Home

1305 Adjustable Frequency AC Drive

image

Contents

1. Item Name Description Speed Indicator Illuminates in steps to give an approximate visual indication of the commanded speed LEDs If the Analog Speed Potentiometer option has been ordered the Increment Decrement keys only available and Speed Indicator LEDs will be replaced by the pot with digital speed control 1305 Series C Parameter List Group Min Max Default Group Min Max Default Parameter No Units Value Value Value Parameter No Units Value Value Value Metering Analog Invert 84 Text Disabled Output Current 54 0 01Amps 0 00 2x Drive Output Current 4 20 mA Loss Sel 81 Text Stop Fault Output Voltage 1 1 Volt 0 Maximum Voltage Stop Select 10 Text Ramp Output Power 23 10 01kW 0 00 2x Rtd Dr Output Power DC Hold Time 12 0 1Sec 0 0 150 0 0 0 DC Bus Voltage 53 1Volt 0 410 230V Drive DC Hold Volts 13 1Volt 0 25 of Max DRV 0 815 460V Drive DB Enable Text Disabled Output Freq 66 0 01 Hz 0 00 Maximum Frequency Motor Type y Text Induc Reluc Freq Command 65 0 01 Hz 0 00 400 00 0 00 Compensation 52 Text Comp MOP Hz 42 0 01 Hz 0 00 400 00 Frequency Set Drive Temp 70 deg C 0 100
2. 1 00 AdaptivelLmt 149 Text Enabled Analog Filter 144 Text 100 Advanced Setup Feature Select Minimum Freq 16 Hz 0 120 0 Run On Power Up 14 ext Disabled Maximum Freq 19 Hz 40 400 60 Reset Run Tries 85 Numeric 0 9 0 Base Frequency 17 Hz 40 400 60 Reset RunTime 15 0 1Sec 0 5 30 0 1 0 Base Voltage 18 Volt 25 of DRV 100 of Max DRV Max DRV S Curve Enable 57 Text Disabled Break Frequency 49 1Hz 0 120 30 S Curve Time 56 0 1 Sec 0 0 300 0 0 0 Break Voltage 50 Volt 0 50 of Max DRV Dr Size Dep Language 47 Text Approp Lang Maximum Voltage 20 1 Volt 25 of DRV 110 of Max DRV Max DRV Cable Length 143 Text Short DC Boost Select 9 ext Break Point Rated Slip 146 0 1Hz 0 0 5 0 2 0 Start Boost 48 1Volt 0 25 of Max DRV Dr Size Dep Slip Comp Adder 148 0 01 Hz 0 00 5 00 _ Run Boost 83 1 Volt 0 25 of Max DRV 0 IR Comp 147 11 0 150 Drv Depend PWM Frequency 45 0 1kHz 2 0 8 0 4 0 Table continued on next page 6 Rockwell Automation Publication 1305 5 2 2 September 2013 1305 Adjustable Frequency AC Drive Group Min Max Default Group Min Max Default Parameter No Units Value Value Value Parameter No Units Value Value Value Output Config Local Mask 93 Byte 01111111 Output 1 Config 90 Text g Faulted Owners Output 2 C
3. Freq Select 1 5 Text Adapter 1 Last Fault 4 Numeric 0 Max Fault No Freq Select 2 6 Text Remote Pot Output Power 3 1 0 200 Drive Rated Power Jog Frequency 24 0 1Hz 0 0 400 0 10 0 Output Curr 2 0 200 Rtd Dr Out Curr Prst 2nd Accel 26 Text Preset Setup Upper Presets 72 Text Disabled Input Mode 21 Text Three Wire Accel Time 2 30 0 1sec 0 0 3600 0 5 0 Freq Select 1 5 ext Adapter 1 Decel Time 2 31 0 1sec 0 0 3600 0 5 0 Accel Time 1 7 0 1 sec 0 0 3600 0 10 0 Preset Freq 1 27 0 1Hz 0 0 400 0 10 0 Decel Time 1 8 0 1 sec 0 0 3600 0 10 0 Preset Freq 2 28 0 1Hz 0 0 400 0 20 0 Base Frequency 17 1Hz 40 400 60 Preset Freq 3 29 0 1 Hz 0 0 400 0 30 0 Base Voltage 18 1Volt 25 of DRV 100 of Max DRV Max DRV Preset Freq 4 73 0 1Hz 0 0 400 0 40 0 Maximum Voltage 20 1 Volt 25 of DRV 110 of Max DRV Max DRV Preset Freq 5 74 10 1Hz 0 0 400 0 50 0 Minimum Freq 16 1Hz 0 120 0 Preset Freq 6 75 0 1 Hz 0 0 400 0 60 0 Maximum Freq 19 Hz 40 400 60 Preset Freq 7 76 0 1 Hz 0 0 400 0 0 0 Stop Select 10 Text Ramp Skip Freq 1 32 1Hz 0 400 400 Current Limit 36 20 of DRC 150 of DRC 150 of DRC Skip Freq 2 33 Hz 0 400 400 Overload Mode 37 ext No Derating Skip Freq 3 34 Hz 0 400 400 Overload Current 38 0 1Amps 20 ofDRC 115 of DRC 115 of DRC Skip Freq Band 35 Hz 0 15 0 Sec Curr Limit 141 0 of DRC 150 of DRC 0 of DRC MOP Increment 22 Hz Sec 0 00 255 00
4. 10 Programmable Output 1 Resistive Rating 115V AC 30V DC 5A Inductive Rating 115V AC 30V DC 2A 11 12 Drive Enable Contact Closure Input 13 12 Reverse Contact Closure Input 14 15 Jog Contact Closure Input 16 15 SW1 Contact Closure Input 17 15 SW2 Contact Closure Input 18 15 SW3 Contact Closure Input 19 20 Programmable Output 2 24V DC 20 50 mA max sink Required to operate drive STOP also used to clear a fault Use HIM Stop button to clear faults Contact Closure Input Internal 5V supply Do not apply external voltage When the ENABLE signal is lost the drive output immediately shuts off and the motor will coast to a stop A Start command will override any Jog command See 1305 User Manual publication 1305 5 2 for input configurations based on the setting of parameter 21 Input Mode Rockwell Automation Publication 1305 5 2 2 September 2013 1305 Adjustable Frequency AC Drive Faults Name Description Diag C Lim Fault F36 The drive output current has exceeded the software Current Limit and the Cur Lim Trip En parameter was enabled Drive gt HIM The checksum read from the HIM s EEPROM does not match the checksum calculated from the EEPROM data Drive Reset Fault F22 Occurs on power up Caused by having the START Input or RUN Input closed with the STOP Input open and Run On Power Up DISABLED EEprom Fault F32 EEPROM has invalid data or cannot be programme
5. Bit 0 of the Direction Mask parameter to 0 to disable the reverse function at TB2 Direction LEDs Indicators These LEDs illuminate to indicate the direction of motor rotation Rotating Forward OFF Steady ON Rotating Reverse Steady ON OFF A Changing Direction Decelerating Reverse will begin z FB to Accelerate Forward Flashing Steady ON i Changing Direction Decelerating Forward will begin 8 to Accelerate Reverse Steady ON Flashing Increment Pressing these keys will increase or decrease the HIM frequency command An indication of Decrement this command will be shown on the visual Speed Indicator LEDs The drive will run at this Arrows command if the HIM is the selected frequency reference See Freq Select 1 2 only available Pressing both keys simultaneously stores the current HIM frequency command in HIM with digital memory The Speed Indicator LEDs will flash momentarily to indicate a successful save if speed control speed is above 20 percent Cycling power or connecting the HIM to the drive will set the frequency command to the value stored in HIM memory Analog Speed If the Analog Speed Potentiometer option has been ordered the Increment Decrement keys Potentiometer and Speed Indicator will be replaced by the pot Rockwell Automation Publication 1305 5 2 2 September 2013 5 1305 Adjustable Frequency AC Drive
6. O User Side Source _ Wiper or 0 10V DC Input Common 4 20mA Input 0 10V Output Start Common Stop Output 1 11 Enable 12 Common 13 Reverse 14 Jog 15 Common 16 SW1 17 SW20 18 SW3 gt 24VDC Source gt gt 19 User Supplied T L Sink ro Output 2 General Run Fwd Rev Remote Pot a a 1 Source owi 2 Wiper or 0 10V DC Input A 3 Common 4 4 20mA Input 5 0 10V Output op Run Forward Y 7 att J oo 7 Common umper aay a stop v lt 9 l a ois Output 1 g L oT 11 Enable seul alan apoo H gt 12 Common Run Reverse U re 13 Reverse cane 14 Jog a 15 Common 16 SW1 00 17 SW2 m 18 SwW3 0 24VDC Source 19 Sink User Supplied ogl Output 2 See footnotes below TB2 Terminal Descriptions Terminals _ Signal Specification 1 2 3 External Speed Potentiometer 10 KQ Potentiometer 2 watts 2 3 0 10V Analog Input Drive Input Impedance 100 kQ 4 3 4 20 mA Analog Input Drive Input Impedance 250 Q 5 3 0 10V Analog Output Meter Impedance gt 4 kQ 6 7 Start Contact Closure Input 8 7 Stop Contact Closure Input 9
7. Quick Reference Allen Bradley 1305 Adjustable Frequency AC Drive Firmware Revision Number 6 01 and Later This publication is designed as a reference tool The 1305 User Manual publication 1305 5 2 must be consulted for more detailed information about parameters faults and hazards of personal injury Rockwell Allen Bradley Rockwell Software Automation 1305 Adjustable Frequency AC Drive Power Terminal Block TB1 Designations TB1 Terminal Designations Input Fusing GDO L 2 13 DC BRK Tt T 73 R sS DC U VvV W A Dynamic Brake Tonore A Option j 0 Motor To Motor we Required Required Branch Input Fusing Circuit Disconnect T T T AC Input Line Connection for Dynamic Brake Resistors for all models except the 200 230 Volt 0 37 to 0 75 kW 0 5 to 1 HP drive Important The DB Enable parameter must be enabled for proper operation For single phase applications the AC input line can be connected to any two of the three input terminals R S T L1 L2 L3 1305 drives provide Class 10 motor overload protection according to NEC Article 430 They do not provide speed sensitive overload protection thermal memory retention and motor over temperature sensing according to NEC Article 430 126 A 2 If such protection is needed in the end use product it must be provided by additional means Important This driv
8. ata Out B1 121 umeric 1 49 1 Power Mode 44 Text Data Out B2 122 umeric 1 49 1 Drive Type 61 Numeric Data Out C1 123 Numeric 1 149 1 Firmware Ver 71 Numeric Data Out 2 124 Numeric 1 49 1 Output Pulses 67 1 Cyde 0 65535 Data Out D1 125 Numeric 1 149 1 Drive Temp 70 1deg C 0 100 Data Out D2 126 umeric 1 49 1 Set Defaults 64 Text Ready Process Display Masks Process Par 127 umeric 1 149 1 Logic Mask 92 Byte 01111111 Process Scale 128 Numeric 327 68 327 67 1 00 Direction Mask 94 Byte 01111111 Process Text 1 129 ASCIltext Start Mask 95 Byte 01111111 Process Text 2 130 ASCIltext Jog Mask 96 Byte 01111111 Process Text 3 131 ASCIltext Reference Mask 97 Byte 01111111 Process Text 4 132 ASCII text Accel Mask 98 Byte 01111111 Process Text 5 133 ASCIltext Decel Mask 99 Byte 01111111 Process Text 6 134 ASCII text Fault Mask 100 Byte 01111111 Process Text 7 135 ASCII text MOP Mask 101 Byte 01111111 Process Text 8 136 ASCIItext 1 See the 1305 5 2 User Manual Appendix B Table B 5 Rockwell Automation Publication 1305 5 2 2 September 2013 Programming System OPERATOR LEVEL Power Up amp Status Display Choose Mode aola 7 ath jeo Poomse d
9. ay will automatically become active allowing another parameter or group to be chosen Description The Start key will initiate drive operation if no other control devices are sending a Stop command This key can be disabled by the Logic Mask or Start Mask a z g Stop If the drive is running pressing the Stop key will cause the drive to stop using the selected stop mode See Stop Select in the User Manual If the drive has stopped due to a fault pressing this key will clear the fault and reset the drive See Flt Clear Mode Logic Mask and Fault Mask JOG Jog When pressed jog will be initiated at the frequency set by Jog Frequency if no other control devices are sending a Stop command Releasing the key will cause the drive to stop using the selected stop mode See Stop Select Logic Mask and Jog Mask Important If the drive is running prior to issuing a jog command the jog command will be ignored A start command from another source will override the jog command D Change Direction Pressing this key will cause the drive to ramp down to zero Hertz and then ramp up to set speed in the opposite direction The appropriate Direction LED will illuminate to indicate the direction of motor rotation See Logic Mask and Direction Mask Note that the factory default for control of the reverse function is the reverse input at TB2 To enable the HIM control of the reverse function change
10. d to valid data Hz Err Fault F29 This fault indicates that there is not a valid operating frequency It can be caused by any of the following 1 Maximum Frequency is less than Minimum Freq 2 Skip frequencies and skip bandwidth eliminate all operating frequencies 3 4 20mA input signal speed reference has been lost or is out of range and 4 20mA Loss Sel is set for Stop Fault Hz Sel Fault F30 An adapter that is not connected has been chosen as the active frequency source HIM gt Drive Error 1 The checksum read from the HIM s EEPROM does not match the checksum calculated from the EEPROM data Error 2 The number of parameters in saved profile does not equal master Error 3 Download was attempted to a different type drive that is 1336 gt 1305 Error 4 Saved data for parameter not correct for new drive Error 5 Drive is running while attempting download IPM Current Fault F44 The internal power module overcurrent limit has been exceeded IPM Overtemp Fault F45 The internal power module thermal limit has been exceeded Max Retries Fault F33 Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of Reset Run Tries Motor Mode Fit F24 Internal error Motor Stall Fault F6 The motor is stalled Neg Slope Fault F35 Drive software detected a portion of the volts Hz curve with a nega
11. e is not intended for use with single phase motors Ground from drive to motor frame must be an independent continuous insulated wire run Terminals GRD Description Earth ground R S T L1 L2 L3 AC input line terminals DC BRK or DC Dynamic brake option see the instructions included with option U V W T1 T2 T3 Motor connections ATTENTION The drive does not provide branch circuit protection Specifications for the recommended fuse size and type which provide branch circuit protection against short circuits are provided below Branch circuit breakers or disconnect switches cannot provide this level of protection for drive components Maximum Recommended AC Input Line Fuse UL Class J T CC or BS88 or equivalent Three Phase Single Phase Fuse Fuse Rating kW HP Rating kW HP 200 230V Rating 380 460V Rating 0 37 0 5 0 19 0 25 6 30 0 55 0 75 0 37 0 5 6 30 0 75 1 0 55 0 75 10 6 1 5 2 0 75 1 15 10 2 2 3 1 5 2 25 15 4 0 5 29 1 Must be dual element time delay Bussmann LP or equivalent 2 _ If fuse blowing is a problem use dual element type fuses Rockwell Automation Publication 1305 5 2 2 September 2013 1305 Adjustable Frequency AC Drive Terminal Block TB2 Designations General Three Wire Remote Pot CO CO Ni GD O71 amp Go P
12. en Funny o gt ERMO fo Senet fool Saute fo Posen 4 4 4 4 4 4 4 4 4 Process Display Reset Defaults Control Logic Login Recall Values Fault Queue Logout Save Values Modify Upload Parameters Download Parameters GROUP LEVEL Parameter Groups See Parameter List PARAMETER LEVEL Parameters See Parameter List Access to the Program and EEPROM modes and the Control Logic and Clear Fault Queue are disabled if the password is Logged Out Series A HIM Firmware Revision 3 00 and later or Series B HIM Firmware Revision 1 01 and later only Series B HIM Firmware Revision 1 01 and later only U S Allen Bradley Drives Technical Support Tel 1 262 512 8176 Fax 1 262 512 2222 E mail support drives ra rockwell com Online www ab com support abdrives Allen Bradley Rockwell Software and Rockwell Automation are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies i I www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberpo
13. onfig 91 Text g EE Running Stop Owner 102 Byte Analog Out Sel 25 Text Sa Frequency Direction Owner 103 Byte Above Freq Val 77 1Hz 0 400 0 Start Owner 104 Byte Above Curr Val 142 1 0 of DRC 150 of DRC 0 of DRC Jog Owner 105 Byte Faults Reference Owner 106 Byte Fault Buffer 0 86 Numeric Accel Owner 107 Byte Fault Buffer 1 87 Numeric Decel Owner 108 Byte Fault Buffer 2 88 Numeric Fault Owner 109 Byte Fault Buffer 3 89 Numeric MOP Owner 110 Byte Clear Fault 51 Text Ready Local Owner 137 Byte Cur Lim Trip En 82 Text Default Run Adapter 1 0 Line Loss Fault 40 ext F03 Enable Data In A1 111 Numeric 0 49 0 Fit Clear Mode 39 ext Enabled Data In A2 112 Numeric 0 149 0 Diagnostics Data In B1 113 Numeric 0 49 0 Drive Command 58 Byte Data In B2 114 Numeric 0 149 0 Drive Status 59 ext Data In C1 115 Numeric 0 49 0 Drive Alarm 60 Byte Data In 2 116 Numeric 0 149 0 Input Status 55 Byte Data In D1 117 Numeric 0 49 0 Freq Source 62 ext Data In D2 118 umeric 0 49 0 Freq Command 65 0 01 Hz 0 00 400 00 0 00 Data Out A1 119 umeric 1 149 1 Drive Direction 69 ext Forward Data Out A2 120 Numeric 1 149 1 Motor Mode 43 ext D
14. rt Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1305 5 2 2 September 2013 Supersedes Publication 1305 2 2 July 1996 Copyright 2013 Rockwell Automation Inc All rights reserved Printed in the U S A
15. s disconnected while it possesses control of a local bus function Undervolt Fault F4 DC Bus voltage fell below the minimum value Line Loss Fault is programmed to U Volt Run UV Short Fault F41 Excessive current has been detected between these two drive output terminals UW Short Fault F42 Excessive current has been detected between these two drive output terminals VW Short Fault F43 Excessive current has been detected between these two drive output terminals Human Interface Module HIM LCD Display Display Panel Digital Speed Control and Indicator also available with Analog Speed Pot Control Panel Rockwell Automation Publication 1305 5 2 2 September 2013 1305 Adjustable Frequency AC Drive HIM Display Panel Descriptions z E Name Escape Description When pressed the ESCape key will cause the programming system to go back one level in the menu structure SEL Select Pressing the SELect key alternately moves the cursor to the next active area A flashing first character indicates which line is active Increment Decrement These keys are used to increment and decrement a value or scroll through different groups or parameters HIM Control Panel Descriptions Ho Enter Name Start When pressed a group or parameter will be selected or a parameter value will be entered into memory After a parameter has been entered into memory the top line of the displ
16. tive slope Network Error Error 0 6 SCANport Error Error 7 9 Communications Error Op Error Fault F11 Motor Type is set to Sync PM and Stop Mode is set to DC Brake Open Pot Fault F9 An external pot is connected and the ground lead of the pot is disconnected creating a potential drive overspeed hazard Overcurrent Fault F12 Overcurrent is detected in overcurrent hardware trip circuit Overload fault F7 Internal electronic overload trip Overspeed Fault F25 Internal error Overtemp Fault F8 Temperature sensor detects excessive heat Overvolt Fault F5 DC bus voltage exceeded maximum value Phase U Fault F38 A phase to ground fault has been detected between the drive and motor in this phase Phase V Fault F39 A phase to ground fault has been detected between the drive and motor in this phase Phase W Fault F40 A phase to ground fault has been detected between the drive and motor in this phase Pin ID Error Communication Hardware problem Power Loss Fault F3 DC bus voltage remained below 85 of nominal for longer than 0 500 sec Line Loss Fault parameter is programmed to F03 Enable Power Mode Fault F26 Internal error Power Test Fault F46 Fault detected during initial start up sequence Reprogram Fault F48 Occurs when drive parameters are reset to defaults Run Boost Fault F34 An attempt has been made to set Run Boost to a value greater than Start Boost Serial Fault F10 An active local bus adapter i