Home

Software Guide - Diginet Control Systems

image

Contents

1. Ir 7 RAPIX ADDRESSING Version 2 6 SOFTWARE MANUAL Copyright 2015 Diginet Control Systems Pty Ltd Member of the Gerard Lighting Group DIGINET CONTROL SYSTEMS RAPIX Addressing Manual Copyright O 2015 Diginet Control Systems Pty Ltd Member of the Gerard Lighting Group All rights reserved No parts of this work may be reproduced in any form or by any means graphic electronic or mechanical including photocopying recording taping or information storage and retrieval systems without the written permission ofthe publisher Products that are referred to in this document may be either trademarks and or registered trademarks of the respective owners The publisher and the author make no claim to these trademarks While every precaution has been taken in the preparation ofthis document the publisher and the author assume no responsibility for errors or omissions or for damages resulting from the use ofinformation contained in this document or from the use of programs and source code that may accompanyit In no event shall the publisher and the author be liable for any loss of profit or any other commercial damage caused or alleged to have been caused directly or indirectly by this document Generated March 2015 Table of Contents 3 Table of Contents Part 1 Part 2 a FF O N Part 3 Part 4 O ON OO oO FP OQ N Part 5 Part 6 Introduction 5 Glossary OF Terms iii A E a a 5
2. Are you sure you want to set the Requested Short Address of each DALI _ Device to clear The Clear All Short Addresses confirmation window Next click Yes to set the requested short address of all DALI Devices to lt Clear gt The list of DALI Devices will now look something like this Copyright 2015 Diginet Control Systems Pty Ltd 92 RAPIX Addressing Manual State Actual SA Requested SA New SA Device Type Contimed Actual Short Address n 10 Alez None B Emergency L n 1 lez None LED L a 12 Clears None LI A 13 Clear gt None a 14 lez None w L p 15 Clears None Z A 16 Clear gt None Q 17 les None E 18 Clear None Fluorescent 19 Alear None Huorescent List of DALI Devices on the DALI Line with requested short addresses set to be cleared The DALI Device short addresses are now ready to be cleared Click the Readdress button to apply the changes The Readdress button Note This action is not undoable Note The next time that the DALI Line is rescanned the DALI Devices with cleared short addresses will be randomly readdressed to unoccupied short addresses starting from address 0 See topic Scanning a DALI LineD42 for more information on what happens during a DALI Line scan Readdressing DALI Devices on a Mobile Device See topic Readdressing a DALI Device44 for more information on readdressing DALI Devices using a mobile device Confirming and Unconfir
3. url 42 usb 7 38 62 usb dali interface device 5 usb driver 62 usb drier 7 user interface 11 12 User Interface topic 11 user interface on a mobile device 28 User Interface on a Mobile Device Go Mobile topic 28 user stories 38 V verifying a dali line 44 Verifying a DALI Line topic 44 W web 42 web access denied 63 disabled 63 overridden 63 timeout 63 web access options auto lock 24 http port number 24 lock 24 password 24 unlock 24 web browser 42 wifi 9 42 63 wireless 9 63 wireless access point setup 9 Copyright 2015 Diginet Control Systems Pty Ltd
4. The Disconnect a Mobile Device button Then clicking the Connect a Mobile Device button again will allow a different mobile device to connect Access Overridden This error message can appear on a mobile device if there are multiple applications running on it which are accessing the RAPIX Addressing mobile interface Copyright 2015 Diginet Control Systems Pty Ltd 68 RAPIX Addressing Manual RAPIX Addressing A Access Overridden Another web browser is currently controlling the RAPIX Addressing software Press on the button below to control RAPIX Addressing from this web browser Reconnect The Access Overridden error page A common example of this error showing up is on a smart phone which has used a third party QR scanning application to scan the QR code 1 The scanned URL is opened in the QR scanning application s own embedded web browser 2 Then the link is reopened in the mobile device s native web browser This leaves two applications with the same web page open one with control and the other without Press the Reconnect button to take control of RAPIX Addressing This will override access in the other open web browser which will now show the Access Overridden error page Timeout A timeout error can occur for one of two reasons 1 When Wi Fi communications between the mobile device and PC running RAPIX Addressing are interrupted This can occur when the mobi
5. Using a Mobile Device To confirm a DALI Device using the mobile interface Copyright 2015 Diginet Control Systems Pty Ltd 54 RAPIX Addressing Manual alja s i gt Selected DALI Device and the Readdress button highlighted in red 1 Select the DALI Device short address to be confirmed and press the Readdress button The page will now update to allow the user to select any short address to readdress the DALI Device to 2 Without choosing a new short address to readdress the DALI Device to press the Apply button This will confirm the DALI Device without readdressing it To unconfirm a DALI Device select the DALI Device to be unconfirmed and the Readdress button will change to an unconfirm button Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 55 RAPIX Addressing we e ES gt ne eee 559 si Eel Ea aa 24 25 26 27 28 Selected confirmed DALI Device and Unconfirm button 1 Press the Unconfirm button The top button bar will now update to show a Cancel Unconfirm All and Unconfirm buttons Unconfirm buttons Cancel Unconfirm All and Unconfirm Selecte d 2 To unconfirm the DALI Device press the Unconfirm button on the right Note The Unconfirm All button allows the user to quickly unconfirm all DALI Devices on the DALI Line 4 9 Mobile Device Simulator RAPIX Addressing allows you to simulate having a mobile device connected for testing purposes This si
6. allowing the user to enter in red and green values seen To do this 1 Put the mobile interface into emergency mode This will put all emergency DALI Devices in identification mode See topic Device Type Modes43 for more information mobile interface modes Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 49 The Mode button when in emergency mode 2 Press the Decode Tridonic Red Green Sequence button The Decode Tridonic Red Green button 3 The Tridonic emergency DALI Devices will continuously emit their short address with a short delay between 4 Once the delay has passed press the Red and Green buttons according to the colour emitted by the identification LEDs 5 Once six colours have been entered the short address will be displayed and the emergency DALI Device with that short address will be selected in the short address grid RAPTX Addressing The Decode Tridonic Red Green Sequence page Tip Because the red and green LED sequence occurs rather quickly you can hold the mobile device with both hands and use your thumbs to press the Green and Red buttons Note If you accidentally press the wrong button you can press the Cancel button and start over See topic Short Address Grid Page428 for more information on the emergency functions available on the mobile interface Audio Feedback On mobile devices that support playing sounds in the web browser audio feedback can be used to
7. 1 The DALI cables are not correctly inserted into the DALI USB Interface Device or 2 The DALI Line is not properly powered or 3 There is a short circuit on the DALI Line Ensure that the DALI Line is plugged into the DALI USB Interface Device and that the DALI Line is correctly powered This can be tested by pressing the Turn DALI Line On and Turn DALI Line Off buttons on the DALI USB Interface Device 6 3 Mobile Interface Problems Can t Connect a Mobile Device Failing to connect a mobile device to RAPIX Addressing can be because 1 Wi Fi is not enabled on the PC running RAPIX Addressing or 2 Wi Fi is not enabled on the mobile device or 3 You are trying to connect the mobile device to RAPIX Addressing via the wrong network interface or The HTTP port number conflicts with another service or You are out of Wi Fi range 6 A firewall on the PC is blocking Wi Fi communications o gt Wi Fi Not Enabled on PC Copyright 2015 Diginet Control Systems Pty Ltd 64 RAPIX Addressing Manual The PC might not be connected to the local network Check that an Ethernet cable to the router is plugged into the PC and that Wi Fi is enabled Then the mobile device must connect to the same Wi Fi network as the PC for communications to work Wi Fi Not Enabled on Mobile Device If Wi Fi is not enabled on the mobile device then it must be enabled Ensure that once Wi Fi is enabled that the mobile device is connected to the same
8. 58 59 60 61 62 63 2 fF 8S Nix e The Actual and Proposed short address grids Actual Short Address Grid The Actual short address grid displays the current contents of the DALI Line Every time that a DALI Device is readdressed the Actual short address grid is automatically updated to reflect the change Proposed Short Address Grid The Proposed short address grid displays the contents of the DALI Line and also displays any proposed short address changes yet to be made to DALI Devices on the DALI Line Proposed short address changes are displayed in red and any DALI Devices that have been confirmed are displayed in black DALI USB Interface Device Properties Properties of the DALI USB Interface Dewce that is currently connected to RAPIX Addressing can be shown by clicking the serial number hyperlink in the bottom right of the main window Copyright 2015 Diginet Control Systems Pty Ltd 18 RAPIX Addressing Manual DALI USE Interface Device 13 licensed to Go Mobile until 07 Oct 2014 The DALI USB Interface Device serial number hyperlink in blue that opens the DALI USB Interface Device Properties window This will open the DALI USB Interface Device Properties window See topic DALI USB Interface Device Properties428 for more information on the properties displayed 3 1 2 Group Addressing Group Addressing requires a RAPIX Addressing license See Licensing 11 for more information Selecting th
9. Diginet and it supersedes any prior proposal representation or understanding between the parties The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties as well as other intellectual property laws and treaties The SOFTWARE PRODUCT is only licensed to you for a specific and limited time period and is not sold 1 GRANT OF LICENSE The SOFTWARE PRODUCT is licensed to you only for the limited subscription period specified in the related invoice as follows a Installation and Use Diginet grants you the right to install and use copies of the SOFTWARE PRODUCT on your computer running a valid licensed copy of the operating system for which the SOFTWARE PRODUCT was designed e g Windows 7 Windows 8 b Limited Right of Use This SOFTWARE PRODUCT must only be used with the Diginet DALI USB interface device Any use or attempted use with other third party DALI interface devices is prohibited and will invalidate this license c Access Key This SOFTWARE PRODUCT requires an access key to access some features and functionality Any key assigned to you must not be shared with any third party or you will invalidate this license d Mandatory Activation This SOFTWARE PRODUCT requires activation within a limited time period after installation or some features and functionality will cease to function Activation sends information to Diginet that associates this SOFTWARE PRODUCT and the assigned access key with th
10. Rapid Find Algorithm between switching DALI Devices on and off can be configured This allows for cases where DALI Devices may take time to switch on or off such as fluorescent devices The minimum value for the time delay is 2 0 seconds and the maximum value is 10 0 seconds See topic Options424 for more information Readdressing a DALI Device DALI Devices can be readdressed using the mobile interface To readdress a DALI Device select the DALI Device to be readdressed and then press the Readdress button highlighted in red below RAPIX Addressing Ed EN 5 067 AE 13 14 15 p w Gy a r DALI Device selected to be readdressed and the Readdress button highlighted in red Upon pressing the Readdress button the top button bar displays a Cancel and Apply button Copyright 2015 Diginet Control Systems Pty Ltd User Interface 35 The Cancel button on the left and the Apply button on the right With the Cancel and Apply button showing select a DALI short address in the grid to readdress the DALI Device to Note The current short address of the DALI Device is displayed wth a red border and the DALI short address to readdress the DALI Device to wil be highlighted and flashing red RAPIX Addressing 3722 v ES 0 5 6 7 AE ae ae 16 17 da 139 20 21 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 lt gt Choosing 22 as a DALI Device s ne
11. Scene checkbox will automatically sort the list of DALI Devices by the Scene that is currently set Copyright 2015 Diginet Control Systems Pty Ltd User Interface 23 Mode Short Addressing Group Addressing Scene Levels State ActulSA 0 1 3 4 5 6 7 8 39 1 11 12 13 14 15 Set Scene Scene 2 A y 2 30 y 3 25 40 80 100 100 100 y 4 51 100 100 100 70 5 00 00 60 00 00 100 80 0 6 00 00 70 00 51 390 90 100 7 0 1 0 1 80 100 65 100 58 100 0 1 Other nd a 1 p 8 100 13 0 1 42 48 100 100 0 1 p 9 10 13 29 78 61 0 1 n 11 100 18 37 45 56 35 95 70 0 1 3 14 Global Programming Global Programming requires a RAPIX Addressing license See Licensing 1 for more information The Global Programming window is used to configure and set DALI level and fade options on all DALI Devices on the DALI Line Global Programming Set options for all DALI Devices on the DALI Line No Fade Dto 100 in 5 7 seconds 44 7 stepssec Set to DALI Defaults The Global Programming window Copyright O 2015 Diginet Control Systems Pty Ltd 24 3 1 5 RAPIX Addressing Manual DALI Levels Min Level This is the minimum level that all DALI Devices will output before turning off Max Level This is the maximum level that all DALI Devices will output Power On Level This is the level that all DALI Devices will output after being powered on If Restore to previous level is ticked then each DA
12. The URL to access RAPIX Addressing on the mobile device can be typed into the device s web browser 2 If the mobile device is equipped with a camera and QR code scanning functionality the QR code can be scanned and then the URL opened in a web browser The Connect a Mobile Device Window The Connect a Mobile Device window allows the user to select which network interface to allow a mobile device to connect to Typically the network interface to choose is the wireless network interface or local area connection Note The window will remember the last network interface chosen when it is reopened When selecting a network interface the web URL and QR code will update to use the IP address of that network interface The QR code is a graphical representation of the URL in blue which can be scanned by a mobile device s camera so that the URL doesn t have to be typed in When the mobile interface is loaded in the mobile device s web browser the Connect to Mobile Device window will automatically close The mobile device now has exclusive control and RAPIX Addressing will prevent modifications from being made to DALI Devices on the DALI Line via the PC The PC user interface will show the IP address of the connected mobile device in the blue bar and the Connect a Mobile Device button will allow disconnection of the mobile device Copyright 2015 Diginet Control Systems Pty Ltd 44 4 5 RAPIX Addressing Manual RAPIX Addressing M
13. Wi Fi network as the PC running RAPIX Addressing Wrong Network Interface It might be possible that the wrong network interface was chosen in the Connect a Mobile Device window E Connect a Mobile Device KN Connect a Mobile Device to Go Mobile Enter the UAL below into your mobile device s web browser or scan the QA code below to conmect to RAPIE Addressing The Connect to Mobile Device window with combo box for choosing a network interface Try choosing a different network interface by selecting a different item in the Network Interface combo box see image above When choosing a different network interface the IP address displayed in the URL will change as well as the QR code Note Normally a network interface labelled Wireless Connection or Local Area Connection will allow a mobile device to connect See topic Connecting a Mobile Device for more information Invalid HTTP Port Number It could be possible though rare that the HTTP port number used for communications is in conflict with another service or application on the PC Try changing the HTTP port number in the Options window and then attempt to reconnect the mobile device See topic Options424 for more information on the HTTP port number Copyright O 2015 Diginet Control Systems Pty Ltd Troubleshooting 65 Web Access is Disabled This problem occurs when mobile web access is disabled RAPIX Addressing A Access Disabled Please enable m
14. allow the user to observe the red green sequence directly and listen for feedback of the buttons pressed without needing to look at the mobile device An ascending sound is played when the Green button is pressed and a descending sound is pressed when the Red button is pressed A bing bong sound is played when all 6 bits have been entered to form a DALI short address Copyright 2015 Diginet Control Systems Pty Ltd 50 4 8 RAPIX Addressing Manual Sounds can be enabled or disabled by pressing the speaker button in the bottom right This option can also be set on the Options dialogue See topic Options for more information Readdressing and Confirming DALI Devices Readdressing DALI Devices can be done on both the PC user interface and the mobile interface Readdressing DALI Devices on the PC To readdress a DALI Device using the PC user interface choose a new short address from the combo box in the Requested SA column for the selected DALI Device State Actual SA Requested SA New SA Device Type Actual Short Address 7 Choose gt B Emergency Choose gt 2 3 LI i Fluorescent 5 a LI Mio gt p 6 O 7 i Huorescent L 8 4 8 Huorescent g 6 Fluorescent The Requested SA column combo box The short addresses that can be chosen are any short addresses that are not occupied by confirmed DALI Devices or any short addresses that do not have proposed DALI Devices DALI Devices can be swapped by
15. device 48 Identify an Emergency DALI Device topic 48 identifying a dali device 46 Identifying a DALI Device topic 46 ignore all 61 once 61 install 62 installing rapix addressing end user license agreement 7 eula 7 Installing RAPIX Addressing topic 7 interface 11 interference 61 introduction 5 Introduction topic 5 ip address 42 L lan 63 led sequence 48 license 11 39 70 local area connection 63 lock 24 42 log level errors 24 information 24 warnings 24 logging 24 mainform 12 main window 11 12 manually 46 max level 23 min level 23 mobile device 5 connect 42 63 mobile device help page 36 Mobile Device Help Page topic 36 mobile device simulator 55 Mobile Device Simulator topic 55 mobile interface 28 mobile interface problems 63 Mobile Interface Problems topic 63 mode all 31 emergency 31 non emergency 31 N network interface 42 63 network name 9 nic 42 63 O options 24 63 deselected duration 44 invert behaviour 44 selected duration 44 Options topic 24 Copyright 2015 Diginet Control Systems Pty Ltd Pp password pc 11 pc user interface problems 62 PC User Interface Problems topic 62 power on level 23 power saving 42 proposed short address 50 Q qr code scan 42 R range 63 rapid find algorithm 5 11 46 63 step time 24 32 Rapid Find Algorithm topic 32 readdress 5 34 50 readdressing a dali device 34 Readdressing a DALI Device topic 34 r
16. in Connect to DALI Interface Window s List The most common reason for a DALI USB Interface Device not appearing in the Connect to DALI Interface window list is that the drivers are not installed Connect To DALI Interface Connect to the DALI USB Interface Device Select the DALI USB Interface Device and click Connect Interface Device Diginet USB DALI Interface HU v E License Info Go Mobile expires on 24 Aug 2015 Copyright 2015 Diginet Control Systems Pty Ltd Troubleshooting 63 The Connect to DALI Interface window When plugging in a DALI USB Interface Device Microsoft Windows should detect a new device was inserted and automatically install the drivers for it Installing device driver software Click here for status Microsoft Windows installing drivers for the DALI USB Interface Device This process may take a few moments Note Installing RAPIX Addressing will also include the USB drivers necessary to use a DALI USB Interface Device and Windows will also automatically download the USB drivers if not installed on the PC After the USB drivers are installed reopen the Connect to DALI Interface window and a new device should be listed in the combo box See topic Installing RAPIX Addressing4 for more information on installing RAPIX Addressing Can t Connect to DALI Ifa DALI USB Interface Device is connected to the PC and RAPIX Addressing has trouble connecting to DALI this may be because
17. in physically locating the DALI Device with the specified short address Finding the Short Address of an Observed DALI Device To find the short address of a DALI Device whose physical location is known and can be seen there are two options 1 Manually toggle DALI Devices one by one until the observed DALI Device is toggled 2 If using a mobile device use the Rapid Find Algorithm which will toggle multiple DALI Devices in stages until the observed DALI Device is found Manually Finding a DALI Device s Short Address Finding the short address of a DALI Device manually can be done by toggling the selected DALI Device or keeping the selected DALI Device on To do this on the PC user interface is cumbersome but can be done by clicking the Turn Selected DALI Device On or Toggle Selected DALI Device button and cycling through all DALI Devices in the list one by one until the observed DALI Device is switched on Note If the invert option is set all DALI Devices on the DALI Line wil be switched on wth the selected DALI Device swtched off This option may be useful in darker conditions On a mobile device this method is easier and can be done by simply selecting a DALI short address in the grid or cycling through DALI short addresses by pressing the Previous and Next buttons Qt gt The button bar with Previous and Next buttons The large button with the selected short address s value displayed in it can be pressed to toggle that
18. quick in cases where it may take time for the DALI Devices on the DALI Line to respond to On and Off commands If this is the case the Rapid Find Algorithm step time which is the delay between successive switching on and off of DALI Devices can be changed The default is 3 0 seconds This value can be changed in the Options window to any value up to 10 0 seconds See topic OptionsO24 for more information Copyright 2015 Diginet Control Systems Pty Ltd 70 RAPIX Addressing Manual End User License Agreement SUBSCRIPTION END USER LICENSE AGREEMENT EULA IMPORTANT PLEASE READ THE TERMS AND CONDITIONS OF THIS LICENSE AGREEMENT CAREFULLY BEFORE CONTINUING WITH THIS PROGRAM INSTALL This Subscription End User License Agreement EULA is a legal agreement between you either an individual or a single legal entity and Diginet Control Systems Pty Ltd ACN 095 788 864 Diginet for the software product s identified above which may include associated software components physical hardware security devices media printed materials and online or electronic documentation SOFTWARE PRODUCT By installing copying or otherwise using the SOFTWARE PRODUCT you agree to be bound by the terms of this EULA If you do not agree to the terms of this EULA do not continue to install or use the SOFTWARE PRODUCT This EULA and the related invoice issued by Diginet represents the entire agreement concerning the program between you and
19. reception is an issue you can connect the wireless access point to the PC va an Ethernet cable and connect the mobile device to the Wi Fi network This allows you to position the wireless access point closer to the mobile device USB Ethernet cable A can be long DALI USB Interface DS PC Wireless Mobile Device Access Point Full setup with Access Point connected via Ethernet Note Consult the user manual for your wireless access point for instructions on how to set up a wireless network Copyright O 2015 Diginet Control Systems Pty Ltd Software Installation 11 2 5 Licensing RAPIX Addressing is a licensed software product and to be able to Go Mobile requires e A DALI USB Interface Device e A product activation key A RAPIX Addressing license which is licensed to a particular DALI USB Interface Device activates e The ability to use the Go Mobile feature which will allow that DALI USB Interface Device connected to RAPIX Addressing to use a mobile device to discover and readdress DALI Devices on a DALI Line e The ability to use Global ProgrammingU2 e The ability to use Group Addressingl18 e The ability to set Scenes 020 See topic User Interface on a Mobile Device Go Mobile 028 for more information on the features available when you Go Mobile See topic Activating a License to Go Mobile439 for more information on how to enter a product activation key in order to Go Mobile 3 User Interface This s
20. selecting a short address that is occupied by another DALI Device The other DALI Device will be moved to occupy the original DALI Device s position DALI Device short addresses can also be cleared by choosing the lt Clear gt option from the Requested SA combo box When a DALI Device s short address has been cleared and programmed it will immediately be removed from the list Note DALI Devices wth cleared short addresses will be reassigned a short address when a rescan is performed on the DALI Line To commit any proposed short address changes click the Readdress button A progress window will be shown when short address changes are being saved to the DALI Devices Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 51 Programming DALI Device Short Addresses Moving DALI Device at short address 4to 13 The Programming DALI Device Short Addresses window See topic Main Window 2 for more information on readdressing options Clearing the Short Address of All DALI Devices on a DALI Line RAPIX Addressing provides the ability to clear the short address of all DALI Devices on a DALI Line in a single step This feature can be used in cases where you want to readdress a DALI Line from scratch To clear the short address of all DALI Devices on a DALI Line press Shift Ctrl C This will display a prompt asking whether you are sure that you want to clear all short addresses Clear All Short Addresses
21. short address on or off The Toggle Selected DALI Device button can also be selected to automatically toggle the selected short address on and off Note This method may not work for maintained emergency DAL Devices as they do not respond to on and off commands Finding a DALI Device s Short Address Automatically Mobile Only Finding the short address of a DALI Device automatically involves using the Rapid Find Algorithm The Rapid Find Algorithm is an automatic DALI Device identification tool that allows the user to determine the DALI short address of a specific DALI Device in a matter of seconds This feature is only available when using a mobile device connected to RAPIX Addressing as it requires the user to be in direct line of sight with the DALI Device being searched for To use this feature on the mobile interface press the Rapid Find Algorithm button Copyright 2015 Diginet Control Systems Pty Ltd 48 4 7 RAPIX Addressing Manual 2 The run Rapid Find Algorithm button While looking at the DALI Device whose short address is being searched for press the Press when load is on and Press when load is off buttons when the DALI Device is switched on or off The Press when load is on and Press when load is off buttons have been designed to be large such they can be pressed while you are looking at the DALI Device and not at the mobile device After doing this a few times the Rapid Find Algorithm will finish with the DALI De
22. EULA grants you no rights to use such content All rights not expressly granted are reserved by Diginet 5 NO WARRANTIES Subject to your rights if any under clause 7 Diginet expressly disclaims any warranty or representation in respect of the SOFTWARE PRODUCT The SOFTWARE PRODUCT is provided As Is without any express or implied warranty of any kind including but not limited to any warranties of merchantability non infringement or fitness for a particular purpose Diginet does not warrant or assume responsibility for the accuracy or completeness of any information text graphics Copyright 2015 Diginet Control Systems Pty Ltd 72 RAPIX Addressing Manual links or other items contained within the SOFTWARE PRODUCT Diginet gives no warranties respecting any harm that may be caused by the transmission of a computer virus worm time bomb logic bomb or other such computer program 6 LIMITATION OF LIABILITY Subject to your rights if any under clause 7 in no event shall Diginet be liable for any damages including without limitation lost profits business interruption or lost information arising out of your use of or inability to use the SOFTWARE PRODUCT even if Diginet has been advised of the possibility of such damages In no event will Diginet be liable for loss of data or for indirect special incidental consequential including lost profit or other damages based in contract tort or otherwise Diginet shall have no
23. I Devices on a DALI Line on and off periodically 4 Putting all emergency DALI Devices in identify mode Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 45 The DALI Line verify buttons in the side bar Switching the DALI Line On The first method involves switching all DALI Devices on the DALI Line on This sends out a broadcast DALI command telling all DALI Devices to switch themselves on Any DALI Devices that do not respond to this broadcast command as indicated by their luminaire not being switched on can be considered to either be faulty and require maintenance or not connected to DALI after the DALI Line was scanned The DALI Line can be switched on by clicking the Turn DALI Line On button in the side bar See topic Main Window for more information on the side bar buttons Switching the DALI Line Off This method involves switching all DALI Devices on the DALI Line off This sends out a broadcast DALI command telling all DALI Devices to switch themselves off Any DALI Devices that do not respond to this broadcast command and are not control devices or maintained emergency devices as indicated by their luminaire not being switched off can be considered to be faulty and require maintenance The DALI Line can be switched off by clicking the Turn DALI Line Off button in the side bar Note This method may not work for maintained emergency DAL Devices as they do not respond to on and off comman
24. LI Device will output the last set level for that particular device System Failure Level This is the level that all DALI Devices will output when the DALI Line remains unpowered for more than 500 milliseconds If Maintain current level is ticked then on system failure each DALI Device will remain at its current level and not change Fade Options Fade Time This is the time for a scene or direct arc power command to go from the current level to a specified new level for a DALI Device The minimum value is no fade and the maximum is 90 5 seconds Fade Rate This is the rate that a DALI Device will ramp via DALI dim up and dim down commands The equivalent time for fading from 0 to 100 that corresponds to the steps sec is also shown The minimum value is 2 8 steps per second and the maximum is 358 steps per second Buttons Set to DALI Defaults Click this button to reset all of the DALI levels and fade options to the defaults defined by the DALI standard Set to Previous Click this button to reset all of the DALI levels and fade options to the values last programmed onto the DALI Line Cancel Click this button to exit the Global Programming window and discard any changes Program DALI Line Click this button to program all of the DALI levels and fade options to all DALI Devices on the DALI Line Options The Options window is used to view and configure various settings in RAPIX Addressing Copyright 2015 Diginet Contr
25. O Oo e Quick guides on how to use the mobile interface Copyright O 2015 Diginet Control Systems Pty Ltd User Interface 37 RAPIX Addressing Press to Close Help Device Colour Legend Unconfirmed Confirmed No Device Other Device Other Device Type Type Top of the mobile interface help page The quick help page can be closed at any time by pressing the Press to Close Help button at the top of the page This will return the mobile interface back to the DALI short address grid page Copyright 2015 Diginet Control Systems Pty Ltd 4 1 38 RAPIX Addressing Manual Basic Working Procedures This section describes the most common and important basic tasks that will be used when commissioning a DALI Line It is designed as a How To guide and reference manual Connecting to a DALI Line To connect RAPIX Addressing to a DALI Line a DALI USB Interface Device is required Run RAPIX Addressing and connect the DALI USB Interface Device to the PC Connecting to a Single DALI USB Interface Device RAPIX Addressing will automatically start scanning the DALI Line if 1 RAPIX Addressing is already running and not connected to any DALI USB Interface Device then a single DALI USB Interface Device is plugged in or 2 A single DALI USB Interface Device is plugged into the PC and then RAPIX Addressing is started Connecting to One of Multiple DALI USB Interface Devices If there is more than one DALI USB Interfa
26. Software Installation 7 System Requirements ciar oia 7 Installing RAPIX AUTOS Ocio A aaa A dade ext 7 Running RAPIX AGGre SSING is asarimda dica acacia adanadan 9 Setting Up a Wireless Access POINL cccccceceeeceeeeneeeeeeeeeeeeeeneneeeeaeaeeeeseeesnenseaeaeeeneges 9 LICENSINO oia 11 User Interface 11 User interlace on the RG IS 12 IVE ANT WV NIG OW aaraa a at 12 Group Addres SING israel daa 18 Scene Level naa 20 Global Programi ming ica tbc Aa ia 23 OO TIONS O accra ee mace ude E A E E satu unload aun AA E 24 DALI USB Interface Device Properties siii irradia 28 User Interface on a Mobile Device Go Mobile o0ccoococococcocococcocccacconccannnnanannnnos 28 SHOrE Address Grid Page nia A A adidat 28 DEVICE Type Modes eb 31 RAPI IM GO AI ON IGM a aa 32 Readaressing a DALI De VIC ui das 34 Mobile Device Help Pain ii A ds 36 Basic Working Procedures 38 C nnecting toa DALLLINE6 una o aia 38 Activating a License to Go Mobile iia di 39 Scanning a DALLAS a 42 Connecting a Mobile Device to Go Mobile ooooocococococococococcncocococananacannnrnrarararananano 42 vVerniying a DAL nessa Io cacon 44 identifying a DALDO VICO cuido 46 Identifying an Emergency DALI Device ooccccccocococococococacocnncororononacaranannnrarararnraranananenes 48 Readdressing and Confirming DALI DeviceS ocococccccccoccccncococococacananannncarararanarananannnos 50 Mobile Device Simulator c oococccccncconconcnnc
27. X Addressing simply run the installer file The installer is a wizard that will guide you through the steps to install RAPIX Addressing including the USB drivers required to use a DALI USB Interface Device 1 Click Next on the first page Copyright 2015 Diginet Control Systems Pty Ltd RAPIX Addressing Manual RAPIX Addressing InstallShield Wizard Ir P RAPIX ADDRESSING Installshield 2 Click Next on the Welcome to InstallShield Wizard for RAPIX Addressing page 3 Read the End User License Agreement and agree to it by clicking the I accept radio button then click Next to start the installation Windows may ask for permission to run the installer to which you answer Yes Note See topic End User License Agreement 70 for more information 4 The installer will start the installation process and then when complete display a page which provides the option to run RAPIX Addressing immediately Click Finish to complete the installation Copyright 2015 Diginet Control Systems Pty Ltd Software Installation 9 2 3 Running RAPIX Addressing RAPIX Addressing can be started either by launching from the desktop icon or from the Windows Start menu Via the Desktop Icon To launch RAPIX Addressing double click the icon on the desktop RAPLA Addressing The RAPIX Addressing desktop shortcut Via the Start Menu T
28. X button Click this to access the About box for RAPIX Addressing Options button Click this button to access the Options window for RAPIX Addressing Help button Click this button to access the help files for RAPIX Addressing Grey Side Bar The grey side bar provides access to the main functionality in RAPIX Addressing Each icon in the side bar is a button that provides access to a specific function Connect to DALI Line button 5 Click this button to connect to a DALI USB Interface Device A window will be shown allowing you to choose a DALI USB Interface Device to connect to from a list of all of the DALI USB Interface Devices connected to the PC Once connected RAPIX Addressing will automatically scan for any DALI Devices on the DALI Line See topic Connecting to a DALI Line438 for more information on connecting to a DALI Line and see topic Scanning a DALI Line442 for more information on scanning a DALI Line Rescan DALI Line button Click this button to rescan a DALI Line See topic Scanning a DALI Line44 for more information on scanning a DALI Line Connect Disconnect Mobile Device button Click this button to connect or disconnect a mobile device to RAPIX Addressing A mobile device can be used to commission DALI Devices while walking around a building See topic Connecting a Mobile Device for more information on using a mobile device with RAPIX Addressing Copyright 2015 Diginet Control System
29. address of a DALI Device by using RAPIX Addressing s Rapid Find Algorithm See topic Rapid Find Algorithm for more information RAPIX Addressing also provides the ability to simulate the use of a mobile device with a mock smart phone window See topic Mobile Device Simulator4 for more information 3 1 User Interface on the PC This section describes the user interface of RAPIX Addressing on the PC 3 1 1 Main Window The main user interface for RAPIX Addressing consists of a single window When connected to a DALI USB Interface Device it shows all of the DALI Devices on a DALI Line RAPIX Addressing No DALI Connected Mode Short Addressing Group Addressing Scene Levels Filter Unconfirmed State ActualSh Requested 54 NewS4 Device Type Confirmed E 0 41 E 18 6 98 DPOBNdas BG BOOOE BORBPERE BBB OG MEE coogagg No DALI Devices to display Confirmed ES Edit Device The RAPIX Addressing main user interface Copyright O 2015 Diginet Control Systems Pty Ltd User Interface 13 Blue Bar The blue bar at the top of the main window provides the user with basic status information including whether e RAPIX Addressing is connected to DALI e A mobile device is connected to RAPIX Addressing or not RAPIX Addressing Diginet USB DALI Serial Port COM3 The RAPIX Addressing blue bar The blue bar also provides access to the About box the Options window and the RAPIX Addressing help files RAPI
30. are detected and resolved such that no two DALI Devices have the same short address e DALI Devices without short addresses are assigned unoccupied short addresses e The DALI Device types of all discovered DALI Devices are retrieved Discover DALI Devices Discover DALI Devices Detects and resolves DALI Short Address conflicts and then allocates DAL Short Addresses to unaddressed DALI Devices 1 Detecting Short Address conflicts normal scan 2 Resolving Short Address conflicts The Discover DALI Devices window Note Rescanning a DALI Line that has contirmed DALI Devices on it wil mark all of the DALI Devices as unconfirmed Connecting a Mobile Device to Go Mobile To use a mobile device with RAPIX Addressing both the PC running RAPIX Addressing and the mobile device must be connected to the same Wi Fi network With RAPIX Addressing running and connected to a DALI Line click on the Connect Mobile Device button to open the Connect a Mobile Device window The Connect a Mobile Device button Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 43 E Connect a Mobile Device Connect a Mobile Device to Go Mobile Enter the URL below into your moble device s web browser or scan the QR code below lo connect to RAPI Addressing Network interface Ethers s The Connect a Mobile Device window This window provides two ways that the mobile device can be connected 1
31. being identified Copyright O 2015 Diginet Control Systems Pty Ltd 20 RAPIX Addressing Manual Mode Short Addressing Group Addressing Scene Levels State Actual SA o 1 2 3 4 5 6 7 82 9 0 1 BGB H Identify Group Group 2 a A A ha on it 1 0 2 g JE mN i t a 2 3 D Other IA p 3 3 gt 4 10 m 5 n 6 6 7 8 gt 7 T n g n 9 0 14 Sort by Selected Group gt 11 1 12 3 13 Scene Levels Scene Levels requires a RAPIX Addressing license See Licensingl 11 for more information Selecting the Scene Levels mode on the main window changes the view to enable a user to configure and set DALI scenes for all DALI Devices on the DALI Line Mode Short Addressing Group Addressing Scene Levels Filter LAN Unconfirmed Scene Levels List The list displays all of the DALI Devices on the DALI Line including their DALI Scene membership and levels Mode Short Addressing Group Addressing Scene Levels State AculSA O 1 2 3 4 5 6 7 8 9 011 12 13 14 15 Actual Short Address A n 1 n 2 30 n 3 25 A0 80 100 100 100 y 4 100 100 100 a 5 00 00 60 00 00 100 80 For the shown setup the DALI Device at Short Address 4 is a member of DALI Scenes 2 5 6 7 and 15 Add DALI Device to Scene Copyright O 2015 Diginet Control Systems Pty Ltd User Interface 21 To add a DALI Device to a Scene click the bullet in the column of the scene to display a pop up dialog Either un check the Mask checkbox or move the slide
32. bile The product activation prompt in the main window Click the Activate button on the product activation panel to open the Register Activation Key window Register Activation Key Register DALI USB Interface Device Please enter the product Activation Kew for DALI USB Interface Device serial number Activation Key 1234 56 3 9012 3456 Canes The Register Activation Key window Enter the activation key provided to you by Diginet Control Systems and click Activate This will provide you with a license to Go Mobile for the selected DALI USB Interface Device If the registration is successful the DALI USB Interface Device will now be licensed to Go Mobile up until the expiry date that was purchased Finding the Serial Number of a DALI USB Interface Device The serial number of a DALI USB Interface Device is printed on the DALI USB Interface Device To view the serial number remove the red protective cover from the DALI USB Interface Device Copyright 2015 Diginet Control Systems Pty Ltd 42 4 3 4 4 RAPIX Addressing Manual which will reveal the serial number on its underside Lost Activation Key If you lose your product activation key contact Diginet Control Systems via email at sales diginet net au or by phone on 61 1300 XL DALI 61 1300 95 3254 Scanning a DALI Line Scanning or rescanning a DALI Line performs the following tasks when discovering DALI Devices e Short address conflicts
33. ce Device connected to RAPIX Addressing then you will need to manually choose a DALI USB Interface Device to connect to To do this click the Connect to DALI USB Interface Device button in the side bar The Connect to DALI side bar button The Connect to DALI USB Interface Device window will be shown allowing you to choose a DALI USB Interface Device from a list of those currently connected to the PC Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 39 iss Connect To DALI Interface Connect to the DALI USB Interface Device Select the DALI USB Interface Device and click Connect Interface Device Diginet USB DALI Interface EE License Info Go Mobile expires on 24 Aug 2015 The Connect to DALI USB Interface Device window When selecting a DALI USB Interface Device from the combo box RAPIX Addressing will automatically try and verify the connection This ensures that there is a powered DALI Line connected to the DALI USB Interface Device The refresh button can be used to refresh the list of DALI USB Interface Devices that are connected When the DALI USB Interface Device has been selected click the Connect button This will start scanning the DALI Line for any DALI Devices Note This window will remember the last DALI USB Interface Device that was chosen next time it is displayed See topic Scanning a DALI Line442 for more information on scanning for DALI Devices 4 2 Activating a Lice
34. ddress grid as well as a description of all of the buttons on the web page The help page also briefly describes how to use the mobile web pages to locate and identify DALI Devices in the quickest way possible Top Button Bar The button bar above the short address grid provides access to toggling the DALI Line and DALI Devices as well as readdressing DALI Devices Copyright 2015 Diginet Control Systems Pty Ltd 30 RAPIX Addressing Manual The top button bar Identify the DALI Line button Press this button to toggle the DALI Devices on the DALI Line on and off automatically This function is useful to determine whether all DALI Devices on the Line are wired and functioning correctly Emergency DALI Devices will also commence an emergency identify Press again to stop automatically toggling the DALI Line Note This button wil be highlighted in blue while toggle mode is active e Turn DALI Line On button Press this button to switch all DALI Devices on the DALI Line on See topic Verifying a DALI Line for more information Turn DALI Line Off button Press this button to switch all DALI Devices on the DALI Line off See topic Verifying a DALI Line for more information Auto toggle Selected DALI Device button alts Press this button to automatically toggle the selected DALI Device in the grid on and off periodically Press again to stop toggling the DALI Device See topic Identify
35. detected 61 generated 61 Copyright 2015 Diginet Control Systems Pty Ltd Index 73 interference 61 dali command interference 61 DALI Command Interference topic 61 dali device 5 42 50 emergency 44 46 find 46 identify 44 46 48 observed 46 readdress 11 search 46 toggle 44 46 turn off 44 turnon 44 verify 11 dali device filter 12 dali device list 12 dali device toggle options deselected duration 24 invert behaviour 24 selected duration 24 dali device type 31 42 DALI groups 18 daliline 5 connect 11 38 connecting 38 scan 42 verify 44 DALI scenes 20 dali usb interface device 39 multiple 38 properties 28 single 38 dali usb interface device properties 28 DALI USB Interface Device Properties topic 28 debug 24 debugging 24 desktop icon 9 device type mode 48 device type modes 31 Device Type Modes topic 31 disabled 63 disconnect 63 discover 42 display sleep 42 E end user license agreement 70 End User License Agreement topic 70 ethernet 9 42 74 RAPIX Addressing Manual eula 70 expiry 11 F fade rate 23 fade time 23 fast 32 find 46 G getting started 5 global programming 12 23 Global Programming topic 23 glossary 95 Glossary of Terms topic 5 go mobile 5 11 28 39 42 green 48 grey side bar 12 group addressing 18 Group Addressing topic 18 groups 18 guide 36 H help 36 61 howto 36 38 http port number 63 identify 46 48 identify an emergency dali
36. ds See topic Main Window 2 for more information on the side bar buttons Toggling the DALI Line This method involves periodically switching all DALI Devices on the DALI Line on and off This sends out a broadcast DALI command telling all DALI Devices to switch themselves on followed by a broadcast DALI command telling all DALI Devices to switch themselves off after a delay This process then repeats itself after another delay Toggling the DALI Line also sends out additional broadcast commands to identify emergency DALI Devices as well as some other control devices The DALI Line can be toggled by clicking the Toggle DALI Line button in the side bar Copyright 2015 Diginet Control Systems Pty Ltd 46 4 6 RAPIX Addressing Manual The delays between switching the DALI Devices on and off can be configured in the Options window See topic Options for more information Emergency DALI Device Identification Because maintained emergency DALI Devices do not respond to DALI broadcast on and off commands they can be identified separately by putting them into an identify mode This mode can be set by clicking the Identify All Emergency DALI Devices button in the side bar Note This mode does not affect non emergency DALI Devices Verifying DALI Devices Using the Mobile Interface DALI Devices can also be verified using much the same procedure on the mobile interface s short address grid page DALI Device verification but
37. e Group Addressing mode on the main window changes the view to enable a user to configure and set DALI groups for all DALI Devices on the DALI Line Mode Short Addressing Group Addressin Scene Levels Filter Unconfirmed Group Addressing List The list displays all of the DALI Devices on the DALI Line including their DALI Group membership Mode Short Addressing Group Addressing Scene Levels Sate AculSA O 1 2 3 4 5 6 7 8 9 011 12 13 14 15 Actual Short Address s a 0 0 a a 1 0 2 8 Y 2 2 a y 3 3 y 4 10 For the shown setup the DALI Device at Short Address 2 is a member of DALI Groups 2 and 8 Copyright 2015 Diginet Control Systems Pty Ltd User Interface 19 Add DALI Device to Group To add a DALI Device to a Group click the bullet in the column of the group The bullet will change to the number of the group Remove DALI Device from Group To remove a DALI Device from a Group click the number in the column of the group The number will change to a bullet when it is no longer in the group Identify DALI Devices in a Group To locate all DALI Devices in a DALI group click the Identify Group button that matches the group number to be identified Identify Group Note that buttons will only be available if the corresponding group exists on the DALI Line Sort by Selected Group Selecting the Sort by Selected Group checkbox will automatically sort the list of DALI Devices by the Group that is currently
38. e serial number of the specific device on which it is operated This information includes the Internet protocol address of the computer This is to prevent unlicensed use of this SOFTWARE PRODUCT e Commercial in Confidence This SOFTWARE PRODUCT is provided commercial in confidence and shall not be reproduced or transmitted to unauthorised personnel without the expressed written permission of Diginet Copyright 2015 Diginet Control Systems Pty Ltd End User License Agreement 71 f Backup Copies You may only make copies of the SOFTWARE PRODUCT as may be necessary for backup and archival purposes 2 DESCRIPTION OF OTHER RIGHTS AND LIMITA TIONS a Maintenance of Copyright Notices You must not remove or alter any copyright notices on any copies of the SOFTWARE PRODUCT b Distribution You may not distribute copies of the SOFTWARE PRODUCT to third parties c Prohibition on Reverse Engineering Decompilation and Disassembly You may not reverse engineer decompile or disassemble the SOFTWARE PRODUCT except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this limitation d Rental You may not rent lease or lend the SOFTWARE PRODUCT to any other person e Support Services Diginet may provide you with support services related to the SOFTWARE PRODUCT Support Services Any supplemental software code provided to you as part of the Support Services shall be considered pa
39. eaddressing and confirming dali devices 50 Readdressing and Confirming DALI Devices topic 50 red 48 registration 11 requested sa 50 rescan 42 Running RAPIX Addressing topic 9 S sa 5 34 42 46 50 scan 38 dali line 42 scanning a dali line 42 scanning a DALI Line topic 42 scenarios 38 scene levels 20 Scene Levels topic 20 scenes 20 search 46 security 24 42 select mode 31 serial number 62 Setting Up a Wireless Access Point topic 9 9 24 42 Copyright O 2015 Diginet Control Systems Pty Ltd Index 75 short address 5 34 46 allocate 42 conflicts 42 requested 50 unallocated 42 short address grid 28 actual 12 proposed 12 short address grid page 28 Short Address Grid Page topic 28 side bar 12 simulator 55 sleep 42 smart phone simulator 42 ssid 9 start menu 9 system failure level 23 system requirements free space 7 hard disk 7 memory 7 mobile device 7 operating system 7 ports 7 processor 7 screen resolution 7 wifi 7 wireless 7 System Requirements topic 7 T tablet 42 timeout 63 toggle 32 top button bar decode tridonic red green sequence 28 identify emergency dali devices 28 readdress and confirm 28 toggle dali line 28 turn dali line off 28 turn dali line on 28 tridonic 48 decode 46 green 46 red 46 troubleshoot 61 troubleshooting 24 61 Troubleshooting topic 61 turn load off 32 76 RAPIX Addressing Manual turn load on 32 U ui 12 unconfirm 5 34 42 50 unlock 24 42
40. ection describes RAPIX Addressing s user interface DALI Devices on a DALI Line can be commissioned by using RAPIX Addressing on the PC but RAPIX Addressing also provides the ability to rapidly search and commission DALI Devices using the Rapid Find Algorithm on a smart phone or tablet device Using RAPIX Addressing on a PC you can e Connect to a DALI USB Interface Device and discover DALI Devices on a DALI Line See topic Connecting to a DALI LineO for more information e Verify that all DALI Devices are correctly functioning by switching them on and off See topic Verifying a DALI Line for more information e Readdress DALI Devices and mark them as confirmed so that they don t get accidentally readdressed See topic Readdressing and Confirming DALI Devices for more information Going Mobile Because using RAPIX Addressing on a PC can make it difficult to quickly identify which DALI Device is which due to DALI Dewces not being within line of sight RAPIX Addressing provides the ability to connect up a mobile device and e Verify that all DALI Devices are correctly functioning by switching them on and off See topic Verifying a DALI Line444 for more information e Readdress DALI Devices and mark them as confirmed so that they don t get accidentally readdressed Copyright O 2015 Diginet Control Systems Pty Ltd 12 RAPIX Addressing Manual See topic Readdressing a DALI DeviceD for more information e Quickly find the short
41. ed left and right to change the threshold and Min and Max level values Threshold Slider s There may be one or two threshold sliders visible These sliders can be moved to change the value of the DALI relay device s threshold s The name and behaviour of the thresholds depend on whether the Use Hysteresis and Invert options are set Min and Max Level Slider s There are two sliders for the Min and Max levels that can be moved when the Manually Set Levels option is set Buttons Reset to DALI Defaults Click this button to reset the threshold and Min Max level configuration back to the defaults specified by the DALI standard OK Click this button to program the threshold and Min Max level data into the DALI relay device Cancel Click this button to exit the Configure DALI Relay Device window and discard any changes Examples of Threshold Configurations Below are some examples demonstrating a few common threshold level setups Example 1 Switch on at Level 200 and off at Level 150 To have the DALI relay switch on when the DALI level goes above 200 and switch off when the DALI level drops below 150 the Use Hysteresis option must be enabled The setup will look like this Copyright 2015 Diginet Control Systems Pty Ltd Editing DALI Device Properties 59 Use Hysteresis Check this to configure separate DALI Levels for switching the relay ON and OFF C Invert Check this to have lower DALI Levels correspond to the relay b
42. eing switched ON Max 254 Onc 200 MOJO uG Mirc 1 0 DALI Level 234 Up Switch On 150 Down Switch Off Switch on at 200 and switch off at 150 Example 2 Switch on and off at Level 128 To have the DALI relay switch on and off at the same DALI level 128 the Use Hysteresis option must be disabled This will allow the on and off thresholds to be identical The threshold slider or blue line can then be dragged to the correct value The setup will look like this _ Use Hysteresis Check this to configure separate DALI Levels for switching the relay ON and OFF C Invert Check this to have lower DALI Levels comespond to the relay being switched ON Max 254 He Jo UG hic 1 0 DALI Level 254 128 Switch On Off Switch on and off at 128 Example 3 Switch on at Levels less than 64 To have the DALI relay switch off when the DALI level reaches or goes above 64 and switch on when the DALI level reaches or falls below 64 the Invert option must be enabled This will flip the graph upside down indicating that lower DALI levels correspond to the DALI relay being switched on The Copyright 2015 Diginet Control Systems Pty Ltd 60 RAPIX Addressing Manual threshold slider or blue line can then be dragged to the correct value The setup will look like this Use Hysteresis Check this to configure separate DALI Levels for switching the relay ON and OFF Invert Check this to have lo
43. ended w This log level logs any erors or wamings that may occurin RAPIX Addressing This is the default and recommended log level for RAPIX Addressing Export Log Files Logging options on the Options window Log Level The log level defines the amount of detail that RAPIX Addressing logs to disk The options available are e Errors only e Errors and Warnings e Errors Warnings and Information The default value is Errors and Warnings Export Log Files button The Export Log Files button exports all of the logs associated with RAPIX Addressing and saves them to disk There they can be attached and emailed to Diginet Control Systems technical support if required Copyright 2015 Diginet Control Systems Pty Ltd 28 RAPIX Addressing Manual 3 1 6 DALI USB Interface Device Properties The DALI USB Interface Device Properties window displays device information DALI Line information and historical DALI frame statistics E DALI USB Interface Device Properties The properties of this DALI USE interface Device are shown below DALI USB interface Device Device information Device Name QEMGTIN Not Set es Transmit OEM Sanal Number Not Set A y Total Sent 61018 Software Product 1D 1 Total Successes 51018 Firmware Name SERIAL_DID Total Collisions O The DALI USB Interface Device Properties window This information can be used for documentation or troubleshooting if there are issues on the DALI Li
44. es to update the settings This value has been changed so Windows will ask for HTTP Port Number 12345 administrator privileges in order to apply this change Warning shown when HTTP port number is changed Auto Lock The auto lock option will lock the PC as soon as a connection is made between a mobile device and RAPIX Addressing Enable this option to stop unauthorised users from using the PC when you are not using the PC directly Note To unlock the PC in order to continue using it press Ctrl Alt Del and enter your PC user account password Mobile Sounds Copyright 2015 Diginet Control Systems Pty Ltd 26 RAPIX Addressing Manual The mobile sounds option enables or disables the use of sounds on the mobile interface when using the Rapid Find Algorithm or decoding the Tridonic red green LED identification sequence on emergency DALI Devices See topics Rapid Find Algorithm and Identifying an Emergency DALI DeviceD for more information on how the sounds are used on the mobile interface Selection Behaviour Tab Selection Behaviour Section This option flips the selection behaviour such that either the selected DALI Device is switched on with all others on the DALI Line switched off or vice versa Note There is summary text in the DALI Device Toggle Options section below which describe the behaviour of DALI Device and DALI Line toggling to ensure that the desired behaviour can be determined before saving the opti
45. fied during communication on DALI Unconfirm The process of unconfirming a DALI Device such that its short address can be changed in RAPIX Addressing All DALI Devices are unconfirmed by default and are automatically confirmed when readdressed DALI USB Interface Device A DALI USB Interface Device is a device that permits the communication between DALI Devices and RAPIX Addressing va a USB connection Wi Fi Wi Fi is a popular wireless networking technology that provides high speed network connectivity between devices based on the IEEE 802 11 standards Copyright 2015 Diginet Control Systems Pty Ltd Introduction 7 2 Software Installation 2 1 System Requirements The minimum system requirements for running RAPIX Addressing are as follows Processor Intel Core i5 or higher Memory 4 GB Hard Disk 1 GB free Ports 1x USB 2 0 port Operating System Microsoft Windows 7 Microsoft NET Framework Version 4 0 or above bundled with RAPIX Addressing RAPIX Addressing provides the ability to commission DALI Devices on a DALI Line with a mobile device To use this feature you will require Mobile Device A smart phone or tablet with a touch interface Wi Fi capability and HTML5 support Mobile Screen Resolution 320 x 480 minimum Wireless Network A method of establishing a Wi Fi network that both the PC running RAPIX Addressing and a mobile device can connect to 2 2 Installing RAPIX Addressing To install RAPI
46. for more information about setting log levels and exporting logs 6 1 DALI Command Interference RAPIX Addressing provides functionality that can switch DALI Devices on and off If there are any Devices on the DALI Line that generate commands that can also switch DALI Devices on or off this can interfere with the normal operation of RAPIX Addressing in that lights can be switched on or off when not expected If there are any Devices on the DALI Line that generate commands the following message will be shown DALI Command Detected A device on the DALI Line has generated a command that can interfere with RAPIX Addressing Please ensure that this device is disabled or disconnected from the DALI Line before continuing roe A DALI Command Detected warning message on the PC Copyright 2015 Diginet Control Systems Pty Ltd 62 6 2 RAPIX Addressing Manual RAPIX Addressing A DALT Command Detected A device on the DALI Line has generated a command that can interfere with RAPIX Addressing Ignore All Ignore Once DALI Command Detected warning message on the mobile interface This message allows you to e Ignore Once This message will be displayed the next time that a DALI command is seen on the DALI Line that RAPIX Addressing did not generate e Ignore All This message will not be displayed again until the DALI Line is rescanned PC User Interface Problems DALI USB Interface Device Not Appearing
47. ing a DALI Device44 for more information Note This button wil be highlighted in blue while toggle mode is active a Readdress and Confirm button y Press this button to apply any proposed short address changes to the DALI Devices on the DALI Line See topic Readdressing and Confirming DALI DevicesO for more information on readdressing DALI Devices lf the mobile web page is in emergency mode then the top button bar will have two different icons detailed below Identify Emergency DALI Devices button Press this button to identify all emergency DALI Devices on the DALI Line Press again to stop identifying the DALI Devices See topic Identifying a DALI DeviceW46 for more information _ Decode Tridonic Red Green Sequence button 2 Press this button to decode a red green sequence that is emitted by Tridonic emergency DALI Devices when being identified which represents a DALI short address See topic Identifying an Emergency DALI DeviceD48 for more information on decoding Tridonic red green identification sequences Bottom Button Bar The button bar below the short address grid allows for cycling through DALI Devices manually as well as starting the Rapid Find Algorithm Copyright 2015 Diginet Control Systems Pty Ltd User Interface 31 The bottom button bar Rapid Find Algorithm button Press this button to run the Rapid Find Algorithm to find the short address of a DALI Device See to
48. ise any right or remedy for breach of any Consumer Guarantee strictly in accordance with your rights and responsibilities under the Consumer Law d Where the SOFTWARE PRODUCT is not of a kind ordinarily acquired for personal domestic or household use or consumption then unless Diginet is the manufacturer of the SOFTWARE PRODUCT under the Consumer Law its liability to you for breach of any Consumer Guarantee is limited at its option to repairing or replacing the SOFTWARE PRODUCT supplying an equivalent SOFTWARE PRODUCT or paying the costs of the repair or replacement of the SOFTWARE PRODUCT or of acquiring an equivalent SOFTWARE PRODUCT Copyright 2015 Diginet Control Systems Pty Ltd Index A access 63 access point 9 activate 39 activate license 39 Activating a License topic 39 activation key 11 39 auto lock 42 automatically 46 B Basic Working Procedues topic 38 basic working procedures 38 binary search 32 blue bar 12 blue menu bar 28 bottom button bar auto toggle selected dali device 28 run rapid find algorithm 28 select next dali device 28 select previous dali device 28 toggle dali device 28 C command 61 confirm 5 34 50 conflict detection 24 conflicts 42 connect 42 55 63 connect to dali line 39 connecting a mobile device 42 Connecting a Mobile Device topic 42 connecting to a dali line 38 Connecting to a DALI Line topic 38 D dali 5 connect 62 interface 62 dali command
49. l DALI Devices This option allows the user to search readdress and confirm DALI Devices of any type Note This is the default mode All non emergency DALI Devices This option allows the user to search readdress and confirm DALI Devices of any type except for emergency Ig b Emergency DALI Devices only This option allows the user to search identify readdress and confirm only emergency DALI Devices 3 2 3 Rapid Find Algorithm The Rapid Find Algorithm is an automatic tool that can find the short address of a specific DALI Device in a matter of seconds Note This feature is only available when using a mobile device connected to RAPIX Addressing as it requires the user to be in direct line of sight with the DALI Device being searched for Copyright 2015 Diginet Control Systems Pty Ltd User Interface 33 RAPIX Addressing Finding a Short Address The Rapid Find Algorithm user interface in action Benefits The benefit of using the Rapid Find Algorithm is that it dramatically cuts down the time it takes to determine the short address of observed DALI Devices on the DALI Line With this method it takes only seconds to find the short address of a DALI Device How it Works The Rapid Find Algorithm when in action turns on and off DALI Devices in stages and asks you to press the Press when load is on or Press when load is off buttons when the DALI Device you are interested in is switched on or off This allow
50. le device goes out of Wi Fi range of the PC 2 When RAPIX Addressing on the PC is not running but the web page remains open on the mobile device RAPIX Addressing A Timeout The Web Server is not responding Please check that the RAPIX Addressing software is running The Timeout error page Copyright 2015 Diginet Control Systems Pty Ltd Troubleshooting 69 Out of Wi Fi Range If the mobile device has gone out of Wi Fi range you will need to 1 Ensure that Wi Fi is still turned on on the mobile device 2 Check that Wi Fi is connected to the same Wi Fi network that the PC is connected to 3 If the mobile device has lost the Wi Fi connection completely you may need to move closer to the PC running RAPIX Addressing where Wi Fi reception is stronger Then try refreshing the page if it does not automatically display the short address grid page again 4 If the mobile device is still unable to connect ensure that Wi Fi is still active on the PC and that RAPIX Addressing is still running RAPIX Addressing Not Running To use the mobile interface on a mobile device RAPIX Addressing needs to be running If RAPIX Addressing is not running open it and click the Connect to Mobile Device button which will display the Connect a Mobile Device window Then refresh the page in the mobile device s web browser The Connect to Mobile Device button Rapid Find Algorithm Too Quick The Rapid Find Algorithm can be too
51. liability with respect to the content of the SOFTWARE PRODUCT or any part thereof including but not limited to errors or omissions contained therein libel infringements of rights of publicity privacy trademark rights business interruption personal injury loss of privacy moral rights or the disclosure of confidential information 7 GOVERNING LAW This agreement is governed by the laws of New South Wales Australia including the Australian Consumer Law or where the SOFTWARE PRODUCT is supplied in New Zealand by the laws of New Zealand including the Consumer Guarantees Act Consumer Laws 8 CONSUMER LAWS Diginet acknowledges the following rights liabilities and limitations under Consumer Law Where you purchase the SOFTWARE PRODUCT as a Consumer under a relevant Consumer Law a The SOFTWARE PRODUCT is purchased subject to the statutory guarantees under the Consumer Law Consumer Guarantees b If the SOFTWARE PRODUCT fail to meet any Consumer Guarantee you will be entitled to such rights and remedies as are permitted or provided in the Consumer Law for such failure to the extent that such rights and remedies cannot be lawfully excluded This may include the right to reject or return the SOFTWARE PRODUCT and obtain a refund have the failure remedied by repair or replacement substitution or to receive compensation for any reduction in the value of the SOFTWARE PRODUCT below the price paid or payable for them c You may only exerc
52. ls Use Hysteresis Check this to configure separate DALI Levels for switching the relay ON and OFF Invert Check this to have lower DALI Levels correspond to the relay being switched ONJ O10 ug Minc 254 DALI Level Up Switch On Down Switch Off Manually Set Levels Advanced setting Check this to allow configuration of the Min and Max Levels Min Level The default configuration Switches ON when the level is set to any value above 0 Switches OFF when the level set to 0 Reset to DALI Defaults m i ey Copyright 2015 Diginet Control Systems Pty Ltd 58 RAPIX Addressing Manual The Configure DALI Relay Device window Threshold Options Use Hysteresis Enable this option to allow two independent DALI level thresholds to be set The difference between these two threshold levels is called the hysteresis This option is useful when small changes in the DALI level should not affect the on or off state of the DALI relay device This option is enabled by default Invert This option specifies whether lower DALI levels correspond to the DALI relay s load being switched on and higher DALI levels correspond to the DALI relay s load being switched off This option is disabled by default Threshold Graph The threshold graph displays a visual representation of the threshold and Min and Max level options that are currently configured for the DALI relay device The vertical lines can be dragg
53. ming DALI Devices DALI Devices that are considered by the user to have the correct short address can be marked as confirmed A confirmed DALI Device can no longer be readdressed to prevent accidental changes from occurring Copyright 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 53 Confirmed DALI Devices are also excluded from the Rapid Find Algorithm thereby decreasing the amount of time it takes to determine the short address of non confirmed DALI Devices Using the PC To confirm a DALI Device click the check box in the Confirmed column for the DALI Devce Confirmed A L The Confirmed column in the DALI Device list lf a DALI Device has a proposed short address change and the Confirmed check box is checked then the DALI Device will be readdressed immediately Filter Unconfirmed The DALI Device filter options with the Unconfirmed option selected RAPIX Addressing allows you to hide any confirmed DALI Devices so that you can concentrate on only unconfirmed DALI Devices by clicking the Unconfirmed filter option above the DALI Device list Note Any DALI Devices that need to be moved out of the way in order for the original DALI Device to be moved will be moved first These DALI Devices cannot be confirmed To unconfirm a DALI Device uncheck the check box in the DALI Device s Confirmed column This will enable that DALI Device to be readdressed again and be a part of the Rapid Find Algorithm
54. mulator can be accessed by clicking the URL hyperlink in the Connect to Mobile Device window http 192 163 10 102 669 diginet rapmaddressin Clickable hyperlink in the Connect a Mobile Device window This can be closed at any time by clicking the close button in the top right corner of the window Copyright O 2015 Diginet Control Systems Pty Ltd 56 RAPIX Addressing Manual The mobile phone simulator The mobile device simulator is functionally equivalent to the interface that can be used on a physical mobile device See topic Short Address Grid PageD28 for more information on the mobile interface Copyright O 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 57 9 Editing DALI Device Properties RAPIX Addressing allows the user to edit the properties of certain DALI Devices on the DALI Line 5 1 Editing a DALI Relay Device To edit the properties of a DALI relay device select the device in the DALI Devices list and either click the Edit Device button or double click the DALI relay device in the list We l3 lt Lhoose gt l3 Fluorescent L Fluorescent y 14 lt Choose gt 14 Relay DALI Devices 15 Edit Device A DALI Relay device selected with the Edit Device button enabled This will open the Configure DALI Relay Device window Configure DALI Relay Device Settings Drag the sliders or blue and green lines to set up DALI relay thresholds and ow minimum and maximum leve
55. n marked by the user to indicate that they occupy the intended short address See topic Readdressing and Confirming DALI DevicesU50 for more information on confirming DALI Devices State Actual SA Requested 5A New SA Device Type Confirmed Actual Short Address A y 0 lt Choose gt 0 Emergency 4 y 3 lt Choose gt 3 Relay L 4 4 Choose 4 HAuorescent LJ The DALI Device list with confirmed and unconfirmed DALI Devices Filter Unconfirmed All and Unconfirmed filter buttons All button Click this button to display all DALI Devices on the DALI Line including those that have been confirmed Unconfirmed button Click this button to display only unconfirmed DALI Devices on the DALI Line When a DALI Device is confirmed in this mode it immediately disappears from view Actual and Proposed Short Address Grids The actual and proposed short address grids display a graphical representation of the DALI Line Each of the 64 DALI short address are displayed as a cell and the type of DALI Device occupying each short address is represented by different colours Cells without any colour are short address that are currently unoccupied Copyright 2015 Diginet Control Systems Pty Ltd User Interface 17 Act ual PDE 12 13 14 15 16 17 18 19 20 212 A 4 25 26 27128 29 30 Pd 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57
56. ne 3 2 User Interface on a Mobile Device Go Mobile This section describes the user interface on a mobile device allowing you to Go Mobile 3 2 1 Short Address Grid Page The user interface for the mobile web page consists of a DALI short address grid that displays DALI Devices in the same way as on the RAPIX Addressing main window There are 64 cells each representing a DALI short address each colour coded to represent a DALI Device that may be occupying each short address The colours used are identical to the DALI Device type colours used in the PC user interface Copyright 2015 Diginet Control Systems Pty Ltd User Interface 29 The main mobile web landing page Blue Menu Bar The blue bar at the top of the page is much the same as in the RAPIX Addressing PC user interface RAPIX Addressing The mobile web page s blue menu bar Mode button Press this button to change the mode that the mobile web page is operating in This takes the user to an Select DALI Device Type Mode page which allows the user to select what type of DALI Devices to work on See topic Device Type Modes31 for more information on mobile web page operating modes Help button E Press this button to vew a quick help page designed to answer most questions relating to the mobile interface The help page contains a colour legend for the DALI Device short a
57. nncnccnccncnncancnncnnrnnrnnrnnrnnrnnrnnrnnannancannancanrancnnos 55 Editing DALI Device Properties 57 Eding a DALI Relay DEVICE aaaea A iaa 57 Troubleshooting 61 DALI Command Interterence ssrsnriciniania aia 61 PC User Interface PrODIO MS 62 Copyright O 2015 Diginet Control Systems Pty Ltd 4 RAPIX Addressing Manual 3 Mobile Interface Problems cies al ade 63 Part 7 End User License Agreement 70 Index 73 Copyright O 2015 Diginet Control Systems Pty Ltd Introduction 5 1 Introduction e lt E RAPIX ADDRESSING Welcome to RAPIX Addressing the best in class software application for discovering and commissioning DALI Devices S RAPIX Addressing will allow you to Connect to a DALI Line and assign short addresses to DALI Devices Find the short addresses of DALI Devices Reprogram the short addresses of DALI Devices Test that DALI Devices are functioning correctly Getting Started with RAPIX Addressing The general process for using RAPIX Addressing to commission a site involves 1 Installing RAPIX Addressing on the designated computer See topic Installing RAPIX Addressing for more information 2 Running RAPIX Addressing with a Diginet Control Systems DALI USB Interface Device connected See topic Connecting to a DALI Line438 for more information 3 Programming the short addresses of DALI Devices See topic Readdressing and Confirming DALI Devices450 for more information Each of the steps ab
58. nnect to DALI Interface window with no license for the selected DALI USB Interface Device The window will display the serial number of the selected DALI USB Interface Device as well as the expiry date of the license associated with that DALI USB Interface Device To activate the DALI USB Interface Device to allow you to Go Mobile click the Activate button The Register Activation Key window will appear asking for the activation key Register Activation Key Please enter the product Activation Kew for DALI USB Interface Device se al number LTS The Register Activation Key window Enter the activation key provided to you by Diginet Control Systems and click Activate This will provide you with a license to Go Mobile for the selected DALI USB Interface Device If the registration is successful the DALI USB Interface Device will now be licensed to Go Mobile up until the expiry date that was purchased Copyright O 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 41 License Activation from the Main Window A DALI USB Interface Device can be licensed to Go Mobile by activating it with an activation key in RAPIX Addressing s main window If RAPIX Addressing is connected to a DALI Line and the DALI USB Interface Device is not licensed to Go Mobile there will be a prompt for product activation in the bottom right of the main window DALI USB Interface Device _ __ is currently not licensed to Go Mo
59. nse to Go Mobile There are two ways to activate a license in order to Go Mobile The first method when not connected to a DALI Line is to activate the license from inside the Connect to DALI Interface window The second method when RAPIX Addressing is connected to a DALI Line is to activate the license from the main window Note Activation requires that the DALI USB Interface Device is connected to the PC the PC is connected to internet and you have a 16 digit long activation key License Activation from the Connect to DALI Interface Window A DALI USB Interface Device can be licensed to Go Mobile by activating it with an activation key in the Connect to DALI Interface window To open the Connect to DALI Interface window click the Connect to DALI Line button in the grey side bar Copyright 2015 Diginet Control Systems Pty Ltd 40 RAPIX Addressing Manual 5 The Connect to DALI Line button The Connect to DALI Interface window will be shown and if there is no license associated with the DALI USB Interface Device currently selected in the combo box an Activate button will be displayed a Connect To DALI Interface Connect to the DALI USB Interface Device Select the DALI USB Interface Device and click Connect Interface Device Diginet USB DALI Interface HU v E License Info No Go Mobile license found Activate Cancel The Co
60. o launch RAPIX Addressing via the Start menu 1 Open the Start menu 2 Click All Programs 3 Open the Diginet folder then the RAPIX Addressing folder 4 Click RAPIX Addressing J Diginet J RAPIX Addressing Y Help File E Manual Si RAPIX Addressing 2 4 Setting Up a Wireless Access Point To be able to commission DALI Devices by using a mobile device a wireless access point must be set up The wireless access point must be set up to provide a Wi Fi network that can be connected to by specifying e Network name SSID e Network password optional Note These settings can be set up prior to going on site The wireless access point can either be e Connected to the PC and mobile device over Wi Fi recommended or e lf Wi Fi reception is an issue connected to the PC via an Ethernet cable and connected to the Copyright 2015 Diginet Control Systems Pty Ltd 10 RAPIX Addressing Manual mobile device over Wi Fi Option 1 Connecting the PC and Access Point via Wi Fi This is the recommended practice for setting up a wireless access point for RAPIX Addressing Plug in a wireless access point with a Wi Fi network set up and then connect the PC and mobile device to it 9 gt USB y EE AL N DALI USB Interface SS An iN een Q PC Wireless Mobile Device Access Point Full setup with Access Point connected via Wi Fi Option 2 Connecting the PC and Access Point via Ethernet If Wi Fi
61. obile Device at 192 168 10 102 Connected The top blue bar displaying a mobile device s IP address The Disconnect a Mobile Device button PC Power Saving Options and Security RAPIX Addressing provides two features related to power saving options and security when a mobile device is connected Power Saving Options When a mobile device is connected to RAPIX Addressing in order to maintain the connection the PC is prevented from going to sleep The PC s display will turn off after a period of time if this option has been set in Windows in order to conserve power Security When using a mobile device connected to RAPIX Addressing the PC may be out of sight In order to help keep the PC secure RAPIX Addressing provides an option in the Options window to lock the PC when a mobile device is connected This will prevent unauthorised users from accessing the PC while you are not in front of it Note To unlock the PC in order to continue using it press Ctrl Alt Del and enter your PC user account password Note See topic Options424 for more information on setting this option Verifying a DALI Line Verifying a DALI Line involves ensuring that all of the DALI Devices on the DALI Line are functioning correctly This can be done in four ways each accessible by a button in the RAPIX Addressing side bar They are 1 Turning all DALI Devices on a DALI Line on 2 Turning all DALI Devices on a DALI Line off 3 Toggling all DAL
62. obile access in the RAPIX Addressing Software to control it from this device Web Access Disabled error page To enable mobile web access click the Connect a Mobile Device button The Connect a Mobile Device button The web browser currently displaying the Access Disabled error should automatically refresh and display the short address grid page Manually refresh the page if this does not occur No HTML5 If you are using a mobile device with a web browser that does not support HTML5 you may find that the mobile interface neither renders nor functions properly If you are experiencing issues viewing the mobile interface on your mobile device ensure that your mobile device software is up to date Javascript is Disabled Javascript must be enabled in your mobile device s web browser for RAPIX Addressing to function If Javascript is not enabled the following error page will be shown Copyright 2015 Diginet Control Systems Pty Ltd 66 RAPIX Addressing Manual RAPIX Addressing A JavaScript is Disabled JavaScript needs to be enabled to control the RAPIX Addressing software using a mobile device Please enable JavaScript in your browser s options or preferences settings Javascript is Disabled error page If you turn on Javascript and refresh the page you will be redirected to the short address grid page where you can use RAPIX Addressing Cookies Are Disabled Cookies must be enabled in your mobile device s web b
63. ol Systems Pty Ltd User Interface 25 RAPIX Addressing Options Set options for RAPIA Addressing including the HTTP port number DALI Device toggle times the Rapid Find Algorithm step time and logging options Go Mobile Options i Selection Behaviour ma Selection Behaviour Behaviour Selected DALI Device is ON with all others OFF Selected DALI Device is OFF with all others ON DALI Device Toggle Options Selected Duration 3 0 seconds Deselected Duration 1 0 seconds Summary When toggling DALI Devices the selected DALI Device will turn ON for 3 0 seconds then turn OFF for 1 0 seconds When toggling the DALI Line the DALI Devices will turn ON for 3 0 seconds then turn OFF for 1 0 seconds Reset to Defaults The Options window Go Mobile Options Tab HTTP Port Number The HTTP port number is used when connecting a mobile device to RAPIX Addressing to commission a DALI Line The default HTTP port number value is set to 7669 and can be changed if this port conflicts with any third party software The minimum value is 1024 and the maximum is 65535 Note Changing this option requires administrator privileges so when clicking Save Windows will prompt for administrator privileg
64. ons DALI Device Toggle Options The DALI Device toggle options change the behaviour when RAPIX Addressing is automatically toggling DALI Devices on and off Selected Duration The selected duration is the time in seconds that a DALI Device remains in the selected on state when being toggled The default value is 3 0 seconds The minimum value is 1 0 seconds and the maximum is 5 0 seconds Deselected Duration The deselected duration is the time in seconds that a DALI Device remains in the deselected off state when being toggled The default value is 1 0 seconds The minimum value is 1 0 seconds and the maximum is 5 0 seconds Rapid Find Algorithm Tab Step Time The step time is the interval between consecutive steps in the Rapid Find Algorithm for finding the short address of a DALI Device The default value is 3 0 seconds The minimum value is 2 0 seconds and the maximum is 10 0 seconds See topic Rapid Find Algorithm43 for more information on this feature Conflict Detection Tab Select the short address conflict detection algorithm that will be used when Scanning a DALI Line D42 The normal scan will successfully find and resolve DALI Short Address conflicts for a DALI Line that contains DALI Devices that are all DALI compliant The deep scan is slower but is able to resolve DALI Short Address conflicts for a DALI Line that may contain some non compliant DALI Devices these are sometimes referred to as DALI C
65. opyright 2015 Diginet Control Systems Pty Ltd User Interface 27 compatible devices Offsets Tab Address Offsets Section The Address Offset options allow offsetting DALI addresses by one on the display E g when the option is applied DALI address 5 will appear as 6 in all windows in RAPIX Addressing However internally address 5 will still be used when communicating with DALI Line Apply offset to DALI Short Address This option offsets DALI Short Addresses by 1 on the display When enabled the lowest DALI Short Address will appear as 1 instead of the standard DALI value 0 and the highest DALI Short Address will appear as 64 instead of the standard DALI value 63 Apply offset to DALI Group Address This option offsets DALI Group Addresses by 1 on the display When enabled the lowest DALI Group Address will appear as 1 instead of the standard DALI value 0 and the highest DALI Group Address will appear as 16 instead of the standard DALI value 15 Apply offset to DALI Scene Address This option offsets DALI Scene Addresses by 1 on the display When enabled the lowest DALI Scene Address will appear as 1 instead of the standard DALI value 0 and the highest DALI Scene Address will appear as 16 instead of the standard DALI value 15 Logging Tab The logging options on the Logging tab allow the user to send detailed logs to Diginet Control Systems technical support in case of troubleshooting Log Level Errors and Wamings Recomm
66. ove will be explained within this manual 1 1 Glossary of Terms This glossary lists many of the terms that are used in this manual Confirm The process of confirming a DALI Device such that its short address cannot be changed in RAPIX Addressing All DALI Devices are unconfirmed by default and are automatically confirmed when readdressed DALI DALI is an acronym that stands for Digital Addressable Lighting Interface which is an open standard for network based systems that can control the lighting in buildings DALI Device Copyright 2015 Diginet Control Systems Pty Ltd RAPIX Addressing Manual A DALI Device as referenced in this document is a lighting device that is connected to a DALI Line DALI Line A DALI Line consists of a pair of wires that allows the connection of multiple DALI Devices that can communicate to each other Go Mobile This is a feature of RAPIX Addressing that allows a mobile device to connect to it in order to control and readdress DALI Devices on a DALI Line Mobile Device A smart phone or tablet that is capable of running a web browser that can access RAPIX Addressing s mobile web interface Rapid Find Algorithm Algorithm in RAPIX Addressing that is used to determine the short address of an observed DALI Device Readdress The process of programming a new short address into a DALI Device Short Address SA A short address is an address that each DALI Device is assigned so that it can be identi
67. pic Rapid Find Algorithm 32 for more information Select previous DALI Device button Press this button to select a DALI Device at the previous occupied short address Toggle DALI Device button This button displays the currently selected DALI short address Press this button to manually toggle on and off the currently selected DALI Device Note This button wil be highlighted in yellow when the DALI Device is swtched on Select next DALI Device button Press this button to select a DALI Device at the next occupied short address 3 2 2 Device Type Modes The mobile web page can be used in multiple modes depending on the type of DALI Device that is currently being commissioned There are options to search readdress and confirm e DALI Devices of any type e All non emergency DALI Devices e Only emergency DALI Devices The Select DALI Device Type Mode page can be accessed by pressing the Mode icon in the blue bar Copyright 2015 Diginet Control Systems Pty Ltd 32 RAPIX Addressing Manual RAPTX Addressing DALI Device Types to Show All Non emergency b Emergency Only O DALI Device type selection page The currently active mode will be highlighted in blue Pressing on any of the buttons will select that mode and return the user to the short address grid page The icon for the new mode will now be shown in the blue bar The options available are FA Al
68. r to the desired scene level value Click elsewhere on the form to commit the change This will add this DALI Device to the Scene Sale AtalSA 0111213 F aE 10111112 13 14 Actual Short Address 1 2 3 gb 100 100 4 ih uta LT O 100 710 0 1 01 100 65 100 5 8 100 100 13 0 1 42 100 100 Change Scene level for DALI Device To change a level of a Scene click the number or bullet in the column of the scene to display a pop up dialog Move the slider to the desired scene level value Click elsewhere on the form to commit the change State Actual SA 0 1 23 Fl 11 12 13 14 Actual Short Address 1 1 2 3 0 100 100 4 0 100 100 100 0 1 01 80 100 65 100 58 100 100 13 0 1 42 100 100 Remove DALI Device from Scene To remove a DALI Device from a Scene click the number in the column of the scene to display a pop up dialog Check the Mask checkbox Click elsewhere on the form to commit the change Copyright O 2015 Diginet Control Systems Pty Ltd 22 RAPIX Addressing Manual Mode Short Addressing Group Addressing State Actual SA D 1 i 1 1 12 13 14 Actual Short Address 0 100 100 100 100 100 0 1 01 80 100 6 100 56 100 100 13 01 42 48 100 100 Set a Scene To test a DALI scene click the Set Scene button that matches the scene number to be set Note that buttons will only be available if the corresponding scene exists on the DALI Line Sort by Selected Scene Selecting the Sort by Selected
69. rowser for RAPIX Addressing to work If cookies are not enabled the following error page will be shown RAPIX Addressing As Cookies are not enabled This web browser needs to have cookies enabled in order to be able to access the rapid software Cookies can be enabled in the browser options or preferences settings Cookies Disabled error page If you turn on cookies and refresh the page you will be redirected to the short address grid page where you can use RAPIX Addressing Web Access is Denied This problem can occur if there are multiple web enabled devices attempting to connect to RAPIX Addressing Copyright 2015 Diginet Control Systems Pty Ltd Troubleshooting 67 RAPIX Addressing A Access Denied Another mobile device is currently controlling the RAPIX Addressing software The Access Denied error page RAPIX Addressing supports only one mobile device connected at a time The IP address of the mobile device connected to RAPIX Addressing will be displayed in the PC interface s blue bar as seen below RAPIX Addressing Mobile Device at 192 168 10 102 Connected Mobile Device with IP address 192 168 10 102 is connected to RAPIX Addressing If you wish to connect another mobile device to RAPIX Addressing you must first disconnect the currently connected mobile device by closing the RAPIX Addressing web page and then click the Disconnect a Mobile Device button in RAPIX Addressing
70. rt of the SOFTWARE PRODUCT and subject to the terms and conditions of this EULA f Compliance with Applicable Laws You must comply with all applicable laws regarding use of the SOFTWARE PRODUCT 3 RENEWALS AND TERMINA TION This EULA will expire at the end of the subscription period specified in your invoice unless you renew this EULA before the expiry date by payment of a further subscription at the prevailing subscription price at that time Without prejudice to any other rights Diginet may terminate this EULA if you fail to comply with the terms and conditions of this EULA Diginet may also terminate this EULA at any time for convenience subject to giving you 5 days prior notice and in that event you will be refunded a pro rata proportion of the subscription amount paid for the current subscription period On termination of this EULA for any reason certain critical functions of the SOFTWARE PRODUCT will cease to operate Clauses 4 to 8 inclusive of this agreement survive the termination of this agreement for any reason 4 COPYRIGHT All title including but not limited to copyrights in and to the SOFTWARE PRODUCT and any copies thereof are owned by Diginet or its suppliers All title and intellectual property rights in and to the content which may be accessed through use of the SOFTWARE PRODUCT is the property of the respective content owner and may be protected by applicable copyright or other intellectual property laws and treaties This
71. s Pty Ltd 14 RAPIX Addressing Manual Global Programming button Click this button to open the Global Programming window which will allow the programming of DALI levels and fade otions across all DALI Devices on the DALI Line See topic Global Programming for more information Identify All DALI Devices on the DALI Line button Click this button to toggle the DALI Devices on the DALI Line on and off periodically as well as identify emergency DALI Devices This function is useful to determine whether all DALI Devices on the DALI Line are wired and functioning correctly See topic Verifying a DALI Line444 for more information Turn DALI Line On button Click this button to turn on all DALI Devices on the DALI Line See topic Verifying a DALI Line444 for more information Turn DALI Line Off button Click this button to turn off all DALI Devices on the DALI Line See topic Verifying a DALI Line4 4 for more information Identify All Emergency DALI Devices button Click this button to identify all emergency DALI Devices on the DALI Line See topic Identifying an Emergency DALI DeviceO for more information Identify the Selected DALI Device button Click this button to toggle the selected DALI Device in the list on and off periodically If it is an emergency DALI Device it will commence an emergency identify See topic Identifying a DALI Device446 for more information Turn Selected DALI Device On bu
72. s RAPIX Addressing to eliminate DALI Devices not being observed until only one is left Audio Feedback On mobile devices that support playing sounds in the web browser audio feedback of the Rapid Find Algorithm can be used to allow the user to observer the DALI Dewce directly and listen for feedback from the Rapid Find Algorithm rather than look at the mobile device An ascending sound is played when the Press when load goes on button is pressed and a descending sound is played when the Press when load goes off button is pressed A bing bong sound is played when the Rapid Find Algorithm completes Sounds can be enabled or disabled by pressing the speaker button in the bottom right This option can also be set on the Options dialogue See topic OptionsO24 for more information Cancelling the Rapid Find Algorithm You may want to cancel the Rapid Find Algorithm for any reason or if a mistake was made e g Copyright 2015 Diginet Control Systems Pty Ltd 34 3 2 4 RAPIX Addressing Manual e Pressing the Press when load is on off button when not meant to or e Not pressing the Press when load is on off when meant to or e You need a coffee break The Rapid Find Algorithm process can be cancelled at any stage by clicking the Cancel button which will return you to the short address grid page The Rapid Find Algorithm can be started again at any time Changing the Delay Between Each Step The time delay between each step of the
73. tons on the mobile interface The buttons shown above can be used to verify and identify DALI Devices on the DALI Line See topic Short Address Grid Pagel28 for more information on each button Identifying a DALI Device Identifying a DALI Device can mean two things 1 Finding a DALI Device with a specific DALI short address 2 Finding the DALI short address of an observed DALI Device RAPIX Addressing supports methods of achieving both goals Finding a DALI Device With a Specific Short Address To locate a DALI Device with a specific DALI short address select the DALI Device in the list and click one of the following options in the side bar 1 Turn Selected DALI Device On This will turn the selected DALI Device on keeping all other DALI Devices on the DALI Line off Note If the invert option has been set the selected DALI Device wil be turned off wth all other DALI Devices on the DALI Line on See topic Options424 for more information on the invert option 2 Toggle Selected DALI Device This will toggle the selected DALI Device on and off with a delay between Note If the invert option has been set the on and off delay intervals will be reversed for the selected DALI Device and all other DALI Devices will remain on See topic OptionsU24 for more information on the delay intervals and invert options Copyright O 2015 Diginet Control Systems Pty Ltd Basic Working Procedures 47 Using one of these options will help
74. tton Click this button to turn the DALI Device that is currently selected in the list on with all other DALI Devices on the DALI Line remaining off This function is useful to quickly identify a DALI Device See topic Identifying a DALI Device446 for more information Note The behaviour of this function will be inverted if the selection behaviour is changed See topic Options424 for more information Identify Selected Emergency DALI Device button Click this button to identify the selected emergency DALI Device in the list See topic Identifying a DALI Device44 for more information Readdress and Confirm button Click this button to commit any proposed short address changes on the DALI Line See topic Readdressing and Confirming DALI DevicesO for more information on readdressing DALI Devices DALI Devices List The list displays all of the DALI Devices on the DALI Line Copyright 2015 Diginet Control Systems Pty Ltd User Interface 15 Group Addressing Scene Levels Filter Uncontirmed State Actual SA Requested SA New SA Device Type Confirmed Actual Short Address A y 0 Choose 0 Emergency LI 1 Choose Fuorescent L 4 2 lt Choose gt 2 LED LJ y 3 lt Choose gt 3 Relay O 4 4 4 Auorescent L Choose The DALI Device list columns Each row represents a single DALI Device and displays the following attributes for each one e State column Whether the DALI Device is on or off or is c
75. urrently in identify mode for emergency DALI Devices only e Actual SA column The current short address of the DALI Device e Requested SA column The short address of the DALI Device that the user has requested to move it to e New SA column The proposed new short address of the DALI Device This is normally the same as the requested short address except in cases where the DALI Device must be moved to make room for another DALI Device e Device Type column The DALI Device Type of the DALI Device whether it s a fluorescent LED emergency or other type of fitting e Confirmed column Whether or not the DALI Device has been confirmed Edit Device Button Beneath the DALI Devices list is a button that allows the user to edit the properties of certain DALI Devices Edit Device The Edit Device button at the bottom left of the list Currently this button allows for the editing the properties of a DALI relay device DALI device type 7 Switching function and will only be enabled when a DALI relay device is selected in the DALI Devices list See topic Editing DALI Device Properties5 for more information on editing the properties of certain DALI devices Copyright 2015 Diginet Control Systems Pty Ltd 16 RAPIX Addressing Manual DALI Devices Filter RAPIX Addressing allows the user to filter out DALI Devices that have been marked as confirmed Confirmed DALI Devices are DALI Devices that have bee
76. vice whose short address has been found selected in the short address grid If your mobile device supports audio a sound will be played indicating that the process is complete See topic Rapid Find Algorithm4 for more information on how the Rapid Find Algorithm works Note This method may not work for maintained emergency DALI Devices as they do not respond to on and off commands Identifying an Emergency DALI Device Finding the short address of an emergency DALI Device can be done by putting the DALI Device in identification mode This method can be used much like toggling individual DALI Devices on and off to locate an emergency DALI Device with a specific short address All emergency DALI Devices on the DALI Line can also be put into identification mode as well which may be useful if the identification mode for the DALI Devices emits any identifiable sequence Note To indicate that DALI Devices that are currently in emergency identification mode they will flash between green and white on the mobile interface See topic Short Address Grid Pagel28 for more information on the functions available on the mobile interface Decoding the Tridonic Red Green Sequence Tridonic emergency DALI Devices when in identification mode emit their short addresses in the form of a binary sequence depicted by flashing the red and green indicator LEDs RAPIX Addressing s mobile interface provides a method of decoding this red green sequence by
77. w short address In addition to pressing a cell to readdress a DALI Dewce to the Previous and Next buttons can be used to cycle back and forward through potential short addresses lt gt The Previous button on the left and the Next button on the right To readdress the DALI Device press the Apply button To cancel readdressing the DALI Device press the Cancel button Confirmed DALI Devices lf a DALI Device has been confirmed then it cannot be readdressed If a confirmed DALI Device is selected then the Readdress button at the top right of the page changes into an Unconfirm button del The Unconfirm button Copyright 2015 Diginet Control Systems Pty Ltd 36 RAPIX Addressing Manual ma a A ES i LELI El A j 3 Ml ann F a F LA QI lt 22 22 D gt Confirmed DALI Device selected and Unconfirm button Pressing the Unconfirm button will unconfirm the selected DALI Device thereby allowing that DALI Device to be readdressed See topic Readdressing and Confirming DALI Devices4 for more information on readdressing and confirming DALI Devices 3 2 5 Mobile Device Help Page The mobile interface provides a quick help guide which provides access to A legend that describes the different colours for DALI Devices of different types A description of the DALI Device type modes that the mobile interface can operate in A guide to all of the buttons available in the mobile interface Oo
78. wer DALI Levels correspond to the relay being switched OM Max 254 MOJO ug Hirc 1 0 DALI Lewel 25d Switch On Off 64 Switch off at Level 64 or greater Example 4 Switch on and off at Level 128 with Min Level at 100 and Max Level at 160 To have the DALI relay use different from default Min and Max levels the Manually Set Levels option must be enabled The green Min and Max level bars can then be dragged to the desired level values The setup will look like this _ Use Hysteresis Check this to configure separate DALI Levels for switching the relay ON and OFF Invert Check this to have lower DALI Levels correspond to the relay being switched ON Or 128 Max 160 a Oo Win 100 ere 0 DALI Level 254 Switch On Off 128 Manually Set Levels Advanced setting Check this to allow configuration of the Min and Max Levels Min Level 100 Max Level 160 Copyright 2015 Diginet Control Systems Pty Ltd Editing DALI Device Properties 61 Set Min and Max levels Note An invalid Relay configuration is possible when manually setting the Min and Max levels It is not recommended setting threshold levels outside the Min and Max level boundaries 6 Troubleshooting if you have any problems using RAPIX Addressing this section lists common problems and potential solutions If attempting to diagnose a difficult problem the logs generated by RAPIX Addressing can be a useful tool See topic Options424

Download Pdf Manuals

image

Related Search

Related Contents

ひこの商品についてのお問い合わせは、ご購入の販売店または当社  Mercedes-Benz 2007 S 550 Automobile User Manual  Samsung RB1855SL Manuel de l'utilisateur  eSWIS User Manual - Proposed Project Summary  Husqvarna Cut-n-Break K 760 User's Manual    The Java™ Web Services Tutorial  - AudioCodes  Correlación de parámetros de biometría hemática  