Home
        (PDF 4.3 MB)
         Contents
1.                                                       7215 3100 63 1TD                NOTE       Always keep the user manual and installation    and servicing instructions with the boiler for  future reference              7215 3100 64 1TD          Fig  64 Refit casing       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    Buderus  45    Le  Inspection    3 Inspection    3 1 General directions     Do a visual and functional test of the installation     3 2 Preparing the boiler for inspection  e Disconnect the boiler from the mains power supply     DANGER OF FATAL INJURY     due to electric shock when system is  opened     e Before opening the system   Isolate the boiler at the dedicated electri   cal spur    e Ensure that the heating system cannot be  reconnected by accident       Remove the burner housing or cover from the heating  boiler     NOTE   i  If the gas supply pipes are to be disconnect     ed from the burner  the housing MUST ONLY  be removed by a qualified service technician  and checked for tightness on reassembly              Replace the following seals two yearly       Flat seal between the gas pipe and gas air unit       Seal ignition unit       Seal ionisation electrode       Seal heat exchanger       Burner seal      Fill out the Benchmark     3 2 1 Internal leak test  e Disconnect the boiler from the mains power supply     e Do not allow the product to come into contact with the  electrical wiring     3 2 2 Check the 
2.                                      e  Measure the working gas supply pressure              The working gas supply pressure should be between       a minimum of 17 mbar and a maximum of 25 mbar   nominal connection pressure of 20 mbar  for Natu        i  ral gas         a minimum of 30 mbar and a maximum 50 mbar 1 2     nominal connection pressure 37 mbar for LPG     7215 3100 57 1TD          e  Pull off the tube from the gas testing nipple        e Tighten the gas testing nipple screw  Fig  57 Gas valve    item 1  Gas valve closed    ATTENTION item 2  Gas valve open      If the required connection pressure is incor     rect  contact your gas supplier        Ensure that all disturbed joints and connections are  checked for gas tightness on completion of tasks                                                                 7215 3100 58 1TD             Fig  58 Measuring the gas supply pressure    Buderus    42 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements          2 1 7 Checking the gas air ratio and adjust as  required    Turn mains power switch to  0    gt  fig  56  item 1        Shut the gas shut off valve underneath the boiler    gt  fig  57  item 1                  e Ensure at least two radiators are open to hot water  flow     e Open the top measuring nipple   gt  fig  59  item 1  two  turns        e  Set the pressure gauge to  0               e Connect a tube from the     side of the pressure  gauge to burner pressure testing nippl
3.                             oA    TA                                              y  i    7215 3100 10 1TD             Fig  10 Pipe connections  Key to fig  6    CH flow  DHW outlet  Gas   MCW inlet  CH return    TEON T             A 7215 3100 11 1TD             Fig  11 Insert pipe       14 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    1 8 4 Hot water temperature    CAUTION       DO NOT use galvanised pipes or fittings     The hot water heat exchanger contains cop   per and can suffer from electrolytic corro   sion     Installation  a           Note       When using plastic pipes  observe the sup     plier   s instructions   especially those referring  to recommended jointing techniques and the  notes relating to the heating system water on  page 3        1 8 5 Condensate removal  Positioning and termination of the condensate  drain pipe    Warning       Any external run must be insulated with water    proof insulation     The condensate pipe should be run and terminate inter     nally to the house soil and vent stack or waste pipe  Alter     natively  the condensate can be discharged into the    rainwater system if connected to a foul water draining sys     tem  or into a purpose made soak away  condensate  absorption point      All connecting drainage pipework should generally have a  fall of at least 2 5   to the horizontal  or approximately 50  mm per metre of pipe run  If this is can not be achieved   consider the use of a conden
4.                          7215 3100 68 1TD          Fig  70 Remove restrictor baffle       48 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       e Replace the seal of the heat exchanger   gt  fig  71   item 1   The seal must be placed without tension and  cut at the proper length at the end of it    e Replace the 4 o rings   gt  fig  71  item 2   2 pieces at  each side                                                                    e Remove the old burner seal   gt  fig  72       Place a new burner seal                       Place anew flat seal between the gas pipe and the gas    valve   gt  fig  73   2e NN  e Reassemble in reverse order  aoe     Te                7215 3100 085 1TD       Fig  73 Place a new flat seal    Buderus    Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 49         4   Maintenance       4 2 Cleaning the condensate trap and  syphon  e  Remove the condensate trap   gt  fig  74 and fig  75                                                        7215 3100 69 1TD          Fig  74 Disconnect hose from condensate trap       e  Clean the condensate trap with tap water and a brush     If required  place a new lip seal   e Fill the condensate trap with water and reassemble     e Undo the condensate drain connection   gt  fig  74   item 1  and remove the syphon     e  Rinse and refit the syphon                             7215 3100 70 1TD          Fig  75 Remove the condensate trap    
5.                   7215 3100 18 1TD                                  Terminal position Maximum  Spacing  A  Directly below  above or alongside an  300 mm  opening window  air vent or other venti   lation opening  B  Below guttering  drain pipes or soil 200 mm  pipes  C  Below eaves 200 mm  D  Below balconies or a car port roof 200 mm  Not recommended   From vertical drain pipes or soil pipes  150 mm  F  From internal or external corners 300 mm  Above adjacent ground  roof or balcony  300 mm  level  H  From a surface facing the terminal 600 mm     From a terminal facing a terminal 1200 mm  J  From an opening in a car port  e g  1200 mm  door or window  into dwelling   Not recommended   K  Vertically from a terminal on the same  1500 mm  wall  L  Horizontally from a terminal on the wall  300 mm  M  Adjacent to opening 300 mm  N  Above intersection with roof 300 mm  O  From a vertical structure on the roof 500 mm                Fig  18 Flue terminal position    1 under carport    Danger    N Only use Buderus flue gas systems   As other flue gas systems are not tested with    this appliance     The flue must be installed in accordance with the recom     mendations of BS 5440 1 2000     Pluming will occur at the terminal so terminal positions  where this could cause a nuisance should be avoided     The air supply and the flue gas exhaust must meet the    applicable general regulations  Please consult the instruc     tions provided with the flue terminal kits prior to installa   tio
6.                 Tab  6 Gas injector diameter    Buderus  40 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       2 1 5 Adjusting the DHW flow regulator    Caution       It is important to adjust the flow of hot water     due to the resistance of the pipes in the in   stallation and the differences in water pres   sure     The DHW flow regulator is located on the bottom frame  of the boiler   gt  fig  55      e Adjust the DHW flow regulator  fig  55  to the desired  setting         To increase the flow of hot water   turn valve clockwise                 To reduce the flow of hot water   turn valve counterclockwise             Factory setting   10 I min of 48   C  assuming that the DHW cold is 10   C  and there is a pre pressure of 2 5 bar     2 1 6 Measuring the gas supply pressure   flow pressure     There are two ways to measure the gas supply pressure         measuring the standing gas supply pressure  boiler not  in operation          measuring the working gas supply pressure  boiler  operating at full power         NOTE       The difference between the standing and    working pressure may never be greater than  5 mbar  If the difference between the two is  greater than 5 mbar then the pressure loss in  the gas pipe is too great        Measuring the standing gas supply pressure       Take the boiler out of service by pressing the mains  switch   gt  fig  56  item 1  to  0         Close the gas shut off valve   gt  fig  57  item 1    e 
7.    7215 3100 066 2TD          Fig  67 Remove connectors of the gas air unit    Buderus  Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 47         4   Maintenance    e Remove the glow ignitor   gt  fig  55  item 1  and ionisa     tion electrode   gt  fig  55  item 2         Mount a new glow ignitor with mounting plate and nut     e Mount the old ionisation electrode with a new seal   mounting plate and nut     e By turning the unit a quarter turn   gt  fig  69  step 1   the  unit can be removed by lifting it out of the boiler    gt  fig  69  step 2        e Clean the burner when necessary  The burner may only  be cleaned with a soft brush or compressed air     Caution    N Replace the burner seal after removing the    burner from the gas air unit     e  Now the front cover of the heat exchanger can be  removed by opening the latches   gt  fig  65  item 1      e  Remove the restrictor baffle from the heat exchanger    gt  fig  70  item 1       Inspect the heat exchanger  When required  clean the  heat exchanger with a soft brush or compressed air     NOTE   x  Only when a heat exchanger is heavily soiled    is it recommended to drain the system  to re   move the heat exchanger for cleaning        e  Check the seal for damage  Always replace the seal if  in doubt     Buderus             1 7215 3100 082 1TD          Fig  68 Remove the glow ignitor and ionisation elec                                      Fig  69 Remove gas air unit            
8.   9  onto the upper wall spacing    frame bracket     1 7 Water circulation system    The central heating system should be installed in accord     ance with BS 6798 and  in addition  for smallbore and  microbore systems  BS 5449 or EN 12823                                      7215 3100 08 1TD       Fig  8 Mounting the manifold                                                                                     1    7215 3100 09 1TD          Fig  9 Hanging the boiler    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    13    EE Installation    1 8 Pipe connections      Connect pipes as shown in fig  10  Ensure that all pipe   work is routed so as to minimise any strain on the boiler  fittings     The first 600 mm of pipework must be in copper  then  another approved material type can be used     CAUTION    N Do not use galvanised radiators or pipes     1 8 1 Gas supply    The gas installation must be installed in accordance with  BS 6891     CAUTION    N Pipework from the meter to the boiler MUST    be of adequate size  generally 22 mm     The complete installation MUST be tested for gas tight   ness and purged as described in IGE UP 1b     1 8 2 Gas connection    e Connect to gas supply according to relevant stand   ards     1 8 3 Compression fitting pressure relief valve  outlet    e Insert the small piece of pipe   gt  fig  11    e Attach the compression fitting   gt  fig  12      Buderus                 N        DA   E   
9.   Subject to modifications resulting from technical improvements 9    EE Installation       1 4 Items supplied with unit      Check the contents against the packing list to ensure  that nothing is missing                                            7215 3100 03 1TD             Fig  3 Items supplied with unit  Key to fig  3     Wall mounted condensing gas boiler   Wall bracket   Manifold Assembly   Wall spacing frame   Bracket for ModuLink 250 RF   Technical documents    1 x Installation and maintenance manual   1 x User manual   1 x Wall mounting template   1 x Benchmark Logbook   1 x Warranty card   1 x Envelope for Warranty card   7  Plastic bag containing the following accessories   4 x wall fixing screws   4 x wall plugs   4 x washers   4 x push fit rivet for wall spacing frame   2 x rubber stops for wall spacing frame   3 x cable clamp   top part   6 x cable clamp   fixing screw   Seals  1 x G2      1     2 x 34    22 mm  2 x Yo    15 mm   1 x MCW inlet filter   Initial start up sticker   Second identification plate   Pressure Relief Valve compression fitting   brass insert  Radiator key    Se oN    Buderus    10 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       1 5 Hanging the boiler    Note   i  Pipework from the boiler is routed down     wards as standard  but may be routed up   wards behind the boiler using the wall   spacing frame  supplied with the boiler     If using the supplied wall spacing frame  fol   low the procedure i
10.   button     service    button  display      menu    button  adjusting arrow up  adjusting arrow down    No oh OD         7215 3100 50 1TD       Fig  50 DBA with open ended spanner    7215 3100 51 1TD             Fig  51 DBA display Lo    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 37       E  Commissioning    The boiler operates at full load when the Service button  is pressed again  An open end spanner D appears  in the top left hand corner of the display     Press the  A  button if you want to make sure that the  boiler is actually operating at full load   Hi  appears in the  display   gt  fig  52      The boiler returns to regular operation when the Service  button is pressed once again or after the boiler has  operated at partial  or full load for 30 minutes     4  Display   gt  fig  49    Setting  adjustments and fault codes are displayed on the  DBA  see fig  53     5  Menu button      gt  fig  49     The menu button    allows you to scroll through the menu  items     Press the    button once  to display the current warm start  function setting     Press the    button twice to display the current  DHW temperature setting     Press the    button three times to display the current  setting of summer operation     Press the    button four times to display the current  CH flow temperature setting     6  and 7  Up      and Down   keys   gt  fig  49     These keys can be used for adjusting temperatures and  activating or
11.   gt  fig  32      e Using a screwdriver  remove the grey 230V cover    gt  fig  38  item 1      The grey 230V cover houses one fused circuit board   The board has four terminals   gt  fig  39        Lout     LR  N     Nour     SPARE   Lour  amp  Nour are optional LIVE  amp  NEUTRAL supplies from  the boiler which are isolated via the on off power switch    on the front of the DBA  If required  these can be used to  power a third party 230V thermostat   programmer etc     Alternatively 230V controls can be powered from a sepa     rate mains supply external to the boiler  i e  Loyt  amp  Noyt  terminals are not used      Installation  a                           7215 3100 37 1TD       Fig  37 Room thermostat connection on DBA    1 2 Room Thermostat  3 HW Tank Sensor  5 24VAC   6 7 3 Way Valve       7215 3100 38 1TD             Fig  38 Room thermostat connection on DBA    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 29    ai  Installation       Using a separate supply is not recommended as the third  party controls will not be isolated by the power switch on  the front of the DBA  although in some replacement instal   lations this may be unavoidable        230V controls must be from the same fused  spur that supplies the boiler  described in  subsection 1 10      a  The direct external mains supply to third party       Lptn must be connected with the live return   switched  live signal from the third party 230V controls     
12.   set of 10 pc   78152s     Screw 4 x 20 Hydroframe 78179s  80   O ring 73 x5 78177  set of 5 pe    81   O ring 48 9 x 2 62 78178     Screw M5 x 30 Pump 78180s  F  set of 5 pc     82   O ring  set of 10 pc   78157s  83   Screw   screwcase 78181s    set of 2 pc    84   Drain plug 78139  85   CH return pipe 7746900067  86   O ring  set of 10 pc   38472s  87   34  Seal  set of 10 pc   15002s  88   O ring  set of 10 pc   38478s  89   Cover seal 78174  90   Seal 73561  91   O ring  set of 2x2 pc   73642s  92   Seal  set of 10 pc   8718600045  93   1  Seal  set of 5 pc   73527s  94   Casing lock 73901  95   Cut off cock with pressure 78150   gauge  96   Valve Sanitary Hot 75962  97   Gas valve 78201  98   Valve Sanitary Cold 75963  99   Valve CH return 75964  100   Spring  set of 5 pc   73490s  101   Spring Hydroframe 78164s    set of 5 pc    102   1   2  Seal  set of 10 pc   15033s  103   1  Seal  set of 5 pc   73527s  104   Connection set combi 73784  105         Buderus  56 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements          Appendix 5     Exploded view Combi unit  Buderus 500 24C  500 28C                                                                                                                                         agar   gt   101  Ss    100                                                                                                                                              7215 3100 075 3TD             Buderus  Buderus 500
13.  24C 28C   Subject to modifications resulting from technical improvements 57       Notes       Buderus  58 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    Notes       Buderus  Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 59    Buderus  Cotswold Way  Warndon  Worcester WR4 9SW    Customer Services  0870   421 5933  Technical Product Support  0870   421 5944  Fax  01905   753 130    www buderus co uk    In the UK and IE  Buderus is a brand name of Bosch Thermotechnology Ltd     721 531A 0010    Buderus    
14.  CHR   Central Heating Return  DHW   Domestic Hot Water   JB   Junction Box RTh Relay  LSV   Lock Shield Valve   MCW   Mains Cold Water   PL   Permanent Live   PRT   Programmable Room Thermostat    Volt Free Contacts    T   Timer   TRV   Thermostatic Radiator Valve  Buderus       33 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       E  Commissioning    2 Commissioning    When a boiler starts up there are a couple of things that  happen  Below is a short process description     When there is a heat demand   The fan starts up and the glow ignitor turns on     When there is a DHW request then the three way valve  switches from CH operation to DHW operation     The pump starts up as soon as the three way valve is in  the right position     Once all the requirements are met  glow ignitor is hot  enough  fan is operating at the correct speed and the  pump is on  then the gas valve will open     A flame may or may not develop  but regardless of that  fact  the glow ignitor extinguishes  The operating controls  are released once a flame is sensed  After a possible  check  the boiler will deliver the requested output     Should the flow check fail  the boiler will shut down for a  short while and then try to start up again     If no flame develops then the gas valve closes and the fan  continues to run for a while to purge the appliance  The  boiler will try to start up three times  If no flame develops  after three attempts the boiler will lock
15.  Heating curve 40 30   C kW 6 0   24 0 6 0   24 0   Seasonal efficiency  SEDBUkK    for natural gas   90 0 90 0   for LPG   92 3 92 3   Max  gas rate for heating m h 2 43 2 43   Max  gas rate preparing hot water m3 h 2 43 3 02   Central heating installation   Heating water temperature   C 30   80 30   80   AT at residual head of 200 mbar   C  lt 20  lt 20   Max  operating pressure of boiler bar 3 0 3 0   Pump over run time min 5 5   Expansion vessel   Capacity of expansion vessel   7 5 7 5   Admission pressure of expansion vessel bar 1 0 1 0   Plate heat exchanger   DHW flow rate at 35   C rise l min 9 4 11 7   Adjustable hot water temperature   C 40   60 40   60   Minimum connection pressure bar 0 8 0 9   Maximum connection pressure bar 10 0 10 0   Pipe connections   Maximum connection pressure    mm 22   CH flow return  compression fitting     mm 22   MOW inlet   DHW outlet  compression fitting     mm 15   Condensate water outlet    mm 21 5   Pressure relief valve  compression fitting     mm 15  adapter supplied with boiler        Buderus       6 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       Installation aT        500 Series wall mounted condensing gas                                                                                  Description Unit combi boiler  500 24C 500 28C   Flue gas values   Condensate water quantity  natural gas  40 30   C l h 1 6 1 6   Exhaust fume mass flow rate   Full load g s 10 6 10 6   Part load g s 
16.  Set the pressure gauge to  0    e Loosen the gas test nipple screw two turns        Attach a tube from the pressure gauge to the gas test  nipple  the lower one   gt  fig  58  item 2      e  Slowly open the gas shut off valve   gt  fig  57  item 2    e Measure the standing gas supply pressure    e  Pull off the tube from the gas test nipple      Tighten the gas testing nipple screw       Tighten the gas testing nipple screw           7215 3100 55 1TD             Fig  55 DHW flow regulator                                           7215 3100 56 1TD             Fig  56 DBA front    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 41    E  Commissioning    Measuring the working pressure       Take the boiler out of service by pressing the mains  switch   gt  fig  56  item 1  to  0      Close the gas shut off valve   gt  fig  57  item 1    Set the pressure gauge to  0      Loosen the gas test nipple screw two turns     Attach a tube from the pressure gauge to the gas test  nipple  the lower one   gt  fig  58  item 2      Slowly open the gas shut off valve   gt  fig  57  item 2         e Ensure at least two radiators are open to hot water    flow     e Set the mains switch   gt  fig  56  item 1  to  1     oO 0    e  Create a heat demand by pressing the service     button   gt  fig  56  item 2   until an open ended    spanner D appears in the top left hand corner of the    i          display  l                                       
17.  de activating certain summer operation     The  A  key  when pressed  gives the current operating  status of the boiler  Press the  A  key once to display the  current DHW flow in l m     Setting the warm start function  e Press the menu button once     e Use the      and    keys to turn the warm start func   tion on or off   Factory setting  warm start function is  on      Buderus       7215 3100 52 1TD             Fig  52 DBA display Hi          7215 3100 53 1TD          Fig  58 DBA display       Setting Meaning       More energy efficient  less  chance of calcification  longer  waiting periods     rol  ECO     cold start       Maximum comfort due to short  waiting period for warm water   Not as energy efficient as the  cold start and there is more      comfort    warm start          chance of calcification        Tab  4  Warm start function       38 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements          Setting the domestic hot water  DHW  temperature  e Press    button twice then adjust the DHW tempera   ture to the desired temperature  40   C   60   C  using  the  A  and  A  keys   gt  fig  54  item 1    Factory setting is 48   C     Setting the boiler to summer operation   When you want to make sure that your boiler will not oper   ate for central heating in the summer then you can set the  boiler to summer operation  The boiler will then only oper   ate for DHW     e Press the    button   gt  fig  54  item 2  three times   The cu
18.  each other  F The contacts of the KIM  EEPROM on  or there is a short circuit to earth the DBA control panel circuit board  may   ground   or the flow or safety sensor has be loose or short circuited   detected a CH flow temperature of      above 130   C  r E Reset is carried out   This code appears after the reset  P The contacts of the flow sensor or safety button    is pressed for 5 seconds   sensor are broken   Buderus  52 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements          Appendix  ey    5 2 Wiring diagram    Warning       Do not connect 230 V to the connection block on the back of the DBA                                                                                                                                                                                                                                                                                                                                                                   7 pees oo   oe erg  O0000000000000000 e0000000000000000  E AP     i             Tf fr    D  C0    SS      Ta  gt  S    JP1 T JP4 Ta     iS    S sS f    E  amp   MCs 8     S a a6 aS a  j High voltage DBA Low voltage  X a  MAINS SWITCH  i T i  i 20   A    s lh    R MAINS  230 VAC 50 Hz  N  HOL     f S        3    22l     HN uw o   45  L 5    i _JP1       DBA  J       Ste  flue gas      ermosta  1  ENO     Q Switch contact   i    i 3 WAY VALVE  do not  8 bX S   ovac   II use for 500 24C and 28C   a
19.  l   Il  OON i   24 VAC    z 2 3     l i 24 VAC      DX    ok Nees wy i HW TANK SENSOR  do not    O use for 500 24C and 28C   2        JP4 ROOM THERMOSTAT OR  i D ui   i MODULINK 250 RF  ERRO  O    LO       15  S  o  Flow sensor          JP3  Safety sensor i  Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       5  Appendix    IMPORTANT  The wires in this mains lead are coloured in accordance with the following code     GREEN AND YELLOW   EARTH    BLEU   NEUTRAL    BROWN   LIVE    As the colours of the wires in the mains lead of of the appliance may not correspond with the coloured markings identi   fying the terminals in your connector proceed as follows     The wire coloured green and yellow must be connected to the terminal on the connector marked with the letter E or by  the earth symbol or coloured green or green and yellow  The wire coloured brown must be connected to the terminal  marked with the letter L or coloured red  The wire coloured blue must be connected to the terminal marked with the letter  N or coloured black     WARNING  THIS APPLIANCE MUST BE EARTHED    Ensure that your appliance is connected correctly   if you are in any doubt consult a qualified electrician     For location of individual components  see service section and the exploded views in this manual     5 3 Residual pump lift    This graphic shows the amount of pump lift remaining for  the heating system        400       350    300             25
20.  leak detector to check all connections  for possible escapes  The product must be certified as  a gas leak testing agent  DO NOT allow the product to  come into contact with electrical wiring     The test pressure of the gas pipe when the gas shut off  valve is open may not exceed 150 mbar     Warning  ATTENTION   N Check the used measuring nipples for gas    tightness        2 1 4 Checking the gas type     lt n l Type of gas   Factory settings of gas burners  Ensure that the boiler is set up to run on the gas type avail        Natural gas   When delivered ready for operation and  set to Wobbe index 14 1 kWh m    referred to 15   C  1013 mbar   appli     able  If this is not the case  then the boiler must not be put  into operation        e Check the gas type with your gas supplier and com  cable for Wobbe index range 11 3 to  pare this to the boiler s gas type as registered on the 15 2 kWh m3  Inscription on gas type  identfication tag   gt  table 6   indicating label    It is possible to change the boiler to another gas type Category setting  2H G 20_20 mbar     gt  table 5   This accessory can be ordered from your LPG After adaptation by a CORGI regis    supplier  tered installer  the unit can be run on   LPG  Inscription on gas type indicating  label        Category setting  3P G 31_37 mbar       Tab  5 Gas supply types             Gas injectors     Type of gas  mm  Venturi  Buderus 500 24C 28C tubes  Natural gas H  G20    4 45 4 45 Standard  LPG 3 45 3 45 Standard      
21.  out     When the heat demand stops   The gas valve closes   The fan will run for a short time to purge the appliance     The pump will continue to run for a short time to disperse  any remaining heat energy from the boiler into the heating  system     If there has been a heat request  then the three way valve  will switch back to the central heating setting     Follow the steps described in this chapter to properly  commission the boiler and fill out the commissioning log  book     NOTE   i  If a fault occurs  then refer to the servicing    manual or contact Buderus           Buderus  34 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       2 1 Preparing the boiler for operation    Caution       DO NOT operate the condensing gas boiler    if large amounts of dust are present  e g  due  to building work in and around the place of  installation     2 1 1 Fill the heating system    Caution   A The wall mounted condensing gas combi  boiler must not be activated at this stage      a  NOTE    ter and domestic hot water on page 3 care   fully        Please read the notes on heating system wa   e Loosen the automated air vent one turn   gt  fig  43    e  f necessary open the CH flow and CH return servicing  valves   gt  fig  44  item 1 and 2      e Connect filling loop   gt  fig  45    e Open both stop valves   gt  fig  45      e Fill the system to a pressure of approx  1 5 bar    gt  fig  44  item 3      e Close both stop valves     e  Vent the 
22.  rooms    Key to abbreviations     CB   Connection Block   CHF   Central Heating Flow   CHR   Central Heating Return  DHW   Domestic Hot Water   JB   Junction Box   LSV   Lock Shield Valve   MCW   Mains Cold Water   PL   Permanent Live   RT   Room Thermostat   RV   ModuLink 250 RF Receiver  TRV   Thermostatic Radiator Valve  Buderus       31 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       EE Installation    Buderus 500 24C or 500 28C with external 230V controls                          a2                         7215 3100 41 1TD       Fig  41    1 Condensing gas boiler 500 24C   28C  2 radiator   3 reference room   main living area   4 other rooms    Key to abbreviations     CB   Connection Block  CHF   Central Heating Flow  CHR   Central Heating Return  DHW   Domestic Hot Water  JB   Junction Box  LSV   Lock Shield Valve  MCW   Mains Cold Water  PL   Permanent Live  RT   Room Thermostat  T   Timer  TRV   Thermostatic Radiator Valve  Buderus       32 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       Ea Installation    Buderus 500 24C or 500 28C with external Volt Programmable Room thermostat                                    TRV M  D E   PHU unimu    LSV                         7215 3100 42 1TD       Fig  42    1 Condensing gas boiler 500 24C   28C  2 radiator   3 reference room   main living area   4 other rooms    Key to abbreviations     CB   Connection Block   CHF   Central Heating Flow  
23.  the wall spacing  brackets and hang this on the wall bracket   gt  fig  6                        7215 3100 06 1TD             Fig  6 Hanging the wall spacing bracket       e  Mount the two strips on the upper and lower wall spac   ing brackets using the snap rivets   gt  fig  7    The lower wall spacing bracket is fitted upside down CSN  compared to the upper wall spacing bracket  ie  with  the hooks facing down       Attach this lower wall spacing bracket to the wall                                o               ae    7215 3100 07 1TD                         Fig  7 Mounting the lower bracket    Buderus    12 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       e  Mount the lower bracket on the wall and attach the  manifold assembly  If the manifold does not sit flat     check the orientation of the lower wall spacing bracket      gt  fig  8        Make the pipework connections to the manifold   See also subsection 1 8     e Open the case locking mechanism  using a radiator key      gt  fig  5  item 1   The radiator key is included in the  delivery of the boiler  in the accessory bag     e  Remove the boiler case       Remove the polystyrene foam piece from the top of the    boiler     Installation  a           Note       If the boiler is not to be connected the pipe     work immediately  then place caps on the  pipe connections          Connect the manifold unions to the boiler  using the  seals supplied     e Hang the boiler   gt  fig
24.  water treatment  only products  suitable for use with Buderus heat exchang   ers are permitted  e g  Sentinel X100     Your warranty is at risk if an incorrect water  treatment product is used in conjunction with  this appliance    For more information  contact Buderus Tech   nical Product Support Department    It is most important that the correct concen   tration of the water treatment product is  maintained in accordance with the manufac   turer s instructions    If the boiler is used in an existing system any  unsuitable additives MUST be removed by  thorough cleaning  BS 7593 details the  steps necessary to clean a domestic central  heating system     Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 3    E Regulations and directives    Warning  In hard water areas  treatment to   N prevent lime scale may be necessary   how    ever  the use of artificially softened water is   NOT permitted    Under no circumstances should the boiler be   fired before the system has been thoroughly   flushed    Do not use artificially softened water    When using plastic pipes  then they must   contain a polymeric barrier    It is allowed to use copper for the first 600   mm  See also subsection 1 8     Pipe connec    tions    in this manual          The domestic hot water service must be in  accordance with BS 5546 and BS 6700     e The boilers are suitable for connection to  most types of washing machine and dish   washer appliances     
25. 0       200             150                                                       100 i  50    0 i  0 100 200 300 400 500 600 700 800 900 1000  4 7215 3100 74 1TD  Fig  78    1 Buderus 500 24C and 500 28C series  2  Residual pump lift  mbar    3  275 mbar at 900 I h   4  Flow  l h     Buderus  54 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       5 4    Spare parts list    Appendix  Fe     The following are parts commonly required due to damage or expendability  Their failure or absence is likely to affect  safety or performance of this appliance  For a pictorial representation of the part see the respective position number on    the exploded view pictures on page 57                                                                                                                                                                                                                    Description Product No   1   Casing 78155  2   Bracket 38092  3   Grommet cover 78145  4   Fan 73639  5   Fan seal  set of 5 pc   73640s  6   Gas injector 2E 73210  7   Gas valve 73645  8   Venturi 73641  9   50mm seal 73574  10   Air silencer tube 73646  11   Gas air supply valve 73756s  12   Syphon 75986  13   Service set GLE complete  also   7746900411  includes item 5  11  14  16  23   24  25  27  68 and 92   14   Burner seal  set of 2 pc   8718600197  15       16   Heat exchanger   Gas air supply 73728  seal  17   Backside heat exchanger 8718600023  18   Gasket 
26. 2 mm      403 8 mm     A  7215 3100 76 1TD  A  outside edge frame  1  CH flow      22 mm  compression fitting  Note  2  CH return      22 mm  compression fitting  See wall mounting template for the neces   3  DHW outlet      15 mm  compression fitting  sary clearances   4  MCW inlet      15 mm  compression fitting  The wall spacing frame may not always be  5  Gas   Gas connection    22 mm  compression fitting  necessary   6  CDO  Condensate drainage outlet    21 5 mm  7  PRV   Pressure relief valve    15 mm  compression fitting   Buderus  8 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    1 3 Boiler locations and clearances    Bathroom Installations  This appliance is rated IP X4D     The boiler may be installed in any room or internal space   although particular attention is drawn to the requirements  of the current IEE  BS 7671  Wiring Regulations and  in  Scotland  the electrical provisions of the building regula   tions applicable in Scotland  with respect to the installa   tion of the boiler in a room or internal space containing a  bath or shower  If the appliance is to be installed in a room  containing a bath or shower then  providing water jets are  not going to be used for cleaning purposes  as in commu   nal baths showers   the appliance can be installed in  Zone 3  as detailed in BS 7671     Compartment Installations    A compartment used to enclose the boiler should be  designed and constructed especially for this purpose  A
27. 4 3 4 3   Exhaust fume temperature  full load   Heating curve 75 60   C   C 77 77   Heating curve 40 30   C   C 55 55   Exhaust fume temperature  partial load   Heating curve 75 60   C   C 60 60   Heating curve 40 30   C   C 35 35   CO  full load  natural gas   standard test gas G20   9 2 9 2   CO  full load  natural gas   standard test gas LPG   10 3 10 3   Standard emission factor CO mg kWh  lt 22  lt 22   Standard emission factor NO  mg kWh  lt 30  lt 30   Flow pressure available for use Pa 75 75   Flue gas system   Type of exhaust fume connection C13 x   C x   C53 x  C73 x    Diameter of flue take off mm Concentric 60 100   Electrical data   Mains connection voltage  50 Hz  V 230   Electrical power consumption   Full Partial load Standby W 110 88 4   Electrical protection rating IP X4D   Boiler dimensions and weight   Height x Width x Depth mm 780 x 460 x 330 780 x 460 x 330   Weight  without casing  kg 31 31   Weight  without casing  kg 3 3   Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    EE Installation                                                                                                                                              1 2 Dimensions  connections and assembly  8 mm 330 mm 35 mm       460 mm 150 mm  E  E  5 mm   5mm a  1  A  f 3  V4  a  Le  YY  E       fo       N     E  A  E 1       3 4  70 mm    a     152 mm  1 2 5  85 mm z  157 mm   162 mm  7  93 mm  a z  ppc    6  108 mm  282 mm   287 mm  35
28. 7215 3100  05 2009  GB IE    Installation and maintenance  instructions       Buderus 500 24C  Buderus 500 28C    aay Fee S   benchmark     Gas wall hung Boiler  condensing       For the installer    Please read thoroughly    Buderus    E Contents                               Contents Preface  Important general instructions  Regulations and directives 3 The appliance is designed exclusively for heating water as  part of a domestic central heating and or hot water sys   Hazard definitions and abbreviations 5 tem  Do not use the appliance for any other purpose   Installation  maintenance and repair must be carried out  by a competent engineer  e g  CORGI registered   Only  1 Installation 6 use the boiler in conjunction with Buderus accessories  1 1  Technical specifications 6 and spares  Other accessories and consumables may be  1 2 Dimensions  connections and assembly 8 used if they are expressly provided for the designated use  i3  Beilerlossticns snd eisarances 9 and if system performance and safety are not affected in  1 4 Items supplied with unit 10 anyway   1 5 Hanging the boiler 11 The boiler is suitable for connection to fully pumped   1 6 Install the wall spacing frame 12 central heating systems ONLY   1 7 Water circulation system 13  1 8 Pipe connections 14    1 9 Flue installation 19  henchmen J  1 10 Electrical connections 25  1 11 External controls 26 BENCHMARK  Log Book  112 System i a a All Buderus gas fired boilers include an installation  com   missioning and 
29. Buderus  50 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements          4 3 Cleaning or replacing the plate heat  exchanger  e Disconnect the boiler from the mains power supply     e Drain the system   gt  page 36      e  Remove the condensate trap and the syphon    gt  page 36      e  Remove the two screws of the plate heat exchanger    gt  fig  76      e Remove the plate heat exchanger   gt  fig  77      e Hook up a descaling device and clean the plate heat  exchanger     e  Thoroughly rinse the plate heat exchanger before reas   sembly       Replace the o rings when necessary     Open a hot water faucet to rinse and purge the system        Close the hot water faucet and reconnect the boiler to  the mains supply                                7215 3100 71 1TD             Fig  76 Remove screws of plate heat exchanger             7215 3100 72 1TD             Fig  77 Remove plate heat exchanger    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 51    5  Appendix    5    Appendix                                                                                                       5 1 Fault codes   Code Key to display code Code Key to display code   o 4 The flow sensor or safety sensor has B H After four startup attempts  the system  detected that the current CH flow tem  has detected insufficient ionisation cur   perature is higher than 95   C  rent    i C The flue gas STL  flue monitoring devi
30. G  Notes related to domestic hot water       When connecting to suitable showers  en   sure that   a The shower is capable of accepting  mains pressures and temperatures  up to 65   C   b The shower is ideally thermostatic or  pressure balancing       Where temporary hardness exceeds  150 mg litre  it is recommended that a  proprietary scale reducing device is fitted  into the boiler cold supply with the require   ments of the local water company        Caution      Provision must be made to accommodate  the expansion of DHW contained within the  appliance  where a back flow prevention de   vice is fitted BS  67989    5 4 3     Safe handling of substances    No asbestos  mercury or CFCs are included in any part of  the boiler and its manufacture     Buderus    4 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       Hazard definitions and abbreviations is    Hazard definitions and abbreviations    Hazard definitions    Danger     Indicates the presence of hazards that will  cause severe personal injury  death or sub   stantial property damage     Warning    Indicates the presence of hazards that can  cause severe personal injury  death or sub   stantial property damage     Caution   Indicates presence of hazards that can    cause minor personal injury or property dam     age        e Be a Oa    NOTICE    Indicates special instructions on installation   operation or maintenance that are important  but not related to personal injury or proper
31. Spare is a terminal not connected to the circuit board and  can be used as a connection point     There are two strain relief clamps  The clamps are sup   plied in the accessory bag  on top of the boiler                 The underside of the grey 230V cover contains a holder Hee eae wD  for a spare fuse  Only 2 5 Ampere slow blow silica filled Fig  39 Connection box   230 Volt connection  fuses should be used   1 Nout     Tighten the strain relief clamps to secure the cables  F w    Replace the grey 230V cover  4 Spare    e Raise and secure the Boiler Control Unit  DBA    e Refit the boiler casing if necessary   gt  fig  5      1 11 3 Volt free external control device connection      Remove the securing screw of the DBA and lower the  DBA   gt  fig  32        Connect the wire to terminal 1 and 2 of the connection  block  marked Room Thermostat   gt  fig  37      Buderus  30 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       EE Installation    1 12 System examples       NOTE       These system schematics are simplified heating schematics showing the main electrical and water connec   tions        Buderus 500 24C or 500 28C with ModuLink 250 RF  or other Buderus controls                                           TRV A   gt  lt  EW  MCW PHU    LSV                         7215 3100 40 1TD       Fig  40    1 Condensing gas boiler 500 24C   28C  2  RT programmer   3   ModuLink 250 RF   4 radiator   5 reference room   main living area   6 other
32. W inlet  CH return  drain  drainage hose    oahwh                                    Se l A TT i  J  i T  Z 2 S pi TENN a          7215 3100 47 1TD             Fig  47 Disconnect hose from condensate trap                                  7215 3100 48 1TD       Fig  48 Remove the condensate trap and fill with water       36 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       2 1 2 DBA adjustments    The boiler is equipped with a boiler control unit  DBA    This is the internal control of the boiler  The DBA is  located behind the access panel     The DBA allows you to operate the boiler and to make  adjustments in its settings     DBA overview   1  Mains switch   gt  fig  49   Use this switch to turn the boiler on or off     2  Reset button   gt  fig  49     When a blinking code is in the display  it is possible to try  and restart the boiler by pressing this button        NOTE       It is not possible to reset the boiler when    there is no fault code blinking in the display        3  Service button   gt  fig  49     The boiler will operate on partial load when the Service  button is pressed once  An open ended spanner I  appears in the top left hand corner of the display     gt  fig  50      Press the  A  button if you want to make sure that the  boiler is actually operating at partial load   Lo  appears in  the display   gt  fig  51                                    7215 3100 49 1TD             Fig  49 DBA    mains switch      reset  
33. air from all radiators starting with the lowest  radiator and working up to the highest point     e  Check the pressure after venting  If the pressure has  dropped under 1 0 bar then top up the system as  described previously     e Disconnect the filling loop and cap off                                                           m 7215 3100 43 1TD       Fig  43 Automatic air vent                                                                   7215 3100 44 1TD          Fig  44 Servicing shut off valves    AUN      CH flow  DHW outlet  Gas   MCW inlet  CH return                7215 3100  45 1TD       Fig  45 Connecting filling loop    AUN      MCW inlet   stop valve   double check valve  filling loop   CH return    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 35    E  Commissioning    To drain the boiler take the following steps     Close the MCW inlet and the CH return valve     e Connect drainage hose   gt  fig  46      e Close the CH return and CH flow valves     e Connect draining hose to draining point on the mani     fold   gt  fig  46  item 1      e Open draining point to drain the boiler   gt  fig  46   item 1      Fill the condensate trap    e  Remove the condensate trap and fill with water    gt  fig  47 and fig  48      Buderus                     a    JU 3  2                                                                            7215 3100 46 1TD          Fig  46 Draining the boiler    stop valve  CH flow  MC
34. ce  C The system has detected an ionisation  or the burner thermostat has detected current before burner startup or an ioni   too high a temperature and has been sation current has been measured as  opened  soon as the burner shuts down    g F The flow sensor and safety sensor have  L The flame goes out during the operating  after burner startup  not detected any phase   temperature increase in the heating 7 C The power supply was shut off during a  water  or they have determined that the crucial breakdown   temperature difference between the flow      sensor and safety sensor is too high  q A The DBA control panel is defective    P  The flow sensor has detected a tempera  F The contacts of the gas valve have been  ture increase  in the heating system broken   water  of over 5   C sec  H The DBA control panel is defective      A The tacho signal from the fan has failed L The contacts of the gas valve have been  during the operating phase  broken or the DBA control panel is  L The tacho signal from the fan is not defective   present during the preoperative or oper  P The DBA control panel is defective   ating phase or there is no current of air 4 Short circuit in the gas valve   after a certain time  E 7  y The fan runs too slowly or too fast   4 H The flow sensor and safety sensor have  detected a CH flow temperature of over J The DBA control panel is defective   105   C  4  E The sensor test has failed  A  L The contacts of the flow sensor and G  safety sensor are shorted to
35. combustion chamber and heat  exchanger for contamination    3 2 3 Check the burner    3 2 4 Check the functioning and safety of the flue  gas exhaust    3 2 5 Check the pre pressure of the expansion  vessel    3 2 6 Check the programming of the room ther   mostat    Buderus  46 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       4 Maintenance    NOTE       The described cleaning of the burner and    heat exchanger is only necessary when the  boiler is heavily contaminated  Otherwise it is  sufficient to clean the burner and heat ex   changer with a soft brush or compressed air  without disassembling them              4 1 Cleaning the heat exchanger and  burner      Switch the boiler off by setting the mains switch to  0     gt  fig  56  item 1                        e Close the gas shut off valve   gt  fig  57  item 1           Unlock the securing screw with a radiator key and  remove the casing     e  Loosen the gas connection between the gas supply a  and the gas air unit   gt  fig  65         7215 3100 65 1TD                   Replace the flat seal between the gas pipe and the gas  air unit   gt  fig 66            7215 3100 081 1TD                e Remove the connectors   gt  fig  67  item 1  2 and 3   from the gas air unit    e  Remove the air silencer from the gas air unit   gt  fig  67   item 4       Then remove the connectors of the glow ignitor    gt  fig  67  item 5  and the ionisation electrode    gt  fig  67  item 6   5       
36. djustment        Measuring the ionisation current   gt  fig 63     Turn the mains power switch to  0    gt  fig  56  item 1    e Loosen the connector and socket connection of the    ionisation electrode and connect the multimeter in  series     Buderus  44 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       e  On the measuring device  select the u Amp d c  range   The measuring device must have a resolution of at least  1 uA  1 micro ampere      e Set mains power switch to  1    gt  fig  56  item 1        Set the boiler in to partial load by pressing the Service  button once     e Measure the ionisation current  The ionisation current  being checked must measure  gt 2 pA   gt 2 micro  ampere  direct current        Enter the reading on the report form   e Set the mains power switch to  0    gt  fig  56  item 1      e  Remove multimeter and restore the connector and   socket connection to its original state       Refit the casing and secure the boiler with the radiator  key   gt  fig  64      e Set the mains power switch to  1    gt  fig  56  item 1      2 1 11 Handing over   After completing the installation and commissioning of the  system the installer should hand over to the householder  by the following actions        Hand over all relevant documentation to the end user  and explain his her responsibilities under the relevant  national and regional regulations        Explain and demonstrate the lighting and shutting  down procedures  
37. e   gt  fig  59   item 2                  e Open the gas shut off valve   gt  fig  57  item 2         e Set the mains switch to  1    gt  fig  56  item 1         7215 3100 59 1TD             Fig  59 Check the gas air ratio         Set the boiler to partial load by pressing the service    button once  A symbol of an open ended spanner  D appears in the upper left hand corner of the display   see fig  60      7215 3100 60 1TD             Fig  60 DBA with open ended spanner         The optimum gas air ratio is  5 Pa   0 05 mbar    The pressure difference should be between  10 and 1 2 1  0 Pa   gt  fig  61              NOTE       If the reading is in the shaded area no adjust     ment is required                 If this is not the case then adjustment is needed   15  10  5 0 5  Pa     i    0 15  0 10  0 05 0 00 0 05  mbar     Remove the safety screw with a flat head screwdriver      gt  fig  62  item 1   3   4      lt   gt     e Adjust the adjustment screw of the burner pressure to 7215 3100 61 1TD  the correct gas air ratio using an  4 mm  Allen key and  by referring to fig  61                 Fig  61 Pressure difference of gas air ratio at partial load        1 wron  e Replace the safety screw   gt  fig  62  item 1   2  eee  e Set mains power switch to  0    gt  fig  56  item 1   3  left turn  4  right turn    e Close the gas shut off valve   gt  fig  57  item 1      Buderus  Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 43       E  Commis
38. e at an incline of 50 mm per metre  length to prevent condensate dripping from  the flue terminal  This means that the clear   ance above the appliance must be increased  to match the duct length  See figure on  page 8           NOTE   a  Take into account the extra depth of the boil     er when using the wall spacing frame        1 9 5 Connecting the vertical flue adaptor   e Push the vertical flue adaptor   gt  fig  23  onto the  appliance flue connector  Ensure that the flue adapter  is fully engaged into the top of the boiler     1 9 6 Connecting the horizontal flue turret   e Push the horizontal flue turret   gt  fig  23  onto the  appliance flue connector  Ensure that the flue turret is  fully engaged into the top of the boiler     Installation  a           7215 3100 24 1TD             Fig  24 Vertical flue adaptor          7215 3100 25 1TD             Fig  25 Horizontal flue turret with flue gas testing point    1 Flue gas testing point    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 23    EE Installation    1 9 7 Installation of the horizontal flue      The standard flue is suitable for lengths upto 660 mm    gt  fig  26   For longer flue runs upto 12 0 m  extension  air flue ducts are available        NOTE       Use the wall mounting template to help you    mark the position of the side flue opening        1 9 8 Flue duct preparation and assembly      Measure the flue length L  Refer to figures 27 and 28   The len
39. ert of the stack  The trap built into the  boiler will provide this 75 mm   gt  fig  14  conden   sate seal  A o          6              7215 3100 14 1TD             Fig  14 Internal termination of condensate drainage pipe  to internal stack    Boiler    21 5 mm min    internal soil and vent stack  No length restriction   450 mm min    invert    ORONT    Buderus    16 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       External termination via internal branche  e g  sink  waste     The condensate drainage pipe should have a minimum  outside diameter of 21 5 mm with no length restriction   The connection should preferably be made downstream  of the sink waste trap  If the connection is only possible  upstream  then the air break is needed between the two  traps  This can be provided by the sink waste pipe     gt  fig  14 and fig  15      Installation  a        ine   iN         E    7215 3100 15 1TD             Fig  15 External termination of condensate drainage  pipe via internal discharge branch  e g  sink  waste  and condensate syphon    Sink   Boiler   No length restriction    21 5 mm min    open end of pipe direct into gully  below ground but above  water level       PRONE          7215 3100 16 1TD             Fig  16 External termination of condensate drainage  pipe via internal discharge branch  e g  sink  waste  and condensate syphon    Sink   Boiler   No length restriction    21 5 mm min    open end of pipe direct into gully  belo
40. g  36                           7215 3100 36 1TD             Fig  36 Hang bracket under boiler    e Remove the securing screw   gt  fig  32  item 1  and  lower the Boiler Control Unit  DBA    gt  fig  32  item 2      Buderus  28 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       e  Connect the two wires of cable from the ModuLink  receiver to terminal 1 and 2 of the connection block on  the back of the DBA   gt  fig  37   The wires are not  polarity sensitive    A green LED will light on the receiver  when installed  correctly and the boiler is reconnected to the mains  electricity supply     There is no requirement to setup the RF link between the  thermostat and receiver  This has been completed as part  of the manufacturing process     The room thermostat sends a signal to the receiver at  least every 30 minutes to see if they are still in contact  with each other        If you want to test whether you have reception then  press the M button on the thermostat for more than  5 seconds  The thermostat will now send out a signal  continuously  The LED on the receiver flashes green  and the thermostat shows connecting in the display         The receiver will stay in this test mode until the       button on the thermostat is pressed     e Raise and secure the DBA       Refit the boiler casing if necessary     1 11 2 External 230 V controls    Caution       This appliance must be earthed     e  Remove the securing screw and lower the DBA  
41. gth L is from the centre line of the flue turret to  the outside face of the wall        NOTE       The flue must be inclined from the boiler           NOTE       An inner flue finishing kit is provided which    should be fitted to the ducts before assem   bly          When just the terminal assembly is to be used  meas   ure the length L from the raise ring back   gt  fig  29    The overall measurement for the outer duct is L minus  70 mm  The overall measurement for the inner duct is  L minus 50 mm  Ensure that the cuts are made square  and a free from burrs     e  f the final flue piece is an extension  measure from the  formed end  back  As before the final measurement are  minus 70 mm for the outer and minus 50 mm for the  inner     e Assemble flue system completely  Push the ducts fully  together   The assembly will be made easier if a solvent free  grease is lightly applied to the male end of the ducts     Buderus                   7215 3100 26 1TD          Fig  26 Installation with horizontal flue gas turret    Maximum length  Terminal assembly  Flue turret  Finishing kit  Outer wall    Sa Pons                7215 3100 27 1TD             Fig  27 Flue length   rear    item A   150 mm without the use of a wall spacing frame  item A   185 mm with the use of a wall spacing frame                7215 3100 28 1TD             Fig  28 Flue length   side       24 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements      Push the assembly through 
42. heat exchanger 8718600021  19   Heat exchanger 73659  20   Frontside heat exchanger 6718600141  21   Sight glass 73662  22   Combustion divider 73670  23   Ignition unit 8718600054  24   lonisation electrode 38320  25   lonisation electrode seal 73666s   set of 2 pc    26       27   Bracket ionisation electrode and fe  glow ignitor   2 pc    28       29   Concentric adapter 78120  30   100 mm Lipring 78121  31   60 mm seal  bottom flue gas 73563  pipe   32   Flue gas pipe 78122  33   60 mm seal  top flue gas pipe  73736  34   Flue gas pipe seal 73579                            Description Product No   35   Flue gas thermostat  STL  87105062670   push in type   36   Condensate collector 73630  37   Condensate trap 7746900187  38   Connection return 73583  39   Gas pipe 8718600028  40   Connection supply 73672  41   Automatic airvent 38618  42   Spring heat exchanger 73582s  43   O ring heat exchanger 73580s   set of 10 pc    44   Heat exchanger seal 73584s   set of 2 pc    45   Safety sensor 78154  46   Supply pipe 78130  46   Supply pipe 7746900068  47   Pump Uper 15 50 78142  48   Connection return pipe 78133  49   Return pipe 78132  50   Connection return combi 78165  51   Internal mechanism three way 73685  valve  52   Servomotor three way valve 73686  53   Securing pin of the servomotor 73687  54   Discharge pipe of pressure 78134  relief valve  55a   Pressure relief valve 3 bar 78198  55b   Key to Pressure relief valve 78202  3 bar  56   By pass 78143  57   Expansion ves
43. ing 3 mm contact separation on  both poles  or by a three pin plug and socket arrange   ment     Damaged mains supply cables must be replaced using    cable as described above  and fitted by a qualified electri     cian    The means of isolation must be accessible to the user  after installation  fig  30  item 1     The electrical connection to the mains supply should be  readily accessible and adjacent to the boiler     Installation  a           7215 3100 29 1TD             Fig  29 Flue terminal position    Flue Finishing Kit   Flue Terminal   Outer Wall Face   Raised Ring locating the terminal relative to the outside  wall face    PONS                                                 7215 3100 30 1TD       Fig  30 DBA    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 25    EE Installation    Electrical wiring    Caution    N THIS APPLIANCE MUST BE EARTHED    Ensure that your appliance is connected cor   rectly  If you are in any doubt consult a quali   fied electrician        NOTE   x  The wires in this mains lead are coloured in    accordance with the following code     EARTH   GREEN AND YELLOW  NEUTRAL  BLUE  LIVE   BROWN    The appliance mains cable  wire colours may  not correspond with the markings that identi   fy the terminals on the fuse spur connector   refer to the guide below     e Connect green and yellow wire to terminal  marked E or   or coloured green or  green and yellow    e  Connect brown wire to terminal 
44. m   Maintain a minimum side clearance of 5 mm   gt  fig  20      Ensure the flue is adequately supported  Buderus recom   mend securing each flue extension with a minimum of one  wall bracket     The additional flue parts listed can be ordered from your                                              supplier   Flue size 60 100  Flue size 80 125  optional    For every bend or For every bend  extension the or extension the  60 100 flue system max  flue length 80 125 flue system max  flue length   L  has to be  L  has to be  reduced by  reduced by   500 mm extension 0 5 m 500 mm extension 0 5 m  1000 mm extension 1 0 m 1000 mm extension 1 0 m  90   bend 1 4m 90   bend 1 6m  45   bend 0 7 m 45   bend 0 9m  Tab  2 Tab  3  NOTE NOTE   x  The total reduction length must never exceed  a  Vertical adaptor  60 100    gt  80 125  is re     quired for 80 125 flue gas systems  because  the flue outlet of the boiler is 60 100     the maximum flue length           Buderus  22 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       1 9 4 Standard 100 mm flue systems   The standard concentric flue system provides for a maxi   mum horizontal straight length of upto 12 0 m for 60 100  flue connection  see subsection 1 9 3     Full instructions for fitting this flue are in subsection 1 9 7    Installation of the horizontal flue  on page 24        IMPORTANT       Any horizontal flue system fitted to a conden     sing boiler must be inclined towards the ap   plianc
45. marked L  or coloured red    e  Connect blue wire to terminal marked N or  coloured black       1 11 External controls    Buderus boilers are designed to modulate based on room  temperature  this reduces the amount of energy used to  heat the property  when compared with using 230V or volt  free controls     Buderus recommend thermostats from the ModuLink and  RC series in order that the customer can benefit from the  increased comfort and savings of modulating on room  temperature     The wall mounted condensing gas combi boiler can be fit     ted with the following external controls     1  ModuLink 250 RF   gt  subsection 1 11 1  or other rec     ommended Buderus 24V controls     2  Room temperature control device and timer at 230V  connected under the grey cover    gt  subsection 1 11 2      3  ON OFF temperature controller  volt free    gt  subsection 1 11 3      Connecting any external controls will require the case  removal to gain access to the boiler control unit  DBA     Gain access to the DBA connection block  e  Remove the boiler s case   gt  fig  5 on page 11      e Remove the securing screw   gt  fig  32  item 1      e Lower the boiler control unit  DBA    gt  fig  32  item 2      Buderus                7215 3100 31 1TD          Fig  31 Electrical wiring    1 Permanent live          7215 3100 32 1TD          Fig  32 Lower the DBA       26 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       1 11 1 Modulink 250 RF thermostat c
46. metres for the 60 100 flue   gt  table 2         35 metres for the 80 125 flue   gt  table 3    see also fig  22 and 23      When you have determined the length L for the flue sys   tem  add up all the bends and extensions used     Refer to the appropriate table for the effective lengths of  each bend or extension     The total of the bends and extensions must not add up to  more than the reduction lenghts of the flue length L        Installation  a           7215 3100 21 1TD                     Ti                                                                                                                                                                                                             7215 3100 22 1TD             Fig  22 Vertical flue length    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 21    EE Installation    Example 60 100        2 x 1 metre extension   2 0 m  2 x 90   bend   2 8 m  Total effective length   4 8 m        Maximum allowed is 12 m  So this is allowed   Example 80 1250     2 x 1 metre extension   2 0 m  2 x 90   bend   3 2 m  Total effective length   5 2 m           7215 3100 23 1TD          Maximum allowed is 35 m  So this is allowed        Fig  23 Horizontal flue length    Take the flue terminal clearances into account when plan   ning the layout of the place of installation  see  subsection 1 9 1   Siting the flue terminal  on page 19      Maximum wall thickness without extensions is 415 m
47. n     The boiler MUST be installed so that the terminal is  exposed to external air     It is important that the position of the terminal allows the  free passage of air at all times           Tab  1 Balanced flue terminal position    Minimum acceptable spacing from the terminal to  obstructions and ventilation openings are specified in  table 1     If the lowest part of the terminal is less than 2 metres  above the level of the ground  balcony  flat roof or place to  which any person has access  the terminal must be pro   tected by a guard     Ensure that the guard is fitted centrally     The flue assembly shall be so placed or shielded as to  prevent ignition or damage to any part of the building     The air inlet products outlet duct and the terminal of the  boiler MUST NOT be closer than 25 mm to combustible  material  Detailed recommendations on the protection of  combustible material are given in BS 5440 1 2000     Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 19    zal Installation       NOTE  It is absolutely essential to ensure  in prac     tice  that products of combustion discharg   ing from the terminal cannot re enter the  building or any other adjacent building  through ventilators  windows  doors  other  sources of natural air infiltration  or forced  ventilation air conditioning        If this could occur the appliance MUST be turned off  with  the owners permission   and labelled as unsafe until cor   recti
48. n  existing cupboard or compartment may be used  provided  that it is modified for the purpose  In both cases  details of  essential features of cupboard  compartment design   including airing cupboard installation  are to conform to  the following  BS 6798  No cupboard ventilation is  required   see  Air Supply  for details      It is not necessary to have a purpose provided air vent in  the room or internal space in which the boiler is installed   Neither is it necessary to ventilate a cupboard or compart   ment in which the boiler is installed  due to the low surface  temperatures of the boiler casing during operation  there   fore the requirements of BS 6798  Clause 12  and   BS 5440 2 may be disregarded     The permanent clearances required are     A  in front 8 mm  B   below 21 mm  C   right side 5 mm  D   left side 5 mm  E   above 21 mm    The position selected for installation MUST allow ade   quate space for servicing     A  in front 350 mm  B   below 180 mm  C   right side 5 mm  D   left side 5 mm  E   above 200 mm    In addition  sufficient space may be required to allow lift   ing access to the wall mounting bracket     Installation  a        600mm    600mm  La    750mm           2250mm                                           600mm  e  750mm  rf  0O       2250mm  S   600mm A          7215 3100 01 1TD       Fig  1  A   Radius    Bathroom Installations       E       7215 3100 02 1TD             Fig  2 Compartment Installations    Buderus       Buderus 500 24C 28C 
49. n section 1 6     CAUTION       DO NOT remove the polystyrene foam bot     tom slab until lifted into position    During installation work  cover the condens   ing boiler and flue connection to prevent site  dirt from entering           Attach the wall mounting template   e Drill the necessary holes     e Attach the manifold assembly to the wall   gt  fig  4   item 1      e Make the pipework connections to the manifold   e Attach the wall bracket   gt  fig  4  item 2        Open the locking mechanism using a radiator key    gt  fig  5  item 1   The radiator key is included in the  delivery of the boiler in the accessories bag     e  Detach the casing of the condensing gas boiler    gt  fig  5        Remove the polystyrene foam piece from the top of the  boiler       Hang the condensing gas boiler onto the wall bracket    gt  fig  4      Installation  a                    7215 3100 04 1TD                   t          Note       If the boiler isn t connected to the pipework    immediately  place caps on the pipe connec   tions        e Connect manifold unions to the boiler using supplied  seals        2 cm    7215 3100 05 1TD          Fig  5 Remove casing    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    11    ai  Installation    1 6 Install the wall spacing frame     Attach the wall mounting template        e Drill the necessary holes   e Attach the wall bracket   gt  fig  4  item 2      e  Mount the rubber stops in one of
50. onnection  The ModuLink 250 RF thermostat modulates on room  temperature  The Buderus boilers work most efficiently  with Buderus thermostats  Therefore these thermostats  are recommended by Buderus     See subsection 1 12 for an installation example with the  ModuLink 250 RF     The ModuLink 250 RF thermostat comprises         wall bracket       receiver       thermostat        thermostat programmer  refer to the instruc     B For installation and operation of the Buderus  tions supplied with that thermostat        ModuLink Receiver and bracket installation    Warning    N Do not connect 230 V AC to the receiver        The receiver is not waterproof     Prevent water coming into contact with the  receiver        e Remove the receiver terminal cover   gt  fig  33  item 1      e Connect the grey 2 core cable  supplied with  ModuLink 250 RF thermostat  to the receiver    gt  fig  34   The wires are not polarity sensitive       To refit the cover  slide back on and click into place    gt  fig  34  item 1      Installation  a                 7215 3100 33 1TD       Fig  33 Receiver bracket                7215 3100 34 1TD       Fig  34 Connect cable    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 27    ai  Installation         Slide the receiver securely into the bracket  supplied  with the boiler   gt  fig  35               7215 3100 35 1TD            Slide the bracket in the guide rails on the underside of  the boiler   gt  fi
51. rrent setting blinks     e Use the  A  or A keys to adjust to desired setting                                To Central heating is on              Central heating is off  summer operation    TH DHW is still available              NOTE   When summer operation is active then the  boiler will not operate for central heating until  summer operation has been deactivated        Setting the flow temperature       NOTE       It is not possible to set the flow temperature    when the boiler is set to summer operation     e Press    button   gt  fig  54  item 2  four times then  adjust the flow temperature to the desired temperature   30   C   80   C  using the   and    keys   gt  fig  49   item 1   Factory setting is 80   C     Frost protection   The boiler has an automatic frost protection  When the  CH flow temperature drops below 7   C then the boiler will  start up           7215 3100 54 1TD          Fig  54 DBA   adjusting arrows       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    Buderus  39    E  Commissioning    2 1 3 Checking for gas leaks   Use a suitable pressure gauge for the different pressure  readings  It should be able to handle pressures up to  50 mbar with an accuracy of 0 01 mbar minimum     e Disconnect the system from the power supply    e Check all sections of gas pipework and connections  for signs of leaks before starting up the system for the  first time  If a leak is detected during tightness testing   use an approved
52. s of Prac   tice     Regulations and directives ee    The manufacturer s notes must not be taken  in any way   as overriding the statutory instrument laws     The design and construction of the Buderus wall   mounted condensing gas combi boiler 500 24C and  500 28C conforms to the basic specifications listed in  the European directive governing gas fired appliances  90 396 EEC  and with respect to EN 625  EN 483 and  EN 677     For optimum long term reliable functioning under domes   tic conditions  the boiler must be inspected and main   tained as per these instructions  at least once a year by an  officially recognised service engineer     The term  domestic conditions  means that the boiler is  used to provide central heating and   or hot water to no  more than one single family dwelling     Failure to comply with these instructions will invalidate the  appliance warranty     Timer Frame Buildings   If the boiler is to be fitted in a timber framed building it  should be fitted in accordance with the Institute of Gas  Engineering document IGE UP and BS 5440 1     The appliance must only be installed along with Buderus  flue kits  as these are certified for use with the boiler     Warning  Notes relating to the heating      system water     Thoroughly flush the system before it is filled  with water  Use only untreated water or water  treatment product such as Sentinel X100 to  fill and top up the system  For more informa   tion about Sentinel call 0151 420 9563   When using
53. s pump     If an external pipe run is unavoidable then the run should  be limited to 3 m in length  Should this be exceeded then  the pipework diameter should be increased to 32 mm     It should be noted that the connection of a condensate  pipe to a drain may be subject to local building controls                                   7215 3100 12 1TD          Fig  12 Compression fitting    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements    15    ai Installation       Materials for condensate    Note       Ensure that the condensate trap is filled with    water           The condensate drainage pipe should be run in a stand   ard drain pipe material  e g  PVC  polyvinyl chloride    PVC u  unplasticized polyvinyl chloride   ABS  acryloni   trile butadienestyrene   PP  polypropylene  or PVC C   cross linked polyvinyl chloride      The condensate drain can be attached to the syphon   Ensure that the black rubberised olive   gt  fig  13  is cor   rectly aligned        7215 3100 13 1TD                   Fig  13 Condensate outlet  Any internal pipework should be of a diameter to match    the requirements of the condensate exit pipe on the appli   ance        Internal termination to internal stack   The condensate drainage pipe should have a minimum  outside diameter of 21 5 mm with no length restriction   It should incorporate a trap with a 75 mm condensate seal  and be connected to the stack at a point at least 450 mm 2  above the inv
54. sel pipe 78135  58   Expansion vessel 78163  59   Connection plate heat 78167  exchanger  60   DHW flow regulator 78138  61   DHW flow sensor 78137  62   Connection supply combi 78166  63   Flow sensor 78136  64   Mounting button 7746900854  65   Plate heat exchanger 78144  66   O ring  set of 10 pc   78158s  Buderus  55    Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       5  Appendix                                                                                                                                                                      Description Product No  Description Product No   67   Clips  set of 2x3 pc   78156s 106        68   Burner thermostat 7746900412 107   Receiver bracket 78200  69   CH connector 78161 108   Wall spacing frame 75972  70   Sanitary connector 78162     Spring gaspipe  set of 5 pc   73531  71   DBA 24 S and 28 C 7746900063       LPG kit 24 kW   28 kW 73734  71   DBA 24C 7746900069     O ring sensor  set of 10 pc   38434s  72   Power switch 73660     O ring 16x2 pressure relief 73729s  73   Cable harness 7746900064 valve  set of 10 pc    74   Clips  set of 5 pc   73653s     Fuse 2 5 AT  DBA  73739s   l  set of 10 pc    75   Clips  set of 5 pc   73056s      O ring  large  flow sensor 78153s  76   Condensate trap seal 73463  set of 10 pc    77   Drainpipe seal  set of 5 pc   73638s     O ring 9 19 x 2 62 sensor 78175s  78   O ring  set of 10 pc   78151s supply return  set of 10 pc    79   O ring small
55. service record log book  The details of the  2 Commissioning 34 log book will be required in the event of any warranty work  2 1 Preparing the boiler for operation 35 being requested   Please complete the appropriate sections on completion  5 of the installation and commissioning   3 Inspection 46  3 1 General directions 46 REMEMBER  Please leave the log book with the  3 2 Preparing the boiler for inspection 46 installed boiler   Gas Council Aplliance No     4 Maintenance 47 Buderus 500 24C 47 110 04  4 1 Cleaning the heat exchanger and burner 47 Buderus 500 28C   47 110 03  4 2 Cleaning the gongen ats trap and syphon 50 These Installation and maintenance instructions apply to   4 3 Cleaning or replacing the plate heat exchanger 51 Buderus wall mounted condensing gas combi boilers  models 500 24C and 500 28C   5 Appendix 52  5d Bi n in Flue type  C13 C334   C536   C73   52  Wiingdiagam 53 Type  GB IE lloy3p 20 mbar  37 mbar  5 3 Residual pump lift 5A In this document     NG 2H G20 20 mbar  5 4 Spare parts list 55 LPG   3P G31 37 mbar  Electrical rating  230 VAC  50 Hz  IP X4D  Fuse rating  2 5 Ampere slow blow silica filled  The boiler type consists of the following components     500 Gas condensing boiler    28 Maximum output is 28 kW   C Combination boiler  Integrated  domestic hot water supply    Other manuals available for this boiler are       user manual       service instructions   Buderus  2 Buderus 500 24C 28C   Subject to modifications resulting from technical impro
56. sioning         Remove the tube from from the burner pressure testing    nipple     Tighten the screw on the burner pressure testing nip   ple   gt  fig  59  item 1      e Open the gas shut off valve   gt  fig  57  item 2        Turn the mains power switch to  1    gt  fig  56  item 1            NOTE   Technically it is not necessary to use a com   bustion analyzer for COs measurements   The CO  level is secured by the gas air ratio  as described above    A combustion analyzer  if available  can be  used to confirm CO  levels   gt  technical  specifications on page 6      Caution    N Check the test nipples for gas tightness                          7215 3100 62 1TD       Fig  62 Adjust gas air ratio    2 1 8 Gas rating test  e Isolate all other appliances     e Press the service button to set the boiler to full  load        Ensure that there is no modulating of the fan gas valve     e  Carry out the Gas Rating procedure as described in   Essential Gas Safety  3rd edition on pages 169 176     2 1 9 Checking for leaks while boiler is in opera   tion  e Use an approved leak detector to check all connec   tions for possible leaks  The product must be certified  as a gas leak testing agent     e Do not allow the product to come into contact with the  electrical wiring     2 1 10 Function testing    NOTE   i  During initial start up and annual servicing     make sure that all control  regulating and  safety devices are in full working order and  if  applicable  check for correct a
57. the wall and slide the turret  onto the flue connector  Refer to figure 25  Ensure that    the turret is fully engaged into the socket on the boiler       From the outside fix the flue finishing kit to the terminal  and  after ensuring the duct is properly inclined  towards the boiler  fix the finishing kit to the wall    If the terminal is within 2 m of the ground where there    is access then an approved terminal guard must be fit     ted    The guard must give a clearance of at least 50 mm  around the terminal and be fixed with corrosion resist   ant screws     1 10 Electrical connections  Mains connection to the appliance  Warning  Boiler damage   A e Connect the supply cable supplied with  the the boiler to the 230 Volt mains     e DO NOT connect 230 Volts mains supply  to any other point on the boiler     Caution  Electric shock       Electrically isolate the appliance at the fused    spur before removing the case   gt  fig  30         NOTE       All Buderus boilers require a permanent    mains supply of 230 Volts at 50 Hz        Wiring to the boiler MUST be in accordance with the cur     rent   E E   BS 7671  Wiring Regulations and any local  regulations  Wiring should be a 3 core PVC insulated  cable  not less than 0 75 mm   24 x 0 2 mm   and to  table 16 of BS 6500    The mains supply to the appliance  and any system con   trols  thermostat  timer   must be from a dedicated fused  spur    The spur must be capable of being isolated by either a  double pole switch  hav
58. ty  damage        Abbreviations    AB  AV  BCT  BDV  CB  CH  CHF  CHR  CT  CWDO  DHW  DV    LSV  MCW    JB  PL  Prog  PRV  RT  RV    TRV    WC  ZV      Automatic Bypass     Air Vent     Buderus cylinder thermostat    Buderus diverter valve     Connection Block     Central Heating     Central Heating Flow     Central Heating Return     Cylinder Thermostat     Condensate water drainage outlet    Domestic Hot Water     Diverter Valve     Earth     Live     Lock Shield Valve     Mains Cold Water     Neutral     Junction Box   RTH Relay     Permanent Live     Programmer     Pressure relief valve  safety valve     Room Thermostat     ModuLink 250 RF Receiver    Timer     Thermostatic Radiator Valve    micro  as pA   micro Amps     Wiring Centre      Two Port Zone Valve    Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 5    EE Installation    1 Installation    1 1 Technical specifications       500 Series wall mounted condensing gas                                                                                        Description Unit combi boiler  500 24C 500 28C   Type of gas supply as established in GB IE Iloy3p 20 mbar  37 mbar   EN 437  GB IE   natural gas H and LPG P    Rated thermal load for heating kW 5 7   23 0 5 7   23 0   Rated thermal load for preparing hot water kW 5 7   23 0 5 7   28 5   Rated heating capacity for system temperature    modulating from 30   to 100      Heating curve 75 60   C kW 5 3   22 0 5 3   22 0  
59. ve action can be taken        1 9 2 Air supply and flue gas exhaust in a closed  installation   The boiler case incorporates the seal for the air supply   system  It is important that the case is fitted correctly     To ensure optimal operation  the 500 Series appliances  must be connected to a Buderus horizontal or vertical flue  terminal  These terminals have been developed specifi   cally for Buderus condensing gas boilers and have been  comprehensively tested for trouble free operation when  correctly installed        7215 3100 19 1TD             Fig  19 Standard horizontal flue pack       Standard horizontal flue pack   gt  fig 19        item 1  Flue turret 60 100         item 2  Horizontal flue terminal 60 100          item 3  Flue finishing kit                                                                    7215 3100 20 1TD             Fig  20 Side flue and rear flue installation    Buderus  20 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       Standard vertical flue pack   gt  fig  21         item 1  Vertical flue terminal 60 100       item 2  Weather collar        item 3  Flue support bracket         item 3  Vertical flue adaptor     1 9 3 Maximum Flue length    A standard flue comprises a 90 degree takeoff bend and  the horizontal flue outlet or straight takeoff and the vertical  flue outlet  The flue can be extended upto a maximum  effective length  L   gt  fig  22 and 23      The maximum effective flue length is       12 
60. vements    Regulations and directives    All gas appliances must be installed by a competent per     son in accordance with the current Gas Safety  Installa   tion and Use  regulations     Failure to install appliances correctly could lead to prose     cution     The appliance installation must comply with the current     Gas Safety Regulations    IEE Regulations    Building Regulations    Building Standards  Scotland   Consolidation    Building Regulations  Northern Ireland     local water by laws     Health and Safety Document 635  The Electricity Work  regulations 1989  and any other local requirements     The relevant British Standards should be followed   including     BS7074 1   Code of practice for domestic and  hot water supply   BS6891   Installation of low pressure gas  pipework up to 28mm  R1    BS5546   Installation of gas hot water sup     plies for domestic purposes    EN 12828   Central heating for domestic    premises    BS5440 1   Flues and ventilation for gas appli   ances of rated heat input not ex     ceeding 70 kW  net   Flues    BS5440 2   Flues and ventilation for gas appli   ances of rated heat input not ex   ceeding 70 kW  net   Air Supply   BS5449   Forced circulation of hot water  systems   BS7593   Treatment of water in domestic hot  water central heating systems   BS6798   Installation of gas fired boilers of    rated input up to 70 kW  net      Where no specific instruction is given  reference should  be made to the relevant British Standard code
61. w ground but above  water level    SF PON  gt     Buderus       Buderus 500 24C 28C   Subject to modifications resulting from technical improvements 17    EE Installation       Condensate absorption point    The condensate drainage pipe should have a minimum  outside diameter of 21 5 mm and the external pipe length  should not be more than 3 m  The condensate absorption  point should be sited in a convenient position as close as  possible to the boiler but not in the vicinity of other serv   ices  For information  gt  fig  17     Note       When discharging condensate to an outside    drain caution must be taken to ensure block   age cannot occur during freezing conditions   If this is likely to occur  the use of a syphon  trap is recommended                    7215 3100 17 1TD             Fig  17 External termination of condensate drainage  pipe to absorption point    External length of pipe 3 m max     21 5 mm min      1000 mm min     100 mm min  plastic tube   bottom of tube sealed   limestone chippings   Two rows of three 12 mm holes at 25 mm centres 50 mm  from bottom of tube and facing away from house  8  Ground  either or    9  25mmmin    10  300 mm min    11 hole depth 400 mm min     SS  OF NE    Buderus    18 Buderus 500 24C 28C   Subject to modifications resulting from technical improvements       1 9 Flue installation    1 9 1 Siting the flue terminal    Installation  a                    AN      A  y   lt    ve   O  A ius   O      A       un        n   7  A       
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
X3 User Manual  TM-V7 - Kenwood  Installation Manual      SZ-31MR - Olympus    ASUS EA-N66 A8660 User's Manual  TITLE      Copyright © All rights reserved. 
   Failed to retrieve file