InBio X60 Series Access Control Panel User Manual
Contents
1. 1 Reader 2Reader 3 Reader 8 Reader Connection between InBio460 and InBio Readers YA Note In InBio reader connection if the reader shares the power with the control panel it is recommended that the wire should be less than 100 meters If you need to use a longer distance please use a separate power supply 2 Connected with Wiegand readers InBiol60 can connect two Wiegand readers in the one door two way mode InBio260 provides four readers which can be connected in the two door two way mode InBio460 provides four readers which can be connected in the two door two way or four door one way mode 19 InBio X60 Series User Manual The Wiegand interfaces provided by the InBio series can be connected to different types of readers If your card reader does not use the voltage of DC 12V an external power supply is needed A reader should be installed at a height of about 1 4 meter above the ground and at a distance of 30 50mm away from a door frame vow om paw oew k 4 27 473 ve a WOU ees Wiegand Reader nce CRW nnee LancorW mure l ori 2 Door anal Wiegand Reader Reyes non poun FELTI EK ETTE H SET 3 Door Wiegand Reader pe ET REERERGSES FERRE AZEZY AGE KER KGS AGE it moun 53 oo s238ER 9 AA Wiezand Reader Ti ak ee A Connection between InBio460 and Readers 20 3 Connection and Installation 3 7 Relay Output C
2. l l l l l l l Lock powe x Q O O Z DC12V 3 Dry mode External power supply for NO Lock Dry mode jumper 12345 Access control rc NO LOCK pou 4 Dry mode External power supply for NC Lock 23 InBio X60 Series User Manual m an am an an an az am am am am am a LI Lock power g en ai 7 S Qi S t AOU NC LOCK a Si DI oO aril i E DC12V kman ee a e kk yn i 5 Dry mode NO Lock under the binary value control 6 Dry mode NC Lock under the binary value control 24 3 Connection and Installation GVEZI Jjedwnf epou Aug NC LOCK 25 InBio X60 Series User Manual 3 8 System Power Supply Structure Master switch of fire prevention power supply UPS Management workstation Coatrol panel Control panel Control panel power 12V power 12V power 12V Master switch of building power supply t Coatrol Panel 28 Control Panel n Control Panel Coatrol panel Control panel Control panel power i2V power 12V power 12V 0 Master switch of building 220V AV power supply 18 Control Panel 26 Control Panel a Control Panel An access control operator panel is powered by 12V DC Generally to reduce 26 3 Connection and Installation power interference between control panels each control panel should be powered separately When high reliabilit
3. W Violation of any of the following cautions is likely to lead to equipment failure or even personal injury e Before installation switch off the external circuit that supplies power to the system including lock power Before connecting the equipment to power supply ensure the output voltage is within the specified range Never connect power before completion of installation 1 Important Security Instructions 1 2 Installation Cautions 1 The conduits of wires under relay must be matched with metaled conduits other wires could use PVC conduits to prevent failure caused by rodent damage Although a control panel is designed with good antistatic lightning proof and leakage proof functions ensure its chassis and the AC ground wire are connected properly and the AC ground wire is grounded physically 2 It is recommended to not plug unplug connection terminals frequently when the system is energized Be sure to unplug the connection terminals before starting any relevant welding job 3 Do not detach or replace any control panel chip without authorization because unprofessional operation may cause damage to the control panel 4 It is recommended to not connect any other auxiliary devices without permission Before all non routine operations must communicate with our engineers in advance 5 A control panel should not share one power supply with any other large current device 6 It is recommended that reader
4. Auxiliary Input D EXTRS485 E State Indicator Door Button D Wiegand reader B Wiegand reader B InBio X60 Series User Manual InBio260 Terminal Connection diagram SD Card Slot LINK gt Ethemet interface ACT gt Dip switch PC RS485 interface D Auxiliary output D Auxiliary output2 C 1 Door C 2Door A Lock Power A Power of Control Panel A FE AA inox MONN l a 3 pi a Q 3 2 14 Auxiliary Input D arasus E State Indicator 1 Door Exit Button D 1 Door Wiegand in reader B 1 Door Wiegand out reader B Exit Button D 2 Door Wiegand in reader B 2 Door Wiegand out wader B pou 3 Connection and Installation InBio460 Terminal Connection diagram SD Card Slot LINK gt Auxiliary Input D Auxiliary Input2 D Auxiliary Input3 D Ethernet interface ACT gt Wiegand reader B Dip switch Auxiliary Input4 D EXT RS485 E PC RS485 interface 4 a D Awiliary output on i te tnt D Auxiliary output2 si Door 5 D Auxiliary output3 i ai D Auxiliary output4 2 Door Exi Button D C 1 Door 2 Door Wiegand reader B C 2 Door 3 Door Exit Button D C 3Doo 3 Door 7 Wiegand reader B P 4 Door C H 4Door 3 Exit Button D A S EE EE enn enn ae enn E TR SPECS CRESS SHEER EGZEJR FHS EZE EJE Ep 001 4 Door A Lock Power Wiegand reader B A Power of Control Panel jo4uon
5. ON 60 OFF OFF ON ON ON ON 61 ON OFF ON ON ON ON 62 OFF ON ON ON ON ON 63 ON ON ON ON ON ON 2 Restoring factory setting The silk screened 7 number 7 of the DIP switch is the switch for restoring system settings The switch is set to OFF by default When it is moved upwards and downwards for three times within 10 seconds and finally returned to OFF position the factory settings will be restored after the access control panel is restarted 3 Terminal resistance setting Number 8 is for setting the RS485 termination resistance Putting the switch to ON position is equivalent to parallel connection of a 120ohm termination resistance between 485 and 485 34 4 System Networking kat pRS485 Terminal Resistance i 4 gan konnnen gt Restore Factory Settings 35
6. battery terminals Do not incinerate Flush with water at once if contact is made with electrolyte Acid 2 Introduction Do not attempt to disassemble the battery 2 3 Indicators Description When the InBio160 260 460 is powered on normally the POWER indicator red is lit constantly the RUN indicator green flashes indicating the system is normal and other indicators are all off Except the cases as following cases 1 LINK indicator green Constant Light indicates TCP IP communication is normal 2 ACT indicator yellow Flashing indicates data is in transmitting through TCP IP communication 3 EXT RS485 indicator yellow amp green Flashing indicates it is sending or receiving data through RS485 communication 4 PC RS485 indicator yellow amp green Flashing indicates it is sending or receiving data through RS485 communication 5 CARD indicator yellow Flashing indicates a card is punched on reader See the indicators in the following figure InBio X60 Series User Manual 9 z AUXI a z AUX2 2 z AUX c z AUX4 SWITCH Zr 3 0 a STATE AUXOUT1 9 z B s G zo BUTTON1 AUXOUT2 999 2882 ze a8 33 READER BUTTON2 AUXOUT3 AUXOUT4 Lock 9859 Z z 8 8 9 z 9 z READER2 z BUTTONS READERS BUTTON4 READER4 CI caro Co rv CI rower Advanced Access Control PO in the InBio460 1cators 1n ti Ind 3 Connec
7. eer com aso m iz em fi a we ot 1 2 Door m fe HL Door Sensor hal oe g H Exit Button w tou sen 2 Door Sensor F gwo 0 come 3 Door Exit Buttoe na RI Door Sensor wo w cou s Ri Door Sensor L ae 4 Door wo ki Exit Button tou wo si o4U0J S800Y PEoUBAPY Connections between InBio460 and external accessories TA Note The above shows InBio460 By contrast InBio160 provides one auxiliary input interface InBio260 provides two and InBio460 provides four 3 6 Connection with Readers The control panel supports InBio biometric verification reader and Wiegand reader The InBio reader executes all operations including storage verification etc In the 18 3 Connection and Installation control panel There is no need to re register the fingerprints after changing the reader because of the existing biometric reader connection 1 Connected with InBio readers InBio160 can connect two InBio readers in the one door two way mode InBio260 provides four readers which can be connected in the two door two way mode InBio460 provides eight readers which can be connected in the four door two way mode 485 reader connection First use the software DIP switch or keypad method to set the address devices number of the 485 reader For example 1 2 the odd number is to enter reader and the even number is to exit reader where the 485 address is 1 2 and the door number is 1
8. not attempt unauthorized repair of the equipment Disassembly or detachment is likely to cause shock or other risks All repair work should be done by qualified repair personnel 7 Damages in need of repair In any of the following cases first disconnect the AC DC power supply from the equipment and notify qualified repair personnel for repairs e Ifthe power cord or connector is damaged e Ifthereis presence of liquid or any other foreign object into the equipment e Ifthe equipment is wetted or exposed to bad weather rain snow etc If the equipment does not work properly even though it is operated as instructed Please be sure to adjust only the control components specified in the operation instructions Incorrect adjustment of other control components may cause damage to the equipment and add to troubleshooting complexity for the qualified technicians e Ifthe equipment is dropped or its performance noticeably changes InBio X60 Series User Manual 8 Replacing components If it is necessary to replace a component the repair personnel must use only the substitutes specified by the manufacturer 9 Security inspection After the equipment is repaired the repair personnel are should conduct a security inspection to ensure the equipment is working properly 10 Power supply Operate the equipment with only the type of power supply indicated on the label Contact the operator for any uncertainty about the type of power supply
9. ss9899y peouvapy 15 Descriptions of the terminals InBio X60 Series User Manual 1 The auxiliary input may be connected to infrared body detectors etc Used for signal detection of human body only does not used for invasion burglar alarm application 2 The auxiliary output may be connected to alarms cameras door bells etc 3 All the terminals mentioned above are set through relevant access control software SD card function Backup event records of access control for client Descriptions of the terminals Terminals on the InBio X60 series control panel InBio160 InBio260 InBio460 No Functional Port One Door Two Door Four Door One Way Two Way Two Way Two Door Two Way i Wiegand card reader 2 4 P interface 2 Exit button 1 2 4 3 Control lock relay 1 2 4 4 Door sensor 1 2 4 a Extension input 1 2 4 6 Extension output 1 2 4 7 InBio Reader 2 4 8 B RS485 i l x a J communication 9 RS485 ice 4 N J communication 10 TCP IP y y y 16 3 Connection and Installation 3 5 Connection with External Accessories 1 Door sensor A door sensor is used to detect the open closed status of a door With a door sensor switch an access control panel can detect illegal opening of a door and will trigger an alarm Moreover if a door is not closed within a specified period of time after it is opened the door control panel will also prompt an alarm It is recomme
10. FF ON OFF 19 ON ON OFF OFF ON OFF 20 OFF OFF ON OFF ON OFF 32 4 System Networking 21 ON OFF ON OFF ON OFF 22 OFF ON ON OFF ON OFF 23 ON ON ON OFF ON OFF 24 OFF OFF OFF ON ON OFF 25 ON OFF OFF ON ON OFF 26 OFF ON OFF ON ON OFF 27 ON ON OFF ON ON OFF 28 OFF OFF ON ON ON OFF 29 ON OFF ON ON ON OFF 30 OFF ON ON ON ON OFF 31 ON ON ON ON ON OFF 32 OFF OFF OFF OFF OFF ON 33 ON OFF OFF OFF OFF ON 34 OFF ON OFF OFF OFF ON 35 ON ON OFF OFF OFF ON 36 OFF OFF ON OFF OFF ON 37 ON OFF ON OFF OFF ON 38 OFF ON ON OFF OFF ON 39 ON ON ON OFF OFF ON 40 OFF OFF OFF ON OFF ON 41 ON OFF OFF ON OFF ON 42 OFF ON OFF ON OFF ON 43 ON ON OFF ON OFF ON 44 OFF OFF ON ON OFF ON 45 ON OFF ON ON OFF ON 46 OFF ON ON ON OFF ON 47 ON ON ON ON OFF ON 48 OFF OFF OFF OFF ON ON 33 InBio X60 Series User Manual 49 ON OFF OFF OFF ON ON 50 OFF ON OFF OFF ON ON 51 ON ON OFF OFF ON ON 52 OFF OFF ON OFF ON ON 53 ON OFF ON OFF ON ON 54 OFF ON ON OFF ON ON 55 ON ON ON OFF ON ON 56 OFF OFF OFF ON ON ON 57 ON OFF OFF ON ON ON 58 OFF ON OFF ON ON ON 59 ON ON OFF ON ON
11. InBio X60 Series Access Control Panel User Manual Version 1 4 Date Nov 2015 About This Manual This manual introduces the installation connection and user manual of the InBio X60 Series Access Control Panel Table of Contents Table of Contents 1 Important Security Instructions 00 eee ee eeeeseeeeeeeeeeeeseeeeeeeeaees 1 1 1 Important Security Instructions 0 eee eeeeeeeeeseeteeeeeees 1 1 2 Installation Cautions eonenni iT NEE 3 25 AMMO MUCH OM kaa pet iii ko Deed ee vre vie A A e ia 5 2 1 System Function Paramet rS ireveeoeeoooeoonoouooosossoonoonooone 9 2 2 Product Technical Parameters cscesccesccesceeseeeeeeeeeeeeeeeeeeeees 6 2 3 Indicators Description neniet S 7 3 Connection and Installation nenen cee eeseeseceneceneceseceseeeseceaeeeaeeeneeeaeees 9 3 1 Panel Box Installation eee eesceeseeeseeeseeeneeeneeeseeeeeeeneeeneeeeees 9 3 2 Installation and Wiring ee eee ceeee ee ceeeeeetaeeaeeneeeaees 10 3I System S WUCIUITE a oto ire ak odas kav babe Dei paske PDA beki kai fon 11 3 4 Connection Terminals 0urtieroteroereeresorososososoaosoaosososononone 13 3 5 Connection with External Accessories 17 3 6 Connection with Readers oo eee ceeeeeseeeeceeeeseeseeeeeeeeeaees 18 3 7 Relay Output Connection 0 cece eeeeceesesseceeeeeeeseeeeeeeesees 21 3 8 System Power Supply Structure oe eee eeeeeeeeeeeeeeees 26 A System NCCworkin g iii cscs csesseessesgucoesdesteesieveereoscoetuc
12. L Four door two way controlling inBIO Reader InBio460 System Structure 11 InBio X60 Series User Manual TA Note The above example shows the InBio460 By contrast only one door two way access is applicable to the InBio160 system only two door one way or two door two way access is applicable to the InBio260 system The Access Control Management System consists of two parts a management workstation PC and a control panel They communicate via TCP IP or RS485 networks On a 485 bus each management workstation can be connected with up to 63 InBio control panels preferably fewer than 32 The communication wires should be kept as far away from high voltage wires as possible and should be neither routed in parallel with nor bundled with power wires A management workstation is actually a PC connected to the network By running the Access Control Management software installed on the PC Access Control Management personnel can remotely perform various management functions like adding deleting a user viewing event records opening closing doors and monitoring the status of each door in real time 12 3 Connection and Installation 3 4 Connection Terminals InBio160 Terminal Connection diagram SD Card Slot nn LINK Ethernet interface ACT gt ESE mH OTH Dome i OF d Dip switch PC RS485 interface D Auxiliary output A Power of Control Panel a i De Q i Q 3 Q 13
13. ards Use of dual communication technologies The Ethernet and the RS485 industrial bus for reliable communications A watchdog hardware built in the control panel to prevent crash Over current over voltage and inverse voltage protection for input of power supply to the control panel Over current protection for the power supply to card readers Instant over voltage protection for all input output ports Instant over voltage protection for communication ports InBio X60 Series User Manual 2 2 Product Technical Parameters Working power supply Rated voltage 12V 42090 DC Rated current 2A Working environment Temperature 0 C 55 C humidity 10 80 Electronic lock relay output The maximum switching voltage 36V DC The maximum switching current 2A Auxiliary relay output The maximum switching voltage 36V DC The maximum switching current 1 25A With detachable connection terminals made of alloy steel non magnetic flange materials Outline dimensions of the control panel 185 1mm length x 106mm width x 36mm thickness for InBio160 260 226mm length x 106mm width x 36mm thickness for InBio460 eExternal box dimensions 395mm x 350mm x 135mm Value regulated lead acid battery Constant voltage charge voltage regulation Cycle use 14 5V 14 9V 25 Initial current less than 2 88A Standby use 13 6V 13 8V 25 Caution Do not charge in a gas tight container Do not short the
14. el 485 networking 485 485 GND Serial port cable Incorrect ontrol panel connections for 485 485 GND 485 networking ADA Pas j RS485 Communication System Networking 4 4 DIP Switch Settings 1 485 address setting Number 1 6 of the DIP switch are reserved to set the device number for RS485 communication The code is binary and the lower places are in the front When the switch is set to ON position it indicates 1 on when the switch is set downwards it indicates 0 off For example to set a device number 39 1 2 4 32 which corresponds to the binary code 111001 put number 1 2 3 and 6 to ON position as illustrated below 31 InBio X60 Series User Manual 00 O NT 3 3 465 67 8 485 address setting table Switch Setting Place Address 1 2 3 4 5 6 Address No l 2 4 8 16 32 01 ON OFF OFF OFF OFF OFF 02 OFF ON OFF OFF OFF OFF 03 ON ON OFF OFF OFF OFF 04 OFF OFF ON OFF OFF OFF 05 ON OFF ON OFF OFF OFF 06 OFF ON ON OFF OFF OFF 07 ON ON ON OFF OFF OFF 08 OFF OFF OFF ON OFF OFF 09 ON OFF OFF ON OFF OFF 10 OFF ON OFF ON OFF OFF 11 ON ON OFF ON OFF OFF 12 OFF OFF ON ON OFF OFF 13 ON OFF ON ON OFF OFF 14 OFF ON ON ON OFF OFF 15 ON ON ON ON OFF OFF 16 OFF OFF OFF OFF ON OFF 17 ON OFF OFF OFF ON OFF 18 OFF ON OFF O
15. etwork Communication 1 RS485 communication wires are made of internationally accepted RVVP wires shielded twisted pairs which prove effective to prevent and shield interference RS485 communication wires should be connected by means of bus cascade instead of in a star form to achieve a better shielding effect by reducing signal reflection during communications A single 485 bus can be connected with 63 access control operator panels at most but preferably should be connected with less than 32 To eliminate signal attenuation in communication cables and suppress interference if the bus is longer than 300 meters one 120ohm resistance is usually inserted between the first and last access control operator panels on the RS485 bus In InBio reader connection if the reader shares the power with the control panel it is recommended that the wire should be less than 100 meters in length If you need to use in a longer length please use a separate power supply For this access control operator panel putting place 8 of the DIP switch to the ON position is equivalent to parallel connection of one 120ohm resistance between the 485 and 485 lines As shown in the figure below put number 8 of the DIP switches of the first and last control panels to ON position 30 4 System Networking Correct ontrol panel ontrol panel connections for 5 485 485 485 GND 485 networking k he amp Incorrect connections for ontrol pan
16. hiesteastcesbavstesvedts 28 4 1 System Wiring and Wires Requirements sssss 28 4 2 TCP IP Network Communication ccceeeeseeseeseeeteeenneesees 29 4 3 RS485 Network Communication cece eseeeeeeeeeeeeaes 30 4 4 DIP Switch Settings srna a pou aa oke poo besse yon 31 inBIOX60 Series User Manual 1 Important Security Instructions 1 1 Important Security Instructions 1 Read follow and keep the instructions Before operating the equipment read and follow strictly all security and operation instructions Please keep the instructions for reference 2 Accessories Please use the accessories recommended by the manufacturer or delivered with the product Any other related product is not recommended as the major alarming or monitoring system The major alarming or monitoring system should comply with the local applicable fire prevention and security standards 3 Installation cautions Do not place this equipment on any unstable table tripod mount support or base to prevent the equipment from falling and becoming damaged or worse cause severe personal injury Therefore it is important to install the equipment as instructed by the manufacturer 4 All peripheral devices must be grounded 5 No external connection wires can be exposed All connections and idle wire ends must be wrapped with insulating tapes to prevent accidental contact with exposed wires and damaging the equipment 6 Repair Do
17. n electronic lock at the moment of switching off on it is necessary to InBio X60 Series User Manual connect a diode in parallel please use the FR107 delivered with the system with the electronic lock to release the self induced electromotive force 15 It is recommended that an electronic lock and a control panel should use respective power supplies 16 It is recommended that the power supply included with the system be used as the control panel 17 In a place with strong magnetic interference galvanized steel conduit or shielded cables are recommended and proper grounding is required 18 Only be installed by professionals 2 Introduction 2 Introduction The Access Control Management System is a new modernized security management system that is an effective measure for security and protection management It is mainly used to manage entrances and exits of secured locations such as banks hotels equipment rooms offices smart communities and factories 2 1 System Function Parameters High speed 32 bit 400MHz CPU 32M RAM and 256M Flash Embedded LINUX operating system InBio160 supports one door one two way InBio260 supports two door one two way InBio460 supports two door two way or four door one way access control A maximum of 30 000 card holders 3 000 fingerprints and 100 000 offline event records Support of multiple Wiegand card formats and a password keypad compatible with various types of c
18. nded to select two core wires over 0 22 mm A door sensor may be omitted if it is unnecessary to monitor online the open closed status of a door trigger an alarm when the door is not closed for a long time or there is illegal access and use the interlock function 2 Exit button An exit button is a switch installed indoors to open a door When you press the button the door will be opened An exit button is fixed at a height of about 1 4 meters above the ground Ensure it is located in the right position without slant and its connection is correct and secure Cut off the exposed end of any unused wire and wrap it with insulating tape Note to prevent the electromagnetic interference such as light switches and computers It is recommended to use two core wires over 0 3mm as the connection wire between an exit button and a control panel 3 Auxiliary input InBiol60 provides one auxiliary input interface InBio260 provides two and InBio460 provides four which are connected to infrared body detectors etc Used for signal detection of human body only does not used for invasion burglar alarm application Auxiliary inputs are set through relevant access control software 17 InBio X60 Series User Manual ow a Auxiliary input Auxiliary Input 2 Auxiliary Input 3 Ww ow DIW 005 A7 A 478 P Auxiliary Input 4 LI EN a YAN ma cou un E oo En EL 1 Door a you Exit Button
19. onnection InBio160 has two relays by default one used as a control lock and the other used as an auxiliary output InBio260 has four relays by default two used as control locks and the other two used as auxiliary outputs InBio460 has eight relays by default four used as control locks and the other four used as auxiliary outputs The relays for auxiliary outputs may be connected to monitors alarms door bells etc Auxiliary outputs are set through relevant access control software A lock relay can be connected in the dry and wet modes while an auxiliary output relay cannot The following illustrates a relay output connection in the example of door connection 1 An access control panel provides multiple electronic lock outputs The COM and NO terminals are applicable to the locks that are unlocked when power is connected and locked when power is disconnected that is NO lock The COM and NC terminals are applicable to the locks that are locked when power is connected and unlocked when power is disconnected that is NC lock 2 The control panel supports dry mode and wet mode by using the jumper For wet mode short 2 3 and 4 5 terminals The control panel and the lock use the separate power supplies One is connected with 12V and GND of POWER interface for the control panel the other is connected with V and V of LOCK interface for the lock Dry mode jumper setting Short 1 2 and 3 4 and the device power suppl
20. rallel with nor share a conduit with large power electric wires like electronic lock wires and power cables If parallel wiring is unavoidable for environmental reasons the distance must be over 50cm e Try to avoid using any wire with a connector during wiring When a connector is indispensable it must be crimped or welded No mechanical force can be applied to the joint or branch of conductors e In a building distribution lines must be installed horizontally or vertically They should be protected in conduit like plastic or iron water pipes to be selected according to the technical requirements of indoor distribution Metal hoses are applicable to ceiling wiring but must be secure and visually appealing Shielding measures and shielding connection If the electromagnetic interference in the wring environment is found strong in the survey before 28 4 System Networking construction it is necessary to consider shielding protection for data cables when designing a construction scheme Overall shielding protection is required if there is a large radioactive interference source or wiring has to be parallel with a large current power supply on the construction site Generally shielding measures include Keeping a maximum distance from any interference source and using metal wiring troughs or galvanized metal water pipes to ensure reliable grounding of the connection between the shielding layers of data cables and the metal
21. s and buttons be installed at heights of 1 4 1 5m above the ground but the heights may be adjusted according to the customers usual practice 7 The appliance shall be installed and wired in accordance with national electrical code and by qualified personnel only 8 It is advised to install control panels at places easy of maintenance like a weak electric well 9 It is strongly recommended that the exposed part of any connection terminal should not be longer than 4mm to avoid short circuit or communication failure resulting from accidental contact with excessive exposed wires 10 To save access control event records download data periodically from control panels 11 Prepare for unexpected power failure according to application situations like connecting power supply with UPS 12 For InBio reader biometric fingerprint reader collect the fingerprint only all the other operations such as storage verification and etc execute in the control panel connections if the reader shares the power with the control panel it is recommended that the wire should be less than 100 meters If you need to use in the longer distances please use a separate power supply 13 The connection between a PC and a control panel should be less than 1200m for RS485 communications A length of 600m or less is recommended to increase communications stability 14 To protect the Access Control System against self induced electromotive force generated by a
22. tion and Installation 3 Connection and Installation 3 1 Panel Box Installation Installation steps for the control panel After the following installation fix the panel on the track first and then install other components to original positions A Serews Control Panel Thread holes 1 Get through the thread hole 115 2 Fix the box 115 3 Install other components Appearance and Internal of the panel box 1 State Indicator Box Lock Hole IBackup Battery 1 Control Panel H Temper Switch yo ontrol Panel Air Switch l l Panel Track oS Thread Hole Dissipation Hole Power Supply i Funol sais ERTS Panel Box Inside Get the Panel off the track InBio X60 Series User Manual 3 2 Installation and Wiring 20V ipit RS485 Communication Wire TCPAP Communication Wire Access Control Panel Wire Installation PA Notes 1 Before connection make sure the power supply is disconnected Any operation with power connected will cause severe damage to the equipment 2 The access control wires must be separated according to heavy and light current the control panel wires electronic lock wires and exit button wires must run through their respective conduits 10 3 Connection and Installation 3 3 System Structure TCP IP Ethernet Printer pe PEE Ul Four door one way controlling Wiegand Reader Access Control Panel TA
23. troughs or pipes Note that a shielding enclosure can have a shielding effect only when it is grounded reliably Ground wire connection method Reliable large diameter ground wires in compliance with applicable national standards are needed on the wiring site and should be connected in a tree form to avoid DC loop These ground wires must be kept far away from lightning fields No lightning conductor can serve as a ground wire and ensure there is no lightning current through any ground wire when there is lightning Metal wiring troughs and pipes must be connected continuously and reliably and linked to ground wires through large diameter wires The impedance of this section of wire cannot exceed 2ohm The shielding layer also must be connected reliably and grounded at one end to guarantee uniform current direction The ground wire of the shielding layer must be connected through a larger wire not smaller than 2 5mm 4 2 TCP IP Network Communication The Ethernet 10 100Base T Crossover Cable a type of crossover network cable is mainly used for cascade hubs and switches or used to connect two Ethernet end points directly without a hub Both 10Base T and 100Base T are supported 29 InBio X60 Series User Manual Manaoement konsi Printer fanagement he P nm Mma A MRE ps Card issuer Hub TCPAP Ethernet C3 control panel C3 control panel C3 control panel TCP IP Communication System Networking 4 3 RS485 N
24. y is required control panels and electronic locks should be powered respectively To prevent power failure of a control panel from making the whole system unable to work normally the access control management system is usually required to have at least one UPS and access control locks are powered externally to guarantee the access control management system can still work normally during a power failure 27 InBio X60 Series User Manual 4 System Networking 4 1 System Wiring and Wires Requirements 1 RS485 communication wires are made of internationally accepted shielded twisted pairs which provide effective protection and shield of interference 2 The power supply is 12V DC converted from 220V 3 The Wiegand readers use 6 core communication shielded wires RVVP 6x0 5mm usually there are 6 8 and 10 core types available for users to select to reduce interference during transmission 4 As an electronic lock has a big current it generates strong interference signal during an action To reduce the effect of an electronic lock during an action on other elements 4 core wires RVV 4x0 75mm two for a power supply and two for door sensor are recommended 5 For EXT485 communication we suggest to using 4 conducotor wire RVVP 40 5mm 6 Other control cables like exit buttons are all made of 2 core wires RVV 2x0 5mm 7 Notes for wiring e Signal wires like network cables and RS 485 wires can neither run in pa
25. y will be used for the relay output WA Note The factory default jumper setting is set as dry mode To change the jump mode you need to open the panel box first Stick the screw driver to the rectangular hole on the four corner of the panel back push it from outside to inside After hearing the click sound you can remove the case from the panel 3 Considering of the consumption of the control panel the Wiegand reader and the 21 InBio X60 Series User Manual InBio reader the standard power supply is 12V 3A Therefore we do not recommend the lock and the control panel use a common power supply If it is necessary to use we suggest using a bigger one such as 12V SA Excluding the reserve power consumption there are 2A current for the lock For the common electrical lock the standby current is 300mA the max current is 500mA the maximum connected lock is 4 4 To protect the access control system against the self induced electromotive force generated by an electronic lock at the instant of switching off on it is necessary to connect a diode in parallel please use the FR107 delivered with the system with the electronic lock to release the self induced electromotive force 1 Wet mode External power supply for NO Lock GHVEZI Lock power DEIN PW wis PRE 2 Wet mode External power supply for NC Lock 3 Connection and Installation Wet mode jumper 12345 I l I TEE i I Access control
Download Pdf Manuals
Related Search
Related Contents
GiD User Manual 410Kb - AMETEK Programmable Power Mode d - Primo Franklin English Language Trainer Calculator User Manual Makita HR4040C User's Manual LED Zoom Par SI-051 User Manual RX1575 Service Manual - Multiquip Service & Support Center 210_7014_02 BGH Joy Smart A6d Mobile Phone User Manual Copyright © All rights reserved.