Home
NDC-F18 Access Control Panel
Contents
1. Terminal Name Function X1 Z1 Z1 GND GND a Terminals for inputs connection Z3 Z3 GND GND Z4 Z4 buzzer 1GN green LED 1RD red LED 1D1 data 1 Reader A terminals 1D0 data 0 GND GND 9V 9V C3 Common NOS Normally open Relay 3 terminals C1 Common 1NC1 Normally closed Relay 1 terminals NO1 Normally open ACG Battery dead Power supply signals PWG 220 power good X3 Direct or alternate power supply AC DC Power connection X2 A RS485 A En foe B RS485 dropline EB Additional devices power TES IME Tamper connection GND GND NO2 Normally open NC2 Normally closed Relay 2 terminals C2 Common NO4 Normally open C4 Gammon Relay 4 terminals 9V 9V GND GND 2D0 data 0 2D1 data 1 Reader B terminals 2RD red LED 2GN green LED 2BZ buzzer Z8 Z8 GND GND Zr A Inputs connection terminals Z6 Z6 GND GND Z5 Z5 Control Panel Operation Terminal assignment Connectors X5 Not Used for future use X4 RS 232 communication port Jumpers and LED RST Reset jumper S2 Address of the control panel S3 S4 S6 Jumpers for RS 485 load selection BAT Real time clock power switch LED Live function indicator Yellow Set jumper BAT during panel installation and withdraw it for storage and transportation to avoid lithium battery discharge Control Panel Operat
2. Blocked mode The blocked mode is designed for situations when access to the premises should be prohibited for everyone in case of security alarm for instance When access point is in blocked mode access is granted to cardholders of IDs with Security Service sign Door cannot be unlocked with RTE button When access point is in blocked mode reader s LED blinks red and green alter nately Access point switches into blocked mode by operator s command or when input programmed as BLOCKING is open Access point remains in blocked mode until this input is open or until operator cancels the mode Mounting NDC F18 is delivered in the rugged metal box with rechargeable battery Mount the panel in place convenient for service To mount the panel on a wall proceeds as follows Open box cover place the box in the required position on a wall and mark the holes for mounting screws using backplate as a template pass the wires through the holes on a back plate fasten the frame connect the wires Q Set jumper S7 during control panel mounting before programming Withdraw jumper 7 for long term storage and transportation http www itvsystems com ua Integrated Technical Vision Ltd 15 Wiring Wiring Readers connection NDC F18 has two sets of terminals for Wiegand readers connection The wiring is shown on Figure 3 Reader connection Figure 3 Readers connection orange N m N z v N fa 4 N Un 2 N
3. So that the panel could work properly set attached inputs as RTE button inputs Door Contact Door state opened or closed is determined by the status of door contact If door contact is not connected the panel is not able to determine the events of door force or not closed door The wiring of door contacts normally closed to Z3 and Z7 terminals is shown on wiring diagram Door contact of Door contact of access point A access point B So that door contact could work properly set attached inputs as door contact inputs Provide a door under system control with door closer Door contact and RTE button Control panel inputs can be pro grammed for simultaneous use of RTE button and door contact Input break means Door contact violation and input shortage means RTE button pressing Door contact and Door contact and RTE button of RTE button of access point A access point B http www itvsystems com ua Integrated Technical Vision Ltd 17 Wiring Q Any of eight inputs can be programmed as combined one that is for simultaneous use of door contact and RTE button Free Pass and Blocking Owing to the factthat any input may be programmed for Free Pass or Blocking the control panel can be easily integrated to intruder alarm system Ifthe input is programmed for Free Pass Free Pass Door A or Free Pass Door B then shortage or opening of this input unlocks the corresponding locking device and personnel can pass th
4. department employee and the other one to a guardian Time zone Any interval of time which has the beginning and the end http www itvsystems com ua Integrated Technical Vision Ltd 9 What s inside What s inside The layout of NDC F 18 is shown on picture below Figure 1 View of the Panel inside the box IO 1 Mains power connection terminal with fuse 2 Transformer 3 Power supply plate 4 Box 5 Control panel baseplate 6 Battery The wiring of the power supply plate to the control panel base plate is shown on diagram to the right 50v 50d TON TON TT AC 24V 12V GND PWG ACG transformer econdary winding 10 Integrated Technical Vision http www itvsystems com ua What s inside Wiring diagram Figure 2 NDC F18 access control panel wiring Future used S INCON LXH SX n nuuc Sz 9T4 ITV NDC F18 Up to two 4 Wiegand 7 4 readers Free Pass buttons Blocking buttons RS232 Door contacts RTE buttons e 06000000000000000000000008 x EN x4 GS 69699950555 9555909050 Bell Output of power supply with direct or Da alternate current protected against overvoltage and crosspolarity Diagram of null modem cable used for connection to PC is shown below pg PC http www itvsystems com ua Integrated Technical Vision Ltd 11 What s inside Controls and connections on the board
5. i e ci 18 Locking devices idet Rorate tha ERR e Ran REED GER Ete b Eun 18 Sirens Bells and agents essere 19 I3S 485 Interface ove i m t erbe santa 20 Address settiigs acanto 21 Limited Warranty opere neaei eee 22 http www itvsystems com ua Integrated Technical Vision Ltd 5 Preface Preface NDC F 18 access control panel is designed for use in access control systems Primary goals of Access Control System are identification of a person confirmation or not confirmation of access control of movements in a necessary zone It can provide time and attendance logging in addition to the usual task of restricting individuals access to certain areas All users access information is gathered by a server where administrators can retrieve and analyze it This data provides recording of staff movement within an organization whether it is a small company or a company that employs thou sands NDC F18 panel operates as a total stand alone unit with fully distributed database All valid card numbers time zones and relay pulse times are loaded into controller s memory The panel controls access on two access points on a stand alone basis with no dependency on central computer system Control panels are connected via RS 485 dropline in Access Control Systems Features o Supports all Wiegand reader technologies o Distributed database for independent operation o Operates in remote site configurations wi
6. NDC F18 Access Control Panel Installation Manual ACCCESS CONTROL PANEL Integrated Technical Vision http www itvsystems com ua This manual covers installation programming and utilization of NDC F18 access control panel Read this manual carefully prior to installing and programming the unit Design Change Disclaimer Due to design changes and product improvements information in this manual is subject to change without notice ITV reserves the right to change product design any time which may subsequently affect the contents of this manual ITV assumes no responsibility for any errors that may appear in this manual ITV will make every reasonable effort to ensure that this Installation Programming Manual is up to date and corresponds with your shipped unit Reproduction Disclaimer All rights on this document are preserved by Integrated Technical Vision Ltd Copying printing and any other kind of reproduction of the document or its part without permission of Integrated Technical Vision Ltd is prohibited Trademarks ITV is a registered trademark of Integrated Technical Vision Ltd Training and technical support Integrated Technical Vision Ltd performs training on the installation programming and utilization of NDC F 18 access control panel For additional information about training and discussing of your particular requirements to the unit please contact our personnel by the phone numbers below It is recommended to
7. e door freely Ifthe input is programmed for Blocking then shortage or opening of this input denies access rights to all cards except those with Security service mark Executive devices NDC F18 has four relay outputs to control operation of executive devices that can be electric locks turnpike turnstile bell and so on Relay 4 loading loading Relay 1 and 2 have normally open and normally closed contacts rating 5 A 24 V Relay 3 and 4 have normally open contacts rating 1A 24V Q Do notuse diodes when executive devices are attached to alternate current net When selecting power supply for the control panel mind that its capacity should correspond to power consumption ofthe control panel and executive devices Locking devices NDC F 18 has two relay outputs with form C contacts The operation time of these outputs may be programmed from 1 to 255 sec which allows control ling of any type of locking device Lock of access Lock of access point A point B Commutation of the inductive load electric lock for instance causes high energy electric impulse induced through relay contacts To save the contacts from damage protect them with diode connected in reverse to current supply of the coil Q Note the fact that some cheap electric door strikes are not intended for been energized for a prolonged time Program relay time as short as possible to avoid door strike coil overheat ing 18 Integrated Tec
8. hip and not damaged incurred in shipping or handing or damaged due to causes beyond the control of Integrated Technical Vision Ltd such as lightning excessive voltage mechanical shock water damage or damage arising out of abuse alteration or improper application of the equipment The foregoing warranty shall apply only to the original buyer and is and shall be lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Integrated Technical Vision Ltd This warranty contains the entire warranty Integrated Technical Vision Ltd neither assumes nor authorizes any other person purporting to act on its behalf to modify or to change this warranty nor to assume for it any warranty or liability concerning this product In no event shall Integrated Technical Vision Ltd be liable for any direct indirect or consequential damages Loss of anticipated profits loss of time or any other losses incurred by the buyer in connection with the purchase installation or operation or failure of this product Integrated Technical Vision http www itvsystems com ua http www itvsystems com ua Integrated Technical Vision Ltd 23 24 Integrated Technical Vision http www itvsystems com ua 060504
9. hnical Vision http www itvsystems com ua Wiring Sirens Bells and agents When connecting a bell study carefully user manual of the bell Consumption power of the bell should not exceed 1A Some sirens require polarity observing Often Electric bells are the inductive load for i Mec power supply Connecting the bells observe the warning about the inductive load above Sothat the siren could work properly set attached relay output as siren output while programming http www itvsystems com ua Integrated Technical Vision Ltd 19 Wiring RS 485 Interface RS 485 Interface is used for networking of the system components PC and panels The range of RS 485 bus is up to 1200 meters The number of devices in one bus segment is up to 32 RS 485 port is protected against overvoltage 60 V and crosspolarity The unshielded four wire cable may be used for RS 485 wiring For maximal range of 1200 meters please use 0 4 mm2 cross section wire 0 2 mm2 cross section wire will provide the range of 500 meters On the first and the last panel in the dropline short jumpers S3 S4 and S6 which connect loading resistors loading is on Q Take care of proper grounding of all panels in the network RS485 cables are connected to A and B GND and EB contacts Connect wires of one color always to the same terminal for example blue colored wire always connect to terminal A 20 Integrated Technical Vision ht
10. ion Control panels are supplied unprogrammed In this state reader s LEDs do not light Yellow LED situated on PCB blinks 5 times per second Panel does not respond to cards passing and inputs opening and closing The panel should be downloaded to start the operation with DC Configurator or Golden Gate program Yellow LED starts to blink one time per second and switches to the main mode automatically after successful settings downloading The panel can be turned to unloaded status only with command from PC see programming instruction The panel can control two independent access points Each access point may be in one of the four modes main mode alarm blocked or free pass Free pass mode has the highest priority as panel switches to this mode in case of fire then blocked alarm and main modes follow Main Mode Panel grants or denies access to cardholders in this mode In main mode reader s LEDs blink red Access with ID To access the premises cardholder passes RF ID to reader If it is valid panel grants access unlocks the door and switches on green LED of the reader Access with ID and PIN To access the premises cardholder passes RF ID to the reader Panel checks up the necessity of PIN entry and if it is necessary reader s LED blinks yellow which means PIN is awaited After valid PIN entry door is unlocked Reader s LED lights green RTE button To exit from the premises with single sided door user has to depress
11. nel There are several types of ID s and readers for them It is essential that reader and control panel should use the same interface NDC F18 utilizes Wiegand interface RTE Request to Exit To exit from the premises with a single sided door the button wired to the control panel is used This button is called RTE Request To Exit button If someone opens the door otherwise than pressing the RTE button by reenergizing locking device opening lock with a key etc the Door Forced Open event arises RTE button may be used for remote door opening as well Schedules NDC F18 is capable to store up to 100 time zones 100 week schedules can be combined from these time zones including 70 holidays Moreover NDC F 18 can store several floating schedules based on the period different to a week The number of such floating schedules depends on the period length Several ID s access To access the high security premises the presence of more than one person may be required NDC F 18 allows assigning of up to 15 groups of people with the access rights The access is granted only in case when one person from each group is present For instance you have the room which can be attended only by the personnel of R amp D department escorted with guard You can form two groups for this access group of R amp D employees and group of guard The access is granted if two ID s from different groups read on panel readers one belongs to the R amp D
12. ntended for connection of these sensors Door time If the door contact is open the corresponding access point goes into alarm Alarm is not invoked if the contact is opened during the Door Time interval of time This interval starts when access is granted and lasts for the programmed time or terminates on opening and subsequent closing of the door contact Downloading NDC F18 is to be downloaded after setting all parameters modes of inputs outputs access rights and others on the computer During the downloading parameters are rewritten into the access control panel If you change control panel parameters in your computer they will not take effect until this parameters down loaded into the control panel PIN Personal Identification Number Some readers have built in keypad The keypad may be used to enter ID in this 8 Integrated Technical Vision http www itvsystems com ua Preface case Usually this ID is named PIN Personal Identification Number It can be both self dependant or used as an additional code for ID When this PIN is programmed as additional code NDC F 18 waits for PIN entrance after the ID read out PIN is associated with ID Proximity Identificator In access control systems each user has ID identificator with the unique code Proximity ID s may be in shape of plastic card key trinket etc Reader Readers are devices assigned for reading information from ID s and transmitting it to the control pa
13. o 2 N 2 A v gt n Wire colors correspondence white data 1 green data 0 blue buzzer brown red LED orange green LED black GND red 9V The wires colors can differ in readers from other vendors Please refer to reader s Installation manual Inputs wiring NDC F18 has eight EOL inputs All inputs are programmable Their functions are set during programming The possible inputs functions are door contact RTE button door contact and RTE button free pass A B A B blocking A B A B state monitoring 16 Integrated Technical Vision http www itvsystems com ua Wiring After reset to factory defaults all inputs become unassigned and not supervised All inputs supervise shortage and break The EOL usage is mandatory o Input normal state is from 1 4 kOm up to 3 kOm Input short circuit is less than 1 4 kOm and input break is more than 3 kOm RTE button Request To Exit RTE button is to be used for one sided door In this case the door opens on depressing of RTE button for exit RTE button may be used for remote door opening secretary or guard can open the door for instance On the diagram to the right wiring RTE button of RTE button of of normally opened RTE button access point A access point B contacts is shown RTE is wired to Z4 and Z8 terminals Usage of the deblocking button on the electric lock instead of RTE will cause Door Forced event
14. ode In alarm mode reader s red LED lights constantly Access point goes into alarm mode for following reasons n case of door ajar Panel box tampering both Access points Attempt of access with lost ID If door is opened too long door time expired Incase of attempt of code matching if switched on during programming In alarm mode the panel activates outputs assigned for BELL and ALARM Alarm output is deactivated when panel switches into the mode different from alarm mode and BELL output is deactivated after programmed time If access point is in alarm mode to pass through this point is prohibited RTE button unlocks the door To switch alarm mode off pass card with Alarm OFF sign or with command from computer Free Pass mode Sometimes the conditions arise when door should be opened for free pass for everyone in case of fire earthquake or other disaster for instance For this case panel has free pass mode Integrated Technical Vision http www itvsystems com ua Mounting In the free pass mode reader s LED blinks red and yellow alternately Access point switches into free pass mode at operator s command or when input programmed as FREE PASS is open Access point remains in free pass mode until this input is open or until operator cancels this mode While Access point is in free pass mode the locking device is in unlocked state and panel does not respond to ID passing PIN entry or RTE button pressing
15. pass the training in Integrated Technical Vision Ltd to person nel intended for sales and installation of NDC F 18 access control panel on perma nent basis Technical support for all products of Integrated Technical Vision Ltd can be obtained at business time by the phones below 380 0 44 248 65 88 380 0 44 248 65 89 380 0 44 248 65 90 This support assumes the calls of trained specialists End users must apply to their dealers or installers before calling us This information is available on our web site www itvsystems com ua http www itvsystems com ua Integrated Technical Vision Ltd 3 Integrated Technical Vision http www itvsystems com ua Contents Prelace MENT CREE RES 6 Features sci o t DER ts ture e fatte detinere opa a le YES 6 Specifications eee teet teen RE re e ev Ehre pres 7 MESURE LINER 8 WhIabsinsideresl Willis ode 10 Wiring diagrammi rana cacao tenera disse 11 Controls and connections on the board 12 Control Panel Operation ia 19 Mounting pev Tre 15 VVIFIFYO cocci eie Lower cendo idee dept peo aliante attica 16 Readers connection nennen nennen nennen 16 Inputs Wining un cae icc enitn e etu dtes eclesie out ira ot it ana 16 PR es DUO Ms RII EDENDUM 17 Doot GCOntdct ssi Reti t b E a oo bu e e s He de Porro iua 17 Door contact and RTE button 17 Free Pass and Blocking gains scores oietetie ette ertet dy p tenes 18 Exec tive deviCes
16. press and release Request To Exit button Reader s LED lights green http www itvsystems com ua Integrated Technical Vision Ltd 13 Control Panel Operation Outputs use and operation modes All outputs of the panel can be programmed at will one of the use variants lock bell alarm or programmed output Moreover every output is set an operational mode start stop an output is activated whilst the proper command is present for example during the time of control panel Alarm mode impulse an output is activated for the programmed time trigger at first event an output is activated at the next event it is switched off and continuous Access Denial Access may be denied to cardholder for the following reasons Panel was not downloaded reader s LED does not light or blink ID was not enrolled in panel on ID passing panel switches reader s red LED and buzzer for 1 second ID expired on ID passing panel switches reader s red LED and buzzer for 1 second Access is not allowed according to the schedule on ID passing panel Switches reader s red LED and buzzer for 1 second Antipassback violation on ID passing panel switches reader s red LED and buzzer for 1 second Lost or Blocked ID passed on ID passing panel switches reader s red LED and buzzer for 1 second Access point is in alarm mode reader s red LED lights constantly Access point is in blocked mode reader s red LED lights constantly Alarm M
17. th dial up requires NDC B052 o 4 wire RS 485 communications protection rated at 3000 V o RS 232 communication port for local programming 08 supervised programmable inputs o Tamper switch contact 04 Form C relays o Up to 255 time zones to control card access o Real time clock o PC programming o Local antipassback function Integrated Technical Vision http www itvsystems com ua Specifications Primary power supply Preface 220 V 50 hertz Power consumption of alternate current net 25 VA Secondary power supply Peak current Voltage ripple Inputs Outputs Networking Operation temperature Relative Humidity 10 8 V 38 V of continuous current 11V 24 V of alternating current 100 mA 12V 500 mV 12V 8 programmable EOL supervised inputs 2 inputs for battery and power state control Two 1 A 24 V relays Two 5 A 24 V relays RS232 485 interface 0 C 55 C 95 relative at 25 C Nonvolatile memory capacity is shown in the table below Identificators 4096 Events 8094 Time zones 250 Schedules 250 Holidays 250 Overall dimensions 300x310x80 mm Weight http www itvsystems com ua 2 45 kg Integrated Technical Vision Ltd 7 Preface Terms Access point Access point is a logical concept of the access control system implying the control of passing through the door in one direction It consists of reader access control panel or it s part door super
18. tp www itvsystems com ua Address settings Address settings Each panel on RS 485 dropline must have the unique address from 0 to 31 To adjust the panel address use the S2 jumpers set Jumpers Address S2 6 2 5 S2 4 S2 3 S2 2 2 1 0 1 2 3 4 5 6 T 7 8 9 B T T 10 t F 11 12 E FI 13 z 14 15 16 17 18 19 20 21 s E 22 23 24 25 26 27 E 28 E z E Fi 29 30 E z 31 jumper is shorted Jumper is open http www itvsystems com ua Integrated Technical Vision Ltd 21 Limited Warranty Limited Warranty 22 Integrated Technical Vision Ltd warrants that for a period of eighteen months from the date of purchase the product shall be free of defect in materials and workman ship under normal use and that in fulfillment of any breach of such warranty Integrated Technical Vision Itd shall at its option repair or replace the defective equipment upon return of the equipment to its repair depot This warranty applies only to defects in parts and workmans
19. vision devices like magnetic contact RTE etc and door locking device For instance the turnstile with two way passes has two Access points one for entrance and the other one for exit door of this type is called double sided door A door with the reader on one side has only one Access point Entry point and itis called single sided door Antipassback The Antipassback function is implemented in the NDC F 18 access control panel in order to prevent the situation when user gives his ID to another person after passing to the premises If this function is on NDC F 18 tracks an ID position Inside or Outside the premises On any attempt to pass in the same direction twice NDC F18 denies access and stores Access Denied Antipassback event into the Log The antipassback function can be set on only in case of the double sided door control Code matching NDC F18 can arise alarm in case of an attempt of a code or ID matching The Code matching is considered when invalid code or ID entered several times Valid code entrance clears the counter This function switching on and number of code entrances are subjects of programming Door Contact DC In access control systems various sensors are used to supervise the status opened or closed of the pass way magnetic door sensor sensor of the turnstile rotor position inductive sensor of car passing through the road barrier etc The Door Contact terminal of NDC F 18 is i