1.     6  Installation of this equipment shall be carried out by  Suitably trained personnel in accordance with the  applicable code of practice    7  Repair of this equipment shall only be carried out by  the manufacturer or in accordance with the  applicable code of practice    8  The certification of this equipment relies on the  following materials used in its construction    Enclosure  ABS Plastic   lf the equipment is likely to come into contact with   aggressive substances  then it is the responsibility of   the user to take suitable precautions that prevent it  from being adversely affected  thus ensuring that the  type of protection is not compromised        Aggressive substances      e g  acidic liquids or  gases that may attack metals  or solvents that may  affect polymeric materials        Suitable precautions      e g  regular checks as part  of routine inspections or establishing from the  material   s data sheet that it is resistant to specific  chemicals     SPECIAL CONDITIONS FOR SAFE USE  as stated on the  EC Type Examination Certificate SIRA 0O4ATEX2301X     The equipment shall only be supplied via Terminals   w r t   Terminals   from a barrier having a maximum open circuit  voltage Uo that is  lt  28 V and a maximum short circuit current  lo that is  lt  93 mA  where lo is resistively limited  The barrier  shall be ATEX certified by a notified body     The total capacitance connected to terminals   wrt      i e  the  capacitance of the cable plus any other ca
2.    warning signals       The IS A105N sounder is CE marked for  compliance with the European  Explosive Atmospheres Directive  94 9 EC and the European EMC  Directive 89 336 EEC    1  Introduction    The IS A105N is an ATEX and IECEx certified intrinsically  safe sounder which produces a loud warning signal in a  hazardous area  Forty nine first stage alarm sounds can be  selected by internal switches and each one can be externally  changed to a second or third stage alarm sound  The  sounder may be used in all gas groups IIA  IIB and IIC  The  IS A105N sounder may be used in conjunction with an IS   L101L intrinsically safe beacon  allowing a combined audible  and visual alarm to be constructed     2  Description    Fig 1 shows a simplified block diagram of an IS A105N  sounder  The device operates immediately power is applied  to the   and     terminals which are duplicated to allow a  second sounder to be connected in parallel  or for an end of  line monitoring resistor to be installed  The output tone is  defined by the positions of the six internal switches and this  tone can be changed to a second or third stage alarm tone by  connecting terminals S2 or S3 to OV  The tone generator is  crystal controlled to ensure that when two sounders are  started at the same time the output tones remain  synchronised     3  Supply Voltage    The IS A105N sounder has been designed to operate in a  hazardous area from a 24V dc supply via 28V 93mA resistive  ATEX and IECEx certified Zen
3.   and    Power is supplied to the sounder via the   and     terminals  which have the following input safety parameters     Ui   28V   li   93mA  Pi   660mW  Ci 0 Li 0    The IS A105N sounder may be powered from an ATEX  certified Zener barrier or galvanic isolator which have output  parameters equal to or less than 28V  93mA and 660mW  where lo is resistively limited  The cable parameters stated  on the selected Zener barrier or galvanic isolator certificate  must be observed     Up to three IS A105N sounders can be connected in parallel  and powered from a common barrier or isolator  Connecting  two sounders in parallel will reduce the output from each by  about 3dB  Three sounders should only be powered from a  common supply when the maximum supply voltage is  available     4 4 Terminals S2 and S3   When terminals S2 or S3 are connected to OV    terminal  the  sounder output tone changes to the second or third stage  alarm respectively  The input safety parameters for these  terminals are     Ui  li    28V  OmA    Because the permitted input current is zero  these terminals  may only be connected to a diode return barrier  an    sales e2s com    www e2s com    Tel   44  0 20 8743 8880  Fax   44  0 20 8740 4200    Sheet 2 of 6    intrinsically safe relay or a galvanic isolator  all of which must  have been certified by an EC Notified Body  Only diode  return barriers with a voltage drop of less than 0 9V may be  used  Alternatively  these terminals may be connected  directl
4.   o  Q   Co   Ceante    oo T ee Ti  o ST    o   f   IS A105N Sounder    re o Control Drawing for shunt zener  A  MRS_ 17 02 06 diode barrier   diode return barrier     Issue   Appd   Date    Drawn  GU Date  1910 05       1  No revision to drawing without prior FM approval   2  The associated apparatus must be FM approved     3  The associated apparatus manufacturer s Installation drawing must  be followed when installing this equipment     4 Installation should bein accordance with ANSVISA RP12 06 01   Installation of Intrinsically Safe Systems for Hazardous  Classified   Locations  and the National Electrical Code  ANSINFPA 70      5  The resistance between the intrinsically safe ground andthe earth  ground must be less the 1 ohm     6  The Shunt Zener Diode Barrier must be a FM approved  resistively  limited  single channel barrier having parameters less than  or equal  ta  those quoted  and for which the output is nan ignitian capable far  the Class  Division or Zone and Group of use     T  The  S A105N Sounder enclosure has an ingress protection rating  of IF 66  If Suppli d without cable entry devices then me  tallic or plastic  cable glands  or conduit hubs  shall be fitted that provide the required  environmental protection     8  To preventignition of flammable or combustible atmospheres   disconnect power before servicing     9  Substitution of components may impair safety     10  The total capacitance connected to terminals  4 of the sounder   iE  Ceabe plus any Oth
5.  the volume control potentiometer  see Fig 2      10  Servicing    No attempt should be made to repair a faulty IS A105N  sounder  Suspect sounders should be returned to European  Safety Systems Ltd  for repair     11  Guarantee    Sounders that fail within the guarantee period should be  returned to European safety Systems Ltd  It is helpful if a  brief description of the fault symptoms is provided     12  Customer Comments    European Safety Systems Lid  is always pleased to receive  comments from customers about our products and services   All communications are acknowledged and whenever  possible  suggestions are implemented     sales e2s com    www e2s com    Tel   44  0 20 8743 8880  Fax   44  0 20 8740 4200    Sheet 5 of 6    IECEx Certification       The IS A105N Sounder has also been approved to the IECEx  scheme     The installation requirements for IS A105N_ sounders  approved to the IECEx scheme are the same as the  installation requirements for IS A105N sounders approved to  the ATEX directive     Certificate No   ECEx SIR 04 0038X    Marking  Ex ia IIC T4 Ga  Ta    40  C to  60  C     IEC 60079 0 2004 Edition 4  IEC 60079 11 2006 Edition 5  IEC 60079 26 2006 Edition 2    Standards     CONDITIONS OF CERTIFICATION  as stated on the IECEx  Certificate of Conformity IECEx SIR 04 0038X     1  The equipment shall only be supplied via Terminals    w r t  Terminals   from a certified barrier having a  maximum open circuit voltage Uo that is less than or  equal to 28 V a
6. 11001  111001  000101  100101  010101  110101  001101  101101  011101  111101  000011    Second  Stage  Alarm    Tone 2  Tone 17  Tone 2  Tone 6  Tone 3  Tone 7  Tone 10  Tone 2  Tone 15  Tone 7  Tone 2  Tone 4  Tone 15  Tone 4  Tone 2  Tone 18  Tone 2  Tone 2  Tone 2  Tone 2  Tone 2  Tone 2  Tone 6  Tone 29  Tone 29  Tone 2  Tone 26  Tone 2  Tone 7  Tone 2  Tone 26  Tone 26  Tone 2  Tone 38  Tone 36  Tone 35  Tone 9  Tone 34  Tone 23  Tone 31  Tone 2  Tone 2  Tone 2  Tone 2  Tone 38  Tone 47  Tone 46  Tone 49  Tone 26    Tone 5  Tone 5  Tone 5  Tone 5  Tone 20  Tone 5  Tone 5  Tone 5  Tone 2  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 27  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 15  Tone 5  Tone 5  Tone 5  Tone 5  Tone 5  Tone 15  Tone 5  Tone 45  Tone 5  Tone 5  Tone 45  Tone 45  Tone 17  Tone 27  Tone 5  Tone 5  Tone 5  Tone 5  Tone 34  Tone 37  Tone 37  Tone 5  Tone 37       European Safety Systems Ltd  Impress House  Mansell Road  Acton  London W3 7QH sales e2s com Tel   44  0 20 8743 8880  www e2s com Fax   44  0 20 8740 4200    Document No  IS 4501 Issue E 27 11 09 Sheet 4 of 6    7  Electrical System Design For Installation In  Hazardous Areas Using Galvanic Isolators    Galvanic isolators although more expensive than Zener  barriers  do not require a high integrity earth connection  For  small systems where a high integrity earth is not already  available  the use of galvanic isolators often reduces the  overall installat
7. 800Hz   Intermittent 660Hz 150Ns ON  150ms OFF   Alternating 544Hz  100ms    440Hz  400ms      NFS 32 001  Intermittent 660Hz 1 8s ON  1 8s OFF   Sweep 1400Hz to1600Hz up 1s 1600Hz to 1400Hz down 0 5s  Continuous 660Hz   Alternating 554 440Hz   1Hz   Intermittent 544Hz   0 875Hz   Intermittent 800Hz   2Hz   Sweeping 800 1000Hz   50Hz   Sweeping 2400 2900Hz   50Hz   Simulated bell   Continuous 554Hz   Continuous 440Hz   Sweeping 800 1000Hz   7Hz   Continuous 300Hz   Sweeping 660 1200   1Hz  Two Tone Chime   Intermittent 745Hz   Alternating 1000 2000Hz   0 5s     Singapore   420Hz   0 625s   Australian Alert   500 1200HZz 3 75s   0 25s   Australian Evacuate  Continuous 1000Hz   Continuous 2000Hz   Intermittent 800Hz 0 25s ON 1s OFF   Alternating 544Hz  100ms    440Hz  400ms      NFS 32 001  Motor Siren     Slow rise to 1200Hz   Motor Siren     Slow rise to 800Hz   Continuous 1200Hz   Motor Siren     Slow rise to 2400Hz   Intermittent 1000Hz 1s ON  1s OFF   Sawtooth 1200 500Hz   1Hz   D I N   PFEER P T A P   Intermittent 1000Hz 1s ON  1s OFF     PFEER General Alarm  420Hz   0 625s   Australian Alert   500 1200HZz 3 75s   0 25s   Australian Evacuate    Switch  Settings  123456    000000  100000  010000  110000  001000  101000  011000  111000  000100  100100  010100  110100  001100  101100  011100  111100  000010  100010  010010  110010  001010  101010  011010  111010  000110  100110  010110  110110  001110  101110  011110  111110  000001  100001  010001  110001  001001  101001  0
8. er Barriers or Galvanic  Isolators  The sounders may be tested or used in safe areas  without a Zener barrier or galvanic isolator  but at supply  voltages above 16V the internal current limit will function and  therefore it is recommended that they are not operated  continuously with a direct supply greater than 16V     European Safety Systems Ltd  Impress House  Mansell Road  Acton  London W3 7QH    Document No  IS 4501 Issue E 27 11 09    INSTRUCTION MANUAL    IS A105N    intrinsically Safe Sounder       IS A105N Sounder    Volume Control    Tone Selection Switches       Fig 1 Simplified block diagram    4  Intrinsic Safety Certification    4 1 ATEX certificate  The IS A105N sounder complies with the following  standards      EN60079 0 2006   EN60079 11 2007   EN60079 26 2007     EC60079 0 2007  used for guidance in respect of marking      Ex  iG  ExiallC T4 Ga   40  C  lt   Ta  lt    60  C     The EC Type Examination Certificate SIRA O4ATEX2301 X  has been issued by the Notified Body Sira  This confirms  compliance with the European ATEX Directive 94 9 EC for  Group ll  Category 1G equipment  The sounder carries the  Community Mark and subject to local codes of practice  may  be installed in any of the EEA member countries  This  instruction sheet describes installations which conform to  EN60079 Part14 2008 Electrical Installation in Hazardous  Areas  When designing systems for installation outside the  UK  the local Code of Practice should be consulted     1  The certif
9. er Capacitance  Shall not exceed 63nF     Motes        CAUTION   Bonding between conduit connections is not automatic  and must be provided as part of this installation     CAUTION   The clearance between sounder terminals S  and S3 is  less than 4mm     European Safety Systems Ltd     Impress House   2 S Mansell Hoad  Acton    waming signals  London W3 rGH    Drawing No  Computer 3ef  3 4528a ding    D 4528 Sheet 1 of 2       Hazardous  Classified  Lacation Unclassified Location 1  Nao revision to drawing without prior FM approval     Class    Division 1  Groups A  B  C  D    Class    Zone 0  Groups IA  IIB  IIC 2  The associated apparatus must be FM approved     3  The associated apparatus manufacturer s installation drawing must  be followed when installing this equipment     IS5 A105N Sounder  IS Class    Zone 0  AEx ia lC T4   40  C    Ta    60  C     4  Installation should be in accordance with AMSI ISA RP12 06 01   Installation of Intrinsically Safe Systems for Hazardous  Classified     Associated Apparatus   Galvanically Isolated Locations  and the National Electrical Code  ANSINFPA 70    Supply with Entity Parameters     Uo   28W 5  The Galvanically Isolated Supply mustbe a FM approved   lo   Farm resistively limited  single channel supply having parameters less than     Po   G6 Orv ar equal to  those quoted  and for which the output is non ignition    Co   Ceoabe  see note 9  capable for the Class  Division or Zane and Group of use   Lo   Leste         Entity Parame
10. ication marking is as follows     IS A105N Sounder    Il 1G_ Ex ia IIC T4 Ga   40  C  lt  Ta lt    60  C   SIRA 04ATEX2301X    IECEx SIR 04 0038X  C E 0518  IS Class I  Zone 0  AEx ia IIC T4    IS Class l  Division 1  Groups A  B  C  D  Control Drawing No  D 4528  APPROVED Term    w r t  Term    Ui  28V li   93mA  Pi 660mMW Ci 0 Li 0  WARNINGS  Term  S28S3 w r t  Term    Ui 28V li  0mA  To avoid a possible electrostatic Year   Serial No   charge only clean with a damp cloth 09   15000001    To prevent ignition of flammable or combustible  atmospheres  disconnect power before servicing  Substitution of components may impair safety     2 S european safety systems Itd  London W3 7QH UK  www e2s com       sales e2s com    www e2s com    Tel   44  0 20 8743 8880  Fax   44  0 20 8740 4200    Sheet 1 of 6    2  The equipment may be used in zones 0  1 and 2  with flammable gases and vapours with apparatus  groups IIA  IIB  amp  IIC and with temperature classes  T1  T2  T3 and T4    3  The equipment is only certified for use in ambient  temperatures in the range  40  C to  60  C and  should not be used outside this range    4  The certificate number has an    X    suffix  which  indicates that the certificate contains one of more  special conditions for safe use  Those installing or  inspecting the equipment should refer to this section  of the certificate    5  The equipment has not been assessed as a safety   related device  as referred to by Directive 94 9 EC  Annex II  clause 1 5 
11. ion cost and simplifies design     7 1 Single stage alarm   The IS A105N sounder may be powered by any galvanic  isolator having output parameters within the limits specified in  section 4 3  which has been certified Ex ia by an EC Notified  Body  The sounder may be controlled by turning the galvanic  isolator on and off  or by a mechanically activated switch on  the hazardous area side of the isolator     Hazardous Area Safe Area    IS A105N sane  Sounder seer       Power    Fig 6 Single stage alarm using galvanic isolator     7 2 Multi stage alarm   The IS A105N sounder second and third stages may be  activated by using Galvanically Isolated Relays that have  output parameters within the limits specified in section 4 4   which have been certified Ex ia by an EC Notified Body     Hazardous Area Safe Area    Galvanic Isolator  IS A105N    Sounder       Power    Power    Fig 7 Multi stage alarm using galvanic isolated relays    8  Cable Parameters    The maximum permitted cable parameters are as specified  on the certificate of the Zener barrier or galvanic isolator that  has been selected for the installation  Normally the limits are  not restrictive  but care should be taken not to exceed a  capacitive limit of 83nF for installations when very long cables  are used     European Safety Systems Ltd  Impress House  Mansell Road  Acton  London W3 7QH    Document No  IS 4501 Issue E 27 11 09    9  Volume Control    The output level of the IS A105N sounder can be set by  adjusting
12. nd a maximum short circuit current lo  that is less than or equal to 93 mA  where lo is  resistively limited     2  The total capacitance connected to terminals   wrt       i e  the capacitance of the cable plus any other  capacitance  shall not exceed 83nF     3  The equipment has an ingress protection rating of  IP66  however  if it has been supplied without a  cable entry device  then the user shall ensure that  the device that is fitted will provide an ingress  protection that is appropriate to the environment in  which it is installed i e  IP20 or better     4  The enclosure is non conducting and may generate  an ignition capable level of electrosatic charges  under certain extreme conditions  The user should  ensure that the equipment is not installed in a  location where it may be subjected to external  conditions that might cause a build up of  electrostatic charges on non conducting surfaces   additionally  cleaning of the equipment should be  done only with a damp cloth     European Safety Systems Ltd  Impress House  Mansell Road  Acton  London W3 7QH    Document No  IS 4501 Issue E 27 11 09    FM Approval    The IS A105N Sounder has also been FM Listed     Marking  IS Class I  Zone 0  AEx ia IIC T4  IS Class l  Division 1  Groups A  B  C  D    See the Control Drawings D 4528 Sheets 1 and 2 for  installation details and entity parameters     The IS A105N sounders are marked with the certification  requirements for the ATEX  IECEx and FM approvals     IS A105N Sounde
13. nd adjust the internal   volume control to provide the required sound level     f  Replace the front of the sounder and tighten the four     A    screws     6  Electrical System Design For Installation In  Hazardous Areas Using Zener Barriers    6 1 Single stage alarm    Document No  IS 4501 Issue E 27 11 09    lf the control switch is in the positive supply  or the power  Supply is being turned on and off  only a single channel Zener  barrier is required as shown in Fig 3  This circuit may also be  used if the sounder is being controlled by a mechanically  activated switch on the hazardous area side of the barrier     Hazardous Area Safe Area    28V 93mA  Positive        IS A105N  Sounder    Fig 3 Single stage alarm using single channel barrier     If the control switch must be in the negative supply  the circuit  shown in Fig 4 may be used  Any diode return barrier certified  Ex ia by a EC Notified Body may be used  providing its  voltage drop is less than 0 9V     Hazardous Area Safe Area    28V 93mA    1S AION Positive    Sounder         Power  Supply    Fig 4 Single stage alarm using two channel barrier     6 2 Multi stage alarm   Connecting terminal S2 to OV activates the second stage  alarm  and similarly terminal S3 for the third stage alarm  Fig  5 shows how the diode return barriers may be used  If only  two stages of alarm are required the third stage barrier  should be omitted  the 28V 93mA barrier and the single diode  return channel may then be contained in one 
14. nically me oren    S S isolated supply   isolated relay Drawing No  Computer Ret  D 4528b chug    A  MRS  17 02 06      issue   Appd   Date    Drawn  GU Date  19 10 05 installation  D 4528 Sheet 2 of 2       EC DECLARATION OF CONFORMITY    v2       Manufacturer  European Safety Systems Ltd   Impress House  Mansell Road  Acton   i  London  W3 7QH  UK warning signals  Equipment Type  IS A105N    Directive 94 9 EC  Electrical and Mechanical equipment for use in explosive atmospheres  ATEX       Notified Body for EC type Examination  Sira Certification Service  Notified Body No   0518  Rake Lane  Eccleston  Chester CH4 9JN  UK    EC type Examination Certificate  SIRA 04ATEX2301X    Notified Body for Quality Assurance Notification  Sira Certification Service  Notified Body No   0518  Rake Lane  Eccleston  Chester CH4 9JN  UK    Quality Assurance Notification  SIRA 05 ATEX M342  Provisions fulfilled by the equipment  Il 1G Ex ia IIC T4 Ga   40   C  lt  Ta  lt   60   C   Standards applied  EN 60079 0 2006    IEC 60079 0 2007  EN 60079 11 2007  EN 60079 26 2007    Directive 2004 108 EC  Electromagnetic Compatibility Directive  EMC       Standards applied  EN 61000 6 1 2007  EN 61000 6 2 2005  EN 61000 6 3 2007  EN 61000 6 4 2007    The standards EN 60079 0  2006 and EN 60079 11 2007 are no longer harmonized  The requirements of these  standards have been checked against the harmonized standards EN 60079 0 2009 and EN 60079 11 2012 and there  were no major technical changes affecting 
15. pacitance  shall  not exceed 83nF     The enclosure is non conducting and may generate an  ignition capable level of electrosatic charges under certain  extreme conditions  The user should ensure that the  equipment is not installed in a location where it may be  Subjected to external conditions that might cause a build up  of electrostatic charges on non conducting surfaces   additionally  cleaning of the equipment should be done only  with a damp cloth     The equipment has an ingress protection rating of IP66   however  if it has been supplied without a cable entry device   then the user shall ensure that the device that is fitted will    European Safety Systems Ltd  Impress House  Mansell Road  Acton  London W3 7QH    Document No  IS 4501 Issue E 27 11 09    provide an ingress protection that is appropriate to the  environment in which it is installed i e  IP20 or better     4 2 Zones  Gas Groups and Temperature Classification  The IS A105N sounder has been certified Ex ia IIC T4 Ga   When connected to an approved system it may be installed  in     ZoneOQ explosive gas air mixture  continuously present     Zone1 explosive gas air mixture likely to occur in  normal operation     Zone2 explosive gas air mixture not likely to occur   and if it does  it will only exist for a short time   Be used with gases in groups   Group A propane    Group B ethylene  Group C hydrogen    Having a temperature classification of     T1 450  C  T2 300  C  T3 200  C  T4 135  C    4 3 Terminals 
16. package     Hazardous Area Safe Area    28V 93mA  Positive    IS A105N  Sounder       European Safety Systems Ltd  Impress House  Mansell Road  Acton  London W3 7QH    sales e2s com    www e2s com    Tel   44  0 20 8743 8880  Fax   44  0 20 8740 4200    Sheet 3 of 6    Tone Selection     To select the required first stage tone set the tone switches 1 to 6  see  Fig 2  to the tone setting shown in the table below  The table also shows which 2 and 3  stage tones are available for use with the selected first stage tone if more than one tone   output stage is required     Tone 1   Tone 2   Tone 3   Tone 4   Tone 5   Tone 6   Tone 7   Tone 8   Tone 9   Tone 10  Tone 11  Tone 12  Tone 13  Tone 14  Tone 15  Tone 16  Tone 17  Tone 18  Tone 19  Tone 20  Tone 21  Tone 22  Tone 23  Tone 24  Tone 25  Tone 26  Tone 27  Tone 28  Tone 29  Tone 30  Tone 31  Tone 32  Tone 33  Tone 34  Tone 35  Tone 36  Tone 37  Tone 38  Tone 39  Tone 40  Tone 41  Tone 42  Tone 43  Tone 44  Tone 45  Tone 46  Tone 47  Tone 48  Tone 49    Tone Description    Continuous 340Hz   Alternating 800 1000Hz   0 25s intervals   Slow whoop 500 1200Hz   0 3Hz with 0 5s gap repeated  Sweeping 500 1000Hz   1Hz   Continuous 2400Hz   Sweeping 2400 2900Hz   7Hz   Sweeping 2400 2900Hz   1Hz   Siren 500 1200 500Hz   0 3Hz   Sawtooth 1200 500Hz   1Hz   D   N    Alternating 2400 2900Hz   2Hz   Intermittent 1000Hz   1Hz   Alternating 800 1000Hz   0 875Hz   Intermittent 2400Hz   1Hz   Intermittent 800Hz 0 25s ON  1s OFF   Continuous 
17. r    Ex  Il 1G Ex ia IIC T4 Ga   40  C  lt  Ta lt    60      SIRA 04ATE X2301X    IECEx SIR 04 0038X  C E 0518  IS Class l  Zone 0  AEx ia IIC T4    IS Class l  Division 1  Groups A  B  C  D    M gt  Control Drawing No  D 4528  APPROVED Term    w r t  Term   Ui  28V li  93mA    Pi 660mW Ci 0 Li 0  WARNINGS  Term  S2 amp S3 w r t  Term    Ui   28V li OmA  To avoid a possible electrostatic Year   Serial No   charge only clean with a damp cloth 09   15000001  To prevent ignition of flammable or combustible  atmospheres  disconnect power before servicing  Substitution of components may impair safety     82S european safety systems Itd  London W3 7QH UK  www e2s com       sales e2s com    www e2s com    Tel   44  0 20 8743 8880  Fax   44  0 20 8740 4200    Sheet 6 of 6    Hazardous  Classified  Location Unclassified Location    Class    Division 1  Groups A  B  C  D  Class    Zone 0  Groups IHA  IB  IO    IS5 A105N Sounder  IS Class    Zone 0  AEx ia IC T4   40  C   Ta    60  C     Assaciated Apparatus   Shunt Zener Diode    Barrier with Entity Parameters   Uo   26  lo   93 mA  Po   660rrivy  Co   rabe  bee bok 10   Lo  gt  Leaive    Entity Parameters     Terminals   wort     U   26V       Fama   Fi   B     ri   G  0   ea       ASSoOciat  d Apparatus   Diode Return Barrier  te 32  amp  So wrt    with Entity Parameters   fen S   Us   28V   a la  O    ci 0     Uo   168V oer    lo   7 amA  Po   3inmvy    Associated Apparatus   Diode Return Barrier  with Entity Parameters    Wo   26W 
18. ters     Terminals   wert     U   2b       93mA   Fi   B   ri   i  0   Li 0    6  The  S A105N Sounder enclasure has an ingress protection rating  of IF 66 1f supplied without cable entry devices then metallic or plastic  cable glands  or canduit hubs  shall be fitted that provide the required  environmental protection     7  To prevent ignition of flammable ar combustible atmospheres   Associated Apparatus   Galvanically Isolated disconnect power before servicing     Relay with Entity Parameters    a  Io  O 6  Substitution of components may impair safety     o  0    Terminals 52  amp  S3 wert    S      U   48W   0  C   Uo   16 8  lo   7 3mA  Po   aimi    4 The total capacitance connected to terminals    ofthe sounder  ie   Ceabe plus any other capacitance  shall not exceed d3nF        10  The Ceable and Leabe of the cables connecting the galvanically  isdlated relays to sounder terminals 52  and SS shall be less than   or equal ta  the Ceabe and Leable of the cable connecting the  qalvanically isolated supply to sounder terminals  4     Associated Apparatus   Galvanically Isolated  Relay with Entity Parameters   o  Q  o  Q   See Note 70     Notes        CAUTION   Bonding between conduit connections is not automatic  and must be provided as part of this installation     iil it H       CAUTION   The clearance between sounder temninals 52 and S53is  less than mm        oo o o    European Safety Systems Ltd   T S IS A105N Sounder  2s Mansell oad  oo T o Control Drawing for galva
19. the latest technical knowledge for the products listed above     On behalf of European Safety Systems Ltd     declare that  on the date the equipment accompanied by this declaration is  placed on the market  the equipment conforms with all technical and regulatory requirements of the above listed  directives        Martin Streetz Date and Place of Issue  London  04 07 2012    Quality Assurance Manager Document No  DC 009 Issue_C   Telephone   44  0 20 8743 8880 European Safety Systems Ltd  Facsimile   44  0 20 8740 4200 Company Registration No  2763350  E mail  sales e2s com Registered Office  Impress House    www e2s com Mansell Road  London  UK  W3 7QH  UK    
20. y to a mechanically activated switch within the  hazardous area        Input Terminals Volume Tone Setting  Control Switches 1 6    Fig 2 Location of field terminals and controls     4 5 Other intrinsic safety certifications  Please contact European Safety Systems Lid  for details of  non European intrinsic safety approvals     5  Installation    IS A105N sounders should only be installed by trained  competent personnel     5 1 Mounting   The IS A105N sounder may be secured to any flat surface  using the two 7mm diameter fixing holes  The enclosure  provides IP66 protection and is suitable for installation in  exterior locations providing it is positioned so that water can  not collect in the horn  and the cable entry is sealed     5 2 Installation procedure    a  Secure the IS A105N sounder to a flat surface via the  two 7mm dia fixing holes in the mounting feet     b  Remove the front of the sounder by unscrewing the  four captive    A    screws and pulling the front away from  the enclosure     c  Fit a 20mm cable gland or conduit entry into the  untapped hole in the enclosure and connect the field  wiring to the appropriate sounder terminals as shown  in section 6 and fig 2 of this manual  The power supply  terminals   and   are duplicated so that sounders may  be connected in parallel  or an end of line monitoring  resistor may be fitted    d  Select the required output tone ye postlioning the six  switches as shown in Table 1 and Fig 2    e  Apply power to the sounder a
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
オキシウェル-3X - 医療用・酸素濃縮装置  BOÎTE MULTIFONCTION URGO  User Manual  HOLS電気温水器取扱説明書 HE-3704-B,HE-4604-B  Scaricare - File PDF  Manual de Usuario - Planquin, SA de CV  TAFCO WINDOWS NU2-018V-I Installation Guide  Starting Your LIFEBOOK Notebook  Sony SLV-SE30EE User's Manual    Copyright © All rights reserved. 