1. If status indicator 1 is green the minimum level is between 0 75 Vpp and 2Vpp this is still acceptable If status indicator 1 is red however at least one signal is being received at a level less than 750mVpp To identify the nodes that are producing the low signals scan all of the node addresses on the network with the Node Finder If it is necessary to ensure that the signal at each node input meets the ControlNet Receive Mask specification 510mVpp at minimum verify the minimum level with an oscilloscope connected to the NetChecker If status indicator 7 top of the scale turns red a level of signal greater than 9 5 Vpp was detected This may indicate a strong mismatch on the network Check if terminations are present Rockwell Automation Publication 1788 UM001B EN P August 2012 20 ControlNet NetChecker Additional Tips Use these tips to troubleshoot intermittent problems and maintain continuous network monitoring Intermittent Problems Various intermittent problems are often are caused by the BNC connectors on the trunk cable such as the center pin not crimped causing an unreliable contact The NetChecker in Diagnostic mode is a valuable tool to help locate such problems Read the NetChecker while subjecting each trunk connector or tap to a moderate mechanical stress If faults are reported the BNC connector has not been mounted correctly and must be replaced Continuous Network Monitoring To provide continuous monito
2. 4 ControlNet NetChecker Product Overview The 1788 CNCHKR NetChecker is a hand held tool for testing active ControlNet networks It is pocket sized and battery powered for field use The NetChecker helps commissioning and troubleshooting ControlNet installations by verifying signals on the ControlNet cabling For example installers are able to find shorts and termination faults by using the NetChecker The tool is designed to evaluate the quality of the signal on the coaxial medium It does not interpret the content of messages except for the addresses of the nodes issuing messages The NetChecker checks several electrical characteristics of the signal e Level of distortion e Noise or signal reflections e Rising and falling edges e Minimum message duration e Minimum between message duration e Peak to peak amplitude e Violations to Manchester signal encoding An evaluation of the signal quality is made using a combination of criteria on all the above characteristics Most of the criteria used are fixed by design and therefore cannot be modified by the user The input signal from the network is converted to a 2 level digital signal using a voltage reference This voltage reference or threshold is the only criteria that can be modified by the user by means of a slide switch SW3 The results of the signal analysis are displayed by bi color status indicators Additional features include a Node Finder and an oscilloscope output The Node F
3. bargraph shows that the minimum level is correct Slow Edges may also be reported along with Poor Signal Quality and Illegal Framing in the case of strong impedance mismatches on the network causing a high amount of distortion In this situation the threshold setting may influence the recurrence of the faults Reporting Examples The figures below show examples of the reporting by the NetChecker Check the Signal Level by Using the Threshold Setting In the example at left the NetChecker reports no fault at the highest sensitivity low threshold The network is OK at the point of test The status indicator Node On Line is green because there is a node transmitting at address 07 The example at right shows faults reported at High Threshold Generally this indicates a high level of reflections on the network the network may not be correctly terminated is accidentally open or shorted or there is bad contact in a BNC connector The status indicator Node On Line is Off because there is no node at address 11 Rockwell Automation Publication 1788 UM001B EN P August 2012 18 ControlNet NetChecker Low Threshold Setting highest sensitivity level TRAFFIC INPUT Low Bat Output to Scope O Signal 1 4 GND OTrigger Power Switch m OFF OON O Push ON Node Finder a E Ou a E Push ON Buzzer o pc s ControNet NetChecker Rockwell Allen Bradley Automation Check the Signal Level by Us
4. level on the network either global from all nodes or from a selected node It is selected when slide switch SW3 is in its rightmost position Diagnostic Mode In Diagnostic mode positions L M and H on slide switch SW3 select one of three fixed voltage references or thresholds used by the NetChecker to convert the analog input signal to a binary signal Table 2 Threshold Settings Sensitivity to Noise SW3 Position Reference Voltage mV Volts peak to peak Most sensitive L 300 0 6 Moderately sensitive M 450 0 9 Least sensitive H 600 1 2 The L low reference voltage setting is the most sensitive to input signal or noise When the L position is selected any input signal exceeding 300mvV will be converted to a logical 1 and processed by the NetChecker All input signals between 300mV and 300mV will be converted to a logical 0 and ignored Note that this sensitivity range is deliberately set above the absolute minimum peak to peak voltage required by the ControlNet specification 510mVpp The M medium and H high positions provide higher voltage references and less sensitivity as shown in the table above Rockwell Automation Publication 1788 UM001B EN P August 2012 8 ControlNet NetChecker Status Indicator Functions When slide switch SW3 is in the Diagnostic left area of the front panel the status indicators have the following functions e Pass Fail status indicator Indicates
5. of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running United States or Canada 1 440 646 3434 7 Use the Worldwide Locator at Outside United States or A Canada http www rockwellautomation com support americas phone_en html or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback United States Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Allen Bradley Rockwell Software Rockwell Automation and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Ro
6. the overall quality of the signal on the coaxial cable Green when the input signal is clean this status indicator will turn progressively red if one or more of the criteria of quality are violated e Poor Signal Quality status indicator Blinks red when the message signal is distorted and or when the between messages gap is polluted by noise so that the NetChecker is uncertain if the signal received is a valid message or noise Distortion and noise are generally the result of reflections of signal on the cable caused by impedance mismatches The Poor Signal Quality fault detection is dependent on the threshold settings L M and H on SW3 Note that there area number of violations to the Manchester encoding in the ControlNet frame in Start and End Delimiters The NetChecker can detect if there are fewer or more violations than expected In the case of very large distortion of the signal the NetChecker may interpret that there are unexpected violations although the message was generated correctly by the originator node e Illegal Framing status indicator Blinks red when erratic message detection occurs The NetChecker verifies the duration of messages and generates a fault if any message is shorter than 7 bytes NULL message length In addition the time gap between messages must not be less than 6 bytes These errors are generally caused by high noise level or signal reflection at the end of the messages or during the time gap between message
7. FF disconnects the batteries e ON turns on the tool permanently e Push ON provides momentary power Push switch SW2 Momentary switch to turn on the instrument when SW1 is in the Push ON position Slide switch SW3 4 position function switch e Positions L M H select the Diagnostic mode and low medium and high thresholds e The rightmost position selects the Bargraph mode BNC connector Display Signal input Connects to the network trunk cable via a standard tap or the provided cable and BNCT The NetChecker is electrically isolated from the network by a transformer 8 bi color Red Green status indicators Status indicators numbered 1 to 7 are dual function for Diagnostic or Bargraph modes Status indicators named TRAFFIC also indicates a low battery condition Thumbwheel switches 2 digit decimal switches for entering the address of the Node to find 0 to 99 DC jack External DC power from AC adapter nominal 5V DC max 5 5V 0 25A Jack should have 3 5 mm external diameter and 1 35 mm internal diameter Oscilloscope connector 3 pin Phoenix connector with Network Ground and Trigger signals Buzzer Piezo Buzzer provides an audible indication of detected faults Batteries 2 alkaline batteries 1 5V AA LR6 size located in the battery compartment on the back of the tool Batteries are provided uninstalled with the tool A screwdriver is required to install or replace the bat
8. User Manual Allen Bradley ControlNet NetChecker Catalog Number 1788 CNCHKR Topic Page Important User Information 2 European Communities EC Directive Compliance 3 Additional Resources 3 Product Overview 4 Diagnostic Mode 7 Bargraph Mode 9 Operation 11 Reporting Examples 17 Additional Tips 20 Waveform Examples 21 Rockwell Allen Bradley Rockwell Software Automation 2 ControlNet NetChecker Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http www rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associ
9. ated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequences SHOCK HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures PPP e IMPORTANT Identifies information that is critical for successful application and understanding of the product Rockwell Automation Publication 1788 UM001B EN P Augus
10. ckwell Otomasyon Ticaret A Kar Plaza ly Merkezi E Blok Kat 6 34752 erenk y istanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1788 UM001B EN P August 2012 PN 165196 Supersedes Publication 1788 UM001A US P November 1999 Copyright 2012 Rockwell Automation Inc All rights reserved Printed in the U S A
11. dicators If you need your hands free set SW1 to the ON position middle so that the NetChecker remains powered on Remember to put SW1 back to the OFF position when you are done Use a Wall Adapter to Power the NetChecker The NetChecker may also be powered by a wall adapter connected to the External Power connector on the side of the tool The adapter should produce a regulated 5V DC 0 25A 5 5 volts max The internal batteries are disconnected when the adapter s jack is inserted in the connector The NetChecker remains operating as long as power is provided switches SW1 and SW72 are not active in the external power mode however it is better to leave SW1 in the OFF position ATTENTION Make sure that your adapter is CE compliant and that the system formed by the NetChecker plus the adapter is also CE compliant Rockwell Automation Publication 1788 UM001B EN P August 2012 12 ControlNet NetChecker Connect to the Network Connect the NetChecker to the network in one of these ways e Use the provided cable and BNC T as shown in the left example This method requires you to break the trunk to install the BNC T which disrupts a running system The BNC T is intended for temporary use only We do not recommend leaving the BNC T installed e Use the provided BNC T with a 1786 TCAP tap and 1786 BNCP barrel connector as shown in the right example The tap 1786 TCAP and 1786 BNCP connector must be purchased separately Th
12. e tap can be left in the system for testing purposes but the tap must not be left unconnected Install a 1786 TCAP on all unused taps Provided BNC T ControlNet Trunk Tap EEE ControlNet Trunk 4 i pt i INA Provided Cable gt Tap Drop ISN e Provided BNC T 1786 BNCP gt ine NetChecker asm 32320M NetChecker Ifyou do not want to open the network you can install some free taps for testing With a redundant network you can temporarily disconnect one of a node s taps from the network and test from this Recognize however that you are removing a node from the network Test that node later from a different location on the network Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 13 When you press the ON switch the TRAFFIC status indicator should turn green to indicate that messages are being detected The greater the volume of traffic seen on the network the brighter the status indicator will be illuminated If the status indicator remains off the network is either inactive or the tested segment of cable is disconnected from the network Check the cable and the connectors Select Testpoints on the Network Good diagnostic results verify that the network signal is clean at the point of test only Becau
13. ellow or red Buzzer Sounds A blinking Poor Signal Quality status indicator often indicates that signal reflections are present on the network If you receive this indication check the network for impedance mismatches inadequate coaxial cable used for all or part of the trunk cable no termination or wrong termination high contact resistance or intermittent contact in BNC connectors near the taps Generally the faults are reported at the lower threshold settings and disappear or decrease at the higher settings Use the Bargraph mode to verify the minimum signal level If the signal level is low 2 or less on the bargraph scale check the trunk cable length versus the number of nodes and compare it to the ControlNet specification Terminate any unused taps with a dummy load 1786 TCAP Also ensure that no BNC connector is in contact with any conductive material such as a metal wireway or DIN rail IMPORTANT An unused drop cable should be terminated by a dummy load 1786 TCAP Do not use a 75 ohm termination along with a bullet connector The impedance here is not 75 ohms In disorders caused by impedance mismatches Poor Signal Quality may be reported along with Illegal Framing and possibly Slow Edges for all the threshold settings This indicates large impedance mismatches caused by an open trunk cable or a short circuit In such cases the Node Finder may have difficulty detecting the presence of some nodes on the network because of
14. han the one being tested is the level of signal from the repeater Perform a Global Survey of Signal Levels To perform a global survey of the signal levels of all messages on a network set SW3 to its rightmost position and set the Node Finder thumbwheels to 00 The NetChecker will display two green status indicators indicating the strongest and the weakest levels encountered on the network The maximum and the minimum levels indicated remain latched until NetChecker power is cycled Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 11 Oscilloscope Output in Bargraph Mode In Node Signal Level Bargraph mode the oscilloscope output is operational in the same way as in Diagnostic mode In Global Bargraph mode however no trigger signal is provided since there can be no ControlNet node at address 00 Operation This section describes how to operate your NetChecker device Install the Batteries Use a screwdriver to remove the two screws from the battery cover on the back of the NetChecker Install the two 1 5V AA batteries supplied as indicated in the compartment Batteries installed incorrectly may damage the instrument Use only alkaline batteries for replacement Conserve Battery Power To conserve battery power when using the NetChecker set power switch SW1 to the Push ON position then press and hold the Push ON button for just the time necessary a few seconds to read the status in
15. inder detects the presence of a given node on the network The user enters the node address on thumbwheel switches The oscilloscope output provides a trigger and an electrically isolated network signal for displaying messages from a specified node on an oscilloscope The NetChecker is designed to be connected to a network via either a standard tap or the provided BNC T and cable The NetChecker is a passive instrument It does not send any signal on the network under test Rockwell Automation Publication 1788 UM001B EN P August 2012 Left SW1 on the side o BNC Connector TRAFFIC Low Bat Output to Scope O Signal x1 4 m GND OTrigger Power Switch m OFF ooN O Push ON Node Finder a E o Poor Signal Quality E E Pass Fail Buzzer o ControlNet NetChecker Rockwell Allen Bradley Automation 1788 CNCHKR ControlNet NetChecker SW3 ControlNet NetChecker Right Rockwell Automation Publication 1788 UM001B EN P August 2012 5 6 ControlNet NetChecker Table 1 NetChecker Specifications Attribute 1788 CHNHKR Dimensions 152 x 83 x 33 5 mm BNC connector not included 164 x 83 33 5 mm BNC connector included Weight with batteries 250 grams 8 18 oz Environmental Operating Temperature 0 50 C 32 122 F Storage Temperature 40 85 C 40 185 F Slide switch SW1 3 position power switch O
16. ing the Bargraph Blinking Red Red High Threshold Setting lowest sensitivity level TRAFFIC INPUT Low Bat Diagnostic Output to Scope Bargraph O Signal x14 m GND OTrigger Power Switch m OFF OON O Push ON E E E on ControlNet NetChecker Rockwell Allen Bradley Automation Set slide switch SW3 to its bargraph rightmost position and set the Node Finder to zero to get a global level indication Press the ON switch and make sure that the TRAFFIC status indicator is green Generally the bargraph displays two green status indicators indicating the maximum and the minimum level of signal seen at the point of test on the network Normally these should be in the range of status indicators 2 6 Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 19 TRAFFIC INPUT Low Bat Output to Scope Diagnostic Bargraph O Signal x1 4 m GND OTrigger Power Switch E OFF OON O Push ON Slow Edges Node Finder Illegal Framing E Poor Signal ES Push ON w lt ControNet NetChecker TRAFFIC INPUT Low Bat Diagnostic Bargraph Output to Scope O Signal 1 4 m GND OTrigger Power Switch m OFF OON O Push ON Node Finder Push ON ControlINet NetChecker Rockwell Rockwell Allen Bradley Automation Allen Bradley Automation Bargraph Global Mode Bargraph Node Level
17. ly is bad it will appear bad everywhere on the network The NetChecker can only rely on the signal it receives at one point on the network That is why a network should always be checked at several points Buzzer The Buzzer sounds any time a fault is detected Node Finder and Oscilloscope Output The address MAC ID of the message originator is the only information from a message that can be decoded by the NetChecker This address is compared to the address entered on the two thumbwheels the possible node addresses range from 01 to 99 Depending on the setting of SW3 the comparator either activates the Node On Line status indicator Diagnostic mode or enables the display of the level of signal received from the node Bargraph mode The Node Finder also provides a synchronization signal for viewing the messages from a given node with a digital storage oscilloscope DSO This signal trigger is provided on the 3 pin connector on the left side of the NetChecker The connector pin labeled Signal delivers the signal from the network via an input transformer with a 1 4 isolation stage The NetChecker ground is provided on the center pin The Trigger signal rises at the end of the transmission of the originator address MAC ID if the address matches the number on the thumbwheels set the oscilloscope trigger to rising edge We recommend fastening small pieces of solid copper wire 1 inch long 18 22 AWG to the terminal block for attachme
18. ming is reported e Itis not affected by the threshold setting e The fault is reported everywhere on the network but the bargraph shows correct signal levels In this case try to identify the node with the Node Finder Check the Node On Line status indicator for each of the known addresses of your network The faulty node is signalled by the Node On Line status indicator turning red Slow Edges Slow Edges has the following indications Status Indicator State TRAFFIC Green Slow edges Blinking red Illegal Framing May also be blinking red Poor signal Quality May also be blinking red Pass Fail Yellow or red Buzzer Sounds Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 17 Slow Edges is generally reported when a weak input signal with poor slow rising falling edges is identified This may occur with signals received from remote stations on long networks with a large number of nodes In this case Slow Edges detection is not influenced by the threshold setting on SW3 Make sure that the cable length versus number of nodes meets the ControlNet specification Check for possible high signal attenuation caused by inadequate coaxial media used for the trunk cable or segments High resistance at the contact points of the BNC connectors on the trunk cable may add abnormal signal attenuation A small amount of Slow Edges can be tolerated on long networks provided that the
19. ned the following results the NetChecker did not detect any problem at the testpoint Status Indicator State TRAFFIC Green Pass Fail Green Fault All Off for all thresholds L M H Buzzer Does not sound Bargraph indication Within range of 2 6 Refer to the table in the following section to determine the overall state of your network Rockwell Automation Publication 1788 UM001B EN P August 2012 14 ControlNet NetChecker Faults and Their Origins The NetChecker checks for Poor Signal Quality Illegal Framing and Slow Edges If a fault is detected when checking in the Diagnostic mode the buzzer will sound and one or more of the three fault status indicators will blink red The detection of Poor Signal Quality and Illegal Framing depends on the threshold setting on SW3 Generally faults that are detected at the L Low threshold level will disappear or be seen less frequently as the threshold is increased However in some cases where the received signal has a low level less than 2 on the bargraph scale faults may appear or their recurrence may increase as the threshold is raised Use the table below as a guideline when evaluating your network Threshold SW3 TJM JH Network quality at the point of test No fault No fault No fault Very clean Fault No fault No fault Clean acceptable Fault Fault No fault May be acceptable after cabling inspection Fault Fault Fault Network needs ins
20. network architecture IMPORTANT Each coaxial segment must be terminated with a 1786 TCAP terminator at each end Effect of Attenuation on Signal Edges 7 000 V D 100 ns DIV Excessive attenuation causes loss of signal e Poor quality coaxial cable Resistance too high Losses in dielectric e Overloaded network Too long trunk segment Excessive number of nodes per segment e Impedance mismatches Rockwell Automation Publication 1788 UM001B EN P August 2012 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical manuals technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools You can also visit our Knowledgebase at http www rockwellautomation com knowledgebase for FAQs technical information support chat and forums software updates and to sign up for product notification updates For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect programs For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com support support Installation Assistance If you experience a problem within the first 24 hours
21. nt of the oscilloscope s probes preferably high impedance 10 1 probes Also remember that the peak to peak voltage on the Signal pin is one fourth the peak to peak voltage on the network Bargraph Mode When slide switch SW3 is in its rightmost position the Bargraph mode is enabled and status indicators 1 to 7 function as a maximum minimum signal level indicator This indicator displays the level of the signal from the node selected by the Node Finder When the Node Finder is set to 00 it provides a global view of the signal level maximum and minimum of all the messages seen on the network In Bargraph mode the Poor Signal Quality and Illegal Framing detections are performed with the threshold defaulted to M medium If Poor Signal Quality or Illegal Framing are detected they are signalled only by the buzzer The Slow Edges detection is not performed in Bargraph mode Rockwell Automation Publication 1788 UM001B EN P August 2012 10 ControlNet NetChecker Bargraph Scale The Bargraph is not a precision voltmeter The status indicators are numbered from 1 lowest peak to peak voltage or Vpp to 7 highest Vpp Also note that the scale is not linear The following table shows the approximate peak to peak voltages indicated by each status indicator Status Indicator Vpp Level Status Indicator GREEN if Status Indicator RED if 7 9 5 No green state Signal level gt 9 5Vpp 6 7 5 7 5Vpp lt signal level lt 9 5Vp
22. p No red state 5 5 75 5 75Vpp lt signal level lt 7 5Vpp 4 4 5 4 5Vpp lt signal level lt 5 75Vpp 3 3 25 3 25Vpp lt signal level lt 4 5Vpp 2 2 2Vpp lt signal level lt 3 25Vpp 1 0 75 0 75Vpp lt signal level lt 2Vpp Signal level lt 0 75SVpp Status indicator 7 will turn red if the signal level exceeds 9 5Vpp Otherwise it will be off Status indicator 1 can have one of three states red if the signal input is less than 0 75Vpp green if the signal input is between 0 75 and 2Vpp and off under any other condition Status indicators 2 6 can only be green or off Only two status indicators on the bargraph can be turned on at the same time one indicating the maximum level and the other indicating the minimum If the maximum and the minimum levels are the same only one status indicator will turn on View a Node Signal Level in Bargraph Mode To check the signal level from a particular node set SW3 to the rightmost position and set the address of the node on the Node Finder thumbwheels Note that the bargraph indication is the level seen at the point of test so a low or high indication does not necessarily mean that the node itself is faulty If all of the status indicators are off the NetChecker does not detect any signal from a node having the address entered IMPORTANT In networks in which repeaters are used the level read on the bargraph for nodes that are behind a repeater such as on another trunk cable t
23. pection severe problem on the network The third type of fault detection Slow Edges checks for a low signal with poor rising and falling edges caused by an abnormal attenuation of the signal This fault detection is not dependent on the threshold setting of SW3 When analyzing a network the NetChecker indication may differ from one point of test to another A network may be acceptable if the NetChecker reports faults with a low or even medium threshold setting at some points but a network that exhibits faults everywhere should be inspected Try to evaluate residual problems using the Node Finder and an oscilloscope to ensure that the signals meet the ControlNet requirements Examine the nodes that are reported faulted the Node On Line status indicator appears red or yellow and analyze the messages the faults may come from signal distortion signal weakness poor edges noise or signal reflections TIP Remember that the purpose of the NetChecker is to alert for possible problems with network cabling and that its sensitivity is greater than required by the ControlNet specification Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 15 Poor Signal Quality Poor Signal Quality has the following indications Status Indicator State TRAFFIC Green Slow Edges May also be blinking red Illegal Framing May also be blinking red Poor Signal Quality Blinking red Pass Fail Y
24. ring the NetChecker powered by an AC wall adapter can be installed temporarily or permanently on the network The NetChecker will signal immediately any degradation of the signal quality at the media level even if the network is still performing correctly The NetChecker should be set in Diagnostic mode Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 21 Waveform Examples This section shows the types of waveforms that may be seen on a ControlNet network Ideal Transmitted Packet on ControlNet Network as seen at transmitting node 5 Mbps Manchester Encoded Transmit Level 8 2Vpp 1 3V iy ene a V One Bit Time 200nS Waveform on Cable Ideal Received Packet on ControlNet Network as seen at receiving node 40nS max jitter Receive Mask Rockwell Automation Publication 1788 UM001B EN P August 2012 22 ControlNet NetChecker Typical Waveforms Good Signal Small Amount of Reflection Remote Station 100 nS D i Example of Waveform Seen When Network Is Improperly Terminated ee Le AY eae Deine Sere 2 000V D 500 ns DIV Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 23 Impedance mismatches cause reflections on the media e Network not correctly terminated e Impedance of coaxial cable not equal to 75 Q e High resistance of contact in connectors e Incorrect
25. s These faults are the result of large impedance mismatches on the network This fault detection is dependent on the threshold settings L M and H on SW3 e Slow Edges status indicator Blinks red when the NetChecker has identified a weak signal with poor rise fall times This may result from high signal attenuation caused by bad coaxial cable excessive cable length or an overloaded network This fault detection is not dependent on the threshold settings on SW3 e Node On Line status indicator Turns green if a node having the address entered in the Node Finder is detected on the network and the signal received from it is good The status indicator will turn red or appear yellow rapidly flashing red and green if the messages received from this node exhibit one or more of the faults signaled by the fault status indicators Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 9 Note that when the Node On Line status indicator is red it generally does not mean that the node itself is bad but rather that the signal received by the NetChecker from this node is affected by a problem on the network An impedance mismatch may cause some nodes to be received as good Node On Line status indicator green while others are received as bad Node On Line status indicator red Testing at another point on the network will show that nodes that were received as bad are now received as good or vice versa Ifa Node real
26. se the defects caused by a single impedance mismatch are variable along the cable and are also related to the node that is transmitting a network segment should be tested at several points For example test near the two ends of the cable and at one or more points along the cable depending on the cable length and the number of nodes If repeaters are used every segment between repeaters should be checked On a redundant network check both of the cables The NetChecker can indicate that there is a problem on the tested network but it cannot indicate where the problem originated However it can help to locate intermittent defects as described in Additional Tips on page 20 Keep in mind that the source of a problem may be far away from the point of analysis TIP Abad diagnostic result does not necessarily mean that the network is not functional However it may require a closer check of system components such as wiring component quality connectors and impedance matching Network Diagnostics This section describes procedures for evaluating the quality of the ControlNet network How to Begin Checking Your Network Start checking in Diagnostic mode You can start checking at any of the three threshold settings L M and H but be sure to perform the test at all three settings Then set SW3 to the bargraph rightmost position and examine the global signal level on the network by setting the Node Finder thumbwheels to 00 If you obtai
27. t 2012 ControlNet NetChecker 3 European Communities EC Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions and has been designed and tested to meet the following directive EMC Directive This product is tested to meet the Council Directive 89 336 EC Electromagnetic Compatibility EMC by applying the following standards in whole or in part documented in a technical construction file e FEN 50081 2 EMC Generic Emission Standard Part 2 Industrial Environment e EN 50082 2 EMC Generic Immunity Standard Part 2 Industrial Environment This product is intended for use in an industrial environment Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resource Description Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Rockwell Automation Publication 1788 UM001B EN P August 2012
28. teries Battery life 6 hours continuous use Accessories 3 pin plug connector to fit in the oscilloscope output BNC male to BNC female coaxial cable 1 meter long BNCT connector e User Manual 1788 UM001 Agency certification when product or packaging is so marked CE e EN 55011 Radiated Emission Class A e ENV 50204 Radiated immunity from digital radio e IEC 1000 4 2 ESD susceptibility e IEC 1000 4 3 Radiated immunity e IEC 1000 4 4 EFT B immunity e IEC 1000 4 6 conducted RF immunity Rockwell Automation Publication 1788 UM001B EN P August 2012 ControlNet NetChecker 7 TRAFFIC Status Indicator This bi color status indicator at the top of the instrument has two functions e Green network activity When the NetChecker is connected to an active network and powered on this status indicator will turn green to indicate there is activity on the network Only messages in which a Start Delimiter is detected in the header and thus are considered valid can cause this status indicator to turn green e Red low battery If the batteries are low the status indicator will turn red whether or not the tool is connected to a network Modes of Network Analysis The NetChecker offers two modes of analysis to evaluate a network e Diagnostic mode Provides a global network evaluation It is selected when slide switch SW3 is in the L M or H position e Bargraph mode Provides a quick view of the signal
29. the high amount of distortion In cases where the received signal has a low level less than 2 on the Bargraph scale with distortion and or poor edges the faults may appear or their recurrence may increase as the threshold is increased Make sure that the cable length versus number of nodes does not exceed the ControlNet specification Check for possible high signal attenuation caused by inadequate coaxial media used for the trunk cable or segments High resistance at the contact points of the BNC connectors on the trunk cable may also add abnormal signal attenuation Rockwell Automation Publication 1788 UM001B EN P August 2012 16 ControlNet NetChecker Illegal Framing Illegal Framing has the following indications Status Indicator State TRAFFIC Green Slow Edges May also be blinking red Illegal Framing Blinking red Poor signal Quality May also be blinking red Pass Fail Yellow or red Buzzer Sounds Illegal Framing occurs if short messages or short between message gaps have been detected Illegal Framing detection is dependent on the threshold setting SW3 Generally recurrence decreases as the threshold is made higher This fault is often reported along with Poor Signal Quality Illegal Framing most likely indicates a high level of signal reflections on the network see previous section but can also be caused by a faulty node A faulty node can be suspected in these scenarios e Only Illegal Fra