Sola 2000 Off-Line Uninterruptible Power Systems (UPS)

image

Contents

1. 15 8 8 8 x 6 2 x 15 8 8 8 x6 2 x 15 8 Shipping H x W x D 226 x 156 x 404 226 x 156 x 404 226 x 156 x 404 Approx Shipping Weight Ibs kg 13 2 6 0 15 4 7 0 22 0 10 0 Input AC Parameters Voltage Range without Battery Operation STIOAA NAG Line to Boost Transfer 104 VAC Line to Buck Transfer 124 VAC Output AC Parameters Overload Warning Utility and Battery Modes 101 120 Uan baa le aah Overload 15 30 W Overload 20 40 W Overload 30 60 W Battery Parameters Battery Type Sealed Valve Regulated Lead Acid 3 5 years typical Battery Qty x Voltage x Rating 1 x12 V x 7 0 AH 1 x 12 V x7 AH 1 x 12 V x 10 AH Transfer Time 4 6 ms typical 7 10 hours to 90 capacity after full discharge into 100 resistive load Environmental 432 F to 104 F 0 C to 40 C 45 F to 122 F 15 C to 50 C 0 to 90 non condensing Up to 10 000 ft 3000 m at 95 F 35 C without derating Agency feo T T Co E Fax on Demand 877 888 9329 Document 8371 158 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 www stevenengineering com Mig HeviDuTy Uninterruptible Power Systems 13 Sola 2000 230 VAC Specifications Capacity VA Watts 350 210 470 282 700 420 Dimensions inches mm i 6 5x4 5 x139 6 5 x 4 5 x 13 9 6
2. 5 x 4 5 x 13 9 Unit Hae W xD 166 x 115 5 x 352 5 166 x 115 5 x 352 5 166 x 115 5 x 352 5 ae 8 8 x 6 2 x 158 8 8 x 6 2 x 15 8 8 8 x 6 2 x 15 8 Shipping H x W x D 226 x 156 x 404 226 x 156 x 404 226 x 156 x 404 Approx Shipping Weight Ibs kg 13 2 6 0 15 4 7 0 22 0 10 0 Input AC Parameters Voltage Range without Battery Operation 166 to 275 VAC Line to Boost Transfer 198 VAC Line to Buck Transfer 250 VAC Frequency 50 60 Hz Input Power Cord EN60320 C14 recessed plug Output AC Parameters Voltage Battery Mode 230 VAC 5 Receptacles 4 EN60320 C 13 sockets 2 detachable EN60320 2 2 1 8m 6 power cords Waveform Battery Mode Stepped Sinewave Overload Warning Utility and Battery Modes e end Beien M aded Overload 15 30 W Overload 20 40 W Overload 30 60 W 101 120 Battery Parameters Transfer Time 4 6 ms typical 7 10 hours to 90 capacity after full discharge into 100 resistive load Environmental 32 F to 104 F 0 C to 40 C 5 F to 122 F 15 C to 50 C 0 to 90 non condensing Up to 10 000 ft 3000 m at 95 F 35 C without derating Agency C E E Co E Fax on Demand 877 888 9329 Document 8371 Contact Technical Services at 800 377 4384 with any questions 159 Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenen
3. VAC models Applications e PCs Workstations e PLCs e Computer peripherals Selection Table Capacity Catalog Volts Frequency taal Input Plug Paceline VA W Number In Out minutes Output Receptacle Ez ka 350 210 2350 115 115 50 60 Hz 5 15 5 15P 4 5 15R 13 2 6 0 470 282 2470 115 115 50 60 Hz 5 12 5 15P 4 5 15R 15 4 7 0 oazo 518P 6 5458 00 350 210 EN60320 C14 4 EN60320 C13 13 2 6 0 470 282 EN60320 C14 4 EN60320 C13 15 4 7 0 700 420 EN60320 C14 4 EN60320 C13 22 10 0 Full Half load in minutes Fax on Demand 877 888 9329 Document 8371 156 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenengineering com Mig HeviDury Uninterruptible Power Systems 13 Power A C Distribution PAD and Associate Receptacles Line Cord Options for the Series 2000 PADs provide output distribution receptacle input _ Catalog connection and a rotary maintenance bypass switch The PAD is field installable by the customer Use of the 120 Volt 5 15P Line Cord 8 5 15R PAD allows the UPS to be removed without interrupting aon 120 Volt 5 15P Line Cord 6 5 15R 2 L5 15R AD115B power to the load 230 Volt 50 Hz IEC 320 10A Line Cord AD220K Note PADs can only be used with units having matching receptacles 4 IE
4. 13 Uninterruptible Power Systems Mig HEVioUry Sola 2000 Off Line Uninterruptible Power Systems UPS The most complete off line Features UPS on the market Sola j 2000 UPS s protect against Off line with Automatic Voltage Regulation AVR topology most adverse power A conditions This UPS e Protects against most adverse power conditions protects against over and including under voltages by raising Frequency variations Lightning and lowering utility power Surge Spike to the right level for sensitive Noise Brownouts equipment all without Blackouts Over and under voltages transfer to battery Overload protection continually Data line surge protection for phone or network monitors the UPS load preventing inadvertent shutdown included on every unit during emergency situations and optimizing battery life DB9 Communications Interface Greater uptime with intelligent power management Full sequence battery testing delivers comprehensive testing of your battery and system through both a 14 day full sequence battery testing and two level overload automatic test and a single push manual test ensuring the protection battery is emergency ready With its comprehensive power e Two year warranty with optional extensions protection the Sola 2000 is perfect for PC Point of Sale to five years Network or Industrial applications UL and cUL 115 VAC 25 000 UPS Power Protection Promise models TUV GS and CE 230
5. 9200 www stevenengineering com 1 3 1 Modes of Operation The UPS shall be designed to operate as an off line system in the following modes A Normal The critical AC load is continuously supplied with filtered power The battery charger shall maintain a float charge on the battery B Emergency Upon failure of utility AC power the critical AC load is supplied by the inverter which obtains power from the battery C Recharge Upon restoration of utility AC power after a utility AC power outage the critical AC load shall be supplied with filtered power and the battery charger shall simultaneously recharge the battery automatically The unit shall recharge whether the switch is in the on or off position off state charging E Dark Start 400 600 VA only The UPS shall have the ability to startup in the back up mode without the presence of utility power 1 3 2 Design Requirements A Voltage Input Output voltage specifications of the UPS shall be Input 115V units 0 to 135 VAC 50 60 Hz single phase 2 wire plus ground 230V units 0 to 270 VAC 50 60 Hz single phase 2 wire plus ground Output 115V units 115 VAC 50 60 Hz single phase 2 wire plus ground 230V units 230 VAC 50 60 Hz single phase 2 wire plus ground B Output Load Capacity Specified output load capacity of the UPS shall be e 250VA 150W e 400VA 240W e 600VA 360W C Internal Battery The battery shall consist of sealed valve regulated reduced maint
6. C 320 10 Receptacles for the line cords provided Plug amp Receptacle Reference Chart 5 15P 5 15R IEC 320 10 fa ar nn CTA if u 0 2 Le G Sola 2000 Battery Run Time Charts 2350 and S2350 5 Models 2470 and S2470 5 Models Minutes Minutes 70 70 60 60 50 50 40 40 30 30 350 VA 470 VA 20 20 N 0 10 25 30 40 30 60 73 80 90 100 Load 10 D 10 25 30 40 50 60 75 80 90 100 Load 350 VA 65 15 8 5 470 VA 45 12 7 5 2700 and S2700 5 Models Minutes 70 60 50 40 30 700 VA 20 io o 10 25 30 40 50 60 75 80 90 100 Load 700 VA 60 13 75 5 Fax on Demand 877 888 9329 Document 8371 Contact Technical Services at 800 377 4384 with any questions 157 Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 www stevenengineering com 13 Uninterruptible Power Systems Mig HeVioury Sola 2000 115 VAC Specifications Capacity VA Watts 350 210 470 282 700 420 Dimensions inches mm 6 5 x 4 5 x 13 9 6 5 x 4 5 x 13 9 6 5 x 4 5 x 13 9 Unit HWD 166 x 115 5 x 352 5 166 x 115 5 x 352 5 166 x 115 5 x 352 5 D 8 8 x 6 2 x
7. are present The test shall operate the same as the automatic weekly test described in section 2 2 3 of this specification Should the UPS batteries not be capable of supporting the connected load for the test duration the UPS shall immediately return to normal operation without loss of connected load and fault signals visual audible and remote via communication port shall be enunciated No audible or remote via communication port contact closures indication of the battery test shall be enunciated during the duration of the manual battery test 2 2 5 Internal Battery Sealed valve regulated reduced maintenance lead acid cells shall be used as a stored energy source for the specified UPS system The battery shall be housed internal to the UPS cabinet and sized to support the inverter at rated load and power factor with ambient temperature between 20 and 30 C for a minimum of 5 minutes reserve time The batteries shall be user replaceable 2 2 6 Output Distribution 115 VAC units Output distribution shall be integral to the UPS and located on the rear of the unit with the following receptacles 250VA 2 NEMA 5 15 400VA 4 NEMA 5 15 600VA 4 NEMA 5 15 7 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 www steve
8. at will allow the following Switch 1 50 60Hz selection Switch 2 Enable or Disable High Line Alarm Switch 3 Transfer to Battery Setpoint Switch 4 Enable Disable line to neutral reversal alarm D Alarm Silence On 400 and 600 VA models the alarm silence switch shall be used to silence the On Battery alarm only whether utility power is present or not except when operating in a low battery condition 2 2 3 Automatic self diagnostic tests The UPS shall perform three 3 different automatic self diagnostic tests as described below A Automatic self diagnostic test Power ON The UPS must qualify the utility line voltage before initiating start up Qualification of the utility shall consist of verifying utility power is within start up voltage range Once the utility power has been qualified and followed by the UPS being switched ON the UPS shall perform start up tests consisting of an electronics and battery test prior to enabling output power from the inverter Should the UPS fail any start up test the output power shall not be enabled and fault signals visual and audible shall be enunciated 6 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenengineering com B Automatic self diagnostic test Auto resta
9. based on lighter loading 2 2 2 Display and Controls A General The UPS shall provide the operator with both visual and audible status indicators and shall indicate the following conditions 400 amp 600 VA Units Fail startup battery test Input L N reversed Input frequency mismatch with DIP switch setting Input line voltage below threshold Output overload short circuit e Normal Mode e Charger fail e Battery test fail e Input line overvoltage 5 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenengineering com Output overload short circuit Low battery UPS shutdown end of discharge UPS shutdown via communication port 250 VA Units Fail startup battery test Input L N reversed Input frequency mismatch with DIP switch setting Input line voltage below threshold Output overload short circuit Normal Mode Battery test fail Input line over voltage Output Overload short circuit Low Battery UPS shutdown end of discharge B Controls The UPS shall contain a front panel mounted main On Off switch The UPS shall also contain microcontroller based monitoring and controls for reliable operation C DIP Switch Operation The UPS shall contain four user selectable DIP switches th
10. enance lead acid cells The batteries shall be user replaceable D Reserve Time Minimum 5 minutes at full load with ambient temperature between 20 and 30 C E Battery Recharge The recharge time shall be the following to 90 capacity after discharge into a full load e 250VA 12 14hrs maximum e 400 600VA 6 8hrs maximu 1 3 3 Performance Requirements 2 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenengineering com 1 3 3 1 AC Input to UPS A Voltage Configuration 115VAC 10 25 90 to 135 VAC single phase 2 wire plus ground 230VAC 15 22 180 to 270 VAC single phase 2 wire plus ground B Frequency 50 Hz or 60 Hz UPS frequency is set via a DIP switch C Surge Protection Sustains input surges without damage per criteria listed below 115VAC IEEE587 Category A amp B 240 Joules 230VAC IEC 801 5 Draft 80 Joules D Input 115 VAC units All models shall have a 6 foot input power cord with a NEMA 5 15P plug 230 VAC units The input for all models shall be a CEE 22 recessed plug on the UPS Specific country receptacles shall be accommodated by using the computer s input cord to feed the UPS 1 3 3 2 AC Output UPS Inverter On Backup A Voltage Configuration 115VAC si
11. gineering com SOLA Sola 2000 i HEVI DUTY Guide Specifications Fax on Demand 8221 Uninterruptible Power Supply Systems Sola 2000 Guide Specifications for a Sola2000 250 to 600 VA Single Phase Uninterruptible Power Supply System 1 0 GENERAL 1 1 SUMMARY This specification defines the electrical and mechanical characteristics and requirements for a continuous duty single phase solid state uninterruptible power supply system The uninterruptible power supply system hereafter referred to as the UPS shall provide continuous AC power for sensitive electronic equipment loads 1 2 STANDARDS The UPS shall be designed in accordance with the applicable sections of the current revision of the following documents Where a conflict arises between these documents and statements made herein the statements in this specification shall govern 115V Units e UL Standard 1778 UL Standard 1449 FCC Part 15 Subpart B Class B IEEE 587 Category A and B C UL CAN CSA 22 2 No 107 1 230V Units EN 50091 1 EN 55022 Class B IEC 801 2 IEC 801 3 IEC 801 4 IEC 801 5 EN60950 EN50091 1 CE compliance mark EMC Directive 89 336 EEC 1 3 SYSTEM DESCRIPTION 1 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258
12. gual 1 6 WARRANTY The UPS manufacturer shall warrant the UPS against defects in materials and workmanship for two 2 years The warranty shall cover all parts and labor An optional one 1 or three 3 year extended warranty shall be available from the manufacturer 1 7 QUALITY ASSURANCE 1 7 1 Manufacturer Qualifications A minimum of twenty years experience in the design manufacture and testing of solid state UPS systems is required 1 7 2 Factory Testing Before shipment the manufacturer shall fully and completely test the system to assure compliance with the specification 2 0 PRODUCT 2 1 FABRICATION All materials and components making up the UPS shall be new of current manufacture and shall not have been in prior service except as required during factory testing All active electronic devices shall be solid state All relays shall be provided with dust covers 2 1 1 Cabinet The UPS unit shall be comprised of battery charger inverter transfer switches all associated controls monitoring major protection devices and battery consisting of the appropriate number of sealed battery cells The UPS cabinet shall be cleaned primed and painted with the manufacturer s standard color Dimensions shall be 250 VA 3 51 90mm W x 10 18 261mm D x 6 79 174mm H 400 VA 4 25 108mm W x 10 18 261mm D x 7 02 186mm H 600 VA 4 85 124mm W x 10 18 261mm D x 8 15 215mm H 2 1 2 Cooling The UPS sha
13. ll be convection cooled 4 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenengineering com 2 2 COMPONENTS 2 2 1 Power Train A Input Protection The UPS shall employ an input circuit breaker The UPS shall sustain input surges without damage per criteria listed in 115VAC IEEE587 Category A amp B 240 Joules 230VAC IEC 801 5 Draft 80 Joules B Battery Recharge The battery shall use constant voltage charging to recharge and maintain the battery C Unit DC Protection The unit shall be protected by the following DC shutdown levels e DC Undervoltage Shutdown End of Discharge e DC Undervoltage Warning Low Battery Reserve D Overload The UPS shall be capable of supplying current and voltage for overloads exceeding 115 of full load current for 30 minutes A visual indicator and audible alarm shall indicate overload operation The 400 600VA models shall provide a visual indicator and audible alarm E Output Frequency The output frequency during normal operation shall follow the incoming AC frequency within a 3Hz window F Battery Over Discharge Protection To prevent battery damage from over discharging the UPS control logic shall automatically raise the shutdown voltage set point
14. nengineering com 230 VAC units Output distribution shall be integral to the UPS and located on the rear of the unit with the following receptacles 250VA 2 CEE 22 400VA 4 CEE 22 600VA 4 CEE 22 2 cords shall be provided with each unit to connect the UPS output to the load 2 2 7 Communications The 400 and 600 VA models shall contain a DB25 connector on the rear panel to allow UPS status communications to a computer system The DB25 shall contain contact closures to signal on battery and low battery operational status The UPS shall also be capable of receiving a signal from the connected host system to initiate a UPS shutdown This signal shall be a 5 V to 12 V RS232 level that must remain for gt 0 1 second duration G techsvcspecs info cdrominfo ups guidespecs 2000GuideSpec doc 8 99 8 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 www stevenengineering com
15. ngle phase 2 wire plus ground B Voltage Regulation 5 for entire battery voltage range C Frequency Regulation 2Hz D Output Power Rating 6pf for all models E Overload Capability 115 of power rating F Transient Recovery Response Time 100 step load to within 90 of nominal output voltage within 500 milliseconds 1 4 ENVIRONMENTAL CONDITIONS A Ambient Temperature Operating 0 C to 40 C Storage 35 C to 50 C w o battery 20 C to 40 C for optimum battery performance B Relative Humidity Operating 0 to 95 non condensing Storage 0 to 95 non condensing 3 Fax on Demand 877 888 9329 Document 8221 Contact Technical Services at 800 377 4384 with any questions Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Main Office 650 588 9200 Outside Local Area 800 258 9200 e www stevenengineering com C Altitude Operating 3000 m 10 000 ft max D Audible Noise Noise generated by the UPS during battery operation shall not exceed 40 dB measured at 1 meter from the surface of the UPS 1 5 USER DOCUMENTATION The specified UPS shall be supplied with one 1 user s manual Manuals shall include installation drawings and instructions a functional description of the equipment with block diagrams safety precautions illustrations step by step operating procedures and general maintenance guidelines User manual for the 230V models shall be multi lin
16. rt The UPS must qualify the utility line voltage before auto restarting Auto restart shall be defined as the restart of the UPS once utility power has returned and qualified after the UPS has shutdown due to battery depletion Once the utility power has been qualified the UPS shall perform auto restart tests consisting of an electronics and battery test prior to enabling output power from the unit Should the UPS fail any test the output power shall not be enabled and fault signals visual audible and remote via communications port shall be enunciated C Automatic self diagnostic test Weekly The UPS contains a counter which will initiate a battery test after seven days 168 hrs of continuous normal mode operation The test duration shall be approximately 15 seconds Should a failure of the battery occur the UPS will immediately return to normal mode and fault signals visual audible and remote via communications port shall be enunciated The seven day timer shall be reset after a manual battery test back up mode operation or if the UPS is switched OFF No audible or remote via communications port contact closures indication of the battery test shall be enunciated during the duration of the automatic battery test 2 2 4 Manual Battery Test 400 and 600 VA only The manual battery test switch on the back of the 400 amp 600 VA units shall initiate a manual battery test only when utility power is present and no alarm conditions