Eurocheck CS 2099 User manual

image

Contents

1. lAn reference value Accuracy 30 mA 1 Trip out time reference value Accuracy 50 ms 2 ms CURRENT LO indication Accuracy 28 mA 1 mA CURRENT HI indication Accuracy 35 mA 1 mA Automatic reset after 3 seconds Automatic mains polarity verification Test is performed in 2 seconds after connection of Eurocheck to mains socket Note about reference values Instead of relying on accuracy specifications given in this chapter it is possible to use calibrated reference values noted in Eurocheck Production validation certificate They express lower uncertainty thus enabling better evaluation of tested instrument Note about EN and IEC standards Text of this manual contains references to European standards All standards of EN 6xxxx e g EN 61010 series are equivalent to IEC standards with the same number e g IEC 61010 and differ only in amended parts required by European harmonization procedure 24
2. 2 Safety and operational considerations 2 1 Warnings Read and understand all warnings and cautions before using this product This will ensure your safety as well as keep the test equipment undamaged Q Q Q Q symbol on the instrument means Read the Instruction manual with special care The symbol requires an action If the test equipment is used in a manner not specified in this user manual the protection provided by the equipment may be impaired Read this user manual carefully otherwise use of the instrument may be dangerous for the operator for the instrument or for the equipment under test Do not use the test equipment and accessories if any damage is noticed In case a fuse has blown follow the instructions in this manual to replace it Consider all generally known precautions in order to avoid risk of electric shock while dealing with hazardous voltages Do not use the test equipment in supply systems with voltages higher than 230 V Do not disassemble risk of electric shock service intervention or adjustment procedure is allowed to be carried out only by a competent authorized person Use only standard or optional test accessories supplied by your distributor Do not short circuit any of the calibrator inputs outputs Immediately disconnect from the power line and discontinue use if Q Q the calibrator is dropped or subjected to an impact in which the interior is exposed the calibrator emits a strange
3. For repairs under warranty or at any other time please contact your distributor Unauthorised person is not allowed to open the Eurocheck calibrator There are no user replaceable components inside the instrument except one fuse refer to chapter 3 3 CS 2099 Eurocheck Eurocheck operation 4 Eurocheck operation 4 1 Recommended calibration sequence and practice This chapter lists recommended sequence for calibration of installation test instruments It is not obligatory to follow this sequence Eurocheck offers additional calibration functions all functions are explained in detail in the following chapters Calibration using universal test cable Step Calibrated function Purpose 1 LowQ Determination of measurement accuracy Verification of universal test cable wire continuity incomplete 2 Continuity Determination of measurement accuracy 3 Insulation Determination of measurement accuracy Verification of universal test cable wiring insulation resistance incomplete 4 Voltage Determination of measurement accuracy Verification of universal test cable or tip commander wiring continuity and insulation state complete in most cases refer to chapter 4 13 Calibration using plug cable Step Calibrated function Purpose 5 Fault loop Determination of measurement accuracy impedance Verification of plug cable wiring continuity incomplete and or Trip lock impedance 6 RCD trip out time Determinati
4. Eurocheck CS 2099 User manual Version 1 3 Code no 20 750 127 ZB N en T METREL Distributor Producer METREL d d Ljubljanska cesta 77 1354 Horjul Slovenia web site http www metrel si e mail metrel metrel si 2005 METREL Mark on your equipment certifies that this equipment meets the requirements of the EU European Union concerning safety and electromagnetic compatibility regulations No part of this publication may be reproduced or utilized in any form or by any means without permission in writing from METREL CS 2099 Eurocheck Table of contents 1 Introduction to CS 2099 Euroche ck cccccccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 4 2 Safety and operational considerations uszsusnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn ann 5 221 MVGMMINGS ocizdaradedascusuadadrahacaa Apes tuadeatausectdaus baes sae E guaeee ehesten 5 2 2 Standards applied 222 RAN AR 5 3 Eurocheck description and maintenance us220000nnnnnnnonnnnnnnnnnn 6 Soils Frontpanel VPUSOPBEBUERSEHENTUNDEBUDDSRUEENDRENUESEORDSUDTIUEEEURSEUESNONSDERLTURSEURGEUHBUDDSSERBUUEREUEDEN S 6 32 LOIS Dae MERRESERENBESSPRAN is daa ata R EEE ERREERERFE BEER BOBR PET EREREEN ER SERR 7 33 Replacing TUSE zeli masse 8 34 Cleaning ee Er 8 3 5 Periodic calibration DRBERRARLEUSSBUNERUESEENUNDE PEUNDUUENEAPHEDEUPUNDUUEDEFFUPDENEONUEUEDBUDEEUEPEONUNDE DEBR 8 SiO SEVICE ne a a e a Aaa ee al EEEa D E eE eaa e ae AEAE
5. 3 a It is not necessary to power on Eurocheck when performing insulation resistance calibration a Observe any warnings displayed on the tested instrument If any is present remove the causes before proceeding 4 a Perform insulation measurement with the tested instrument a Write down measurement result for documentation purposes 5 a If measured insulation resistance deviates significantly from reference value it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment 6 a Repeat steps 4 and 5 with the other reference insulation resistance value 7 a Set another insulation measuring voltage and repeat steps 4 6 a Make sure to select all available measuring voltages Notes a Some instruments like MI 3101 EurotestAT support measurement of all three insulations in standard mains cable between L and N Land PE N and PE In such case it is necessary to calibrate each insulation measurement separately a Itis advisable to perform at least three consecutive measurements to verify stability of results If the tested instrument supports continuous insulation measurement it is advisable to test this functionality as well function is usually engaged by pressing and holding TEST button 4 11 LowQ and continuity resistance calibration Eurocheck offers 3 low resistance values for calibration 0 5 Q 5 Q and 15 Q It is always possible and reco
6. RCD trip out time measurement is performed Eurocheck automatically indicates if test current was too low or too high LEDs CURRENT LO or CURRENT HI light respectively Eurocheck low limit indication is set to 28 mA and high limit to 35 mA 4 10 Insulation resistance calibration Eurocheck offers 2 insulation resistance values for calibration 2 MO and 50 MQ It is always possible and recommended to add third value into your calibration procedure 0 Q short circuited test leads It is necessary to calibrate insulation resistance function with all available measuring voltages If measuring voltage is set continuously it is recommended to perform calibration with the following voltages 50 V 100 V 250 V 500 V and 1000 V Fault loop impedance calibration can be performed with universal test cable or tip commander Make sure to follow connection instructions for the tested instrument determine the leads of the test cable which are used for this measurement Generic connection diagram is shown in Figure 4 3 Figure 4 3 Performing insulation resistance calibration using universal test cable 17 CS 2099 Eurocheck Eurocheck operation Step Action 1 a Connect tested instrument into Eurocheck insulation resistance test sockets using universal test cable follow connection diagram shown in Figure 4 3 2 a Switch on the tested instrument and select insulation resistance function a Set the first measuring voltage
7. of measurement leads verification PE test terminal operation verification Oooccoco Note a For descriptions of instrument measurement functions refer to its User manual 4 4 Selecting appropriate test cable for calibration Functions that use Eurocheck RCD Fault loop calibration output can be calibrated using universal test cable plug cable or plug commander Use test tips to connect universal test cable into Eurocheck RCD Fault loop calibration output Fault loop impedance Trip lock impedance RCD trip out time and instrument test current IAn Line impedance PE test terminal operation verification OCoocodo Measurement results should be the same regardless of selected cable It is possible that the cause for incorrect calibration result is broken wire or deteriorated insulation in measurement cable Correctness of universal test cable wiring can be easily verified see chapter 4 13 If this cable passes verification use it to perform calibration of functions listed above Write down measurement results Then use other type of cable and repeat calibration Compare measurement results they should be close to each other Other functions can be calibrated with universal test cable and tip commander a Insulation resistance a LowQ and continuity resistance a Voltage and frequency a Continuity and insulation of measurement leads verification For further information on how to use each cable type see User manu
8. results Consider accuracy of trip lock function when evaluating calibration results accuracy is defined in User manual of your instrument 4 7 Line impedance calibration Line impedance is measured between L and N conductors Line impedance calibration can be performed with universal test cable plug cable or even plug commander Calibration procedure is basically the same as the procedure for fault loop impedance function chapter 4 5 Only differences between both procedures are noted below Step Action 1 a The same as fault loop impedance function a Follow connection diagrams shown in Figure 4 1 and Figure 4 2 2 a Switch on the tested instrument and select line impedance function 3 a The same as fault loop impedance function 4 a The same as fault loop impedance function line impedance will be measured instead of loop 5 a Perform line impedance measurement with the tested instrument a Write down measurement result for documentation purposes it will be in 11 Q 12 Q range in most cases 6 a The same as fault loop impedance function line impedance will be measured instead of loop 7 a Perform line impedance measurement with the tested instrument a Write down measurement result for documentation purposes it will be in 10 2 Q range in most cases 8 a Calculate the difference between LOOP 11 Q and LOOP 1 Q measurement results it has to be close to 9 8 Q see Eurocheck technical speci
9. smell excessive heat or smoke Function specific warnings applies to all operations performed with Eurocheck Q Q A In some countries the type of mains plug determines L and N wiring positions If Eurocheck signals incorrect polarity this represents an installation fault which should be corrected immediately A When performing fault loop trip lock line impedance calibration Eurocheck always connects loop calibration output to mains line impedance L and N thus avoiding tripping an RCD on mains supply When evaluating absolute measurement results line impedance of the mains has to be considered not fault loop impedance Recommended calibration procedure described in this document relies on the absolute result and the difference between two measured values 2 2 Standards applied The CS 2099 Eurocheck calibrator is manufactured and tested in accordance with the following regulations Q Q Safety regulations sce eee cee cate bccencetncenntenonemvsenetetmtenetons EN 61010 1 Electromagnetic compatibility regulations EN 61326 CS 2099 Eurocheck Eurocheck description and maintenance 3 Eurocheck description and maintenance 3 1 Front panel Note Figure 3 1 Front panel Output connector type is country dependent Insulation calibration outputs LowQ and continuity calibration outputs Caution do not use test currents higher than 200 mA Power supply cord connection polarity in
10. E Eiaa 8 4 Eur check operation 2225er ee 9 4 1 Recommended calibration sequence and practice 444 nenn 9 4 2 Sample test report Tossa session 10 4 3 Selecting calibration function sub function 444444444Hennnnn nennen nennen 11 4 4 Selecting appropriate test cable for calibration 11 4 5 Fault loop impedance Calibration cccccceceecceeeeeeeeeeeeeeeeeeaeeeeeeeeeetess 12 4 6 Trip lock impedance Calibration ccccccceecceceeeeeeseeeeeeeeeeeeeeeseeeeeeeees 14 4 7 LINE imped nce salibration a anne ee a eedsexees 15 4 8 RCD trip out time Calibration 0044444444008400 nenn nnnnnnnnnnnnnnnnnnennnnennnn 16 4 9 RCD measuring current IAn 30 mA verification een nennen 17 4 10 Insulation resistance Calibration 2244444440000400Rnnnnnnnn nenne nnnnnnnnn 17 4 11 LowQ and continuity resistance Calibration 444444444HRnnn nennen 18 4 12 Voltage and frequency Calibration 444444444444HHRRnRnnnnnnnnnnnnnnnnnnnnnnen 20 4 13 Continuity and insulation of measurement leads verification 21 4 14 PE test terminal operation verification ccccccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeees 22 5 Technical specifications uuu00004000nnnnnn non nun nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnen 23 941 Beneldini een ee een ee 23 5 2 Calibration referentes t
11. al of your instrument 11 CS 2099 Eurocheck Eurocheck operation 4 5 Fault loop impedance calibration Fault loop impedance is measured between L and PE conductors Fault loop calibration will not trip an RCD if it s present in installation where Eurocheck is connected regardless of selected lAn current Caution a A when performing fault loop impedance calibration Eurocheck connects fault loop calibration output to mains line impedance L and N important when evaluating calibration measurement results a When evaluating absolute measured values first perform line impedance measurement of the wall socket to which Eurocheck is then connected Consider that the impedance of Eurocheck mains cable is added to this value Fault loop impedance calibration can be performed with universal test cable plug cable or even plug commander Ste Action 1 a Connect the tested instrument into Eurocheck RCD Fault loop output using one of available cables plug cable plug commander universal test cable follow connection diagrams shown in Figure 4 1 and Figure 4 2 2 a Switch on the tested instrument and select fault loop impedance function 3 a Connect Eurocheck into mains wall socket and enable its output Observe any warnings displayed on the tested instrument and Eurocheck If Eurocheck signals incorrect L and N polarity reverse connection Select LOOP 11 Q function on Eurocheck using RCD LOOP button LOOP 11 Q LED light
12. ation Continuity of measurement leads Continuity of universal test cable measurement leads could be verified by voltage calibration between all 3 installation wires between L and N L and PE N and PE Refer to chapter 4 12 for more information If the tested instrument measures voltage of around 0 V at least one of connected leads is broken By connecting different measurement lead pairs it is possible to determine which one is broken Complete verification can be performed with universal test cable only Other types of measuring cables plug cable plug commander and tip commander can be verified indirectly First verify universal test cable using procedure for voltage and frequency calibration see chapter 4 12 Measure voltages between all measurement lead pairs If all results pass perform any of calibrations using different Eurocheck sockets and universal test cable At last perform these calibrations with the other type of cable and compare the results If they re the same or close to each other the other cable is acceptable as well Notes a Suggested calibrations for verifying continuity of plug cable and plug commander are fault loop verification of L and PE and line impedance verification of L and N a Suggested calibration for verifying continuity of tip commander is low resistance measurement a For quick continuity verification of L and N wires of universal test cable perform low resistance calibration with any refer
13. ative humidity RH Function Eurocheck value Measured value LowQ 200 mA 0 50 Q 50 Q 150 Q Continuity 7 mA 0 50 Q 50 Q 150 Q Insulation 100 V 2 MQ MQ 50 MO MQ Insulation 250 V 2 MQ MQ 50 MO MQ Insulation 500 V 2 MQ MQ 50 MO MQ Insulation 1000 V 2 MQ MQ 50 MO MOQ Voltage frequency Un 50 V V UL pe 50 V V Un pe 50 V V 50 Hz Hz Fault loop impedance LOOP 1 Q Q LOOP 11Q Q Trip lock impedance IAn 30 LOOP 1 O Q mA LOOP 11Q Q RCD trip out time IAn 30 mA 50 ms ms CURRENT LO PASS FAIL CURENT HI PASS FAIL Reference equipment SN Calibration certificate no Date of calibration Metrel Eurocheck Operator s name and signature 10 CS 2099 Eurocheck Eurocheck operation 4 3 Selecting calibration function sub function The following measurements can be selected with the RCD LOOP function selection button see Figure 3 1 Appropriate LED lights when particular function sub function is selected a Fault loop and trip lock impedance calibration two impedance values available a RCD trip out time calibration and instrument test current verification The following measurements are not indicated with LEDs on front panel Connect the tested instrument to the outputs particular to each function a Insulation resistance LowQ and continuity resistance Voltage and frequency calibration Line impedance calibration Continuity and insulation
14. dication LED lights if L and N lines are incorrectly connected reverse connection Incorrect test current indication for RCD trip out time function verification appropriate LED lights if test current is too low or too high RCD test calibration function selected Fault loop calibration function selected each LED indicates sub function also used for trip lock line impedance calibration LED lights if voltage is present at RCD Fault loop calibration output Press RCD LOOP selection button 9 once after connecting the calibrator to the power supply to enable voltage at output connector LED goes out whenever RCD simulator trips and is automatically restored 3 seconds afterwards other LEDs remain lit during this period RCD Fault loop calibration output used for fault loop trip lock line impedance and RCD trip out time calibration Caution line voltage present on test terminals A Consider specified duty cycle when calibrating fault loop or line impedance to avoid overheating of Eurocheck RCD Fault loop selection button Press repeatedly to cycle through available options enable output LOOP 11 Q LOOP 1 Q RCD disable output Voltage frequency calibration output CS 2099 Eurocheck Eurocheck description and maintenance 3 2 Side panel Note Output connector type is country dependent Figure 3 2 Side panel Legend UHREN Power supply cord Deseo Fuse F1 Note Eurocheck powers on automaticall
15. een Ss ocGeuSdauGieubenxti ae Geenideu ar euSiaxdeonteen tie 23 CS 2099 Eurocheck Introduction to CS 2099 Eurocheck 1 Introduction to CS 2099 Eurocheck CS 2099 Eurocheck is a professional multifunctional field calibrator intended for use with Metrel installation test instruments In addition to its durable body and simple operation it boasts the following features a Insulation calibration with test voltages up to 1000 V a LowQ and continuity function calibration a Continuity and insulation of measurement leads verification a Fault loop and trip lock impedance calibration all test currents supported on Metrel instruments a Calibration of RCD trip out time measurement including test current verification 30 mA test current is supported a Line impedance calibration a Voltage and frequency calibration a PE test terminal functional verification Functioning and accuracy of all Metrel and most other manufacturer s installation test instruments can be verified with Eurocheck However not all instruments support all functions available on Eurocheck Refer to your instrument User manual for a complete list of its measuring functions The instrument list includes but is not limited to a MI3100 EurotestEASI MI3101 EurotestAT MI3102 EurotestXE MI2086 Eurotest MI2037 Instaltest MI2087AL2 Easitest Smartec family of instruments Ooooco Installation test instruments are usually used on a dail
16. ence value see chapter 4 11 21 CS 2099 Eurocheck Eurocheck operation Insulation of measurement leads Insulation of measurement leads may deteriorate over time This can cause measurement and or safety related problems If insulation material leaks current measured results will be wrong Also in such case there is a risk of electric shock when the user touches deteriorated part of insulation Eurocheck is not needed to perform this test Step Action 1 a Switch on the tested instrument and select insulation measurement with 1000 V test voltage highest available 2 a Connect universal test cable to the instrument Make sure that all measurement leads are in direct connection to each other over the whole length a Leave all leads open 3 a Start insulation measurement The instrument must signal over range measurement result 4 a If the instrument measures lower than maximum insulation stop using this measurement cable immediately Note a Itis possible to verify other types of measurement cables as well Just connect them to the instrument and perform insulation measurement as described above 4 14 PE test terminal operation verification Warning a A This test uses voltages that are hazardous live Only adequately trained personnel may perform this test Ensure that disconnected lead is not exposed Verification can be performed with universal test cable only Step Action 1 a Con
17. fication a If impedance difference deviates significantly from 9 8 Q it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment 15 CS 2099 Eurocheck Eurocheck operation 4 8 RCD trip out time calibration Eurocheck simulates an RCD with lAn of 30 mA and trip out time of 50 ms Trip out time calibration will not trip an RCD if it s present in installation where Eurocheck is connected regardless of selected lAn current Caution a A Pay special attention when selecting appropriate IAn current It should be set to 30 mA and multiplier should be set to x1 Otherwise the reading of trip out time may be wrong RCD trip out time calibration can be performed with universal test cable plug cable or even plug commander Step Action 1 a Connect the tested instrument into Eurocheck RCD Fault loop output using one of available cables plug cable plug commander universal test cable follow connection diagrams shown in Figure 4 1 and Figure 4 2 2 a Switch on the tested instrument and select RCD trip out time function usually denoted as RCD t a Set IAn to 30 mA and current multiplier to x1 3 a Connect Eurocheck into mains wall socket and enable its output a Observe any warnings displayed on the tested instrument and Eurocheck a If Eurocheck signals incorrect L and N polarity reverse connection 4 a Select RCD calibration function usin
18. g RCD LOOP button RCD LED lights when the function is selected Observe any warnings displayed on the tested instrument and Eurocheck If any is present remove the causes before proceeding D 5 a Perform RCD trip out time measurement with the tested instrument a 30 mA RCD test current is verified simultaneously chapter 4 9 a Write down measurement result for documentation purposes 6 a If measured trip out time deviates significantly from 50 ms it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment 7 a Repeat steps 5 and 6 with reverse polarity of test current in RCD trip out time function if the tested instrument enables reverse polarity selection Note a Consider accuracy of RCD trip out time measurement when evaluating calibration results accuracy is defined in User manual of your instrument 16 CS 2099 Eurocheck Eurocheck operation 4 9 RCD measuring current IAn 30 mA verification This test is part of RCD trip out time calibration and couldn t be performed separately it is valid only for An 30 mA Refer to chapter 4 8 for more information It is essential that the test instrument measuring current is within certain limits For example standard EN 61557 defines low limit as An 0 and high limit as An 20 Metrel test instruments has even narrower specification high limit is defined as lAn 10 When
19. imum relative humidity 95 RH 10 C 40 C non condensing Storage conditions Temperature range 0 C 50 C Maximum relative humidity 90 RH 0 C 40 C 80 RH 40 C 50 C 5 2 Calibration references Accuracies apply for 1 year in reference conditions Insulation resistance Reference value MQ Accuracy 2 1 Maximum test voltage 1500 V d c 1200 V d c continuously In case the calibrator gets moistened the results could be impaired It is recommended to dry the calibrator for at least 24 hours Low resistance Reference value Q Accuracy 0 5 5 2 15 A Maximum test current 220 mA d c 23 CS 2099 Eurocheck Technical specifications Voltage and frequency Reference value Accuracy 50 0 V 230 V a c 5 accuracy of mains voltage Short circuit current lt 6 mA Nominal output resistance 25 kQ Specified accuracy is valid only if Eurocheck output is enabled Fault loop impedance trip lock impedance line impedance Reference value Q Accuracy 1 2 LOOP 1 Q 0 2 Q 11 0 LOOP 11 Q 0 5 QO This value is added to the actual loop line impedance Mains voltage fluctuations affect accuracy of the reference A Loading at 230 V a c max 3 minutes 25 duty ratio RCD trip out time simulation and lAn current measurement
20. ll An currents are supported The same as fault loop impedance function The same as fault loop impedance function Perform trip lock impedance measurement with the tested instrument Write down measurement result for documentation purposes it will be in 11 O 12 Q range in most cases 6 a The same as fault loop impedance function 7 Perform trip lock impedance measurement with the tested instrument Write down measurement result for documentation purposes it will be in 10 2 Q range in most cases 8 a Calculate the difference between LOOP 11 Q and LOOP 1 Q measurement results it has to be close to 9 8 O see Eurocheck technical specification If impedance difference deviates significantly from 9 8 Q it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment 9 a Repeat steps 4 8 with reverse polarity of test current in trip lock impedance function if the tested instrument enables reverse polarity selection 2 3 4 5 D OJOJOO OJD D DO D Notes a In some instruments the function is named Rs resistance RI resistance loop rcd or loop rcd10mA The calibration procedure is the same regardless of the name 14 CS 2099 Eurocheck Eurocheck operation a Selected lAn current will affect dissipation of measurement results Lower lAn currents especially 10 mA will cause larger variations in
21. mmended to add fourth value into your calibration procedure 0 Q short circuited test leads Metrel installation test instruments usually offer 2 distinctive functions for measuring low resistances LowQ usually stands for measuring low resistances with 200 mA test current often with automatic polarity reversal Continuity denotes a function with lower measuring current usually around 7 mA Both functions can be calibrated with Eurocheck Low resistance measurement calibration can be performed with universal test cable or tip commander Make sure to follow connection instructions for the tested instrument determine the leads of the test cable which are used for this measurement Generic connection diagram is shown in Figure 4 4 18 CS 2099 Eurocheck Eurocheck operation Figure 4 4 Performing low resistance calibration using universal test cable Step Action 1 a Switch on the tested instrument and select LowQ function 200 mA measuring current a Compensate measurement leads resistance see User manual of your instrument for further instructions 2 a Connect tested instrument into Eurocheck low resistance test sockets with universal test cable follow connection diagram shown in Figure 4 4 3 a It is not necessary to power on Eurocheck when performing insulation resistance calibration a Observe any warnings displayed on the tested instrument If any is present remove the causes before proceeding Perfo
22. nect tested instrument into Eurocheck RCD Fault loop output using universal test cable use test tips a Connect only PE and N leads into L and N sockets respectively 2 a Switch on the tested instrument and select fault loop impedance line impedance or RCD function 3 a Connect Eurocheck into mains wall socket and enable RCD Fault loop output a If Eurocheck signals incorrect L and N polarity reverse connection 4 a Touch PE terminal on the tested terminal with your finger the instrument must signal dangerous line situation a Write down test result for documentation purposes 5 a If test fails the tested instrument is damaged Send it immediately to your distributor or manufacturer for repair 22 CS 2099 Eurocheck Technical specifications 5 Technical specifications 5 1 General Power supply voltage 230 V a c 207 V 255 V 50 Hz 60 Hz Protection classification double insulation Pollution degree 2 Protection degree IP 40 Overvoltage category CAT II 300 V Power consumption 222222220000 5 VA Dimensions w x h x d 0000eeeee 103 mm x 61 mm x 205 mm WENU tere 780g Reference conditions Reference temperature range 18 C 28 C Reference humidity range 40 RH 70 RH Operation conditions Working temperature range 10 C 40 C Max
23. on of measurement accuracy For further information on how to perform each measurement with your instrument see its User manual Notes a Itis advisable to perform at least 3 consecutive measurements to verify stability of measurement results Consider accuracy of calibrated function when evaluating calibration results Accuracy of each function is defined in User manual of your instrument a If calibration results deviate significantly from reference values it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment a Itis a good practice to file results after each calibration Variation of results over time period may indicate malfunctioning of the instrument a Itis best to perform calibrations in similar environment conditions since changes of temperature and relative humidity influence test instrument operation and Eurocheck reference values In any case note environmental conditions of calibration when storing measurement results CS 2099 Eurocheck Eurocheck operation 4 2 Sample test report form Caution a This sample test report form is suitable for Metrel installation test instruments like MI3100 EurotestEASI It could be easily modified to suit other types of instruments a Itis not based on any regulation or recommendation Type of calibrated instrument SN of calibrated instrument Date of calibration Temperature C Rel
24. p impedance calibration using plug cable Figure 4 2 Performing fault loop impedance calibration using universal test cable 13 CS 2099 Eurocheck Eurocheck operation 4 6 Trip lock impedance calibration Fault loop impedance is measured between L and PE conductors Trip lock calibration will not trip an RCD if it s present in installation where Eurocheck is connected regardless of selected lAn current Caution a A when performing fault loop impedance calibration Eurocheck connects fault loop calibration output to mains line impedance L and N important when evaluating calibration measurement results a When evaluating absolute measured values first perform line impedance measurement of the wall socket to which Eurocheck is then connected Consider that the impedance of Eurocheck mains cable is added to this value Trip lock impedance calibration can be performed with universal test cable plug cable or even plug commander Calibration can be performed with all An currents supported by the tested instrument even IAn 10 mA Calibration procedure is basically the same as the procedure for fault loop impedance function chapter 4 5 Only differences between both procedures are noted below Step Action 1 a The same as fault loop impedance function Follow connection diagrams shown in Figure 4 1 and Figure 4 2 Switch on the tested instrument and enter trip lock impedance function Select appropriate lAn current A
25. rm resistance measurement with the tested instrument Write down measurement result for documentation purposes 5 a If measured resistance deviates significantly from reference value it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment 6 a Repeat steps 4 and 5 with other reference resistance values 7 a Select continuity function and repeat steps 4 6 a Compensation of test leads performed in LowQ function usually applies also for continuity measurement 4 D DO Notes a Most Metrel installation test instruments use L and N measuring leads of universal test cable to perform low resistance measurements However there are exceptions to this rule like MI 3101 EurotestAT which uses N and PE leads a When calibrating LowQ function make sure that R and R values are also close to reference value If this is not the case check measurement cable or use universal multimeter to measure reference resistors make sure to reverse polarity Contact your local distributor or manufacturer for further information 19 CS 2099 Eurocheck Eurocheck operation 4 12 Voltage and frequency calibration Eurocheck offers a c voltage source of 50 V at 230 V mains voltage This source can be used for voltage and frequency calibration It is possible and recommended to include second value into your calibration procedure 0 V short circuited te
26. s a Observe any warnings displayed on the tested instrument and Eurocheck If any is present remove the causes before proceeding Perform fault loop impedance measurement with the tested instrument Write down measurement result for documentation purposes it will be in 11 0 12 Q range in most cases Select LOOP 1 Q function on Eurocheck LOOP 1 Q LED lights Observe any warnings displayed on the tested instrument and Eurocheck If any is present remove the causes before proceeding Perform fault loop impedance measurement with the tested instrument Write down measurement result for documentation purposes it will be in 10 20 range in most cases 8 a Calculate the difference between LOOP 11 Q and LOOP 1 Q measurement results it has to be close to 9 8 O see Eurocheck technical specification a If impedance difference deviates significantly from 9 8 Q it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment D D D m o D O O D O N D O 9 a Repeat steps 4 8 with reverse polarity of test current in fault loop impedance function if the tested instrument enables reverse polarity selection 12 CS 2099 Eurocheck Eurocheck operation Note a In some instruments the function is named Fault loop resistance however the calibration procedure is the same Figure 4 1 Performing fault loo
27. st leads not open Frequency is equal to mains and is usually very close to 50 Hz or 60 Hz Most Metrel installation test instruments measure all three line voltages UL n UL pe and Un pe Newer models offer special function where all three voltages can be monitored at the same time Older models require that separate measurements of all three voltages are performed in different functions like Rune UL n Rioop UL pe and Rn PE Un pe In some models it is possible to use phase rotation function to measure all voltages at the same time Refer to the User manual of your instrument for more information However only one voltage can be calibrated at a time since Eurocheck offers only 2 lead connection Leave the unused lead disconnected Voltage and frequency measurement calibration can be performed with universal test cable or tip commander Only universal test cable makes possible calibration of all 3 line voltages Make sure to follow connection instructions for the tested instrument Generic connection diagram is shown in Figure 4 5 Step Action 1 a Connect tested instrument into Eurocheck voltage test sockets using universal test cable follow connection diagram shown in Figure 4 5 start with L and N leads UL calibration 2 a Switch on the tested instrument and select appropriate voltage measurement function a Start voltage measurement manually if necessary 3 a Connect Eurocheck into mains wall socket and enable i
28. ts output Observe any warnings displayed on the tested instrument and Eurocheck If Eurocheck signals incorrect L and N polarity reverse connection D Perform voltage and frequency measurement with the tested instrument Write down measurement result for documentation purposes DO DJO If measured voltage or frequency deviates significantly from reference values it is very likely the tested instrument is damaged Send it to your distributor or manufacturer for repair and or readjustment 6 a Connect another pair of measurement leads to voltage source L and PE N and PE and repeat steps 4 5 Notes a Stability of reference voltage depends on mains voltage fluctuations Use stabile reference a c source with 230 V output if better accuracy is necessary Alternatively measure reference voltage with universal DMM simultaneously accuracy class 1 or better a Calibration value represents safe a c voltage limit as defined in European LVD directive and is often used as a safe contact voltage limit when testing RCDs a When calibrating 3 voltage measurement system unused voltmeters may show irregular results this is hardware dependent and presents no problem a When using 230 V source the reference voltage is 47 9 V 20 CS 2099 Eurocheck Eurocheck operation Figure 4 5 Performing voltage and frequency calibration using universal test cable 4 13 Continuity and insulation of measurement leads verific
29. y 2 seconds after it is connected to the mains supply It checks for correct mains supply plug orientation during power up If the orientation is wrong incorrect polarity LED lights In such case reverse connection of power supply cord CS 2099 Eurocheck Eurocheck description and maintenance 3 3 Replacing fuse A fuse is located under side cover of the Eurocheck unit a F1 T 4 A 230 V 32 mm x 6 3 mm General input protection fuse Warnings a Disconnect any connected instrument accessory and power off the calibrator before opening fuse compartment cover hazardous voltage inside a Replace blown fuse with original type only otherwise the calibrator may be damaged and or operator s safety impaired Position of the fuse can be seen in Figure 3 2 in chapter 3 2 3 4 Cleaning No special maintenance is required for the housing To clean the surface of the instrument use a soft cloth slightly moistened with soapy water or alcohol Then leave the instrument to dry totally before use Warnings a Do not use liquids based on petrol or hydrocarbons a Do not spill cleaning liquid over the instrument 3 5 Periodic calibration It is essential that the unit is regularly calibrated in order technical specification listed in this manual is guaranteed We recommend an annual calibration An authorised technical person should do the calibration Please contact your dealer or manufacturer for further information 3 6 Service
30. y basis in harsh environment conditions Often the user doesn t have confidence in instrument operation and its accuracy Continuity of measurement leads presents additional problem Many times it is not possible to conclude the instrument state from ordinary measurement results Such results may look correct but in fact they are wrong due to the instrument malfunctioning Regular test instrument calibration with Eurocheck will reveal such problems Eurocheck doesn t provide a complete calibration solution for installation test instruments Regular 6 months or 1 year calibration of all measurement functions of the instrument is still recommended What it does provide is simple field calibration of the most frequently used functions when testing installations Furthermore in some countries it is obligatory for approved contractors to demonstrate trustworthy control system for ensuring accuracy of test instruments like NICEIC in United Kingdom Eurocheck represents one simple solution in such cases Notes a If in doubt about instrument operation and or its accuracy send it to your distributor or manufacturer for a complete calibration and service if required The same is valid if you re in doubt about Eurocheck operation a Installation measurements in general and typical applications are explained in Metrel handbook Measurements on electric installations in theory and practice CS 2099 Eurocheck Safety and operational considerations

Download Pdf Manuals

image

Related Search

Related Contents

Motorola LPCI810 Network Card User Manual  Guia do Usuário - Konica Minolta  Warehouse of Tiffany RL1304/5 Instructions / Assembly  About IEIMobile  SQ-1 Owner's manual  Catalogue REED  Atlas OCAP 5-Device Universal Remote Control with Learning  IAN 79723  Bedienungsanleitung  1 User Manual for the UofL CDK20 System at Mt Kent Observatory  