1.      OUTPUT    CS         Figure 5 3 Battery Mode          2  When the battery capacity decreases  the number of battery capacity indicators  turned on will decrease  If the battery voltage drops to the pre alarm level  the  alarm will beep every second to remind the user of insufficient battery capacity    3  The other four display pages are load percent page  actual load page  battery  information page and the maximum temperature page     5 2 3 Bypass Mode    When operating in bypass mode set up through UPSilon software  the display on  the front panel is shown as the figure 5 4  the utility power indicator and the bypass  indicator are turned on  Load information area shows load value  and the battery  level area indicates dynamically when the battery is not fully charged  the battery  level icons lit one after another circularly   When the battery is fully charged  all  the level icons are turned on     1  When operating in bypass mode  the UPS beeps every 2 minutes  If the     Function    key is pressed for more than 2 seconds  the alarm will not beep   silence function   Press the    Function    key more than 2 seconds again to  resume the alarm function     2  If the utility power indicator blinks  it shows that the voltage or frequency of the  utility power is out of the input range of the UPS or there are problems with  reversed polarity  L N  of site wiring or disconnect to the ground for protection    3  The other four display pages are load percent page  actual lo
2.    the No of lighted load led   indicator represents current output frequency setting value    If you need to set the voltage  check the voltage setting is enabled  the inverter   indicator is lit   If not  press the  F  more than one second  then release  the   inverter indicator will be turn on  at this point you can start to set output   voltage    4  Release the  OFF  key after you press it more than one second  the next load led  indicator will be turn on    5  Repeat the fourth step until the No of lighted load indicator meets the required  voltage    6  Press  ON  key about one second  the output voltage setting completed   7 The frequency setting is the same as the voltage setting  but before the setting    15    a    3    please confirm the frequency setting is enabled  the inverter indicator blink   if  not  press  ON  key about one second in order to switch to the frequency setting  screen    8  When done  Press the  F  and  OFF  button more than one second  then release   the buzzer will beep once  exit the setting mode     In the setting process  if no key is detected within twenty second  the UPS exits the  setting screen automatically     The relation of the No of lighted load led and voltage  frequency as follows    value of output    voltage and 220V 230V 240V 208V 200V    frequency 50Hz 60Hz Automatically  detect the    frequency    Note  L1   L4 are the green lights  L5 is the yellow light  L6 is the red light    4 3 3 Audible alarm and LED indication of UP
3.   second  y to the backup power   Blink once Beep once UPS power on Check the battery of the  A03 every UPS connected  every second abnormal  second properly   Blink once Bee Batte Please contact the  A04 every peep 1y distributor or Service  continuously overcharging  second center  BEBE once Beep once   Ensure that the fan is  A05 every Fan failure  every second not locked  second  Maybe reversed Please check the polarity    of the neutral wiring and  polarity  L  N  of   M    2x the line wiring  ensure  SEWING UE that The green yellow  Blink once   Beep once disconnect with    8 ddp  wire connect protective  A06 every every two ground  Or the ound bropeily    r  second minutes voltage between 8 proper y              neutral wiring to  protective  ground is to high       make sure the voltage   between neutral wiring   to protective ground is  less than 36V AC       Table 7 2 UPS troubleshooting of LCD panel indicator    When you contact the service center  please provide the following information    e Model No  and Serial No  of the UPS    e The date when the problem arose    e Complete description of the problem  including the panel display  alarm warning   and power condition and the load capacity  If the UPS is a long backup time  model  you may also provide the battery information     30          8 Specifications    8  1 Electrical       Model    HT111K   HTI1IKL   HT112K   HTII2KL   HT113K   HT113KL                Rating          IKVA 800W 2KVA 1600W 3KVA 2400W       
4.  cable to ensure normal operation of the UPS     3 Installation    3 3 3 Connecting Communication Cable  1  Computer interface    Computer Interface       Computer  Communication cable      g     mR        Y    Computer interface  The type of signals is provided by the UPS to communicate  with a host computer through communication cable included  in the standard accessory  User can use special monitor  software UPSilon in the standard accessory to monitor the    8    UPS through the port     2  Alternative connection of communication    Intelligent slot       Intelligent Slot  It is designed for installing the dry contact card  SNMP card and  485 card  You can choose for one of them to installed  a    dry contact card  You can utilize monitor function of dry contact to manage the  power supply directly   b    SNMP  It enables you monitor the UPS remotely through Internet   c   485  Central monitor card     Note  Please remove the cover board of the intelligent slot before any card is  installed     4 Operation  LED model       4  1 Introduction of Display Panel    4  Load battery capacity indicator 3  Load battery capacity indicator  5  Load battery capacity indicator 2  Load battery capacity indicator  6  Load battery capacity indicator GO        Fault indicator   BT  l      9s Inverter indicator    8  Utility power indicator      ee    3     J      waen indicator  sal    7  Bypass indicator  POWER ON                ou                 rucrioN    POWER OFF          1  ON butt
5.  ran in normal mode  pressing this button  more than 2 seconds  buzzer beeps twice  can start the battery self diagnosis    b  Silence function in battery bypass mode  In battery bypass mode  when the buzzer beeps  pressing and holding the  function button for more than 2 seconds  buzzer beeps two times  can silence  the buzzer  Press the button for more than 2 seconds  buzzer beeps twice  again  to resume the alarm function   c  LCD display screen switch  Pressing the function button for more than 1 seconds and less than 2 seconds   buzzer beeps once  to switch LCD display screen   4  LED indicators   The LED indicators contains  Bypass indicator  utility power indicator  Inverter   indicator  Battery indicator  The definition of each indicator is the same as LED   panel  refer to table 4 1      19    5 Operation  LCD model   5 2 Operation Mode    UPS Operation Mode contains normal mode  battery mode and bypass mode   Under the three modes  the page showing output voltage and output frequency is  the main display page  If users need more information about UPS  Pressing the  function button can initiate display screen switch  If the current page is not the  main page  UPS will automatically switch back the main page after 30 seconds  In  order to extend the LCD usage life  the backlight will turn off after 1 minute  without any switch operation  At this point  Users just need to touch any button  briefly to turn on the backlight     5 2 1 Normal mode    When operating in the 
6.  the UPS outlets  system completely power down     4 3 2 Conducting Battery self diagnosis    In UPS operation  users can manually initiate battery self diagnosis to check the   battery conditions  There are two methods to initiate the battery self diagnosis      Through the function button  In normal mode  press and hold the function for more than 2 seconds until the  buzzer beeps twice  At this point the indicators  LED7 10  will blink cyclically   indicating the UPS has worked in battery mode and the battery self diagnosis  has started  The battery self diagnosis will last for 10 seconds default  In the  event of a battery fault during battery self diagnosis  the UPS will transfer to  normal mode automatically          2  Through the monitor software  Users can also initiate battery self diagnosis through the background monitoring  software     4 3 3 Setting the output voltage and frequency   1  Connect the mains input to the UPS  and make the UPS works in standby mode  or bypass mode    2 Press the  F  and  OFF  button more than one second  then release  the buzzer will  beep once  and the bypass indicator with battery indicators will flash once  every second  which means all of bottom are used for UPS setting  At this point   if the voltage setting is enabled the Inverter indicator is lit   the No of lighted    4 Operation  LED model     load led indicator represents current setting value of output voltage  and if the   frequency setting is enabled  inverter lights flash
7.  without utility power    1  Turning on with utility power   Connect the mains input to the UPS  press the ON button more than one second   UPS starts to turn on  At this point  the LCD begins to conduct self diagnosis   all the LCD indicators are turn on about 4 seconds   A few seconds later  the  UPS will begin to operate in Normal mode  meanwhile  the utility power  indicator  inverter indicators will turn on  If the utility power is abnormal  the  UPS will work in battery mode     2  Turning on without utility power   With no mains input feed to the UPS  press the ON button more than one second   ups start to turn on  At this point  the LCD begins to conduct self diagnosis  all    24    the LCD indicators are turn on about 4 seconds   A few seconds later  the battery  indicator  inverter indicators will be turn on to indicate that the UPS is working  in battery mode     5 Operation  LCD model    2     Powering down the UPS    The operation of powering down the UPS contains  turning off ups in normal mode   turning off ups in battery mode    1  Completely power down the UPS from Normal mode    Hold and press the OFF button persistently for more than 1 second to power off  the UPS  If it bas been set up to work in bypass mode by software  the bypass  indicator will be turned on to indicate that the UPS is working in bypass mode   In order to cut off the output from the UPS  simply cut off the utility power  supply  LCD begins to conduct self diagnosis  all the LCD indicator
8. 1 Introduction  1  1 Description of Commonly Used Symbols  Some or all of the following symbols may be used in this manual and may appear    in your application process  Therefore  all users should read the form carefully and  thoroughly        Symbol  amp  Description                Symbol Description   N Caution  danger  IN Danger electric shock  NY Alternating current  AC        z  Direct current  DC        Protective ground       Recycle                Do not dispose with ordinary trash       1  2 Safety Instructions             Read this manual carefully and thoroughly before operation the UPS and save  this manu        operly for future reference   2  Do not tear up or shatter the alarm table on the UPS and pay attention to it     Please do ngt overload the UPS   The UPS  htains large capacity batteries  The case of the UPS must not be  opened by untrained personnel  Otherwise  it may cause electric shock   5  Do not short the positive and negative electrodes of battery  Otherwise  it may  cause elect X  shock or fire   6  Do not plunge or insert any objects into the air vents and other inlets   7  Do not store or use the device in the following environment       Where there is inflammable gas  corrosive agents or heavy dust      Where the temperature is very high or low  above 40  C or below 0 C  or the  humidity is very high more than 90        Under direct sunlight or close to heating facilities      Place of strong vibrations  8  In the event of fire occurring in th
9. Input system    Single phase  amp  earth ground       Voltage range        90 5 VAC  290 5 VAC                                                                                                       Input Power factor 20 99  Voltage range of  8045 VAC   28645 VAC  default  80VAC 264VAC  bypass Could be adjusted by software   Output system Single phase  amp  earth ground  Rated voltage 220VAC  V  Power factor 0 8  Voltage precision 2   1 The output frequency synchronizes with the input  None i hen the input fi is in th f 46  hee requency when the input frequency is in the range o  Output Hz 54 Hz  frequency 2 The output frequency is 50Hz when the input frequency is  Output pud not in the range of 46 Hz   54 Hz  moc     3 Can be set as 60Hz  Inverter overload   105  5  lt Load lt 125  5  50s transfer to bypass  capacity  Utility   125  45  lt  Load  lt 150    5  25s transfer to bypass  power  25 C  Load  gt  150  5  300ms transfer to bypass    Oms  Normal mode          Battery mode   Transfer time   lt 4ms  Normal mode      Bypass mode    Crest factor 3 1  Batteries voltage 36VDC 72VDC 96VDC 96VDC 72VDC  Battery Quantity 3 none 6 8 none 8 6 none  Battery Battery Type Sealed maintenance free se   P battery of battery voltage  Backup Time 25 C   Full load25min  Standard   Charge current lA 7A 1A 7A 1A 5 5A                              Notel  Output voltage can be set  200V 208V 220V 230V 240V     31    8 Specifications    8  2 Mechanical                            Model W H D mm  W
10. S operating status and faults                                                    LED indicators  No  Operating status 1 2 3 4 5 6  7  819  10   Audible alarm                                1 0   25 Load e ee none  2 26   50  Load e o ele none  Normal   51   75  Load e  ele ele none  mode 76    100   4 e e  ele ele none  Load  101   105  Beep once  5 e  e e 0 e0 ele  Load every sec  Battery 0 25  Beep once  6   e e e  mode battery capacity every sec                                     16                                                                                        26 50  Beep once  7 P ele e  e  battery capacity every 4sec   8 51 75  els aie Beep once  battery capacity every 4 sec   76 100  Beep once  9   e l e lele e e  battery capacity every 4 sec   10 10096 e  aee le FUP Beep once  battery capacity every 4sec   Beep once  11 Bypass mode Tti fTIT e 9  1 every 2 min   12 Overloaded in bypass e e e alaa i Beep twice  mode  pre alarm every sec  13 Utility power abnormal TITITITI EITI wet  t T  14 Overload in Battery mode  FR T Beep once  pre alarm every sec  Overloaded in Normal Beep once  15 ele ele  mode  pre alarm every sec    Sustained  16 Overheating fault e  e  T7 f beep  17 Inverter fault e  e  da ean  eep          4 Operation  LED model                                                                    LED indicators  No  Operating status 112 3 4 5 6 7  8  9   10   Audible alarm                         SIE  Sustained  18 BUS voltage fault e e 111 beep  19 Over 
11. The battery life depends on the ambient  temperature  charging and discharging times  High ambient temperature and deep  discharging will shorten the battery life            Ww    N      Sealed maintenance free lead    acid battery be used in the standard  When being    connected to the utility power whether the UPS has been turned on or not  the  UPS keeps charging the battery and also offers the protective function of  charging and discharging       Keep the ambient temperature between 15  C and 25  C    If the UPS has not been used for a long period  charging is recommended at the    intervals 3 months       Batteries should not be replaced individually     Under normal conditions  the battery life lasts 3 to 5 years  In case if the battery    is found not in good condition  earlier replacement should be made  The battery  should only be replaced by qualified service personnel     Note  1 Prior to battery replacement  the UPS must be turned off and disconnected    from utility power    2  Metal objects such as rings and watches should be removed    3  Use the screwdriver with insulated handle  Tools and other metal objects  should not be placed on the battery    4  Short circuit or reverse connection between the positive and negative  terminal of the battery is strictly forbidden     6  2 Checking UPS function    Every time when conducting field maintenance  please check the regular function  of the UPS  including     1      Check the operation status of the UPS    If the 
12. ad page  input  information page and the maximum temperature page     Notes  When operating in bypass mode  the backup function of the UPS is not  22    available and the power used by the load is directly from the utility power  via internal EMI filter   5 Operation  LCD model       c     VAC  DD Hz    OUTPUT    TJ  e         Figure 5 4 Bypass Mode             5 2 4 LCD indication of UPS alarm status and faults    In the event of an UPS fault  UPS enters fault operation mode  at this point  the  fault icon turns on consistently  the buzzer beeps continuously and the data  information area shows current fault code  refer to table 7 2   the display on the  front panel is shown as the figure 5 5  users can switch to output page by pressing  function button     FO        GET  eo    Figure 5 5 Fault display          When a warning occurred  the fault icon blinks every second  and users can switch  to the alarm display page shown as the figure 5 6 to check the warning code     23    5 Operation  LCD model             GET        Figure 5 6 Alarm display    5 3 Operating Instructions    5 3 1 UPS ON OFF Operation    Note  The battery is fully charged before delivery  However  storage and  transportation will inevitably cause some charge loss  Therefore  it is  advisable to charge the battery for 10 hours before using it  so as to ensure  adequate battery capacity     1  Turning on the UPS    The operation of turning on the UPS contains  turning on with utility power and   turning on
13. any problem  it may be due to the defect or aging of the battery  please refer to  the    troubleshooting    in chapter 7 to solve the problem accordingly    4  The other four display pages are load percent page  actual load page  input  information page and the maximum temperature page     Note  Connection to the power generator should be made according to the   following steps    e Activate the power generator and wait until the operation is stable before  connecting the output of the power generator to the UPS  be sure that the  UPS is in idle mode   Then  turn on the UPS according to the startup  procedure  After the UPS is turned on  the loads are connected one by one        It recommended that the capacity of the AC generator chosen should double  that of the UPS     5 2 2 Battery Mode    When operating in the battery mode  the display of main page on the front panel is  shown as the figure 5 3  The battery indicator and the Inverter indicator are turned  on  If the utility power indicator blinks at the same time  it shows that the utility  power is abnormal  Load information area shows load value  and bat level area  shows current battery capacity     1  When the UPS is running in battery mode  the alarm will beep every 4 seconds    If the    Function    key is pressed for more than 2 seconds  the alarm will not beep    silence function    Press the    Function    key more than 2 seconds again to  resume the alarm function     21    5 Operation  LCD model    ecu Suu   
14. blocked so as  to ensure good ventilation       In case if the UPS is unpacked  installed and used at very low temperatures     condensations of water drops may appear  It is necessary to wait until the UPS  fully dried inside out before proceeding to installation and use  Otherwise  they  may be a risk of electric shock       Place the UPS near the utility power source outlet which supplies power to the    UPS  In any emergency  switch off the main input socket  cut off the battery  voltage input  All power sockets must be connected with ground protection     3 3 Cable Connection    3 3 1 Connecting Input and Output Cables    1     Input cable connection   If the UPS is connected via the power cable  please use a proper socket with  over current protection  and pay attention to the capacity of the socket  over 10A  for HT111K  L   over 16A for HT112K  L  and HT113K  L   A side of input    5    wiring has been fixed with the UPS  and the other side is just need to plug into  the input socket  The wiring configuration is shown in the following diagram     3 Installation          J        gopagaeogggog         DDOODCODODOOOD              HERES    o  ES  e          Figure 3 1 Connection Method of Input    N      Output cable connection  The output of HT111K  L  HT112K  L   HT113K  L  all available to uses  sockets  The total output power shall not exceed 1kVA 0 8kW  2kVA 1 6 kW   3kVA 2 4 kW  Simply plug the load power cable to the output sockets of UPS to  complete connection a
15. ct to the ground for protection    2  When operating in bypass mode  the UPS beeps every 2 minutes  If the     Function    key is pressed for more than 2 seconds  the alarm will not beep    silence function    Press the    Function    key more than 2 seconds again to  resume the alarm function     Notes  When operating in bypass mode  the backup function of the UPS is not  available and the power used by the load is directly from the utility power  via internal EMI filter    4 Operation  LED model          Ez O                GET  QO   O    Figure 4 4 Bypass Mode          4  3 Operating Instructions    4 3 1 Turning On and Completely Powering Down the UPS   Note  The battery is fully charged before delivery  However  storage and  transportation will inevitably cause some charge loss  Therefore  it is  advisable to charge the battery for 10 hours before using it  so as to ensure  adequate battery capacity     1  Turning on the UPS    The operation of turning on the UPS contains  turning on with utility power and  turning on without utility power     1  Turning on with utility power   Connect the mains input to the UPS  press the ON button more than one second   UPS starts to turn on  At this point  the UPS begins to conduct self diagnosis   with the load battery capacity indicators on the front panel turned on and then  off one after another  A few seconds later  the UPS will begin to operate in  Normal mode  meanwhile  the utility power indicator  inverter indicators will  tu
16. e vicinity  please use dry powder fire  extinguishers  The use of liquid fire extinguishing agents may cause electric  1    AU    shock   2 Product Description    The UPS is an on line uninterruptible power supply device incorporating  double converter technology with single phase input and single phase output  It  offers the high quality power supply with the greatest degree of availability and  reliability  The UPS is compact and convenient for users  especially for the basic  equipments in some areas such as  finance  communication  government  traffic   manufacture  education and so on     2  1 System Type and Configuration    There are two types of UPS according to the battery configuration  standard type  and long backup time type  each available in the following ratings  IKVA  2kVA  and 3kVA UPS    Table 2 1 UPS types and configurations                Type Model Remark  With a 1A internal charger and 3 build in batteries of  PAS 12V  7AH  With a 1A internal charger and 6  or 8  build in  Bere HIER batteries of 12V  7AH  HT113K With a 1A internal charger and 8  or 6  build in    batteries of 12V  7AH   HTIIIKL   Witha 7A internal charger and external battery slot   HT112KL   Witha 7A internal charger and external battery slot   HT113KL   With a 5 5A internal charger and external battery slot           Long Backup  Time                      Note     L    model means Long Backup Time     2 Product Description  2 2 The Appearance of the UPS    Computer Interface       Inte
17. eight kg   HT111K 144x229x350 11 5  HTIIIKL 144x229x350 6  HT112K  72VDC     96VDC  190x328x424 24 28  HT112KL 190x328x424 12  HT113K  96VDC    72VDC  190x328x424 28 24  HT113KL 190x328x424 12                8  3 Environmental                                              Item Normal range  Ambient temperature 0  C    40 C  Environment humidity 20  90   No condensation     Lower than 1000m  no derating  Alude Over 1000m  1  derating for every 100m rise  Storage temperature  15 C    45 C  8  4 EMC  Item Standard Level  ESD IEC61000 4 2 LEVEL4  RS IEC61000 4 3 LEVEL3  EFT IEC61000 4 4 LEVEL4  Surge TEC61000 4 5 LEVEL4                   8 5 Safety    32    Comply with GB4943 2001  IEC62040 1 and CE requirements     8 6 Industry Standard    Comply with EN62040  YD T 1095 2000 requirements   9 Appendix    9 1 Consignment Lists       Model Type Accessories No        Machine       Standard Model Intelligent monitor software CD       User Manual       Serial communication cable       Machine       Intelligent monitor software CD       Long backup time    Model User Manual       External Battery Cable                                              rem          Serial communication cable          Table 9 1    33    
18. em  In the event of a UPS fault that  will not lead to UPS shutdown  the load will be automatically transferred to the  bypass  Meanwhile  the LED indicators will indicate the fault type  and the fault  information will be reported through the communication ports    6  Charger  The charger of standard UPS provides 1A charging current  and long   backup time provided 7A  3K is 5 5A  charging current    7  Battery  Sealed maintenance free lead    acid battery can be used as the DC   source of the UPS     N    LoS     Nn    8     Output filter  It filters the output and provides clean AC power to the load     3 Installation    3   1     2     B    o             U    1 Unpacking Inspection    Open the packing box of UPS and take it out  visually examine the unit for  transit damage    Check against the accessory lists that the accessories of the UPS are present    Refer to Table 9 1        Make sure the model is what you wanted from the nameplate on the rear panel    If the UPS arrives damaged  or there is any missing accessory or other question  above  please contact the distributor immediately       2 Installation Notes      When locating the UPS  make sure there is no hazardous objects such as water     inflammable gas  corrosive agents and so on around the UPS  and that the  installation environment meets the specifications    The UPS should not be placed on a side  The air inlet port at the front panel and  the outlet port on the rear panel and two side panels should not be 
19. enter  LED are on  The 1  Fault Bee Over chargin The charger of the UPS is defective   LED and 3  veep rgng Please contact the distributor or  continuously Protection    LED are on Service center  Check the load and remove the  The 1  Fault Bee Bir  non Critical device  Recalculate the  LED and 2  db iu the load load power and reduce the member of  LED are on y devi loads connected to the UPS  Check  EE whether the load device is fault  The 1  Fault    LED and 2  Beep once Fan of UES is Please contact the distributor or  not connected    LED and 6    every second Service center  or fault  are on  Turn off the UPS  Remove all loads   They Fault The UPS Ensure that the loads are not failed or  LED and 2  Beep   i    output is short the UPS has no internal short before  LED and 5    continuously EN     3  deo circuited turn on it again  If failed  please             contact the distributor or service center       27       7 Troubleshooting       Problem          LED display Alarm Possible cause Solution  The 1  fault     Beep  LED is on  2  The 10  once The charger of the   Please contact the distributor or  battery LED every UPS is defective Service center  is blinks second       The 8  utility  power LED  blinks in  normal mode       Maybe reversed  polarity  L N  of site  wiring or disconnect    with ground  or the  voltage between  neutral wiring to    protective ground is  to high    Please check the polarity of the  neutral wiring and the line wiring   ensure that The gree
20. ervice center  Turn off the UPS  Remove  The UPS all loads  Ensure that the  B puti loads are not failed or the  F04 on ae ae S UPS has no internal short  constantly   continuously short       ircuited before turn on it again  If  adus failed  please contact the  distributor or service center  on Beep Internal Please contact the  F05 3 E    constantly   continuously fault  distributor or Service center  on Beep Internal Please contact the  F06 4 D    constantly   continuously fault  distributor or Service center  F07 on Beep Overload   Reduce the member of loads  constantly   continuously fault connected to the UPS   Ensure that the UPS is not  overloaded and the  ventilation opening is not  blocked and ambient  F08 on Beep Internal temperature is not too high   constantly   continuously   overheat Wait for 10 minutes for the  UPS to cool down before  turning it on again  If it does  not work  Please contact the  distributor or service center   on Beep The charger Please contact the  F09   ofthe UPS      constantly   continuously       distributor or Service center  is defective  Blink once   Beep once Overload   Reduce the member of loads  A01    every   every second   pre warning connected to the UPS              29                second                7 Troubleshooting                            Faults  Fault Warning Fault icon Alarm Possible cause Solution  code  Blink once The UPS output will be  Beep once Battery voltage    A02 every d EM M Om iom cut off  please switch
21. ity power  indicator blinks at the same time  it shows that the utility power is abnormal  The  load battery capacity indicators will be turned on in accordance with the battery  capacity  Please note that the load battery capacity indicator in normal mode will  indicate the battery capacity in battery mode     4 Operation  LED model       1  When the UPS is running in battery mode  the alarm will beep every 4 seconds   If the    Function    key is pressed for more than 2 seconds  the alarm will not beep   silence function   Press the    Function    key more than 2 seconds again to  resume the alarm function     mm mg SHE HS   O    C8  o                              Figure 4 3 Battery Mode    2  When the battery capacity decreases  the number of load battery capacity  indicators turned on will decrease  If the battery voltage drops to the pre alarm  level  the alarm will beep every second to remind the user of insufficient  battery capacity     4 2 3 Bypass mode   When operating in bypass mode set up through UPSilon software  the display on   the front panel is show in the following diagram  The utility power indicator and   the bypass indicator are turn on  The load battery capacity indicator will be turned  on in accordance with the load capacity connected    1  If the utility power indicator blinks  it shows that the voltage or frequency of the  utility power is out of the input range of the UPS or there are problems with  reversed polarity  L N  of site wiring or disconne
22. lligent Slot    Connect Worknet    Output    External  Battery Connector       Input       Figure 2 1 The rear panel of HT111K  L        A    Computer Interface H    Ee Intelligent Slot    Gua       Connect Worknet    Output    External    Battery Connector Input          Figure 2 2 The rear panel of HT112K  L    HTI 13K  L       The picture for back panel is just for reference  it subjects to change on  customer s requirement  please refer to the real subject     3    Note  The appearances above are examples with the long backup time  the  corresponding standard type is without the    External Battery slot      2 Product Description       2  3 Operating Principle             AC DC    Input filter  converter    ato  DCIAC Output filter  inverter              DC DC  sd converter    Figure 2 3 The UPS operating principle           Input filter  it filters the input and provides clean AC power to the UPS      AC DC converter  In Normal mode  it converts the AC input power to regulated  DC power  and raises the regulated DC voltage for DC AC converter      DC DC converter  Raises the DC Voltage from the battery system to the  optimum operating voltage for the inverter when the UPS operates in Battery  mode    4  DC AC inverter  In Normal mode  it utilizes the DC output of the AC DC  converter and inverts it into precise  regulated sine wave AC power  In Battery  mode  it receives energy from the battery through the DC DC converter      Bypass  It is very important in the UPS syst
23. main voltage is within the specifications  the UPS should operate in  normal mode  if the main voltage is abnormal  the UPS should operate in battery  mode  In both cases  there should be no fault indication       Check the transfer between the UPS operation modes    Disconnect the main input to simulate a mains failure  the UPS should transfer  to battery mode and operate normally  then recover the mains input  the UPS  should transfer to normal mode and operate normally      Check the LED indicators of the UPS    During the check processes stated above  check that the LED indication of the  UPS agrees with the UPS operation mode     26    7 Troubleshooting    In the event of an UPS fault  shoot the trouble according to Table 7 1 or Table 7 2   If the fault still persists  please contact our customer service center                                   Problem Possible Solution  LED display Alarm cause  Ensure that the UPS is not overloaded  and the ventilation opening is not  The 1  Fault blocked and ambient temperature is  Beep Internal not too high  Wait for 10 minutes for  LED and 6    E  continuously overheat the UPS to cool down before turning it  LED are on      on again  If it does not work  Please  contact the distributor or service  center   Thel  Fault ae  LED and 5  Beep Internal fault  Please contact the distributor or  continuously Service center  LED are on  The 1  Fault       LED and 4  Beep Internal fault Please contact the distributor or  continuously Service c
24. model               NH O          CS J  O eo    Figure 4 2 Normal Mode       2  If output overloaded  the load level indicators will be turned on and alarm will  beep every second  You should get rid of some unnecessary loads one by one to  decrease the loads connected to the UPS less than 10096 capacity of the UPS     11        0S       If the battery indicator blinks  it indicates that no battery is connected to the UPS  or battery voltage is too low  You should check if battery is properly connected  to the UPS  and press function button more than 2 seconds to start the battery  self diagnosis  If the connection between battery and UPS is confirmed without  any problem  it may be due to the defect or aging of the battery  please refer to  the    troubleshooting    in chapter 7 to solve the problem accordingly     Note  Connection to the power generator should be made according to the  following steps        Activate the power generator and wait until the operation is stable before  connecting the output of the power generator to the UPS  be sure that the  UPS is in idle mode   Then  turn on the UPS according to the startup  procedure  After the UPS is turned on  the loads are connected one by one        It recommended that the capacity of the AC generator chosen should double  that of the UPS     4 2 2 Battery mode   In battery mode the display on the front panel is shown in the following diagram   The battery indicator and the inverter indicator are turned on  If the util
25. n yellow wire  connect protective ground  properly  or make sure the voltage  between neutral wiring to  protective ground is less than  36VAC       The battery has not    Keep the UPS connected to utility  power persistently for more than                   been fully charged   10 hours to charge the battery  again  The battery discharge The UPS Check the load status and remove  time diminishes overloaded the non critical device  Replace the batteries  Please  Battery aged contact the distributor to obtain  the replacement components for  battery  The power on key is Press the power on key    persistently for more than 1  pressed too briefly  second  The UPS cannot power The DES ane Check the connection of the    on after pressing  power on key    the    connect to battery  or the battery  voltage is too low    battery  Turn on the UPS without  load if the battery voltage is low       Internal fault       Please contact the distributor or  Service center          Table 7 1 UPS troubleshooting of LED panel indicator    28       7 Troubleshooting       Faults                                              Fault Warning   Possible Solution  Fault icon Alarm cause  code  on Beep Internal Please contact the  F01   DM    constantly   continuously fault  distributor or Service center  F02 on Beep Internal Please contact the  constantly   continuously fault  distributor or Service center  on Beep Internal Please contact the  F03   AT    constantly   continuously fault  distributor or S
26. normal mode  the display of main page on the front panel is  shown as the figure 5 2  The utility power indicator and the Inverter indicator are  turned on  Load information area shows load value  and the battery level area  indicates dynamically when the battery is not fully charged  the battery level icons  lit one after another circularly   When the battery is fully charged  all the level  icons are turned on     1  If the utility power indicator blinks  it indicates that there are problems with  reversed polarity  L  N  of site wiring or disconnect with ground  UPS is still  working in normal mode  If the battery indicator is turned on at the same time  it  shows that the voltage or frequency of the utility power is out of the normal  input range of the UPS  The UPS works in battery mode     ecu Suu     OUTPUT    GET        Figure 5 2 Normal Mode          2  If load is more than 100 percent  the buzzer beeps every second  meanwhile  the  20    warning icon blinks every second too  reminding that UPS is overloaded     5 Operation  LCD model     You should get rid of some unnecessary loads one by one to decrease the loads  until the alarm clear    3  If the battery indicator blinks  it indicates that no battery is connected to the UPS  or battery voltage is too low  You should check if battery is properly connected  to the UPS  and press function button more than 2 seconds to start the battery  self diagnosis  If the connection between battery and UPS is confirmed without  
27. on   Pressing the ON button more than 1 second  the UPS system is turned on     2  OFF button   By pressing this button more than 1 second turns off the UPS system whenever the    9    UPS run under the normal mode battery mode     3  Function button   The Function button provides the following functions    1  Battery self  diagnosis  When the UPS ran in normal mode  pressing this button  more than 2 seconds  buzzer beeps twice  can start the battery self diagnosis    2  Silence function in battery bypass mode  In battery bypass mode  when the buzzer beeps  pressing and holding the  function button for more than 2 seconds  buzzer beeps two times  can silence  the buzzer  Press the button for more than 2 seconds  buzzer beeps twice  again  to resume the alarm function    Note  The alarm silencing function of the Function button is valid only in battery  mode  and invalid for any other UPS alarm     4  LED indicators  The LEDs contains Fault indicator  Load battery capacity indicator  Bypass  indicator  utility power indicator  Inverter indicator  Battery indicator     4 Operation  LED model     Table 4 1 Description of indicators       No    Color Indicator Description       ae When the indicator on  it shows that  i Red Faulvindicaine the UPS in abnormal condition        2    Orange   Load battery capacity indicator   Show the capacity of load battery        3  Green   Load battery capacity indicator   1 Indicate the percentage of the load                4    Green   Load bat
28. rn on  If the utility power is abnormal  the UPS will work in battery mode     2  Turning on without utility power   With no mains input feeding to the UPS  press the ON button more than one  second  ups start to turn on  In the power on process  the UPS has the same  operation as if it is connected to utility power except that the utility power  indicator is not turned on and the battery indicator is turned on instead     4 Operation  LED model     2  Powering down the UPS    The operation of powering down the UPS contains  turning off ups in normal mode   turning off ups in battery mode    1  Completely power down the UPS from Normal mode  Hold and press the OFF button persistently for more than 1 second to power off  the UPS  If it bas been set up to work in bypass mode by software  the bypass  indicator will be turn on to indicate that the UPS is working in bypass mode  In  order to cut off the output from the UPS  simply cut off the utility power supply   Finally  not any display is shown on the front panel and no output is available  from the UPS outlets  system completely power down    2  Completely power down the UPS from Battery mode  Press the    ON OFF    button persistently for more than 1 second to power off the  UPS  When being powered off  the UPS will start self diagnosis and all the    14    load battery capacity indicators will be turn on and off one after another  Finally   not any display is shown on the front panel and no voltage output is available  from
29. s are turned  on about 4 seconds  a few seconds later  not any display is shown on the front  panel and no output is available from the UPS outlets  system completely power  down     2  Completely power down the UPS from Battery mode    Press the  OFF  button persistently for more than 1 second to power off the UPS   When being powered off  the LCD will start self diagnosis  all the LCD  indicators are turn on about 4 seconds   a few seconds later  not any display is  shown on the front panel and no voltage output is available from the UPS outlets   system completely power down     5 3 2 Conducting Battery self diagnosis    In UPS operation  users can manually initiate battery self diagnosis to check the  battery conditions  There are two methods to initiate the battery self diagnosis             N      Through the function button    In normal mode  press and hold the function for more than 2 seconds until the  buzzer beeps twice  At this point the indicators  LED7 10  will blink cyclically   indicating the UPS has worked in battery mode and the battery self diagnosis  has started  The battery self diagnosis will last for 10 seconds default  In the  event of a battery fault during battery self diagnosis  the UPS will transfer to  normal mode automatically       Through the monitor software    Users can also initiate battery self diagnosis through the background monitoring  software     25    6 Maintenance    6 1 Battery Maintenance    The battery is key component of the UPS  
30. s shown in the following diagram        Figure 3 2 Connection method of output    3 Installation    3 3 2 Operation Procedure of External Battery for Long Backup Time UPS   The battery connection procedure is very important for long backup model  Any  incompliance may result in the risk of electric shock  Therefore  the following  steps must be strictly complied with          U      First connect in series the batteries of the pack to ensure proper battery voltage    that HT111KL for 36VDC  HT112KL for 72VDC  or 96VDC   HT113KL for  96VDC  or 72VDC     Take out the battery cable delivered with the UPS  one end of the external  battery cable is a plug for connecting the UPS  the other end has 3 open wires  for connecting the battery pack       Connect the external battery cable to the battery terminal  DO NOT connect the    battery socket of the UPS first  Otherwise  it may cause electric shock   Connect  the red wire to the         terminal of the battery  The black wire is connected to the      terminal of the battery  The green yellow wire is grounded for protection  purpose    Connect the plug of the external battery cable to the external battery slot on the  rear panel of the UPS to complete the connection procedure        BATTERY    Figure 3 3 Battery connection diagram for Long Backup time models    Note  The length of the external battery cable is 1 6 m  If users need a longer one   please consult the distributor  There is a limit to the length of the external  battery
31. tery capacity indicator capacity in normal mode and bypass   5  Green   Load battery capacity indicator mode       6  Green   Load battery capacity indicator n bc d S capacity levelin  When the indicator on  it shows that   7    Orange Bypass indicator the loading current is supplied from the  utility power directly       When the indicator on  it shows that    8  Green Utility power indicator the utility power is normal           When the indicator on  it shows that  9    Green Inverter indicator the load current is supplied from utility  power or battery via the inverter                 10             When the indicator on  it shows that  10    Orange Battery indicator the load current is supplied from  battery via the inverter                 4 2 Operation Mode    4 2 1 Normal mode   In the normal mode  the display on the front panel is shown in the following  diagram  The utility power indicator and the Inverter indicator are turned on    The load battery capacity indicator will be turned on in accordance with the load  capacity connected     1  If the utility power indicator blinks  it indicates that there are problems with  reversed polarity  L  N  of site wiring or disconnect with ground that may result  in shock hazard  UPS is still working in normal mode  If the battery indicator is  turned on at the same time  it shows that the voltage or frequency of the utility  power is out of the normal input range of the UPS  The UPS works in battery  mode     4 Operation  LED 
32. voltage of charger R R  m Sustained  output beep  20 Output short circuit ee e n Sustained  beep  21 Overload fault ee e tT a  eep  22 Battery voltage abnormal   t  t  tT   T  tT  e T    1  Reversed polarity  L  N  Beep once  did of input wiring or TITI TATI  every 2 min        17             disconnected with ground           Beep once  24 Charger or battery fault e   e  25 Fan failure e e e 1 titi t ci                                              LED indictor description  e  On       Flash 1  Depending on other conditions       18       5 Operation  LCD model   5 1 Operation Display Panel    Unit display area    Data information area    Current status display    Alarm Fault indicator    Battery Level indicator 100   Battery Level indicator Da    E  oad Level indicator 100   Load Level indicator 75   Battery Level indicator 50  E  oad Level indicator 50   Battery Level indicator 25  Load Level indicator 25              8 Untility indicator NK 9  Inverter indicator  10  Battery indicator    7 Bypass indicator    POWE RON         on                3 unction    POWER OFF                      1  ON button   Pressing the ON button more than 1 second  buzzer beeps once   the UPS system is  turned on     2  OFF button   By pressing this button more than 1 second  buzzer beeps once  turns off the UPS  system whenever the UPS run under the normal mode battery mode     3  Function button   The Function button provides the following functions    a  Battery self  diagnosis  When the UPS
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Tripp Lite 3 Breaker Maintenance Bypass Panel for SU20K3/3, SU20K3/3XR5, SU20K3/3X and SU20KX UPS  1 Chapter 1 Introduction  Manual LEAHUA  The Red Pill The Red Pill  Multiquip mtr-40hs User's Manual  3. Using the USB 2-to-2 Share Switch Station  熟語筆記回答対戦ソフトウェア Ver.1.0 取扱説明書  Untitled  HQ RC UNI/AIRCO2 remote control  M-Cab 1m eSATA Extension    Copyright © All rights reserved. 