        Hardware and Installation Manual
         Contents
1.       i  5 4  Inverter Communication Connection                       5 5  String Supervisor Description   5 6  Overvoltage Protection                      i    COMMISSIONING                       ss ss sressesenieaaena nane neon e eee nananana zone e agas assa ioni e nie iii iaia iene  6 1  Initial Conditions     6 2  Verniy IMO WV INNO NES TT  63 OWC cesses cece e ee io ae sce cece eet ee    TRANSPORT AND HANDLIND      1 iii  7 1  Freesun Weights and dimensions                    nennen nnn  7 2  Transpor Procedure me  YS B Prior to CORMECUON nm                                     M       DECLARATION OF CONFORMITY CE                               1rrrrrrererezzez zzz nie nhan nana nnne    FREESUN    INDEX    5    LTO  P 0 e m    FREESUN POWER ELECTRONICS    SAFETY INSTRUCTIONS    IMPORTANT     Head this manual carefully to maximise the performance of this product and to ensure its safe  use        n order to use appropriately the FREESUN  please  follow all instructions described in the  installation manual referred to transport  installation  electrical connection  and commissioning of  the equipment       Power Electronics accepts no responsibility or liability for any and all damage resulting from  inappropriate use of the equipment       The information contained in the installation guide must be observed when installing the inverter     PRIOR TO CONNECTION    In the rear side of the solar inverter are located the SECURITY FIXATIONS FOR TRANSPORT in  both the transforme
2.     1  The maximum PV Power depends on the geographic location and type of installation        12 SAFETY INSTRUCTIONS    POWER ELECTRONICS FREESUN    2  TECHNICAL CHARACTERISTICS        FREESUN LVT SERIES    ov eon    DC Voltage Range MPP  VDC  450V     820V  INPUT    Maximum permissible DC current  A        52   65   77   90   103   129   155   206   258      Recommended cable section  mm   2     Max  Efficiency Pac  nom  n  95 9  96 2  97 1   EFFICIENCY Euroeta  n  95 0  95 5  96 5   Standby Operating Consumption  Duc   lt  approx  40W    External Auxiliary Voltage 230V  50   60Hz  AUXILIARY    External Back up Fuse for Auxiliary B16A  1 pole  Supply x    Dimensions  WxHxD  mm 840 x 1600 x 755 1040 x 1600 x 755 1440 x 1700 x 1040  CANE Weight  kg  1125  I Intake thorough rear lower part and both sides blown out through upper side  Outdoor   Air Flow  Intake thorough rear lower part blown out through upper side  Indoor     A l IP44   IP54  Outdoor   Protection Rating as per EN 60529 IP21  Indoor     ENVIRONMENT Permissible Ambient Temperature  3   20  C     50  C  Relative Humidity  non condensing 10  to 95   Max  Altitude  above sea level   4  1000m    Modbus  CAN  Ethernet  optional GSM   GPRS        LTO  P 0 e m       Digital Inputs 2 programmable inputs  Galvanically isolated     2 programmable and differential inputs  Analogue Inputs Current signal  0 20mA  Voltage signal  full scale configurable    10mV to   10V      CONTROL PT100 Input 1 Input  INTERFACE String Superv
3.     24 ELECTRICAL CONNECTION    POWER ELECTRONICS FREESUN    5 1 2  PV Generator Power Connection  DC Connection     A busbar that allows string distribution boxes to be connected is located in the left lower area of  the inverter sidewall  Cables rated for a minimum of 900V    1000V are required for connecting the  DC cables to the fuse inputs of the inverter     Suitable cable screw connections must be installed in the busbar plates to provide strain relief for  the cable  The DC cables are connected directly to the busbar using M10 cable lugs     The DC voltage of the PV generator must never exceed the maximum permissible inverter input  voltage  Otherwise the inverter is in acute danger when connected  Upy    900    1000 V     FSITP0008A       Figure 5 3  View of DC connection area with on load disconnector  A  and circuit breaker  B     ELECTRICAL CONNECTION    25    ck H   se PF GA e m    FREESUN POWER ELECTRONICS    5 1 3  General dimensions for AC and DC connection        FRONT SIDE    840                   FSDTDOOO4AI    Figure 5 4  AC and DC Input   Output cable plates Frame 1    FRONT SIDE                   FSDTDOOOSAI    Figure 5 5  AC and DC Input   Output cable plates Frame 2    26 ELECTRICAL CONNECTION    POWER ELECTRONICS FREESUN       FRONT SIDE       FSDTDOOOGAI    Figure 5 6  AC and DC Input   Output cable plates Frame 3    5 2  Disconnect    External disconnection of the device must always be done when the inverter is operating under no   load conditions  
4.     FSITG0009A       Figure 4 1  FREESUN Frame 1 internal view    22 GENERAL INFORMATION    POWER ELECTRONICS FREESUN                       gt  bal D  AIR   rA LLL LLL LLL LLL LLL LLL Ne    FSITG0010A       Figure 4 2  FREESUN Frame 3 internal view    4 7  Cooling system maintenance    The device is equipped with several fans for cooling  To perform any work on the fans is  recommended that the equipment is switched off as explained in the previous section  This procedure  should be taken into account for commissioning  maintenance and repair work     4 8  Hearing Protection    The device fans and the power unit create significant levels of operating noise  In addition to this  a  fault in the device can lead to very high sound levels  For these reasons we recommend the use of  hearing protection in its vicinity    We recommend the use of ear protection when in the vicinity of the device for extended periods     4 9  Burns    Immediately after isolating the device  depending on the operating conditions  certain components  can be very hot  e  g  fuses  transformer core  sine wave filter  heatsinks  etc      Safety gloves should always be worn when working near components that can be expected to be  very hot    We recommend that safety gloves be worn during all work on the inverter     GENERAL INFORMATION 23    ck  H   cz rozm    FREESUN POWER ELECTRONICS    9  ELECTRICAL CONNECTION    The electrical connection can be set up after the inverter has been correctly placed on site
5.     FSITG0012AI  Figure 5 15  String Supervisor internal view    The environmental conditions that should be considered for the correct installation of the string  supervisor are     o TEMPERATURE RANGE  20  C to  50  C   o RELATIVE HUMIDITY 15 to 95    o ALTITUDE 1000m over sea level  o POLLUTION DEGREE Type Il    The information for the correct electrical connections  leds indications and dimensions  is provided  with the technical specification of the string supervisor  Please refer to this specific document for  further information     34 ELECTRICAL CONNECTION    POWER ELECTRONICS FREESUN    9 6  Overvoltage Protection    The Freesun Outdoor model is equipped with internal overvoltage protection as standard  Optional in  Frame 1   Optionally  the inverter can also be equipped with lightning protection     This built in overvoltage protectors will provide the corresponding protection for AC connection  DC  connection and also CAN interface for connecting the String Supervisors     The Freesun inverter requires auxiliary internal control voltage of 230VAC  In case the user provides  this power supply externally  as long as permitted by the current legislation of the country where the  installation takes place  the Freesun will provide the corresponding overvoltage protection for this  line     The user must consider that before measuring the insulation  it is required to remove or disconnect  the overvoltage protectors or the existing fuses must be removed     ELECTRICAL CO
6.     The cables are inserted from below through the pedestal and the base of the cabinet  opening the base  grilles in the front of the cabinet or in the rear part of the cabinet  according to installation requirements   In this way  it is possible the access to the bottom plates     Required glands must be installed in these bottom plates to let the correct installation of input and output  cables     5 1  External Connections    5 1 1  Electrical Connections to the AC Grid Power    The AC grid connection is made at the TN C  TN S  TT grid connection type  which must be  provided by the customer  using a 3 phase system equipped for 400V     In addition  it is also necessary to verify that existing rotary field on L1  L2 and L3 is the same  than inverter phase sequence  on the contrary a trip will be generated     The grid connection must be installed in a way such that a right hand rotary field lies at the input  of the cabinet  In case of a left hand rotary field is present  the inverter will generate a trip     Ensure the grid connection cable is fused at the nominal current indicated on the name plate  If  the specified nominal current differs from the nominal current of the fuse plug  the fuse plug  having the next highest nominal current may be used     The cables for AC connection will be fixed using M8 cable lugs        Figure 5 1  View of the base plates for cable routing and the FREESUN electrical connections       FSITP0007A       Figure 5 2  AC connection terminals
7.    reesun    SOLAR INVERTER       Solar Inverter    Hardware and Installation Manual    f  POWER ELECTRONICS          reesun    LVT SERIES    Solar Inverter    Hardware and Installation Manual    Edition  March 2011  FSMTHWO1HI Rev  H    FREESUN POWER ELECTRONICS    POWER ELECTRONICS FREESUN    SAFETY SYMBOLS    Always follow safety instructions to prevent accidents and potential hazards from occurring     WARNING This symbol means improper operation may results in serious personal  injury or death     be given because dangerous voltage may be present  Maintenance    Identifies shock hazards under certain conditions  Particular attention should  CAUTION  operation should be done by qualified personnel    Identifies potential hazards under certain conditions  Read the message and  follow the instructions carefully     be given because dangerous voltage may be present        Identifies shock hazards under certain conditions  Particular attention should    Edition of October 2010    This publication could present technical imprecision or misprints  The information here included will be  periodically modified and updated  and all those modifications will be incorporated in later editions   To consult the most updated information of this product you might access through our website  www power electronics com where the latest version of this manual can be downloaded     SAFETY SYMBOLS    TO rozm    FREESUN POWER ELECTRONICS    Revisions   Date Revision Description   30   03  2010 A
8.   H WIDTH  W DEPTH  D    1600                   FREESUN    FSDTD0002A    Figure 7 2 Freesun Frame 2 dimensions    FS0080                    Dimensions  mm            HEIGHT  H WIDTH  W DEPTH  D       FS0100    1440       1700          Figure       1700 1440 1040    7 3  Freesun Frame 3 dimensions       1125       FSDTD0003A    TRANSPORT AND HANDLING 39    LOr GA e m    FREESUN POWER ELECTRONICS    7 2  Transport Procedure    Transport Using a Pallet Truck   Crane     The inverter is properly labelled with instructions for handling with the packaging and must be  respected at all times  This also applies to the proper signalling of gravity symbol  Figure 7 4      The plinth panels must be unscrewed to transport the cabinet without a palette  This allows the fork of  a pallet truck forklift or crane to be inserted under the cabinet     To avoid damage or accidents during transport and on the installation site  the following measures  have been introduced        he transport markings stipulate that forklift or pallet trucks must always load the switch cabinets  by their long sides  front and rear sides of the FREESUN   It is forbidden to lift them by their sort  sides   Figure 7 5       Transport by crane is allowed if a suitable crane fork is used which is pushed through the  Openings in the base of the cabinet  Figure 7 6        The cabinets must not be tilted       To perform this manipulation is recommended that the inverter is left as close as possible to their  final locat
9.  82 01    Declares under its own responsibility  that the product   Solar Inverter  Brand  Power Electronics    Model name  Freesun Series    Is in conformity with the following European Directives     References Title  2006 95 CE Electrical Material intended to be used with certain limits of voltage  2004 108 CE Electromagnetic Compatibility    References of the harmonized technical norms applied under the Low Voltage Directive     References Title  EN 50178  1997     Electric devices to be used in power installations    References of the harmonized technical norms applied under the Electromagnetic  Compatibility Directive     References Title  EN 61000 6 2 2005 Electromagnetic compatibility  EMC     Part 6 2  Generic standards   Immunity for  industrial environments   EN 61000 6 4 2007 Electromagnetic compatibility  EMC     Part 6 4  Generic standards   Emission  standard for industrial environments  Electromagnetic compatibility  EMC     Part 3 12  Limits   Limits for harmonic  currents produced by equipment connected to public low voltage systems with input  current  gt  16 A and  lt   75 A per phase  Electromagnetic compatibility  EMC    Part 3 4  Limits   Limitation of emission of  harmonic currents in low voltage power supply systems for equipment with rated  current greater than 16 A  Electromagnetic Compatibility  EMC    Part 3 11  Limits     Limitation of voltage  changes  voltage fluctuations and flicker in public low voltage supply systems      Equipment with rate
10.  First edition   16 04 2010 B Data verification  String supervisor information   06   05  2010 C Datasheet updating    11 05 2010 D Inclusion of Frame 1 and Frame 2   30   06   2010 E Datasheet updating    16 07 2010 F Communications drawings    02 08 2010 G Figures and configuration table updating    21 03 2011 H Technical characteristics and configuration table updating     The equipment and technical documentation are periodically updated  Power Electronics reserves the right to modify all or part of the  contents of this manual without previous notice     POWER ELECTRONICS    INDEX    SAFET INS TAUG 08 fc                       T     INTRODUCTION EE  MES cuo NUMEN T                                                   ee VU mme    TEGANCGALGHABRALIERSTIOO    lalla    INSTALLATION Wie E VE  3 1  Requisites for the Installation                      GENERAL INFORMATION             0000cccccceeseesssnnnnnnseseeeeneeeeeceeeeeseccnnnnnsnsseeseeeeeseneeeesocoaannnsseees  dell  CONC NERIS mm  4 2  Electrical Connechons eene n nans nnn  sc M e SE SUDO NCS MR m                           did  Emergency SiOD RT                                         HE  Ai  CONCA E E  4 6  Commissioning  Maintenance and Repair                      i  4 7  Cooling system maintenance                      e    ELEGTRICALCONNEGTION                ai  51  External EREECHEN m                                     52 PISCINE Tc                        5 3  Sensors and Control Signals for the User                 
11.  dimensions and clearance FREESUN Frame 1 Indoor    Lone   e r  500  gt  I    FSTDT0008A    L     500                         Figure 3 5 General dimensions and clearance FREESUN Frame 2 Indoor    16 INSTALLATION REQUIREMENTS    POWER ELECTRONICS FREESUN                         S  uw    ba 1040                                       FSDTD0009A    Figure 3 6 General dimensions and clearance FREESUN Frame 3 Indoor    3 1 3  Minimum Workspace Requirements  Outdoor                    DULL RA    DOANDO OOOO noO     Concrete foundation slab Concrete foundation slab    FSDTD0010AI       Figure 3 7 General dimensions and clearance FREESUN Frame 1 Outdoor    INSTALLATION REQUIREMENTS 17    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    i 7 Ls   ee   ee 1  Concrete foundation slab    FSDTD0011AI                                  ADAM IDTNALDOD VAL ALNINCOTVLL eC UNA M CODI ODD          CPCI TCC LOODAN TTT      Concrete foundation slab       Figure 3 8 General dimensions and clearance FREESUN Frame 2 Outdoor    a    1040    Concrete foundation slab    FSDTD0012AI                Sinn    8 Concrete foundation slab         Figure 3 9 General dimensions and clearance FREESUN Frame 3 Outdoor    18 INSTALLATION REQUIREMENTS    POWER ELECTRONICS FREESUN    3 1 4  Inverter Protection Degree   EMC   Sound Levels    The outdoor model of the FREESUN is suitable for outdoor installation according to the IP54  protection degree  The control area of the inverter is implemented so that it is separate
12.  external   internal     The solar inverter must receive an internal 230VAC 50 60Hz single phase supply  In case of the  power supply for control voltage is externally provided  as long as permitted by the current  legislation of the country where the installation takes place  it must be protected with a back up  external auxiliary supply fuse B16A  1 pole     6 2 3  DC Power Connections    The DC power connections are made over the main DC plates of the inverter   Consider that DC connections should be checked to ensure they are mechanically tightened     The voltage on each of the main DC cables should be identical and should never exceed the  maximum DC voltage level of the inverter  It is also important to check not only DC voltage levels  but also the polarity of each of the DC main cables because the wrong polarity in one of the DC  main cables can damage the PV generator     COMMISSIONING    POWER ELECTRONICS FREESUN    6 2 4  Serial Interfaces    For external communication and string current supervision  the data cables have to be connected   Detailed information has been above described and specific connection is described in String  Supervisor documentation     6 3  Switch On    Once all tests and measurements have been performed  and all measured values lie within the  acceptable range  the inverter can be switched on for the first time     For this  all circuit breakers and overload switches in the Freesun must be switched on     At this time  the graphic display 
13.  make up the  installation and its interconnection  as well as the different lines that may be necessary for both power  and communications     In case the 230Vac power supply for control is externally provided  it will be connected to the  elements showed in the scheme     The provision of this power supply to the inverters is legislated by the relevant regulatory agency of  the country where the installation is located and must therefore be respected     28 ELECTRICAL CONNECTION    POWER ELECTRONICS    FREESUN    To connect and power those elements that are not part of the scope of Power Electronics  consider    the installation instructions of the respective manufacturers  switch  router             Please  consider the following general cable layout           LEGEND NETWORK  CONFIGURATION           230VAC AUX  POWER SUPPLY   gt  gt  gt     24VDC STRING SUPERVISOR   POWER SUPPLY              CAN COMMUNICATION   FE   cass  ETHERNET COMMUNICATION PC   RIPPLE CONTROL RECEIVER  ZZZ COMMUNICATION   n A    ETHERNET CAT 6    nonno     o  mm o o mm mm mm wm    MASTER    Freesun  Data Center    v    CAN   Y  2x2x0 75mm    Y  SCREENED   Y    Iv    STRING SUPERVISOR          lt   INTERNET   gt     ALZA  ELECTRICITY  SUPPLIER  T BA  beem   Public Grid  vimIIETRT Operator         230VAC AUX   3x2 5mm   POWER SUPPLY         Ripple Control  Receiver    Switch    6x0 5mm   TWISTED  SCREENED        ee ee ee ee ee ee eelere                               I        I        LI       Power Cont
14.  present for a longer period of time  For these reasons  wait a minimum of 10 minutes after switching  off before opening the device and wait until the voltage indicator LEDs of the DC bus are off     Following this procedure it is possible to work on the solar inverter in a safe way     ELECTRICAL CONNECTION 27    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    9 9  sensors and Control Signals for the User    All required information about digital I O and analogue I O are described below   Two analogue sensors and one PT100 temperature sensor can be connected to the Freesun     Their connection is made in the connection area of the inverter     Factory Settings            CONNECTOR X1 CONNECTOR X2   ER 00  ALWAYS OFF AO   00  NONE  DO1 2    AO    8    PEN d An    9  E 5 00  ALWAYS ON Alt   2   DO2 8 AI2    1  13  2  14  PT100 a  is   24V Usr DI   16  SEES Common Terminal  24Vdc    0  Non used  0  Non used     24V Usr  FSDTC0002AI    Figure 5 7  Control terminals for the user    Further information about setting of each input and output  please refer to the Freesun Programming  and Software Manual     5 4  Inverter Communication Connection    The device can be equipped with various interface cards for the communication between the inverter  and a PC or modem   The data can be transferred using the following    o Ethernet   o RS232 RS485   USB   o GAN  For the String Supervisor    o GSM     The following control scheme provides information of the different elements that can
15. 86 10  6437 9197   Fax   86 10  6437 9181   Power Electronics Asia Ltd    20 F Winbase Centre   208 Queen s Road Central   HONG KONG    R P  CHINA  Power Electronics Asia HQ Co   Room   305  SK Hub Primo Building   953 1  Dokok dong  Gangnam gu   135 270    SEOUL   KOREA   Tel    82  2 3462 4656   Fax   82  2 3462 4657   Power Electronics India   No 26 3rd Cross    Vishwanathapuram   625014   MADURAI   Tel    91  452 434 7348   Fax   91  452 434 7348   P E  Internacional Mexico S de RL   Calle Cerrada Jos   Vasconcelos  9   Colonia Tlalnepantla Centro    Tlanlnepantla de Baz   CP 54000   MEXICO DF   Tel    52  55 5390 8818   Tel    52  55 5390 8363   Tel    52  55 5390 8195   Power Electronics Nueva Zelanda Ltd   12A Opawa Road  Waltham   CHRISTCHURCH 8023   P O  Box 1269  CHRISTCHURCH 8140   Tel    64 3  379 98 26   Fax   64 3  379 98 27    42     POWER ELECTRONICS           www power electronics com    
16. D  6x0 5mm                 RIPPLE CONTROL  RECEIVER           Non Used Ei Terminal   5Vdc       DIGITAL INPUTS    Output Relays       FSDTR0003AI    Figure 5 11  Connection between the Power Control Interface and the radio ripple control receiver    5 9  String Supervisor Description    The main function of the string supervisor is monitoring the strings status to detect quickly their  malfunction  To do this  using a current transducer  hall effect   the current provided by each string is  measured and in this way it is possible to analyse easily the performance of each single one  In case  of one of the string produces less energy than the others will be detected thanks to the string  supervisor     The string supervisor is a  slave  of the solar inverter  Its function is to inform the solar inverter and to  connect in parallel the panel strings  To achieve this  the string supervisor is provided with two  communication buses already implemented  CAN bus to communicate with the inverter and RS485   just in case the user requires to access to the STRING SUPERVISOR  via MODBUS     Each string supervisor is provided with an overvoltage protector that protects the installation  Power  Electronics string supervisor detects the status of this overvoltage protector and in case it is out of  service  as the result of action against a very high energetic value overvoltage  it will inform to the  solar inverter  With this information the maintenance people will have able of managing 
17. NA  Tel    34  96 853 51 94   Fax   34  96 812 66 23  VIZCAYA   Parque de Actividades e Empresariales Asuar  n   Edificio Asua  1  B   Ctra  Bilbao   Plencia   48950    ERANDIO   Tel   434  96 136 65 57   Fax   34  94 431 79 08  MADRID    Avda  Rey Juan Carlos    98  4  C   28916    LEGAN  S  Tel    34  96 136 65 57   Fax   34  91 687 53 84  SEVILLA   C  Averroes  6   Edificio Eurosevilla   41020   SEVILLA  Tel    34  96 136 65 57   Fax   34  95 451 57 73  LA CORUNA   Plaza Agramar  5   Bajo   Perillo   Oleiros   15172   LA CORUNA  Tel    34  96 136 65 57   Fax   34  98 163 45 83   INTERNATIONAL SUBSIDIARIES  Power Electronics Deutschland GmbH    Dieselstrasse  77   D 90441 e N  RNBERG e GERMANY  Tel    49  911 99 43 99 0   Fax   49  911 99 43 99 8  Power Electronics Australia Pty Ltd   U6  30 34 Octal St  Yatala    BRISBANE  QUEENSLAND 4207   P O  Box  3166  Browns Plains  Queensland 4118   AUSTRALIA  Tel    61  7 3386 1993   Fax   61  7 3386 1997  Power Electronics Brazil Ltda   Av  Guido Caloi  1985 Galpao 09   CEP 05802 140   SAO PAULO   BRASIL  Tel    55  11 5891 9612   Tel    55  11 5891 9762  Power Electronics Chile Ltda   Los Productores   4439     Huechuraba   SANTIAGO   CHILE  Tel    56   2  244 0308   0327   0335   Fax   56   2  244 0395    Oficina Petronila   246  Casa 19   ANTOFAGASTA   CHILE  Tel   456   55  793 965    Power Electronics Beijing   Room 509  Yiheng Building   No 28 East Road  Beisanhuan   100013  Chaoyang  District   BEIJING   R P  CHINA   Tel    
18. NNECTION    35    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    36    6  COMMISSIONING    Before the first commissioning  all work performed on the device should be thoroughly checked  Special  care with the voltages on the DC and AC sides is required to ensure conformance with the limits allowed  on the inverter  Nameplate data must be observed     6 1  Initial Conditions    Following conditions must be observed to allow a correct commissioning of the solar inverter  Before  the inverter is put into operation  will be required     o Ensure an appropriate grounding resistance  This is decisive for the safety of the  complete system and must therefore be determined before the system is started for the  first time     o Every circuit breaker and overload switch in the Freesun must be switched off when it is  delivered     6 2  Verify the Wiring    When performing the cabling checks  the connections are first checked for correctness and proper  installation     6 2 1  AC Grid Connection    The connection made to the feed in cables is 3 phase     It must be checked that the inverter is connected to the correct grid connection type  TN C  TN S  or TT   In addition  it is also necessary to verify that existing rotary field on R  S and T is the same  than inverter phase sequence  on the contrary a trip will be generated     The level of the AC voltage should be measured and logged  The Freesun feeds into the grid  using 3 x 400V  10      6 2 2  Auxiliary Control Voltage Supply 
19. ONSIDERATIONS    The cable for CAN connection between the solar inverter and the String Supervisor must meet the  following specifications to ensure proper operation     o Family  CAN BUS 2x2x0 75mm  VIOLET  o Section  0 75mm    o Colour code  DIN 47100   o Ext cover  PVC   o Characteristic impedance  1200    The recommended maximum cable length is between 75m and 100m for a data transmission speed of  500Kbps  For longer distances please contact Power Electronics    Excessive bending of CAN cables can reduce their ability to meet the CAN specification  Standard    Thick     cables shall have a bending radius of greater than 75mm  3    Standard    Thin    cables shall have a bending  radius of greater than 50mm  2      These generic cable types are available in a variety of different offerings such as FLEX  HAZ DUTY   CLASS I  600V   UV RESISTANT  etc     30 ELECTRICAL CONNECTION    POWER ELECTRONICS FREESUN    Case B  J900 connector is a screw terminal connector                FREESUN PS    LVT SERIES POWER ELECTRONICS       ni TWISTED     _   Jj SHIELDED  2x2x0 75mm     1 TWISTED  4 SHIELDED    lei 2x2x0 75mm               SHIELDED  3x0 5mme   SHIELDED     TT 3x0 5mm                    E    LA 3   ERI STRING SUPERVISOR   HVDC 124vac Dee  24Vde OVde  VDC IN VDC OUT    STRING SUPERVISOR        YDC IN VDC OUT        POWER ELECTRONICS       POWER ELECTRONICS    EEN ET  FEAT  FTT TI FTT TI  till 1l illl Ll    STRING STRING STRING STRING STRING STRING STRING STRING STRING STRING 
20. STRING STRING       FSDTROOO2BI    Figure 5 10  Connection with String Supervisor using a screw terminal connector    CONSIDERATIONS    The cable for CAN connection between the solar inverter and the String Supervisor must meet the  following specifications to ensure proper operation     o Family  CAN BUS 2x2x0 75mm  VIOLET  o Section  0 75mm    o Colour code  DIN 47100   o Ext cover  PVC   o Characteristic impedance  1200    The recommended maximum cable length is between 75m and 100m for a data transmission speed of  500Kbps  For longer distances please contact Power Electronics    Excessive bending of CAN cables can reduce their ability to meet the CAN specification  Standard    Thick     cables shall have a bending radius of greater than 75mm  3    Standard    Thin    cables shall have a bending  radius of greater than 50mm  2      These generic cable types are available in a variety of different offerings such as FLEX  HAZ DUTY   CLASS I  600V   UV RESISTANT  etc     ELECTRICAL CONNECTION 3 1    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    5 4 2  Details for connection between Power Control Interface  PCI  and the  Ripple Control Receiver    In the following drawing is described the connection of the Power Control Interface to a radio  ripple control receiver  Please  check the manufacture s user manual for more information about  the configuration of the radio ripple control device     POWER CONTROL  INTERFACE    f gt     POWER ELECTRONICS         TWISTED  SHIELDE
21. To achieve this it is required to switch off the inverter  Once the device is switched  off  both AC and DC contactors will be open and normally there will be no voltage in the internal  circuits  Nevertheless  residual voltage may be present in the DC bus  Therefore to disconnect the  inverter  the following procedure must be followed     o Switch off the inverter with the    OFF ON    switch  OFF position   or with the graphic  display unit when it is in local mode  by pressing the STOP RESET button     o  Thefollowing power supplies must be disconnected       AC Grid voltage for the grid feed in  by switching off the main AC internal circuit  breakers        Auxiliary control voltage 230Vac  by switching off the circuit breakers       DC voltage from the photovoltaic generator  disconnection is normally done  automatically by the motorized switch  In case the disconnection is done  manually  use the handle attached to the inverter   To ensure that we have no  voltage on the DC side also will be necessary to switch off the breaker included  in each String Supervisor  Thus even in case of accident or other unforeseen  events  it will be possible to disconnect the inverter safely     The device contains capacitors on the AC and DC sides that must discharge once the device has  been switched off  After switching off  there are dangerous accidental contact voltages present within  the device for several minutes  If there is a fault in the device  these voltages may also remain 
22. abelling  L1  L2 and L3      e Check the polarity of DC voltages  DV  and PV   in the connection plates of the  inverter     e The photovoltaic generator has been checked with an insulation test to ensure  that there is no ground fault     GENERAL INFORMATION 21    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    4 4  Emergency Stop    The Freesun inverter outdoor model is not provided with external emergency stop  but it can be  ordered as an option  The emergency stop button will provide the corresponding normally closed  contacts free potential to be correspondly wired to the Freesun     Each emergency stop must be powered only from the corresponding inverter     4 5  Operation    Apart from the FREESUN Control  there are no control elements on the device  The cabinet doors  must only be opened for commissioning  maintenance and troubleshooting  as well as for data query  and parameter setting  Please also note the following safety instructions for working on the device     4 6  Commissioning  Maintenance and Repair    All work on the FREESUN may only be performed when the device is safely disconnected from de  PV voltage  DC   the grid voltage  AC   and the auxiliary power supply  internal or external   when  these power sources are secured against being switched on again  and when it has been checked  that the device is voltage free  Only qualified technical personnel may undertake any such task        JIDD   AAMALLHALHAALLHALLALLHALLTLLHALLTLLE ALLE ALLELUEUEI UUNIIN 
23. cial hazards       An active power source is connected  This means that  regardless to the operating mode of the  inverter  there may be voltage present  either from the photovoltaic generator and or the  FREESUN  This is especially important to consider when disconnecting particular parts of the  system       Very high DC voltages are present  no zero crossing  which  in case of a fault or inappropriate  use of fuses or plugs  may lead to arcing       The short circuit current of the photovoltaic generator is only slightly more than the maximum  operating current and is also dependent on the level of a solar irradiation  This means that  if a  short circuit occurs in the system  the existing circuit breakers are not guaranteed to switch off       A highly branched generator array may be difficult to disconnect if a fault develops  e  g  short  circuit   We recommend the extra use of external DC circuit breakers for disconnecting the  inverter and or the DC main cables   String supervisors  DC circuit breakers are built in   One  circuit breaker should be allocated to each input  and these should be located near to de  FREESUN as described in the standard VDE0100 part 7 712 and the VDI 6012 regulations       Power Electronics must be informed of the required AC grid connection type      The device contains capacitors on the AC and DC sides  The discharge time of the capacitors is  longer than 10 minutes  For this reason  it is required to wait longer than this time before mak
24. d current 75 A and subjected to conditional connection    EN 61000 3 12 2005  IEC 61000 3 4 1998    EN 61000 3 11 2000    Note      the requirements of the new norm IEC 61209 1 2010 have been considered in the design and test of our range  FREESUN    Paterna  28  of April 2010    David Salvo  Executive Director       f   POWER ELECTRONICS    www powerelectronics es   www power electronics com  24 Hours Technical Assistance 365 days a year     34 96 136 65 57    HEADQUARTER   VALENCIA    SPAIN    C  Leonardo da Vinci  24     26   Parque Tecnol  gico   46980     PATERNA   VALENCIA   ESPANA  Tel  902 40 20 70   Tel    34  96 136 65 57   Fax   34  96 131 82 01    CATALUNA    CANARIAS    LEVANTE    NORTE  CENTRO  SUR  GALICIA  GERMANY    AUSTRALIA    BRAZIL    CHILE    CHINA    KOREA    INDIA    MEXICO    NEW  ZEALAND    BRANCHES   BARCELONA    Avda  de la Ferrer  a  86 88    08110    MONTCADA I REIXAC  Tel    34  96 136 65 57   Fax   34  93 564 47 52  LLEIDA    C  Terrasa  13   Bajo   25005   LLEIDA  Tel    34  97 372 59 52   Fax   34  97 372 59 52  LAS PALMAS   C  Juan de la Cierva  4   35200   TELDE  Tel    34  928 68 26 47   Fax   34  928 68 26 47  VALENCIA   Leonardo da Vinci  24 26   46980 e PATERNA  Tel    34  96 136 65 57   Fax   34  96 131 82 01  CASTELL  N    C  Juan Bautista Poeta   2  Piso   Puerta 4   12006   CASTELL  N  Tel    34  96 434 03 78   Tel    34  96 136 65 57   Fax   34  96 434 14 95  MURCIA   Pol  Residencial Santa Ana   Avda  Venecia  17   30319   CARTAGE
25. d from the  power area        Qe       S    e     nece  IK  om    i               FSITG0007A  Figure 3 10 Internal view of the FREESUN    With regard to the EMC emissions and the noise level  the inverter has been designed to be  installed in an industrial environment or for outdoor installation     INSTALLATION REQUIREMENTS    19    LTO  P D   e In    FREESUN POWER ELECTRONICS    3 1 5  Ventilation    In order to cool the inverter  the ventilation system must be free of any obstructions to ensure the    required inlet ventilation and heat dissipation   The specified minimum clearances must be maintained to ensure the proper ventilation and heat    dissipation     The permissible ambient temperature in order to ensure the correct operation and maximum feed   in performance is between  20  C and  50  C   The exhaust air  waste heat  is blown out through the upper cover        FSITG0008A    Figure 3 11  Ventilation Concept of the FREESUN     20 INSTALLATION REQUIREMENTS    POWER ELECTRONICS FREESUN    4  GENERAL INFORMATION    4 1  Correct Use    Appropriate use of the equipment includes     o Observation of the safety instructions described in the whole manual   o Observation of the instructions in the FREESUN user manual     o Observation of additional documentation for variants and options  such as grounded  operation  GFDI  and the extended voltage range  EVR      o Observation of the technical data for the device     4 2  AC grid connection    The customer must determine t
26. e front cover is  removed       Handle the solar inverter with care according to its weight        nstall the inverter according to the instructions within this manual     Do not place heavy objects on the inverter      Ensure that the mounting orientation is correct      Do not drop the inverter or subject it to impact       The Freesun inverters contain static sensitive printed circuits boards  Use static safety  procedures when handling these boards       Avoid installing the inverter in conditions that differ from those described in the Technical  Characteristics section     TRIAL RUN    Verify all parameters before operating the inverter       Always apply voltage and current signals to each terminal that are within levels indicated within  this manual  Otherwise  damage to the inverter may result     SAFETY INSTRUCTIONS    POWER ELECTRONICS FREESUN    OPERATION PRECAUTIONS    Do not modify or alter anything within the inverter       Before programming or operating the Freesun Series  initialise all parameters back to factory  default values     WHO S ABLE TO APPLY THE FOLLOWING INSTRUCTIONS       Only trained electricians approved by the responsible energy supply company may install and  commission the inverters  The instructions assume that you  the installer  are familiar with  electrical installations and know the corresponding rules and regulations     SPECIAL HAZARDS OF PHOTOVOLTAIC SYSTEMS    Photovoltaic systems have special characteristics that can represent spe
27. h parts missing even if the  installation is complete   Otherwise you may get an electric shock     Do not allow lint  paper  wood chips  dust  metallic chips or other foreign matter into the inverter   Otherwise fire or accident could occur     SAFETY INSTRUCTIONS    7    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    8      N  WARNINGS    RECEPTION     he Freesun is carefully tested and perfectly packed before leaving the factory        n the even of transport damage  please ensure that you notify the transport agency and POWER  ELECTRONICS  902 40 20 70  International  34 96 136 65 57  or your nearest agent  within  24hrs from receipt of the goods     UNPACKING    Make sure model and serial number of the solar inverter are the same on the box  delivery note  and unit       Each solar inverter is supplied with a technical manual     RECYCLING      Packing of the equipments should be recycled  For this  it is necessary to separate different  materials included  plastic  paper  cardboard  wood       and deposit them on proper banks       Waste products of electric and electronic devices should be selectively collected for their correct  environmental management     SAFETY      Before operating the solar inverter  read this manual thoroughly to gain and understanding of the  unit  If any doubt exists then please contact POWER ELECTRONICS   902 40 20 70    34 96  136 65 57  or your nearest agent       Wear safety glasses when operating the inverter with power applied and th
28. he required grid connection type for the AC grid connection  TN C   TN S  TT grid  and coordinate it with Power Electronics     Ensure the grid connection cable for grid feeding is fused at the nominal current indicated on the  name plate  If the specified nominal current differs front the nominal current of the fuse plug  the fuse  plug having the next highest nominal current may be used  A power switch is used for the optional  load disconnecting switch     4 3  Power Supplies    Switching on the different power supplies     o Connection of main AC grid voltage for the grid feed in     o Connection of auxiliary control voltage 230Vac  internal power supply   There is the  option of feeding it externally  as long as permitted by the current legislation of the  country where the installation takes place     o DC voltage connection from the photovoltaic generator must occur in the sequence  described and may only be performed when the following conditions are satisfied     e Verify that all connections have been made according to the  Electrical  Connections  section     e The protective ground connection for grid feed in and for internal power supply  is correctly connected     e  t must be checked that the inverter is connected to the correct grid connection  type  TN C  TN S or TT   In addition  it is also necessary to verify that existing  rotary field on R  S and T is the same than inverter phase sequence  on the  contrary a trip will be generated  To this end  consider l
29. ightning and  V overvoltage  protections    ck  H   cz rozm    With AC and DC overvoltage protection       With AC and DC overvoltage protection and lightning protection  From 450 to 820V   Transformer connection to 270V    From 405 to 820V     Transformer connection to 240V         Maximum power  point range  MPP       N  String Supervisor SI   F With auxiliary power supply for String Supervisor connection   N Not included Indoor    Heating   Includes heating resistance Indoor     15kV  20kV  22kV  24kV  30kV  1MPPT  2MPPT          Without auxiliary power supply for String Supervisor connection           Medium Voltage  Output    1  2          MPPT Configuration    10MPPT        1  Option H is only suitable for Freesun HE and Freesun HES series  Modular inverter      2 Available for LVT Series     3  Included in the Outdoor model of the Freesun LVT series     4  This option is only suitable for Freesun HES series  For other output voltages consult with Power Electronics     5  Onl available for HE and HES series  The maximum number of MPPTs depends on the number of modules implemented in  each inverter  One MPPT per module  This is an optional kit configured according to the MPPT number                             INTRODUCTION 11    FREESUN POWER ELECTRONICS    1 2  Standard Ratings      INPUT   OUTPUT  Max  PV Nominal AC Output   Operating Grid Voltage Nominal AC  REFERENCE Power  1  Power  10  Current   Ppv   Pac   Vac   lac  nom     n FS00200TOO0000       24kWp 20kW 400V 
30. ing  any operation or maintenance actions in the unit     SAFETY INSTRUCTIONS    9    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    1 INTRODUCTION    In order to guarantee correct connection and reliable operation of the device  it is recommended to read  carefully the safety and installation instructions in the following sections        FSITG0002A    Figure 1 1  FREESUN Frame 1 Outdoor Front View    For a safe transport of the unit  the internal transformer will be fixed  It is important to remove the  corresponding fixations once the unit has been correctly placed on site and before starting with electrical  connections         gt  PIT      4 ul    PRIM  INIHI tI ji      wll       FSITG0003A    Figure 1 2  FREESUN Frame 3 Indoor Front View    10 SAFETY INSTRUCTIONS    DAWED CI CRTONMAIC C EDI   CI I N  POWER ELECTRONICS FHEESUN                            1 1  Configuration Table    EXAMPLE    CODE  FS01000TOSAVAFRXXY      FS   Freesun Series    0100   100kw   Output Power 0080   80kw  Inverter Location   Outdoor    TH Isolating Inverter with Low Voltage Transformer  LVT Series     Transformer H High Efficiency Inverter  HE and HES Series     Maximum input 09   900VDC  voltage 10   1000vDC    Adjustable isolation between          and earth                                          Monitoring of the    i Negative of the photovoltaic installation earth connected   isolation    Positive of the photovoltaic installation earth connected     Without overvoltage protection    L
31. ion     P uli x   an E uat     ul pt    Figure 7 4  Gravity centre marking       Figure 7 5  With  forklift   pallet truck     40 TRANSPORT AND HANDLING    POWER ELECTRONICS FREESUN       Figure 7 6   Crane fork     7 3  Prior to connection    In the rear side of the solar inverter are located the SECURITY FIXATIONS FOR TRANSPORT in  both the transformer and the inductance of the inverter  Before making any connections to the  inverter is necessary to consider     If the inverters are going to be installed side by side  it is NECESSARY to REMOVE these  SECURITY FIXATIONS BEFORE placing them in their final location     It is ESSENTIAL to REMOVE them BEFORE CONNECTING  Make sure that all fixations are  properly removed and put back the rear covers of the inverter     The inverter can now be placed in its final location and the connection procedure can be done as  described in the installation manual attached to the inverter        J FSITM0002A    Figure 7 7  Security fixation for transport Frame 1    TRANSPORT AND HANDLING    41    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS       FSITM0003A    Figure 7 8  Security fixations for transport Frame 2    en Y I E        i RK  FSITM0004A FSITM0005A       Figure 7 9  Security fixations for transport Frame 3    42 TRANSPORT AND HANDLING    DECLARATION OF CONFORMITY CE    The Company    Name  POWER ELECTRONICS ESPANA  S L    Address  C  Leonardo Da Vinci  24 26  46980 Paterna  Valencia   Telephone   34 96 136 65 57   Fax   34 96 131
32. isor Interface CANopen   Modbus    RS232   RS485   USB   Ethernet  BOISE  Modbus Protocol  Modbus TCP  a 2 electrically isolated programmable switched relays  She hel Cupue  250VAC  8A or 30 VDC  8A   Analogue Outputs 1 Analogue  Output galvanically isolated     Standard  Outdoor    Optional  Indoor   No  Outdoor    Optional  Indoor   Standard  bed     Overvoltage Protectors for Auxiliary POEM  Supply yp    Lightning Protections Optional Type      Certification CE  2006 95 CE  2004 108 CE  Safety  7  EN 62109 1  REGULATIONS EMV EN 61000 6 2  EN 61000 6 4  EN 61000 3 4  EN 61000 3 12    Designed according to BDEW     MV Guideline    Notes     1  Note the possible increase of the panel s voltage Voc at low temperatures     2  For copper conductors  The installer must also consider factors such as length of cable for each installation  environmental conditions   aluminium conductors  installation methods and requirements set out in current regulations applicable in the country of installation     3  In case other temperature range is required  please  contact with Power Electronics     4  For higher altitude consult with Power Electronics     5  In cases where the installation has the positive pole or the negative pole earth connected  this protection will be disconnected     6  In T  V certification process        INTRODUCTION 13    FREESUN POWER ELECTRONICS    3  INSTALLATION REQUIREMENTS    3 1  Requisites for the Installation    3 1 1  Foundation    The foundation must guara
33. ntee that the positioning of the inverter is solid and safe  It must  provide the load carrying capacity necessary to cope with the weight of the inverter    Pouring and structural inspection of the foundation slab should be performed on site    The inverter cabinet must be installed on a level surface     The cables must be routed into the inverter from below  where the plates that allows access to the  DC and AC terminals  The foundation must include access for them  To make this possible  the  foundation must include a pipe or cable carrier  Dimensions drawings for this input and output  connections are described in  Electrical Connection  section     FSITG0004A       Figure 3 1  Installation of the Frame 1 Outdoor with concrete foundation slab     14 INSTALLATION REQUIREMENTS    POWER ELECTRONICS FREESUN    Cth   pt LUUUTIVITTVKKKEKKKKTKKKHEKKCKKKKKKKKKKTKKKKKKKKKKKKKKKKKKKKKKKKKKKKKXK soe    FSITG0005A    Figure 3 2  Installation of the Frame 2 Outdoor with concrete foundation slab     III   IIT LT LL PEUT    FSITG0006A    Figure 3 3  Installation of the Frame 3 Outdoor with concrete foundation slab     INSTALLATION REQUIREMENTS          15    Oo bom       FREESUN POWER ELECTRONICS    3 1 2  Minimum Workspace Requirements  Indoor     Please  be sure that the installation site meet with the minimum clearances and passage widths  as described below  when installing the equipment     i  I    755 a  500 i                              L        FSDTD0007A    Figure 3 4 General
34. r and the inductance of the inverter  Before making any connections to the  inverter is necessary to consider     If the inverters are going to be installed side by side  it is NECESSARY to REMOVE these  SECURITY FIXATIONS BEFORE placing them in their final location     It is ESSENTIAL to REMOVE them BEFORE CONNECTING  Make sure that all fixations are  properly removed and put back the rear covers of the inverter     The inverter can now be placed in its final location and the connection procedure can be done as  described in the installation manual attached to the inverter     WARNINGS AND RECOMMENDATIONS    connected  the following instructions must be considered    The only point in the installation where the positive or the negative pole should be  grounded is in the proper inverter  through the 4 pole circuit breaker that is added to that  effect   It is important to note that if there was another grounded connection elsewhere in  the installation  in the panels themselves  in the String Supervisor  etc    the protection  provided by the additional circuit breaker would have NO effect       If your device has the positive or negative pole of the photovoltaic system earth    Therefore  it is recommended to revise periodically the insulation between the pole that is going to be  grounded and the earth  Like this  it will be possible to detect a ground fault unwanted in other points of the  installation  This will prevent the circuit breaker from providing inappropriate pro
35. rol  Interface        TIERE RN ERE IN        24VDC   3x0 5mm     SCREENED      Ej E i    STRING SUPERVISOR STRING SUPERVISOR STRING SUPERVISOR    D wn    cceccecccecccecc              lt  lt  lt  lt  lt             lt  lt  lt  lt  lt                lt  lt  lt  lt  lt              lt  lt  lt  lt  lt     Al    Figure 5 8  General communications layout    ELECTRICAL CONNECTION 29    ck H   se P GA e m    FREESUN POWER ELECTRONICS    5 4 1  Details for connection between Freesun and String Supervisor    The Freesun and the String Supervisor are connected by a CAN interface  The CAN interface  connector is J900 and it is located in the control board of the Freesun     Connections of String Supervisor with the Freesun inverter are described in the following  drawings     Case A  J900 connector is a DB9 connector     FREESUN een    LVT SERIES POWER ELECTRONICS  CONTROL BOARD                 J900    N C NOT CONNECTED  CAN L   GND   N C NOT CONNECTED  N C NOT CONNECTED  GND   CAN H   N C NOT CONNECTED  N C NOT CONNECTED       oo   o GoOo m o jN       il TWISTED  SHIELDED            LS 2x2x0 75mm     HVDC  24vac OVde   24V dc OVde  VDC IN VDC OUT             STRING SUPERVISOR STRING SUPERVISOR         YDC IN VDC OUT    POWER ELECTRONICS POWER ELECTRONICS       iili ll iilii Il    STRING STRING STRING STRING STRING STRING STRING STRING STRING STRING STRING STRING    Trt Tr I  INI II  TTT TI TTT T    FSDTR0002AI    Figure 5 9  Connection with string supervisor using a DB9 connector     C
36. tection due to eventual  uncontrolled ground leakages     6 SAFETY INSTRUCTIONS    POWER ELECTRONICS FREESUN    In this manual  safety messages are classified as follows      N WARNING    If possible do not remove the solar inverter cover while the power is applied or the unit is in  operation  Otherwise electric shock could occur     If possible do not run the solar inverter with any of the covers removed  Otherwise you may get an  electric shock due to the high voltage terminals inside the inverter     Do not open the inverter doors except when necessary for installation or maintenance  even in  such cases  remove the input power if possible  Otherwise you may access the charged circuits and  get an electric shock     Operate the switches with dry hands   Otherwise you may get an electric shock     Do not use cables with damaged insulation   Otherwise you may get an electric shock     Do not subject the cables to abrasions  excessive stress  heavy loads or pinching   Otherwise  you may get an electric shock      N CAUTION    Install the inverter on a non flammable surface  Do not place flammable material nearby   Otherwise fire could occur     Disconnect the input power if the solar inverter gets damaged   Otherwise it could result in a secondary accident or fire     After the input power is applied or removed  the inverter will remain hot for a couple of minutes   Touching hot parts may result in skin burns     Do not apply power to a damaged inverter or to an inverter wit
37. the situation    properly    The string supervisor has two fuses for each string that disconnects the panels forming this string in  case of overload  If the fuse is blown  it would be detected by the supervisor string  because the  current of this string would be zero    The string supervisor provides a digital input to detect the theft of panels    The string supervisor has one on load disconnector already built in that allows a complete isolation of    the string from the installation by switching off both  the positive and the negative poles  This is very  useful when maintenance operations are required but without stopping energy production     32 ELECTRICAL CONNECTION    POWER ELECTRONICS FREESUN       FSITG0011A    Figure 5 12  String Supervisor External View    External dimensions for string supervisor are described in the following drawing     ck  H   cz P 0 e m       FSDTD0013A    Figure 5 13  String Supervisor dimensions    ELECTRICAL CONNECTION 33    FREESUN POWER ELECTRONICS    In the following drawing main components of the string supervisor are shown         HALL EFFECT  FUSE TRANSFORMER  1 0      E R TI    8 0  2 OVERVOLTAGE     amp   PROTECTOR ON LOAD  ui   PE DISCONNECTOR      o0  HVDC      CONTROL BOARD O CAN COMMUNICATION    O RS485 COMMUNICATION nt   HVDC  FUSE  1          2        8          FSDTP0001AI  Figure 5 14  String Supervisor components  CONTROL BOARD TERMINAL     TERMINAL     BREAKER       STRING FUSES     STRING FUSES     OVERVOLTAGE PROTECTOR
38. unit is connected  the LED  FAULT  is flashing while the inverter is  synchronizing     Once the inverter is synchronized  the LED will turn off  In this way  the inverter is completely  connected in both AC and DC sides  After that  you can proceed to start the unit by pressing the  START button of the graphic display unit if it is in local mode  or with the key switch  select  ON   position  inside the cabinet     The Freesun will now start automatically after checking the grid voltage and frequency parameters   Finally  the motorized DC breaker is activated automatically and connects the PV generator     COMMISSIONING    37    ck  H   cz P 0 e m    FREESUN POWER ELECTRONICS    38       T  TRANSPORT AND HANDLING    Only the transport methods described in the installation guide are permissible  please follow the transport  requirements here described  Any other transport method or system could damage the unit     7 1  Weights and dimensions Freesun    Please note the heavy weight of the inverter  To assist with transporting  the data sheet of the  dimensions and weight must be considered      N CAUTION    Heavy weight of the cabinet unit   Danger of tipping during transport  The cabinet must always be transported upright       REFERENCE     HEIGHT  H    WIDTH  W eee ng   FS000      FS0020  FS0025  FS0030 1600 840  FS0035          FSDTD0001A  Figure 7 1 Freesun Frame 1 dimensions    TRANSPORT AND HANDLING    POWER ELECTRONICS    FS0040  FS0050          DIMENSIONS  mm   HEIGHT
    