IEC 60870-5-103 Master (OPC) User`s Manual

image

Contents

1. Name Value or Value range Default Description Receiver Interrupt 0 255 Delay of the receiving activation in milli Delay seconds Default 0 Response Timeout 0 65535 Maximum waiting time of a link layer response in seconds Default 2 RTS Keep Up 0 255 RTS keep up padding characters Default 0 RTS Keep Up Delay 0 20 Keep up delay of the RTS Default 1 Time Synchroniza 0 65535 Time synchronization interval in seconds tion Interval Default 15 Transmission Wait 0 65535 Transmission wait delay after given CTS Delay in milliseconds Default 0 Enquiry Limit 0 255 Number of times that a message is retransmitted Default 3 One link one station True One link one station poll If true master poll infinitely polls the first link which responds False typically used with dial up If false all the links are polled normally Default False Polling Delay 0 65535 Delay between polling messages in milli seconds Default 50 Polling Limit 2 100 Limits the number of successive polls of a device Default 10 Polling Period 1 255 The polling frequence of a suspended station Default 10 Reply Poll Count 1 20 The reply polling specifies the number of successive polls to a station where a Default 10 command has been sent Secondary Polling 0 100 Limits the number of successive class 2 Limit polls of a device The value must be Default 0 smaller than the value of Polling Lmit 1MRS752278
2. lt 51 gt Earth fault forward i e line lt 52 gt Earth fault reverse e busbar Fault indications in monitor direction lt 64 gt Start pick up L lt 65 gt Start pick up L2 lt 66 gt Start pick up L lt 67 gt Start pick up N lt 68 gt General trip lt 69 gt Trip L lt 70 gt Trip L lt 71 gt Trip Ls lt 72 gt Trip 1 gt gt backup operation lt 73 gt Fault location X in ohms lt 74 gt Fault forward line lt 75 gt Fault reverse busbar lt 76 gt Teleprotection signal transmitted lt 77 gt Teleprotection signal received lt 78 gt Zone 1 lt 79 gt Zone 2 lt 80 gt Zone 3 lt 81 gt Zone 4 lt 82 gt Zone 5 lt 83 gt Zone 6 lt 84 gt General start pick up 55 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 1MRS752278 lt 85 gt Breaker failure lt 86 gt Trip measuring system L lt 87 gt Trip measuring system L lt 88 gt Trip measuring system L lt 89 gt Trip measuring system E lt 90 gt Trip I gt lt 91 gt Trip I gt gt lt 92 gt Trip IN gt lt 93 gt Trip IN gt gt Auto reclosure indications in monitor direction R lt 128 gt CB on by AR a lt 129 gt CB on by long time AR lt 130 gt AR blocked Measurands in monitor direction lt 144 gt Measurand lt 145 gt Measurands V lt 146 gt Measurands I V P Q lt 147 gt Measurands la Ven lt 148 gt Measurands lza Visa P Q f Generic f
3. A Each IEC103 physical device must have at least one Logical Device object as a child object Adding Logical Node objects To add a Logical Node 1 Select a Logical Device object and right click it 2 Adda Logical Node object 3 Rename the new object The names of the Logical Node objects have to be unique A You should have only one Logical Node 0 LLNO as a child object to a Logical Device object Adding data objects To add a data object 1 Select a Logical Node object and right click it 2 Add a data object 3 Rename the new object The names of the data objects have to be unique Configuring objects General about configuring objects After the objects have been added configure the object properties Figure 3 4 1 1 shows an example of how to use SAB600 to configure the object properties for IEC103 Device To configure an object 1 Select an object in the object tree of the communication structure e The object properties appear now in the Object Properties window The proper ties and their values can be viewed as shown in Figure 3 4 1 1 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 1MRS752278 3 4 2 20 2 Object Properties v AX 5 21 E 010 Basic Diagnostics Enabled False In Use In Use Simulation Mode False El 020 Addresses Polling Address 1 Station Address 1 030 Communication Control Complete Event Time Tag From Inte
4. Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 4 4 Configuring IEC103 Device properties Table 3 4 4 1 lists the value ranges and or default values for the IEC103 Device properties that you can define The actual configuration by using SAB600 is performed as described in 3 4 1 General about configuring objects Table 3 4 4 1 IEC103 Device properties Name Basic Diagnostics Enabled In Use Simulation Mode Addresses Polling Address Station Address Communication Control Complete Event Time Tag From Internal Clock Confirmation Timeout Prevents Auto matic Sending of General Interroga tion Reply Timeout Value or Value range Default True False Default False In Use Not In Use Default In Use True False Default False 0 255 Default 1 0 255 Default 1 True False Default True 0 255 Default 60 True False Default True 0 255 Default 10 Description Specifies whether diagnostic AE events are sent for the device Controls whether the device communication is initially in use or not Specifies whether the device is in simulation mode or not Station polling address Common address of ASDU Completion of event time tag by adding year date and hour If true event time tags are completed based on the internal clock of the master If false time tags are completed based on cl
5. ss eee eee e 47 Complex measured value CMV sese sese ee eree ereenn 45 Controllable single point SPC rrie arasta Eaa EPEAREN EET RAINA EERE 46 Delta DEL ancaran a aa rado 46 Device name plate DPEN oa ein nanena ENE TEE AE R 44 Double point status DPS oiei ienai a A a ANRT 43 Integer status INS Jerri arar RE E AEE RE 43 Logical node name plate LPL orori ar a TEE RE 44 Measured Value MV oire eerren iniciada dida KEENE STREN RETE RRAN 45 Protection activation information ACD see eee 44 Protection activation information ACT eee eee 43 Single point status SP Sua 42 WY O eit E A ET 46 Integer status INS 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual DOBER Aa td 25 L Logical Device object AO ita date 19 Logical node A O 19 Logical node name plate LPL EC 61850 da ta modeling nior Larada td 44 properties mosg en A i Aa TT 29 Measured value MV IEC 61850 data modeling cies segs hae oa ghee dea cinco dana tag dade eas dad pa ed 45 properties tai bead egal lt cda ena lee beg ee ee eet 30 O object CONRO ias 19 object tree O 17 OPC Server TOMES A aaah ieee a ae ae 14 01a els nile cs pitches Msi EE nideteteditacind E iidatedd sabato Hetil eedcaidened idasedtaat 20 OPC Server object A ii A A darned nee viens ee de a eet 18 P properties Binary controlled step position information BSC ss eee eee ee 36 STT A A A A sesh A E E ceases 21 Complex measu
6. 1 Server attributes Name Value or Value range Default Description Protocol stack ver Value Version information Data type Text sion Access Read only Version information of the protocol stack Reset The Reset button for resetting the OPC Server File version File version of the executable OPC Server Product version Version information of the installed OPC Server 48 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 5 3 3 1EC103 Channel attributes Table 5 3 3 1 IEC103 channel attributes Name Value or Value range Default Description In use 0 Not in use the channel Data type Integer communication is stopped Access No limitations 1 In use The state of the channel whether it is in Default 1 use or not When a channel is not in use no data can be transmitted on it and no data is received from it The channel attributes can be read as usual Generally a channel must be taken out of use by setting this attribute to O before the chan nel attributes can be written When a channel is stopped by setting the IU attribute 0 all data transmission on the channel ceases However before that the protocol stack executes to the end all on going data transactions For example the polling of the station in turn is completed Modem signal Data type Integer Access Read only Clear To Send 0 Passive signal Indicates the sta
7. 21 3 4 4 Configuring IEC103 Device properties 65 23 3 4 5 Data objects for status information see eee 24 3 4 5 1 General about data objects for status information coocccocccoconaccnooonnnnnn ono nono nn non nnnnnnnns 24 3 4 5 2 Single point status SDS eee 24 3 4 5 3 Double point status DPS ee 25 3 4 5 4 Integer status INS eee eee 25 3 4 5 5 Protection activation information ACT 26 3 4 5 6 Directional protection activation information AD ri ida caida 27 3 4 5 7 Device name plate DPL eee 28 3 4 5 8 Logical node name plate LPL 29 3 4 6 Data objects for measurand information 5 30 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 6 1 General about data objects for measurand information coocococcccccccononononn nono nono nono non nnnnnnnns 30 3 4 6 2 Measured value WV sese 30 3 4 6 3 Complex measured value CMV 30 3 4 6 4 UU Eos Serra AT AE AA 31 3 4 6 5 Delta DEL oa tard 32 3 4 7 Data objects for controllable status information 33 3 4 7 1 General about data objects for controllable status information eee eee eee 33 3 4 7 2 Controllable single point SPC 34 3 4 7 3 Controllable double point DPC 35 3 4 7 4 Binary controlled step position information BOG E is 36 A 38 4 1 Aboutthis SECTION rsono eaa E
8. E One COMMON ADDRESS OF ASDU identical with station address O More than one COMMON ADDRESS OF ASDU Selection of standard information numbers in monitor direction System functions in monitor direction a lt 0 gt End of general interrogation lt 0 gt Time synchronisation lt 2 gt Reset FCB lt 3 gt Reset CU lt 4 gt Start restart AE EA EB B E lt 5 gt Power on Status indications in monitor direction lt 16 gt Auto recloser active lt 17 gt Teleprotection active lt 18 gt Protection active lt 19 gt LED reset lt 20 gt Monitor direction blocked lt 21 gt Test mode lt 22 gt Local parameter setting lt 23 gt Characteristic 1 lt 24 gt Characteristic 2 lt 25 gt Characteristic 3 lt 26 gt Characteristic 4 lt 27 gt Auxiliary input 1 lt 28 gt Auxiliary input 2 lt 29 gt Auxiliary input 3 lt 30 gt Auxiliary input 4 Supervision indications in monitor direction a lt 32 gt Measurand supervision E lt 33 gt Measurand supervision V 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual lt 35 gt Phase sequence supervision lt 36 gt Trip circuit supervision lt 37 gt gt gt backup operation lt 38 gt VT fuse failure lt 39 gt Teleprotection disturbed lt 46 gt Group warning lt 47 gt Group alarm Earth fault indications in monitor direction lt 48 gt Earth fault L lt 49 gt Earth fault L lt 50 gt Earth fault L
9. Master OPC User s Manual Name Type Description Protocol informa OPC data types tion element Value Value Mandatory range Optional Text O VT_BSTR 5 2 2 2 Name stVal Double point status DPS DPS represents ASDUs 1 and 2 Table 5 2 2 2 1 Double point status DPS information Type Value Value Mandatory Protocol informa OPC data types range Optional tion element Intermediate state VT Id 0 off 1 on 2 bad state 3 TimeStamp Full_ Timestamp ore VT_DATE Description Text VT_BSTR 5 2 2 3 Integer status INS INS represents ASDUs 3 4 and 9 Table 5 2 2 3 1 Integer status INS information Name Type Description TimeStamp Mandat Protocol informa OPC data types tion element Value Value range ory Optional ity Text O VT_BSTR 5 2 2 4 Protection activation information ACT ACT represents ASDUs 1 and 2 43 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual Table 5 2 2 4 1 Proptection activation information ACT Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element general BOOLEAN AN cee DPI 1 OFF 2 0N VT_BOOL phsA BOOLEAN I IT DPI 1 0FF 2 0N VT_BOOL phsB BOOLEAN e E DPI 1 OFF 2 0N VT_BOOL phsC BOOLEAN i 4 sor DPI 1 0FF 2 0N VT_BOOL neut BOOLEAN E AE aa DPI 1 0FF 2 0N VT_B
10. in a message received from the IEC103 channel Checksum errors Incremented each time a framing error is detected in a message received from the Framing errors 1EC103 channel Buffer overflow Incremented each time a buffer overflow errors occurs in the IEC103 channel 1EC103 Device attributes Table 5 3 4 1 IEC103 Device attributes Name Value or Value range Default Description In use 0 Out of use Data type Integer 1 In use Access No limitations Default 1 The operational status of the device in use or out of use Taking the device out of use with this attribute stops all data communication with the device All opera tions that would result in data exchange are disabled The device itself is not affected by the attribute only the protocol stack s image of the device Setting IU to 1 is allowed only if the device address is legal 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 5 4 Name Value or Value range Default Description Object status 1 Re transmit system mes Data type Integer sage Access No limitations A status code for example Indicates the detailed information about 0 OK communication works the station device status Writing to the properly OS attribute OS 1 of a device makes the protocol stack to re transmit the last 13863 Device suspended system message caused by the device Possible Stopped and
11. in the Courier font For example if you enter a value out of range the following message is displayed 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 1 5 1 6 Entered value is not valid The value must be 0 30 e YOU can be asked to enter the string MIF349 in a field The string is shown as follows in the procedure MIF349 e Variables are shown using lowercase letters sequence name Use of symbols This publication includes warning caution and information icons that point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The corresponding icons should be interpreted as follows T The electrical warning icon indicates the presence of a hazard which could result in electrical shock T The warning icon indicates the presence of a hazard which could result in personal injury The caution icon indicates important information or warning O related to the concept discussed in the text It may indicate the presence of a hazard which could result in corruption of software or damage to equipment or property A The information icon alerts the reader to relevant facts and conditions RT The tip icon indicates advice on for example how to design your project or how to use a certain function Terminology Term Description Alarm An abnormal state of a condition Gr
12. right click the desired object and select SCL Import For more information about the SCL Import function see COM600 User s Manual Connectivity Packages for certain protection and control devices can also support other ways to build this structure depending on the configuration of an individual device for example device related object types and wizards Typically Connectivity Packages include SCL description files which must be installed For further information on these Connectivity Packages see the Connectivity Package of a certain device in the product documentation Adding IEC103 Channel objects To add an IEC103 Channel object 1 Select an IEC103 OPC Server object and right click it 2 Add an IEC103 Channel object 3 Rename the new object The names of the IEC103 Channels have to be unique Adding IEC103 Device objects To add an IEC103 Device object 1 Select an IEC103 Channel object and right click it 2 Add an IEC103 Device object 3 Rename the new object The names of the IEC103 Devices within an IEC103 OPC Server have to be unique 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 3 6 3 3 7 3 3 8 3 4 3 4 1 Adding Logical Device objects To add a Logical Device object 1 Select an IEC103 Device object and right click it 2 Adda Logical Device object 3 Rename the new object The names of the Logical Device objects have to be unique
13. type for phase B Type Default 160 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Property Para Value or Value range Default Description meter Phase B Information 0 255 1EC103 information number for phase B Number Default 144 Phase C Addresses Phase C Function 0 255 IEC103 function type for phase C Type Default 160 Phase C Information 0 255 IEC103 information number for phase C Number Default 144 Neutral Function 0 255 IEC103 function type for neutral Type Default 160 Neutral Information 0 255 IEC103 information number for neutral Number Default 144 3 4 5 6 Directional protection activation information ACD Table 3 4 5 6 1 Configurable ACD properties for OPC servers Property Para Value or Value range Default Description meter Common Data ACD Common data class according to IEC Class 61850 General Function Type IEC103 function type for general Default 160 General Information 0 255 IEC103 information number for general Number Default 144 Phase A Addresses Phase A Function 0 255 IEC103 function type for phase A Type Default 160 Phase A Information 0 255 IEC103 information number for phase A Number Default 144 27 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 5 7 28 Property Para Value or Val
14. 1 General about configuring objects 3 4 6 2 Measured value MV Table 3 4 6 2 1 Configurable MV properties for OPC servers Property Para Value or Value range Default Description meter Common Data MV Common data class according to IEC Class 61850 Indication Function 0 255 1EC103 indication function type Type Default 101 Indication Index 1 255 IEC103 indication index Default 1 Indication Informa 0 255 IEC103 indication information number tion Number Default 105 Scale Default None Scale to be used with this data object 3 4 6 3 Complex measured value CMV Table 3 4 6 3 1 Configurable CMV properties for OPC servers Property Para Value or Value range Default Description meter Basic 30 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 4 6 4 Property Para Value or Value range Default Description meter Common Data CMV Common data class according to IEC Class 61850 Indication Function 0 255 IEC103 indication function type Type Default 101 Indication Index 1 255 1EC103 indication index Default 1 Indication Informa 0 255 1EC103 indication information number tion Number Default 105 Scale Default None Scale to be used with this data object WYE Table 3 4 6 4 1 Configurable WYE properties for OPC servers Property Para Value or Value range Default Description meter Com
15. 1 Configurable DEL properties for OPC servers Property Para Value or Value range Default Description meter Basic Common Data Class Common data class according to IEC 61850 Phase AB Addresses 32 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Property Para Value or Value range Default Description meter Phase AB Function 0 255 IEC103 function type for phase AB Type Default 160 Phase AB Index 1 255 IEC103 index for phase AB Default 1 Phase AB Informa 0 255 IEC103 information number for phase AB tion Number Default 144 Phase BC Addresses Phase BC Function 0 255 IEC103 function type for phase BC Type Default 160 Phase BC Index 1 255 IEC103 index for phase BC Default 2 Phase BC Informa 0 255 IEC103 information number for phase BC tion Number Default 144 Phase CA Addresses Phase CA Function 0 255 IEC103 function type for phase CA Type Default 160 Phase CA Index 1 255 IEC103 index for phase CA Default 3 Phase CA Informa 0 255 IEC 103 information number for phase CA tion Number Default 144 Phase Scale Default None Scale to be used with phases with this data object 3 4 7 Data objects for controllable status information 3 4 7 1 General about data objects for controllable status information There are three different data objects providing controllable status information e 3 4 7 2 Controll
16. 2 12 30 03 625 Unmapped Address Update Channel 11M002_AEF 54361 16777471 0 L gt Figure 4 3 3 IEC103 OPC Server Diagnostic AE client IEC103_OPC_Server_Diagnostic_AE_client jpg 39 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 4 4 4 5 40 Monitoring and controlling IEC103 Channel Activity The IEC103 Channel activity can be monitored with the Online diagnostics function You can also take a channel into use or out of use as described in this section To monitor and control IEC103 Channel activity 1 Select the channel you want to monitor in the object tree of SAB600 2 Right click the channel 3 Select Online diagnostics In the Diagnostic counters field you can monitor the channel activity To reset Diagnostic counters click Reset counters You can take an IEC103 Channel into use by marking the In use check box If you unmark the check box the channel is taken out of use Diagnostic counters are updated every 2 seconds To update them manually click Refresh For more information on the channel online diagnostics with the Analyzer function see COM600 User s manual Monitoring and controlling IEC103 Device communication The IEC103 device communication can be monitored with the Online diagnostics function You can also take a device or module into use or out of use as described in this section To monitor and control IEC103 Device communication 1 Select the
17. BEP 4351 OK 05 2004 06 22 12 38 08 203 Device Connection Status Channel 11H002_REF 43_S1Devwce Connection Status Connection OK 2004 06 22 12 36 08 343 Urmapped Address Update Channel 11H002_REF 543_51 672 0003 ODABSRELAYO gt 0 2004 06 22 12 30008 403 Unmapped Address Update Channel 11H002_AEF S43_St 1184 0003 ODABERELAYO D gt 2004 06 22 12 38 08 453 Urmapped Address Update Channel EEZ REF 543_51 255 2004 06 22 12 38 03 553 Urmapped Address Update Channel 11H002_REF 543_51 21668 z 2004 06 22 12 90 08 663 Unmapped Address Update Channel 11002 AEF S43 51 24740 2 2004 06 22 12 38 08 723 Urmapped Address Update Channel 11H002_REF 543_51 21672 2 2004 06 22 12 36 08 773 Urmapped Adkbess Update Channel 11H002_REF 543_51 21675 2 2004 06 22 12 30 00 823 Urmapped Address Update Channel 11H002 AEF 543 51 24235 2 2004 06 22 12 38 03 374 Urmapped Address Update Channel Z REF 543_51 21675 2 2004 06 22 12 38 08 924 Urmapped Address Update Channel 11H002_REF 543_51 24236 2 2004 06 22 12 38 09 324 Urmapped Address Update Channel tyH002 REF S43 St 23293 2 2004 06 22 12 56 09 374 Urmapped Address Update Channel t H002_PEF 543_51 23549 Z 2004 06 22 12 38 03 424 Unmapped Address Update Channel 11H002_REF 543 51 23805 2 2004 06 22 12 30 03 474 Unmapped Address Update Channel 11M002_AEF 543_51 24061 2 2004 06 22 12 36 09 524 Urmapped Address Update Channel 1 HO02_REF 543_51 79317 Z 2004 06 22 12 38 09 575 Urmepped Address Update Channel 11H002_REF 543 51 24573 2 2004 06 2
18. C103 indication information number tion Number Default 105 Binary controlled step position information BSC Table 3 4 7 4 1 Controllable BSC properties for OPC servers Property Para Value or Value range Default Description meter Common Data BSC Common data class according to IEC Class 61850 Subtype of the current data object Same com mand and indica tion addresses Addresses Command ASDU 0 255 IEC103 command ASDU type Type Default 20 Command Function 0 255 IEC103 command function type Type Default 101 Command Informa 0 255 1EC103 command information number tion Number Default 105 Scale and Unit Scale Default None Scale to be used with this data object Subtype of the current data object Separate command and indication addresses Addresses Command ASDU 0 255 IEC103 command ASDU type Type Default 20 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Property Para Value or Value range Default Description meter Command Function 0 255 IEC103 command function type Type Default 101 Command Informa 0 255 IEC103 command information number tion Number Default 105 Indication Function 0 255 IEC 103 indication function type Type Default 101 Indication Index 1 255 IEC103 indication index Default 1 Indication Informa 0 255 IEC103 indication information number tion Number
19. Click Refresh to update the status information To be able to receive events from a certain device diagnostic events must be enabled for this respective device To enable diagnostic events 1 Right click the device 2 Select Online diagnostics 3 Mark the Diagnostic events enabled check box See Figure 4 3 3 for example Evert courts 30 NR y AS H aE Message Address Value ameh 2004 06 22 12 37 29 166 System Message Channel M003 AEF S43 62 ox 0 2004 06 22 12 37 29 166 Device Connection Status Channel 11H003_REF S43_S7 Device Connection Status Conrection OK Settings 2004 06 22 12 37 30 549 System Message Channel 11K010_REX 521 79 x 0 2004 06 22 12 37 30 849 Device Connection Status Channel 11K010_REx 21_79Device Connection Status Connection OK Chose 2004 06 22 12 37 32 631 System Message Channel 11R001_REM 610_60 ox 0 E J Device Connection Status Channel t R001_REM 610 _60Devke Connection Status Connection OK L073 System Message Channel t H002_PEF 543_51 Ok 0 tt 2004 06 22 12 37 34 073 Device Connection Status Channel 11H002_REF S43_5t Davice Connection Status Connection OK 2004 06 22 12 36 06 650 System Message Channel 1H002_AEF S43_St ICE DEV T Active 2004 06 22 12 38 06 650 Device Connection Status Channel GRIZ REF 43_S Dewice Connection Satus Device Con 2004 06 22 12 58 07 782 System Message Channel RZ BEP 543_51 ICCC DEVI tato gerol 2004 06 22 12 38 00 203 System Message Channel OERZ
20. Default 105 Scale Default None Scale to be used with this data object 37 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 4 1 4 2 4 3 38 Operation About this section This section describes the basic operation procedures you can carry out after the IEC103 OPC Server has been configured After this you can for example monitor and control the condition of connections in an IEC103 network This is done by using the Online diagnostics function in SAB600 Activating COM600 with new configurations For information about activating COM600 with new configuration see COM600 User s Manual 1EC103 OPC Server diagnostics To view the IEC103 OPC Server diagnostics right click the IEC103 OPC Server object and select Online diagnostics see Figure 4 3 1 Online attributes Version information Product version File version 1 0 107 Protocol stack version 9 0 00PCO1 Reset View log File Clear log file Tool connection IV Eollow selected IEC103_OPC_Server_Online_diagnostics jpg Figure 4 3 1 IEC103 OPC Server Online diagnostics You have the following alternatives e to view version information e to reset the IEC103 OPC Server e to view the event log file see Figure 4 3 2 e to clear the log file 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual OPCS_1EC103 1 Eventiog txt i i t E IRIS conf
21. EE TESNE ARNO 38 4 2 Activating COM600 with new configurations 38 4 3 1EC103 OPC Server diagnostics sse eee eee eee 38 4 4 Monitoring and controlling IEC103 Channel Activity 40 4 5 Monitoring and controlling IEC103 Device communication 40 4 6 Data object diagnostics sse eee eee eee 41 A e Te 1 121 7171 7 42 NN ASA 42 5 2 IEC 61850 data modeling sss 42 5 2 1 General about IEC 61850 data modeling 42 5 2 2 Data objects for status information sees eee 42 5 2 2 1 Single point status SPS ee 42 5 2 2 2 Double point status DPS ee 43 5 2 2 3 Integer status NBI sese eee 43 5 2 2 4 Protection activation information ACT 43 5 2 2 5 Protection activation information ACD 44 5 2 2 6 Device name plate DPL eee 44 5 2 2 7 Logical node name plate LPL 44 5 2 3 Data objects for measurand information 5 45 5 2 3 1 Measured value MV ceee 45 5 2 3 2 Complex measured value CMV 45 5 2 3 3 WYE Nati 46 5 2 3 4 Delta DEL irnar noa 46 5 2 4 Data objects for controllable status information 46 5 2 4 1 Controllable single point SPC 46 5 2 4 2 Controllable double point DPC 47 5 2 4 3 Binary controlled step position information A EA 47 5 3 CAM TIDUTOS iii A daa caajes ce 48 5 3 1 General about
22. Fax 1 407 732 2335 www abb com substationautomation Power and productivity for a better world 1MRS752278 H 31 5 2012 Copyright 2011 ABB All rights reserved AA ED ED FADED
23. IEC 60870 5 103 Master OPC User s Manual Power and productivity for a better world 1MRS752278 Grid Automation Controller COM600 4 0 Issued 30 6 2004 Version H 31 5 2012 IEC 60870 5 103 Master OPC User s Manual Contents 1 About this manual s s ici 7 th Copyrights del e caaenliarOaanats 7 AA Hez e ON 7 13 General sreci a a Ee aa A EA A RASER ASA EE S E EERE 7 1 4 Document conventions sese eee 8 1 5 CUBES OF symbols ir ia 9 E A ET AET 9 Life Abbreviations neen dia da 11 1 8 Related documents see 12 1 9 Document revisions serere eee 12 Zi INTRODUCTION ci ii idad si E 13 2 1 Functional overview asses eee eee eee 13 2 2 IEC 103 OPC Server features eee 14 3 COMMQUPAU OM ui A A A A AAA Ssu us saa 15 3 1 V Abo tthis Sect oN aia ea aa 15 3 2 Overview of configuration sees eee eee eee 15 3 3 Building object ree cion ii e 17 3 3 1 General about building object tree eee 17 3 3 2 Adding Gateway object viciosa naci dante 18 3 3 3 Adding IEC103 OPC Server object sees 18 3 3 4 Adding IEC103 Channel objects sse eee 18 3 3 5 Adding IEC103 Device objects sss 18 3 3 6 Adding Logical Device objects sees 19 3 3 7 Adding Logical Node objects sese sese 19 3 3 8 Adding data objects see 19 3 4 Config ring R elei eT 19 3 4 1 General about configuring objects 2 0 0 0 eee eee ee 19 3 4 2 1EC103 OPC Server properties see 20 3 4 3 Configuring IEC103 Channel properties
24. OOL q Quality M ER OV Time VT_14 Validity IV NT SB BL OV d Description Text VT_BSTR 5 2 2 5 Protection activation information ACD ACD is configured the same way as ACT since IEC103 does not support direction information All direction item tags dir always have the direction value unknown and OPC data type VT_I4 5 2 2 6 Device name plate DPL DPL represents ASDU 5 Table 5 2 2 6 1 Device name plate DPL information Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element vendor VisibleString A ee ASC chars 1 8 VT_BSTR swRev VisibleString CAM PR ASC chars 9 12 VT_BSTR location VisibleString VT_BSTR 5 2 2 7 Logical node name plate LPL LPL represents ASDU 5 44 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Table 5 2 2 7 1 Logical node name plate LPL information Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element vendor VisibleString M ef ASC chars 1 8 VT_BSTR swRev VisibleString 0 OE ASC chars 9 12 VT_BSTR d VisibleString O VT_BSTR 5 2 3 Data objects for measurand information 5 2 3 1 Measured value MV MV represents ASDUs 3 4 and 9 Table 5 2 3 1 1 Measured value MV information Name Type Value Value range Mandat Protocol informa OPC data types ory Optional tion element
25. Suspended messages cause old marking of OPC items By reading the OS attribute the status code of the system message can be read See the Status Codes manual for detailed information Device connection True Device connection OK status Data type Boolean False Device connection Access Read only suspended Indicates the status of the device connec tion Diagnostic coun ters Data type Integer Access Read only Incremented each time the communication with the IEC103 device is broken and the device is considered suspended Suspensions Send data mes Incremented each time a data message sages is sent Send command Incremented each time a command mes messages sage is sent Received data mes sages Incremented each time a data message is received Incremented each time the device sends a confirmation message to a command Received confirma tion messages Incremented each time an unknown mes sage is received Unknown messages Received too long Incremented each time a message messages exceeding the expected allowed max imum length is received Status codes 0 Device OK 51 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 52 13857 13858 13863 13864 13865 13866 13870 13871 13872 13881 17600 17601 17602 17604 17605 17606 17607 17608 17610 17611 17612 Message buffer full The va
26. able single point SPC e 3 4 7 3 Controllable double point DPC e 3 4 7 4 Binary controlled step position information BSC 33 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 7 2 34 The parameters are stored in Object Properties of SAB600 see the tables for each data object type The actual configuration using SAB600 is performed as described in 3 4 1 General about configuring objects Controllable single point SPC Table 3 4 7 2 1 Configurable SPC properties for OPC servers Property Para Value or Value range Default Description meter Common Data SPC Common data class according to IEC Class 61850 Subtype of the current data object Same com mand and indica tion addresses Addresses Command ASDU Type IEC103 command ASDU type Default 20 Command Function 0 255 IEC103 command function type Type Default 101 Command Informa 0 255 1EC103 command information number tion Number Default 105 Subtype of the current data object Separate command and indication addresses Addresses Command ASDU Type IEC103 command ASDU type Default 20 Command Function Type IEC103 command function type Default 101 Command Informa 0 255 1EC103 command information number tion Number Default 105 Indication Function 0 255 IEC 103 indication function type Type Default 101 1MRS752278 Grid Automation Cont
27. attributes oooooocccicccicccicnicccnccnncnnss 48 5 3 2 Server attriDUtes ci 48 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 5 3 3 1EC103 Channel attributes 49 5 3 4 1EC103 Device attributes e 50 LR Status ele A aca ea 51 PAPRDONGIK 1 atinada Aira uss sesedvacasvacesins 53 Interoperability list for IEC103 OPC Master eee 53 Tp To AP oo sasndectaceSsaieVeseudassedesvadanecansastaees 59 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 1 1 1 2 1 3 About this manual Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy ABB Oy assumes no responsibility for any errors that may appear in this document In no event shall ABB Oy be liable for direct indirect special incidental or consequential damages of any nature or kind arising from the use of this document nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document This document and parts thereof must not be reproduced or copied without written per mission from ABB Oy and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose The software or hardware described in this document is furnished under a license and may be used copied or di
28. cal device consists of one or several LDs The smallest part of a function that exchanges data An LN is an object defined by its data and methods A communication protocol developed by Echelon A proprietary method of ABB on top of the standard LON pro tocol Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry Representation of a connection to the data source within the OPC server An OPC item is identified by a string lt object path gt lt property name gt Associated with each OPC item are Value Quality and Time Stamp Named data item The report control block controls the reporting processes for event data as they occur The reporting process continues as long as the communication is available ABB proprietary communication protocol used in substation automation Protection and or Control Product supporting the SPA protocol version 2 5 or earlier XML based description language for configurations of electrical substation IEDs Defined in IEC 61850 standard 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 1 7 Abbreviations Abbreviation AE ASDU BRCB DA DMCD DO GW HMI IEC IED LAG LAN LD LMK LN LSG NCC NUC NV OLE OPC P amp C PLC POU RTS SA SCD SCL SFC SLD SNMP Description Alarms and Events Application Service Data Unit Buf
29. ct revision History A 30 6 2004 B 16 10 2006 C 21 12 2007 Document created Document revised Document revised ml a uo n oj o D 17 6 2008 Document revised E 13 2 2009 Document revised F 06 11 2009 Document revised G 30 6 2011 Document revised H 31 5 2012 4 0 Document revised 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 2 1 Introduction Functional overview The IEC103 OPC Server provides methods for OPC clients to exchange data with devices communicating via the IEC 60870 5 103 Master protocol hg F 2 3 8 IEC_103_Master_protocol_a jpg Figure 2 1 1 IEC 103 OPC Server system overview 1 NCC Network Control Center 2 COM600 with IEC103 OPC Server 3 Station Automation Builder 600 SAB600 4 Protection and control devices communicating through the IEC 60870 5 103 Master Protocol The IEC103 OPC Server software has two parts Engineering and diagnostic tools and the actual IEC103 OPC Server Engineering and diagnostic tools utilize the Station Automation Builder 600 later referred to as SAB600 framework and provide the user interface for engineering and diagnosing the IEC103 OPC Server The IEC103 OPC Server handles the data transfer and conversion between the IEC103 protocol and OPC interfaces To create a common and protocol independent data interface between the OPC server and client the process data from the IEC103 devices
30. data object 3 4 5 4 Integer status INS Table 3 4 5 4 1 Configurable DPS properties for OPC servers Property Para Value or Value range Default Description meter Basic Common Data INS Common data class according to IEC Class 61850 25 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 5 5 26 Property Para Value or Value range Default Description meter Addresses Indication Function 0 255 1EC103 indication function type Type Default 101 Indication Index 1 255 1EC103 indication index Default 1 Indication Informa 0 255 1EC103 indication information number tion Number Default 105 Scale and Unit Scale Default None Scale to be used with this data object Protection activation information ACT Table 3 4 5 5 1 Configurable ACT properties for OPC servers Property Para Value or Value range Default Description meter Common Data ACT Common data class according to IEC Class 61850 General Function Type IEC 103 function type for general Default 160 General Information 0 255 Number IEC103 information number for general Default 144 Phase A Addresses Phase A Function Type IEC103 function type for phase A Default 160 Phase A Information 0 255 IEC103 information number for phase A Number Default 144 Phase B Addresses Phase B Function 0 255 IEC103 function
31. device module you want to monitor in the object tree of SAB600 2 Right click the device module 3 Select Online diagnostics In the Status information field you can monitor the device status The Diagnostic counters field provides information on device activity To reset diagnostic counters click Reset counters You can take an IEC103 device into use by marking the In use check box If you unmark the check box the device is taken out of use Diagnostic counters are updated every 2 seconds To update them manually click Refresh 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Online attributes State Y In use V Diagnostic events enabled Status information Connection status OK Detailed status Device communication OK Diagnostic counters Suspensions 0 Transmitted data messages a Transmitted command messages 16 Received Data Messages s11 Received Confirm Messages 2 Unknown Messages 0 Received Too Long Messages 0 Reset counters Refresh Tool connection Reconnect IV Follow selected IEC103_Device_Online_diagnostics jpg Figure 4 5 1 IEC103 Device Online diagnostics 4 6 Data object diagnostics For information on data object diagnostics refer to COM600 User s Manual 41 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 5 1 5 2 5 2 1 5 2 2 5 2 2 1 Technical refer
32. e Type Value Value range Mandat 1EC103 informa OPC data types ory Optional tion element Bees O CS A G S E L gt iS ER 5 2 4 2 Controllable double point DPC DPC represents ASDU 20 Table 5 2 4 2 1 DPC represents ASDU 20 Name Type Value Value range Mandat 1EC103 informa OPC data types ory Optional tion element stVal ENUMERATED intermediate state DPI 1 OFF 2 ON VT_14 0 off 1 on 2 bad state 3 d Description Text Config VT_BSTR 5 2 4 3 Binary controlled step position information BSC BSC represents ASDU 20 Table 5 2 4 3 1 Binary controlled step position information BSC Name Type Value Value M O Protocol informa OPC data types range tion element ctlVal ENUMERATED stop 0 lower 1 DCO 1 OFF VT 1 higher 2 2 0N reserved 3 TimeStamp VT_DATE 47 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual Name Type Value Value M O Protocol informa OPC data types range tion element d Description Text O VT_BSTR 5 3 Attributes 5 3 1 General about attributes In addition to item tags for process data indications and commands the IEC103 OPC Server also provides some item tags for controlling the devices and retrieving status information from them These item tags are called attributes There are several categories of attributes which are described in the following subsections 5 3 2 Server attributes Table 5 3 2
33. ects Table 3 2 1 describes the objects shown in the object tree Figure 3 2 1 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 3 3 3 1 Table 3 2 1 1EC103 Server related objects Object Description 1EC103 OPC Server An object representing the IEC103 OPC Server 1EC103 Channel An object representing a physical communication channel You can define up to three channels per OPC server 1EC103 IED An object representing a physical device You should not have more than 30 devices per each channel Logical Device LD An object representing a group of functions Each function is defined as a Logical Node A physical device consists of one or several LDs Logical Node LN An object defined by its data and methods LN is the smallest part of a function that exchanges data Data Object DO Data object is an instance of one of the IEC 61850 Data Object Classes such as Single point status and Measured Value Depending on the class each data object has a set of attributes for monitoring and controlling the object e g value quality and control Building object tree General about building object tree The object tree is built in the Communication structure of SAB600 see Figure 3 2 1 It 1s built by adding objects in a logical order starting from the Gateway You have several possible ways to add objects to the object tree e You can right click the object t
34. ence About this section This section provides reference information about the following issues e TEC 61850 data modeling e Attributes e Status codes IEC 61850 data modeling General about IEC 61850 data modeling The relationship between the IEC 61850 data modeling and IEC103 OPC Server is described in this section For each data class there is a table giving a detailed description about the relation between the IEC103 data and IEC 61850 data object attributes and services The tables also describe how the data is presented on the OPC Server name space The columns in the tables have the following content types e Name specifies the OPC item name of the attribute service e Type specifies the IEC 61850 type of the attribute Value Value range specifies the allowed values and ranges of the attribute service Mandatory Optional specifies whether the attribute is considered as mandatory or optional according to the IEC 61850 standard e OPC data types specify the OPC data type used for the OPC item Data objects for status information Single point status SPS SPS represents ASDUs 1 and 2 Table 5 2 2 1 1 Single point status SPS information Name Type Value Value Mandatory Protocol informa OPC data types range Optional tion element BOOLEAN TRUE FALSE DPI 1 OFF 2 VT_BOOL ON TimeStamp M CP32 VT_DATE 42 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103
35. execution lt 251 gt Write entry abort OHOoOddcdaAoOoOOoD Basic application functions Test mode Blocking of monitor direction Disturbance data Generic services R D DUR U Private data Miscellaneous Measurands are transmitted with ASDU 3 as well as with ASDU 9 The maximum MVAL can either be 1 2 or 2 4 times the rated value No different rating shall be used in ASDU 3 and ASDU 9 since there is only one choice for each measurand Measurand Max MVAL 1 2 or Max MVAL 2 4 times the rated value times the rated value Current L E E 57 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual Current L Current L Voltage Li Voltage Le Voltage Ls Active power P Reactive power Q Frequency f Voltage L L 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Index A adding hannel ODJET seis sinewedesdebcentsttec tr Data object aaa E E osado ti H ET device ODJOCE vite TO Gateway Object acgevonaces Logical Device Object tuenti ideas Logical Mecca r SS NS fence cette Er evaeidedseittvdln A ETE eet ated eae attributes CHARMS A GOVICG carioca a A ON B Binary controlled step position information BSC IEC 61850 data Modeling a 2 na RZ ToS 70 R Ea nn sle TTT C channel A A ST sls e a geies Meets nee properties nia id channel object AO O ita ad li pd dt A aod cave ue A E dc Complex measu
36. fered Report Control Block Data Access Data Message Code Definition Data Object Gateway component connecting two communication networks together Human Machine Interface International Electrotechnical Commission Intelligent Electronic Device LON Application Guideline for substation automation Local Area Network Logical Device LonMark interoperable device communicating in LonWorks network In this document the term is used for devices that do not support the ABB LON LAG communication Logical Node LON SPA Gateway Network Control Center Norwegian User Convention Network Variable Object Linking and Embedding OLE for Process Control Protection amp Control Programmable Logic Controller Program Organization Unit Request To Send Substation Automation Substation Configuration Description Substation Configuration Language Sequential Function Chart Single Line Diagram Simple Network Management Protocol 11 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 1 8 1 9 12 Abbreviation Description SNTP Simple Network Time Protocol SOAP Simple Object Access Protocol RCB Report Control Block URCB Unbuffered Report Control Block XML eXtended Markup Language Related documents Name of the manual MRS number COM600 User s Manual 1MRS756125 COM600 HMI Configuration Manual 1MRS756740 Document revisions Document version date Produ
37. id Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 10 Term Alarms and Events AE Data Access DA Data Object DO Data Set Device Event Intelligent Electronic Device Logical Device LD Logical Node LN LON LON Application Guideline for substation automation LAG OPC OPC item Property Report Control Block SPA SPA device Substation Configuration Lan guage SCL Description An OPC service for providing information about alarms and events to OPC clients An OPC service for providing information about process data to OPC clients Part of a logical node object representing specific information for example status or measurement From an object oriented point of view a data object is an instance of a class data object DOs are normally used as transaction objects that is they are data structures The data set is the content basis for reporting and logging The data set contains references to the data and data attribute val ues A physical device that behaves as its own communication node in the network for example protection relay Change of process data or an OPC internal value Normally an event consists of value quality and timestamp A physical IEC 61850 device that behaves as its own commu nication node in the IEC 61850 protocol Representation of a group of functions Each function is defined as a logical node A physi
38. iguration TAS down EventLog opcs_reclO3 1 0 107 2004 05 19 06 29 started Device onreplyreceived STS 0 dicb4a205a0101080168000106005359000000002b36 oPcrequest Request completed with fail code 80004005 Configuration shutting down Eventiog OPCS_IECTO3 1 0 107 2004 05 19 06 29 started Configuration shutting down EventLog opcs_Iecio3 1 0 107 2004 05 19 06 29 started Configuration shutting down 20090 PECEREGELE IA Eventiog opcs_recto3 1 0 107 2004 05 19 06 29 started configuration shutting down EventLog OPCS_IEC 03 1 0 107 Configuration shutting down EventLog opcs_1eclo3 1 0 107 Configuration shutting down coo 2004 05 19 06 29 started 2004 05 19 06 29 started EventLog opcs_recto3 1 0 107 2004 05 19 06 29 started configuration shutting down Eventlog oPCS_1EC O3 1 0 107 2004 05 19 06 29 started configuration Shuet Ing down EventLog OPCS_IE oe 1 0 107 2004 05 19 06 29 started own EventLog opcs_1EC103 1 0 107 2004 05 19 06 29 started Be hr T FRIA SESSESSSSE SES SES ESS ESE NN NN NNN NNN NNN NM N NN PS ID Configuration shuttin NNN A PA HA PA NNN A PA PA HA NNN oo Figure 4 3 2 Event log file Configuration shutting down Diagnostic AE Client Eventlog_103 jpg Diagnostic events can be monitored and controlled using the Diagnostic AE Client function see Figure 4 3 3
39. ing Address 1 E 93 1EC103 OPC Server Station Address 1 E XR IEC103 Channel E A lEC1031ED1 fi LO Logical Device El 030 Communication Control Complete Event Time Tag True Confirmation Timeout 60 LN LUNO Prevents Automatic Sendr True G LN GGIO1 Reply Timeout 10 ses Alm Time Synchronization Inter 15 Ge LN MMUT El 060 Control Authorization fe LN CSWH Station R emote Switch OF H gt H 1EC1031ED2 El 070 OPC Alarm and Event Misc 1EC103_configuration_overview bmp Figure 3 2 1 Example view of SAB600 The configuration work can basically be divided into two separate tasks 1 building an object tree and 2 configuring object properties First you need to build an object tree This is done by adding objects to the object tree see 3 3 1 General about building object tree Connectivity Packages for certain Protection and Control products usually contain preconfigurations and tools to facilitate the building of the object tree Figure 3 2 1 shows an example of how the object tree may look like after 1t has been built In the example tree you can see the IEC103 OPC Server object and its child objects like channels devices and data objects Indentation is used to indicate the parent child relationship between the objects After you have added the necessary objects to the object tree in the communication structure you need to configure them see 3 4 1 General about configuring obj
40. is remodeled using the IEC 61850 data modeling Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 2 2 The configuration data is stored in the SCL format After the IEC103 OPC Server has been launched it reads the configuration file and establishes communication with the IEC103 devices through the IEC103 protocol stack Configured IEC103 devices and data modeled according to the IEC 61850 model see 5 2 1 General about IEC 61850 data modeling are then exposed to OPC clients through a Data Access DA server IEC 103 OPC Server features The IEC 103 OPC Server supports the following features e OPC Data Access v 1 0 2 0 e OPC Alarms and Events specifications v 1 10 e TEC 61850 data modeling e System supervision e JEC103 channel communication e JEC103 device communication e Supported IEC103 data types and functions Event based indications e Event based and cyclically updated measurements e General commands Time synchronization 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 1 3 2 Configuration About this section This section guides you in the configuration tasks required before you can start using the IEC103 OPC Server For information on the IEC 61850 data modeling refer to COM600 User s Manual Start SAB600 to open and name a project 1 Select File gt Open Manage Project In the Open Manage Pro
41. ject dialog select the required location for the project e Projects on my computer e Projects on network 3 Select New Project on the left Enter a Project Name The Description is optional 4 Click Create 5 Click Open Project Overview of configuration Before you can start using the IEC103 OPC Server you need to build and configure an object tree in SAB600 to define the Communication structure The possible objects are e Gateway e IEC103 OPC Server e JEC103 Channel e JEC103 IED e Logical Device objects e Logical Node objects e Data objects Figure 3 2 1 shows an example view of SAB600 including an object tree in the commu nication structure on the left and Object Properties window displaying the object properties on the right A When configuring OPC servers the following characters cannot be used in object names Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 16 ff Local Server IEC103_Project Station Automation Builder 600 File Edit View Tools Window Help Dd ima ler Project Explorer Communication Substation Structure a 8 E IO OB e Benar 32 Diagnostics Enabled False Ea Process Event Definitions InUse In Use Ba Communication Diagnostic Event Definitions Simulation Mode False Sa Common Event Settings El 020 Addresses H E Scale Definitions Poll
42. lue of the Message Length parameter may be too small Message filling error The value of the Message Length parameter may be too small Device suspended The reason could be that the link is not properly established for example incorrect communication cable wiring or the client station does not respond Message sending error The error may be the result of a problem in communic ation cable wiring or hardware Remote device replies with no acknowledged response The client did not accept the message but responded with a negative acknowledgment instead Not used in the unbalanced mode Link not ready A message is sent to a link with a non established communication Confirmation timeout An activation confirmation to a command was not received from the IEC client in the time defined by the Reply Timeout parameter Negative confirmation received The activation confirmation received from the IEC client was negative that is the command failed Device taken out of use Device taken in use Remote link continuously busy The Data Flow Control DFC bit of the messages from the client is set for more than 15 s Timeout while transmitting The CTS signal or the end of transmitted message is not received in correct time The DE attribute controls the CTS waiting time the transmission time of the message is automatically calculated Timeout while waiting for an acknowledgment to a message Link not ready The application level se
43. mag range q t rangeC units d 5 2 3 2 Complex measured value CMV CMV represents ASDUs 3 4 and 9 Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element cVal mag range q t rangeC units 45 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element d Description Text O VT_BSTR 5 2 3 3 WYE WYE represents ASDUs 3 4 and 9 Table 5 2 3 3 1 WYE information Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element d Description O Separate signal VT_BSTR 5 2 3 4 Delta DEL DEL represents ASDUs 3 4 and 9 Table 5 2 3 4 1 Delta DEL information Name Type Value Value Mandat Protocol informa OPC data types range ory Optional tion element d Description Text Separate signal VT_BSTR 5 2 4 Data objects for controllable status information 5 2 4 1 Controllable single point SPC SPC represents ASDU 20 Table 5 2 4 1 1 SPC represents ASDU 20 Name Type Value Value range Mandat 1EC103 informa OPC data types ory Optional tion element ctlVal BOOLEAN FALSE TRUE M DCO 1 0FF VT_BOOL 2 0N 46 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Nam
44. mon Data WYE Common data class according to IEC Class 61850 Phase A Addresses Phase A Function 0 255 IEC103 function type for phase A Type Default 160 Phase A Index 1 255 1EC103 index for phase A Default 1 Phase A Information 0 255 IEC103 information number for phase A Number Default 144 Phase B Addresses Phase B Function 0 255 IEC103 function type for phase B Type Default 160 Phase B Index 1 255 IEC103 index for phase B Default 2 31 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual Property Para Value or Value range Default Description meter Phase B Information 0 255 IEC103 information number for phase B Number Default 144 Phase C Addresses Phase C Function 0 255 1EC103 function type for phase C Type Default 160 Phase C Index 1 255 IEC103 index for phase C Default 3 Phase C Information 0 255 1EC103 information number for phase C Number Default 144 Neutral Function 0 255 IEC103 function type for neutral Type Default 160 Neutral Index 1 255 IEC103 index for neutral Default 4 Neutral Information 0 255 1EC103 information number for neutral Number Default 144 Scale and Unit Neutral Scale Default None Scale to be used with neutral for this data object Phase Scale Default None Scale to be used with phases for this data object 3 4 6 5 Delta DEL Table 3 4 6 5
45. nds a command before the communication between the server and the client is established Remote link busy Remote link not responding The server does not receive a reply from the client Channel set in use Channel set out of use Receiver out of buffers Dial up function inactivated Dial up function activated 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Appendix 1 Interoperability list for IEC103 OPC Master O Not supported a Supported a Supported may need additional configuring Physical layer Electrical interface E EIA RS 485 O Number of loads for one protection equipment RS 232 A EIA RS 485 standard defines unit loads so that 32 of them can be operated on one line For detailed information refer to clause 3 of the EIA RS 485 standard Optical interface O Glass fibre O Plastic fibre O F SMA type connector O BFOC 2 5 type connector E Depends on tranceiver Transmission speed L 9 600 bit s a 19 200 bit s Link layer There are no choices for the link layer Application layer Transmission mode for application data 53 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 54 Mode 1 The least significant octet first as defined in clause 4 10 of IEC 870 5 4 is used exclusively in this companion standard Common address of ASDU system specific parameter
46. nfigured and value ranges for them can be found in Table 3 4 3 1 The actual configuration by using SAB600 is performed as described in 3 4 1 General about configuring objects Table 3 4 3 1 1EC103 Channel properties Name Value or Value range Default Description In Use In Use Controls whether the device communica tion is initially in use or not Not In Use Default In Use Communication Port Bit Rate 300 bits s 600 bits s 1200 bits s Transmission rate used on the line 2400 bits s 4800 bits s 9600 bits s 19200 bits s Default 19200 bits s Communication Port COM1 COM4 Serial port used by the IEC 60870 5 103 protocol Default COM1 Parity No parity check Specifies the used parity check Odd parity Even parity Default No parity check Communication Control Carrier Blocking Carrier Detect ignored Usage of DCD signal of the serial port Carrier Detect must be set Default Carrier Detect must be set CTS Delay 1 65535 CTS waiting delay in milliseconds Default 50 Header Timeout 0 65535 Maximum waiting time of a link layer response in milliseconds Default 2000 Ignore the DFC bit True Ignore the DFC bit If true master contin ues polling normally If false master sends False the request status of link until the remote station clears the DFC bit Default False 21 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual
47. o which you want to add a child object Select New gt Object type group gt Object name for example New gt IEC103 gt IEC103 gt IED e YOU can right click the object type and select New gt New A New Object window appears Select the object type you want to add and click OK or double click it e You can copy the object Add the objects in the following order Gateway 1EC103 OPC Server 1EC103 Channel IEC103 Device Logical Device objects Logical Node objects Data objects SNe Re QS For information on building a substation structure refer to COM600 HMI Configuration Manual Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 3 2 3 3 3 3 3 4 3 3 5 Adding Gateway object To start building the object tree add a Gateway object in the Communication structure by selecting the project name right click it and select New gt Communication gt Gate way Adding IEC103 OPC Server object After the Gateway object has successfully been added you can continue building the object tree by adding an IEC103 OPC Server object To add an IEC103 OPC Server object 1 Select the Gateway object in the communication structure and right click it 2 Add an IEC103 OPC Server object By using the SCL Import function it is possible to import an entire server s or individual device s configurations without having to insert them manually To open the SCL Import function
48. ock informa tion sent by the slave Command confirmation timeout in seconds Sending of general interrogation If true Gl is not sent If false Gl is sent always when communica tion is re established successfully Link layer command acknowledgment timeout in seconds 23 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 5 3 4 5 1 3 4 5 2 24 Name Value or Value range Description Default Time Synchroniza 0 65535 Time synchronization interval in seconds tion Interval Default 15 Control Authoriza tion Station Remote Default None OPC path of the station remote switch position is Switch OPC Path used with this device The format is Node Prog D For OPC Server Channel NamelED Name Logical Device Name Logical Node Name Data Object Name e g GW ABB IEC103_OPC_DA_Server Instance 1 Chan nel1 lIED1 LD1 GGIO Moc OPC Alarm and Event Device Connection Default Device Connec Device connection status class definition used with status Class tion Status current device Data objects for status information General about data objects for status information There are seven different data objects providing status information e 3 4 5 2 Single point status SPS e 3 4 5 3 Double point status DPS e 3 4 5 4 Integer status INS e 3 4 5 5 Protection activation information ACT e 3 4 5 6 Directional protection activation inf
49. oftware revision Serial Number Default 0 A simple textstring describing the serial number Location Default 0 A simple textstring describing the location 3 4 5 8 Logical node name plate LPL Table 3 4 5 8 1 Configurable LPL properties for the OPC servers Property Para Value or Value range Default Description meter Common Data LPL Common data class according to IEC Class 61850 Addresses Indication Function 0 255 IEC 103 indication function type Type Default 101 Indication Informa 0 255 IEC103 indication information number tion Number Default 105 Vendor Vendor Default ABB A simple textstring describing the vendor Software Revision Software Revision Default O Asimple textstring describing the software revision Description Description Default 0 A simple textstring describing the description for logical node 29 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 6 Data objects for measurand information 3 4 6 1 General about data objects for measurand information There are four different data objects providing measurand information e 3 4 6 2 Measured value MV e 3 4 6 3 Complex measured value CMV 3 4 6 4 WYE e 3 4 6 5 Delta DEL The parameters are stored in Object Properties of SAB600 see the tables for each data object type The actual configuration using SAB600 is performed as described in 3 4
50. ormation ACD e 3 4 5 7 Device name plate DPL e 3 4 5 8 Logical node name plate LPL The parameters are stored in Object Properties of SAB600 see the tables for each data object type The actual configuration using SAB600 is performed as described in 3 4 1 General about configuring objects Single point status SPS Table 3 4 5 2 1 Configurable SPS properties for OPC servers Property Para Value or Value range Default Description meter Basic 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Property Para Value or Value range Default Description meter Common Data Class Common data class according to IEC 61850 Addresses Indication Function 0 255 IEC103 indication function type Type Default 101 Indication Informa 0 255 IEC103 indication information number tion Number Default 105 Scale and Unit Scale Default None Scale to be used with this data object 3 4 5 3 Double point status DPS Table 3 4 5 3 1 Configurable DPS properties for OPC servers Property Para Value or Value range Default Description meter Common Data DPS Common data class according to IEC Class 61850 Indication Function 0 255 IEC103 indication function type Type Default 101 Indication Informa 0 255 1EC103 indication information number tion Number Default 105 Scale Default None Scale to be used with this
51. red value CMV IEC 61850 data modeling oococooocccccccoccccncnnccnnnnnnnonnnnnnncnnnnnnnrnnnnnncrnnnnnnrrnn nana Propert criada ta adn dedica Date tdo configuring ODECE a e a T Controllable double point DPC IEC 61850 data modeling sico ld properties iii A A dition ease a AE E Controllable single point SPC IEC 61850 data modeling se syagcnotasvc ioeo zra oczt eiiaoe Caved gs 4 7 ayan c aslen D Data object AGGING O ubanreds EAN data object 59 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual ARMOR A oe ade te eles 41 Delta DEL IEC 61850 data MOdelING PTT 46 1KO 8153 KU EPEE 025 A Seals tates Gaetan Mitac cud festa ened 32 device A aici E E A E EA 50 o RR 23 device communication monitoring and controling a Kaa ZT Oea TL Z TdT Tana TR Za TTL A EAT RIT 40 Device name plate DPL IEC 61850 data MOdelING PTT 44 Tais lT 28 device object addict idad 18 diagnostics A NN 40 SOVET NA 38 Directional protection activation information ACD Properties te ciatoteer acs ccteaclad oben teatrenaNiins taunt E EAE Mechta E ESAS Ed 27 Double point status DPS IEC 61850 data modeling n reia e EAA ARARE ARA TERE TRAAT 43 DrOperties P E SEATA E E ES 25 F features OPC Server o r nets ea e A A A dod olay d aa aana Aa a 14 G Gateway object AGING an a A A acest AR E E A A A ARAARA 18 IEC 61850 data modeling Binary controlled step position information BSC
52. red value CMV eee 30 Controllable double point DPC sese sese sese eee eenn 35 Controllable single point SPC eee ee 34 Delta DEL voca d 32 O aie deed 23 Device name plate DPL eso azy car acetona iio arden pote ttasdeag van de 28 Directional protection activation information ACD see ee eee 27 Double point status DPS Galdar casa ee 25 Integer status INS ccoo ad dine idee eae eed id di 25 Logical node name plate LPL asses sees tenet eeeeaeeeeeeeaaeeeeeeaaeeeeeaaeeeees 29 Measured value MV asses ese sere serres tenet seer nner 30 ORC SEVO TTT 20 Protection activation information ACT eee eee 26 single point status ASP Siurana 24 WE id srl dpi 31 61 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 1MRS752278 62 Protection activation information ACD IEC 61850 data Modeling siiis sinnene eari Ei Protection activation information ACT IEC 61850 data modeling sss sese sese sees eser ereenn enne silen S server AttIDULES vdd diagnostics ii ee a edn ead Single point status SPS IEC 61850 data modeling sees eee properties oa tallada ds W WYE IEC 61850 data modeling sees eee properties sennen a a a atagde de too Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 ABB Inc Distribution Automation 655 Century Point Lake Mary FL 32746 USA Tel 1 407 732 2000
53. rnal C True Confirmation Timeout 60 Prevents Automatic Sending of General In True Reply Timeout 10 Time Synchronization Interval 15 E 060 Control Authorization Station Remote Switch OPC Path 070 OPC Alarm and Event Device Connection Status Class Device Connection Status E Misc Caption IEC103 IED Configuration Version Description IEC103 IED IED Type ECIO3 IED Manufacturer Technical Key Caption IEC103_Obj_Prop bmp Figure 3 4 1 1 Example of object properties in the Objects Properties window configuring is always done either by e selecting a predefined value from a drop down menu or e entering a text string or a numerical value in a text field 1EC103 OPC Server properties Table 3 4 2 1 IEC103 OPC Server properties Select the property you want to configure Depending on the property value type The available properties for different objects are listed in the following subsections Table 3 4 2 1 lists the IEC103 OPC Server properties their value ranges defaults and descriptions These properties are not configurable Prog ID for OPC Alarm and Event Server Name Value or Value range Default Description Basic AE Prog ID Default None DA Prog ID Default None Prog ID for OPC Data Access Server 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 4 3 Configuring IEC103 Channel properties The IEC103 Channel properties that can be co
54. roller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual 3 4 7 3 Property Para Value or Value range Default Description meter Indication Informa 0 255 1EC103 indication information number tion Number Default 105 Controllable double point DPC Table 3 4 7 3 1 Configurable DPC properties for OPC servers Property Para Value or Value range Default Description meter Common Data DPC Common data class according to IEC Class 61850 Subtype of the current data object Same com mand and indica tion addresses Addresses Command ASDU Type IEC103 command ASDU type Default 20 Command Function 0 255 IEC103 command function type Type Default 101 Command Informa 0 255 1EC103 command information number tion Number Default 105 Subtype of the current data object Separate command and indication addresses Addresses Command ASDU Type IEC103 command ASDU type Default 20 Command Function 0 255 IEC103 command function type Type Default 101 Command Informa 0 255 1EC103 command information number tion Number Default 105 35 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 3 4 7 4 36 Property Para Value or Value range Default Description meter Indication Function 0 255 IEC103 indication function type Type Default 101 Indication Informa 0 255 IE
55. sclosed only in accordance with the terms of such license Copyright 2012 ABB All rights reserved Trademarks ABB is a registered trademark of ABB Group All other brand or product names men tioned in this document may be trademarks or registered trademarks of their respective holders General This manual provides thorough information on the IEC 60870 5 103 Master protocol later referred to as IEC103 OPC Server and the central concepts related to it You find instructions on to take it into use The basic operation procedures are also discussed Information in this user s manual is intended for application engineers who configure IEC103 OPC Server AS a prerequisite you should understand IEC 60870 5 103 protocol and the basic pro cedures in Station Automation Builder 600 later referred to as SAB600 This user s manual is divided into following sections Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 1 4 Introduction This section gives an overview of the IEC103 OPC Server and states the system requirements to be met when using the client Configuration In this section you find an overview of the configuration tasks and instructions on how to create and configure IEC103 OPC Server related objects Operation This section covers the basic operation procedures you can carry out when transferring or activating Grid Automation Controller COM600 later referred
56. te of the Clear To Send CTS CTS signal 1 Active signal Data Carrier Detect 0 Passive signal Indicates the state of the Data Carrier DCD Detect DCD signal 1 Active signal Diagnostic coun ters Data type Integer Access Read only Transmitted tele grams Incremented each time a message is transmitted to the IEC103 channel by the 1EC103 OPC Server Failed transmissions Incremented each time a message trans mission to the IEC103 channel fails for some reason Incremented each time a transaction based transmission does not receive a response within a configured timeout Transmit timeouts Transmitted com Incremented each time a command is mands transmitted to the IEC103 channel by the 1EC103 OPC Server Transmitted replies Incremented each time a reply is transmit ted to the IEC103 channel by the IEC103 OPC Server 49 Grid Automation Controller COM600 4 0 1MRS752278 IEC 60870 5 103 Master OPC User s Manual 5 3 4 50 Name Value or Value range Default Description Incremented each time a telegram is received by the IEC103 OPC Server from the IEC103 channel Received telegrams Incremented each time a parity error is detected in a message received from the IEC103 channel Parity errors Incremented each time an overrun error is detected in a message received from the IEC103 channel Overrun errors Incremented each time a checksum error is detected
57. to as COM600 with new configurations You are also given instructions on how to monitor and control the IEC103 commu nication Technical reference This section contains a list of status codes and information about the IEC 61850 data modeling Document conventions The following conventions are used for the presentation of material The words in names of screen elements for example the title in the title bar of a window the label for a field of a dialog box are initially capitalized e Capital letters are used for the name of a keyboard key if it is labeled on the keyboard For example press the ENTER key e Lowercase letters are used for the name of a keyboard key that is not labeled on the keyboard For example the space bar comma key and so on e Press CTRL C indicates that you must hold down the CTRL key while pressing the C key to copy a selected object in this case e Press ESC E C indicates that you press and release each key in sequence to copy a selected object in this case The names of push and toggle buttons are boldfaced For example click OK The names of menus and menu items are boldfaced For example the File menu e The following convention is used for menu operations MenuName gt Menu Item gt CascadedMenultem For example select File gt New gt Type The Start menu name always refers to the Start menu on the Windows taskbar e System prompts messages and user responses input are shown
58. ue range Default Description meter Phase B Addresses Phase B Function 0 255 IEC103 function type for phase B Type Default 160 Phase B Information 0 255 IEC103 information number for phase B Number Default 144 Phase C Addresses Phase C Function 0 255 IEC103 function type for phase C Type Default 160 Phase C Information 0 255 IEC103 information number for phase C Number Default 144 Neutral Function 0 255 IEC103 function type for neutral Type Default 160 Neutral Information 0 255 IEC103 information number for neutral Number Default 144 Device name plate DPL Table 3 4 5 7 1 Configurable DPL properties for OPC servers Property Para Value or Value range Default Description meter Common Data DPL Common data class according to IEC Class 61850 Indication Function 0 255 1EC103 indication function type Type Default 101 Indication Informa 0 255 1EC103 indication information number tion Number Default 105 Vendor Default ABB A simple textstring describing the vendor Hardware Revision 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual Property Para Value or Value range Default Description meter Hardware Revision Default 0 A simple textstring describing the hard ware revision Software Revision Software Revision Default O Asimple textstring describing the s
59. unctions in monitor direction lt 240 gt Read headings of all the defined groups lt 243 gt Read directory of a single entry lt 244 gt Read value or attribute of a single entry lt 249 gt Write entry with confirmation lt 250 gt Write entry with execution lt 251 gt Write entry aborted OOodoooo E lt 241 gt Read values or attributes of all the entries of one group lt 245 gt End of general interrogation of generic data Selection of standard information numbers in control direction System functions in control direction E lt 0 gt Initiation of general interrogation E lt 0 gt Time synchronisation 1MRS752278 Grid Automation Controller COM600 4 0 IEC 60870 5 103 Master OPC User s Manual General commands in control direction lt 16 gt Auto recloser on off lt 17 gt Teleprotection on off lt 18 gt Protection on off lt 19 gt LED reset lt 23 gt Activate characteristic 1 lt 24 gt Activate characteristic 2 lt 25 gt Activate characteristic 3 lt 26 gt Activate characteristic 4 Generic functions in control direction lt 240 gt Read headings of all the defined groups lt 241 gt Read values or attributes of all the entries of one group lt 243 gt Read directory of a single entry lt 244 gt Read value or attribute of a single entry lt 245 gt General interrogation of generic data lt 248 gt Write entry lt 249 gt Write entry with confirmation lt 250 gt Write entry with