Home
User`s Manual for
Contents
1. If a problem occurs while the system is running a Bell symbol will appear in the upper left corner of the screen and the system will present a note across the bottom of the screen If you tap the bar which includes the message the system will present more information about the problem Press the OK button to indicate that you have seen the Lockout or Alert Lead Lag Active service None Temperature 70 F Al Ope ation en able ON Setpoint 1200F 1 y Slaves Burner 0 0 Disabled Disabled 1 2 configure Details Diagnostics ype If an audible alarm on the display is active tap the Bell symbol to stop it Each error message includes a number For a more detailed description of each message see the Installation and Operation Manual Page 10 BRADFORD WHITE GENERAL CARE Keep the area around the Brute clear and free from combustible materials gasoline and other flammable vapors and liquids Clean the jacket surfaces with a damp cloth and mild soap Do not use flammable cleaning materials Keep the vent terminal free of obstructions Do not pile snow against the vent terminal ANNUAL INSPECTION AND SERVICE You should visually inspect the vent pipe once a year Should any corrosion or leaks exist have the affected parts replaced Once each year a qualified service agency should conduct a detailed inspection of all flue product carrying areas of the boiler and vent system Fo
2. Manual for instructions on filling and purging Brute BOILERS AND VOLUME WATER HEATERS 1 000 amp 1 200 MBTU h Page 7 CONTROLS AND INDICATORS On Off switch User Boiler outlet temperature and system pressure User Interface Each Brute includes two burners and each of these burners has a separate burner controller A complete system can include up to four boilers with up to eight burners and eight burner controllers All managed through one 1 User Interface on the Lead boiler After the system starts the User Interface Panel will automatically present the Home screen ER DE CREE a cee The icon for each burner controller will appear in one of four colors Blue Normal operation Red Lockout Gray Standby mode Burner switch off Gray and Communication problem crossed out Yellow Hold state This could be Anti short cycle fan speed transitions etc Page 8 BRADFORD WHITE The operation of the whole system is supervised by the Lead Lag control function To monitor the operation of the Lead Lag system press the View Lead Lag button on the Home screen Lead Lag View Individual In the Lead Lag Master example shown above the complete system includes one boiler with two burners To check the operation of an individual burner press one of the large icons on the Home screen The system will present a Status Summary screen for that burner Demand OFF Firing
3. See the section on About Lockouts Holds and Alerts 2 Turn up the thermostat to call for heat 3 In approximately 2 seconds the blower will operate Ignition should occur after 35 40 seconds It may take as long as 2 1 2 minutes 4 Ifignition does not occur wait 5 minutes and then repeat steps through 3 5 If after three attempts the unit still does not light shut down the boiler and call your service technician If the unit has been drained follow these steps 1 See the Installation and Operation Manual for instructions on filling and purging the unit 2 Remove the front access panel and turn ON the main manual gas valve 3 Switch on the main electrical disconnect switch The pump and blower will start and the igniter will be energized After 35 seconds the gas valve will be energized and ignition will occur If ignition does not occur within 2 1 2 minutes switch off the main disconnect switch wait 5 minutes and switch it on again If after three attempts ignition does not occur shut down the unit and call for service IN THE EVENT OF POWER FAILURE The Brute will not operate during an electrical power outage If there is an extended power outage with danger of freezing then the Brute and all other water systems should be completely drained Before draining the unit turn off the gas and turn off the main power switch When you replace the unit in service refer to the Installation and Operation
4. rate 0 RPM Burner state Standby Fan speed 0 RPM Setpoint EE ECS lt a EEN EZI E Setpoints Pumps ON Modulation OFF Central Heat 1350F 1409F 1509F Domestic Hot Water 1150F 1209F 1309F History The Lead Lag Master button will also get you to some additional information about the system Tap to Stop Alarm Active service None Temperature 120 F al Configure Details Diagnostics oer Deiis ype The yellow box in the upper right corner shows the setpoint and the line above that shows the current temperature Brute BOILERS AND VOLUME WATER HEATERS 1 000 amp 1 200 MBTU h Page 9 ABOUT LOCKOUTS HOLDS AND ALERTS The system responds to three kinds of trouble indications e A lockout is caused by a serious problem that might involve a safety issue Once the controller enters a lockout the burners will shut down and will not be allowed to run again until the cause of the problem is corrected and you reset the control system e The system may enter a hold for a period of time before locking out This allows the controller to see if the error becomes resolved prior to the hard lockout e An alert indicates that some feature of the control system s operation was not correct delayed or waiting for a response This does not necessarily indicate a problem If a problem occurs while the system is starting up the system will declare a Hold or Lockout
5. tuyau de gaz 9 Remplacer le panneau d acc s avant 10 R glez le thermostat la temp rature d sir e 11 R tablissez l alimentation lectrique l appareil 12 Si l appareil ne fonctionne pas suivez les directives relatives la fermeture de l alimentation en gaz et communiquez avec votre technicien de service ou le fournisseur de gaz FERMETURE DE L ALIMENTATION EN GAZ 1 Coupez toute alimentation lectrique l appareil si celui ci doit faire l objet d un entretien 2 R glez le thermostat au r glage le plus bas 3 D poser le panneau d acc s avant 4 Mettez la soupape d arr t de gaz OFF La valve est en position OFF lorsque la poign e se trouve angle droit du tuyau de gaz 5 Remplacer le panneau d acc s avant Page 6 BRADFORD WHITE SHUTTING DOWN THE BRUTE It may sometimes be necessary to shut down the Brute Here are the steps required to do this 1 Switch off the main electrical disconnect switch 2 Remove the front access panel and close the main manual gas valve 3 If freezing is anticipated drain the Brute Also be sure to protect the piping in the building from freezing The steps listed above may require qualified service personnel RESTARTING THE BRUTE It may be necessary to restart the Brute for example after a power interruption Here are the steps required to do this 1 Reset any errors using the user interface
6. User s Manual Doc 1267B User s Manual for Brute Modulating Boiler Water Heater Model BNTH1000 Model BNTV1000 1 000 MBTU h 1 000 MBTU h Model BNTH1200 Model BNTV1200 1 200 MBTU h 1 200 MBTU h FOR YOUR SAFETY This product must be installed and serviced by a professional service technician qualified in hot water boiler and heater installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty A WARNING If this Users Information A AVERTISSEMENT sicette Manual not followed exactly a fire or explosion information utilisateurs manuel n a pas suivi may result causing property damage personal exactement un incendie ou une explosion peut injury or death entra ner des dommages mat riels des blessures ou la mort Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or an P 4 i Ne pas entreposer ni utiliser d essence ni d autres other appliance ppu vapeurs ou liquides inflammables dans le voisinage de WHAT TO DO IF YOU SMELL GAS cet appareil ou de tout autre appareil eo et ane a RIA e QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ e Do not touch any electrical switch do not use any Ne pas tenter d allumer d appareils phone in your building e Ne touchez aucun interrupteur Ne pas vous servir e Immediat
7. Z Ne pas tenter d allumer d appareil Ne toucher aucun interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur appelez le service des incendies Page 4 BRADFORD WHITE LIGHTING THE UNIT l 2 3 4 Un 10 11 182 Gas inlet STOP Read the safety information on the previous pages first Set the thermostat to the lowest setting Turn off all electric power to the unit This unit is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand Remove the front access panel Turn OFF the manual gas valve The valve 1s off when the valve handle is at a right angle to the gas pipe Wait five minutes to allow any gas to clear Smell for gas Manual gas valve including the area near the floor If you do smell gas STOP shown in the Off position Follow Step B in the safety information listed above If you don t smell gas go to the next step Slowly turn the manual gas valve to ON The handle on the valve will be parallel to the gas pipe Replace the front panel Turn ON the electric power to the unit Set the thermostat to the desired setting If the unit will not operate follow the instructions in Turning Off the Gas to the Unit and call your service t
8. echnician or gas supplier TURNING OFF THE GAS TO THE UNIT l 2 3 4 Before doing any service work turn off all electric power to the unit Set the thermostat to the lowest setting Remove the front access panel Turn OFF the manual gas valve The valve is off when the valve handle is at a right angle to the gas pipe Replace the front panel Brute BOILERS AND VOLUME WATER HEATERS 1 000 amp 1 200 MBTU h Page 5 INSTRUCTIONS DE MISE EN MARCHE 1 ARRETEZ Lisez les informations de s curit sur les pages pr c dentes premiere Entr e 2 Coupez l alimentation lectrique de l appareil de gaz 3 R glez le thermostat a la temperature la plus basse 4 4 Cet appareil est dote d un dispositif d allumage qui allumera automatiquement le br leur Ne tentez pas d allumer le br leur manuellement O O LT 5 D poser le panneau d acc s avant 6 Mettez la soupape d arr t de gaz OFF La valve est en position OFF lorsque la poign e se trouve a angle droit du tuyau de gaz 7 Attendez cing minutes afin que le gaz se dissipe Si vous croyez sentir une odeur de gaz ARR TEZ Reportez vous aux instructions B ci dessus sur cette tiquette S il n y a pas d odeur de gaz passez la prochaine tape Valve de gaz manuel le se trouvant en position OFF 8 Remettez lentement la soupape d arr t de gaz en position ON La poign e sera parall le au
9. ely call your gas supplier from a des t l phones dans le b timent o vous vous trouvez neighbor s phone Follow the gas supplier s e Appelez imm diatement votre fournisseur de gaz instructions depuis un voisin Suivez les instructions du fournisseur e If you cannot reach your gas supplier call the fire e Si vous ne pouvez rejoindre le fournisseur de gaz department appelez le service des incendies L installation et l entretien doivent tre assures par un installateur ou un service d entretien qualifi ou par le fournisseur de gaz Installation and service must be performed by a qualified installer service agency or the gas supplier a BRADFORD WHITE H2360700B BRADFORD WHITE Brute BOILERS AND VOLUME WATER HEATERS 1 000 amp 1 200 MBTU h Page 1 CONTENTS Familiarizing yourself with the Brute l FOR YOUR SAFETY PLEASE READ THIS BEFORE OPERATING 2 What to Do If You Smell Gas 2 POUR VOTRE S CURIT LISEZ AVANT DE METTRE EN MARCHE un 3 Que Faire si Vous Sentez une Odeur de Gaz 3 Lonne ie Un e OS 4 Torning Off the Gas to the Unit 4 Instructions de Mise en Marche 5 Fermeture de l Alimentation en Gaz 5 Shutting Down the Brute osc ed 6 Rooca no NG BE A TAAA 6 In the Event of Power Failure 5 6 THE USER INTERFACE AND INDICATORS 7 About Lockouts Holds and Alerts 9 Cate Inspection ANG SO a 10 FAMILIARIZING YOURSELF WITH THE Brute User Interface Powe
10. llow the service instructions in the Installation and Operating Instructions Manual for the Brute Caution Do not use this boiler if any part has been under water Immediately call a qualified service technician to inspect the boiler Any part of the control system and any gas control which has been under water must be replaced WARNING If the unit overheats or the gas supply fails to shut off do not turn off or disconnect the electrical supply to the pump Instead shut off the gas supply at a location external to the Brute En cas de surchauffe ou si l admission de gaz ne peut tre coup e ne pas couper ni d brancher l alimentation lectrique de la pompe Fermer plut t le robinet d admission de gaz l ext rieur de l appareil FOR SERVICE Contact your installing contractor gas utility Bradford White dealer or check www Bradfordwhite com for the nearest authorized representative in your area Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement Si 3 AFTRA CERTIFIED CERTIFIED C US Low Lead Content NSF ANSI 372 H2360700B 200 Lafayette St Gress l BRADFORD WHI TE Middleville MI 49333 www BradfordWhite com Warranty 800 531 2111 Litho in U S A Bradford White 1509 Document 1267B
11. neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Brute BOILERS AND VOLUME WATER HEATERS 1 000 amp 1 200 MBTU h Page 3 POUR VOTRE SECURITE LISEZ AVANT DE METTRE EN MARCHE AVERTISSEMENT Quiconque ne respecte pas la lettre les instructions dans la pr sente notice risque un d but d incendie ou une explosion entra nant des dommages des blessures ou la mort A Cet appareil est muni d un dispositif d allumage qui allume automatiquement la veilleuse Ne tentez pas d allumer la veilleu manuellement B Avant de faire fonctionner reniflez tout autour de l appare l pour d celer une odeur de gaz Reniflez pr s du plancher car certains gaz sont plus lourds que l air et peuvent s accumuler au niveau du sol C N utilisez que votre main pour fermer la soupape d arr t de gaz N utilisez jamais d outils Si la poign e de la valve ne tourne pas manuellement ne tentez pas de la r parer Communiquez avec un technicien de service qualifi Le fait de forcer ou de tenter de r parer la poign e pourrait causer un incendie ou une explosion D N utilisez pas cet appareil s il a t plong dans l eau m me partiellement Faites inspecter l appareil par un technicien qualifi et remplacez toute partie du syst me de contr le et toute commande qui ont t plong es dans l eau QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GA
12. r Switch Pressure and Temperature Gauge Na Protective Cover wie slides downward i Manual Gas Valve Model 1000 Location of Components shown without jacket Page 2 BRADFORD WHITE FOR YOUR SAFETY PLEASE READ THIS BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This unit does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand B Before operating the unit check for any smell of gas in the area around it Be sure to smell next to the floor because some gas 1s heavier than air and will settle near the floor C Use only your hand to turn the handle on the gas valve Never use tools If the valve handle will not turn by hand don t try to repair it Call a qualified service technician If you force the valve or try to repair it this may result in a fire or explosion D Do not use this unit if any part has been under water Immediately call a qualified service technician to inspect the unit Any part of the control system or any gas control which has been under water must be replaced WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance or device that uses gas Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supplier from a
Download Pdf Manuals
Related Search
Related Contents
SpectraLink LINK 6020 User's Manual D-Link DCS-900 Network IP Camera La Lettre de Cairon n°65 "取扱説明書" Canon 9147B001 Digital Camera User Manual Caliber MPD109 Bedienungsanleitung (mehrsprachig) TEFAL FV3510C0 Instruction Manual Manuale tecnico centrale allarme Vedo 68 Copyright © All rights reserved.