1. Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8k V air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on Ethernet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on Ethernet ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 8 Rockwell Automation Publication 1756 TD003D EN E February 2013 Table 6 Certifications 1756 EtherNet IP XT Module 1756 ControlLogix Communication Modules Specifications Certification 1756 EN2TXT 1756 EN2TRXT c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN 61326 1 Meas Control Lab Industrial Requirements e EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmab
2. Ethernet cable Multimode fiber LC connector 802 3 compliant shielded or unshielded twisted pair USB port USB 1 1 full speed 12 Mbps Wiring category 3 on USB ports 2 on Ethernet ports 2 on Ethernet ports 3 on USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style Transmitter launch power at Beginning of Life BOL min Allow 1 dB at End of Life EOL 19 dBm into 62 5 125 um fiber N A 0 275 22 5 dBm into 50 125 um fiber N A 0 20 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Table 2 Environmental Specifications 1756 EtherNet IP Modules E Attribute 1756 EN2F 1756 EN2T 1756 EN2TR 1756 EN3TR 1756 ENBT 1756 EWEB 1756 EN2TSC Temperature operating 0 60 C 32 140 F IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock Temperature surrounding air max 60 C
3. All modules except 1756 EN2TSC FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 EtherNet IP ODVA conformance tested to EtherNet IP specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Table 4 Technical Specifications 1756 EtherNet IP XT Module Attribute 1756 EN2TXT 1756 EN2TRXT EtherNet IP communication rate 10 100 Mbps Logix communication connections 256 TCP IP communication connections 128 Current draw 5 1V DC 1A Current draw 24V DC 3mA Power dissipation 5 2W Thermal dissipation 17 7 BTU hr Isolation voltage 30V continuous basic insulation type Ethernet network to backplane No isolation between USB and backplane Type tested 853V AC for 60s Slot width Module location Chassis based any slot Chassis 1756 A4LXT 1756 A5XT 1756 A7XT 1756 A7LXT Power supply standard 1756 PAXT 1756 PBXT Power supply redundant None Ethernet port 1 Ethernet RJ45 Category 5 Ethernet cable 802 3 compliant shielded or unshielded twisted pair Rockwell Automation Publication 1756 TD003D EN E February 2013 7 1756 ControlLogix Communication Modules Specifications Table
4. Attribute 1756 DH485 Communication rate 19 2 Kbps 9600 Kbps Current draw 5 1V DC 850 mA Current draw 24V DC 1 7mA 26 Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Table 22 Technical Specifications 1756 DH485 Module Attribute 1756 DH485 Power dissipation 45W Thermal dissipation 15 4 BTU hr Isolation voltage 50V continuous basic insulation type DH485 A B to backplane and DH485 A to DH485 B Type tested at 750V DC for 60s Slot width 1 Module location Chassis Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 Ports 2 DH 485 9 pin D shell Wiring category 2 on DH485 ports North American temperature code T5 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Table 23 Environmental Specifications 1756 DH485 Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DH485 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F
5. 140 F Temperature storage 40 85 C 40 185 F IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity 5 95 noncondensing IEC 60068 2 30 Test Db Unpackaged damp heat Vibration 29 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emission Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 1 kHz sine wave 80 AM IEC 61000 4 3 10V m with 200 Hz 50 Pulse 100 AM 900 MHz from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 10V m with 200 Hz 50 Pulse 100 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 2 kV at 5 kHz on 3 kV at 5 kHz on Ethernet ports 2 kV at 5 kHz on Ethernet ports IEC 61000 4 4 Ethernet ports Surge transient immunity 2 kV line earth CM on Ethernet ports IEC 61000 4 5 Conducted RF immunity 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 6 Rockwell Aut
6. Attribute Communication rate 1756 DHRIO as a Remote 1 0 Scanner a Sam EEEE 1794 1 0 PLC 5 Table 16 Technical Specifications 1756 DH and Remote 1 0 Modules 1756 DHRIO E 57 6 Kbps 115 2 Kbps 230 4 Kbps 1791 1 0 PanelView Plus a ogo 1756 RI0 as a Remote 1 0 Adapter 1756 RI0 B Remote 1 0 communication Remote 1 0 scanner only 32 logical rack connections per remote 1 0 channel 16 block transfer connections per remote 1 0 channel Remote 1 0 scanner or adapter 32 physical racks 0 76 any combination of rack size and block transfers Connections supported max 32 10 scheduled 1 0 Current draw 5 1V DC 850 mA 450 mA Current draw 24V DC 1 7mA 5mA Power dissipation 45W 25W Thermal dissipation 15 4 BTU hr 8 5 BTU hr Isolation voltage 30V continuous basic insulation type DHRIO A B to backplane 50V continuous basic insulation type RIO and DHRIO A programming port to DHRIO B communication lines to backplane No isolation between DHRIO A and Programming port Type tested at 500V AC for 60 s Type tested at 877V DC for 60 s Slot width 1 Module location Chassis based any slot C
7. 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certification 1756 DHRIOXT c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN 61326 1 Meas Control Lab Industrial Requirements e EN 61000 6 2 Industrial Immunity e EN 61000 6 4 Industrial Emissions e EN 61131 2 Programmable Controllers Clause 8 Zone A amp B Rockwell Automation Publication 1756 TD003D EN E February 2013 25 1756 ControlLogix Communication Modules Specifications Table 21 Certifications 1756 DH and Remote 1 0 XT Module C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n e EN60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories DH and Remote 1 0 Networks Cat No Description Specifications 1
8. 14 Environmental Specifications 1756 DNB DeviceNet Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DNB E 0 60 C 32 140 F 1756 ControlLogix Communication Modules Specifications Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 3 kV at 5 kHz on DeviceNet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on DeviceNet po
9. 2 kV line earth CM on ControlNet ports IEC 61000 4 5 Conducted RF immunity 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Rockwell Automation Publication 1756 TD003D EN E February 2013 13 1756 ControlLogix Communication Modules Specifications Table 9 Certifications 1756 ControlNet Modules Certification 1756 CN2 B 1756 CN2R B 1756 CNB E 1756 CNBR E c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with the following EN61326 1 Meas Control Lab Industrial Requirements EN61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions EN61131 2 Programmable Controllers Clause 8 Zone A amp B CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment complian
10. 13 Rockwell Automation Inc All rights reserved Printed in the U S A
11. 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DHRIOXT 25 70 C 13 158 F 1756 ControlLogix Communication Modules Specifications Temperature surrounding air max 70 C 158 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on DHRIO ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on DHRIO ports Conducted RF immunity IEC 61000 4 6 Table 21 Certifications 1756 DH and Remote 1 0 XT Module
12. 2013 11 1756 ControlLogix Communication Modules Specifications Table 7 Technical Specifications 1756 ControlNet Modules Attribute 1756 CN2 B 1756 CNBR E Slot width 1 Module location Chassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 ControlNet port 1 ControlNet BNC 2 ControlNet BNC 1 ControlNet BNC 2 ControlNet BNC ControlNet cable 1786 RG6 quad shield RG6 coaxial cable USB port USB 1 1 full speed 12 Mbps NAP port 1 NAP RJ45 1 NAP RJ45 NAP cable 1786 CP Wiring category 1 on ControlNet ports 1 on ControlNet ports 3 on USB ports 3 on NAP ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 3 128 connections are available for standard use An additional three connections are reserved for redundant control 12 Rockwell Automation Publica
13. 4 Technical Specifications 1756 EtherNet IP XT Module Continued Attribute 1756 EN2TXT 1756 EN2TRXT USB port USB 1 1 full speed 12 Mbps Wiring category 0 2 on Ethernet ports 3 on USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Table 5 Environmental Specifications 1756 EtherNet IP XT Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 EN2TXT 1756 EN2TRXT 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged damp heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 2g 10 500 Hz
14. 5 B 1756 PH75 B Power supply redundant 1756 PA1756 PA75R 1756 PB75R 1756 PSCA2 Ports 2 fiber optic Cable fiber type 200 230 micron HCS Hard Clad Silica Cable fiber termination type Versalink V System Cable length 1 300 m 3 28 984 2 ft North American Temp Code T4A Enclosure type rating None open style Rockwell Automation Publication 1756 TD003D EN E February 2013 29 1756 ControlLogix Communication Modules Specifications Table 26 Environmental Specifications 1756 SYNCH Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 SYNCH 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF im
15. 756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 DeviceNet power To comply with the CE low voltage directive LVD the DeviceNet network must be powered from a source compliant with the safety extra low voltage SELV or protected extra low voltage PELV To comply with UL restrictions the DeviceNet network must be powered from a source compliant with Class 2 or limited voltage current DeviceNet port 1 DeviceNet open style 5 or 10 pin linear plug DeviceNet connector torque 0 56 0 79 Nem 5 7 Ibein USB port USB 2 0 full speed 12 Mbps Wiring category 1 On DeviceNet ports 3 On USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Refer to the DeviceNet Media Design and Planning Guide publication DNET UM072 for information specific to your DeviceNet network 18 Rockwell Automation Publication 1756 TD003D EN E February 2013 Table
16. 770 CD Cable to connect communication module to DH network Belden 9463 twinaxial 9300 RADKIT Remote access dial in kit 56 Kbps modem connection to devices on a DH network including the following Preconfigured modem Communication module e DIN rail mounting hardware e Associated cables DH 485 Network On the DH 485 network the controller can send and receive messages to and from other controllers on the network The DH 485 connection does support remote programming and monitoring via the Studio 5000 environment Excessive traffic over a DH 485 connection can adversely affect overall performance and can lead to timeouts and loss in the Studio 5000 environment configuration performance IMPORTANT Use Logix5000 controllers on DH 485 networks only when you want to add controllers to an existing DH 485 network For new applications with Logix5000 controllers we recommend open architecture networks You need a 1761 NET AIC converter for each controller on the DH 485 network You can have two controllers per one 1761 NET AIC converter but you need a different cable for each controller Connect one controller to port 1 9 pin connector and one controller to port 2 mini DIN connector Use this cable 1747 CP3 1761 CBL ACO0 To connect to this port Port 1 DB 9 RS 232 DTE connection Port 2 1761 CBL AP00 1761 CBL PM02 mini DIN 8 RS 232 connection Table 22 Technical Specifications 1756 DH485 Module
17. ControlNet nodes for which there is no specific support currently available in the programming software A module configured as a generic ControlNet module communicates with the controller in the form of input output status and configuration tags For example use the generic module configuration to set up communication between a ControlLogix controller and a 1203 CN1 ControlNet communication module Then use the CIP generic MSG instruction type to send and receive messages from the 1203 CN1 module Table 7 Technical Specifications 1756 ControlNet Modules Attribute 1756 CN2 B 1756 CNBR E Configuration Standard Redundant Standard Redundant ControlNet communication rate 5 Mbps Logix communication connections 128 40 48 Connections supported max 1319 64 Number of nodes max 99 Current draw 5 1V DC 1100 mA 1300 mA 970 mA Current draw 24V DC 3mA 1 7mA Power dissipation 5 7W 6 7W 5 1W Thermal dissipation 19 5 BTU hr 22 9 BTU hr 17 4 BTU hr Isolation voltage Standard 30V continuous basic insulation type ControlNet network to backplane Redundant 30V continuous basic insulation type ControlNet A B to backplane and ControlNet A to ControlNet B No isolation between NAP or USB and backplane Type tested at 500V AC for 60 s Weight approx 0 26 kg 0 57 Ib 0 293 kg 0 64 Ib 0 26 kg 0 57 Ib 0 293 kg 0 64 Ib Rockwell Automation Publication 1756 TD003D EN E February
18. Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity N61000 6 4 Industrial Emissions EN61131 2 Programmable Controllers Clause 8 Zone A amp B CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories DH 485 Network Cat No 1747 CP3 Description 9 pin D shell straight 9 pin D shell right angle Specifications 3m 9 8 ft 1761 CBL AC00 9 pin D shell right angle 9 pin D shell right angle 45 cm 17 7 in 1761 CBL AP00 9 pin D shell right angle 8 pin mini DIN 45 cm 17 7 in 1761 CBL PM02 9 pin D shell straight 8 pin mini DIN 2m 6 5 ft 1761 NET AIC Advanced Interface Converter AIC connects each channel on the 1756 DH485 module to the DH 485 network 20 4 28 8V DC power source required Typical 120 mA 24V DC current draw 9300 RADKIT 28 Remote access dial in kit 56 Kbps modem connection to devices on
19. EN E February 2013 1756 EWEB web server Table 1 Technical Specifications 1756 EtherNet IP Modules 1756 ControlLogix Communication Modules Specifications Attribute 1756 EN2F 1756 EN2T 1756 EN2TR 1756 EN3TR 1756 ENBT 1756 EWEB 1756 EN2TSC EtherNet IP communication rate 100 Mbps 10 100 Mbps 10 100 Mbps 10 100 Mbps 10 100 Mbps Logix communication connections 256 128 TCP IP communication connections 128 64 Current draw 5 1V DC 1 2A 1A 1A 700 mA Current draw 24V DC 3mA 3mA 3mA 3mA Power dissipation 6 2W 5 1W 5 1W 3 7W Thermal dissipation 21 28 BTU hr 17 4 BTU hr 17 4 BTU hr 12 6 BTU hr Isolation voltage No isolation between USB and 30V continuous basic 30V continuous basic insulation 30V continuous basic insulation system insulation type Ethernet type Ethernet network to backplane type Ethernet network to backplane network to backplane No isolation between USB and Type tested 707V DC for 60 s No isolation between USB backplane and backplane Type tested 853V AC for 60 s Type tested 510V AC for 60s Slot width 1 Module location Chassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 756 PA75R 1756 PB75R 1756 PSCA2 Ethernet port 1 Ethernet fiber 1 Ethernet RJ45 Category 5 1 Ethernet RJ45 Category 5
20. IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2kV at 5 kHz on DHRIO port 2 kV at 5 kHz on RIO ports Surge transient immunity IEC 61000 4 5 2kV line earth CM on DHRIO ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Table 18 Certifications 1756 DH and Remote 1 0 Modules Certification 1756 DHRIO E 1756 RI0 B c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certifie
21. RIO Data Highway Plus Remote 1 0 module 22 1756 DHRIOXT ControlLogix XT Data Highway Plus Remote 1 0 module 22 Remote 1 0 1756 DHRIO Data Highway Plus Remote 1 0 module 22 1756 RI0 B Remote 1 0 module 22 1756 DHRIOXT ControlLogix XT Data Highway Plus Remote 1 0 module 22 Serial 1756 DH485 Compatible with RS 232 serial communication supports the DF1 protocol send and 26 receive messages does not support remote programming and monitoring SynchLink 1756 SYNCH SynchLink fiber optic communication link 29 1 128 connections are available for standard use An additional three connections are reserved for redundant control Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Communication Connections A ControlLogix system uses connections to establish communication links between devices The types of connections include the following Controller to local I O modules or local communication modules Controller to remote I O or remote communication modules Controller to remote I O rack optimized modules Produced and consumed tags Messages Controller access with the Studio 5000 environment Controller access with RSLinx software for HMI or other applications You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system The limit of connections may ultimately reside in t
22. SB 1 1 full speed 12 Mbps Wiring category 1 on ControlNet ports 3 on USB port North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 3 There are 128 connections are available for standard use An additional 3 connections are reserved for redundant control Rockwell Automation Publication 1756 TD003D EN E February 2013 15 1756 ControlLogix Communication Modules Specifications Table 11 Environmental Specifications 1756 ControlNet XT Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 CN2RXT B 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpac
23. Technical Data Allen Bradley 1756 ControlLogix Communication Modules Specifications Standard ControlLogix Catalog Numbers 1756 EN2F 1756 EN2T 1756 EN2TR 1756 EN3TR 1756 ENBT 1756 EWEB 1756 CN2 1756 CN2R 1756 CNB 1756 CNBR 1756 DNB 1756 DHRIO 1756 RIO 1756 DH485 1756 SYNCH 1756 EN2TSC ControlLogix XT Catalog Numbers 1756 EN2TXT 1756 EN2TRXT 1756 CN2RXT 1756 DHRIOXT Topic Page Additional Resources 2 Studio 5000 Environment 2 Available Communication Modules 3 EtherNet IP Network 4 Stratix Switches 10 ControlNet Network 11 DeviceNet Network 18 DH and Remote 1 0 Networks 21 DH 485 Network 26 SynchLink Communication 29 Separate communication interface modules are available for different networks Install multiple communication interface modules into the ControlLogix backplane to configure a gateway to bridge or route control and information data between different networks You do not need a ControlLogix controller in the chassis LISTEN THINK SOLVE Rockwell Allen Bradley Rockwell Software Automation 1756 ControlLogix Communication Modules Specifications Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resource Description EtherNet IP Modules Installation Instructions publication ENET IN002 Provides information on installing EtherNet IP modules EtherNet IP Secure Communication User Ma
24. Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 2g 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity AkV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz Rockwell Automation Publication 1756 TD003D EN E February 2013 27 1756 ControlLogix Communication Modules Specifications Table 23 Environmental Specifications 1756 DH485 Module Attribute EFT B immunity IEC 61000 4 4 1756 DH485 2 kV at 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line earth CM on communication ports Conducted RF immunity IEC 61000 4 6 Table 24 Certifications 1756 DH485 Module 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certification 1756 DH485 c UL us UL Listed for Class
25. a DH network including the following Preconfigured modem e Communication module e DIN rail mounting hardware e Associated cables Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications SynchLink Communication The SynchLink module provides time synchronization and data broadcasting capabilities for distributed motion and coordinated drive control The 1756 SYNCH SynchLink module connects a ControlLogix chassis to a SynchLink fiber optic communication link The module does the following e Coordinates Coordinated System Time across multiple ControlLogix chassis e Moves a limited amount of data from one chassis to another at a high speed e Lets one controller consume motion axes data from a controller in another chassis Table 25 Technical Specifications 1756 SYNCH Module Attribute 1756 SYNCH SynchLink data rate 5 Mbps Operating wavelength 650 nm red Type of communication Synchronous Frame period 50 us Frame parameters 3 Flags 3 bytes Control field 1 byte Data field 24 bytes CRC field 2 bytes Current draw 5 1V DC 1200 mA Current draw 24V DC 3mA Power dissipation 6 2W Thermal dissipation 21 2 BTU hr Slot width 1 Module location Chassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC7
26. d Process Control Equipment for Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with the following e EN 61326 1 Meas Control Lab Industrial Requirements e EN61000 6 2 Industrial Immunity e EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B Rockwell Automation Publication 1756 TD003D EN E February 2013 23 1756 ControlLogix Communication Modules Specifications Table 18 Certifications 1756 DH and Remote 1 0 Modules CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EX European Union 94 9 EC ATEX Directive compliant with the following e EN 60079 15 Potentially Explosive Atmospheres Protection n e EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X I Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Table 19 Technical Specifications 1756 DH and Remote 1 0 XT Module Attribute Communication rate 1756 DHRIOXT 57 6 Kbps 115 2 Kbps 230 4 Kbps DH communication connections 32 DH messages per DH module Remote 1 0 communication connections Rem
27. en permission of Rockwell Automation Inc is prohibited Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation Rockwell Software Allen Bradley ControlLogix ControlLogix XT Data Highway Plus DH KwikLink Logix5000 PLC S PanelView SLC Stratix 8300 Stratix 5700 Stratix 8000 Stratix 6000 Stratix 2000 RSLinx RSLogix NetLinx Studio 5000 and SynchLink are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1756 TD003D EN E February 2013 Supersedes Publication 1756 TD003C EN E December 2010 Copyright 20
28. ent compliant with Article 58 2 of Radio Waves Act Clause 3 DeviceNet ODVA conformance tested to DeviceNet specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories DeviceNet Network Cat No Description KwikLink Lite flat media KwikLink Lite flat media is a newer ODVA approved solution for wiring DeviceNet networks Drop lines for connecting nodes are added by using the KwikLink Lite two piece connectors This cable system supports the intermixing of DeviceNet cable types thin round with flat All of the KwikLink Lite connectors provide insulation displacement technology with reduced assembly time KwikLink flat media The KwikLink flat media system provides a modular cabling method with its flat four wire cable and Insulation Displacement Connectors IDCs The KwikLink system allows nodes to be added to the network without severing the trunkline Cutting or stripping of the trunkline is eliminated as is the need for predetermined cable lengths Round media Round trunk cable is available in bulk spools or as pre molded cordsets or patchcords in varying lengths A wide variety of rugged durable DeviceNet components is available for use in round trunk systems Stainless steel versions of round cable system components are also available Thick trunk round media systems use thick cable for maxi
29. et fiber ring repeater long distance 1786 RPFRXL ControlNet fiber ring repeater extra long distance 1786 RPFS ControlNet fiber repeater short distance 1786 RPFM ControlNet fiber repeater medium distance For more information see ControlNet Media System Components List publication AG PA002 Rockwell Automation Publication 1756 TD003D EN E February 2013 17 1756 ControlLogix Communication Modules Specifications DeviceNet Network The DeviceNet network is open providing connections between simple industrial devices such as sensors and actuators and higher level devices such as controllers and computers The DeviceNet network uses the Common Industrial Protocol CIP to control configure and collect data for industrial devices Table 13 Technical Specifications 1756 DNB DeviceNet Module Attribute 1756 DNB E DeviceNet communication rate 125 Kbps 500 m max 250 Kbps 250 m max 500 Kbps 100 m max Number of nodes max 64 Current draw 5 1V DC 400 mA Current draw 24V DC OmA DeviceNet current draw 24V DC 60 mA DeviceNet voltage range 11 25V DC CL 2 SELV Power dissipation 3 5W Thermal dissipation 11 9 BTU hr Isolation voltage 50V continuous basic insulation type DeviceNet network to backplane Type tested at 853V AC for 60s No isolation between USB and backplane Slot width 1 Module location Chassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1
30. f their control system Rockwell Automation Publication 1756 TD003D EN E February 2013 Provides information on system architecture configuring secure communication and Provides general guidelines for installing a Rockwell Automation industrial system 1756 ControlLogix Communication Modules Specifications Available Communication Modules Network Cat No Description Page EtherNet IP 1756 EN2F EtherNet IP bridge fiber 256 Logix connections 5 1756 EN2T EtherNet IP bridge copper 256 Logix connections 5 1756 EN2TSC EtherNet IP secure communication module 5 1756 EN2TR EtherNet IP bridge embedded switch copper 5 Supports as many as 8 axis of motion 1756 EN3TR EtherNet IP bridge embedded switch copper 5 Supports as many as 128 axis of motion 1756 ENBT EtherNet IP bridge copper 128 Logix connections 5 1756 EWEB Ethernet web server 128 Logix connections Class 3 messaging only 5 1756 EN2TXT ControlLogix XT EtherNet IP bridge copper 256 Logix connections 7 1756 EN2TRXT ControlLogix XT EtherNet IP bridge module with embedded switch 7 ControlNet 1756 CN2 B 1756 CN2R B ControlNet bridge 128 Logix connections 11 1756 CNB 1756 CNBR ControlNet bridge 64 connections recommend using only 40 48 Logix 11 connections for 1 0 1756 CN2RXT ControlLogix XT ControlNet bridge 128 Logix connections 11 DeviceNet 1756 DNB E DeviceNet bridge 19 Data Highway Plus 1756 DH
31. hassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 Ports 2 individually selectable for DH or remote 1 0 1 for remote 1 0 Screw terminal torque 0 5 0 6 Nem 5 7 bein Wire size 0 519 mm 20 AWG Belden 9463 copper twinaxial Wiring category 2 on DHRIO ports 2 on RIO ports 3 on local programming port North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 22 Rockwell Automation Publication 1756 TD003D EN E February 2 013 1756 ControlLogix Communication Modules Specifications Table 17 Environmental Specifications 1756 DH and Remote I 0 Modules Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DHRIO E 1756 RI0 B 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat
32. he communication module you use for the connection If a message path routes through a communication module the connection related to the message also counts towards the connection limit of that communication module EtherNet IP Network The Ethernet Industrial EtherNet IP network protocol is an open industrial networking standard that supports both real time I O messaging and message exchange The EtherNet IP network uses al off the shelf Ethernet communication chips and physical media If you need to e Control 1 0 modules and drives e Actas an adapter for 1 0 on remote EtherNet IP links e Communicate with other EtherNet IP devices messages and HMI Bridge EtherNet IP links to route messages to devices on other networks Select this interface 1756 EN2F bridge 1756 EN2T bridge 1756 ENBT bridge Support device level ring DLR and linear topologies 1756 EN2TR bridge 1756 EN3TR bridge Provide control in environments where temperatures range from 25 70 C 13 158 F 1756 EN2TXT bridge 1756 EN2TRXT redundant bridge Secure access to a control system from within the plant network 1756 EN2TSC bridge e Use an Internet browser to remotely access tags in a ControlLogix controller e Communicate with other EtherNet IP or generic Ethernet devices messaging only no 1 0 control Bridge EtherNet IP links to route messages to devices on other networks Rockwell Automation Publication 1756 TD003D
33. ion Publication 1756 TD003D EN E February 2013 31 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http www rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this publication are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without writt
34. kaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 2g 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on ControlNet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on ControlNet port Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 16 Rockwell Automation Publication 1756 TD003D EN E February 2013 Table 12 Certifications 1756 ControlNet XT Module 1756 ControlLogix Communication Modules Specifications Certification 1756 CN2RXT B c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Require
35. le Controllers Clause 8 Zone A amp B CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n e EN60079 0 General Requirements Il 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 EtherNet IP ODVA conformance tested to EtherNet IP specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories Ethernet Network Cat No 1585J M8PBJM x Description Ethernet RJ45 patchcord X 2 2m 5 5m or 10 10 m Specifications 8 conductor teal riser PVC cable flex rated cable also available 1585J M8CC H RJ45 insulation displacement connector IDC 0 128 0 325 mm 26 22 AWG Cat 6 IDC no tool required 1585J M8CC C RJ45 crimp connector with boot qty 50 pieces 0 128 0 205 mm 26 24 AWG Cat 5e requires crimp tool for assembly 1585A JCRIMP Crimp tool 9300 RADES Remote access dial in kit 56 Kbps modem connection to devices on an Ethernet network Rockwell Automation Publication 1756 TD003D EN E February 2013 9 1756 ControlLogix Communication Modules Specifications Stratix S
36. ments EN61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions EN61131 2 Programmable Controllers Clause 8 Zone A amp B CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 al ControlNet International conformance tested to ControlNet specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories ControlNet Network Cat No Description Taps 1786 TCT2BD1 T tap straight IP67 rated 1786 TPR T tap right angle 1786 TPS T tap straight 1786 TPYR Y tap right angle 1786 TPYS Y tap straight Cables 1786 CP Programming cable to ControlNet RJ45 port 1786 RG6 ControlNet network shield high flex cable 1756 RG6F ControlNet network quad shield high flex coax cable Other 1786 TNCLXT4 ControlNet IP67 termination resistor 1786 XT ControlNet termination resistor Repeaters 1786 RPA ControlNet modular repeater adapter 1786 RPCD ControlNet coaxial hub repeater 1786 RPFRL ControlN
37. mum DeviceNet trunk line length e Round media thin trunk systems use thin cable to reduce maximum trunk line distances with a more compact and cost effective installation for some applications Thin cable outer jacket material is TPE for additional chemical resistance For more information on selecting DeviceNet media see the NetLinx Selection Guide publication NETS SG001 20 Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications DH and Remote 1 0 Networks The Data Highway Plus network supports messaging between devices The remote I O link connects to remote I O chassis and other intelligent devices The 1756 DHRIO module supports messaging between devices on DH networks The remote I O functionality enables the module to act as a scanner for transferring digital and block transfer data to and from remote I O devices The 1756 RIO module can act as a scanner or adapter on a remote I O network In addition to digital and block transfer data the 1756 RIO module transfers analog and specialty data without message instructions Example Configuration DH Network PLC 5 1784 U2DHP Studio 5000 environment i i PanelView Plus z ControlLogix ACSO 1756 DHRIO Rockwell Automation Publication 1756 TD003D EN E February 2013 21 1756 ControlLogix Communication Modules Specifications Example Configuration Remote 1 0 Network
38. munity IEC 61000 4 3 Table 27 Certifications 1756 SYNCH Module 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM at 900 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz Certification 1756 SYNCH UL UL Listed Industrial Control Equipment See UL file 65584 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA file LR69960C CE European Union 2004 108 EC EMC Directive compliant with the following e EN 61131 2 Programmable Controllers Clause 8 Zone A amp B e EN 61326 1 Meas Control Lab Industrial Requirements e EN61000 6 2 Industrial Immunity e EN 61000 6 4 Industrial Emissions C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details 30 Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Accessories SynchLink Network Description 1403 CFxxx Rockwell Automation fiber optic cable assembly HCP M0200T VO1RK Lucent Technologies 200 um simplex cable Rockwell Automat
39. nual publication ENET UM003 diagnostics Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Studio 5000 Environment The Studio 5000 Engineering and Design Environment combines engineering and design elements into a common environment The first element in the Studio 5000 environment is the Logix Designer application The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix5000 controllers for discrete process batch motion safety and drive based solutions r Rockwell Software Studio 5000 Create Open New Project Explore Existing Project Help From Import Sample Project Release Notes From Sample Project From Upload About Recent Projects g Sept_Test g Integrated_Motion_Co g August_2012 The Studio 5000 environment is the foundation for the future of Rockwell Automation engineering design tools and capabilities This environment is the one place for design engineers to develop all of the elements o
40. omation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Table 3 Certifications 1756 EtherNet IP Modules Certification c UL us 1756 EN2F 1756 EN2T 1756 EWEB 1756 EN2TSC 1756 EN2TR 1756 EN3TR 1756 ENBT UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with e EN 61326 1 Meas Control Lab Industrial Requirements e EN61000 6 2 Industrial Immunity e EN 61000 6 4 Industrial Emissions e EN 61131 2 Programmable Controllers Clause 8 Zone A amp B C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n e EN 60079 0 General Requirements e 13 GExnAIICT4GcX FM
41. ote 1 0 scanner only 32 logical rack connections per remote 1 0 channel 16 block transfer connections per remote 1 0 channel Connections supported max 32 Current draw 5 1V DC 850 mA Current draw 24V DC 1 7mA Power dissipation 45W Thermal dissipation 15 4 BTU hr Isolation voltage 30V continuous basic insulation type DHRIO A B to backplane and DHRIO A programming port to DHRIO B No Isolation between DHRIO A and Programming port Type tested at 853V AC for 60 s Slot width 1 Module location Chassis based any slot Chassis 1756 A4LXT 1756 A5XT 1756 A7XT 1756 A7LXT Power supply standard 1756 PBXT Power supply redundant None Ports 2 individually selectable for DH or remote 1 0 Screw terminal torque 0 5 0 6 Nem 5 7 Ibein Wire size 0 519 mm2 20 AWG Belden 9463 copper twinaxial Wiring category 2 on DHRIO ports 3 on local programming port North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 24 Rockwell Automation Publication 1756 TD003D EN E February 2013 Table 20 Environmental Specifications 1756 DH and Remote 1 0 XT Module Attribute Temperature operating IEC 60068
42. rts Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Rockwell Automation Publication 1756 TD003D EN E February 2013 19 1756 ControlLogix Communication Modules Specifications Table 15 Certifications 1756 DNB DeviceNet Module Certification 1756 DNB E c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity N61000 6 4 Industrial Emissions e EN61131 2 Programmable Controllers Clause 8 Zone A amp B CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements II 3 G Ex nA IIC T4 Gc X FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations KC Korean Registration of Broadcasting and Communications Equipm
43. st traffic e Requires diagnostics data e Requires security options Stratix 6000 fixed managed switch Requires easy setup and direct replacement of switches e Is a small isolated network Stratix 2000 unmanaged switch 10 Rockwell Automation Publication 1756 TD003D EN E February 2013 ControlNet Network 1756 ControlLogix Communication Modules Specifications The ControlNet network is an open control network for real time high throughput applications The ae ControlNet network uses the Common Industrial Protocol CIP to combine the functionality of an I O network E and a peer to peer network providing high speed performance for both functions The ControlNet network gives you deterministic repeatable transfers of all mission critical control data in addition to supporting transfers of If your application requires 128 ControlNet connections per communication module non time critical data I O updates and controller to controller interlocking always take precedence over program uploads and downloads and messaging Select this interface 1756 CN2 B 1756 CN2R B 1756 CN2RXT B Control in environments where temperatures range from 25 70 C 13 158 F 1756 CN2RXT 40 48 ControlNet connections per communication module 1756 CNB 1756 CNBR Connect to Other Devices via a ControlNet Network The Studio 5000 environment supports a generic ControlNet module that allows connections to
44. t with Article 58 2 of Radio Waves Act Clause 3 FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations al ControlNet International conformance tested to ControlNet specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details 14 Rockwell Automation Publication 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Table 10 Technical Specifications 1756 ControlNet XT Module Attribute 1756 CN2RXT B Configuration Redundant ControlNet communication rate 5 Mbps Logix communication connections 128 Connections supported max 1319 Number of nodes max 99 Current draw 5 1V DC 1300 mA Current draw 24V DC 3mA Power dissipation 67W Thermal dissipation 22 9 BTU hr Isolation voltage 30V continuous basic insulation type ControlNet A B to backplane and ControlNet A to ControlNet B No isolation between USB and backplane Type tested at 500V AC for 60 s Weight approx 0 293 kg 0 64 Ib Slot width 1 Module location Chassis based any slot Chassis 1756 A4LXT 1756 A5XT 1756 A7XT 1756 A7LXT Power supply standard 1756 PAXT 1756 PBXT Power supply redundant None ControlNet port 2 ControlNet BNC ControlNet cable 1786 RG6 quad shield RG6 coaxial cable USB port U
45. tion 1756 TD003D EN E February 2013 1756 ControlLogix Communication Modules Specifications Table 8 Environmental Specifications 1756 ControlNet Modules Attribute 1756 CN2 B 1756 CN2R B 1756 CNB E 1756 CNBR E Temperature operating 0 60 C 32 140 F IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock Temperature surrounding air max 60 C 140 F Temperature storage 40 85 C 40 185 F IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity 5 95 noncondensing IEC 60068 2 30 Test Db Unpackaged Damp Heat Vibration 29 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz IEC 61000 4 3 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 3 kV at 5 kHz on ControlNet ports IEC 61000 4 4 Surge transient immunity
46. witches To effectively manage real time control and information flow throughout the manufacturing and IT enterprise Rockwell Automation offers a full portfolio of industrial Ethernet switches and media including a line of Stratix switches integrated with Cisco technology The Stratix line of switches includes modular managed fixed managed and unmanaged switches For detailed specifications for Stratix switches refer to the Stratix Ethernet Switch Specifications Technical Data publication 783 TD 001 If your application Requires full Ethernet capability full firmware or a streamlined set of Ethernet features lite firmware Integrates enterprise and manufacturing environments e Can benefit from using an SD card instead of onboard flash to easily restore a switch configuration in case of failure or to easily duplicate configurations when you are deploying a new network Requires encryption SSH SNMPv3 HTTPS Select Stratix 5700 modular managed switch e Requires Layer 3 routing e Integrates enterprise and manufacturing environments e Manages multicast traffic Requires diagnostics data e Requires security options Stratix 8300 modular managed switch Integrates enterprise and manufacturing environments e Manages multicast traffic e Requires diagnostics data e Requires security options Stratix 8000 modular managed switch Integrates plant floor devices e Manages multica