276 3 Monel 400 or UNS N04400 4 Supplied as 316 SS or as Grade CF8M the casting equivalent of 316 SS Carbon Steel heads are zinc plated and not recommended for water service due to hydrogen migration For that service use 316 stainless steel wetted Process Heads Hastelloy C 276 or UNS N10276 Supplied as indicated or as Grade CW12MW the casting equivalent of Hastelloy C 276 7 Monel 400 or UNS N04400 Supplied as indicated or as Grade M30C the casting equivalent of Monel 400 SMV 800 Smart Pressure Transmitter 9 Communications Protocols amp Diagnostics HART Protocol Honeywell Digitally Enhanced DE Version DE is a Honeywell proprietary protocol which provides HART 7 multivariable DE communications between Honeywell DE Power Supply enabled field devices and Hosts Voltage 10 8 Vdc to 42 4 Vdc at terminals Power Supply Load Maximum 1440 ohms See Figure 2 Voltage 15 Vdc to 42 4 Vdc at terminals Minimum Load 0 ohms For handheld communications a Load Maximum 900 ohms See Figure 2 minimum load of 250 ohms is required Standard Diagnostics SMV 800 top level diagnostics are reported as either critical or non critical and readabl
23. tance amean tenet teenie a peers te is required to support communications Loop resistance barrier resistance wire resistance Loop Ch ee ee a receiver resistance Resistance Pn Re ee ae A A eee peripheral device resistance ohms l E itr HART t H Operating TS a H Area opi 20 f t F DE H H Operating 0 d i i i Area i it i 1 Ii i i tot HART 0 10 8 116 3206 25 28 3 37 42 4 a a oes DE 0 15 22 1 27 9 33 6 37 9 42 4 For DE Rimax 35 Power Supply Voltage 15 For HART Rimax 45 6 Power Supply Voltage 10 8 Figure 2 Supply voltage and loop resistance chart amp calculations HART DE Protocols SMV 800 Smart Pressure Transmitter Performance Under Rated Conditions All Models Parameter Description Analog Output Digital Communications Two wire 4 to 20 mA HART amp DE Transmitters only Honeywell DE HART 7 protocol or FOUNDATION Fieldbus ITK 6 0 1 compliant All transmitters irrespective of protocol have polarity insensitive connection Output Failure Modes Honeywell Standard NAMUR NE 43 Compliance Normal Limits 3 8 20 8 mA 3 8 20 5 mA Failure Mode lt 3 6 mA and 2 21 0 mA lt 3 6 mA and 2 21 0 mA Supply Voltage Effect 0 005 span per volt Transmitter Turn on Time includes power up amp test algorithms HART or DE 5 0 sec Response Time DP delay time constant DE HART Analog Output 144mS Damping Time Constant
24. y validated hand held configuration device Measurement Types SMV is capable of mass flow measurements for liquids gases and superheated and saturated steam SMV 800 Smart Pressure Transmitter Personal Computer Configuration Honeywell s PC Based configuration Toolkit SCT3000 provides an easy way to configure the SMV800 DE devices SMV800 HART Device can be configured using Device Description based DCs Hosts and Asset Management Systems HART device can also be configured using PC based DTMs DTMs provide enhanced features like o Easy to use Flow Configuration o Units Preference Configurable Engineering units o Auto Calculation of Viscosity and Density Coefficients Auto Calculation of K User Beta Factor o Export and Import Configurations to from external file with predefine schema format o Summary Page Primary Element Compatibility Flow The SMV is compatible with and provides dynamic calculation capabilities for the following primary flow elements o Orifice Plates ASME MFC 3M amp AGA No 3 ISO 5167 GOST 8 586 Integral Orifice Small Bore Orifice ASME MFC 14M Conditional Orifice ISO5167 2003 Nozzles ASME MFC 3M ISO 5167 GOST 8 586 Venturi Tubes ASME MFC 3M ISO 5167 GOST Averaging Pitot Tubes V Cone Wafer Cone Wedge Oo Oo 0 0 0 0 0 Fixed Parameters Fixed Cd Y1 Viscosity Density are supported for user to customize the flow calculation Temperature The SMV also has the following temperature input
Download Pdf Manuals