1. Wy Allen Bradley ControlNet PLC 5 User Manual Hot Backup System Includes Cat No 1785 CHBM Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will the Allen Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation the Allen Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Allen Bradley Company with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of the Allen Bradley Company is prohibited
2. Publication 1785 6 5 24 February 1999 4 2 Using the 1785 CHBM Cartridge Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System Status Indicators The 1785 CHBM cartridge status indicators indicate the operational state of the ControINet PLC 5 backup system The following table lists the various LED states and the recommended action LED Color Indicates Probable Cause Corrective Action PRI Green This processor is the primary i e it controls the Normal operation No action required outputs Green blinking This processor is in the Lonely Primary backup No good scheduled Check media for broken cables state connections loose connectors missing terminators etc Red The backup system is not yet completely Improper backup Refer to Troubleshooting the configured i e system is in the Invalid backup configuration parameters Invalid Backup State section later state Improper ControlNet in this chapter Backup Integer file Off This processor is not the primary i e system is Normal operation No action required in the No Control or Secondary backup state SEC Yellow This processor is the qualified secondary i e Normal operation No action required system is in the Secondary backup state Red The backup system is not yet completely Improper backup Refer to Troubleshooting the configured i e system is in the Invalid backup configuration parameters Invalid
3. Take this corrective action No action required 1 Receive handshake connection not found in I O Map Table Configure the handshake connections in the I O map table Enter the handshake connection numbers in words 1 and 2 of the ControlNet Backup Configuration and Status file Send handshake connection not found in I O map table Configure the handshake connections in the I O map table Enter the handshake connection numbers in words 1 and 2 of the ControlNet Backup Configuration and Status file Receive handshake connection wrong size Make the handshake connection in the I O map table 5 words long Send handshake connection wrong size Make the handshake connection in the I O map table 5 words long Node address number wrong Enter the odd node number of the odd even backup pair into word 0 of the ControlNet Backup Configuration and Status file Operation mode word invalid Enter a valid operation mode value into word 10 of the ControlNet Backup Configuration and Status file 0 asynchronous 1 synchronous Equivalence mode word invalid Enter a valid equivalence mode word i e 0 63 into word 11 of the ControlNet Backup Configuration and Status file Designated Primary word invalid Enter a valid Designated Primary word into word 12 of the ControlNet Backup Configuration and Status file 0 inactive 1 active Maximum Program Scan Time word invalid Enter a valid
4. When a PLC 5 ControlNet backup system is in Run mode and is not actively controlling the system outputs it is in the Secondary backup state The Secondary LED is solid yellow the Primary LED is off and the Qualified LED is solid green The PLC 5 can go out of Secondary backup state if either the PLC 5 system goes out of Run mode or the partner PLC 5 system is no longer the primary If the partner PLC 5 is no longer the primary the PLC 5 in the Secondary backup state becomes the primary and assumes control of the system outputs When the PLC 5 is in the Secondary backup state you cannot make any backup configuration changes to that PLC 5 system All backup configuration changes must be made to the primary system and those changes are immediately passed on to the secondary system In the previous section we described the possible states of the PLC 5 ControINet backup system with references to transitions between states For example when in the No Control backup state if you change a configuration parameter to an invalid value the PLC 5 ControINet backup system transitions into the Invalid backup state This section describes two backup state transitions Qualification and Switchover Qualification Qualification occurs when the PLC 5 ControlNet backup system transitions from the No Control backup state to either the Secondary backup state or the Primary backup state You activate this backup state transition by changing the PLC
5. E 2 Application Guidelines Publication 1785 6 5 24 February 1999 System outputs are in many cases a function of past events or states An output may be in the present state based on a timing event a counting event or some other prior event If the secondary comes online and immediately assumes control its outputs are likely to be in an opposite state from the primary because the secondary was not in operation while the primary was accumulating the past events In order to ensure seamless switchover of control the secondary should be refreshed with the primary s past events before assuming control The ControINet PLC 5 backup system transfers many system state variables automatically In addition the secondary transfers the entire primary data table on power up Upon entering Run mode the secondary transfers all timer accumulators counter accumulators PD file type structures and selected files which you have specified a second time This transfer places these critical state variables in the freshest state possible In most applications you can transfer all necessary information by configuring a few parameters in the ControINet Hot Backup Configuration file The secondary PLC processor uses the configuration parameters to determine which files to transfer What Information Should Be Transferred The secondary PLC processor transfers selected processor memory files on power up Timers counters and PID structures contain past s
6. The first crossload performed during qualification is the Qualification data table crossload This crossload is performed when the processor is still in Program mode The second crossload done during qualification is the Qualification State data table crossload This crossload is performed once the processor has transitioned into Run mode Even though the processor has transitioned into Run mode qualification is not complete until the Qualification State data table crossload is complete Qualification Data Table Crossload The Qualification data table crossload occurs when a processor in the No Control state transitions from Program mode to Run mode and the other processor is the primary processor This complete data table crossload is performed while the qualifying PLC 5 system is still in Program mode It is necessary to remain in Program mode until the complete data table crossload is finished in order to prevent the qualifying system from major faulting or going off into an odd state due to uninitialized data table values Publication 1785 6 5 24 February 1999 C 6 Data Table Crossloading Publication 1785 6 5 24 February 1999 All elements of all data table files are crossloaded in the Qualification data table crossload with the exception of the following files These files cannot be crossloaded because they contain processor specific configuration and status information e System Status File S2 e ControlNet Backup Integer File
7. When setting up the backup system the location of the data that needs to be crossloaded is important We recommend that you place all of the crossload data into a few consecutively addressed files Then by configuring those files in the range User Selectable crossload files only those files will be crossloaded This shortens the time necessary to perform the crossload as well as preventing unwanted files from being crossloaded For example if there are 10 integer files that need to be crossloaded place those 10 integer files into consecutively numbered files e g N100 through N109 Then fill the User Defined Crossload Range Low File Word 57 of the CHBI file with 100 and the User Defined Crossload Range High File Word 58 of the CHBI file with 109 Now all 10 integer files will be crossloaded when User Selected File operation of the On Demand data table crossload is triggered Triggering an On Demand Data Table Crossload On Demand data table crossloads are initiated by writing a value into the On Demand crossload command word word 33 of the ControlNet Backup Integer File The On Demand data table crossload can be initiated from either the primary or secondary processor Since the On Demand crossload command word is located in an integer file you have many options concerning how the On Demand data table crossload gets triggered The crossload could be triggered via the ControINet Backup Configuration and Status tool via the RSL
8. e ControlNet Configuration File e ControlNet I O Status File e ControlNet Diagnostic File e ControlNet Data Output File DOF e ControlNet Data Input File DIF Although the System Status File is not crossloaded the real time clock 6 words in the System Status File is crossloaded from the primary processor to the partner processor Qualification State Data Table Crossload Even though a Qualification data table crossload has occurred during qualification some of the crossloaded data may have become stale This is because the Qualification data table crossload occurs while the processor is in Program mode For example if the Qualification data table crossload takes 10 seconds the data in the original data table file that was transferred is 10 seconds old In order to bring certain state information in the data table up to date a Qualification State data table crossload is performed The Qualification State data table crossload occurs when the qualifying processor has transitioned into Run mode but before the qualifying processor has become qualified The Qualification State data table crossload is almost identical to the On Demand data table crossload discussed previously The only differences are e the Qualification State data table crossload occurs automatically during qualification whereas you must trigger the On Demand data table crossload e the Qualification State data table crossload always performs all four cro
9. e critical failures in the primary processor e g hardware faults e internal conditions within the primary processor e g a major fault causing it to relinquish control of the process to the sec ondary processor e external conditions recognized by the secondary processor e g loss of communications with the primary processor causing it to assume control of the process e a manual switchover i e a forced switchover where you cause the secondary processor to become primary and vice versa you may choose to do this when testing your system for backup performance and integrity or as part of a system maintenance program The ideal switchover time from the primary processor to the secondary processor would be instantaneous The ControlNet PLC 5 backup system typically provides a switchover time of 30 50 ms This time is adequate to avoid a bump in most systems but you should determine the maximum allowable switchover time for your applications Chapter Objectives Chapter 2 Understanding the ControlNet PLC 5 Backup System Components This chapter describes the components that make up the ControlNet PLC 5 backup system Hardware Components These components include e two Series F PLC 5 ControlNet processors either 1785 L40C15 F or 1785 L80C15 F Each processor must be in a separate 1771 chassis and each chas sis must have its own power supply Various chassis and power supplies are available choose them bas
10. Each packet of data is immediately written into the other processor s data table So no matter how long the data table crossload takes the data table elements which are crossloaded into the qualifying or secondary processor closely match the values in the primary processor Effect of Data Table Crossloading on the ControlNet Channel Data table crossloading only transfers one file at a time Also only one unscheduled buffer is used at any one time So the impact of the data table crossloading on available ControINet channel unscheduled bandwidth should be minimal Also the impact of data table crossloading on the available unscheduled buffers is minimal Inhibiting Data Table Crossloads All crossloading is inhibited if there is any difference at all in the data table structures between the two processors This inhibits all data table crossloads not just data table crossloads to files whose structures differ between the two systems You can make the data table structures differ between the two systems by creating an extra data table file on one of the systems or by increasing the size of one of the data table files For a qualified backup system you are given an indication as to whether the data table structures match in the Equivalence Check Error word word 49 of the ControlNet Backup Integer File bit 1 You can ensure that the qualifying system fails qualification and major faults if the data table structures do not match by e
11. The ControlNet I O Map Table checksum only includes the scheduled redundant connections Thus as long as the scheduled redundant connections are the same between the backup PLC 5 systems the ControlNet I O Map Table checksums will match Publication 1785 6 5 24 February 1999 B 8 Backup States Publication 1785 6 5 24 February 1999 ControlNet Backup Configuration and Status file This checksum is only calculated when the PLC 5 system goes through qualification Since this checksum cannot change when the PLC 5 system is in Run mode this checksum does not change after qualification The ControlNet Backup Configuration and Status File checksum is only calculated on the first 3 words of the ControlNet Backup Configuration and Status File Force Tables This checksum is calculated for all I O force tables and for force control words and continues to be calculated when the backup system is qualified This allows status to be available regarding whether the Force Table checksums differ for a qualified backup system Included in the Force Tables checksum are I O Force Table values Extended Force Table values Force Status is forcing enabled and are forces present No SFC information is included in the Force Tables checksum Also note that you cannot perform forcing on DIF or DOF files Status File This checksum is calculated for various configured words in the Status File and continues to be calculated when the backup sys
12. Throughout this manual we use notes to make you aware of safety considerations ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you e identify a hazard e avoid the hazard recognize the consequences Important Identifies information that is especially important for successful application and understanding of the product ControlLogix ControlBus Logix5550 Data Highway Plus and PLC 5 are trademarks of Rockwell Automation ControlNet is a trademark of ControlNet International Ltd DeviceNet is a trademark of the Open DeviceNet Vendor Association Ethernet is a registered trademark of Digital Equipment Company Intel and Xerox Corporation Publication 1785 6 5 24 February 1999 Manual Objectives Who Should Use This Manual What This Manual Contains Preface Using This Manual This manual shows you how to use the ControINet PLC 5 Backup system This backup system uses a pair of standard PLC 5 40 or PLC 5 80 ControINet processors Series F Revision A or higher with I O remotely connected to the processors via ControINet Note For the ControINet PLC 5 processors to operate in backup mode each processor must have the new ControINet Backup Cartridge Cat No 1785 CHBM inserted into its EEPROM memory module slot Using ControINet the PLC 5 processors communicate with each other and with ControINet remote
13. 5 system from Program mode to Run mode You can tell that a qualification is active when the Qualified LED blinks yellow and green alternately Qualification From the No Control State to the Primary State The backup state transition from No Control backup state to the Primary backup state occurs when the PLC 5 system transitions from Program mode to Run mode and e there is no partner PLC 5 system OR e the partner PLC 5 system is not in Primary backup state OR e the partner PLC 5 system is not communicating with this PLC 5 processor The transition from No Control backup state to Primary backup state is simple There are no checks to be done The transition occurs immediately if there is no Qualification Connection Delay Once the transition to the Primary Backup State is complete the LED s on the 1785 CHBM cartridge indicate the new backup state Publication 1785 6 5 24 February 1999 B 6 Backup States Publication 1785 6 5 24 February 1999 Qualification From the No Control State to the Secondary State The backup state transition from No Control backup state to Secondary backup state occurs when the PLC 5 system transitions from Program mode to Run mode and the partner PLC 5 processor is in the Primary backup state and is communicating with this PLC 5 processor The entire qualification process has many components Connection delay There may be up to a 10 second delay before qualification begins because of the time
14. Forced Switchover word of the Backup Integer File You can activate this switchover from either the primary or secondary processor Forced Switchover is useful when you want to test edits you have made in your application program In this case you make edits to the secondary system force a switchover and monitor the results of the edits If the edits cause problems you can perform another Forced Switchover to give the original processor control of the system outputs on the ControlNet channel Since the Forced Switchover feature is activated from writing to the Backup Integer File you can activate Forced Switchovers from external applications writing to the Backup Integer File as well as the application on the processor itself Forced Switchover does not activate for an unqualified PLC 5 ControlNet backup system or for a PLC 5 ControlNet backup system in which the Designated Primary feature is enabled Publication 1785 6 5 24 February 1999 B 14 Backup States Unqualified Switchovers Unqualified Switchovers occur when the primary processor of a qualified PLC 5 ControlNet backup system is no longer in Run mode or when the secondary processor loses its peer to peer handshake connection with the primary processor The secondary processor then does a switchover to become a stand alone primary processor There are many reasons why an Unqualified Switchover can occur you changed the primary PLC 5 system out of Run mode a major fau
15. I O to create a PLC 5 backup system that provides high availability of control applications where it is essential for process continuity to be high In this manual we describe e backup system concepts hardware and software components required for the system procedures for installing and configuring the system e operation of the backup system e troubleshooting diagnostics procedures for the backup system Before you read this manual or attempt to use the ControINet PLC 5 backup system you should be familiar with the use and operation of ControINet PLC 5 processors You should also be familiar with remote I O the ControINet network e RSLogix 5 programming software RSNetWorx for ControINet software e RSLinx communications software Refer to the following table to guide you through the information contained in this manual In this manual we describe For information on Refer to chapter appendix concepts for using a backup system in 1 Backup Concepts for the ControlNet PLC 5 a ControlNet system basic system Backup System architecture the hardware and software 2 Understanding the ControlNet PLC 5 Backup components required for a backup System Components System installing backup system components 3 Installing and Configuring Your ControlNet configuring the backup system PLC 5 Backup System the diagnostic capabilities of the 4 Monitoring and Troubleshooting Your backup system troubleshoo
16. crossloads specific parts of the data table There are 4 different parts of the data table that are crossloaded Timer Accumulators Counter Accumulators PD elements User selectable files It may take many seconds for the Qualification State Data Table crossload to finish The time it takes to complete the data table crossload primarily depends on the amount of data table data to be crossloaded Even though the State Data Table crossload may take many seconds to complete the data that is transferred from the primary system to the qualifying system is fresh In other words the crossloaded data is not sitting in a buffer getting stale waiting for all the data to be crossloaded Each packet of data is immediately written into the qualifying system s data table So no matter how long the Qualification State Data Table crossload takes the data table elements which are crossloaded into the qualifying system closely match the values in the primary system The Qualification State Data Table crossload does not occur if the Data Table Structures are not the same If you want to ensure that a Qualification State Data Table crossload occurs you must enable equivalence checking for the Data Table structure area If for some reason the State Data Table crossload fails qualification also fails and a major fault is declared for the qualifying system Transition to Secondary backup state After the State Data Table crossload is succ
17. during qualification No action required 10 Files being created or deleted during qualification Refrain from editing the data table file or program files during qualification 11 Upload or Download in progress during qualification Refrain from uploading or downloading to the processor during qualification 12 ControlNet channel reconfiguration in progress during Refrain from performing a ControlNet channel reconfiguration qualification during qualification 13 The processor changed from the No Control backup state Refrain from modifying the ControlNet backup configuration to the Invalid backup state during qualification parameters during qualification 14 The partner processor was in the Primary backup state Clear the fault and go back into Run mode when qualification started The partner processor changed out of the Primary backup state during qualification 15 The partner s ControlNet Hot Backup configuration Refrain from changing the partner processor s ControlNet Hot parameters are invalid Backup configuration parameters during qualification 17 Qualification crossload failed Refer to the Troubleshooting Qualification Crossloads section in this chapter 18 Edits in progress during qualification Refrain from editing during qualification Publication 1785 6 5 24 February 1999 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System 4 5 Troubleshooting Qualification Crossloads ControlNet Backup Configuration and Status File If
18. for validity before being accepted Note If a newly entered configuration parameter is invalid the backup system uses the previous configuration values Lonely Primary Backup State The Primary LED is solid green if there is at least one good scheduled connection on the ControINet channel If there are no good scheduled connections on the ControlNet channel the Primary LED blinks green This is referred to as the Lonely Primary backup state Since there are no valid scheduled connections on the ControlNet channel this PLC 5 is not controlling the system outputs on the ControlNet channel A system could go into Lonely Primary backup state for example when the ControlNet cable is disconnected When in Lonely Primary backup state the PLC 5 waits 10 seconds after the first connection is established before actively controlling the system outputs on the ControlNet channel This is so that if an existing partner PLC 5 is controlling the system outputs on the ControlNet channel the PLC 5 system in Lonely Primary backup state does not take control of the system outputs from the partner If during the 10 second wait the PLC 5 in Lonely Primary backup state establishes communication with the partner PLC 5 and notices that the other PLC 5 is a primary the PLC 5 in the Lonely Primary backup state major faults Refer to chapter 4 for description of specific major fault codes Backup State Transitions Backup States B 5 Secondary Backup State
19. in this file are initialized when the file exists the value in S 67 is correct and at least one of the three connection parameters i e one of the first three words of the file is invalid The ControINet Backup Configuration and Status file consists of 200 words as defined in the following table Word Definition 0 Odd node address of the odd even pair of node addresses for the two PLC 5 backup processors 1 Message number of the scheduled Backup Handshake connection being sent from the processor at the Odd node address 2 Message number of the scheduled Backup Handshake connection being sent from the processor at the Even node address 3 Backup state of the processor Valid values include 0 Invalid 1 No Control e 2 Primary 4 Secondary 4 Qualification state of the system Valid values include 0 No qualified secondary present 1 Qualified secondary present Publication 1785 6 5 24 February 1999 4 6 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System Word 5 Definition Reason code indicating why the processor is in the Invalid backup state This word is constantly updated until the processor is no longer in this state Valid values include 0 In valid state Receive handshake connection not found in I O map table Send handshake connection not found in I O map table Receive handshake connection wrong size Send handshake connection wrong size node address nu
20. processor the primary and the unedited processor the secondary If problems occur within the edited system a second forced switchover makes the unedited processor primary again Note that Qualification crossloading and on demand crossloading are disabled when the data table structures between the processors are different Publication 1785 6 5 24 February 1999 3 18 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 Chapter Objectives ControlNet PLC 5 Backup Specific Major Fault Error Codes Chapter 4 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System This chapter describes the diagnostic capabilities of the ControINet PLC 5 backup system and provides you with tips to help you in troubleshooting difficulties with your system The PLC 5 ControINet backup system generates diagnostic information to assist you with troubleshooting problems that may arise within a backup application Most of the diagnostic information is stored within the ControINet Backup Configuration and Status file Other ControINet backup diagnostic information is stored in the Major Fault Code word of the Status File S 12 and on the LEDs of the 1785 CHBM ControlNet backup cartridge You can access the ControINet Backup Configuration and Status file directly via ladder logic and the data monitor or indirectly via the Hot Backup utility within RSLogix 5 The sections in this chapter ref
21. program scan time in both controllers i e scan times will be longer although this impact is not significant in most cases You can change the operational mode from the Configure tab of the ControlNet Hot Backup screen 3 ControlNet Hot Backup of x Crossload Status ackup Data File r Equivalence Checks Backup File 5 67 Ladder Logic Equivalent Data Table Structure Equivalent Connection 1 0 Map Structure Equivalent ODD Node Addr Backup Integer File Equivalent Send Message Force Table Receive Message Status File Equivalent r Properties Designated Primary Operational Mode MaxProgamScanTime n Publication 1785 6 5 24 February 1999 3 14 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 Note When you choose Synchronous mode you will have to enter a Maximum Program Scan Time as well Before selecting Synchronous mode enter a value into the Max Program Scan Time field This value should be slightly larger than the maximum program scan time recorded in the Processor Status file Refer to Appendix D for more information on program synchronization To change the operational mode click on the Operational Mode box and choose the mode you would like to use The default mode is Asynchronous Equivalence Checks You can perform equivalence checking to verify that selected areas in both the
22. system is in an Invalid backup state refer to Appendix B for more information on backup states a description of the problem is displayed Refer to chapter 4 for information on corrective actions you can take Maximum Pscan Information This information is applicable for Synchronous mode operation only The following parameters are listed in this section e Configured Scan the Maximum Program Scan Time e Adjusted Scan the Maximum Program Scan Time rounded up to the next integer multiple of the NUT NUT Time ms the parameter configured in RSNetWorx Number of NUTS the number of NUTS in the Adjusted Maximum Program Scan Time Processor Editing Considerations Installing and Configuring Your ControlNet PLC 5 Backup System 3 17 There are some considerations you should be aware of when editing the processor of a ControlNet PLC 5 backup system Editing in this context refers to any changes you make to the program files data table structure force tables and status file Edits that you make to one processor are not automatically transferred to the other processor Thus if you wish for edits to apply to both processors you must take the steps to make that happen Most simply you can ensure the changes are made to both processors by manually making those changes yourself If your edits are small this might be the fastest and easiest solution However if you have made large amounts of editing changes to one processor it ma
23. the ControINet producer consumer architecture allows for input data to be broadcast to and shared by both processors There is no special wiring required to implement ControINet PLC 5 backup system as opposed to a standalone system other than connecting the second processor onto the ControINet network e The ControlNet PLC 5 backup system offers a simple mechanism to crossload data The BCM backup approach requires complicated block transfer application programming in order to crossload data In terms of how data is provided to the two PLC 5 systems similar to the BCM system the ControINet PLC 5 backup system does automatically present the ControINet input data both discrete and analog to both PLC 5 processors Unlike the BCM however the ControINet PLC 5 backup system does NOT provide the remote output data discrete and analog to both processors The secondary processor in the ControINet PLC 5 backup system system generates its own output data based upon internal program execution Should you wish to do so you can develop and implement message instructions to crossload output data from one PLC 5 processor to the other Publication 1785 6 5 24 February 1999 F 2 Comparison to the 1785 BCM System Publication 1785 6 5 24 February 1999 Another difference in the two backup systems is that the ControINet backup system does NOT provide a Customer Relay Because of the system architecture it is possible with the ControINet backup sy
24. the next housekeeping Even when the processor are resynchronized the Sync LED remains solid red until you clear the Maximum Program Scan Time Exceed Counter Should frequent program scan overruns occur it may be necessary for you to increase the Maximum Program Scan Time parameter The Maximum Program Scan Time parameter can be changed on the fly to the primary processor while the processor is in RUN mode Both processors will automatically begin using the new Adjusted Maximum Program Scan Time parameter Publication 1785 6 5 24 February 1999 D 4 Program Synchronization Publication 1785 6 5 24 February 1999 Chapter Objectives Redundancy Considerations Switchover Considerations Appendix E Application Guidelines This Appendix will provide you with application examples as well as information on other items to consider while operating your ControINet PLC 5 hot backup system The PLC 5 system for redundancy is designed to allow a secondary PLC processor to take over I O and system control from a primary PLC processor which has become disabled The main goal in designing a redundant PLC system is to ensure that the secondary processor executes as closely as possible to the primary system That way when control is transferred from the primary to the secondary the transfer is seamless or bumpless meaning that the outputs of the system are maintained in the same state after switchover occurs When the systems produce radi
25. this selection for both processors and they must be in Program mode Synchronous and Asynchronous modes provide you with the opportunity to choose synchronous or asynchronous program scanning for your backup system Equivalence Checking when enabled equivalence checking is the performance of verification checks to ensure the qualifying secondary matches the primary The current equivalence status of the two processors is displayed Note If Equivalence checking is enabled during qualification and differences are found a major fault will occur Crossloading allows you to perform an on demand transfer of data files from the primary to the secondary processor Forced Switchover allows you to force the primary processor to secondary and vice versa on demand This option is available while both PLC processors are in Run mode To force a switchover simply click on the Force Switchover button on the Configure tab of the ControINet Hot Backup screen Status provides you with informational messages and parameter settings Installing and Configuring Your ControlNet PLC 5 Backup System 3 13 Synchronous and Asynchronous Program Scanning One of the most important considerations when implementing a backup system is the effect of divergence on the system Divergence occurs when the primary and secondary controllers are running their applications and scanning the I O asynchronously to each other This mode of operation can cause a cond
26. time has exceeded the parameter too small value into the clear diagnostics counters adjusted maximum program scan time i Spike in program scan e word 32 the ETAT parameter While the out of sync condition may time possibly due to online onfiguration and Status file have been temporary this LED pero editing Increase Maximum Program Scan Time illuminated to indicate that an out of sync configuration parameter word 14 of the condition has occurred ControlNet Backup Configuration and Status file Off The system is operating in Asynchronous mode Normal operation No action required Publication 1785 6 5 24 February 1999 Troubleshooting the Invalid Backup State Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System 4 3 The Invalid Backup state is indicated when both the PRI and SEC LEDs are red The first thing to check is that you have created the ControINet Backup Configuration and Status file and that the file number of this file is placed into the processor status file word S 67 This file must be an Integer file file type N and must be exactly 200 words in length The ControINet Backup Configuration and Status file contains a diagnostic word word 5 that indicates the reason for the Invalid backup state The following table lists the various Invalid backup state reason codes and suggested corrective action If you see reason code Which indicates this condition 0 Valid backup state
27. your system is properly configured the PRI and SEC LEDs on the first processor s backup cartridge are off Save the configuration This completes the backup configuration for the first processor Installing and Configuring Your ControlNet PLC 5 Backup System 3 7 Create and Download the Project for the Second PLC Processor The next step in configuring your system is to duplicate the fully configured project from the first processor and apply it to the second processor Important You must keep the ControlNet configuration you create for the second processor since it is not completely identical to that of the first processor 1 In RSLogix 5 open the project associated with the first processor offline From the File menu choose Save As and save the project under a new name to be associated with the second processor From the Comms menu choose System Comms and change the processor node value from the current standalone processor to the other processor of the odd even pair e g if the standalone processor was processor 1 change the value from 1 to 2 From the Comms menu choose Download to download the project to the new processor When prompted to decide whether you wish to keep the existing ControlNet configuration choose Yes Note This is not the default option Go online with the new processor From the File menu choose Save to save the project The QUAL LED on both processors should now be yellow and you
28. Backup State section later state Improper ControlNet in this chapter Backup Integer file Off This processor is not the secondary i e system Normal operation No action required is in the No Control or Primary backup state QUAL Green The system has both a primary and a secondary Normal operation No action required processor which are communicating properly with each other the secondary processor is qualified Yellow The system has both a primary and a secondary Normal operation No action required processor which are communicating properly with each other but the secondary is not yet qualified Alternating yellow Qualification active Normal operation No action required and green Off The primary and secondary processors are not Standalone processor Verify that the connection communicating properly with each other One or both processors are parameters words 0 2 of the in the Invalid backup state ControlNet Backup Integer file are the same for both processors e Improper backup configuration parameters SYNC Green The system is operating in synchronous mode Normal operation No action required and this processor has never exceeded the adjusted maximum program scan time parameter Red The system is operating in synchronous mode e Maximum Program Scan Clear the Maximum Program Scan and this processor has been out of sync i e its Time configuration Exceeded counter by writing a non zero actual program scan
29. LC 5 ControlNet backup system each processor has its own data table and values are not automatically exchanged between the PLC 5 processors During operation each processor simultaneously receives the same set of input data executes its program logic and places program logic results in its own data table Over time the data table values may diverge between the primary processor and the secondary processor due to such things as internal timer differences or asynchronous events such as CIO instruction completion Once backup system qualification is completed there is no automatic data table crossloading from the primary processor to the secondary processor in the default PLC 5 ControlNet backup system However there may be applications where it is highly desirable to be able to easily and automatically crossload data table data from the primary processor to the secondary processor To meet this need there is a feature called On Demand data table crossloading that greatly simplifies the transfer of data table information from the primary processor to corresponding data table locations on the secondary processor An On Demand data table crossload transfers data table data from the primary processor to the secondary processor To set up On Demand data table crossload operations you must load configuration information identifying the files to be crossloaded Then to trigger an On Demand data table crossload you must enter a non zero value int
30. Maximum Program Scan Time word i e less than or equal to 128 NUT into word 13 of the ControlNet Backup Configuration and Status file 11 Handshake Requested Packet Interval RPI invalid Make the handshake connection s RPI in the I O map table at least one NUT but less than 2 NUTs 12 Crossload file number parameters invalid Enter valid file numbers 0 999 into words 55 through 58 of the ControlNet Backup Configuration and Status file Make sure the crossload range low word word 57 value is less than or equal to the crossload range high word word 58 value 13 ControlNet NUT not established Until the processor is attached to the ControlNet channel the NUT is unknown Attach the processor to the ControlNet channel Publication 1785 6 5 24 February 1999 4 4 Major Faults Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System Troubleshooting Qualification When a qualification major fault occurs S 12 234 the ControINet Backup Configuration and Status file contains a diagnostic word word 46 that indicates the reason why the qualification major fault occurred The following table lists the various qualification major fault reason codes and the suggested corrective action If you see reason code Which indicates this condition Take this corrective action 0 Qualification successful
31. T is 5ms the Primary Timeout is 20ms If the NUT is 10ms the Primary Timeout is 35ms The Primary Timeout is not the only factor in the Timeout Switchover Time There is also processing which must occur on the secondary system after a Primary Timeout occurs This processing can take up to 5ms The formula for the Timeout Switchover Time is Timeout Switchover Time Primary Timeout 5ms So if the NUT is 5ms the Timeout Switchover Time is equal to 25ms plus 5ms or 30ms Publication 1785 6 5 24 February 1999 B 16 Backup States Publication 1785 6 5 24 February 1999 Chapter Objectives Data Table Crossloading Appendix C Data Table Crossloading This appendix provides you with reference information on the data table crossloading feature Data table crossloading is a feature you can enable to minimize the bump in system outputs when a processor switchover occurs This feature is most useful when identical PLC 5 processors are used in the backup system To minimize a bump in system outputs it is often important for the secondary processor s data table values to closely match the primary processor s data table values This is true in control applications where output values are dependent upon other data table variables If the data table values between the processors are different there may be a bump in the system outputs when the secondary processor takes over from the primary processor after a switchover In the P
32. an the primary the secondary data table may diverge from the primary since its instruction is behind the primary When Should the Information Be Transferred The primary data table is transferred at power up Then selected state variables are transferred again to account for transfer delays in updating the secondary If nothing else occurs the primary and secondary operate independently There are some opportunities however for the processors to diverge over time For instance timers in both systems run off of different system clocks Over time these clocks may drift apart causing the timer values to diverge You should periodically update Timers setting the appropriate transfer bit in the transfer register You should update as necessary other variables not accounted for by the transfer register via a message read instruction in the secondary program How Often Should the Information Be Transferred Since timers may diverge with time you should periodically refresh them thereby synchronizing the secondary with the primary Since ControlNet bandwidth is important it is probably adequate for you to complete this refresh on a daily or weekly basis A PLC program should not simply continue to set the transfer bits to cause continuous updating after the secondary has completed a transfer We recommend that you set up a daily or weekly counter that occasionally toggles the transfer bit Publication 1785 6 5 24 February 1999 E 4 Appl
33. and choose ControlNet Configuration Right click on the odd node Node 1 in this example and choose Insert Receive Scheduled Message The Receive Scheduled Message dialog appears The Node Number field is already filled in for you This number indicates the node number from which you will receive the Receive scheduled message In your ControlNet backup system the odd node will receive the message from the even node and vice versa Repeat steps 2 through 4 creating a Receive Scheduled Message for the even node Record the Send and Receive message numbers from the odd processor node below Send message number Receive message number You will use these numbers later in the configuration process Reconfigure ControlNet I O on the Second PLC Processor Reconfigure all ControlNet I O adapters and modules that will be in your ControlNet PLC 5 backup system by changing their ControlNet connection from Exclusive Owner default to Redundant 1 2 Launch RSNetWorx for ControlNet Check the Edits Enabled checkbox on the toolbar Right click on the second PLC 5 processor the even node and choose ControlNet Configuration The ControlNet Configuration screen appears See page 8 For each entry under the Connection Type column double click on Exclusive Owner choose Redundant from the pull down menu and press Enter From the File menu choose Save to save the ControlNet configuration Installing and Configuring Your Con
34. backup state 14 Qualification failed due to partner no longer being a primary e 15 Qualification failed due to invalid backup configuration parameters 16 unused 17 Qualification crossload failed 18 Qualification failed due to unavailable edit resource 41 Lost Partner Counter A counter which increments every time you lose communication with the partner processor 48 Maximum Program Scan Exceed Counter A counter which increments every time the maximum program scan time is exceeded This counter is reset for the processor on transition into Run mode 49 Equivalence Check Error A bit is set for each area in which an equivalence mismatch is detected There is a background check of the ladder program force tables and status files for differences Bit 0 Set if the ladder programs between the two systems are different it 1 Set if the data table structures between the two systems are fferent Note the data table structure is not the same as the values in the ata table files it 2 Set if the I O map tables between the two systems are different it 3 Set if the Backup Configuration and Status files between the two ystems are different it 4 Set if the Force tables between the two systems are different it 5 Set if the Status files between the two systems are different vuv g2 uv wn ww Publication 1785 6 5 24 February 1999 Monitoring and Troubleshooting You
35. cally different outputs based on different data table variables divergence occurs When divergence occurs outputs may change state when control is transferred from primary to secondary To minimize divergence state information must be transferred from the primary processor to the secondary processor Much if not all of the information transfer between the primary and secondary processors can be performed automatically by the secondary processor Depending on the design of the PLC application program additional information may have to be exchanged by the application program in order for the secondary system to be in the same state as the primary You can accomplish this information exchange if necessary simply by adding a PLC 5 message instruction in the secondary system The following sections provide information on factors you should keep in mind when performing a switchover Why Transfer Information When the primary PLC processor is operating system outputs are a function of current and prior I O events Outputs may be in the present state because a current input condition requires a certain output state If the secondary system comes online and senses the input condition it will place its output in the same state Ifa switchover occurs so that the secondary becomes primary system control switches over seamlessly because the new primary maintains the output in the present or current state Publication 1785 6 5 24 February 1999
36. ce checking for the Data Table structure area If for some reason the Qualification Data Table crossload fails qualification also fails and a major fault is declared for the qualifying system Refer to Chapter 4 for descriptions of specific major fault codes Transition to Run mode Once the complete Data Table crossload is complete the qualifying PLC 5 system transitions into Run mode Although the PLC 5 system is now in Run mode the PLC 5 processor is not through with qualification and is still in the No Control backup state Also note that any outputs in the qualifying processor that are not ControlNet redundant connections are now controlled by the PLC 5 processor This includes any local resident chassis outputs remote I O channel outputs and non redundant I O connections on the ControINet channel State data table crossload Even though a Qualification Data Table crossload has occurred some of the crossloaded data may have become stale For example if the Qualification Data Table crossload takes 10 seconds the data in the original data table file that was transferred is 10 seconds old In order to bring certain state information in the data table up to date a Qualification State Data Table crossload is performed Backup States B 11 The Qualification State Data Table crossload reads data table values from the primary PLC 5 system and writes these values to the qualifying PLC 5 system The State Data Table crossload only
37. cessors in a ControlNet PLC 5 backup system execute their own program logic You can configure the ControlNet PLC 5 backup system to have either Asynchronous program scans or Synchronous program scans Asynchronous mode allows the program scans on the two processors to run as if they were stand alone processors When a program scan on a processor is finished housekeeping is performed and the next program scan is immediately started The program scan on one processor is completely independent of the program scan on the other processor Synchronous mode provides both program scan synchronization as well as housekeeping synchronization When a program scan on a processor is finished housekeeping is delayed until a synchronization point is reached This synchronization point is the same for both processors Housekeeping is then performed at the same time on both processors By having housekeeping performed at the same time both processors should be updating the Input Image Table with the same input values When housekeeping is finished the program scans then immediately start and the cycle repeats itself Synchronous mode allows the inputs used by the two backup processors to closely match each other as well as forcing each program scan to begin at the same time Synchronous mode offers only one synchronization point per program scan After the synchronization point is passed the two control programs run asynchronously until the next synchronizat
38. d in order to prevent the qualifying system from major faulting or going into an odd state due to uninitialized data table values It is safer for the qualifying PLC 5 system to first do the Data Table crossload and then to go into Run mode In that case the data table values are close to the values on the currently executing primary system Note The time it takes to do the Qualification Data Table crossload primarily depends on the amount of data table data to be crossloaded Publication 1785 6 5 24 February 1999 B 10 Backup States Publication 1785 6 5 24 February 1999 All elements of all data table files are crossloaded in the Qualification Data Table crossload with the exception of the following files These files cannot be crossloaded because they contain processor specific configuration and status information Status File ControlNet Backup Configuration and Status File ControlNet Data Input File DIF ControlNet Data Output File DOF ControlNet Configuration File ControlNet I O Status File ControlNet Diagnostic File Though the complete Status File is not crossloaded there are six words in this file that are transferred from the primary system to the qualifying system These six words are the real time clock The Qualification Data Table crossload does not occur if the Data Table Structures are not the same If you want to ensure that a Qualification Data Table crossload occurs you must enable equivalen
39. de during qualification Inability to retrieve the Edit Resource at the beginning of qualification e Presence of one or more invalid backup configuration parameters e Achange in the primary status of the partner PLC 5 processor i e either the partner PLC 5 processor became primary during qualification or the partner PLC 5 went from primary to non primary during qualification e The ControlNet backup state was Invalid backup state Refer to Chapter 4 Troubleshooting for information on fixing a Qualification major fault Switchover Switchover occurs when one of the processors of the PLC 5 ControlNet backup system transitions from the Secondary backup state to the Primary backup state The new primary processor gains control of the system outputs on the ControlNet channel the old primary processor loses control There are two categories for switchovers e Qualified Switchovers e Unqualified Switchovers Qualified Switchovers Qualified Switchovers are switchovers that transition the primary processor to the Secondary backup state and the secondary processor to the Primary backup state Thus after a Qualified Switchover there is still a qualified backup system There are 2 Qualified Switchover cases e Designated Primary When you configure the PLC 5 ControlNet backup system and enable the Designated Primary feature the odd ControlNet node of the odd even ControlNet pair is always the primary processor if the odd node
40. ded earlier e Receive Message Enter the message number of the Receive Scheduled Message from the odd node address Refer to the number you recorded earlier If your system is properly configured the PRI and SEC LEDs on the first processor s backup cartridge are off Publication 1785 6 5 24 February 1999 3 12 Installing and Configuring Your ControlNet PLC 5 Backup System Advanced Configuration Options Publication 1785 6 5 24 February 1999 9 10 Save the configuration Repeat steps 1 through 9 for the second processor saving the configuration under a different name The QUAL LED on both processors should now be yellow and you have a fully qualified backup system If desired you can now go to Run mode The procedures in the previous sections outlined the steps required to configure a basic ControlNet PLC 5 backup system In addition there are other options you can configure for the backup system In addition to the information provided here you can find specific details on these features in the appendices of this manual Designated Primary allows you to force the processor at the odd node address to always be the primary PLC processor as long as that processor is in Run mode and is qualified You can select the designated primary option from the Configuration tab of the ControlNet Hot Backup screen in RSLogix 5 Simply choose the Odd PLC Node from the Designated Primary pull down menu Note You must make
41. e primary PLC 5 processor to accept the new configuration parameters After the PLC 5 processor has done so it will zero this word This command is only in effect for the primary processor The configuration parameters you change are Operational mode Maximum Program scan time Equivalence checks Designated primary Crossload parameters 31 Force Switchover A non zero value written into this location forces the primary processor to switch over control to a secondary processor After the processor has read the non zero value the PLC 5 processor will zero this word This command works for both the primary and secondary processors However if there is a Designated Primary this command will not function 32 Clear Diagnostic Counters A non zero value written into this location clears the maximum program scan exceed counter the lost partner counter and the lonely primary backup state counter After the processor has read the non zero value it will clear this word This feature works for both the primary and secondary processors but will only work in Run mode Publication 1785 6 5 24 February 1999 4 8 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System Word 33 Definition Perform On Demand Crossload You can specify whether to crossload timers counters PID files or user defined files configured in words 55 56 57 and 58 of the ControlNet Backup Configuration and Status file by setting a
42. each PLC 5 processor Note that the power must be OFF on the processor before you do this Important If the ControlNet backup cartridge is not inserted into the PLC 5 processor that processor will operate as a normal standalone processor and will not exhibit any of the necessary backup functions Install a power supply for each chassis and connect to ac power Wire the ControlNet network to the PLC 5 processors and to the ControlNet I O adapters being used for the backup system The network cabling may consist of single or redundant channels Important In non redundant media applications place your two PLC 5 processors as the 2 nodes closest to a terminator on a ControlNet segment This eliminates the possibility for a malfunctioning cable between the processors to allow each processor to control a subset of the I O 6 Basic installation is now complete Set the keyswitch to Program mode on each processor and apply power to the processors Publication 1785 6 5 24 February 1999 3 2 Installing and Configuring Your ControlNet PLC 5 Backup System Configuring Your Backup System Publication 1785 6 5 24 February 1999 Before you begin make sure that you have installed RSLinx RSLogix5 and RSNetWorx for ControlNet software For assistance with installing any of these packages refer to their respective installation documentation There are two basic configuration paths Select the appropriate path based upon the type of bac
43. ed upon standard 1771 and 1785 selection and installation criteria Note Though we do not recommend it it is possible for you to use a mixed set of processors as a backup pair e g one PLC 5 40 and one PLC 5 80 two 1785 CHBM A ControlNet backup cartridges one for each PLC 5 processor e two 1771 chassis one for each PLC 5 processor e two 1771 power supplies one for each chassis You can elect to use redundant power supplies within a chassis if you wish We do not recommend the use of I O within the chassis since provisions for backing up the local I O are not provided e one or more ControlNet I O adapters e ControlNet network cables taps and terminators for making connections between the PLC 5 processors and the I O adapters e aPC with a 1784 KTCX15 card or a laptop computer with a 1784 PCC card e other ControlNet devices including HMI optional Software Components The basic ControlNet PLC 5 backup system includes the following software components e RSLogix 5 programming software Release 3 21 or later e RSNetWorx for ControlNet software Release 1 08 or later e RSLinx gateway communication software Release 2 00 97 30 or later Publication 1785 6 5 24 February 1999 2 2 Understanding the ControlNet PLC 5 Backup System Components ControlNet Backup Cartridge Publication 1785 6 5 24 February 1999 Each ControlNet PLC 5 processor requires a 1785 CHBM A ControlNet backup cartridge inserted into t
44. elect a sing e file number written in this word to be crossloaded during the Qualification crossload and on demand when setting the appropriate bit in word 33 57 User Defined Crossload Range Low File You can select a range of files to be crossloaded during the Qualification crossload and on demand when setting the appropriate bit in word 33 The lower file number of the range of files to be crossloaded must be written into this register 58 User Defined Crossload Range High File You can select a range of files to be crossloaded during the Qualification crossload and on demand when setting the appropriate bit in word 33 The higher file number of the range of files to be crossloaded must be written into this register 59 64 The secondary time date stamp of when the processor last took over as Secondary processor The format of the date is the same as the system clock in the status file 65 68 These words are functionally the same as words 55 through 58 The difference is that these words display the current PLC 5 processor state of these configuration parameters When in Run mode the processor continuously updates words 65 through 68 In other words new configuration parameters are written into words 55 through 58 while the PLC 5 processor writes its internal state of these configuration parameters into words 65 through 68 When you accept a configuration the configuration parameters in word
45. er default to Redundant 1 2 Launch RSNetWorx for ControlNet Check the Edits Enabled checkbox on the toolbar Right click on the first PLC 5 processor the odd node and choose ControlNet Configuration The ControlNet Configuration screen appears Gre Pras Pm SepapePeliege 1G perep EEE E D bisp teeny Lege ETE ED TmrTumanFie lime DOMINO BOT Dame himi Dame TS rr sd Corre Emmi Emre ae Lasik gaaces Pla P Pasiya fi ftw T Tw Us Dwgawcaadee rs Pau irai Fi a E Dukan ris Sue EE alu E l xL Ter Help pera Dieii es Habi MeeR For each entry under the Connection Type column double click on Exclusive Owner choose Redundant from the pull down menu and press Enter Installing and Configuring Your ControlNet PLC 5 Backup System 3 9 Configure Handshaking Messages With RSNetWorx Within your backup system you must use RSNetWorx to set up the send and receive scheduled messages that allow handshaking to occur between the two ControlNet PLC 5 processors that comprise your backup system For each of the processors comprising a backup system you must create two scheduled peer to peer messages one Send and one Receive These messages must be exactly five words in length From the ControINet Configuration screen for the first processor follow these steps 1 Rightclick on the even node Node 2 in this example and choose Insert Receive Scheduled Message The Receive Scheduled Message dialog appea
46. er only to direct access to the ControINet Backup Configuration and Status file though we recommend performing the same operation via the Hot Backup utility whenever possible The PLC 5 processor stores major fault codes in word 12 of the processor status file S 12 The following table lists new major fault codes specific to the ControINet Hot Backup processor and the suggested corrective action for each If you see fault code Which indicates this fault Take this corrective action 230 System attempted transition to Run mode with processor Change from the Invalid backup state to the No Control backup in Invalid backup state state before transitioning into Run mode Refer to the Invalid backup state troubleshooting table later in this chapter 231 Bypassed qualification may occur during race condition Transition the PLC 5 processors into Run mode one at a time when both processors attempt to go into Run mode at the same time 232 Both processors attempted to be primaries Check all media for broken cables loose connectors missing terminators etc 233 ControlNet configuration invalid on transition into Run Reconfigure the ControlNet channel mode 234 Failed Qualification Refer to the qualification major faults troubleshooting table later in this chapter ATTENTION The processor does not invoke the fault routine for any ofthe new fault codes for the ControINet PLC 5 backup system since they are non recoverable faults
47. erred E 2 When Should the Information Be Transferred E 3 How Often Should the Information Be Transferred E 3 Performance Considerations eee E 4 Comparison to the 1785 BCM System Chapter Objectives usto pores ee rene He aea een o esa ee e e eR 0d F 1 Comparison to the BCM System eese F 1 Chapter Objectives Why Use a Backup System Chapter 1 Backup Concepts for the ControlNet PLC 5 Backup System This chapter describes concepts for using a backup system with your programmable controller In particular this chapter describes the use of the ControlNet PLC 5 backup system including its basic system architecture The objective of any redundant system i e backup system is to improve the amount of up time of a machine or process by ensuring consistent availability of that machine thereby reducing costs associated with equipment failure By using this backup system you can help guard your application against shutdowns caused by the programmable controller ATTENTION When using identical programs in both PLC 5 processors using a backup system does not necessarily protect you from faults caused by programming errors or system timeouts Such errors or timeouts can also occur in the secondary processor Be certain to carefully check your programming and to thoroughly check redundant operations before implementing the backup system The back
48. essfully completed the secondary system transitions into the Secondary backup state and qualification is complete The LED s on the 1785 CHBM cartridge indicate the new backup state Also the Qualified LED on the primary system turns solid green indicating that there is a qualified secondary system If you selected the Designated Primary feature and the odd node of the odd even backup pair has just gone through secondary qualification a switchover automatically occurs The odd node becomes the primary system and the even node transitions from the primary system to the secondary system The even node s transition from primary to secondary happens immediately The even node does not go through qualification when it becomes the secondary system Publication 1785 6 5 24 February 1999 B 12 Backup States Publication 1785 6 5 24 February 1999 Reasons for Qualification Major Fault While qualification should complete without any problems there are several checks performed during qualification that can cause it to fail When the qualification procedure fails a major fault is declared Qualification could fail under any of the following circumstances or conditions e Failure of the Qualification Data Table crossload e Failure of the Qualification State Data Table crossload e Failure of the Equivalence Check e The occurrence of an unrelated major fault in the PLC 5 system during qualification e Movement of the keyswitch to Program mo
49. ght 1999 of Rockwell International Corporation Printed in USA
50. has passed qualification This feature is useful when you want a particular processor to always be the primary whenever that processor is available Backup States B 13 If the even ControlNet node is the only processor to pass qualification it is the primary processor However should the odd ControlNet node pass qualification a switchover immediately occurs the odd ControlNet node becomes the primary processor and the even ControlNet node becomes the secondary processor Once there is a qualified primary processor you cannot change i e enable or disable the Designated Primary feature The first processor that goes through qualification determined whether the Designated Primary feature is enabled or disabled The second processor that goes through qualification inherits the configuration setting from the first processor In order to enable or disable the Designated Primary feature for a PLC 5 ControlNet backup system both processors must be in Program mode You can then change the Designated Primary feature on one of the processors You should then qualify the processor on which you have changed this feature Forced Switchover Forced Switchover allows you to switch over a qualified PLC 5 ControlNet backup system at any time You activate a Forced Switchover by writing a non zero value into the Forced Switchover word word 31 of the Backup Integer File Once the Forced Switchover is activated the processor writes a zero into the
51. have a fully qualified backup system If desired you can now go to Run mode Configuring With Differing Applications This section assumes that you intend for the secondary controller in your backup system to run a different application than the primary you have already developed separate control applications for the primary and secondary processors the control applications are loaded onto their respective processors both processors are powered on are in Program mode and are physically connected to the ControlNet network you have not yet configured these processors to function within a backup system Publication 1785 6 5 24 February 1999 3 8 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 To create and configure your backup system under these circumstances complete the following steps wm de wc Reconfigure ControlNet I O on the first processor Configure handshaking messages between both processors Reconfigure ControINet I O on the second processor Save the ControlNet configuration Configure the hot backup parameters on the first processor and save the project Configure the hot backup parameters on the second processor and save the project Reconfigure ControlNet I O on the First PLC Processor Reconfigure all ControlNet I O adapters and modules that will be in your ControlNet PLC 5 backup system by changing their ControlNet connection from Exclusive Own
52. he PLC 5 EEPROM memory cartridge slot to enable backup functionality The ControlNet backup cartridge contains EEPROM memory cartridge functionality i e the cartridge can also be used as a standard PLC 5 EEPROM memory storage cartridge for the PLC 5 processor with up to 100K of memory Important The 1785 CHBM ControlNet backup cartridge cannot be used with non backup PLC 5 processors Chapter Objectives Installing the Hardware Chapter 3 Installing and Configuring Your ControlNet PLC 5 Backup System This chapter outlines the steps you must perform to install the backup system components and to subsequently configure them to create a functioning backup system Before you begin be sure that you have all of the required hardware components as listed in Chapter 2 Follow these steps to install the required hardware for your backup system 1 Set the ControlNet node address number for each of the PLC 5 processors Important The node addresses must be consecutive with the lower number being odd For example a valid node address pair is 1 and 2 You set the ControlNet node address via the rotary switches on the top of each processor You may need to change the ControlNet node address of other devices so that you have two consecutive addresses available on your ControlNet network Install each PLC 5 processor into a separate 1771 chassis 3 Insert the 1785 CHBM ControlNet backup cartridge into the EEPROM slot of
53. ication Guidelines Publication 1785 6 5 24 February 1999 Performance Considerations One approach to redundant system design is to transfer as much of the primary data table to the secondary as possible and as frequently as possible This approach is not required and actually lowers the overall performance of the system First ControlNet bandwidth is lowered because much more unscheduled message traffic is used to transfer data Secondly because of transfer delays in getting information to the secondary many instructions are updated with stale primary information when the secondary is in fact perfectly synchronized with the primary For example PID instructions are updated at power up of the secondary so that the secondary PID output variable quickly catches up with the primary output variable The next time the PID is executed by the primary and secondary both PLC processors calculate the next output based on the current value of the input variable which both PLC processors acquire from ControINet at the same time Since both PID outputs are a function of the same input conditions both PLC processors produce the same outputs independently There is no need to transfer PID variables after the initial transfers on power up Most variables in a PLC system can be traced to some input condition Once the secondary is refreshed after power up the secondary tracks the primary because the secondary executes upon the same input conditions a
54. ion point during the next housekeeping When the ControlNet backup system is configured in Asynchronous mode the Sync LED is off When the ControlNet backup system is configured in Synchronous mode the Sync LED is either solid green or solid red Publication 1785 6 5 24 February 1999 D 2 Program Synchronization Publication 1785 6 5 24 February 1999 Determining Which Mode to Use Determining whether to select Asynchronous mode or Synchronous mode depends on your application If the program logic is completely different between the two processors it is appropriate to select Asynchronous mode Also if the program scan time frequently bumps out from a small value to a very large value so that the configured Maximum Program Scan Time is too large for the application it would be appropriate to select Asynchronous mode On the other hand if the program logic between the two processors is identical or very similar and if the configured Maximum Program Scan Time is small enough for the application it is advantageous to select Synchronous mode Synchronous mode minimizes data table divergence between the two processors resulting in bumpless switchovers Using Synchronous Mode There are two considerations to keep in mind when using synchronous mode First synchronous mode requires you to determine the Maximum Program Scan Time There is no formula to determine the maximum program scan time for a particular program you must determi
55. it is not set no check is performed By default all equivalence checking is enabled The remaining 10 bits in the word must be set to 0 Bit 0 Ladder Logic equivalence check Bit1 Data Table Structure equivalence check Bit 2 I O Map Table equivalence check Bit 3 Backup Configuration and Status file equivalence check Bit 4 Force Table equivalence check Bit5 Status file equivalence check 12 Designated Primary Valid values are 0 No Designated Primary default 1 The PLC 5 processor with the odd node address is the Designated Primary 13 Qualification Delay This is the amount of time in ms to delay the secondary in Run mode before becoming qualified The default value is 0 14 Maximum Program Scan Time Synchronous mode only the amount of time in ms for the largest program scan This value cannot be greater than 127 times the NUT value Publication 1785 6 5 24 February 1999 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System 4 7 Word 15 19 Definition reserved 20 24 These words are functionally the same as words 10 through 14 The difference is that words 20 through 24 display the current internal PLC 5 processor state of these configuration parameters When in Run mode the PLC 5 processor will continuously update words 20 through 24 In other words the software tool will write the configuration parameters into words 10 through 14 while the PLC 5
56. ition where one of the controllers is several program and I O scans ahead of or behind the other Because of this condition the logic in each controller could resolve differently thus creating differences i e divergence in the I O and data tables As divergence between the primary and secondary controllers increases the possibility of a bump in the process when a switchover occurs also increases This could be critical in some backup applications Asynchronous program scanning allows both the primary and secondary controllers to operate as fast as they possibly can without attempting to synchronize with each other This mode of operation should be used when the divergence of programs I O tables and data tables is not a critical consideration Asynchronous program scanning has no effect on program scan time You should select this mode of operation when the primary is programmed to run the normal application and the secondary is programmed to perform a different task e g a safety shutdown a clean and wash operation etc Synchronous program scanning forces the primary and secondary controllers to synchronize their program and I O scanning Both controllers start their program scan at the same time and both gather input data at the same time This mode of operation should be used when minimizing the divergence of programs I O tables and data tables is a critical and necessary consideration Synchronous program scanning impacts
57. kup system you are creating e If you are creating a backup system with identical or nearly identical control applications in the primary and secondary controllers complete the steps in the section of this chapter entitled Configuring With a Single Control Application e If you are creating a backup system where the secondary controller is running a different application than the primary complete the steps in the section of this chapter entitled Configuring With Different Applications Configuring With a Single Control Application This section assumes that you have already developed your control application and have loaded it onto a single ControlNet PLC 5 processor i e a non backup system Throughout this section we will refer to this processor as the first processor Furthermore we assume that you have a second processor installed powered on and in its default state Both processors must be in Program mode and must be physically connected to your ControINet network To create and configure your backup system under these circumstances complete the following steps Reconfigure ControlNet I O on the first processor Configure handshaking messages between both processors Configure ControlNet I O on the second processor Save the ControlNet configuration Pee Ne Configure the hot backup parameters on the first processor and save the project 6 Create and download the project for the second processor and sa
58. le the secondary acquires the past state information Application Guidelines E 3 Other state variables include the control registers used in FAL Diagnostic Sequencing FSC FIFO and Fill instructions The control registers are stored in file type R e g R6 0 All of these variables are transferred upon power up of the secondary PLC Many of these instructions operate in All mode In other words the instruction begins and completes within a program scan and the instruction control register is armed for reset on the next enable condition All mode execution of instructions typically does not raise different state issues between primary and secondary because both programs begin and execute the instruction to completion upon the enabling event Therefore the instructions are synchronized to produce the same outcome Many of the above instructions can also operate in incremental mode In other words each time the instruction is enabled the control register counter is incremented Instruction completion depends either on the instruction reaching the end of file condition or upon satisfying the instruction s purpose e g a File Search and Compare finds a matching word and stops Any instruction that takes several program scans for completion may be a candidate for transfer to the secondary because past event information is recorded in the control register If the secondary begins execution with the control register at a different point th
59. les are downloaded into your processors On Demand Data Table Crossloads It may be necessary for you to crossload data table data after the backup system has a qualified secondary processor For example the Timer Accumulators may have diverged between the primary and secondary processor over time Or you may have modified some data table values on the primary processor and would like to copy those values into the secondary processor The On Demand data table crossload only occurs when you initiate it and can be performed only on a qualified backup system i e a backup system in which there is both a primary and secondary processor The On Demand data table crossload transfers specific files and subelements of files from the primary processor to the secondary processor There are 4 different and individually selectable operations that can be performed as part of an On Demand data table crossload Each operation transfers a different part of the data table as shown below Data Table Crossloading C 3 Timer Accumulators When Timer Accumulators are crossloaded during the On Demand data table crossload only the Accumulator subelements of the Timer structures are crossloaded Crossloading only the Accumulator subelements of the Timer structures allows the secondary processor to match the Accumulator values in the primary processor without corrupting the control bit subelements of the Timer structures in the secondary processor All fi
60. les of Timer file types are crossloaded i e you cannot crossload a subset of Timer file types Also all file elements of each Timer file are crossloaded i e you cannot crossload a subset of file elements for a particular file Counter Accumulators When Counter Accumulators are crossloaded during the On Demand data table crossload only the Accumulator subelements of the Counter structures are crossloaded Crossloading only the Accumulator subelements of the Counter structures allows the secondary processor to match the Accumulator values in the primary processor without corrupting the control bit subelements of the Counter structures in the secondary processor All files of Counter file types are crossloaded i e you cannot crossload a subset of Counter file types Also all file elements of each Counter file are crossloaded i e you cannot crossload a subset of file elements for a particular file PD Files The entire PD file structure is crossloaded during the On Demand data table crossload from the primary processor to the non primary processor All PD files are crossloaded as well as all elements in the PD files You are not able to crossload a subset of PD file types i e if there are 20 PD data table files all 20 PD data table files will be crossloaded User Selectable Files You can select two individual files and a range of files inclusive to be crossloaded from the primary processor to the non primary process
61. lt occurred on the primary PLC 5 system the primary PLC 5 system failed the primary PLC 5 system lost power problems with the ControlNet network caused the loss of the handshake connection with the primary processor Switchover Considerations Switchovers do not occur without some potential problems Publication 1785 6 5 24 February 1999 Divergence when the data table values diverge between the primary processor and secondary processor If the output values in the data tables are different between the primary and secondary systems there will be a bump in the outputs when the new primary processor takes control of the outputs There are features in the PLC 5 ControlNet backup system which minimize the divergence of outputs between the primary and secondary processors These features are synchronized program scans and data table crossloads Switchover time the time delay before the new primary processor can control the system outputs on the ControlNet channel There is a time period between when the old primary processor has relinquished control of the system outputs on the ControlNet channel and the new primary processor writes new system outputs on the ControlNet channel This time period is called Switchover Time There are two separate cases to consider Note that the Switchover Times described below are the worst case times Actual Switchover Times may be smaller Communicated Switchover when the processor indicates t
62. lue This value must be the same in both PLC 5 processors In the Message Size field enter a value of 5 and click OK The Receive scheduled message is inserted in your ControINet Configuration for the odd node The corresponding Send scheduled message is automatically inserted for the even node From the main RSNetWorx screen right click on the second PLC 5 processor and choose ControlNet Configuration Right click on the odd node Node 1 in this example and choose Insert Receive Scheduled Message The Receive Scheduled Message dialog appears The Node Number field is already filled in for you This number indicates the node number from which you will receive the Receive scheduled message In your ControlNet backup system the odd node will receive the message from the even node and vice versa Repeat steps 2 through 4 creating a Receive Scheduled Message for the even node Installing and Configuring Your ControlNet PLC 5 Backup System 3 5 8 Record the Send and Receive message numbers from the odd processor node below Send message number Receive message number You will use these numbers later in the configuration process Configure ControlNet I O on the Second PLC Processor Configure all ControlNet I O adapters and modules that will be in your backup system and ensure that the ControINet I O mapping and data file assignments on the second processor match those on the first 1 From the ControlNet Configuration scree
63. ly completed No action required 1 Failed Qualification Equivalence check Ladder programs Disable ladder program equivalence check if desired different Make ladder programs identical in each processor 2 Failed Qualification Equivalence check Data Table Disable data table structure equivalence check if desired Structures different Make data table structures identical in each processor 3 Failed Qualification Equivalence check Redundant Disable Redundant Connections in I O Map Table connections in 1 0 Map Tables different equivalence check if desired Make redundant connections identical in each processor 4 Failed Qualification Equivalence check ControlNet Hot Disable ControlNet Hot Backup file connection parameters Backup file connection parameters different equivalence check if desired Make ControlNet Hot Backup file connection parameters identical in each processor 5 Failed Qualification Equivalence check Force Tables Disable Force Tables equivalence check if desired different Make Force Tables identical in each processor 6 Failed Qualification Equivalence check Configuration Disable processor status file equivalence check if desired parameters in processor status file different Make processor status file configuration parameters identical in each processor 8 Processor major faulted during qualification Fix the reason for the major fault Refer to 5 12 for major fault Codes 9 Keyswitch changed to Program
64. m and are passed from the primary system to the qualifying system before equivalence checking is performed If you enable configuration checking for a particular area and the primary checksum is different than the qualifying checksum qualification fails and the qualifying system declares a major fault There are 6 different areas in which equivalence checking can be performed Program File Structure and Program Files This checksum is calculated for all the Program files with the notable exception of SFC files This checksum continues to be calculated when the backup system is qualified This allows status to be available regarding whether the Program file checksums differ for a qualified backup system Data Table Structure This checksum is only calculated when the PLC 5 system goes through qualification Since the Data Table structure cannot change when in Run mode this checksum does not change after qualification The Data Table Structure checksum includes the data table file number the data table file type and the size of the data table file The Data Table Structure checksum does not include the data table file privilege information or the values of the data table file elements ControlNet I O Map Table This checksum is only calculated when the PLC 5 system goes through qualification Since the ControlNet I O map table cannot change when the PLC 5 system is in Run mode this checksum does not change after qualification
65. mber wrong Operation mode word invalid Equivalence mode word invalid Designated Primary word invalid 9 Max Program Scan Time word invalid 11 Handshake is not 1 NUT 12 Crossload parameters invalid 13 NUT not established OOo O Ui 4 UJ hJ rm This is a checksum of the first 3 words of this file If the checksum is not valid the firmware will continuously write default values for the configuration parameters in this file Partner present This word is constantly updated by the PLC 5 processor indicating whether a partner processor is handshaking with the current processor This word is updated only when the processor is in a valid backup state i e No Control Secondary or Primary Valid values include 0 No partner found e 1 Partner PLC 5 handshaking with this PLC 5 Output Ownership Invalid Count word This word indicates how many connections are not owned by this processor Primary backup state only This value is 1 when the processor is in the Secondary backup state Lonely Primary Backup State Counter This counter is incremented every time this processor goes into the Lonely Primary backup state 10 Operational mode of the system Valid values include 0 Asynchronous default 1 Synchronous 11 Equivalence checks there are 6 bits defined i e one bit per equivalence check If a bitis set the corresponding equivalence check will be performed If the b
66. n for the second processor right click on the node corresponding to your I O adapter and choose Auto Module Selected Device All 1794 non discrete I O modules on your ControlNet network are added to your configuration as pending map entries 2 Enter data table file addresses for the Diagnostics Status Configuration Data Input and Data Output files Note that these addresses must be the same for both processors Be careful to enter file numbers which do not conflict with existing data table files 3 Select each adapter and module in the backup system and enter the data table address that matches the address assigned on the first processor 4 From the Network menu choose Save to save the completed ControlNet configuration Configure the Hot Backup Parameters 1 Launch RSLogix 5 2 From the Comms menu choose System Comms The System Options dialog appears with the System Communications tab selected System Options x Preferences System Communications Driver Route Processor Node ect a Caan Ez Current settings AB KTC 1 Node 2d local Last Configured Reply Timeout Upload fio Sec Who Active Online cme Help Publication 1785 6 5 24 February 1999 3 6 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 3 In the Processor Node field enter the node number of the first process
67. n Manual 1786 6 2 1 ControlNet Coax Tap Installation Instruction 1786 2 3 ControlNet Network Access Cable Installation Instructions 1786 2 6 ControlNet Repeater Installation Instructions 1786 2 7 For more information on any of the software components of the ControlNet PLC 5 backup system e g RSLogix 5 RSLinx and RSNetWorx refer to the software documentation and online help for the individual software packages Table of Contents Chapter 1 Backup Concepts for the ControlNet PLC 5 Backup System Chapter ODIECHVES acinus tasti teens oboe funditus 1 1 Why Use a Backup System eese 1 1 Basic System Architecture Lu o Fiet Opi grex NOME REER 1 2 How the Backup System Works eee 1 2 OualifiCdtloHscotossesohtktsddasensd du tavi nace Serb e aesti 1 3 Equivalence Check eer I eae 1 3 B umpless TANS FOL 22599 itene t das oss ated tok 1 4 WDC OVER Laredo i race aan A ESE ESE RI tease 1 4 Chapter 2 Understanding the ControlNet PLC 5 Backup System Components Chapter Objectives si ccsieesessnesasnccedesegeededavennceedateneedcavantes sts 2 1 Hardware Components 55 oocrteet tetro hoe eo oen 2 1 Software Components ceeeeceeececsscecssececseeeeesteeeeaees 2 1 ControlNet Backup Cartridge sese 2 2 Chapter 3 Installing and Configuring Your ControlNet PLC 5 Backup System Chapter Objective S vic uo c ees e 3 1 Installing the Hardware 2 oer direct tede 3 1 Configu
68. n edges B 3 Primary Backup SUM o os etitaee ru ae IE Herode B 4 Lonely Primary Backup State teeeeiteeteese tees B 4 Secondary Backup State eo eee eee editieren B 5 Backup State Transitions hoe eed eo tnde ees B 5 OU ANTEC ats ies asocia ia Io ee EOD debe oM aaa ade B 5 Data Table Crossloading Chapter Objectives 5 cette oe e HN der ite aget PER aS C 1 Data Table Crossloading eene C 1 On Demand Data Table Crossloads C 2 Data Table Crossload Time esses C 7 Data Table Crossload Data Latency C 7 Effect of Data Table Crossloading on the ControlNet Channel Minantasled C 7 Inhibiting Data Table Crossloads C 7 Data Table Crossload Diagnostics C 8 Performing Data Table Crossloads Via Your Applications C Program Synchronization Chapter OBjeetlVes ehir atte etae dae Doer bor ute Pow oc vede D 1 Program Synchronization sese D 1 Determining Which Mode to Use sss D 2 Using Synchronous Mode sere D 2 Application Guidelines Chapter Objectives soc eie RT Ue E 1 Redundancy Considerations i e oes ode eene E 1 Switchover Considerations eese E 1 Why Transfer Information eeeeeeeeeeee E 1 What Information Should Be Transf
69. nabling data table Equivalence checking Publication 1785 6 5 24 February 1999 C 8 Data Table Crossloading Publication 1785 6 5 24 February 1999 Data Table Crossload Diagnostics There are some words reserved in the ControINet Backup Integer File for data table crossload diagnostics First there is a data table crossload active word word 52 in the ControlNet Backup Integer file This word is non zero whenever a data table crossload is active This word is zero whenever a data table crossload is inactive When a data table crossload fails diagnostic information is stored in 2 words of the ControlNet Hot Backup Integer CHBI file Word 54 of the CHBI file contains the file number of the crossload that failed Word 53 of the CHBI file contains the error code indicating the reason why the crossload failed These error codes are identical to the Message Instruction Error Codes See the Instruction Set Reference Manual Publication 6200 6 4 11 for a complete listing of the various error codes which can be encountered while executing a Message Instruction For example a qualification crossload could fail if the data table file on the primary processor had read privileges disabled This error would show up as error code OxFOOB privilege error in word 53 of the CHBI file Performing Data Table Crossloads Via Your Applications On Demand data table crossloading greatly simplifies the whole crossloading procedure However you may have
70. ne this value through running the application in its real environment Second in Synchronous mode each program scan is always lengthened to be equal to the maximum program scan time Thus even when a particular program scan takes only a fraction of the maximum program scan time the program scan waits until the synchronization point is reached before continuing with housekeeping Depending on your application and program logic this may affect overall system throughput Determining the Maximum Program Scan Time When configuring Synchronous mode you must enter the Maximum Program Scan Time in ms The Maximum Program Scan Time is a time that should not be exceeded by the program scan The program scan is the time it takes the processor to execute the logic program once perform housekeeping tasks and then start executing logic again Because every program scan is pushed out to the Maximum Program Scan Time it is advantageous to configure the Maximum Program Scan Time parameter to be as close to the largest program scan time as possible The only way to determine the largest program scan time for a particular application is to run the application in Asynchronous mode under all conditions and then determine what the largest program scan time was You can determine this by viewing the Status File word S 9 Be sure to consider all the events that may cause the program scan time to temporarily increase such as PII s STT s On line edits e
71. needed to establish connections on the ControlNet channel It is important to make a connection to the partner PLC 5 processor in order to determine if this processor is to become primary or secondary If the partner PLC 5 processor is primary this processor goes through qualification to become a secondary system If the partner PLC 5 processor is not the primary or if a partner is not on the ControlNet channel this processor goes through qualification to become primary In most cases there is no qualification connection delay There are however two cases where the PLC 5 system waits 10 seconds before starting qualification The first case is when a reconfiguration of the ControlNet channel occurs When this occurs all connections are terminated and must be reestablished the 10 second wait allows the connection to be reestablished with the partner PLC 5 processor Note that at powerup a ControINet channel reconfiguration occurs The second case in which the PLC 5 system waits 10 seconds before starting qualification is when the first connection is established on the ControINet channel This is indicated when the ControINet I O LED changes from red to green This could occur for example when a disconnected cable gets reattached There is no visual indication when a qualification connection delay is active e Backup configuration parameters passed to qualifying system After the qualifying PLC 5 system has waited if necessary for the
72. ng the secondary system to disqualify However if one of the PLC 5 systems goes out of Run mode and back into Run mode and a qualification occurs an equivalence check failure during qualification causes a major fault to be declared for the qualifying system Therefore when performing edits on either PLC we recommend that you disable equivalence checking first to avoid the condition where a PLC 5 processor cannot become qualified due to failing an equivalence check Once all the edits are tested and placed into both PLC 5 systems you can reenable the equivalence check Word 49 in the ControINet Backup Configuration and Status file gives you equivalence check status for a qualified backup system A bit is set for each equivalence check area if the equivalence areas checksum differs between the two processors This word is updated every few seconds so that you can know if secondary qualification were to happen which equivalence checks would pass and which equivalence checks would fail Complete data table crossload If all the equivalence checks pass a Qualification Data Table crossload is performed This crossload reads the data table file values from the primary system and writes those values into the corresponding data table files in the secondary system This data table crossload is performed while the qualifying PLC 5 system is still in Program mode It is necessary to remain in Program mode until the data table crossload is finishe
73. o the secondary processor that a switchover must occur The following events can cause a Communicated Switchover e A Designated Primary switchover e A Forced switchover e Switching the primary PLC 5 system out of Run mode e The occurrence of a major fault on the primary PLC 5 system Backup States B 15 Since the peer to peer handshake connection is one NUT it only takes up to one NUT for the primary system to indicate to the secondary system that a switchover must occur There is up to Sms of processing on each processor to get the switchover indication from the primary system to the secondary system Thus the formula for the Communicated Switchover Time is Communicated Switchover Time 10ms NUT So if the NUT is 5ms the Communicated Switchover Time is equal to 10ms plus 5ms or 15ms Timeout Switchover when the secondary processor loses communication with the primary processor for a certain length of time it times out the primary processor and then performs a switchover The following events can cause a Timeout Switchover e Primary PLC 5 system failure e Loss of power to the primary PLC 5 system e Problems with the ControlNet network which causes loss of the handshake connection with the primary processor The formula that determines the length of time the secondary system waits before timing out the primary processor is as follows Primary Timeout 5 3 NUT or 25ms whichever is greater So if the NU
74. o word 33 of the ControlNet Hot Backup Integer file Functionally an On Demand data table crossload is equivalent to a series of Message Instructions however no ladder programming is required Publication 1785 6 5 24 February 1999 C 2 Data Table Crossloading Publication 1785 6 5 24 February 1999 In addition to the crossloading mentioned above there is Automatic data table crossloading occurring at the time of qualification which transfers data table values from the primary processor to corresponding data table locations on the secondary processor This ensures that when a secondary processor becomes qualified that processor is immediately ready to take over control of the outputs should a switchover occur Both the On Demand data table crossload and Qualification data table crossload use the unscheduled bandwidth of the ControlNet channel You can also perform data table crossloads in ladder logic via the message instruction When you perform data table crossloads via the message instruction you can use any available channel you are not limited to the ControlNet channel Important Neither the On Demand data table crossload nor the Qualification data table crossload can occur unless the data table structures are identical between the two processors Also data table crossloading only crossloads data table data i e there is no mechanism to crossload Program file information It is up to you to ensure that the proper program fi
75. ogix5 Data Monitor or via ladder logic in your application Data Table Crossloading C 5 The On Demand data table crossload operations that get performed depend on the value written into the On Demand Crossload Command word The 4 least significant bits of the On Demand Crossload Command word are defined for the 4 different On Demand data table crossload operations e BitO Timer Accumulators e Bit 1 Counter Accumulators e Bit 2 PD elements e Bit 3 User Selected Files Thus if you wrote a 15 binary 1111 into the On Demand Crossload Command word all On Demand State crossload operations would be performed If you wrote a 5 binary 0101 into the On Demand Crossload Command word only the Timer Accumulators and the PD elements would be crossloaded When the On Demand State crossload is started the On Demand Crossload Command word is cleared by the processor While the On Demand State crossload is active the processor ignores the On Demand Crossload Command word This is true even if the On Demand State crossload was started from the other processor When an active On Demand State crossload finishes the processor then checks to see if a new crossload command is in the On Demand Crossload Command word Qualification Crossloads There are two separate crossloads that are automatically performed during qualification These qualification crossloads are only done if the data table structures are identical between the two processors
76. or Click on the Online button to connect to the processor When prompted click on OK to confirm that you wish to complete the upload This step is required since you have made changes to the ControlNet configuration From the File menu choose Save to save the project Click on the Hot Backup icon under the Controller folder to launch the Hot Backup Configuration utility The ControlNet Hot Backup screen appears with the Configure tab selected 3 ControlNet Hot Backup B x L e Crossload Status Backup Data File r Equivalence Checks Backup File 5 67 Ladder Logic Data Table Structure m Connection 1 0 Map Structure ODD Node Addr Backup Integer File Send Message Force Table Receive Message Status File r Properties Designated Primary Operational Mode MaxProgamScanTime n Set the following e Backup File Enter an unused data file number This creates a 200 word integer file to be used as the ControlNet Backup Configuration and Status file e Odd Node Address Enter the ControlNet node address corresponding to the odd node processor e Send Message Enter the message number of the Send Scheduled Message from the odd node address Refer to the number you recorded earlier e Receive Message Enter the message number of the Receive Scheduled Message from the odd node address Refer to the number you recorded earlier If
77. or during the On Demand data table crossload All the elements of these files are crossloaded There are 4 words in the ControlNet Hot Backup Integer file reserved for user selectable On Demand data table crossloads You must fill in the file numbers into these 4 words for the appropriate files to be transferred You should fill in a zero when you do not wish to perform a crossload User Defined crossload File 1 Word 55 of the CHBI file User Defined crossload File 2 Word 56 of the CHBI file User Defined crossload Range Low File Word 57 of the CHBI file User Defined crossload Range High File Word 58 of the CHBI file Publication 1785 6 5 24 February 1999 C 4 Data Table Crossloading Publication 1785 6 5 24 February 1999 The two individual files as well as the range of files you select are crossloaded regardless of file type There are some notable exceptions the following files are not be crossloaded even when you select them Output Image File File 0 Input Image File File 1 System Status File S2 ControlNet Data Output File DOF ControlNet Data Input File DIF ControlNet Backup Integer File ControlNet Configuration File ControlNet I O Status File ControlNet Diagnostic File Important If a file in the On Demand crossload User Selectable files is either a Timer or Counter file type only the Accumulator for each file element is crossloaded Optimizing On Demand Crossloads
78. or is in the No Control backup state Note that placing an invalid parameter into the ControlNet Backup Configuration and Status file causes the processor to switch to the Invalid backup state Publication 1785 6 5 24 February 1999 B 4 Backup States Publication 1785 6 5 24 February 1999 Primary Backup State When a PLC 5 ControlNet backup system is in Run mode and is actively controlling all of the system outputs it is in the Primary backup state The Primary LED is green either blinking or solid the Secondary LED is off The PLC 5 processor can go out of Primary backup state if either the PLC 5 system is switched out of Run mode or the partner PLC 5 becomes the Primary If there is a valid partner PLC 5 ControlNet backup system and the systems are connected on the ControlNet channel the Qualified LED is on If the Qualified LED is solid yellow the partner PLC 5 is not a qualified secondary system however the two systems are properly configured to communicate with each other If the Qualified LED is solid green the partner PLC 5 is a qualified secondary and could take control of the system outputs if necessary If the Qualified LED is off then there is no partner PLC 5 system communicating with this PLC 5 system on the ControINet channel When the PLC 5 is in the Primary backup state you can no longer force the backup system to be in the Invalid backup state through configuration changes All configuration changes are checked
79. our main backup states Invalid e No Control e Primary and Lonely Primary e Secondary NO BACKUP POWERUP CARD NON BACKUP INVALID po R STATE INVALID BACKUP CONFIGURATION VALID BACKUP CONFIGURATION NO CONTROL STATE PRIMARY FOUND SM BUT MODE QUALIFICATION PASSED IN RUN MODE NOT IN NOT IN RUN MODE RUN MODE PRIMARY SECONDARY STATE STATE n M BACKUP STATE DIAGRAM Publication 1785 6 5 24 February 1999 B 2 Backup States Publication 1785 6 5 24 February 1999 Invalid Backup State When an improper backup configuration exists the PLC 5 ControlINet backup system goes into the Invalid backup state Both the Primary and Secondary LEDs on the 1785 CHBM cartridge are solid red when the system is in this state and the Qualified and Synchronous LEDs are off If you switch the system to Run mode while in the Invalid backup state a major fault occurs Refer to Chapter 4 for definitions of the major fault codes The backup system enters the Invalid backup state when one or more of these conditions exists e the 200 word ControINet Backup Configuration and Status File does not exist e the ControINet Backup Configuration and Status File exists but is the wrong size this file must be exactly 200 words in length e the file number index to the ControINet Backup Configuration and Status File in S 67 is incorrect e the ControlNet peer to peer backup connection
80. ppropriate bits in this word After the PLC 5 has read the word it clears it This feature works for both primary and secondary processors it 0 Crossload Timers t1 Crossload Counters it 2 Crossload PID it 3 Crossload user defined files es CO OD CJ 34 39 reserved 40 45 The timedate stamp indicating when the processor last took over as the primary is stored here The format of the data is the same as the clock in the status file 46 Qualification status The reason code for why the processor failed qualification or if the configuration parameters were changed by the primary Valid values include 0 Passed qualification 1 Equivalence check Ladder programs different 2 Equivalence check Data table structures different 3 Equivalence check I O map tables different 4 Equivalence check ControlNet Backup Configuration and Status files different 5 Equivalence check Force tables different 6 Equivalence check Status files different 7 Qualification passed but configuration parameters changed by primary 8 Qualification failed due to processor being faulted 9 Qualification failed due to keyswitch change to Program mode 10 Qualification failed due to Run mode inhibited 11 Qualification failed due to processor uploading or downloading program 12 Qualification failed due to ContronNet reconfiguration in progress 13 Qualification failed due to invalid
81. primary and secondary PLC processors are identical You can enable various equivalence checks from the Configuration tab of the ControlNet Hot Backup screen Simply check the boxes corresponding to the equivalence checks you wish to enable Equivalence status is updated constantly on both PLC processors while there is a qualified backup system If there are differences between the two processors a status message appears indicating the difference s and warning you that the secondary will major fault upon switching to Run mode The Configure tab provides you with the current status for each equivalence check Equivalent indicates that the two processors are identical and Different indicates that there were differences detected Installing and Configuring Your ControlNet PLC 5 Backup System 3 15 Crossloading You can perform data table crossloading on demand While both PLC processors are running you can initiate a crossload from either the primary or secondary processor You can perform a crossload on the following data file types e all timer accumulation values in the data table e all counter accumulation values in the data table e all PID files in the data table e user defined files which allow you to select up to 2 separate data file numbers and or a range of files You can set up and select the files to be crossloaded from the Crossload tab of the ControlNet Hot Backup screen 3 ControlNet Hot Backup Configure t E Stat
82. processor will write its internal PLC 5 processor state of these configuration parameters into words 20 through 24 When you accept configuration changes the configuration parameters in words 10 through 14 are copied into words 20 through 24 25 Adjusted Maximum Program Scan Time This word is the Maximum Program Scan Time parameter rounded up to the next integer multiple of the NUT value This word is written by the PLC 5 processor and is continuously updated while the processor is in Run mode 26 The number of NUTs per Maximum Program Scan Time This word is the number of NUTs in the Adjusted Maximum Program Scan Time This word is written by the PLC 5 processor and is continuously updated while the processor is in Run mode 27 The NUT time in 10 microsecond units is continuously written here while the processor is in Run mode 28 Configuration status This word gives either the reason why the configuration attempt was unsuccessful or whether the configuration parameters were overwritten because the system went into Run mode as a secondary system 6 Operation mode word invalid 7 Equivalence Check word invalid 8 Designated Primary word invalid 9 Max Program Scan Time word invalid 10 Configuration parameters were overwritten by the primary system 12 Crossload parameter invalid 29 reserved 30 Accept Configuration Changes A non zero value written into this location forces th
83. qualification connection delay the backup configuration parameters are passed from the primary PLC 5 system to the qualifying PLC 5 system The backup configuration parameters which were originally in the qualifying system are overwritten and lost The backup configuration parameters that are passed from the primary system and overwritten on the qualifying system are Operational Mode Equivalence Checks Designated Primary Maximum Program Scan Time Crossload File 1 Crossload File 2 Crossload File Low Crossload File High Backup States B 7 Equivalence checks The PLC 5 ControlNet backup system does not download the entire memory from the primary system to the secondary system there are certain data table values that are crossloaded Areas such as the program files and data table structures may be different between the primary and secondary system In some applications this is desirable However in most applications you must know for certain whether the primary and secondary systems are identical or whether they may differ in certain areas Equivalence checking gives you the option of enforcing a qualification major fault if the systems differ Refer to Chapter 4 for descriptions of specific major faults You can implement qualification equivalence checking by calculating checksums for different memory areas of the PLC 5 system These checksums are calculated on both the primary and qualifying secondary syste
84. r ControlNet PLC 5 Backup System Word 50 Definition Qualification Crossload Time The time in ms it takes to crossload the entire data table from the primary processor to the secondary processor This value is overwritten each time the processor goes through qualification 51 On Demand Crossload Time The time in ms it takes to crossload the data table state information from the primary to the secondary This value is overwritten each time the processor goes through qualification and when you initiate an On Demand Data Table Crossload command 52 Crossload Active This word equals 1 when a crossload is active it is equal to 0 when a crossload is not active This word applies to both Qualification and On Demand crossloads 53 Crossload Status This is a Message instruction error code The processor writes the value into this word For information on error descriptions refer to your PLC 5 Instruction Set Reference Manual 54 Crossload Failed File This word displays the file number on which the crossload failed The crossload status word located in word 53 displays the error code and word 54 di splays its correlated file 55 User Defined Crossload Fi le 1 You can select a sing e file number written in this word to be crossloaded during the Qualification crossload and on demand when setting the appropri ate bit in word 33 56 User Defined Crossload F ile 2 You can s
85. ration parameters by intentionally entering an incorrect configuration value for one of the first 3 words in the ControlNet Backup Configuration and Status File This will force all parameters to be set to their default values For example by setting Word 0 to be equal to 0 the following optional configuration parameters are defaulted e Operational Mode Asynchronous Mode e Equivalence Checks All Disabled e Designated Primary Disabled e Maximum Program Scan Time 0 e Qualification Delay 0 e Crossload File 1 0 e Crossload File 2 0 e Crossload File Low 0 e Crossload File High 0 No Control Backup State When a valid backup configuration exists but the PLC 5 processor is not in Run mode the PLC 5 ControlNet backup system is in the No Control backup state Both the Primary and Secondary LED s on the 1785 CHBM cartridge are off when in this state While in the No Control backup state you can switch the PLC 5 processor to Run mode once in Run mode however the processor is no longer in this state If there is a valid partner PLC 5 ControlNet backup system and the systems are connected on the ControlNet channel the Qualified LED is solid yellow This indicates that the necessary configuration needed to allow the backup pair to successfully communicate with each other has been achieved You can make any configuration changes you wish to the ControlNet Backup Configuration and Status file while the PLC 5 process
86. ring Your Backup System 3 2 Configuring With a Single Control Application 3 2 Configuring With Differing Applications 3 7 Advanced Configuration Options sees 3 12 Synchronous and Asynchronous Program Scanning 3 13 Equivalence Checks incedo oae toris tcai esau 3 14 Crossloading 3 15 Status 3 16 Processor Editing Considerations esses 3 17 Downloading Editing Changes 3 17 Testing Data Table Edits 3 17 Chapter 4 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System Chapter ODiECH VES A seGeoiiiie re oti esca de ales tM eoe 4 1 ControlNet PLC 5 Backup Specific Major Fault Error Codes xis es acess Sac deo o od pati Ded 4 Using the 1785 CHBM Cartridge Status Indicators 4 2 Troubleshooting the Invalid Backup State 4 3 Troubleshooting Qualification Major Faults 4 4 Troubleshooting Qualification Crossloads 4 5 ControlNet Backup Configuration and Status File 4 5 Appendix A Specifications Specification See aa eldest na eM e oe t waco ek A 1 1785 6 5 24 February 1999 Appendix B Appendix C Appendix D Appendix E Appendix F 1785 6 5 24 February 1999 Backup States Chapter Object VES iini ess pane shety A ose tae B 1 Invalid Backup State i5 ore eoe eei i catene B 2 No Control Backup State 12512 ee
87. rising a backup system you must create two scheduled peer to peer messages one Send and one Receive These messages must be exactly five words in length From the ControlNet Configuration screen for the first processor follow these steps 1 Right click on the even node Node 2 in this example and choose Insert Receive Scheduled Message Publication 1785 6 5 24 February 1999 3 4 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 The Receive Scheduled Message dialog appears Receive Scheduled Message 2 x Node Number 2 Message Number Requested Packet Interval E Message Size 5 Cancel The Node Number field is already filled in for you This number indicates the node number from which you will receive the Receive scheduled message In your ControlNet backup system the odd node will receive the message from the even node and vice versa Enter the message number you wish to assign to identify this message Note that the message number for the Receive message must match the message number of the corresponding Send message The node number and message number are used together to identify the specific message In the Requested Packet Interval field enter an RPI value for this message from 1 to 32 767 For purposes of this example we will use an RPI value of 5 In general the RPI value must be no less than the NUT value but less than 2 times the NUT va
88. rs Receive Scheduled Message 2 x Node Number 2 y Message Number Requested Packet Interval E Message Size 5 Cancel The Node Number field is already filled in for you This number indicates the node number from which you will receive the Receive scheduled message In your ControlNet backup system the odd node will receive the message from the even node and vice versa 2 Enter the message number you wish to assign to identify this message Note that the message number for the Receive message must match the message number of the corresponding Send message The node number and message number are used together to identify the specific message 3 In the Requested Packet Interval field enter an RPI value for this message from 1 to 32 767 For purposes of this example we will use an RPI value of 5 In general the RPI value must be no less than the NUT value but less than 2 times the NUT value This value must be the same in both PLC 5 processors 4 Inthe Message Size field enter a value of 5 and click OK The Receive scheduled message is inserted in your ControINet Configuration for the odd node The corresponding Send scheduled message is automatically inserted for the even node Publication 1785 6 5 24 February 1999 3 10 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 5 From the main RSNetWorx screen right click on the second PLC 5 processor
89. s If the primary processor faults or is otherwise unable to continue control of the outputs the secondary processor assumes control and becomes the primary Both PLC 5 processors are actively connected to the ControlNet I O receive all input data sent by the I O adapters and then use that data as they execute their program scans Output data is sent via ControlNet from both processors However only data from the primary processor is used by the I O adapter s In the case of the ControlNet PLC 5 backup system there are several features to consider that though common to many backup systems are uniquely implemented in this particular system Understanding these features and their functions will help you in the design and implementation of your backup applications Backup Concepts for the ControlNet PLC 5 Backup System 1 3 Qualification When bringing the secondary processor of a backup system online it is important to ensure that it is in a state that will enable it to take over the control of the system in the event of a primary failure or switchover This process of verifying and conditioning the state of the secondary processor is known as qualification Switchover will not occur without a qualified secondary processor the backup system is not truly considered a backup system until the secondary processor has successfully completed qualification The qualification phase includes several tests and verifications between the primar
90. s configured in RSNetWorx do not exist or are not correct these connections must besent to and received from the partner processor be5 words long havean actual packet interval rate equal to one NUT e the first 3 words of the ControINet Backup Configuration and Status File are incorrectly configured Word Valid Configuration 0 must equal the odd node number of the odd even PLC 5 processor pair 1 must equal the message number of the ControINet scheduled peer to peer backup connection going from the odd node number to the even node number of the odd even PLC 5 processor pair 2 must equal the message number of the ControINet scheduled peer to peer backup connection going from the even node number to the odd node number of the odd even PLC 5 processor pair Backup States B 3 e one of the optional configuration parameters in the ControINet Backup Configuration and Status File is invalid the following optional parameters are checked Operational mode invalid if not equal to 0 or 1 Equivalence checks invalid if greater than 0x3f Designated primary invalid if not equal to 0 or 1 Maximum program scan time invalid if greater than 128 x NUT and synchronous operational mode Crossload File 1 Crossload File 2 Crossload File Low and Crossload File High invalid if greater than or equal to 1000 While in the Invalid backup state you can set default parameters for the optional configu
91. s 55 through 58 are copied into words 65 through 68 69 199 reserved Important Do not alter any reserved words Values in these words may be changed or used by the PLC 5 processor during normal operation Publication 1785 6 5 24 February 1999 4 10 Monitoring and Troubleshooting Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 Specifications Specifications Appendix A The following specifications are for the 1785 CHBM cartridge Description Value Memory Module 1785 CHBM Capacity 100K words Type Nonvolatile Write Protection By removing the jumper Weight 70 875g 2 5 oz Environment Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 40 to 85 C 40 to 185 F Relative Humidity 5 to 95 without condensation Shock Testing Operating 15 g peak acceleration at 11 ms duration Non operating 3 g peak acceleration at 11 ms duration Vibration Testing 2 g peak acceleration at 10 500 Hz Agency Certification CSA certified CSA Class Division 2 Groups A B C D UL listed CE marked for all applicable directives Publication 1785 6 5 24 February 1999 A 2 Specifications Publication 1785 6 5 24 February 1999 Appendix B Backup States Chapter Objectives This Appendix describes the possible backup states and backup state transitions of the PLC 5 ControINet backup system There are f
92. s the primary The main exception to continuous transfer is with timer variables You should periodically but not continuously refresh variables Chapter Objectives Comparison to the BCM System Appendix F Comparison to the 1785 BCM System This appendix provides you with a comparison between the ControINet PLC 5 backup system and the 1785 BCM backup system Like the BCM scheme the ControINet PLC 5 backup system makes use of a primary and a secondary processor where both the primary and secondary processors simultaneously execute their control logic However these two backup schemes differ in 3 major ways e The ControINet PLC 5 backup system offers the capability of synchronizing each control program scan with the scheduled input data while the BCM backup system does not offer any form of program synchronization With synchronized program execution and scheduled inputs the primary and secondary systems should not diverge to any great degree Thus the ControINet PLC 5 backup system eliminates the need for massive crossloading of data and elaborate application program development to eliminate divergence of the primary and secondary systems e The ControINet PLC 5 backup system eliminates the need for the massive wiring required in the BCM backup system The 1794 FLEX I O Adapters on the ControINet channel are able to listen to data transmissions from both processors as well as determine which processor has primary control Also
93. some special crossloading needs that are not covered by On Demand data table crossloading For example if you want to crossload the data table data over the Ethernet channel instead of the ControlNet channel you cannot use On Demand data table crossloads Or perhaps you only need to crossload certain elements within a file instead of the whole file Or even if you need to crossload the entire Timer structure instead of just the Accumulator subelement On Demand data table crossloads do not meet those needs You can always perform your own data table crossloads using message instructions These message instruction crossloads can be used in conjunction with On Demand data table crossloads or they can be performed separately You are not limited to doing these data table crossloads over the ControlNet channel We recommend that you have the message instruction rung qualified with the backup state of the processor e g secondary backup state Then the instruction will only be executed when the processor is a secondary A bit instruction can be used to condition the rung Word 3 of the ControlNet Hot Backup Integer file contains the backup state of the processor Bit 2 is set if the processor is the primary Bit 3 is set if the processor is the secondary Chapter Objectives Program Synchronization Appendix D Program Synchronization This appendix provides you with reference information on the program synchronization feature Both pro
94. ssload operations Timer Accumulators Counter Accumulators PD files and User Selectable files whereas the On Demand data table crossload allows you to select which combination of the four operations get performed Data Table Crossloading C 7 Data Table Crossload Time It may take many seconds for any of the above instances of data table crossloading to finish The time it takes to do the data table crossload primarily depends on the amount of data table data to be crossloaded The data table crossload is performed using the unscheduled bandwidth of the ControlNet channel The amount of available unscheduled bandwidth on the ControlNet channel also influences the amount of time needed to perform the data table crossload There are two words which indicate how long it takes the data table crossload to finish one for the Qualification data table crossload word 50 in the ControlNet Backup Integer File and one for the most recent occurrence of either the On Demand data table crossload or the Qualification State data table crossload word 51 in the ControINet Backup Integer File The time units are in milliseconds Data Table Crossload Data Latency Even though a data table crossload may take many seconds to complete the data that is transferred from the primary processor to the qualifying or secondary processor is fresh In other words the crossloaded data is not sitting in a buffer getting stale waiting for all the data to be crossloaded
95. stem to have MMI devices actively communicating with both the Primary and Secondary PLC 5s Publication 1785 6 5 24 February 1999 Allen Bradley a Rockwell Automation Business has been helping its customers OA Rockwell Automation improve productivity and quality for more than 90 years We design manufacture Allen Bradley and support a broad range of automation products worldwide They include logic processors power and motion control devices operator interfaces sensors and avariety of software Rockwell is one of the world s leading technology companies Worldwide representation Z7 N Argentina e Australia e Austria e Bahrain e Belgium Brazil e Bulgaria e Canada e Chile e China PRC e Colombia e Costa Rica e Croatia e Cyprus e Czech Republic e Denmark e Ecuador e Egypt e El Salvador e Finland e France e Germany e Greece e Guatemala e Honduras e Hong Kong Hungary e Iceland India e Indonesia e Ireland e Israel e Italy e Jamaica Japan e Jordan e Korea Kuwait e Lebanon e Malaysia e Mexico e Netherlands e New Zealand e Norway Pakistan e Peru e Philippines e Poland Portugal e Puerto Rico e Qatar e Romania e Russia CIS e Saudi Arabia e Singapore e Slovakia e Slovenia e South Africa Republic e Spain e Sweden Switzerland e Taiwan e Thailand e Turkey United Arab Emirates e United Kingdom e United States e Uruguay e Venezuela e Yugoslavia Publication 1785 6 5 24 February 1999 955133 45 Copyri
96. tate information so these critical state variables are automatically transferred You can also select a range of files to transfer by entering the beginning file number and ending file number in the configuration parameters In addition to the file range you can specify a limited number of selected files for transfer By setting the appropriate bit in the transfer register the secondary processor transfers timers counters PD structures and or the files you have selected When the secondary transfers these files the transfer bits are cleared by the secondary and no further transfers take place until the transfer bits are once again set by the secondary PLC application program While the transfer register can in most cases function as the sole mechanism for transferring state files other information may still need to be transferred For instance an integer file may be used as a past event holder in some applications If this file can cause the state of the primary and secondary to be different you may wish to transfer the integer file just shortly after entering Run mode The additional transfer may be necessary even though all of the primary processor s data table is transferred on power up This transfer may be necessary because there can be a time delay between the time that the entire data table is transferred and the time the secondary actually goes into Run mode It is possible for one of the state variables to change on the primary whi
97. tc Program Synchronization D 3 Adjusted Maximum Program Scan Time The Maximum Program Scan Time parameter you enter for Synchronous mode gets adjusted before being used by the ControlNet PLC 5 Backup system The Adjusted Maximum Program Scan Time is equal to the smallest integer number of NUT s whose time value is greater than or equal to the Maximum Program Scan Time parameter For example if the configured Maximum Program Scan Time parameter is 65ms and the ControlNet channel NUT value is 10ms the Adjusted Maximum Program Scan Time would be 70ms i e 10ms x 7 In this example each program scan time would be fixed at 70ms Program Scan Overrun For Synchronous mode operation it is possible for the actual program scan time to exceed the Adjusted Maximum Program Scan Time When this overrun condition occurs the Sync LED turns solid red and the Maximum Program Scan Time Exceed Counter word 48 in the ControINet Backup Integer File is incremented You must zero out the Maximum Program Scan Time Exceed Counter for the Sync LED to turn from solid red to solid green The Maximum Program Scan Counter is cleared by writing a non zero value into the Reset Diagnostic Counters word word 32 of the ControlNet Hot Backup Integer file When a program scan overrun occurs the two processors temporarily go out of sync however they do not stay out of sync They go back into sync at the earliest time possible They should be back into sync at
98. tem is qualified This allows status to be available regarding whether the Status File checksums differ for a qualified backup system The different words included in the Status File checksum for equivalence checking are e Watchdog Set Point e Fault Routine Number STI Set Point STI Routine Number e I O RESET Bits e O INHIBIT Bits PII Routine Number PII Word Number e PII AND Mask e PII Polarity Mask e PII Counter Preset e Data Table Protection File Number e ControlNet Backup Configuration and Status File Number e ControlNet PLC 2 File Number e MCP I O Disable Word e MCP INHIBIT Word e MCP File Numbers Backup States B 9 You can selectively enable equivalence checking for none some or all of the 6 of the equivalence check areas with one exception the Program File Structure and Program File checksum is dependent on the Data Table Structure Thus if you select the Program File Structure and Program File equivalence check you should also select the Data Table Structure equivalence check Equivalence checking is only performed during qualification Once a PLC 5 system passes qualification it does not become disqualified even if the checksums for an area are different and the equivalence checking for that area is enabled For example if the Program File Structure and Program File equivalence check is enabled and there is a qualified secondary you can edit the program files on either system without causi
99. the data table structures are the same between the two processors data table crossloads automatically occur during qualification Should the Qualification Data Table crossloads fail the processor major faults Refer to Appendix C for more information on data table crossloading When a data table crossload fails diagnostic information is stored in 2 words of the ControINet Backup Configuration and Status file Word 54 of this file contains the file number of the crossload that failed word 53 contains the error code indicating the reason why the crossload failed These error codes are identical to the Message Instruction Error Codes See the Instruction Set Reference Manual Publication 6200 6 4 11 for a complete listing of the various error codes which can be encountered while executing a Message Instruction For example a qualification crossload could fail if the Data Table file on the primary processor has read privileges disabled This error shows up as error code OxF00B privilege error in word 53 of the ControINet Backup Configuration and Status file Note Ifthe file number of the crossload that failed word 54 of the ControINet Backup Configuration and Status file is OXFFFFon the qualifying processor then the file number that failed is on the primary processor The data table file number of the ControINet Backup Configuration and Status file can be found in the PLC 5 processor at word S 67 The default configuration parameters
100. ting tips for ControlNet PLC 5 Backup System the backup system Publication 1785 6 5 24 February 1999 ii Using This Manual Related Publications Publication 1785 6 5 24 February 1999 For information on Refer to chapter appendix specifications for the 1785 CHBM A Specifications module backup states and backup state B Backup States transitions the data table crossloading feature C Data Table Crossloading the program synchronization feature D Program Synchronization application examples items to consider E Application Guidelines while operating the backup system reference information on the ControlNet F Comparison to the 1785 BCM System backup module for users familiar with the Allen Bradley 1785 BCM systems For more information about components used with the ControINet PLC 5 backup system refer to the following publications PLC 5 Processor Documentation Publication Title eid 1785 Enhanced PLC 5 Processor System Overview 1785 2 36 ControlNet PLC 5 Programmable Controllers User Manual 1785 6 5 22 ControlNet PLC 5 Programmable Controllers Quick Start 1785 10 6 PLC 5 Programmable Controller Flash Tool User Manual 1785 6 2 ControlNet Documentation Publication Title dod ControlNet System Overview 1786 2 12 Industrial Automation Wiring and Grounding Guidelines 1770 41 ControlNet Cable System Component List AG 2 2 ControlNet Cable System Planning and Installatio
101. tion clean and wash etc In that case equivalence checking may not be required With the ControINet PLC 5 backup system you can enable or disable equivalence checking as required by your application You must have a thorough understanding of your application in order to make this determination Publication 1785 6 5 24 February 1999 1 4 Backup Concepts for the ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 Bumpless Transfer Ideally when a processor switchover takes place in the backup system there should be no adverse effect on system operation and the controlled process should continue to run as though it were still being controlled by the original primary processor This is generally referred to as a bumpless transfer of control Bumpless transfer is not required for many backup applications but it is highly desirable Divergence in program scanning I O tables data tables and long switchover times can all cause bumps when transferring control from a primary to a secondary processor The ControlNet PLC 5 backup system allows you to choose synchronous program scan operation as well on demand crossloading of data table files you select These options can greatly reduce the possibility of bumps during a processor switchover Switchover Switchover is what occurs when the secondary processor assumes control of the process thus becoming the primary processor Several conditions can cause this to happen
102. trolNet PLC 5 Backup System 3 11 Configure the Hot Backup Parameters 1 2 Launch RSLogix 5 From the Comms menu choose System Comms The System Options dialog appears with the System Communications tab selected System Options x Preferences System Communications Driver Route Processor Node Current settings Decimal 22 Octal Last Configured AB KTC 1 Node 2d local Reply Timeout UTE fio Sec Who Active Online Download T Hee In the Processor Node field enter the node number of the first processor Click on the Online button to connect to the processor When prompted click on OK to confirm that you wish to complete the upload This step is required since you have made changes to the ControlNet configuration From the File menu choose Save to save the project Click on the Hot Backup icon under the Controller folder to launch the Hot Backup Configuration utility The ControlNet Hot Backup screen appears with the Configure tab selected Set the following e Backup File Enter an unused data file number This creates a 200 word integer file to be used as the ControlNet Backup Configuration and Status file e Odd Node Address Enter the ControlNet node address corresponding to the odd node processor e Send Message Enter the message number of the Send Scheduled Message from the odd node address Refer to the number you recor
103. u can view system status from the Status tab of the ControlNet Hot Backup screen ControlNet Hot Backup OY xi Configure Crossload Status m CBC Module LED s r Diagnostic Counters ee Ch SECs anda e QUAL Qualified Secondary Present Qualification Error Reason SYNC Program Scan is Synchronous Passed Qualification m Maximum PScan Information Invalid State Reason ConfigwedScan D N A AdiustedScan 5 NUT Time ms Number of NUT s The CBC Module LEDs section mirrors the display of the LEDs on the 1785 CHBM module which is currently online Diagnostic Counters Diagnostic counters provide information on the number of times the Maximum Program Scan has exceeded the Maximum Program Scan Time configured for the system when in Synchronous mode These counters are incremented by 1 every time the actual program scan is greater than the configured program scan The Lost Partner counter increments every time the system has detected a loss of communication between the primary and secondary PLC processors You can press the Clear button to reset these values Qualification Error Reason If the qualification of the system fails the Qualification Error Reason indicates the reason why the failure occurred Refer to Chapter 4 for information on corrective actions you can take Invalid State Reason If the
104. up option is used where you must transfer the control of the process to a secondary system without interrupting the machine process operation To guard against system shutdown a backup system must provide equipment with exceptional reliability e automatic fault isolation minimal disturbance of the process when switching from the primary to the secondary system Publication 1785 6 5 24 February 1999 1 2 Backup Concepts for the ControlNet PLC 5 Backup System Basic System Architecture How the Backup System Works Publication 1785 6 5 24 February 1999 This section describes the various components of the basic ControlNet PLC 5 backup system The following picture illustrates the basic backup system PLC 3 Controltet Final PLC 5 Coetioi ket Lonselior with er other Cusirmiler mth t y85 CHBM cartridge installed interlace Drica 17H5 CHEM cartridge installed 1714 Hex LXI Tras ng Wed vo wt M In a ControlNet PLC 5 backup system one PLC 5 processor referred to as the primary processor controls the operation of the ControlNet I O The other processor referred to as secondary is set up to take control of the ControlNet I O in the event of a fault in the primary processor The ControlNet network is wired to both PLC 5 processors as well as to all ControINet I O in your system Using ControINet the processors communicate or handshake with each other exchanging status information on their operational state
105. us User Defined Crossload Files Individual m Initiate Crossload Of Files First Selected File Crossload User Files Second Selected File Crossload Timer Fil r User Defined Crossload Files Range DessbadTimeies Lowest File Number E Crossload Counter Files Highest File Number Crossload PID Files r Crossload Time Crossload All Above Fil On Demand sec i EH Qualification sec 0 Crossload Status No errors To crossload timer counter or PID values simply click on the respective button The crossload is performed as soon as you click on the appropriate button To set up user defined crossloading you must designate the files you wish to be crossloaded If you are selecting individual files enter the first file you wish to crossload in the First Selected File box If you wish to also crossload a second file enter it in the Second Selected File box If you wish to crossload a range of files enter the lowest file number and the highest file number in the respective boxes Once you have selected the files you wish to crossload click on the Crossload User Files button to perform the operation Note that you can perform a crossload for individual files and for a range of files simultaneously Publication 1785 6 5 24 February 1999 3 16 Installing and Configuring Your ControlNet PLC 5 Backup System Publication 1785 6 5 24 February 1999 Status Yo
106. ve the project Installing and Configuring Your ControlNet PLC 5 Backup System 3 3 Reconfigure ControlNet I O on the First PLC Processor Reconfigure all ControlNet I O adapters and modules that will be in your ControlNet PLC 5 backup system by changing their ControlNet connection from Exclusive Owner default to Redundant 1 2 Launch RSNetWorx for ControlNet Check the Edits Enabled checkbox on the toolbar Right click on the first PLC 5 processor the odd node and choose ControlNet Configuration The ControlNet Configuration screen appears i F imiia oe Pea Com heta Dre Pra Beg ieee iit qa Ta HaacmpaPueiemgm E O Pehle ee EE D Men Beene Lica AED TEI Ternama Pi ee NIE Dame hmi Loge EE E r fees E ni E i rene m s x Piikki nthe 1 5115 F IE ETE mu x Febris 0 HUE 1 a wu Mgr CC LC al E Coren Emri Turni Comm po Ea F roS f Di bpa Fins pu Darha Fn Um Demm P beiga pe Pata ires he Baa PE Desa age ris tee 175 i a Vor Hein peran Gee ii LEGA Habj Meme m For each entry under the Connection Type column double click on Exclusive Owner choose Redundant from the pull down menu and press Enter Configure Handshaking Messages With RSNetWorx Within your backup system you must use RSNetWorx to set up the send and receive scheduled messages that allow handshaking to occur between the two ControlNet PLC 5 processors that comprise your backup system For each of the processors comp
107. y and secondary processors as well as data file crossloading You can tailor these tests verifications and data file crossloads to ensure the level of system integrity required for your application These tests and verifications may cover e configuration file validity and integrity checking e application program and data file structure equivalence checking e O map structure comparison e force table comparison e status file comparison Data file crossloading from the primary to the secondary processor may include the transfer of integer values floating point values timers counters PID values and others you define Equivalence Checking Backup systems are traditionally designed in a way such that both the primary and secondary processors are programmed with identical applications This allows for the controlled process to continue with normal production operation in the event of a primary processor failure Equivalence checks ensure that the primary and secondary processors have identical ladder programs data file structures I O map structures etc You as the designer of the backup system require the ability to enforce equivalence checks between the primary and secondary processors during the qualification process and periodically during normal production operation In some cases you may want the secondary processor to have a completely different application than the primary processor e g safe shutdown limited produc
108. y be difficult and time consuming to make all the same editing changes to the other processor This section describes another method for doing so Downloading Editing Changes Downloading a program saved from one processor to another can greatly simplify the transfer of editing changes from one processor to another If you follow the steps described earlier in this chapter in the section entitled Create and Download the Project for the Second PLC Processor then you can complete this processor to processor download The steps outlined there ensure that a new different project name is created for the program that is downloaded They also ensure that the ControINet configuration information remains unique for each of the processors which must be the case This means that any edits you make to the I O map table you must manually make on each processor Testing Data Table Edits There may be instances where edits are made to the data table structure and these edits need to be tested on a running system If this is the case place one of the processors in your backup system into Program mode and make the edits to that processor Make sure that the data table structure and the ladder program equivalence checks are disabled while performing edit switchovers since ladder program equivalence checks are dependent on data table structures Next place the edited system into Run mode A forced switchover can be performed which makes the edited