1. Z2500P ECCI QUICK START INSTALLATION GUIDE Purpose of this Document This document is designed to assist you in unpacking installing and verifying the operation of a CTI 2500P ECC1 module For comprehensive instructions on configuring and using the product see the CTI 2500P ECC1 Communications Coprocessor User Manual available on our CTI web site http www controltechnology com Introduction The 2500P ECC1 Ethernet Communications Coprocessor module extends the communications capabilities of CTI 2500 Series controllers offering increased connectivity and additional protocols By offloading the processing of communications protocols from the 2500 Series controller the 2500P ECC1 module minimizes the impact of network communications on controller performance while providing a robust set of communications protocols Installation Preparation CTI 2500 Series Controller Firmware To support communications with a 2500P ECC1 module your CTI 2500 Series controller may require a firmware update The installed firmware version may be determined by accessing the controller Product Information web page or by reading Status Words 260 and 261 Refer to the Firmware Revision History for the 2500P ECC1 on the CTI website http www controltechnology com support software_revision to determine whether new firmware is required for your CTI processor A firmware update file can be downloaded from the CTI web site http www controltechnology c
2. P lg UM See ES tty ar wia ty eatin nant X Swi tc hes TS SD Card Receptacle 2 Z 4 E Do 5e rR Lm Sg he oO oo a lt ONI EE Verify SD Card Installation Configuration data is stored on an SD Secure Data card which is inserted in a receptacle located on the 2500P ECC1 printed circuit board See the illustration above The 2500P ECC1 is shipped from CTI with an SD card installed in the receptacle If a card is not installed you will need to obtain and install one before using the product See the CTI 2500P ECC1 Communications Coprocessor User Manual for additional information about the SD card requirements To install the SD card in the 2500P ECC1 receptacle insert the card in the receptacle face up with the beveled edge facing the receptacle Continue insertion until you hear a click then release To remove the card apply insertion pressure until you hear a click then release pressure Page 2 K 2500P ECC1 Quick Start Guide Create a Quick Start Configuration A Quick Start configuration is the simplest configuration that will allow the module to be used This Quick Start configuration will configure the module IP parameters designate the IP address of the 2500 Series controller that will be the Host Controller and enable the CAMP server To create the Quick Start configuration start the 2500P Configuration program and select the Start New Project option as shown in the accompany
3. minutes the PC will cease trying to get an IP address from a DHCP server and assign a compatible link local address You can verify this by opening the Command Prompt window in the accessories program folder and typing IPCONFIG If an address in the link local range is not displayed or your PC is not using DHCP to obtain an IP address you must manually change the IP address of your PC This can be changed in the network section of the Windows Control Panel When the IP address of the PC is compatible with the IP address of the ECC1 module you should be able to ping the module and get a reply Open the Command Prompt window and type PING n n n n where n n n n is the IP address of the ECC1 module Once you can successfully ping the ECC1 module you should be able to transfer the configuration file using the CTI 2500P ECC1 Configuration Program by clicking on the Compile Send to ECC1 item in the task bar After the file is transferred and saved to the SD card the ECC1 module will automatically restart using the new configuration parameters When the restart is complete the status LEDs Multi Segment Display and the Network Status LED should be in the states listed in the Configuration Transferred via SD Card section Siemens and SIMATIC are registered trademarks of Siemens AG Page6 0 2500P ECC1 Quick Start Guide
4. OOD Flashing Indicates that a valid configuration was not found HOST OFF Indicates that the ECC1 module is not connected to the Host Controller ACTIVE Indicates no communication protocols are running MSD Error Displaying an IP address and Err 140 indicating no configuration file was found Before you can transfer the configuration files via Ethernet the IP address of the PC containing the configuration program will likely need to be changed to be compatible with the IP address of the module shown in the MSD To be compatible the network portion of the IP address must be the same and the host portion of the IP address must be different For further information see Appendix B of the CTI 2500P ECC1 Ethernet Coprocessor User Manual When shipped from CTI the ECC1 module flash will contain no IP address When this condition exists the ECC1 module will automatically assign an address from the link local block of IP addresses 169 254 1 0 through 169 254 254 255 This block is also used by Microsoft windows when an address cannot be automatically obtained using DHCP Dynamic Host Configuration Protocol If an address in this range is displayed in the MSD and your PC or laptop is using DHCP to obtain an IP address you can use the following technique after the module is powered up 1 Power down the PC 2 Connect an Ethernet cable between the PC and the ECC1 module 3 Power up the PC After a period of time which could be several
5. a PC to the ECC1 module by saving the files to an SD card which is then inserted into the SD Card receptacle on the ECC1 This capability is especially useful in cases where the IP address of the ECC1 module has not been set If you want to use this capability and your PC not have an SD card slot most don t you will need to obtain a USB to SD Card adapter These adapters are widely available at a nominal cost Unpacking the Module Open the shipping carton and remove the special anti static bag that contains the module After discharging any static build up remove the module from the static bag Do not discard the static bag Always use this bag for protection against static damage when the module is not inserted into the I O base CAUTION The components on the 2500P ECC1 module can be damaged by static electricity discharge To prevent this damage the module is shipped in a special anti static bag Static control precautions should be followed when removing the module from the bag and when handling the printed circuit card during configuration Setting the Module Switches Since the 2500P ECC1 module is software configurable the module switches are used only for special purposes such as firmware update Before proceeding ensure that all switches are in the Open position for normal operation See the following illustration for the location of the module switches T EN z gt gi AS m r sials ee Pou to E ha Module a
6. ave an Ethernet path to the Host Controller and the network containing the devices with which it will communicate There are two options for connecting to the Host Controller as explained in the following sections Paget 20 2500P ECC1 Quick Start Guide Direct Connection to the Host Controller If a single 2500P ECC11 is installed in the same base as the Host controller an Ethernet cable Cat 5 or Cat 5e can be used to connect one Ethernet port on the ECC1 module directly to the Ethernet port of the 2500 Series controller The other port is then connected to the network switch Host Controller An advantage of this method is that the embedded switch on the 2500P ECC1 can provide broadcast storm protection for the 2500 Series programmable controller Connection via a Network Switch If multiple 2500 ECC1 modules are communicating with the Host Controller they should be connected via an external Ethernet switch In this example port 1 of the ECC1 should not be connected to the network However you could directly connect a laptop PC to this port for programming or maintenance tasks Host Controller CAUTION When this method is used the other Ethernet port on the 2500P ECC1 SHOULD NOT be connected to the network switch Doing so could create a loop which will disrupt network communications Apply power to the ECC1 Module After installing the module apply power to the base and observe the module LEDs The expecte
7. d module behavior will depend on whether you transferred the configuration via the SD card or you chose to transfer the configuration later via the Ethernet port See the following sections Configuration Transferred via SD Card If the configuration was previously transferred via the SD card the module should start up in normally After a normal startup the ECC1 module LEDs should be in the state shown below LED FinalState Status Description GOOD ON solid Indicates that module startup was successful communicating with the Host Controller the CAMP server is operational In addition the following should be true e Multi Segment Display MSD is displaying the IP address that you intended to assign to the module e The Network Status NS LED is On Green If all of the above conditions are met you should be able to connect to the module web server by entering the IP address of the module in your browser URL window and to download new configuration s to the module If a problem exists you should refer to the TROUBLESHOOTING OPERATIONAL PROBLEMS section of the CT 2500P ECC1 Ethernet Communications Coprocessor User Manual 2500P ECC1 Quick Start Guide P N 062 00398 010 Page 5 Transferring Configuration Files via Ethernet If you did not transfer a configuration to the SD card and no previous configuration is stored on the SD card the LEDs should be in the state shown below LED Final State Status Description G
8. ert the adapter into a USB connector on your PC e Select the COMPILE SAVE TO SD CARD option e After the configuration has been written to the SD card remove the card from the USB adapter and re install it in the ECC1 module If you would rather use Ethernet to transfer the configuration you will need to wait until the ECC1 module has been installed and powered up Installation Module Installation The 2500P ECC1 can be installed in a CTI 2500 Series or SIMATIC 505 PLC base Before installing the module remove AC power from the base Using the guides align the circuit board with one of the I O slot connectors in the base Slide the 2500P ECC1 module into the rack until the connector seats Then use the thumbscrews to secure the module in the rack egg i H n Ei i i l s E Ste Re bs ait 4 BA 4 z I ti j oM an A 3 Ps q 9 n 3 i t t 7 nai errerey aur i a e SASSA Smee Pe 7 R a ERTE Se N E ij i i Making Ethernet Connections The 2500P ECC1 module provides two Ethernet port connectors on the front panel Both ports connect to a three port switch on the module circuit board The third port of the switch is connected to the ECC1 module microprocessor This design provides additional flexibility in connecting to the Host Controller and the network The switch circuit also provides hardware protection against network traffic storms The ECC1 module must h
9. ing illustration If the selection window does not appear select the NEw option from the File menu item Once the selection has been made the ECC1 Settings window should appear allowing you to enter ECC1 module network parameters and the IP Address of the Host Controller The Host Controller is the 2500 Series PLC for which the ECC1 module will provide communications support r 2500P ECC1 Configuration In the ECC1 Settings window you Welcome to the 2500P ECC1 Configuration Program Start a new project Open an existing project Cancel E Don t show this Welcome Window again File Edit View Tools Help need to enter led Save to File Compile Send to ECC1 l E e The IP address that you want to Untitedlecc assign to the module protocol Selection 4 e The associated subnet mask of nf are the module A a e The IP address of the Host aa Controller Note The default gateway is not configured because this example assumes all communications in on the same local area network After entering this information click Tagname Type Address Count High Prig D E ECC1 Settings General Advanced Module Identifier Location Configuration Description ECC1 Network Settings IP Address Subnet Mask Default Gateway Host Controller Settings Interface type IP Address Time Slice High Speed Backplane on the OK bu
10. om downloads CTI 2500P ECC1 Module Firmware Although CTI installs the latest available firmware version prior to shipping a product it is possible that a new firmware version has been released prior to the installation of your 2500P ECC1 CTI recommends that you check the firmware revision history to determine whether you need to upgrade to newer firmware See the paragraph above for links to the CTI web site CTI 2500P ECC1 Configuration Program Before the 2500P ECC1 module can be used you must configure it for your application This is accomplished by using the CTI 2500P ECC1 Configuration Program You can download this program from the CTI Web site http www controltechnology com downloads The program can be installed on any PC running Microsoft Windows XP Windows Vista or Windows 7 IP Address Selection Before you can use the ECC1 module you must assign an IP address and subnet mask that is on the same IP network as the Host Controller for which it will provide communication services If you will be transferring configuration files to the ECC1 module using Ethernet the PC running the configuration program must also have an IP address that is on the same network Prior to installing the ECC1 module you should determine the IP address and subnet mask that you will assign to it 2500P ECC1 Quick Start Guide P N 062 00398 010 Page 1 SD Card to USB Adapter The 2500P ECC1 supports transferring configuration files from
11. tton Module Identifier ECC1 IP 0 0 0 0 Next click on the CAMP server object 2500P ECC1 Configuration in the Protocol Selection panel as shown below Then click on the File Edit View Tools Help Untitledl ecc amp lafSave to File Compile Send to ECC1 id Compile Save to SD Card ECC1 Settings z Verify Data Enable CAMP Server check box Protocol Selection A CAMP Serve CAMP Client F Open Modbus Server Open Modbus Client T Network Data Exchange Publish Network Data Exchange Subscribe After you have done the above click on the Save to File item in the taskbar to save the configuration onfigure CAMP Server V Enable CAMP Server CAMP Server Properties Enable Multicast Listening Address Nnon 0 0 0 0 Tagname Type Address Count High Priority Description CC MS MC NP NS D E Module Identifier ECC1 IP 172 18 74 50 2500P ECC1 Quick Start Guide P N 062 00398 010 Page 3 Transfer the Configuration to the ECC1 Module If you are configuring the module for the very first time or you are configuring a module that has a previous IP address that is not accessible from your PC the easiest method is to transfer the configuration using the SD card To accomplish this e Remove the SD card from the ECC1 module e Insert the SD card into the SD card slot on your PC or Insert the SD card into a USB to SD card adapter and then ins