Home

REMOTE MONITORING SERVICES USER MANUAL

image

Contents

1. Device Santerno Imola Cabl Jb2 Read failure rate QF105X is higher than 70 Please state code 174 for assistance Best Regards Monitoring amp Automation Team If an inverter is in an emergency the alarm notification is similar to the following Dear Customer The following events have been detected Plant santerno imola Device Santerno Imola Cabs SE Current Alarm ST171X A065 Main Switch Off Please state code 174 for assistance Best Regards Monitoring amp Automation Team If no Internet connection is established to the data logger of the plant the failure notification is similar to the following Dear Customer The following events have been detected Plant santerno imola Device Santerno Imola Cab3 St2 Data logger Santerno Imola ES851 is offline Please state code 174 for assistance Best Regards Monitoring amp Automation Team 18 18
2. The Remote Sunway 2 30 or later installed on the user s laptop allows establishing a connection to each inverter or to the plant devices as if the laptop was connected directly to the PV plant The Remote Sunway allows measure readout configuration parameter write chart creation and real time data storage For any details on the Remote Sunway 2 30 suite please refer to the relevant User Manual A 11 511794 NFEIRTIR CON TROL PANEL fd meti oA INVERTER CONTROL PANEL OPERATING CONDITIONS MEA Geena Mera Meru MODDMIDD MEA Zrep Meru MIKUO MEQ Anderi Maamgez MODS MI2SMO77MOR MEA Digia ingati Hits PAR Geel ntetece Aue 10301033 EE CONTADL PANELI fee MEH Staus R l Ado MOIMHrvertes States PRECHARG E iat INVENTER K AVATEA rw On M ka bal MIO Frog K MSP ND Actrve Power Debvered MOTO PY Frefd Volt DC Bus EI Marry aget D M007 Gud Voltage aeq Gonos M LS a L Hu E HOP feto mo en Ain Ato up 5 e ca D xo Ge Ge PS MOO Gud Current acy W OPFRATING CONDITION v n me MiG dE 0 100 S MIER Ak Code e EM P HOM God Frequency m Aen cst 4 EE el FUSE FLISE Kl EST athe RI MOJ Active Energy Dr veer it neg 1 Ag R MIZY Fois Power D But M Ac E vm za Enl Ais kWh Aube bw SJ MII a End tad MINS rtd Ee DEA Tree Man MEA Antsari M W WEA Dhaire b Pah pad intent T i D Gans 1 J Pay f GanX 1 J KAN En ago el w Ena F De gih Aog Tee fioe tep En Pan Pon Rett Tiec Reed a d Wite a Zoe a
3. downloaded on a daily weekly monthly yearly basis The user may also set a different time period by choosing the start date end date from the relevant fields S U n Way Do rt ql e Demo demol Logout Santerno 1 Imola lt back to results Status Running 1 1 Delivered active power 885 00 W x CT Eoloong e Rated power 6 00 kw Delivered active energy 1 29 MWh Commissioning 05 30 2010 Address ss Selice 47 Bologna IT Lon 11 734394 E Altitude 31 0 m s m f i Potenza A Energia PP Ambient savings co2 0 59 t Coal 0 16 t From 2012 03 1 EI rei 2012 04 17 oil 0 79 bbl Sk Weather conditions f E Bologna Borgo Panigale P is Ak E Partly cloudy S E 3 a S Temperature 17 0 S 3k er a Humidity 45 D 4 Pressure 1007 11 hPa g e 2k z e Wind speed 3 13 m s Ww K eo w Wind direction 80 S m 3 Visibility NZA Km CN Ephemeris Ok y t emm eg Date 17 04 2012 13 Mar 26 Mar 2 Apr 3 Apr 16 Apr Local ti 15 51 16 cal time Satz UTC time 13 51 16 mxs delivered active power w iee CR ransit A m Sunset 19 54 35 Today This week This year Export Csw Day length laze e e Midday Sun altitude 52 09 37 3 Data updated at April 12 2012 2 36 p m Current Sun altitude 42 07 19 5 ne me e SANTERNO Elettronica Santerno Spa Gruppo Carraro A GRUPPO CHA 5 5 Selice 47 40026 Imola PO PIO3686440284 Tel 39 0542 489711 Fax 390542489722 sales santerno com F
4. e E 3k g Kl D v e 2 2k 5 E U k Ok 00 00 04 00 08 00 12 00 16 00 20 00 00 00 mxs delivered active power Today This week This month This year Export Csy Data updated at April 12 2012 2 36 p m Elettronica Santerno Spa Gruppo Carraro Z SANTERNO Figure 8 Real Time Charts From 2012 04 11 To 2012 04 11 5 5 Selice 47 40026 Imola BO PIlO3686440284 Tel 39 0542 489711 Fax 39 0542 489722 sales santerno com SE Comacchio A D _ Sologna e Ee e Easercetz Ravenna ee Fori Cesena gt Rimi San Marino e Address ss Selice 47 Bologna IT Lat 44 377259 N Lon 11 734394 E Altitude 31 0 m s m Ambient savings co2 0 59 t Coal 0 16 t Qil 0 79 bbl Weather conditions Bologna Borgo Panigale E Partly doud Temperature 17 0 Humidity 45 Pressure 1007 11 hPa Wind speed 3 13 m s Wind direction 30 Visibility N A Km Ephemeris Date 17 04 2012 Local time 15 52 50 UTC time 13 52 50 Sunrise 06 32 12 Transit 13 12 59 Sunset 19 54 35 Day length 13h 22m Midday Sun altitude 52 09 37 3 Current Sun altitude 41 53 05 9 Eege 15 18 Remote Monitoring Services Z SANTERNO User Manual CARRARO GROUP 5 4 Sunway Portal History Data The History Data service allows creating the charts showing power output starting from the date of commissioning of the plant Data may be downloaded to csv files Production data may be viewed and
5. section representing output data and solar radiation in a Cartesian graph The graph allows zooming in out and detecting specific measures in selected spots It also allows data export to csv or pdf files If purchased the history data service allows querying a system with no time constraints otherwise only the data logged during the last week will be available 3 SERVICE ACTIVATION In order to get the remote monitoring service activation the purchaser shall provide the technical data of the PV plant required for the service as well as the e mail address or the phone number for SMS receiving reports or alarm notifications The forms to be filled in for the service activation are available from Elettronica Santerno The remote monitoring services are activated only when complete and exhaustive information is given to Elettronica Santerno The quality of the service is dependant on the information given Should PV plant data be changed please contact Elettronica Santerno to purchase a new configuration service 4 ROUTINE MAINTENANCE Elettronica Santerno constantly enhances all the remote monitoring services provided Improvements are made with no obligation of communication 8 18 Remote Monitorin User Manual Z SANTERNO H CARRARO GROUP Services 5 DESCRIPTION OF THE SERVICES 5 1 Link Service The LINK service allows the remote connection via the Internet to the local supervisor computer or ES851 Data Logger boards
6. 40284 Tel 39 0542 489711 Fax 39 0542 489722 sales santerno com Z SANTERNO Figure 6 Real Time Summary 13 18 User Manual Remote Monitoring 5 SANTERNO Services CARRARO GROUP 5 3 3 Sunway Portal Real Time Plant Schematic The Plant Schematic displays a diagram of the plant indicating the monitored inverters and devices Virtual traffic lights indicate the operating conditions of each device Traffic lights also indicate if the energy produced is as expected Welcome Demo demol Logout Sunway Portal m a a a L ve mmm eg nf e E age Santerno 1 Imola lt back to results Status Running 1 1 Delivered active power 3885 00 W Rated power 6 00 ky Delivered active energy 1 29 MWh Commissioning 05 30 2010 Summary Charts Lat 44 377259 N Lon 11 734394 E gt Legenda Show In Lightbox Altitude 31 0ms m Ambient savings co2 0 59 t DL Coal 0 16 t Qil 0 79 bbl INV Weather conditions Bologna f Borgo Panigale EC Partly doudy Temperature LSD Humidity 45 Pressure 1007 11 hPa Wind speed 3 13 m s Wind direction 80 Visibility NZA Km Ephemeris Date Local time UTC time Transit Sunset Day length Midday Sun altitude 17 04 2012 15 48 38 13 48 38 06 32 12 13 12 59 19 54 35 13h 22m 52 09 37 3 Current Sun altitude 42 31 05 5 Figure 7 Real Time Plant Schematic When pointing to each monitored device a window appears showing all the meas
7. N T an 2 Ot INDEX Or Fl Geo eenn E tomar 2 1 GENERAL INFORMAT ION EE 3 Tet REMOTE MONITORING SER VIG ES egene a 3 Mice TR ER EEN 3 kos I ele 4 2 DESCRIPTION OF THE REMOTE MONITORING SYSTEM cece eeeeeeeee eee 4 2 1 OVERVIEW OF THE WHOLE SYSTEM EN 4 2 2 FUNCTIONALITY OF EACH DEVICE IN THE REMOTE MONITORING SYSTEM 5 2 2 1 LOCAL SUPERVISOR COMPUTER OF THE PLANT sissassssseesnnsssssnnnnnnrrerrrrreeeesssenene 5 2 2 2 ES851 DATA LOGGER BOARD INSTALLED ON THEINWVERTER 6 2 2 3 COMPONENTS IN THE WEB SYSTEM 20 cceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 7 3 SERVICE ACTIVATION ccc cccccecccecceseeeeeeeeeteeteeeeseeeneeeeeteeetaeeneeeaeeeueteessaeeneeeaaeeaass 8 ds e ERR KE CHR tt LEE 8 EECH OF THE Ee 9 5T LINK SERVICE sanstacanacenpensdaenendintenavarendesnacanaeduaanedenieietendaiinaundsabasanaenaeiuadenenasedanaietei 9 52 LOG MANAGER E EE 9 e SUNWAY el EEN 10 5 3 1 SUNWAY PORTAL REAL TIME MAP 12 5 3 2 SUNWAY PORTAL REAL TIME SUMMARY n aannnannannnnnnnnnnnnnnnnnsnsnnnnnnnrrnrnrrrenessssennne 13 5 3 3 SUNWAY PORTAL REAL TIME PLANT GCHEMATIC 14 5 3 4 SUNWAY PORTAL CHAT 15 5 4 SUNWAY PORTAL HISTORY DATA 16 6 Vie AY RRE MESSAGING EE 17 oe ADDRES E 17 6 22 INO TIGR ON lee EEN 17 6 3 CONTENTS OF E MAILS AND SMS MESSAGES ccc cceccceceeeeeeeeeeeeeeeeeeeees 17 0 1 Index of Figures Figure 1 The whole Remote Monitoring system cccccccsesccecseeeeeceeeeeeeeeaseeess
8. aeeeeseuseeeseaeeessaueeessaneeeenaeseeesaaes 4 Figure 2 Remote Sunway Inverter Control Panel 9 Figure 2 Sunway Portal NOME page 10 Foue ai reall Oe WEE 12 Figure 4 Real Time Map Plant Gheet ieira nasae n adiando Niege E erakina kinini anenai 13 Figure 5 Real Time Gummam 13 Figure 6 Real Lime E le Ee 14 Figure 7 Real Time CAS eere a a S 15 Figure Cr History Dal NEE 16 2 18 CARRARO GROUP Services Remote Monitorin User Manual Z SANTERNO H 1 GENERAL INFORMATION 1 1 Remote Monitoring Services This manual covers the remote monitoring services offered from Elettronica Santerno SpA The remote monitoring services allow our customers to get updated information and data from their photovoltaic plants receive diagnostic messages and check the correct operating conditions of their plants at any time Besides controlling the correct operation of the PV plants in remote mode and receiving diagnostic messages users can also change the operating parameters of the plant devices 1 2 Main Features Elettronica Santerno SpA offers the following remote monitoring services e Link Data Service this is a remote connection via the Remote Sunway suite enabling communication with ES851 Data Logger boards e Sunway Connect Data Service establishes a remote connection enabling communication with the stand alone data logger e Sunway Portal web service web portal available at https Wwww sunwayportal it allows doing the fo
9. ame e mail or SMS especially if the addressee is configured for more than one plant 6 3 Contents of E mails and SMS Messages The content of the e mails and SMS states the plant where the alarm s tripped or the event s fired the affected device and a brief description of the event The cause responsible for the alarms events can be easily identified For example if the system detects that some strings in a plant are open it sends the following message to one ore more addressees Dear Customer The following events have been detected Plant santerno imola Device Santerno Imola Cab23 Jb43 String status QF105X is 8 String Open on 09 12 2011 09 05 Please state code 1573 for assistance Plant santerno imola Device Santerno Imola Cab23 Jb44 String Status OF105xX as 6 String Open on 0971272011 09205 Please state code 1574 for assistance Best Regards Monitoring amp Automation Team 17 18 Remote Monitoring Services Z SANTERNO User Manual CARRARO GROUP In the example above two alarm messages have been included in one notification message If assistance is required the Remote Monitoring Service shall be informed about the two alarm codes stated in the message above If the read failure rate exceeds 70 serious communication failure the data logger of the PV plant will send a message similar to the following Dear Customer The following events have been detected Plant santerno imola
10. e 15P0701B1006 REMOTE MONITORING SERVICES USER MANUAL Issued on 18 04 12 R 00 English e This manual is integrant and essential to the services and the products described herein Carefully read the instructions given as they provide important hints for use and maintenance safety e The products and services covered in this manual are to be used only for the purposes they have been designed to Any other uses should be considered improper and dangerous The Manufacturer is not responsible for possible damages caused by improper erroneous and irrational uses e The products and services covered in this manual are sold according to Elettronica Santerno s sales and guarantee terms e Elettronica Santerno reserves the right to make any technical changes to this manual and to the products described herein without prior notice If printing errors or similar are detected the corrections will be included in the new releases of this manual e The information contained herein is the property of Elettronica Santerno and cannot be reproduced Elettronica Santerno enforces its rights on the drawings and catalogues according to the law SANTERNO CARRARO GROUP Elettronica Santerno S p A Strada Statale Selice 47 40026 Imola BO Italy Tel 39 0542 489711 Fax 39 0542 489722 santerno com sales santerno com Remote Monitoring Services Z SANTERNO User Manual CARRARO GROUP 0 TABLE OF CONTENTS On WA LEO OJNTE
11. gAn wet 5 Waie sei Save set 7 White ont 6 Seve mod Figure 2 Remote Sunway Inverter Control Panel 5 2 Log Manager Service The Log Manager service is configured for periodic download of the data stored to the local supervisor computer or the Data Logger boards Donwloads are compressed to zip files and stored to the FTP home of the customer to the Santerno FTP 9 18 Remote Monitoring Services Z SANTERNO User Manual CARRARO GROUP 5 3 Sunway Portal This service is available at hitos sunwayportal it Make sure that your browser is updated with the latest release available for the operating system you are using Elettronica Santerno reserves the right to provide no support for certain browser versions such as Internet Explorer 6 the supported browsers however are listed on the home page of the portal The service receives data from the data loggers installed Data items are then aggregated and processed to provide measures detected from individual plants or from the whole plant set of the customer The Sunway Portal service also provides graphical representations allowing monitoring the plant operation and evaluating energy production in real time Sunway Portal Map Control all your plants from everywhere Sunwayportal all the information is Summary data Log in just a click away Monitored plants Santerno Sunway Portal is an exclusive service by which you Ze 2070 Username can monitor your photovo
12. ge indicates that the board is activated and may be reached from remote users The ES851 Data Logger board dialogues with the inverter where it is installed and may have 2 external RS485 links e May be connected to the local supervisor computer through RS485 or Ethernet cable The ES851 Data Logger board acts as a Slave and responds to the read write queries for parameters and measures sent from the local supervisor computer and submits the read write queries for the inverter where it is installed If the ES851 board is connected to the local supervisor computer via RS485 the Modbus RTU protocol is used otherwise if an Ethernet cable is used a proprietary TCP IP protocol is used The ES851 board has an additional RS485 port using the Modbus RTU where it acts as a master and can then read and write measures and parameters relating to all the devices connected to that RS485 Modbus RTU cable If properly configured the ES851 board may be connected to an external Master via standard Modbus TCP IP this protocol however is not currently supported by the Remote Sunway The two RS485 links are segregated from each other i e they are two separate hardware ports COM1 and COM2 From the local supervisor computer ES851 can then communicate with the inverter where it is installed and with the slave devices connected to the additional RS485 link If properly configured ES851 Data Logger board can do the following e Sample the mea
13. he plant local supervisor PC LOG_MANAGER WEB Browser SUNWAYPORTAL Firewall SMTP DATABASE http link elettronicasanterno it Connections active in ports 15101 to 15297 Alive over port 15100 y Firewall Router DHCP DNS GATEWAY PV Plant LAN CL ei i ae 2 on ES851 ES851 ES851 ata logger datalogger data logger data logge E supervisor e Inverter 1 in Inverter 2 in Inverter 3 in inverte PC of the PV plant degen RS485 RS485 EIR Smart String Box Smart String Box Smart String Box TE Bow Sat String Box CH ane Smart String Box Smart String Box Smart String Box Smart String Box Smart String Box gmi Shing Bae Figure 1 The whole Remote Monitoring system 4 18 CARRARO GROUP Services Remote Monitorin User Manual Z SANTERNO H 2 2 Functionality of Each Device in the Remote Monitoring System 2 2 1 Local Supervisor Computer of the Plant The local supervisor computer of the PV plant is connected to the local are network LAN with an Ethernet cable The LAN shall do the following e Provide a valid IP address either a static address or a DHCP Dynamic Host Configuration Protocol address e Provide a valid and reachable DNS Domain Name System e Provide fast access to the Internet 24 hours a day without using any proxy and without any hardware software check on the web traffic e Keep TCP ports open output from 15100
14. he local supervisor computers in the plant via the Remote Sunway suite e the data items sent to ES851 boards to be received by the Sunway Portal e the notifications for the alarms tripped from a device connected to the ES851 board Any query is authenticated and authorised through a strict check on the identity of the caller user or ES851 board or local supervisor computer and on the type of query When an Alive message is received the caller status is updated and the system stores the last instant when the caller has been detected as online When the user queries the list of the ES851 boards installed the system will easily detect when a given board has been seen online for the last time When data items are received they are submitted to the Sunway Portal which will properly store them to Santerno s storage system When an alarm notification is received this is submitted to the Sunway Portal which applies filter and categorization algorithms and sends an e mail or SMS to a list of addressees shared with the customer When a connection request is received a safe communication channel is created between an ES851 board or the local supervisor computer and a remote user using the Remote Sunway The user will then be able to read the measures of the devices connected to the other end point and change the relevant operating parameters 2 2 3 2 Log Manager This is a service made available for whom has purchased the service enabling view
15. igure 9 History Data 16 18 Remote Monitorin User Manual Z SANTERNO H CARRARO GROUP Services 6 E MAIL AND SMS MESSAGING The Sunway Portal parses any data items sent from the PV plants and analyses the operating conditions of the data loggers If malfunction occurs e mail or SMS notifications are sent The text of the messages is given in section 6 2 and may convey information relating to multiple devices Elettronica Santerno reserves the right to change the text of the messages at any time and without prior notice for a better fruition of the service 6 1 Addressees The addressees of e mail and or SMS notifications may be chosen granularly by specifying the contacts the days of the week and the allowable time spans the submit rules and the type of messages to be sent This is done directly by Santerno Customer Service lt may happen that not all the options above can be applied during the activation stage of the service 6 2 Notification Messages Notification messages are sent when an event fires or when an event disappears and normal operating conditions are restored Notification messages can be of 4 types e Alarm e Panel theft e Remote communications failure e Local communications failure Because data items are periodically parsed every few minutes notifications are not sent individually but are grouped together this means that different types of messages or from different PV plants may be included in the s
16. ing history data It periodically connects to the remote data logger boards and downloads the files including stored data Those files are then stored to Santerno s storage servers and are made available to the customers via the FIP service 2200 1 This is a standard FTP server receiving the files containing the data stored every 15 minutes It also receives the ZIP files sent from the LOG_MANAGER and containing the data stored from the Data Logger boards of the customers who purchased the HISTORY service of the Sunway Portal 2 2 3 4 Sunway Connect This is a service dedicated to the connections between a remote user and a Stand Alone data logger enabling a connection between the data logger and the Remote Sunway 2 2 3 5 Sunway Portal This is a web portal available at https www sunwayportal it that can be accessed by customers only It stores real time data and makes them available to the users 7 18 Remote Monitoring 5 SANTERNO User Manual Services CARRARO GROUP The Sunway Portal includes the following e he Map showing the location of the plant through a colour marker e The Plant Data including a chart containing the main production data of the PV plant and of each individual subfield The Plant Schematic reproducing the connected devices Different colours are given to indicate the operating conditions of the devices When pointing to each device its main measures are given A Charts
17. llowing o Real Time Data display o History Data display o E mail or SMS diagnostic messaging Minimum requirements the plants shall be equipped with at least one ES851 Data Logger board or Sunway Bridge The inverters of the Sunway M XS series from Santerno are equipped with an integrated data logger and are capable of sending data in an independent way The Sunway M XS inverters however may also be monitored by an ES851 Data Logger board or by a Sunway Bridge Only the remote monitoring services are covered in this manual Q NOTE For details on the devices below please refer to their respective manuals e Local supervisor computer of the plant e Remote Sunway suite e ES851 Data Logger board e Sunway Bridge e Smart String Box e Sunway inverters e Sunway M XS inverters 3 18 STAFF MANAGING THE CUSTOMER S PLANTS http www sunwayportal it they connect to www sunwayportal it ftp data elettronicasanterno it Remote Monitoring Services Z SANTERNO User Manual CARRARO GROUP 1 3 Scope of this Manual This manual covers the following e exhaustive comprehension of the remote monitoring services provided from Elettronica Santerno e choice of the configuration fitting the customer s needs e usage of the remote monitoring services 2 DESCRIPTION OF THE REMOTE MONITORING SYSTEM 2 1 Overview of the Whole System Remote Sunway CUSTOMER S STAFF they establish a connection to ES851 Data Logger or t
18. ltaic plant within your browser to checkreal time energy production and detect faults to progam a prompt intervention The website reserved to our Password customers is available in 6 languages and offers two service types Real Time service and Historical service The former shows real time acquired data updated every 15 minutes Login with a depth of a week the latter allows the customer to search for production data since the instant of the activation of the service Both services provide the visualization of data English en graph form By using this user friendly tool the monitoring Change of PY plants becomesa simple task always accessible from everywhere You just need an internet connection and your login data demol e SANTERNO Elettronica Santerno Spa Gruppo Carraro A 5 5 Selice 47 40026 Imola BO PI03686440284 Tel 39 0542 489711 Fax 390542489722 sales santerno com Figure 3 Sunway Portal home page Six languages are available English Italian French German Spanish Portuguese The site can be accessed even from the registered domains below www sunwayportal de www sunwayportal es www sunwayportal com 10 18 CARRARO GROUP Services Remote Monitorin User Manual Z SANTERNO H If your login is correct you can access the page of the Real Time service This service includes four main items e The Map e The Plant Set e The Plant Schematic e The Real Time Charts The Map is the fi
19. o the plant status indicating how many inverters are currently running i e are properly operating instant power and energy installed power and date of commissioning of the plant 5 3 2 Sunway Portal Real Time Summary The Plant Set views the production data of the virtual plant set the data of each plant and subfield as well as the data from the ambient sensors when available If auxiliary devices are installed such as meteo centres their measures are also displayed Sunway Portal Santerno 1 Imola Welcome Demo demol Logout lt back to results gt Inverter MX S 1074018 Data updated on April 12 2012 2 36 p m Ambient savings co2 o 59t Coal DIr Qil 0 79 bbl Status Running 1 1 Oo Delivered active power 885 00 W E Se 5 Rated power 6 00 kw ec Delivered active energy 1 29 Mh Commissioning 05 30 2010 Address ss Selice 47 Bologna Schema Charts Lat ee N Expand all Lon 11 734394 E Altitude 31 0 m s m Weather conditions Bologna Borgo Panigale e Partly coudy Temperature 70 Humidity 45 Pressure 1007 11 hPa Wind speed 3 13 m s Wind direction 80 Visibility NA km Ephemeris LG Date 17 04 2012 Local time 15 46 50 UTC time 13 46 50 Sunrise 06 32 12 H Transit 13 12 59 CH Sunset 19 54 35 Day length 13h 22m t bh a Midday Sun altitude 52 09 37 3 5 Current Sun altitude 42 47 13 8 Elettronica Santerno Spa Gruppo Carra 5 5 Selice 47 40026 Imola 60 PI 02E864
20. out Santerno Select plants wl Correct iY Partial wl Alarm D Gz V Bad weather conditions j V Missing data 7 Remove Filters e Ee Elettronica Santerno Spa Gruppo Carraro A SANTERNO 5 5 Selice 47 40026 Imola BO PIO03686440284 Tel 39 0542 489711 Fax 39 0542 489722 sales santerno com a 8 a Figure 4 Real Time Map Colours of the virtual traffic lights e GREEN The plant is properly operating and the energy production is correct e YELLOW One of the inverters in the plant is underproducing energy e RED An alarm tripped in one of the inverters in the plant e WHITE No data is available The marker hand indicates the instantaneous production of the plant as a percentage of the rated power of the inverters installed The bar above the marker indicates the overall solar radiation as a percentage of a theoretical maximum solar radiation of 1100 kW m If you click on the marker a popup appears showing the summary of the plant data 12 18 User Manual Santerno gt Casola F E anna Caseta Tomba kr Pealkiri T KE am A SANTERNO CARRARO GROUP oto plant Status Delivered active power Kated power Delivered active energy Commissioning Figure 5 Real Time Map Plant Sheet Remote Monitoring Services Running 1 885 00 Wy 6 00 KW 1 29 Mudk 05 30 2010 SC The summary data items relate t
21. reached from remote users From their remote computer the customer s technicians can establish a connection to the local supervisor computer of the plant through the LINK service the Remote Sunway suite is required as well as a username and password for login and can establish a connection to any device that can be reached from the local supervisor computer e Every 15 minutes the local supervisor PC samples approx 150 variables from the plant device and sends them to the FTP server 5 18 Services CARRARO GROUP Remote Monitoring 5 SANTERNO User Manual 2 2 2 ES851 Data Logger Board Installed on the Inverter The ES851 Data Logger board is connected to the Local Area Network via the Ethernet cable The LAN shall do the following e Provide a valid IP address either a static address or a DHCP address e Provide a valid and reachable DNS e Provide fast access to the Internet 24 hours a day without using any proxy and without any hardware software check on the web traffic e Keep TCP ports open output from 15100 to 15300 to the link elettronicasanterno it The ES851 Data Logger board is installed on an inverter Q NOTE When the LOGGING function is required or when diagnostic messaging is enabled also at night time the inverter must be continuously supplied with auxiliary power supply Every 5 minutes the ES851 Data Logger board sends an Alive message to the Sunway Portal via the LINK service This messa
22. rst option displayed It shows the location of the plant Virtual traffic lights indicate the correct operation of the plant and a status bar indicates the power production as a percentage of the rated power of the inverters installed The overall average solar radiation of a PV plant is available if that plant is provided with solar radiation sensors The List views a table containing information similar to that given by the Map The Plant Summary views some tables containing the production data of the virtual plant set of the customer including individual plants and subfields as well as environmental sensors when available The Plant Schematic displays a diagram of the plant indicating the monitored inverters and devices The operating conditions of each device are shown Virtual traffic lights also indicate if the energy produced is as expected The Charts graphically represent the power production in a Cartesian graph The charts include power energy solar radiation Data items are sorted by device or by sensor The time period may be up to seven days 11 78 SANTERNO User Manual CARRARO GROUP Remote Monitoring 5 Services 5 3 1 Sunway Portal Real Time Map The Map is a service integrated with Google Maps From the commands on the left you can identify the location of the plant filter the plants by status select the navigator and zoom in up to the maximum available level S U n Way Po tal Wale Demo demo Log
23. sures read from the inverter every 2 minutes and store to the flash memory the measures read from the inverter where it is installed or from the devices it is connected to Also the date and time of each sampling round is stored to the log files When the maximum allowable dimension of the log file is achieved the ES851 restarts writing from the beginning of the file circular buffer e Monitor the logged devices and detect the Events fired These Events can be alarms i e persistent alarms triggered or THEFT signals sent from a String Box If no response to a query of the Data Logger board is received after 3 enquiry attempts a NON RESPONSE event fires All the events fired are stored to an EVT file e Send to Sunway Portal via the LINK service the signals for the detected events Events can be ALARMS THEFT events and NON RESPONSE events e Perform a smart sorting of the detected events to avoid uncontrolled messaging when the RS485 cable is fully disconnected or to avoid continuous event firing from one of the monitored devices 6 18 Remote Monitorin User Manual Z SANTERNO H CARRARO GROUP Services 2 2 3 Components in the Web System 2 2 3 1 Link Service This is a server receiving the following e the Alive messages sent from the Data Logger board and the PCs in the PV plant e the connection queries from the users who want to establish a connection to the Data Logger boards or t
24. to 15300 to the link elettronicasanterno it e Keep TCP ports open output for FTP traffic The local supervisor computer must be powered on 24 hours a day A specific version of the Remote Sunway shall run on the local supervisor computer Full functionality is ensured only if no application other than the Remote Sunway is installed on the local Supervisor computer The local supervisor computer may be connected to the plant devices in two mutually exclusive modes via RS845 using the Modbus RTU protocol via Ethernet using a proprietary protocol The computer is a Master device i e it can query all the connected devices below e ES851 Data Logger DL boards e Sunway TG ST Inverters e Sunway M XR SM Inverters e Sunway M Plus SP Inverters Sunway M XS inverters SA and SL Smart String Boxes QF DC Parallel QPS AC Parallel QPCA DATEXEL I O XD and XA devices e Meteo Station MZ e Device detecting grid voltage and grid current measures XF e PLCs CL Q NOTE For details about the devices above please refer to their respective User Manuals Here is a list of the functions performed by the local supervisor computer of the PV plant e The local supervisor displays a synoptic table including the main measures of the plant measures are sampled and displayed approx every 10 seconds e Every 5 minutes the local supervisor PC sends an Alive message to the LINK service this message indicates that the PC can be
25. ures sampled from the device When the strings are monitored through the Smart String Boxes as shown in the figure the virtual traffic light is green if the output power produced from the monitored strings is approx as expected The expected power is get from the ambient measures detected from solarimeters thermometers anemometers and from the data of the PV panels of the strings connected to each Smart String Box COLOURS OF THE VIRTUAL TRAFFIC LIGHTS For each ES889 board installed on the Smart String Boxes QF The output power of the strings is correct The strings are underperforming or their output power is too weak i No data is available 14 18 User Manual 5 SANTERNO CARRARO GROUP For the SunwayTG or Sunway M XR M Plus inverters Gei Properly operating Inverter in stop ei Night time or adverse weather conditions Inverter in an emergency D No data is available 5 3 4 Sunway Portal Charts Remote Monitoring Services The Real Time Charts represent the daily production of power energy and solar radiation Data items are sorted by device Sunway Portal Santerno 1 Imola Welcome Demo demol Logout lt back to results Status Running 1 1 Delivered active power 885 00 W Rated power 6 00 ky Delivered active energy 1 29 MWh Commissioning 05 30 2010 Summary Schema A Potenza y Energia PP Le Ek 3 e ke OI N a 3 E 5 AL bel E 4k a J oc a Fy 2