Home

Data sheet DB EN IB IL 24 DO8/HD-PAC

image

Contents

1. Pkt IB IL SCN 8 2726337 10 IB IL FIELD 2 2727501 10 IB IL PD GND PAC 2862990 1 FLKM 14 PA INLINE DIO8 2900889 1 Type Order No Pcs Pkt ILSYS INST UME DB GB IBS SYS ADDRESS 2 12 2 mm 119 8 mm 71 5 mm Housing dimensions Green 60g With connector Process data mode with one byte 25 C 55 C 25 C 85 C 10 95 according to DIN EN 61131 2 10 95 according to DIN EN 61131 2 70 kPa 106 kPa up to 3000 m above sea level PHOENIX CONTACT 3 General data Air pressure storage transport Degree of protection Protection class Connection data Name Type of connection Conductor cross section solid stranded Conductor cross section AWG Interface Inline local bus Type of connection Transmission speed Power consumption Segment supply voltage Us Current consumption from Us Communications power UL Current consumption from UL Power consumption Power loss Digital outputs Number of outputs Type of connection Connection method Output voltage Maximum output current per channel Maximum output current per device Nominal load ohmic Nominal load inductive Nominal load lamp Signal delay when switching on an ohmic nominal load Signal delay when switching on an inductive nominal load Signal delay when switching on a lamp nominal load Signal delay when switching off an ohmic nominal load Signal delay when switching off an inductive nominal load Signal
2. bus and logic voltage Status of the outputs 1 3 2 3 Signal output OUT 5 OUT 6 Pink 1 4 2 4 Signal output OUT 7 OUT 8 Function identification 7985 _en_02 PHOENIX CONTACT 7 IB IL 24 DO8 HD PAC 9 Connection notes and examples The actuators can also be connected via external busbars Ensure that GND of the actuators and GND for Us have the same potential When connecting the actuators observe the assignment of the terminal points to the pro cess data NOTE Malfunction GND of the actuators and GND of the supply voltage Us which supply the actuators must have the same potential The simplest way to meet this requirement is to use the IB IL PD GND PAC terminal Wire the GND connections for the ac aA tuators to these terminals In this way they are connected with the potential jumper GND of the Inline station Figure 5 Typical connection of actuators when using ex IB IL 24 DO8 HD PAC_IBIL PD GND PAC ener eueeale Figure 4 Typical connection of actuators when using the IB IL PD GND PAC terminal 7985 _en_02 PHOENIX CONTACT 8 IB IL 24 DO8 HD PAC 10 Application examples 11 Process data IB IL 24 DO8 HD PAC Assignment of the terminal points to the output process IBS IL 24 BK T U PAC IB IL PD GND PAC data Byte Bit Byte Byte 0 view Bit 7 j6 5 4 3 j2 j1 o 1 1 Assign Terminal 2 4 1 4 2 3 1 3 2 2 1 2 2 1 ment point signal Status indi LED 7 5
3. 4 3 2 1 cator For the assignment of the illustrated byte bit view to your INTERBUS control or computer system please refer to the DB GB IBS SYS ADDRESS data sheet Figure 6 Connection of contactors when using the IB IL PD GND PAC terminal Figure 7 Connection of contactors when using external busbars 7985_en_02 PHOENIX CONTACT GmbH amp Co KG 32823 Blomberg Germany Phone 49 0 5235 3 00 9 PHOENIX CONTACT P O Box 4100 Harrisburg PA 17111 0100 USA e Phone 717 944 1300 www phoenixcontact com
4. delay when switching off a lamp nominal load Maximum operating frequency with ohmic nominal load Maximum operating frequency with inductive nominal load Maximum operating frequency with lamp nominal load Reaction time with short circuit Reaction time with ohmic overload Behavior at voltage switch off One time unsolicited energy Limitation of the voltage induced on circuit interruption Output voltage when switched off Output current when switched off 7985 _en_02 IB IL 24 DO8 HD PAC 70 kPa 106 kPa up to 3000 m above sea level IP20 Ill IEC 61140 EN 61140 VDE 0140 1 Inline connectors Spring cage connection 0 08 mm 1 5mm 28 2 16 Inline data jumper 500 kbps 24 V DC nominal value max 4A DC 7 5VDC max 45 mA max 0 34 W at UL max 0 62 W 8 Spring cage connection 1 wire 24 V Us 1 V 500 mA 4A 12 W 48 Q 12 VA 1 2 H 50 O 12 W Typ 500 us Typ 100 ms 1 2 H 50 Q Typ 100 ms Typ 1 ms Typ 50 ms 1 2 H 50 QO Typ 1 ms max 300 Hz this switching frequency is limited by the data rate selected the number of bus devices the structure of the bus the software used and the control or computer system used max 0 5 Hz max 8 Hz this switching frequency is limited by the data rate selected the num ber of bus devices the structure of the bus the software used and the control or computer system used ca 1s ca 3s The output follows the power supply with
5. 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min A To achieve electrical isolation between the logic level and the I O area supply these areas from separate power supply units Interconnection 5 V supply outgoing remote bus 7 5 V supply bus logic 7 5 V supply bus logics 24 V supply I O 24 V supply I O functional earth ground of the power supply units in the 24 V area is not permitted see also user manual Approvals For the latest approvals please visit www phoenixcontact net catalog 7985 _en_02 PHOENIX CONTACT 5 IB IL 24 DO8 HD PAC 5 Additional tables 6 Internal circuit diagram Output characteristic curve when switched on typi cal Output current A Differential output voltage Local bus V 0 0 U 0 1 0 02 0 2 0 03 0 3 0 04 0 4 0 06 0 5 0 07 24V U 24V Up Figure 1 Internal wiring of the terminal points Protocol chip Bus logic including voltage conditioning LED status indicator Optocoupler Transistor Digital output Explanation for other used symbols has been provided in the IL SYS INST UM E user manu al DABE 7985_en_02 PHOENIX CONTACT 6 IB IL 24 DO8 HD PAC 7 Local status and diagnostic 8 Terminal point assignment indicators Figure 2 Local status and diagnostic indicators Designa cze Figure 3 Terminal point assignment tion agnostics c voltage Signal output OUT 1 OUT 2 1 2 2 2 Signal output OUT 3 OUT 4 D Green Diagnostics
6. IB IL 24 DO8 HD PAC Inline digital output terminal 8 outputs 24 V DC 500 mA AUTOMATION Data sheet 7985 _ en_02 PHOENIX CONTACT 2011 01 06 1 Description The terminal is designed for use within an Inline station It is used to output digital signals Features Connections for eight digital actuators Connection of actuators in 1 wire technology Nominal current per output 0 5 A Total current of the terminal 4 A Short circuit and overload protected outputs Diagnostic and status indicators This data sheet is only valid in association with the IL SYS INST UM E user manual Make sure you always use the latest documentation It can be downloaded from the product at www phoenixcontact net catalog pe f D OGD OO GD GD 0 GD OO OD contac GD INSPIRING INNOVATIONS IB IL 24 DO8 HD PAC 2 Table of contents 1 DES CUDUO garments meee oy area Pama ream ie cent tweet tm OOO ee EY Bee aE mR npr ce 1 2 Table OF COMP INS reren R E EEE 2 3 qe 21d i ale da aa a a Re Ke Ee ene mete ee 3 4 Be STed alg fers kee tc Cammeeersmeenesecenea Steenetter o ert tire ote Sea ree ere ee ee ree en ee ee ee 3 5 AddiionaltaDle Ssnan a a aaa AR one 6 6 AMernareCuUtdiagr aN aaen a E A E A 6 7 Local status ANd diagnostic indicators ccecccsececeeeeceeeeneeeeeeeeseeeeseeeseueeseeeeseeesueeseeeeaeeesaeeenes 7 8 Terminal point ASSIGNMENT ccccccecsssceseecesseeseseesseeenseeceueesse
7. eeeeeseaeeseeessseeseesenseeesaeensetensenees 7 9 CONNECTION NOTES and examples ccccecccsecccseecceeeceeecceecsuceceuceceeessueesueesaeeesueesaueeseeeseeeesaaes 8 10 Applicalon example Seaan as eileen ces ce cease ee aaa ee es eee 9 11 PrOCOSS 5 2 Rene nen eR ee a a ee ee ee 9 7985 _en_02 PHOENIX CONTACT 2 3 Ordering data Description Inline digital output terminal complete with accessories connector and la beling field 8 outputs 24 V DC 500 mA single wire connection method Accessories Connector for digital 1 2 or 8 channel Inline terminals Plug Adapter Labeling field width 12 2 mm Marking Inline terminal for power distribution GND complete with accessories connector and labeling field connections for GND VARIOFACE front adapter for 8 channel Inline HD modules Plug Adapter Documentation User manual English Automation terminals of the Inline product range Data sheet English INTERBUS addressing 4 Technical data Dimensions nominal sizes in mm 140 5 119 8 Width Height Depth Note on dimensions General data Color Weight Operating mode Ambient temperature operation Ambient temperature storage transport Permissible humidity operation Permissible humidity storage transport Air pressure operation 7985 _en_02 IB IL 24 DO8 HD PAC Type Order No Pcs PKt IB IL 24 DO8 HD PAC 2700172 1 Type Order No Pcs
8. out delay 300 mJ 15 V lt Udemag lt 45 8 V Udemag demagnetization voltage max 1 V max 300 HA PHOENIX CONTACT 4 Digital outputs Behavior with overload Restart frequency with ohmic overload Restart frequency with lamp overload Behavior with inductive overload Reverse voltage resistance to short pulses Resistance to permanent reverse voltage Overcurrent shut down Overload protection short circuit protection of outputs Programming Data Auto restart 400 Hz 400 Hz Output can be destroyed Reverse voltage proof max 500 mA min 0 7 A Zener diode in output chip ID code hex BD ID code dec 189 Length code hex 81 Length code dec 129 Process data channel 8 bits Input address area O bit Output address area 8 bits Parameter channel PCP O bit Register length bus 8 bits IB IL 24 DO8 HD PAC A For the programming data configuration data of other bus systems please refer to the corresponding electronic device data sheet e g GSD EDS PROFIBUS telegram data Required parameter data Need for configuration data 3 Byte 4 Byte Error messages to the higher level control or computer system Short circuit overload of the digital outputs Error message in the diagnostic code bus and display 2 Hz via the LED D on the module Electrical isolation isolation of the voltage areas 5 V supply incoming remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 500 V AC 50 Hz 1 min

Download Pdf Manuals

image

Related Search

Related Contents

Philips Incand. refl. Crown mirror lam 40W E14  ASUS T100TAM User's Manual  EA21-3047 明電特高油入力変圧器 三相22~77kV 3  compass plm-4  « La Dépêche du Midi » opte pour une certification ISO - WAN-IFRA  Sistema de coluna sem fios com bateria    Community Edition dieser Ausgabe  Biblioteca Digital  Fiche à télécharger  