Home
PAS 153 - Handbuch
Contents
1. MHMARNDOUZ compatible with you PAS 153 PROFIBUS Slave Interface 700 153 1AA03 User Manual Edition 2 19 11 09 HW 1 and FW 1 00 and higher Order number of manual 900 153 1AA03 en Systeme Helmholz GmbH e Hannberger Weg 2 e D 91091 Grofenseebach Phone 49 9135 7380 0 e Fax 49 9135 7380 110 e E Mail info helmholz de e Internet www helmholz de All rights are reserved including those of translation reprinting and reproduction of this manual or parts thereof No part of this manual may be reproduced processed copied or transmitted in any way whatsoever photocopy microfilm or other method without the express written permission of Systeme Helmholz GmbH not even for use as training material or using electronic systems All rights reserved in the case of a patent grant or registration of a utility model or design Copyright 2009 by Systeme Helmholz GmbH Hannberger Weg 2 91091 Grossenseebach Germany Note We have checked the content of this manual for conformity with the hardware and software described Nevertheless because deviations cannot be ruled out we cannot accept any liability for complete conformity The information in this manual is regularly updated When using purchased products please heed the latest version of the manual which can be viewed in the Internet at www helmholz de from where it can also be downloaded Our customers are important to us We are always glad to receive sugge
2. ff The PAS 153 module works according to DP VO and supports baudrates of 9 6 Kbaud to 12 Mbaud The baudrate is detected automatically 3 2 Connections Behind the protective flap on the front of the module you will find the connectors for the power supply and a SUB D female connector for the Profibus Behind the transparent flap you will find an 8 pole DIL switch for address setting PAS 153 PAS 153 3 3 LED displays The PAS 153 module has three LEDs for indicating its operating status These are labeled SF lights up red BF lights up red and ON lights up green The meaning of the LEDs for diagnostics is described in Section 4 3 on page 16 3 4 Accessories Manual German English Profibus connector 90 Profibus connector 90 with PG conn socket Profibus connector 35 Profibus connector 35 with PG conn socket Profibus connector with axial cable outlet Insulation stripping tool for Profibus Compact repeater Repeater for MPI and Profibus 900 153 1AA03 700 972 0BA12 700 972 0BB12 700 972 OBA41 700 972 OBB41 700 972 0CA12 700 972 6AA00 700 972 0RB12 700 972 0AA02 13 14 4 Configuration 4 1 Hardware configurer The PAS 153 module is integrated into the programming software of the PLC via a GSD file This integration is explained below using the Siemens STEP7 programming software To be able to use the PAS 153 in the hardware configuration the GSD file must
3. so then error or the diagnosis diagnosis in the corresponding digital or analog module ON FLASHING ON Difference between Check the the actual and configuration in planned the hardware configuration configurer 16 PAS 153 PAS 153 se oF oN weaning Lou baudrate search Causes Bus communication via PROFIBUS DP to the PAS 153 has been interrupted OFF FLASHING ON PAS 153 is Check the incorrectly Profibus address parameterized on the PAS 153 there is not data and in the exchange between hardware the DP master and configurator the PAS 153 Note The Causes Profibus address Configured and set of the PAS 153 Profibus addresses do will only be not match applied after the Faults on the bus next power reset Check cable lengths with respect to baudrate Check setting of the terminating resistors OFF ON ON No connection to Check the bus the DP master structure connectors and cabling 17 D The Profibus diagnosis can contain multiple module error messages at the same time 18 4 4 Error diagnosis using Profibus diagnostics 4 4 1 Structure of the Profibus diagnosis If the diagnostic alarms of the PAS 153 module and the digital and analog modules are enabled and a digital or analog module detects an error the PAS 153 module outputs a Profibus diagnosis The detected errors are entered there as a channel related diagnostic messages At the same time the S
4. AO 8x 0 10V 20mA 6ES7 332 5HFOO AO 4x 0 10V 20m lt A 15Bit 6ES7 332 7NDO AO 4x 20mA 6ES7 332 5RDOO AI 4x O 10V 20mA AO 2x 0 10V 20mA 6ES7 334 OCEO AI 4x 0 10V 20mA PT100 AO 2x 0 10V 20mA 6ES7 334 0KEOO AI 4x O 10V 20mA AO 4x 0 10V 20mA 4 8 6ES7 335 7HGO1 Modules not supported Typ Siemens Systeme Helmholz CAN 300 CAN 300 PRO 700 600 CANxx AI 8x Thermocouple 6ES7 331 7PF O AI 8x 0 10V 20maA 16Bit 6ES7 331 7NF10 FM modules XXX CP modules XXX 4 9 Restricted use For an extension with more than 8 modules the PAS 153 700 153 1AA03 needs digital and analog input output modules from Systeme Helmholz GmbH with a hardware release similar or higher 30 otherwise the maximum extension works only with 8 or less modules PAS 153 5 Further Information 5 1 Technical data Order number PAS 153 Dimensions Weight Permissible temperature range During storage During operation Profibus interface Type Transmission rate Protocol Pin Power supply Voltage Current consumption Backplane bus Output voltage Output current Addressing range Number of modules Special features Quality assurance Maintenance 700 153 1AA03 116 x 40 x 125 mm L x W x H Approx 280 g 20 C to 85 C 0 C to 40 C for vert mounting 0 C to 60 C for horiz mountin
5. image For error diagnostics of the PAS 153 in the PLC the usual system modules can be used For PLCs of the Simatic S7 range for example the diagnostic alarm OB OB82 and the module rack failure OB OB86 are supported PAS 153 PAS 153 4 7 Modules supported The PAS 153 module supports all digital input output modules from Systeme Helmholz and also numerous modules of the same type from other manufacturers The list of modules supported is constantly expanding Please inquire about the module you want to use if it is not on the list 4 7 1 Digital Typ Siemens Systeme Helmholz DI 16x24V DC 6ES7 321 1BHO 700 321 1BH0O2 DI 16x24V DC 0 05ms input delay 6ES7 321 1BH10 DI 16x24V DC source input 6ES7 321 1BH50 700 321 1BHSO DI 16x24V DC diagnostic 6ES7 321 7BHO 700 321 7BHO1 DI 32x24V DC 6ES7 321 1BL00 700 321 1BLOO DI 8x48 125V DC 6ES7 321 1CFOO DI 16x24 48V DC 6ES7 321 1CHO DI 16x48 125V DC 6ES7 231 1CH20 DI 16x120V AC 6ES7 321 1EHO DI 32x120V AC 6ES7 321 1ELOO 700 321 1ELOO DI 8x230V AC 20pol 6ES7 321 1FFO DI 8x230V AC 40pol 6ES7 321 1FF10 DI 16x230V AC DI 4x24V NAMUR 6ES7 321 1FHOO 6ES7 321 7RDOO 700 321 1FHOO DO 8x24V DC 2A 6ES7 322 1BFO 700 322 1BFO1 DO 16x24V DC 0 5A 6ES7 322 1BHO 700 322 1BH0O1 DO 16x24V DC 0 SA Highspeed 6ES7 322
6. using Profibus dLagmostics 18 Structure of the Profibus diagnosis 00 0 0 eee eeeeeeeee 18 Standard diagnostic information station status 19 Code related diagnostics ee ceeeceeeceeeceeeceeeceeeeeeeeeeees 20 Mod le Status ewe ak kaka aka ke ra kn di en enan kk ae kak ka kk maces 21 Channel related diagnosis ssessseeeeeeeeeeese eese eess resser 22 Ala ES 605 otal Kee a nate 23 Address EEN 24 3 4 6 4 7 4 7 1 4 7 2 4 8 4 9 S 1 5 2 5 3 ProgtaMMiNg ee wae aco Raa Syn ra eau YEARS 24 MOCUIES SUP P TE DE 25 Metal la ka e iere ie ren n n Eed 25 PMA OG EE 26 Modules not supported ec eee eeeeeesseseeeeeeeeeeeeesneaeees 26 R stticted TE 26 Further Information skkekKRKKERK ERR EERK ERR EERREEEER ERKENNEN 27 Technical Cate EEN 27 Pin ASSIS TAM el beat pe cvs ap oan eae e n oak ko kn EEES 28 Further GOCUMENTATON yi sa ga e gesb eguge ergeet kat 28 PAS 153 PAS 153 1 Safety Information For your own safety and for the safety of others always heed the safety information given here The safety information indicates possible hazards and provides information about how you can avoid hazardous situations The following symbols are used in this manual S Caution indicates hazards and sources of error D l Gives information A Hazard general or specific Danger of electric shock 1 1 General The PAS 153 module is only used as part of a complete system S The operator of a mac
7. 1BH10 DO 32x24V DC 0 SA 6ES7 322 1BLOO 700 322 1BLOO DO 8x120V 230V AC 20pol 6ES7 322 1FFO DO 8x120V 230V AC 40pol 6ES7 322 5FFOO DO 16x120V 230V AC 0 5A 6ES7 322 1FHOO DO 16x120V AC 0 5A 6ES7 322 1EHO DO 32x120V AC 1A 6ES7 322 1ELOO DO 8xRelais 2A 6ES7 322 1HFO 700 322 1HFO1 DO 8xRelais 5A 6ES7 322 1HF10 700 322 1HF10 DO 8xRelais 5A 6ES7 322 1HF20 700 322 1HF20 DO 16xRelais 8A 6ES7 322 1HHO 700 322 1HHO1 DO 8xRelais 5A 6ES7 322 SHFOO DI DO 8x24V DC 6ES7 323 1BHO 700 323 1BHO1 DI DO 16x24V DC 6ES7 323 1BL0 700 323 1BLOO DI 8x24V Dx 8x24V 6ES7 327 1BHOO Dummy module 20pol 6ES7 370 0AA0 700 370 0AA01 Dummy module 40pol 700 370 0AL01 25 4 7 2 Analog Typ Siemens Systeme Helmholz AI 2x 0 10V 20mA PT100 6ES7 331 7KBO AI 8x 0 10V 20mA PT100 6ES7 33 1 1KFO 700 331 1KFO1 AI 8x 0 10V 20mA PT100 6ES7 33 1 7KFO AI 4x PT100 700 331 PT100 AI 8x 0 10V 700 331 0V010 AI 8x 20mA 700 331 4MA20 AI 8x 0 10V 20mA 14Bit 6ES7 331 7HFOO AI 4x 20mA 6ES7 331 7RDOO AI 8x Thermocouple 4x PT100 6ES7 331 7SFOO AI 8x 0 10V 20mA ext Resolution 6ES7 331 7NFOO AO 2x 0 10V 20mA 6ES7 332 5HBO 700 332 SHBO1 AO 4x 0 10V 20mA 6ES7 332 5HDO 700 332 5HDO1
8. 3 2 1 0 Meaning of 1 DP slave must be re parameterized and re configured Slave cannot provided valid useful data e g during start up Always 1 Response monitoring activated Module has received a freeze command Module has received a sync command DP slave not contained in the master parameter set DP slave has been removed from the master parameter set Byte 2 Bit 7 6 5 4 3 2 1 0 Meaning of 1 Reserved always 1 There are more channel related messages than can be stated in the diagnostic telegram 19 4 4 3 Code related diagnostics Bytes 6 to 8 contain the code related diagnosis 6 s M bB R h Jo 0 1 0 0 0 0 1 1 Length of the code related diagnostic information in this case 3 bytes Code related diagnosis available Byte 7 7 65 43 2 1 0O Entry for module in slot 1 Byte 8 7 6 5 4 3 2 1 0 Entry for module in slot 10 11 12 13 14 15 16 The bit assigned to slot in question is set to 1 if there is no module in it there is a non configured module in it the module in question has reported a diagnostic alarm 20 PAS 153 AAA Module status The module status signals the status of the configured module
9. F LED of the PAS 153 module lights up The Profibus diagnosis has the following structure ByteNo No __ Meaning 0 T Station status 1 to 3 3 see Section 4 4 2 3 Master PROFIBUS address 4 High byte of the manufacturer ID code in this case OXOB for Helmholz 5 Low byte of the manufacturer ID code in this case OXED for Helmholz Code related diagnosis 8 see Section 4 4 3 9 Module status 16 see Section 4 4 2 17 Channel related diagnosis 18 3 bytes per error message 19 see Section 4 4 5 any other necessary channel related diagnoses each with 3 bytes x up to max Alarms only 1 alarm possible per slave last byte 29 b tes diagnostic telegram max 244 y see Section 4 4 6 The maximum length of the diagnostic telegram of the PAS 153 module is 244 bytes PAS 153 PAS 153 4 4 2 Standard diagnostic information station status The first 3 bytes of the diagnostic telegram contain the station status information Byte O Bit 7 6 5 4 3 2 1 0 Meaning of 1 DP slave not responding DP slave not ready Configuration error External diagnosis available Requested function is not supported by the slave Invalid response of the slave Slave type does not match the configuration Slave has been parameterized by another DP master Byte 1 Bit 7 6 5 4
10. and 60 C for horizontal installation must be complied with to ensure reliable operation 2 1 Mounting orientation The PAS 153 module can be installed with any orientation Permissible ambient temperature e for vertical mounting from 0 C to 40 C e for horizontal mounting from 0 C to 60 C Vertikaler Aufbau Horizontaler Aufbau CHE IZ Wm Die Stromversogung ist immer wie folgt anzuordnen bei horizontalem Aufbau links lt bei vertikalem Aufbau unten 2 2 Minimum clearance Minimum clearances must be observed because Non observance of the minimum distances can they ensure sufficient cooling of the module it is then possible to insert and remove the PAS 153 module without having to remove other system components there is enough space to connect existing connectors and contacts using standard commercial type accessories there is room for any necessary cable routing it increases the mounting height of the module rack to 185 mm although the minimum spacing of 40 mm must still be observed destroy the module at For the PAS 153 module a minimum clearance of 40 mm must be high ambient left above and below and 20 mm at the sides temperatures The following diagram shows the minimum spacing between the module racks and between these and any adjacent cabinet walls equipment cable ducts etc for S7 300s mounted i
11. be installed once First copy the GSD file named HELMOBED GSE supplied to any location on your hard disk Then choose the Install GSD files function from the Options menu in the hardware configuration of STEP7 go to the directory to which you copied the file and then select the file there The information about the PAS 153 module is now added to the selection catalog of the hardware configurer ES HW Config SIMATIC 300 Configuration PAS153 DER ak Station Edit Insert PLC View Options Window Help Des2h S Be dw MO Wry Find PROFIBUS 1 DP Mastersystem 1 E a IR CPU 315 2 DP Profile Standard LES WE PROFIBUS DP Additional Field Devices General Drives Switching Devices Sa PAS 15 28 1 0 HELMHOLZ gn DP CAN Koppler PAs153 Bm PAS 153 D Universal module 700 321 18H02 DI 16x24VDC 700 321 1BL00 DI 32x24YDC 700 321 1BH50 DI 16x24VDC Miles 700 321 7BHO1 DI 16x24VDC Alarm 700 321 1FHOO DI 16x1204 230VAC 700 321 1ELOO DI 32x120VAC Order Number Designatic Address Q Address Comment 700 322 1BH01 DO 16 24VDC 0 54 700 322 1BL00 DO A 4 7 700 322 1BLO0 DO 32x24VDC 0 54 700 322 18L00 DO E 8 11 700 322 1BF01 DO 8x24VDC 24 700 323 1BL00 DI DO 16x24VDC L 12 13 700 322 1HFO1 DO BxRelay 2A 700 323 1BL00 DI DO 16x24VDC W 14 15 700 322 1HF10 DO 8xRelay 54 700 322 1HF20 DO BxRelay SA 700 322 1HHO1 DO 16xRelay 84 700 323 1BHO1 DI DO 8x24VDC 700 323 1BL00 DI DO 16
12. does not influence the module status Important The diagnostic alarm must be enabled for every module The maximum number of channel related diagnoses is limited by the maximum total length of the Profibus diagnostic telegram of 244 bytes The length of the Profibus diagnostic telegram depends on the number of currently available channel related diagnoses Note Errors concerning all channels of a module for example if the power supply of the module is missing are only mapped on channel 0 in the channel related diagnosis This keeps the number of channel related diagnoses low and avoids a flood of diagnoses Byte 17 7 6 5 4 3 2 1 0 1 0 X X X X X X Code number of the module supplying the channel related diagnosis 000000 to 001111 Example Slot 1 has code number 000000 Slot 5 has code number 000100 LR cl Channel related diagnosis available Byte 18 7 6 5 4 3 2 1 0 x x x x A x x x Number of the channel or the channel group supplying the diagnostic information 000000 to 111111 01 Input 10 Output 11 Input output Byte 19 7 6 5 4 3 2 1 0 x x x x A x x x Error type according to Profibus standard Channel resolution 001 1 bit 010 2 bits 011 4 bits 100 1 bytes 101 1 word 110 2 words PAS 153 PAS 153 4 4 6 Alarms The alarm part of the diagnostic telegram includes up
13. found between the planned and actual configuration the PAS 153 module starts data exchange with the DP master Exchange of useful data with modules without a planned actual deviation is possible The SF LED lights up red 2 Start up deactivated If a difference is found between the planned and actual configuration the PAS 153 module does not start data exchange with the DP master A configuration error is detected and the SF LED lights up and the BF LED flashes PAS 153 15 4 3 Error diagnosis using the indicator LEDs The PAS 153 module has three LEDs on the front for LEDs see also Section 3 3 An initial diagnosis is possible using the indications shown by these LEDs The LED signals mean BF Jon OFF OFF OFF No voltage applied Switch on ot module or module power supply defective module or exchange the PAS 153 module OFF OFF ON Error free operation Data_Exchange The DP master is in Operate Run OFF OFF FLASHING Error free operation Data_Exchange The DP master is in Clear Stop ON OFF ON Impermissible Set a valid FLASHING Profibus address Profibus address on the PAS 153 1 125 Start up activated if Check the actual config not configuration in equal to planned the hardware config If so then configurer deviation between planned and actual configuration Is the SF LED of a Check the digital or analog digital or analog module also lit If module with
14. g RS 485 9 6 Kbaud to 12 Mbaud autodetect Profibus DP VO acc to EN 50170 Connector SUB D 9 way 24 V DC via 4 way terminal 625 mA typ depending on number and type of modules slotted in 5 V DC on backplane bus 1 A on backplane bus 244 bytes for inputs 244 bytes for outputs max 16 incl max 8 parameterizable according to ISO 9001 2000 Maintenance free no battery rechargeable or non rechargeable 27 28 5 2 Pin assignment a 5 Profibus SUB D conn 9 way DATA B GND 5V DATA A VD IO IN IA A IA TD N ja Pin 24 V 3 way 24V GND Shield 5 3 Further documentation Internet www helmholz de www profibus de Siemens manuals Installing and Wiring the S7 300 S7 400 7 300 Module Data and System Software for S7 300 and S7 400 Profibus DP DPV1 Manfred Popp Hiithig Verlag PAS 153
15. hine system is responsible for observing all safety and accident prevention regulations applicable to the application in question A During configuration safety and accident prevention rules specific to the application must be observed A Emergency OFF facilities according to EN 60204 IEC 204 must remain active in all modes of the machine system The system must not enter an undefined restart A Faults occurring in the machine system that can cause damage to property or injury to persons must be prevented by additional external equipment Such equipment must also ensure entry into a safe state in the event of a fault Such equipment includes electromechanical safety buttons mechanical interlocks etc see EN 954 1 risk assessment A Never execute or initiate safety related functions using an operator terminal Only authorized persons must have access to the modules During configuration safety and accident prevention rules specific to the application must be observed Make sure in the software that uncontrolled restarts cannot occur Before you start installation work all systems must be disconnected from their power source 1 2 Restriction of access The module is an open item of equipment and must only be installed in electrical equipment rooms cabinets or housings Access to the electrical equipment rooms barriers or housings must only be possible using a tool or key and only permitted to personnel havi
16. n several module racks 10 PAS 153 PAS 153 2 3 Mounting of the module on the DIN rail A wall DIN rail bracket is available as an accessory for mounting on flat surfaces or on DIN rails When connecting the bus connector always start with the PAS 153 module Do not plug a bus connector into the last module of the tier Hook on the module 1 slide it up to the left module 2 and click it downward 3 The available accessories are listed in Section 3 4 with the corresponding order numbers 11 i Active backplane bus modules are currently not supported 12 3 System Overview 3 1 Application and function description The PAS 153 Profibus Slave Interface is for linking digital and analog input and output modules to the Profibus DP The module can be mounted on a sectional rail Up to 16 modules can be connected to the PAS 153 including 8 parameterizable modules The PAS 153 is integrated into the hardware configurer of the programming system by a GSD file The PAS 153 interface performs all communication between the modular I O device and the higher level master unit on the Profibus DP The inputs and outputs are assigned to the master during configuration The PAS 153 module supports all digital and analog input output modules from Systeme Helmholz and also numerous modules of the same type from other manufacturers For more details see Section 4 7 Modules supported on page 25
17. ng received instruction or authorization 1 3 Information for the user This manual is addressed to anyone wishing to configure use or install the PAS 153 module It is intended for use as a programming manual and reference work by the configuring engineer It provides the installing technician with all the necessary data The PAS 153 module is for use in a Profibus network only For that reason the configuring engineer user and installing technician must observe the standards safety and accident prevention rules applicable in the particular application The operator of the automation system is responsible for observing these rules 1 4 Use as intended The PAS 153 module must only be used as a Profibus interface as described in the manual 1 5 Avoiding use not as intended Safety related functions must not be controlled using the PAS 153 module alone 1 6 Installation and mounting instructions Installation and mounting must be effected in compliance with VDE 0100 IEC 364 PAS 153 Before you start installation work all system components must be disconnected from their power source i The module can be mounted either vertically or horizontally PAS 153 2 Installation and Mounting Installation and mounting must be effected in compliance with VDE 0100 IEC 364 Because it is an OPEN type module you must install it in a cabinet The maximum ambient temperature of 40 C for vertical installation
18. s and provides more detail with respect to the configuration than the code related diagnosis The module status begins after the code related diagnosis and fills 8 bytes The module status is structured as follows Length of the module status incl byte 9 in this case 8 bytes Code for device related diagnosis 2 Le status Code for status message Byte 11 On Always 0 Byte 12 0H Always 0 Byte 13 7 6 5 4 3 2 1 0 Status mod 1 Status module 2 Status module 3 Status module 4 Byte 14 7 6 5 4 3 2 1 0 Status mod 5 Status module 6 Status module 7 Status module 8 Byte 15 7 6 5 4 3 2 1 0 Status mod 9 Status module 10 Status module 11 Status module 12 Byte 16 7 6 5 4 3 2 1 0 Status mod 13 Status module 14 Status module 15 Status module 16 The displayed status values mean Value Meaning 00 Module OK valid data 01 Module defective invalid data 10 Incorrect module invalid data 11 No module invalid data PAS 153 21 22 4 4 5 Channel related diagnosis The channel related diagnosis provides information about the channel errors of modules and provides details of the code related diagnosis It starts after the module status The channel related diagnosis
19. s x 4 to x 19 Diagnostic data content of records 0 and 1 In the case of process alarms the length of the additional alarm information is 4 bytes Bytes x 4 to x 7 Additional process alarm information If a diagnostic event is already present for channel channel group O of a module there may be a module error in addition to a channel error In this case the entry is made even if diagnostics has not been enabled for channel channel group 0 of the module 23 Addresses 0 126 and 127 must not be set D Process alarms OB40 are not supported via the GSD file 24 4 5 Address setting The PAS 153 module has an 8 pin DIL switch under the transparent front flap that is used to set the address of the module in the Profibus network Switches 1 to 7 are for the following parts of the address Switch 1 2 3 4 5 6 7 position Value when 1 2 4 8 16 32 64 ON The highest permitted Profibus address is 125 Addresses 0 126 and 127 are impermissible The address set on the DIP switch will only be applied after the next restart power ON Switch 8 has no function 4 6 Programming Programming of the PAS 153 module is unnecessary Parameterization data for the modules connected to the PAS 153 are automatically transferred to the Profibus Depending on the PLC system used the I O information of the PAS 153 is automatically taken over into the process
20. stions for improvement and ideas Step and SIMATIC are registered trademarks of SIEMENS Revision history of this document Edition Date Revision 1 17 04 2009 1st version 2 19 11 2009 Restricted use of modules with hardware release smaller 30 PAS 153 Contents 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3 3 1 3 2 3 3 3 4 4 1 4 2 4 2 1 4 2 2 4 2 3 4 3 4 4 4 4 1 4 4 2 4 4 3 4 4 4 4 4 5 4 4 6 4 5 Safety Information 2egeeeedeekee e SEENEN ENEE 7 reet coh a e pa Sa ap Ak e ed ou 7 Restriction OF ACE SI teka ee Ee 8 Information for the uset ae vo so baeo dae sato ciseetestveabacecaseds 8 LISE aS intended ae arn oe aa io a kaa Rk oe jiss 8 Avoiding use not as intended rrerreeoooooroooronosoee 8 Installation and mounting instructions eeeeeereeoee 8 Installation and Mounting ube 9 Mounting orientation Eeer EE ob pas tes teste ee 9 Minimum clearance EE 10 Mounting of the module on the DIN rail 11 e Re 12 Application and function description 12 ONDE LC 12 REES 13 EE EEN ayia epa li det ye dacs sais ne e ek cca le yates e as A A 13 Configuratio M e dada eines 14 ETAT At configure TE 14 Device specific parameters eceeeceeeceeeceeeceeeceeeeeeeeeeees 15 Diag osti AT AT AAA de Ee 15 Processalari EE 15 Start up if the actual configuration is not the planned COMMS ULATION EE 15 Error diagnosis using the indicator LEIe 16 Error diagnosis
21. to 29 bytes and contains additional information about the alarm type and about the cause that triggered the diagnosis The content of the alarm part depends on the alarm type No more than 1 alarm can be signaled per diagnostic telegram The position of the alarm part in the diagnostic telegram depends on the structure of the diagnostic telegram and on the number of channel related diagnoses The alarm part is however always at the end of the diagnostic telegram The alarm part is structured as follows Byte x 7 16 5 4 3 2 1 0 0 0 xX xX xX xX xX xX Length of the alarm part incl Byte x Code for device related diagnosis Byte x 1 7 6 5 4 3 2 1 0 0 x x x X x x x Alarm type 0000001 Diagnostic alarm 0000010 Process alarm Code for alarm Byte x 2 7 6 5 4 3 2 1 0 x x X X X X X X 01 16 slot number of the module supplying the alarm Byte x 3 716 5 4 3 2 1 JO XIXIX IX IX X xX X 00 Process alarm 01 at least one error is present 10 cleared error 11 reserved not used Alarm sequence number B 4 yte Additional information about the type and cause of the alarm Byte x 29 In the case of diagnostic alarms the diagnostic record 1 for SIMATIC S7 e g 16 bytes is transmitted as the additional alarm information Byte
22. x24VDC 700 331 PT100 Al 4xPT100 700 331 0V010 Al 8x0 10 700 331 4MA20 Al 8x4 20m 700 331 1KFO1 Al 8 700 332 5HB01 AD 2 PROFIBUS DP slaves for SIMATIC 7 M7 and C7 distributed rack Ki Press F1 to get Help You will find the PAS 153 module in the catalog under PROFIBUS DP Additional FIELD DEVICES I O HELMHOIZ PAS153 Configuration then continues in the same way as for Profibus stations PAS 153 4 2 Device specific parameters 4 2 1 Diagnostic alarm Enable diagnostic alarm In the case of a module channel error of a digital or analog module a Profibus diagnosis consisting of a standard diagnosis code related diagnosis modules status channel related diagnosis and alarm incl diagnostic record 1 is output Diagnostics alarm disabled In the case of a diagnostic alarm of a digital or analog module no Profibus diagnosis is output 4 2 2 Process alarm Enable process alarm In the case of a process alarm of a digital or analog module a Profibus diagnosis consisting of a standard diagnosis code related diagnosis module status and alarm is output Process alarm disabled In the case of a process alarm of a digital or analog module no Profibus diagnosis is output 4 2 3 Start up if the actual configuration is not the planned configuration 1 Start up activated If a difference is