FX3U-4AD-PT-ADP USER`S MANUAL
Contents
1. 6 7 TJB S oft G 8 El of Sole aa slgel E oS Oo olf wel oS fo oxH oO ol Cc O E y V Special adapter connector cover is removed Weight Approx 0 1 kg 0 22 Ibs 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter 4 Special adapter connector cover Remove this cover to connect additional special adapters to the left side 5 Direct mounting hole 2 holes of 64 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC 6 POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect platinum resistance thermometer Pt100 three wire type and 24 V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the PT ADP 2 Installation For installation uninstallation details refer to the respective PLC User s manual Hardware Edition INSTALLATION PRECAUTIONS WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause
2. Ver 1 30 or later from the production manufactured in August FX3UC Series PLC 2004 with SER No 48 The version number can be checked by monitoring D8001 D8101 as the last three digits indicate it 4 2 General Specifications Items other than the following are equivalent to the those of the PLC main unit For general specifications refer to the respective PLC User s manual Hardware Edition Item Dielectric withstand Specification voltage Between all terminals and 500 V AC for one minute ground terminal of PLC 5 MQ or more by 500 V DC main unit megger 4 3 Power Supply Specifications Insulation resistance Item Specification A D conversion 24 V DC 20 15 50 mA for 24 V DC circuit driving power Connect a 24 V DC power supply to the terminal block 5V DC 15 mA 5 V DC power is supplied from the internal power supply of main unit Interface driving power 4 4 Performance Specifications Description Item Centigrade C Fahrenheit F input sional 3 wire platinum resistance thermometer sensor Pt100 pee JIS C 1604 1997 Rated temperature 50 C to 250 C 58 F to 482 F range Digital output 500 to 2500 Resolution 0 1 C 580 to 4820 0 18 F 0 5 for full scale when ambient temperature is 25 C 5 C Total accuracy 1 0 for full scale when ambient temperature is in the range of 0 to 55 C e FX3U FX3UC Series PLC 200 us fee The data wil
3. CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 4 1 Applicable PLC Model name FX3S Series PLC FX3G Series PLC Ver 1 00 or later from first production Applicability Ver 1 00 or later from first production FX3GC Series PLC Ver 1 40 or later from first production FX3U Series PLC Ver 2 20 or later from first production Ver 1 30 or later from the production manufactured in August FX3UC Series PLC 2004 with SER No 48 The version number can be checked by monitoring D8001 D8101 as the last three digits indicate it 4 2 General Specifications Items other than the following are equivalent to the those of the PLC main unit For general specifications refer to the respective PLC User s manual Hardware Edition Item Dielectric withstand Specification voltage Between all terminals and 500 V AC for one minute ground terminal of PLC 5 MQ or more by 500 V DCJ main unit megger 4 3 Power Supply Specifications Insulation resistance Item Specification A D conversion 24 V DC 20 15 50 mA for 24 V DC circuit driving power Connect a 24 V DC power supply to the terminal block 5V DC 15 mA 5 V DC power is supplied from the internal power supply of main unit Interface driving power 4 4 Performance
4. electric shock or damage to the product INSTALLATION PRECAUTIONS CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the PLC This section describes the connection method to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion boa
5. of platinum resistance thermometer sensors For the terminal configuration refer to Section 1 2 Precautions on platinum resistance thermometer wiring e Type of platinum resistance thermometer Select Pt100 3 wire platinum resistance thermometer sensors This thermometer will not be affected by voltage drop in the cable connection area and will ensure accurate measurement e Separate the cable of the platinum resistance thermometer sensors from the other motive power cables or areas easily affected by inductive noise of the commercial power etc Example of platinum resistance thermometer wiring Platinum resistance PT ADP thermometer wiring 5 Pt100 Terminal 4 7kQ 4 7kQ Shielded wire block 100kQ2 ch O LO ES O A OOOO O 100kQ Pt100 4 7kQ 4 7KQ nnn 100kQ2 ch Lot SO A O 100kQ External power supply l 5V wiring 24 V DC et ere EAA O E Grounding _L Ground resistance 100 Q or less LCH LO I ch represents the channel number 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be used 3 4 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the following f
6. 5V wiring Q N 24 avoc Hor MA 7 hH H Grounding Ground resistance 100 Q or less LECH LL ID ch represents the channel number 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be used 3 4 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the following figure For details refer to the respective PLC User s manual Hardware Edition Other Other E Q Independent grounding Common grounding Best condition Not allowed Shared grounding Good condition e The grounding wire size should be AWG 22 20 0 3 0 5 mm e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Specifications STARTUP AND MAINTENANCE PRECAUTIONS Z CAUTION Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative Do not drop the product or exert strong impact to it Doing so may cause damage DISPOSAL PRECAUTIONS CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device TRANSPORTATION AND STORAGE PRECAUTIONS
7. JY997D14701L MITSUBISHI ELECTRIC JAPANESE ENGLISH PROGRAMMABLE CONTROLLERS MELSEGIP FX3u 4AD PT ADP USER S MANUAL Manual Number JY997D14701 F X 3U This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2015 Specifications are subject to change without notice 2005 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories AWARNING ana ZXEAUTION Indicates that incorrect handling may cause hazardous Z WARNING conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Depending on the circumstances procedures indicated by CAUTION may also cause severe injury It is important to follow all precautions for personal safety Associat
8. Specifications Description Item Centigrade C Fahrenheit F inputsional 3 wire platinum resistance thermometer sensor Pt100 S JIS C 1604 1997 Rated temperature 50 C to 250 C 58 F to 482 F range Digital output 500 to 2500 Resolution 0 1 C 580 to 4820 0 18 F 0 5 for full scale when ambient temperature is 25 C 5 C Total accuracy 1 0 for full scale when ambient temperature is in the range of 0 to 55 C e FX3U FX3UC Series PLC 200 us eae The data will be updated at every scan time of the PLC time e FX3S FX3G FX3GC Series PLC 250 us The data will be updated at every scan time of the PLC Input characteristics e The photocoupler is adopted to insulate the analog input area from the PLC insulation e The DC DC converter is adopted to insulate the power method supply line from the analog input area e Channels are not insulated from each other Occupied 0 point This number is not related to the maximum number of points input output points of the PLC This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsu
9. bishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JY997D14701L MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEGIP JAPANESE ENGLISH FX3u 4AD PT ADP USER S MANUAL F X 3u Manual Number JY997D14701 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information saf
10. e When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 Nem Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions 3 2 Power Supply Wiring For the power supply wiring refer to the following manual FX3s FX3G FX3GC FX3u FX3uc Series User s Manual Analog Control Edition 3 3 Selection of platinum resistance thermometer sensors For the terminal configuration refer to Section 1 2 Precautions on platinum resistance thermometer wiring e Type of platinum resistance thermometer Select Pt100 3 wire platinum resistance thermometer sensors This thermometer will not be affected by voltage drop in the cable connection area and will ensure accurate measurement e Separate the cable of the platinum resistance thermometer sensors from the other motive power cables or areas easily affected by inductive noise of the commercial power etc Example of platinum resistance thermometer wiring Platinum resistance PT ADP thermometer wiring A Pt100 Terminal 4 7KQ 4 7kKQ Shielded wire Pipe 100kQ ch O T ED O a OO pn Pt100 4 7kQ 4 7kQ 100kQ pch Co LO O a Ss 100k External power supply i
11. ed Manuals Manual name Description JY997D16701 MODEL CODE 09R619 Describes specifications for analog control and programming method for FX3S FX3G FX3GC FX3U FX3UC Series PLC FX3S FX3G F X3GC F X3U FX3UC Series User s Manual Analog Control Edition FX3S FX3G FX3GC F X3U FX3UC Series Programming Manual Basic amp Applied Instruction Edition JY997D16601 MODEL CODE 09R517 Describes PLC programming for basic applied instructions and devices FX3S Series JY997D48601 Explains FX3S Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R535 installation and maintenance FX3G Series JY997D31301 Explains FX3G Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R521 installation and maintenance FX3GC Series User s Manual Hardware Edition JY997D45401 MODEL CODE 09R533 JY997D16501 MODEL CODE Explains FX3GC Series PLC specifications for I O wiring installation and maintenance FX3U Series User s Manual Hardware Edition Explains FX3U Series PLC specifications for I O wiring installation and maintenance 09R516 FX3UC Series User s Manual Hardware Edition JY997D28701 MODEL CODE 09R519 Explains FX3UC Series PLC specifications for I O wiring installation and maintenance How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric deal
12. er from who you purchased your product Applicable standards FX3U 4AD PT ADP units made in June 2005 or later comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual FX3s Series Hardware Manual Manual No JY997D48301 FX3G Series Hardware Manual Manual No JY997D46001 FX3cGc Series Hardware Manual Manual No JY997D45201 FX3u Series Hardware Manual Manual No JY997D18801 FX3uc D DS DSS Series Hardware Manual Manual No JY997D28601 FX3uc 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or ac
13. ety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2015 Specifications are subject to change without notice 2005 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories and A CAUTION A Indicates that incorrect handling may cause hazardous N WARNING conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous NCAUTION conditions resulting in medium or slight personal injury or physical damage Depending on the circumstances procedures indicated by NCAUTION may also cause severe injury It is important to follow all precautions for personal safety Associated Manuals Manual name Description JY997D16701 MODEL CODE 09R619 Describes specifications for analog control and programming method for FX3S FX3G FX3GC FX3U FX3UC Series PLC FX3S FX3G FX3GC F X3U FX3UC Series User s Manual Analog Control Edition FX3S FX3G FX3GC F X3U FX3UC Series Programming Manual Basic amp Applied Instruction Edition JY997D16601 MODEL CODE 09R517 Describes PLC programming for basic applied instr
14. hat neither the terminal block nor the connected parts are directly stressed Make sure to properly wire the terminal block in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual of the PLC main unit Tightening torque should follow the specifications in the manual of the PLC main unit 3 1 Applicable cable and terminal tightening torque 3 1 1 Terminal block European type 1 Wire size The power supply wire should use 22 20 AWG wire Wiring to a Pt100 platinum resistance thermometer should be used the cable of it or a twisted shielded cable 2 Applicable cable Wire size Single wire 0 3 mm to 0 5 mm2 AWG22 to 20 2 pieces of 0 3 mm2 AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt Manufacturer Caulking tool CRIMPFOXx 6 or CRIMPFOX 6T F 2 Al 0 5 8WH 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Phoenix Contact Co Ltd Stick terminal with insulating sleeve Contact area Crimp area Strand wire single wire Insulation sleev
15. hen drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise 1 Do not bundle the power line or shield of the analog input output cable together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit high voltage line or load line 2 Ground the shield of the analog input output cable at one point on the signal receiving side However do not use common grounding with heavy electrical systems Make sure to properly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so t
16. igure For details refer to the respective PLC User s manual Hardware Edition Other Other Other PLE Hleauipment O Q Independent grounding Shared grounding Common grounding Best condition Good condition Not allowed e The grounding wire size should be AWG 22 20 0 3 0 5 mm e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Specifications STARTUP AND MAINTENANCE PRECAUTIONS A CAUTION Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative Do not drop the product or exert strong impact to it Doing so may cause damage DISPOSAL PRECAUTIONS CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device TRANSPORTATION AND STORAGE PRECAUTIONS CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 4 1 Applicable PLC Model name FX3S Series PLC FX3G Series PLC Ver 1 00 or later from first production Applicability Ver 1 00 or later from first production FX3GC Series PLC Ver 1 40 or later from first production FX3U Series PLC Ver 2 20 or later from first production
17. ith a special adapter and perform the procedure as indicated Please replace the following procedures similarly 5 Connect the special adapter fig C to the main unit as shown on the right Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 6 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of an special adapters other than other high speed I O special adapters 3 Wiring WIRING PRECAUTIONS WARN ING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS CAUTION e When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions e Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise 1 Do not bundle the power line or shield of the analog input output cable together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line a
18. l be updated at every scan time of the PLC time e FX3S FX3G FX3GC Series PLC 250 us The data will be updated at every scan time of the PLC Input characteristics e The photocoupler is adopted to insulate the analog input area from the PLC Insulation e The DC DC converter is adopted to insulate the power method f supply line from the analog input area e Channels are not insulated from each other Occupied 0 point This number is not related to the maximum number of points input output points of the PLC This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purpose
19. ng screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the PLC This section describes the connection method to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual FX3u Series User s Manual Hardware Edition 3 Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description w
20. nual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program 1 Outline FX3U 4AD PT ADP hereinafter called PT ADP is an analog special adapter for measuring temperature via four channels three wire sensors of a connected Pt100 platinum resistance thermometer 1 1 Incorporated Items Verify that the following product and items are included in the package Product FX3U 4AD PT ADP Pt100 temperature sensor input special adapter Accessories User s manual This manual 1 2 External Dimensions Part Names and Terminal Layout 5 10 98 3 86 mounting hole pitch Special adapter connector cover is removed Weight Approx 0 1 kg 0 22 Ibs 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter 4 Special adapter connector cover Remove this cover to connect additional special adapters to the left side 5 Direct mounting hole 2 h
21. o JY997D18801 FX3uc D DS DSS Series Hardware Manual Manual No JY997D28601 FX3uc 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this ma
22. oles of 64 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC 6 POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect platinum resistance thermometer Pt100 three wire type and 24 V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the PT ADP 2 Installation For installation uninstallation details refer to the respective PLC User s manual Hardware Edition INSTALLATION PRECAUTIONS WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilli
23. que 3 1 1 Terminal block European type 1 Wire size The power supply wire should use 22 20 AWG wire Wiring to a Pt100 platinum resistance thermometer should be used the cable of it or a twisted shielded cable 2 Applicable cable Wire size Single wire 0 3 mm to 0 5 mm2 AWG22 to 20 2 pieces of 0 3 mm2 AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt Manufacturer Caulking tool CRIMPFOX 6 or CRIMPFOX 6T F 2 Al 0 5 8WH 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Stick terminal with insulating sleeve Insulation sleeve Contact area Crimp area 2 6mm 0 1 Phoenix Contact Co Ltd Strand wire single wire When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 Nem Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions 3 2 Power Supply Wiring For the power supply wiring refer to the following manual FX3s FX3G FX3Gc FX3uU FX3uc Series User s Manual Analog Control Edition 3 3 Selection
24. rd installation procedure refer to the following manual FX3u Series User s Manual Hardware Edition 3 Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description with a special adapter and perform the procedure as indicated Please replace the following procedures similarly 5 Connect the special adapter fig C to the main unit as shown on the right Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 6 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of an special adapters other than other high speed I O special adapters 3 Wiring WIRING PRECAUTIONS WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS CAUTION W
25. s such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN
26. t least 100mm 3 94 or more away from the main circuit high voltage line or load line 2 Ground the shield of the analog input output cable at one point on the signal receiving side However do not use common grounding with heavy electrical systems e Make sure to properly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire the terminal block in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual of the PLC main unit Tightening torque should follow the specifications in the manual of the PLC main unit 3 1 Applicable cable and terminal tightening tor
27. tuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program 1 Outline FX3U 4AD PT ADP hereinafter called PT ADP is an analog special adapter for measuring temperature via four channels three wire sensors of a connected Pt100 platinum resistance thermometer 1 1 Incorporated Items Verify that the following product and items are included in the package Product FX3U 4AD PT ADP Pt100 temperature sensor input special adapter Accessories User s manual This manual 1 2 External Dimensions Part Names and Terminal Layout 5 10
28. uctions and devices FX3S Series JY997D48601 Explains FX3S Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R535 installation and maintenance FX3G Series JY997D31301 Explains FX3G Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R521 installation and maintenance JY997D45401 MODEL CODE 09R533 JY997D16501 MODEL CODE 09R516 JY997D28701 MODEL CODE 09R519 FX3GC Series User s Manual Hardware Edition Explains FX3GC Series PLC specifications for I O wiring installation and maintenance FX3U Series User s Manual Hardware Edition Explains FX3U Series PLC specifications for I O wiring installation and maintenance FX3UC Series User s Manual Hardware Edition Explains FX3UC Series PLC specifications for I O wiring installation and maintenance How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product Applicable standards FX3U 4AD PT ADP units made in June 2005 or later comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual FX3s Series Hardware Manual Manual No JY997D48301 FX3G Series Hardware Manual Manual No JY997D46001 FX3cGc Series Hardware Manual Manual No JY997D45201 FX3u Series Hardware Manual Manual N
Download Pdf Manuals
Related Search
Related Contents
取扱説明書 全自動電気洗濯機 品番 ASW-70AP Manual Transmisor Inalámbrico de audio/video Engel LA BOUGIE - Le Témoin gaulois Nordkap “476” - Billing Boats Energy Conservation Challenge Guide Baliza intermitente y baliza continua Belkin CC3024AED iStarUSA DAGE208U40-2MS disk array User Guide_Video Patrol50_eng_r10 E-Series Manual - July 15.indd Copyright © All rights reserved.