Home

T175HP manual - HellermannTyton

image

Contents

1. Buzzer High noise level buzzer LEDs High bright low current LEDs Battery Holder Buzzer Rotary Selector Battery Holder 4 Preparation for Use When unpacked the tester should be inspected for any visible signs of damage and the preliminary checks described in the user manual should be performed to ensure that itis operating correctly Ifthere is any sign of damage or if the instrument does not operate correctly return it to your nearest supplier This instrument is powered by three C type batteries Checking And Proofing The Tester Switch the sensitivity to SELF TEST The buzzer of the Hi Prox should beep and the LEDs should light This indicates that the Hi Prox is operational Verify the working of this unit by selecting 240Vac and place the dome against a low voltage live conductor or rub the dome with a cloth or against an item of clothing as this generates a static DC which triggers the detection of circuit The light and beeper should go on as if alive wire is being approached Approaching the dome neara computer screen or a TV screen not liquid crystal display type should also trigger the tester while on the 240V selection 5 Typical Uses e Identify and check live cables e Check and detect live high voltage cables using extension hot stick e Find fault in flexible cables e Check earth equipment e Service neon lighting e Trace live wires e Check high frequency radiation
2. e Detect residual or induced voltages Broken Wires In Cables Faults in damaged flexible cables are found by applying low voltage to each conductor Earthing the remainder the wires that do not need to be traced Do not earth the live wire so that they can be detected by the Hi Prox and moving the tester along the cable until the change in condition is obtained Flexible cables as used in mining and building industries are readily repairable when the break in the cable is located 6 High Voltage Testing The rotary switch attenuator is used to identify and differentiate various HV live cables The tester must be used in conjunction with along and insulating rod when measuring high voltage kV Non Contact Itis advised that the tester should never come into contact with cables kV as this tester is merely a non contactAC Proximity tester Limitations On The Hi Prox It is recommended that this tester is not used in HV yards of mixed voltages In the presence of mixed voltages the tester can become unreliable Problems can arise when the tertiary circuit of a 275 133 11kV transformer is tested The electric field of the HV and MV bus bars can trigger the detector when it is about 3m above the ground This is common with most of the electric field voltage detectors Users should be aware of it The tester can pick up adjacent circuit to the one being tested and Indicates the wrong information to the user 7 L
3. repair or replace this product we will make a full refund of the purchase price Consult the user manual for proper instruction regarding use of this instrument Our obligation under this warranty is limited to repairing replacing or making refund of this test equipment which proves to be defective within 36 months from the date of purchase This warranty does not apply to any of our products which have been repaired or altered by unauthorized persons in any way In our sole judgement if the stability or reliability of products are injured or which have been subject to misuse abuse misapplication negligence or accident or the serial numbers have been altered defaced or removed this warranty will not apply All warranties implied by law are hereby limited to a period of 36 months and the provisions of the warranty are expressed in lieu of any other warranties expressed or implied The purchaser agrees to assume all liability for any damages or bodily injury which may result from the use or misuse of the product by the purchaser or its user his employees or others and the remedies provided by this warranty are expressed in lieu of any other liability we may have included in incidental or consequential damages We reserve the right to discontinue models at any time or change specification price or design without notice and without incurring any obligation 10
4. TOP HIGH VOLTAGE A C 7 24 Troe PROXIMITY DETECTOR Hellermanniyton HI PROX T175HP Pa YN United States Design Patent US D474 705 S INDEX PAGE Safety PUIG S a tiverie cs bardadsotieeierenieelanendive 01 General DESCripPlON cncscdccrtosetediesceranielenscn 02 Low Voltage Testing ccccceneee 03 Front Panel Layout cccccc eseeeeeee 04 Preparation for USC iwicicsisesncivssadnacsndcateds 05 Checking and Proofing the Unit 05 Typical eer ere eeren 06 Broken Wires in Cables 0 06 High Voltage TeStinGsciccacicccincinauiecd 07 Limitations of the Hi Prox 5 07 Laboratory and Field Test Result 08 Changing Batteries 22 cc0 08 SPS CINCAUONS xgenscidsedsananntncncecededidtamnsines 09 Limited Warranty 10 AN Caution risk of electric shock Caution refer to the user manual Safety Rules The Hi Prox has been designed with safety in mind However no design can completely protect against incorrect use Electrical circuits are dangerous and lethal through lack of caution or poor safety practice The following rules should reduce the danger e Read the user manual carefully and completely before using the tester Fully understand the instructions before using this product Follow the instructions for every test Take all the necessary precautions Do not exceed the limits of this
5. aboratory And Field Test Results Expected test results laboratory testing Range Operated from 240V Variable from 80V or depending on type of source 3 3kV 300V 6 6kV 800V 11kV 1000V 22kV 1500V 33kV 4000V 66kV 7300V 132kV 8000V 275kV 22kV Typical observation of test results made in the field Min Detection MDV as of Range Voltage MDV Line Voltage 11kV 1kV 9 1 22kV 2kV 9 1 33kV 3 1kV 9 4 132kV 12 5kV 9 5 275kV 22 5kV 8 2 Changing Batteries The Hi Prox uses 3 x 1 5V C cells batteries Open the battery cover turn counter clockwise to remove the batteries Ensure polarity is respected 8 Specifications e Detecting Ranges Selection Detects voltage from 240V Variable from 80V or depending on type of source 3 3kV 300V 6 6kV 800V 11kV 1000V 22kV 1500V 33kV 4000V 66kV 7300V 132kV 8000V 275kV 22kV e Operating Temperature 15 C 55 C e Storage Temperature 20 C 65 C e Humidity 93 R H 40 C e Case Height 260mm e Case Width 96mm e Weight Approx 550g Batteries included e Power Source 1 5V C x 3 Alkaline Batteries e Safety Standard EN 61326 1 EN 61000 4 2 EN 61000 4 3 EN 55011 9 Limited Warranty We warrant the product to be free from defective materials or factory workmanship We agree to repair or replace this product with no charge for parts and service if used under normal operation and is a result of manufacturer defects If we are unable to
6. ed CMOS logical level change The self test inserts a voltage on the sensor plate just like if the sensor would pick up a voltage The Hi Prox allows identification of AC voltages from 220Vac to 275kVac The enclosure is made out of industrial grade polyurethane The enclosure can be attached to a link stick The small cylinder part of the Hi Prox fits into most link stick adaptors 2 Low Voltage Testing The Hi Prox works by proximity Physical contact with electrical conductors is not necessary when testing for live lines Its sensor senses the radiated field which surrounds live conductors It is recommended not to touch high voltage wires with the Hi Prox Radiated field strength increases with voltage and decreases quickly with distance or earth shielding The radiated field from a cable of closely bunched conductors supplied by three phase power tends to cancel See Limitations of the Hi Prox on page 9 Detecting distance of a 250Vac single live wire is about 10 cm and with a bunched neutral and earth cable as seenina flexible cable the distance is reduced to 5 cm 3 Front Panel Layout OFF Turn the pick up sensor off Self Test Check if the entire circuitry is working 240Vac 240Vac selection 3 3kV 3 3kVac selection 6 6kV 6 6kVac selection 11kV 11kVac selection 22kV 22kVac selection 33kV 33kVac selection 66kV 66kVac selection 132kV 132kVac selection 275kV 275kVac selection
7. instrument e The Hi Prox must never be in physical contact with any conductor higher than 1kV This is a proximity detector not a detector which works by contact e Always use a fiber glass rod or any authorized stick e Ahigh voltage test is carried out with the tester attached to an operating stick sometimes called links stick e Verify the rotary switch setting before measuring Make sure it is on the correct setting for your application e Always check that the Hi Prox is working before and after the test e Do not touch any exposed wiring connections or other live parts of an electrical circuit This instrument should only be used by a competent suitably trained person who understands this test procedure fully Personnel working with high voltage should be trained regularly 1 General Description The Hi Prox consists of an internal pickup sensor plate a rotary switch as sensitivity selector a sound annunciator high pitch high power buzzer a visual indicator high bright LEDs and three C size batteries The Hi Prox detects AC voltages using the sensor plate The sensor plate collects part of the radiated electric field V M The electric field is seen by the internal circuitry and triggers the input ofa CMOS integrated circuit The integrated circuit charges a capacitor via a diode Once that capacitor reaches a certain level the buzzerand LEDs annunciator are turned ON The trigger level is fix