        B400R Online UPS
         Contents
1.    During mains  failure or abnormality  the UPS will transfer to Battery mode and the load is supplied continuously     The advantage to this is that the output frequency is fixed  which may be a requirement for some  very sensitive loads     But the disadvantage is the load capacity of UPS will be de rated to 70  in converter mode     6 2 2 Set the function    This function can be enabled through the LCD setting whilst in Bypass mode or Standby mode     36    B400R 1 3kVA User Manual meres    Uninterruptible Power Solutions    7  Trouble Shooting    If the UPS system does not operate correctly  check the operating information on the LCD display     Please use the table below to help identify and resolve the problem  If the problem cannot be  rectified please contact your distributor or Borri for assistance     Possible Cause    No indication or alarm even No Input voltage Check cable condition and  when the system is connected condition of mains socket the  to mains supply UPS is connected to  Emergency supply period Batteries not fully charged   Charge the batteries for at  shorter than nominal value batteries defective least 5     8 hours and then  check capacity  If the problem  persists  please contact your  distributor or Borri for  assistance  Fan Failure Abnormality in fan operation     Check if the fan is running  if  Alarm Code  84 fan defective the fan is not operating  please  contact your distributor or  Borri for assistance  Battery Over Voltage Battery is over
2.   ON OFF Button Select Button    Scrall Bullon Scroll Bullon   Up or Back   Down or Forward     Figure 5 1  On line UPS Control Panel    19    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    Table 5 1  Control Button Functions    The Button Function JDescripton O    When the unit has no power and is  Power On connected with batteries  press this button  for  gt  100ms  amp   lt  1s to power on      1  When the unit is powered on and in Bypass  Turn On mode  press this button for  gt  1s to turn the  unit on  When the unit has been turned on  press  Turn Off  this button for  gt 3s to turn off the unit    When the UPS is displaying the default  Enter Main Menu status summary  press this button for  gt  1s   to enter the main menu tree   Press this button  gt  1s to exit the present  Exit Main Menu menu and return to the default status   summary   Press this button for  gt  100ms  amp   lt  1s to  Scroll Up   scroll up through the menu options   Press this button for  gt  100ms  amp   lt  1s to  Scroll Down   scroll down through the menu options    Press this button for  gt  100ms  amp   lt  1s to  select the present menu option  or enter  the next menu  but do not change any  edited options and change the setting    Table 5 2  Buzzer definition    UPS Condition Buzzer Status  Fault Active  Beep every second       Battery Output Beep every 4 seconds  if battery is low  buzzer will beep every  second    Bypass Output Beep every 2 minutes       20    B400R 1 3
3.   e         5 2 2 Battery mode    An example of the LCD display in battery mode is shown below   Input   Output   Load    0 V   220 V  1000VA  0 Hz 20 Hz   900W    1 100           Figure 5 4  Battery Mode           00        When the UPS is in battery mode  the buzzer beeps once every 4 seconds     22     i       B400R 1 3kVA User Manual    Uninterruptible Power Solutions    5 2 3 Bypass mode    An example of the LCD display in bypass mode is shown in the below diagram  The UPS does not  have the backup function when it is in bypass mode  The power used by the load is supplied from  the mains via an internal filter  The UPS will beep once every 2 minutes whilst in bypass mode        Input   Output  Load    220 V  220 V 1000 VA  50 Hz   50Hz  900 W    1 2 100    all       Pi       Figure 5 5  Bypass Mode    5 2 4 Standby mode    An example of the LCD display in standby mode is shown below     Input   Output  Load    220 V 0 V OVA  60 Hz 0 Hz OW    100  00   0        O im    Figure 5 6  Standby Mode    23       eww fo      Uninterruptible Power Solutions    B400R 1 3kVA User Manual    5 2 5 HE mode  High Efficiency mode    This is also referred to as economy  ECO  mode    After the UPS is turned on  the power used by the load is supplied from the utility power via an  internal filter while the utility power is in normal range  so high efficiency can be obtained in the HE    mode  During mains failure or abnormality  the UPS will transfer to Line mode or Battery mode and  the lo
4.  be active at any one time  The USB Port has priority  over the RS 232 port  When a communication cable is installed  the power management    software can exchange data with the UPS  The software polls the UPS for detailed  information on the status of the power environment  If a mains fail occurs  the software  initiates the saving of all data and the orderly shutdown of the equipment       10 2 RS 232 port    The RS 232 port is available for UPS monitoring  control  and firmware updates  To establish  communication between the UPS and a computer  connect one end of the serial communication  cable that comes with the UPS to the RS 232 port on the UPS  Connect the other end of the serial  cable to the RS 232 port on a computer  The cable pins for the RS 232 communication port are  identified in the following table     Pin   SignalName   Function   Direction fromthe UPS  ao sed Not Applicable  2        Transmittoexternaldevice   Out  2 mW ie fro external devieg  in O  4A  used Not Applicable    6   Unused Not Applicable  Po    Unused Not Applicable  Bo  sed Not Applicable  Do   Unused Not Applicable       10 3 USB port    The UPS can communicate with a USB compliant computer by using HID compatible power  management software  To establish communication between the UPS and a computer  connect the  USB cable that comes with the UPS to the USB port on the UPS and the USB port of a computer     41    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    10 4 Installi
5.  below  And then connect the battery terminal  D  from the first EBM to the battery  terminal  E  of the second EBM  Users need to remove the small gate C  on side of the front panel  to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel        Connecting the Multiple EBMs in rack form   1  Connect an Earth line between the UPS and the first EBM  and then connect an Earth Line  between the first EBM and the second EBM    2  Take off the front panel  and connect the battery terminal  A  from the UPS to the EBM terminal   B  shown as below  Then connect the battery terminal  D  from the first EBM to the battery  terminal  E  of the second EBM  Users need to remove the small gate C  on side of the front panel  to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel        B400R 1 3kVA User Manual       Uninterruptible Power Solutions    Note  Three or more EBMs can be connected to the UPS in the same way as shown above   Note  After connect the EBMs  please do not forget to set the number of EBMs on LCD  If use the  nonstandard EBMs  please call local dealer or distributor for setting method     1 2 Operation    e Do not disconnect the mains cable on the UPS or the building mains supply  grounded  shockproof socket  during operation as this will remove the ground protection to the UPS and all  connected equipment    e The UPS features its own  internal current source  batteries   There is a risk of elect
6.  charged Stop charging the batteries  Alarm Code  16 automatically  after the  battery voltage has returned to  a normal level  and mains is  normal  set batteries to charge  automatically once more  Battery Low Battery Voltage is low Should the alarm sound every  Alarm Code  12 second  it   s recommended the  protected equipment is safely  shutdown     Alarm Code  15 or Borri for assistance    Inverter Temperature High UPS internal temperature is too   Check ventilation to UPS is not   Alarm Code  86 high blocked  check the ambient  temperature   Ambient Temperature High The ambient temperature is too   Check the environment   Alarm Code  82 ventilation  adjust rooms  ventilation settings   Battery Open Battery pack is not connected Power down the UPS and   Alarm Code  11 correctly disconnect from the mains   check that connections  between UPS and batteries are  secure  check the battery  breaker is on   Service Battery Batteries may need to be Please contact your distributor   Alarm code  13 replaced  at end of or Borri for assistance   recommended service life          37    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    Overload Overload Check current load  indicated  Alarm Code  41 42 43 on the LCD remove non critical  equipment until load is within  UPS operating parameters   Site Fail Phase and neutral conductor  Alarm Code  04 connections on the UPS are  reversed    EPO Active EPO function is enabled Turn off the EPO switch  Alarm Code  71    Bus
7.  connector is normally closed with a wire on the rear panel  Once the connector is open  the    UPS will stop the output until the EPO status is disabled     Enable the EPO Status Disable the EPO Status    4 3 Battery charge  Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for    approximately 1 2 hours  The UPS system can be used directly without charging the batteries but  the stored energy time may be shorter than the nominal value specified     17    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    4 4 Operation procedure of external battery for long backup time model      S    model     1  Use the battery pack with voltage    36VDC for 1KS  12V x3 batteries  for B400R 010 B  C    48VDC  12V x4 batteries  for the B400R 020 B  C    72VDC  12V x6 batteries  for the B400R 030 B  C     Connection of battery quantities that exceed or do not meet the above mentioned quantities will  cause abnormal operation or permanent damage to the UPS      2  One hard wired battery terminal on the rear panel is used for connecting the battery pack      3  The battery connection procedure is very important  Any incompliance may result in the risk of  electric shock  Therefore  the following steps must be strictly complied with      4  Make sure the UPS is isolated from the supply  if there is a battery breaker then turn it off first    5  Remove the front panel  connect the battery via Anderson PP45 connectors  Prepare the batte
8.  fault  low   high   UPS Internal fault Please contact your distributor   unbalanced   soft start  or Borri for assistance   Alarm Code  22 21 23 25   Inverter fault  low   high   soft   UPS Internal fault Please contact your distributor   start  or Borri for assistance   Alarm Code  33 32 34   Over temperature fault UPS System overheating Check ventilation to UPS is not   Alarm Code  81 blocked  check the ambient  temperature  and adjust room  ventilation where possible     NTC open UPS Internal fault Please contact your distributor  Alarm Code  87 or Borri for assistance    Inverter Short UPS Output short circuit Remove all protected   Alarm Code  31 equipment and turn off the  UPS  Check whether the UPS  outputs or load are short  circuit  Make sure fault has  cleared and that no internal  faults are present before  switching the UPS back on     Bus short UPS Internal fault Please contact your distributor  Alarm Code  24 or Borri for assistance    Please have the following information to hand before calling the After Sales Service Department        1  Model number  serial number   2  Date on which the problem occurred   3  LCD display information  Buzzer alarm status   4  Mains power condition  load type and capacity  environment temperature  ventilation condition  5  Information of external battery pack if the UPS is    S    model   6  Other information that may assist in the description of the problem    38    B400R 1 3kVA User Manual E IR    Uninterruptible Power Soluti
9.  the UPS is moved directly from a cold to a warm environment  The  UPS must be absolutely dry before being installed  Please allow an acclimatisation time of at    least two hours     e Do not install the UPS near water or in a damp environment  Do not install the UPS where it  would be exposed to direct sunlight or near a heat source     e Do not connect appliances which would overload the UPS  e g  laser printers  etc  to the UPS  output     e Install cables in such a way that no one can step on or trip over them     e Assure UPS system and external battery source are earthed appropriately by a competent  person     e Only connect the UPS to an appropriately earthed shockproof supply   e Connections to the UPS must be easily accessible for maintenance and servicing purposes     e Once equipment has been installed  the sum of the leakage current of the UPS and the  connected load must not exceed 3 5mA     e Do not block ventilation openings in the UPS   s housing  Ensure the air vents on the front and  rear of the UPS are not blocked  Allow at least 25cm of clearance space on each side to allow    correct ventilation     e The UPS has been provided with an earthed terminal  during installation  equipotential earth  bonding to the external battery cabinets should be made     e An appropriate disconnection device as short circuit backup protection should be provided in  the buildings wiring installation  Please see the disconnection device specification in chapter 4 2     e Th
10.  turning on while connecting with the utility at the first time   Attention  Please switch off the connected loads first before turning on the UPS  and switch on the  loads one by one after the UPS is turned on  Switch off all of the connected loads before turning off  the UPS     5 3 1 Turning on the UPS with mains    1  Check allthe connections have been made correctly    2  When the UPS is powered on  the fan begins to rotate  and LCD will display the Borri logo  The  LCD will then show the default UPS status summary screen after the UPS completes its self test    3  By pressing the power button continuously for more than 1 second  the buzzer will beep for 1s  and the UPS will turn on    4  A few seconds later  the UPS will go into Line mode  If mains power is abnormal  the UPS will  transfer to Battery mode without interruption to the UPS or the connected load     5 3 2 Turning on the UPS without mains    1  Check allthe connections have been made correctly    2  By pressing the power button continuously for more than 100ms  the UPS will be powered on  At  this time the fan begins to rotate  and the LCD will display the Borri logo  The LCD will then show the  default UPS status summary screen after the UPS completes its self test    3  By pressing the power button continuously for more than 1 second  the buzzer will beep for 1s  and the UPS will turn on    4  A few seconds later  the UPS will enter Battery mode  If the mains power comes back  the UPS  will transfer to Lin
11. B400R Online UPS    User Manual    B400R 010 B  C   B400R 020 B  C   B400R 030 B  C     208 220 230 240VAC       B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    Contents Page    1  SAFETY AND EMC INSTRUCTIONS wicicccscsscccccsvssesnceccsesacacsesstcasccsessccsecsonsecencsacccsneanscees 3  ASNA   q PR DRE NPR CD ON DR PDR RR RR RD a 3  ELODO LOM AR IR RFI SE RUNU ueaauey sans AE 12  1 3 Maintenance  Servicing and FaUITS            ccccceeecccesccceeececeeccceneeeeeeeeeeneesuceeeecessuceeseceaeaess 12  LA TEQNS OIL ars ao a ea E O SD O A Si 15  IMs SLORG PC sapo ER RD a dO DO E DD O Im 15  HR SE  6 5  go   S AR REI  IR RED ED RR NR 15  2  DESCRIPTION OF COMMONLY USED SYMBOLS              csccsccscssceccsccsccscccceccsccsccecescees 16  SS NUR OD UCT O Nassau aaa 17  A CONNECTION  corinae ene E E E E E A EA 18  AENDE UOI RNS ON E 0 18  ALCON O E E E A A 18     BaN N E NR RN AE E 19  4 4 Operation procedure of external battery for long backup time model   FS pp  Ojo    e E E E T 20  Be OPERATION iioaiecescconcnsunarsnssneceu seca EE E E EEEE E EE E EEE E AEE 21  SEDEN PINCE a e a E E E EEE 21  2 Bel UNM MO O oe e E A RNS 24  5 3 Turning on and Turning off UPS     sesssesssessseeresssrrssressressresereserssssesesesseesressseesreeseeeseeeseee 29  KALC Bojo  Sigo n    o  q eriin E I ENE EIE E E OE O OAE 30  Os SPECIAL FUNCTION pinsera TA 38  OEE UT al sq  0  orenen E E E E E E Ei 38  Go Converter E E E E E E E A EA A EE E E T 38  7  TROUBLE SHOOTING oniccnriniinii
12. EBM to pass through the gate and then reassemble front panel           eww 4      Uninterruptible Power Solutions    B400R 1 3kVA User Manual    e Connecting the EBM in a rack form   1  Using the same method as assembling the UPS in a rack form  assemble the EBM into the rack   mounting above or below the UPS    2  Connect the earth line from UPS  port A  to EBM  port B    3  Take out the LCD box carefully  and unscrew the internal screws    4  Take off the front panel  and connect the battery terminal  A  from UPS to EBM terminal  B  as  shown below  Users need to remove the small gate C  on side of the front panel to allow the outlet  wire of the EBM to pass through the gate and then reassemble front panel    5  After installing the UPS into the rack  the load can then be connected to UPS  Please make sure  the load equipment is turned off before connecting to the UPS output receptacles     Unscrew          mwa lo    Uninterruptible Power Solutions       B400R 1 3kVA User Manual    e Connecting Multiple EBMs  The B400R series includes external battery ports that allow users to connect multiple EBMs in order  to provide additional backup time  Follow the below procedure to install multiple EBMs     Connecting multiple EBMs in Tower form   1  Connect an Earth line between the UPS and the first EBM  and then connect an Earth Line  between the first EBM and the second EBM    2  Take off the front panel  and connect the battery terminal  A  from UPS to EBM terminal  B   shown as
13. Internal Batteries    Follow the below instructions and illustrations to replace batteries      Carefully removed the LCD box  and remove the screws      Slide and Pull the front panel leftward and then take it off      Disconnect the cable from the UPS and battery pack      Remove the right inner battery bracket      Pull the battery pack out onto flat area      Install the new battery pack into the UPS      Re attach the battery bracket and reconnect the battery cable A and B    Re install the front panel back to UPS     CON DU BWHN FR       1 3 5 Testing New Batteries    For a battery test  please check    e The batteries must be fully charged    e The UPS must be in Normal mode with no active alarms   e Don   t take on off the load     To test batteries    1  Connect the UPS to mains supply for at least 48 hours to charge the batteries    2  When the UPS is working on line mode or HE mode  go to the    Start battery test    of the    control     menu to implement the test     12    B400R 1 3kVA User Manual 2u    Uninterruptible Power Solutions    1 3 6 Recycling the Used Battery     Warning   e Never dispose the batteries in a fire  It may explode     e Do not open or mutilate the batteries  Released electrolyte is harmful to the skins and eyes  It  may be toxic  A battery can present a risk of electrical shock and high short circuit current        To properly recycle the used batteries  please follow WEEE Regulations  or your local regulations and  procedures from the co
14. ad is supplied continuously     Input   Output  Load    220 V  220 V 1000VA  50 Hz   50Hz  900W    tido 100   E           all    Figure 5 7  HE Mode       1  This function can be enabled through the LCD settings or the UPS Management software   Winpower    2  It is Important that the transfer time of the UPS output from HE mode to battery mode is less than  10ms  Although this is a short transfer time it may be too excessive for some sensitive load    5 2 6 Converter mode   When operating in converter mode  the UPS will operate with a fixed output frequency  50Hz or    60Hz   During mains failure or abnormality  the UPS will transfer to battery mode and the load is  supplied continuously     Input   Output   Load    220 V  220 V   700VA  50 Hz   50Hz   630W    100  100      um     l    Figure 5 8  Converter Mode    24    mew lo j    Uninterruptible Power Solutions       B400R 1 3kVA User Manual    1  This function can be enabled through the LCD settings or the UPS Management software   Winpower   2  The available UPS capacity is de rated to 70  in converter mode     5 2 7 Warning    When the warning occurs  it illustrates that there is problems affecting the UPS standard operations   Normally these problems are not fatal and the UPS continues working  but they should be rectified  quickly  or the UPS may fail  The detailed warning table is shown in chapter 7     Input  Output  Load    220 Vi 220 V 1000 VA  50 Hz 50 Hz   900 W    100  100       00   ous      Figure 5 9  Warnin
15. al E IR    Uninterruptible Power Solutions    6  Special function  The B400R series has some special functions  which could satisfy some applications  These functions have    their own features  please contact your distributor or Borri for further information before using these  functions     6 1 HE function    6 1 1 Brief introduction to the HE function   If the HE function is set to enabled  after the UPS is turned on  the power used by the load is directly  supplied from the mains via an internal filter while the mains is in normal range  so high efficiencies  can be gained in HE mode  It is also called economy  ECO  mode  If the mains is lost or abnormal   the UPS will transfer to Line mode or Battery mode and the load is supplied continuously    The great advantage to this mode is that overall efficiency is  gt 96  of UPS  meaning less power is  wasted  But the disadvantages are    1  The load does not have the same level of protection as it does in Line mode  as the load is directly  supplied from the mains    2  The transfer time of the UPS output from HE mode to Battery mode is about 10ms  So the  function is not suitable to some sensitive loads  and the region where mains power is unstable     6 1 2 Set the function    This function can be enabled through the LCD setting whilst in Bypass mode or Standby mode     6 2 Converter function  6 2 1 Brief introduction of Converter function    In converter mode  the UPS will operate with a fixed output frequency  50Hz or 60Hz
16. ced  insulation to the utility is required  The relay output contact has a maximum rating of 30Vac 1A and    60VDC   2A normal values     The following diagrams show schematic of the dry out in contacts     42    B400R 1 3kVA User Manual Bere    Uninterruptible Power Solutions       y    Normally open  RY1  pig  8 Activated close  no  Dry Out contact schematic  Dry in    Normally open  Activated by pulse signal trigger       Dry In contact schematic    The following table shows the options for the dry out in contacts     Dry Out Signal   Description  S  Summary Alarm   Activated when any warning occurs o o  On Battery   Activatedwhenthe UPSisoperatingfrombatteries  Batterylow _  Activates with the batteries low alarm  Alarm Code  12       UPSok   Activated when the UPS has no active alarms or faults  On Bypass   Activated when UPS is operating on Bypass Output  Dry in Signal   Description o  Disable   Disable the function O SSS    UPS On One second pulse activated  the UPS turns on when the UPS is not  on inverter  Itis the same as a remote button to control the UPS  Status    UPS off One second pulse activated  the UPS turns off when the UPS is on  inverter  It is the same as a remote button to control the UPS  Status     Maintain Bypass One second pulse activated  the UPS transfers to bypass mode  To  recover the UPS to normal status  first deactivate the signal  and  then the UPS needs to be turned on via manual operation        43          B400R 1 3kVA User Manual    Unin
17. e equipment is powered by more than one source     B400R 1 3kVA User Manual a    Uninterruptible Power Solutions    1 1 1 Inspection of Unit    Inspect the UPS upon arrival  If the UPS is apparently damaged during shipment  please keep the  box and packaging material in its original form for the courier and notify the Borri immediately     1 1 2 Unpacking the Cabinet    To unpack the system    1  Open the outer carton and remove the accessories packaged with the cabinet    2  Carefully lift the cabinet out of the outer carton and set it on a flat  stable surface   3  Discard or recycle the packaging in a responsible manner  or store it for future use     1 1 3 UPS Setup    All models of the B400R series are designed for tower and rack purpose  They can be installed into a  19 inch equipment rack or installed within a provided stand as a tower  Please follow the below  instruction for Tower or Rack Mount Setup     e Tower setup   The B400R Series can be installed horizontally and vertically  As a tower configuration  it is provided  with optional UPS stands to stabilize the UPS  The UPS stand must be attached to the bottom of the  tower  Use the following procedure to install the UPS within the stands     1  Position the UPS stands appropriately so that 1 stand will be at either end of the UPS    2  Lift and carefully place down the UPS within the stands    3  Pull out the LCD box carefully and rotate it in a clockwise direction by 90 degrees and then place it  back in the fro
18. e mode without interruption to the UPS or the connected load     5 3 3 Turning off the UPS with mains    1  Turn off the inverter of the UPS by pressing the power button continuously for more than 3  seconds and the buzzer will beep for 3s  The UPS will then enter Bypass mode    2  When the above step is complete the UPS output voltage is still present  In order to cut off the  UPS output  simply turn off the mains supply to the UPS  A few seconds later the LCD display will  shut down and no output voltage will be available from the UPS output terminals     5 3 4 Turning off the UPS without mains  1  Turn off the UPS by pressing the power button continuously for more than 3 seconds  and the  buzzer will beep for 3s  The UPS will cut off the output at once     2  A few seconds later the LCD display will shut down and no voltage will be available from the UPS  output terminals     27       B400R 1 3kVA User Manual    Uninterruptible Power Solutions    5 4 LCD operation  Apart from the default UPS status summary screen  the user can get access to more information  about the UPS current status  details on various measurements  old events which have occurred  the    UPS    own identification  and can change the settings to fit the users own requirements  allowing  optimisation of the UPS functionality     5 4 1 The main menu    Whilst on the default UPS summary screen  pressing the  lt j or   gt  button for  lt 1s  will bring up  detailed information about alarms  battery will be 
19. ease check the battery connection or contact Borri or your distributor to order new  batteries     WARNING    e Turn off the UPS and disconnect the UPS power cord from the wall outlet    e Servicing should be performed by qualified service personnel knowledgeable of batteries and  required precautions  Keep unauthorized personnel away from batteries    e Batteries can present a risk of electrical shock or burn from high short circuit current  The  following precautions should be observed   1  Remove watches  rings  or other metal objects   2  Use tools with insulated handles   3  Do not lay tools or metal parts on top of batteries   4  Wear rubber gloves and boots   5  Disconnect the charging source prior to connecting or disconnecting battery terminal    e When replacing batteries  replace them with the same type and number of batteries or battery  packs  Contact your service representative to order new batteries    e Donot dispose of battery in a fire  Batteries may explode when exposed to flame    e Proper disposal of batteries is required  Ensure these are disposed of in relation to WEEE and  other local legislation    e Do not open or mutilate the battery  Released toxic electrolyte is harmful to skin and eyes     Note  If you are not qualified to replace the battery  do not attempt to open the battery    cabinet  Please call Borri or your distributor immediately        11       mwa lo    Uninterruptible Power Solutions    B400R 1 3kVA User Manual    1 3 4 Replacing UPS 
20. g          5 2 8 Fault  When a fault occurs  it illustrates that some fatal problem s  is present  the UPS will be directly cut    off the output or transfer to bypass  and keep alarming  The backlight of LCD will also change to red   The detailed fault table is shown in chapter 7     Input  Output  Load  220 V 0 V OVA  50 Hz 0Hz O W    100  10      zz        Figure 5 10  Fault    25    wares j    Uninterruptible Power Solutions       B400R 1 3kVA User Manual    5 2 9 Other status    When the UPS is overloaded  the alarm will beep twice every second  Some unnecessary loads  should be removed from the ups one by one to decrease the loads connected until it reaches a value  less than 90  of its nominal power capacity        Input  Output  Load    220 V  220 V 1200VA  50Hz  50Hz 1080W    110     all    Figure 5 11  Overload       me 00        While doing a battery test  the symbol for battery test will be shown on the display   Input   Output   Load    220 V  220 V 1000VA  50 Hz  50Hz  900W    100     100  100  ap    Figure 5 12  Battery Test                If the battery status is    bad battery detected    or    battery disconnected     the symbol for battery  failure will be shown and UPS will alarm     Input  Output  Load    220 V  220 V 1000 VA  50 Hz  50Hz  900 W    1 ii    1 poog    Figure 5 13  Battery Fails    N             26    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    5 3 Turning on and Turning off the UPS    Attention  The UPS could only be
21. guidance  If the UPS is to be hardwired  it is  recommended that 2 5mm  wires are used  the    GND    terminal should be connected first     The UPS System has no input breaker on the standard cabinet  When installing the UPS  the user  needs to connect the external breakers and protective components to the input terminals  It is  recommended to select the ISOLATOR instead of the traditional combination kit including breaker  and fuse     When selecting the ISOLATOR  the user can refer to below table     Model No  UPS INPUT ISOLATION  VOLTAGE CURRENT    B400R 010 B  C  300VAC  B400R 020 B  C  300VAC  B400R 030 B  C  300VAC        2  UPS Output Connection  The output terminals of the UPS are an IEC socket type  IEC320 C13 for 10A load  IEC320 C19 for 16A  load  Simply plug the load power cord to the output sockets to complete connection     Model No  Output Socket  pcs   B400R 010 B  C    B400R 020 B  C  8   IEC320 C13  B400R 030 B  C  8    EC320 C13  1   C19    Caution     Do not connect equipment which would overload the UPS system  e g  laser printers        16    B400R 1 3kVA User Manual meres    Uninterruptible Power Solutions     3  EPO Connection   The User can select the polarity of the EPO  the EPO is normally close by default settings     e NO  The EPO connector is normally open on the rear panel  Once the connector is closed with a wire  the    UPS will stop the output until the EPO status is disabled     Disable the EPO Status Enable the EPO Status    e NC  The EPO
22. he    button for  gt 1s  the display will return to the previous menu tree     UPS status  Out put    850w 1130va    Event log    Out put Temperature    49  75  22 C       By press q  gt is Out put DC Bus  Measurements  230 4v 50 0  360  Iv 359 9  By presse4 lt 1s  Input Battery  Control 220 4y 50 0 54 2w 100         Figure 5 17  Measurement menu tree    32    B400R 1 3kVA User Manual a    Uninterruptible Power Solutions    5 4 5 The control menu    By pressing the   button whilst on the menu item    Control     the display will enter the next menu  tree  The following options are available     1  Buzzer mute  the buzzer will stop beeping  enter silence mode     2  Start battery test  commands the UPS to do a battery test    3  Load segments  commands to control two load segments when the UPS is in output mode    4  Clear EPO status  once the EPO status is enabled  the UPS output will be cut off  To recover to  normal status  first the EPO connector should be closed  and then enter this menu to clear EPO  status  the UPS alarm will then stop and recover to bypass or standby mode  The UPS needs be  turned on by manual operation    5  Reset Fault status  when a fault occurs  the UPS will remain in Fault mode and alarm  To recover  to normal status  enter this menu to reset error status  the UPS alarm will then stop and recover to  bypass or standby mode  The reason for the fault should be checked and rectified before the UPS is  turned on again by manual operation    6  Clear e
23. kVA User Manual       mwa lo      Uninterruptible Power Solutions    The UPS provides useful information about itself  load status  events  measurements  identification   and settings through the front panel display     After powering on  the LCD will display the logo for several seconds and then show the default UPS  status summary screen     The display automatically returns to the default UPS status summary screen when no button has  been pressed for 15 minutes  On the UPS status summary screen the following information is given     e Status summary  including mode and load  e Alarm status  if any are present  Notes  alarm including fault and warning information  e Battery and charger status  including battery voltage  charge  level and charger status  e Running information including UPS operating mode and running time    Utility input UPS output  information information          gt          o             foo  am    UPS operating Battery Load  status information information       Figure 5 2  The default LCD Display    More details on the operation of the LCD is illustrated in chapter 4 4    21       B400R 1 3kVA User Manual    Uninterruptible Power Solutions    5 2 Operating mode    Different graphic symbols could be displayed dependent on the current operating mode or status     5 2 1 Line mode    An example of the LCD display in Line mode is shown below        Input   Output   Load    220 V  220 V  1000VA  50 Hz  50Hz  900 W    poora    Figure 5 3  Line Mode    100      
24. n table and pictures are shown as below     Function  B400R 1 3kVA        o 8 O O          B400R 030 B  C     45       B400R 1 3kVA User Manual  Uninterruptible Power Solutions    The EBM rear panel description table and picture are shown below     No O Function  B4BB3  B4BB4  amp  B4BB5 EBM   Earth Line Port    OO Ch O G U O G G D 0 O D U O dA oo G D OU O DO OO Oo OO OOOO OO U G oO D A ES  2000000000 80000 00 0 0 0000 O20 2909000 C2000 00080  CO 0 OOO OO OOO oOo Doo ooa a 0000 oa oe ooo O   OO O00 0000 OOO GD   0000 0000 0000 0 0 0 00 O 00  0006 00  0 0 0 0 0 00 0 00 0  00  07 oO 0000 0000000 CG0 0060 ooo ogc oceoe ogee 00000000 00 O    L    OO O O O O G O O 0 U D O O D OU D O G oO O 00000000000000000000   O      os oo 0000000000 00 00 so o OOOO 00 00 000000000  0000000000000006000 00 0 no a a 0 0 0 on a 0 0 0 0 00 E  0000 0000 000000 0000 06 00    0090 DDD DD O DD DO  M     0000 0000 0000 0 0 0 0 ooo fh              B4BB3  B4BB4  amp  B4BB5 EBM 0    46    B400R 1 3kVA User Manual    Borri Ltd   Systems House     Eckington Business Park  Rotherside Road     Eckington   Sheffield     S21 4HL   Tel   44 01246 431431   Fax   44 01246 431 444   Email  sales borri co uk   Web  www borri co uk    Borri S p A   Via 8 Marzo  2   52010 Bibbiena  Arezzo   Italy   Tel   39 0575 5351   Fax   39 0575 651 438  Email  info borri it  Web  www borri it    47    mea ee    Uninterruptible Power Solutions    
25. ng a Network Management Card  optional     Each UPS in the B400R range has one available communication bay  which supports the optional  Network Management Card  After you install a Network Management Card  you can connect an  environmental monitoring probe to the UPS     Note  You do not have to shut down the UPS before you install a communication card    To install the Network Management Card  complete the following steps    1  Locate the UPS communication bay    2  Remove the two screws that secure the communication bay cover to the UPS and save the screws   3  Insert the Network Management Card into the slot on the UPS     4  Secure the Network Management Card to the UPS with both screws     For more information about the Serial Network Management Card  see the Serial Network  Management Card User s Guide     10 5 Dry Contact port    The UPS incorporates build in single programmable relay output with potential free contact for  remote alarm indication  Dry out port  and incorporates single signal input  Dry in port  See figure in  the UPS rear panel for the locations of the ports     The relay output can be configured by LCD setting menu or protocol command  the default output  contact is    Summary Alarm     the signal input to control UPS On Off Maintain bypass status need to  be configured by LCD setting menu or protocol command  the default input contact is    Disable       Note  The relay output contact must not be connected to any utility connected circuits  Reinfor
26. ni toinnin AE aaa 39  S  MAINTENANCE ssgssa  sssaa  n  snusmaasd si  a a E E EEE E E 41  SME Oa   ee g E E E E IRA TE 41  DEO Se E ens EEE E E E UN 41  E Bater REP ACO ai E E E E E E 41  9  TECHNICALDATA e E EE 42  9 1 Electrical specifications xcvsancssanciezenccanauncsasaieavacivaancs dass nissan a DEAN dd ita Cana bte ia 42  9 2 Operating Environment RO RUN 43  9 3 Typical backup time  Typical values at 25  C in mMinutes             00000 0 00  42  9 4 Dimensions and Welt Sxxssas  s   is is   li A A a 42  10  COMMUNICATION POR Ia ss doa a Si a Dana 43  10 1 RS 232 and USB communication ports    sera arts arts 43  10 2 952 DOTE sessa tea A  al A na   SM 43  TOS USB POR GK IR REIS TR TO ETTA SU RIFIN 43  10 4 Installing a Network Management Card  Optional               cs ccccssssecesessseecessseceecesseeeeseees 44  LOS IAC OA ACK ONL EN EU UA 44        SO UY ARE oirro E E 46  Free Software Download     WINPOWEL           cccseseccecessseceeceseseeeeceecesseaeeceseseeeeceeceseseaeecescessasaeeeees 46  APPENDIX  REAR PANEL  sacccapscsconsscdtssnsexceyssescnnaes es ese csessnaenextasatuesersesesecsossnaeeus   kunn 47    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    1  Safety and EMC Instructions    Please read carefully through the following user manual and    safety instructions before installing and using the UPS        1 1 Installation    Read through the installation instructions before connecting UPS system to the supply   e Condensation may occur if
27. nt panel     Illustrations are shown on the page below           O  5            Sm  Q  N   gt    lt      gt      on  el      S         co    Uninterruptible Power Solutions       mew lo      Uninterruptible Power Solutions       B400R 1 3kVA User Manual    e Rack mount setup  The B400R series can also be installed in a 19 inch rack  Both the UPS and external battery  enclosure S  require 2U of rack space each  Use the following procedure to install UPS in a rack     1  Align the mounting ears with the screw holes on the side of the UPS  and tighten the screws   2  Assemble the rack rails within the rack mounting    3  Slide in the UPS into the rack rail and lock it into the Rack mounting    4  Tighten the screws  to secure the UPS into place and then the load can be connected           mwa lo    Uninterruptible Power Solutions    B400R 1 3kVA User Manual    1 1 4 EBM Installation  Optional     e Connecting the EBM in Tower form    1  Position the extended UPS stands appropriately so that 1 stand will be at either end of the UPS  and EBM    2  Tighten the screw on the metal sheet for stabilization and secure the UPS and EBM together  then  lift and place down the UPS and EBM carefully into the stands    3  Connect the Earth line from UPS  port A  to EBM  port B    4  Take off the front panel  and connect the battery terminal  A  from UPS to EBM terminal  B  as  shown below  Users need to remove the small gate C  on the side of the front panel to allow the  outlet wire of the 
28. ons    8  Maintenance    8 1 Operation    The UPS system contains no user serviceable parts  If the battery service life  3 5 years at 25  C  ambient temperature  has been exceeded  the batteries must be replaced  In the event that you  require new batteries please contact your distributor or Borri for assistance     8 2 Storage    If the batteries are stored in temperate climatic zones  they should be charged every three months  for 1 2 hours  You should shorten the charging intervals to two months at locations subject to high  temperatures i e  temperatures exceeding 25  C     8 3 Battery Replacement    If the battery service life has been exceeded  the batteries must be replaced   Battery replacement should be performed only by qualified personnel     It is recommended to isolate the UPS completely from the mains before the replacement  If there is  a battery breaker then turn it off first  Disconnect the battery cable carefully and make sure no  exposed wires can be touched  Reconnect the new batteries to the UPS by following section 5 8   Then turn on the battery breaker and start the UPS     If batteries need to be replaced while the UPS is running  make sure the UPS will not shut down  during the replacement  If there is a battery breaker then turn it off first  Disconnect the battery  cable carefully and make sure no exposed wires can be touched  Reconnect the new batteries to the  UPS by following section 5 8  Then turn on the battery breaker and press the ON switch 
29. r electrical equipment     The double conversion principle eliminates all mains power disturbances  A rectifier converts the  alternating current from the mains to direct current  This direct current charges the batteries and  powers the inverter  On the basis of this DC voltage  the inverter generates a sinusoidal AC voltage   which permanently supplies the loads     Computers and periphery are thus powered entirely by the mains voltage  In the event of power  failure  the maintenance free batteries power the inverter     This manual covers the UPS listed as follows  Please confirm whether it is the model you intend to  purchase by performing a visual inspection of the Model No  on the rear panel of the UPS     Model No  Model No  B400R 010 B    Internal batteries a  B400R 020 B j a B400R 020 C Internal Charger Model  B400R 030 B B400R 030 C       15    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    4  Connection    4 1 Inspection    Inspect the packaging carton and its contents for damage  Please inform Borri or your supplier  immediately should you find signs of damage     Please keep the packaging in a safe place for future use     Note  Please ensure that the incoming feeder is isolated and secured to prevent it from being  switched back on again     4 2 Connection     1  UPS Input Connection   If the UPS is connected via the power cord  please use an appropriate socket with protection against  electric current  the user can refer to below table for 
30. ric shock if  you touch the UPS output sockets or output terminal block even if the UPS is not connected to  the mains    e In order to fully disconnect the UPS  first press the ON OFF button to turn off the UPS  and then  disconnect the mains lead    e Ensure that no liquid or other foreign objects can enter the UPS    e Do not remove the enclosure    e This system is to be serviced by qualified service personnel only    e Remove the protective panel only after disconnecting the terminal connections     1 3 Maintenance  servicing and faults    e The UPS operates with hazardous voltages  Repairs must be carried out by qualified  maintenance personnel    e Caution   risk of electric shock  Even after the unit is disconnected from the mains power supply   components inside the UPS are still connected to the batteries which are potentially dangerous    e Before carrying out any kind of service and or maintenance  disconnect the batteries  Verify that  no current is present and no hazardous voltage exists in the capacitor or BUS capacitor  terminals    e Batteries must be replaced only by qualified personnel    e Caution   risk of electric shock  The battery circuit is not isolated from the input voltage   Hazardous voltages may occur between the battery terminals and the ground  Verify that no  voltage is present before servicing    e Batteries have a high short circuit current and pose a risk of shock  Take all precautionary  measures specified below and any other measures nece
31. rrect disposal of electrical products  Please contact Borri or your distributor  for further information     1 4 Transport   Please transport the UPS only in the original packaging  to protect against shock and impact    1 5 Storage   The UPS must be stockpiled in a room that is well ventilated and dry to protect UPS Service life     1 6 Standards    EM  IEC EN62040 2  IEC EN62040 2  IEC EN 61000 3 2   ES  IEC EN 61000 4 2  IEC EN 61000 4 3  IEC EN 61000 4 4  IEC EN 61000 4 5  IEC EN 61000 4 6  IEC EN 61000 4 8    IEC EN 61000 4 11  IEC EN 61000 2 2       13    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    2  Description of Commonly Used Symbols    Some or all of the following symbols may be used throughout this manual  It is advisable to  familiarize yourself with them and understand their meaning     Symbol and Explanation    Symbol Explanation Symbol Explanation  Alert you to pay Protective Ground  Special attention  voltages present  a Turn on the UPS Overload Indication      Idle or shut down the Recvcle  UPS      NU Alternating Current Do not dispose with  Source  AC  ordinary waste  Direct Current Source   DC        14    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions  3  Introduction    The B400R Series is an uninterruptible power supply incorporating online double conversion  technology  The UPS s flexibility to handle an array of network devices makes it the perfect choice  to protect your LANS  servers  workstations  and othe
32. ry    cable which should be able to carry the current of  gt 50A for all models  the cross section area should  be greater than 4mm    for all models  Battery wire colour is recommended as following     ND    Green Yellow     6  The brown wire is connected to the     terminal of the battery  The blue wire is connected to the      terminal of the battery   Note  the green yellow wire is grounded for protection purpose       7  Make sure all wires are connected correctly  and install the terminal block cover on the rear  panel of the UPS      8  Connect the UPS to the load  Then  turn on the mains switch or connect the power cord of the  UPS to utility power supply  the battery would start to be charged     Caution     A DC Breaker must be connected between the UPS and external battery     Caution   The output terminals of the UPS system may still be electrically live even if the UPS has been  disconnected from mains or if the Bypass switch is in the    OFF    Position       18    B400R 1 3kVA User Manual Bere    Uninterruptible Power Solutions  5  Operation    5 1 Display Panel    The UPS has a four button graphical LCD with dual colour backlight  Standard back light is used to  light up the display with white text and a blue background  When the UPS has a critical alarm  the  backlight changes the text to dark amber and the background to amber  See Figure below     Input   Output   Load  220 V  220 V   1000VA    50 Hz 90 Hz 500 W              LCD Screen  100  100     e       
33. shown     Whilst on the default UPS summary screen  when pressing the  lt j button  gt 1s  will allow the user to  enter the main menu tree     The main menu tree includes six branches  the UPS status menu  the event log menu  the  measurement menu  the control menu  the identification menu  and the setting menu     28    B400R 1 3kVA User Manual       Uninterruptible Power Solutions       Input  Outputy Lond       cora 220 v  220 v i      va  UPS status 5 Hz s   ds  ooo W    a      na    Alarm   4   Event log    Oui pat overload    Alarm Rall      Battery Volt  44 2    Battery charging  Measurements Charger level  100     Statis   Line mode  Running time     p001  03  01  00  Control    Identification    Settings    Figure 5 14  Main menu tree    29       mares j    Uninterruptible Power Solutions    B400R 1 3kVA User Manual    5 4 2 The UPS status menu    By pressing the    button whilst on the menu item    UPS status     the display will enter the next  menu tree     The content of UPS status menu tree is the same as the default UPS summary menu     By pressing the    button for  gt 1s  the display will return to the previous menu tree     Input Output  Load    By press     gt is 220 Vi 220 V  1000VA   A    UPS status 50Hz  50Hz  900 W       By press 4J  lt 1s   q 100  pe   i       Alarm   4   Out put overload         By press dor    lt 15  Event log    Battery Volt  54 2V  Battery charging  e Charger level  100     Status   Line mode  Running time   0001  03  01 00    Fig
34. ssary when working with batteries        Remove all jewellery  wristwatches  rings and other metal objects      Use insulated tools only    e When changing batteries  replace with the same quantity and the same type of batteries    e Do not attempt to dispose of batteries by burning them  It could cause an explosion    e Do not open or destroy batteries  Effluent electrolyte can cause injury to the skin and eyes and  may be toxic    e Please replace the fuse only by a fuse of the same type and of the same amperage in order to  avoid fire hazards    e Dismantling of the UPS must only be performed by qualified service personnel     10    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions  1 3 1 UPS and Battery Care    For the best preventative maintenance  keep the area around the UPS clean and dust free  If the  atmosphere is very dusty  clean the outside of the system with a vacuum cleaner  For long battery  life  keep the UPS at an ambient temperature of 25  C  77  F     1 3 2 Storing the UPS and Batteries    When the UPS is intended to be stored for a long period  recharge the batteries every 6 months by  connecting the UPS to mains supply  The batteries charge to 90  capacity in approximately 4 hours   However  it is recommended that the batteries charge for 48 hours after a period of long term  storage     1 3 3 Time to Replace Batteries    When the discharge time is less than 50  of is specified after fully charging  the battery may need to  be replaced  Pl
35. terruptible Power Solutions    11  Software    Free Software Download     WinPower    Winpower is UPS monitoring software which provides a user friendly interface to monitor and  control your UPS  This unique software provides safe auto shutdown for multiple computer  systems during a power failure  With this software the user can monitor and control any UPS  on the same LAN regardless of distance from the UPS                m sn RD RF i   m cael  fi Winpessar Menager 4304   boni pphilim        ete     System Logs Devoe Jook Monfor SNMP Preference Language Helo            gt  8 Be    Rost    Normal ma    s  re Modot ON LINE Com Pot USS Sena   CASVDTDBSD  130100    g uz  WAN  Ed  25 04 V7 ER Se LOAD   ad one    Charger         Haters voltage  4   2y  UPS Temp Load       Pee gt Ser lee oe SO OT DA 400 LES Cute Bypast mote  20930706 094920 Output Normal mode    Installation procedure     1  Go to the website  http   www borri co uk softwaredownload    2  Choose the operating system you use and follow the instructions described on the website  to download the software     3  When downloading the required files from the internet  enter the serial No   S11C1 01220   0100 478DF2A to initiate installation of the software  When the computer restarts  the  Winpower software will appear as a green plug icon located in the system tray  near the clock     44       mwa lo    Uninterruptible Power Solutions    B400R 1 3kVA User Manual    Appendix  Rear Panel    The UPS rear panel descriptio
36. to start the  battery test  check that the battery information is normal     39    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    9  Technical Data    9 1 Electrical specifications    Input Parameters    Model No  B400R 010 B  C  B400R 020 B  C  B400R 030 B  C     Phase 1    Frequency  45 55   54 66  Hz    Max Current  A     Output Parameters    Power Rating 1kVA 0 9kW 2kVA 1 8kW 3kVA 2 7kW    Voltage 208 220 230 240    1    Frequency 50 60   0 2  Hz  Battery mode   Wave form Sinusoidal   Batteries    Model No  B400R 010 B B400R 020 B B400R 030 B  Number and Type 3 x 12V 7Ah 4 x 12V 9AH 6 x 12V 9Ah    9 2 Operating Environment    Ambient Temperature 0  C to 40  C  Operating Humidity        lt  1000m  Storage Temperature 0  C to 45  C       9 3 Typical backup time  Typical values at 25  C in minutes       3 10             B400R 030 8 Oo 3 E fk    9 4 Dimensions  amp  Weights    B400R 010 B   C B400R 020 B   C B400R 030 B   C    Net Weight 16 2   8 4 19 7  9 3 28 6   13 2   KG   UPS Case    Dimensions   mm    WxDxH       F 440 x 440 x 88  2U  440 x 605 x 88  2U   Dimensions   mm   EBM Case ED   KG       40    B400R 1 3kVA User Manual E IR    Uninterruptible Power Solutions    10  Communication Port    10 1 RS 232 and USB communication ports    To establish communication between the UPS and a computer  connect the UPS via one of the  communication ports by using the appropriate communications cable  USB RS232      Note     Only one of communication ports can
37. ure 5 15  UPS Status menu tree    30    eww 2 oe      Uninterruptible Power Solutions       B400R 1 3kVA User Manual    5 4 3 The event log menu    By pressing the a button whilst on the menu item    Event log   the display will enter the next  menu tree     All the old events  alarms and faults will have been recorded and stored in this menu  The  information available includes the illustration  the event code  and the operating time of UPS when  the event happened  By pressing the  lt q or  gt  button for  lt 1s  all the events can be displayed    one by one     The max number of recorded events is 50  when the number is larger than 50  the oldest fault event  is overwritten by the newest event fault     By pressing the A button for  gt 1s  the display will return to the previous menu tree     UPS status    0001  05  01  00  By press d  gt 1s Alarm  41  oo            Output overload  By press a    lt 15 1 3    Event log    0001  03  01  00  Event  02  Utility Abnormal    Measurements  2 3       0000  00  00  03  Alarm  84  Fan Failure       Figure 5 16  Event menu tree    31     ea       B400R 1 3kVA User Manual  Uninterruptible Power Solutions    5 4 4 The measurement menu    By pressing the A button whilst on the menu item    Measurement     the display will enter the next  menu tree     A lot of useful information can be checked here  including the output voltage and frequency  the  output current  the load capacity  the input voltage and frequency  etc     By pressing t
38. vent log  To clear the entire event  alarm and fault history that has been recorded    7  Restore factory settings  all the settings will be reset to default factory settings  This can only be  done whilst in bypass or standby mode     33    8       B400R 1 3kVA User Manual    Uninterruptible Power Solutions       By prose     gt 15    Status  fault active  Reset fault no    Total events 50  Clear event log  no    Figure 5 18  Control menu tree    34       B400R 1 3kVA User Manual    Uninterruptible Power Solutions    5 4 6 The identification menu    By pressing the   button whilst on the menu item    Identification     the display will enter the next  menu tree     The identification information includes  the UPS serial number  firmware serial number and UPS  model type     By pressing the  lt 4 button for  gt 1s  the display will return to the previous menu tree             Identification          gt is   Type Model        By pross a     vis B400 010 B       By press al or  mis    Seral Number  Settings BO0O0OOO00OO    UPS Fimwawe   MAMA AA    Figure 5 19  Identification menu tree    5 4 7 The setting menu    Please contact your local distributor for further information before altering the settings  Some  settings will change the specification  and some settings will enable or disable UPS functions  The  unsuitable alteration of settings by users may result in potential UPS failure  and even cause direct  damage to the load  batteries or UPS     35    B400R 1 3kVA User Manu
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  Home Decorators Collection 1599600270 Instructions / Assembly  Elmo Computer Hardware BUT- X/YYY User's Manual  USHMID SMS CLIENT USER MANUAL    Panduit MPO/LC, 8 m  V7 Capped USB 2.0 Flash Drive 4GB black  Nuance Dragon NaturallySpeaking Professional 11  CE STW, ZUB, BM - Rieber & Co. KG    Copyright © All rights reserved. 