Home
        22F-UM001 - Rockwell Automation
         Contents
1.                                                          Save a change to a parameter value     No  LED LED State Description    Run Direction   Steady Red ndicates drive is running and commanded motor direction   Status Flashing Red   Drive has been commanded to change direction  Indicates   actual motor direction while decelerating to zero    B Alphanumeric   Steady Red ndicates parameter number  parameter value  or fault code    Display Flashing Red  Single digit flashing indicates that digit can be edited    All digits flashing indicates a fault condition      Displayed Units   Steady Red ndicates the units of the parameter value being displayed       Program Status   Steady Red ndicates parameter value can be changed        Fault Status Flashing Red   Indicates drive is faulted      Pot Status Steady Green   Indicates potentiometer on Integral Keypad is active        Start Key Status   Steady Green   Indicates Start key on Integral Keypad is active   The Reverse key is also active unless disabled by A434  Reverse Disable     No    Key Name Description   e Escape Back one step in programming menu   Cancel a change to a parameter value and exit Program Mode    Select Advance one step in programming menu   Select a digit when viewing parameter value   Up Arrow Scroll through groups and parameters   TAD Increase decrease the value of a flashing digit   AR Down Arrow  Enter Advance one step in programming menu     PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User M
2.                     AK U0 RJ45 TR1  Terminating Resistor   end of network       kl or j d or    Customer supplied RJ45 male to RJ45 male  cables with wires connected at pins 4 and 5 only           Both the Master  M  and Slave  S  ports on the RJ45 Splitter  Cable operate as standard RS 485 ports in this configuration     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    D 4 RJ45 DSI Splitter Cable    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    A   AC Supply  Ground  1 5  Source  1 3  Ungrounded  1 3    Advanced Program Group  Parameters  3 19    Ambient Temperatures  1 2  Armored Cable  1 10   Auto Rstrt Tries Fault  4 4  Auxiliary Input Fault  4 3    B  Before Applying Power  2 1  2 2    C  Cable Length  1 13  Cable  Power  1 9  Catalog Number Explanation  P 4  CE Conformity  1 21  Checklist  Start Up  2 1  2 2  Circuit Breakers  Input  1 7  Comm Loss Fault  4 4    Command Sources for Start and  Speed  1 19    Communications Group Parameters   3 17  Contactors  Input  1 12  Control  2 and 3 Wire  1 15  1 18  Conventions  Manual  P 2  Cover  Opening  1 1  Cross Reference  Parameter  by Name  3 31    D  Dimensions   Drive  B 6   Minimum Clearances  1 2  Display  2 3  Display Group Parameters  3 3  Peston Systems  Ungrounded     Index    Drive Frame Size  P 2  B 6  Drive Grounding  1 5   Drive Overload Fault  4 4  Drive Ratings  P 4  A 1  DriveExecutive  3 1  Dri
3.                  Cause s  Indication Corrective Action   Digital input is not selected for   None Check  Digital Inx Sel   See    reversing control  page 3 13   Choose correct input  and program for reversing mode    Digital input is incorrectly None Check input wiring   See page 1 14    wired    Motor wiring is improperly None Switch two motor leads    phased for reverse    Reverse is disabled  None Check A434  Reverse Disable         Drive does not power up              Cause s  Indication Corrective Action  No input power to drive  None Check the power circuit    e Check the supply voltage    e Check all fuses and disconnects   Jumper between I O Terminals   None Install jumper or connect DC Bus    P2 and P1 not installed and or  DC Bus Inductor not  connected           Inductor        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    4 8 Troubleshooting    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Appendix A    Supplemental Drive Information    For information on     Drive  Fuse  amp  Circuit Breaker Ratings A 1  Specifications A 2             Drive  Fuse  amp  Circuit Breaker Ratings    The tables on the following pages provide recommended AC line input  fuse and circuit breaker information  See Fusing and Circuit Breakers  below for UL and IEC requirements  Sizes listed are the recommended  sizes based on 40   C  104   F  and the U S  N E C  Other coun
4.         PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 2 Installation Wiring    Mounting Considerations    e Mount the drive upright on a flat  vertical and level surface       Install on 35 mm DIN Rail  for frames A and B      or      Install with screws     Table 1 A Screw Mounting Recommendations    Minimum Panel Thickness  1 9 mm  0 0747 in      M4   8 32   e Protect the cooling fan by avoiding dust or metallic particles   e Do not expose to a corrosive atmosphere   e Protect from moisture and direct sunlight        Minimum Mounting Clearances  Refer to Appendix B for mounting dimensions     b gt      Screw Size   Mounting Torque    1 56 1 96 N m  14 17 Ib  in      a See Table 1 B             Ween N    A GF ni  T 76 2 mm  3 0 in            Va      76 2 mm  3 0 in                                                                                                i   0008 Mi A O  isa  Closest object that San  S taw  e   may obstruct air flow psd      80  m  through the drive  heat sink and chassis Powerriex  Pawerriex      6600   Il ooo LI  o Bo 00 Bo   lt  gt   76 2 mm  3 0 in       y        4 76 2 mm  3 0 in    v             Airflow lu    TITMA f TIT    Ambient Operating Temperatures    Table 1 B Enclosure and Clearance Requirements             Horizontal Clearance between drives     Ambient Temperature  Minimum Maximum   0 mm and greater  10  C  14  F  40  C  104  F    25 mm and greater  10  C  14  F  50  C  122  F       
5.     125 4 0 25RB005  11 0 15 0 32 2 68 32RB003                      Use MTE RB Series or equivalent inductors     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    B 4 Accessories and Dimensions    Table B F EMC Line Filters    Drive Ratings                                                                                  S Type Filter L Type Filter  Input Voltage kw HP Catalog Number  1  Catalog Number  3   120V 50 60 Hz 0 2 0 25 E 22F RF010 AL  1 Phase 0 4 0 5   22F RFO10 AL  0 75 1 0 Ni 22F RFO2S BL  1 1 15   22F RFO25 BL  240V 50 60 Hz 0 2 0 25  2  22F RFO10 AL  l Phase 0 4 0 5 B 22F RF010 AL  0 75 1 0 2  22F RF010 AL  1 5 2 0  2  22F RF025 BL  22 3 0  2  22F RF025 BL  240V 50 60 Hz 0 2 0 25 22F RF9P5 AS 22F RFOPS AL  3 Phase 0 4 0 5 22F RF9P5 AS 22F RF9P5 AL  0 75 1 0 22F RF9P5 AS 22F RF9P5 AL  15 2 0 22F RF9P5 AS 22F RF9P5 AL  22 3 0 22F RF021 BS 22F RFO21 BL  37 5 0 22F RF021 BS 22F RFO21 BL  55 75 22F RF039 CS 22F RF039 CL  75 10 0 22F RF039 CS 22F RF039 CL  480V 50 60 Hz 0 4 0 5 22F RFEPO AS 22F RF6PO AL  3 Phase 0 75 1 0 22F RF6P0 AS 22F RF6P0 AL  1 5 2 0 22F RFEPO AS 22F RF6PO AL  22 3 0 22F RFO12 BS 22F RFO12 BL  37 5 0 22F RFO12 BS 22F RFO12 BL  55 75 22F RF026 CS 22F RF026 CL  75 10 0 22F RF026 CS 22F RF026 CL  11 0 15 0 22F RFO26 CS 22F RF026 CL     1  This filter is suitable for use with a cable length up to 5 meters  16 feet  for Class A and  1 meter  3 feet  for Class B environments       These ratings can be 
6.    1  Check the motor and drive output   terminal wiring for a shorted   condition    Replace drive if fault cannot be   cleared    1  Clear the fault or cycle power to   the drive    Program the drive parameters as   needed     2     Check load requirements and A448   SW Current Trip  setting     Reduce load or extend Accel Time            Cycle power       Replace drive if fault cannot be  cleared       Cycle power      Check communications cabling     Check network adapter setting     Check external network status       If adapter was not intentionally  disconnected  check wiring to the  port  Replace wiring  port  expander  adapters or complete  drive as required    Check connection     An adapter was intentionally  disconnected    Turn off using C304  Comm Loss  Action     Set P112  Reset To Defalts  to  option 1    Reset Defaults        M       FOoONM      3     4     1  Cycle power     2  Replace drive if fault cannot be  cleared      i   See page 4 1 for a descri    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    Troubleshooting 4 5    Common Symptoms and Corrective Actions  Motor does not Start        Cause s     Indication    Corrective Action       No output voltage to the motor     None    Check the power circuit   e Check the supply voltage   e Check all fuses and disconnects     Check the motor   e Verify that the motor is  connected properly     Check the control input signals    e Verify that a Start signal
7.    2 xx User Manual  Publication 22F UM001D EN E    Integral EMI filters are available on 240V  1 Phase drives and 380V  3 Phase drives     Installation Wiring 1 23    EN61000 3 2    0 75 kW  1 HP  240V 1 Phase and 3 Phase drives and   0 4 kW  0 5 HP  240V 1 Phase drives are suitable for installation on  a private low voltage power network  Installations on a public low  voltage power network may require additional external harmonic  mitigation    Other drive ratings meet the current harmonic requirements of  EN61000 3 2 without additional external mitigation     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 24 Installation Wiring    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Chapter 2  Start Up    This chapter describes how to start up the PowerFlex 4M Drive  To  simplify drive setup  the most commonly programmed parameters are  organized in a single Basic Program Group     Important  Read the General Precautions section before proceeding     ATTENTION  Power must be applied to the drive to perform the  following start up procedures  Some of the voltages present are at  incoming line potential  To avoid electric shock hazard or damage to  equipment  only qualified service personnel should perform the  following procedure  Thoroughly read and understand the procedure  before beginning  If an event does not occur while performing this  procedure  Do Not Pr
8.    Clear an OverVoltage  UnderVoltage or Heatsink OvrTmp fault  without restarting the drive    1  Set A451  Auto Rstrt Tries  to a value other than    0       2  Set A452  Auto Rstrt Delay  to    0        Auto Restart  Reset Run     The Auto Restart feature provides the ability for the drive to  automatically perform a fault reset followed by a start attempt without  user or application intervention  This allows remote or    unattended     operation  Only certain faults are allowed to be reset  Certain faults   Type 2  that indicate possible drive component malfunction are not  resettable     Caution should be used when enabling this feature  since the drive will  attempt to issue its own start command based on user selected  programming     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Fault Descriptions    Troubleshooting 4 3    Table 4 4 Fault Types  Descriptions and Actions             No    Fault g Description Action  L  Z   F2  Auxiliary Input   Q    Auxiliary input interlock is open   1  Check remote wiring    2  Verify communications  programming for intentional fault    F3   Power Loss      Excessive DC Bus voltage ripple    1  Monitor the incoming line for  phase loss or line imbalance    2  Check input line fuse    F4   UnderVoltage   DC bus voltage fell below the Monitor the incoming AC line for low  minimum value  voltage or line power interruption    F5   OverVoltage Q   DC bus voltage exceeded Monitor the A
9.   1090     3 Phase Input  0   460V 3 Phase Output  with Filter  22F D1P5N113  0 4 0 5  11 5 340 528  1 5 1 8 3 140M C2E B25  100 C09 1655       22F D2PSN113  0 75  1 0   2 5 340 528 13 0  3 5 6 140M C2E B40  100 CO9 1655       22F DAP2N113  1 5  2 0  14 2 340 528  5 0 6 0 10 140M C2E C10  100 CO9 1655       22F D6PON113  2 2  3 0  6 0 340 528  5 2  6 2 10 140M C2E C10  100 C09 1655       22F D8P7N113  3 7  5 0  18 7 340 528  7 0  8 3 15 140M C2E C16  100 C12 1655          22F D013N114015 5  7 5   13 0 1340 528 112 9  15 4  25 140M D8E C20  100 C23  3441          22F D018N114    7 5  10 0   18 0 340 528  16 3  195 130 140M F8E C25  100 C23 13441          22F D024N114    11 0  15 0   24 0  340 528  21 7  261 40 140M F8E C32  100 C30  3441                             1  Catalog suffix ending with    4     such as N104 and N114  indicate that an internal brake IGBT is supplied     The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary  See Bulletin 140M Motor Protection  Circuit Breakers Application Ratings      3  Manual Self Protected  Type E  Combination Motor Controller  UL listed for 208 Wye or Delta  240 Wye or Delta  480Y   277 or 600Y 347  Not UL listed for use on 480V or 600V Delta Delta  corner ground  or high resistance ground systems                 PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Supplemental Drive Information A 3     4  When using a Manual Self Protected  Type E  Combination 
10.   Accel Time 1  Related Parameter s   P108  P110  1201  t202  A401  A410 A413    Sets the rate of acceleration for all speed increases     Maximum Freq             Accel Time   pcselfale  Values Default 10 0 Secs  Min Max  0 0 600 0 Secs  Display  0 1 Secs       P105  Maximum Freq        ry P109 or A401 le wl P110 or A402 ja    0  Accel Time x  Time  Decel Time x     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 12 Programming and Parameters    Basic Program Group  continued     P110  Decel Time 1  Related Parameter s   P108  P109  t201  t202  A402  A410 A413  Sets the rate of deceleration for all speed decreases        Maximum Freq             Decel Time   Decel Rate  Values Default 10 0 Secs  Min Max  0 1 600 0 Secs  Display  0 1 Secs       P105  Maximum Freq     Speed       ry P109 or A401 jq    P110 or A402  0  Accel Time x     le     Decel Time x     Time    P111  Motor OL Ret  Related Parameter s   P103    Enables disables the Motor Overload Retention function  When Enabled  the value held in the motor  overload counter is saved at power down and restored at power up  A change to this parameter  setting resets the counter        Options 0    Disabled     Default        1    Enabled       P112  Reset To Defalts       Stop drive before changing this parameter   Resets all parameter values to factory defaults        Options 0    Idle State     Default        1    Reset Defaults    e After the reset function is complet
11.   e Cycle power   e Set A450  Fault Clear  to option 1     Clear Faults       e Cycle digital input if t201   t202   Digital Inx Select  is set to option  7    Clear Fault           Incorrect programming    e P106  Start Source  is set to  option 0    Keypad    or option 5     RS485  DSI  Port       e 1201 1202  Digital Inx Select  is  set to option 5    Local    and the  input is active     None    Check parameter settings        Incorrect input wiring    See 1 15 for wiring examples    e 2 wire control requires Run  Forward  Run Reverse or Jog  input    e 3 wire control requires Start and  Stop inputs   e Stop input is always required     None    Wire inputs correctly and or install  jumper        Incorrect Sink Source DIP switch  setting        None       Set switch to match wiring scheme        Drive does not respond to changes in speed command        Cause s     Indication    Corrective Action       No value is coming from the  source of the command     The drive    Run    indicator is lit  and output is 0 Hz     Check 4012  Control Source  for   correct source    e Ifthe source is an analog input   check wiring and use a meter to  check for presence of signal    e Check d002  Commanded Freq    to verify correct command        Incorrect reference source is  being selected via remote  device or digital inputs        None       e Check d012  Control Source  for  correct source    e Check 014  Dig In Status  to  see if inputs are selecting an  alternate source  Verify setti
12.   on the splitter and configured for    Auto     default  or    Master      Parameter 9  Device Type  on the DSI keypads and Parameter 1   Adapter Cfg  on the Serial Converter are used to select the type   Auto   Master   Slave     e If two peripherals will be powered up at the same time  one must be  configured as the    Master    and connected to the Master port  M  and  the other must be connected as the    Slave    and connected to the  Slave port  S      PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    D 2 RJ45 DSI Splitter Cable    DSI Cable Accessories    RJ45 Splitter Cable     Catalog Number  AK U0 RJ45 SC1                                                       n Fa Slave Port  f HHH     pa  ARARA H    s  lt t Master Port  LI                                           PIN 1 PIN 8    RJ45 Two Position Terminal Block Adapter      Catalog Number  AK U0 RJ45 TB2P                                                                         TB2   PIN OK ge 8              TB1 Fa i   PIN 4  PIN 1    RJ45 Adapter with Integrated Termination Resistor      Catalog Number  AK U0 RJ45 TR1    N       PIN 1    PIN 8                                  PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    RJ45 DSI Splitter Cable D 3    Connecting an RS 485 Network             DSI Drives  s 5  SA  0  SM  O  CY  _ Q            Iz                    ooooq  Nee Go                                      
13.  0 1 kHz  100  96  92  _ 88   gt  9  8 80  S 76  81  Q 68    12 3 4 5 6 7 8 9 10  Carrier Frequency  kHz              A448  SW Current Trip  Related Parameter s   P103  Enables disables a software instantaneous  within 100 ms  current trip   Values Default 0 0  Disabled    Min Max  0 0  Drive Rated Amps x 2    Display  0 1 Amps    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 28 Programming and Parameters    Advanced Program Group  continued     A450  Fault Clear      Stop drive before changing this parameter   Resets a fault and clears the fault queue  Used primarily to clear a fault over network communications        Options 0    Ready Idle     Default        1    Reset Fault          2    Clear Buffer     Parameters d007 d009  Fault x Code      A451  Auto Rstrt Tries     Sets the maximum number of times the drive attempts to reset a fault and restart   Clear a Type 1 fault and restart the drive    1  Set A451  Auto Rstrt Tries  to a value other than    0       2  Set A452  Auto Rstrt Delay  to a value other than    O        Clear an OverVoltage  UnderVoltage or Heatsink OvrTmp fault without restarting the drive   1  Set A451  Auto Rstrt Tries  to a value other than    0      2  Set A452  Auto Rstrt Delay  to    0        ATTENTION  Equipment damage and or personal injury may result if this parameter  is used in an inappropriate application  Do not use this function without considering  applicable local  national and in
14.  018 18 0 7 5  10 0   025 25 0 5 5  7 5  024 24 0 10 0  15 0   033 33 0 7 5  10 0     Additional accessories  options and adapters are available  See Appendix B for details     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Chapter 1    Installation Wiring    This chapter provides information on mounting and wiring the  PowerFlex 4M Drive                             For information on    See page For information on    See page   Opening the Cover 1 1 Fuses and Circuit Breakers   1 7   Mounting Considerations 1 2 Power Wiring 1 9   AC Supply Source Considerations   1 3 VO Wiring 1 13  Recommendations   General Grounding Requirements   1 5 EMC Instructions 1 21             Most start up difficulties are the result of incorrect wiring  Every  precaution must be taken to assure that the wiring is done as instructed   All items must be read and understood before the actual installation  begins     ATTENTION  The following information is merely a guide for proper  installation  Rockwell Automation  Inc  cannot assume responsibility  for the compliance or the noncompliance to any code  national  local or  otherwise for the proper installation of this drive or associated  equipment  A hazard of personal injury and or equipment damage  exists if codes are ignored during installation     Opening the Cover  1  Press and hold in the tabs on each side of the cover     2  Pull the cover out and up to release                              
15.  2 13 4                                                    Input Power Conditioning    The drive is suitable for direct connection to input power within the rated  voltage of the drive  see Appendix A   Listed in Table 1 C are certain  input power conditions which mav cause component damage or  reduction in product life  If anv of the conditions exist  as described in  Table 1 C  install one of the devices listed under the heading Corrective  Action on the line side of the drive     Important  Only one device per branch circuit is required  It should be  mounted closest to the branch and sized to handle the total  current of the branch circuit     Table 1 C Input Power Conditions    Input Power Condition Corrective Action    Low Line Impedance  less than 1  line reactance   e Install Line Reactor      e or Isolation Transformer       Greater than 120 kVA supply transformer       Line has power factor correction capacitors       Line has frequent power interruptions       Line has intermittent noise spikes in excess of  6000V  lightning        Phase to ground voltage exceeds 125  of normal Remove MOV jumper to ground   line to line voltage e or Install Isolation Transformer  with grounded secondary if  necessary        Ungrounded distribution system        i   Refer to Appendix B for accessory ordering information     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring 1 5    General Grounding Requirements    
16.  2 A412 Advanced Program  3 14 Preset Freq 3 A413 Advanced Program  3 28 Process Display d010 Display   3 28 Process Factor A440 Advanced Program  3 29 Process Time Hi A439 Advanced Program  3 26 Process Time Lo A438 Advanced Program  3 17 Program Lock A458 Advanced Program  3 18 PWM Frequency A446 Advanced Program  3 17 Relay Out Level t222 Terminal Block  3 18 Relay Out Sel t221 Terminal Block  3 17 Reset To Defalts P112 Basic Program   3 6 Reverse Disable A434 Advanced Program  3 18 S Curve   A403 Advanced Program  3 3 Skip Freq Band A419 Advanced Program  3 25 Skip Frequency A418 Advanced Program  25 Slip Hertz   FLA A437 Advanced Program  3 5 Speed Reference P108 Basic Program   3 6 Start At PowerUp A433 Advanced Program  3 26 Start Source P106 Basic Program  3 24 Stop Mode P107 Basic Program  3 23 SW Current Trip A448 Advanced Program  3 23 Testpoint Data d019 Display   3 21 Testpoint Sel A459 Advanced Program  3 3   3 12   3 19   3 6   3 13   3 13   3 4   3 7   3 6   3 7   3 4   3 4   3 4   3 28   3 24   3 20   3 20   3 20   3 17   3 8   3 30   3 8   3 30   3 8   3 8   3 8   3 12    3 31    SE  mo      919    je  Ido       joo  loo       so  19  ico       joo  bed    K g  ES    joo  ba       Ke  re          e Ie  IND    D       9  n gt   on    Io  Po  in       joo  loo  IS    eo  Ino  INI       Ie  D       ico  Ion    Qo  Mo       Io  n gt   jis    Io  In  IS       Qo  Ino  NJ    xo  is       a  Po  In       joo     ss   Ino  EN       ad  ko    jid  is       Qo  Ino  I
17.  200   240V AC   10     3 Phase Input  0   230V 3 Phase Output  22F B1P6N103 0 2  0 25   1 6 180 265  0 8 1 9 3 140M C2E B25  100 C09 1655       22F B2P5N103  0 4  0 5  12 5 180 265  1 2  2 7 6 140M C2E B40   100 C09 1655       22F B4P2N103  0 75  1 0  14 2 180 265  2 1 14 9 10 140M C2E B63 100 CO9 1655       22F B8PON103  1 5  2 0  8 0 180 265  4 0 19 5 15 140M C2E C16  100 C12 1655       22F BO12N103  2 2  3 0   12 0 180 265  6 3  15 0  25 140M C2E C20   100 C23 1655       22F BO17N103  3 7  5 0   17 5 180 265  8 8  21 1  35 140M F8E C25   100 C23 1655       22F BO25N104 1 5 5  7 5   25 0 180 265  11 4  27 2  45 140M F8E C32  100 C37  3441       22F BO33N104 1 7 5 10 0  33 0  180 265  16 1  38 5  60 140M F8E C45  100 C60 3441  380   480V AC   10     3 Phase Input  0   460V 3 Phase Output  22F D1P5N103 10 4  0 5  11 5 340 528  1 5  1 8 3 140M C2E B25 100 CO9 1655       22F D2PS5N103  0 75  1 0   2 5 340 528 13 0  3 5 6 140M C2E B40 100 CO9 1655       22F D4P2N103  1 5  2 0  14 2 340 528 5 0 6 0 10 140M C2E C10  100 C09 1655       22F D6PON103  2 2  3 0  16 0 340 528  5 2 6 2 10 140M C2E C10   100 C09 1655       22F D8P7N103 13 7  5 0  18 7 340 528  7 0  8 3 15 140M C2E C16  100 C12 1655       22F D013N104    5 5  7 5   13 0 340 528  129  15 4 125 140M D8E C20  100 C23 13441       22F DO18N10411 7 5  10 0   18 0 1340 528 116 3  19 5  30 140M F8E C25  100 C23 13441          22F DO24N104 1 11 0  15 0  24 0      340 528  21 7  26 1  40 140M F8E C32  100 C30 3441  380   480V AC  
18.  Drive enclosure is rated IP20  NEMA UL Type Open     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    A    Installation Wiring 1 3    Storage  e Store within an ambient temperature range of  40   to  85  C     e Store within a relative humidity range of 0  to 95    non condensing     e Do not expose to a corrosive atmosphere     AC Supply Source Considerations   Ungrounded Distribution Systems   ATTENTION  PowerFlex 4M drives contain protective MOVs that  are referenced to ground  These devices must be disconnected if the    drive is installed on an ungrounded or resistive grounded distribution  system     Disconnecting MOVs    To prevent drive damage  the MOVs connected to ground shall be  disconnected if the drive is installed on an ungrounded distribution  system where the line to ground voltages on any phase could exceed  125  of the nominal line to line voltage  To disconnect these devices   remove the jumper shown in the Figures 1 1 and 1 2     1  Turn the screw counterclockwise to loosen   2  Pull the jumper completely out of the drive chassis     3  Tighten the screw to keep it in place     Figure 1 1 Jumper Location  Frame A shown     Important   Tighten screw after  jumper removal                    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring    Figure 1 2 Phase to Ground MOV Removal    Three Phase ne On  AC Input SiL2  T L3    l Jumper 1
19.  Input       4 20mA Input     e  e  iile  c I  14 Common        44o  ommon                  115  1     o B       Analog Input  PTC  For Drive Fault       Wire the PTC and External Resistor  typically matched to the PTC Hot  Resistance  to I O Terminals 12  13  14     Wire R2 R3 Relay Output  SRC  to I O Terminals 5  amp  11   1201  Digital Int Sel    3    Aux Fault      1221  Relay Out Sel    10    Above Anlg V    1222  Relay Out Level      Voltage Trip                               R2                         Re       y  PTC  hot   mss a 100      P Rete  hat    Re  Retc B los                         PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    1 16    Connection Example    Input    2 Wire SRC Control    Non Reversing    Installation Wiring    Internal Supply  SRC     External Supply  SRC                                                                                                                                                              P106  Start Source    2  3 lo 01  or 4 B  02 02  Input must be active for Sona ee  the drive to run  When P 04  input is opened  the drive  will stop as specified bv  24V Common  P107  Stop Mode    If desired  a User Supplied ee  24V DC power source can Each digital input draws 6 mA   be used  Refer to the     External Supply  SRC      example   2 Wire SNK Control   Internal Supply  SNK   Non Reversing    lot  9   02  Stop Run     04  2 Wire SRC Control   Internal Supply  SRC  Exter
20.  Voltage kW HP Current  A    Panel Mount Size  480V 50 60 Hz 0 4 0 5 15 22F D1P5N113 A  3 Phase 075 lto 125 22F D2P5N113 A  With Integral EMC Filter      1 5 2 0 4 2 22F D4P2N113 A  2 2 3 0 6 0 22F D6P0N113 B  3 7 5 0 8 7 22F D8P7N113 B  5 5 7 5 13 0 22F D013N114    c  75 10 0  18 0 22F DO18N114 3  c  11 0 15 0  24 0 22F D024N114    C                    1  This filter is suitable for use with a cable length of up to 5 meters  16 feet  for EN55011 class A and  1 meter  3 feet  for EN55011 class B environment   2  This filter is suitable for use with a cable length of up to 10 meters  33 feet  for EN61800 3 Second  environment    3  Catalog suffix ending with  4   such as N104 and N11A  indicate that an internal brake IGBT is supplied           Table B C Dynamic Brake Modules                Drive Ratings  Minimum   Input Voltage kW HP Resistance Q   Catalog Number  1   2   240V 50 60 Hz 5 5 7 5 18 AK R2 030P1K2  3 Phase 75 10 0 12 AK R2 030P1K2  480V 50 60 Hz 5 5 7 5 60 AK R2 120P1K2  3 Phase   7 5 10 0 39 AK R2 120P1K2   11 0 15 0 36 AK R2 120P1K20                  1  The resistors listed in this table are rated for 5  duty cycle       Use of Rockwell resistors is always recommended  The resistors listed have been carefully  selected for optimizing performance in a varity of applications  Alternative resistors may be used   however care must be taken when making a selection  Refer to the PowerFlex Dynamic Braking  Resistor Calculator  publication PFLEX AT001         3  Require
21.  and Editing Parameters         2 4  About Parameters                 0   3 1  Parameter Organization                3 2  Display Group    3 3  Basic Program Group                  3 8  Terminal Block Group                3 13  Communications Group               3 17  Advanced Program Group             3 19    Parameter Cross Reference     by Name   3 31    Drive  Status sie na ei hii aes 4 1  Faults   oath one Klacid b cha  4 1  Fault Descriptions                    4 3    Common Symptoms and Corrective Actions      4 5    Supplemental Drive Information    Drive  Fuse  amp  Circuit Breaker Ratings    A 1    Accessories and Dimensions    Specifications                 00000  A 2  Product Selection                 04  B 1  Product Dimensions                   B 6    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    ii Table of Contents    Appendix C RS485  DSI  Protocol    Network Wiring  LL C 1  Parameter Configuration                C 3  Supported Modbus Function Codes       C 3  Writing  06  Logic Command Data       C 4  Writing  06  Reference                 C 5  Reading  03  Logic Status Data          C 5  Reading  03  Feedback                 C 6  Reading  03  Drive Error Codes          C 6  Reading  03  and Writing  06  Drive  Parameters IL Akbar e C 7  Additional Information                 C 7  Appendix D RJ45 DSI Splitter Cable  Connectivity Guidelines                D 1  DSI Cable Accessories                 D 2  C
22.  contents of this manual  in whole or in part  without written  permission of Rockwell Automation  Inc  is prohibited     Throughout this manual  when necessary we use notes to make you aware of safety  considerations     WARNING  Identifies information about practices or circumstances  that can cause an explosion in a hazardous environment  which may  lead to personal injury or death  property damage  or economic loss      gt     Important  Identifies information that is critical for successful application and  understanding of the product     ATTENTION  Identifies information about practices or circumstances  that can lead to personal injury or death  property damage  or economic  loss  Attentions help you    e identify a hazard   e avoid the hazard   e recognize the consequences    Shock Hazard labels may be located on or inside the equipment  e g    drive or motor  to alert people that dangerous voltage may be present     Burn Hazard labels may be located on or inside the equipment  e g    drive or motor  to alert people that surfaces may be at dangerous  temperatures      gt ei D    Allen Bradley  Rockwell Automation  and PowerFlex are registered trademarks of Rockwell Automation  Inc   DriveExplorer  DriveExecutive  and SCANport are trademarks of Rockwell Automation  Inc   PLC is a registered trademark of Rockwell Automation  Inc     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Summary of Changes    The information below summarizes the changes 
23.  f g h i j k Weight  A 72 0 59 0 174 0   1516      5 4      5 4   5 2     136 0   90 9 81 3 1 6  3 5    283     2 32     6 85     5 97     0 21     0 21     0 20   5 35     3 58     3 20   B 100 89 0 174 0   1685      5 4      5 4   5 2 0 5 136 0   90 9 81 3 2 1  4 6    3 94     3 50     6 85     6 44     0 21     0 21     0 20     0 02     5 35     3 58     3 20   Cc 130 0   116 0   260 0   2475      5 5      55 60 1 0 180 0   128 7      4 8  10 6    5 12     4 57     10 24    9 74     0 22     0 22     0 24     0 04     7 09     5 07                                            PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Accessories and Dimensions B 7                                                                                                    Figure B 2 Dynamic Brake Modules     Dimensions are in millimeters and  inches   Frame B  61 0 _   310   240  59 0   1 22     2 32   b en  a  386 0 405 0   15 20   15 94   i  ir  GO  a I  Frame Catalog Number  B AK R2 030P1K2  AK R2 120P1K2    Figure B 3 Recommended External Brake Resistor Circuitry          T  L3   Three Phase S  L2  AC Input RUI                                     U 000o L  Hee or R          Note  Applicable to Frame C drives only     Power Off Power On    anya  p    DB Resistor Thermostat             jw    Power Source    PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    B 8 Accessories and Dimensions    F
24.  is  present  If 2 Wire control is used   verify that either the Run  Forward or Run Reverse signal  is active  but not both    e Verify that I O Terminal 01 is  active    e Verify that P106  Start Source   matches your configuration    e Verify that A434  Reverse  Disable  is not prohibiting  movement              Improper boost setting at initial  start up     None       Set A453  Boost Select  to option 2     35 0  VT           Drive is Faulted    Flashing red status light       Clear fault    e Press Stop   e Cycle power   e Set A450  Fault Clear  to option 1     Clear Faults       e Cycle digital input if t201   t202   Digital Inx Sel  is set to option 7     Clear Fault           Drive does not Start from Integral Keypad        Cause s     Indication    Corrective Action       Integral keypad is not enabled     Green LED above Start key is  not illuminated     e Set parameter P106  Start  Source  to option 0    Keypad       e Set parameter t201   t202  Digital  Inx Select  to option 5    Local     and activate the input        I O Terminal 01    Stop    input is  not present        None       Wire inputs correctly and or install  jumper        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    4 6 Troubleshooting    Drive does not Start from Start or Run Inputs wired to the terminal block        Cause s     Indication    Corrective Action       Drive is Faulted    Flashing red status light    Clear fault    e Press Stop 
25.  is important to  connect I O Terminal 14 common together for all drives  I O Terminal 14  common and I O Terminal 13  potentiometer wiper  should be daisy chained to  each drive  All drives must be powered up for the analog signal to be read  correctly        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring    Start and Speed Reference Control    The drive speed command can be obtained from a number of different  sources  The source is normally determined by P108  Speed Reference    However  when t201 or t202 Digital Inx Sel is set to option 2  4  5 or 6     and the digital input is active  t201 or t202 will override the speed    reference commanded by P108  Speed Reference   See the chart below    for the override priority                Jog Input  Enabled and Active   t201 or t202   2    Drive will Start and Run at Jog Speed     Direction comes from  Terminal 03 Dir Run REV             Local Remote Input  Enabled and Active   1201 or t202   5       Start  Speed and Direction commands  come from Integral Keypad              Comm Select Input  Enabled and Active   1201 or t202  6        Start  Speed and Direction commands  come from RS485  DSI  port              P108  Speed Reference   740r5       Run as specified bv  P108  Speed Reference      Start and Direction commands come  from P106  Start Source                   1201   t202  Preset Inputs Active    Yes       Run as specified by  A411 A413  Preset 
26.  no sensitive circuits   the use of shielded wire may not be necessary  but is always recommended     I O Terminal Block    Table 1 H I O Terminal Block Specifications    Maximum Wire Size    Minimum Wire Size  1  Torque    1 3 mm   16 AWG  0 2 mm   24 AWG  0 5 0 8 N m  4 4 7 Ib  in          1   Maximum minimum sizes that the terminal block will accept   these are not  recommendations     Maximum Control Wire Recommendations    Do not exceed control wiring length of 30 meters  100 feet   Control  signal cable length is highly dependent on electrical environment and  installation practices  To improve noise immunity  the I O terminal block  Common must be connected to ground terminal protective earth  If using  the RS485  DSI  port  I O Terminal 16 should also be connected to  ground terminal protective earth     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 14 Installation Wiring    Figure 1 5 Control Wiring Block Diagram     Important  I O Terminal 01 is always a coast to stop input except                                                                                                                                                                                                                                                                                           when P106  Start Source  is set to  3 Wire  control  In three wire istert Source    vo ee 0  control  I O Terminal 01 is controlled by P107  Stop Mode   All
27.  or A401 jq    P110 or A402  0  Accel Time x     ha     Decel Time x     Time    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 20 Programming and Parameters    Advanced Program Group  continued     A403  S Curve       Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve  Time  is added  1 2 at the beginning and 1 2 at the end of the ramp                 Values Default 0   Disabled   Min Max  0 100   Display  1   Example   Accel Time   10 Seconds 50  S Curve  S Curve Setting   50  Target             S Curve Time   10 x 0 5   5 Seconds  Total Time   10   5   15 Seconds l    l  Tigi         4 1 2 S Curve Time   4 Accel Time oe 1 2 S Curve Time p     2 5 Seconds 10 Seconds 2 5 Seconds    4 Total Time to Accelerate   Accel Time   S Curve Time  gt                                    A404  Jog Frequency  Related Parameter s   P105  t201  t202  A405  Sets the output frequency when a jog command is issued   Values Default 10 0 Hz  Min Max  0 0 P 105  Maximum Freq   Display  0 1 Hz  A405  Jog Accel Decel  Related Parameter s   1201  t202  A404  Sets the acceleration and deceleration time when a jog command is issued   Values Default 10 0 Secs  Min Max  0 1 600 0 Secs  Display  0 1 Secs  A409  Internal Freq  Related Parameter s   P108    Provides the frequency command to the drive when P108  Speed Reference  is set to 1    Internal  Freq     When enabled  this parameter will change the freq
28.  other op mop  Keypad Per P107 Coast  stop sources are controlled by P107  Stop Mode      3 Wire Per P107 Per P107  Important  The drive is shipped with a jumper installed between I O 2 Wire Per P107 Coast  Terminals 01 and 11  Remove this jumper when using I O Terminal RS485 Port Per P107 Coast  01 as a stop or enable input   g Two wire control shown  For three wire control use a momentary 240V AG  input ar on I O Terminal 02 to command a start  Use a Resistive  30A   30A   30A  maintained input oo for I O Terminal 03 to change direction  Inductive  054   05A   0 5A   1  Typical Typical  SRC Wiring SNK Wiring  g1 Stop ta  Q alc  nD  lt  02 Start Run FWD BAG oo  03 Direction Run REV o ot  SNK o Ap SRC 04 Digital Common  Vv 05 Digital Input 1 oo ot  Digital Input 2  Potentiometer 06 0 o  must be  24V 424V DC  1 10k ohm Seed ti  2 Watt Min  i HOV J 12  10V DC ii    TI l  13 0 10V In l  Relav N O  l li Analog Common i l  Ri 14 G  Relav Common R2 3   li 15 4 20mA In  Relav N C  R3 16 RS485 Shield  No    Signal Default Description Param  R1   Relay N O  Fault Normally open contact for output relay  1221  R2   Relay Common i Common for output relay   R3__  Relay N C  Fault Normally closed contact for output relay  1221  Sink Source DIP Switch Source  SRC  Pha be wired as Sink  SNK  or Source  SRC  via DIP Switch   1  The factory installed jumper or a normally closed input  1   01   Stop Coast must be present for the drive to start  P106  02   Start Run FWD Not Active   P106  P107  
29.  the changes to the PowerFlex 4M  User Manual since the February 2007 release     Manual Updates                Description of New or Updated Information Page s   Input description and attention text for Multiple Digital Input Connection 1 18  example corrected    Description for option 21 of parameter 1221  Relay Out Sel  corrected  3 15  Invalid catalog number for L Type Filter deleted  B 4  B 10  Graphic for the    Connecting an RS 485 Network    section corrected D 3    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Preface    Chapter 1    Chapter 2    Chapter 3    Chapter 4    Appendix A    Appendix B    Overview    Installation Wiring    Start Up    Table of Contents    Programming and Parameters    Troubleshooting    Who Should Use this Manual           P 1  Reference Materials                   P 1  Manual Conventions                  P 2  Drive Frame Sizes       000 000000  P 2  General Precautions                   P 3  Catalog Number Explanation            P 4  Opening the Cover         000 00000  l 1  Mounting Considerations               l 2  AC Supplv Source Considerations        l 3  General Grounding Requirements        l 5  Fuses and Circuit Breakers              l 7  Power Wiring LL 1 9  T O Wiring Recommendations          1 13  Start and Speed Reference Control      1 19  EMC Instructions                    1 21  Prepare For Drive Start Up             2 1  Integral Keypad                  00  2 3  Viewing
30.  the safety ground terminal  The  conduit box option may be used with a cable clamp for a grounding point  for the cable shield     When shielded cable is used for control and signal wiring  the shield  should be grounded at the source end only  not at the drive end     RFI Filter Grounding    Using single phase drives with integral filter  or an external filter with  any drive rating  may result in relatively high ground leakage currents   Therefore  the filter must only be used in installations with grounded  AC supply systems and be permanently installed and solidly  grounded  bonded  to the building power distribution ground  Ensure  that the incoming supply neutral is solidly connected  bonded  to the  same building power distribution ground  Grounding must not rely on  flexible cables and should not include any form of plug or socket that  would permit inadvertent disconnection  Some local codes may require  redundant ground connections  The integrity of all connections should be  periodically checked     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring 1 7    Fuses and Circuit Breakers    The PowerFlex 4M does not provide branch short circuit protection  This  product should be installed with either input fuses or an input circuit  breaker  National and local industrial safety regulations and or electrical  codes may determine additional requirements for these installations     ATTENTION  To guard a
31.  use this function without considering  applicable local  national and international codes  standards  regulations or industry  guidelines        Options 0    Disabled     Default        1    Enabled       A434  Reverse Disable  Related Parameter s   d006      Stop drive before changing this parameter     Enables disables the function that allows the direction of motor rotation to be changed  The reverse  command may come from a digital command  the keypad or a serial command  All reverse inputs  including two wire Run Reverse will be ignored with reverse disabled        Options 0    Rev Enabled     Default        1    Rev Disabled       A435  Flying Start En     Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM        Options 0    Disabled     Default        1    Enabled       PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 25    Advanced Program Group  continued     A436  Compensation     Enables disables correction options that may improve problems with motor instability        Options 0    Disabled       1    Electrical     Default  Some drive motor combinations have inherent instabilities  which are exhibited as non sinusodial motor currents  This  setting attempts to correct this condition           2    Mechanical    Some motor load combinations have mechanical resonances  which can be excited by the drive current regulator  This  setting slows down th
32. 04 f ovoo  P_00004       mA mA  to x   Po   o   0 U g S   Ue      p_   E A A A  JO  TD  ea oy   Controller I ope See                        For information regarding DeviceNet or other communication protocols     refer to the appropriate user manual     Network Wiring  Network wiring consists of a shielded 2 conductor cable that is  daisy chained from node to node     Figure C 1 Network Wiring Diagram    PowerFlex 4M PowerFlex 4M PowerFlex 4M  2 Node  n        Master lode Node FRONT  TxRxD      4 eo NDE 4     DPRD 4 120 ohm resistor  120 ohm resistor  TxRxD  _t 5 TxRxD  5 TxRxD   PIN 1  Shield Shield Shield PIN 8    NOTE  The shield should be grounded at ONLY ONE location     01 02 03 04 05 06    01 02 03 04 05 06                                                                         DOPOD   11 12 18114 15 16   OOGOSG   EEF os   U    U  lt    AK U0 RJ45 TB2P  TXAXD     G TxXRXD  x    TXAXD      GA TR xD                                 Terminal block for Frame A and B drives  is shown here     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    RS485  DSI  Protocol    Only pins 4 and 5 on the RJ45 plug should be wired  The other pins on  the PowerFlex 4M RJ45 socket contain power  etc  for other Rockwell  Automation peripheral devices and must not be connected     Wiring terminations on the master controller will vary depending on the  master controller used and    TxRxD        and    TxRxD     are shown for  illustration purpos
33. 1  t202       Sets the analog input level that corresponds to P104  Minimum Freq  if a 4 20mA input is used by  P108  Speed Reference     Analog inversion can be accomplished by setting this value larger than t214  Anlg In4 20mA Hi  or by  setting t201   1202  Digital Inx Sel  to option 15  Anlg Invert                 Values Default 0 0   Min Max  0 0 100 0   Display  0 1     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 15    Terminal Block Group  continued     t214  Anlg In4 20mA Hi  Related Parameter s   d021  P105  P108  1201  t202  Sets the analog input level that corresponds to P105  Maximum Freq  if a 4 20mA input is used by  P108  Speed Reference      Analog inversion can be accomplished by setting this value smaller than t213  Anlg In4 20mA Lo  or  by setting t201   t202  Digital Inx Sel  to option 15  Anlg Invert                                                                    Values Default 100 0   Min Max  0 0 100 0   Display  0 1   t221  Relay Out Sel  Related Parameter s   P103  1222  A451  Sets the condition that changes the state of the output relay contacts   Options 0    Ready Fault    Relay changes state when power is applied  This indicates   Default  that the drive is ready for operation  Relay returns drive to  shelf state when power is removed or a fault occurs    1    At Frequency    Drive reaches commanded frequency    2    MotorRunning    Motor is receiving power fro
34. 1202    Displays the active source of the Start Command and Speed Command which are normally defined  by the settings of P106  Start Source  and P108  Speed Reference  but may be overridden by digital  inputs  Refer to the flowcharts on pages 1 19 and 1 20 for details        WANNA  is                   Start Command Digit 0  0   Keypad  1  3 Wire  2 2 Wire  3   2 Wire Level Sensitive  4   2 Wire High Speed  5   RS485  DSI  Port  9   Jog  Speed Command Digit 1  0   Drive Potentiometer  1   A409  Internal Freq   2 0 10V ee Potentiometer  3   4 20mA In npu  4   A410   A413  Preset Freq x    t201   t202  Digital Inx Sel  must be set to 4   5   RS485  DSI  Port                         9   Jog Freq  Reserved Digit 2  Reserved Digit 3                Values Default Read Only  Min Max  0 9  Display  1  d013  Conirl In Status  Related Parameter s   4002  P104  P10    Status of the control terminal block control inputs   Important  Actual control commands may come from a source other than the control terminal block                                      GG   1   Input Present  0   Input Not Present  Start   Run FWD Input  I O Terminal 02  Bit 0  Direction   Run REV Input  I O Terminal 03  Bit 1  Stop Input    I O Terminal 01  Bit 2          Dynamic Brake Transistor ON  Frame C only    Reserved  Other Frames  _ Bit 3          The stop input must be present in order to start the drive   When this bit is a 1 the drive can be started   When this bit is a 0 the drive will stop              Val
35. 140M C2E C10   100 C09 1655  0 75  1 0 15 140M C2E C16   100 C12 1655  1 5  2 0  35 140M D8E C25   100 C23 1655  2 2  3 0  40 140M F8E C32   100 C30 1655  240V AC  0 2  0 25 3 140M C2E B25   100 C09 1655  3 Phase 0 4  0 5  6 140M C2E B40   100 C09 1655  0 75  1 0 10 140M C2E B63   100 C09 1655  1 5  2 0  15 140M C2E C16   100 C12 1655  2 2  3 0  25 140M D8E C20   100 C23 1655  3 7  5 0  35 140M F8E C25   100 C23 1655  5 5  7 5  45 140M F8E C32   100 C37 3441  7 5  10 0  60 140M F8E C45   100 C60 3441  480V AC   0 4  0 5  3 140M C2E B25   100 C09 1655  3 Phase 0 75  1 0  6 140M C2E B40   100 C09 1655  1 5  2 0  10 140M C2E C10   100 C09 1655  2 2  3 0  10 140M C2E C10   100 C09 1655  3 7  5 0  15 140M C2E C16   100 C12 1655  5 5  7 5  25 140M D8E C20   100 C23 3441  7 5  10 0  30 140M F8E C25   100 C23 3441  11 0  15 0  50 140M F8E C32   100 C30 3441   1   Recommended Fuse Type  UL Class J  RK1  T or Type BS88  600V  550V  or equivalent     The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary  See Bulletin 140M       Motor Protection Circuit Breakers Application Ratings     3  Manual Self Protected  Type E  Combination Motor Controller  UL listed for 208 Wye or Delta  240  Wye or Delta  480Y 277 or 600Y 347  Not UL listed for use on 480V or 600V Delta Delta  corner  ground  or high resistance ground systems          When using a Manual Self Protected  Type E  Combination Motor Controller  the drive must be  installed in a ventilated or non ventilated 
36. 3    10V In Ctrl    Selects 0 10V or  10V control as the frequency reference   202 Start source is not changed   Options 44    20mA In Ctrl    Selects 4 20mA control as the frequency reference  Start   Cont   source is not changed    15  Anlg Invert  Inverts the scaling of the analog input levels set in    t211  Anlg In 0 10V Lo  and 1212  Anlg In 0 10V Hi  or  1213  Anlg In4 20mA Lo  and 1214  Anlg In4 20mA Hil        16 27 Reserved    t211  Anlg In 0 10V Lo  Related Parameter s   4020  P104  P108  1201  t202  Sets the analog input level that corresponds to P104  Minimum Freq  if a 0 10V input is used by P108   Speed Reference      Analog inversion can be accomplished by setting this value larger than t212  Anlg In 0 10V Hi  or by  setting t201   1202  Digital Inx Sel  to option 15  Anlg Invert                    Values Default 0 0   Min Max  0 0 100 0   Display  0 1        P105  Maximum Freq     P104  Minimum Freq        1211  Anlg In 0 10V Lo  t212  Anlg In 0 10V Hi     t212  Anlg In 0 10V Hi  Related Parameter s   d020  P105  P108  1201  1202  Sets the analog input level that corresponds to P105  Maximum Freq  if a 0 10V input is used by P108   Speed Reference      Analog inversion can be accomplished by setting this value smaller than t211  Anlg In 0 10V Lo  or by  setting t201   1202  Digital Inx Sel  to option 15  Anlg Invert                    Values Default 100 0   Min Max  0 0 100 0   Display  0 1   t213  Anlg In4 20mA Lo  Related Parameter s   d021  P104  P108  120
37. 3150 MCM SLC Modbus scanner  and 8193 for others   e g  Panel Views      PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    C 4 RS485  DSI  Protocol    Writing  06  Logic Command Data    The PowerFlex 4M drive can be controlled via the network bv sending  Function Code 06 writes to register address 8192  Logic Command    P106  Start Source  must be set to 5  RS485  DSI  Port    in order to    accept the commands     In addition to being written  register address 8192 can be read using    Function Code 03     Logic Command       Address  Decimal    Bit s   0    Description  1   Stop  0   Not Stop       1   Start  0   Not Start       1   Jog  0   No Jog       1  2  3    1   Clear Faults  0   Not Clear Faults       5 4    00   No Command       01   Forward Command       10   Reverse Command       11   No Command       Controls the C form relay when the value of parameter 1221 is  set to 13   1   On  0   Off       1   MOP Increment  0   Not Increment       98  8192    00   No Command       01   Accel Rate 1 Enable       10   Accel Rate 2 Enable       11   Hold Accel Rate Selected       11 10    00   No Command       01   Decel Rate 1 Enable       10   Decel Rate 2 Enable       11   Hold Decel Rate Selected       14 13 12    000   No Command       001   Freq  Source   P108  Speed Reference        010   Freq  Source   A409  Internal Freq        011   Freq  Source   Comms  Addr 8193        100   A410  Preset Freq 0        101   A411  
38. 4 22 Reserved             PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 16 Programming and Parameters    Terminal Block Group  continued     t222  Relay Out Level   X9  32 bit parameter    Sets the trip point for the digital output relay if the value of t221  Relay Out Sel  is 6  7  8  10 or 11    t221 Setting         222 Min Max    6 0 400 Hz  7 0 180    8 0 815 Volts  10 0 100     0 1    Related Parameter s   t221          Values Default 0 0  Min Max  As above  Displav  0 1       PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 17    Communications Group    C301  Language     Selects the language displayed by the remote communications option        Options 1    English     Default        2    Second Lang     Reserved     C302  Comm Data Rate  Related Parameter s   d015  Sets the serial port rate for the RS485  DSI  port   Important  Power to drive must be cycled before any changes will affect drive operation        Options 0    1200                      1    2400     2    4800     3    9600     Default   4    19 2K     5    38 4K     C303  Comm Node Addr  Related Parameter s   d015    Sets the drive node address for the RS485  DSI  port if using a network connection   Important  Power to drive must be cycled before any changes will affect drive operation              Values Default 100  Min Max  1 247  Display  1  C304  Comm Loss Action  Re
39. Allen Bradley       Adjustable  Frequency AC  Drive    FRN 1 Xx   2 XX    User Manual          Rockwell  Automation       Important User Information    Solid state equipment has operational characteristics differing from those of  electromechanical equipment  Safety Guidelines for the Application  Installation  and Maintenance of Solid State Controls  Publication SGI 1 1 available from your  local Rockwell Automation sales office or online at  http   www rockwellautomation com literature  describes some important  differences between solid state equipment and hard wired electromechanical  devices  Because of this difference  and also because of the wide variety of uses for  solid state equipment  all persons responsible for applying this equipment must  satisfy themselves that each intended application of this equipment is acceptable     In no event will Rockwell Automation  Inc  be responsible or liable for indirect or  consequential damages resulting from the use or application of this equipment     The examples and diagrams in this manual are included solely for illustrative  purposes  Because of the many variables and requirements associated with any  particular installation  Rockwell Automation  Inc  cannot assume responsibility or  liability for actual use based on the examples and diagrams     No patent liability is assumed by Rockwell Automation  Inc  with respect to use of  information  circuits  equipment  or software described in this manual     Reproduction of the
40. C line for high line  maximum value  voltage or transient conditions  Bus   overvoltage can also be caused by  motor regeneration  Extend the  decel time or install dynamic brake  option    F6 Motor Stalled     Drive is unable to accelerate Increase P109 and or A402  Accel  motor  Time x  or reduce load so drive   output current does not exceed the  current set by parameter A441   Current Limit     F7  Motor Overload    4   Internal electronic overload trip    1  An excessive motor load exists   Reduce load so drive output  current does not exceed the  current set by parameter P103   Motor OL Current     2  Verify A453  Boost Select   setting   F8   Heatsink Q    Heatsink temperature exceeds a   1  Check for blocked or dirty heat   OvrTmp predefined value  sink fins  Verify that ambient  temperature has not exceeded  40  C  104  F  for IP 30 NEMA 1 UL  Type 1 installations or 50  C  122  F   for IP20 Open type installations    2  Check fan    F12  HW OverCurrent       The drive output current has Check programming  Check for  exceeded the hardware current   excess load  improper A453  Boost  limit  Select  setting  DC brake volts set   too high or other causes of excess  current    F13   Ground Fault     A current path to earth ground   Check the motor and external wiring  has been detected at one or to the drive output terminals for a  more of the drive output grounded condition   terminals    i  See page 4 1 for a description of fault types        PowerFlex 4M Adjustable Fr
41. Code  Fault 3 Code  Fault Clear   Flying Start En  Internal Freq   Jog Accel Decel  Jog Frequency  Language  Maximum Freq  Maximum Voltage  Minimum Freq  Motor NP FLA  Motor NP Hertz  Motor NP Volts  Motor OL Current  Motor OL Ret    P109  A401  020  021    Basic Program  Advanced Program  Display   Display   Terminal Block  Terminal Block  Terminal Block  Terminal Block  Advanced Program  Advanced Program  Advanced Program  Advanced Program  Communications  Communications  Communications  Communications  Communications  Display  Communications  Display   Advanced Program  Display   Display   Display   Advanced Program  Advanced Program  Advanced Program  Advanced Program  Advanced Program  Display   Basic Program  Advanced Program  Display   Terminal Block  Terminal Block  Display   Display   Display   Display   Display   Display   Display   Advanced Program  Advanced Program  Advanced Program  Advanced Program  Advanced Program  Communications  Basic Program  Advanced Program  Basic Program  Advanced Program  Basic Program  Basic Program  Basic Program  Basic Program                                                                                                                                        Page Parameter Name Number Group   3 11 Motor OL Select A444 Advanced Program  3 19 Output Current d003 Display   3 7 Output Freq d001 Display   3 7 Output Voltage d004 Display   3 14 Preset Freq 0 A410 Advanced Program  3 14 Preset Freq 1 A411 Advanced Program  3 15 Preset Freq
42. Command comes from the integral keypad by default  To  03   Direction Run REV   Not Active disable reverse operation  see A095  Reverse Disable   a P107   A ii For digital inputs  Electronicallv isolated with digital inputs  04  Digital Common from analog VO   05   Digital Input 1 Preset Freq Program with t201  Digital Int Sel   1201  06  Digital Input 2 Preset Freq Program with t202  Digital In2 Sel   1202  ie Drive supplied power for digital inputs   ll    28N DG Maximum output current is 100mA                 PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E                         Installation Wiring 1 15  No    Signal Default Description Param  2 woo   oo ae  13 0 10V In 6  IMI f d HA di  14    Analog Common   ror ie cae bier AC aga isolated with  15  4 20mA in      Not Active ied sd dal P108  18  PSMBSIDS Sna    a hammer     d  Only one analog frequency source may be connected at a time  If more than one reference is connected at the same  requencv reference will result     time  an undetermined       1 0 Wiring Examples    Input  Potentiometer  1 10k Ohm Pot     Recommended   2 Watt minimum     Connection Example  P108  Speed Reference    2  0 10V Input                                     Analog Input   0 to  10V  100k ohm  impedance   4 20 mA  100 ohm  impedance                                                                               Voltage Current  P108  Speed Reference    2    0 10V   P108  Speed Reference    3 
43. Common    Each digital input draws 6 mA        3 Wire SNK Control    Reversing             O  Direction                               PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 18 Installation Wiring    Typical Multiple Drive Connection Examples    Input Connection Example  Multiple Digital  Input Connections  Customer Inputs can  be wired per  External Supply   SRC  examples on  page 1 16  Customer Inputs 7 7 7 Optional Ground Connection    02 04 02 04 02 04 02 704                                                                      When connecting a single input such as Run  Stop  Reverse or Preset Speeds  to multiple drives  it is important to connect I O Terminal 04 common together  for all drives  If thev are to be tied into another common  such as earth ground  or separate apparatus ground  only one point of the daisy chain of I O Terminal  04 should be connected     ATTENTION  Digital inputs on multiple drives should not be  tied together when using SNK  Internal Supply  mode  In SNK  mode  if power is removed from one drive  inadvertent operation  of other drives that share the same I O Common connection  may occur                                   Connections OOOO O  OOOOO ooa  12 13 14 13 14 13 14 13 14  oeogecollcoegoojkoeecvolooeeco                            Multiple Analog                Remote Potentiometer  7 7 7 Optional Ground Connection    When connecting a single potentiometer to multiple drives it
44. Default 60 Hz  Min Max  10 400 Hz  Display  1 Hz  P103  Motor OL Current  Related Parameter s   P111  t221  A441  A444  A448  A437    Set to the maximum allowable motor current     The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150  for 60  seconds or 200  for 3 seconds                          Values Default Based on Drive Rating  Min Max  0 0  Drive Rated Amps x 2   Display  0 1 Amps  P104  Minimum Freq  Related Parameter s   d001  d002  d013  P105  t211  t213  A438  Sets the lowest frequency the drive will output continuously   Values Default 0 0 Hz  Min Max  0 0 400 0 Hz  Display  0 1 Hz  P105  Maximum Freq  Related Parameter s   d001  d002  d013  P104  A404        1212  t214  A438     Stop drive before changing this parameter   Sets the highest frequency the drive will output              Values Default 60 Hz  Min Max  0 400 Hz  Display  1 Hz    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 9    Basic Program Group  continued     P106  Start Source  Related Parameter s   d012  P107       Stop drive before changing this parameter     Sets the control scheme used to start the drive    Refer to Start and Speed Reference Control on page 1 19 for details about how other drive settings  can override the setting of this parameter    Important  For all settings except option 3  the drive must receive a leading edge from the start input  for the drive to 
45. Freq 1 3      Start and Direction commands come  from P106  Start Source               Run as specified by  P108  Speed Reference      Start and Direction commands  come from P106  Start Source               PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E          1 20 Installation Wiring    Accel Decel Selection    The selection of Accel Decel rates can be made through digital inputs   RS485  DSI  communications and or parameters              Jog Input  Enabled and Active   1201 or t202   2    A405  Jog Accel Decel  used                 Active when  A401  Accel Time 2  A402  Decel Time 2   is selected by RS485  DSI  port     RS485  DSI  Port  Controls Speed                       Input is programmed  as    Accel 2  amp  Decel 2     1201 or t202   1    A401  Accel Time 2  A402  Decel Time 2   is active when input is active                       P109  Accel Time 1  P110  Decel Time 1    A401  Accel Time 2  A402  Decel Time 2   determined by the active Preset Frequency   See A410 A413  Preset Freq 0 3   on page 3 21     Speed is controlled  by  Preset Freq x   t201 or t202   4                       P109  Accel Time 1  P110  Decel Time 1   are used              PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring 1 21    EMC Instructions    CE Conformity    Conformity with the Low Voltage  LV  Directive and Electromagnetic  Compatibility  EMC  Directive has been dem
46. HIM     Dimensions are in millimeters and   inches  Catalog Number  22 HIM C2S                                                 25 93  7  0 98  ji  3 66   gt   L 2  a A  Hp  180  HB  7 09   k          2m     gt     aa  H  _      ee Yy                                     Important  The 22 HIM C2S is smaller than the 22 HIM C2 and  cannot be used as a direct replacement     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    B 14 Accessories and Dimensions    Figure B 10 NEMA Type 1 Bezel     Dimensions are in millimeters and  inches   Catalog Number  22 HIM B1    11 1    93  0 44     25 2  3 66      fess  re                                           OO0O0CO  CO0O0CO 180  L QOO0O0  7 09   OOOC   OOOC     k em y ae    rt  aaran    y                                                    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Appendix C    RS485  DSI  Protocol    PowerFlex 4M drives support the RS485  DSI  protocol to allow  efficient operation with Rockwell Automation peripherals  In addition   some Modbus functions are supported to allow simple networking   PowerFlex 4M drives can be multi dropped on an RS485 network using    Modbus protocol in RTU mode                                                                                                                                                                                                                                000
47. Manual    Publication 22F UM001D EN E    Accessories and Dimensions B 9    Figure B 5 Frame A EMC Line Filters     Dimensions are in millimeters and  inches   Catalog Numbers  22F RF010 AL  22F RF9P5 AS  22F RF9P5 AL  22F RFEPO AS   22F RF6P0 AL                                                                                                                                                                                           B 72 0   283  7   TR iil   lt    1 97   31 0     ib  lt      sse  6 Q z i     fell T fi  Ke   54 0   lt      2 13       229 0  218 5  9 02    8 60   2185   6  8 60   5 oeelelelo  TA A  y P A   om e L   i  lt    5 5  0 22   i _   24 0   0 94        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    B 10 Accessories and Dimensions    Figure B 6 Frame B EMC Line Filters     Dimensions are in millimeters and  inches   Catalog Numbers  22F RF025 BL  22F RF021 BS  22F RF021 BL  22F RF012 BS     22F RFO12 BL                                                                                                                                                                                                                                                       1010  f  398     50 0  Ea iij   a l 250m  ay  TO EES GF     74 0      lt    291   229 0  216 0  9 02       8 50   216 0   8 50          a   Oleefeeo d  y y mene  s0  ie i f f   059  T  240 bl  TA 7  0 94     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx Us
48. Motor Controller  the drive must be installed in a ventilated or  non ventilated enclosure with the minimum volume specified in this column  Application specific thermal considerations  may require a larger enclosure            Input Output Ratings  Output Frequency  0 400 Hz  Programmable   Efficiency  97 5   Typical     Approvals  UL508C EMC Directive 89 336 EEC  LV Dir  73 23 EEC   ID  CSA 22 2 LV  EN 50178  c US No  14 EMC  EN 61800 3     Analog Control Inputs          Digital Control Inputs  Input Current   6mA   SRC  Source  Mode  SNK  Sink  Mode           4 20mA Analog  250 ohm input impedance  0 10V DC Analog  100k ohm input impedance    18 2AV   ON 0 6V   ON External Pot  1 10k ohms  2 Watt minimum    0 6V   OFF 18 24V   OFF  Control Output  Programmable Output  form C relay   Resistive Rating  3 0A at 30V DC  125V AC and 240V AC Inductive Rating  0 5A at 30V DC  125V AC  and 240V AC    Recommended Fuses and Circuit Breakers  Fuse  UL Class J  RK1  T or Type BS88  600V  550V  or equivalent  Circuit Breakers  HMCP or Bulletin 140M or equivalent     Protective Features  M    otor Protection  I7t overload protection   150  for 60 Secs  200  for 3 Secs  Provides Class 10 protection   Overcurrent  200  hardware limit  300  instantaneous fault    Over Voltage   100 120V AC Input     Trip occurs at 405V DC bus voltage  equivalent to 150V AC incoming line   200 240V AC Input     Trip occurs at 405V DC bus voltage  equivalent to 290V AC incoming line   380 460V AC Input     T
49. N 1 1 3       Drive Voltage Rating Rating Enclosure HIM Emission Class Type  Table B B PowerFlex 4M Drives                                                                                  Drive Ratings Catalog Number  Output Frame  Input Voltage kW HP Current  A    Panel Mount Size  Y2oveneoHz  02  025 16  JAFVIPENIOS    JALI  1 Phase 04 0 5 25 22F V2P5N103 A  0 75 1 0 45 22F V4P5N103 B  1 1 1 5 6 0 22F VEPON103 B  240V 50 60 Hz 0 2 0 25 1 6 22F A1P6N103 A  1 Phase 04 0 5 25 22F AZPSN103 A  0 75 1 0 42 22F A4P2N103 A  1 5 2 0 8 0 22F ABPON103 B  2 2 3 0 11 0 22F A011N103 B  a  50 60 Hz 0 2 0 25 1 6 22F A1P6N113 A   rnase o a 104 0 5 2 5 22F A2P5N113 A  With Integral EMC Filter    as li re  Serer  15 2 0 8 0 22F ABPON113 B  2 2 3 0 11 0 22F A011N113 B  240V 50 60 Hz 0 2 0 25 1 6 22F B1P6N103 A  3 Phase 04 0 5 25 22F B2P5N103 A  0 75 1 0 42 22F BAP2N103 A  1 5 2 0 8 0 22F BBPON103 A  2 2 3 0 12 0 22F B012N103 B  3 7 5 0 17 5 22F BO17N103 B  55 75 25 0 22F BO25N104 3  c  75 10 0 33 0 22F BO33N104 3  C  480V 50 60 Hz 0 4 0 5 1 5 22F D1P5N103 A  3 Phase 075 110 25 22F D2P5N103 A  15 2 0 4 2 22F D4P2N103 A  2 2 3 0 6 0 22F DEPON103 B  3 7 5 0 8 7 22F D8P7N103 B  55 75 13 0 22F D013N104    C  75 10 0  18 0 22F D018N104    c  11 0 115 0 124 0 22F D024N104   c                      PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    B 2 Accessories and Dimensions                            Drive Ratings Catalog Number  Output Frame  Input
50. NI    je  l       be  do  S       PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 32 Programming and Parameters    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Chapter 4    Troubleshooting    Chapter 4 provides information to guide you in troubleshooting the  PowerFlex 4M drive  Included is a listing and description of drive faults   with possible solutions  when applicable      For information on    See page       Drive Status om Descriptions 4 3    Faults FF Common Svmptoms and 4 5  Corrective Actions                     Drive Status    The condition or state of your drive is constantly monitored  Any  changes will be indicated through the integral keypad     LED Indications    See page 2 3 for information on drive status indicators and controls     Faults    A fault is a condition that stops the drive  There are two fault types     Type   Fault Description    D  Auto Reset Run When this type of fault occurs  and A451  Auto Rstrt Tries  is  set to a value greater than    0     a user configurable timer  A452   Auto Rstrt Delay   begins  When the timer reaches zero  the  drive attempts to automatically reset the fault  If the condition  that caused the fault is no longer present  the fault will be reset  and the drive will be restarted       Non Resetable This type of fault may require drive or motor repair  or is  caused by wiring or programing errors  The 
51. Preset Freq 1        110   A412  Preset Freq 2        111   A413  Preset Freq 3              1  MOP Decrement  0   Not Decrement    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    RS485  DSI  Protocol C 5    Writing  06  Reference    The Speed Reference to a PowerFlex 4M drive can be controlled via the  network bv sending Function Code 06 writes to register address 8193   Reference   P108  Speed Reference  must be set to 5    RS485  DSI   Port  in order to accept the Speed Reference     In addition to being written  register address 8193 can be read using  Function Code 03     Reference       Address  Decimal    Description    A decimal value entered as xxx x where the decimal point is fixed  For  example  a decimal    100    equals 10 0 Hz and    543    equals 54 3 Hz               8193    Reading  03  Logic Status Data    The PowerFlex 4M Logic Status data can be read via the network by  sending Function Code 03 reads to register address 8448  Logic Status                                                      Logic Status  Address  Decimal    Bit s  Description  0 1   Ready  0   Not Ready  1 1 Active  Running   0   Not Active  2 1   Cmd Forward  0   Cmd Reverse  3 1   Rotating Forward  0   Rotating Reverse  4 1   Accelerating  0   Not Accelerating  5 1   Decelerating  0   Not Decelerating  6 1   Alarm  0   No Alarm  T 1   Faulted  0   Not Faulted  8448  8 1   At Reference  0   Not At Reference  9 1   Reference Controlled 
52. The drive Safety Ground       PE  must be connected to system ground   Ground impedance must conform to the requirements of national and  local industrial safety regulations and or electrical codes  The integrity  of all ground connections should be periodically checked     Figure 1 3 Typical Grounding                                                                                                                                     Ground Fault Monitoring    If a system ground fault monitor  RCD  is to be used  only Type B   adjustable  devices should be used to avoid nuisance tripping     Safety Ground        PE     This is the safety ground for the drive that is required by code  One of  these points must be connected to adjacent building steel  girder  joist   a  floor ground rod or bus bar  Grounding points must comply with national  and local industrial safety regulations and or electrical codes     Motor Ground    The motor ground must be connected to one of the ground terminals on  the drive     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 6    Installation Wiring    Shield Termination   SHLD    Either of the safety ground terminals located on the power terminal  block provides a grounding point for the motor cable shield  The motor  cable shield connected to one of these terminals  drive end  should also  be connected to the motor frame  motor end   Use a shield terminating or  EMI clamp to connect the shield to
53. Time 1   0 1 A412  Preset Freq 2     Accel Time 2     Decel Time 2   1 1 A413  Preset Freq 3     Accel Time 2     Decel Time 2        When a Digital Input is set to    Accel 2  amp  Decel 2     and the input is active  that input overrides the settings in       this table     A418  Skip Frequency  Related Parameter s   A419  Sets the frequency at which the drive will not operate   A setting of 0 disables this parameter              Values Default 0 Hz  Min Max  0 400 Hz  Display  1 Hz    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 22 Programming and Parameters    Advanced Program Group  continued     A419  Skip Freq Band  Related Parameter s   A418    Determines the bandwidth around A418  Skip Frequency   A419  Skip Freq Band  is applied above  and below the actual skip frequency  See the diagram below     A setting of 0 0 disables this parameter                      Values Default  0 0 Hz  Min Max  0 0 30 0 Hz  Display  0 1 Hz  Frequency Command     Frequency    l Drive Output   i  u pFrequency i l       EEN Sere  EPEE ETE ee eee ee OE    PN   2x Skip   l a i nl i  Frequency Band  eee ee eee   eee a ee A    Skip Frequency  gt        A424  DC Brake Time  Related Parameter s   P107  A425    Sets the length of time that DC brake current is    injected    into the motor  Refer to parameter A425  DC  Brake Level               Values Default 0 0 Secs  Min Max  0 0 99 9 Secs  A setting of 99 9   Continuous   Display  0 1 Sec
54. achinery or unintentional flow of liquid  gas or solids exist   an additional hardwired stop circuit may be required to remove the AC  line to the drive  When the AC line is removed  there will be a loss of  any inherent regenerative braking effect that might be present   the  motor will coast to a stop  An auxiliary braking method may be  required     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring 1 13     O Wiring Recommendations    Important points to remember about I O wiring     e Always use copper wire   e Wire with an insulation rating of 600V or greater is recommended     e Control and signal wires should be separated from power wires by at  least 0 3 meters  1 foot      Important  I O terminals labeled    Common    are not referenced to the  safety ground  PE  terminal and are designed to greatly  reduce common mode interference     ATTENTION  Driving the 4 20mA analog input from a voltage  source could cause component damage  Verify proper configuration  prior to applying input signals    Control Wire Types   Table 1 G Recommended Control and Signal Wirel        Wire Type s  Description Minimum  Insulation Rating    Belden 8760 9460  0 8 mm  18AWG   twisted pair  100  300V           or equiv   shield with drain  60 degrees C  Belden 8770 0 8 mm   1 8AWG   3 conductor  shielded for  140 degrees F    or equiv   remote pot only      1  Ifthe wires are short and contained within a cabinet which has
55. anual    Publication 22F UM001D EN E                      2 4 Start Up  No  LED LED State Description  O     Speed Used to control speed of drive  Default is active   L A Potentiometer   Controlled by parameter P108  Speed Reference    TR  D  Start Used to start the drive  Default is active      Controlled by parameter P106  Start Source    Reverse Used to reverse direction of the drive  Default is active      Controlled by parameters P106  Start Source  and A434   Reverse Disable    Stop Used to stop the drive or clear a fault  This key is always     active  Controlled by parameter P107  Stop Mode      Viewing and Editing Parameters    The last user selected Display Group parameter is saved when power is removed and is displayed by    default when power is reapplied     The following is an example of basic integral keypad and display functions  This example provides basic  navigation instructions and illustrates how to program the first Program Group parameter     Step   1  When power is applied  the last user selected  Display Group parameter number is briefly  displayed with flashing characters  The display  then defaults to that parameter   s current value    Example shows the value of d001  Output  Freq  with the drive stopped      2  Press Esc once to display the Display Group  parameter number shown on power up  The  parameter number will flash     3  Press Esc again to enter the group menu  The  group menu letter will flash     4  Press the Up Arrow or Down Arrow to s
56. ary to disconnect  power to the motor with the drive outputting power  an auxiliary contact  should be used to simultaneously disable drive control run commands     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Installation Wiring 1 11    Power Terminal Block    The drive utilizes a finger guard over the power wiring terminals   To remove     1  Press in and hold the locking tab     2  For the finger guard on the top of the drive  slide it down and out   For the finger guard at the bottom of the drive  slide it up and out     Replace the finger guard when wiring is complete     Figure 1 4 Power Terminal Block                                                    Terminal  R LI  S L2          Frame A and B  RILI S2 Ts        SLEE    Frame C  RILI S L2 TL3 PI P2        OOS                                                                                                          Frame A and B    SILERS    UT1 V T2 WT3 DC  DC    S 6     Frame C    BR   UTI VIT2 W T3 DC  BR  DC     BRL  80 B                                                                                                             Description  1 Phase Input       R L1  S L2  T L3    3 Phase Input       DC Bus Inductor Connection  Frame C drives only                              The Frame C drive is shipped with a jumper between Terminals P1  Pi   pal  and P2  Remove this jumper only when a DC Bus Inductor will be UI U  connected  Drive will not power up without a ju
57. bare copper grounds in contact with shield  Shawflex 2ACD 3ACD or  e PVC jacket  equivalent  Class    amp  Il    Tray rated 600V  75  C or  e Three tinned copper conductors with XLPE insulation  Division    amp  Il 90  C  167  F or 194  F  e 5 mil single helical copper tape  25  overlap min    RHH RHW 2 with three bare copper grounds in contact with shield  e PVC copper grounds on  10 AWG and smaller          Reflected Wave Protection    The drive should be installed as close to the motor as possible   Installations with long motor cables may require the addition of external  devices to limit voltage reflections at the motor  reflected wave  phenomena   See Table 1 E for recommendations     The reflected wave data applies to all frequencies 2 to 10 kHz   For 240V ratings  reflected wave effects do not need to be considered     Table 1 E Maximum Cable Length Recommendations             Reflected Wave   380 480V Ratings Motor Insulation Rating Motor Cable Only    1000 Vp p 15 meters  49 feet   1200 Vp p 40 meters  131 feet   1600 Vp p 170 meters  558 feet            1  Longer cable lengths can be achieved by installing devices on the output of the drive     Consult factory for recommendations     Output Disconnect    The drive is intended to be commanded by control input signals that will  start and stop the motor  A device that routinely disconnects then  reapplies output power to the motor for the purpose of starting and  stopping the motor should not be used  If it is necess
58. blication 22F UM001D EN E    P 2 Overview    Manual Conventions    e In this manual we refer to the PowerFlex 4M Adjustable Frequency  AC Drive as  drive  PowerFlex 4M or PowerFlex 4M Drive     e Parameter numbers and names are shown in this format   P101  Motor NP Volts     Name          Number          Group   d   Display Group   P   Basic Program Group   t   Terminal Block Group   C   Communications Group  A   Advanced Program Group       e The following words are used throughout the manual to describe an    action     Word  Can    Meaning  Possible  able to do something       Cannot    Not possible  not able to do something       May    Permitted  allowed       Must    Unavoidable  you must do this       Shall    Required and necessary       Should    Recommended       Should Not       Not Recommended    Drive Frame Sizes    Similar PowerFlex 4M drive sizes are grouped into frame sizes to  simplify spare parts ordering  dimensioning  etc  A cross reference of  drive catalog numbers and their respective frame sizes is provided in    Appendix B     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E     gt   gt  PP  D    Overview P 3    General Precautions    ATTENTION  To avoid an electric shock hazard  verify that the  voltage on the bus capacitors has discharged before performing any  work on the drive  Measure the DC bus voltage at the  DC and  DC  terminals on the Power Terminal Block  refer to Chapter 1 Power  Terminal de
59. by Comm  10 1   Operation Cmd Controlled by Comm  11 1   Parameters have been locked  12 Digital Input 1 Status  13 Digital Input 2 Status  14 Not Used  15 Not Used          PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    RS485  DSI  Protocol    Reading  03  Feedback    The Feedback  Output Frequency  from the PowerFlex 4M drive can be  read via the network by sending Function Code 03 reads to register  address 8451  Feedback      Feedback     Address  Decimal    Description    A xxx x decimal value where the decimal point is fixed  For example  a decimal     423    equals 12 3 Hz and    300    equals 30 0 Hz      1   Returns the same data as Reading  03  Parameter d001  Output Freq                8451       Reading  03  Drive Error Codes    The PowerFlex 4M Error Code data can be read via the network by  sending Function Code 03 reads to register address 8449  Drive Error  Codes                                                                                 Logic Status  Address  Decimal    Value  Decimal   Description  0 No Fault  2 Auxiliary Input  3 Power Loss  4 Undervoltage  5 Overvoltage  6 Motor Stalled  7 Motor Overload  8 Heatsink Overtemperature  12 HW Overcurrent  300    13 Ground Fault  29 Analog Input Loss  33 Auto Restart Tries  8449 38 Phase U to Ground Short  39 Phase V to Ground Short  40 Phase W to Ground Short  41 Phase UV Short  42 Phase UW Short  43 Phase VW Short  63 Software Overcurrent  64 Drive Over
60. cause of the fault  must be corrected before the fault can be cleared           PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    4 2    Troubleshooting    Fault Indication    Condition Display    Drive is indicating a fault                       The integral keypad provides visual eda   F 7     T ovat  notification of a fault condition by mo PT  Onus    displaying the following  rs AiAi   e Flashing fault number a    e Flashing fault indicator  Press the Escape key to regain control of  the integral keypad                                      Manually Clearing Faults  Step LEG   1  Press Esc to acknowledge the fault  The fault information will be  removed so that you can use the integral keypad   Access d007 Fault 1 Code to view the most recent fault information     2  Address the condition that caused the fault   The cause must be corrected before the fault can be cleared   See Table 4 A     3  After corrective action has been taken  clear the fault by one of these  methods    Press Stop if P107  Stop Mode  is set to a value between    0    and    3       Cycle drive power       Set A450  Fault Clear  to    1    or    2       Cycle digital input if t201   t202  Digital Inx Select  is set to option 7     Clear Fault           Automatically Clearing Faults   Clear a Type 1 fault and restart the drive    1  Set A451  Auto Rstrt Tries  to a value other than    0       2  Set A452  Auto Rstrt Delay  to a value other than    0    
61. ce    Set to 5    RS485  DSI  Port    if the Speed Reference is  Page 3 11  controlled from the network   C302  Comm Data Rate    Sets the data rate for the RS485  DSI  Port  All nodes   Page 3 17  on the network must be set to the same data rate   303  Comm Node Addr    Sets the node address for the drive on the network  Page 3 17  Each device on the network requires a unique node  address   C304  Comm Loss Action    Selects the drive s response to communication problems    Page 3 17  305  Comm Loss Time    Sets the time that the drive will remain in Page 3 18  communication loss before the drive implements A105   Comm Loss Action       306  Comm Format  Sets the transmission mode  data bits  parity and stop   Page 3 18          bits for the RS485  DSI  Port  All nodes on the network  must be set to the same setting     Supported Modbus Function Codes    The peripheral interface  DSI  used on PowerFlex 4M drives supports  some of the Modbus function codes     Modbus Function Code  Decimal    Command                03 Read Holding Registers  06 Preset  Write  Single Register  16  10 Hexadecimal  Preset  Write  Multiple Registers    Important  Modbus devices can be 0 based  registers are numbered  starting at 0  or 1 based  registers are numbered starting at  1   Depending on the Modbus Master used  the register  addresses listed on the following pages may need to be  offset by  1  For example  Logic Command may be register  address 8192 for some master devices  e g  ProSoft  
62. croll  through the group menu  d  P  t  C and A      Press Enter or Sel to enter a group  The  rightmost digit of the last viewed parameter in  that group will flash     5  Press the Up Arrow or Down Arrow to scroll  through the parameters in the group        Key s     oT    or    p    D            or    5    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E       Example Displays  0 Mes    e HERTZ     a                PROGRAM FAULT    O O       I pevu  d U LI l    HERTZ  PROGRAM FAULT  d Inam ER  l U L f  o HERTZ    PROGRAM FAULT       o VOLTS  o AMPS  o HERTZ          J Im  P ioi    PROGRAM FAULT       oO l  u plo vons  l  ff loner  PROGRAM FAULT   O O    Step   6  Press Enter or Sel to view the value of a  parameter  If you do not want to edit the value   press Esc to return to the parameter number     7  Press Enter or Sel to enter program mode to  edit the parameter value  The rightmost digit will  flash and the Program LED will illuminate if the  parameter can be edited     8  Press the Up Arrow or Down Arrow to change  the parameter value     If desired  press Sel to move from digit to digit  or bit to bit  The digit or bit that you can change  will flash     9  Press Esc to cancel a change  The digit will  stop flashing  the previous value is restored and  the Program LED will turn off     Or    Press Enter to save a change  The digit will stop  flashing and the Program LED will turn off     10  Press Esc to return to t
63. e  this parameter will set  itself back to    0        e Causes an F48 Params Defaulted fault     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 13    Terminal Block Group    t201  Digital Ini Sel     O Terminal 5    t202  Digital In2 Sel     O Terminal 6        Related Parameter s   d012  d014  P108  P109  P110   1211 1214  A401  A402  A404  A405  A410 A413        Stop drive before changing this parameter        Selects the function for the digital inputs  Refer to the flowchart on page 1 19 for more information on    speed reference control priority        Options 0    Not Used       Terminal has no function but can be read over network  communications via d014  Dig In Status        1    Acc 2  amp  Dec 2       e When active  A401  Accel Time 2  and A402  Decel Time  2  are used for all ramp rates except Jog     e Can only be tied to one input     Refer to the flowchart on page 1 20 for more information on  Accel Decel selection           2    Jog       e When input is present  drive accelerates according to the  value set in A405  Jog Accel Decel  and ramps to the  value set in A404  Jog Frequency     e When input is removed  drive ramps to a stop according to  the value set in A405  Jog Accel Decel     e A valid    Start    command will override this input        3    Aux Fault       When enabled  an F2 Auxiliary Inout fault will occur when the  input is removed        4    Preset Freq     D
64. e current regulator response and  attempts to correct this condition        3    Both       A437  Slip Hertz   FLA  Related Parameter s   P103    Compensates for the inherent slip in an induction motor  This frequency is added to the commanded  output frequency based on motor current              Values Default 2 0 Hz  Min Max  0 0 10 0 Hz  Display  0 1 Hz  A438  Process Time Lo  Related Parameter s   d010  P104    Scales the time value when the drive is running at P104  Minimum Freq   When set to a value other  than zero  d010  Process Display  indicates the duration of the process              Values Default 0 00  Min Max  0 00 99 99  Display  0 01  A439  Process Time Hi  Related Parameter s   d010  P105    Scales the time value when the drive is running at P105  Maximum Freq   When set to a value other  than zero  d010  Process Display  indicates the duration of the process              Values Default 0 00  Min Max  0 00 99 99  Display  0 01    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 26 Programming and Parameters    Advanced Program Group  continued     A440  Process Factor  Related Parameter s   d010    Scales the value displayed by d010  Process Display    Output   Process _ Process    Freq X Factor   Display             Values Default 30 0  Min Max  0 1 999 9  Display  0 1    A441  Bus Reg Mode     Controls the operation of the drive voltage regulation  which is normally operational at deceleration or  when t
65. ection and Speed Control   Factory default parameter values allow the drive to be controlled from   the integral keypad  No programming is required to start  stop  change   direction and control speed directly from the integral keypad     Important  To disable reverse operation  see A434  Reverse Disable      If a fault appears on power up  refer to Fault Descriptions on page 4 3  for an explanation of the fault code        Variable Torque Fan Pump Applications    For improved motor tuning performance when using a premium efficient  motor on a variable torque load  set A453  Boost Select  to option 2     35 0  VT        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Integral Keypad       Menu    d    Description    Display Group  View Only   Consisi  conditions     is of commonly viewed drive operating       Basic Program Group  Consis   functions     s of most commonly used programmable       Terminal Block Group  Consis  terminals     s of programmable functions for control       Communications Group  Consis  communications     is of programmable functions for       sara fT o    Advanced Program Group  Consis     s of remaining programmable functions              conditions  Displayed only when fault is present     TM       Fault Designator  Consis       s of list of codes for specific fault          Start Up 2 3                                  9 NANE    REVO  LI  UI  OHERTZ      os  se  a   tO                    80   W 
66. efault     Refer to A410   A413  Preset Freq x     Important  Digital Inputs have priority for frequency control  when programmed as a Preset Speed and are active  Refer  to the flowchart on 1 19 for more information on speed  reference control priority                 5    Local    When active  sets integral keypad as start source and  potentiometer on the integral keypad as speed source   6    Comm Port    e When active  sets communications device as default start   speed command source   e Can only be tied to one input   7    Clear Fault    When active  clears an active fault   8    RampStop CF    Causes drive to immediately ramp to a stop regardless of how    P107  Stop Mode  is set        9    CoastStop CF       Causes drive to immediately coast to a stop regardless of  how P107  Stop Mode  is set        10    DCInjStop CF       Causes drive to immediately begin a DC Injection stop  regardless of how P107  Stop Mode  is set        11    Jog Forward       Drive accelerates to A404  Jog Frequency  according to A405   Jog Accel Decel  and ramps to stop when input becomes  inactive  A valid start will override this command        12    Jog Reverse       Drive accelerates to A404  Jog Frequency  according to A405   Jog Accel Decel  and ramps to stop when input becomes  inactive  A valid start will override this command     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 14 Programming and Parameters             t201 amp  1
67. enclosure with the minimum volume specified in this  column  Application specific thermal considerations may require a larger enclosure        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E     gt     Installation Wiring 1 9    Power Wiring    ATTENTION  National Codes and standards  NEC  VDE  BSI  etc    and local codes outline provisions for safely installing electrical  equipment  Installation must comply with specifications regarding wire  types  conductor sizes  branch circuit protection and disconnect  devices  Failure to do so may result in personal injury and or equipment  damage     ATTENTION  To avoid a possible shock hazard caused by induced  voltages  unused wires in the conduit must be grounded at both ends   For the same reason  if a drive sharing a conduit is being serviced or  installed  all drives using this conduit should be disabled  This will help  minimize the possible shock hazard from    cross coupled    power leads     Motor Cable Types Acceptable for 200 600 Volt Installations    General   A variety of cable types are acceptable for drive installations  For many  installations  unshielded cable is adequate  provided it can be separated  from sensitive circuits  As an approximate guide  allow a spacing of 0 3  meters  1 foot  for every 10 meters  32 8 feet  of length  In all cases   long parallel runs must be avoided  Do not use cable with an insulation  thickness less than 15 mils  0 4 mm 0 015 in    D
68. equency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E          4 4 Troubleshooting   No    Fault      Description  2       F33 JAuto Rstrt Tries       Drive unsuccessfully attempted  to reset a fault and resume  running for the programmed  number of A451  Auto Rstrt Tries     F38  Phase U to Gnd _    A phase to ground fault has been   F39  Phase V to Gnd detected between the drive and   F40 Phase W to Gnd motor in this phase    F41   Phase UV Short       Excessive current has been   F42   Phase UW Short detected between these two   F43 Phase VW Short output terminals    F48  Params The drive was commanded to   Defaulted write default values to EEPROM    F63   SW OverCurrent   Q    Programmed A448  SW Current  Trip  has been exceeded    F64  Drive Overload       Drive rating of 150  for 1 minute  or 200  for 3 seconds has been  exceeded    F70   Power Unit      Failure has been detected in the  drive power section    F71  Net Loss The communication network has  faulted    F81  Comm Loss    RS485  DSI  port stopped  communicating    F100   Parameter     The checksum read from the   Checksum board does not match the  checksum calculated    F122  I O Board Fail       Failure has been detected in the  drive control and I O section    ption of fault types           Action    Correct the cause of the fault and  manually clear              Check the wiring between the  drive and motor      Check motor for grounded phase      Replace drive if fault cannot be  Cleared 
69. er Manual  Publication 22F UM001D EN E    Accessories and Dimensions B 11    Figure B 7 Frame C EMC Line Filters     Dimensions are in millimeters and  inches   Catalog Number  22F RF039 CS  22F RF039 CL  22F RF026 CS  22F RF026 CL                                                                                                                                                                                                                                                                ja 130 0  61  7   800   rd IK  32 0  lt _   1 26  7   99902  4 A Li T  TRI   eo EE  4  900 y   3 54   309 0   12 17  309 0   12 17       297 0 297 0   11 69   11 69             Ooae  l y S A   Pm WIETIZTITI i   ZI 55 5  0 22        170  B     1 18     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    B 12 Accessories and Dimensions    Figure B 8 Remote  Panel Mount  HIM     Dimensions are in millimeters and  inches   Catalog Number  22 HIM C2    17 6 104          lt      e  gt j     0 69   4 09     lim          B                                                                                  EB  220   8 66    lt        2 9m        gt   K ral ia   UI B  i 194     7 64   i   A  i 125     4 92          60 5    AR            238   38  19 1  1075   1 50  l    t Y Y  i a     0 19     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Accessories and Dimensions B 13    Figure B 9 Remote  Panel Mount  Small 
70. erage of 75  or better  metal conduit or  equivalent attenuation     3  Allowable cable length in Table 1 1 is not exceeded     Table 1 1 Allowable Cable Length    Filter Type    Integral  240V    EN61800 3  Second  Environment    5 meters  16 feet     EN61800 3 First  Environment  Restricted  Distribution  2    5 meters  16 feet     EN61800 3 First  Environment  Unrestricted  Distribution  3   1 meter  3 feet        Integral  480V    10 meters  33 feet        External   S Type        5 meters  16 feet     5 meters  16 feet     1 meter  3 feet        External   L Type          100 meters  328 feet        100 meters  328 feet      1  Refer to Appendix B for details on optional external filters    2  Equivalent to EN55011 Class A    3  Equivalent to EN55011 Class B     Figure 1 6 Connections and Grounding                                2  Shielded Enclosure    EMI Filter  Li Li  File  L2 Lo  S L2                                                 L3 L3                                   2    AS       Enclosure Ground Connection    Building Structure Steel     1                           U T1                                              Shielded Motor Cable          25 meters  82 feet     Fittings and Metal Conduit                               First Environment Unrestricted Distribution installations require a shielded enclosure     Keep wire length as short as possible between the enclosure entrv point and the EMI    filter    2     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx
71. es  3 1  Viewing and Editing  2 4  Parameter Checksum Fault  4 4  Parameter Cross Reference  by Name  3 31  Parameters  Advanced Program Group  3 19  Communications Group  3 17  Display Group  3 3  Program Group  3 8  Terminal Block Group  3 13  PE Ground  1 5  Phase Short Fault  4 4  Phase to Ground Fault  4 4  Potentiometer  Wiring  1 15  Power Cables Wiring  1 9  Power Conditioning  Input  1 4  Power Loss Fault  4 3  Power Unit Fault  4 4  Powering Up the Drive  2 1  2 2  Precautions  General  P 3  Product Selection  B 1  Program Group Parameters  3 8  Programming  3 1  PTC Analog Input Wiring  1 15    R  Ratings  A 1  Reflective Wave Protection  1 10  Removing Cover  1 1  Repeated Start Stop  1 12  Repeated Start Stop Precautions     RFI  see EMC RFI    RWR  Reflective Wave Reducer    1 10    S  Safety Ground  1 5  Shielded Power Cables  1 10  Short Circuit Protection  1 7    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Index 3    Software  3 1    Start and Speed Reference Selection  and Control  1 19  1 20    Start Stop  Repeated  1 12  Start Up Checklist  2 1  2 2  Static Discharge  ESD  P 3  Status LEDs  2 3   Supply Source  AC  1 3  SW OverCurrent Fault  4 4  System Grounding  1 5    T  Terminal Block    O  1 13   Power  1 12  l l Block Group Parameters     Three Wire Control  1 15  1 18  Two Wire Control  1 15  1 18    U  UnderVoltage Fault  4 3  Ungrounded Supply  1 3  Unshielded Power Cables  1 9    W  Watts Lo
72. es only  Refer to the master controller   s user manual  for network terminations  Note that there is no standard for the         and     79 wires  and consequently Modbus device manufacturers interpret  them differently  If you have problems with initially establishing  communications  try swapping the two network wires at the master  controller     Standard RS485 wiring practices apply     e Termination resistors need to be applied at each end of the network  cable     e RS485 repeaters may need to be used for long cable runs  or if  greater than 32 nodes are needed on the network     e Network wiring should be separated from power wires by at least 0 3  meters  1 foot      e Network wiring should only cross power wires at a right angle     Control Terminal 16 on the PowerFlex 4M must also be connected to PE  ground  there are two PE terminals on the drive   See Figure 1 5 for more  information     Network Common is internally tied to I O Terminal 04  Digital  Common   Tying I O Terminal 04 to PE ground may improve noise  immunity in some applications     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    RS485  DSI  Protocol C 3    Parameter Configuration    The following PowerFlex 4M parameters are used to configure the drive  to operate on a network                       Parameter Details Reference  P106  Start Source  Set to 5    RS485  DSI  Port    if Start is controlled from   Page 3 9  the network   P108  Speed Referen
73. eter is set to 1    Normal RA Res    and an appropriate RA resistor is used  see  selection Table B C   the drive provides calculated resistor overload protection  However  the drive  cannot protect against a brake IGBT failure        external resistor package must be self protected from over temperature or the protective    ATTENTION  A risk of fire exists if external braking resistors are not protected  The  A circuit shown in Figure B 3 on page B 7  or equivalent  must be supplied              Values Default 0  Min Max  0 3  Display  1    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 24 Programming and Parameters    Advanced Program Group  continued     A428  DB Duty Cycle  Related Parameter s   A427       Stop drive before changing this parameter     Selects the duty cycle allowed for an external dynamic braking resistor when A427  DB Resistor Sel   is set to 3  This parameter applies only to Frame C drives              Values Default 5   Min Max  1 99   Display  1   A433  Start At PowerUp        Stop drive before changing this parameter     Enables disables a feature that allows a Start or Run command to automatically cause the drive to  resume running at commanded speed after drive input power is restored  Requires a digital input  configured for Run or Start and a valid start contact     ATTENTION  Equipment damage and or personal injury may result if this parameter  is used in an inappropriate application  Do not
74. gainst personal injury and or equipment  damage caused by improper fusing or circuit breaker selection  use only  the recommended line fuses circuit breakers specified in this section     Fusing    The PowerFlex 4M has been UL tested and approved for use with input  fuses  The ratings in the table that follows are the maximum  recommended values for use with each drive rating  The devices listed in  this table are provided to serve as a guide     Bulletin 140M  Self Protected Combination Controller  UL489  Circuit Breakers    When using Bulletin 140M or UL489 rated circuit breakers  the  guidelines listed below must be followed in order to meet the NEC  requirements for branch circuit protection     e Bulletin 140M can be used in single and group motor applications     e Bulletin 140M can be used up stream from the drive without the  need for fuses     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 8 Installation Wiring    Table 1 D Minimum Recommended Branch Circuit Protective Devices                            Voltage Drive Rating   Fuse Rating    140M  3  Recommended   Min  Enclosure  Rating kW  HP  Amps Catalog No  MCS Contactors   Volumeld   Catalog No  Inches   120V AC   0 2  0 25 10 140M C2E C10   100 C09 1655  1 Phase 0 4  0 5  15 140M C2E C16   100 C12 1655  0 75  1 0 30 140M D8E C20   100 C23 1655  1 1  1 5  40 140M F8E C32   100 C30 1655  240V AC   0 2  0 25 10 140M C2E B63   100 C09 1655  1 Phase 0 4  0 5  10 
75. he bus voltage rises     Refer to the Attention statement on page P 3 for important information on bus regulation        Values 0    Disabled          1    Enabled     Default              A442  Current Limit   Maximum output current allowed before current limiting occurs   Values Default Drive Rated Amps x 1 5  Min Max  0 1  Drive Rated Amps x 1 8   Display  0 1 Amps  A444  Motor OL Select  Related Parameter s   P102  P103    Drive provides Class 10 motor overload protection  Settings 0 2 select the derating factor for the et  overload function        Options 0    No Derate   Default        1    Min Derate        2    Max Derate            No Derate     Min Derate     Max Derate      100    100    100   3 5 3   S 80 S 80 S 80   o         3 60 5 60 3 60   8 8 8      40   40   40   8 8 8   a 20 a 20 a 20   2 0 So 3 0     0 25 50 75 100 125 150 175 200 i 0 25 50 75 100 125 150 175 200   0 25 50 75 100 125 150 175 200  96 of P102  Motor NP Hertz    of P102  Motor NP Hertz    of P102  Motor NP Hertz     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 27    Advanced Program Group  continued     A446  PWM Frequency     Sets the carrier frequency for the PWM output waveform  The chart below provides derating  guidelines based on the PWM frequency setting     Important  Ignoring derating guidelines can cause reduced drive performance                 Values Default 4 0 kHz  Min Max  2 0 10 0 kHz  Display 
76. he parameter list     Continue to press Esc to back out of the  programming menu     If pressing Esc does not change the display   then d001  Output Frequency  is displayed    Press Enter or Sel to enter the group menu   again        Key s                      or    Be PG eb       Start Up    Example Displavs    cau    PROGRAM          FAULT             O O  379  Z J U  PROGRAM von       30    PROGRAM    JU       FAULT    O                PROGRAM FAULT    O       m  U    FIQ  Mo             PROGRAM    O    FAULT    O       Pi    PROGRAM       m I  UI    FAULT    The Basic Program Group  page 3 8  contains the most commonly changed parameters     2 5    e VOLTS  o AMPS  o HERTZ    e VOLTS  o AMPS  o HERTZ    e VOLTS  o AMPS  o HERTZ    e VOLTS  o AMPS  o HERTZ    e VOLTS  o AMPS  o HERTZ    o VOLTS  o AMPS  o HERTZ    PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    2 6 Start Up    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Chapter 3    Programming and Parameters    Chapter 3 provides a complete listing and description of the PowerFlex  4M parameters  Parameters are programmed  viewed edited  using the  integral keypad  As an alternative  programming can also be performed  using DriveExplorer    or DriveExecutive    software  a personal  computer and a serial converter module  Refer to Appendix B for catalog  numbers                                For informati
77. igure B 4 Bulletin 1321 3R Series Line Reactors        Dimensions are in millimeters and  inches   Weights are in kilograms and  pounds                                                                                       Catalog Number A B Cc D E Weight  1321 3R2 A 112  4 40    104  4 10    70  2 75   50 1 98    37  1 44    1 8  4  1321 3R2 B 112  4 40    104  4 10   70  2 75   50 1 98    37  1 44    1 8  4  1321 3R4 B 112  4 40    104  4 10   76  3 00   50 1 98   37  1 44    1 8  4  1321 3R4 C 112  4 40    104  4 10    86  3 38   60 2 35   37  1 44  2 3  5  1321 3R4 D 112  4 40    104  4 10    92  3 62   66 2 60   37 1 44   2 7  6  1321 3R8 A 152  6 00    127  5 00    76  3 00   53 2 10   51  2 00    3 1  7   1321 3R8 B 152  6 00    127  5 00    76  3 00   53 2 10   51 2 00    3 6  8  1321 3R8 C 152  6 00    127  5 00    85  3 35    63  2 48   51  2 00    4 9  11   1321 3R12 A 152  6 00    127  5 00   76  3 00   53 2 10   51 2 00    4 1  9  1321 3R12 B 152  6 00    127  5 00    76  3 00   53 2 10   51 2 00    4 5  10   1321 3R18 A 152  6 00    133  5 25   79  3 10   54  2 13   51  2 00    4 1  9  1321 3R18 B 152  6 00    135  5 30   89  3 50   63  2 48   51 2 00    5 5  12   1321 3R25 A 183  7 20    146  5 76   85  3 35   60 2 35    76  3 00    4 9  11   1321 3R25 B 183  7 20    147  5 80   89 3 50   60 2 35   76  3 00    6 4  14   1321 3R35 A 193  7 60    146  5 76   91  3 60   66  2 60   76 3 00   6 3 14        PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User 
78. lated Parameter s   d015  P107  C305    Selects the drive   s response to a loss of the communication connection or excessive communication  errors                 Options 0    Fault     Default  Drive will fault on an F81 Comm Loss and coast to stop   1    Coast to Stop    Stops drive via coast to stop   2    Stop    Stops drive via P107  Stop Mode  setting   3     Continu Last    Drive continues operating at communication commanded    speed saved in RAM     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 18 Programming and Parameters    Communications Group  continued     C305  Comm Loss Time  Related Parameter s   d015  C304    Sets the time that the drive will remain in communication loss before implementing the option selected  in C304  Comm Loss Action               Values Default 5 0 Secs  Min Max  0 1 60 0 Secs  Display  0 1 Secs  C306  Comm Format     Selects the protocol  RTU only   data bits  8 data bits only   parity  None  Even  Odd   and stop bits  1  stop bit only  used by the RS485 port on the drive     Refer to Appendix C for details on using the drive communication features   Important  Power to drive must be cycled before any changes will affect drive operation        Options 0    RTU 8 N 1   Default                    1    RTU 8 E 1     2    RTU 8 0 1     3    RTU 8 N 2     4    RTU 8 E 2     5    RTU 8 0 2     C307  Comm Write Mode     Determines whether parameter changes made over communication port a
79. limit is exceeded     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 11    Basic Program Group  continued        P108  Speed Reference  Related Parameter s   d001  d002  d012  P109  P110  t201  t202   A409  A410 A413  t211  1212  1213  1214       Sets the source of the speed reference to the drive    The drive speed command can be obtained from a number of different sources  The source is  normally determined by P108  Speed Reference   However  when t201   t202  Digital Inx Sel  is set to  option 2  4  5  6  11  12  13  14 and the digital input is active  the speed reference commanded by  P108  Speed Reference  will be overridden  Refer to the flowchart on page 1 19 for more information  on speed reference control priority     Options 0    Drive Pot     Default  Internal frequency command from the potentiometer on the  integral keypad                       InternalFreq    Internal frequency command from A409  Internal Freq    2    0 10V Input    External frequency command from the 0 10V analog input or  remote potentiometer   3     4 20mA Input    External frequency command from the 4 20mA analog input      Preset Freq    External frequency command as defined by A410   A413     Preset Freq x  when t201 and 1202  Digital Inx Sel  are  programmed as    Preset Frequencies    and the digital inputs          are active   5    Comm Port    External frequency command from the communications port   P109
80. ll start  automatically when power is cycled     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 10 Programming and Parameters    Basic Program Group  continued     P107  Stop Mode   Active stop mode for all stop sources  e g  keypad  run forward  I O Terminal 02   run reverse  I O  Terminal 03   RS485 port  except as noted below     Important  I O Terminal 01 is always a coast to stop input except when P106  Start Source  is set for   3 Wire  control  When in three wire control  I O Terminal 01 is controlled by P107  Stop Mode      Related Parameter s   P106  A418  A425  A427  C304                               Options 0    Ramp  CF    Default  Ramp to Stop     Stop    command clears active fault   1    Coast  CF   Coast to Stop     Stop    command clears active fault   2    DC Brake  CF   Prl njection Braking Stop     Stop    command clears active  ault   3    DCBrkAuto  CF  DC Injection Braking Stop with Auto Shutoff   e Standard DC Injection Braking for value set in A424  DC  Brake Time    OR  e Drive shuts off if the drive detects that the motor is  stopped      Stop    command clears active fault   4    Ramp    Ramp to Stop   5    Coast    Coast to Stop   6    DC Brake    DC Injection Braking Stop   7    DC BrakeAuto    DC Injection Braking Stop with Auto Shutoff      1  Stop input also clears active fault     e Standard DC Injection Braking for value set in A424  DC  Brake Time      OR  e Drive shuts off if current 
81. load  70 Power Unit Fail  80 AutoTune Fail  81 Communication Loss  100 Parameter Checksum Error  122 I O Board Fail          PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    RS485  DSI  Protocol C 7    Reading  03  and Writing  06  Drive Parameters    To access drive parameters  the Modbus register address equals the  parameter number  For example  a decimal    1    is used to address  Parameter d001  Output Freq  and decimal    39    is used to address  Parameter P109  Accel Time 1      Additional Information    Refer to http   www ab com drives  for additional information     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    C 8 RS485  DSI  Protocol    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Appendix D    RJ45 DSI Splitter Cable    The PowerFlex 4M drive provides a RJ45 port to allow the connection of  a single peripheral device  The RJ45 DSI Splitter Cable can be used to  connect a second DSI peripheral device to the drive     Connectivity Guidelines    peripherals may not perform as intended if these Connectivity  Guidelines are not followed  Precautions should be taken to follow  these Connectivity Guidelines     ATTENTION  Risk of injury or equipment damage exists  The    e Two peripherals maximum can be attached to a drive    e Ifa single peripheral is used  it must be connected to the Master port   M
82. m the drive    3    Reverse    Drive is commanded to run in reverse direction    4    Motor Overld  Motor overload condition exists    5    Ramp Reg    Ramp regulator is modifying the programmed accel decel  times to avoid an overcurrent or overvoltage fault from  occurring    6    Above Freq    Drive exceeds the frequency  Hz  value set in t222  Relay Out  Level     7    Above Cur    Drive exceeds the current    Amps  value set in t222  Relay  Out Level     Important  Value for t222  Relay Out Level  must be entered  in percent of drive rated output current    8    Above DCVolt  Drive exceeds the DC bus voltage value set in t222  Relay  Out Level     9    Retries Exst  Value set in A451  Auto Rstrt Tries  is exceeded    10    Above Anlg V    e Analog input voltage  I O Terminal 13  exceeds the value   set in 1222  Relay Out Level     e This parameter setting can also be used to indicate a PTC  trip point when the input  I O Terminal 13  is wired to a  PTC and external resistor    e Use t222 to set threshold    11  ParamControf  Enables the output to be controlled over network  communications by writing to t222  Relay Out Level     0   Off  1   On     12    NonRec Fault    e Value set in A451  Auto Rstrt Tries  is exceeded     e A451  Auto Rstrt Tries  is not enabled   e ANon resettable fault has occurred     13    I O Control    Enables the output to be controlled by bit 6 of the logic  command word  See Writing  06  Logic Command Data on  page C 4 for more information     1
83. mms Power  Supply    Optional 100 240V AC Power Supply for External  DSI Communications Kit     20 XCOMM AC PS1       Compact I O Module    Three channel     1769 SM2       Serial Converter Module   RS485 to RS232     Provides serial communication via DF1 protocol  for use with DriveExplorer and DriveExecutive  software  Includes    DSI to RS232 serial converter  1    1203 SFC serial cable  1    22 RJ45CBL C20 cable  1    DriveExplorer Lite CD  1     22 SCM 232       DSI Cable    2 0 meter RJ45 to RJ45 cable  male to male  connectors     22 RJ45CBL C20       Serial Cable    2 0 meter serial cable with a locking low profile  connector to connect to the serial converter and a  9 pin sub miniature D female connector to  connect to a computer     1203 SFC       Null Cable Converter    For use when connecting the serial converter to  DriveExplorer on a handheld PC     1203 SNM       Splitter Cable    RJA5 one to two port splitter cable    AK U0 RJ45 SC1       Terminating Resistors    RJ45 120 Ohm resistors  2 pieces     AK U0 RJ45 TR1       Terminal Block    RJA5 Two position terminal block  5 pieces     AK U0 RJ45 TB2P          DriveExplorer Software   Windows based software package that provides   9306 4EXP01ENE   CD ROM  Version 3 01   an intuitive means for monitoring or configuring  or later Allen Bradley drives and communication adapters  online   Compatibility  Windows 95  98  ME  NT 4 0   Service Pack 3 or later   2000  XP and ce    DriveExecutive software   Windows based 
84. mper or inductor  connected   UTI To Motor U T1 Q Switch any two motor  W T2 To Motor V T2   G 1G leads to change forward  W T3 To Motor W T3     direction     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 12    Terminal    Installation Wiring    Description    DCHO  DC  JDC Bus Connection       BR     BR      Dynamic Brake Resistor Connection             Safety Ground   PE        i   For Frame C only  5 5 kW  7 5 HP  ratings and higher      Not applicable to 120 V  1 Phase drives     A    Table 1 F Power Terminal Block Specifications          Frame   Maximum Wire Size     Minimum Wire Size  Torque   A 3 3mm   12 AWG      10 8 mm   18 AWG  1 4 1 6 N m  12 14 Ib  in    B 8 4 mm   8 AWG  0 8 mm   18 AWG  1 6 1 9 N m  14 17 Ib  in    c 13 3mm   6 AWG  13 3mm   12 AWG     _   2 7 3 2  N m  24 28 Ib  in                1  Maximum minimum sizes that the terminal block will accept   these are not  recommendations     Motor Start Stop Precautions    ATTENTION  A contactor or other device that routinely disconnects  and reapplies the AC line to the drive to start and stop the motor can  cause drive hardware damage  The drive is designed to use control input  signals that will start and stop the motor  If used  the input device must  not exceed one operation per minute or drive damage can occur     ATTENTION  The drive start stop control circuitry includes  solid state components  If hazards due to accidental contact with  moving m
85. nal Supply  SRC   Run FWD Run REV  P106  Start Source    2  3 7 jo  Input must be active for Sop Run    03 Forward  the drive to run  When Forward OTO  input is opened  the drive oe slop Pun  will stop as specified by Stop Run  P107  Stop Mode   ve sV Common  If both Run Forward and  Run Reverse inputs are igital j  dosed at th   same time  Each digital input draws 6 mA   an undetermined state  could occur   2 Wire SNK Control   Internal Supply  SNK   Run FWD Run REV     J01  Sio un pa  02  Foward S   03  os    od  Stop Run  Reverse    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E                                                                                                          Installation Wiring 1 17   Input Connection Example  3 Wire SRC Control   Internal Supply  SRC  External Supply  SRC   Non Reversing  P106  Start Source    1  A momentary input will 6   01 01  start the drive  A stop B  jo2 02  input to I O Terminal 01     will stop the drive as i  specified bv P107  Stop    e  Mode    24V Common   Each digital input draws 6 mA   3 Wire SNK Control      Non Reversing                      3 Wire SRC Control    Reversing    P106  Start Source    1    A momentary input will  start the drive  A stop  input to I O Terminal 01  will stop the drive as  specified by P107  Stop  Mode   I O Terminal 03  determines direction     External Supply  SRC                          9   01  9   02      08    9   04          O   24V 
86. ngs  for t201   t202  Digital Inx Select     e Check P108  Speed Reference   for the source of the speed  reference  Reprogram as  necessary    e Review the Speed Reference  Control chart on page 1 19           PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    Troubleshooting 4 7    Motor and or drive will not accelerate to commanded speed                             Cause s  Indication Corrective Action   Acceleration time is excessive    None Reprogram P109  Accel Time 1  or  A401  Accel Time 2     Excess load or short None Compare 4003  Output Current  with   acceleration times force the A441  Current Limit     drive into current limit  slowing Remove excess load or reprogram   or stopping acceleration  P109  Accel Time 1  or A401  Accel  Time 2    Check for improper A453  Boost  Select  setting    Speed command source or _  None Verify d002  Commanded Freq     value is not as expected  Check d012  Control Source  for the  proper Speed Command    Programming is preventing the   None Check P105  Maximum Freq  to   drive output from exceeding insure that speed is not limited by   limiting values  programming    Motor operation is unstable    Cause s  Indication Corrective Action   Motor data was incorrectly None 1  Correctly enter motor nameplate   entered  data into P101  P102 and P103   2  Enable A436  Compensation    3  Use A453  Boost Select  to   reduce boost level              Drive will not reverse motor direction   
87. o not route more than  three sets of motor leads in a single conduit to minimize    cross talk     If  more than three drive motor connections per conduit are required   shielded cable must be used    UL installations in 50  C ambient must use 600V  75  C or 90  C wire   UL installations in 40  C ambient should use 600V  75  C or 90  C wire   Use copper wire only  Wire gauge requirements and recommendations  are based on 75 degree C  Do not reduce wire gauge when using higher  temperature wire     Unshielded   THHN  THWN or similar wire is acceptable for drive installation in dry  environments provided adequate free air space and or conduit fill rates  limits are provided  Do not use THHN or similarly coated wire in wet  areas  Any wire chosen must have a minimum insulation thickness of  15 mils and should not have large variations in insulation concentricity     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E          1 10 Installation Wiring  Shielded  Location Rating Type Description  Standard 600V  75  C or 90  C  167  F  e Four tinned copper conductors with XLPE insulation   Option 1  jor 194  F  RHH RHW 2  e Foil shield and tinned copper drain wire with 85  braid  Belden 29501 29507 or coverage  equivalent e PVC jacket  Standard Tray rated 600V  75  C or  e Three tinned copper conductors with XLPE insulation   Option 2    90  C  167  F or 194  F  e 5 mil single helical copper tape  25  overlap min    RHH RHW 2 with three 
88. oceed  Remove All Power including user  supplied control voltages  User supplied voltages may exist even when  main AC power is not applied to the drive  Correct the malfunction  before continuing     Prepare For Drive Start Up  Before Applying Power to the Drive    1  Confirm that all inputs are connected to the correct terminals and are  secure     2  Verify that AC line power at the disconnect device is within the rated  value of the drive     3  Verify that any digital control power is 24 volts     4  Verify that the Sink  SNK  Source  SRC  Setup DIP Switch is set to  match your control wiring scheme  See Figure 1 5 on page l 14 for  location        Important  The default control scheme is Source  SRC   The Stop  terminal is jumpered  I O Terminals 01 and 11  to allow  starting from the keypad  If the control scheme is changed  to Sink  SNK   the jumper must be removed from I O  Terminals 01 and 11 and installed between I O Terminals  01 and 04     5  Verify that the Stop input is present or the drive will not start     Important  If I O Terminal 01 is used as a stop input  the jumper  between I O Terminals 01 and 11 must be removed     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    2 2    Start Up    Applying Power to the Drive   6  Apply AC power and control voltages to the drive    7  Familiarize yourself with the integral keypad features  see page 2 3   before setting any Program Group parameters    Start  Stop  Dir
89. on on    See page     About Parameters 3 1  Parameter Organization 3 2   Display Group 3 3   Basic Program Group 3 8  Terminal Block Group 3 13  Communications Group 3 17  Advanced Program Group 3 19  Parameter Cross Reference     by Name 3 31       About Parameters    To configure a drive to operate in a specific way  drive parameters may  have to be set  Three types of parameters exist     e ENUM  ENUM parameters allow a selection from 2 or more items  Each item  is represented by a number     e Numeric Parameters  These parameters have a single numerical value  i e  0 1 Volts      e Bit Parameters  Bit parameters have four individual bits associated with features or  conditions  If the bit is 0  the feature is off or the condition is false  If  the bit is 1  the feature is on or the condition is true     Some parameters are marked as follows           Stop drive before changing this parameter     W     32 bit parameter  Parameters marked 32 bit will have two  parameter numbers when using RS485 communications and  programming software     PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Programming and Parameters    Parameter Organization    Group  Basic Display    Display To    Basic Program       Terminal Block          Communications       Advanced Program          Publication 22F UM001D EN E    Parameters    Output Freq  Commanded Freq  Output Curren
90. onnecting an RS 485 Network          D 3    Index    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Preface    Overview    The purpose of this manual is to provide you with the basic information  needed to install  start up and troubleshoot the PowerFlex 4M  Adjustable Frequency AC Drive                       For information on    See page     Who Should Use this Manual  P 1  Reference Materials P 1  Manual Conventions P 2  Drive Frame Sizes p2  General Precautions P 3  Catalog Number Explanation P 4          Who Should Use this Manual     This manual is intended for qualified personnel  You must be able to  program and operate Adjustable Frequency AC Drive devices  In  addition  you must have an understanding of the parameter settings and  functions     Reference Materials    The following manuals are recommended for general drive information     Title Publication Available Online at      Wiring and Grounding DRIVES INO01     Guidelines for Pulse Width  Modulated  PWM  AC Drives  Preventive Maintenance of DRIVES SB001     Industrial Control and Drive  System Equipment          Safety Guidelines for the SGI 1 1 www rockwellautomation com   Application  Installation and literature   Maintenance of Solid State   Control       A Global Reference Guide for  0100 2 10  Reading Schematic Diagrams  Guarding Against Electrostatic  8000 4 5 2  Damage             PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Pu
91. onstrated using  harmonized European Norm  EN  standards published in the Official  Journal of the European Communities  PowerFlex Drives comply with  the EN standards listed below when installed according to the User  Manual     CE Declarations of Conformity are available online at   http   www ab com certification ce docs     Low Voltage Directive  73 23 EEC     e EN50178 Electronic equipment for use in power installations    EMC Directive  89 336 EEC     e EN61800 3 Adjustable speed electrical power drive systems Part 3   EMC product standard including specific test methods     General Notes   e The motor cable should be kept as short as possible in order to avoid  electromagnetic emission as well as capacitive currents    e Use of line filters in ungrounded systems is not recommended    e Conformity of the drive with CE EMC requirements does not  guarantee an entire machine installation complies with CE EMC  requirements  Many factors can influence total machine installation  compliance     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    1 22     gt     Installation Wiring    Essential Requirements for CE Compliance    Conditions 1 3 listed below must be satisfied for PowerFlex drives to  meet the requirements of EN61800 3     1  Grounding as described in Figure 1 6  Refer to page 1 6 for  additional grounding recommendations     2  Output power  control  I O  and signal wiring must be braided   shielded cable with a cov
92. ordered with internal    S Ty  explanation on page P 4 and Table B B for detai          S     pe    filters  Refer to the Catalog Number     3  This filter is suitable for use with a cable length up to 100 meters  328 feet  for Class A and    25 meters  82 feet  for Class B environments     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    Accessories and Dimensions    B 5    Table B G Human Interface Module  HIM  Option Kits and Accessories    Item    LCD Display  Remote Panel    Mount    Description    Digital speed control   CopyCat capable   IP66  NEMA Type 4X 12  indoor use only  22 HIM C2 includes 2 9 meter cable   22 HIM C28 includes 2 meter cable     Catalog Number    22 HIM C2  22 HIM C2s  1        LCD Display  Remote Handheld    Digital speed control   Full numeric keypad   CopyCat capable   IP30  NEMA Type 1    Includes 1 0 meter cable   Panel mount with optional Bezel Kit    22 HIM A3       Bezel Kit    Panel mount for LCD Displav  Remote  Handheld unit  IP30  NEMA Tvpe 1     22 HIM B1       DSI HIM Cable   DSI HIM to RJ45 cable      1   The 22 HIM C2S is smaller than the 22 H    1 0 Meter  3 3 Feet   2 9 Meter  9 51 Feet           Table B H Communication Option Kits    Item    External DSI     Communications Kit    Description  External mounting kit for 22 COMM C   D   E   P     22 HIM H10  22 HIM H30       M C2 and cannot be used as a direct replacement     Catalog Number  2   22 XCOMM DC BASE       External Co
93. re saved and stored in  Non Volatile Storage  NVS  or RAM only  If they are stored in RAM  the values will be lost at  power down     Options 0    Save     Default           1    RAM Only          ATTENTION  Risk of equipment damage exists  If a controller is programmed to  write parameter data to Non Volatile Storage  NVS  frequently  the NVS will quickly  exceed its life cycle and cause the drive to malfunction  Do not create a program that  frequently uses configurable outputs to write parameter data to NVS unless C307   Comm Write Mode  is set to option 1     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 19    Advanced Program Group    A401  Accel Time 2  Related Parameter s   P109    When active  sets the rate of acceleration for all speed increases except jog  Refer to the flowchart on  page 1 20 for details     Maximum Freq             Accel Time   Accel pate  Values Default 20 0 Secs  Min Max  0 0 600 0 Secs  Display  0 1 Secs       P105  Maximum Freq     Speed       ry P109 or A401 jq    P110 or A402  0  Accel Time x     le     Decel Time x     Time    A402  Decel Time 2  Related Parameter s   P110    When active  sets the rate of deceleration for all speed decreases except jog  Refer to the flowchart  on page 1 20 for details     Maximum Freq             Decel Time   Decel Rate  Values Default 20 0 Secs  Min Max  0 1 600 0 Secs  Display  0 1 Secs       P105  Maximum Freq        A P109
94. rip occurs at 810V DC bus voltage  equivalent to 575V AC incoming line                            Under Voltage  100 120V AC Input     Trip occurs at 210V DC bus voltage  equivalent to 75V AC incoming line   200 240V AC Input     Trip occurs at 210V DC bus voltage  equivalent to 150V AC incoming line   380 480V AC Input     Trip occurs at 390V DC bus voltage  equivalent to 275V AC incoming line     Control Ride Through  Minimum ride through is 0 5 Secs   typical value 2 Secs  Faultless Power Ride Through  100 milliseconds  Dynamic Braking    Internal brake IGBT included with power ratings 5 5 kW  7 5 HP  and 7 5 kW  10 0 HP  for 240V  3 phase drives and 5 5 kW   7 5 HP   7 5 kW  10 0 HP  and 11 0 kW  15 0 HP  for 480V  3 phase drives  See Appendix B for ordering information                 PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E                                                                         A 4 Supplemental Drive Information  Category Specification  Environment Altitude  1000 m  3300 ft  max  without derating  Maximum Surrounding Air  Temperature without derating   IP20   10 to 50   C  14 to 122   F   IP20 zero stacking   10 to 40   C  14 to 104   F   Cooling Method  Convection  120V  1 Phase  0 75 kW  1 HP  and below  240V  1 Phase  0 4 kW  0 5 HP  and below  240V  3 Phase  0 75 kW  1 HP  and below  480V  3 Phase  0 75 kW  1 HP  and below  Fan  All other drive ratings    Storage Temperature     40 to 85 degree
95. roup  continued              A457  Maximum Voltage    Sets the highest voltage the drive will output    Values Default Drive Rated Volts  Min Max  20 Drive Rated Volts  Display  1 VAC    A458  Program Lock     Protects parameters against change by unauthorized personnel        Options 0    Unlocked     Default                 1    Locked     A459  Testpoint Sel   Used by Rockwell Automation field service personnel   Values Default 400  Min Max  O FFFF  Display  1 Hex    A461  Motor NP FLA     Set to the motor nameplate rated full load amps              Values Default Drive Rated Amps  Min Max  0 1  Drive Rated Amps x 2   Display  0 1 Amps    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters    Parameter Cross Reference     by Name    Parameter Name    Number Group       Accel Time 1  Accel Time 2  Analog In 0 10V  Analog In 4 20mA  Anlg In 0 10V Hi  Anlg In 0 10V Lo  Anlg In4 20mA Hi  Anlg In4 20mA Lo  Auto Rstrt Delay  Auto Rstrt Tries  Boost Select   Bus Reg Mode  Comm Data Rate  Comm Format  Comm Loss Action  Comm Loss Time  Comm Node Addr  Comm Status  Comm Write Mode  Commanded Freq  Compensation  Contrl In Status  Control Source  Control SW Ver  Current Limit   DB Duty Cycle  DB Resistor Sel  DC Brake Level  DC Brake Time  DC Bus Voltage  Decel Time 1  Decel Time 2   Dig In Status  Digital In1 Sel  Digital In2 Sel  Drive Status   Drive Temp   Drive Type  Elapsed Run Time  Fault 1 Code  Fault 2 
96. s    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 23    Advanced Program Group  continued     A425  DC Brake Level  Related Parameter s   P107  A418    Defines the maximum DC brake current  in amps  applied to the motor when P107  Stop Mode  is set  to either    Ramp    or    DC Brake                    Values Default Drive Rated Amps x 0 05  Min Max  0 0  Drive Rated Amps x 1 8   Display  0 1 Amps  Ramp to Stop Mode DC Injection Braking Mode     lt   S  a   a             Speed    DC Brake Time     Volts Speed  Volts Speed        DC Brake Level       Time   Time  Stop Command Stop Command    ATTENTION  Ifa hazard of injury due to movement of equipment or material exists   A an auxiliary mechanical braking device must be used     ATTENTION  This feature should not be used with synchronous or permanent  A magnet motors  Motors may be demagnetized during braking     A427  DB Resistor Sel  Related Parameter s   A428      Stop drive before changing this parameter   Enables disables external dynamic braking  This parameter applies only to Frame C drives     Setting Min Max    0    Disabled      1    Normal RA Res     5  Duty Cycle    Refer to Table B C on page B 2  2    No Protection     100  Duty Cycle    3      Duty Cycle    Limited  1      99  of Duty Cycle    see A428    The drive is able to provide full braking indefinitely  Braking power is limited by the external DB  resistor  When this param
97. s C   40 to 185 degrees F    Atmosphere  Important  Drive must not be installed in an  area where the ambient atmosphere contains  volatile or corrosive gas  vapors or dust  If the  drive is not going to be installed for a period of  time  it must be stored in an area where it will not  be exposed to a corrosive atmosphere    Relative Humidity  0 to 95  non condensing   Shock  operating   15G peak for 11ms duration    1 0ms    Vibration  operating   1G peak  5 to 2000 Hz   Control Carrier Frequency 2 10 kHz  Drive rating based on 4 kHz    Frequency Accuracy   Digital Input  Within  0 05  of set output frequency   Analog Input  Within 0 5  of maximum output frequency    Speed Regulation   Open Loop   2  of base speed across a 40 1 speed range    with Slip Compensation    Stop Modes  Multiple programmable stop modes including    Ramp  Coast  DC Brake  Ramp to Hold and   Curve    Acceleration Deceleration  Two independently programmable acceleration  and deceleration times  Each time may be  programmed from 0   600 seconds in 0 1 second  Increments    Intermittent Overload  150  Overload capability for up to 1 minute  200  Overload capability for up to 3 seconds   Electronic Motor Overload Provides class 10 motor overload protection   Protection according to NEC article 430 and motor  over temperature protection according to NEC  article 430 126  A   2   UL 508C File 29572    Electrical Voltage Tolerance  200 240V  10   380 480V  10   460 600V  10    Frequency Tolerance  48 63 H
98. s Default Read Only  Min Max  Based on Drive Rating  Display  1 VDC    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 4 Programming and Parameters    Display Group  continued                                            d006  Drive Status  Related Parameter s   A434  Present operating condition of the drive   ANA  Wii    1   Condition True  0   Condition False  Running Bit 0  Forward Bit 1  Accelerating Bit 2  Decelerating Bit 3                Values Default Read Only  Min Max  0 1  Displav  1    d007  Fault 1 Code    d008  Fault 2 Code    d009  Fault 3 Code    A code that represents a drive fault  The codes will appear in these parameters in the order they occur   d007  Fault 1 Code    the most recent fault   Repetitive faults will only be recorded once    Refer to Chapter 4 for fault code descriptions              Values Default Read Only  Min Max  F2 F122  Display  FI  d010  Process Display  Related Parameter s   d001  A440  A438  A439     7 32 bit parameter     The output frequency scaled by A440  Process Factor  or by A438  Process Time Lo  and A439   Process Time Hil     Output   Process _ Process  Freq Factor   Display             Values Default Read Only  Min Max  0 00 9999  Display  0 01  1    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 5    Display Group  continued     d012  Control Source  Related Parameter s   P106  P108  t201  
99. s two resistors wired in parallel     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E                                                                   Accessories and Dimensions B 3  Table B D Bulletin 1321 3R Series Line Reactors  Maximum  Fundamental   Continuous Watts   Catalog  Input Voltage   kW  HP  Amps Amps Inductance  Loss _   Number  1   240V 50 60 Hz  0 2 10 25 12 3 12 0 mh 7 5W   1321 3R2 A  grase o4 105 14 6 120mh  21W   1321 3R4 D  0 75  1 0  8 12 3 0 mh 29W 1321 3R8 B  1 5  20  8 12 1 5 mh 19 5 W   1321 3R8 A  2 2  3 0  12 18 1 25 mh 26 W 1321 3R12 A  3 7  5 0  18 27 0 5 mh 36 W 1321 3R18 A  5 5  7 5 125 37 5 0 5 mh 48 W 1321 3R25 A  7 5  10 0  35 52 5 0 4 mh 49 W 1321 3R35 A  480V 50 60 Hz  0 4 10 5   2 3 20 0 mh 11 3W_ 1321 3R2 B  3 Phase 0 75 11014 6 9 0mh   20W 11321 3A4 C  15  2 0  4 6 6 5 mh 20 W 1321 3R4 B  2 2  3 0  8 12 5 0 mh 25 3 W   1321 3R8 C  3 7  5 0   12 18 2 5 mh 31 W 1321 3R12 B  55  7 5   12 18 2 5 mh 31 W 1321 3R12 B  75  10 0   18 27 1 5 mh 43 W 1321 3R18 B  11 0  15 0   25 37 5 1 2mh 52 W 1321 3R25 B   1  Catalog numbers listed are for 3  impedance open style units  NEMA Type 1 and 5  impedance  reactor types are also available  Refer to publication 1321 TD001        Table B E DC Bus Inductors             Inductance  Input Voltage kw HP Amps Imh MTE Catalog Number  2   240V 50 60 Hz 5 5 75 32 0 85 32RB001  S phase 75 100  40 05 40RB001  480V 50 60 Hz 5 5 7 5 18 3 75 18RB004  3 Phase 75 100 
100. scriptions   The voltage must be zero     Darkened LEDs or a darkened LCD display is not an indication that  capacitors have discharged to safe voltage levels     ATTENTION  Only qualified personnel familiar with adjustable  frequency AC drives and associated machinery should plan or  implement the installation  start up and subsequent maintenance of the  system  Failure to comply may result in personal injury and or  equipment damage     ATTENTION  This drive contains ESD  Electrostatic Discharge   sensitive parts and assemblies  Static control precautions are required  when installing  testing  servicing or repairing this assembly   Component damage may result if ESD control procedures are not  followed  If you are not familiar with static control procedures   reference A B publication 8000 4 5 2     Guarding Against Electrostatic  Damage    or any other applicable ESD protection handbook     ATTENTION  An incorrectly applied or installed drive can result in  component damage or a reduction in product life  Wiring or application  errors  such as  undersizing the motor  incorrect or inadequate AC  supply  or excessive ambient temperatures may result in malfunction of  the system     ATTENTION  The bus regulator function is extremely useful for  preventing nuisance overvoltage faults resulting from aggressive  decelerations  overhauling loads  and eccentric loads  However  it can  also cause either of the following two conditions to occur    1  Fast positive changes in input 
101. software package that provides   9303 4DTEO1ENE     CD ROM  Version 1 01  or later       an intuitive means for monitoring or configuring  Allen Bradley drives and communication adapters  online and offline    Compatibility  Windows 98  ME  NT 4 0  Service  Pack 3 or later   2000 and XP     i  See www ab com drives driveexplorer htm for supported devices    2  For pricing information  refer to the PowerFlex 4 Class Price List  Publication 22 PL001           PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    B 6 Accessories and Dimensions    Product Dimensions  Table B I PowerFlex 4M Panel Mount Drives     Ratings are in kW and  HP           oO      120V AC 1 Phase   240V AC   1 Phase   240V AC   3 Phase   480V AC   3 Phase  L  A 102 025  0 2  0 25  0 2  0 25  0 4  0 5   0 4  0 5  0 4  0 5  0 4  0 5  0 75  1 0   0 75  1 0  0 75  1 0  1 5  2 0   1 5  2 0   B 10 75  1 0  1 5  2 0  2 2  3 0  2 2  3 0   1 1  1 5  22  3 0  3 7  5 0  3 7  5 0   C    5 5  7 5  5 5  7 5   7 5  10 0  75  10 0   11 0  15 0              Figure B 1 PowerFlex 4M Panel Mount Drives      Dimensions are in millimeters and  inches   Weights are in kilograms and  pounds            a                                                                                                                                                             e mb 19  5 Gan  dc  f Note   Wee So  fi   1   m DIN rail mounting is not applicable to Frame C   i i Shipping  Frame    a b c d e
102. ss  A 5  Wiring  1 1  Block Diagram  1 14  I O  1 13   O Examples  1 15  1 18  Potentiometer  1 15  Power  1 9  PTC Example  1 15    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Index 4    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    o    www rockwellautomation com       Power  Control and Information Solutions Headquarters    Americas  Rockwell Automation  1201 South Second Street  Milwaukee  WI 53204 2496 USA  Tel   1  414 382 2000  Fax   1  414 382 4444  Europe Middle East Africa  Rockwell Automation  Vorstlaan Boulevard du Souverain 36  1170 Brussels  Belgium  Tel   32  2 663 0600  Fax   32  2 663 0640  Asia Pacific  Rockwell Automation  Level 14  Core F Cyberport 3  100 Cyberport Road  Hong Kong  Tel   852  2887 4788  Fax   852  2508 1846    Publication 22F UM001D EN E     June 2013  Supersedes 22F UM001C EN E     July 2008 Copyright    2013 Rockwell Automation  Inc  All rights reserved     
103. start after a stop input  loss of power or fault condition     Options 0    Keypad     Default  e Integral keypad controls drive operation   e 1 O Terminal 1    Stop      coast to stop     e When active  the Reverse key is also active unless  disabled by A434  Reverse Disable                           1  3 Wire  I O Terminal 1    Stop      stop according to the value set in  P107  Stop Mode    2  2 Wire  I O Terminal 1    Stop      coast to stop   3    2 W Lvl Sens    Drive will restart after a    Stop    command when   e Stop is removed  and    e Start is held active    ATTENTION  Hazard of injury exists due to unintended operation  When  P106  Start Source  is set to option 3  and the Run input is maintained  the  Run inputs do not need to be toggled after a Stop input for the drive to run  again  A Stop function is provided only when the Stop input is active  open         4    2 W Hi Speed    Important  There is greater potential voltage on the output  terminals when using this option     e Outputs are kept in a ready to run state  The drive will  respond to a    Start    command within 10 ms     e   O Terminal 1    Stop      coast to stop        5    Comm Port   e Remote communications  Refer to Appendix C for details   e 1 0 Terminal 1    Stop      coast to stop     W  When using option 5    Comm Port     if the drive is using a network for control and the user s program  is maintaining a    Start    or    Jog    command without sending a    Stop command     the drive wi
104. t  Output Voltage  DC Bus Voltage  Drive Status   Fault 1 Code  Fault 2 Code  Fault 3 Code  Process Display    Motor NP Volts  Motor NP Hertz  Motor OL Current  Minimum Freq  Maximum Freq  Start Source    Digital In1 Sel  Digital In2 Sel  Analog In 0 10V Lo  Analog In 0 10V Hi    Language   Comm Data Rate  Comm Node Addr  Comm Loss Action  Comm Loss Time  Comm Format  Comm Write Mode    Accel Time 2  Decel Time 2   S Curve     Jog Frequency  Jog Accel Decel  Internal Freq  Preset Freq 0  Preset Freq 1  Preset Freq 2  Preset Freq 3  Skip Frequency  Skip Freq Band  DC Brake Time  DC Brake Level  DB Resistor Sel  DB Duty Cycle  Start At PowerUp  Reverse Disable  Flying Start En    d001  d002  d003  d004  d005  d006  d007  d008  d009  d010    P101  P102  P103  P104  P105  P106    t201  t202  t211  t212    C301  C302  C303  C304  C305  C306  C307    A401  A402  A403  A404  A405  A409  A410  A411  A412  A413  A418  A419  A424  A425  A427  A428  A433  A434  A435    Control Source  Contrl In Status  Dig In Status  Comm Status  Control SW Ver  Drive Type  Elapsed Run Time  Testpoint Data  Analog In 0 10V  Analog In 4 20mA  Drive Temp    Stop Mode  Speed Reference  Accel Time 1  Decel Time 1  Motor OL Ret  Reset To Defalts          Analog In 4 20mA Lo  Analog In 4 20mA Hi  Relav Out Sel   Relav Out Level    Compensation  Slip Hertz   FLA  Process Time Lo  Process Time Hi  Process Factor  Bus Reg Mode  Current Limit  Motor OL Select  PWM Frequency  SW Current Trip  Fault Clear   Auto Rs
105. t Protection  Number Voltage 140M Motor Min  Enejosurg  kW  HP   Amps Range  kVA  Amps  Fuses  Protectors    3   Contactors  Volume     in       100   120V AC   10     1 Phase Input  0   230V 3 Phase Output  22F V1P6N103 0 2  0 25   1 6 90 126 0 8  6 4 10 140M C2E C10 J100 CO9 1655       22F V2P5N103  0 4 0 5  12 5 90 126 71 1  9 0 15 140M C2E C16  100 C12 1655       22F V4P5N103 0 75  1 0  14 5 90 126  2 2  18 0  30 140M D8E C20  100 C23 1655       22F V6PON103  1 1  1 5   6 0 90 126  29  24 0  40 140M F8E C32   100 C30 1655  200   240V AC   10     1 Phase Input  0   230V 3 Phase Output  22F A1P6N103 0 2  0 25   1 6 180 265  0 7 5 3 10 140M C2E B63  100 C09 1655       22F A2P5N103  0 4  0 5  12 5 180 265  1 6  6 5 10 140M C2E C10   100 C09 1655       22F A4P2N103  0 75  1 0  14 2 180 265  2 0 8 2 15 140M C2E C16  100 C12 1655       22F A8PON103  1 5  2 0  8 0 180 265  5 4   22 3  35 140M D8E C25  100 C23 1655       22F AO11N103  2 2 3 0   11 0  180 265 5 9 24 3  40 140M F8E C32   100 C30 1655  200   240V AC   10     1 Phase Input  0   230V 3 Phase Output  with Filter  22F A1P6N113 0 2  0 25   1 6 180 265  1 3   5 3 10 140M C2E B63   100 C09 1655       22F A2P5N113  0 4  0 5  12 5 180 265  1 6  6 5 10 140M C2E C10  100 C09 1655       22F A4P2N113 0 75  1 0  14 2 180 265  2 0 8 2 15 140M C2E C16  100 C12 1655       22F A8PON113  1 5 2 0  8 0 180 265  5 4   22 3  35 140M D8E C25   100 C23 1655       22F A011N113  2 2 3 0   11 0  180 265  5 9 24 3 J40 140M F8E C32  100 C30 1655 
106. ternational codes  standards  regulations or industry             guidelines   Values Default 0  Min Max  0 9  Display  1  A452  Auto Rstrt Delay  Related Parameter s   A451    Sets the time between restart attempts when A451  Auto Rstrt Tries  is set to a value other than zero        Values Default 1 0 Secs       Min Max  0 0 120 0 Secs       Display  0 1 Secs    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 29    Advanced Program Group  continued     A453  Boost Select  Related Parameter s   d004  P101  P102  Sets the boost voltage    of P101  Motor NP Volts   and redefines the Volts per Hz curve   1      i  Drive may add additional voltage unless option 5 is selected        Options 1    30 0  VT        35 0  VT                                                         Variable Torque  3    40 0  VT     4    45 0  VT     5    0 0 no IR     6 0 0   7    2 5  CT      Default for  3 7  5 5  7 5  amp  11 0 kW   5 0  7 5  10 0  amp  15 0 HP  Drives   8 _ 5 0  CT     Default  Constant Torque     7 5  CT     10    10 0  CT     11    12 5  CT     12    15 0  CT     13    17 5  CT     14    20 0  CT     100    1 2  Motor NP Volts     50 F             4  5 E   a a  a T F 1  v      Settings i   a  5 14 l 2   e LE  4  50 100    96 P102  Motor NP Hertz     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 30 Programming and Parameters    Advanced Program G
107. time drive is outputting power  Time is displayed in 10 hour increments                                               Values Default Read Only  Min Max  0 9999 Hrs  Display  1    10 Hrs   d019  Testpoint Data  Related Parameter s   A459  The present value of the function selected in A459  Testpoint Sel    Values Default Read Only  Min Max  O FFFF  Display  1 Hex  d020  Analog In 0 10V  Related Parameter s   t211  t212  The present value of the voltage at I O Terminal 13  100 0    10 volts    Values Default Read Only  Min Max  0 0 100 0   Display  0 1   d021  Analog In 4 20mA  Related Parameter s   1213  t214  The present value of the current at I O Terminal 15  0 0    4mA  100 0    20mA    Values Default Read Only  Min Max  0 0 100 0   Display  0 1     d022  Drive Temp     Present operating temperature of the drive power section              Values Default Read Only  Min Max  0 120 degC  Display  1 degC    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 8 Programming and Parameters    Basic Program Group    P101  Motor NP Volts  Related Parameter s   004  A453       Stop drive before changing this parameter   Set to the motor nameplate rated voltage                    Values Default Based on Drive Rating  Min Max  20 Drive Rated Voltage  Display  1 VAC  P102  Motor NP Hertz  Related Parameter s   A453  A444        Stop drive before changing this parameter   Set to the motor nameplate rated frequency                 Values 
108. to the PowerFlex 4M  User Manual since the July 2008 release     Manual Updates          Description of New or Updated Information Page s   Minimum Enclosure Volume column and new footnotes added  1 8  A 2  Drive  Fuse  amp  Circuit Breaker Ratings topic updated  A 1  Electronic Motor Overload Protection description updated  A 4       The information below summarizes the changes to the PowerFlex 4M  User Manual since the August 2007 release     Manual Updates                Description of New or Updated Information Page s   Footnote  2  deleted from    EN61800 3 Second Environment    in Table 1 1  1 22  Note to stop drive before changing parameter t211  Anlg In 0 10V Lo  3 14  removed    New option 13  I O Control  for parameter t221  Relay Out Sel  added  3 15  Fault description for F3 corrected  4 3          Corrected Table B F by adding the 0 75 kW  1 0 HP  and 1 5 kW  2 0 HP   B 4  ratings for the 22F RF025 BL EMC line filter     Description for bits 14  13  and 12 of register address 8192 corrected  C 4  Information on reading register address 8192 clarified  C 4  Description for bits 6  7  and 15 of register address 8192 updated  C 4  C 5  Ci                Information on reading register address 8193 clarified   Figure C 1  Network Wiring Diagram  updated   Guidelines on standard RS485 wiring practices added              O  el    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    soc 2    The information below summarizes
109. trt Tries  Auto Rstrt Delay  Boost Select  Maximum Voltage  Program Lock  Testpoint Sel  Motor NP FLA    d012  d013  d014  d015  d016  d017  d018  d019  d020  d021  d022    P107  P108  P109  P110  P111  P112    d213  d214  1221  1222    A436  A437  A438  A439  A440  A441  A442  A444  A446  A448  A450  A451  A452  A453  A457  A458  A459  A461    Programming and Parameters 3 3                Display Group  d001  Output Freq  Related Parameter s   d002  d010  P104  P105  P108  Output frequency present at T1  T2  amp  T3  U  V  amp  W    Values Default Read Only  Min Max  0 0 P105  Maximum Freq   Display  0 1 Hz  d002  Commanded Freq  Related Parameter s   d001  d013  P104  P105  P108       Value of the active frequency command  Displays the commanded frequency even if the drive is not  running    Important  The frequency command can come from a number of sources  Refer to Start and Speed  Reference Control on page 1 19 for details                 Values Default Read Only  Min Max  0 0 P105  Maximum Freq   Display  0 1 Hz    d003  Output Current   The output current present at T1  T2  amp  T3  U  V  amp  W                                 Values Default Read Only  Min Max  0 00  Drive Rated Amps x 2   Display  0 01 Amps  d004  Output Voltage  Related Parameter s   P101  A453  A457  Output voltage present at terminals T1  T2  amp  T3  U  V  amp  W    Values Default Read Only  Min Max  0 Drive Rated Volts  Displav  0 1 VAC  d005  DC Bus Voltage   Present DC bus voltage level   Value
110. try  state or  local codes may require different ratings     Fusing   The recommended fuse types are listed below  If available current ratings  do not match those listed in the tables provided  choose the next higher  fuse rating     e IEC  BS88  British Standard  Parts 1  amp  2      EN60269 1  Parts 1  amp   2  type gG or equivalent should be used     e UL UL Class RK1  T or J must be used  2     Circuit Breakers   The    non fuse    listings in the following tables include inverse time  circuit breakers  instantaneous trip circuit breakers  motor circuit  protectors  and 140M self protected combination motor controllers  If  one of these is chosen as the desired protection method  the following  requirements apply     e IEC   Both types of circuit breakers and 140M self protected  combination motor controllers are acceptable for IEC installations     e UL  Only inverse time circuit breakers and the specified 140M  self protected combination motor controllers are acceptable for UL  installations      1  Typical designations include  but may not be limited to the following  Parts 1  amp  2  AC   AD  BC  BD  CD  DD  ED  EFS  EF  FF  FG  GF  GG  GH    2  Typical designations include  Type J   JKS  LPJ  DFJ  Type T   JJS  JIN  Type RK1   LPS  KTS  KTN    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    A 2 Supplemental Drive Information    Specifications    Drive Ratings       Catalo Output Ratings  Input Ratings Branch Circui
111. uency command in    real time    using the  integral keypad Up Arrow or Down Arrow when in program mode    Important  Once the desired command frequency is reached  the Enter key must be pressed to store  this value to EEPROM memory  If the ESC key is used before the Enter key  the frequency will return  to the original value following the normal accel decel curve              Values Default 60 0 Hz  Min Max  0 0 400 0 Hz  Display  0 1 Hz    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 21    Advanced Program Group  continued                 A410  Preset Freq 0     Related Parameterfs   P108  P109  P110  t201  1202   A411  Preset Freq 1  i  A412  Preset Freq 2   A413  Preset Freq 3   Values A410 Default 0 0 Hz   A411 Default 5 0 Hz   A412 Default 10 0 Hz   A413 Default 20 0 Hz   Min Max  0 0 400 0 Hz   Display  0 1 Hz       Provides a fixed frequency command value when t201   t202  Digital Inx Sel  is set to 4    Preset  Frequencies      An active preset input will override speed command as shown in the flowchart on page 1 20      1  To activate A410  Preset Freq 0  set P108  Speed Reference  to option 4    Preset Freq 0 3                       Input State of Digital In 1   Input State of Digital In 2   I O Terminal 05   I O Terminal 06  Frequency Source   Accel Decel Parameter Used   0 0 A410  Preset Freq 0     Accel Time 1     Decel Time 1   1 0 A411  Preset Freq 1     Accel Time 1     Decel 
112. ues Default Read Only  Min Max  0 1  Displav  1    PowerFlex 4M Adjustable Frequency Drive FAN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    3 6 Programming and Parameters    Display Group  continued                                                  d014  Dig In Status  Related Parameter s   t201  t202  Status of the control terminal block digital inputs   AAAI  LIL i    1   Input Present  0   Input Not Present  Digital Int Sel  I O Terminal 05  Bit 0  Digital In2 Sel  I O Terminal 06  Bit 1  Reserved Bit 2  Reserved Bit 3                                                       Values Default Read Only  Min Max  0 1  Displav  1  d015  Comm Status  Related Parameter s   C302   C306  Status of the communications ports   ANIA  WILL IL  l 1   Condition True  0   Condition False  Receiving Data Bit 0  Transmitting Data Bit 1  RS485  DSI  Based Option Connected Bit 2   Allen Bradley devices only    Communication Error Occurred Bit 3                Values Default Read Only  Min Max  0 1  Displav  1    d016  Control SW Ver     Main Control Board software version                       Values Default Read Only  Min Max  1 00 99 99  Display  0 01   d017  Drive Type    Used by Rockwell Automation field service personnel    Values Default Read Only  Min Max  1001 9999  Display  1    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Programming and Parameters 3 7    Display Group  continued     d018  Elapsed Run Time     Accumulated 
113. veExplorer  3 1    E  Earthing  see Grounding  EMC RFI  Grounding  Filter  1 6  Interference  1 21  Enclosure Rating  Changing  1 2  ESD  Static Discharge  P 3    F  Faults  Auto Rstrt Tries  4 4  Auxiliary Input  4 3  Comm Loss  4 4  Drive Overload  4 4  Ground Fault  4 3  Heatsink OvrTmp  4 3  HW OverCurrent  4 3   O Board Fail  4 4  Motor Overload  4 3  Motor Stalled  4 3  OverVoltage  4 3  Parameter Checksum  4 4  Phase Short  4 4  Phase to Ground Short  4 4  Power Loss  4 3  Power Unit  4 4  SW OverCurrent  4 4  UnderVoltage  4 3  Filter  RFI  1 6  Frame Designations  P 2  A 1  B 6  Fuses  Input  1 7  Ratings  A 1    PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    Index 2    G  General Precautions  P 3  Ground Fault  4 3  Grounding   Filter  1 6   General  1 5    H  Heatsink OvrTmp Fault  4 3  HW OverCurrent Fault  4 3       I O   Wiring  1 13   Wiring Examples  1 15  1 18  I O Board Fail Fault  4 4  Input Contactor  1 12  Input Fusing  1 7  Input Potentiometer  1 15  Input Power Conditioning  1 4  Installation  1 1  Integral Keypad  2 3  Interference  EMC RFI  1 21    K  Keypad  2 3    L  LEDs  2 3    M  Minimum Clearances  1 2  Motor Cable Length  1 10  Motor Overload Fault  4 3  Motor Stalled Fault  4 3  motor starter  1 7  Mounting Options and Clearances     MOVs  1 3     0   Opening the Cover  1 1  Operating Temperatures  1 2  Operator Interface  2 3  OverVoltage Fault  4 3    P  Parameter  Descriptions  3 1  Typ
114. voltage or imbalanced input voltages  can cause uncommanded positive speed changes    2  Actual deceleration times can be longer than commanded  deceleration times    However  a    Stall Fault    is generated if the drive remains in this state  for 1 minute  If this condition is unacceptable  the bus regulator must be  disabled  see parameter A441   In addition  installing a properly sized  dynamic brake resistor will provide equal or better performance in most  cases     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    P 4 Overview    Catalog Number Explanation              1 3 4 5 6 8 9 10 11 12 13 14  22F AA  i Optional  Code Code Version  22F PowerFlex 4M 3 No Brake IGBT  4 Standard  Code Voltage Ph  Code Rating  V 120VAC 1 0 Not Filtered  A 240VAC 1 i Filtered  B 240V AC 3  D 480V AC 3    Code Interface Module  1 Fixed Keypad    Code Purpose  AA Reserved for    thru custom firmware  ZZ    Code Enclosure    N Panel Mount   IP 20  NEMA Type Open     Output Current   100 120V Input Output Current   200 240V Input Output Current   380 480V Input  W  H  H kW  HP        Code Amps kW  HP  Code Amps kW  HP  Code Amps   1P6 1 6 0 2  0 25  1P6 1 6 0 2  0 25  1P5 15 0 4  0 5    2P5 25 0 4  0 5  2P5 25 0 4  0 5  2P5 25 0 75  1 0    4P5 45 0 75  1 0  4P2 42 0 75  1 0  4P2 42 1 5  2 0    6PO 6 0 1 1  1 5  8PO 8 0 1 5  2 0  6PO 6 0 2 2  3 0   011 11 0 2 2  3 0  8P7 87 3 7  5 0   012 12 0 2 2  3 0  013 13 0 5 5  7 5   017 17 5 3 7  5 0 
115. z   Input Phases  Three phase input provides full rating  Single phase  operation provides 35  rated current    Displacement Power Factor  0 98 across entire speed range   Maximum Short Circuit Rating  100 000 Amps Symmetrical   Actual Short Circuit Rating  Determined by AIC Rating of installed fuse circuit  breaker   Transistor Type  Isolated Gate Bipolar  IGBT     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual    Publication 22F UM001D EN E    Supplemental Drive Information A 5    PowerFlex 4M Estimated Watts Loss  Rated Load  Speed  amp  PWM                 Voltage kW  HP  Watts Loss  100 120V  1 Phase 0 2  0 25  17  0 4  0 5  28  0 75  1 0  50  1 1  1 5  76  200 240V  1 Phase 0 2  0 25  14  0 4  0 5  25  0 75  1 0  43  1 5  2 0  82  2 2  3 0  109  200 240V  3 Phase 0 2  0 25  16  0 4  0 5  26  0 75  1 0  44  1 5  2 0  84  2 2  3 0  115  3 7  5 0  159  5 5  7 5  239  7 5  10  329  380 480V  3 Phase 0 4  0 5  24  0 75  1 0  4  1 5  2 0  74  2 2  3 0  92  3 7  5 0  135  5 5  7 5  190  7 5  10  294  11  15  378          PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    A 6 Supplemental Drive Information    Notes     PowerFlex 4M Adjustable Frequency Drive FRN 1 xx   2 xx User Manual  Publication 22F UM001D EN E    Appendix B    Accessories and Dimensions       For information on    See page  Product Selection B 1  Product Dimensions B 6  Product Selection  Table B A Catalog Number Description  22F   D 8P7 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
取扱説明書(スピーカー部) - 274.42 KB  KBCH 120, 130, 140 - ElectricalManuals.net  Origin Storage DL-M6500 rechargeable battery    Avaya VisAbility Management Suite Release 1.2 Installation Manual  Manual de instrucciones modelo 1767 ES  研ぎ澄まされたスマートな即戦力。 一歩先行くビジネスを切り  Guide d`utilisation  TU/TC Series      Copyright © All rights reserved. 